apollo valves backflow preventers - wainbee · backflow preventers cross reference 5 apollo...

of 76 /76

Author: tranthuy

Post on 29-Apr-2018

226 views

Category:

Documents


0 download

Embed Size (px)

TRANSCRIPT

  • 3www.apollovalves.com

    SELECTION GUIDE

    * Limited back pressure to 10 head

    APPLICATION

    *

    *

    *

    Throughout this catalog, products that have a Lead Free1 optionwill be identified with this logo and the following statement applies:1LEAD FREE: The wetted surfaces of these products shall contain

    no more than 0.25% lead by weighted average. Complies with CAAB 1953 and VT S.152. ANSI 3rd party certified & listed.

    TYPE OF DEVICE SERIES BACK BACK CONTINUOUS LOW HIGH PAGESIPHONAGE PRESSURE PRESSURE HAZARD HAZARD NO.

    DC-4A 6, 8DC-40 7

    DOUBLE CHECK VALVE DC-4An 10DC-4S 16,17

    DC-4SG 18

    DCDA-4A 12DOUBLE CHECK DCDA-4An 14DETECTOR ASSEMBLY DCDA-4SG 19

    DCDA-4S 20

    REDUCED PRESSURE RP-4A 21 26PRINCIPLE RP-40 22,24,34

    REDUCED PRESSURE RP-40-n 23PRINCIPLE (n & Z Flow) RP-40-Z 23

    RP-4An 28

    REDUCED PRESSURE RP-40-S 26PRINCIPLE (Stn. Steel)

    RPDA-4A 30REDUCED PRESSURE RPDA-4An 32DETECTOR ASSEMBLY RPDA-40 35

    ATMOSPHERIC AVB1 36VACUUM BREAKER AVB2 36

    PRESSURE PVB-4A 37VACUUM BREAKER PVB-4V 38

    SPILL RESISTANT PRESSUREVACUUM BREAKER SVB-4W 39

    DUAL CHECK W/ ATMOS. PORT DCAP 40

    CARBONATED BEVERAGEBACKFLOW PREVENTER CBBP 44

    HOSE CONNECTIONVACUUM BREAKER HBV2 45

    ANTI FREEZE HOSE CONN.VACUUM BREAKER HBVAF2 45

    HOSE CONNECTIONBACKFLOW PREVENTER HBDUC 46

    LAB FAUCETVACUUM BREAKER LFDUC 46

    Backflow Preventers

  • 4

    TABLE OF CONTENTS

    OrderingProducts Model Code Size Page

    Backflow Cross Reference 5Selection Guide 3Double Check Valve DC-4A 4A-100 1/2-2 6Double Check Valve DC-40 40-100 3/4-2 7Double Check Valve DC-4A (LBF) 4A-100 2-1/2-12 8-9Double Check Valve DC-4An 4An-100 2-1/2-12 10-11Double Check Valve Detector Assembly DCDA-4A 4A-600 2-1/2-12 12-13Double Check Valve Detector Assembly DCDA-4An 4An-600 2-1/2-12 14-15Double Check Valve DC-4S 4S-100 1/2 16Double Check Valve DC-4SG 4SG-100 2-1/2-10 17Double Check Detector Assembly DCDA-4SG 4SG-600 2-1/210 18Reduced Pressure Principle RP-4A 4A-200 1/2-2 19Reduced Pressure Principle RP-40 40-200 1/4-2, 2-1/2-10 20-23, 32Reduced Pressure Principle RP-4A (LBF) 4A-200 2-1/2-12 24-25Reduced Pressure Principle RP-4An 4An-200 2-1/2-12 26-27Reduced Pressure Detector Assembly RPDA-4A 4A-700 2-1/2-12 28-29Reduced Pressure Detector Assembly RPDA-4An 4An-700 2-1/2-12 30-31Reduced Pressure Detector Assembly RPDA-40 40-700 3-10 33Atmospheric Type Vacuum Breaker AVB1/AVB2 38-100/200 1/4-2 34Pressure Vacuum Breaker PVB-4A 4A-500 1/2-2 35Freeze Resistant Pressure Vacuum Breaker PVB-4V 4V-500 1/2-2 36Spill Resistant Pressure Vacuum Breaker SVB-4W 4W-500 1/4-1/2 37Dual Check w/Atmospheric Port DCAP 40-400 1/2-3/4 38Dual Check Valve DUC-4N 4N-300 3/8-1-1/4 39Dual Check Valve DUC-4FP DUC4FP 1-1-1/4 40Dual Check Valve DUC-40 40-300 1/2-1 41Carbonated Beverage Backflow Preventer CBBP 4C-100 1/4, 3/8 42Hose Connection Vacuum Breaker HBV2 38-300 3/4 43Anti-Freeze Hose Connection Vacuum Breaker HBVAF2 38-400 3/4 43Hose Connection Dual Check HBDUC 38-300 3/4 44Lab Faucet Dual Check LFDUC 38-500 1/4-3/8 44Freeze Protection Valve FPV 40-000 1/4 45Y Strainers YB, YSCF 59 & 125YF 1/4-10 46Thermal Expansion Valve EXV 78-RV 3/4-1 47Hose Connection Pressure Gauge HCPG W-8078 3/4 48Test Kits TK 40-200-TK 3,5 Hose 48Test Kit Accessories TKF 40-000-TFK 1/4-3/4 48Valve Setters 4An 4An-000 2-1/2-12 49Air Gap Drain AGD 40-200-X 1/4-12 50Backflow Shut-Off Valves 51Available Shut-Off Valve Options 52Pressure Drop vs. Flow Curves 54-71Relief Valve Discharge Rates 72Product Approvals 73Warranty and Limitations of Liability 74Notes 75

  • Backflow PreventersCross Reference

    5www.apollovalves.com

    Apollo Testable Backflow Preventors Cross Reference

    Double Check Valve Assembly

    Apollo Apollo FlomaticSize Model# Order Code Watts Ames Wilkins Febco Cash Acme

    1/2 - 2 DC-4A, DC-40 40-10X, 4A-10X 007, 719 2000B 950XL, 950XLT 850 DCVEDC-4S (1/2) 4S-103 719, 775 2000B 350, 350XL 850

    2-1/2 - 12 DC-4SG (2-1/2-8) 4SG-10X 709 2000CI 850DC-4S (10) 4S-10G 757, 757A C-200, C-200A

    DC-4A 4A-10X M-200, M-200A007 (2-1/2, 3) 774 (2-1/2-12) 2000SS (2-1/2-12) 350, 350A DCV

    774X (2-1/2,6,8) 2000SE (2-1/2,6,8)DC-4AN 4An-10X 450 870

    Double Check Detector Assembly

    2-1/2 - 12 DCDA-4SG (2-1/2-8) 4SG-60X 007 DCDA (2-1/2, 3)DCDA-4S (10) 4S-60G 70 DCDA 3000CI 856

    DCDA-4A 4A-60X 774DCDA 3000SS 350ADA350DA

    757DCDA, 757ADCDA C300, C300AM300, M300A

    DCDA-4An 4An-60X 450DA 876

    Reduced Pressure Assembly

    1/2 - 2 RP-4S, RP-40 40-20X, 4A-20X 009, 909,919, 995 4000B 975XL 825Y RPZE400B 375, 375XL 860 RPZEII

    RP-40-N 40-20X-T4U U009A 975XLSE 825YA

    2-1/2 - 12 RP-40 40-20X 909 4000CI 860RP-4D (Discontinued) 4D-20X 957 C400 375A, 375

    RP-4A 4A-20X M400009 (2-1/2,3), 995 4000SS RPZ

    RP-4An 4An-20X 957N C400N, M400N 475 880

    Reduced Pressure Detector Assembly

    2-1/2 - 12 RPDA-4A 4A-70X 909RPDA 5000CI 826YD957RPDA C500 375DA,

    375ADARPDA-40 40-70X M500

    5000SSRPDA-4An 4An-70X 957NRPDA C500N, M500N 475DA

    Pressure Vacuum Breaker

    3/4 - 2 PVB-4A, PVB-4V 4V-50X, 4A-50X 800QT, 800MQT, 800M4FR N/A 720A 765 PVBN/A 420 767FR

    Spill Resistant Vacuum Breaker

    1/2 - 3/4 SVB-4W (1/4-1/2) 4W-50X 008QT N/A 460 N/A N/S

  • 6Customer Service 1-704-841-6000

    TOP ENTRY DOUBLE CHECK VALVE ASSEMBLYThe Apollo MODEL DC4A Double Check Valves are designed to prevent contamination of thepotable water supply due to back-siphonage or backpressure from substances that are objectionable, but non-health hazards. The modular check valve cptured spring cartridges havereplaceable seats and reversible silicone seat discs. Apollo ball valve shut-offs with stainlesssteel handles and nuts are standard.

    OPERATIONDuring normal flow conditions, the two check valves are held off their seats, supplying waterdownstream. Each check valve is designed to maintain a minimum of 1 psi across the valve during normal operation. Should the downstream pressure increase to within 1 psi of supply pressure, both check valves will close to prevent a backflow condition.

    FEATURES

    Low pressure loss Captured spring cartridge check valves Compact yet easy to maintain Apollo ball valves w/ SS handles & nuts

    standard Top access for fast testing and

    maintenance Corrosion resistant No special tools required 5 year, domestic warranty Lead-Free1 option

    UL - Pending ASSE 1015 (other approvals pending*) CSA Chloramine-resistant elastomers Patent pending Horizontal and vertical up approvals* Maximum working pressure 175 psi Temperature range 33F - 180F Designed, manufactured, assembled

    and tested in South Carolina, USA

    Sizes 1/2", 3/4, 1", 1-1/4", 1-1/2", 2"

    DC-4A Series

    Dimensions (in) (mm) NetOrdering No. Model No. Size A B C D Wt. lbs.(kg.)4A-103-T2 DC4A12 1/2 (15) 11 (279) 7-3/8 (187) 3-1/4 (83) 2-1/2 (64) 4.4 (2.0)4A-104-T2 DC4A34 3/4 (20) 12-3/4 (324) 8-1/2 (215) 3-1/2 (89) 3 (76) 6.0 (2.7)4A-105-T2 DC4A1 1 (25) 14-5/8 (341) 9-1/2 (241) 4 (100) 3-1/4 (83) 10 (4.5)4A-106-T2 DC4A114 1-1/4(32) 18-5/8 (473) 11-3/4 (298) 4-1/2 (114) 4-3/4 (121) 14 (6.4)4A-107-T2 DC4A112 1-1/2(40) 18-3/4 (476) 11-5/8 (295) 4-1/2 (114) 4-3/4 (121) 17 (7.7)4A-108-T2 DC4A2 2 (50) 21-1/8 (537) 12-3/4 (324) 5 (127) 5-3/8 (136) 25.4 (11.5)

    4A [X] - 1 X X - TXX

    Y-STRAINER0-Standard1-w/ Y-strainer

    (shipped loose)

    SHUT-OFF VALVES1-less ball valves2-w/ball valves (Standard)3-w/OS&Y gate valves#

    4-w/union ball valves

    SIZE3-1/24-3/4"5-1"6-1-1/4"7-1-1/2"8-2"

    OPTIONS (CAN BE COMBINED)F-SAE threaded test cocks (standard 1/2 3/4, 1)LL-locking lever handles (1-1/4, 1-1/2, 2)*LR -Locking round handles (1/2, 3/4, 1)*

    Example: 4A-104-T4LR = 3/4 doublecheck valve assembly with union ballvalves with round locking lever handles

    ORDERING CODE -

    *Contact factory for approval details

    SEE PAGE 53 FOR FLOW CURVES

    4A - Standard4ALF - Lead Free1

    * Locking handles not available on T3 option # 1 to 2 only

    MATERIALSBody BronzeCaps Cast Bronze C84400Check Valves Glass-Filled PPOSprings 300 Series Stainless SteelSeat Discs Chloramine-resistant

    SiliconeO-rings Chloramine-resistant EPDMBall Valve Handles Stainless Steel

  • 7www.apollovalves.com

    Double Check ValveBackflow Preventers

    TOP ENTRY DOUBLE CHECK VALVE ASSEMBLYThe Apollo DC-40 Series Top Entry Double Check Valve Assembly is designed to protect against backflow from a cross-connection of non-health hazard pollutant. Within theassembly are two mechanically independent, spring-loaded poppet type check valves set in an integral cast bronze body. Both check valves are designed at an inclined angle upward from horizontal centerline of the assembly, and all test cocks are mounted at the top to assure easyaccess during repair and maintenance when unit is installed in a pit or tight places.

    OPERATIONDuring normal flow conditions, the two poppet check valves are held off their seats, supplyingwater downstream. Each check valve is designed to maintain a minimum of 1 psi across thevalve during normal operation. Should the downstream pressure increase to within 1 psi ofsupply pressure, both check valves will close to prevent a backflow condition.

    FEATURES Top access for fast testing, and

    maintenance Corrosion resistant Low head loss Interchangeable poppets and springs Replaceable seats & Reversible Seat

    Discs Approved for horizontal installations 5 year, domestic warranty Lead-Free1 option

    CSA USC FCCCHR AWWA C-510 ASSE 1015 Comes standard with Apollo full port

    ball valves with stainless steel handles Maximum working pressure 175 psig Temperature range 33F-180F Designed, manufactured, assembled

    and tested in South Carolina, USA

    40 [X] - 1 X X - TXX

    Y-STRAINER0-Standard1-w/ Y-strainer

    (1-1/4-2shippedloose)

    SHUT-OFF VALVES1-less ball valves (UL Classified)2-w/ball valves (Standard)4-w/union ball valves

    SIZE4-3/4"5-1"6-1-1/4"7-1-1/2"8-2"

    Sizes 3/4", 1", 1-1/4", 1-1/2", 2"

    DC-40 Series

    MATERIALSBody and covers BronzeSprings Stainless SteelPoppets Glass-Filled CelconSeat discs Silicone RubberReplaceable seats Glass-Filled PPOFasteners Stainless SteelBall valve handles Stainless Steel

    OPTIONS (CAN BE COMBINED)F-SAE threaded test cocksLL-locking lever handles (1-1/4, 1-1/2, 2)

    Example: 40-104-T4LL = 3/4 doublecheck valve assembly with union ballvalves with locking lever handles

    ORDERING CODE -

    40 - Standard40LF - Lead Free1

    SEE PAGE 53 FOR FLOW CURVES

    Dimensions - in(mm) - Weights - lbs.(kg)Model No. DC4034 DC401 DC40114 DC40112 DC402Ordering No. 40-104-T 40-105-T 40-106-T 40-107-T 40-108-TBody Size 3/4 (20) 1 (25) 1-1/4 (32) 1-1/2 (40) 2 (50)A 13 (330) 14-3/4 (375) 20-3/4 (525) 21-3/8 (545) 23-1/8 (590)B 7-1/4 (185) 7-1/4 (185) 12-3/8 (315) 12-3/8 (315) 12-3/8 (315)C 4-5/16 (110) 4-5/16 (110) 6-1/8 (155) 6-1/8 (155) 6-1/8 (155)D 1-5/8 (41) 1-7/8 (48) 2-3/16 (56) 2-5/8 (67) 3 (75)E 2-7/16 (62) 2-7/16 (62) 3-13/16 (97) 3-13/16 (97) 3-13/16 (97)F 5-7/16 (138) 5-7/16 (138) 6-3/8 (162) 6-3/8 (162) 6-3/8 (162)G 13/16 (20) 13/16 (20) 1-3/8 (35) 1-3/8 (35) 1-3/8 (35)Test Cocks 1/8 x 1/4 NPT 1/8 x 1/4 NPT 1/4 x 1/4 NPT 1/4 x 1/4 NPT 1/4 x 1/4 NPTNet Weight 8.8 (4.0) 9.5 (4.3) 23.2 (10.5) 25.7 (11.7) 31.5 (14.3)Shipping Weight 10.1 (4.6) 10.8 (4.9) 25.9 (12.0) 28.8 (13.1) 35.5 (16.1)

  • Double Check ValveBackflow Preventers

    8Customer Service 1-704-841-6000

    DC-4A Series

    Sizes 2-1/2"-12

    DOUBLE CHECK VALVE ASSEMBLYThe Apollo MODEL DC-4A Double Check Valves are designed to prevent contamination of thepotable water supply due to back-siphonage or backpressure from substances that are objectionable, but non-health hazards. The TriForce center stem guided check valves featurereplaceable and reversible silicone seat discs. The body is stainless steel from 2-1/2-8 and FDA epoxy coated ductile iron in the 10 and 12. Available with a wide variety of shutoff valveoptions.

    OPERATIONDuring normal flow conditions, the two check valves are held off their seats, supplying waterdownstream. Each check valve is designed to maintain a minimum of 1 psi across the valve during normal operation. Should the downstream pressure increase to within 1 psi of supply pressure, both check valves will close to prevent a backflow condition.

    FEATURES Stainless steel body: 2-1/2-8 FDA epoxy coated ductile iron body:

    10 & 12 Easy maintenance - no special tools

    required Snap-in check retainers: 2-1/2-6 Bolted-in checks: 8-12

    Low pressure loss as documented byASSE or USC FCCC&HR backflow preventer approval agencies

    Center stem guided TriForce check valves

    Lead-Free1 option

    Approved for horizontal and vertical up flow*

    Chloramine-resistant elastomers ASSE 1015 (other approvals pending)* UL, ULC Classified Maximum working pressure 175 psi Temperature range 33F - 140F,

    180F intermittent US Patent Nos. 6,443,184; 7,025,085;

    7,533,699 Made in the USA 5 year, domestic warranty

    *Contact factory for approval details

    4A [X] - 1 X X - 0X

    Y-STRAINER0-Standard1-w/ Y-strainer

    (shipped loose)

    SHUT-OFF VALVES1-Less Shut-off Valves2-NRS Flg x NRS Flg 3-OS&Y Flg x OS&Y Flg4-OS&Y Flg x Monitored

    Butterfly Vlv Grv6-OS&Y Flg x Post indicator Flg**7-OS&Y Flg x OS&Y Grv8-OS&Y Grv x OS&Y Grv9-Mon. Butterfly Vlv Grv x Mon.

    Butterfly Vlv Grv10-OS&Y Flg x Post Indicator Grv**11-NRS Grv x NRS Grv12-NRS Flg x NRS Grv

    SIZE9-2-1/20-3"A-4"C-6"E-8"G-10"H-12

    Example: 4A-10A-03 = 4 size with OS&Yflanged x flanged shut-off valves(shown above)

    ORDERING CODE -

    ** Post indicator with plate & nut option not available in 2-1/2 size.

    4A - Standard4ALF - Lead Free1

    MATERIALSBody (2-1/2-8) 304 Stainless SteelBody (10 & 12) FDA Epoxy Coated Ductile IronCovers (2-1/2-6) Glass Filled PPO/SSCovers (8) 304 Stainless SteelCovers(10 & 12) FDA Epoxy Coated Ductile IronRelief Valve BronzeCheck Valves Bronze/Glass-filled PPO/SSSprings Stainless SteelSeat Discs Chloramine-resistant Silicone

  • Double Check ValveBackflow Preventers

    www.apollovalves.com9

    Dimensions - in.(mm) Weights - lbs.(kg)2-1/2 3 4 (100) 6 (150) 8 (200) 10 12

    A (Butterfly Valves) 27-7/8 (708) 28-3/8 (721) 32-7/8 (835) 38-1/2 (978) 46 (1168)A (Gate Valves) 30-7/8 (784) 31-7/8 (810) 38-1/8 (968) 45-1/2 (1156) 53 (1346)B (Less Shut-off Valves) 15-7/8 (403) 15-7/8 (403) 19-5/8 (498) 24-1/2 (622) 30 (762)C (Butterfly Valves) 8 (203) 8-3/8 (213) 9-1/8 (233) 10-1/8 (257) 12 (306)C (NRS Gate Valves) 11-3/8 (289) 12-3/8 (314) 14-3/4 (375) 19 (483) 22-1/2 (572)C (OS&Y Open) 16-3/8 (416) 18-7/8 (467) 22-3/4 (578) 30-1/8 (765) 37-3/4 (959)D Center to Bottom 3-7/8 (98) 3-7/8 (98) 4-5/8 (117) 6 (152) 8-1/8 (206)E Width (Max) 10-1/2 (267) 11 (279) 12-1/2 (318) 14-3/8 (365) 17-5/8 (448)F (Check Removal Clearance) 4-3/4 (121) 4-3/4 (121) 6-1/2 (165) 7-1/2 (191) 7-1/2 (191)Test Cocks (NPT) 1/2 (13) 1/2 (13) 1/2 (15) 3/4 (20) 3/4 (20)Net Wt. (Less Valves) 22 (10.0) 23 (10.4) 39 (17.7) 75 (34.0) 208 (94.3)Net Wt. (w/Butterfly Valves) 49 (22.2) 53 (24.0) 83 (37.7) 143 (64.9) 339 (153.8)Net Wt. (w/NRS Gate Valves) 108 (49.0) 134 (60.8) 188 (85.3) 314 (142.4) 671 (304.4)Net Wt. (w/OS&Y Gate Valves) 118 (53.5) 144 (65.3) 194 (88.0) 324 (147.0) 685 (310.7)

    PE

    ND

    ING

    PE

    ND

    ING

    SEE PAGE 54 FOR FLOW CURVES1. Nominal dimensions are shown. Allowances must be made for manufacturers tolerances2. Internal body connections are grooved on 2-1/2-10 sizes.3. Internal body connections are flanged on 12 size.

    F

  • DC-4An Series n STYLE DOUBLE CHECK VALVE ASSEMBLYThe Apollo MODEL DC-4An Double Check Valves are designed to prevent contamination of thepotable water supply due to back-siphonage or backpressure from substances that are objectionable, but non-health hazards. The TriForce center stem guided check valves featurereplaceable and reversible silicone seat discs. The normally vertical up/vertical down orientedbody incorporates an internal swivel connection providing the ability to pivot the second check.The n style flow body is stainless steel from 2-1/2-8 and FDA epoxy coated ductile iron in the10 and 12. Available in a wide variety of shut-off valves.

    OPERATIONDuring normal flow conditions, the two check valves are held off their seats, supplying waterdownstream. Each check valve is designed to maintain a minimum of 1 psi across the valve during normal operation. Should the downstream pressure increase to within 1 psi of supply pressure, both check valves will close to prevent a backflow condition.

    FEATURES Stainless steel body: 2-1/2-8 FDA epoxy coated ductile iron body:

    10 & 12 Easy maintenance - no special tools

    required Snap-in check retainers: 2-1/2-6 Bolted-in checks: 8-12

    Low pressure loss as documented byASSE or USC FCCC&HR backflow preventer approval agencies

    Center stem guided TriForce check valves

    5 year, domestic warranty Lead-Free1 option

    Small installation space required - smallfootprint

    Chloramine-resistant elastomers ASSE 1015 (other approvals pending)* UL, ULC Classified Maximum working pressure 175 psi Temperature range 33F - 140F,

    180F intermittent Optional valve setters eliminate need for

    thrust blocks US Patent Nos. 6,443,184; 7,025,085;

    7,533,699 Made in the USA

    *Contact factory for approval details

    Sizes 2-1/2"-12

    n Flow

    4An [X] - 1 X X - 0X

    Y-STRAINER0-Standard1-w/ Y-strainer

    (shipped loose)

    SHUT-OFF VALVES1-Less Shut-off Valves2-NRS Flg x NRS Flg 3-OS&Y Flg x OS&Y Flg4-OS&Y Flg x Monitored

    Butterfly Vlv Grv6-OS&Y Flg x Post indicator Flg**7-OS&Y Flg x OS&Y Grv8-OS&Y Grv x OS&Y Grv9-Mon. Butterfly Vlv Grv x Mon.

    Butterfly Vlv Grv10-OS&Y Flg x Post Indicator Grv**11-NRS Grv x NRS Grv12-NRS Flg x NRS Grv

    SIZE9-2-1/20-3"A-4"C-6"E-8"G-10"H-12

    Example: 4AN-10A-03 = 4 size withOS&Y flanged x flanged shut-off valves(shown above)

    ORDERING CODE -

    Optional Valve Setter (see pg 49)

    10Customer Service 1-704-841-6000

    Double Check ValveBackflow Preventers

    ** Post indicator with plate & nut option not available in 2-1/2 size.

    4An - Standard4AnLF - Lead Free1

    MATERIALSBody (2-1/2-8) 304 Stainless SteelBody (10 & 12) FDA Epoxy Coated Ductile IronCovers (2-1/2-6) Glass Filled PPO/SSCovers (8) 304 Stainless SteelCovers(10 & 12) FDA Epoxy Coated Ductile IronRelief Valve BronzeCheck Valves Bronze/Glass-filled PPO/SSSprings Stainless SteelSeat Discs Chloramine-resistant Silicone

  • Dimensions - in.(mm) Weights - lbs.(kg)2-1/2 3 4 (100) 6 (150) 8 (200) 10 12

    A (Centerline to Centerline) 12-1/2 (318) 12-1/2 (318) 14 (356) 16 (406) 18-1/2 (470)B Lay Length Space (Gate Valves) 26 (660) 26 (660) 26-1/4 (667) 32-1/4 (819) 37-7/8 (962)B Lay Length Space (Butterfly Valves) 24-1/2 (622) 24-1/2 (622) 28-3/8 (721) 35 (889) 37-3/8 (949)C Height (Gate Valves) 19-5/8 (498) 20 (608) 22-1/2 (572) 28-1/4 (718) 32-7/8 (835)C Height (Butterfly Valves) 18-1/4 (464) 18-1/2 (470) 20-7/8 (530) 25-5/8 (651) 29-3/8 (746)D (Gate Valves) 13 (330) 13-1/2 (343) 14-7/8 (378) 18 (457) 21-3/8 (543)D (Butterfly Valves) 11-1/2 (292) 11-3/4 (298) 13-1/4 (337) 15-3/8 (391) 17-7/8 (453)E (OS&Y Open) 19-7/8 (505) 22-1/4 (565) 27-1/4 (692) 35-5/8 (905) 44-1/2 (1130)E (Butterfly Valves) 11-1/2 (292) 12-1/8 (308) 12-7/8 (327) 15-7/8 (403) 22-1/4 (565)E (NRS/PI) 14-7/8 (378) 16-1/8 (410) 19-1/4 (489) 24-1/2 (622) 29-1/4 (743)F (OS&Y Open) 16-3/8 (416) 18-7/8 (480) 22-3/4 (578) 30-1/8 (765) 37-3/4 (959)F (Butterfly Valves) 8 (703) 8-3/8 (213) 9 (229) 10-7/8 (276) 12-7/8 (327)F (NRS/PI) 11-3/8 (289) 12-3/8 (314) 14-3/4 (375) 19 (483) 22-1/2 (572)G (Clearance needed for check removal) 6 (152) 6 (152) 6 (152) 8 (203) 8-1/2 (216)Test Cocks (NPT) 1/2 (15) 1/2 (15) 1/2 (15) 3/4 (20) 3/4 (20)Net Wt. (Less valves) 30 (13.6) 30 (13.6) 39 (17.7) 74 (33.6) 305 (138.3)Net Wt. (w/butterfly valves) 57 (25.9) 60 (27.2) 84 (38.1) 142 (64.4) 436 (197.8)Net Wt. (w/NRS gate valves) 116 (57.6) 141 (64.0) 188 (85.3) 313 (142.0) 768 (348.4)Net Wt. (w/OS&Y gate valves) 126 (57.2) 151 (68.5) 194 (88.0) 323 (146.5) 782 (354.7)

    PE

    ND

    ING

    PE

    ND

    ING

    SEE PAGE 55 FOR FLOW CURVES1. Nominal dimensions are shown. Allowances must be made for manufacturers tolerances2. Internal body connections are grooved on 2-1/2-10 sizes.3. Internal body connections are flanged on 12 size.

    11www.apollovalves.com

    Double Check ValveBackflow Preventers

  • Double Check DetectorBackflow Preventers

    12Customer Service 1-704-841-6000

    DCDA-4A Series

    Sizes 2-1/2"-12

    DCDA-4A DOUBLE CHECK DETECTOR ASSEMBLYThe Apollo MODEL DCDA-4A Double Check Detector Assembly is designed to prevent contamination of the potable water supply due to back-siphonage or backpressure from substances that are objectionable, but non-health hazards. The TriForce center stem guided check valves feature replaceable and reversible silicone seat discs. The by-pass assemblyserves to measure accurate water use of up to 2 GPM. Available in a wide variety of shut-offoptions.

    The Type 2 bypass uses the first check of the mainline assembly as the first check of the bypass.The second check of the bypass is a single check valve with a model number and serial numberfor test recording. This arrangement is approved by the Tenth Edition of the USC FCC&HRManual of Cross Connection Control as well as ASSE. The arrangement provides the same levelof protection as the original (still optional) Type 1 bypass and the testing procedure is the same.

    FEATURES Stainless steel body: 2-1/2-8 FDA epoxy coated ductile iron body:

    10 & 12 Easy maintenance - no special tools

    required Snap-in check retainers: 2-1/2-6 Bolted-in checks: 8-12

    Low pressure loss as documented byASSE or USC FCCC&HR backflow preventer approval agencies

    Center stem guided TriForce check valves

    Lead-Free1 option

    Approved for horizontal and vertical up flow*

    Chloramine-resistant elastomers ASSE 1048 (other approvals pending)* UL, ULC Classified Maximum working pressure 175 psi Temperature range 33F - 140F,

    180F intermittent US Patent Nos. 6,443,184; 7,025,085;

    7,533,699 Made in the USA 5 year, domestic warranty Optional mounting of bypass on either

    side for ease of installation

    *Contact factory for approval details

    4A [X] - 6 X X - X [X]

    METER OPTIONC-Cubic feet/minE-Gallons/minG-Less meter

    SHUT-OFF VALVES (Inlet x Outlet)1-Less Shut-off Valves2-NRS Flg x NRS Flg 3-OS&Y Flg x OS&Y Flg4-OS&Y Flg x Monitored (Mon.)

    Butterfly Vlv Grv6-OS&Y Flg x Post indicator Flg**7-OS&Y Flg x OS&Y Grv8-OS&Y Grv x OS&Y Grv9-Mon. Butterfly Vlv Grv x Mon.

    Butterfly Vlv Grv10-OS&Y Flg x Post Indicator Grv**11-NRS Grv x NRS Grv12-NRS Flg x NRS Grv

    SIZE9-2-1/20-3"A-4"C-6"E-8"G-10"H-12

    Example: 4A-60A-E3 = 4 size with OS&Yflanged x flanged shut-off valves w/ meterin gallons.

    ORDERING CODE -

    BY-PASS SUB-ASSEMBLY OPTIONS0 - Type 1 w/ 1/2 Double Check2 - Type 2 w/1/2 Single Check (Standard)3 - Type 1 w/ bypass on left*4 - Type 2 w/ bypass on left*

    Type 2(Standard)

    Type 1

    4A - Standard4ALF - Lead Free1

    MATERIALSBody (2-1/2-8) 304 Stainless SteelBody (10 & 12) FDA Epoxy Coated Ductile IronCovers (2-1/2-6) Glass Filled PPO/SSCovers (8) 304 Stainless SteelCovers(10 & 12) FDA Epoxy Coated Ductile IronRelief Valve BronzeCheck Valves Bronze/Glass-filled PPO/SSSprings Stainless SteelSeat Discs Chloramine-resistant Silicone

    * Orientation of bypass looking downstream.Standard is right hand side. Left hand is onopposite side

    ** Post indicator with plate & nut option not available in 2-1/2 size.

  • Double Check DetectorBackflow Preventers

    www.apollovalves.com13

    Dimensions - in.(mm) Weights - lbs.(kg)2-1/2 3 4 (100) 6 (150) 8 (200) 10 12

    A (Butterfly Valves) 27-7/8 (708) 28-3/8 (594) 32-7/8 (832) 38-1/2 (968) 46 (1168)A (Gate Valves) 30-7/8 (784) 31-7/8 (810) 38-1/8 (968) 45-1/2 (1156) 53 (1346)B (Less Shut-off Valves) 15-7/8 (403) 15-7/8 (403) 19-5/8 (498) 24-1/2 (622) 30 (762)C (Butterfly Valves) 8 (203) 8-3/8 (213) 9-1/8 (233) 10-1/8 (257) 12 (306)C (NRS/PI Gate Valves) 16-3/8 (416) 18-7/8 (479) 14-3/4 (375) 19 (483) 22-1/2 (572)C (OS&Y Open) 11-3/8 (289) 12-3/8 (314) 22-3/4 (578) 30-1/8 (765) 37-3/4 (959)D Center to Bottom 3-7/8 (98) 3-7/8 (98) 4-5/8 (117) 6 (152) 8-1/8 (206)E Width 17 (432) 17 (432) 12-1/2 (318) 14-3/8 (365) 17-5/8 (448)F (Check Removal Clearance) 4-3/4 (121) 4-3/4 (121) 6-1/2 (165) 7-1/2 (191) 7-1/2 (191)Test Cocks (NPT) 1/2 (15) 1/2 (15) 1/2 (15) 3/4 (20) 3/4 (20)Net Wt. (Less Valves) 37 (16.8) 38 (17.2) 54 (25) 90 (41) 223 (101)Net Wt. (w/Butterfly Valves) 64 (29.0) 68 (30.8) 98 (45) 158 (72) 354 (161)Net Wt. (w/OS&Y Gate Valves) 133 (60.3) 159 (72.1) 209 (95) 339 (154) 700 (318)

    PE

    ND

    ING

    PE

    ND

    ING

    SEE PAGE 57 FOR FLOW CURVES1. Nominal dimensions are shown. Allowances must be made for manufacturers tolerances2. Internal body connections are grooved on 2-1/2-10 sizes.3. Internal body connections are flanged on 12 size.

  • Double Check DetectorBackflow Preventers

    14Customer Service 1-704-841-6000

    DCDA-4An Series n STYLE DOUBLE CHECK DETECTOR ASSEMBLYThe Apollo MODEL DC-4An Double Check Valves are designed to prevent contamination of thepotable water supply due to back-siphonage or backpressure from substances that are objectionable, but non-health hazards. The TriForce center stem guided check valves featurereplaceable and reversible silicone seat discs. The by-pass assembly serves to measure wateruse of up to 2 GPM. The normally vertical up/vertical down oriented body incorporates an internalswivel connection providing the ability to pivot the second check. The grooved connections onthe bodies from 2-1/2 to 10 allow for easy connection to butterfly or gate shut-off valves. The 12DCDA-4An has flanged connections for gate shut-off valves.

    The Type 2 bypass uses the first check of the mainline assembly as the first check of the bypass.The second check of the bypass is a single check valve with a model number and serial numberfor test recording. This arrangement is approved by the Tenth Edition of the USC FCC&HRManual of Cross Connection Control as well as ASSE. The arrangement provides the same levelof protection as the original (still optional) Type 1 bypass and the testing procedure is the same.

    FEATURES Stainless steel body: 2-1/2-8 FDA epoxy coated ductile iron body:

    10 & 12 Easy maintenance - no special tools

    required Snap-in check retainers: 2-1/2-6 Bolted-in checks: 8-12

    Low pressure loss as documented byASSE or USC FCCC&HR backflow preventer approval agencies

    Center stem guided TriForce check valves

    5 year, domestic warranty Lead-Free1 option

    Small installation space required - smallfootprint

    Chloramine-resistant elastomers ASSE 1048 (other approvals pending)* UL, ULC Classified Maximum working pressure 175 psi Temperature range 33F - 140F,

    180F intermittent Optional valve setters eliminate need for

    thrust blocks below grade US Patent Nos. 6,443,184; 7,025,085;

    7,533,699 Made in the USA Optional mounting of bypass on either

    side for ease of installation*Contact factory for approval details

    4An [X] - 6 X X - X [X]

    Example: 4AN-62A-E7 = 4 size withOS&Y flanged x grooved shut-off valveswith Type 2 bypass w/ meter in GPM

    ORDERING CODE -

    Sizes 2-1/2"-12

    Type 2(Standard)

    Type 1

    Optional Valve Setter (see pg 49)

    METER OPTIONC-Cubic feet/minE-Gallons/minG-Less meter

    SHUT-OFF VALVES (Inlet x Outlet)1-Less Shut-off Valves2-NRS Flg x NRS Flg 3-OS&Y Flg x OS&Y Flg4-OS&Y Flg x Monitored (Mon.)

    Butterfly Vlv Grv6-OS&Y Flg x Post indicator Flg**7-OS&Y Flg x OS&Y Grv8-OS&Y Grv x OS&Y Grv9-Mon. Butterfly Vlv Grv x Mon.

    Butterfly Vlv Grv10-OS&Y Flg x Post Indicator Grv**11-NRS Grv x NRS Grv12-NRS Flg x NRS Grv

    SIZE9-2-1/20-3"A-4"C-6"E-8"G-10"H-12

    BY-PASS SUB-ASSEMBLY OPTIONS0 - Type 1 w/ 1/2 Double Check2 - Type 2 w/1/2 Single Check (Standard)3 - Type 1 w/ bypass on left*4 - Type 2 w/ bypass on left*

    4An - Standard4AnLF - Lead Free1

    MATERIALSBody (2-1/2-8) 304 Stainless SteelBody (10 & 12) FDA Epoxy Coated Ductile IronCovers (2-1/2-6) Glass Filled PPO/SSCovers (8) 304 Stainless SteelCovers(10 & 12) FDA Epoxy Coated Ductile IronRelief Valve BronzeCheck Valves Bronze/Glass-filled PPO/SSSprings Stainless SteelSeat Discs Chloramine-resistant Silicone

    * Orientation of bypass looking downstream.Standard is right hand side. Left hand is onopposite side

    ** Post indicator with plate & nut option not available in 2-1/2 size.

  • Double Check DetectorBackflow Preventers

    15www.apollovalves.com

    SEE PAGE 58 FOR FLOW CURVES* Type 2 Weights1. Nominal dimensions are shown. Allowances must be made for manufacturers tolerances2. Internal body connections are grooved on 2-1/2-10 sizes.3. Internal body connections are flanged on 12 size.

    Dimensions - in.(mm) Weights - lbs.(kg)2-1/2 3 4 (100) 6 (150) 8 (200) 10 12

    A (Centerline to Centerline) 12-1/2 (318) 12-1/2 (318) 14 (356) 16 (406) 18-1/2 (470)B (Gate Valves) 26 (660) 26 (660) 29 (737) 35 (889) 38 (965)B (Butterfly Valves) 24-1/2 (622) 24-1/2 (622) 29 (737) 35 (889) 38 (965)C (Gate Valves) 19-5/8 (498) 20 (508) 22-1/2 (572) 28-1/4 (718) 32-7/8 (835)C (Butterfly Valves) 18-1/4 (464) 18-1/2 (470) 22 (559) 27 (686) 32 (813)D 9 (229) 9 (229) 10-1/8 (257) 11-1/4 (286) 12-1/2 (318)E (OS&Y Open) 19-7/8 (505) 22-1/4 (565) 27-1/4 (692) 35-5/8 (829) 44-1/2 (1130)E (Butterfly Valves) 11-1/2 (292) 12-1/8 (308) 12-7/8 (327) 15-7/8 (403) 22-1/4 (565)E (NRS/PI) 14-7/8 (378) 16-1/8 (410) 19-1/4 (489) 24-1/2 (622) 29-1/4 (743)F (OS&Y Open) 16-3/8 (416) 18-7/8 (479) 22-3/4 (578) 30-1/8 (765) 37-3/4 (959)F (Butterfly Valves) 8 (203) 8-3/8 (213) 9 (229) 10-7/8 (276) 12-7/8 (327)F (NRS/PI) 11-3/8 (289) 12-3/8 (314) 14-3/4 (375) 19 (483) 22-1/2 (572)G (Clearance needed for check removal) 6 (152) 6 (152) 6 (152) 8 (203) 8-1/2 (206)Test Cocks (NPT) 1/2 (15) 1/2 (15) 1/2 (15) 3/4 (20) 3/4 (20)Net Wt.* (Less valves) 45 (20.4) 45 (20.4) 54 (25) 89 (40) 320 (145)Net Wt.* (w/butterfly valves) 72 (32.7) 75 (34.0) 99 (45) 157 (71) 451 (205)Net Wt.* (w/OS&Y gate valves) 141 (64.0) 166 (75.3) 209 (95) 338 (153) 797 (362)

    PE

    ND

    ING

    PE

    ND

    ING

    Type 1 Bypass Type 2 Bypass (Standard)

  • 16Customer Service 1-704-841-6000

    DC-4S Series (Previously Model DC)TOP ENTRY DOUBLE CHECK VALVE ASSEMBLYThe Apollo DC-4S Top Entry Double Check Valve Backflow Preventer is designed to preventbackflow by either back-pressure or back-siphonage from a cross-connection between potablewater lines and substances that are objectionable, but not a health hazard. It is an economicaldevice that is easily repaired in the line. The device consists of two independently acting, spring-loaded poppet type cartridge check valves in an integral cast bronze body. Four test cocks andtwo shut-off valves which are quarter-turn, full-port, resilient-seated and ball type complete theassembly.

    OPERATIONDuring normal flow conditions, the two check valves are held off their seats, supplying water down-stream. Each check valve is designed to maintain a minimum of 1 psid across the valve during normal operation. If at any time the pressure downstream of the device increases to within 1 psi ofsupply pressure, both check valves will close to prevent a backflow condition from occurring.

    FEATURES Corrosion resistant Easy to install, repair and maintain Low head loss Replaceable check cartridge modules Comes standard with Apollo full-port

    ball valves with stainless steel handles USC FCCCHR AWWA C-510 Lead-Free1 option

    ASSE 1015 Approved for vertical and horizontal

    installations Maximum working pressure 175 psig Operating temperature range 33F-180F Designed, manufactured, assembled and

    tested in South Carolina, USA 5 year, domestic warranty

    4S [X] - 1 0 3 - A XX

    SHUT-OFF VALVES1 -less ball valves2 -w/ ball valves (standard)4 -w/union ball valves

    Dimensions - in.(mm) Weights - lbs.(kg)Model No. DC4S12Ordering No. 4S-103-ABody Size 1/2"(15)A 9-3/4 (250)B (w/o Ball Valves) 5-5/8 (143)C 4-1/2 (115)D 3-1/2 (90)E 1 (25)F 3-5/8 (92)Net Wt. (w/o Ball Valves) 2.68 (1.2)Net Wt. (with Ball Valves) 4.38 (2.0)Shpg. Wt. (w/o Ball Valves) 3.8 (1.7)Shpg. Wt. (with Ball Valves) 5.1 (2.3)

    Sizes 1/2"

    OPTIONS (CAN BE COMBINED)F-SAE threaded test cocks (standard

    on lead free) LL-locking lever handlesLR -Locking round handles

    Example: 4S-103-A2 = 1/2 double check valve assemblywith ball valves

    ORDERING CODE -

    Double Check ValveBackflow Preventers

    SEE PAGE 54 FOR FLOW CURVES

    4S - Standard4S-LF - Lead Free1

    MATERIALSBody and Cover BronzeCheck Modules Acetal w/Stainless

    Steel SpringsSpacer Stainless SteelBall Valve Handles Stainless Steel

    Contact local water authorities for installation/service requirements.

  • Double Check ValveBackflow Preventers

    www.apollovalves.com17

    DC-4SG Series

    Sizes 2-1/2, 3", 4", 6", 8", 10*

    DC-4SG SERIES DOUBLE CHECK VALVE ASSEMBLYThe Apollo DC-4SG Series Double Check Valve is designed to prevent contamination of the potablewater supply due to back-siphonage or backpressure from substances that are non-health hazards.The modular check valves have replaceable seats and reversible EPDM seat discs. Grooved con-nections on an epoxy-coated ductile iron body allow for easy connection to butterfly valves or gatevalves.

    FEATURES Lightweight Short lay length Low pressure loss Modular check valves Individual access to check valves Reversible/replaceable seat discs Approved for vertical (up) and horizontal

    installations Lead-Free1 option (2-1/2 - 6 only)

    Corrosion resistant epoxy-coated ductileiron body

    Gate valves epoxy coated (FDA) ASSE 1015 CSA USC FCCCHR AWWA C-510 UL Classified FM approved US Patents #5,711,341 and #6,343,618

    4SG [X] - 1 X X - 0 X - X

    SIZE9 - 2-1/20 - 3A - 4C - 6E - 8G - 10#

    Y-STRAINER0 - None (Standard)1 - With Y-Strainer

    (Flanged only,shipped loose)

    SHUT-OFF VALVES (Inlet x Outlet)1 - Less Shut-off Valves (grooved-end body)2 - NRS Flg x NRS Flg3 - OS&Y Flg x OS&Y Flg4 - OS&Y Flg x Monitored Butterfly Valve Grv6 - OS&Y Flg x Flg Post Indicator**7 - OS&Y Flg x OS&Y Grv8 - OS&Y Grv x OS&Y Grv9 - Mon. Butterfly Vlv Grv x Mon. Butterfly Vlv Grv

    10 - OS&Y Flg x Grv Post Indicator**

    Example: 4SG-10A-07 = 4 size with OS&Y flanged x grooved shut-off valves

    # 10 body is flanged internal connections only (Model 4S)**Post indicator option not available in 2-1/2 size

    *Nominal dimensions are shown. Allowancesmust be made for manufacturers tolerances.

    FLOW (OPTIONAL)N -n Flow

    ORDERING CODE -

    Dimensions - in(mm) - Weights - lbs.(kg)Model No. DC4SG212 DC4SG3 DC4SG4 DC4SG6 DC4SG8 DC4S10Ordering No. 4SG-109 4SG-100 4SG-10A 4SG-10C 4SG-10E 4S-10GSize 2 1/2"(65) 3"(80) 4"(100) 6"( 150) 8(200) 10 (250)A (Butterfly Valves)* 29 (737) 29 1/2 (749) 29 3/4 (756) 32 1/2 (815) 43 (1092) N/AA (Gate Valves)* 32 (813) 33 (838) 34 1/2 (876) 39 (991) 50 1/4(1276) 55-3/4 (1416)B (Grooved End Body) 17 (432) 17 (432) 16 1/2 (419) 18 (457) 27 (686) 29-1/2 (750)C (Butterfly Valves) 8 (200) 8 1/2 (216) 9 1/4 (235) 10 1/4 (260) 12 (300) N/AC (OS&Y Open) 16 3/8 (416) 18 7/8 (479) 22 3/4 (578) 30 1/8 (765) 37 3/4 (959) 46 (1168)D (Butterfly Valves) 4 1/2 (114) 4 1/2 (114) 4 1/2 (114) 4 1/2 (114) 6 1/2 (165) N/AD (Gate Valves) 3 1/2 (89) 3 3/4 (95) 4 1/2 (114) 5 1/2 (140) 6 3/4 (171) 8.0 (203)E (Butterfly Valves) 9 (229) 9 (229) 9 1/2 (241) 12 (300) 15 (381) N/AE (Gate Valves) 9 5/8 (244) 10 3/8 (264) 11 7/8 (302) 14 5/8 (371) 16 3/4 (425) 18.0 (457)H (Post Indicator Valve) 14.75 (375) 14.80 (376) 14.80 (376) 18.75 (476) 23.42 (595) 26.5 (673)Test Cocks (NPT) 1/2 1/2 1/2 3/4 3/4 3/4Net Wt. (Less Valves) 53 (24) 53 (24) 53 (24) 60 (27) 375 (170) 470 (213)Net Wt. (w/Butterfly Valves) 80 (36) 83 (38) 97 (44) 128 (58) 506 (230) N/ANet Wt. (w/OS&Y Valves) 149 (68) 174 (79) 208 (94) 309 (140) 852 (386) 1320 (599)

    SEE PAGE 56 FOR FLOW CURVES

    4SG - Standard4SGLF - Lead Free1

    (2-1/2-6 only)

    MATERIALS Body Epoxy-coated (FDA)

    Ductile IronCovers (2-1/2 - 6) Epoxy-coated (FDA)

    SteelCovers (8) Epoxy-coated (FDA)

    Ductile IronCheck Valves (2-1/2 - 6) Glass-Filled PPOCheck Valves (8) BronzeSprings Stainless SteelSeat Discs Chloramine-resistant

    EPDMTest Cock Handles Stainless Steel

  • Customer Service 1-704-841-6000

    Double Check DetectorBackflow Preventers

    18

    *Nominal dimensions are shown. Allowances must be made for manufacturers tolerances.

    DCDA-4SG SeriesDCDA-4SG SERIES DOUBLE CHECK DETECTOR ASSEMBLYThe Apollo DCDA-4SG Series Double Check Detector Assembly is designed to prevent contamination of the potable water supply due to back-siphonage or backpressure from sub-stances that are non-health hazards. The device consists of a mainline double check valve withresilient seated shut-off valves. The by-pass serves to measure water use of up to 3 gpm.Grooved connections on an epoxy-coated ductile iron body allow for easy connection to butterflyvalves or gate valves.

    FEATURES Lightweight Short lay length Low pressure loss Modular check valves Individual access to check valves Reversible/replaceable seat discs Approved for vertical and horizontal

    installations Gate valves epoxy coated (FDA) Lead-Free1 option (2-1/2 - 6 only)

    Corrosion resistant FDA epoxy-coatedductile iron body

    UL Classified FM approved USC FCCCHR ASSE 1048 CSA US Patents #5,711,341 and #6,343,618

    Sizes 2-1/2, 3", 4", 6", 8",10*

    4SG [X] - 6 0 X - X [X] - X

    SHUT-OFF VALVES (Inlet x Outlet)1 - Less Shut-off Valves (grooved-end body)2 - NRS Flg x NRS Flg3 - OS&Y Flg x OS&Y Flg4 - OS&Y Flg x Monitored Butterfly Valve Grv6 - OS&Y Flg x Flg Post Indicator**7 - OS&Y Flg x OS&Y Grv8 - OS&Y Grv x OS&Y Grv9 - Mon. Butterfly Vlv Grv x Mon. Butterfly Vlv Grv

    10 - OS&Y Flg x Grv Post Indicator**

    SIZE9 - 2-1/20 - 3A - 4C - 6E - 8G - 10#

    METER OPTIONC - Cubic feet/minE - Gallons/minG - Less meter

    Example: 4SG-60A-E7 = 4 size with meter ingpm and OS&Y flanged x groovedshut-off valves

    # 10 body is flanged only model 4S**Post indicator with plate & nut option not available in 2-1/2 size

    FLOW (OPTIONAL)N -n- Flow

    ORDERING CODE -

    SEE PAGE 59 FOR FLOW CURVES

    4SG - Standard4SGLF - Lead Free1

    (2-1/2-6 only)

    Dimensions - in(mm) - Weights - lbs.(kg)Model No. DCDA4SG212 DCDA4SG3 DCDA4SG4 DCDA4SG6 DCDA4SG8 DCDA4S10Ordering No. 4SG-609 4SG-600 4SG-60A 4SG-60C 4SG-60E 4S-60GSize 2 1/2"(65) 3"(80) 4"(100) 6"(150) 8(200) 10(250)A (Butterfly Valves)* 29 (737) 29 1/2 (749) 29 3/4 (756) 32 1/2 (815) 43 (1092) N/AA (Gate Valves)* 32 (813) 33 (838) 34 1/2 (876) 39 (991) 50 1/4(1276) 55-3/4 (1416)B (Grooved End Body) 17 (432) 17 (432) 16 1/2 (419) 18 (457) 27 (686) 29-1/2 (750)C (Butterfly Valves) 8 (200) 8 1/2 (216) 9 1/4 (235) 10 1/4 (260) 12 (300) N/AC (OS&Y Open) 16 3/8 (416) 18 7/8 (479) 22 3/4 (578) 30 1/8 (765) 37 3/4 (959) 46 (1168)D (Butterfly Valves) 4 1/2 (114) 4 1/2 (114) 4 1/2 (114) 4 1/2 (114) 6 1/2 (165) N/AD (Gate Valves) 3 1/2 (89) 3 3/4 (95) 4 1/2 (114) 5 1/2 (140) 6 3/4 (171) 8.0 (203)E 9 (229) 9 (229) 9 (229) 9 (229) 10 3/4 (273) 13.0 (330)H (Post Indicator Valve) 14.75 (375) 14.80 (376) 14.80 (376) 18.75 (476) 24.42 (595) 11-1/2 (292)Test Cocks (NPT) 1/2 1/2 1/2 3/4 3/4 3/4Net Wt. (Less Valves) 65 (29) 65 (29) 65 (29) 72 (33) 395 (179) 490 (222)Net Wt. (w/Butterfly Valves) 92 (42) 95 (42) 109 (49) 140 (64) 526 (239) N/ANet Wt. (w/OS&Y Valves) 161 (73) 186 (84) 220 (100) 321 (146) 872 (397) 1340 (607)

    MATERIALS Body (mainline) Epoxy-coated (FDA)

    Ductile IronBypass DC BronzeCovers (2-1/2 - 6) Epoxy-coated (FDA)

    SteelCovers (8) Epoxy-coated (FDA)

    Ductile IronCheck Valves (2-1/2 - 6) Glass-Filled PPOCheck Valves (8) BronzeSprings Stainless SteelSeat Discs Chloramine-Resistant

    EPDMTest Cock Handles Stainless Steel

  • www.apollovalves.com19

    Reduced PressureBackflow Preventers

    Dimensions - in.(mm) Weights - lbs.(kg)Model No. RP4A12 RP4A34 RP4A1 RP4A114 RP4A112 RP4A2Ordering No. 4A-203-T 4A-204-T 4A-205-T 4A-206-T 4A-207-T 4A-208-TBody Size 1/2" (15) 3/4" (20) 1" (25) 1-1/4" (32) 1-1/2" (40) 2" (50)A 11-1/8 (283) 12-3/4 (324) 14-5/8 (371) 18-5/8 (473) 18-3/4 (476) 21-1/8 (537)B 7-3/8 (187) 8-1/2 (216) 9-1/2 (241) 11-3/4 (298) 11-5/8 (295) 12-3/4 (324)C 7-1/8 (181) 7-3/8 (187) 8 (203) 9-7/8 (251) 9-7/8 (251) 11 (279)D 2-7/8 (73) 3-1/8 (79) 3-1/4 (83) 5-1/8 (130) 5-1/8 (130) 5-7/8 (149)E 3-1/4 (83) 3-1/2 (89) 4 (100) 4-1/2 (114) 4-1/2 (114) 5 (127)F 3-7/8 (98) 3-7/8 (98) 4 (100) 5-3/8 (137) 5-3/8 (137) 6 (150)Net Wt. 7.2 (3.3) 8.8 (4.0) 12.6 (5.7) 18.5 (8.4) 21.5 (9.8) 33.4 (15.1)

    REDUCED PRESSURE PRINCIPLEThe Apollo Series RP-4A Reduced Pressure Principle Backflow Preventer is designed to givemaximum protection against backflow caused by either back-pressure or back-siphonage fromsubstances that are hazardous. The durable but economical device is easily maintained in the linewith modular check cartridge assemblies that require no special tools. It consists of two independently acting spring-loaded check valves with an automatic differential relief valve locatedbetween the check valves. All testcocks are mounted at the top of the unit to assure easy accessduring repair and maintenance when unit is installed in tight places.

    FEATURES

    Maximum protection against back-pressure/back-siphonage

    Modular check valve cartridges w/easilyreplaced parts

    Reversible/removable chloramine-resistant silicone seat discs

    Low head pressure loss Top mounted test cocks Internal sensing passage ASSE 1013 (other approvals pending) Lead-Free1 option

    CSA B64.4 Standard with Apollo full port

    ball valves with stainless steel handles Corrosion resistant Maximum working pressure 175 psig Operating temperature range 33F-180F Horizontal installation approvals on 1/2

    through 2 Designed, manufactured, assembled and

    tested in South Carolina, USA 5 year, domestic warranty

    Sizes 1/2", 3/4", 1", 1-1/4", 1-1/2", 2"

    RP-4A Series

    Example: 4A-215-T4LR = 1 Reduced Pressure Backflow Preventer with strainer, union ball valves and

    round locking handles

    See page 50 for air gap drain information.

    4A [X] - 2 X X - TXX

    Y-STRAINER0-Standard1-w/ Y-strainer

    (shipped loose)

    SHUT-OFF VALVES1-less ball valves2-w/ball valves (Standard)3-w/OS&Y gate valves 4-w/union ball valves

    SIZE3-1/24-3/4"5-1"6-1-1/4"7-1-1/2"8-2"

    OPTIONS (CAN BE COMBINED)F-SAE threaded test cocks (standard 1/2, 3/4, 1)L-lever handle (3/4 & 1 only)LL-locking lever handles (1-1/4, 1-1/2, 2)*LR -Locking round handles (1/2, 3/4, 1)*

    ORDERING CODE -

    4A - Standard4ALF - Lead Free1

    SEE PAGE 60 FOR FLOW CURVES

    * Locking handles not available on T3 options

    MATERIALSBody and Covers BronzeSprings 300 Series SSSeat Discs Chloramine-resistant

    SiliconeDiaphragm Nitrile and NylonCheck Modules Glass-Filled PPOO-rings Chloramine-resistant

    EPDMBall Valve Handles Stainless Steel

    Contact local water authorities for installation/service requirements.

    (4A-214-T2F with optional Y - strainer shown)

  • 20Customer Service 1-704-841-6000

    Reduced PressureBackflow Preventers

    Dimensions - in.(mm) Weights - lbs.(kg)Model No. RP4014 RP4038 RP4012 RP4034 RP401 RP40114 RP40112 RP402Ordering No. 40-201-T 40-202-T 40-203-T 40-204-T 40-205-T 40-206-T 40-207-T 40-208-TBody Size 1/4" (6) 3/8" (10) 1/2" (15) 3/4" (20) 1" (25) 1-1/4" (32) 1-1/2" (40) 2" (50)A 10-3/16 (259) 10-1/4 (260) 10-3/4 (273) 13-3/4(349) 15-3/8 (390) 19.5 (495) 19.0 (483) 21-1/2 (546)B (w/o Ball Valves) 5-3/4 (146) 5-3/4 (146) 5-3/4 (146) 8 (200) 8 (200) 11 (280) 11 (280) 11 (280)C 6-7/8 (175) 6-7/8 (175) 6-7/8 (175) 9-3/4 (248) 9-3/4 (248) 12-5/8 (320) 12-5/8 (320) 12-5/8 (320)D 2-5/8 (67) 2-5/8 (67) 2-5/8 (67) 4-1/16(103) 4-1/16 (103) 5-3/8 (137) 5-3/8 (137) 5-3/8 (137)E 3-1/8 (79) 3-1/8 (79) 3-1/8 (79) 4-1/2 (115) 4-1/2 (115) 5-11/16 (145) 5-11/16 (145) 5-11/16 (145)F 3-3/4 (95) 3-3/4 (95) 3-3/4 (95) 5-1/8 (130) 5-1/8 (130) 7-1/8 (180) 7-1/8 (180) 7-1/8 (180)Test Cocks 1/8x1/4NPT 1/8x1/4NPT 1/8x1/4NPT 1/8x1/4NPT 1/8x1/4NPT 1/4x1/4NPT 1/4x1/4NPT 1/4x1/4NPTNet Wt. (w/o Ball Valves) 5.7 (2.6) 5.7 (2.6) 5.1 (2.3) 11-1/2 (5.2) 11 (5.0) 30.5 (13.8) 27.5 (12.5) 27 (12.2)Net Wt. (w/ Ball Valves) 7 (3.2) 7 (3.2) 7.4 (3.4) 14 (6.4) 14.5 (6.7) 35.5 (16.1) 37 (16.8) 39-1/2 (17.9)Shpg. Wt. (w/o Ball Valves) 6.6 (3.0) 6.6 (3.0) 6 (2.7) 12.5 (5.7) 12 (5.4) 32.5 (14.7) 29 (13.2) 29 (13.2)Shpg. Wt. (w/ Ball Valves) 7.9 (3.6) 7.9 (3.6) 8.3 (3.8) 15 (6.8) 15.5 (7.0) 38 (17.2) 39 (17.7) 41 (18.6)

    REDUCED PRESSURE PRINCIPLEThe Apollo Series RP-40 Reduced Pressure Principle Backflow Preventer is designed to give max-imum protection against backflow caused by either back-pressure or back-siphonage. Thedurable, but economical, device is easily maintained in the line without any special tools. It con-sists of two independently acting spring-loaded check poppet valves with an automatic differentialrelief valve located between the check valves. Three of the testcocks are mounted at the top toassure easy access during repair and maintenance when unit is installed in tight places. (#2 test-cock mounted on relief valve cover for tight installations.)

    FEATURES

    Maximum protection against back-pres-sure/back-siphonage

    Reversible/Removable silicone seat discs Internal sensing passage Designed for easy maintenance Low head loss Economical Corrosion resistant Replaceable seat rings Comes standard with Apollo full port

    ball valves with stainless steel handles Lead-Free1 option

    Maximum working pressure 175 psig Operating temperature range 33F-180F Replaceable seats UL Classified (less shut-offs) USC FCCCHR AWWA 511 ASSE 1013 CSA B64.4 Designed, manufactured, assembled and

    tested in South Carolina, USA 5 year, domestic warranty

    40 [X] - 2 X X - T X X

    Y-STRAINER0-Standard1-w/ Y-strainer

    (1-1/4-2shippedloose)

    SHUT-OFF VALVES1-less ball valves (UL Classified)2-w/ball valves (Standard)4-w/union ball valves

    SIZE1-1/4"2-3/8"3-1/2"4-3/4"5-1"6-1-1/4"7-1-1/2"8-2"

    Sizes 1/4", 3/8", 1/2", 3/4", 1", 1-1/4", 1-1/2", 2"

    RP-40 Series

    OPTIONS (CAN BE COMBINED)F-SAE threaded test cocksL - lever handle (3/4 & 1 only)LL-locking lever handles (1-1/4, 1-1/2, 2)

    Example: 40-218-T4LL = 2 Reduced Pressure Backflow Preventer with strainer, union ball valves and

    locking lever handles

    ORDERING CODE -

    See page 50 for air gap drain information.

    40 - Standard40LF - Lead Free1

    SEE PAGE 60 FOR FLOW CURVES

    MATERIALSBody and covers BronzeSprings Stainless SteelPoppets Glass-Filled Celcon

    Seat Discs Silicone RubberDiaphragm Nitrile and NylonR.V. Stem PPOFasteners Stainless SteelReplaceable Seats Glass-Filled PPOBall Valve Handles Stainless Steel

    Contact local water authorities for installation/service requirements.

  • www.apollovalves.com21

    Reduced PressureBackflow Preventers

    Sizes 3/4", 1", 1-1/4", 1-1/2", 2"

    n AND Z FLOW REDUCED PRESSURE PRINCIPLEThe Apollo Series RP-40 Reduced Pressure Principle Backflow Preventer is designed to givemaximum protection against backflow caused by either back-pressure or back-siphonage. Thedurable, but economical, device is easily maintained in the line without any special tools. It consists of two independently acting spring-loaded poppet check valves with an automatic differential relief valve located between the check valves. The diaphragm and the sensing passage are built into the all bronze body to eliminate possible damage. The assembly offersinstallation flexibility by providing inlet and outlet bronze elbows to meet space requirements,adaptability and lower installation cost. The No. 3 and No. 4 test cocks are mounted at the top toassure easy access during repair and maintenance when unit is installed in tight places.

    OPERATIONDuring normal flow conditions, the two check valves are held off their seats, supplying water down-stream. The relief valve is held shut by supply pressure acting through the internal sensing passage,on the relief valve diaphragm. In the area between the check valves, called the zone, the pressure ismaintained at approximately 7 psi lower than supply pressure. Should a back-pressure or back-siphonage condition occur, the second check valve will seal, prohibiting the backflow of water. Shouldthe second check valve become fouled, the pressure in the zone will increase causing the differentialrelief valve to open to atmosphere. This will maintain the pressure in the zone at least 2 psi lowerthan supply pressure.

    FEATURES Maximum protection against back-pres-

    sure/back-siphonage Flexibility in installation Low installation cost Compact Internal sensing passage Low head loss Reversible/Removable seat discs Replaceable seat rings 5 year, domestic warranty Lead-Free1 option

    Comes standard with Apollo full port ball valves with stainless steel handles

    Maximum working pressure 175 psig Temperature range 33F-180F UL Classified (less shut-offs) USC FCCCHR AWWA 511 ASSE 1013 CSA B64.4 Designed, manufactured, assembled and

    tested in South Carolina, USA

    40 [X] - 2 0 X - T X X X

    SIZES4-3/4"5-1"6-1-1/4"7-1-1/2"8-2"

    Z-Flow

    n-Flow

    FLOWN - n-FlowZ - Z-Flow

    Dimensions -in.(mm) Weights - lbs.(kg)Model No. RP40x34 RP40x1 RP40x114 RP40x112 RP40x2Ordering No. 40-204-T 40-205-T 40-206-T 40-207-T 40-208-TBody Size 3/4" (20) 1" (25) 1-1/4" (32) 1-1/2" (40) 2" (50)A 10-1/2 (267) 10-11/16 (271) 14-3/16 (360) 15-1/8 (384) 15-3/4 (381)B 8 (200) 8 (200) 11 (279) 11 (279) 11 (279)C 4-1/8 (105) 5-3/16 (132) 6 (150) 6-5/8 (168) 7-5/8 (194)D 4-7/16 (113) 4-9/16 (116) 5-3/4 (146) 5-7/8 (149) 6-1/4 (159)E 13-7/8 (352) 15-1/8 (333) 19 (483) 20-3/4 (527) 22-1/8 (562)F 4-7/16 (113) 4-7/16 (113) 5-11/16 (145) 5-11/16 (145) 5-11/16 (145)G 5-1/8 (130) 5-1/8 (130) 7-1/8 (196) 7-1/8 (196) 7-1/8 (196)Test Cocks 1/8 x 1/4NPT 1/8 x 1/4NPT 1/4 x 1/4NPT 1/4 x 1/4NPT 1/4 x 1/4NPTNet Wt. (with Ball Valves) 14.7 (6.7) 15.6 (7.1) 37.5 (17.0) 39.37 (17.9) 43.8 (19.9)Shpg. Wt. (with Ball Valves) 15.7 (7.1) 16.6 (7.5) 40 (18.1) 41.37 (18.8) 45.3 (20.5)

    Shown withoption (F) -SAE threadedtest cocks

    SHUT-OFF VALVES1-less ball valves (UL Classified)2-w/ball valves (Standard)4-w/union ball valves

    OPTIONS (CAN BE COMBINED)F-SAE threaded test cocksL-Lever handles (3/4 & 1)LL-locking lever handles (1-1/4, 1-1/2, 2)

    Example: 40-208-T4ULL = 2 Reduced Pressure Backflow Preventer with union ball valves, with U-flow, and lockinglever handles

    ORDERING CODE -

    See page 50 for air gap drain information.

    RP-40 Series

    x = n or ZFlow

    SEE PAGE 61 FOR FLOW CURVES

    40 - Standard40LF - Lead Free1

    MATERIALSBody, covers Bronze& elbowsSprings Stainless SteelPoppets Glass-Filled Celcon

    Seat Discs Silicone RubberDiaphragm Nitrile and NylonR.V. Stem PPOFasteners Stainless SteelReplaceable Seats Glass-Filled PPOBall Valve Handles Stainless Steel

    Contact local water authorities for installation/service requirements.

  • 22Customer Service 1-704-841-6000

    Reduced PressureBackflow Preventers

    RP-40 Series

    FIRE HYDRANT BACKFLOW METERThe Apollo Series RP-40 Fire Hydrant Backflow Meter shall measure potable water flow from a fire hydrant or other non-permanent installation. At the same time it shall protect against backflowby either back-pressure or back-siphonage from a cross-connection between potable water systemand substances that are non-health and health hazards. The unit shall consist of a 3/4" Short WaterMeter, 1" 40-205 RP device, 1" resilient-seated full port ball valve with locking device, 2 1/2"-7 1/2"NST threaded hose couplings, strainer on inlet of meter and adjustable support rod assembly.

    OPERATION The Fire Hydrant Backflow Meter is connected directly to a fire hydrant with a 2 1/2"-7 1/2" NST firehose female swivel coupling. The device operates like a standard Reduced Pressure device exceptthe flow through the device is measured by a Water Meter connected to the inlet of the backflow preventer. Support rod assembly is adjustable to accommodate fire hydrants at different heights from the ground.

    FEATURES Normal operating flow range 2-30 gpm Accuracy 100% 1.5% of actual thruput Low flow registration 95% at 1/2 gpm Maximum pressure loss 11.0 psi at 30 gpm Maximum operating pressure 150 psi Measuring element oscillating piston Register is straight reading, hermetically

    sealed magnetic drive Meter maincase is bronze, measuring

    chamber is Rocksyn, a corrosion resistantthermoplastic material, maincase bottomplate is bronze, gears are self-lubricating,molded plastic for long life and minimumfriction, magnets are Alnico, trim and casing bolts are stainless steel and straineris thermoplastic.

    Tamperproof locking system inside the meter

    2 1/2"-7 1/2" NST fire hose swivel couplings, female inlet, male outlet

    Maximum rate listed is for intermittent flow only. Maximum continuous flow rateas specified by AWWA is 15 gpm.

    Designed, manufactured, assembled andtested in South Carolina, USA

    5 year, domestic warranty

    Contact local water authorities for installation/service requirements.

    Size 1"

    Model Number40-205-FHB (meter in cu. ft.)40-205-FHBG (meter in gallons)

    DIMENSIONS (in.)WEIGHTS (lbs.)NET WEIGHT 24.1SHIPPING WEIGHT 27.6

    See page 52 for air gap drain information.

  • www.apollovalves.com23

    Reduced PressureBackflow Preventers

    STAINLESS STEEL REDUCED PRESSURE PRINCIPLEBACKFLOW PREVENTERThe Apollo Series RP-40S Stainless Steel Reduced Pressure Principle Backflow Preventer isdesigned to give maximum protection against backflow caused by either backpressure or back-siphonage from a cross-connection wherein a contaminant hazard exists (i.e. a health hazard),or a pollutant hazard exists (i.e. a non-hazard). The assembly is composed of two spring-loadedpoppet type check valves and a mechanically independent, hydraulically dependent pressuredifferential relief valve set in an integral stainless steel body. Three of the testcocks are mount-ed at the top to assure easy access during repair and maintenance when unit is installed intight places.

    OPERATIONDuring normal flow conditions, the two check valves are held off their seats, supplying waterdownstream. The relief valve is held shut by supply pressure acting through the internal sens-ing passage, on the relief valve diaphragm. In the area between the check valves, called thezone, the pressure is maintained at approximately 7 psi lower than supply pressure. Should aback-pressure or back-siphonage condition occur, the second check valve will seal, prohibitingthe backflow of water. Should the second check valve become fouled, the pressure in the zone will increase causing the differential relief valve to open to atmosphere. This will maintain thepressure in the zone at least 2 psi lower than supply pressure.

    FEATURES Stainless steel body and covers Easy to install and repair Internal sensing passage Low head loss Reversible/Removable seat discs Replaceable seats Comes standard with Apollo stainless steel

    full port ball valves with stainless steel handles Lead-Free1 option (Standard)

    Maximum working pressure 175 psig Temperature range 33F-180F USC FCCCHR ASSE 1013 CSA Designed, manufactured, assembled and

    tested in South Carolina, USA 5 year, domestic warranty

    40 - 2 X X - T X S X

    SHUT-OFF VALVES 1-less ball valves (UL classified-3/4,1)2-w/SS ball valves (Standard)

    SIZE1-1/4"2-3/8"3-1/2"4-3/4"5-1"

    MATERIALSBody and Cover Stainless SteelSprings Stainless SteelFasteners Stainless SteelPoppets Glass-Filled Celcon

    Seat Discs Silicone RubberDiaphragm FDA Fluorocarbonand O-RingsReplaceable Seats Glass-Filled PPOTest Cocks & Handles Stainless Steel

    Contact local water authorities for installation/service requirements.

    Sizes 1/4", 3/8", 1/2", 3/4", 1"

    RP-40S Series

    Dimensions - in.(mm) Weights - lbs.(kg)Model No. RP40S14 RP40S38 RP40S12 RP40S34 RP40S1Ordering No. 40-201-TxS 40-202-TxS 40-203-TxS 40-204-TxS 40-205-TxSBody Size 1/4" (6) 3/8" (10) 1/2" (12) 3/4" (20) 1" (25)A 10-1/2 (267) 10-1/2 (267) 10-1/2 (267) 13-1/2 (343) 15-1/4 (387)B 5-3/4 (146) 5-3/4 (146) 5-3/4 (146) 7-15/16 (202) 7-15/16 (202)C 6-7/8 (175) 6-7/8 (175) 6-7/8 (175) 9 (229) 9 (229)D 2-5/8 (68) 2-5/8 (68) 2-5/8 (68) 4-1/16 (103) 4-1/16 (103)E 3-3/16 (81) 3-3/16 (81) 3-3/16 (81) 4-3/8 (111) 4-3/8 (111)F 3-3/4 (95) 3-3/4 (95) 3-3/4 (95) 5-1/8 (130) 5-1/8 (130)Test Cocks 1/8 x 1/4NPT 1/8 x 1/4NPT 1/8 x 1/4NPT 1/8 x 1/4NPT 1/8 x 1/4NPTNet Wt. (w/o Ball Valves) 4.3 (2.0) 4.3 (2.0) 4.1 (1.9) 8.1 (3.8) 8.1 (3.7)Net Wt. (with Ball Valves) 5.5 (2.5) 5.5 (2.5) 5.4 (2.4) 10.8 (4.9) 11 (5.0)Shpg. Wt. (w/o Ball Valves) 5.2 (2.4) 5.1 (2.3) 5 (2.3) 9.8 (4.4) 9.6 (4.3)Shpg. Wt. (with Ball Valves) 6.4 (2.9) 6.4 (2.9) 6.3 (2.8) 12.3 (5.6) 12.8 (5.8)

    ORDERING CODE -

    See page 50 for air gap drain information.

    Y-STRAINER0-Standard1-w/ SS Y-strainer

    (shipped loose)

    OPTIONS (CAN BE COMBINED)LL-locking lever handlesLR -Locking round handles

    x=Shut-off valve configuration

    SEE PAGE 61 FOR FLOW CURVES

  • 24Customer Service 1-704-841-6000

    Reduced PressureBackflow Preventers

    RP-4A Series

    Sizes 2-1/2"-12

    REDUCED PRESSURE PRINCIPLE BACKFLOW PREVENTERThe Apollo MODEL RP-4A Reduced Pressure Principle Backflow Preventers consist of two independently acting, TriForce center stem guided check valves with a differential pressurerelief valve located between the check valves. The unit is designed to give maximum protectionagainst backflow of health or non-health hazard fluids by either back-pressure or back-siphonage. The durable stainless steel units (2-1/2-8) and the FDA epoxy coated ductile ironunits (10 and 12) are easily maintained in the line without any special tools. The TriForcecheck valves operate with a spring assist in the flowing condition to provide excellent flow rateswhich are documented by ASSE or USC FCCC&HR approval curves.

    OPERATIONDuring normal flow conditions, the two check valves are held off their seats, supplying waterdownstream. The relief valve is held shut by supply pressure acting through the sensing tube onthe relief valve diaphragm. In the area between the check valves, called the zone, the pressureis maintained approximately 7 psi lower than supply pressure. Should a back-pressure or back-siphonage condition occur, the second check valve will seal, prohibiting the backflow of water.Should the second check become fouled, the pressure in the zone will increase causing the differential relief valve to open to atmosphere. This will maintain the pressure in the zone atleast 2 psi lower than supply pressure.

    FEATURES Stainless steel body: 2-1/2-8 FDA epoxy coated ductile iron body:

    10 & 12 Easy maintenance - no special tools

    required Snap-in check retainers: 2-1/2-6 Bolted-in checks: 8-12

    Low pressure loss as documented byASSE or USC FCCC&HR backflow preventer approval agencies

    Center stem guided TriForce check valves

    Lead-Free1 option

    Approved for horizontal flow* Chloramine-resistant elastomers ASSE 1013 (other approvals pending)* UL, ULC Classified Maximum working pressure 175 psi Temperature range 33F - 140F,

    180F intermittent US Patent Nos. 6,443,184; 7,025,085;

    7,533,699 Made in the USA Optional Air Gap Drains (see page 50 for

    details and discharge rates) 5 year, domestic warranty

    *Contact factory for approval details

    4A [X] - 2 X X - 0X

    Y-STRAINER0-Standard1-w/ Y-strainer

    (shipped loose)

    SHUT-OFF VALVES1-Less Shut-off Valves2-NRS Flg x NRS Flg 3-OS&Y Flg x OS&Y Flg4-OS&Y Flg x Monitored (Mon.)

    Butterfly Vlv Grv6-OS&Y Flg x Post indicator Flg**7-OS&Y Flg x OS&Y Grv8-OS&Y Grv x OS&Y Grv9-Mon. Butterfly Vlv Grv x Mon.

    Butterfly Vlv Grv10-OS&Y Flg x Post Indicator Grv**11-NRS Grv x NRS Grv12-NRS Flg x NRS Grv

    SIZE9-2-1/20-3"A-4"C-6"E-8"G-10"H-12Example: 4A-20A-07 = 4 size with OS&Y

    flanged x OS&Y grooved (exterior assemblyconnections) shut-off valves.

    ORDERING CODE -

    ** Post indicator with plate & nut option not available in 2-1/2 size.

    4A - Standard4ALF - Lead Free1

    MATERIALSBody (2-1/2-8) 304 Stainless SteelBody (10 & 12) FDA Epoxy Coated Ductile IronCovers (2-1/2-6) Glass Filled PPO/SSCovers (8) 304 Stainless SteelCovers(10 & 12) FDA Epoxy Coated Ductile IronRelief Valve BronzeCheck Valves Bronze/Glass-filled PPO/SSSprings Stainless SteelSeat Discs Chloramine-resistant Silicone

  • www.apollovalves.com25

    Reduced PressureBackflow Preventers

    Dimensions - in.(mm) Weights - lbs.(kg)2-1/2 3 4 (100) 6 (150) 8 (200) 10 12

    A (Butterfly Valves) 27-7/8 (708) 28-3/8 (721) 32-7/8 (835) 38-1/2 (978) 46 (1168)A (Gate Valves) 30-7/8 (784) 31-7/8 (810) 38-1/8 (968) 45-1/2 (1156) 53 (1346)B (Less Shut-off Valves) 15-7/8 (403) 15-7/8 (403) 19-5/8 (498) 24-1/2 (622) 30 (762)C (Butterfly Valves) 8 (203) 8-3/8 (213) 9-1/8 (233) 10-1/8 (257) 12 (306)C (NRS Gate Valves) 11-3/8 (289) 12-3/8 (314) 14-3/4 (375) 19 (483) 22-1/2 (572)C (OS&Y Open) 16-3/8 (416) 18-7/8 (479) 22-3/4 (578) 30-1/8 (765) 37-3/4 (959)D Center to Bottom 9-5/8 (238) 9-5/8 (238) 10-3/8 (264) 11-5/8 (295) 15-5/8 (397)E Width (Max) 11-1/2 (292) 12 (305) 12-1/2 (318) 14-3/8 (365) 17-5/8 (448)F (Check Removal Clearance) 4-3/4 (121) 4-3/4 (121) 6-1/2 (165) 7-1/2 (191) 7-1/2 (191)Test Cocks (NPT) 1/2 (15) 1/2 (15) 1/2 (15) 3/4 (20) 3/4 (20)Net Wt. (Less Valves) 31 (14.1) 32 (4.5) 48 (21.8) 84 (38.1) 228 (103.4)Net Wt. (w/Butterfly Valves) 58 (26.3) 62 (28.1) 92 (41.7) 152 (68.9) 359 (162.8)Net Wt. (w/NRS Gate Valves) 117 (53.1) 143 (64.9) 197 (89.4) 323 (146.5) 691 (313.4)Net Wt. (w/OS&Y Gate Valves) 127 (57.6) 153 (69.4) 203 (92.1) 333 (151.0) 705 (319.8)

    PE

    ND

    ING

    PE

    ND

    ING

    SEE PAGE 62 FOR FLOW CURVES1. Nominal dimensions are shown. Allowances must be made for manufacturers tolerances2. Internal body connections are grooved on 2-1/2-10 sizes.3. Internal body connections are flanged on 12 size.

    F

  • Customer Service 1-704-841-6000

    Reduced PressureBackflow Preventers

    26

    RP-4An Series REDUCED PRESSURE PRINCIPLE BACKFLOW PREVENTERThe Apollo MODEL RP-4AN Reduced Pressure Principle Backflow Preventer consists of twoindependently acting, TriForce center stem guided check valves with a differential pressurerelief valve located between the check valves. The unit is designed to give maximum protectionagainst backflow of health or non-health hazard fluids by either back-pressure or back-siphonage. The normally vertical up/vertical down oriented body incorporates an internal swivelconnection providing the ability to pivot the second check 180 to a vertical up/vertical up flow.The durable stainless steel units (2-1/2 to 8) and the FDA epoxy coated ductile iron units (10and 12) are easily maintained in the line without any special tools. The TriForce check valvesoperate with a spring assist in the flowing condidion to provide excellent flow rates which aredocumented by ASSE or USC FCCC&HR approval curves.

    OPERATIONDuring normal flow conditions, the two check valves are held off their seats, supplying waterdownstream. The relief valve is held shut by supply pressure acting through the sensing tube onthe relief valve diaphragm. In the area between the check valves, called the zone, the pressureis maintained approximately 7 psi lower than supply pressure. Should a back-pressure or back-siphonage condition occur, the second check valve will seal, prohibiting the backflow of water.Should the second check become fouled, the pressure in the zone will increase causing the differential relief valve to open to atmosphere. This will maintain the pressure in the zone atleast 2 psi lower than supply pressure.

    FEATURES Stainless steel body: 2-1/2-8 FDA epoxy coated ductile iron body:

    10 & 12 Easy maintenance - no special tools

    required Snap-in check retainers: 2-1/2-6 Bolted-in checks: 8-12

    Low pressure loss as documented byASSE or USC FCCC&HR backflow preventer approval agencies

    Center stem guided TriForce check valves

    Optional Air Gap Drains (see page 50 fordetails and discharge rates)

    Lead-Free1 option

    Small installation space required - smallfootprint

    Approved for n-flow and vertical up flow* Chloramine-resistant elastomers ASSE 1013 (other approvals pending)* UL, ULC Classified Maximum working pressure 175 psi Temperature range 33F - 140F,

    180F intermittent Optional valve setters eliminate need for

    thrust blocks between elbows US Patent Nos. 6,443,184; 7,025,085;

    7,533,699 Made in the USA 5 year, domestic warranty

    *Contact factory for approval details

    Sizes 2-1/2"-12

    n Flow

    Vertical UpFlow

    4An [X] - 2 X X - 0X

    Y-STRAINER0-Standard1-w/ Y-strainer

    (shipped loose)

    SHUT-OFF VALVES1-Less Shut-off Valves2,3

    2-NRS Flg x NRS Flg 3-OS&Y Flg x OS&Y Flg4-OS&Y Flg x Monitored (Mon.)

    Butterfly Vlv Grv6-OS&Y Flg x Post indicator Flg**7-OS&Y Flg x OS&Y Grv8-OS&Y Grv x OS&Y Grv9-Mon. Butterfly Vlv Grv x Mon.

    Butterfly Vlv Grv10-OS&Y Flg x Post Indicator Grv**11-NRS Grv x NRS Grv12-NRS Flg x NRS Grv

    SIZE9-2-1/20-3"A-4"C-6"E-8"G-10"H-12Example: 4AN-20A-07 = 4 size with

    OS&Y flanged x OS&Y grooved valves

    ORDERING CODE -

    Optional Valve Setter (see pg 49)

    ** Post indicator with plate & nut option not available in 2-1/2 size.

    4An - Standard4AnLF - Lead Free1

    MATERIALSBody (2-1/2-8) 304 Stainless SteelBody (10 & 12) FDA Epoxy Coated Ductile IronCovers (2-1/2-6) Glass Filled PPO/SSCovers (8) 304 Stainless SteelCovers(10 & 12) FDA Epoxy Coated Ductile IronRelief Valve BronzeCheck Valves Bronze/Glass-filled PPO/SSSprings Stainless SteelSeat Discs Chloramine-resistant Silicone

  • www.apollovalves.com

    Reduced PressureBackflow Preventers

    27

    Dimensions - in.(mm) Weights - lbs.(kg)2-1/2 3 4 (100) 6 (150) 8 (200) 10 12

    A (Centerline to Centerline) 12-1/2 (318) 12-1/2 (318) 14 (356) 16 (406) 18-1/2 (470)B Lay Length Space (Gate Valves) 26 (660) 26 (660) 27-1/4 (692) 36-3/4 (933) 35-1/2 (902)B Lay Length Space (Butterfly Valves) 24-1/2 (622) 24-1/2 (622) 29-1/4 (743) 36-3/4(933) 39 (991)C Height (Gate Valves) 19-5/8 (498) 20 (508) 22-1/2 (572) 28-1/4 (718) 32-7/8 (835)C Height (Butterfly Valves) 18-1/4 (464) 18-1/2 (470) 20-7/8 (530) 25-5/8 (651) 29-3/8 (746)D (Gate Valves) 13 (330) 13-1/2 (343) 14-7/8 (378) 18 (457) 21-3/8 (543)D (Butterfly Valves) 11-1/2 (292) 11-3/4 (298) 13-1/4 (337) 15-3/8 (391) 17-7/8 (453)E (OS&Y Open) 19-7/8 (505) 22-1/4 (565) 27-1/4 (692) 35-5/8 (829) 44-1/2 (1130)E (Butterfly Valves) 11-1/2 (292) 17-1/8 (308) 12-7/8 (327) 15-7/8 (403) 22-1/4 (565)E (NRS/PI) 14-7/8 (378) 16-1/8 (410) 19-1/4 (489) 24-1/2 (622) 29-1/4 (743)F (OS&Y Open) 16-3/8 (416) 18-7/8 (479) 22-3/4 (578) 30-1/8 (765) 37-3/4 (959)F (Butterfly Valves) 8 (203) 8-3/8 (213) 9 (229) 10-7/8 (276) 12-7/8 (327)F (NRS/PI) 11-3/8 (289) 12-3/8 (314) 14-3/4 (375) 19 (483) 22-1/2 (572)G (Gate Valves) 5-1/2 (140) 6 (152) 6 (152) 9 (229) 9 (229)G (Butterfly Valves) 4-1/8 (105) 4-1/2 (114) 4-3/8 (111) 6-1/2 (165) 5-1/4 (133)H (Gate Valves) 26 (660) 27 (686) 29-3/4 (756) 36 (914) 42-3/4 (1086)H (Butterfly Valves) 23 (584) 23-1/2 (597) 26-1/2 (673) 30-3/4 (781) 35-3/4 (908)I (Clearance needed for check removal) 6 (152) 6 (152) 6 (152) 8 (203) 8-1/2 (216)Test Cocks (NPT) 1/2 (15) 1/2 (15) 1/2 (15) 3/4 (20) 3/4 (20)Net Wt. (Less valves) 39 (17.7) 39 (17.7) 48 (21.8) 83 (37.7) 325 (147.4)Net Wt. (w/butterfly valves) 66 (29.9) 69 (31.3) 92 (41.7) 151 (68.5) 456 (206.8)Net Wt. (w/NRS gate valves) 125 (56.7) 50 (68.0) 197 (89.4) 322 (146.1) 788 (357.4)Net Wt. (w/OS&Y gate valves) 135 (61.2) 160 (72.6) 203 (92.1) 332 (150.6) 802 (363.8)

    PE

    ND

    ING

    PE

    ND

    ING

    SEE PAGE 63 FOR FLOW CURVES1. Nominal dimensions are shown. Allowances must be made for manufacturers tolerances2. Internal body connections are grooved on 2-1/2-10 sizes.3. Internal body connections are flanged on 12 size.

  • Customer Service 1-704-841-600028

    RPDA-4A Series

    RPDA-4A REDUCED PRESSURE DETECTOR ASSEMBLYThe Apollo MODEL RPDA-4A Reduced Pressure Detector Assembly consists of two independ-ently acting, TriForce center stem guided check valves with a differential pressure relief valvelocated between the check valves. The unit is designed to give maximum protection againstbackflow of health or non-health hazard fluids by either back-pressure or back-siphonage andat the same time detect leakage or unauthorized use of water from fire or automatic sprinklersystems. The durable stainless steel units (2-1/2 to 8) and the FDA epoxy coated ductile ironunits (10 and 12) are easily maintained in line without any special tools. The TriForcecheck valves operate with a spring assist in the flowing condition to provide low flow rateswhich are documented by ASSA or USC FCCC&HR approval curves.

    The Type 2 bypass uses the first check of the mainline assembly as the first check of thebypass. The second check of the bypass is a single check valve with a model number andserial number for test recording. This arrangement is approved by the Tenth Edition of theUSC FCC&HR Manual of Cross Connection Control as well as ASSE. The arrangement pro-vides the same level of protection as the original (still optional) Type 1 bypass and the testingprocedure is the same.

    FEATURES

    Stainless steel body: 2-1/2-8 FDA epoxy coated ductile iron body:

    10 & 12 Easy maintenance - no special tools

    required Snap-in check retainers: 2-1/2-6 Bolted-in checks: 8-12

    Low pressure loss as documented byASSE or USC FCCC&HR backflow preventer approval agencies

    Center stem guided TriForce check valves

    Lead-Free1 option

    Approved for horizontal flow* ASSE 1047 (other approvals pending)* UL, ULC Classified Maximum working pressure 175 psi Temperature range 33F - 140F,

    180F intermittent Optional air gap drains (see page 50 for

    details and discharge rates.) US Patent Nos. 6,443,184; 7,025,085;

    7,533,699 Made in the USA 5 year, domestic warranty Optional mounting of bypass on either

    side for ease of installation

    *Contact factory for approval details

    4A [X] - 7 X X - X [X]

    Example: 4A-72A-E3 = 4 size with OS&Y flanged x flangedshut-off valves Type 2 Bypass w/ meter in gallons.

    ORDERING CODE -

    METER OPTIONC-Cubic feet/minE-Gallons/minG-Less meter

    SHUT-OFF VALVES (Inlet x Outlet)1-Less Shut-off Valves2-NRS Flg x NRS Flg 3-OS&Y Flg x OS&Y Flg4-OS&Y Flg x Monitored (Mon.)

    Butterfly Vlv Grv6-OS&Y Flg x Post indicator Flg**7-OS&Y Flg x OS&Y Grv8-OS&Y Grv x OS&Y Grv9-Mon. Butterfly Vlv Grv x Mon.

    Butterfly Vlv Grv10-OS&Y Flg x Post Indicator Grv**11-NRS Grv x NRS Grv12-NRS Flg x NRS Grv

    SIZE9-2-1/20-3"A-4"C-6"E-8"G-10"H-12

    BY-PASS SUB-ASSEMBLY OPTIONS0 - Type 1 w/ 1/2 Reduced Pressure2 - Type 2 w/1/2 Single Check (Standard) 3 - Type 1 w/ bypass on left*4 - Type 2 w/ bypass on left*

    * Orientation of bypass looking downstream.Standard is right hand side. Left hand is onopposite side

    ** Post indicator with plate & nut option not available in 2-1/2 size.

    Sizes 2-1/2"-12

    Type 2(Standard)

    4A - Standard4ALF - Lead Free1

    MATERIALSBody (2-1/2-8) 304 Stainless SteelBody (10 & 12) FDA Epoxy Coated Ductile IronCovers (2-1/2-6) Glass Filled PPO/SSCovers (8) 304 Stainless SteelCovers(10 & 12) FDA Epoxy Coated Ductile IronRelief Valve BronzeCheck Valves Bronze/Glass-filled PPO/SSSprings Stainless SteelSeat Discs Chloramine-resistant Silicone

    Reduced PressureDetector Assembly

    Type 1

  • www.apollovalves.com29

    Dimensions - in.(mm) Weights - lbs.(kg)2-1/2 3 4 (100) 6 (150) 8 (200) 10 12

    A (Butterfly Valves) 27-7/8 (708) 28-3/8 (721) 32-7/8 (832) 38-1/2 (968) 46 (1168)A (Gate Valves) 30-7/8 (784) 31-7/8 (810) 37-5/8 (956) 45-1/2 (1156) 53 (1346)B (Less Shut-off Valves) 15-7/8 (403) 15-7/8 (403) 19-5/8 (498) 24-1/2 (622) 30 (762)C (Butterfly Valves) 8 (203) 8-3/8 (213) 9-1/8 (233) 10-1/8 (257) 11-7/8 (302)C (NRS Gate Valves) 11-3/8 (289) 12-3/8 (314) 14-3/4 (375) 19 (483) 22-1/2 (572)C (OS&Y Open) 16-3/8 (416) 18-7/8 (479) 22-3/4 (578) 30-1/8 (765) 37-3/4 (959)D Center to Bottom 3-7/8 (98) 3-7/8 (98) 10-3/8 (264) 11-5/8 (295) 15-5/8 (397)E Width 17 (432) 17 (432) 17 (432) 20 (508) 21-1/2 (546)F (Check Removal Clearance) 4-3/4 (121) 4-3/4 (121) 6-1/2 (165) 7-1/2 (191) 7-1/2 (191)Test Cocks (NPT) 1/2 (15) 1/2 (15) 1/2 (15) 3/4 (20) 3/4 (20)Net Wt. (Less Valves) 48 (21.8) 49 (22.2) 65 (30) 101 (46) 245 (111)Net Wt. (w/Butterfly Valves) 75 (34.0) 79 (35.8) 109 (50) 169 (77) 376 (170)Net Wt. (w/OS&Y Gate Valves) 144 (65.3) 170 (77.1) 220 (100) 350 (159) 722 (327)

    PE

    ND

    ING

    PE

    ND

    ING

    SEE PAGE 65 FOR FLOW CURVES1. Nominal dimensions are shown. Allowances must be made for manufacturers tolerances2. Internal body connections are grooved on 2-1/2-10 sizes.3. Internal body connections are flanged on 12 size.

    Reduced PressureDetector Assembly

  • Customer Service 1-704-841-600030

    RPDA-4An Series n STYLE REDUCED PRESSURE DETECTOR ASSEMBLYThe Apollo MODEL RPDA-4An Reduced Pressure Detector Assembly consists of two independently acting, TriForce center stem guided check valves with a differential pressurerelief valve located between the check valves. The unit is designed to give maximum protectionagainst backflow of health or non-health hazard fluids by either back-pressure or back-siphonageand at the same time detect leakage or unauthorized use of water from fire or automatic sprinklersystems. The normally vertical up/vertical down oriented body incorporates an internal swivelconnection providing the ability to pivot the second check 180 to a vertical up/vertical up flow.The durable stainless steel units (2-1/2 to 8) and the FDA epoxy coated ductile iron units (10and 12) are easily maintained in the line without any special tools. The TriForce check valvesoperate with a spring assist in the flowing condition to provide low flow rates which are documented by ASSA or USC FCCC&HR approval curves.

    The Type 2 bypass uses the first check of the mainline assembly as the first check of the bypass.The second check of the bypass is a single check valve with a model number and serial numberfor test recording. This arrangement is approved by the Tenth Edition of the USC FCC&HRManual of Cross Connection Control as well as ASSE. The arrangement provides the same levelof protection as the original (still optional) Type 1 bypass and the testing procedure is the same.

    FEATURES Stainless steel body: 2-1/2-8 FDA epoxy coated ductile iron body:

    10 & 12 Easy maintenance - no special tools

    required Snap-in check retainers: 2-1/2-6 Bolted-in checks: 8-12

    Low pressure loss as documented byASSE or USC FCCC&HR backflow preventer approval agencies

    Center stem guided TriForce check valves

    Optional air gap drains (see pg 50) Lead-Free1 option

    Small installation space required - smallfootprint

    Approved for n-flow and vertical up flow* Chloramine-resistant elastomers ASSE 1047 (other approvals pending)* UL, ULC Classified Maximum working pressure 175 psi Temperature range 33F - 140F,

    180F intermittent Optional valve setters eliminate need for

    thrust blocks below grade US Patent Nos. 6,443,184; 7,025,085;

    7,533,699 Made in the USA 5 year, domestic warranty Optional mounting of bypass on either

    side for ease of installation

    *Contact factory for approval details

    4An [X] - 7 X X - X [X]

    Example: 4AN-70A-E3 = 4 size withmeter in GPM and OS&Y flanged x flangedshut-off valves.

    ORDERING CODE -

    Sizes 2-1/2"-12

    Type 1

    Type 2(Standard)

    Optional Valve Setter (see pg 49)

    METER OPTIONC-Cubic feet/minE-Gallons/minG-Less meter

    SHUT-OFF VALVES (Inlet x Outlet)1-Less Shut-off Valves2-NRS Flg x NRS Flg 3-OS&Y Flg x OS&Y Flg4-OS&Y Flg x Monitored (Mon.)

    Butterfly Vlv Grv6-OS&Y Flg x Post indicator Flg**7-OS&Y Flg x OS&Y Grv8-OS&Y Grv x OS&Y Grv9-Mon. Butterfly Vlv Grv x Mon.

    Butterfly Vlv Grv10-OS&Y Flg x Post Indicator Grv**11-NRS Grv x NRS Grv12-NRS Flg x NRS Grv

    SIZE9-2-1/20-3"A-4"C-6"E-8"G-10"H-12

    BY-PASS SUB-ASSEMBLY OPTIONS0 - Type 1 w/ 1/2 Reduced Pressure2 - Type 2 w/1/2 Single Check (Standard)3 - Type 1 w/ bypass on left*4 - Type 2 w/ bypass on left*

    4A - Standard4AnLF - Lead Free1

    MATERIALSBody (2-1/2-8) 304 Stainless SteelBody (10 & 12) FDA Epoxy Coated Ductile IronCovers (2-1/2-6) Glass Filled PPO/SSCovers (8) 304 Stainless SteelCovers(10 & 12) FDA Epoxy Coated Ductile IronRelief Valve BronzeCheck Valves Bronze/Glass-filled PPO/SSSprings Stainless SteelSeat Discs Chloramine-resistant Silicone

    Reduced PressureDetector Assembly

    * Orientation of bypass looking downstream.Standard is right hand side. Left hand is onopposite side

    ** Post indicator with plate & nut option not available in 2-1/2 size.

  • www.apollovalves.com31

    SEE PAGE 66 FOR FLOW CURVES

    Dimensions - in.(mm) Weights - lbs.(kg)2-1/2 3 4 (100) 6 (150) 8 (200) 10 12

    A (Centerline to Centerline) 12-1/2 (318) 12-1/2 (318) 14 (356) 16 (406) 18-1/2 (470)B (Gate Valves) 26 (660) 26 (660) 33-3/8 (848) 36-3/4 (933) 35-1/2 (902)B (Butterfly Valves) 24-1/2 (622) 24-1/2 (622) 30-1/4 (768) 36-3/4 (933) 39 (991)C (Gate Valves) 19-5/8 (498) 20 (508) 22-1/2 (572) 28-1/4 (718) 32-7/8 (835)C (Butterfly Valves) 18-1/4 (464) 18-1/2 (470) 20-7/8 (530) 25-5/8 (651) 29-3/8 (746)D Center to Bottom (Gate Valves) 13 (330) 13-1/2 (343) 14-7/8 (378) 18 (457) 21-3/8 (543)D Center to Bottom (Butterfly Valves) 11-1/2 (292) 11-3/4 (298) 13-1/4 (337) 15-3/8 (391) 17-7/8 (453)E (OS&Y Open) 19-7/8 (505) 22-1/4 (565) 27-1/4 (692) 35-5/8 (905) 44-1/2 (1130)E (Butterfly Valves) 11-1/2 (292) 12-1/8 (308) 14-1/4 (362) 15-7/8 (403) 22-1/4 (565)E (NRS/PI) 14-7/8 (378) 16-1/8 (410) 19-1/4 (489) 24-1/2 (622) 29-1/4 (743)F (OS&Y Open) 16-3/8 (416) 18-7/8 (479) 22-3/4 (578) 30-1/8 (765) 37-3/4 (959)F (Butterfly Valves) 8 (203) 8-3/8 (213) 9 (229) 10-7/8 (276) 12-7/8 (327)F (NRS/PI) 11-3/8 (289) 12-3/8 (314) 14-3/4 (375) 19 (483) 22-1/2 (572)G (Gate Valves) 5-1/2 (140) 6 (152) 6 (152) 9 (229) 9 (229)G (Butterfly Valves) 4-1/8 (105) 4-1/2 (114) 4-3/8 (111) 6-1/2 (165) 5-1/4 (133)H (Gate Valves) 26 (660) 27 (686) 29-3/4 (756) 36 (914) 42-3/4 (1086)H (Butterfly Valves) 23 (584) 23-1/2 (597) 26-1/2 (673) 30-3/4 (781) 35-3/4 (908)I (Clearance needed for check removal) 6 (152) 6 (152) 6 (152) 8 (203) 8-1/2 (216)Test Cocks (NPT) 1/2 (15) 1/2 (15) 1/2 (15) 3/4 (20) 3/4 (20)Net Wt. (Less valves) 58 (26.3) 58 (26.3) 67 (30) 102 (46) 346 (157)Net Wt. (w/butterfly valves) 85 (38.6) 88 (39.9) 111 (50) 170 (77) 475 (215)Net Wt. (w/NRS gate valves) 144 (63.5) 169 (76.7) 216 (98) 341 (155) 807 (366)Net Wt. (w/OS&Y gate valves) 154 (69.9) 179 (81.2) 222 (101) 351 (159) 821(372)

    PE

    ND

    ING

    PE

    ND

    ING

    * Type 2 Weights1. Nominal dimensions are shown. Allowances must be made for manufacturers tolerances2. Internal body connections are grooved on 2-1/2-10 sizes.3. Internal body connections are flanged on 12 size.

    Type 1

    Type 2(Standard)

    Reduced PressureDetector Assembly

  • Reduced PressureDetector Assembly

    Customer Service 1-704-841-600032

    40 [X] - 2 X X - 0 X

    Y-STRAINER0-Standard1-w/ epoxy Y-strainer

    (shipped loose)

    SIZE9-2-1/2"0-3"A-4"C-6E-8G-10

    VALVES1-less gate valves2-w/ NRS gate valves3-w/OS&Y gate valves5-w/Epoxy coated ball valves6-OS&Y flg x flg post indicator*7-OS&Y flg x OS&Y grv8-OS&Y grv x OS&Y grv10-OS&Y flg x grv post indicator*

    REDUCED PRESSURE PRINCIPLEThe Apollo Series 40-RP Reduced Pressure Backflow Preventer consists of two independently acting, spring-loaded center stem guided check valves with a differential pressure relief valve located between the check valves. The all bronze relief valve module iseasily removed from the ductile iron check valve body. Pressure sensing passages are builtinto the bronze relief valve module to prevent possible damage from mishandling or vandalism. The unit is available with inlet and outlet shutoff valves. Four test cocks, three onthe backflow preventer valve body and one on the inlet shutoff valve, complete the assembly.

    The Type II bypass uses the first check of the mainline assembly as the first check of thebypass. The second check of the bypass is a single check valve with a model numberand serial number for test recording. This arrangement is approved by the Tenth Editionof the USC FCC&HR Manual of Cross Connection Control as well as ASSE. Thearrangement provides the same level of protection as the original (still optional) Type Ibypass and the testing procedure is the same.

    FEATURES Maximum protection against back-

    pressure/back-siphonage Reversible/Removable seat discs Replaceable bronze seats Internal sensing passage Designed for easy maintenance Low head loss Economical Corrosion resistant Maximum working pressure 175 psig Gate valves epoxy coated (FDA) Lead-Free1 option

    Horizontal installation approvals Operating temperature range 33F -

    140F UL Classified FM approved USC FCCCHR ASSE 1013 CSA AWWA 511 Designed, manufactured, assembled

    and tested in South Carolina, USA 5 year, domestic warranty

    Sizes 2-1/2", 3", 4", 6, 8, 10

    Dimensions - in.(mm) Weights - lbs.(kg)Model No. RP40212 RP403 RP404 RP406 RP408 RP4010Ordering No. 40-209 40-200 40-20A 40-20C 40-20E 40-20GBody Size 2-1/2" (65) 3" (80) 4" (100) 6 (150) 8 (200) 10 (250)A 37-1/16 (941) 38-1/16 (967) 46-3/4 (1187) 63 (1600) 75 (1905) 88-1/4 (2242)B 22-1/16 (560) 22-1/16 (560) 28-1/2 (724) 42 (1067) 52 (1448) 62-1/16 (1576)C NRS 20-7/8 (530) 21-7/8 (556) 25-3/16 (640) 30-1/2 (775) 38-1/2 (978) 44 (1118)C OS&Y (OPEN) 25-7/8 (657) 28-3/8 (721) 33-3/16 (843) 41-5/8 (1057) 53-3/4 (1365) 63-1/4 (1607)D NRS 11-3/8 (289) 12-3/8 (314) 14-3/4 (375) 19 (483) 22-1/2 (572) 26-1/2 (673)D OS&Y (OPEN) 16-3/8 (416) 18-7/8 (479) 22-3/4 (578) 30-1/8 (765) 37-3/4 (959) 45-3/4 (1162)E 9-1/2 (241) 9-1/2 (241) 10-7/16 (265) 11-1/2 (292) 16 (406) 17-1/2 (445)F 9-5/8 (244) 10-3/8 (264) 11-7/8 (302) 14-5/8 (371) 16-3/4 (425) 19-1/4 (489)G 7 (178) 7-1/2 (191) 9 (229) 11 (279) 13-1/2 (343) 16 (406)Test Cocks 1/2 x 1/2 NPT 1/2 x 1/2 NPT 1/2 x 1/2 NPT 3/4 x 3/4 NPT 3/4 x 3/4 NPT 3/4 x 3/4 NPTNet Wt. (Less Gate Valves) 120 (54) 122 (55) 196 (89) 430 (195) 715 (324) 1443 (655)Net Wt. (With NRS Valves) 219 (99) 252 (114) 388 (176) 736 (334) 1155 (524) 2148 (974)Net Wt. (With OS&Y Valves) 229 (104) 259 (117) 402 (182) 754 (342) 1210 (549) 2286 (1037)Net Wt. (With Ball Valves) 188 (85) 198 (90) 312 (142) 666 (302) N/A N/A N/A N/AShpg. Wt. (Less gate Valves) 184 (83) 186 (84) 260 (118) 528 (239) 885 (401) 1613 (732)Shpg. Wt. (With NRS Valves) 283 (128) 316 (143) 452 (205) 872 (396) 1335 (606) 2364 (1072)Shpg. Wt. (With OS&Y Valves) 293 (133) 323 (147) 466 (211) 890 (404) 1390 (630) 2502 (1135)Shpg. Wt. (With Ball Valves) 252 (114) 262 (119) 376 (171) 836 (379) N/A N/A N/A N/A

    RP-40 Series

    ORDERING CODE -

    *Post indicator w/ plate & nut option not available in 2-1/2 size.

    SEE PAGE 64 FOR FLOW CURVES

    40 - Standard40LF - Lead Free1

    MATERIALSBody and covers Epoxy Coated

    (FDA Approved)Ductile Iron

    Springs Stainless SteelSeats BronzeC.V. Discs EPDMR.V. Disc SiliconeR.V. Diaphragm Nitrile and NylonR.V. Body Bronze (2-1/2-6)R.V. Body Epoxy Coated

    (FDA Approved)Ductile IronFor 8 & 10 only

    Fasteners Stainless SteelTest Cock Handles Stainless Steel

    Contact local water authorities for installation/service requirements.

  • Reduced PressureDetector Assembly

    www.apollovalves.com33

    Dimensions - in.(mm) Weights - lbs.(kg)Model No. RPDA403 RPDA404 RPDA406 RPDA408 RPDA4010Ordering No. 40-700 40-70A 40-70C 40-70E 40-70GSize 3"(80) 4"(100) 6 (150) 8 (200) 10(250)A 38-1/16 (968) 46-3/4 (1187) 63 (1600) 75 (1905) 88-1/4 (2242)B 22-1/16 (562) 28-1/2 (724) 42 (1067) 52 (1321) 62-1/16(1578)C (OS&Y) OPEN 18-7/8 (479) 22-3/4 (578) 30-1/8 (765) 37-3/4 (969) 45-3/4 (1152)D 3-3/4 (95) 4-1/2 (114) 5-1/2 (140) 6-3/4 (171) 8 (200)E (OS&Y) OPEN 28-3/8 (721) 33-3/16 (843) 41-5/8 (1057) 53-3/4 (1365) 63-1/4 (1607)F 9-1/4 (235) 10-1/2 (267) 13-1/4 (337) 14-3/4 (375) 17-1/2 (445)G 3-3/4 (95) 4-1/2 (114) 5-1/2 (140) 6-3/4 (171) 8 (200)Test cocks (line) 1/2" NPT 1/2" NPT 3/4 NPT 3/4 NPT 3/4 NPTTest cocks (by-pass) 1/4" NPT 1/4" NPT 1/4" NPT 1/4" NPT 1/4" NPTNet Wt. (less gate valves) 145 (66) 217 (98) 452 (205) 738 (335) 1471 (667)Net Wt. (with 0S&Y valves) 282 (128) 423 (192) 776 (352) 1233 (559) 2314 (1050)Shipping Wt. (less gate valves) 209 (95) 281 (127) 550 (249) 908 (412) 1641 (744)Shipping Wt. (with OS&Y valves) 346 (157) 487 (221) 912 (414) 1413 (641) 2530 (1148)

    40 [X] - 7 0 X - X X

    SIZE0 3"A 4"C 6"E 8"G 10"

    GATE VALVES1 Less gate valves3 With OS&Y gate valves6 w/OS&Y gate valve on inlet,

    NRS gate valve w/ post plate and nut on outlet

    7 - With Flanged Inlet x GroovedOutlet (both OS&Y)

    8 - With Grooved x GroovedOS&Y gate valves

    10 - OS&Y Flg x Grv Post Indicator

    METERC With meter in cubic feetE With meter in gallonsG Less water meter

    RPDA-40 SeriesREDUCED PRESSURE DETECTOR ASSEMBLYThe Apollo Series RPDA-40 Reduced Pressure Detector Assembly is designed to provide reduced pressure principle protection against cross-connections that present a health hazard, and at the same time detect leakage or unauthorized use of water from fire or automatic sprinklersystems. The mainline unit consists of two independent spring-loaded, poppet type check valveassemblies with a diaphragm actuated and spring-loaded, relief valve assembly located betweencheck valves. Two resilient wedge gate valves and four test cocks complete the mainline unit. Theby-pass consists of an approved reduced pressure assembly, four test cocks, two shut-off valvesand a water meter.

    OPERATIONDuring no flow conditions, the mainline and by-pass check valves will remain closed. Also, bothmainline and by-pass relief valves stay closed due to the pressure differential between supply andzone pressure. If there is a low flow demand (up to a minimum of 3 gpm) of water downstream,which may be caused by a system leak or unauthorized use, the flow is routed through the watermeter to monitor such consumption. Higher flow will tend to open the mainline check valves atwhich point water continues to flow at the by-pass at a rate below capacity. In the event pressureincreases downstream, tending to reverse direction of flow, both check valves in the mainline andby-pass are closed to prevent backflow. If the second check valve in either the mainline or by-passis prevented from closing tightly, leakage into the reduced pressure zone increases pressure andwill cause the relief valves to open. If the supply pressure