Page 9 of European Technical Approval ETA-10/0280
Apolo MEA Quick fix anchor
Apolo MEA Quick fix anchor after installation
Product and intended use
Annex 1
of EuropeanTechnical ApprovalETA - 10 / 0280
Apolo MEA Quick fix anchor
Marking: Identifying mark: Anchor identity: Category:
Max. fixture thickness: Material:
Examples:
Marking: Identifying mark: Anchor identity: Category*1):
Thread size: Max. fixture thickness:f
Material*1):
Examples:
*1): Where applicable
SKAH (stainless steel)K (hot dip galvanized)1)
M8 … M16tfixHCR*1)
S-KA 10/20S-KAK 10/20S-KAH 10/20S-KAH 10/20 HCR
- zinc plated- hot dip galvanized- stainless steel A4- stainless steel HCR
BAZ:BAZ HD:BAZ A4:BAZ HCR:
Page 10 of European Technical Approval ETA-10/0280
Apolo MEA Quick fix anchor
Table 1a: Materials BAZ and BAZ HD
Partfyk
[N/mm²]fuk
[N/mm²]560 660475 560
2 - -
3 - -
4 - -
1) BAZ: Parts 1, 3 and 4 are zinc electroplated according to EN ISO 4042 ≥ 5μm and bright passivated.2) BAZ HD: Parts 1, 3 and 4 are hot dip galvanized according to EN ISO 10684.
Table 1b: Materials BAZ A4
Partfyk
[N/mm²]fuk
[N/mm²]
2 - -
3 - -
4 - -
Table 1c: Materials BAZ HCR
Partfyk
[N/mm²]fuk
[N/mm²]
2 - -
3 - -
4 - -
1
Designation
Bolt
Sleeve
Washer
Hexagonal Nut
M10 + M12M8 + M16
M8 - M16 Steel, electroplated, EN ISO 4032,grade 8
Diameters Material 1) 2)
M8 - M16
M8 - M16
Cold rolled galvanized steel strip, EN 10147
Steel, electroplated, EN ISO 7089
Cold forged steel, EN 10263-2
Designation Diameters Material
1 Bolt Cold forged stainl. steel, EN 10088-31.4578
M8 - M16 Stainless steel strip, EN 10088-21.4401 / 1.4404 / 1.4571
Washer M8 - M16 Stainless steel, EN ISO 70891.4401 / 1.4404 / 1.4571
530 600
Designation Diameters Material
Hexagonal Nut M8 - M16 Stainless steel, EN ISO 40321.4401 / 1.4404 / 1.4571 - grade 80
M8 - M16
Sleeve
1 Bolt M8 - M16 Cold forged stainl. steel, EN 10088-31.4529 / 1.4565 530 600
Sleeve M8 - M16 Stainless steel strip, EN 10088-21.4401 / 1.4404 / 1.4571
Washer M8 - M16 Stainless steel, EN ISO 70891.4529 / 1.4565
Hexagonal Nut M8 - M16 Stainless steel, EN ISO 40321.4529 / 1.4565 - grade 70
Materials
Annex 2
of EuropeanTechnical ApprovalETA - 10 / 0280
Apolo MEA Quick fix anchor
Page 11 of European Technical Approval ETA-10/0280
Apolo MEA Quick fix anchor
Table 2: Dimensions of the anchor
Expansion sleeve
Size L f dcf dnom lc ls s d1 d2 sw m[mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm]
M8 62…420 22...220 7,1 8 20,9 15,9 1,6 8,4 17,0 13,0 6,5
M10 82…420 37…215 9,0 10 25,7 17,9 2,0 10,5 21,0 17,0 8,0
M12 98…420 48…210 10,8 12 30,3 19,1 2,5 13,0 24,0 19,0 10,0
M16 118..420 60…202 14,6 16 38,1 26,3 3,0 17,0 30,0 24,0 13,0
Hexagonal nut
StudboltMain dimensions
12 / 0…..322
Anchor type
WasherConebolt
16 / 0…..302
10 / 0......338
8 / 0…....358
Dimensions of the anchor
Annex 3
of EuropeanTechnical ApprovalETA - 10 / 0280
Apolo MEA Quick fix anchor
Page 12 of European Technical Approval ETA-10/0280
Table 3: Installation data
Drill hole diameter d0 [mm] 8 10 12 16
Cutting diameter at the upper tolerance limit (maximum diameter bit)
dcut,max ≤ [mm] 8,45 10,45 12,5 16,5
Depth of drilled hole to deepest point h1 ≥ [mm] 60 75 90 110Effective anchorage depth hef [mm] 45 60 70 85
Diameter of clearance hole in the fixture df ≤ [mm] 9 12 14 18
Thickness of fixture tfix,min…max [mm] 0…358 0…338 0…322 0…302Width across flats SW [mm] 13 17 19 24
Required BAZ / BAZ HD 20 / 15 1) 35 50 120torque BAZ A4 / BAZ HCR 20 35 70 120
1) Installation torque for BAZ is 20 Nm and for BAZ HD 15 Nm
Table 4: Minimum thickness of concrete member, spacing and edge distance
Minimum thickness of concrete member hmin [mm] 100 120 140 170smin [mm] 50 55 60 70c ≥ [mm] 50 80 90 120cmin [mm] 50 50 55 85s ≥ [mm] 50 100 145 150
Intervalues may be interpolated linearly.
Tinst [Nm]
Minimum edge distance
M10 M12 M16
Minimum spacing
Apolo MEA Quick fix anchorAnchor size
M8
Anchor sizeApolo MEA Quick fix anchor
M16M8 M10 M12
Installation data,Minimum thickness of concrete member,
Spacing and edge distance
Annex 4
of EuropeanTechnical ApprovalETA - 10 / 0280
Apolo MEA Quick fix anchor
Page 13 of European Technical Approval ETA-10/0280
Table 5:
Steel failureCharacteristic resistance BAZ / BAZ HD NRk,s [kN] 13 26 38 69
Characteristic resistance BAZ A4 / BAZ HCR NRk,s [kN] 15 24 35 75
Partial safety factor γMs 1) [ - ]
Pull-out failure
NRk,p [kN] 9 16 20 35
C25/30
C30/37
C35/45
C40/50
C45/55
C50/60
Partial safety factor γMp 1) [ - ] 1,50 3)
Concrete cone failureEffective anchorage depth hef [mm] 45 60 70 85
Spacing scr,N [mm] 135 180 210 255
Edge distance ccr,N [mm] 68 90 105 128
Partial safety factor γMc 1) [ - ] 1,50 3)
Concrete splitting failureSpacing ( splitting ) scr,sp [mm] 180 240 280 340
Edge distance ( splitting ) ccr,sp [mm] 90 120 140 170
Partial safety factor γMsp 1) [ - ] 1,50 3)
1) In absence of other national regulations.2) The installation safety factor of γ2 = 1,2 is included.3) The installation safety factor of γ2 = 1,0 is included.
Table 6:
N [kN] 2,0 3,6 4,8 9,5 δN0 [mm] 0,3 0,6 0,6 0,7δN∞ [mm] 1,8 1,6 2,0 1,4
Apolo MEA Quick fix anchorAnchor size
M8 M10 M12 M16
Displacements under tension loads
1,80 2)
M8Apolo MEA Quick fix anchor
1,20ΨCIncreasing factor for NRk,p
Characteristic resistance innon cracked concrete C20/25
Characteristic resistancein cracked concrete C20/25
1,80 2)
Cracked and non-cracked concreteC20/25 - C50/60
1,24
12 20NRk,p
1,80 2)
1,10
1,16
1,04
1,28
Design method A - Characteristic values for tension loads
[kN]
Anchor size
1,40
5 9
M16M10 M12
Design method A :Characteristic values for tension loads and displacements
Annex 5
of EuropeanTechnical ApprovalETA - 10 / 0280
Apolo MEA Quick fix anchor
Page 14 of European Technical Approval ETA-10/0280
Table 7:
Steel failure without lever arm
Characteristic resistance BAZ / BAZ HD VRk,s [kN] 10 18 23 44
Characteristic resistance BAZ A4 / BAZ HCR VRk,s [kN] 11 17 25 47
Partial safety factor γMs 1) [ - ]
Steel failure with lever arm
Characteristic resistance BAZ / BAZ HD M0Rk,s [Nm] 21 48 72 186
Characteristic resistance BAZ A4 / BAZ HCR M0Rk,s [Nm] 22 45 79 200
Partial safety factor γMs 1) [ - ]
Concrete pryout failure
Factor in equation ( 5.6 ) of
ETAG Annex C, § 5.2.3.3
Partial safety factor γMc 1) [ - ]
Concrete edge failure
Effective length of anchor under shear load lf [mm] 45 60 70 85
Outside diameter of anchor dnom [mm] 8 10 12 16
Partial safety factor γMc 1)
[ - ]1) In absence of other national regulations.
Table 8:
V [kN] 5,7 10,3 13,1 25,1
δV0 [mm] 1,7 1,7 2,4 3,2
δV∞ [mm] 2,6 2,6 3,6 4,8
Cracked and non-cracked concreteC20/25 - C50/60
Apolo MEA Quick fix anchorAnchor size
M8 M10 M12 M16
1,40
M8 M10 M12
2
Design method A - Characteristic values for shear loads
Anchor sizeApolo MEA Quick fix anchor
M16
1,50
1,50
Displacements under shear loads
Cracked concrete with straight edge reinforcement > Ø12 mm
Cracked concrete with edge reinforcementand closely spaced stirrups (a ≤ 100mm)or non cracked concrete
Cracked concrete without any edge reinforcement
Ψucr,V [ - ]
1,00
1,20
k [ - ] 1
1,50
1,50
Annex 6
of EuropeanTechnical ApprovalETA - 10 / 0280
Apolo MEA Quick fix anchor
Design method A: Characteristic values for shear loads and displacements
Table 9:
R… [min] 30 60 90 120 30 60 90 120 30 60 90 120 30 60 90 120
BAZ / BAZ HD 1,3 0,7 0,4 0,3 2,3 1,3 0,8 0,5 3,6 2,0 1,3 0,9 5,3 3,0 1,8 1,3
BAZ A4 / BAZ HCR 5,7 3,9 2,0 1,1 9,1 6,1 3,2 1,8 13,2 8,9 4,7 2,6 24,5 16,6 8,7 4,8
NRk,p,fi [kN] 1,0 1,8 2,4 4,0
N0Rk,c,fi [kN] 2,0 4,0 5,9 9,6
scr,N [mm]
smin [mm]
ccr,N [mm]
In absence of other national regulations the partial safety factor for resistance under fire exposure γM,fi = 1,0 is recommended.
2,3 3,0 5,0
2,4 5,0 7,4 12,0
cmin [mm]
Spacing
Edge distance
cmin ≥ 300 mmcmin = 2 x hefFire attack from one side:
Fire attack from more than one side:
50 55 60
Characteristic resistance
4 x hef
2 x hef
70
Pull-out failure
Anchor sizeApolo MEA Quick fix anchor
Steel failure
M8 M10 M12 M16
Page 15 of E
uropean Technical Approval E
TA-10/0280
1,3
Concrete cone failure
Design method A - Characteristic tension resistance in cracked and non-cracked C20/25 to C50/60under fire exposure
Fire resistance duration
Characteristic resistanceNRk,s,fi [kN]
Characteristic resistance
Characteristic values of tension load resistance
under fire exposure
Annex 7
of European
Technical Approval
ETA - 10 / 0280
Apolo M
EA Q
uick fix anchor
Table 10:
R… [min] 30 60 90 120 30 60 90 120 30 60 90 120 30 60 90 120
Steel failure without lever arm
BAZ / BAZ HD 1,3 0,7 0,4 0,3 2,3 1,3 0,8 0,5 3,6 2,0 1,3 0,9 5,3 3,0 1,8 1,3
BAZ A4 / BAZ HCR 5,7 3,9 2,0 1,1 9,1 6,1 3,2 1,8 13,2 8,9 4,7 2,6 24,5 16,6 8,7 4,8
Steel failure with lever arm
BAZ / BAZ HD 1,8 1,3 0,8 0,6 3,6 2,6 1,6 1,1 6,4 4,6 2,8 1,9 16,2 11,7 7,2 4,9
BAZ A4 / BAZ HCR 5,8 4,0 2,1 1,1 11,7 7,9 4,2 2,3 20,4 13,9 7,3 4,0 52,0 35,2 18,5 10,2
Concrete pryout failure
k [-]
V0Rk,cp,fi [kN] 2,0 8,0 11,8 19,2
Concrete edge failure
In absence of other national regulations the partial safety factor for resistance under fire exposure γM,fi = 1,0 is recommended.
Page 16 of E
uropean Technical Approval E
TA-10/0280
Design method A - Characteristic shear resistance in cracked and non-cracked C20/25 to C50/60under fire exposure
Fire resistance duration
Characteristic resistanceVRk,s,fi [kN]
M8 M10 M12 M16
2,4 24,0
Anchor sizeApolo MEA Quick fix anchor
Factor in equation (5.6) ofETAG 001 Annex C, 5.2.3.3
Characteristic resistanceM0
Rk,s,fi [Nm]
1,0 2,0
The initial value V0Rk,c,fi of the characteristic resistance in concrete C20/25 to C50/60 under fire exposure may be determined by:
V0Rk,c,fi = 0,25 x V0
Rk,c (≤ R90) V0Rk,c,fi = 0,20 x V0
Rk,c (R120)with V0
Rk,c initial value of the characteristic resistance in cracked concrete C20/25 under normal temperature.
2,0 2,0
10,0 14,8Characteristic resistance
Characteristic values of shear load resistance
under fire exposure
Annex 8
of European
Technical Approval
ETA - 10 / 0280
Apolo M