application guide for trv for high-voltage circuit breakers.pdf
TRANSCRIPT
-
8/10/2019 Application Guide for TRV for High-Voltage Circuit Breakers.pdf
1/39
WG PC37.011 - Meeting May 20111 1
IEEE WG Revision C37.011Application Guide for TRV for High-Voltage Circuit Breakers
Agenda of WG meeting in Orlando/Lake Buena Vista, May 18th 2011
Introduction of Members & Guests
IEEE SA Bylaws on Patents
Minutes of meeting in Las Vegas
Reminder: ballot of draft D7
Resolution of comment 76 (TRV interpolation) Resolution of non critical comments (input by e mail)
Resolution of remaining comments
Next steps
Denis Dufournet
Chair WG C37.011
-
8/10/2019 Application Guide for TRV for High-Voltage Circuit Breakers.pdf
2/39
WG PC37.011 - Meeting May 20112 2
(First) Ballot Open Date:02-Jul-2010
Ballot Close Date:08-Aug-2010
112 eligible people in the ballot group (72 in 2004, previous revision)
98 votes received = 87% returned, > 75%: requirement is met
89 affirmative votes 92% affirmative, requirement is met
7 negative votes with comments
0 negative votes without comments
2 abstention votes
Ballot of draft D7
-
8/10/2019 Application Guide for TRV for High-Voltage Circuit Breakers.pdf
3/39
WG PC37.011 - Meeting May 20113 3
General overview on negative votes
4 mainly based on minor technical / editorial comments
1 with technical comments that can be easily accepted
2 with comments that need a WG discussion
Main issue
Interpolation of TRV withstand capabilities between T30 andT60
Comments
181 comments
Ballot of draft D7
-
8/10/2019 Application Guide for TRV for High-Voltage Circuit Breakers.pdf
4/39
WG PC37.011 - Meeting May 20114 4
Discussion of Comments on D7
Comment # 76 Subclause 4.2
Comment
This subclause talks about Circuit breaker capability. it is assumed to bethe required TRV as defined by the system. This is understood and
technically sound for the interpolation between T10 and T30 as well as forthe interpolation between T60 and T100. However the transition from 2parameter ( T30) to 4 parameter (T60) is not understood. It is understood
that the first freq. is defined by a transformer, inductance close to thebreaker while the second freq. is given by the traveling wave. In this casethe peak voltage of the first frequency ( u1) should be always in the sameorder of magnitude, while the time to Uc may change
Proposed change
Develop a more technical sound method to interpolate between T30 and
T60.
-
8/10/2019 Application Guide for TRV for High-Voltage Circuit Breakers.pdf
5/39
WG PC37.011 - Meeting May 20115 5
Discussion of Comments on D7
Comment # 76
Resolution
Two methods to interpolate TRVs between T30 and T60, selected
during the meeting in Las Vegas (see next slide) Approach 1 as defined in the present draft (u1 is interpolated between
u1 of T60 and uc of T30)
Approach 2 as discussed in Las Vegas, with u1 constant between T30and T60
Discussion done by WG in November-December 2010 and April-May2011
-
8/10/2019 Application Guide for TRV for High-Voltage Circuit Breakers.pdf
6/39
WG PC37.011 - Meeting May 20116 6
Discussion of Comments on D7
Resolution of Comment # 76
Approach 1
-
8/10/2019 Application Guide for TRV for High-Voltage Circuit Breakers.pdf
7/39
WG PC37.011 - Meeting May 20117 7
Discussion of Comments on D7
Resolution of Comment # 76
Approach 2
-
8/10/2019 Application Guide for TRV for High-Voltage Circuit Breakers.pdf
8/39
WG PC37.011 - Meeting May 20118 8
Discussion of Comments on D7
Resolution of Comment # 76
What is the issue?
It is the TRV withstand by a circuit breaker that can be expected after
current zero until a time up to (approximately) t3 for T30.
0
50
100
150
200
250
300
0 10 20 30 40 50 60
Comparison of the approaches
in case of T40 145kV kpp =1.5
T(s)
TRV withstand
(kV)
Approach 1
Approach 2
-
8/10/2019 Application Guide for TRV for High-Voltage Circuit Breakers.pdf
9/39
WG PC37.011 - Meeting May 20119 9
Discussion of Comments on D7
Resolution of Comment # 76
Comparison of the TRV for T30 and the two approaches for T40
0
50
100
150
200
250
300
0 10 20 30 40 50 60
Comparison of the approaches
in case of T40 145kV kpp =1.5
T(s)
TRV withstand
(kV)
T40 Approach
T40 Approach
T30
-
8/10/2019 Application Guide for TRV for High-Voltage Circuit Breakers.pdf
10/39
WG PC37.011 - Meeting May 201110 10
Discussion of Comments on D7
Comment # 76
Resolution by WG vote
17 in favour to keep the approach 1 of Draft 7
1 in favour to adopt approach 2 with a constant u1 between T30
and T60
1 abstention
Approach 1 will be kept in the next draft.
-
8/10/2019 Application Guide for TRV for High-Voltage Circuit Breakers.pdf
11/39
WG PC37.011 - Meeting May 201111 11
Discussion of Comments on D7
Comment # 142
Subclause Table 2 page 32
Comment
On page 31 it explains that the first-pole-to-clear factors considered inTable 2 are 1.5 for 120 and 161 kV and 1.3 for 230, 315 and 735 kV. Thisshould be in a note for Table 2 so the user can quickly see this detailwithout have to look in the text for it.
Proposed change
Add a NOTE to Table 2: "The first-pole-to-clear factors considered are 1.5for 120 kV and 161 kV, and 1.3 for 230 kV, 315 kV and 735 kV."
Resolution status
Accepted
Resolution detail
a note will be added to give the values of the first-pole-to-clear and to
explain the meaning of d and Z. Rated voltages will be used.
-
8/10/2019 Application Guide for TRV for High-Voltage Circuit Breakers.pdf
12/39
WG PC37.011 - Meeting May 201112 12
Discussion of Comments on D7
Comment # 144 Subclause 4.2.4.7
Comment
In line 16 the term "short-line fault" is spelled out and in line 18 theabbreviation SLF is used. Not sure when SLF is defined for the first time,but the term should be handled consistently.
Proposed change
Consistantly use "short-line fault" of SLF within the text.
Resolution status
Accepted
Resolution detail
short-line fault will be used here.
The use of SLF will be checked in the document.
-
8/10/2019 Application Guide for TRV for High-Voltage Circuit Breakers.pdf
13/39
WG PC37.011 - Meeting May 201113 13
Discussion of Comments on D7
Comment # 153 Subclause Annex A.2 Table A.2
Comment
Add typical surge impedance for 170kV overhead lines in Table A.2.
Proposed change
Here are surge impedance values for 3 different 161kV line configurations.
161-kV Horizontal config on steel towers:Xseries = 0.7366 ohms/mileYshunt = 5.800/10^6 = mhos/mile
Zc = sqrt(0.7366/[5.800/10^6]) = 356.37 ohms161 kV H-frame steel-pole line:
Xseries = 0.7390 ohms/mile
Yshunt = 5.849/10^6 = mhos/mileZc = sqrt(0.7390/[5.849/10^6]) = 355.45 ohms
161 kV Double circuit steel-pole line with both sides strung:Xseries = 0.7417 ohms/mile
Yshunt = 5.779/10^6 = mhos/mile
Zc = sqrt(0.7417/[5.779/10^6]) = 358.25 ohms
-
8/10/2019 Application Guide for TRV for High-Voltage Circuit Breakers.pdf
14/39
WG PC37.011 - Meeting May 201114 14
Discussion of Comments on D7
Comment # 153 (Contd)
Resolution status
Accepted in principle
Resolution detail
In the second column 145kV will be replaced by 145/170 kV
-
8/10/2019 Application Guide for TRV for High-Voltage Circuit Breakers.pdf
15/39
WG PC37.011 - Meeting May 201115 15
Discussion of Comments on D7
Comment # 154 Subclause Annex B page 70
Comment
Add capacitance values for other voltage CVTs.
Proposed change
Capacitances of commercially available 170kV CVTs range from 4000 to16000 pF. I'll provide info to the WG Chair for available CVTs.
Resolution status
Accepted
Resolution detail
Values for 170kV will be added and values will be updated.
-
8/10/2019 Application Guide for TRV for High-Voltage Circuit Breakers.pdf
16/39
WG PC37.011 - Meeting May 201116 16
Discussion of Comments on D7
Comment # 157 Subclause Figure 2 page 5
Comment
add "at T100" after "cable-system TRV"
Proposed change
change to "Figure 2-Comparison of line-system TRV and cable-systemTRV at T100"
Resolution status
Not accepted
Resolution detail
It will be indicated that time is in s and TRV is in kV
-
8/10/2019 Application Guide for TRV for High-Voltage Circuit Breakers.pdf
17/39
WG PC37.011 - Meeting May 201117 17
Discussion of Comments on D7
Comment # 158 Subclause 4.2.1 page 13
Comment
In the top figure, change "2.106" to "2.107" to be consistent with themultiplier Ku1 at T30 for 100 kV and above breakers in Table 1.
Proposed change
In the top figure, change "2.106" to "2.107" to be consistent with the
multiplier Ku1 at T30 for 100 kV and above breakers in Table 1
Resolution status
Accepted in principle.
Resolution detail
The numbers will be given with 3 significant digits.
-
8/10/2019 Application Guide for TRV for High-Voltage Circuit Breakers.pdf
18/39
WG PC37.011 - Meeting May 201118 18
Discussion of Comments on D7
Comment # 166 Subclause Figures 22a and 22b page 33
Comment
In Figure 22a, change one of the solid red curves and one of the solid bluecurves to dash lines for easier identifications.
Proposed change
In Figure 22a, change one of the solid red curves and one of the solid blue
curves to dash lines for easier identifications
Resolution status
Accepted
Resolution detail
The figure will be modified as proposed.
-
8/10/2019 Application Guide for TRV for High-Voltage Circuit Breakers.pdf
19/39
WG PC37.011 - Meeting May 201119 19
Discussion of Comments on D7
Comment # 167 Subclause 4.2.4.10 page 34
Comment
change "special customized tests or other means may be required" to"special customized tests or other means should be required". This isconsistent with CIGRE WG A3.19 report that "Utilities for whom thisposition is unacceptable should request special type tests for the particularconditions" and is consistent with our company's emphasis on safety.
Proposed change
change "special customized tests or other means may be required" to"special customized tests or other means should be required". This isconsistent with CIGRE WG A3.19 report that "Utilities for whom this
position is unacceptable should request special type tests for the particularconditions" and is consistent with our company's emphasis on safety.
-
8/10/2019 Application Guide for TRV for High-Voltage Circuit Breakers.pdf
20/39
WG PC37.011 - Meeting May 201120 20
Discussion of Comments on D7
Comment # 167 (Contd) Resolution status
Not accepted
Resolution detail
The text will be changed to "special customized tests or other means canbe specified"
-
8/10/2019 Application Guide for TRV for High-Voltage Circuit Breakers.pdf
21/39
WG PC37.011 - Meeting May 201121 21
Discussion of Comments on D7
Comment # 173 Subclause 1.1 page 10
Comment
calculation should be plural
Proposed change
change "calculation" to "calculations"
Resolution status
Not accepted
Resolution detail
The scope cannot be changed (without changing the PAR). The wording istaken from the existing standard.
-
8/10/2019 Application Guide for TRV for High-Voltage Circuit Breakers.pdf
22/39
WG PC37.011 - Meeting May 201122 22
Discussion of Comments on D7
Comment # 86 Subclause 3.3.1
Comment
C37.04 Subclause 5.9 states "At the rated maximum voltage, each circuitbreaker shall be capable of interrupting three phase grounded andungrounded terminal faults at the rated short circuit current in any circuit inwhich the TRV does not exceed the rated TRV envelope." The documentneeds a statement related to terminal faults in a three phase common gas-insulated switchgear enclosure.
Proposed change
In the case of a three phase common gas-insulated switchgear enclosure, anarc between phase and ground will, within a few milliseconds, evolve into athree phase fault between conductors, owing to the ionization of the gap
between the conductors, and at the same time the phase to ground arc willextinguish. Consequently, an enclosure burn-through is not likely. Since withinthe range of 20-50ms the fault has evolved into a three phase ungroundedfault, and since the breaker contacts typically begin to part at or after 50ms,then the three phase ungrounded fault should be considered in TRV analysis
for three phase common gas-insulated switchgear enclosures.
-
8/10/2019 Application Guide for TRV for High-Voltage Circuit Breakers.pdf
23/39
WG PC37.011 - Meeting May 201123 23
Discussion of Comments on D7
Comment # 86 Subclause 3.3.1
Resolution
Accepted in principle
Resolution detail
The following text will be added:
For GIS with all three phases in one enclosure a grounded fault can
evolve into a three-phase ungrounded fault prior to interruption. The usershould choose the appropriate first pole to clear factor i.e. kpp=1.5 forthree-phase ungrounded faults.
-
8/10/2019 Application Guide for TRV for High-Voltage Circuit Breakers.pdf
24/39
WG PC37.011 - Meeting May 201124 24
Discussion of Comments on D7
Comment # 102 Subclause 4.2.4.1 page 21
Comment
I have not seen any documentation that relates the 450ohm surgeimpedance with conductor clashing. Many tests have been done to causeconductor clashing without success. It is very rare and therefore the450ohm surge impedance has no relevance to clashing.
Proposed changeRemove all instances where the 450ohm surge impedance is related to
conductor clashing.
Resolution status
Not accepted
-
8/10/2019 Application Guide for TRV for High-Voltage Circuit Breakers.pdf
25/39
WG PC37.011 - Meeting May 201125 25
Discussion of Comments on D7
Comment # 102 Resolution detail
Early editions of international standards (ANSI/IEEE and IEC) for HVcircuit breakers have values of (line) surge impedance that were lower
than 400 ohms in case of bundle conductors, due to their geometry.Studies made at the end of the 1960's-beginning of the 1970's showedthat if conductors clash during a short-circuit then the surge impedancerise to a value approaching 450 ohm as the bundle can then approximatedby a single conductor. This studies lead to the generalization of the 450
ohm value in the full voltage range, in both IEC and ANSI/IEEE standards(previously IEC had 375 for 2 conductors/phase and 330 for 3 or 4
conductors per phase, ANSI/IEEE had similar values for bundledconductors: 360 ohm for 362kV and above).
Information on conductor clashing can be found in particular in "Surgeimpedance of overhead lines with bundle conductors during short-line
fault". Electra N17 , published in April 1971. The conclusion of the paperis as follows: "When the conductors are clashed together, these surgeimpedances will take a value of approximately 450 ohm whatever the
number of conductor in bundle may be".
-
8/10/2019 Application Guide for TRV for High-Voltage Circuit Breakers.pdf
26/39
WG PC37.011 - Meeting May 201126 26
Discussion of Comments on D7
Comment # 102 Resolution detail (Contd)
Link between the generalization of 450ohm and bundle contraction canalso be found in CIGRE Technical Brochure 305 (page 37).
This matter has been recently reviewed by CIGRE WG A3-22 for thespecification of the surge impedance of lines in 1100 kV networks. Due to
their large geometry and weight it has been concluded that conductor
clashing cannot occur in this case, so that the surge impedance had to be
reduced to 330 ohm.
In case of multi-conductors per phase, conductor clashing is theassumption behind the 450 ohm value, the guide presents the existingsituation, if later on standards are revised with a different assumption(leading to a lower value of the surge impedance) then this guide will be
aligned.
-
8/10/2019 Application Guide for TRV for High-Voltage Circuit Breakers.pdf
27/39
WG PC37.011 - Meeting May 201127 27
Discussion of Comments on D7
Comment # 103 Subclause 4.2.4.1 page 17
Comment
An assumption is implied that the majority of cases has short lines with X0being 2 to 3 times larger than X1. This is not necessarily true and shouldbe removed.
Proposed change
Remove this assumption.
Resolution status
Not accepted
Resolution detail
The text is correct, this is generally true. It should be reminded thateffectively grounded systems have by definition a ratio X0/X1 equal orlower than 3.
-
8/10/2019 Application Guide for TRV for High-Voltage Circuit Breakers.pdf
28/39
WG PC37.011 - Meeting May 201128 28
Discussion of Comments on D7
Comment # 104 Subclause 4.2.4.4 page 28
Comment
Remove reference to bundle clashing, it is not a proven phenomenon thataffects these calculations.
Proposed change
Remove the reference to bundle clashing.
Resolution status
Not accepted
Resolution detail
See resolution to comment 102.
-
8/10/2019 Application Guide for TRV for High-Voltage Circuit Breakers.pdf
29/39
WG PC37.011 - Meeting May 201129 29
Discussion of Comments on D7
Comment # 105 Subclause 4.2.4.5 page 30
Comment
450ohm surge impedance is not over-specified and is bundle clashing isnot common and should not be referenced to the 450ohm surgeimpedance.
Proposed change
Remove this whole paragraph as it does not provide any usefulinformation.
Resolution status
Not accepted
Resolution detail
See resolution to comment 102.
-
8/10/2019 Application Guide for TRV for High-Voltage Circuit Breakers.pdf
30/39
WG PC37.011 - Meeting May 201130 30
Discussion of Comments on D7
Comment # 106 Subclause 4.2.4.7 page 32
Comment
The CIGRE study referenced is highly controversial and it conclusion arenot widely accepted by users who would be using this guide. Thisdocument is not written to show that testing is sufficient for all cases andtherefore all references to that effect should be removed. In reading thisdocument it appears to be pointing to tests that cover certain fault cases.
This guide is to help evaluate the system and not testing.
Proposed change
Remove the reference and conclusions of the highly controversial CIGREstudy.
Resolution status
Not accepted
-
8/10/2019 Application Guide for TRV for High-Voltage Circuit Breakers.pdf
31/39
WG PC37.011 - Meeting May 201131 31
Discussion of Comments on D7
Comment # 106 Resolution detail
Concerning the reference to CIGRE: see resolution to comment #109
This subclause explains the influence of the short-circuit power of thesource on the TRV for a given current. There is nothing controversialabout this as explained in the answer to comment #107.
When the short-circuit power of the source is reduced, a given faultcurrent, e.g. 90% or 75% of rated short-circuit current, is obtained with a
shorter length of line, as a consequence the TRV peak is lower (RRRV isthe same but the time to peak related to the travel time of the wave isshorter). When the short-circuit power of the source is reduced, for thesame length of faulted line the fault current is lower and as a consequencethe TRV peak is lower (RRRV is lower as it is proportional to current, and
the time to peak is unchanged). This subclause could be developedfurther to explain this. What is explained here is pure physics and cannot
be contested.
-
8/10/2019 Application Guide for TRV for High-Voltage Circuit Breakers.pdf
32/39
WG PC37.011 - Meeting May 201132 32
Discussion of Comments on D7
Comment # 107 Subclause Figures 22a & 22b page 33
Comment
These graphs are relevant in C37.09 not in an application guide. Theseare conclusions drawn by a highly controversial CIGRE study.
Proposed change
Remove both figures.
Resolution status
Not accepted
-
8/10/2019 Application Guide for TRV for High-Voltage Circuit Breakers.pdf
33/39
WG PC37.011 - Meeting May 201133 33
Discussion of Comments on D7
Comment # 107 Resolution detail
Figures are better than a thousand words, they illustrate in a clear waythat for a given fault current, the amplitude of the first peak of TRV is
greatly influenced by the short-circuit power of the source. This is relevantin a Guide on TRVs in which the influence of different parameters onTRVs is explained. There is nothing controversial about this (as well asother parts of the CIGRE study), it could be proven also by a simplifiedcalculation that the Chair will be happy to provide, if necessary.
These figures have nothing to do with testing and would be of no interestin C37.09.
-
8/10/2019 Application Guide for TRV for High-Voltage Circuit Breakers.pdf
34/39
WG PC37.011 - Meeting May 201134 34
Discussion of Comments on D7
Comment # 108 Subclause 4.2.4.10 page 34
Comment
This clause appears to be the conclusion of the comparison added to thedocument. This is not the place to repeat a highly controversialconclusion. This guide should show how to calculate/determine thesystem TRV and compare it to the TRV testing. Anything beyond that usesassumptions and rationals that are controversial and not proven by tests.
Proposed change
Remove the clause.
Resolution status
Not accepted
Di i f C D7
-
8/10/2019 Application Guide for TRV for High-Voltage Circuit Breakers.pdf
35/39
WG PC37.011 - Meeting May 201135 35
Discussion of Comments on D7
Comment # 108 Resolution detail
After the explanations given in the previous subclauses, the aim of thisone is to draw the attention of the reader to a few important aspects that
need to be taken into consideration, in particular when writingspecifications, to avoid unrealistic demands. Experience shows that thereis some misunderstanding concerning the TRVs during three-phaseterminal faults (kpp= 1.5 is not applicable to the last pole to clear), suchmisunderstanding must be avoided also in the case of three-phase line
faults.
The reader of the guide must understand that a peak factor (d) higher than
2 is only possible when there is coupling between phases, and thereforecannot be requested for the last-pole-clear and the relevant arcing times
(no coupling possible when the other lines are opened).This has nothing to do with testing, but is about the understanding of thee-
phase line fault TRVs. The wording can be improved but this must becovered here.
Di i f C t D7
-
8/10/2019 Application Guide for TRV for High-Voltage Circuit Breakers.pdf
36/39
WG PC37.011 - Meeting May 201136 36
Discussion of Comments on D7
Comment # 109 Subclause reference B19 page 81
Comment
This is highly controversial and does not belong in the document.
Proposed change
Remove this reference.
Resolution statusNot accepted
Di i f C t D7
-
8/10/2019 Application Guide for TRV for High-Voltage Circuit Breakers.pdf
37/39
WG PC37.011 - Meeting May 201137 37
Discussion of Comments on D7
Comment # 109 Resolution detail
The reference to CIGRE Technical Brochure 408 will be kept as itrepresents the most comprehensive and recent study on line fault
phenomena and their implications for 3-phase short and long line faultclearing. It is useful to the reader who wants to have a deepunderstanding of these phenomena.
CIGRE is a world renowned organization that thoroughly checks the
content of its publications. The document was submitted to the membersof the CIGRE study committee A3 and approved before publication.
In TB 408 CIGRE gives technical information and refrains from makingrecommendation on standardization work. The view expressed in thecomment is personal and not accepted.
The reference is also needed as text and Figures are taken from [B18](formerly B19).
Discussion of Comments on D7
-
8/10/2019 Application Guide for TRV for High-Voltage Circuit Breakers.pdf
38/39
WG PC37.011 - Meeting May 201138 38
Discussion of Comments on D7
Next steps/ActionsThe file of comments made during the ballot of Draft 7 will be updated with
the resolutions decided during the meetings in Las Vegas and Lake Buena
Vista. It will be sent to WG members (Denis).
Prepare a new draft that takes into account the resolutions on comments(Denis)
The revised draft will be sent to WG members to check that the changesreflect the resolutions (All).
Helmut will send a proposal to revise the TLF section (Helmut).
Roy will provide a text to comment on range on CVT capacitance values in
Table B.4 (Roy).
The new draft for recirculation will be D9
Recirculate D9 preferably between mid-August and mid-September onorder to have votes and comments available for the next WG meeting inOctober 2011 (Denis).
The comments made during recirculation will be sent before the next WGmeeting in October (Denis).
IEEE WG C37 011
-
8/10/2019 Application Guide for TRV for High-Voltage Circuit Breakers.pdf
39/39
WG PC37.011 - Meeting May 201139 39
Thanks for your participation !
IEEE WG C37.011Application Guide for TRV for High-Voltage Circuit Breakers