application notes
DESCRIPTION
Since 1992 Bayside HVAC products has provided engineering support and sales for HVAC control peripherals and specialty controls. We provide consulting engineers with design assistance, contractors with product and support and end users with service. Contact us for information or a quote.TRANSCRIPT
![Page 1: Application Notes](https://reader038.vdocument.in/reader038/viewer/2022100501/568c4d581a28ab4916a3978c/html5/thumbnails/1.jpg)
FILENAME
ISOLATION ROOM 3 MONITORING LAYOUTS.VSD
SCALE
NTS
DATE
11/1/2010
Isolation Room Pressure Monitoring
Various Layouts Page 1 of 2
BY
DS
REV
1
Bayside HVAC
Products LLC
415-333-5099
Single Isolation Room
Ante Room & (1) Isolation Room
-0.01 InWc
Patient Room
(Pressure Monitored
Room)
120:24
120VAC
BMS
Symbol Key
120:24
Transformer
Use TSI supplied transformer.
Separate transformer for each DIM
DIM
(Digital Indication Module) Keypad &
Display, A/V Alarms. Mount outside
room, 60" AFF
Room Pressure Sensor
UL 2 Hour Fire Wall Rated
Bi-Directional, Mount over door
-0.01 InWc
Nurse A/V Alarm
Locate at nurse station
Not generally required for Pharmacies
Output To BMS
Alarm Relays, Room Pressure Analog
signal, Network connection (BACnet,
LON, N2, Modbus, see quote)
Door Switch
SPDT On Each Door into room
Note: Door witches are optional,
reduces nuisance callbacks.
Patient Room
120:24
120VAC
Ante Room
Door switch on all doors
-0.01 InWc
Hallway
Hallway
BMS
![Page 2: Application Notes](https://reader038.vdocument.in/reader038/viewer/2022100501/568c4d581a28ab4916a3978c/html5/thumbnails/2.jpg)
Dual Isolation Rooms with
(1) Shared Ante Room
Patient Room
120:24
120VAC
Output To BMS
Patient Room
120:24
120VAC
Ante Room
Door switch on all doors
See plans for # of doors
DIM #1
-0.01 InWc
Output To BMS
DIM #2
Symbols Key
120:24
Transformer
Use TSI supplied transformer.
Separate transformer for each DIM
DIM
(Digital Indication Module) Keypad &
Display, A/V Alarms. Mount outside
room, 60" AFF
Room Pressure Sensor
UL 2 Hour Fire Wall Rated
Bi-Directional, Mount over door
-0.01 InWc
Nurse A/V Alarm
Locate at nurse station
Not generally required for Pharmacies
Output To BMS
Alarm Relays, Room Pressure Analog
signal, Network connection (BACnet,
LON, N2, Modbus, see quote)
Door Switch
SPDT On Each Door into room
Note: Door witches are optional,
reduces nuisance callbacks.
-0.01 InWc
Hallway
FILENAME
ISOLATION ROOM 3 MONITORING LAYOUTS.VSD
SCALE
NTS
DATE
11/1/2010
Isolation Room Pressure Monitoring
Various Layouts Page 2 of 2
BY
DS
REV
1
Bayside HVAC
Products LLC
415-333-5099