un WASHiNaTONSTATEMTBOl Washington State Patrol Fire Protection Bureau Phone: (360)596-3900 Business Name Address City, State, Zip Ashley Gardens of Bremerton 3231 Pine RD, Bremerton, WA 98337 Provider Number Approval Status Facility Type 001947 Approved Residential Care On 4/5/2018 the Office of the State Fire Marshal conducted an inspection at your facility. Code Requirement Statement of Violation 1 Admin New Requirements For your information: 703.2 Opening protectives. Opening protective shall be maintained in an operative condition in accordance with NFPA 80. NFPA80 Chapter 19 Installation, Testing, and Maintenance of Fire Dampers. 19.4 Periodic Inspection and Testing. 19.4.1 Each damper shall be tested and inspected 1 year after installation. 19.4.1.1 The test and inspection frequency shall then be every 4 years, except in hospitals, where the frequency shall be every 6 years. EFFECTIVE JULY 1,2018. 907.10 National Institute for Certification in Engineering Technologies. 907.10.1 Scope. This section shall apply to new and existing fire alarms systems. 907.10.2 Design review. All construction documents shall be reviewed by a NICET III in fire alarms or a licensed professional engineer (PE) in Washington prior to being submitted for permitting. The reviewing professional shall submit a stamped, signed, and dated letter; or a verification method approved by the local authority having jurisdiction indicating the system has been reviewed and meets or exceeds the design requirement of the Washington and the local jurisdiction (effective July 1 , 2018). 907.10.3 Testing/maintenance: All inspection, testing maintenance and programing not defined as "electrical trade" by chapter 19.28 ROW shall be completed by a NICET II in fire alarms (effective July 1, 2018). Ensure your Fire Sprinkler company verifies placement of sprinkler heads and light fixtures and documents the findings for your records. All tests shall be conducted each quarter and documented below. These are minimum requirements. Check with your fire sprinkler contractor for the specific needs of your system. NOTE: NOTIFY MONITORING AGENCY PRIOR TO CONDUCTING TESTS. Main Drain Test Record the static water supply pressure in psi as indicated of the lower pressure gauge. Open the main drain and allow water flow to stabilize. Record the residual water supply pressure while water is flowing from the 2" main drain as indicated on the lower pressure gauge in psi. Close the main drain (slowly). Wet Pipe System Flow Alarm Test water flow alarms by opening the inspectors test valve. (Notify alarm company to avoid false alarms). Wet Pipe System Gauges Inspect & Alarm Test (monthly) Gauges are in good condition and normal pressures are maintained. Alarm Devices - Inspect exterior. Fire Department Connections Verify connection is visible and accessible, not damaged, caps or plugs are in place, identification sign is in place, and automatic drain is working properly. Hydraulic Nameplate If system was hydraulically calculated, assure nameplate is legible and 1 of 5 Initials of Authorized Facility Representative:

Upload: others

Post on 20-Oct-2021

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Approved Approval Status 3231 Pine RD ... - Washington

unWASHiNaTONSTATEMTBOl

Washington State PatrolFire Protection Bureau

Phone: (360)596-3900

Business Name

Address

City, State, Zip

Ashley Gardens of Bremerton

3231 Pine RD,

Bremerton, WA 98337

Provider Number

Approval Status

Facility Type

001947

Approved

Residential Care

On 4/5/2018 the Office of the State Fire Marshal conducted an inspection at your facility.

Code Requirement Statement of Violation

1 Admin New Requirements

For your information:

703.2 Opening protectives. Opening protective shall bemaintained in an operative condition in accordance with NFPA80.

NFPA80 Chapter 19 Installation, Testing, and Maintenance ofFire Dampers.19.4 Periodic Inspection and Testing.19.4.1 Each damper shall be tested and inspected 1 year afterinstallation.19.4.1.1 The test and inspection frequency shall then be every4 years, except in hospitals, where the frequency shall be every6 years.

EFFECTIVE JULY 1,2018.907.10 National Institute for Certification in EngineeringTechnologies.907.10.1 Scope. This section shall apply to new and existingfire alarms systems.907.10.2 Design review. All construction documents shall bereviewed by a NICET III in fire alarms or a licensed professionalengineer (PE) in Washington prior to being submitted forpermitting. The reviewing professional shall submit a stamped,signed, and dated letter; or a verification method approved bythe local authority having jurisdiction indicating the system hasbeen reviewed and meets or exceeds the design requirementof the Washington and the local jurisdiction (effective July 1 ,2018).907.10.3 Testing/maintenance: All inspection, testingmaintenance and programing not defined as "electrical trade"by chapter 19.28 ROW shall be completed by a NICET II in firealarms (effective July 1, 2018).

Ensure your Fire Sprinkler company verifies placement ofsprinkler heads and light fixtures and documents the findingsfor your records.

All tests shall be conducted each quarter and documentedbelow.

These are minimum requirements. Check with your firesprinkler contractor for the specific needsof your system.NOTE: NOTIFY MONITORING AGENCY PRIOR TOCONDUCTING TESTS.Main Drain TestRecord the static water supply pressure in psi as indicated ofthe lowerpressure gauge.Open the main drain and allow water flow to stabilize.Record the residual water supply pressure while water isflowing from the 2"main drain as indicated on the lower pressure gauge in psi.Close the main drain (slowly).Wet Pipe System Flow AlarmTest water flow alarms by opening the inspectors test valve.(Notify alarmcompany to avoid false alarms).Wet Pipe System Gauges Inspect & Alarm Test (monthly)Gauges are in good condition and normal pressures aremaintained.Alarm Devices - Inspect exterior.Fire Department ConnectionsVerify connection is visible and accessible, not damaged, capsor plugs arein place, identification sign is in place, and automatic drain isworkingproperly.Hydraulic NameplateIf system was hydraulically calculated, assure nameplate islegible and

1 of 5 Initials of Authorized Facility Representative:

Page 2: Approved Approval Status 3231 Pine RD ... - Washington

Washington State PatrolFire Protection Bureau

Phone: (360)596-3900

Business Name

Address

City, State, Zip

Ash ley Gardens of Bremerton

3231 Pine RD,

Bremerton, WA 98337

Provider Number

Approval Status

Facility Type

001947

Approved

Residential Care

On 4/5/2018 the Office of the State Fire Marshal conducted an inspection at your facility.

Code Requirement Statement of Violation

securely attached to riser.Valves all Types - Visually inspect pressure reducing andrelieve valves.Dry Pipe System Flow AlarmOpen the alarm bypass valve. (Notify alarm company to avoidfalse alarms).Caution: opening the inspectors test connection can cause thesystem totrip accidentally, allowing the pipes to fill with water andcreating a potentialfor a serious freeze problem.Dry Pipe Priming LevelCheck dry priming water level by opening the test valve andchecking for asmall amount of water to discharge. If no water flows out of thetest line,add priming water.Dry Pipe system Low-Air-Pressure AlarmLow air pressure alarms, if provided, shall be .tested quarterlyin accordancewith the manufacturers instructions.NOTIFY MONITORING AGENCY THAT TEST ISCOMPLETED ANDSYSTEM IS BACK IN SERVICE.

2 Ceiling clearance.

Storage shall be maintained 2 feet (610 mm) or more below theceiling in nonsprinklered areas of buildings or a minimum of 18inches (457 mm) below sprinkler head deflectors in sprinkleredareas of buildings.

(IFC 315.3.1 2052)

2 of 5 Initials of Authorized Facility Representative:

Page 3: Approved Approval Status 3231 Pine RD ... - Washington

Washington State PatrolFire Protection Bureau

Phone: (360)596-3900

Business Name

Address

City, State, Zip

Ashley Gardens of Bremerton

3231 Pine RD,

Bremerton, WA 98337

Provider Number

Approval Status

Facility Type

001947

Approved

Residential Care

On 4/5/2018 the Office of the State Fire Marshal conducted an inspection at your facility.

Code Requirement Statement of Violation

3 Operational Inspection and Testing

Emergency power systems, including all appurtenantcomponents shall be inspected and tested under load inaccordance with NFPA 110 and NFPA 111.

Exception: Where the emergency power system is used forstandby power or peak load shaving, such use shall berecorded and shall be allowed to be substituted for scheduledtesting of the generator set, provided that appropriate recordsare maintained.

(IFC 604.5 2015)

4 Activation test record.

Records of tests shall be maintained The record shall includethe location of the emergency lighting tested, whether the unitpassed or failed, the date of the test, and the personcompleting the test.

(IFC 604.5.1.1 2015)5 Inspection, testing and maintenance.

Fire detection, alarm, and extinguishing systems, mechanicalsmoke exhaust systems, and smoke and heat vents shall bemaintained in an operative condition at all times, and shall bereplaced or repaired where defective. Nonrequired fireprotection systems and equipment shall be inspected, testedand maintained or removed.

(IFC 901.6 2012,2015)

3 of 5 Initials of Authorized Facility Representative:^

Page 4: Approved Approval Status 3231 Pine RD ... - Washington

RJWASH

Washington State PatrolFire Protection Bureau

Phone: (360)596-3900

Business Name

Address

City, State, Zip

Ashley Gardens of Bremerton

3231 Pine RD,

Bremerton, WA 98337

Provider Number

Approval Status

Facility Type

001947

Approved

Residential Care

On 4/5/2018 the Office of the State Fire Marshal conducted an inspection at your facility.

Code Requirement Statement of Violation

6 Portable Fire Extinguishers - General Requirements

Portable fire extinguishers shall be selected, installed andmaintained in accordance with this section and NFPA 10.

Exceptions:

1. The distance of travel to reach an extinguisher shallnot apply The travel distance to reach an extinguisher shall notapply to the spectator seating portions of Group A-5occupancies.

2. Thirty-day inspections shall not be required andmaintenance shall be allowed to be once every three years fordry-chemical or halogenated agent portable fire extinguishersthat are supervised by a listed and approved electronicmonitoring device, provided that all of the following conditionsare met:

2.1. Electronic monitoring shall confirm that extinguishersare properly positioned, properly charged and unobstructed.

2.2. Loss of power or circuit continuity to the electronicmonitoring device shall initiate a trouble signal.

2.3. The extinguishers shall be installed inside of abuilding or cabinet in a noncorrosive environment.

2.4. Electronic monitoring devices and supervisorycircuits shall be tested every three years when extinguishermaintenance is performed.

2.5. A written log of required hydrostatic test dates forextinguishers shall be maintained by the owner to verify thathydrostatic tests are conducted at the frequency required byNFPA10.

3. In Group 1-3, portable fire extinguishers shall bepermitted to be located at staff locations.

IFC 906.2 2015

4 of 5 Initials of Authorized Facility Representative:

Page 5: Approved Approval Status 3231 Pine RD ... - Washington

WAsmwaTON STATE P»TROL

Washington State PatrolFire Protection Bureau

Phone: (360)596-3900

Business Name

Address

City, State, Zip

Ashtey Gardens of Bremerton

3231 Pine RD,

Bremerton, WA 98337

Provider Number

Approval Status

Facility Type

001947

Approved

Residential Care

On 4/5/2018 the Office of the State Fire Marshal conducted an inspection at your facility.

Code Requirement Statement of Violation

7 Smoke detector sensitivity.

Smoke detector sensitivity shall be checked within one yearafter installation and every alternate year thereafter. After thesecond calibration test, where sensitivity tests indicate that thedetector has remained within its listed and marked sensitivityrange (or 4-percent obscuration light grey smoke, if notmarked), the length of time between calibration tests shall bepermitted to be extended to a maximum of five years. Wherethe frequency is extended, records of detector-causednuisance alarms and subsequent trends of these alarms shallbe maintained. In zones or areas where nuisance alarms showany increase over the previous year, calibration tests shall beperformed.

(IFC 907.8.3 2012)

Next inspection scheduled on or after: 3/31/2019

Right of appeal. Any person may appeal any decision made by the Fire Protection Bureau in accordance with WAC 212-12.

Owpe^or Authorized Representative

( ^^^-(C}^^\ . fl^S!>^^ ^c^^a-0,^h/^

Print Name and Title

Deputy State Fire Marshal Scott Campos2803 156AVESEBellevueWA 98007(360)481-9360

Signature

5 of 5 Initials of Authorized Facility Representative:

Page 6: Approved Approval Status 3231 Pine RD ... - Washington

WABIIIUQTONiiTATC FATOai

Washington State PatrolFire Protection Bureau

Phone: (360)596-3900

Business Name

Address

City, State, Zip

Ashley Gardens of Bremerton

3231 Pine RD,

Bremerton, WA 98337

Provider Number

Approval Status

Facility Type

001947

Disapproved

Residential Care

On 03/06/2018 the Office of the State Fire Marshal conducted an inspection at your facility.

Code Requirement Statement of Violation

1 Admin New Requirements

For your information:

703.2 Opening protectives. Opening protective shall bemaintained in an operative condition in accordance with NFPA80.NFPA 80 Chapter 19 Installation, Testing, and Maintenance ofFire Dampers.19.4 Periodic Inspection and Testing.19.4.1 Each damper shall be tested and inspected 1 year afterinstallation.19.4.1.1 The test and inspection frequency shall then be every4 years, except in hospitals, where the frequency shall be every6 years.

EFFECTIVE JULY 1,2018.907.10 National Institute for Certification in EngineeringTechnologies.907.10.1 Scope. This section shall apply to new and existingfire alarms systems.907.10.2 Design review. All construction documents shall bereviewed by a NICET III in fire alarms or a licensed professionalengineer (PE) in Washington prior to being submitted forpermitting. The reviewing professional shall submit a stamped,signed, and dated letter; or a verification method approved bythe local authority having jurisdiction indicating the system hasbeen reviewed and meets or exceeds the design requirementof the Washington and the local jurisdiction (effective July 1,2018).907.10.3 Testing/maintenance: All inspection, testingmaintenance and programing not defined as "electrical trade"by chapter 19.28 RCW shall be completed by a NICET II in firealarms (effective July 1, 2018).

1 of 4 Initials of Authorized Facility Representative:

Page 7: Approved Approval Status 3231 Pine RD ... - Washington

BJB.Washington State PatrolFire Protection Bureau

Phone: (360)596-3900

Business Name

Address

City, State, Zip

Ashley Gardens of Bremerton

3231 Pine RD,

Bremerton, WA 98337

Provider Number

Approval Status

Facility Type

001947

Disapproved

Residential Care

On 03/D6/2018 the Office of the State Fire Marshal conducted an inspection at your facility.

Code Requirement

2 Ceiling clearance.

Statement of Violation

Storage shall be maintained 2 feet (610 mm) or more below theceiling in nonsprinklered areas of buildings or a minimum of 18inches (457 mm) below sprinkler head deflectors in sprinkleredareas of buildings.

HFC 315.3.1 2052)

The linen closets in Buildings A, B, C,and D had storagewithin 24 inches of the ceiling. No sprinkler head was observedin the closets.

3 Operational Inspection and Testing

Emergency power systems, including all appurtenantcomponents shall be inspected and tested under load inaccordance with NFPAHOand NFPA111.

Exception: Where the emergency power system is used forstandby power or peak load shaving, such use shall berecorded and shall be allowed to be substituted for scheduledtesting of the generator set, provided that appropriate recordsare maintained.

(IFC 604.5 2015)

The monthly load bank test records for the run hours were notaccurate. The hours were going up and down from week toweek and month to month. The facility was made aware of theerrors. Run hours should only go up.

4 Activation test record.

Records of tests shall be maintained The record shall includethe location of the emergency lighting tested, whether the unitpassed or failed, the date of the test, and the personcompleting the test.

(IFC 604.5.1.1 2015)

The facility was missing the December 2017 and February2018 emergency light testing records.

5 Inspection, testing and maintenance.

Fire detection, alarm, and extinguishing systems, mechanicalsmoke exhaust systems, and smoke and heat vents shall bemaintained in an operative condition at all times, and shall bereplaced or repaired where defective. Nonrequired fireprotection systems and equipment shall be inspected, testedand maintained or removed.

(IFC 901.6 2012,2015)

The sprinkler heads in D building kitchen had excessive dirt onit.

The annual sprinkler report stated that the majority of sprinklerheads in the building were blocked by light fixtures.

The annual sprinkler report stated that the tamper switch wiresneeded to be switched.

2 of 4 Initials of Authorized Facility Representative:

Page 8: Approved Approval Status 3231 Pine RD ... - Washington

BHWSliiUOTONSrAf^PA'rBSl

kM

Washington State PatrolFire Protection Bureau

Phone: (360)596-3900

Business Name

Address

City, State, Zip

Ashley Gardens of Bremerton

3231 Pine RD,

Bremerton, WA 98337

Provider Number

Approval Status

Facility Type

001947

Disapproved

Residential Care

On 03/D6/2018 the Office of the State Fire Marshal conducted an inspection at your facility.

Code Requirement

6 Portable Fire Extinguishers - General Requirements

Statement of Violation

Portable fire extinguishers shall be selected, installed andmaintained in accordance with this section and NFPA 10.

Exceptions:

1. The distance of travel to reach an extinguisher shallnot apply The travel distance to reach an extinguisher shall notapply to the spectator seating portions of Group A-5occupancies.

2. Thirty-day inspections shall not be required andmaintenance shall be allowed to be once every three years fordry-chemical or halogenated agent portable fire extinguishersthat are supervised by a listed and approved electronicmonitoring device, provided that all of the following conditionsare met:

2.1. Electronic monitoring shall confirm that extinguishersare properly positioned, properly charged and unobstructed.

2.2. Loss of power or circuit continuity to the electronicmonitoring device shall initiate a trouble signal.

2.3. The extinguishers shall be installed inside of abuilding or cabinet In a noncorrosive environment.

2.4. Electronic monitoring devices and supervisorycircuits shall be tested every three years when extinguishermaintenance is performed.

2.5. A written log of required hydrostatic test dates forextinguishers shall be maintained by the owner to verify thathydrostatic tests are conducted at the frequency required byNFPA10.

3. In Group 1-3, portable fire extinguishers shall bepermitted to be located at staff locations.

IFC 906.2 2015

D Building:

Extinguisher by D4 was missing the February sign off.The extinguisher by the food pantry was undercharged and inthe red.

C Building:

Extinguisher by C9 and C3 missing February sign off

B Building:

Extinguisher by B3 missing February sign off

3 of 4 Initials of Authorized Facility Representative;

Page 9: Approved Approval Status 3231 Pine RD ... - Washington

WAtllHHGTQNSrATI: IWIR31.I^P^^^J^^^

Washington State PatrolFire Protection Bureau

Phone: (360)596-3900

^Business Name

[Address

City, State, Zip

Ashley Gardens of Bremerton

3231 Pine RD ,

Bremerton, WA 98337

Provider Number

Approval Status

Facility Type

001947

Disapproved

Residential Care

On 03/U6/201 8 the Office of the State Fire Marshal conducted an inspection at your facility.

Code Requirement

7 Smoke detector sensitivity.

Statement of Violation

The facility had not been keeping a nuisance log.I Smoke detector sensitivity shall be checked within one yearI after installation and every alternate year thereafter. After thesecond calibration test, where sensitivity tests indicate that the

I detector has remained within its listed and marked sensitivity[range (or 4-percent obscuration light grey smoke, if notmarked), the length of time between calibration tests shall be

[permitted to be extended to a maximum of five years. Wherethe frequency is extended, records of detector-caused

[nuisance alarms and subsequent trends of these alarms shallbe maintained. In zones or areas where nuisance alarms showany increase over the previous year, calibration tests shall beperformed.

/IFC 907.8.3 2012) _.Next inspection scheduled on or after; 04/05/2018

Right of appeal. Any person mayafipeal any decision made by the Fire Protection Bureau in accordancs with WAC 212-12.