apvvdt1402 cautions on product corrosion - · pdf fileit enables long piping length up to 165m...

6
*Specifications, designs and other content appearing in this brochure are current as of April 2014 but subject to change without notice. Warning Ask a qualified installer or contractor to install this product. Do not try to install the product yourself. Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion. Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or contractor to install those parts and accessories. Use of unauthorised parts and accessories or improper installation of parts and accessories can result in water or refrigerant leakage, electrical shock, fire or explosion. Read the User's Manual carefully before using this product. The User's Manual provides important safety instructions and warnings. Be sure to follow these instructions and warnings. If you have any enquiries, please contact your local importer, distributor and/or retailer. Cautions on product corrosion 1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced. 2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install the outdoor unit close to the sea shore, contact your local distributor. © All rights reserved VRV +AHU System DAIKIN NEW STANDARD SERIES UNIT MODEL AHUR-CA/SA PREVIEW APVVDT1402 Daikin Industries (Thailand) Ltd. United Business Center II Building, Floor 17 591 Sukhumvit Rd, Sukhumvit 33, North Klongton, Wattana, Bangkok 10110

Upload: trinhdien

Post on 18-Mar-2018

218 views

Category:

Documents


4 download

TRANSCRIPT

Page 1: APVVDT1402 Cautions on product corrosion - · PDF fileIt enables long piping length up to 165m and ... • AHU Coil Material Type Blue Fin Copper Fin ... AHU SPECIFICATION VRV+AHU

*Specifications, designs and other content appearing in this brochure are current as of April 2014 but subject to change without notice.

Warning Ask a qualified installer or contractor to install this product. Do not try to install the product yourself. Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.

Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or contractor to install those parts and accessories. Use of unauthorised parts and accessories or improper installation of parts and accessories can result in water or refrigerant leakage, electrical shock, fire or explosion.

Read the User's Manual carefully before using this product. The User's Manual provides important safety instructions and warnings. Be sure to follow these instructions and warnings.

If you have any enquiries, please contact your local importer, distributor and/or retailer.

Cautions on product corrosion1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install the outdoor unit close to the sea shore, contact your local distributor.

© All rights reserved

VRV+AHU SystemDAIKIN NEW STANDARD SERIES UNIT MODEL AHUR-CA/SA

PR

EV

IEW

AP

VV

DT

140

2

Daikin Industries (Thailand) Ltd.United Business Center II Building, Floor 17591 Sukhumvit Rd, Sukhumvit 33,North Klongton, Wattana, Bangkok 10110

Page 2: APVVDT1402 Cautions on product corrosion - · PDF fileIt enables long piping length up to 165m and ... • AHU Coil Material Type Blue Fin Copper Fin ... AHU SPECIFICATION VRV+AHU

VRV+AHU Applications

Sports Hall

Shopping Mall

Factory

Hospital

Lobby

Airport

Warehouse

What is VRV?Daikin VRV system is a multi-split type air conditioner for commercial buildings that uses variable refrigerant flow control developed by Daikin.

It enables long piping length up to 165m and maximum level difference (between outdoor and indoor units) of 90m to provide more design flexibility which can match even large-sized buildings.

It allows one touch selection control using intelligent Touch Manager and includes options to link with BACnet® to enhance the Building Management System (BMS).

Daikin release a new standard series unit model AHUR-CA/SA (Single Skin / Double Skin). It is a DX AHU system that is specially designed to work with the VRV IV outdoor unit. This new model release is an inlet temperature control type AHU. This will enable the users to reduce maintenance costs and enjoy more space savings.

AHUR-CA/SA also improves the indoor air quality from haze, pollutants, etc using the options of pre-filers and primary filters. VRV+AHU are the only total AHU solutions provided and manufactured completely by Daikin.

Total Daikin Solutions (All products

manufacture by Daikin Factory)

Total Daikin Solutions (All products

manufacture by Daikin Factory)

Air Handling Unit

VRV+AHU System Connection Overview

VRV+AHU Introduction

01 02

???? ?

?

?

?

VRV+AHU ApplicationFor small to large commercial spaces Daikin offers a range of R-410A inverter condensing units for use in conjunction with Air Handling Units (AHU) from 6 HP to 60 HP.

AHU provide large volumes and high ESPs (External Static Pressure) enabling the use of extensive ductwork runs. The refrigerant flows through the copper pipes using R-410A and operates like a large VRV fan coil unit.

Daikin AHU represents the ideal solution for large storage places, atrium, lobby, banquet halls, showrooms, exhibition halls, shopping malls, etc.

It also have the options to customize the specifications such as the filtration type, direction of air in-take and discharge, service access door and blower type (backward or forward curves and plug fan).?

Remote Control Wiring (P1P2)

Liquid

Gas

Control Wiring

Showroom

Page 3: APVVDT1402 Cautions on product corrosion - · PDF fileIt enables long piping length up to 165m and ... • AHU Coil Material Type Blue Fin Copper Fin ... AHU SPECIFICATION VRV+AHU

Features of VRV+AHU - Inlet Temperature control

• Harnessing VRV IV current and latest

technology of VRT

• Inverter controlled system (only Z - Control)

• Can be easily controlled via standard wired remote

control (BRC1E62)

• Comes in dual skin type model - double skin panel

model and single skin panel model

• Easily manage using intelligent Touch Manager

central control system

Communication protocol using DIII-Net to

communicate with all existing Dakin

communication devices and even BMS.

• Can be placed indoor or outdoor*

*Optional items required

Benefits of using VRV+AHU

• Quality assured

VRV+AHU are manufactured by Daikin factory.

• Ease of the installation

No additional system such as cooling tower, chiller,

and long water piping system are required. This

also reduces the total system maintance costs.

Flexible design of the ducting system.

• Cover large area with different ducting configuration.

• VRV+AHU can provide ESP up to 500Pa*

(Standard Model)

• Total solution concept

Integrating an AHU into the total building climate

system enables both design and installation

procedures to be based on a single common

technology. This simplifies project follow-up,

installation, commissioning and maintenance

since only one party is involved.

• VRV+AHU system can be coupled and mixed with

other type indoor unit to work together concurrently.

(Connection ratio 50% - 110%)

Options

Wide range of options are available to meet your design

requirements.

Please contact Daikin’s Sales Office regarding below

mentioned options:

• Fan Type

Backward Curve Aerofoil

Plug Fan

• AHU Coil Material Type

Blue Fin

Copper Fin

Gold Fin

Aluminum Tube

Stainless Tube

Anti-Corrosive Epoxy Coating

• AHU Drain Pan Type

Steel Coating with

Acrylic Enamel

Galvanized Steel

• AHU Air Filter Type

Medium Filter

Extra Filter

Synthetic

Bag

HEPA

Aluminum

Cartridge

ULPA

• Special Option

Electric Heater

Mixing Box

Outdoor Roof

Panel Thickness 50mm

• Customisation

Airflow

Capacity

ESP

Discharge Direction

Piping Outlet

Comparison Table and Diagram for Conventional AHU System and VRV+AHU System

Conventional AHU System VRV+AHU System

Easy Maintenance (same as common A/C System)

No Additional Maintenance Cost

Require Small Installation Space(AHU, VRV)

Simple System(HVAC Ducting)

Simple Control(Remote Control / intelligent Touch Manager)

* For ESP more than 500Pa, please contact Daikin’s Sales Office

Require Frequent Maintenance (Cooling Tower + Chiller)

Higher Cost Due to Frequent Maintenance

Require Larger Installation Space(AHU, Chiller, Cooling Tower)

Complex System(HVAC Ducting, Chiller and Water Piping)

Extensive Control (Variable Frequency Device, Variable Air Volume Control)

03 04

VR

V IV

Max

. 90

m

AHU

Office

Office

Office

Basement CarparkChiller

AHU

Office

Office

Office

Lobby Lobby

Free Space

Underground

CoolingTower

Conventional AHU System VRV+AHU System

Page 4: APVVDT1402 Cautions on product corrosion - · PDF fileIt enables long piping length up to 165m and ... • AHU Coil Material Type Blue Fin Copper Fin ... AHU SPECIFICATION VRV+AHU

VRV+AHU Inlet Temperature Standard Series Range

The VRV+AHU standard series are available from the capacity range of 6HP to 60HP, also with airflow ranging from 3,240 CMH – 28,080 CMH.

Airflow (x 103 CMH)

VRV+AHU Standard Series Coil, Expansion Valve Kit and Control BoxAHUR-CA/SA standard series model is using the DX coil. Each DX coil will be connected to one external expansion valve kit (EKEXV) and controlled by one control box kit (EKEQMCB).

VRV+AHU Standard Series Coil

• 3 Type of Coils - 6HP used by 6HP, 12HP AHU unit - 8HP used by 8HP, 16HP AHU unit - 10HP used by 10HP, 20HP, 30HP, 40HP, 50HP, 60HP AHU unit

VRV+AHU Expansion Valve Kit (EKEXV)

• 3 Type AHU Expansion Valve Kit - EKEXV140 for 6HP Coil - EKEXV200 for 8HP Coil - EKEXV250 for 10HP Coil

VRV+AHU Control Box Kit (EKEQMCB)

Possibility Z (Ts/Tr control):Using Daikin wired remote controller (BRC1E62 - optional) Set point can be fixed via standard Daikin wired remote controller. Remote ON/OFF can be achieved by an optional adapter KRP4AA51.

No additional external controller is required. The cooling load is determined from the air suction temperature and set point on the Daikin controller.

Ts = Air suction temperatureTd = Air discharge temperatureTr = Room temperature

Te = Evaporating temperatureAHU = Air Handling Unit

KRP4AA51

Ts Te Td

AHU

Tr RoomBRC1E62

ON / OFF

Daikincontrol box:EKEQMCB

VR

V+

AH

U C

apa

cit

y

60 HP

50 HP

40 HP

30 HP

20 HP

16 HP

12 HP

10 HP

8 HP

6 HP 3.24

4.08

4.68

6.48

8.16

9.36

14.04

18.27

23.40

28.08

0 5 10 15 20 25 30

Comparison for External Static Pressure and Capacity between VRV+AHU and Duct Typed Unit

FXMQ VRV+AHU

0 200

External Static Pressure (Pa)

400 600

From To

100 PaFXMQ 270 Pa

250 PaVRV+AHU 500 Pa

FXMQ

VRV+AHU

0 10 20 30 40 50 60 70

Capacity (HP)

From To

2 HPFXMQ 10 HP

6 HPVRV+AHU 60 HP

Expanded Line Up for Daikin VRV Indoor Series

VRV+AHU offers higher ESP and Capacity as compared to duct typed unit.

VRV+AHU Operation Range

VRV+AHU AHUR-CA/SA operation is similar as other VRV indoor unit. Following table is the list of operation range limit condition for the AHU unit to work.

Cooling

Entering Air Temperature Minimum 14°C WB

On Heat Exchanger AHU Maximum 35°C DB / 25°C WB

Outdoor Unit VRV 4 Minimum -5°C DB

Maximum 43°C DB

Expansion Valve Kit Minimum -20°C WB

Maximum 46°C DB

Control Box Minimum -10°C WB

Maximum 40°C DB

TemperatureRange

VRV AHU Expansion Valve Kit

Front View Side View

VRV AHU Control Box KitEKEQMCB

Application Multi

Outdoor Unit VRV IV

Casing Colour White grey

Material Resin

Dimensions Unit H x W x D mm 132 x 400 x 200

Weight Unit Kg 3.6

Operation Range Cooling Min. ~ Max. ˚CDB -10.0 ~ 40.0

Power Supply

Phase 1 Frequency Hz 50 Voltage V 230

EKEXV250EKEXV200EKEXV140

Casing Colour Ivory white

Material Metal

Dimensions Unit H x W x D mm 401 x 215 x 78

Weight Unit Kg 2.9

Operation Cooling Min. ~ Max. ˚CDB -5.0 ~ 46.0Range

Refrigerant Type R-410A

Liquid Type / OD mm Braze connection / 9.52

Gas Type / OD mm Braze connection / 9.52 Heat Insulation Both inlet and outlet

Pipingconnections

Depth

Hei

gh

t

Width

05 06

Page 5: APVVDT1402 Cautions on product corrosion - · PDF fileIt enables long piping length up to 165m and ... • AHU Coil Material Type Blue Fin Copper Fin ... AHU SPECIFICATION VRV+AHU

VRV Connection to AHU Configuration

Multiple Connections with Other Indoor Unit Configuration

Multiple VRV Systems Connection Configuration

VRV IV6 – 60 HP

VRV IV20 HP

VRV IV20 HP VRV IV

20 HP

VRV IV6 – 20 HP

Single VRV System Connection Configuration

Each coil up to 10 HP (Max combination of 6) = 60 HP

Up to 60 HPMax.6 circuits

VRV Combined System Connection Configuration

07 08

Remote Control Wiring (P1P2) LiquidControl Wiring Gas

Page 6: APVVDT1402 Cautions on product corrosion - · PDF fileIt enables long piping length up to 165m and ... • AHU Coil Material Type Blue Fin Copper Fin ... AHU SPECIFICATION VRV+AHU

AHU SPECIFICATIONSAHU SPECIFICATION VRV+AHU (CA/SA)

CASING / INSULATION(CA SERIES)

CASING / INSULATION(SA SERIES)

CASING-FRAME

COILTUBEFINHEADERFRAMEWORKING PRESSURE

FANTYPEWHEELHOUSINGFRAME

MOTOR

VIBRATION ISOLATOR

DRAIN PAN

AIR FILTER

25mm Thickness Single Skinned Panel0.5mm Thickness White Colourbond Steel Sheet25mm Thickness PU Foam 40Kg/M3

20mm Thickness Single Skinned Panel1.2mm Thickness Steel Sheet with Ivory White Powder Coated20mm Thickness PU Sponge 18Kg/M3 Density

Steel Made With Black Colour Epoxy Paint

DX CoilCopper TubeAluminum MadeCopper TubeGalvanized Steel10Kg/cm2G or Below

(Brand = Kruger)Double Inlet Forward Curved Centrifugal Belt Drive FanGalvanized SteelGalvanized SteelSteel With Polyester Powder Coated

(Brand = Inline)Three-Phrase Induction Motor Totally Enclosed Fan-Cooled TypeProtection = IP55 Insulation Class = F

Spring Isolator

1.2mm (SUS 304)Beneath The Drain Pan is Covered With 20mm PE Insulation 35Kg/M3 Density

(Brand = AAF)Type = R29 Class = G3 (AFI = 80%) washableSize = Full (24" x 24" x 2") Half (12" x 24" x 2")Frame Galvanized Steel

Notes:1. Net capacity includes indoor fan heat.2. Gross capacity does not include indoor fan heat.3. With pre filter, AAF synthetic R29 & class G3 (Wasable) eff 80-85%.4. Motor is induction motor class F, IP 55.5. It is necessary to reduce piping size by reducer when connection (19.1 → 15.9, 22.2 → 19.1, 28.6 → 22.2)6. The connection ratio of the outdoor unit must be within the limits specified by the outdoor unit and must additionally be within 50% and 110%.

Conversion formular

kcal/h=kWx860

cfm=m3/minx35.3

Drawings and Dimension of AHU

1300 x 1300 x 1100

1300 x 1200 x 1100

1500 x 1200 x 1100

1400 x 1500 x 1300

1400 x 1500 x 1300

1500 x 1500 x 1300

1500 x 1900 x 1900

1500 x 1900 x 2200

2800 x 2000 x 1800

2800 x 2100 x 1800

AHUR06CA/SA

AHUR08CA/SA

AHUR10CA/SA

AHUR12CA/SA

AHUR16CA/SA

AHUR20CA/SA

AHUR30CA/SA

AHUR40CA/SA

AHUR50CA/SA

AHUR60CA/SA

ModelDimension

W x D x H (mm)

Total Cooling Capacity KW 16.9 16.8 16.7 16.5 16.4 22.9 22.8 22.7 22.4 22.3 28.4 28.3 28.2 28 27.8 34 33.8 33.7 33.3 33 45.5 45.3 45.1 44.7 44.5

Total Sensible Cooling Capacity KW 12.4 12.3 12.2 12 11.9 16.8 16.7 16.6 16.3 16.2 20.9 20.8 20.7 20.5 20.3 25 24.8 24.7 24.3 24 33.3 33.1 32.9 32.5 32.3

Total Cooling Capacity KW

Sensible Cooling Capacity KW

CMH

⁰CDB/⁰CWB

⁰CDB/⁰CWB

m2

m/s

Pa

Pa

PCS.

PCS.

Pa

Pa 250 300 350 450 500 250 300 350 450 500 250 300 350 450 500 250 300 350 450 500 250 300 350 450 500

Pa 460 510 560 660 710 460 510 560 660 710 460 510 560 660 710 460 510 560 660 710 460 510 560 660 710

KW 3.0 2.2 4.0 3.0

POLE

Volt/Ph./Hz.

amp. 6.76 5.0 8.8 6.76

kg 540 610 630 630

dBA 84 85 86 88 89 77 78 79 81 82 77 78 79 81 82 87 88 89 92 93 87 88 89 91 92

Model / PCS.

Model / PCS.

Liquid pipes mm

Gas pipes *5 mm

Drain pipes mm

620 640Machine Weight 485 495 480 485 530

32 32

Electronic expanison valve Electronic expanison valve

9.5 (Brazing connection) x 2 9.5 (Brazing connection) x 2

19.1 (Brazing connection) x 2 22.2 (Brazing connection) x 2

EKEQMCBV3 / 2 pcs. EKEQMCBV3 / 2 pcs.

EKEXV140 / 2 pcs. EKEXV200 / 2 pcs.

4 4

380-415/3/50 380-415/3/50

6.76 8.8

30 30

FORWARD CURVE

FDA315TM FDA315TM

3.0 4.0

80 80

2 2

2 2

0.982 0.886

1.83 2.56

100 100

DX.COIL(R410A) ф8mm. WAVE SLIT SURFACE & STRAIGHT EDGE

6,480 8,160

27/19 27/19

14.4/13.1 13.6/12.714.4/13.1 13.6/12.7 12.5/12.4

AHUR12CA/SA AHUR16CA/SA

35.8 48.0

26.8 35.8

Refrigerant Control Electronic expanison valve Electronic expanison valve Electronic expanison valve

Panel

PipingConnections

9.5 (Brazing connection) 9.5 (Brazing connection) 9.5 (Brazing connection)

19.1 (Brazing connection) 22.2 (Brazing connection) 28.6 (Brazing connection)

32 32 32

Outlet Sound Level ( Pressure )

Control Box Kit EKEQMCBV3 / 1 pcs. EKEQMCBV3 / 1 pcs. EKEQMCBV3 / 1 pcs.

Expansion Valve Kit EKEXV140 / 1 pcs. EKEXV200 / 1 pcs. EKEXV250 / 1 pcs.

Power Supply 380-415/3/50 380-415/3/50 380-415/3/50

FLA 3.7 5.0 3.7 5.0 5.0

Fan Motor *41.5 2.2 1.5 2.2 2.2

4 4 4

ESP.Initial

Total Statics Pressure

Fan Type FORWARD CURVE

Model FSA315CM FDA250TM FDA250TM

Air Filter Size 24"X24X2" *3 1 1 2

Air PD.In Casing 30 30 30

Air PD.In Pre Filter *3 80 80 80

Air Filter Size 12"X24X2" *3 1 1 -

Coil Face Vel. 1.83 2.56 2.41

Air PD.In Coil 100 100 100

Coil Type

Coil Face Area 0.491 0.443 0.54

Ent.Temp. 27/19 27/19 27/19

Lea.Temp.

17.9 22.3

Air Flow 3,240 4,080 4,680

Model AHUR06CA/SA AHUR08CA/SA AHUR10CA/SA

NET *1

GROSS *217.9 24.0 29.8

13.4

313 429Capacity Index 157 214 266

CA/SA Double Skinned/Single Skinned

Total Cooling Capacity KW 57.3 57.1 56.9 56.4 56.2 86.1 85.8 85.5 84.9 84.6 115 114 114 113 113 144 143 143 142 141 172 172 171 170 169

Total Sensible Cooling Capacity KW 42.3 42.1 41.9 41.4 41.2 63.6 63.3 63 62.4 62.1 84.5 84.2 83.8 83 82.6 106 106 105 104 104 127 127 126 125 124

Total Cooling Capacity KW

Sensible Cooling Capacity KW

CMH

⁰CDB/⁰CWB

⁰CDB/⁰CWB

m2

m/s

Pa

Pa

PCS.

PCS.

Pa

Pa 250 300 350 450 500 250 300 350 450 500 250 300 350 450 500 250 300 350 450 500 250 300 350 450 500

Pa 460 510 560 660 710 460 510 560 660 710 460 510 560 660 710 460 510 560 660 710 460 510 560 660 710

KW 4.0 5.5

POLE

Volt/Ph./Hz.

amp. 8.8 11.5

kg 880 980

dBA 82 83 84 86 88 85 86 87 89 91 85 86 87 89 89 86 87 87 89 90 84 84 85 87 88

Model / PCS.

Model / PCS.

Liquid pipes mm

Gas pipes *5 mm

Drain pipes mm

1460 1540Machine Weight 665 675 895 1000 1420

DX.COIL(R410A) ф8mm. WAVE SLIT SURFACE & STRAIGHT EDGE

32 32 32

Electronic expanison valve Electronic expanison valve Electronic expanison valve

9.5 (Brazing connection) x 4 9.5 (Brazing connection) x 5 9.5 (Brazing connection) x 6

28.6 (Brazing connection) x 4 28.6 (Brazing connection) x 5 28.6 (Brazing connection) x 6

EKEQMCBV3 / 4 pcs. EKEQMCBV3 / 5 pcs. EKEQMCBV3 / 6 pcs.

EKEXV250 / 4 pcs. EKEXV250 / 5 pcs. EKEXV250 / 6 pcs.

380-415/3/50 380-415/3/50 380-415/3/50

15.3 15.3 22.3 22.3

7.5 7.5 11 114 4 4

30 30 30

FORWARD CURVE

FDA500TM FDA560TM FDA630TM

- 4 4

6 8 8

100 100 100

80 80 80

2.16 2.7 3.24

2.41 2.41 2.41

27/19 27/19 27/19

12.5/12.4 12.5/12.4 12.5/12.4

89.2 111.5 133.8

18,720 23,400 28,080

AHUR40CA/SA AHUR50CA/SA AHUR60CA/SA

119.2 149.0 178.8

Refrigerant Control Electronic expanison valve Electronic expanison valve

PipingConnections

9.5 (Brazing connection) x 2 9.5 (Brazing connection) x 3

28.6 (Brazing connection) x 2 28.6 (Brazing connection) x 3

32 32

Outlet Sound Level (Pressure)

Control Box Kit EKEQMCBV3 / 2 pcs. EKEQMCBV3 / 3 pcs.

Expansion Valve Kit EKEXV250 / 2 pcs. EKEXV250 / 3 pcs.

Power Supply 380-415/3/50 380-415/3/50

FLA 6.76 8.8 11.5

Fan Motor *43.0 4.0 5.5

4 4

ESP.Initial

Total Statics Pressure

Fan Type FORWARD CURVE

Model FDA355TM FDA450TM

Air Filter Size 24"X24X2" *3 2 4

Air PD.In Casing 30 30

Air PD.In Pre Filter *3 80 80

Air Filter Size 12"X24X2" *3 2 2

Coil Face Vel. 2.41 2.41

Air PD.In Coil 100 100

Lea.Temp. 12.5/12.4 12.5/12.4

Coil Type

Coil Face Area 1.08 1.62

Air Flow 9,360 14,040

Ent.Temp. 27/19 27/19

Model AHUR20CA/SA AHUR30CA/SA

NET *1

GROSS *259.6 89.4

44.6 66.9

Panel CA/SA Double Skinned/Single Skinned

1064 1330 1586Capacity Index 532 798

10

* Dimension does not include Control Box, Expansion Valve and Pre-filter

Front View

Hei

gh

t

Side View

Depth110

(Filter)Width

3

09

* Dimension does not include Control Box, Expansion Valve and Pre-filter

1

2

3

4

5

6

7

8