aquam phil walker presentation v2 - world watertech london · 2019-03-27 · title: microsoft...

12
Zero Leakage Phil Walker February 25 th 2019 www.aquamcorp.co.uk

Upload: others

Post on 11-Aug-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Aquam Phil Walker Presentation v2 - World WaterTech London · 2019-03-27 · Title: Microsoft PowerPoint - Aquam Phil Walker Presentation v2 Author: Laura Hodgkiss Created Date: 2/25/2019

Zero Leakage

Phil Walker

February 25th 2019

www.aquamcorp.co.uk

Page 2: Aquam Phil Walker Presentation v2 - World WaterTech London · 2019-03-27 · Title: Microsoft PowerPoint - Aquam Phil Walker Presentation v2 Author: Laura Hodgkiss Created Date: 2/25/2019

Toolbox

www.aquamcorp.co.uk 2

Page 3: Aquam Phil Walker Presentation v2 - World WaterTech London · 2019-03-27 · Title: Microsoft PowerPoint - Aquam Phil Walker Presentation v2 Author: Laura Hodgkiss Created Date: 2/25/2019

3

Technology Capability Features Pipe Diameter Range Access

Bullet Visual inspectionLeak detection

• All pipe materials• Tri-sensor head (camera,

hydrophone, sonde)

4+ Inches 12 Miles (untethered)

Most valves, hot taps

Investigator Visual inspectionLeak detection

• All pipe materials• Tri-sensor head (camera,

hydrophone, sonde)

3+ Inches 100 Meters Fire hydrant, most valves, hot taps

LDS1000 Visual inspectionLeak detection

• All pipe materials• Tri-sensor head (camera,

hydrophone, sonde)

12+ Inches 1,000 Meters Most valves, hot taps

Amplus Visual inspectionLeak detectionCondition assessment

• Iron & steel pipes• Tri-sensor head (camera,

hydrophone, sonde)

8-24 Inches 1,000 Meters Most valves

Pipe Diagnostics

www.aquamcorp.co.uk 3

Page 4: Aquam Phil Walker Presentation v2 - World WaterTech London · 2019-03-27 · Title: Microsoft PowerPoint - Aquam Phil Walker Presentation v2 Author: Laura Hodgkiss Created Date: 2/25/2019

• Inspection and leak detection• Potable water pipelines of 50-300mm (2-12

inch) diameter, through live fire hydrants. • Up to 100m (300 feet) • Pressures of up to 16 bar (232psi)

• Internal inspection without disruption• Live-feed CCTV images • Real-time hydrophone data• High-powered sonde information• GPS tracking and plotting of leaks and

defects• Used for valve assessment

www.aquamcorp.co.uk

InvestigatorTM Benefits

4

Page 5: Aquam Phil Walker Presentation v2 - World WaterTech London · 2019-03-27 · Title: Microsoft PowerPoint - Aquam Phil Walker Presentation v2 Author: Laura Hodgkiss Created Date: 2/25/2019

• Internal inspection without disruption• GPS tracking and plotting of leaks and

defects• Operates in pressures of up to 16 bar

(232psi)• Pre and post rehabilitation assessment• Used for valve assessment

InvestigatorTM Benefits

BENEFITS:

www.aquamcorp.co.uk 5

Page 6: Aquam Phil Walker Presentation v2 - World WaterTech London · 2019-03-27 · Title: Microsoft PowerPoint - Aquam Phil Walker Presentation v2 Author: Laura Hodgkiss Created Date: 2/25/2019

• GPS track and plotting of leaks and defects

• Operates under pressures of 16 bar (232psi)

• CCTV inspection of pipelines

• Enables long-distance line tracing

• Identifies illegal connections and services

BENEFITS:

www.aquamcorp.co.uk

LDS1000TM Benefits

6

Page 7: Aquam Phil Walker Presentation v2 - World WaterTech London · 2019-03-27 · Title: Microsoft PowerPoint - Aquam Phil Walker Presentation v2 Author: Laura Hodgkiss Created Date: 2/25/2019

Visual Inspection

• Obstructions

• Illegal Connections

• Deflected Joints

• Fractures

• Tuberculation

• Air Pockets

• Sedimentation

www.aquamcorp.co.uk 7

Page 8: Aquam Phil Walker Presentation v2 - World WaterTech London · 2019-03-27 · Title: Microsoft PowerPoint - Aquam Phil Walker Presentation v2 Author: Laura Hodgkiss Created Date: 2/25/2019

Case Study: Fast & Thorough Leak Detection

Water Company A Working in Collaboration with Contractor

Technology/Approach• Investigator™ is a push rod system up to 200m- 100m in either direction - camera, sonde,

hydrophone• Highly skilled team• Two units used by two gangs to accurately find leaks in difficult to access locations and where above

ground conditions cause issues

Results• Successful identification of leaks – 100%• Dry holes reduced- almost to zero as leak found within 30cm accuracy• Reduction of TMA and notices as access quick and via TBH or drilling saddle• Efficient - 5 different sites per day

www.aquamcorp.co.uk 8

Page 9: Aquam Phil Walker Presentation v2 - World WaterTech London · 2019-03-27 · Title: Microsoft PowerPoint - Aquam Phil Walker Presentation v2 Author: Laura Hodgkiss Created Date: 2/25/2019

Water Company B - Super Leakage Team- Contractor

Technology/Approach• Use of new technology to identify leaks – Investigator™• Specific technology critical to assist leakage gangs• Small, highly skilled team• Valve left open• Supply to different DMA• Small leakage on main 4 inch

Results• Leaks found estimated to be over 5 years old• Over 500m3 of water loss over 5 year period found in 6 months• Zero dry holes• DMA Water balance corrected

Case Study: Super Leakage Team

www.aquamcorp.co.uk 9

Page 10: Aquam Phil Walker Presentation v2 - World WaterTech London · 2019-03-27 · Title: Microsoft PowerPoint - Aquam Phil Walker Presentation v2 Author: Laura Hodgkiss Created Date: 2/25/2019

Case Study: Upskilled Workforce Provides Efficiencies

Water Company C use employee with technology

Technology/Approach• Technology- hydrant camera/ Investigator™

• Access through hydrant- TBH• No or little TMA• Provides solutions to pressure/discoloration and leakage issues

• Inspectors with knowledge of DMA• Use technology to understand local impacts if leakage gangs unsuccessful

Results• Upskilled with technology - provided training and technology to support existing team• Improved efficiency

www.aquamcorp.co.uk 10

Page 11: Aquam Phil Walker Presentation v2 - World WaterTech London · 2019-03-27 · Title: Microsoft PowerPoint - Aquam Phil Walker Presentation v2 Author: Laura Hodgkiss Created Date: 2/25/2019

Case Study: NRW - A “Smart” Approach

Water Company D needed to improve Non Revenue Water through Water Balance

Technology/Approach• Aquam above ground GPRS smart units on all standpipes that access hydrants• Use of existing standpipes – up skill with smart technology• Created an above ground network• Metered and non metered standpipes• Data captured every 15 mins and available at control centre - location, date and time, water used• Water consumption from access to hydrants daily, weekly, monthly, annually• Use on DMA assumptions• Can identify cause of network issues such as bursts and discoloration

Results• Improve data on water balance• Increase value of Non Revenue Water as accurately measured• Efficient use of leakage teams• Reduction of leakage

www.aquamcorp.co.uk 11

Page 12: Aquam Phil Walker Presentation v2 - World WaterTech London · 2019-03-27 · Title: Microsoft PowerPoint - Aquam Phil Walker Presentation v2 Author: Laura Hodgkiss Created Date: 2/25/2019

Case Study In Detail: India Trials 2018 (MCGM)

www.aquamcorp.co.uk 12

Wednesday, October 3, 2018:Inspection – Lodha Complex, Kanjur Village RdPipe Diameter: 150mmPipe Material: Ductile ironInsertion Tap: 50mm ball valvePressure: 20psiVelocity: N/A

Inspection Detail Points:Total distance inspected upstream: 43.8 metersTotal distance inspected downstream: 93.4 metersSimulated leak detected at 25.9 meters downstreamSimulated leak detected at 39.4 meters upstreamSensor head located using sonde at 37.6 meters and 20 meters

Full distance of the inspection was achieved downstream, total of 43.8 meters was achieved upstream due to the bend configuration and the tuberculation in the bends.

Insertion Point