aramco fireproofing drawing ad-036711-001
TRANSCRIPT
-
7/22/2019 Aramco Fireproofing Drawing AD-036711-001
1/1
990 AD-0367110
CONCRETE FIREPROOFING F
07 06.09.85LMLCOMPLETELY REDRAWN, REVISED &
SEE NOTE-3
0
0
50
CHANGED DWG. SIZE FROM E TO D.
25mm
50
WIRE MESH
50
50
12-720-570).
4. ALL DIMENSIONS ARE IN MILLIMETER
UNLESS NOTED OTHERWISE.
MANDATORY DRAW
08
Q
12-743-620).
KMS08-13-90
4"x4"-10 GA.x10 GA., (SAMS NO. 12-7OR 2"x2"-14 GA.x14 GA., (SAMS NO.
1. ALL FIREPROOFING SHALL BE IN ACWITH SAES-B-006. THIS DRAWING SHO
ACCEPTABLE DETAILS FOR CONCRETEFIREPROOFING ONLY. FOR OTHER MAT
ETC., REFER TO SAES-B-006, SECTIO
TACK-WELDED AT 600mm CTRS. (SAM
REVISED & CHANGED INDEX
FROM "S" TO "Q".
09RLO
ESSDGENERAL REVISION.MAY95
STRUCTURAL MEMBERS
STD. DWG.
990QAD-03671100109
(TYP.)
SEE NOTE-2
SPACERS (TYP.)
CHAMFER
(TYP.)
BEAMS
(EXCEPT ANGLES, AND
PIPE SUPPORTS)
50
50
SPACERS (TYP.)SEE NOTE-3
WIRE MESH(TYP.)SEE NOTE-2
25mmCHAMFER(TYP.)
COLUMNS
(EXCEPT PIPES)
50
50mmCHAMFER
WIRE MESH(TYP.)SEE NOTE-2
SPACERS (TYP.)SEE NOTE-3
50
25mmCHAMFER
(TYP.)
20mm DIA.CONNECTORS
SEE NOTE-3
PIPE SUPPORTS
50
50
50
50
SEE NOTE-3SPACERS (TYP.)
WIRE MESH(TYP.)SEE NOTE-2
CHAMFER
(TYP.)
25mm
ANGLES
D
A=D+140 (TYP.)
SPACERS (TYP.)SEE NOTE-3
C=0.30A, (TYP.)
A
WIRE MESH, SEE NOTE-2(MAINTAIN 20mm
SPACING FROM STEEL)
PIPE COLUMNS
2. ALL WIRE MESH SHALL BE
3. 20mm DIA.x125mm SPACERS (AND CO
PLANT NO. INDEX DRAWING NUMBER SHE
PLANTNO.INDEXDRAWINGNUMBERSHEETNO.REV.NO.
THIS DRAWING IS NOT TO BE USED FOR
CONSTRUCTION OR FOR ORDERING
MATERIAL UNTIL CERTIFIED AND DATED
CERTIFIED
DRAWN BY
DATE STARTED
OPRG. DEPT.
APPD. FOR CONSTR.
CHECKED BY
DATE COMPLETED
ENG. DEPT.
DATE BY DESCRIPTION CREV.
NO.JO/EWO
NOTES:
BY
OIL COMPASAUDI ARABIAN
Saudi Aram
CopyrightSaudi Aramco 2009. All rights reserved.