Sheet Number Sheet Name Area Plan Project Phase Project Number Issue Date in cite v . to provoke thought Licensed Architect MIKE HILMES License MO #2000157579 Cert. of Authority A - 2004016376 INCITE DESIGN STUDIO, LLC Architect INCITE DESIGN STUDIO 1800 LAFAYETTE AVENUE, SUITE B ST. LOUIS, MO 63104 PHONE: 314 - 279 - 4500 Mech., Plumb., Elec., Telecom. BRiC PARTNERSHIP, LLC 3636 SOUTH GEYER ROAD, SUITE 305 ST. LOUIS, MO 63127 PHONE: 314 - 725 - 5889 Construction Manager NAVIGATEl: 9920 WATSON RD., SUITE 201 ST. LOUIS, MO 63126 PHONE: 314 - 713 - 6205 Revision No. Description Date Issued KSD PROJECT # NGL - 2021 - SECURED VESTIBULE KSD PROJECT # NGL - 2021 - SECURED VESTIBULE 4/7/2021 8:22:06 AM C:\Users\brian.nash\Documents\20-203 North Glendale Elem Vestibule Add_bnashFHP5U.rvt BID DOCUMENTS 04/08/2021 SHEET INDEX 04/08/2021 20 - 203 BID DOCUMENTS G0.1 765 N. SAPPINGTON ROAD GLENDALE, MO 63122 NORTH GLENDALE ELEMENTARY SCHOOL SECURED VESTIBULE RENOVATION PROJECT SECURED VESTIBULE RENNOVATION PROJECT NORTH GLENDALE ELEMENTARY SCHOOL KIRKWOOD SCHOOL DISTRICT DRAWING INDEX INTERIOR RENDERING ARCHITECT MEP ENGINEER LOCATION: 765 N SAPPINGTON RD, ST. LOUIS, MO 63122 GENERAL G0.1 SHEET INDEX G0.2 SYMBOLS & ABBREVIATIONS ARCHITECTURAL A1.1 Demolition, Floor & Reflected Ceiling Plans A9.1 DOOR SCHEDULE ELEVATIONS, FRAME TYPES & DETAILS A11.00A FINISH LEGEND, SCHEDULE & DETAILS MECHANICAL M0.1 LEGENDS, SYMBOLS, AND NOTES - MECHANICAL M0.2 DEMOLITION, FLOOR, & REFLECTED CEILING PLANS - MECHANICAL M1.1 SEISMIC CODE BLOCK - MECHANICAL ELECTRICAL E0.1 SEISMIC CODE BLOCK - ELEC. & TECH. COMM. E0.2 LEGEND, SYMBOLS & NOTES - ELETRICAL E1.1 DEMOLITION PLAN - ELECTRICAL E2.1 FLOOR PLAN - NEW WORK - POWER E3.1 REFLECTED CEILING PLAN - NEW WORK - LIGHTING E5.1 DETAILS - ELECTRICAL TECHNOLOGY T0.2 LEGEND, SYMBOLS & NOTES - TECHNOLOGY T1.1 DEMOLITION PLAN - TECHNOLOGY COMMUNICATION T2.1 FLOOR PLAN - NEW WORK - TECHNOLOGY COMMUNICATION T5.1 DETAILS - TECHNOLOGY COMMUNICATION INCITE DESIGN STUDIO, LLC 1800 LAFAYETTE AVENUE, SUITE B ST. LOUIS, MO 63104 PHONE: 314 - 279 - 4500 CONSTRUCTION MANAGER BRiC PARTNERSHIP, LLC 3636 SOUTH GEYER ROAD, SUITE 305 ST. LOUIS, MO 63127 PHONE: 314 - 725 - 5889 NAVIGATE BUILDING SOLUTIONS 9920 WATSON RD., SUITE 201 ST. LOUIS, MO 63126 PHONE: 314 - 713 - 6205

Upload: others

Post on 20-Jul-2021

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Architect NORTH GLENDALE ELEMENTARY SCHOOL...FOC FOF FOM FOS FOW FP FPM FR FR FS FS FSD FT FT FTG FUT FVC FWC G G GA GAL GALV GB GC GCO GCMU GD GEN GEN GFA GFI GFRC GI GLAM GL GMU

Sheet Number

Sheet Name

Area Plan

Project Phase

Project Number

Issue Date

in • cite v. to provoke thought

Licensed Architect

MIKE HILMES

License

MO #2000157579

Cert. of Authority

A-2004016376INCITE DESIGN STUDIO, LLC

Architect

INCITE DESIGN STUDIO1800 LAFAYETTE AVENUE, SUITE BST. LOUIS, MO 63104PHONE: 314-279-4500

Mech., Plumb., Elec., Telecom.

BRiC PARTNERSHIP, LLC3636 SOUTH GEYER ROAD, SUITE 305ST. LOUIS, MO 63127PHONE: 314-725-5889

Construction Manager

NAVIGATEl: 9920 WATSON RD., SUITE 201ST. LOUIS, MO 63126

PHONE: 314-713-6205

Revision No. Description Date Issued

KSD PROJECT # NGL-2021-SECURED VESTIBULE

KSD PROJECT # NGL-2021-SECURED VESTIBULE

4/7

/2021 8

:22:0

6 A

M

C:\

Users

\bri

an.n

ash\D

ocum

ents

\20-2

03

Nort

h G

lendale

Ele

m V

estibule

Add_bnashF

HP

5U

.rvt

BID DOCUMENTS04/08/2021

SHEET INDEX

04/08/2021

20-203

BID DOCUMENTS

G0.1

765 N. SAPPINGTON ROADGLENDALE, MO 63122

NORTH GLENDALEELEMENTARYSCHOOL SECUREDVESTIBULERENOVATIONPROJECT

SECURED VESTIBULE RENNOVATION PROJECT

NORTH GLENDALE ELEMENTARY SCHOOLKIRKWOOD SCHOOL DISTRICT

DRAWING INDEXINTERIOR RENDERING

ARCHITECT MEP ENGINEER LOCATION: 765 N SAPPINGTON RD, ST. LOUIS, MO 63122

GENERAL

G0.1 SHEET INDEX

G0.2 SYMBOLS & ABBREVIATIONS

ARCHITECTURAL

A1.1 Demolition, Floor & Reflected Ceiling Plans

A9.1 DOOR SCHEDULE ELEVATIONS, FRAME TYPES &DETAILS

A11.00A FINISH LEGEND, SCHEDULE & DETAILS

MECHANICAL

M0.1 LEGENDS, SYMBOLS, AND NOTES - MECHANICAL

M0.2 DEMOLITION, FLOOR, & REFLECTED CEILING PLANS -MECHANICAL

M1.1 SEISMIC CODE BLOCK - MECHANICAL

ELECTRICAL

E0.1 SEISMIC CODE BLOCK - ELEC. & TECH. COMM.

E0.2 LEGEND, SYMBOLS & NOTES - ELETRICAL

E1.1 DEMOLITION PLAN - ELECTRICAL

E2.1 FLOOR PLAN - NEW WORK - POWER

E3.1 REFLECTED CEILING PLAN - NEW WORK - LIGHTING

E5.1 DETAILS - ELECTRICAL

TECHNOLOGY

T0.2 LEGEND, SYMBOLS & NOTES - TECHNOLOGY

T1.1 DEMOLITION PLAN - TECHNOLOGY COMMUNICATION

T2.1 FLOOR PLAN - NEW WORK - TECHNOLOGYCOMMUNICATION

T5.1 DETAILS - TECHNOLOGY COMMUNICATION

INCITE DESIGN STUDIO, LLC1800 LAFAYETTE AVENUE, SUITE B

ST. LOUIS, MO 63104PHONE: 314-279-4500

CONSTRUCTION MANAGER

BRiC PARTNERSHIP, LLC3636 SOUTH GEYER ROAD, SUITE 305

ST. LOUIS, MO 63127PHONE: 314-725-5889

NAVIGATE BUILDING SOLUTIONS9920 WATSON RD., SUITE 201

ST. LOUIS, MO 63126PHONE: 314-713-6205

Page 2: Architect NORTH GLENDALE ELEMENTARY SCHOOL...FOC FOF FOM FOS FOW FP FPM FR FR FS FS FSD FT FT FTG FUT FVC FWC G G GA GAL GALV GB GC GCO GCMU GD GEN GEN GFA GFI GFRC GI GLAM GL GMU

ABBREVIATIONS

A/CA AMPAAAPABABSACACCACCUACMACSTACTADADADDNADJADJTADMINAFAFFAHUAIALTALUMALCWALSFAMBANCHAPAPCAPPARARCHASBASPHAUTOAVAVAWGAWP

B to BBBOBCMUBDBFPBFRBHPBKRBLBLDGBLKBLCKGBLKHDBMBMBOBODBOFBRDGBRKTBSMTBTUBTUHBUR

CCABCANTCAPCASCDCCTVCECEMCENTCERCFCFHCFMCGCHCICIPCIRCCJCKTCKT BKCLCLGCLOSCLRCMCMPCMUCOCOCO2COLCOMCOMBCOMMCOMPCOMPCOMPRCONCCONFCONFIGCONNCONNCONSTCONTCONTRCONVCORRCPCPCPSCPTCRCSCSKCSTJCSWKCTCTR

COPPERCONDENSING UNITCUBICCOMBINATION UNITCOLD WATERCUBIC YARDCYLINDER

DRAINDEPTHDATADRY BULBDECIBELDEFORMED BAR ANCHORDOUBLEDIRECT CURRENTDUST COLLECTORDUMMY CONTROL JOINTPENNY (AS NAIL 100)DIRECT DIGITAL CONTROLDEGREEDEPRESS(ION)(ED)DEPARTMENTDETENTIONDRINKING FOUNTAINDOOR GRILLEDUCT HEATERDUCTILE IRONDIAMETERDIAGONALDIFFUSERDIMENSIONDISCONNECT SWITCHDISCONNECTDISCHARGEDISTRIBUTIONDEAD LOADDAMPER MOTORDAMPERDOWNDOWNSPOUT NOZZLEDITTODAMPPROOFINGDOORDRAINDOWNSPOUTDRY STANDPIPEDETAILDUCT THRU ROOFDISHWASHERDRAWINGDOWELDRAWERDOUBLE EXTRA STRONG

EASTEACHEXPANSION BOLTELECTRICAL CONTRACTOREACH ENDENERGY EFFICIENT RATIOEMERGENCY EYEWASHEMERGENCY EYEWASH/SHOWEREACH FACEEXHAUST FANEFFICIENCYELECTRICAL HEATEREXTERIOR INSULATION & FINISH SYSTEMEXPANSION JOINTELEVATIONELASTOMERICELECTRIC(AL)EMERGENCYESTIMATED MAXIMUM DEMANDEMERGENCY MIXING VALVEENCLOSUREENTRANCEEND OF MAIN DRIPELECTRO-PNEUMATICEMERGENCY POWER OFFEPOXY RESIN FLOORINGEQUALEQUIPMENTEMERGENCY SHOWEREXTRA STRONGESTIMATEEXPANSION TANKEACH WAYEXCAVATEEXISTINGEXHAUSTEXPANSIONEXPOSEDEXTERIOR

FAHRENHEITFIRE LANEFURNACEFIRE ALARMFABRICATEDFACE BRICKFOOT CANDLEFLUTED CONCRETE MASONRY UNITFLOOR CLEAN OUTFAN COIL UNITFIRE DAMPERFLOOR DRAINFIRE DEPARTMENT CONNECTIONFOUNDATIONFEEDERFIRE EXTINGUISHERFIRE EXTINGUISHER CABINETFINISH FLOORFILTER HOUSINGFIRE HYDRANTFIRE HOSE CABINETFIGUREFINISHFIXTUREFLOORFLASHINGFLEXIBLEFLUORESCENTFLOORINGFULL LENGTH MIRROR

FMFMFOFOFOCFOFFOMFOSFOWFPFPMFRFRFSFSFSDFTFTFTGFUTFVCFWC

GGGAGALGALVGBGCGCOGCMUGDGENGENGFAGFIGFRCGIGLAMGLGMUGNDGOVTGPHGPMGRGRGRCGRGPGRSGSGVGWBGYPGYP BD

HHBHCHCHCBHDHDBDHDRHDWDHDWRHDHMHOAHORIZHPHPHPHRHRHSHSTRHTHTGHTRHTWRHTWSHUMHVHVAC

HXHZ

IAQIAWIBIBCICIDIEIESIFIGIFIJSININCINSULINTIPIWJANJBJCTJFBJSTJTLLALABLAMLAVLBLBRLBSLDGLF

LENGTH (LONG)LINEARLINOLEUMLIVE LOADLONG LEG HORIZONTALLONG LEG VERTICALLOCATIONLONGITUDINALLAWN SPRINKLERLIFE SAFETY CODELIGHTLIGHTINGLOUVERLAVATORY VACUUMLONG WAY

THOUSANDMIXED AIRMACHINEMAGNETICMAINTENANCEMANUALMASONRYMATERIALMAKEUP AIR UNITMANUAL AIR VENTMAXIMUMMODIFIED BITUMEN MEMBRANEMARKER BOARDMOP/BROOM HOLDERTHOUSAND BTU PER HOURTHOUSAND BTU PER HOURMECHANICAL CONTRACTORMEDICINE CABINETMINIMUM CIRCUIT AMPSMAIN CIRCUIT BREAKERTHOUSAND CIRCULAR MILLSMEDIUM DENSITY OVERLAYMECHANICALMEMBRANEMETALMEZZANINEMANUFACTURERMANUFACTURINGMANHOLEMETAL HALIDEMINIMUMMISCELLANEOUSMOTORIZED LOUVERMOULDINGMILLWORKMASONRY OPENINGMIRRORMAGNETIC STARTERMETAL SOFFIT PANELMOUNTEDMOUNTINGMETALMULLIONMETAL WALL PANEL

NITROGENNORTHNOT APPLICABLENOISE CRITERIANORMALLY CLOSEDNURSE CALLNATIONAL ELECTRIC CODENATIONAL ELECTRICAL MANUFACTURERS ASSN.NEUTRALNOT IN CONTRACTNORMALLY OPENNUMBERNITROUS OXIDENOMINALNEUTRAL SENSORNOT TO SCALE

OPERATION AND MAINTENANCEOUT TO OUTOVERALLOUTSIDE AIROBSCUREON CENTEROUTSIDE DIAMETEROVERFLOW DRAINOUTSIDE FACEOWNER FURNISHED CONTRACTOR INSTALLEDOFFICEOWNER FURNISHED OWNER INSTALLEDOTHER HANDOVERHEAD POWEROVERHEAD TELEPHONEOPENINGOPPOSITEOVERFLOW STORM DRAINOPEN TO CEILING SPACEOVERFLOWOVERHEADOXYGEN

POLEPUMPPRESSURE/TEMPERATURE TEST PORTPUBLIC ADDRESSPANIC BOLTPARALLELPARTICLE BOARDPULL BOXPUSH BUTTONPUSH BUTTON STARTPRECASTPOUNDS PER CUBIC FOOTPORCELAIN CERAMIC TILEPUMP DISCHARGEPLUMBING & DRAINAGE INSTITUTEPENTHOUSEPERFORATEDPERPENDICULARPOWER FACTORPRESSURE GAUGEPHASEPOINT OF INTERSECTION

PLACE(S)PLATEPLASTIC LAMINATEPLASTERPLUMBINGPLYWOODPANELPOINT OF CONNECTIONPORCELAINPAIRPREFABRICATEDPRE-FINISHEDPROJECTIONPIPE SUPPORTPROJECTION SCREENPOUNDS PER SQUARE FOOTPOUNDS PER SQUARE INCHPAINTPOINTPAPER TOWEL DISPENSERPAPER TOWEL DISPENSER/RECEPTACLEPARTITIONPOLYVINYL CHLORIDESOUND POWER LEVELPOWER

QUARRY TILEQUARTER ROUNDQUARTZ

RISERRETURN AIRRADIATORRADIUSRUBBER BASEREMOTE CONTROLREFLECTED CEILING PLANREINFORCED CONCRETE PIPEROOF DRAINREFRIGERANT DISCHARGERECOMMENDEDRECEPTACLEREFERENCEREFLECTEDREFRIGERATORREGISTERREINFORCEMENTREMOVABLEREQUIRE(D)RESILIENTRETAINING (WALL)REVISIONSRETURN FANRUBBER FLOORRECESSED FLOOR MATRELATIVE HUMIDITYRELIEF HOODROUGH IN AND CONNECTRISE IN JOIST SPACEROOMROUNDROUGH OPENINGREVOLUTIONS PER MINUTEROOF TOP UNIT

SINKSANITARY SEWERSOAP DISHSOUTHSPRINKLER LINESHOCK ABSORBERSUPPLY AIRSANITARY WASTESTYRENE-BUTADIENE-STYRENE (ROOFING)SEALED CONCSECURITYSOLID CORESPECIAL COATINGSEAT COVER DISPENSERSCHEDULESTRUCTURAL CLAY TILESOAP DISPENSERSMOKE DETECTORSTORM DRAINSECONDARYSECTIONSECRETARYSENSIBLESQUARE FOOTSUPPLY FANSPLIT-FACED CONCRETE MASONRY UNITSTRUCTURAL FACING UNITSINGLESHEATHINGSECURITY HOLLOW METALSHEETSIMILARSHORT LEGSEALANTSHEET METALSPRINKLER MAINSANITARY NAPKIN DISPOSALSANITARY NAPKIN VENDORSTAND PIPESPECIFICATIONSSPRINKLERSPECIALSPLASH BLOCKSQUARESTAINLESS STEELSOLID SURFACESTORM SHELTER AREASTAIRSTORM SEWERSTAGGEREDSOUND TRANSMISSION CLASSSTANDARDSINGLE TAPERED ENDSTRINGERSTEELSTORAGESTRUCTURAL / STRUCTURESUBSTATIONSUBFLOORSURFACESUSPENDEDSHEET VINYL

SHORT WAYSWITCHSWITCH BOARDSYMMETRICAL

TEMPEREDTHERMOSTATTREADTOP & BOTTOMTONGUE & GROOVETRANSFER AIRTEST AND BALANCETANGENTTERMINAL BOXTACK BOARDTEMPERATURE CONTROLTIME CLOCKTRENCH DRAINTELEPHONETEMPERATURETEMPERED - TEMPORARYTERRAZZOTEXTURE(D)TOGGLETHRESHOLDTHICK(NESS)TOP OF BEAMTOP OF CONCRETETOP OF FOOTINGTOILETTOP OFTOP OF PAVINGTOP OF STEELTOP OF WALLTRAP PRIMERTRIPTRANSVERSETREADTEMPERATURE SENSORTUBE STEELTOTAL STATIC PRESSURETERAZZO TILETOILET TISSUE DISPENSERTELEVISIONTACK WALLTYPICAL

URINALUNIT COOLERUNDERGROUNDUNDERGROUND ELECTRICALUNDERGROUND TELEPHONEUNIT HEATERUNDERWRITERS LABORATORIESUNEXCAVATEDUNFINISHEDUNLESS NOTED OTHERWISEURINALUTILITY SHELFUTILITYUNIT VENTILATOR

VENTVOLTVALVEVACUUMVARIABLE AIR VOLUMEVAPOR BARRIERVINYL BASEVENT BELOW FLOORVENTED COVE BASEVINYL COMPOSITION TILEVELOCITYVENTILATIONVENTILATORVERTICALVESTIBULEVINYL FLOORVERIFY IN FIELDVOLUMEVENEER PLASTERVACUUM PUMPVINYL TILEVENT THROUGH ROOFVINYL WALLCOVERINGVERIFY WITH MANUFACTURER

WIDE; WIDTHWASTE (PLUG)WATTWESTWIDE FLANGEWITHWITHOUTWALL BASEWALL COVERINGWATER CLOSETWATER COOLED CONDENSERWATER CLOSET/LAVATORYCOMBINATIONWALL CLEAN OUTWOODWINDOWWASH FOUNTAINWALL HYDRANTWATER HEATERWATT HOUR METERWATER MOTOR GONGWAINSCOTWEATHERPROOFWATERPROOFWATERPROOFINGWATER RESISTANTWASTE RECEPTACLEWEIGHTWELDED WIRE FABRIC

TRANSFORMERTRANSMITTER

YARDYARD HYDRANT

IMPEDANCE

ANDATTHAT ISNUMBER

AIR CONDITIONING(ER)AMPERECOMPRESSED AIRAREA ALARM PANELANCHOR BOLTACRYLONITRILE-BUTADIENE-STYRENEALTERNATING CURRENTAIR COOLED CONDENSERAIR COOLED CONDENSING UNITALUMINUM COMPOSITE MATERIALACOUSTICACOUSTICAL CEILING TILEACCESS DOORAREA DRAINADDITION OR ADDITIONALADJUSTABLEADJACENTADMINISTRATIONAIR FILTERABOVE FINISH FLOORAIR HANDLING UNITAREA INLETALTERNATEALUMINUMALUMINUM CURTAIN WALLALUMINUM STORE FRONTAMBIENTANCHORACCESS PANELACOUSTICAL PANEL CEILINGATACTIC-POLYPROPYLENE (ROOFING)ACID RESISTINGARCHITECTURALASBESTOSASPHALTAUTOMATICAIR VENTAVERAGEAMERICAN WIRE GAUGEACOUSTICAL WALL PANEL

BACK TO BACKBOILER BLOW OFFBURNISHED CONCRETE MASONRY UNITBOARDBACKFLOW PREVENTERBELOW FLOORBREAK HORSE POWERBREAKERBUILDING LINEBUILDINGBLOCKBLOCKINGBULKHEADBEAMBENCH MARKBOTTOM OFBOTTOM OF DUCTBOTTOM OF FOOTINGBRIDGINGBRACKETBASEMENTBRITISH THERMAL UNITBRITISH THERMAL UNIT PER HOURBUILT UP ROOFING

CONDUITCABINETCANTILEVERCAPACITYCASINGCONDENSATE DRAINCLOSED CIRCUIT TELEVISIONCOVER ELEVATIONCEMENTCENTRIFUGALCERAMICCUBIC FEETCUBIC FEET PER HOURCUBIC FEET PER MINUTECORNER GUARDCHANNELCURB INLETCAST IN PLACECIRCULATINGCONTROL JOINTCIRCUITCIRCUIT BREAKERCENTER LINECEILINGCLOSETCLEARCEILING MOUNTEDCORRUGATED METAL PIPECONCRETE MASONRY UNITCLEAN OUTCONDUIT ONLYCARBON DIOXIDECOLUMNCOMMONCOMBINATIONCOMMUNICATIONSCOMPOSITECOMPRESSOR UNITCOMPRESSIBLECONCRETECONFERENCECONFIGURATIONCONNECTCONNECTIONCONSTRUCTIONCONTINUOUSCONTRACTOR OR CONTRACTCONVECTORCORRIDORCONDENSER PUMPCOVER PLATECYCLES PER SECONDCARPETCORROSION RESISTANTCOUNTERSINKCOUNTERSUNKCONSTRUCTION JOINTCASEWORKCERAMIC TILECENTER

CUCUCUCUCWCYCYL

DDDDBDBDBADBLDCDCDCJdDDCDEGDEPRDEPTDETDFDGDHDIDIADIAGDIFFDIMDISC SWDISCDISCHDISTRDLDMDMPRDMDNDO OR "DPFGDRDRDSDSPDTLDTRDWDWGDWLDWRDXS

EEAEBECEEEEREEWEEWSEFEFEFFEHEIFSEJELELASELECEMEREMDEMVENCLENTREOMDEPEPOERFEQEQUIPESESESTETEWEXCEXGEXHEXPEXPEXT

FFFFAFABFBFCFCMUFCOFCUFDFDFDCFDNFDRFEFECFFFHFHFHCFIGFINFIXFLFLASHFLEXFLOURFLGFLM

FACTORY MUTUALFIRE MAINFACE OFFINISH OPENINGFACE OF CONCRETEFACE OF FINISHFACE OF MASONRYFACE OF STUDFACE OF WALLFIREPROOFINGFEET PER MINUTEFIRE RESISTIVEFRAMEFLOOR SINKFLOW SWITCHFIRE/SMOKE DAMPERFEET (FOOT)FLOW TRANSMITTERFOOTINGFUTUREFIRE VALVE CABINETFABRIC WALL COVERING

GRILLENATURAL GASGAUGEGALLONGALVANIZEDGRAB BARGENERAL CONTRACTORGROUND CLEAN OUTGLAZED CONCRETE MASONRY UNITGARBAGE DISPOSALGENERALGENERATORGROSS FLOOR AREAGROUND FAULT INTERRUPTERGLASS FIBER REINFORCED CONCRETEGALVANIZED IRONGLUE LAMINATEDGLASSGLASS MASONRY UNITGROUNDEDGOVERNMENTGALLONS PER HOURGALLONS PER MINUTEGUARD RAILGRILLEGLASS REINFORCED CONCRETEGLASS REINFORCED GYPSUM PLASTERGALVANIZED ROD STEELGASOLINEGATE VALUEGYPSUM WALL BOARDGYPSUMGYPSUM BOARD

HEIGHTHOSE BIBHANDICAPHOLLOW COREHANDICAP BENCHHAND DRYER OR HAIR DRYERHARDBOARDHEADERHARDWOODHARDWAREHIGH INTENSITY DISCHARGEHOLLOW METALHAND OFF AUTOMATICHORIZONTALHEAT PUMPHIGH PRESSUREHORSEPOWERHANDRAILHOURHEAD STUDHIGH STRENGTHHEIGHTHEATINGHEATERHIGH TEMP HOT WATER RETURNHIGH TEMP HOT WATER SUPPLYHUMIDIFIERHEATING VENTILATING UNITHEATING VENTILATING AND AIR CONDITIONINGHEAT EXCHANGERHERTZ

INDOOR AIR QUALITYIN ACCORDANCE WITHINFRARED BURNERINTERNATIONAL BUILDING CODEINTERCOMINSIDE DIMENSIONINVERT ELEVATIONILLUMINATING ENGINEERING SOCIETYINSIDE FACEISOLATED GROUNDISOLATION JOINTIN JOIST SPACEINCHINCLUDE (ING)INSULATIONINTERIORIRON PIPEINDIRECT WASTEJANITORJUNCTION BOXJUNCTIONJOINT FILLER BOARDJOISTJOINT ANGLELAVATORYLABORATORY COMPRESSED AIRLAVATORYLAMINATE(D)LAVATORYPOUNDLUMBERPOUNDSLOADINGLINEAR FOOT (FEET)

LGLNLINOLLLLHLLVLOCLONGLSLSCLTLTGLVLVLW

MMAMACMAGMAINTMANMASMATLMAUMAVMAXMBSMBDMBHMBHMBTUHMCMCMCAMCBMCMMDOMECHMEMBMETMEZZMFCTRMFRGMHMHMINMISCMLMLDGMLWKMOMRMSMSPMTDMTGMTLMULMWP

NNN/ANCNCNCNECNEMA

NEUTNICNONONONOMNSNTS

O&MO to OOAOAOBSCOCODODOFOFC

OFFOFIOHOHPOHTOPGOPPOSDOTCSOVFLOVHDOX

PPP/TPAPAN BPARPBPBPBPBSPCPCFPCTPDPDIPENTPERFPERPPFPGPHPI

PLPLPLAMPLASPLBGPLWDPNLPOCPORCPRPREFABPRE-FINPROJPSPSPSFPSIPT/PNTPTPTDPTD/RPTNPVCPWLPWR

QTQTR RNDQTZ

RRARADRAD or RRBRCRCPRCPRDRDREC'DRECPREREFLREFRREGREINFREMREQ'DRESILRETREVRFRFRFMRHRHRI&CRIJSRMRNDRORPMRTU

SSSSSSASASANSBSSCSCSCSCSCDSCHEDSCTSDSDSDSECSECTSECYSENSSFSFSFCMUSFUSGLSHEATHSHMSHTSIMSLSLNTSMSMSNDSNVSPSPECSPKSPLSPL BLKSQSSSSSSASTSTSTAG’DSTCSTDSTESTGRSTLSTORSTRUCTSUBSUBFLSURFSUSPSV

SWSWSWBDSYM

TTTT & BT & GTATABTANTBTBDTCTCTDTELTEMPTEMPTERRTEXTTGLTHTHKTOBTOCTOFTOILTOTOPTOSTOWTPVTRTRANSTRDTSTSTSPTTTTDTVTWTYP

UUCUGUGEUGTUHULUNEXUNFINUNOURUSUTILUV

VVVAVACVAVVBVBVBFVCBVCTVELVENTVENTVERTVESTVFVIFVOLVPVPVTVTRVWCVWM

WWWWWW/W/OWBWCWCWCCWCL

WCOWDWDWWFWHWHWHMWMGWNSCTWPWPFWPFGWRWRWTWWF

XFMRXMTR

YDYH

Z

&@i.e.#

GENERAL NOTES

1. GENERAL NOTES APPLY TO ALL SHEETS.

2. ALL DIMENSIONS ARE ACTUAL AND ARE TO FACE OF STUDS, FACE OF CONCRETE WALLS, FACE OF CMU WALLS, FACE OF FRAMES, OR CENTERLINE OF COLUMNS, UNLESS NOTED OTHERWISE.

3. ALL PENETRATIONS THROUGH WALLS SHALL BE SEALED WITH FIRE STOPPING MATERIAL AS REQUIRED TO ACHIEVE THE RESPECTIVE FIRE-RESISTIVE RATING AND SMOKE STOPPAGE. SEE DETAILS ON SHEET A10.10.

4. GYPSUM BOARD SURFACES SHALL BE ISOLATED WITH CONTROL JOINTS WHERE SHOWN ON DRAWINGS AND AS DESCRIBED IN THE SPECIFICATIONS.

5. THE CONTRACTOR SHALL FURNISH AND INSTALL ALL RUBBER BASE AROUND CASEWORK AND MILLWORK.

6. THE OWNER SHALL BE RESPONSIBLE FOR PROVIDING THE CONTRACTOR WITH ROUGH-IN INFORMATION NECESSARY TO ACCOMMODATE THE INSTALLATION OF OWNER FURNISHED AND INSTALLED OR CONTRACTOR INSTALLED ITEMS.

7. THE CONTRACTOR SHALL INCLUDE ALL OWNER FURNISHED AND INSTALLED ITEMS AND OWNER FURNISHED AND CONTRACTOR INSTALLED ITEMS IN THE CONSTRUCTION SCHEDULE, AND SHALL COORDINATE WITH THE OWNER TO ACCOMMODATE THESE ITEMS.

8. THE OWNER SHALL BE RESPONSIBLE FOR ADHERING TO THE CONSTRUCTIONS SCHEDULE AS ESTABLISHED BY THE CONTRACTOR.

9. DIMENSIONS FOR DOOR AND WINDOW OPENINGS ARE SHOWN NOMINAL.

10. SEE SHEETS A9.1FOR ROOM SIGNAGE.

GENERAL SYMBOLS

LEGEND / KEY NOTE

EARTH

A11.11

1

PT

8

AT 40 SF/OCC

REVISION NUMBER

DETAIL OR WALL SECTION

BUILDING SECTION

BUILDING ELEVATION

INTERIOR ELEVATION WITH MULTIPLE ELEVATIONS ON ONE SHEET

ROOM NAMEROOM NUMBER

OCCUPANT LOAD

DOOR NUMBER

WINDOW NUMBER

WALL TYPE

TOILET ACCESSORY TAG/EQUIPMENT TAG

STRUCTURAL GRID

GRAVEL / BALLAST

MORTAR / GROUT

CONCRETE

STEEL

GYM FLOOR

WOOD(TRIM / FINISH)

GLASS

STONEMETAL STUDS

PLYWOOD

RIGID INSULATION

CONCRETE MASONRY UNIT

BRICK

GYPSUM WALL BOARD

BATT / MINERAL FIBER INSULATION

WOOD BLOCKING -CONTINUOUS

WOOD BLOCKING -NON-CONTINUOUS

45

45 45

45

1

1

XXX

XXX

A102

B2

A102

Sheet Number

Sheet Name

Area Plan

Project Phase

Project Number

Issue Date

in • cite v. to provoke thought

Licensed Architect

Mike Hilmes

License

MO #2000157579

Cert. of Authority

A-2004016376INCITE DESIGN STUDIO, LLC

Architect

INCITE DESIGN STUDIO1800 LAFAYETTE AVE., SUITE B, ST. LOUIS, MO 63104314.279.4500

Mech., Plumb., Elec., Telecom.

BRiC PARTNERSHIP, LLC3636 SOUTH GEYER ROAD, SUITE 305ST. LOUIS, MO 63127PHONE: 314-725-5889

Construction Manager

NAVIGATE

PHONE:

Revision No. Description Date Issued

KSD PROJECT # NGL-2021-SECURED VESTIBULE

4/7

/2021 8

:22:0

8 A

M

C:\

Users

\bri

an.n

ash\D

ocum

ents

\20-2

03

Nort

h G

lendale

Ele

m V

estibule

Add_bnashF

HP

5U

.rvt

SYMBOLS & ABBREVIATIONS

NORTH GLENDALEELEMENTARYSCHOOL SECUREDVESTIBULERENOVATIONPROJECT

04/08/2021

20-203

BID DOCUMENTS

G0.2

765 N. SAPPINGTON ROADGLENDALE, MO 63122

Page 3: Architect NORTH GLENDALE ELEMENTARY SCHOOL...FOC FOF FOM FOS FOW FP FPM FR FR FS FS FSD FT FT FTG FUT FVC FWC G G GA GAL GALV GB GC GCO GCMU GD GEN GEN GFA GFI GFRC GI GLAM GL GMU

DNDN

1. ALL DIMENSIONS ARE ACTUAL AND ARE TO FACE OF STUD, FACE OF CONCRETE WALL, FACE OF CMU WALL, FACE OF FRAME, OR CENTERLINE OF COLUMN, UNLESS NOTED OTHERWISE.

2. DIMENSIONS FOR DOOR AND WINDOW OPENINGS ARE SHOWN NOMINAL.

FLOOR PLAN NOTES

PRINCIPAL

A106

WORK ROOM

A108

MAIN OFFICE

A10177

78

79 79

80

81

82

83

84

85

86

88

8989

90

83

92

A100A

A1

00B

VESTIBULE

A100

EX. T

A103

EX. STOR

A102

EX. STOR.

A104

ASST.PRINCIPAL

A107

CORRIDOR

A105

A1

00

C

93

PRINCIPAL

A106

WORK ROOM

A108

MAIN OFFICE

A101

VESTIBULE

A100

EXISTINGCORRIDOR

A105

EX. T

A103

EX. STOR.

A104

EX. STOR

A102

ASST.PRINCIPAL

A107

WORK ROOM

EXISTING

ASST.PRINCIPAL

EXISTING

CORRIDOR

079075

074

077

077

078

EXISTING

OFFICE

EX. STOR

EX. T

A103

PRINCIPAL

A106

VESTIBULE

A100

EX. STOR.

A104

FV

FV

2' - 0" 4' - 0"

079

THE CONTRACTOR SHALL:

1. COORDINATE ALL DEMOLITION/PHASING EFFORTS WITH THE ARCHITECT-ENGINEER AND OWNER'S REPRESENTATIVES. EVERY EFFORT SHALL BE MADE TO MINIMIZE DISRUPTION OF SCHOOL OPERATION AND TO PROVIDE PATRON, FACULTY, AND STUDENT SAFETY. EXCESSIVE NOISE OR VIBRATION SHALL BE PRE-APPROVED AND COORDINATED WITH THE OWNER'S REPRESENTATIVE.

2. COORDINATE WITH THE OWNER ANY PRE-APPROVED DISRUPTION AND VERIFICATION OF SERVICE WITHIN THE EXISTING BUILDING SO AS TO MINIMIZE THE DISRUPTION OF SERVICE.

3. MAINTAIN A SECURE, WEATHER-TIGHT ENCLOSURE AT THE EXTERIOR OF THE EXISTING BUILDING THROUGHOUT THE DEMOLITION/CONSTRUCTION PORTION OF THE WORK IN THAT AREA. BUILDING SECURITY SHALL BE COORDINATED WITH THE OWNER.

4. VERIFY ALL EXISTING CONDITIONS, DIMENSIONS, AND ELEVATIONS AND NOTIFY THE ARCHITECT-ENGINEER OF ANY DISCREPANCIES.

5. REMOVE IN THEIR ENTIRETY ALL EXISTING WALLS, DOORS, MILLWORK, PLUMBING FIXTURES ETC. AS REQUIRED TO EXECUTE THE DEMOLITION/CONSTRUCTION WORK DESCRIBED BY THE ARCHITECT-ENGINEER.

6. REMOVE ALL DEMOLITION MATERIALS FROM THE SITE UNLESS NOTED OTHERWISE. THE OWNER SHALL RESERVE THE RIGHT TO SALVAGE ANY MATERIALS.

7. PROVIDE PROTECTION FOR ALL EXISTING BUILDING MATERIALS AND EQUIPMENT FROM DAMAGE DUE TO ANY DEMOLITION OR CONSTRUCTION-RELATED INCIDENT PERFORMED UNDER THIS CONTRACT.

8. REPAIR OR REPLACE ANY WALLS, FLOORS, OR EQUIPMENT DAMAGED AS A RESULT OF DEMOLITION OR CONSTRUCTION TO MATCH EXISTING FINISH AND/OR CONDITION.

9. THE CONTRACTOR SHALL COORDINATE WITH THE ARCHITECT-ENGINEER ANY MATERIALS TO BE REUSED AND WILL BE RESPONSIBLE FOR VERIFYING AND MAINTAINING THE FUNCTIONAL AND AESTHETIC INTEGRITY OF THE MATERIALS.

10. VERIFY AND MAINTAIN THE LOCATION OF EXISTING POWER, COMMUNICATION AND DATA CABLES SO AS NOT TO INADVERTENTLY INTERRUPT THE CONTINUITY OF THEIR SERVICE.

11. PATCH ALL FLOOR AND CEILING PENETRATIONS RESULTING FROM REMOVAL OR REROUTING OF NEW OR EXISTING PIPING, DUCTWORK, CONDUIT, ETC...AS REQUIRED TO MAINTAIN FIRE SEPARATIONS. FINISH AS REQUIRED FOR NEW OR EXISTING ADJACENT SURFACES.

12. CAP ALL DISCONNECTED MECHANICAL PIPING LINES WITHIN THE WALL OR FLOOR. PATCH AND FINISH AS REQUIRED TO MATCH NEW OR EXISTING ADJACENT SURFACES.

13. SEE MECHANICAL AND ELECTRICAL DRAWINGS AND NOTES FOR FURTHER SEQUENCING AND SCOPE OF WORK.

DEMOLITION NOTES (APPLIES TO ALL DEMOLITION SHEETS) REFLECTED CEILING PLAN LEGEND

10' - 0"

VINYL SOFFIT - VENTED

CEILING HEIGHT

GYPSUM BOARD

CAN LIGHT

SUPPLY

RETURN

EXHAUST

VINYL SOFFIT

FIRE EXIT SIGN (CEILING MOUNTED)

FIRE EXIT SIGN (WALL MOUNTED)

2' x 4' LIGHT FIXTURE

EMERGENCY LIGHT

2' x 2' LIGHT FIXTURE

STRIP LIGHT FIXTURE

2' x 4' LAY-IN CEILING

2' x 2' LAY-IN CEILING

Sheet Number

Sheet Name

Area Plan

Project Phase

Project Number

Issue Date

in • cite v. to provoke thought

Licensed Architect

Mike Hilmes

License

MO #2000157579

Cert. of Authority

A-2004016376INCITE DESIGN STUDIO, LLC

Architect

INCITE DESIGN STUDIO1800 LAFAYETTE AVE., SUITE B, ST. LOUIS, MO 63104314.279.4500

Mech., Plumb., Elec., Telecom.

BRiC PARTNERSHIP, LLC3636 SOUTH GEYER ROAD, SUITE 305ST. LOUIS, MO 63127PHONE: 314-725-5889

Construction Manager

NAVIGATE

PHONE:

Revision No. Description Date Issued

KSD PROJECT # NGL-2021-SECURED VESTIBULE

4/7

/2021 8

:22:0

2 A

M

C:\

Users

\bri

an.n

ash\D

ocum

ents

\20-2

03

Nort

h G

lendale

Ele

m V

estibule

Add_bnashF

HP

5U

.rvt

Demolition, Floor & ReflectedCeiling Plans

NORTH GLENDALEELEMENTARYSCHOOL SECUREDVESTIBULERENOVATIONPROJECT

04/08/2021

20-203

BID DOCUMENTS

A1.1

765 N. SAPPINGTON ROADGLENDALE, MO 63122

SCALE: 1/8" = 1'-0"A1.1

FLOOR PLAN1

SCALE: 1/8" = 1'-0"A1.1

REFLECTED CEILING PLAN2

SCALE: 1/8" = 1'-0"A1.1

DEMOLITION PLAN4

DEMO PLAN KEYNOTES

FLOOR PLAN KEYNOTES

DEMO PLAN KEYNOTES

KeyValue Keynote Text

074 REMOVE EXISTING MB.

075 REMOVE EXISTING ADJUSTABLE WALL SHELVING

077 REFER TO MEP FPR ADDITIONAL DEMOLITIONSCOPE OF THIS AREA.

078 REMOVE PORTION OF EXISTING MASONRYCORRIDOR WALL AS INDICATED FOR NEWBORROW LITE. ALTERNATE BID SCOPE.

079 EXISTING UNITY HEATER TO BE REMOVED. SEEMECH.

FLOOR PLAN KEY NOTES

KeyValue Keynote Text

83 NEW UNIT HEATER - SEE MECH

84 NEW CARD READER. SEE ELECT / TECH.

85 EXISTING AIPHONE LOCATION.

86 EXISTING WOOD / GLASS DOOR AND SIDELITES TOREMAIN.

88 PRIVACY FILM APPLIED TO INTERIOR SURFACE. SEEFRAME TYPE F3.

89 EXISTING F.A. PANELS TO REMAIN.

90 EXISTING P.A CABINET TO REMAIN.

92 NEW WOOD FRAME BORROW LITE. ALTERNATE BIDSCOPE. SEE DETAILS. SEE FRAME TYPE F4

93 NEW PANEL SIGNAGE TO MATCH EXISTING SEESHEET A9.1.

FLOOR PLAN KEY NOTES

KeyValue Keynote Text

77 NEW ALUMINUM STOREFRONT SYSTEM ANDENTRANCE DOORS WITH LAMINATED SECURITYGLAZING. SEE FRAME TYPE F2, DOOR SCHEDULE ANDSPECS.

78 NEW ALUMINUM ENTRANCE DOOR WITH LAMINATEDSECURITY GLAZING. SEE DOOR SCHEDULE.

79 EXISITNG OFFICE / RECEPTION DESK FURNITURERELOCATED.

80 EXISITNG COPIER RELOCATED FROM WORK ROOM.

81 SEE ROOM FINIHS SCHEDULE AND SPECS.

82 NEW CARPET FLOORING.

ALL CEILINGS ARE EXISTING TO REMAIN U.N.O - SEE ROOM FINISH SCHEDULE AND MEP

DRAWINGS

Page 4: Architect NORTH GLENDALE ELEMENTARY SCHOOL...FOC FOF FOM FOS FOW FP FPM FR FR FS FS FSD FT FT FTG FUT FVC FWC G G GA GAL GALV GB GC GCO GCMU GD GEN GEN GFA GFI GFRC GI GLAM GL GMU

DOOR TYPE ELEVATIONS

FLUSH ALUMINUM DOOR WITH GLASS

D1

DO

OR

HE

IGH

T P

ER

SC

HE

D.

LEAF WIDTH PER SCHED.

3' -

0"

3 1

/2"

5 1

/4"

7"

5" 5"

F1FRAMED TYPE ELEVATIONS F2

2" DOOR WIDTH 2"

DO

OR

HE

IGH

T2

"

F3 F4

4' - 0"

4' -

0"

FIE

LD

VE

RIF

Y

10

' - 0

"

FIELD VERIFY

12' - 0 7/8"

GL-1 GL-1 GL-1 GL-1

GL-1GL-1

GL-1

GL-3

A33

A9.1

24

A9.1

GL-1

GL-2

GL-3

THE FOLLOWING ABBREVIATIONS ARE USED WITH GLAZING:

.06 INCH PVB, LAMINATED GLASS

.09 INCH PVB, LAMINATED GLASS (3MM)

TEMPERED GLASS

RESTROOM

7"

TOILET SIGN

7"

6"

6"

7"

7"

7"

2"

7 1/2"

9"

0000CLASSROOM

EQ EQ

7/8

"

7/8

"3

/8"

7/8

"

STORAGE

NOTICE

OCCUPANCY

FOR YOUR SAFETY

IS LIMITED TO:

BY ORDER OFTHE CODE OFFICIAL

Keep Posted Under Penalty of Law

PERSONS

RESTROOM

1/4

"

1/2

"1

/4"

3/4

"

1/4

"

3/4

"7

/8"

1"

3/8

"

INTERNATIONAL SYMBOL OF ACCESSIBILITY

TACTILE ROOM NAME AND NUMBER - 3/4" ARIAL

ENGRAVED BRAILLE

INTERNATIONAL SYMBOL OF ACCESSIBILITY

TACTILE ROOM NAME AND NUMBER - 3/4" ARIAL

ENGRAVED BRAILLE

TACTILE ROOM NUMBER - 1" ARIAL

TACTILE ROOM NAME - 3/4" ARIAL

ENGRAVED BRAILLE

CHANGEABLE MESSAGE INSERT

TACTILE ROOM NAME - 3/4" ARIAL

ENGRAVED BRAILLE

TACTILE TEXT -3/4" ARIAL

CHANGEABLE MESSAGE INSERT

NOTES:1. EXACT ROOM NAMES AND ROOM NUMBERING TO BE COORDINATED WITH OWNER.2. EXISTING SIGNAGE IN SCOPE AREAS TO BE REMOVED AND REINSTALLED AS

REQUIRED UNLESS NOTED OTHERWISE.3. NEW SIGNAGE STYLE TO MATCH EXISTING U.N.O.4. ALL SIGNAGE TO BE PHENOLIC-BACKED PHOTOPOLYMER SHEET5. FIELD COLOR TO BE RED TO MATCH EXISTING, UNLESS NOTED OTHERWISE.6. TEXT AND SYMBOL COLOR TO BE WHITE TO MATCH EXISTING UNLESS OTHERWISE.7. ENGRAVED BRAILE TO BE GRADE II, 24 POINT8. TACTILE TEXT TO BE MEDIUM RAISED 1/32"

A

TOILET SIGNC

DNAME & NUMBER SIGN

NAME ONLY SIGNE

FASSEMBLY SIGN

7"

6"

RESTROOM

TOILET SIGNB

MASONRY INFILL AT JAB: TOOTH-IN/PATCH AT EXISTING MASONRY WALL & MATCH WIDTH

1/4" SHIM W/ SEALANT BOTH SIDES

EQ

4 1

/2"

EQ

2"ALUM. DOOR/GLASS; RE: PER SCHEDULE

ALUM. STOREFRONT FRAME; RE: DOOR SCHEDULE

EXISTING PLASTER WALL FINISH

PLASTER WALL FINISH; MATCH TEXTURE AND FINISH

EXISTING MASONRY WALL

EXISTING MASONRY WALL

GROUT CAVITY SOLID

WA

LL

WID

TH

EX

IST

ING

SEALANT, EACH SIDES

FACE OF EXISTING MASONRY WALL

WD SHIM, AS REQUIRED

GLAZING; RE: FRAME TYPE

ALUM. STOREFRONT FRAME; RE: DOOR SCHED

ALUM. STOREFRONT DOOR; RE: DOOR SCHED

2"2"

4 1

/2"

PROVIDE BLOCKING TO DEPTH WHICH ALLOWS FOR PASSAGE OF EXISTING SGT TOP LIP & SURFACE CONDUIT (CONSTRACTOR TO FIELD VERIFY)

2"

4 1/2"

SEALANT, EACH SIDES

WD SHIM, AS REQUIRED

GLAZING; RE: FRAME TYPE

ALUM. STOREFRONT FRAME; RE: DOOR SCHEDULE

ALUM. DOOR/GLASS; RE: PER SCHEDULE

EXISTING FRAMING & FINISHED BULKHEAD. CONTRACTOR TO

FIELD VERIFY ALL EXISITNG CONDITIONS AND CONFIRM

CAPACITY TO ANCHOR THE NEW STOREFRONT SYSTEM PER THE

MANUFACTURER'S RECOMMENDATIONS. PROVIDE AS

REQUIRED.

2"

ALUM. STOREFRONT FRAME; RE: DOOR

SCHEDULE

GLAZING; RE: PER SCHEDULE

FINISH FLOOR; RE: ROOM FINISH SCHEDULE AND FINISH PLANS

ALSF SUB-SILL; COLOR MATCHING ALSF FRAME

EXISTING CONC SLAB

4 1/2"

EXISTING CONC SLAB

ALSF DOOR; RE: DOOR SCHED

GLAZING PER DOOR SCHEDULE STOREFRONT JAMB

FRAME BEYOND

4 1/2"

FINISH FLOOR; RE: ROOM FINISH SCHEDULE AND FINISH PLANS

4"

FIELD VERIFY

12' - 0"

6' - 0"3' - 0" 3' - 0"

7' -

0"

FIE

LD

VE

RIF

Y

7' -

3"

2"

4 3/4"

Sheet Number

Sheet Name

Area Plan

Project Phase

Project Number

Issue Date

in • cite v. to provoke thought

Licensed Architect

Mike Hilmes

License

MO #2000157579

Cert. of Authority

A-2004016376INCITE DESIGN STUDIO, LLC

Architect

INCITE DESIGN STUDIO1800 LAFAYETTE AVE., SUITE B, ST. LOUIS, MO 63104314.279.4500

Mech., Plumb., Elec., Telecom.

BRiC PARTNERSHIP, LLC3636 SOUTH GEYER ROAD, SUITE 305ST. LOUIS, MO 63127PHONE: 314-725-5889

Construction Manager

NAVIGATE

PHONE:

Revision No. Description Date Issued

KSD PROJECT # NGL-2021-SECURED VESTIBULE

4/7

/2021 8

:22:0

3 A

M

C:\

Users

\bri

an.n

ash\D

ocum

ents

\20-2

03

Nort

h G

lendale

Ele

m V

estibule

Add_bnashF

HP

5U

.rvt

DOOR SCHEDULEELEVATIONS, FRAME TYPES& DETAILS

NORTH GLENDALEELEMENTARYSCHOOL SECUREDVESTIBULERENOVATIONPROJECT

04/08/2021

20-203

BID DOCUMENTS

A9.1

765 N. SAPPINGTON ROADGLENDALE, MO 63122

DOOR AND FRAME SCHEDULEOPENINGNUMBER ROOM

NO. OFLEAVES

WIDTH EA.LEAF

TOTALWIDTH HEIGHT

DOOR FRAME

FIRE RATING

DETAILS

TYPE MATERIAL FINISH GLASS TYPE MATERIAL FINISH GLASS HEAD JAMB SILL

A100A MAIN OFFICE 1 3' - 0" 3' - 0" 7' - 0" D1 ALUM -- GL-2 F1 ALUM -- -- -- 21/A9.1 SIM 21/A9.1 32/A9.1

A100B VESTIBULE 1 3' - 0" 3' - 0" 7' - 0" D1 ALUM -- GL-2 F2 ALUM -- GL-1 -- 23/A9.1 22/A9.1 32/A9.1

A100C VESTIBULE 1 3' - 0" 3' - 0" 7' - 0" D1 ALUM -- GL-2 F2 ALUM -- GL-1 -- 23/A9.1 22/A9.1 32/A9.1

PANEL SIGN TYPES

ALUM. DOOR JAMB @ REMOVED EXISTING MASONRY INFILL

ALUM. S.F. JAMB @ EXSTG. CORRIDOR WALL ALUM. S.F. DOOR HEAD

@ EXSTG. BULKHEAD

ALUM. S.F. SILL

ALUM. S.F. DOOR

HEAD SIDELIGHT (JAMB SIMILAR

EXISTING PLASTER FINISH TO REMAIN -PATCH/FINIHS TO MATCH EXISTING AS REQUIRED.

PROVIDE NEW BULL NOSE CORNER BEAD TO MATCH EXISTING

NEW WOOD FRAMED GLASS BORROW LITE (SEE F4) TO MATCH PROFILE, SPECIES AND FINISH OF ADJACENT EXISTING FRAME F3

ALIGN TOP OF OPENING WITH EXISTING ADJACENT DOOR

PROVIDE PRIVACY FILM TO OFFICE SIDE OF ALL EXISTING SIDELIGHT AND DOOR WIRE GLASS IN THIS FRAME B.O.D. FOR FILM 3M CRYSTAL GLASS FINISH 7725SE-324, FROSTED CRYSTAL

EXISTING WOOD & GLASS ASSEMBLY NEW WOOD FRAMED BORROW-LITE TO MATCH EXISTING ADJACENT

4 1/2" ALUM STOREFRONT4 1/2" ALUM STOREFRONT

GL-2

21

A9.1

22

A9.1

32

A9.1

33

A9.1

23

A9.1

24

A9.1

CONTRACTOR TO FIELD VERIFY ALL RELATED EXISTING CONDITIONS AND PROVIDE APPROVED CONCEALED LINTEL AS REQUIRED.

Page 5: Architect NORTH GLENDALE ELEMENTARY SCHOOL...FOC FOF FOM FOS FOW FP FPM FR FR FS FS FSD FT FT FTG FUT FVC FWC G G GA GAL GALV GB GC GCO GCMU GD GEN GEN GFA GFI GFRC GI GLAM GL GMU

1. WALL PAINT TO BE: PNT-1 UNO

2. BASE TO BE: RB-1 UNO

3. WHERE FLOOR FINISH CHANGES FROM ONE ROOM TO ANOTHER, SET JOINT BETWEEN THE MATERIALS AT THE CENTER OF THE COMMUNICATING DOOR OPENING, UNO.

4. GYP CEILINGS TO BE PAINTED PNT-1 UNO.

5. ALL EXPOSED STEEL TO BE PAINTED UNO.

ROOM FINISH SCHEDULE GENERAL NOTES

VCT

TRANSITION

CARPET

VCT

TRANSITION

RUBBER

VESTIBULE

A100

MAIN OFFICE

A101

EX. T

A103 EX. STOR.

A104

EX. STOR

A102

EXISTINGCORRIDOR

A105

PRINCIPAL

A106

ASST.PRINCIPAL

A107

WORK ROOM

A108

RF-1

CPT-1

FINISH FLOOR PLAN LEGEND

EXISTING TO REMAIN

Sheet Number

Sheet Name

Area Plan

Project Phase

Project Number

Issue Date

in • cite v. to provoke thought

Licensed Architect

Mike Hilmes

License

MO #2000157579

Cert. of Authority

A-2004016376INCITE DESIGN STUDIO, LLC

Architect

INCITE DESIGN STUDIO1800 LAFAYETTE AVE., SUITE B, ST. LOUIS, MO 63104314.279.4500

Mech., Plumb., Elec., Telecom.

BRiC PARTNERSHIP, LLC3636 SOUTH GEYER ROAD, SUITE 305ST. LOUIS, MO 63127PHONE: 314-725-5889

Construction Manager

NAVIGATE

PHONE:

Revision No. Description Date Issued

KSD PROJECT # NGL-2021-SECURED VESTIBULE

4/7

/2021 8

:22:0

4 A

M

C:\

Users

\bri

an.n

ash\D

ocum

ents

\20-2

03

Nort

h G

lendale

Ele

m V

estibule

Add_bnashF

HP

5U

.rvt

FINISH LEGEND, SCHEDULE& DETAILS

NORTH GLENDALEELEMENTARYSCHOOL SECUREDVESTIBULERENOVATIONPROJECT

04/08/2021

20-203

BID DOCUMENTS

A11.00A

765 N. SAPPINGTON ROADGLENDALE, MO 63122

SCALE: 6" = 1'-0"A11.00A

CARPET TO VCT23

FINISH LEGENDTYPE KEY DESCRIPTION MANUFACTURER STYLE, COLOR & SIZE CONTACT NOTES

FLOOR

FLOOR CPT-1 CARPET J+J FLOORING collection: KINETEX style: CATALYST 1841 color: MOTIVATE 2842 install: ASHLAR MAIN OFFICE

FLOOR RF-1 RUBBER FLOOR FLEXCO collection: EVOLVING STYLES CREATIVE ELEMENTS profile: RADIAL III color: CHARCOAL W/ BLACK CE-143 VESTIBULE

MISC

MISC TR-1 VINYL TRANSITION ROPPE style: #159 TILE CARPET JOINER color: 123 CHARCOAL RUBBER TO VCT / RUBBER TO CARPET

MISC TR-2 RUBBER TRANSITION ROPPE style: #50 TILE/CARPET JOINER 7/32" color: 123 CHARCOAL CARPET TO VCT

WALL

WALL PNT-1 PAINT BENJAMIN MOORE color: VESTIBULE

WALL PNT-2 PAINT BENJAMIN MOORE color: MAIN OFFICE

LOOK AT GRADUS FOR MORE OPTIONS

ROOM FINISH SCHEDULE

RM. NO. ROOM NAME

FLOORS WALL FINISH

CEILING FINISH

CASEWORK

FLOOR WALL BASE NORTH WALL EAST WALL SOUTH WALL WEST WALL COUNTERTOP BASE CABINET UPPER CABINET

A100 VESTIBULE RF-1 EXISTING TO REMAIN PNT-1 PNT-1 PNT-1 PNT-1 EXISTING TO REMAIN --- --- ---

A101 MAIN OFFICE CPT-1 EXISTING TO REMAIN PNT-2 PNT-2 PNT-2 PNT-1 EXISTING TO REMAIN --- --- ---

A105 CORRIDOR EXISTING TO REMAIN EXISTING TO REMAIN EXISTING TO REMAIN EXISTING TO REMAIN EXISTING TO REMAIN EXISTING TO REMAIN EXISTING TO REMAIN --- --- ---

A106 PRINCIPAL EXISTING TO REMAIN EXISTING TO REMAIN EXISTING TO REMAIN EXISTING TO REMAIN EXISTING TO REMAIN EXISTING TO REMAIN EXISTING TO REMAIN --- --- ---

A107 ASST. PRINCIPAL EXISTING TO REMAIN EXISTING TO REMAIN EXISTING TO REMAIN EXISTING TO REMAIN EXISTING TO REMAIN EXISTING TO REMAIN EXISTING TO REMAIN --- --- ---

SCALE: 6" = 1'-0"A11.00A

RUBBER TO VCT22

SCALE: 1/8" = 1'-0"A11.00A

FINISH FLOOR PLAN32

Page 6: Architect NORTH GLENDALE ELEMENTARY SCHOOL...FOC FOF FOM FOS FOW FP FPM FR FR FS FS FSD FT FT FTG FUT FVC FWC G G GA GAL GALV GB GC GCO GCMU GD GEN GEN GFA GFI GFRC GI GLAM GL GMU

TABLE 4.4, GENERAL EXEMPTION - SEISMIC BRACING NOT REQUIRED FOR ALL MEP COMPONENTS IN SEISMIC DESIGN CATEGORY A OR B.

TABLE 4.4, GENERAL EXEMPTION - SEISMIC BRACING NOT REQUIRED FOR ALL MEP COMPONENTS IN SEISMIC DESIGN CATEGORY C AND THE COMPONENT IMPORTANCE FACTOR = 1.0.

TABLE 4.4, GENERAL EXEMPTION - SEISMIC BRACING NOT REQUIRED FOR ALL MEP COMPONENTS IN SEISMIC DESIGN CATEGORY D, E OR F, AND THE COMPONENT IMPORTANCE FACTOR = 1.0, AND COMPONENTS HAVE APPROVED FLEXIBLE CONNECTIONS NO LESS THAN 3 FEET IN LENGTH TO THE ASSOCIATED DUCTWORK, PIPING AND CONDUIT, AND THE COMPONENTS ARE EITHER:

1. MOUNTED 4 FEET OR LESS ABOVE THE FLOOR LEVEL AND WEIGH 400 POUNDS OR LESS.2. WEIGH 20 POUNDS OR LESS, OR FOR DISTRIBUTION SYSTEMS WEIGHING 5 LB/FT OR LESS.

TABLE 4.4, DUCT EXEMPTION - SEISMIC BRACING NOT REQUIRED FOR DUCTS NOT PART OF HAZARDOUS EXHAUST SYSTEMS OR FIRE PROTECTION SYSTEMS SUCH AS SMOKE CONTROL OR EVACUATION SYSTEMS WHEN EITHER: 1. HVAC DUCTS SUSPENDED FROM HANGERS 12 INCHES OR LESS IN LENGTH: HANGERS SHALL BE DETAILED TO AVOID SIGNIFICANT BENDING OF THE HANGERS AND THEIR ATTACHMENTS.2. HVAC DUCTS HAVING A CROSS-SECTIONAL AREA OF LESS THAN 6 SQUARE FEET.

TABLE 4.4, PIPING SYSTEM EXEMPTIONS - SEISMIC BRACING NOT REQUIRED FOR PIPING THAT IS SUPPORTED BY ROD HANGERS: HANGERS IN THE PIPE RUN ARE 12 INCHES OR LESS IN LENGTH FROM THE TOP OF THE PIPE TO THE SUPPORTING STRUCTURE; HANGERS ARE DETAILED TO AVOID BENDING OF THE HANGERS AND THEIR ATTACHMENTS; AND PROVISIONS ARE MADE FOR PIPING TO ACCOMMODATE EXPECTED DEFLECTIONS.

TABLE 4.4, PIPING SYSTEM EXEMPTIONS - SEISMIC BRACING NOT REQUIRED FOR HIGH DEFORMABILITY PIPING; PROVISIONS ARE MADE TO AVOID IMPACT WITH LARGER PIPING OR MECHANICAL COMPONENTS OR TO PROTECT THE PIPING IN THE EVENT OF SUCH IMPACT; AND THE NOMINAL PIPE SIZES ARE LIMITED TO:

1. 1 INCH OR LESS FOR SEISMIC DESIGN CATEGORY D, E OR F, AND IMPORTANCE FACTOR > 1.0.2. 2 INCHES OR LESS FOR SEISMIC DESIGN CATEGORY C, AND IMPORTANCE FACTOR > 1.0.3. 3 INCHES OR LESS FOR SEISMIC DESIGN CATEGORY D, E OR F, AND IMPORTANCE FACTOR = 1.0.

TABLE 4.4, GAS PIPING SYSTEM EXEMPTIONS - SEISMIC BRACING NOT REQUIRED FOR ALL TYPES OF EXTERIOR GAS PIPING INSTALLED ON ROOFS IN SEISMIC DESIGN CATEGORY C, D, E OR F, WHEN SUCH PIPING WILL SUPPLY GAS UNDER NO MORE THAN 2 PSI AND IS PROTECTED BY ONE OF THE TWO FOLLOWING METHODS:

1. AN APPROVED SEISMIC SHUT-OFF VALVE IS INSTALLED WITHIN 5 FEET OF THE BEGINNING OF THE RUN OF GAS PIPE ON THE ROOF, OR OTHER APPROVED LOCATION. 2. APPROVED FLEXIBLE PIPING NO LESS THAN 3 FEET IN LENGTH IS INSTALLED WITHIN 3 FEET OF THE BEGINNING OF THE RUN OF GAS PIPE ON THE ROOF AND AT THE CONNECTION

TO THE EQUIPMENT SERVED BY THE PIPE AND AT INTERVALS ALONG THE RUN OF NO MORE THAN 42 FEET.

CONTRACTOR SHALL PROVIDE SHOP DRAWINGS TO THE ENGINEER OF RECORD FOR REVIEW AND APPROVAL PRIOR TO SUBMITTAL TO THE PLAN REVIEWER.

REFER TO ROOFTOP UNIT CURB DETAIL FOR ADDITIONAL INSTALLATION REQUIREMENTS.

COMPONENTS THAT ARE INSTALLED IN-LINE WITH THE DUCT SYSTEM AND HAVE AN OPERATING WEIGHT GREATER THAN 75 LBS. SHALL BE SUPPORTED AND LATERALLY BRACED INDEPENDENT OF THE DUCT SYSTEM.

UNBRACED PIPING ATTACHED TO IN-LINE EQUIPMENT SHALL BE PROVIDED WITH ADEQUATE FLEXIBILITY TO ACCOMMODATE DIFFERENTIAL DISPLACEMENTS.

APPURTENANCES SUCH AS DAMPERS, LOUVERS AND DIFFUSERS SHALL BE POSITIVELY ATTACHED WITH MECHANICAL FASTENERS.

TYPICAL NOTES: 1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

OCCUPANCY CATEGORY: IV

LISTING OF EQUIPMENT AND SYSTEMCOMPONENTS

FIRE PROTECTION, DETECTION &ALARM EQUIPMENT & SYSTEMCOMPONENTS:

HAZARDOUS EQUIPMENT ANDSYSTEM COMPONENTS:

OTHER EQUIPMENT AND SYSTEMCOMPONENTS NEEDED FORCONTINUED OPERATION OF SEISMICGROUP IV FACILITIES OR WHOSEFAILURE COULD IMPAIR THEIRCONTINUED OPERATION:

N/A

N/A

Ip=1.5

ROOF-MOUNTED EQUIPMENT > 400 POUNDS

Ip=1.5

ROOF-MOUNTED EQUIPMENT < 400 POUNDS

ROOFTOP UNITS

Ip=1.5

EQUIPMENT SUSPENDED FROM STRUCTURE

HVAC DUCTWORK < 6 S.F.

HVAC DUCTWORK > 6 S.F.N/A

LAY-IN AIR DEVICES < 20 POUNDS

MECHANICAL SEISMIC DESIGN CODE SCHEDULE

SEISMIC DESIGN CATEGORY: D

ANCHORAGE TO FLOORS, ROOFS, ETC.

NOT PROVIDED PROVIDED

SWAY BRACING LOCATION OF PROFESSIONALLY SEALED ANCHORAGE AND SWAY BRACING DETAILS.

ON CONST. DOCUMENTS

DWG. NO. SPEC SECT.

SUBSEQUENT SUBMITTAL

SHOP DWGS SEP. PERMIT

COMMENTS

EXHAUST FAN CONDENSING UNITS

CONDENSATE DRAIN PIPING

NOTE #XX

NOT PROVIDED PROVIDED

XX

XX

XX

XX

XX

XX

XX

XXXXXXXXXXXXXXXXXXXXXXXXXX XX

XX

NOTE #

NOTE #

NOTE #

NOTE #

NOTE #

NOTE #

NOTE #

NOTE #

NOTE #

Sheet Number

Sheet Name

Area Plan

Project Phase

Project Number

Issue Date

in • cite v. to provoke thought

Architect

INCITE DESIGN STUDIO1800 LAFAYETTE AVE., SUITE B, ST. LOUIS, MO 63104314.279.4500

Mech., Plumb., Elec., Telecom.

BRiC PARTNERSHIP, LLC3636 SOUTH GEYER ROAD, SUITE 305ST. LOUIS, MO 63127PHONE: 314-725-5889

Construction Manager

NAVIGATE

PHONE:

Revision No. Description Date Issued

KSD PROJECT # NGL-2021-SECURED VESTIBULE

4/7

/2021 9

:59:2

0 A

M

C:\

Users

\bro

oksg\D

ocum

ents

\2338-0

2_M

EP

_C

entr

al_

v20_bgerr

ityB

67F

2.r

vt SEISMIC CODE BLOCK -

MECHANICAL

NORTH GLENDALEELEMENTARYSCHOOL SECUREVESTIBULERENOVATIONPROJECT

04/08/2021

20-203

BID DOCUMENTS

M0.1

765 N. SAPPINGTON ROADGLENDALE, MO 63122

BRiC MO CERTIFICATE OF

AUTHORITY 2002028690

ENGINEER OF RECORD:

MO. LICENSE NO. 2013000576

EXP:12/31/2021

MICHAEL HOFF

BRiC MO CERTIFICATE OF

AUTHORITY 2002028690

ENGINEER OF RECORD:

MO. LICENSE NO. 2013000576

EXP:12/31/2021

MICHAEL HOFF

Page 7: Architect NORTH GLENDALE ELEMENTARY SCHOOL...FOC FOF FOM FOS FOW FP FPM FR FR FS FS FSD FT FT FTG FUT FVC FWC G G GA GAL GALV GB GC GCO GCMU GD GEN GEN GFA GFI GFRC GI GLAM GL GMU

GENERAL NOTES (HYDRONIC) GENERAL NOTES (DEMOLITION)GENERAL NOTES (AIR SIDE)

GENERAL NOTES

R

D

CS

CR

DTS

DTR

G

CWS

CWR

CA

LPS

MPS

LPC

MPC

HPS

HPC

CPD

HWS

HWR

RS

RL

RD

VL

D

MWL

FOV

FOR

FOS

K A

M

S

S

M

B

CL

GAS

FS

U

PIPING SPECIALTIES

GENERAL CONSTRUCTION CONTRACTOR

HEATING & AIR CONDITIONING CONTRACTOR

PLUMBING CONTRACTOR

ELECTRICAL CONTRACTOR

AUTOMATIC CONTROL SUB-CONTRACTOR

FIRE PROTECTION CONTRACTOR

KITCHEN EQUIPMENT CONTRACTOR

RISER DESIGNATION

(RISER INDICATION P=PLUMBING, P =KITCHEN, P =ACID)

(RISER NUMBER)

ACCESS PANEL

NEW CONNECTION

SA SOUND ATTENUATOR

FLEXIBLE CONNECTIONFC

SPLITTER DAMPER

HUMIDISTAT

CONDENSING WATER SUPPLY

CONDENSING WATER RETURN

DUAL TEMPERATURE SUPPLY

DUAL TEMPERATURE RETURN

CHILLED WATER SUPPLY

CHILLED WATER RETURN

COMPRESSED AIR

LOW PRESSURE STEAM

MEDIUM PRESSURE STEAM

LOW PRESSURE CONDENSATE

MEDIUM PRESSURE CONDENSATE

HIGH PRESSURE STEAM

HIGH PRESSURE CONDENSATE

CONDENSATE PUMP DISCHARGE

HEATING WATER SUPPLY

HEATING WATER RETURN

REFRIGERANT SUCTION

REFRIGERANT LIQUID

REFRIGERANT DISCHARGE

VENT LINE (OTHER THAN PLUMBING)

DRAIN LINE (OTHER THAN PLUMBING)

MAKE - UP WATER LINE

FUEL OIL VENT

FUEL OIL RETURN

FUEL OIL SUPPLY

AP

FINISH FLOOR ELEVATION

ABOVE FINISH FLOOR

TOP ELEVATION

BOTTOM ELEVATION

FFE

AFF

TE

BE

FL FLOW LINE

INVERT ELEVATIONINV

CENTER LINE

HALON SUB-CONTRACTOR

(MIXING OR BY-PASS AS INDICATED)

FLOW MEASURING DEVICE

COMBINATION BALANCING & MEASURING DEVICE

TEE (SIDE OUTLET DOWN)

FLEXIBLE PIPE CONNECTION

SOC SHUT-OFF COCK

PRESSURE REDUCING VALVE

TEMPERATURE AND PRESSURE RELIEF VALVE

FLOW CONTROL VALVE (GPM INDICATED)

VALVE W/ SUPERVISORY SWITCH

THERMOMETER (TUBE OR DIAL AS INDICATED)TH

DIAPHRAGM VALVE

MOTORIZED VALVE

PIPE GUIDES

ANCHORS

DIRECTION OF FLOW

DV

MV

PRV

FLOW SWITCH

BUTTERFLY VALVE

PRESSURE GAUGE

SOLENOID VALVE

PG

T&PR

FCV

BFV

SLV

STEAM TRAP

ECCENTRIC REDUCER

ELBOW (TURNED DOWN)

ELBOW (TURNED UP)

FMD

ECR

BMD

TEE (SIDE OUTLET UP)

CONCENTRIC REDUCER

EXPANSION JOINT

AIR VENT (AUTOMATIC)

AIR VENT (MANUAL)

RELIEF VALVE

AVA

CCR

EX

AVM

FC

RV

BALL VALVE

UNION

STRAINER

BALANCING COCK

GLOBE VALVE

CHECK VALVE

GATE VALVE

BC

BLV

STR

GV

GLV

CV

PETES PLUG

3 - WAY VALVE

STOP AND WASTE VALVE

HOSE END VALVE

LUBRICATED VALVE

SWV

TWV

HEV

LPV

GC

HAC

PC

EC

ACS

FPC

HSC

KEC

1. THESE PLANS ARE DIAGRAMMATIC IN NATURE SINCE THEY REFLECT ONLY THE AVAILABLE INFORMATION OBTAINED FROM EXISTING PLANS, SPECIFICATIONS, AND FIELD SURVEYS. THE EXACT LOCATION OF EXISTING DUCTWORK, PIPING, AND EQUIPMENT MAY DEVIATE FROM THE LOCATION INDICATED ON THE DRAWINGS. THE CONTRACTOR SHALL BE PREPARED TO MAKE SOME ALTERATIONS TO NEW AND/OR EXISTING SERVICES TO FIT ACTUAL JOB CONDITIONS.

2. THE SPACE ALLOWED FOR MECHANICAL (HVAC, PLUMBING, FIRE PROTECTION) AND ELECTRICAL WORK ABOVE THE SUSPENDED CEILING IS CRITICAL AND REQUIRES COORDINATION BETWEEN TRADES. CONTRACTORS SHALL THOROUGHLY FAMILIARIZE THEMSELVES WITH THE ARCHITECTURAL, STRUCTURAL, MECHANICAL, AND ELECTRICAL DRAWINGS PRIOR TO FABRICATION OR INSTALLATION OF ANY MATERIALS. DUCTWORK SHALL BE HUNG AS CLOSE AS POSSIBLE TO THE STRUCTURE ABOVE UNLESS INDICATED OTHERWISE. REWORK OF PIPING, DUCTWORK, EQUIPMENT LOCATION, CONDUIT, ETC. AS A RESULT OF POOR PLANNING, COORDINATION, OR SCHEDULING SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR.

3. ANY HOLES LEFT IN EXISTING WALL CONSTRUCTION DUE TO DEMOLITION OR NEW WORK SHALL BE PATCHED TO MATCH EXISTING CONDITIONS.

4. PIPES/DUCTS/ETC. PENETRATING EXTERIOR WALLS AND ROOFS SHALL BE SEALED WEATHER PROOF.

5. CONTRACTOR TO FIRESTOP ALL PENETRATIONS THROUGH FIRE-RATED FLOORS AND WALLS CREATED BY DEMOLITION OR NEW WORK WITH "SPECSEAL SSS" OR EQUAL.

6. THERMOSTATS & ROOM TEMPERATURE SENSORS SHALL BE MOUNTED AT 48" A.F.F. TO THE TOP OF THERMOSTAT UNLESS NOTED OTHERWISE. DO NOT MOUNT IN DIRECT SUNLIGHT OR NEAR HEAT PRODUCING EQUIPMENT.

7. INSTALL H.V.A.C. SYSTEM IN ACCORDANCE WITH ALL STATE AND LOCAL CODES.

8. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE COORDINATION OF ANY FRAMING REVISIONS, EQUIPMENT LOCATIONS, ADDITION OF CONTROLS, ELECTRICAL CIRCUITING REVISIONS, ETC. THAT RESULT FROM USING EQUIPMENT OTHER THAN INDICATED ON THE DRAWINGS. APPROVAL OF THE SHOP DRAWINGS BY THE ENGINEER WILL NOT WAIVE THE CONTRACTOR OF THIS RESPONSIBILITY.

9. THE CONTRACTOR SHALL HAVE THE FINAL RESPONSIBILITY FOR SYSTEM START UP AND TURN OVER TO THE OWNER.

10. ALL ITEMS INCLUDED ON THESE DRAWINGS AND THE SPECIFICATIONS SHALL BE INCLUDED IN THE CONTRACTOR'S BID. IF THE CONTRACTOR DOES NOT CLEARLY UNDERSTAND THESE PLANS OR IS NOT SURE OF THEIR MEANING, THE CONTRACTOR SHOULD OBTAIN THE ENGINEER'S WRITTEN EXPLANATION AND INTERPRETATION PRIOR TO BID TIME. THE CONTRACTOR WILL BE HELD TO THE INTERPRETATION OF THE ENGINEER.

11. CAULK ALL PENETRATIONS THRU WALLS TO MINIMIZE SOUND PENETRATION THRU WALLS.

12. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO COORDINATE ALL TEMPERATURE CONTROL SYSTEM REQUIREMENTS.

13. ANY DAMAGE TO THE SITE (SIDEWALKS, CURBS, ETC) OR TO THE BUILDING AS A RESULT OF WORK PERFORMED UNDER THIS CONTRACT SHALL BE FIXED BY THE CONTRACTOR AT NO ADDITIONAL COST TO THE OWNER.

14. CONTRACTOR WILL BE RESPONSIBLE FOR ALL CUTTING AND PATCHING OF ROOFS/WALLS/FLOORS AND CORE DRILLS REQUIRED TO COMPLETE THEIR RESPECTIVE WORK.

15. THE OWNER SHALL HAVE FIRST SALVAGE RIGHTS OF EQUIPMENT AND MATERIALS REMOVED. ALL EQUIPMENT AND MATERIALS NOT CLAIMED BY THE OWNER SHALL BE REMOVED FROM THE PREMISES BY THE CONTRACTORS.

16. OWNER SHALL BE RESPONSIBLE FOR REMOVING ALL ASBESTOS-CONTAINING MATERIAL ASSOCIATED WITH THIS PROJECT.

17. ALL EXISTING MECHANICAL EQUIPMENT, DUCTWORK, ETC. THAT SERVES SPACES ON OTHER FLOORS SHALL REMAIN AS IS. DO NOT DISCONNECT OR REMOVE ANY EQUIPMENT NOT SHOWN IN THESE PLANS.

18. REMOVE AND RE-INSTALL EXISTING LAY-IN CEILING AS REQUIRED TO COMPLETE ALL DEMOLITION AND NEW WORK. REPLACE CEILING TILES DAMAGED DURING CONSTRUCTION WITH NEW TILES MATCHING EXISTING.

1. THE SPACE ABOVE THE SUSPENDED CEILINGS SHALL BE USED AS A RETURN AIR PLENUM. IT IS THE RESPONSIBILITY OF THE MECHANICAL CONTRACTOR TO COORDINATE THE WORK OF OTHER TRADES TO PROVIDE ADEQUATE SPACE FOR THE FLOW OF RETURN AIR (250 FPM MAXIMUM VELOCITY). WHERE PARTITIONS EXTEND TO THE CONSTRUCTION ABOVE, OPENINGS SHALL BE PROVIDED IN THE PARTITION ABOVE THE CEILING.

2. DUCT DIMENSIONS NOTED ON THE DRAWINGS ARE NET FREE AREA. WHERE ACOUSTIC LINER IS INDICATED OR SPECIFIED THE SHEET METAL SIZE MUST BE INCREASED TO ACCOMMODATE THE LINER.

3. AREAS ABOVE THE CEILING SERVE AS A RETURN AIR PLENUM. ALL MATERIALS EXPOSED IN THE PLENUM SHALL HAVE A 25/50 SMOKE/FLAME SPREAD RATING.

4. CONTRACTOR SHALL BALANCE EACH AREA OF COMPLETED WORK. THE CONTRACTOR SHALL BALANCE SUPPLY, RETURN, AND EXHAUST AIR FLOWS AT EACH AIR DEVICE AFFECTED BY RENOVATION TO QUANTITY INDICATED ON THE DRAWINGS.

BALANCING VALVE

FLEXIBLE CONNECTION

TEMPERATURE CONTROL CONTRACTOR

MECHANICAL CONTRACTORMC

TCC

AFMS

CVR

AIR FLOW MEASURING STATION

CONSTANT VOLUME REGULATOR

EQUIPMENT OR PLUMBING FIXTURE DESIGNATION

(DETAIL NUMBER)DETAIL DESIGNATION

(SHEET NUMBER WHERE DETAIL IS FOUND)

(SECTION NUMBER)SECTION DESIGNATION

(SHEET NUMBER WHERE SECTION IS FOUND)

KEYED NOTES

REVISIONS

MANUAL VOLUME DAMPERVD

TV TURNING VANES

RETURN/TRANSFER/COMBUSTION AIR DISCHARGE DUCT UP

INCLINED DROP IN THE DIRECTION OF AIR FLOW

INCLINED RISE IN THE DIRECTION OF AIR FLOW

D

R

FXD FLEXIBLE DUCT

CEILING AIR DEVICE

SIDEWALL AIR DEVICE

(AIR DEVICE TYPE) - (SCHEDULE NUMBER)

(AIR FLOW IN CFM)E - EXHAUST GRILLE

S - SUPPLY DIFFUSER

T - TRANSFER GRILLE

R - RETURN GRILLE

DUCT SIZE DESIGNATION:1ST FIGURE SIDE SHOWN. (SIZE SHOWN IS FREE AREA SIZE, ALLOWANCE HAS NOT BEEN MADE FOR INTERIOR INSULATION WHERE SPECIFIED.)

24" x 12" RA

THERMOSTAT / TEMPERATURE SENSORT

NOTE: NOT ALL SYMBOLS OR ABBREVIATIONS MAY BE USED.

HEATING AND VENTILATION SYMBOLS

ABBREVIATIONS

MISCELLANEOUS SYMBOLS

S-1

1000

AIR DEVICE TYPE:

DUCT SYSTEM TYPE DESIGNATION:

DUCT SYSTEM TYPE:

SA - SUPPLY AIR

RA - RETURN AIR

EA - EXHAUST AIR

TA - TRANSFER AIR

OA - OUTDOOR AIR

RETURN/TRANSFER/COMBUSTION AIR DISCHARGE DUCT DOWN

SUPPLY AIR/COMBUSTION AIR INTAKE UP

SUPPLY AIR/COMBUSTION AIR INTAKE DOWN

EXHAUST AIR DUCT UP

EXHAUST AIR DUCT DOWN

CONCENTRIC DUCT TRANSITION

ECCENTRIC DUCT TRANSITION

RECTANGULAR DUCT TO ROUND DUCT TRANSITION

DAMPERED SHOE DUCT TAP FROM RECT. MAIN

45° DAMPERED DUCT TAP

SHOE DUCT TAP FROM RECT. MAIN

45° DUCT TAP

SADDLE TAP

STRAIGHT RECT. DUCT TAP FROM RECT. MAIN

STRAIGHT RECT. DUCT TAP FROM ROUND MAIN

ROUND DUCT UP

ROUND DUCT DOWN

AIR DEVICE THROW DESIGNATION:

(HATCHING DESIGNATES ZERO THROW)

24"/12" FLAT OVAL DUCT

TEMPERATURE SENSORS

CARBON MONOXIDE SENSORCO

MOTORIZED VOLUME DAMPERMD

FIRE DAMPERFD

M

ELBOW

TEE

NITROGEN OXIDE SENSORNOS

T

S

M

FD

SMOKE DAMPERSD

FIRE DAMPERFD

SD

FSD

H

1. THE CONTRACTOR SHALL COORDINATE SYSTEM SHUT-DOWNS, INCLUDING CHILLED WATER AND HEATING WATER SYSTEM SHUT-DOWNS, WITH THE OWNER. PROVIDE A MINIMUM TWO DAY NOTICE PRIOR TO ANY SYSTEM SHUT-DOWN.

2. THE CONTRACTOR SHALL BE RESPONSIBLE FOR DRAINING, FILLING, AND VENTING OF ALL HYDRONIC SYSTEMS IMPACTED BY THIS PROJECT.

1. THESE PLANS ARE DIAGRAMMATIC IN NATURE. SINCE THEY REFLECT ONLY THE AVAILABLE INFORMATION OBTAINED FROM EXISTING PLANS, SPECIFICATIONS, AND FIELD SURVEYS. THE EXACT LOCATION OF EXISTING DUCTWORK, PIPING, AND EQUIPMENT MAY DEVIATE FROM THE LOCATION INDICATED ON THESE DRAWINGS. THE CONTRACTOR SHALL BE PREPARED TO MAKE SOME ALTERATIONS TO NEW AND/OR EXISTING SERVICES TO FIT ACTUAL JOB CONDITIONS.

2. ITEMS SHOWN BOLD AND/OR DASHED ON THE DEMOLITION SHEETS INDICATE ITEMS TO BE REMOVED.

3. CROSS HATCHING INDICATES ITEMS TO BE REMOVED.

4. OWNER HAS FIRST RIGHT OF REFUSAL FOR ALL EQUIPMENT BEING REMOVED. CONTRACTOR TO DISPOSE OF EQUIPMENT BEING REMOVED BUT NOT RETAINED BY OWNER.

GRAVITY BACKDRAFT DAMPERBD

BDBD

Sheet Number

Sheet Name

Area Plan

Project Phase

Project Number

Issue Date

in • cite v. to provoke thought

Architect

INCITE DESIGN STUDIO1800 LAFAYETTE AVE., SUITE B, ST. LOUIS, MO 63104314.279.4500

Mech., Plumb., Elec., Telecom.

BRiC PARTNERSHIP, LLC3636 SOUTH GEYER ROAD, SUITE 305ST. LOUIS, MO 63127PHONE: 314-725-5889

Construction Manager

NAVIGATE

PHONE:

Revision No. Description Date Issued

KSD PROJECT # NGL-2021-SECURED VESTIBULE

4/7

/2021 9

:59:2

1 A

M

C:\

Users

\bro

oksg\D

ocum

ents

\2338-0

2_M

EP

_C

entr

al_

v20_bgerr

ityB

67F

2.r

vt LEGENDS, SYMBOLS, AND

NOTES - MECHANICAL

NORTH GLENDALEELEMENTARYSCHOOL SECUREVESTIBULERENOVATIONPROJECT

04/08/2021

20-203

BID DOCUMENTS

M0.2

765 N. SAPPINGTON ROADGLENDALE, MO 63122

BRiC MO CERTIFICATE OF

AUTHORITY 2002028690

ENGINEER OF RECORD:

MO. LICENSE NO. 2013000576

EXP:12/31/2021

MICHAEL HOFF

BRiC MO CERTIFICATE OF

AUTHORITY 2002028690

ENGINEER OF RECORD:

MO. LICENSE NO. 2013000576

EXP:12/31/2021

MICHAEL HOFF

Page 8: Architect NORTH GLENDALE ELEMENTARY SCHOOL...FOC FOF FOM FOS FOW FP FPM FR FR FS FS FSD FT FT FTG FUT FVC FWC G G GA GAL GALV GB GC GCO GCMU GD GEN GEN GFA GFI GFRC GI GLAM GL GMU

DN

DN

FV

FV

2' - 0" 4' - 0"

PrincipalA106

WORK ROOMA108

Existing Asst.

PrincipalA115

Exisitng

CorridorA105

T

T T

EX

IST

. S

A

EX

IST

. R

A

1 1/4"øHWR

1 1/4"øHWS

EXIST. BASEBOARD HEATER ETR

EXIST. UNIT HEATER

EX

IST

. S

A

1

2

2

2

2

2

2 2

EXIST. HWS&R DN THRU FLOOR

EXIST. SA EXIST. SA

3

A100A

A1

00B

A1

00

C

PrincipalA106

WORK ROOMA108

Main OfficeA101

Exisitng

CorridorA105

T

T T

EX

IST

. R

A

EX

IST

. S

A

EX

IST

. S

A

EXIST. SA EXIST. SA

1

11

1

1

1 1

2

EXIST. BASEBOARD HEATER ETR

1 1/4"øHWS

1 1/4"øHWR

EXIST. HWS&R DN THRU FLOOR

UH

1

GENERAL NOTES

A. SEE SHEET M0.2 FOR GENERAL NOTES THAT MAY APPLY TO THIS SHEET.

KEYED NOTES (NEW WORK)

CONTRACTOR SHALL BALANCE EXISTING AIR DEVICE TO CFM PER ENGINEER DIRECTION BASED ON PRE MEASUREMENT REPORT.

EXISTING THERMOSTAT RELOCATED. MODIFY SURFACE MOUNTED CONDUIT AND WIRING AS REQUIRED.

1

2

KEYED NOTES (DEMOLITION)

RELOCATE EXISTING THERMOSTAT TO NEW LOCATION INDICATED ON PLANS. COORDINATE EXACT LOCATION WITH TELECOM EQUIPMENT ON WALL.

MEASURE AIRFLOW AT EXISTING AIR DEVICE PRIOR TO START OF CONSTRUCTION. RECORD AND PROVIDE REPORT TO ENGINEER.

DISCONNECT AND REMOVE EXISTING UNIT HEATER.

1

2

3

BALL VALVE

CIRCUITSETTER

HOSE ENDDRAIN VALVE

RETURNAIR

NOTES:VALVES SHALL BE ACCESSIBLE THROUGH ACCESS PANEL ON CABINET UNIT HEATER

MANUALAIR VENTS

AIRFLOW

HW

R

HW

S

ESCUTCHEON PLATE AT CASINGPENETRATION AND AT WALLPENETRATION (WHERE APPLICABLE)

CONTROL VALVE

UNION(TYP.)

STRAINER

Sheet Number

Sheet Name

Area Plan

Project Phase

Project Number

Issue Date

in • cite v. to provoke thought

Architect

INCITE DESIGN STUDIO1800 LAFAYETTE AVE., SUITE B, ST. LOUIS, MO 63104314.279.4500

Mech., Plumb., Elec., Telecom.

BRiC PARTNERSHIP, LLC3636 SOUTH GEYER ROAD, SUITE 305ST. LOUIS, MO 63127PHONE: 314-725-5889

Construction Manager

NAVIGATE

PHONE:

Revision No. Description Date Issued

KSD PROJECT # NGL-2021-SECURED VESTIBULE

4/7

/2021 9

:59:2

1 A

M

C:\

Users

\bro

oksg\D

ocum

ents

\2338-0

2_M

EP

_C

entr

al_

v20_bgerr

ityB

67F

2.r

vt PLANS, DETAILS,

SCHEDULES, MECHANICAL

NORTH GLENDALEELEMENTARYSCHOOL SECUREVESTIBULERENOVATIONPROJECT

04/08/2021

20-203

BID DOCUMENTS

M1.1

765 N. SAPPINGTON ROADGLENDALE, MO 63122

SCALE: 1/8" = 1'-0"M1.1

FLOOR PLAN - DEMOLITION - MECHANICAL1

SCALE: 1/8" = 1'-0"M1.1

FLOOR PLAN - NEW WORK - MECHANICAL2

BRiC MO CERTIFICATE OF

AUTHORITY 2002028690

ENGINEER OF RECORD:

MO. LICENSE NO. 2013000576

EXP:12/31/2021

MICHAEL HOFF

NTSM1.1

CABINET UNIT HEATER PIPING DETAIL3

CABINET UNIT HEATER SCHEDULEPLAN MARK

MANUFACTURER MODEL

DESIGNSUPPLY

AIRFLOW(CFM)

HOT WATER COIL

MOTORPOWER (HP) NOTES

TOTAL HEATING CAPACITY(MBH) EDB LDB GPM EWT WPD (FT HD)

UH 1 TRANE FFBB020 150 9.4 70 128 1 160 4.08 .005 ALL

NOTES:

1. TWO-WAY CONTROL VALVE, MODULATING.2. LH PIPING ARRANGEMENT (CONTRACTOR TO VERIFY).3. INTERNAL T-STAT.4. FACTORY INSTALLED DELUXE PIPING PACAKGE INCLUDING MANUAL CIRCUIT SETTER.5. UNIT HEATER CONTROLLED BY EXISTING BAS.6. UNIT SHALL BE 115V/1 PH. SEE ELECTRICAL DRAWINGS FOR MORE INFORMATION.

BRiC MO CERTIFICATE OF

AUTHORITY 2002028690

ENGINEER OF RECORD:

MO. LICENSE NO. 2013000576

EXP:12/31/2021

MICHAEL HOFF

Page 9: Architect NORTH GLENDALE ELEMENTARY SCHOOL...FOC FOF FOM FOS FOW FP FPM FR FR FS FS FSD FT FT FTG FUT FVC FWC G G GA GAL GALV GB GC GCO GCMU GD GEN GEN GFA GFI GFRC GI GLAM GL GMU

LISTING OF EQUIPMENT ANDSYSTEM COMPONENTS

ANCHORAGE TO FLOORS,ROOFS, ETC.

SWAY BRACING

LOCATION OF PROFESSIONALLY SEALEDANCHORAGE AND SWAY BRACING DETAILS

ONCONSTRUCTION

DOCUMENTS

SUBSEQUENTSUBMITTAL

COMMENTS

NOT PROVIDEDFOR PROJECT

DWG. NO. ORSPEC. SECTION

SHOPDRAWINGS

SEPERATE PERMIT AND

PLANS

X

NOTES:

1. IT IS THE BASIC INTENT OF THIS CODE BLOCK TO DECLARE WHETHER OR NOT ANCHORAGE AND SWAY BRACING IS BEING PROVIDED ON THE PROJECT. IF SO, TO DECLARE WHETHER OR NOT THE DETAILS ARE SHOWN ON THE PLANS OR WILL BE SHOWN ON A SUBSEQUENT SUBMISSION. IF SEISMIC RESTRAINT OF A COMPONENT IS NOT REQUIRED BY CODE THIS SHOULD BE STATED IN THE COMMENTS. IF SEISMIC RESTRAINT, WHICH IS NOT REQUIRED BY CODE, IS BEING PROVIDED DUE TO OWNER/DESIGNER REQUIREMENTS THIS SHOULD ALSO BE STATED IN THE COMMENTS.

2. SHOP DRAWINGS NEED TO BE SUBMITTED TO THE COUNTY A MINIMUM OF TWO WEEKS PRIOR TO THE PLANNED INSTALLATION TO ALLOW FOR PLAN REVIEW AND DISTRIBUTION TO THE INSPECTOR. ADDITIONAL TIME MAY BE NEEDED IF SUCH SUBMISSIONS ARE DEFICIENT.

3. FIRE ALARM SYSTEM TO BE DESIGNED IN ACCORDANCE WITH NFPA 72. SHOP DRAWINGS TO PROVIDE SEISMIC DETAILS FOR COMPONENTS.4. TABLE 4.4, GENERAL EXEMPTION 1, SEISMIC DESIGN CATEGORY D, Ip = 1.0, AND WEIGHT LESS THAN 5LB/FT.5. TABLE 4.4, GENERAL EXEMPTION 1, SEISMIC DESIGN CATEGORY D, Ip = 1.0, WEIGHT LESS THAN 20 POUNDS, 3' OR MORE FLEXIBLE CONNECTION, AND MECHANICALLY

ATTACHED TO CEILING GRID OR STRUCTURE.

X

FIRE PROTECTION, DETECTION & ALARM EQUIPMENT AND SYSTEM COMPONENTS:FIRE ALARM PANELFIRE ALARM WIRING

EMERGENCY OR STANDBY EQUIPMENT AND SYSTEM COMPONENTS:EMERGENCY GENERATORAUTOMATIC TRANSFER SWITCHEMERGENCY DISTRIBUTION PANELCONDUIT AND WIRING

N/A, NO OCCUPANCYCATEGORY IV IN THEPROJECT

OTHER GENERAL EQUIPMENT AND SYSTEM COMPONENTS:MAIN SWITCHGEARTRANSFORMERSDISTRIBUTION PANELSLIGHTING FIXTURESCONDUIT AND WIRING

OTHER EQUIPMENT AND SYSTEMCOMPONENTS NEEDED FOR CONTINUEDOPERATION OF OCCUPANCY CATEGORYIV FACILITIES OR WHOSE FAILURECOULD IMPAIR THEIR CONTINUEDOPERATION:

XX

PROVIDED FORPROJECT

NOT PROVIDEDFOR PROJECT

PROVIDED FORPROJECT

XX

XX

XX

XX

X XX XX XX X

N/A, NO EMERGENCYOR STANDBYEQUIPMENT IN THEPROJECT

ELECTRICAL & TECHNOLOGY COMMUNICATION SYSTEM COMPONENTS EARTHQUAKE LOAD RESISTANCE

X X

NO NEW WORK

OCCUPANT CATEGORY (III) SEISMIC DESIGN CATEGORY (D)

N/AN/AN/ASEE NOTE #5SEE NOTE #4

Sheet Number

Sheet Name

Area Plan

Project Phase

Project Number

Issue Date

in • cite v. to provoke thought

Architect

INCITE DESIGN STUDIO1800 LAFAYETTE AVE., SUITE B, ST. LOUIS, MO 63104314.279.4500

Mech., Plumb., Elec., Telecom.

BRiC PARTNERSHIP, LLC3636 SOUTH GEYER ROAD, SUITE 305ST. LOUIS, MO 63127PHONE: 314-725-5889

Construction Manager

NAVIGATE

PHONE:

Revision No. Description Date Issued

KSD PROJECT # NGL-2021-SECURED VESTIBULE

4/7

/2021 9

:29:0

1 A

M

C:\

Users

\mattj\D

ocum

ents

\2338-0

2_M

EP

_C

entr

al_

v20_m

jaenkeP

ES

NW

.rvt

Seismic Code Block - Elec. &Tech. Comm.

NORTH GLENDALEELEMENTARYSCHOOL SECUREVESTIBULERENOVATIONPROJECT

04/08/2021

20-203

BID DOCUMENTS

E0.1

765 N. SAPPINGTON ROADGLENDALE, MO 63122

BRiC MO CERTIFICATE OF

AUTHORITY 2002028690

ENGINEER OF RECORD:

MO. LICENSE NO. 016688

EXP:12/31/22

CARL V. HAUCK

Page 10: Architect NORTH GLENDALE ELEMENTARY SCHOOL...FOC FOF FOM FOS FOW FP FPM FR FR FS FS FSD FT FT FTG FUT FVC FWC G G GA GAL GALV GB GC GCO GCMU GD GEN GEN GFA GFI GFRC GI GLAM GL GMU

M

A 1a

A

A

a

A

a

A

A

A

CLG

B

X

WALL

1a

1a

1a

1a

1a

1a

1a

ELECTRICAL LEGEND AND ABBREVIATIONS (SEE SPECIFICATIONS & SCHEDULES)

ONE-LINE DIAGRAM SYMBOLS

WIRING PLANS

JUNCTION AND PULL BOXES LIGHTING FIXTURES

SWITCHES - LIGHTING CONTROL

DRAWING REFERENCES

POWER EQUIPMENT ABBREVIATIONS

WIRING DEVICES, RECEPTACLES - MISC.

TRANSIENT VOLTAGE SURGE SUPPRESSOR

GAP TYPE SURGE ARRESTOR

MOTOR OPERATED MEDIUM VOLTAGELOAD INTERRUPTER SWITCH

CAPACITOR

N

VOLTAGE TRANSFORMER

POWER TRANSFORMER

CURRENT TRANSFORMER

KEY-INTERLOCK

NEUTRAL BUS

GROUND BUS

CONTACTOR

GENERATOR

MOTOR STARTER

XX/XX

CIRCUIT BREAKER (FRAME/TRIP)

DRAWOUT CIRCUIT BREAKER

FUSIBLE SWITCH (SIZE/FUSE)

XX/XX

GROUND

PULL BOX

JUNCTION BOX (4"x4"x1/2" MINIMUM)

LIGHTING FIXTURE -LIFE SAFETY BRANCH

RECESSED OR SURFACE LIGHTING FIXTURE(EMERGENCY, CRITICAL OR LIFE SAFETY IF SHADED AS ABOVE)

WALL MOUNTED LIGHTING FIXTURE(EMERGENCY, CRITICAL OR LIFE SAFETYIF SHADED AS ABOVE)

STRIP FIXTURE

EXIT SIGN DOUBLE-SIDED FIXTUREDIRECTIONAL ARROWS AS INDICATED

EXIT SIGN SINGLE-SIDED FIXTUREDIRECTIONAL ARROWS AS INDICATED

BATTERY OPERATED EMERGENCY LIGHTING UNIT

LIGHTING FIXTURE WITH INTEGRAL EMERGENCY BATTERY PACK

LIGHTING FIXTURE -CRITICAL BRANCH

2.1.NOTES:

SECTION NUMBER

DRAWING NUMBER

SECTION REFERENCE TITLE

NORTH ARROW

1

E-1

SWITCHES - SINGLE POLE, 2 POLE, 3-WAY, 4-WAY

TYPICAL MOUNTING HEIGHT - 48" AFF

TYPEL - LIGHTINGP - POWERE - EMERGENCY/EQUIPMENT BRANCHLS - LIFE SAFETY BRANCHC - CRITICAL BRANCHX - X-RAY

VOLTAGEH - 480VL - 240V OR 208/120V

FLOOR

DRAWING NUMBER

DETAIL NUMBER

PLAN DETAIL REFERENCE TITLE

KEYED NOTE DESIGNATION

2

SC-8

DDIMMER SWITCH

STARTERS (MANUAL, MAGNETIC & COMB. MAGNETICWITH DISC.)

1LL1

32 4

G

3

3.

ELECTRICAL SERVICE METER

WALL MOUNTED LIGHTING FIXTURE.HEIGHT AS NOTED.

EXTERIOR LIGHTING FIXTURE - POLE MOUNTEDTYPES AND DETAILS AS NOTED

3 POLE UNITSU.O.N.

3 POLE UNITSU.O.N.

CONDUIT RUN CONCEALED IN CEILING OR WALL CONSTRUCTION

CONDUIT RUN IN FLOOR CONSTRUCTION OR UNDERGROUND

CONDUIT RUN EXPOSED

CONDUIT TURNING UP

CONDUIT TURNING DOWN

CONDUIT CAPPED FOR FUTURE.

HOMERUN TO PANEL OR DESTINATION NOTED

LIGHTING FIXTURE(A - DESIGNATES FIXTURE TYPE1 - DESIGNATES CIRCUIT NUMBERa - DESIGNATES CONTROLLING SWITCH)

STRIP FIXTUREEMERGENCY POWER

MOTOR - SEE EQUIPMENT DATA SCHEDULE FORHORSEPOWER

PANELBOARD

SEQUENCE NUMBER

TRANSFORMER

DISCONNECT SWITCH. FUSED OR UNFUSED AS NOTED

ELECTRICAL SERVICE METER

SHADINGINDICATESFACE(S)

NOT ALL SYMBOLS AND ABBREVIATIONS ARE USED ON THESE PLANS.ALL MOUNTING HEIGHTS ARE TO CENTERLINE OF DEVICES AND EQUIPMENT UNLESS NOTED OTHERWISEIN GENERAL, SYMBOLS SHOWN WITH LIGHT LINES DENOTE EXISTING WORK. SYMBOLS SHOWN WITH HEAVY LINES DENOTE PROPOSED WORK.

SHIELDED (AS IN CABLE)SHLD

EXISTING RELOCATEDER

ELECTRIC WATER COOLER

GROUND FAULT CIRCUIT INTERRUPTER

EXISTING TO REMAIN

GFCI

HH

GRD

-

-

-

HANDHOLE

GROUND

FM

F/O

GF

FS

-

-

-

-

EWC

FA

ETR

-

-

-

-

F/O MODEM

GROUND FAULT

FUSIBLE SWITCH

FIBER OPTIC

FIRE ALARM

UNINTERUPTIBLE POWER SUPPLY

UNLESS OTHERWISE NOTED

WATERTIGHTWT

WEATHER-PROOF

EXPLOSION PROOF

WP

XP --

-

VAPORTIGHT

SWITCHBOARD

TYPICAL

TELEPHONE

UNGROUNDEDUNG

U.O.N.

VT

UPS

-

-

-

-

T

TYP.

SWBD

-

-

-

-

BELOW CEILINGB.C.

CIRCUIT BREAKER

CONTROL CONTACTOR

CLOSED CIRCUIT TELEVISION

COUNTER CLOCKWISE

DISTRIBUTED CONTROLLER UNIT

DISTRIBUTION PANEL

ELECTRICAL CONTRACTOR

ELECTRIC OR ELECTRICAL

-DCU

DT

E.C.

ELEC

DWG

-

-

-

-

DN

DP -

-

DUSTTIGHT

DRAWING

DOWN

CC

CCTV

CCW

CW -

-

-

CB

CAM

C

-

-

-

-

CLOCKWISE

CONDUIT

CAMERA

ACCESS CONTROL SYSTEM

ABOVE FINISHED FLOOR

AUTOMATIC TRANSFER SWITCH

A.C.S.

A.F.F.

ATS -

-

-

-

MASTER ANTENNA TELEVISIONMATV

POLYVINYL CHLORIDE CONDUIT

PORTABLE INTERFACE

MOTOR CONTROL PANEL

MOTOR CONTROL CENTER

PI

RECESSED

RAINTIGHT

PAIR

POWER PANEL

PASSIVE INFRA RED

RADIO FREQUENCY

PVC

RF

RT

R

-

-

-

-

PP

PR.

P.I.R.

-

-

-

-

PUBLIC ADDRESS

NIGHT LIGHT

NURSE CALL

EMPTY CONDUIT

MANHOLE

-MT

NL

PA

NC

-

-

-

MCP

MH

MCC

-

-

-

LOCAL AREA NETWORK

INPUT/OUTPUT

LIGHTING PANEL

LAN

LP

I/O

-

-

-

-

ELECTRICAL METALLIC TUBINGEMT -

RGS RIGID GALVANISED STEEL-

IMC INTERMEDIATE METAL CONDUIT-

METAL CLADMC -

GENERAL CONTRACTORG.C. -

VARIABLE FREQUENCY DRIVEVFD -

ILSM INTERIM LIFE SAFETY MEASURES-

FLOOR BOX - SYMBOL DESIGNATES TYPE OF SERVICE

DUPLEX RECEPTACLE OUTLET - GROUND FAULT TYPE

DUPLEX RECEPTACLE OUTLET

SPECIAL PURPOSE OUTLET AS NOTED

SINGLE RECEPTACLE OUTLET

DUPLEX RECEPTACLE OUTLET MOUNTED +8" ABOVE COUNTER

DUPLEX RECEPTACLE OUTLET WITH ISOLATED GROUND

DOUBLE DUPLEX RECEPTACLE OUTLET

GFCIDUPLEX RECEPTACLE OUTLET MOUNTED +8" ABOVE COUNTER -GROUND FAULT TYPE

FEEDER NUMBER

EB

GFCI

COMBINATION DUPLEX RECEPTACLE AND USB OUTLET USB

TYPICAL MOUNTING HEIGHT - 18" AFF

HACHURES INDICATE NUMBER OF CONDUCTORS IN CONDUIT NOTE:

IG

GEN

K

M

TVSS

J

P

1

X

X

X

A

1a

OCCUPANCY SENSORS AND TIMERS(SEE SPECIFICATION FOR ADDITIONAL INFORMATION)

MLOW VOLTAGE MOMENTARY SWITCH - WATTSTOPPER DCC2 OR EQUIVALENT

PPASSIVE INFRARED TYPE WALL SWITCH OCCUPANCY DETECTOR - WATTSTOPPER PW-301 OR EQUIVALENT

PUDUAL TECHNOLOGY TYPE WALL SWITCH OCCUPANCY DETECTOR - WATTSTOPPER DSW-301 OR EQUIVALENT

PASSIVE INFRARED TYPE CEILING OCCUPANCY DETECTOR - WATTSTOPPER CI-300 OR EQUIVALENT

DUAL TECHNOLOGY TYPE CEILING OCCUPANCY DETECTOR - WATSOTPPER DT-300 OR EQUIVALENT

P

PU

LIGHTIG CONTROL POWER PACK - WATTSTOPPER BZ-150 OR EQUIVALENT

PP

F N

M

LONG HACHURE - NEUTRAL CONDUCTOR SHORT HACHURE -HOT OR SWITCHED CONDUCTORS LONG HACHURE WITH DOT - GROUND CONDUCTOR LONG HACHURE WITH DOT & RETURN LINE - ISOLATED GROUND CONDUCTOR. WHEN HACHURES ARE NOT SHOWN AND WIRING IS FOR POWER OR LIGHTING CIRCUITS, PROVIDE HOT, NEUTRAL, AND GROUND. WHEN FOR MULTIPLE CIRCUITS, PROVIDE NO. OF PHASE CONDUCTORS, NEUTRAL CONDUCTORS AND A GROUND CONDUCTOR. HACHURES ARE SHOWN AS A GUIDE AND MAY NOT BE EXACT COUNTS IN ALL CASES. PROVIDE WIRING REQUIRED BY THE CIRCUITING AND SWITCHING REQUIREMENTS FOR THE PARTICULAR CIRCUITS INVOLVED.

Sheet Number

Sheet Name

Area Plan

Project Phase

Project Number

Issue Date

in • cite v. to provoke thought

Architect

INCITE DESIGN STUDIO1800 LAFAYETTE AVE., SUITE B, ST. LOUIS, MO 63104314.279.4500

Mech., Plumb., Elec., Telecom.

BRiC PARTNERSHIP, LLC3636 SOUTH GEYER ROAD, SUITE 305ST. LOUIS, MO 63127PHONE: 314-725-5889

Construction Manager

NAVIGATE

PHONE:

Revision No. Description Date Issued

KSD PROJECT # NGL-2021-SECURED VESTIBULE

4/7

/2021 9

:29:0

2 A

M

C:\

Users

\mattj\D

ocum

ents

\2338-0

2_M

EP

_C

entr

al_

v20_m

jaenkeP

ES

NW

.rvt

Legend, Symbols & Notes -Electrical

NORTH GLENDALEELEMENTARYSCHOOL SECUREVESTIBULERENOVATIONPROJECT

04/08/2021

20-203

BID DOCUMENTS

E0.2

765 N. SAPPINGTON ROADGLENDALE, MO 63122

ELECTRICAL SHEET LIST

SheetNumber Sheet Name

E0.1 Seismic Code Block - Elec. & Tech. Comm.

E0.2 Legend, Symbols & Notes - Electrical

E1.1 Demolition Plan - Electrical

E2.1 Floor Plan - New Work - Power

E3.1 Reflected Ceiling Plan - New Work - Lighting

E5.1 Electrical Details and Light Fixture Schedule

BRiC MO CERTIFICATE OF

AUTHORITY 2002028690

ENGINEER OF RECORD:

MO. LICENSE NO. 016688

EXP:12/31/22

CARL V. HAUCK

Page 11: Architect NORTH GLENDALE ELEMENTARY SCHOOL...FOC FOF FOM FOS FOW FP FPM FR FR FS FS FSD FT FT FTG FUT FVC FWC G G GA GAL GALV GB GC GCO GCMU GD GEN GEN GFA GFI GFRC GI GLAM GL GMU

DN

J

J

J

J

FV

FV

2' - 0" 4' - 0"

PrincipalA106

WORK ROOMA108

Existing Asst.

PrincipalA115

Exisitng

CorridorA105

1D-NG

1

2

3

VESTIBULEA100

EX. STOR.A104

EXISTING

OFFICEA117

EX. STORA119

EX, TA121

1

GENERAL NOTES

1. THE ELECTRICAL CONTRACTOR SHALL REMOVE, CAP, AND/OR RELOCATE EQUIPMENT, OUTLETS, CONDUIT, WIRE, ETC., WHETHER INDICATED ON THE DRAWINGS OR NOT, AND AS MAY BECOME NECESSARY BECAUSE OF EXISTING FIELD CONDITIONS. IT SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR TO VISIBLY EXAMINE ALL EXISTING WALLS DESIGNATED FOR REMOVAL OR MODIFICATION TO DETERMINE THE CONDUIT AND THE WIRING THAT WILL REQUIRE CAPPING AND/OR REMOVAL. THE CONTRACTOR SHALL BE HELD TO HAVING VISITED THE SITE AND TAKEN ALL EXISTING CONDITIONS INTO CONSIDERATION.

2. PROTECT ADJACENT MATERIALS INDICATED TO REMAIN. INSTALL AND MAINTAIN DUST AND NOISE BARRIERS TO KEEP DIRT, DUST, AND NOISE FROM BEING TRANSMITTED TO ADJACENT AREAS. REMOVE PROTECTION AND BARRIERS AFTER DEMOLITION OPERATIONS ARE COMPLETE.

3. LOCATE, IDENTIFY, AND PROTECT ELECTRICAL SERVICES PASSING THROUGH DEMOLITION AREA AND SERVING OTHER AREAS OUTSIDE THE DEMOLITION LIMITS. MAINTAIN SERVICES TO AREAS OUTSIDE DEMOLITION LIMITS. WHEN SERVICES MUST BE INTERRUPTED, INSTALL TEMPORARY SERVICES FOR AFFECTED AREAS.

4. MAINTAIN CIRCUIT CONTINUITY TO ALL EXISTING FIXTURES, EQUIPMENT, OUTLETS, ETC., TO REMAIN IN USE WHETHER NOTED ON THE PLANS OR NOT. FIELD VERIFY EXISTING ITEMS TO REMAIN IN USE. WIRING FOR EXISTING CIRCUITS WHICH MUST BE RE-ROUTED OR WHICH ARE PARTIALLY ABANDONED, SHALL BE RECONNECTED TO SERVICE THE REMAINING OUTLETS ON THE CIRCUIT.

5. IN THE DEMOLITION WORK, REMOVE ALL UNUSED WIRING AND CABLES AND UNUSED CONDUIT THAT IS EXPOSED OR WITHIN ACCESSIBLE CEILINGS WHICH IS AFFECTED BY AND IS IN THE AREA OF THE WORK OF THIS CONTRACT.

6. THE INTENTION OF THE ELECTRICAL DEMOLITION IS TO DISCONNECT AND REMOVE ALL ELECTRICAL WORK MADE VOID BY THE SCOPE OF THE CONSTRUCTION AND ALTERATION. FIELD VERIFY EXACT MATERIAL QUANTITIES REQUIRED TO BE REMOVED.

7. WHERE ELECTRICAL EQUIPMENT, CONDUIT, BOXES, AND SUPPORTING HARDWARE ARE REMOVED, PATCH, AND FINISH THE SURFACE AS REQUIRED TO MATCH THE EXISTING, UNLESS OTHERWISE NOTED.

8. WHERE BURIED CONDUITS EXTENDING OUT OF A CONCRETE SLAB BECOME ABANDONED, CUT AND GRIND THE CONDUITS OFF FLUSH WITH TOP OF SLAB AND PLUG WITH NON-SHRINK WATERPROOF GROUT FILL.

9. OWNER HAS FIRST SALVAGE RIGHTS TO ALL REMOVED MATERIALS AND EQUIPMENT. ALL MATERIAL AND EQUIPMENT NOT CLAIMED BY THE OWNER SHALL BECOME THE PROPERTY OF THE CONTRACTOR AND SHALL BE REMOVED FROM THE PROJECT SITE. COORDINATE AT PROJECT COMMENCEMENT.

10. ACCEPTANCE OF CONTRACT MEANS INSTALLER ACCEPTS EXISTING CONDITIONS.

11. CONTRACTOR SHALL COORDINATE ALL DEMOLITION WORK WITH ALL OTHER TRADES.

12. IN WALLS OR FLOORS WHERE A FLUSH DEVICE IS BEING REMOVED, BUT THE WALL OR FLOOR REMAINS OR FOR ANY OUTLET WHICH MUST REMAIN, BUT HAS A DEVICE REMOVED, PROVIDE A BLANK COVER OVER THE OUTLET. MATCH THE COLOR AND MATERIAL OF EXISTING REMAINING COVERS IN THE ROOM OR SPACE.

13. LEGALLY DISPOSE OF HAZARDOUS MATERIALS AND BALLASTS OR OTHER EQUIPMENT CONTAINING PCB'S AND LAMPS CONTAINING MERCURY. COMPLY WITH ALL FEDERAL, STATE, AND LOCAL LAWS.

14. MODIFY EXISTING PANEL DIRECTORIES (OR REPLACE) FOR PANELS WHICH HAVE HAD ALTERATIONS TO THE CIRCUITS ORIGINATING THEREIN. DESCRIBE THE LOAD AND LOCATION.

15. WHERE WORK IS TO BE PERFORMED ABOVE EXISTING ACCESSIBLE CEILINGS, CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVING CEILING TILES AND GRID WITHOUT DAMAGE; STORAGE OF EXISTING TILES AND GRID WHILE WORK IS BEING PERFORMED, AND INSTALLATION OF EXISTING GRID AND TILES AFTER DIVISION 26 WORK IS COMPLETED.

16. ALL EXISTING ELECTRICAL WORK AND ASSOCIATED RACEWAY AND WIRING WHICH HAS BEEN MADE OBSOLETE BY THE WORK AND/OR IS SHOWN DASHED ON THE ELECTRICAL DEMOLITION DRAWINGS, SHALL BE DISCONNECTED AND REMOVED, UNLESS OTHERWISE NOTED. ALTHOUGH AN ATTEMPT HAS BEEN MADE TO INDICATE ALL OF THIS WORK, TOTAL ACCURACY IS NOT GUARANTEED. CONTRACTOR SHALL VISIBLY EXAMINE ALL AREAS AND WALLS AND CEILINGS SCHEDULED FOR REMOVAL TO DETERMINE EXISTING ELECTRICAL ITEMS TO REMAIN.

17. ALL PANELS SHOWN ARE EXISTING TO REMAIN UNLESS NOTED OTHERWISE.

18. EXISTING WIRING TO REMAIN SHALL BE TEMPORARILY SUPPORTED AND PROTECTED. IF WIRING IS DAMAGED DURING THE CONSTRUCTION PROCESS, CONTRACTOR SHALL REPLACE WIRING WITH NEW PER SPECIFICATIONS.

KEYED NOTES

REMOVE LIGHT SWITCH ONLY. ROUGH-IN AND WIRING TO REMAIN FOR RECONNECTION TO NEW OCCUPANCY SENSOR CONTROL SWITCH.

REMOVE ALL SURFACE MOUNTED RACEWAYS AND RECEPTACLES IN THIS ROOM. SALVAGE (2) 20A, 120V CIRCUITS FOR EXTENSION TO NEW RECEPTACLES. FOR BIDDING PURPOSES IT SHALL BE ASSUMED THAT THESE CIRCUITS EXIST. IF DURING DEMOLITION IT IS DETERMINED THAT THEY DO NOT EXIST, NOTIFY ENGINEER IMMEDIATELY.

REMOVE PORTION OF SURFACE MOUNTED RACEWAY SERVING EXISTING MECHANICAL UNIT AS REQUIRED FOR NEW DOOR INSTALLATION.

1

2

3

Sheet Number

Sheet Name

Area Plan

Project Phase

Project Number

Issue Date

in • cite v. to provoke thought

Architect

INCITE DESIGN STUDIO1800 LAFAYETTE AVE., SUITE B, ST. LOUIS, MO 63104314.279.4500

Mech., Plumb., Elec., Telecom.

BRiC PARTNERSHIP, LLC3636 SOUTH GEYER ROAD, SUITE 305ST. LOUIS, MO 63127PHONE: 314-725-5889

Construction Manager

NAVIGATE

PHONE:

Revision No. Description Date Issued

KSD PROJECT # NGL-2021-SECURED VESTIBULE

4/7

/2021 9

:29:0

2 A

M

C:\

Users

\mattj\D

ocum

ents

\2338-0

2_M

EP

_C

entr

al_

v20_m

jaenkeP

ES

NW

.rvt

Demolition Plan - Electrical

NORTH GLENDALEELEMENTARYSCHOOL SECUREVESTIBULERENOVATIONPROJECT

04/08/2021

20-203

BID DOCUMENTS

E1.1

765 N. SAPPINGTON ROADGLENDALE, MO 63122

SCALE: 1/4" = 1'-0"E1.1

FLOOR PLAN - DEMOLITION - ELECTRICAL1

BRiC MO CERTIFICATE OF

AUTHORITY 2002028690

ENGINEER OF RECORD:

MO. LICENSE NO. 016688

EXP:12/31/22

CARL V. HAUCK

Page 12: Architect NORTH GLENDALE ELEMENTARY SCHOOL...FOC FOF FOM FOS FOW FP FPM FR FR FS FS FSD FT FT FTG FUT FVC FWC G G GA GAL GALV GB GC GCO GCMU GD GEN GEN GFA GFI GFRC GI GLAM GL GMU

DN

J

GENERAL NOTES

1. ALL WORK SHALL BE IN ACCORDANCE WITH THE 2005 NATIONAL ELECTRICAL CODE.

2. ALL PANELS SHOWN ARE EXISTING TO REMAIN UNLESS NOTED OTHERWISE.

3. THE ELECTRICAL DRAWINGS HAVE BEEN PREPARED UTILIZING EXISTING DRAWINGS AND BUILDING OBSERVATIONS AND MAY NOT SHOW ALL CONDITIONS. CONTRACTOR SHALL VISIT THE BUILDING PRIOR TO BID SUBMISSION AND BECOME FAMILIAR WITH ALL EXISTING CONDITIONS. CONTRACTOR WILL NOT BE ALLOWED ADDITIONAL FUNDS OR TIME DUE TO THE CONTRACTOR'S FAILURE TO BECOME FAMILIAR WITH ALL EXISTING CONDITIONS. ACCEPTANCE OF CONTRACT MEANS INSTALLER ACCEPTS EXISTING CONDITIONS.

4. CONTRACTOR SHALL SCHEDULE ALL ELECTRICAL SYSTEM POWER OUTAGES WITH THE OWNER'S REPRESENTATIVE AT LEAST 7 CALENDAR DAYS IN ADVANCE OF A SHUTDOWN. DOWNTIME ON BRANCH CIRCUIT PANELBOARDS, SWITCHBOARDS, DISTRIBUTION PANELBOARDS, MOTOR CONTROL CENTERS, ETC., WHICH SERVE LOADS OUTSIDE OF THE CONSTRUCTION AREAS SHALL BE LIMITED TO A (1) HOUR (MAXIMUM) OUTAGE. MORE THAN (1) SCHEDULED OUTAGE MAY OCCUR ON EACH PIECE OF EQUIPMENT, BUT THE MAXIMUM OUTAGE TIME MUST BE MAINTAINED.

5. ALL PENETRATIONS THROUGH CONCRETE OR MASONRY WALLS AND FLOOR SLABS SHALL BE CORE DRILLED. AFTER CONDUITS HAVE BEEN INSTALLED, SEAL WALL AROUND CONDUIT TO MAINTAIN 2-HOUR FIRE RATING USING UL LISTED METHODS AND MATERIALS. EXTERIOR WALLS SHALL BE SEALED WATERTIGHT.

6. CONTRACTOR SHALL UPDATE EXISTING PANELBOARD CIRCUIT DIRECTORIES TO REFLECT ALL CHANGES MADE TO EXISTING PANELBOARDS DURING THIS PROJECT.

7. WHEN INSTALLING CIRCUIT BREAKERS IN EXISTING PANELBOARDS, MATCH EXISTING CIRCUIT BREAKER TYPES AND INTERRUPTING RATINGS.

8. COORDINATE INSTALLATION WITH THE WORK OF OTHER TRADES THAT AFFECT THE PLACEMENT OF CEILING MOUNTED EQUIPMENT.

9. THIS CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING EXISTING DIVISION 26 RELATED ITEMS TO REMAIN IN PLACE WITH THE INSTALLATION OF GENERAL CONSTRUCTION WORK, DUCTWORK, PIPING, ETC. ALL ATTEMPTS SHALL BE MADE PRIOR TO THE START OF CONSTRUCTION TO AVOID THE REMOVAL AND RELOCATION OF EXISTING DIVISION 26 RELATED ITEMS WHICH ARE NOT AFFECTED BY WORK OF THIS CONTRACT.

10. CONTRACTOR SHALL PROVIDE A SET OF HAND MARKED RECORD DRAWINGS TO THE ENGINEER AT THE COMPLETION OF THE PROJECT INDICATING ACTUAL INSTALLED CONDITIONS. THE HAND MARKING SHALL BE CLEARLY LEGIBLE AND SHALL BE MARKED IN RED. MARKS SHALL INCLUDE ITEMS SUCH AS CIRCUITING CHANGES, DEVICE AND EQUIPMENT LOCATION CHANGES, MAJOR FEEDER AND CABLING ROUTING CHANGES, ETC.

11. CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATION OF ALL DEVICE LOCATIONS (RECEPTACLES, VOICE/DATA OUTLETS, SWITCHES, ETC.) WITH ARCHITECTURAL ELEVATIONS AND FURNITURE SUBMITTALS PRIOR TO ROUGH-IN TO ENSURE THAT DEVICES ARE NOT LOCATED BEHIND CABINETS OR FURNITURE. FAILURE TO COORDINATE SHALL NOT RESULT IN ADDITIONAL COST TO THE PROJECT, AND THE DEVICE(S) SHALL BE RELOCATED AT THE CONTRACTORS EXPENSE.

12. ALL NEW AND RELOCATED LIGHT FIXTURES SHALL BE POSITIVELY ATTACHED TO THE BUILDING STRUCTURE WITH TWO (2) #12 GAUGE SUPPORT WIRES PER FIXTURE. THE WIRE AND ATTACHMENTS SHALL BE CAPABLE OF SUPPORTING THE FULL WEIGHT OF THE FIXTURE. PROVIDE ALL NECESSARY COMPONENTS AND MOUNTING HARDWARE FOR A COMPLETE INSTALLATION PER DETAIL 3/E501.

13. PROVIDE A MINIMUM OF 6 INCHES OF HORIZONTAL OFFSET BETWEEN RECEPTACLES ON OPPOSITE SIDES OF THE SAME WALL TO MINIMIZE SOUND TRANSMISSION THROUGH WALLS. DO NOT INSTALL RECEPTACLES ON OPPOSITE SIDES OF THE SAME WALL "BACK-TO-BACK".

14. PROVIDE #10 CONDUCTORS FOR ALL 120V, 20A CIRCUITS EXCEEDING 75'-0" IN LENGTH. PROVIDE #8 CONDUCTORS FOR ALL 120V, 20A CIRCUITS EXCEEDING 150'-0" IN LENGTH. MINIMUM CONDUIT SIZE IS 3/4".

15. ALL RECEPTACLES SHALL BE TAMPER RESISTANT TYPE.

16. PROVIDE FIRE CAULKING AT ALL RECESSED ELECTRICAL DEVICES INSTALLED IN FIRE RATED ASSEMBLIES. SEE ARCHITECTURAL DRAWINGS FOR LOCATION OF FIRE RATED ASSEMBLIES.

17. EMERGENCY BATTERIES FOR LIGHT FIXTURES SHALL BE CONNECTED TO UNSWITCHED LIGHTING CIRCUITS. MODIFY AND EXTEND EXISTING CIRCUITS AS NECESSARY.

18. REFER TO DRAWING E5.1 FOR OCCUPANCY SENSOR WIRING DIAGRAMS.

19. EXIT LIGHTS AND EMERGENCY BATTERIES SHALL BE CONNECTED TO UNSWITCHED LEG OF CIRCUIT INDICATED.

20. ELECTRICAL EQUIPMENT SHALL BE MOUNTED TO AVOID THE IMPEDANCE OF OPERATION AND/OR ACCESS TO ELECTRICAL AND MECHANICAL EQUIPMENT. ALL MOUNTING OF ELECTRICAL GEAR ON EQUIPMENT SUPPLIED BY ANOTHER CONTRACTOR SHALL BE APPROVED IN ADVANCE BY THE OTHER CONTRACTOR.

KEYED NOTES

EXTEND EXISTING RECEPTACLE CIRCUIT TO NEW RECEPTACLE. MOUNT NEW RECEPTACLE ADJACENT TO DATA CABLING ACCESS HOLE.

EXTEND EXISTING SURFACE RACEWAY AND WIRING OVER NEW DOOR AND CONNECT TO NEW MECHANICAL UNIT UH-1.

MOUNT NEW DUAL CHANNEL RACEWAY AT HEIGHT(S) REQUIRED TO BE BELOW WINDOWS ON EAST WALL AND ABOVE COUNTER TOP ON SOUTH WALL. CONNECT (2) 20A, 120V SALVAGED CIRCUITS TO RECEPTACLES INSTALLED IN RACEWAY AS INDICATED BY CIRCUITS "1" AND "2". ONE CHANNEL OF RACEWAY SHALL BE USED FOR POWER AND THE OTHER FOR DATA - SEE TECHNOLOGY DRAWINGS.

CONTINUE DUAL CHANNEL RACEWAY VERTICALLY TO ABOVE ACCESSIBLE CEILING AND TRANSITION TO EMT CONDUIT. MODIFY ACT CEILING AS REQUIRED.

CLOSE OPEN KNOCKOUTS IN EXISTING JUNCTION BOX.

1

2

3

5

4

A100A

A1

00B

A1

00

C

PrincipalA106

WORK ROOMA108

Main OfficeA101

(E)

(E)(E)

(E)

(E)

(E)

1 (EC)

1D-NG

(E)

(E)

(E)

(EC)

2

3

5

(E)

ASST.

PRINCIPALA107

EX. STORA102

EX. STOR.A104

EX. TA103

VESTIBULEA100

Exisitng

CorridorA105

1

1 2

2

2

4

3

Sheet Number

Sheet Name

Area Plan

Project Phase

Project Number

Issue Date

in • cite v. to provoke thought

Architect

INCITE DESIGN STUDIO1800 LAFAYETTE AVE., SUITE B, ST. LOUIS, MO 63104314.279.4500

Mech., Plumb., Elec., Telecom.

BRiC PARTNERSHIP, LLC3636 SOUTH GEYER ROAD, SUITE 305ST. LOUIS, MO 63127PHONE: 314-725-5889

Construction Manager

NAVIGATE

PHONE:

Revision No. Description Date Issued

KSD PROJECT # NGL-2021-SECURED VESTIBULE

4/7

/2021 9

:29:0

3 A

M

C:\

Users

\mattj\D

ocum

ents

\2338-0

2_M

EP

_C

entr

al_

v20_m

jaenkeP

ES

NW

.rvt

Floor Plan - New Work - Power

NORTH GLENDALEELEMENTARYSCHOOL SECUREVESTIBULERENOVATIONPROJECT

04/08/2021

20-203

BID DOCUMENTS

E2.1

765 N. SAPPINGTON ROADGLENDALE, MO 63122

SCALE: 1/4" = 1'-0"E2.1

FLOOR PLAN - NEW WORK - POWER1

BRiC MO CERTIFICATE OF

AUTHORITY 2002028690

ENGINEER OF RECORD:

MO. LICENSE NO. 016688

EXP:12/31/22

CARL V. HAUCK

Page 13: Architect NORTH GLENDALE ELEMENTARY SCHOOL...FOC FOF FOM FOS FOW FP FPM FR FR FS FS FSD FT FT FTG FUT FVC FWC G G GA GAL GALV GB GC GCO GCMU GD GEN GEN GFA GFI GFRC GI GLAM GL GMU

PP

KEYED NOTES

INSTALL NEW OCCUPANCY SENSOR SWITCH IN EXISTING ROUGH-IN.

UTLIZE SURFACE BOX AND RACEWAY TO INSTALL NEW OCCUPANCY SENSOR SWITCH.

CONNECT OCCUPANCY SENSOR POWER PACK TO EXISTING LIGHTING CIRCUIT IN THIS ROOM.

CONNECT NEW EXIT SIGN TO EXISTING UNSWITCHED LIGHTING CIRCUIT.

1

2

3

4

PrincipalA106

WORK ROOMA108

Main OfficeA101

(E)-(EC)-b

(E)-(EC)-b (E)-(EC)-b

(E)

(E) (E)

(E)-(EC)-a(E)-(EC)-a

(E)-(EC)-a (E)-(EC)-a(E)

(E)

(E) (E) (E)

(E)

(E)

(E)

(E)(E)

1

2

1PUa

Mb

Mb

(EC)PU

3

1D-NG

VESTIBULEA100

EX. TA103

EX. STORA102

EX. STOR.A104

ASST.

PRINCIPALA107

CORRIDORA105

4-(EC)X

GENERAL NOTES

1. ALL WORK SHALL BE IN ACCORDANCE WITH THE 2005 NATIONAL ELECTRICAL CODE.

2. ALL PANELS SHOWN ARE EXISTING TO REMAIN UNLESS NOTED OTHERWISE.

3. THE ELECTRICAL DRAWINGS HAVE BEEN PREPARED UTILIZING EXISTING DRAWINGS AND BUILDING OBSERVATIONS AND MAY NOT SHOW ALL CONDITIONS. CONTRACTOR SHALL VISIT THE BUILDING PRIOR TO BID SUBMISSION AND BECOME FAMILIAR WITH ALL EXISTING CONDITIONS. CONTRACTOR WILL NOT BE ALLOWED ADDITIONAL FUNDS OR TIME DUE TO THE CONTRACTOR'S FAILURE TO BECOME FAMILIAR WITH ALL EXISTING CONDITIONS. ACCEPTANCE OF CONTRACT MEANS INSTALLER ACCEPTS EXISTING CONDITIONS.

4. CONTRACTOR SHALL SCHEDULE ALL ELECTRICAL SYSTEM POWER OUTAGES WITH THE OWNER'S REPRESENTATIVE AT LEAST 7 CALENDAR DAYS IN ADVANCE OF A SHUTDOWN. DOWNTIME ON BRANCH CIRCUIT PANELBOARDS, SWITCHBOARDS, DISTRIBUTION PANELBOARDS, MOTOR CONTROL CENTERS, ETC., WHICH SERVE LOADS OUTSIDE OF THE CONSTRUCTION AREAS SHALL BE LIMITED TO A (1) HOUR (MAXIMUM) OUTAGE. MORE THAN (1) SCHEDULED OUTAGE MAY OCCUR ON EACH PIECE OF EQUIPMENT, BUT THE MAXIMUM OUTAGE TIME MUST BE MAINTAINED.

5. ALL PENETRATIONS THROUGH CONCRETE OR MASONRY WALLS AND FLOOR SLABS SHALL BE CORE DRILLED. AFTER CONDUITS HAVE BEEN INSTALLED, SEAL WALL AROUND CONDUIT TO MAINTAIN 2-HOUR FIRE RATING USING UL LISTED METHODS AND MATERIALS. EXTERIOR WALLS SHALL BE SEALED WATERTIGHT.

6. CONTRACTOR SHALL UPDATE EXISTING PANELBOARD CIRCUIT DIRECTORIES TO REFLECT ALL CHANGES MADE TO EXISTING PANELBOARDS DURING THIS PROJECT.

7. WHEN INSTALLING CIRCUIT BREAKERS IN EXISTING PANELBOARDS, MATCH EXISTING CIRCUIT BREAKER TYPES AND INTERRUPTING RATINGS.

8. COORDINATE INSTALLATION WITH THE WORK OF OTHER TRADES THAT AFFECT THE PLACEMENT OF CEILING MOUNTED EQUIPMENT.

9. THIS CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING EXISTING DIVISION 26 RELATED ITEMS TO REMAIN IN PLACE WITH THE INSTALLATION OF GENERAL CONSTRUCTION WORK, DUCTWORK, PIPING, ETC. ALL ATTEMPTS SHALL BE MADE PRIOR TO THE START OF CONSTRUCTION TO AVOID THE REMOVAL AND RELOCATION OF EXISTING DIVISION 26 RELATED ITEMS WHICH ARE NOT AFFECTED BY WORK OF THIS CONTRACT.

10. CONTRACTOR SHALL PROVIDE A SET OF HAND MARKED RECORD DRAWINGS TO THE ENGINEER AT THE COMPLETION OF THE PROJECT INDICATING ACTUAL INSTALLED CONDITIONS. THE HAND MARKING SHALL BE CLEARLY LEGIBLE AND SHALL BE MARKED IN RED. MARKS SHALL INCLUDE ITEMS SUCH AS CIRCUITING CHANGES, DEVICE AND EQUIPMENT LOCATION CHANGES, MAJOR FEEDER AND CABLING ROUTING CHANGES, ETC.

11. CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATION OF ALL DEVICE LOCATIONS (RECEPTACLES, VOICE/DATA OUTLETS, SWITCHES, ETC.) WITH ARCHITECTURAL ELEVATIONS AND FURNITURE SUBMITTALS PRIOR TO ROUGH-IN TO ENSURE THAT DEVICES ARE NOT LOCATED BEHIND CABINETS OR FURNITURE. FAILURE TO COORDINATE SHALL NOT RESULT IN ADDITIONAL COST TO THE PROJECT, AND THE DEVICE(S) SHALL BE RELOCATED AT THE CONTRACTORS EXPENSE.

12. ALL NEW AND RELOCATED LIGHT FIXTURES SHALL BE POSITIVELY ATTACHED TO THE BUILDING STRUCTURE WITH TWO (2) #12 GAUGE SUPPORT WIRES PER FIXTURE. THE WIRE AND ATTACHMENTS SHALL BE CAPABLE OF SUPPORTING THE FULL WEIGHT OF THE FIXTURE. PROVIDE ALL NECESSARY COMPONENTS AND MOUNTING HARDWARE FOR A COMPLETE INSTALLATION PER DETAIL 3/E501.

13. PROVIDE A MINIMUM OF 6 INCHES OF HORIZONTAL OFFSET BETWEEN RECEPTACLES ON OPPOSITE SIDES OF THE SAME WALL TO MINIMIZE SOUND TRANSMISSION THROUGH WALLS. DO NOT INSTALL RECEPTACLES ON OPPOSITE SIDES OF THE SAME WALL "BACK-TO-BACK".

14. PROVIDE #10 CONDUCTORS FOR ALL 120V, 20A CIRCUITS EXCEEDING 75'-0" IN LENGTH. PROVIDE #8 CONDUCTORS FOR ALL 120V, 20A CIRCUITS EXCEEDING 150'-0" IN LENGTH. MINIMUM CONDUIT SIZE IS 3/4".

15. ALL RECEPTACLES SHALL BE TAMPER RESISTANT TYPE.

16. PROVIDE FIRE CAULKING AT ALL RECESSED ELECTRICAL DEVICES INSTALLED IN FIRE RATED ASSEMBLIES. SEE ARCHITECTURAL DRAWINGS FOR LOCATION OF FIRE RATED ASSEMBLIES.

17. EMERGENCY BATTERIES FOR LIGHT FIXTURES SHALL BE CONNECTED TO UNSWITCHED LIGHTING CIRCUITS. MODIFY AND EXTEND EXISTING CIRCUITS AS NECESSARY.

18. REFER TO DRAWING E5.1 FOR OCCUPANCY SENSOR WIRING DIAGRAMS.

19. EXIT LIGHTS AND EMERGENCY BATTERIES SHALL BE CONNECTED TO UNSWITCHED LEG OF CIRCUIT INDICATED.

20. ELECTRICAL EQUIPMENT SHALL BE MOUNTED TO AVOID THE IMPEDANCE OF OPERATION AND/OR ACCESS TO ELECTRICAL AND MECHANICAL EQUIPMENT. ALL MOUNTING OF ELECTRICAL GEAR ON EQUIPMENT SUPPLIED BY ANOTHER CONTRACTOR SHALL BE APPROVED IN ADVANCE BY THE OTHER CONTRACTOR.

Sheet Number

Sheet Name

Area Plan

Project Phase

Project Number

Issue Date

in • cite v. to provoke thought

Architect

INCITE DESIGN STUDIO1800 LAFAYETTE AVE., SUITE B, ST. LOUIS, MO 63104314.279.4500

Mech., Plumb., Elec., Telecom.

BRiC PARTNERSHIP, LLC3636 SOUTH GEYER ROAD, SUITE 305ST. LOUIS, MO 63127PHONE: 314-725-5889

Construction Manager

NAVIGATE

PHONE:

Revision No. Description Date Issued

KSD PROJECT # NGL-2021-SECURED VESTIBULE

4/7

/2021 9

:29:0

3 A

M

C:\

Users

\mattj\D

ocum

ents

\2338-0

2_M

EP

_C

entr

al_

v20_m

jaenkeP

ES

NW

.rvt

Reflected Ceiling Plan - NewWork - Lighting

NORTH GLENDALEELEMENTARYSCHOOL SECUREVESTIBULERENOVATIONPROJECT

04/08/2021

20-203

BID DOCUMENTS

E3.1

765 N. SAPPINGTON ROADGLENDALE, MO 63122

SCALE: 1/4" = 1'-0"E3.1

REFLECTED CEILING PLAN - NEW WORK - LIGHTING1

BRiC MO CERTIFICATE OF

AUTHORITY 2002028690

ENGINEER OF RECORD:

MO. LICENSE NO. 016688

EXP:12/31/22

CARL V. HAUCK

Page 14: Architect NORTH GLENDALE ELEMENTARY SCHOOL...FOC FOF FOM FOS FOW FP FPM FR FR FS FS FSD FT FT FTG FUT FVC FWC G G GA GAL GALV GB GC GCO GCMU GD GEN GEN GFA GFI GFRC GI GLAM GL GMU

NEUTRAL

LINE

GREEN

BLACK

GROUND

GROUND

RED

LIGHTINGLOAD

GREEN

NEUTRAL

YELLOW

NEUTRAL

LINE

LIGHTINGLOAD

PARALLEL WIRE MULTIPLE SENSORS WHERE REQUIRED

WHITE

BLACK

RED

YELLOW

COMMON

+24V IN

CONTROL

BLACK

WHITE

RED

RED

BLU

E

RE

D

BLA

CK

GR

EY

OR

AN

GE

BR

OW

N

PARALLEL WIRE MULTIPLE POWER PACKS WHERE REQUIRED

MARK MANUFACTURERS INFORMATION LAMP INFO LED LUMENOUTPUT

COLORTEMPERATURE

WATTAGE PERFIXTURE

VOLTAGE FIXTURECONTROL

MANUFACTURER MODEL DRIVER LAMP MOUNTING / CEILING INFO COMMENTS

DESCRIPTION

NOTES:

1. CONTRACTOR IS RESPONSIBLE FOR ALL MISCELLANEOUS HARDWARE, CLIPS, ANGLES, FRAMES, ETC. AS REQUIRED TO MOUNT THE FIXTURES IN OR ON THE SURFACES THEY ARE TO BE INSTALLED.

2. REFER TO ARCHITECTURAL DOCUMENTS FOR EXACT MOUNTING LOCATIONS OF LIGHT FIXTURES.

3. WHEN INSTALLING LUMINAIRES, THE CONTRACTOR SHALL USE THE MANUFACTURER'S MOUNTING HARDWARE AND FOLLOW ALL MANUFACTURER'S INSTALLATION INSTRUCTIONS.

4. ALL LIGHT FIXTURES SHALL HAVE A U.L. LABEL.

5. REFER TO DIVISION 26 SPECIFICATIONS FOR ADDITIONAL INFORMATION CONCERNING FIXTURES, FINISHES, DRIVERS, ETC.

6. VERIFY CEILING CONDITIONS AND COORDINATE LIGHT FIXTURE MOUNTING HARDWARE AND TRIMS NEEDED PRIOR TO ORDERING.

7. VERIFY QUANTITIES, MODEL NUMBERS AND DESCRIPTIONS WITH MANUFACTURER PRIOR TO PLACING ORDER.

8. CATALOG NUMBERS SHALL NOT BE CONSIDERED COMPLETE AND MATERIAL SHALL NOT BE ORDERED BY MANUFACTURER AND CATALOG NUMBERS ONLY. CONTRACTOR SHALL CONSIDER THE COMPLETE DESCRIPTION, NOTES, SPECIFICATIONS, MOUNTING AND INSTALLATION CONDITIONS IN CONJUNCTION WITH THE CATALOG NUMBER TO DETERMINE THE EXACT MATERIAL AND ACCESSORIES TO BE ORDERED. THE MANUFACTURERS LISTED ARE THE BASIS FOR DESIGN.

9. CONTRACTOR SHALL PROVIDE ALL LIGHT FIXTURES UNLESS NOTED OTHERWISE.

10. EMERGENCY BATTERIES FOR LIGHT FIXTURES SHALL BE CONNECTED TO THE UNSWITCHED LIGHTING CIRCUIT IN THE SAME ROOM/AREA.

11. IN LIEU OF THE LIGHT FIXTURE OPTIONS LISTED IN THE SCHEDULE, CONTRACTOR MAY SUBMIT EQUAL FIXTURES FOR REVIEW AND APPROVAL BY ENGINEER

LIGHT FIXTURE SCHEDULE

X LITHONIA LIGHTING LE-S-W-(#FACES)-R-EL-N-SD LED

EXIT/CA-R-WF-WHT-EM-SDT-D

N/A PROVIDE NUMBER OF FACES AS INDICATED ON DRAWINGS.N/ALED EXIT SIGN

H.E. WILLIAMS INC.

MULE LIGHTING

UNV

UNV

UNVMD-B-(#FACES)-R-WW-SD

N/A N/A 1 VA

3 VA

5 VA

CEILING / SURFACE

Sheet Number

Sheet Name

Area Plan

Project Phase

Project Number

Issue Date

in • cite v. to provoke thought

Architect

INCITE DESIGN STUDIO1800 LAFAYETTE AVE., SUITE B, ST. LOUIS, MO 63104314.279.4500

Mech., Plumb., Elec., Telecom.

BRiC PARTNERSHIP, LLC3636 SOUTH GEYER ROAD, SUITE 305ST. LOUIS, MO 63127PHONE: 314-725-5889

Construction Manager

NAVIGATE

PHONE:

Revision No. Description Date Issued

KSD PROJECT # NGL-2021-SECURED VESTIBULE

4/7

/2021 9

:29:0

3 A

M

C:\

Users

\mattj\D

ocum

ents

\2338-0

2_M

EP

_C

entr

al_

v20_m

jaenkeP

ES

NW

.rvt

Electrical Details and LightFixture Schedule

NORTH GLENDALEELEMENTARYSCHOOL SECUREVESTIBULERENOVATIONPROJECT

04/08/2021

20-203

BID DOCUMENTS

E5.1

765 N. SAPPINGTON ROADGLENDALE, MO 63122

NTSE5.1

OCCUPANCY SENSOR WIRING DIAGRAM1

NTSE5.1

OCCUPANCY SENSOR, WALL SWITCH, AND POWER PACK WIRING DIAGRAM2

ROOM A107

ROOM A101

BRiC MO CERTIFICATE OF

AUTHORITY 2002028690

ENGINEER OF RECORD:

MO. LICENSE NO. 016688

EXP:12/31/22

CARL V. HAUCK

Page 15: Architect NORTH GLENDALE ELEMENTARY SCHOOL...FOC FOF FOM FOS FOW FP FPM FR FR FS FS FSD FT FT FTG FUT FVC FWC G G GA GAL GALV GB GC GCO GCMU GD GEN GEN GFA GFI GFRC GI GLAM GL GMU

COMMUNICATION SYMBOLS:FIRE ALARM SYMBOLS:

SECURITY SYMBOLS:

4

T301

OTHER:

COMMUNICATION GENERAL NOTES:

PUBLIC ADDRESS OR INTERCOM SYMBOLS:

COMMUNICATION OUTLET. REFER TO SPECIFICATIONS AND COMMUNICATION DETAIL SHEETS FOR ADDITIONAL REQUIREMENTS. REFER TO COMMUNICATION OUTLET IDENTIFIERS AND CABLING IDENTIFICATION LISTED BELOW.

FIRE ALARM MANUAL PULL STATION: MOUNT 48" A.F.F. TO CENTER LINE OF OPERABLE LEVER.

FIRE ALARM STROBE: WHEN WALL MOUNTED, MOUNT WITH BOTTOM OF STROBE LENS AT THE LOWER OF 80" A.F.F OR 6" BELOW CEILING. NUMERAL WHEN USED INDICATES CANDELA RATING OF MORE THAN 15.

DETAIL REFERENCE. "4" INDICATES DETAIL # "T301" INDICATES SHEET.REFER TO DETAIL FOR ADDITIONAL REQUIREMENTS.

SHEET KEYED NOTE "1" INDICATES NOTE #.1

F

F

75

FIRE ALARM COMBINATION HORN WITH STROBE: WHEN WALL MOUNTED, MOUNT WITH BOTTOM OF STROBE LENS AT THE LOWER OF 80" A.F.F OR 6" BELOW CEILING. NUMERAL WHEN USED INDICATES CANDELA RATING OF MORE THAN 15.

F

75

HEAT DETECTOR (FIXED TEMPERATURE). TEMPERATURE RATING TO BE COORDINATED WITH ENVIRONMENT IN WHICH IT'S INSTALLED

FHF

SMOKE DETECTOR: PHOTO-ELECTRIC TYPE.F

SD

SPRINKLER SYSTEM WATER FLOW SWITCH.F

WF

SPRINKLER SYSTEM TAMPER (SUPERVISORY) SWITCH.F

TS

SPRINKLER SYSTEM ELECTRICAL SOLENOID VALVE.F

ESV

DUCT MOUNTED SMOKE DETECTOR: PHOTO-ELECTRIC TYPE.FDD

EXTINGUISHING SYSTEM PRESSURE SWITCH.F

PR

SMOKE DAMPER OR FIRE/SMOKE DAMPER. REFER TO MECHANICAL FOR ADDITIONAL INFORMATION.

FSMD

FIRE ALARM ELECTROMAGNETIC DOOR HOLDER.F

DH

ADDRESSABLE CONTROL RELAY.F

ACR

ADDRESSABLE MONITOR MODULE.F

AMM

DUCT MOUNTED SMOKE DETECTOR KEY ACTIVATED REMOTE TEST STATION. MOUNT 48" A.F.F. TO CENTER OF DEVICE. PROVIDE LABEL ON REMOTE TEST STATION COVER WHICH IDENTIFIES RELATED AHU DESIGNATION AND RELATED DUCT MOUNTED SMOKE DETECTOR ADDRESS.

F

RTS

FAAP FIRE ALARM ANNUNCIATOR PANEL

FACP FIRE ALARM CONTROL PANEL

FAPS FIRE ALARM POWER SUPPLY

LED DEVICE LOCATION INDICATING LIGHT.F

LED

CARD READER: DEVICE SHALL BE MOUNTED AT APPROXIMATELY 48" A.F.F. TO CENTER OF DEVICE.

S

CR

DOOR POSITION SWITCH/CONTACTS.S

PS

DOOR LOCKING MECHANISM - ELECTRONIC WITH INTEGRATED DOOR CONTACT/POSITION SWITCH.

S

L

REQUEST TO EXIT DEVICE.RXB = WALL MOUNT PUSH BUTTONRXM = WALL MOUNT MOTION SENSOR ABOVE DOOR

S

RXM

ACCESS CONTROL SYSTEM

A. PROVIDE ALL REQUIRED PROGRAMMING OF THE ACCESS CONTROL SYSTEM. COORDINATE WITH OWNER FOR SCHEDULE AND OPERATION OF EACH DOOR AND DEVELOPMENT OF ACCESS LEVELS.

B. COORDINATE SHUNT TIMES FOR ALL SECURED DOORS WITH THE OWNER.C. COORDINATE CONDUIT AND BOX ROUGH-IN LOCATIONS WITH THE DOOR

HARDWARE INSTALLER PRIOR TO THE START OF CONSTRUCTION. REFER TO COMMUNICATION DETAIL SHEETS.

D. ACCESS CONTROL SYSTEM DOOR DEVICES INCLUDING BUT NOT LIMITED TO LOCKING MECHANISM, POWER TRANSFER HINGES, CRASH BARS AND DOOR POSITION/CONTACTS SHALL BE FURNISHED BY THE DOOR HARDWARE SUPPLIER. THEY SHALL BE INSTALLED AND WIRED BY THE SECURITY SYSTEM CONTRACTOR UNLESS NOTED OTHERWISE.

E. DOOR LOCK POWER SUPPLIES WITH BATTERY BACKUP SHALL BE FURNISHED, INSTALLED, SIZED AND WIRED BY SECURITY SYSTEM CONTRACTOR. IT IS THE SECURITY SYSTEM CONTRACTORS RESPONSIBILITY TO COORDINATE ELECTRICAL LOAD AND WIRING REQUIREMENTS FOR LOCKING MECHANISM. POWER SUPPLIES SHALL BE LOCATED IN THE COMMUNICATION ROOMS UNLESS NOTED OTHERWISE.

F. ACCESS CONTROL SYSTEM CABLE SIZES, TYPE AND QUANTITIES ARE SHOWN FOR REFERENCE AND BIDDING PURPOSES. THE SECURITY SYSTEM CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING CABLING SUITABLE FOR USE WITH THE DEVICES SPECIFIED WITHIN THIS PROJECT.

G. SECURITY SYSTEM CONTRACTOR SHALL COORDINATE EXACT REQUIREMENTS WITH ARCHITECTURAL DOOR HARDWARE, SCHEDULE, DOOR CONTRACTOR AND SUPPLIER PRIOR TO PURCHASE AND INSTALLATION.

H. POWER SUPPLIES AND DOOR INTERFACE BOXES MAY NOT BE SHOWN ON FLOOR PLANS, HOWEVER, ARE REQUIRED FOR A COMPLETE AND OPERABLE ACCESS CONTROL SYSTEM.

SECURITY GENERAL NOTES:

INTRUSION DETECTION MOTION SENSOR.S

M

LOCKDOWN PUSH BUTTONS

LPB

INTERCOM MASTER STATION WITH REMOTE DOOR RELEASES

ICM

AUDIO/VIDEO INTERCOM STATIONS

IC

VIDEO SURVEILLANCE CAMERA

EXISTING OR DEMOLITION COMMUNICATION OUTLET

NEW COMMUNICATION OUTLET

EXISTING OR DEMOLITION WIRELESS ACCESS POINT OUTLET

NEW WIRELESS ACCESS POINT OUTLET

COMMUNICATION OUTLET IDENTIFIER. REFER TO COMMUNICATION OUTLET DESIGNATION DETAIL FOR MOUNTING HEIGHTS. "X" DENOTES ONE OF THE FOLLOWING:

X

= MOUNTED AT CEILING= MOUNTED AT COUNTER ABOVE BACKSPLASH ELEMENT= MOUNTED IN FLOOR BOX OR POKE THROUGH DEVICE= MOUNTED IN SURFACE MOUNT RACEWAY= WALL MOUNT PHONE LOCATION= WIRELESS ACCESS POINT MOUNTED AT OR ABOVE CEILING

ACFRWWAP

COMMUNICATION CABLING IDENTIFICATION. REFER TO CABLING DESIGNATION SCHEME DETAIL.

# X

= DENOTES TOTAL NUMBER OF CABLES= DENOTES ONE OF THE FOLLOWING:

"#""X"

= COAXIAL CABLE= DATA COMMUNICATION CABLE= FIBER OPTIC CABLE= VOICE COMMUNICATION CABLE= AUDIO/VIDEO CABLE

PAGING/INTERCOM SPEAKER: CEILING MOUNT 2x2 CEILING TILE

P

PAGING/INTERCOM SPEAKER: CEILING MOUNT DRYWALL CEILING

PAGING/INTERCOM SPEAKER: WALL MOUNT. SPEAKER SHALL BE MOUNTED AT APPROXIMATELY 8'-0" A.F.F. UNLESS NOTED OTHERWISE.

PAGING/INTERCOM HORN: WALL MOUNT. HORN SHALL BE MOUNTED AT APPROXIMATELY 10'-0" A.F.F. UNLESS NOTED OTHERWISE.

CLOCK: SINGLE SIDED, WALL MOUNT

PAGING/INTERCOM PUSHBUTTON: DEVICE SHALL BE MOUNTED AT APPROXIMATELY 42" A.F.F. TO BUTTON LOCATION UNLESS NOTED OTHERWISE

CDFVAV

A. ALL SYMBOLS SHOWN ARE NOT NECESSARILY USED ON THIS PROJECT.B. THE DRAWINGS HAVE BEEN PREPARED UTILIZING EXISTING DRAWINGS

AND BUILDING OBSERVATIONS AND MAY NOT SHOW ALL CONDITIONS. CONTRACTOR SHALL VISIT THE BUILDING AND SITE PRIOR TO BID SUBMISSION AND BECOME FAMILIAR WITH ALL EXISTING CONDITIONS. CONTRACTORS SHALL NOT BE ALLOWED ADDITIONAL FUNDS OR TIME DUE TO FAILURE TO BECOME FAMILIAR WITH ALL EXISTING CONDITIONS.

C. ACCEPTANCE OF CONTRACT MEANS INSTALLER ACCEPTS EXISTING CONDITIONS.

D. COORDINATE INSTALLATION WITH EXISTING CONDITIONS. FIELD VERIFY EXISTING CONDITIONS.

E. CONTRACTOR SHALL SCHEDULE ALL OUTAGES WITH THE OWNER’S REPRESENTATIVE AT LEAST 14 CALENDAR DAYS IN ADVANCE OF A SHUTDOWN.

F. ALL PENETRATIONS THROUGH CONCRETE OR MASONRY WALLS AND FLOOR SLABS SHALL BE CORE DRILLED. AFTER CONDUITS HAVE BEEN INSTALLED, SEAL WALL AROUND CONDUIT TO MAINTAIN FIRE RATING OF FLOOR OR WALL USING UL LISTED METHODS AND MATERIALS. EXTERIOR WALLS SHALL BE SEALED WATER TIGHT.

G. PROVIDE EMT SLEEVES WITH INSULATED BUSHINGS ON EACH END FOR ALL CABLES PASSING THROUGH WALLS AND FLOORS. ALL PENETRATIONS THROUGH RATED WALLS AND FLOORS SHALL BE FIRE STOPPED. SEAL AROUND OUTSIDE OF CONDUITS AND SEAL INSIDE OF CONDUIT SLEEVES OR UTILIZE AN APPROVED FIRE RATED ASSEMBLY.

H. CABLING TO BE LOCATED INSIDE BUILDINGS SHALL BE CONCEALED WHERE POSSIBLE AND SHALL BE INSTALLED AS FOLLOWS: CABLES CONCEALED INSIDE HOLLOW WALL CONSTRUCTION SHALL BE INSTALLED IN CONDUITS STUBBED INTO ACCESSIBLE PORTION OF CEILING CAVITY AND SHALL BE SUPPORTED UTILIZING J-HOOK PATHWAYS. CABLES LOCATED IN ROOMS WITH AN EXPOSED CEILING STRUCTURE SHALL BE INSTALLED IN CONDUIT. CABLES INSTALLED ABOVE DRYWALL CEILINGS SHALL BE INSTALLED IN CONDUIT. CABLES INSTALLED IN SOLID MASONRY WALLS SHALL BE INSTALLED IN SURFACE RACEWAY. ROUTE CONDUIT AND CABLES TO SUIT FIELD CONDITIONS. REFER TO PLANS AND SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.

I. CONTRACTOR SHALL COORDINATE ALL CONDUIT AND CABLE ROUTING WITH EXISTING CONDITIONS PRIOR TO INSTALLATION.

J. CONTRACTOR SHALL TERMINATE AND TEST ALL COMMUNICATION SYSTEM CABLES PER SPECIFICATIONS AND LATEST TIA/EIA STANDARDS.

K. COMMUNICATION CABLING SHALL NOT EXCEED 90 METERS (295 FEET) PER TIA/EIA STANDARDS.

L. CONTRACTOR SHALL LABEL ALL CABLES AND CONNECTORS (OUTLETS, PATCH PANELS, FACEPLATES, PUNCH DOWN BLOCKS, ETC.) PER SPECIFICATIONS AND OWNER STANDARDS. ALL CABLES SHALL BE PERMANENTLY LABELED WITH A PRE-PRINTED, STICK ON, SELF ADHERING LABELING SYSTEM. REFER TO SPECIFICATIONS.

M. PROVIDE WORK SPECIFIED BUT NOT SHOWN ON DRAWINGS AND PROVIDE WORK SHOWN ON DRAWINGS BUT NOT SPECIFIED AS THOUGH EXPRESSLY REQUIRED BY BOTH.

N. CONTRACTOR SHALL REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR PLACEMENT OF CEILING MOUNTED EQUIPMENT. COORDINATE WITH ALL OTHER TRADES.

O. CONTRACTOR SHALL PROVIDE PULL STRINGS IN ALL EMPTY OR SPARE CONDUIT.

P. COMMUNICATION EQUIPMENT, COMPONENTS AND CABLING SHALL BE FREE FROM PAINT AND PAINT OVERSPRAY UNLESS NOTED OTHERWISE.

Q. COMMUNICATION EQUIPMENT, COMPONENTS AND CABLING SHALL BE FREE FROM CONSTRUCTION DIRT AND DEBRIS.

R. CONTRACTOR SHALL COMPLY WITH HOSPITAL’S INTERIM LIFE SAFETY MEASURES (ILSM).

F

F

F FIRE ALARM HORN: WHEN WALL MOUNTED, MOUNT WITH BOTTOM OF STROBE LENS AT THE LOWER OF 80" A.F.F OR 6" BELOW CEILING. NUMERAL WHEN USED INDICATES CANDELA RATING OF MORE THAN 15.

75

75FIRE ALARM SPEAKER: WHEN WALL MOUNTED, MOUNT WITH BOTTOM OF STROBE LENS AT THE LOWER OF 80" A.F.F OR 6" BELOW CEILING. NUMERAL WHEN USED INDICATES CANDELA RATING OF MORE THAN 15.

FIRE ALARM COMBINATION SPEAKER WITH STROBE: WHEN WALL MOUNTED, MOUNT WITH BOTTOM OF STROBE LENS AT THE LOWER OF 80" A.F.F OR 6" BELOW CEILING. NUMERAL WHEN USED INDICATES CANDELA RATING OF MORE THAN 15.

75

DOOR LOCKING MECHANISM - MAGNETIC LOCK WITH INTEGRATED DOOR CONTACT/POSITION SWITCH..

S

ML

PUSH BUTTON DOOR RELEASE.S

PBR

VIDEO SURVEILLANCE SYSTEM

A. VIDEO FROM SECURITY CAMERA SHALL BE STORED IN A VIDEO MANAGEMENT SYSTEM NETWORK RECORDING SERVER. REFER TO SPECIFICATIONS FOR SERVER REQUIREMENTS. SECURITY SYSTEM CONTRACTOR SHALL CONTACT OWNER FOR RECORDING FRAME RATES, STORAGE DURATION AND MOTION ACTIVATION SETTING REQUIREMENTS. SECURITY SYSTEM CONTRACTOR SHALL CONFIGURE AND PROGRAM VIDEO MANAGEMENT SYSTEM. SERVER LICENSING SHALL BE INCLUDED IN THE BASE BID.

B. SECURITY SYSTEM CONTRACTOR SHALL SCHEDULE AN ON-SITE MEETING WITH OWNER TO REVIEW FINAL CAMERA PLACEMENT AND FIELD OF VIEWS PRIOR TO INSTALLATION.

C. SECURITY SYSTEM CONTRACTOR SHALL OBTAIN ACCESS LAYER SWITCH PORT ASSIGNMENTS AND IP ADDRESSING FOR CAMERAS FROM OWNER AND CONFIGURE SERVER FOR OPERATION ON THE OWNER’S NETWORK.

TECHNOLOGY COMMUNICATION LEGEND AND ABBREVIATIONS (SEE SPECIFICATIONS & SCHEDULES)NOTES: 1. NOT ALL SYMBOLS AND ABBREVIATIONS ARE USED ON THESE PLANS.

2. ALL MOUNTING HEIGHTS ARE TO CENTERLINE OF DEVICES AND EQUIPMENT U.O.N.3. IN GENERAL, SYMBOLS SHOWN WITH LIGHT LINES DENOTE EXISTING WORK. SYMBOLS SHOWN WITH HEAVY LINES DENOTE

PROPOSED WORK.

MULTI-CRITERIA COMBINATION SMOKE/HEAT/CARBON MONOXIDE DETECTORF

MC

CARBON MONOXIDE DETECTOR: PHOTO-ELECTRIC TYPE.F

CO

BURGLAR ALARM KEYPAD.S

KP

INTERCOM CHIMES

CHIME

Sheet Number

Sheet Name

Area Plan

Project Phase

Project Number

Issue Date

in • cite v. to provoke thought

Architect

INCITE DESIGN STUDIO1800 LAFAYETTE AVE., SUITE B, ST. LOUIS, MO 63104314.279.4500

Mech., Plumb., Elec., Telecom.

BRiC PARTNERSHIP, LLC3636 SOUTH GEYER ROAD, SUITE 305ST. LOUIS, MO 63127PHONE: 314-725-5889

Construction Manager

NAVIGATE

PHONE:

Revision No. Description Date Issued

KSD PROJECT # NGL-2021-SECURED VESTIBULE

4/7

/2021 8

:36:0

8 A

M

C:\

Users

\janis

c\D

ocum

ents

\2338-0

2_M

EP

_C

entr

al_

v20_jc

hri

sto

pher7

JR

93.r

vt Legend, Symbols & Notes -

Technology

NORTH GLENDALEELEMENTARYSCHOOL SECUREVESTIBULERENOVATIONPROJECT

04/08/2021

20-203

BID DOCUMENTS

T0.2

765 N. SAPPINGTON ROADGLENDALE, MO 63122

BRiC MO CERTIFICATE OF

AUTHORITY 2002028690

ENGINEER OF RECORD:

MO. LICENSE NO. 016688

EXP:12/31/22

CARL V. HAUCK

Page 16: Architect NORTH GLENDALE ELEMENTARY SCHOOL...FOC FOF FOM FOS FOW FP FPM FR FR FS FS FSD FT FT FTG FUT FVC FWC G G GA GAL GALV GB GC GCO GCMU GD GEN GEN GFA GFI GFRC GI GLAM GL GMU

DN

FS

S

S

S

F

SS

S

J

J

F

F

F

J

J

S

LPB

FACPFAPS

ICM

ETR

1

2

KP

3

4

5

PAGING

6

ETR

ETR

ETR

CHIME7

FAAP

1

ETR

ICCR

L

8

8

9

9

9

9

10

SD

WAPETR

ETR

ETR

SD

WAP

ETR

ETR

11

RXM

ETR

PrincipalA106

WORK ROOMA108

Existing Asst.

PrincipalA115

Exisitng

CorridorA105

EX. TA103

EX. STOR.A104

EXISTING

OFFICEA117

EX. STORA119

ETR

12

GENERAL NOTES

A. ALL DEVICES SHOWN ARE EXISTING TO BE DEMOLISHED UNLESS NOTED OTHERWISE AS EXISTING TO REMAIN (ETR).

B. PLANS ARE DIAGRAMMATIC IN NATURE. THEY REFLECT THE AVAILABLE INFORMATION OBTAINED FROM FIELD OBSERVATION AND EXISTING DOCUMENTATION. ACTUAL LOCATION OF ELEMENTS AND EQUIPMENT MAY DEVIATE FROM THE LOCATION AND QUANTITIES SHOWN.

C. EXISTING CABLING TO REMAIN SHALL BE TEMPORARILY SUPPORTED AND PROTECTED. IF CABLE IS DAMAGED DURING THE CONSTRUCTION PROCESS, CONTRACTOR SHALL REPLACE CABLE WITH NEW PER SPECIFICATIONS.

D. WHILE MOST DEMOLITION WORK IS CONFINED TO CERTAIN AREAS OF THE BUILDING, WORK FOR TECHNOLOGY COMMUNICATION SYSTEMS MAY BE EXTENDED TO INCLUDE OTHER AREAS OUTSIDE THE SCOPE OF WORK. PLAN IN ADVANCE TO PERFORM WORK IN OTHER AREAS TO MINIMIZE INTERRUPTIONS.

E. DEMOLITION REFERS TO THE DISCONNECTION AND REMOVAL OF EQUIPMENT, CABLING AND COMPONENTS BACK TO SOURCE, UNLESS NOTED OTHERWISE.

F. CONTRACTOR SHALL PROVIDE ALL CUTTING AND PATCHING AS REQUIRED FOR EXECUTION OF DEMOLITION WORK AND INSTALLATION OF NEW WORK.

G. COORDINATE THE DISCONNECTION AND REMOVAL OF ALL ITEMS WITH ASSOCIATED TRADES. ENSURE SERVICES THAT ARE REQUIRED TO REMAIN ACTIVE ARE ACTIVE DURING AND AFTER DEMOLITION IS COMPLETED. COORDINATE WITH FLOORS ABOVE AND BELOW FOR THE AVOIDANCE OF INADVERTENT SERVICE DEACTIVATION.

H. CONTRACTOR SHALL VISIT SITE PRIOR TO BID SUBMITTAL TO DETERMINE SITE CONDITIONS AFFECTING THE EXECUTION OF WORK. FAILURE TO BE ACQUAINTED WITH EXISTING CONDITIONS WILL NOT BE JUSTIFICATION FOR ADDITIONAL SERVICES.

KEYED NOTES

FIRE ALARM CONTROL PANEL, ASSOCIATED POWER SUPPLIES AND FIRE ALARM ANNUNCIATOR PANEL ARE EXISTING TO REMAIN.

1

VALCOM CLASS CONNECT PAGING EQUIPMENT CABINET AND ASSOCIATED PAGING PHONE ARE EXISTING TO REMAIN.

2

EXISTING BURGLAR ALARM KEY PAD SHALL BE DISCONNECTED AND REMOVED. MAINTAIN EXISTING CIRCUIT FOR RE-USE. DEVICE SHALL BE RE-INSTALLED IN NEW LOCATION. REFER TO NEW WORK PLAN.

3

DISCONNECT AND REMOVE EXISTING LOCK DOWN PUSH BUTTON. MAINTAIN EXISTING CIRCUIT FOR RE-USE. DEVICE SHALL BE RE-INSTALLED IN NEW LOCATION. REFER TO NEW WORK PLAN.

4

DISCONNECT AND REMOVE EXISTING INTERCOM MASTER STATION. DEVICE SHALL BE RE-INSTALLED IN NEW LOCATION. REFER TO NEW WORK PLAN.

5

EXISTING WALL MOUNT PATCH PANEL AND NETWORK SWITCH ARE EXISTING TO REMAIN. REFER TO NEW WORK PLAN FOR NEW MOUNTING REQUIREMENTS.

6

DISCONNECT AND REMOVE EXISTING CHIME. MAINTAIN EXISTING CIRCUIT FOR RE-USE. DEVICE SHALL BE RE-INSTALLED IN NEW LOCATION. REFER TO NEW WORK PLAN.

7

INTERCOM STATION, CARD READER AND ASSOCIATED DOOR LOCKS ARE EXISTING TO REMAIN.

8

DISCONNECT AND REMOVE SURFACE RACEWAY, COMMUNICATION DEVICE AND ASSOCIATED CABLING INFRASTRUCTURE.

9

DISCONNECT AND REMOVE PAGING SPEAKER AND PUSH BUTTON.10

DISCONNECT AND REMOVE VIDEO SURVEILLANCE CAMERA. CAMERA SHALL BE RE-INSTALLED IN NEW LOCATION. REFER TO NEW WORK PLAN.

11

EXISTING COMMUNICATION CABLING EXITS WALL, IS ROUTED ALONG FLOOR AND EXTENDS TO DESK COMPUTER LOCATIONS. CABLING SHALL BE MANAGED AND PROTECTED FOR RE-ROUTING. REFER TO NEW WORK PLAN.

12

Sheet Number

Sheet Name

Area Plan

Project Phase

Project Number

Issue Date

in • cite v. to provoke thought

Architect

INCITE DESIGN STUDIO1800 LAFAYETTE AVE., SUITE B, ST. LOUIS, MO 63104314.279.4500

Mech., Plumb., Elec., Telecom.

BRiC PARTNERSHIP, LLC3636 SOUTH GEYER ROAD, SUITE 305ST. LOUIS, MO 63127PHONE: 314-725-5889

Construction Manager

NAVIGATE

PHONE:

Revision No. Description Date Issued

KSD PROJECT # NGL-2021-SECURED VESTIBULE

4/7

/2021 8

:36:0

8 A

M

C:\

Users

\janis

c\D

ocum

ents

\2338-0

2_M

EP

_C

entr

al_

v20_jc

hri

sto

pher7

JR

93.r

vt Demolition Plan - Technology

Communication

NORTH GLENDALEELEMENTARYSCHOOL SECUREVESTIBULERENOVATIONPROJECT

04/08/2021

20-203

BID DOCUMENTS

T1.1

765 N. SAPPINGTON ROADGLENDALE, MO 63122

SCALE: 1/4" = 1'-0"T1.1

FLOOR PLAN - DEMOLITION - TECHNOLOGY1

BRiC MO CERTIFICATE OF

AUTHORITY 2002028690

ENGINEER OF RECORD:

MO. LICENSE NO. 016688

EXP:12/31/22

CARL V. HAUCK

Page 17: Architect NORTH GLENDALE ELEMENTARY SCHOOL...FOC FOF FOM FOS FOW FP FPM FR FR FS FS FSD FT FT FTG FUT FVC FWC G G GA GAL GALV GB GC GCO GCMU GD GEN GEN GFA GFI GFRC GI GLAM GL GMU

DN

F

S

S

F

SS

S

F

F

F

S

S

JS

S

SS

F

S

GENERAL NOTES

A. VERIFY CABLE PATHWAY (CABLE TRAY, CONDUIT OR J-HOOKS) WITHIN BUILDING AND ADJUST ELEVATIONS AND ROUTING TO FACILITATE INSTALLATION. COORDINATE WITH ALL OTHER BUILDING TRADES. UTILIZE EXISTING PATHWAYS WHERE APPLICABLE. WHERE PATHWAYS DO NOT EXIST, PROVIDE NEW.

B. ALL COMMUNICATION CABLES SHALL TERMINATE IN WORK ROOM A108 WALL MOUNT RACK, UNLESS NOTED OTHERWISE.

C. VERIFY MOUNTING HEIGHT OF COMMUNICATION DEVICES WITH ARCHITECTURAL ELEVATIONS PRIOR TO ROUGH-IN. WHERE CONFLICTS EXIST, CONTRACTOR SHALL NOTIFY ENGINEER AND ARCHITECT FOR RESOLUTION.

D. COMMUNICATION CABLING FOR WIRELESS ACCESS POINT (COMMUNICATION OUTLET WITH WAP DESIGNATION) SHALL HAVE AN ADDITIONAL 15’ SERVICE LOOP. SERVICE LOOP SHALL BE MANAGED, COILED AND SUPPORTED AT CEILING.

E. ELECTRICAL DEVICES ARE SHOWN LIGHT AND ARE FOR REFERENCE PURPOSES ONLY. REFER TO ELECTRICAL PLANS FOR ADDITIONAL INFORMATION.

F. DEVICES SHOWN LIGHT ARE EXISTING AND DENOTED WITH "ETR". DEVICES SHOWN DARKER/BOLD ARE TO BE PROVIDED UNDER THIS CONTRACT UNLESS NOTED OTHERWISE.

G. COORDINATE ALL WORK IN OFFICES WITH FURNITURE TYPE, SIZE AND LOCATION.

KEYED NOTES

PROVIDE NEW PAGING/INTERCOM PHONE (VALCOM #480e OR SIMILAR) MOUNTED AT NEW DESK. PHONE SHALL BE CONNECTED TO EXISTING VALCOM CLASS CONNECT PAGING EQUIPMENT.

1

RE-INSTALL EXISTING BURGLAR ALARM KEY PAD IN NEW LOCATION UTILIZING EXISTING CIRCUIT. EXTEND CIRCUIT TO NEW LOCATION AS REQUIRED.

2

RE-INSTALL EXISTING LOCK DOWN PUSH BUTTON IN NEW LOCATION UTILIZING EXISTING CIRCUIT. EXTEND CIRCUIT TO NEW LOCATION AS REQUIRED, OR PROVIDE NEW CABLE INFRASTRUCTURE.

3

RE-INSTALL EXISTING INTERCOM MASTER STATION ON DESKTOP. PROVIDE NEW CABLING INFRASTRUCTURE.

4

PROVIDE NEW 2U WALL MOUNTED VERTICAL RACK WITH VENTED ENCLOSURE (NAVEPOINT #00406188 OR SIMILAR). INSTALL EXISTING PATCH PANEL AND NETWORK SWITCH IN VERTICAL RACK. COORDINATE MOUNTING HEIGHT WITH CABLE PATHWAY. CABLES SHALL BE SUPPORTED AND MANAGED WITHIN VERTICAL RACK.

5

RE-INSTALL EXISTING CHIME IN NEW LOCATION UTILIZING EXISTING CIRCUIT. EXTEND CIRCUIT TO NEW LOCATION AS REQUIRED, OR PROVIDE NEW CABLE INFRASTRUCTURE.

6

RE-INSTALL EXISTING VIDEO SURVEILLANCE CAMERA IN NEW LOCATION. PROVIDE NEW CABLE INFRASTRUCTURE. COORDINATE EXACT LOCATION OF CAMERA WITH EXISTING CONDITIONS. COORDINATE CAMERA VIEWING ANGLE WITH DISTRICT SECURITY PERSONNEL.

7

RE-INSTALL FACEPLATE TO WALL OUTLET.8

EXISTING COMMUNICATION CABLING SHALL BE INSTALLED IN NEW SURFACE RACEWAY. PROVIDE PANDUIT HINGED SURFACE RACEWAY, PART NUMBER LDPH10. COLOR SHALL BE COORDINATED WITH AND APPROVED BY ARCHITECT. LENGTH OF RACEWAY SHALL BE COORDINATED WITH OWNER PROVIDED FURNITURE.

9

FACPFAPS

ICM

LPB

ETR

PAGING

ETR

ETR

ETR

ETR

ICCR

FAAPL

SD

WAP

ETR

ETR

ETR

SDETR

ETR

WAP

ETR

1

KP

2

3

4

5

CHIME

6

7

2D 2DR R

2DR

ETR

RXM

ETR ETR

ETR ETRETR

ETR ETR

ETR

PrincipalA106

WORK ROOMA108

Main OfficeA101

VESTIBULEA100

EX. TA103

EX. STORA102

EX. STOR.A104

ASST.

PRINCIPALA107

CORRIDORA105

CR

LRXM

8

2DR

2DR

30

9

L

Sheet Number

Sheet Name

Area Plan

Project Phase

Project Number

Issue Date

in • cite v. to provoke thought

Architect

INCITE DESIGN STUDIO1800 LAFAYETTE AVE., SUITE B, ST. LOUIS, MO 63104314.279.4500

Mech., Plumb., Elec., Telecom.

BRiC PARTNERSHIP, LLC3636 SOUTH GEYER ROAD, SUITE 305ST. LOUIS, MO 63127PHONE: 314-725-5889

Construction Manager

NAVIGATE

PHONE:

Revision No. Description Date Issued

KSD PROJECT # NGL-2021-SECURED VESTIBULE

4/7

/2021 8

:36:0

8 A

M

C:\

Users

\janis

c\D

ocum

ents

\2338-0

2_M

EP

_C

entr

al_

v20_jc

hri

sto

pher7

JR

93.r

vt Floor Plan - New Work -

Technology Communication

NORTH GLENDALEELEMENTARYSCHOOL SECUREVESTIBULERENOVATIONPROJECT

04/08/2021

20-203

BID DOCUMENTS

T2.1

765 N. SAPPINGTON ROADGLENDALE, MO 63122

SCALE: 1/4" = 1'-0"T2.1

FLOOR PLAN - NEW WORK - TECHNOLOGY1

BRiC MO CERTIFICATE OF

AUTHORITY 2002028690

ENGINEER OF RECORD:

MO. LICENSE NO. 016688

EXP:12/31/22

CARL V. HAUCK

Page 18: Architect NORTH GLENDALE ELEMENTARY SCHOOL...FOC FOF FOM FOS FOW FP FPM FR FR FS FS FSD FT FT FTG FUT FVC FWC G G GA GAL GALV GB GC GCO GCMU GD GEN GEN GFA GFI GFRC GI GLAM GL GMU

NOTES:1. COLOR OF FACE PLATE SHALL BE

COORDINATED WITH AND APPROVED BY ARCHITECT AND OTHER DEVICES WITHIN THE SAME SPACE.

2. FACE PLATE IS DIAGRAMMATIC ONLY. REFER TO SPECIFICATIONS FOR EXACT TYPE OF FACE PLATE.

3. BLANKS SHALL BE INSTALLED IN ALL UNUSED PORTS AND COLOR SHALL MATCH FACE PLATE.

4. EXTENSION RING GANGS SHALL BE COORDINATED WITH FACE PLATE.

5. COMMUNICATION CABLES SHOWN ARE FOR REFERENCE PURPOSES ONLY. REFER TO CONSTRUCTION DOCUMENTS FOR EXACT QUANTITIES.

6. CONDUIT SHALL EXTEND FROM OUTLET BOX TO ACCESSIBLE PORTION OF CEILING UNLESS NOTED OTHERWISE.

7. FOR NON-STANDARDIZED OR SPECIALTY OUTLETS, REFER TO ASSOCIATED KEYED NOTE.

4-11/16" SQUARE x 2-1/8"DEEP OUTLET BOX

1" CONDUIT (MINIMUM)

MULTIPLE 4-PAIR UTP CATEGORY CABLES TO COMMUNICATION ROOM

EXTENSION RING DEPTH SHALL BE COORDINATED WITH WALL ASSEMBLY

FACE PLATE LABEL

CONNECTOR JACK

FACE PLATE LABEL

FACE PLATE

CABLE TYPE

CABLE QUANTITY

# X

C = COAXIAL CABLED = DATA CABLEF = FIBER OPTIC CABLES = SECURITY DATA CABLEV = VOICE CABLEAV = AUDIO/VISUAL CABLING

"X" DENOTES ONE OF THE FOLLOWING:

"#" DENOTES TOTAL NUMBER OF CABLES

2D/1V

(2)DATA (1)VOICE

NOTES:1. CABLING SCHEME IS UTILIZED AT ALL COMMUNICATION

OUTLETS TO CLARIFY TYPE AND QUANTITY OF CABLES REQUIRED AT OUTLET.

2. FOR NON-STANDARDIZED OR SPECIALTY OUTLETS, REFER TO ASSOCIATED KEYED NOTE ON PLAN.

SCHEME EXAMPLE

NOTES:1. PLAN SYMBOLOGY WITH ASSOCIATED

MOUNTING HEIGHTS ARE SHOWN. OUTLET MAY BE OPEN OR FILLED.

2. DEVICES SHALL BE MOUNTED A THE HEIGHT SHOWN UNLESS NOTED OTHERWISE.

3. MOUNTING HEIGHT SHOWN IS APPROXIMATE AND SHALL BE TO CENTER OF OUTLET BOX.

4. FOR ITEMS INSTALLED IN AN ENCLOSURE, COORDINATE REQUIREMENTS WITH CEILING TYPE, ENCLOSURE AND OTHER TRADES.

F

W

C

A

FLOOR

FLOOR BOX OR POKE THRU

18

"

1" ABOVE HIGHEST BACK SPLASH ELEMENT TO BOTTOM

OF COMMUNICATION BOX

48

"

AT OR ABOVE CEILING

WIRELESS ACCESS POINT

WAP

CEILING

NOTES:1. JUNCTION BOX SHALL BE COMPATIBLE WITH CAMERA. CAMERA CABLING SHALL BE ROUTED THROUGH

JUNCTION BOX.2. CONTRACTOR SHALL APPROPRIATELY SEAL WHERE CAMERA MEETS WALL WHEN INSTALLED IN AN

EXTERIOR APPLICATION AND SHALL MAINTAIN IP66 RATING OF CAMERA HOUSING.3. CONDUIT SHALL EXTEND INTO APPROPRIATE CEILING CAVITY AND EXTEND TO ACCESSIBLE CEILING

SPACE.4. COORDINATE INSTALLATION AND LOCATION OF CAMERA WITH GENERAL CONTRACTOR AND OTHER

TRADES. PROVIDE BLOCKING AND CEILING REINFORCEMENT AS REQUIRED.5. CAMERA SHALL BE 3MP, VANDAL RESISTANT, DOME CAMERA WITH IR ILLUMINATION AND 3mm TO 9mm

VARIFOCAL LENS.

3/4" CONDUIT 3/4" CONDUIT

JUNCTION BOX

JUNCTION BOX

WALL WALL

DOMECAMERA

DOMECAMERA

NOTES:1. WHEN INSTALLED IN AN INACCESSIBLE CEILING, PROVIDE 3/4" CONDUIT TO AN

ACCESSIBLE CEILING SPACE. WHEN INSTALLED IN AN ACCESSIBLE CEILING, NO CONDUIT IS REQUIRED.

2. COORDINATE INSTALLATION AND LOCATION OF CAMERA HOUSING WITH GENERAL CONTRACTOR AND OTHER TRADES. PROVIDE BLOCKING AND CEILING REINFORCEMENT AS REQUIRED.

3. CONTRACTOR SHALL APPROPRIATELY SEAL WHERE CAMERA MEETS WALL WHEN INSTALLED IN AN EXTERIOR APPLICATION AND SHALL MAINTAIN IP66 RATING OF CAMERA HOUSING.

4. CAMERA SHALL BE 3MP, VANDAL RESISTANT, DOME CAMERA WITH IR ILLUMINATION AND 3mm TO 9mm VARIFOCAL LENS.

4-PAIR UTP CABLEENCLOSURE/HOUSING WITH FINISHED TRIM

CEILING

3/4"C TO CARD READER ON UNSECURED SIDE

DOOR INTERFACE BOX ABOVE CEILING

(SECURE SIDE)

CARD READER

MOUNTED AT 42" AFF

(UNSECURED SIDE)

3/4"C TO DOOR FRAME FOR DOOR POSITION SWITCH/DOOR CONTACTS

3/4"C TO DOOR FRAME FOR LOCKING MECHANISM

CEILING

FLOOR

NOTES:1. PROVIDE ROUGH-IN BOXES, CONDUIT, WIRING, POWER

SUPPLIES, ETC. AS REQUIRED. COORDINATE EXACT REQUIREMENTS WITH SYSTEM VENDOR AND ARCHITECTURAL DOOR HARDWARE SCHEDULE. PROVIDE ALL COMPONENTS REQUIRED.

2. DETAIL IS DIAGRAMMATIC AND IS NOT INTENDED TO BE EXACT OR ALL INCLUSIVE. COORDINATE WITH ARCHITECTURAL PLANS, DETAILS, AND DOOR HARDWARE FOR DEVICE LOCATIONS AND TYPES.

3. PROVIDE PULL STRINGS IN ALL CONDUITS.4. PROVIDE ADDITIONAL 3/4" CONDUIT WHEN A POWER TRANSFER

DEVICE IS UTILIZED.5. MOUNTING HEIGHTS ARE APPROXIMATE AND SHALL BE

COORDINATED WITH ARCHITECTURAL PLANS AND ELEVATIONS.6. SECURE SIDE SHALL BE FREE FOR IMMEDIATE EXIT.7. SECURE SIDE PIR SHALL PROVIDE REQUEST-TO-EXIT INPUT TO

SHUNT ALARM.8. ACCESS CONTROL SYSTEM SHALL UNLOCK ELECTRONIC

LOCKING MECHANISM UPON ACTIVATION OF A VALID CREDENTIAL.

9. CONTRACTOR SHALL PROVIDE ALL REQUIRED PROGRAMMING AND SHALL COORDINATE WITH OWNER FOR SCHEDULE AND OPERATION.

10. DOOR HARDWARE DEVICES SHALL BE FURNISHED AND INSTALLED BY HARDWARE CONTRACTOR AND WIRED BY THE ELECTRICAL/COMMUNICATION CONTRACTOR, UNLESS NOTED OTHERWISE.

11. POWER SUPPLIES SHALL BE FURNISHED, INSTALLED, SIZED AND WIRED BY THE ELECTRICAL CONTRACTOR. IT IS THE ELECTRICAL CONTRACTORS RESPONSIBILITY TO COORDINATE WITH THE DOOR HARDWARE CONTRACTOR. POWER SUPPLIES SHALL BE LOCATED IN THE COMMUNICATION ROOM.

1"C TO ACCESSIBLE PORTION OF CEILING

CABLE TO DOOR CONTROLLER UNIT

3/4"C TO PIRREQUEST-TO-EXIT

3/4"C TO FIRE ALARM ADDRESSIBLE CONTROL RELAY AND POWER SUPPLY

Sheet Number

Sheet Name

Area Plan

Project Phase

Project Number

Issue Date

in • cite v. to provoke thought

Architect

INCITE DESIGN STUDIO1800 LAFAYETTE AVE., SUITE B, ST. LOUIS, MO 63104314.279.4500

Mech., Plumb., Elec., Telecom.

BRiC PARTNERSHIP, LLC3636 SOUTH GEYER ROAD, SUITE 305ST. LOUIS, MO 63127PHONE: 314-725-5889

Construction Manager

NAVIGATE

PHONE:

Revision No. Description Date Issued

KSD PROJECT # NGL-2021-SECURED VESTIBULE

4/7

/2021 8

:36:0

9 A

M

C:\

Users

\janis

c\D

ocum

ents

\2338-0

2_M

EP

_C

entr

al_

v20_jc

hri

sto

pher7

JR

93.r

vt Details - Technology

Communication

NORTH GLENDALEELEMENTARYSCHOOL SECUREVESTIBULERENOVATIONPROJECT

04/08/2021

20-203

BID DOCUMENTS

T5.1

765 N. SAPPINGTON ROADGLENDALE, MO 63122

SCALE: NO SCALET5.1

COMMUNICATION OUTLET1

SCALE: NO SCALET5.1

OUTLET CABLING SCHEME2

SCALE: NO SCALET5.1

OUTLET ELEVATION HEIGHT3

SCALE: NO SCALET5.1

CAMERA - WALL MOUNT4

SCALE: NO SCALET5.1

CAMERA - CEILING MOUNT5

BRiC MO CERTIFICATE OF

AUTHORITY 2002028690

ENGINEER OF RECORD:

MO. LICENSE NO. 016688

EXP:12/31/22

CARL V. HAUCK

SCALE: NO SCALET5.1

ACCESS CONTROL - DOUBLE DOOR6