1GE Multilin
Instrument Transformers, Inc.
Are you using the right CT's and PT's for your application?
John Levine, P.E.
Levine Lectronics and LectricE-mail: [email protected]
GE Multilin / Instrument Transformers, Inc.
![Page 2: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/2.jpg)
2GE Multilin
Instrument Transformers, Inc.
Alternate Title of Presentation
Now I know what I do not know about CT’s and PT’s.
As engineers we do not need to know all the answers just where to get them.
![Page 3: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/3.jpg)
3GE Multilin
Instrument Transformers, Inc.
Current & Voltage Transformer Basics (IEEE Standards)
![Page 4: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/4.jpg)
4GE Multilin
Instrument Transformers, Inc.
Agenda
Current TransformersVoltage TransformersRequired Information for Specifying CTs & VTsTake Home Rules” for CTs & VTsApplications where used
![Page 5: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/5.jpg)
5GE Multilin
Instrument Transformers, Inc.
Why use Instrument Transformers?
Circuit Isolation
Reduce voltage and currents to reasonable working levels.
Phasor combinations for summing and measuring power
![Page 6: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/6.jpg)
6GE Multilin
Instrument Transformers, Inc.
CURRENT TRANSFORMERS TYPES OF C.T. CONSTRUCTION
The most common type of C.T. construction is the “DOUGHNUT” type. It is constructed of an iron toroid, which forms the core of the transformer, and is wound with secondary turns.
Secondary Winding Primary Conductor
Iron Core
![Page 7: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/7.jpg)
7GE Multilin
Instrument Transformers, Inc.
Transformer ratio (TR)
Primary Current(100 amps)
Secondary Current (5 amps)
Primary CurrentSecondary Current
Transformer Ratio = _____________________
100 5___ = 100:5 or 20:1
![Page 8: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/8.jpg)
8GE Multilin
Instrument Transformers, Inc.
Polarity
Direction ofPrimary Current
Direction of Secondary Current
H1
X1
Primary current into “polarity” =
Secondary current out of “polarity”
P1
IEEE
IEC
Primary PolarityMarks
IEEEIECS1
Secondary PolarityMarks
Remember:
![Page 9: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/9.jpg)
9GE Multilin
Instrument Transformers, Inc.
Polarity
Direction ofPrimary Current
Direction of Secondary Current
H1
X1
P1
IEEE
IEC
Primary PolarityMarks
IEEEIECS1
Secondary PolarityMarks
Primary current into “non-polarity” =
Secondary current out of “non-polarity”
Remember:
![Page 10: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/10.jpg)
10GE Multilin
Instrument Transformers, Inc.
Generator typical wiring
![Page 11: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/11.jpg)
11GE Multilin
Instrument Transformers, Inc.
What is your application?
If your application is metering , how high do I need to go in current? 2 times ?
If your application is protective relaying, how high do I need to go in current? 20 times ? 40 times ?
![Page 12: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/12.jpg)
12GE Multilin
Instrument Transformers, Inc.
CT Rating Factor (RF) -- IEEERated current x (RF) =
Maximum continuous current carrying capability:
Without exceeding temperature limits
Without loss of published accuracy class
Typical rating factors for Metering CTs are:1.0, 1.33, 1.5, 2.0, 3.0, 4.0
![Page 13: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/13.jpg)
13GE Multilin
Instrument Transformers, Inc.
0.30
0.30
0.60
0.60
Rating Factor
Accu
racy
Cla
ss -
%CT Rating Factor (RF) -- IEEE
10% 100% 200% 300% 400%
1.0 2.0 3.0 4.0
IEEE C57.13 Accuracy0.3% @ BX.X RF 4.0
0.3% Accuracy Region
0.6% Accuracy
Region
![Page 14: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/14.jpg)
14GE Multilin
Instrument Transformers, Inc.
Short-Time Thermal Current Rating
One (1) – second thermal ratingExpressed as value of RMS primary currentMain influencing factor:
CT primary & secondary wire size Can be converted to thermal rating for any time period (t) up to five (5) seconds:
(New RF at new Ambient/Stated RF at 30 degrees C)2=85-New Ambient/New Ambient
Example: CT with rating factor of 4 at 30 degrees = rating factor of 2.95 at 55 degreesX2/42=85-55/55 X=2.95
![Page 15: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/15.jpg)
15GE Multilin
Instrument Transformers, Inc.
CT Metering Accuracy
Actual secondary current
Rated secondary current=
Difference in % is known as the “Accuracy”
of the CT
![Page 16: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/16.jpg)
16GE Multilin
Instrument Transformers, Inc.
IEEE CT Metering AccuracyAccuracy Class ( * )
Application
0.15 High Accuracy Metering
0.15S “Special” High Accuracy Metering
0.3 Revenue Metering
0.6 Indicating Instruments
1.2 Indicating Instruments* All accuracy classes defined by IEEE C57.13 or C57.13.6
* Accuracy classes include both ratio & phase angle error
![Page 17: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/17.jpg)
17GE Multilin
Instrument Transformers, Inc.
IEEE CT Metering Accuracy
BurdenLoad connected to CT secondary
Includes devices & connecting leads
Expressed in ohms
Standard values = B0.1, B0.2, B0.5, B0.9, B1.8 E0.04, E0.2
All burdens defined by IEEE C57.13 or C57.13.6 for 60 Hz only
![Page 18: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/18.jpg)
18GE Multilin
Instrument Transformers, Inc.
Application Burden Designation
Impedance (Ohms)
VA @ 5 amps
Power Factor
Metering B0.1 0.1 2.5 0.9B0.2 0.2 5 0.9B0.5 0.5 12.5 0.9B0.9 0.9 22.5 0.9B1.8 1.8 45 0.9
Standard IEEE CT Burdens (5 Amp) (Per IEEE Std. C57.13-1993 & C57.13.6)
IEEE CT Metering Accuracy
E0.2E0.04
0.20.04
51
1.01.0
![Page 19: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/19.jpg)
19GE Multilin
Instrument Transformers, Inc.
A current transformer for metering purposes may typically have an accuracy of 0.3%. The C.T. must maintain this accuracy for normal load currents, provided the rated burden on the C.T. is not exceeded. It is quite acceptable, and in fact desirable, for the C.T. to saturate when fault current flows. The accuracy for a typical metering C.T. is specified as: 0.3 M 0.9
O.3% METERING O.9 OHMS BURDEN
This metering C.T. has an accuracy of 0.3% when the connected burden does not exceed 0.9 OHMS.
![Page 20: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/20.jpg)
20GE Multilin
Instrument Transformers, Inc.
IEEE CT Metering Accuracy
Accuracy Class(0.3, 0.6, 1.2) (*)
Burden (Ohms)(B0.1, B0.2, B0.5, B0.9, B1.8)
+
“Accuracy” expressed as:
0.3B0.20.6B0.91.2B1.80.15E0.2
=
Typical Examples
* Accuracy class is stated at 100% rated current* At 10% rated current, twice the error is allowed (5% for 0.15 class)
(0.15*, 0.15S^) E0.2, E0.04)
^ Accuracy class is stated at 100% to 5% rated current
![Page 21: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/21.jpg)
21GE Multilin
Instrument Transformers, Inc.
0.30
0.30
0.60
0.60
Rating Factor
Accu
racy
Cla
ss -
%
10% 200% 300%
1.0 2.0 3.0 4.0
IEEE C57.13 Accuracy0.3 @ BX.X; RF 4.0
0.3% Accuracy Region
0.6% Accuracy
Region
IEEE CT Metering Accuracy
100% 400%
No accuracy guaranteed at current levels less than 10%
![Page 22: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/22.jpg)
22GE Multilin
Instrument Transformers, Inc.
IEEE CT Metering Accuracy
CT Parallelogram – IEEE C57.13
Out of 0.3% Class
0.3 classparallelogram
0.6 classparallelogram
100%10%
Note:Burden must be specified
![Page 23: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/23.jpg)
23GE Multilin
Instrument Transformers, Inc.
IEEE CT Metering Accuracy
Corrected to 0.3% Class
CT Parallelogram – IEEE C57.130.3 classparallelogram
0.6 classparallelogram
100%
10%
Note:Burden must be specified
![Page 24: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/24.jpg)
24GE Multilin
Instrument Transformers, Inc.
0.30
0.30
0.60
0.60
Rating Factor
Accu
racy
Cla
ss -
%
5% 100% 200% 300% 400%
1.0 2.0 3.0 4.0
IEEE C57.13.6 Accuracy0.15 @ E0.04, E0.20; 0.15 @ BX.X; RF4.0
0.15% Accuracy Region
0.3% Accuracy
Region
IEEE CT Metering Accuracy
0.15
0.15
No accuracy guaranteed at current levels less than 5%
![Page 25: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/25.jpg)
25GE Multilin
Instrument Transformers, Inc.
0.30
0.30
0.60
0.60
Rating Factor
Accu
racy
Cla
ss -
%
5% 200% 300%
1.0 2.0 3.0 4.0
IEEE C57.13.6 Accuracy0.15S @ E0.04, E0.20; 0.15S @ BX.X, RF4.0
0.15% Accuracy Region
IEEE CT Metering Accuracy
0.15
0.15
No accuracy guaranteed at current levels less than 5%
400%100%
![Page 26: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/26.jpg)
26GE Multilin
Instrument Transformers, Inc.
IEEE CT Relay AccuracyProtection CT
Standard Relay Accuracy Classes
C or T100
C or T200
C or T400
C or T800
What do these mean?
![Page 27: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/27.jpg)
27GE Multilin
Instrument Transformers, Inc.
IEEE CT Relay Accuracy
Relay class (C or T___ ) designates minimum secondary terminal volts…
At 20 times rated current
Without exceeding 10% ratio error
Into a maximum specified burden
Now that everyone is totally confused let’s look at some simple examples …
![Page 28: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/28.jpg)
28GE Multilin
Instrument Transformers, Inc.
T = Determined by testC = CalculatedK = CalculatedL = Low internal secondary impedanceH = High internal secondary impedance
Format
LetterAccuracy Voltage at 20 times CT
![Page 29: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/29.jpg)
29GE Multilin
Instrument Transformers, Inc.
Primary current24,000 amps
(20 x 1200)
IEEE CT Relay Accuracy
CT1200:5
C or T100
X1X2
Burden ofDevices ()
Burden ofLeads ()
Secondary current 100 amps (20 x 5)
Total Ext Burden1.0
C or T100 example
Terminal Volts = (20 times rated) (Total external burden)
100 Volts = (100 amps) (1.0 )
Term
inal
Vol
ts =
100
![Page 30: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/30.jpg)
30GE Multilin
Instrument Transformers, Inc.
Primary current24,000 amps
(20 x 1200)
IEEE CT Relay Accuracy
CT1200:5
C or T200
X1X2
Burden ofDevices ()
Burden ofLeads ()
Secondary current 100 amps (20 x 5)
Total Ext Burden2.0
C or T200 example
Terminal volts = (20 times rated) (Total external burden)
200 Volts = (100 amps) (2.0 )
Term
inal
Vol
ts =
200
![Page 31: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/31.jpg)
31GE Multilin
Instrument Transformers, Inc.
Standard IEEE CT Burdens (5 Amp) (Per IEEE Std. C57.13-1993)
IEEE CT Relay Accuracy
Application Burden
Designation
Impedance
(Ohms)
VA @
5 amps
Power
Factor
Relaying B1 1 25 0.5
B2 2 50 0.5
B4 4 100 0.5
B8 8 200 0.5
![Page 32: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/32.jpg)
32GE Multilin
Instrument Transformers, Inc.
IEEE CT Relay AccuracyExcitation curve includesvoltage required to overcome internal resistance (DCR) of CT.Approximately 32 volts.
10% ratio error = (20 x 5) (10%) = (100) (0.10) = 10 amps
How many terminal volts would you estimate this CT can produce?
![Page 33: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/33.jpg)
33GE Multilin
Instrument Transformers, Inc.
1000:5 CT
1000 Amps 5amps
IE<0.5amps
IB >4.5 amps
With 10% error, IB is anywhere from 4.5 to 5.5 amps
Most Protection CT’s also have a Metering CT accuracy so you could use this value for calculating the error at lower
currents
![Page 34: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/34.jpg)
34GE Multilin
Instrument Transformers, Inc.
CT Burden Calculation
Primary Current
CT
X1X2
Burden ofDevices ()
Burden ofLeads ()
Secondary current
Total Burden ZT
How do we calculate this?
![Page 35: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/35.jpg)
35GE Multilin
Instrument Transformers, Inc.
CT Burden Calculation
Assumption: 3 phase CTs are “Y” connected
ZT = RCT + RL + ZB
ZT = Total burden in ohms (vector summation of resistance and inductance components)
RCT = CT secondary resistance in ohms @75 deg C (DCR)
RL = Resistance of leads in ohms (Total loop distance)
ZB = Device impedance in ohms
![Page 36: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/36.jpg)
36GE Multilin
Instrument Transformers, Inc.
GE Multilin Electronic Relay Burden
VA = VI. V= IR, So 0.2 = I*I*R.
.2/25 = .008 ohms
![Page 37: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/37.jpg)
37GE Multilin
Instrument Transformers, Inc.
100:5 C.T. Secondary Winding Resistance (DCR) = .062 ohm
Resistance of Cable from C.T. to Relay and back = .1 ohms
Resistance of Relay Coil = .02 ohms
Total Resistance = .182 ohms
If we have a fault of 2,000 amps and the C.T. ratio is 100:5 then the C.T. secondary current is 100 amps. Therefore we will produce a voltage of 100 amps x .182 ohms = 18.2 Volts. To prevent CT saturation, select a CT with a knee point above 18.2 Volts.
.062
.1
.02
![Page 38: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/38.jpg)
38GE Multilin
Instrument Transformers, Inc.
780-102 is a 1000 to 5 CT, Class C100
1000:5 C.T. Secondary Winding Resistance (DCR) = .32 ohm
Resistance of Cable from C.T. to Relay and back = .1 ohms
Resistance of Relay Coil = .008 ohms
Total Resistance = .428 ohms
If we have a fault of 20,000 amps and the C.T. ratio is 1000:5 then the C.T. secondary current is 100 amps. Therefore we will produce a voltage of 100 amps x .428 ohms = 42.8 Volts. To prevent CT saturation, select a CT with a knee point above 42.8 Volts.
What happens if the fault current is 40,000 amps?
.32
.1
.008
![Page 39: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/39.jpg)
39GE Multilin
Instrument Transformers, Inc.
Factors Influencing CT Accuracy
Frequency
Current Ratio
Burden
“Low frequency” and “High accuracy” are not friends!!
“Low ratio” and “high accuracy” are not friends!!
“High burden” and “High Accuracy” are not friends!!
![Page 40: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/40.jpg)
40GE Multilin
Instrument Transformers, Inc.
CT Saturation
What is CT Saturation?
![Page 41: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/41.jpg)
41GE Multilin
Instrument Transformers, Inc.
Power Systems Relay Committee (PSRC) Saturation Calculator
![Page 42: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/42.jpg)
42GE Multilin
Instrument Transformers, Inc.
Factors Affecting Degree of Saturation and Time to Saturation
DC Offset
Fault Magnitude (symmetrical current)•100 to 5 CT@20 times= 2000 amps, at 20,000 amps we have 200 times CT
CT Turns Ratio
Secondary Burden
CT Accuracy
Remanence Flux • Can occur if current interrupted when core is saturated• If DC flows in windings during testing• Need a voltage above 60% of knee point to reduce the remanence to
less than 10% of saturation flux density.
![Page 43: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/43.jpg)
43GE Multilin
Instrument Transformers, Inc.
Tips for Avoiding CT SaturationUse higher ratio CTs
Use separate set of high ratio CTs for high fault current tripping
Reduce secondary burdenSelect low burden relays & metersDistribute single phase burdens among phasesIncrease size of secondary leadsReduce length of secondary leads
Use “step down” auxiliary CTs
![Page 44: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/44.jpg)
44GE Multilin
Instrument Transformers, Inc.
Potential Transformers
![Page 45: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/45.jpg)
45GE Multilin
Instrument Transformers, Inc.
DefinitionsVoltage Transformer (VT)
An instrument transformer used to reflect a primary voltage into a secondary voltage through a magnetic medium. Always connected in parallel with primary conductor across a circuit load.
Secondary (measuring) voltage is usually 115 or 120 volts nominally. The secondary voltage level is selected for ease of measurement and safety.Control Power Transformer (CPT)
Designed to provide power for contractors, relays and devices with high inrush currents, Regulation is not as critical.
![Page 46: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/46.jpg)
46GE Multilin
Instrument Transformers, Inc.
![Page 47: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/47.jpg)
47GE Multilin
Instrument Transformers, Inc.
Relay
14,400/120 = 120/1
4200/120 = 35/1
2400/120 = 20/1
![Page 48: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/48.jpg)
48GE Multilin
Instrument Transformers, Inc.
IEEE VT Accuracy ClassMetering Accuracy
Classes (% error)
0.3
0.6
1.2
0.15
Defined by IEEE C57.13
Applicable from 90% to 110% rated voltage
Defined by IEEE C57.13.6
![Page 49: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/49.jpg)
49GE Multilin
Instrument Transformers, Inc.
IEEE VT Accuracy Class
These standard burden designations have no significance at frequencies other than 60 Hz.
Burden VA PF
W 12.5 0.10X 25 0.70M 35 0.20Y 75 0.85Z 200 0.85
ZZ 400 0.85
Metering Accuracy Class Burdens
![Page 50: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/50.jpg)
50GE Multilin
Instrument Transformers, Inc.
IEEE VT Accuracy Class
Expressed as:
Accuracy Class + Burden Code
0.3 W,X,Y0.6 Z
1.2 ZZ
These standard designations have no significance at frequencies other than 60 Hz.
![Page 51: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/51.jpg)
51GE Multilin
Instrument Transformers, Inc.
![Page 52: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/52.jpg)
52GE Multilin
Instrument Transformers, Inc.
VT Installation Guidelines Caution:
Rated voltage: Do not operate above 110%
Line to ground rated:
Do not connect line to line
Do not use on ungrounded systems w/o consulting factory
Rated Frequency: Do not operate below rated frequency w/o consulting factory
![Page 53: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/53.jpg)
53GE Multilin
Instrument Transformers, Inc.
IEEE VT Groups VT
GroupNo. of
BushingConnection
Method
Neutral Grounding
Notes
1 2 open
Y-Y possible
Any Withstand 25% over rated voltage on an emergency basis
2 2 open
Y-Y possible
Any Withstand 10% over rated voltage continuously. Primary rated for line to line voltage.
3 1 Y-Y-Y Any Outdoor, two secondary windings. Withstand 10% over rated voltage continuously.
4A 1 Y-Y Effectively Withstand 10% over rated voltage continuously & 25% on an emergency basis. For operation at 100% rated voltage.
4B 1 Y-Y
Y-Broken Corner
Non-effectively
Withstand 10% overvoltage continuously. For operation at 58% rated voltage.
5 1 Y-Y Effectively Outdoor. Withstand 40% over rated voltage for 1 minute and 10% over rated voltage continuously
![Page 54: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/54.jpg)
54GE Multilin
Instrument Transformers, Inc.
VT Typical Connections
Open Delta Connection(2) Double Bushing VTs
Y – Y Connection(3) Single Bushing VTs
![Page 55: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/55.jpg)
55GE Multilin
Instrument Transformers, Inc.
FerroresonancePossible with Y connected grounded VTs on ungrounded power systems
A VT is an inductive component
Capacitance to ground exists in the system
When they match ferroresonance may occur
May cause higher VT voltages & saturation
Possible results --High VT currentsOverheatingVT failure
![Page 56: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/56.jpg)
56GE Multilin
Instrument Transformers, Inc.
Ferroresonance
Recommended reading:
“Ferroresonance of Grounded Potential
Transformers on Ungrounded Power Systems”
AIEE Power Apparatus & Systems,
Aug 1959, pg 607-618, by Karlicek and Taylor
![Page 57: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/57.jpg)
57GE Multilin
Instrument Transformers, Inc.
Ferroresonance Damping
Y – Broken Corner VT connection
Ferroresonancedamping resistor RFR
Voltage relay to detect ground fault
Non effectively grounded system
0 volts @ normal condition
3 times normal L-N phasevoltage @ ground fault
Preferred method
![Page 58: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/58.jpg)
58GE Multilin
Instrument Transformers, Inc.
Ferroresonance Damping
Y-Y/Broken Corner Connection
Double secondary VT
(1) Relaying / Metering
(1) Ground fault detectionand ferroresonance damping
Preferred method
![Page 59: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/59.jpg)
59GE Multilin
Instrument Transformers, Inc.
Ferroresonance Damping
Ferroresonancedamping resistor RFR value
Based on 2 variables:Air core inductance of primary winding (La)VT ratio (N)RFR = 100 La / N2
Power rating (watts) of the resistor is a system related problem.General recommendation is 50% of VA rating of a single VT.
![Page 60: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/60.jpg)
60GE Multilin
Instrument Transformers, Inc.
Required Information for Specifying CTs & VTs
![Page 61: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/61.jpg)
61GE Multilin
Instrument Transformers, Inc.
Current Transformer (CT) RFQ Specification Environment: ___Indoor ___Outdoor
System Voltage (kV)0.6
0.723.65.07.28.712152425
34.534.5
Power Frequency (kV)43
10192026283450407070
BIL (kV)10
4060607575
110125125150200
Standard (Check one)IEEE __
IEC __IEC __IEEE __IEC __IEEE __IEC __IEEE __IEC __IEEE __IEEE __IEEE __
CT Application: ___Metering ___Protection
Dimensions: ___ Inches ___ mm
Max. Outside: L ______ x W ______ x D ______
CT Window: Round: ______ Diameter; Rectangular: L ______ x W ______ ; Primary Bar: _____
Current Ratio: _______ : 5 _______ : 1
Continued next slide
![Page 62: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/62.jpg)
62GE Multilin
Instrument Transformers, Inc.
Current Transformer (CT) RFQ Specification (Continued)Accuracy:
Indication Only: _____ %, _____VA (Skip metering & protection selections)
Metering Class:IEEE: ___0.3 ___0.6 ___1.2 ___2.4 ________OtherIEC: ___0.2 ___0.5 ___1.0 ________Other
Metering Burden:IEEE (Ohms): ___B0.1 ___B0.2 ___B0.5 ___B0.9 ___B1.8 ______OtherIEC (VA): ___2.5 ___5.0 ___10 ___15 ___30 ______Other
Protection Class: C______(IEEE) ___VA, ___P___(IEC)
Operating Frequency: ___60HZ ___50HZ
Rating Factor: ___1.0 ___1.33___1.5___2.0______Other
Secondary Connections: ___Terminals___24 inch leads
Outer Insulation: ___Standard___Cotton tape & varnish___Polyester tape
Insulation Class: ___105 0C (Standard)_____Other
Other Special Requirements (dimensional constraints, mounting requirements, …etc):____________________________________________________________________________________________________________________________________________________________
![Page 63: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/63.jpg)
63GE Multilin
Instrument Transformers, Inc.
Voltage Transformer (VT) RFQ Specification Environment: ___Indoor ___Outdoor
System Voltage (kV)0.6
0.723.65.07.28.712152425
34.534.5
Power Frequency (kV)43
10192026283450407070
BIL (kV)10
4060607575
110125125150200
Standard (Check one)IEEE __IEC __IEC __IEEE __IEC __IEEE __IEC __IEEE __IEC __IEEE __IEEE __IEEE __
Continued next slide
Operating Frequency: ___60HZ ___50HZ
Accuracy:
IEEE: ___W ___X ___M ___Y ___Z ___ZZ ________Other(Enter 0.3, 0.6, 1.2, or leave blank)
IEC: ___10VA ___25VA ___50VA ___100VA ___200VA ___500VA ______Other(Enter 0.2, 0.5, 1.0, or leave blank)
![Page 64: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/64.jpg)
64GE Multilin
Instrument Transformers, Inc.
Voltage Transformer (VT) RFQ Specification (Continued)
Thermal Rating: _______VA (Optional)
Primary Voltage: ___1 bushing _________VAC - Phase to neutral
___2 bushing _________VAC - Phase to phase
Secondary Voltage: ___120V ___115V ___110V ___100V___120/3 ___115/3 ___110/3 ___100/3___Other _________________
Rated Voltage Factor (RVF) (1 bushing only): ___1.9 for 30s ___1.9 for 8 hours ___Other____________
Fuses:
___Primary ___Secondary ___None (600 – 720 V)
___Primary ___Live parts only ___Switchgear Style ___Unfused (2.5kV – 15kV)
Note integral fusing not available above 15kV
![Page 65: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/65.jpg)
65GE Multilin
Instrument Transformers, Inc.
Take Home Rule # 1
CTs are intended to be proportional current devices. Very high voltages can result from open circuiting the secondary circuit of an energized CT. Even very small primary currents can cause damage… Consult the factory if you have questions.
Never open circuit a current transformer secondary while the primary is energized
![Page 66: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/66.jpg)
66GE Multilin
Instrument Transformers, Inc.
Never short circuit the secondary of an energized VT
Take Home Rule # 2
VTs are intended to be used as proportional voltage
devices. Damaging current will result from short
circuiting the secondary circuit of an energized VT.
![Page 67: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/67.jpg)
67GE Multilin
Instrument Transformers, Inc.
Take Home Rule # 3
Metering applications do not require a “C” class CT
“C” class ratings are specified for protection purposes only. With some exceptions metering class CTs are typically smaller and less expensive.
![Page 68: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/68.jpg)
68GE Multilin
Instrument Transformers, Inc.
Take Home Rule # 4
CT secondary leads must be added to the CT burden
Electronic relays usually represent very little burden to the CT secondary circuit. In many cases the major burden is caused by the CT secondary leads.
![Page 69: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/69.jpg)
69GE Multilin
Instrument Transformers, Inc.
Take Home Rule # 5
Never use a 60 Hz rated VT on a 50 Hz System
60 Hz VTs may saturate at lower frequencies and exceed temperature limitations. VT failure is likely…severe equipment damage is possible.
![Page 70: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/70.jpg)
70GE Multilin
Instrument Transformers, Inc.
Take Home Rule # 6
Exercise caution when connecting grounded VTs to ungrounded systems
Line to ground voltage on any VT may exceed the primary voltage rating during a fault condition… VT must be designed for application.
![Page 71: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/71.jpg)
71GE Multilin
Instrument Transformers, Inc.
Take Home Rule # 7
It is common practice to apply 600 Volt CT to systems with higher voltages.
This practice is done by passing fully insulated conductors through the Window.
![Page 72: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/72.jpg)
72GE Multilin
Instrument Transformers, Inc.
QUESTIONS?
![Page 73: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/73.jpg)
73GE Multilin
Instrument Transformers, Inc.
![Page 74: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/74.jpg)
74GE Multilin
Instrument Transformers, Inc.
![Page 75: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/75.jpg)
75GE Multilin
Instrument Transformers, Inc.
LV SwitchboardsLV Panelboards
5 Series
8SHT19RT
Typical CT Models
![Page 76: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/76.jpg)
76GE Multilin
Instrument Transformers, Inc.
LV SwitchboardsLV Panelboards
Typical VT Models
460, 467, 475, 2VT460, 3VT460
![Page 77: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/77.jpg)
77GE Multilin
Instrument Transformers, Inc.
L.V. MCC’s
8SHT
19RT
5 Series
3P85
Typical CT Models
![Page 78: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/78.jpg)
78GE Multilin
Instrument Transformers, Inc.
L.V. MCC’s
Typical VT Models
460, 467, 475, 2VT460, 3VT460
![Page 79: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/79.jpg)
79GE Multilin
Instrument Transformers, Inc.
L.V. Switchgear
![Page 80: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/80.jpg)
80GE Multilin
Instrument Transformers, Inc.
L.V. Switchgear Current TransformersGE 2000 amp frameModel 560 MeteringModel 561 Protection
![Page 81: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/81.jpg)
81GE Multilin
Instrument Transformers, Inc.
Current TransformersGE 4000 amp frameModel 562 MeteringModel 563 Protection
L.V. Switchgear
![Page 82: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/82.jpg)
82GE Multilin
Instrument Transformers, Inc.
L.V. Switchgear
No more room in the front? We can recommend a different model CT for the rear bus area.
![Page 83: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/83.jpg)
83GE Multilin
Instrument Transformers, Inc.
L.V. SwitchgearTypical 3 Phase VTInstallation
3VTL4603 Phase VT
![Page 84: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/84.jpg)
84GE Multilin
Instrument Transformers, Inc.
M.V. SwitchgearTypical Line Up
Where are the CTs, VTs, and CPTs?
![Page 85: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/85.jpg)
85GE Multilin
Instrument Transformers, Inc.
Current Transformers778 / 779 680 /780 Series Typical IEEE Metering & Protection
M.V. Switchgear
![Page 86: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/86.jpg)
86GE Multilin
Instrument Transformers, Inc.
M.V. Switchgear Current TransformersMetering & Protection
Model 780, 778
Model 785
![Page 87: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/87.jpg)
87GE Multilin
Instrument Transformers, Inc.
M.V. Switchgear
Model 203 CTs mounted in rear bus compartment
![Page 88: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/88.jpg)
88GE Multilin
Instrument Transformers, Inc.
M.V. Switchgear
Zero Sequence CTModel 593, 594
Is this better than a Residual Connection?
![Page 89: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/89.jpg)
89GE Multilin
Instrument Transformers, Inc.
M.V. SwitchgearTypical VT Rollout Drawer
Installed in enclosure
Withdrawn from enclosure
(2) PTG5’s in open deltaconfiguration
![Page 90: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/90.jpg)
90GE Multilin
Instrument Transformers, Inc.
M.V. SwitchgearTypical CPT Rollout Drawer
Installed in enclosureWithdrawn from enclosure
CPT5 & 15 kV5 to 15 kVA
![Page 91: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/91.jpg)
91GE Multilin
Instrument Transformers, Inc.
MV MCC’s
Let’s open a door and see what’s inside
![Page 92: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/92.jpg)
92GE Multilin
Instrument Transformers, Inc.
MV MCC’s
Typical CT Models112113114115117
![Page 93: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/93.jpg)
93GE Multilin
Instrument Transformers, Inc.
Generators
Board Mounted Generator CT
![Page 94: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/94.jpg)
94GE Multilin
Instrument Transformers, Inc.
Station Class Circuit Breakers
Polyester Taped Bushing CT on Outdoor Circuit Breaker
![Page 95: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/95.jpg)
95GE Multilin
Instrument Transformers, Inc.
Station Class Circuit Breakers
Outdoor BO7 - Replaces BCT’s in shielded aluminum housing
Ground Shield
![Page 96: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/96.jpg)
96GE Multilin
Instrument Transformers, Inc.
Outdoor Type BO7 for Retrofit
Power TransformersSlip over current transformer for installation over exterior of outdoor bushing
![Page 97: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/97.jpg)
97GE Multilin
Instrument Transformers, Inc.
Power TransformersMetering applications for indoor instrument transformerson outdoor power transformers
Air terminal chamber Indoor PT and Bar type CT
![Page 98: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/98.jpg)
98GE Multilin
Instrument Transformers, Inc.
![Page 99: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,](https://reader030.vdocument.in/reader030/viewer/2022020115/5d1b520d88c993656e8d9fba/html5/thumbnails/99.jpg)
99GE Multilin
Instrument Transformers, Inc.
Questions?