Array Boiler PRE-CHECK LIST Boiler set-up details (only fill out the boxes that are applicable to the type of fuel used). 1.Is wiring connected correctly and tight? 2.Have the burner safeties been checked for proper operation? 3.Has every boiler safety devices been tested for proper operation? 4.Have the gas shut off valves been verified for proper operation? 5.Has the gas train been checked for leaks? 6.Is the system sensor mounted in the secondary loop? 7.Is the combustion air damper used? i. Is the end switch wired? ii. Is parameter "out 3" to set to 15 ? 8.Is a step down regulator (service regulator) being used? i. What pressure is the service regulator set at? ii. Is the distance between the service regulator and the boiler greater than 10'? 9.What is the set point (F/C)? 10.What is the CH mode? Please provide the following information with combustion data before contacting Riello Technical Support: (905) 542-0303 Yes No Yes No Yes No No No Yes No Yes No INSERT IMAGE(S) Yes Yes (PLEASE INCLUDE THE RBNA# IN THE EMAIL SUBJECT LINE) Yes No Yes No Yes No Yes No

Upload: others

Post on 14-Feb-2022

2 views

Category:

Documents


0 download

TRANSCRIPT

Array Boiler PRE-CHECK LIST Boiler set-up details (only fill out the boxes that are applicable to the type of fuel used).

1.Is wiring connected correctly and tight?

2.Have the burner safeties been checked for proper operation?

3.Has every boiler safety devices been tested for proper operation?

4.Have the gas shut off valves been verified for proper operation?

5.Has the gas train been checked for leaks?

6.Is the system sensor mounted in the secondary loop?

7.Is the combustion air damper used?

i. Is the end switch wired?

ii. Is parameter "out 3" to set to 15 ?

8.Is a step down regulator (service regulator) being used?

i. What pressure is the service regulator set at?

ii.Is the distance between the service regulator and the boiler greater than 10'?

9.What is the set point (F/C)?

10.What is the CH mode?

Please provide the following information with combustion data before contacting Riello Technical Support: (905) 542-0303

Yes No

Yes No

Yes No

No

No

Yes No

Yes No

INSERT IMAGE(S)

Yes

Yes

(PLEASE INCLUDE THE RBNA# IN THE EMAIL

SUBJECT LINE)

Yes No

Yes No

Yes No

Yes No

MGauntlett
Highlight
MGauntlett
Highlight
MGauntlett
Highlight
MGauntlett
Highlight

Date:

Job Name:

Boiler Model:

Array 1000-2000

Application: Boiler Input:

BTUH:

Notes: Signature:

Boiler Manufacture: Serial Number:

Safeties:

********Correction Factor Formulas

NOx Corrected to 3%O2 = NOx * (17.9/ (20.9 - O2)) SCFM = CFM * (Press/Press+14.7)

Service or Start-up

Array 3000-4000

Type of Fuel

Please provide the following information with combustion data before contacting Riello Technical Support: (905) 542-0303

Select box if the fuel is propane.

Gas And Or Oil Train Parts Models

Array

MOD1

MOD2

MOD3

MOD4

Array 1000

Array 1500

Array 2000

Technician:

BURNER

Load Points

Fan

(RPM)

CO2

(%)

O2

(@3%)

CO

(ppm)

NOX

(%)

Ambient

Temp

(°F)

Flue Gas

Temp

Efficie-

ncy

Inlet

Gas

PSI)

Manifold

Gas

(In WC)

Stack

(In WC)

CHAMBER/FLUE EFFICIENCY WATER

(in WC/ (°F) (%)

Gas Flow

(SCFH)

GAS

Draft

Low

Ign.

High

Low

Ign.

High

Low

Ign.

High

Low

Ign.

High

Speed

Temp

in

Temp

Out

(°F) (°F)

Water

(GPM)

Flow

MGauntlett
Highlight
MGauntlett
Highlight
MGauntlett
Highlight