3.2 2007 ASHRAE HandbookHVAC Applications
Table 1 General Design Criteriaa, b
General Category Specific Category
Inside Design Conditions
Air Movement Circulation, achWinter Summer
DiningandEntertainmentCenters
Cafeterias andLuncheonettes
70 to 74F20 to 30% rh
78Fd
50% rh50 fpm at 6 ftabove floor
12 to 15
Restaurants70 to 74F20 to 30% rh
74 to 78F55 to 60% rh
25 to 30 fpm 8 to 12
Bars70 to 74F20 to 30% rh
74 to 78F50 to 60% rh
30 fpm at 6 ftabove floor
15 to 20
Nightclubs andCasinos
70 to 74F20 to 30% rh
74 to 78F50 to 60% rh
below 25 fpm at 5 ft above floor
20 to 30
Kitchens 70 to 74F 85 to 88F 30 to 50 fpm 12 to 15g
OfficeBuildings
70 to 74F20 to 30% rh
74 to 78F50 to 60% rh
25 to 45 fpm0.75 to 2 cfm/ft2
4 to 10
Museums,Galleries,Libraries,and Archives(also see Chapter 21)
Average68 to 72F
40 to 55% rhbelow 25 fpm 8 to 12
Archival See Chapter 21 below 25 fpm 8 to 12
BowlingCenters
70 to 74F20 to 30% rh
75 to 78F50 to 55% rh
50 fpm at 6 ftabove floor
10 to 15
CommunicationCenters
TelephoneTerminal Rooms
72 to 78F40 to 50% rh
72 to 78F40 to 50% rh
25 to 30 fpm 8 to 20
Radio andTelevision Studios
74 to 78F30 to 40% rh
74 to 78F40 to 55% rh
below 25 fpm at 12 ft above floor
15 to 40
TransportationCenters(also see Chapter 13)
AirportTerminals
70 to 74F20 to 30% rh
74 to 78F50 to 60% rh
25 to 30 fpm at 6 ft above floor
8 to 12
ShipDocks
70 to 74F20 to 30% rh
74 to 78F50 to 60% rh
25 to 30 fpm at 6 ftabove floor
8 to 12
BusTerminals
70 to 74F20 to 30% rh
74 to 78F50 to 60% rh
25 to 30 fpm at 6 ft above floor
8 to 12
Garages j 40 to 55F 80 to 100F 30 to 75 fpm 4 to 6
WarehousesInside design temperatures for warehouses often depend on the materials stored
1 to 4