Produced using Innovation Apex Health and Safety Asset Identifier PHAU00423001 Address WENDOVER, 241-471 & 251A- 256A,THURLOW STREET,AYLESBURY ESTATE,WALWORTH Post Code SE17 2UW Code FRA-PB Version 8 Description FRA-PURPOSE BUILT BLOCKS Assessment Date 15/01/2018 Assessment Version Current Assessor Name Jonathan Conlan

Upload: others

Post on 25-Sep-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Asset Identifier PHAU00423001 Address WENDOVER, 241-471 ...€¦ · The ground and 1st floor are occupied by opened sided car-parking (unused), plant and electrical intake rooms,

Produced using Innovation Apex Health and Safety

Asset Identifier PHAU00423001Address WENDOVER, 241-471 & 251A-

256A,THURLOW STREET,AYLESBURYESTATE,WALWORTH

Post Code SE17 2UW

Code FRA-PBVersion 8Description FRA-PURPOSE BUILT BLOCKS

Assessment Date 15/01/2018Assessment Version CurrentAssessor Name Jonathan Conlan

Page 2: Asset Identifier PHAU00423001 Address WENDOVER, 241-471 ...€¦ · The ground and 1st floor are occupied by opened sided car-parking (unused), plant and electrical intake rooms,

1 CONTENTS

WENDOVER, 241-471 & 251A-256A,THURLOW STREET,AYLESBURY ESTATE,WALWORTH Page 2/26

1.1.............................................................................................................................................

Contents

1.1.1 Contents -

1.1.2 Introduction -

1.1.3 Summary -

1.1.4 General Building Information -

1.1.5 Maintenance Schedules -

1.1.6 Fire Hazards and their Elimination and Control -

1.1.7 Fire Protection Measures -

1.1.8 Management of Fire Safety -

Page 3: Asset Identifier PHAU00423001 Address WENDOVER, 241-471 ...€¦ · The ground and 1st floor are occupied by opened sided car-parking (unused), plant and electrical intake rooms,

2 INTRODUCTION

WENDOVER, 241-471 & 251A-256A,THURLOW STREET,AYLESBURY ESTATE,WALWORTH Page 3/26

2.1.............................................................................................................................................

Introduction

2.1.1 Introduction -

This Fire Risk Assessment (FRA) has been carried out by a competent Fire Risk Assessor onbehalf of the Responsible Person (Southwark Council) in accordance with Article 9 of therequirements of the Regulatory Reform (Fire Safety) Order 2005 (FSO). This report is anassessment of the risk to life from fire and does not address the risk to property or businesscontinuity from fire.

In compliance with the scope of the FSO this FRA is limited to the common areas of thepremises. The site survey undertaken to produce the assessment is limited to a TYPE 1 (non-destructive) survey of common areas only, in accordance with the Responsible Person`sinstructions.

However, where it is deemed relevant, a sample dwelling(s) will be inspected to determine itsrelationship and dependence on the common areas to understand the nature of fire separationbetween dwellings and common areas.

Further investigation may be required by qualified and competent individuals to ascertain theappropriate fitment and fire protection of encased shafts, ducts, risers or voids where asampled non-destructive flat survey cannot confirm this.

In accordance with the limitations of the FSO risk assessment; this report does not include anassessment of external flame spread unless it is identified as impacting on the fire safety ofcommon areas. However, the report may make reference to such issue and/or recommendfurther investigation and assessment if it has been identified as being relevant to the overallfire safety of the premises.

Where appropriate, the FRA will make recommendations to ensure compliance with relevantfire safety legislation. However, it should be understood that this assessment does not replacethe Council's other obligations to carry out fire safety assessments such as those required bythe Health and Housing Safety Rating System (HHSRS) assessment to dwellings undersection 9 of the Housing Act 2004.

This FRA represents the best judgement of the Assessor involved in its preparation, and isbased, in part, on information provided by others.

It is understood by the Assessor that the responsible person has a policy of endeavouring toreduce or maintain the fire safety risk on all it's housing stock to a 'Tolerable' or lower risk level.The FRA includes an Action Plan that sets out measures to enable the Responsible Person toachieve this benchmark risk mitigation level, satisfy the requirements of the FSO and to protectRelevant Persons (as defined in Article 2 of the FSO), from the risks of fire.

Page 4: Asset Identifier PHAU00423001 Address WENDOVER, 241-471 ...€¦ · The ground and 1st floor are occupied by opened sided car-parking (unused), plant and electrical intake rooms,

3 SUMMARY

WENDOVER, 241-471 & 251A-256A,THURLOW STREET,AYLESBURY ESTATE,WALWORTH Page 4/26

3.1.............................................................................................................................................

Summary

3.1.1 Risk Rating HIGH MODERATE

Trivial: These risks are considered acceptable. No further action is necessary other than toensure that the controls are maintained.

Tolerable: No additional actions are required unless they can be implemented at very low cost(in terms of time, money and effort). Actions to further reduce these risks are assigned lowpriority. Arrangements should be made to ensure that the controls are maintained andmonitored

Low Moderate: Consideration should be given as to lowering the risk where applicable, to atolerable level, and preferably to a trivial level, but the costs of additional risk reductionmeasures should be taken into account unless these are managerial issues. The risk reductionmeasures should be implemented within a defined time period. Arrangements should be madeto ensure that the controls are maintained and monitored.

High Moderate: Considerable efforts should be made to reduce the risk to a tolerable level, andpreferably to a trivial level, but the costs of additional risk reduction measures may be takeninto account unless these are managerial issues.The risk reduction measures should be implemented within a defined time period.Arrangements should be made to ensure that the controls are maintained and monitored.

Substantial: Substantial efforts should be made to reduce the risk. Risk reduction measuresshould be implemented urgently within a defined time period. Consideration should be given tosuspending or restricting the use, or to apply interim control measures, until this has beencompleted. Controls should be maintained and monitored. Consideration should be given toconsulting with the Enforcing Authority.

Intolerable: These risks are unacceptable. Substantial improvements in risk controls arenecessary, so that the risk is reduced to a tolerable or trivial level. The activity should be halteduntil risk controls are implemented. If it is not possible to reduce risk the activity should remainprohibited. Enforcing Authority must be consulted.

3.1.2 Next Physical Assessment Due 2019

3.1.3 FRA Type PB

3.1.4 Storeys Ground and Above 14

3.1.5 Storeys Below Ground 0

3.1.6 Units 237

3.1.7 Status COMPLETE

Page 5: Asset Identifier PHAU00423001 Address WENDOVER, 241-471 ...€¦ · The ground and 1st floor are occupied by opened sided car-parking (unused), plant and electrical intake rooms,

3 SUMMARY

WENDOVER, 241-471 & 251A-256A,THURLOW STREET,AYLESBURY ESTATE,WALWORTH Page 5/26

3.1.8 Building Dimensions. Length, width and height.

170m x 20m x 35m

3.1.9 List any tasks that once completed can reduce the risk ratingof this assessment.

Repair the broken bin chute hopperManage the housekeeping and anti social behaviour issues within the blockReplace the three broken FEDS

3.1.10 Does this assessment require a review? Yes No N/A

Page 6: Asset Identifier PHAU00423001 Address WENDOVER, 241-471 ...€¦ · The ground and 1st floor are occupied by opened sided car-parking (unused), plant and electrical intake rooms,

4 GENERAL BUILDING INFORMATION

WENDOVER, 241-471 & 251A-256A,THURLOW STREET,AYLESBURY ESTATE,WALWORTH Page 6/26

4.1.............................................................................................................................................

General Building Information

4.1.1 Building information

Purpose built block of flats with a structure of concrete floors, frame, stairwells, and a flat roof.The external envelope comprises precast concrete walls, brick/block infills, uPVC windows tothe flats and steel framed windows to the staircases and protected access corridors. Thebuilding has four protected staircases linked with an open balcony at the second floor andprotected corridors on the upper even floor levels.The building forms a block of flats over 14 floors with a foot print of approx 20m x 200m (thebuilding reduces to approx 11m deep over the second floor deck level) containing 237maisonettes and single storey flats. Entry to the building is unrestricted via the four stairwellsand second floor access deck which has two external stairs leading to ground. The stair coreswill be refered to as follows Core1 being the stair nearest the Aylesbury centre (North end ofthe block) and Core 4 at the South end.

The ground and 1st floor are occupied by opened sided car-parking (unused), plant andelectrical intake rooms, lock-up store and commercial units (access was restricted preventinginspection of these areas). The commercial units are out of the scope of this assessment. Atthe north end of the block there is a separate unit occupying first, second and third floors,which is occupied by Aylesbury Enterprise Youth Centre and offices. This area falls outside theremit of this assessment and was not inspected. There are four lifts located in pairs within thetwo middle staircases 4031/4032 within core 2, 4033/4034 within core 3 serving even floorsonly.The second floor Flat Entrance Doors (FEDs) open onto an open access balcony with twodirections of escape. The flats on the third floor enter from an open balcony located betweenthe South staircase and the next staircase containing lifts4031/4032, there are two directions of travel from all FEDs. The dwellings on the upper floorsenter into protected corridors spanning the whole length of the building subdivided into asections (approximately 33m) by cross corridor doors or lift lobbies. The maximum traveldistance within the access corridors is approximately 15m with two directions of escape fromall FEDs. There are flats at the South end of the block which FEDs open to two storey stairlobbies with an mezzanine design located in between the South staircase and the accesscorridors. There are separate utility stairs within the lobbies leading up to the odd floor levels.There are two flats entering from each odd or even floor level at the South end lobbies. Smalllobby areas are provided with FD30S SC doors to give a lobby protection to the utility stairs.There are two means of escape from all FEDs. Stair core 4 provides access to dwellings onodd floor levels, cores 1-3 levels also provide access to building service areas and intakerooms most of which were accessible during the inspection. Lift rooms are accessible fromsecurity doors at the top of the middle stair cores. There is a bin chute within the Northstaircase with refuse areas at ground level housing large commercial metal skips. The largehopper hatches are enclosed by FD60S SC doors to prevent smoke from fire in the bin roomentering the staircase. There are private rubbish storage cupboards along the protectedcorridors provided with lockable doors. There is are two dry-riser inlets to the front of thebuilding which serve outlets in middle staircase cores within the lift lobby's on the even floorsand externally on the roof level.

No access could be gained to many of the metal doors at ground floor level and the two metaldoors within the 1st and 4th cores at 2nd floor levels.

Page 7: Asset Identifier PHAU00423001 Address WENDOVER, 241-471 ...€¦ · The ground and 1st floor are occupied by opened sided car-parking (unused), plant and electrical intake rooms,

4 GENERAL BUILDING INFORMATION

WENDOVER, 241-471 & 251A-256A,THURLOW STREET,AYLESBURY ESTATE,WALWORTH Page 7/26

Images

(HSA)PHAU00423001-FRA-SITE-3-1-1-4-1-0-34.jpg

4.1.2 Any further building comments?

Flats Layout:2nd floor: 253-241, (251A-3A) Aylesbury Learning Centre3rd floor: 256-254, (254A-6A)4th floor: 257-297,5th floor: 298-299,6th floor: 300-340,7th floor: 341-342,8th floor: 343-383,9th floor: 384-385,10th floor: 386-426,11th floor: 427-428,

12th floor: 429-467,13th floor: 470-471.

The current risk rating of this building is HIGH MODERATE this could be reduced toTOLERABLE if the following actions are completed. All High and Medium risk actions. Due tothe combination of evidence of arson, drug-taking in common areas (smoking and needles),unauthorised access to restricted areas and other antisocial behaviour including use ofcommon areas by those not living in the block. These issues will need to be addressed mainlyby a comprehensive management strategy. This block is due to be demolished by the end of2019.

The scope of The Regulatory Reform ( Fire Safety ) Order 2005 is limited to the common partsof the building, therefore, areas within the dwellings, such as service ducts and ventilationfacilities for kitchens and bathrooms, risers for electrical, water and heating services were notaccessed at the time of this inspection. It is therefore recommended that any future stockcondition surveys or major works projects, take these areas into consideration and findingsrecorded and kept on file.

Page 8: Asset Identifier PHAU00423001 Address WENDOVER, 241-471 ...€¦ · The ground and 1st floor are occupied by opened sided car-parking (unused), plant and electrical intake rooms,

4 GENERAL BUILDING INFORMATION

WENDOVER, 241-471 & 251A-256A,THURLOW STREET,AYLESBURY ESTATE,WALWORTH Page 8/26

The building contains sleeping occupants in protected dwellings. It is not untypical of a socialhousing block or young persons of various ages, physical & mental health abilities andbehavioural styles to be in the premises by way of lawful and unlawful tenancies or visit. It isnot practical to identify all such persons on the premises. It is expected that lone workers areinformed of risks and have appropriate fire instruction & training.

Storeys 14Number of dwellings: 237 Properties are single level flats and maisonettesNumber of lifts: 4 - serving all access floors in pairs within 2 coresNumber of stairwells: 4Exits: 4Roof: Flat

Emergency lighting: YesLightning Conductor: YesDry Riser: yesSecure Entry: noRoof Access: YesVentilation: to stair via PV lift lobbies via openable windows.Refuse chute hatch within staircase.FD30s SC doors to all flat doors and cross corridor doors.FD60 SC to stairwell, lift lobbies and to open balconies.

Page 9: Asset Identifier PHAU00423001 Address WENDOVER, 241-471 ...€¦ · The ground and 1st floor are occupied by opened sided car-parking (unused), plant and electrical intake rooms,

5 MAINTENANCE SCHEDULES

WENDOVER, 241-471 & 251A-256A,THURLOW STREET,AYLESBURY ESTATE,WALWORTH Page 9/26

5.1.............................................................................................................................................

Maintenance Schedules

5.1.1 Maintenance Schedules

All equipment relating to fire fighting and fire protection in the building are subject to scheduled maintenance which is recorded and stored off site. This maintenance will be in line with the requirements and test methods as given in the relevant British standard. Where no such record exists or where maintenance has not been undertaken (or carried out appropriately), the surveyor will make comments in the relevant section. This survey will be updated in the near future to provide the last test dates for all active fire safety measures installed in this building.

Page 10: Asset Identifier PHAU00423001 Address WENDOVER, 241-471 ...€¦ · The ground and 1st floor are occupied by opened sided car-parking (unused), plant and electrical intake rooms,

6 FIRE HAZARDS AND THEIR ELIMINATION ANDCONTROL

WENDOVER, 241-471 & 251A-256A,THURLOW STREET,AYLESBURY ESTATE,WALWORTH Page 10/26

6.1.............................................................................................................................................

Electrical Sources of Ignition

6.1.1 Are there reasonable measures taken to prevent fires ofelectrical origin?

Yes No N/A

6.1.2 Are fixed installations periodically tested and inspected? Yes No N/A

6.1.3 Is the fuseboard/mains intake suitably fire resistant? Yes No N/A

6.1.4 Comments

Southwark Council undertake 5 yearly inspections and testing of the landlord's electricalinstallation. Records of any testing or maintenance are held on the Council's internal database.

No portable appliances were observed in communal areas which would be subject to PATtesting. Portable electrical appliances are used in the common areas by councils own staff andapproved contractors. The council has a system in place for testing its own portableappliances. Those appliances used by contractors are subject to the contractors owncompany's Health and Safety arrangements which are required by the council.

There is a mains electrical/service intake room or cupboards located in every stair core on 5th,7th, 9th and 13th floors. In addition to this there are service rooms on the ground near all staircores.

6.2.............................................................................................................................................

Gas

6.2.1 Is there gas supplied in the area of inspection? Yes No N/A

6.2.2 Is gas equipment protected/located so as to preventaccidental damage?

Yes No N/A

6.2.3 Are gas installations and appliances free from any obviousdefects?

Yes No N/A

6.2.4 Comments

No observations were made on this inspection of any gas installations which may be prone toaccidental damage or have any defects, (gas pipe works was not evident during inspection).The building is heated by a district heating system therefore there should not be any gasboilers within the building, this installation is subject to the councils maintenance and testingregime in accordance with statutory compliance. Records of inspection and testing are held onthe councils database.

6.3.............................................................................................................................................

Smoking

6.3.1 Is there evidence of smoking in areas where this has beenprohibited?

Yes No N/A

Evidence of smoking and the use of controlled substances in the internal common areas wasobserved at the time of inspection. It was witnessed that common areas of the block are beingused by people to smoke drugs. Action within arson section.

6.3.2 Comments

Page 11: Asset Identifier PHAU00423001 Address WENDOVER, 241-471 ...€¦ · The ground and 1st floor are occupied by opened sided car-parking (unused), plant and electrical intake rooms,

6 FIRE HAZARDS AND THEIR ELIMINATION ANDCONTROL

WENDOVER, 241-471 & 251A-256A,THURLOW STREET,AYLESBURY ESTATE,WALWORTH Page 11/26

Evidence of smoking in the internal common areas was observed at the time of inspection.Smoking in the communal areas is not permitted, however it is understood that residents maysmoke within their own dwellings. No Smoking signs have been installed.

6.4.............................................................................................................................................

Arson

6.4.1 Does basic security against arson from outsiders appear to bereasonable?

Yes No N/A

Open access to building with no internal security measures applied. Evidence of previous firesetting was noted in several areas and anti social behaviour appears to be prevalentthroughout the stair cores and intake rooms.

No evidence of rough sleeping was noted at the time of assessment and many of the issueshighlighted in the previous FRA (25/07/17) were seen to have been rectified - Regular cleaningand inspection regimes appear to have been set up within the building.

6.4.2 Is there an unnecessary fire load within the building or in closeproximity of the premises which is available to ignition fromoutsiders?

Yes No N/A

Although minor infringements were noted the communal areas were generally in a cleancondition.

6.4.3 Is there any shrubbery that needs pruning or removing toprevent fire spread if ignited?

Yes No N/A

6.4.4 Comments

6.5.............................................................................................................................................

Portable Heaters and Heating Installations

6.5.1 Does the area of inspection have any portable heaters orheating installations?

Yes No N/A

No heating installation provided within the common areas.

6.6.............................................................................................................................................

Lightning

6.6.1 Does the premises have a lightning protection system? Yes No N/A

6.6.2 Comments

The lightning conductor system is inspected and tested annually in accordance with BS EN62305. All records of such inspecting and testing are held centrally at Southwark Council`soffices.

6.7.............................................................................................................................................

Housekeeping

6.7.1 Is the standard of housekeeping adequate? Yes No N/A

Page 12: Asset Identifier PHAU00423001 Address WENDOVER, 241-471 ...€¦ · The ground and 1st floor are occupied by opened sided car-parking (unused), plant and electrical intake rooms,

6 FIRE HAZARDS AND THEIR ELIMINATION ANDCONTROL

WENDOVER, 241-471 & 251A-256A,THURLOW STREET,AYLESBURY ESTATE,WALWORTH Page 12/26

At the time of assessment it was evident that housekeeping has been much improved sincethe last FRA, however, a discarded sofa was stored on the 3rd floor open balcony. Rubbishbags were noted in various areas but a cleaning operation was under way to remove themduring the time the assessment was ongoing.

Bin store cupboards provided for each dwelling were found to be open and containing rubbishand personal effects, the bin stores should be emptied and kept locked shut.

6.7.2 Are combustible materials separated from any sources ofignition?

Yes No N/A

Combustibles stored within electrical intake - see 6.7.1

6.7.3 Comments

It was observed that rubbish and residents personal effects were being stored in some areas.These items may present a significant risk to safe escape/fire spread/access for emergencyservices, and should therefore be removed in accordance with the councils Zero TolerancePolicy. The council should ensure regular inspections are carried out and robust reinforcementis applied to maintain clear common areas.

6.8.............................................................................................................................................

Dangerous Substances

6.8.1 Are there any hazardous substances in the area ofinspection?

Yes No N/A

6.8.2 Are the general fire precautions adequate to address thehazards associated with dangerous substances used andstored on the premises?

Yes No N/A

6.8.3 Comments

No dangerous substances noted

6.9.............................................................................................................................................

Hazards Introduced by Contractors or Works

6.9.1 Are there contractors or works taking place in the area ofinspection?

Yes No N/A

6.9.2 Is there satisfactory control over works carried out by the onsite contractors (including hot works permits)?

Yes No N/A

6.9.3 Comments

Page 13: Asset Identifier PHAU00423001 Address WENDOVER, 241-471 ...€¦ · The ground and 1st floor are occupied by opened sided car-parking (unused), plant and electrical intake rooms,

6 FIRE HAZARDS AND THEIR ELIMINATION ANDCONTROL

WENDOVER, 241-471 & 251A-256A,THURLOW STREET,AYLESBURY ESTATE,WALWORTH Page 13/26

No hot works were being carried out at the time of the inspection. The building is slowly beingdecanted over the next 18 months so as a property becomes vacant it is mothballed andboarded over, currently the boarding up is done with steel uni strut and plate spot welded overthe FED, although no evidence of incorrect or improper works was noted, the ceilingdecoration in each protected corridor is delaminating and in a parlous state, any incorrect hotworks may result in rapid flame spread due to the poor decoration, it is recommended thatpaintwork is scraped back to substrate to reduce the opportunity for flame spread. Issue dealtwith in 7.1.2

Contractors carrying out work at Southwark Council premises are pre-selected from anapproved list. They will have undergone a selection and training process prior to being allowedto carry out work at council premises. All contractors should receive a permit to work. Thereshould be no reliance on council staff to perform safety checks on hot works carried out bycontractor.

Page 14: Asset Identifier PHAU00423001 Address WENDOVER, 241-471 ...€¦ · The ground and 1st floor are occupied by opened sided car-parking (unused), plant and electrical intake rooms,

7 FIRE PROTECTION MEASURES

WENDOVER, 241-471 & 251A-256A,THURLOW STREET,AYLESBURY ESTATE,WALWORTH Page 14/26

7.1.............................................................................................................................................

Measures to Prevent Fire Spread and Development

7.1.1 Is compartmentation suitable? Yes No N/A

Panels to service cupboards near FEDs are loose or not fixed in place in numerous location:Near FEDs - all to be refixed.

Access to wet service risers is via an FD30 door, 1 per every 2 dwellings. On opening thisFD30 access door it was evident that panels within the riser had been removed in virtually allrooms thus providing direct access into the dwellings via the bathroom, although the risk isminimal panels within the rooms should be replaced to ensure compartmental integrity to eachdwelling, access rooms should be kept sterile and locked at all times

7.1.2 Is there reasonable limitation of linings that might promote firespread?

Yes No N/A

No hot works were being carried out at the time of the inspection. The building is slowly beingdecanted over the next 18 months so as a property becomes vacant it is mothballed andboarded over, currently the boarding up is done with steel uni strut and plate spot welded overthe FED, although no evidence of incorrect or improper works was noted, the ceilingdecoration in each protected corridor is delaminating and in a parlous state, any incorrect hotworks may result in rapid flame spread due to the poor decoration, it is recommended thatpaintwork is scraped back to substrate to reduce the opportunity for flame spread.

Images

(HSA)PHAU00423001-FRA-SITE-3-1-1-4-1-0-46.jpg

(HSA)PHAU00423001-FRA-SITE-3-1-1-4-1-0-51.jpg

7.1.3 Where ducting is provided can it be ascertained if firedampers are provided to prevent the spread of fire throughcompartments to protect the means of escape?

Yes No N/A

7.1.4 Comments

Page 15: Asset Identifier PHAU00423001 Address WENDOVER, 241-471 ...€¦ · The ground and 1st floor are occupied by opened sided car-parking (unused), plant and electrical intake rooms,

7 FIRE PROTECTION MEASURES

WENDOVER, 241-471 & 251A-256A,THURLOW STREET,AYLESBURY ESTATE,WALWORTH Page 15/26

It is considered that the concrete slab and brick/block construction will provide the required fireseparation. However this form of construction is subject to general building conditions of age,and incorrectly installed/maintained services/works that can lead to smoke or fire spread. Forthis standard of construction we deem this risk to be medium to low. Any riser within thebuilding requires inspection for fire stopping between floors. These risks are continuallymonitored through post fire investigation and the void process. The common parts internalwalls are in a good order but it was not possible to ascertain the construction of compartmentwalls and floors within the individual flats. LBS have an ongoing programme of type 4 surveysto meet this risk.

Individual flats have boilers which are vented to an outside wall and external service vents areprovided in the building. Any internal service ducting should be inspected for fire stoppingbetween compartments. LBS have an ongoing programme of type 4 surveys to meet this risk.

No ventilation ducts were identified in communal areas which would allow the spread of fire orsmoke to other parts of the building. It should be confirmed however that no ducts exist insidethe flats which may allow the spread of fire or smoke to other flats or other parts of the building.

Access to the roof areas was not gained; LB Southwark has an ongoing programme of roofinspections.

No internal inspection of dampers/ducts and concealed spaces within the dwelling themselveshas been undertaken as part of this assessment. It is recommended that these areas areperiodically inspected and upgraded where required to ensure adequate fire protection andcompartmentation throughout the property. Ensure that there is adequate provision to preventthe spread of fire and smoke between ducts and concealed spaces.

7.2.............................................................................................................................................

Means of Escape from Fire

7.2.1 Are there adequate provisions for exits in the area assessed? Yes No N/A

7.2.2 Are exits immediately openable where necessary? Yes No N/A

All other upper flats have a separate balcony escape originally designed to allow accessthrough a pass door within the balconies at a different level to the FED it assumed that thisthen allows access back into the building through a neighbours flat. It was noted that all theescape balconies were blocked by personal storage, this secondary MOE is considereduntenable. From a sample inspection these maisonettes had a protected internal stair and Pt6LD2 Grade D alarm system installed and cross corridor doors now restrict their travel distanceto 15m within a protected ventilated corridor.

7.2.3 Are the means for securing the exit doors appropriate? Yes No N/A

7.2.4 Is there suitable protection for the escape routes? This is toinclude any glazing.

Yes No N/A

Attention is drawn to a more detailed internal flat inspection which was carried out by(LBS Fire Safety Surveyor) around the 3rd July 2017 and the following was found:

Within the dwellings most doors were found to be existing fire doors in acceptable condition.However, some bedroom doors were hollow-core doors which will not meet a fire resistantstandard. Where the kitchen and living room are semiopen plan smoke detection has not beenprovided in the living room area. (fire detection devices were located in all other areas). In lightof this the following would be required to mitigate for the removal of the secondary escape: Alldoors within the dwellings should be FD30 fire doors (with exception of bathrooms and WCs).Given the risk fire detection should be provided to hall/stairs, bedrooms, living rooms andkitchens. This would include a smoke device in the living room where semi-open plan to akitchen.

7.2.5 Are there any inner room scenarios? Yes No N/A

Page 16: Asset Identifier PHAU00423001 Address WENDOVER, 241-471 ...€¦ · The ground and 1st floor are occupied by opened sided car-parking (unused), plant and electrical intake rooms,

7 FIRE PROTECTION MEASURES

WENDOVER, 241-471 & 251A-256A,THURLOW STREET,AYLESBURY ESTATE,WALWORTH Page 16/26

7.2.6 Are the escape routes free from obstructions orelectrical/telecom installations likely to give rise to anobstruction in the event of a fire?

Yes No N/A

Individual flat entrance doors and the main front entrance door all open inwards against thedirection of escape. However, this is acceptable due to the nature of the premises and the lowevacuation requirements. It was noted through sampling that FEDs have mortise locks fittedwhich will prevent/delay escape through the door without the use of a key. It is considered thatthis met the standard at the time the door was installed and acceptable pending the renewal ofthe door through a planned programme of FED replacement to meet the current standard orthe final decant of the building which will precede demolitionIt is recommended that all final exit doors to open balcony escapes within the maisonettes arefitted with single action locks, which do not require a key to open them internally. Rather thanexpend funds and resources to remedy this issue it is advised that LBS take a view on thenecessity of this recommendation based on time frame to full building decant.There were communication and electrical cables running above the FED to flat and in frontof each FED on the 3rd floor open balcony, these cables could become involved in any fireallowing them to drop presenting an entrapment risk to occupiers or firefighters. These cablesshould be fixed securely within a metal conduit or with substantial metal fixings.

7.2.7 Do any doors have additional security grilles or gates fittedover the means of escape that will hamper an individual in theevent of a fire?

Yes No N/A

7.2.8 Where final exit doors are fitted with electrical overrides toopen will this door open in the event of an electrical failure?

Yes No N/A

7.2.9 Do the travel distances in the common areas comply withthose escape distances specified in current/previous buildingregulations?

Yes No N/A

7.2.10 Comments

The building is approximately 40m (14 floors) from the ground to the to (habitable) upper floorsurface in height, 170m in length and 20m (the building reduces to approx 10.m deep over thesecond floor deck level) wide giving a square footprint of 800m2. Entrance to dwellings on thesecond floor upwards. The internal dwelling layout could not be confirmed by externalinspection, there was a limited access provided by residents. A defend in place escapestrategy has been adopted for the building. Where this type of strategy is adopted currentguidance makes the following assumptions:1. A high degree of compartmentation which would ensure a reduced probability of firespread beyond the residence of origin.2. The enclosure of communal staircases to form protected staircases.3. The enclosure of common access corridors to form protected routes.4. Provision of smoke ventilating systems to maintain the escape routes clear of smoke.Individual flat entrance doors all open inwards against the direction of escape. However, this isacceptable due to the nature of the premises and the low evacuation requirements.

Page 17: Asset Identifier PHAU00423001 Address WENDOVER, 241-471 ...€¦ · The ground and 1st floor are occupied by opened sided car-parking (unused), plant and electrical intake rooms,

7 FIRE PROTECTION MEASURES

WENDOVER, 241-471 & 251A-256A,THURLOW STREET,AYLESBURY ESTATE,WALWORTH Page 17/26

Means of escape: The second floor Flat Entrance Doors (FEDs) open onto an open accessbalcony with two directions of escape. FEDs on the fifth and eighth floor open on to protectedcorridors, mostly with two directions of escape with the only exception being dwellings at eitherend of the blockwith have a single means of escape (FEDs ). The dwellingswith dead end conditions from the FED have a second means of escape through privatebalconies which lead to doors entering the stairwells in stair-cores 1 and 5 at a different level tothe FED. All other upper flats have a separate balcony escape originally designed to allowaccess through a pass door within the balconies at a different level to the FED it assumed thatthis then allows access back into the building through a neighbours flat. It was noted that allthe escape balconies were blocked by personal storage and the escape doors into thestairwells could not be accessed to confirm they are servicable. These maisonettes have aprotected internal stair and Pt6 LD2 Grade D alarm system installed and cross corridor doorsnow restrict their travel distance to 15m within a protected ventilated corridor. On the 5th and8th floor flat entrance doors lead into a ventilated corridor less than 30 metres in lengthbetween cross corridor doors with two directions of escape, with the exception of the flats ateither end of the block which have a single means of escape. These corridors lead into lobbies(with lifts in cores 2-4) and then stairs which are ventilated. In two instances the escapedistance for dwellings with single direction of escape is in excess of 7.5metres (approx 15metres), corridors serving flats it appears these dwellings weredesigned with an alternative means of escape via crossover balconies and a door leadingdirectly on to the stairs in core 5 which must be secured for their use to compensate forextended travel dead end conditions within the corridor.The second floor FEDs open onto a wide open access deck 3.6 m wide, with doors recessedapprox 2.2m beyond this. All FEDs have two directions of escape along the access balcony tointernal stairwells and external stairs to rear. Travel distances are in accordance withdiagram8/table 1 with AD B (corridors) and section 7.3 of BS9991 (open access decks) to allflats and exit capacities would be acceptable for the number of persons in residence. This isassuming the secondary MOE to the flats with dead end conditions is available to them.There was a limited access into the maisonettes but those inspected had FD20 internal doorsand LD2 fire alarm system

7.3.............................................................................................................................................

Emergency Escape Lighting

7.3.1 Is Emergency Lighting provided and if so is there fullcompliance?

Yes No N/A

7.3.2 Comments

Emergency lighting has been installed within the building. It must be assumed that it is installedin line with BS5266: Pt. 1: 2011

7.4.............................................................................................................................................

Fire Safety Signs and Notices

7.4.1 Is there reasonable provision for all notices? Yes No N/A

7.4.2 Is there suitable signage for automatic, self closing and lockedfire doors?

Yes No N/A

7.4.3 Is the fire action notice fitted in the correct area and displayingthe correct information?

Yes No N/A

7.4.4 Are the 'No Smoking' signs fitted and are there sufficientnotices?

Yes No N/A

Page 18: Asset Identifier PHAU00423001 Address WENDOVER, 241-471 ...€¦ · The ground and 1st floor are occupied by opened sided car-parking (unused), plant and electrical intake rooms,

7 FIRE PROTECTION MEASURES

WENDOVER, 241-471 & 251A-256A,THURLOW STREET,AYLESBURY ESTATE,WALWORTH Page 18/26

7.4.5 Have 'areas of special risks' such as boiler rooms, oiltransformer rooms, switchgear rooms and telecommunicationrooms been appropriately signed?

Yes No N/A

7.4.6 Comments

Directional escape signage is fitted throughout and is considered acceptable.

7.5.............................................................................................................................................

Means of Giving Warning in Case of Fire

7.5.1 Does the common area of the building have an automaticdetection and warning fire alarm system?

Yes No N/A

7.5.2 Is the extent of the detection fitted appropriate for theoccupancy and fire risk?

Yes No N/A

7.5.3 Is there the remote transmission of alarm signals to an AlarmReceiving Centre in place?

Yes No N/A

7.5.4 Comments

In Line with normal practice for purpose built and converted residential blocks designed tofacilitate a ‘defend in place’ evacuation strategy there is no need for communal automatic firedetection and alarm system to be fitted in the building. Such a system is not normally requiredfor purpose built residential blocks and is not required under the Building Regulations 2010,other than to activate any automatic opening vents.

LB Southwark are undergoing a major program of works to ensure all flats are fitted withsmoke detection, the design of this system is in accordance with BS 5839 (2013) part 6 LD2Grade D.

Random checks on several flats showed smoke detection has been fitted to LD2 grade Dstandard.

7.6.............................................................................................................................................

Smoke Ventilation Requirements

7.6.1 Is it considered that the premises has been provided withreasonable means of smoke ventilation in the event of a fire?

Yes No N/A

7.6.2 Is the building ventilated naturally? Yes No N/A

7.6.3 If permanently ventilated in the common area is theresufficient free area?

Yes No N/A

7.6.4 If permanently ventilated in the stair is there sufficient freearea?

Yes No N/A

7.6.5 Are vents/openings obstructed in any location where they arerequired?

Yes No N/A

7.6.6 Is the building ventilated naturally by AOV's, shutters ordoors?

Yes No N/A

7.6.7 Are detectors that operate AOV's, shutters and vents silentoperating?

Yes No N/A

Page 19: Asset Identifier PHAU00423001 Address WENDOVER, 241-471 ...€¦ · The ground and 1st floor are occupied by opened sided car-parking (unused), plant and electrical intake rooms,

7 FIRE PROTECTION MEASURES

WENDOVER, 241-471 & 251A-256A,THURLOW STREET,AYLESBURY ESTATE,WALWORTH Page 19/26

7.6.8 Is the building ventilated by a mechanical smoke extractionsystem?

Yes No N/A

7.6.9 Comments

Ventilation: Corridors: Eight permanently open vents (POV) each 1.2m x 600mm within each30m corridor section. Ther are also openable windows which have been screwed shut.Staircase: POVs 2x 1.2m x 600mm at each access level. Lobbies: openable windows withrestrictors

7.7.............................................................................................................................................

Fire Brigade Access and Facilities

7.7.1 Is there suitable access for fire appliances with adequateprovision for a turning circle, hammerhead or other point avehicle can turn if required?

Yes No N/A

7.7.2 Are there any obstructions in the form of a gate, bollards orremovable posts that may hinder appliance access?

Yes No N/A

7.7.3 Is the building fitted with either a wet or dry rising main? Yes No N/A

The original dry rising main installation has two inlets at ground floor level and outlets at 2nd,5th, 8th and roof levels. As the building is scheduled for demolition in the near future the LFBhave been appraised of the shortfaslls of the current installled system (e-mailed 31/07/17)

7.7.4 Is the hose distance to the riser or dwelling acceptable? Yes No N/A

7.7.5 Does the front entry door have a firefighter's override? Yes No N/A

7.7.6 Is the current access provision suitable and sufficient forfirefighters? Is there an inappropriate level of security beforeentry is made into an affected dwelling by Firefighters?

Yes No N/A

7.7.7 Where locked do all firefighting facilities have FB locks? Yes No N/A

7.7.8 Are firefighting lifts installed? Yes No N/A

7.7.9 Do the lifts in the area inspected have firefighting overrides? Yes No N/A

7.7.10 Where fitted are all wet/dry riser outlets and inlets accessible? Yes No N/A

7.7.11 Is there suitable signage for firefighting facilities that wouldallow for effective use during firefighting operations?

Yes No N/A

7.7.12 Where panels are fitted for smoke ventilation and fire alarmsystems-have zonal charts been sited in a prominent positionwhich have easy to follow instructions and are accurate?

Yes No N/A

7.7.13 Does the building signage give correct directions to dwellingsin an emergency?

Yes No N/A

7.7.14 Where fitted does the Premises Information Box contain thecorrect and relevant information?

Yes No N/A

7.7.15 Comments

Page 20: Asset Identifier PHAU00423001 Address WENDOVER, 241-471 ...€¦ · The ground and 1st floor are occupied by opened sided car-parking (unused), plant and electrical intake rooms,

7 FIRE PROTECTION MEASURES

WENDOVER, 241-471 & 251A-256A,THURLOW STREET,AYLESBURY ESTATE,WALWORTH Page 20/26

Fire appliance is able to gain access to the building from the main road to the front and toroads at bothe side elevations.

Storage within the common parts will obstruct firefighter access.

Flats and floors levels are clearly numbered.

Fire hydrant is located to both side elevations of the building

The block has a dry riser facility fitted.

7.8.............................................................................................................................................

Fire Doors

7.8.1 Are all dwelling front entry doors and hardware (whererequired) compliant with certification carried out to BS476-22/BSEN 1634-1 or of a suitable notional value? (Considerseals and strips)

Yes No N/A

All doors sampled were notional FD30 SC.

The following FEDS were found to be damaged and will no longer provide the correct period ofresistance, flats

7.8.2 Are all cross corridor, stair and lobby doors certified to a testregime under BS476-22 or BS EN 1634-1 or of a suitablenotional value?

Yes No N/A

The cross corrdior door outside flat is missing an intumescent strip and cold smoke sealon the lock stile

7.8.3 Are all electrical intake/boiler/utility service room doorssuitably fire resistant as tested under the BS476-22 or BS EN1634-1 regime or of a suitable notional value?

Yes No N/A

7.8.4 Are all ancillary doors (in escape routes) suitably fire resistantas tested against BS476-22/BS EN 1634-1 or of suitablenotional value?

Yes No N/A

7.8.5 Are all doors leading to rubbish areas or bin chutes wherethey are in the escape routes suitably tested to BS476-22/BSEN 1634-1 regime or of a suitable notional value?

Yes No N/A

the bin chute hopper on the 6th floor is broken in the open position preventing the bin chutedoor from closing, the hopper requires repair

7.8.6 Do all fire doors have self closing devices compliant with BSEN 1154? Where not applicable are fire doors kept lockedshut?

Yes No N/A

7.8.7 Are any fire doors surveyed at this site constructed ofanything else other than wood?

Yes No N/A

7.8.8 Do doors on the means of escape open in the direction ofescape where necessary?

Yes No N/A

7.8.9 Are doors on the means of escape fitted with appropriatepanic bolts or latches where required?

Yes No N/A

Page 21: Asset Identifier PHAU00423001 Address WENDOVER, 241-471 ...€¦ · The ground and 1st floor are occupied by opened sided car-parking (unused), plant and electrical intake rooms,

7 FIRE PROTECTION MEASURES

WENDOVER, 241-471 & 251A-256A,THURLOW STREET,AYLESBURY ESTATE,WALWORTH Page 21/26

7.8.10 Where applicable are doors appropriate for use by disabledindividuals?

Yes No N/A

7.8.11 Where applicable does the door have a vision panel fitted? Yes No N/A

7.8.12 Comments

FEDs: Timber FD30s SCCross-corridor doors: Timber FD30s SCLobby doors: Metal FD30s SCStair doors: Metal FD30s SCPlant rooms: MetalElectrical riser access rooms: metal .Bin chute doors: Metal FD60s SC

7.9.............................................................................................................................................

External Wall Finish

7.9.1 Is this building over 18 metres in height? Yes No N/A

7.9.2 Does this building have an external cladding system whichoverlays the original structure?

Yes No N/A

7.9.3 Does the building's exterior wall contain infill panels? Yes No N/A

7.9.4 Comments

All buildings at the time of construction and/or alteration the external walls would havecomplied with the building regulations at the time. Southwark Council has an assessmentprocess in place that will ensure the external fabric of a block is compliant to the currentbuilding regulations. This assessment not only includes the external finish of the wall but thematerials used for insulation and fire breaks and how these materials are fixed to the building.

All panels are being examined as part of a process. This includes any that form part of theexternal fascia and those on escape routes with a single direction of escape. Where found tobe deficient or the fire rating cannot be ascertained they will be replaced as part of the MajorWorks programme.

Page 22: Asset Identifier PHAU00423001 Address WENDOVER, 241-471 ...€¦ · The ground and 1st floor are occupied by opened sided car-parking (unused), plant and electrical intake rooms,

8 MANAGEMENT OF FIRE SAFETY

WENDOVER, 241-471 & 251A-256A,THURLOW STREET,AYLESBURY ESTATE,WALWORTH Page 22/26

8.1.............................................................................................................................................

Procedures and Arrangements

8.1.1 Are procedures in the event of fire appropriate and properlydocumented?

Yes No N/A

8.1.2 Have staff and relevant individuals been given appropriate firesafety training?

Yes No N/A

8.1.3 Are checks carried out by staff on fire safety systems whereappropriate and logged?

Yes No N/A

8.1.4 Are external stairs and in particular those devised as a meansof escape regularly inspected, maintained and appropriate foruse in all weathers?

Yes No N/A

8.1.5 Comments

The fire evacuation policy for this building being a purpose built block of flats is; if in aprotected dwelling stay put unless affected by fire or smoke. If in the dwelling on fire or in thecommon parts, leave the building immediately, if safe to do so, and remain a safe distancefrom the building.

It is understood that tenants are provided with a planned evacuation policy in the tenant’sinformation pack which are given to them on tenancy sign up. Additionally fire action noticesdisplayed throughout the building forms a crucial part of the evacuation policy.

It is expected that the person discovering the fire will summon the fire service by telephone.Details of how to summon the fire service are contained within the tenants pack and on fireaction notices. It is not considered practicable to provide a controlled emergency evacuationassembly point for purpose built blocks of flats. It should be communicated to residents that inthe event of fire, all evacuees should wait in a safe place at a distance from the building so asnot to be affected by smoke, flame, possible explosion and fire fighting. Residents should alsounderstand that they should remain local to be available for liaison with the fire fighting crew.

Council Staff that frequently visit the building are given regular fire safety training. This trainingclearly informs them what to do in the event of fire. Employees from other organisations areexpected to have regular training on carrying out an evacuation in the event of an emergency.The training records are submitted to the council before these persons are allowed to visitcouncil property.

Southwark carry out a strict regime of inspection, testing, repair and maintenance of all buildingservices and systems in accordance with the relevant statutory regulations. Records relevantto testing & maintenance are available for inspection at the council’s offices but not on site as itis not practicable to store them.

Page 23: Asset Identifier PHAU00423001 Address WENDOVER, 241-471 ...€¦ · The ground and 1st floor are occupied by opened sided car-parking (unused), plant and electrical intake rooms,

WENDOVER, 241-471 & 251A-256A,THURLOW STREET,AYLESBURY ESTATE,WALWORTH Page 23/26

Action Plan

Issue No: 6.7.1.1.............................................................................................................................................PriorityLocationFloor

HIGH

Question Is the standard of housekeeping adequate?Issue Discarded sofa left on 3rd floor open baclonyAction remove the discarded sofaStatus ResolvedTarget Date 14/02/2018

Images

(HSA)PHAU00423001-FRA-SITE-3-1-1-4-1-0-60.jpg

Issue No: 6.7.1.2.............................................................................................................................................PriorityLocationFloor

MEDIUM

Question Is the standard of housekeeping adequate?Issue Bin store cupboards provided for each dwelling were found to be open and containing rubbish

and personal effects, the bin stores should be emptied and kept locked shut.Action Due to anti social behaviour issues within the block and evidence of previous fire setting the

bin store cupboards should be removed from use and kept locked shut.Status ResolvedTarget Date 15/04/2018Comments Completed on Work Ref APEX-HSI-1004151.

Images

(HSA)PHAU00423001-FRA-SITE-3-1-1-4-1-0-42.jpg

Issue No: 7.1.1.1.............................................................................................................................................PriorityLocationFloor

MEDIUM

Question Is compartmentation suitable?

Page 24: Asset Identifier PHAU00423001 Address WENDOVER, 241-471 ...€¦ · The ground and 1st floor are occupied by opened sided car-parking (unused), plant and electrical intake rooms,

WENDOVER, 241-471 & 251A-256A,THURLOW STREET,AYLESBURY ESTATE,WALWORTH Page 24/26

Issue Panels to service cupboards near FEDs are loose or not fixed in place in numerous location:Near FEDs - all to be refixed.

Action Replace or refix all access panelsStatus ResolvedTarget Date 15/04/2018

Images

(HSA)PHAU00423001-FRA-SITE-3-1-1-4-1-0-49.jpg

(HSA)PHAU00423001-FRA-SITE-3-1-1-4-1-0-56.jpg

(HSA)PHAU00423001-FRA-SITE-3-1-1-4-1-0-55.jpg

Issue No: 7.1.1.2.............................................................................................................................................PriorityLocationFloor

MEDIUM

Question Is compartmentation suitable?Issue Access to wet service risers is via an FD30 door, 1 per every 2 dwellings. On opening this

FD30 access door it was evident that panels within the riser had been removed in virtually allrooms thus providing direct access into the dwellings via the bathroom, although the risk isminimal panels within the rooms should be replaced to ensure compartmental integrity to eachdwelling, access rooms should be kept sterile and locked at all times

Action Replace missing access panels in each wet riser access cupboard and maintain cupboards inlocked shut position

Status ResolvedTarget Date 15/04/2018

Page 25: Asset Identifier PHAU00423001 Address WENDOVER, 241-471 ...€¦ · The ground and 1st floor are occupied by opened sided car-parking (unused), plant and electrical intake rooms,

WENDOVER, 241-471 & 251A-256A,THURLOW STREET,AYLESBURY ESTATE,WALWORTH Page 25/26

Images

(HSA)PHAU00423001-FRA-SITE-3-1-1-4-1-0-45.jpg

Issue No: 7.2.6.1.............................................................................................................................................PriorityLocationFloor

MEDIUM

Question Are the escape routes free from obstructions or electrical/telecom installations likely to giverise to an obstruction in the event of a fire?

Issue Non metallic means of support can fail when subject to the effects of a fire which may lead towiring systems hanging across escape routes hindering evacuation and firefighting operations.A suitable fire resistant means of support retention must be provided to prevent electricalcables falling across the FED to flat and each flat on the 3rd floor open balcony

Action Remove all plastic cable clips and replace with metal fixingsStatus ResolvedTarget Date 15/04/2018

Images

(HSA)PHAU00423001-FRA-SITE-3-1-1-4-1-0-47.jpg

(HSA)PHAU00423001-FRA-SITE-3-1-1-4-1-0-59.jpg

Issue No: 7.8.1.1.............................................................................................................................................PriorityLocationFloor

HIGH

Question Are all dwelling front entry doors and hardware (where required) compliant with certificationcarried out to BS476-22/BSEN 1634-1 or of a suitable notional value? (Consider seals andstrips)

Page 26: Asset Identifier PHAU00423001 Address WENDOVER, 241-471 ...€¦ · The ground and 1st floor are occupied by opened sided car-parking (unused), plant and electrical intake rooms,

WENDOVER, 241-471 & 251A-256A,THURLOW STREET,AYLESBURY ESTATE,WALWORTH Page 26/26

Issue The following FEDS were found to be damaged and will no longer provide the correct period ofresistance, flats

Action Replace flats with FD30S SCStatus OutstandingTarget Date 14/02/2018

Images

(HSA)PHAU00423001-FRA-SITE-3-1-1-4-1-0-58.jpg

Issue No: 7.8.2.1.............................................................................................................................................PriorityLocationFloor

LOW

Question Are all cross corridor, stair and lobby doors certified to a test regime under BS476-22 or BSEN 1634-1 or of a suitable notional value?

Issue The cross corridor door outside flat is missing an intumescent strip and cold smoke sealon the lock stile

Action Replace missing intumescent strip and cold smoke seal.Status OutstandingTarget Date 15/01/2019

Images

(HSA)PHAU00423001-FRA-SITE-3-1-1-4-1-0-54.jpg

Issue No: 7.8.5.1.............................................................................................................................................PriorityLocationFloor

HIGH

Question Are all doors leading to rubbish areas or bin chutes where they are in the escape routessuitably tested to BS476-22/BS EN 1634-1 regime or of a suitable notional value?

Issue the bin chute hopper on the 6th floor is broken in the open position preventing the bin chutedoor from closing, the hopper requires repair

Action Repair bin chute hopper to allow bin room door to close fullyStatus OutstandingTarget Date 14/02/2018