LonWork / Modbus GEZC Service School Slide 1 of 23

ATS Communication Overview

IBM Compatible

485 Communication link

Viewpoint ATS

Page 2: ATS Communication Overview · Microsoft PowerPoint - ATS Communication Intro R1_1 Author: 208019930 Created Date: 10/17/2007 8:26:21 AM

Contents

1. Introduction

2. LonWork

3. Modbus Cards

4. Modbus Factory Configuration

5. Modbus Test Software

6. ModScan

7. EnerVista Viewpoint Software

8. Modbus Protocol

9. Repeater / Opto-isolator

10. Troubleshooting

11. Frequently Asked Questions (FAQ)

GEZC Service School Slide 2 of 23LonWork / Modbus

Page 3: ATS Communication Overview · Microsoft PowerPoint - ATS Communication Intro R1_1 Author: 208019930 Created Date: 10/17/2007 8:26:21 AM

1. Introduction

IBM Compatible

485 Communication link

Viewpoint ATS

GEZC ATS Controller

• LonWork –

• Proprietary Protocol

• Closed Loop system

• Need binding in the factory

• Modbus –

• Open Architecture

• Configurable Address 1 ~ 247

• Support up to 32 devices.

• One master & Multiple slaves

Slide 3 of 23LonWork / Modbus

Page 4: ATS Communication Overview · Microsoft PowerPoint - ATS Communication Intro R1_1 Author: 208019930 Created Date: 10/17/2007 8:26:21 AM

2. LonWork

GEZC ATS Controller Slide 4 of 23LonWork / Modbus

Page 5: ATS Communication Overview · Microsoft PowerPoint - ATS Communication Intro R1_1 Author: 208019930 Created Date: 10/17/2007 8:26:21 AM

2. LonWork

1. Need rebind if additional units (either annunciators or LonWork cards) are added

GEZC ATS Controller Slide 5 of 23LonWork / Modbus

Page 6: ATS Communication Overview · Microsoft PowerPoint - ATS Communication Intro R1_1 Author: 208019930 Created Date: 10/17/2007 8:26:21 AM

3. Modbus (for MX150/250)

Slide 6 of 23

If MX200/150/250 firmware version is 5.4 or below• use Modbus 1.96• See O&M manual, 50R-2200• Regs up to 48• Card Assy P/N: 50P-1105• Configuration Assy P/N: 50P-1124

GEZC Service School

If MX150/250 firmware version is 6.0 or above• use Modbus 2.1• See O&M manual, 71R-2200• Regs up to 232• Card Assy P/N: 50P-2035• Configuration Assy P/N: 50P-1124

LonWork / Modbus

Page 7: ATS Communication Overview · Microsoft PowerPoint - ATS Communication Intro R1_1 Author: 208019930 Created Date: 10/17/2007 8:26:21 AM

4. Modbus Factory Configuration

Slide 7 of 23

Connection differences between Modbus and MX150/250 Factory Configuration

RS232-to-485 Converter: 50W-1208Belden Shielded Twisted Pair cable:

GEZC Service School

For MX150/250 factory configuration:

1. Connect TD(A) of 50W-1208 to Pin 2 (socket J4) of MX150/250 Controller via PS5133.

2. Connect TD(B) of 50W-1208 to Pin 1 (socket J4) of MX150/250 Controller via PS5133.

For Modbus configuration/communication:

1. Connect TD(A) of 50W-1208 to the upper position via PS5140.

2. Connect TD(B) of 50W-1208 to the lower position via PS5140.

LonWork / Modbus

Page 8: ATS Communication Overview · Microsoft PowerPoint - ATS Communication Intro R1_1 Author: 208019930 Created Date: 10/17/2007 8:26:21 AM

4. Modbus Factory Configuration

Slide 8 of 23

Modbus Factory Configuration Software (50P-1111) Rev 1.8

Belden Twisted Pair cableRS232-to-485 Converter: 50W-1208

Supporting accessory:

One Port USB-232 converter (with GEZC’s part number: 50W-1223 or NI part number: 778472-01) shall be used.

For information about the USB converter, visit --http://sine.ni.com/nips/cds/view/p/lang/en/nid/12844

GEZC Service SchoolLonWork / Modbus

Page 9: ATS Communication Overview · Microsoft PowerPoint - ATS Communication Intro R1_1 Author: 208019930 Created Date: 10/17/2007 8:26:21 AM

4. Modbus Configuration Software (50P-1111)

Slide 9 of 23GEZC Service SchoolLonWork / Modbus

Page 10: ATS Communication Overview · Microsoft PowerPoint - ATS Communication Intro R1_1 Author: 208019930 Created Date: 10/17/2007 8:26:21 AM

4. Modbus Configuration Software (50P-1111)

Slide 10 of 23GEZC Service SchoolLonWork / Modbus

Page 11: ATS Communication Overview · Microsoft PowerPoint - ATS Communication Intro R1_1 Author: 208019930 Created Date: 10/17/2007 8:26:21 AM

5. Modbus Test Software (50P-1170)

Slide 11 of 23GEZC Service SchoolLonWork / Modbus

Page 12: ATS Communication Overview · Microsoft PowerPoint - ATS Communication Intro R1_1 Author: 208019930 Created Date: 10/17/2007 8:26:21 AM

5. Modbus Test Software (50P-1170)

Slide 12 of 23GEZC Service SchoolLonWork / Modbus

Page 13: ATS Communication Overview · Microsoft PowerPoint - ATS Communication Intro R1_1 Author: 208019930 Created Date: 10/17/2007 8:26:21 AM

5. Modbus Test Software (50P-1170)

Slide 13 of 23GEZC Service SchoolLonWork / Modbus

Page 14: ATS Communication Overview · Microsoft PowerPoint - ATS Communication Intro R1_1 Author: 208019930 Created Date: 10/17/2007 8:26:21 AM

6. ModScan Software

Slide 14 of 23

• Need to know register map• ModScan trial version have limited com time

GEZC Service School

Step 1:Open browser to “modscan” folder

Step 2:Double click “ModScan32.exe”

Step 3:Click “OK” without enter info.

Step 4:Wait till OK appears. Then click OK again.

LonWork / Modbus

Page 15: ATS Communication Overview · Microsoft PowerPoint - ATS Communication Intro R1_1 Author: 208019930 Created Date: 10/17/2007 8:26:21 AM

6. ModScan Software

Slide 15 of 23

• Need to know register map• ModScan trial version have limited com time

GEZC Service SchoolLonWork / Modbus

Page 16: ATS Communication Overview · Microsoft PowerPoint - ATS Communication Intro R1_1 Author: 208019930 Created Date: 10/17/2007 8:26:21 AM

7. EnerVista ViewPoint

Slide 16 of 23

GEZC P/N: EnerVista O&M manual: http://www.geindustrial.com/products/manuals/enervista/EVVPmon510.pdfTrial Version can be downloaded at: http://www.geindustrial.com/multilin/enervista/viewpoint/monitoring.htm

GEZC Service SchoolLonWork / Modbus

Page 17: ATS Communication Overview · Microsoft PowerPoint - ATS Communication Intro R1_1 Author: 208019930 Created Date: 10/17/2007 8:26:21 AM

7. EnerVista ViewPoint

Slide 17 of 23

Step 1: Create a device name and intended COM settings (depends on the dominant equipment).Step 2: From the field “Device Type”, select OTHERS. Step 3: From the field “Order Code”, enter MX150 or MX250.Step 4: From the field “Version”, select 5.4x or 6.0x.

GEZC Service SchoolLonWork / Modbus

Page 18: ATS Communication Overview · Microsoft PowerPoint - ATS Communication Intro R1_1 Author: 208019930 Created Date: 10/17/2007 8:26:21 AM

8. Modbus Protocol

Slide 18 of 23

• Supported Modicon functions• 01 -- Coils Read• 03 -- Registers Read• 05 -- Coil Write Single• 06 -- Register Write Single• 15 -- Coil Write Multiple• 16 -- Register Write Multiple

• Query and Response• Handshaking• Exception response• Fn -- 81, 83

GEZC Service SchoolLonWork / Modbus

Page 19: ATS Communication Overview · Microsoft PowerPoint - ATS Communication Intro R1_1 Author: 208019930 Created Date: 10/17/2007 8:26:21 AM

9. Repeater / Opto-Isolator (50W-1225)

Slide 19 of 23

• Optically isolated• Repeater• Support 2-or-4 wires (half duplex and full duplex)• Allows grounding both @ master and slave devices -- No ground loop issue• Product description Link -- http://www.bb-elec.com/product_family.asp?FamilyId=1• Datasheet link -- http://www.bb-elec.com/bb-elec/literature/485OP_2004ds.pdf

GEZC Service SchoolLonWork / Modbus

Page 20: ATS Communication Overview · Microsoft PowerPoint - ATS Communication Intro R1_1 Author: 208019930 Created Date: 10/17/2007 8:26:21 AM

9. Repeater / Opto-Isolator (50W-1225)

Slide 20 of 23GEZC Service School

Data In (A)

Data In (B)

Data Out (A)

Data Out (B)

Signal Gnd

PROT Gnd

Ground

+12VDC

B&BModel: 485OP

RS485 to RS485 Optical Isolator/Repeater

Data In (A)

Data In (B)

Data Out (B)

Signal Gnd

PROT Gnd

RS485 twisted pair(from PLC or PC)

Data Out (A)

(-)(+)

Cable gnd

shield

ModbusAssy

A

B

Connect to MX

chassis ground

J4

1

3

+12V (Output)400mA max.

Circuit Gnd

MX150/250 Controller

Length of cable shall be less than 1 foot to prevent transients pick up from adjacent power line

Wiring Diagram for 485OP Connection

LonWork / Modbus

Page 21: ATS Communication Overview · Microsoft PowerPoint - ATS Communication Intro R1_1 Author: 208019930 Created Date: 10/17/2007 8:26:21 AM

10. Troubleshooting

Slide 21 of 23

Technique of Troubleshooting

• Make sure Network option is ON• For MX150/250 -- can be set in user menu• For MX200 – Must be set in factory mode

GEZC Service SchoolLonWork / Modbus

Page 22: ATS Communication Overview · Microsoft PowerPoint - ATS Communication Intro R1_1 Author: 208019930 Created Date: 10/17/2007 8:26:21 AM

10. Troubleshooting

Slide 22 of 23

Technique of Troubleshooting

• Make sure cable is less than 3000ftOtherwise add repeater.

• Perform local communication1 master – to – 1 slave device

• Perform global communicationa. Configuration via 50P-1111b. EnerVista:

b.1 – Setupb.2 – Plug-n-play

• Have spare (good) devices(I.e. Converter, Modbus card)

GEZC Service SchoolLonWork / Modbus

Page 23: ATS Communication Overview · Microsoft PowerPoint - ATS Communication Intro R1_1 Author: 208019930 Created Date: 10/17/2007 8:26:21 AM

11. Q&A

Slide 23 of 23

• Terminating Resistor – For noise cancellation

• Noise issue due to EMI effect (I.e. Motor drive)

• Typically chassis ground one (master) end of shield but not both.(use Belden shielded pair)

• Network length –• up to 3000 feet• More than 3000 feet will need a repeater

• Need to understand the register map

• Modbus’ connection is polarity specific

• LonWork’s connection is non-polarity specific

• Conversion of Half-to-full duplex or vice versa: Use 50W-1225

GEZC Service SchoolLonWork / Modbus