LonWork / Modbus GEZC Service School Slide 1 of 23
ATS Communication Overview
IBM Compatible
485 Communication link
Viewpoint ATS
![Page 2: ATS Communication Overview · Microsoft PowerPoint - ATS Communication Intro R1_1 Author: 208019930 Created Date: 10/17/2007 8:26:21 AM](https://reader033.vdocument.in/reader033/viewer/2022051919/600b22d87ab4dc1c21580e68/html5/thumbnails/2.jpg)
Contents
1. Introduction
2. LonWork
3. Modbus Cards
4. Modbus Factory Configuration
5. Modbus Test Software
6. ModScan
7. EnerVista Viewpoint Software
8. Modbus Protocol
9. Repeater / Opto-isolator
10. Troubleshooting
11. Frequently Asked Questions (FAQ)
GEZC Service School Slide 2 of 23LonWork / Modbus
![Page 3: ATS Communication Overview · Microsoft PowerPoint - ATS Communication Intro R1_1 Author: 208019930 Created Date: 10/17/2007 8:26:21 AM](https://reader033.vdocument.in/reader033/viewer/2022051919/600b22d87ab4dc1c21580e68/html5/thumbnails/3.jpg)
1. Introduction
IBM Compatible
485 Communication link
Viewpoint ATS
GEZC ATS Controller
• LonWork –
• Proprietary Protocol
• Closed Loop system
• Need binding in the factory
• Modbus –
• Open Architecture
• Configurable Address 1 ~ 247
• Support up to 32 devices.
• One master & Multiple slaves
Slide 3 of 23LonWork / Modbus
![Page 4: ATS Communication Overview · Microsoft PowerPoint - ATS Communication Intro R1_1 Author: 208019930 Created Date: 10/17/2007 8:26:21 AM](https://reader033.vdocument.in/reader033/viewer/2022051919/600b22d87ab4dc1c21580e68/html5/thumbnails/4.jpg)
2. LonWork
GEZC ATS Controller Slide 4 of 23LonWork / Modbus
![Page 5: ATS Communication Overview · Microsoft PowerPoint - ATS Communication Intro R1_1 Author: 208019930 Created Date: 10/17/2007 8:26:21 AM](https://reader033.vdocument.in/reader033/viewer/2022051919/600b22d87ab4dc1c21580e68/html5/thumbnails/5.jpg)
2. LonWork
1. Need rebind if additional units (either annunciators or LonWork cards) are added
GEZC ATS Controller Slide 5 of 23LonWork / Modbus
![Page 6: ATS Communication Overview · Microsoft PowerPoint - ATS Communication Intro R1_1 Author: 208019930 Created Date: 10/17/2007 8:26:21 AM](https://reader033.vdocument.in/reader033/viewer/2022051919/600b22d87ab4dc1c21580e68/html5/thumbnails/6.jpg)
3. Modbus (for MX150/250)
Slide 6 of 23
If MX200/150/250 firmware version is 5.4 or below• use Modbus 1.96• See O&M manual, 50R-2200• Regs up to 48• Card Assy P/N: 50P-1105• Configuration Assy P/N: 50P-1124
GEZC Service School
If MX150/250 firmware version is 6.0 or above• use Modbus 2.1• See O&M manual, 71R-2200• Regs up to 232• Card Assy P/N: 50P-2035• Configuration Assy P/N: 50P-1124
LonWork / Modbus
![Page 7: ATS Communication Overview · Microsoft PowerPoint - ATS Communication Intro R1_1 Author: 208019930 Created Date: 10/17/2007 8:26:21 AM](https://reader033.vdocument.in/reader033/viewer/2022051919/600b22d87ab4dc1c21580e68/html5/thumbnails/7.jpg)
4. Modbus Factory Configuration
Slide 7 of 23
Connection differences between Modbus and MX150/250 Factory Configuration
RS232-to-485 Converter: 50W-1208Belden Shielded Twisted Pair cable:
GEZC Service School
For MX150/250 factory configuration:
1. Connect TD(A) of 50W-1208 to Pin 2 (socket J4) of MX150/250 Controller via PS5133.
2. Connect TD(B) of 50W-1208 to Pin 1 (socket J4) of MX150/250 Controller via PS5133.
For Modbus configuration/communication:
1. Connect TD(A) of 50W-1208 to the upper position via PS5140.
2. Connect TD(B) of 50W-1208 to the lower position via PS5140.
LonWork / Modbus
![Page 8: ATS Communication Overview · Microsoft PowerPoint - ATS Communication Intro R1_1 Author: 208019930 Created Date: 10/17/2007 8:26:21 AM](https://reader033.vdocument.in/reader033/viewer/2022051919/600b22d87ab4dc1c21580e68/html5/thumbnails/8.jpg)
4. Modbus Factory Configuration
Slide 8 of 23
Modbus Factory Configuration Software (50P-1111) Rev 1.8
Belden Twisted Pair cableRS232-to-485 Converter: 50W-1208
Supporting accessory:
One Port USB-232 converter (with GEZC’s part number: 50W-1223 or NI part number: 778472-01) shall be used.
For information about the USB converter, visit --http://sine.ni.com/nips/cds/view/p/lang/en/nid/12844
GEZC Service SchoolLonWork / Modbus
![Page 9: ATS Communication Overview · Microsoft PowerPoint - ATS Communication Intro R1_1 Author: 208019930 Created Date: 10/17/2007 8:26:21 AM](https://reader033.vdocument.in/reader033/viewer/2022051919/600b22d87ab4dc1c21580e68/html5/thumbnails/9.jpg)
4. Modbus Configuration Software (50P-1111)
Slide 9 of 23GEZC Service SchoolLonWork / Modbus
![Page 10: ATS Communication Overview · Microsoft PowerPoint - ATS Communication Intro R1_1 Author: 208019930 Created Date: 10/17/2007 8:26:21 AM](https://reader033.vdocument.in/reader033/viewer/2022051919/600b22d87ab4dc1c21580e68/html5/thumbnails/10.jpg)
4. Modbus Configuration Software (50P-1111)
Slide 10 of 23GEZC Service SchoolLonWork / Modbus
![Page 11: ATS Communication Overview · Microsoft PowerPoint - ATS Communication Intro R1_1 Author: 208019930 Created Date: 10/17/2007 8:26:21 AM](https://reader033.vdocument.in/reader033/viewer/2022051919/600b22d87ab4dc1c21580e68/html5/thumbnails/11.jpg)
5. Modbus Test Software (50P-1170)
Slide 11 of 23GEZC Service SchoolLonWork / Modbus
![Page 12: ATS Communication Overview · Microsoft PowerPoint - ATS Communication Intro R1_1 Author: 208019930 Created Date: 10/17/2007 8:26:21 AM](https://reader033.vdocument.in/reader033/viewer/2022051919/600b22d87ab4dc1c21580e68/html5/thumbnails/12.jpg)
5. Modbus Test Software (50P-1170)
Slide 12 of 23GEZC Service SchoolLonWork / Modbus
![Page 13: ATS Communication Overview · Microsoft PowerPoint - ATS Communication Intro R1_1 Author: 208019930 Created Date: 10/17/2007 8:26:21 AM](https://reader033.vdocument.in/reader033/viewer/2022051919/600b22d87ab4dc1c21580e68/html5/thumbnails/13.jpg)
5. Modbus Test Software (50P-1170)
Slide 13 of 23GEZC Service SchoolLonWork / Modbus
![Page 14: ATS Communication Overview · Microsoft PowerPoint - ATS Communication Intro R1_1 Author: 208019930 Created Date: 10/17/2007 8:26:21 AM](https://reader033.vdocument.in/reader033/viewer/2022051919/600b22d87ab4dc1c21580e68/html5/thumbnails/14.jpg)
6. ModScan Software
Slide 14 of 23
• Need to know register map• ModScan trial version have limited com time
GEZC Service School
Step 1:Open browser to “modscan” folder
Step 2:Double click “ModScan32.exe”
Step 3:Click “OK” without enter info.
Step 4:Wait till OK appears. Then click OK again.
LonWork / Modbus
![Page 15: ATS Communication Overview · Microsoft PowerPoint - ATS Communication Intro R1_1 Author: 208019930 Created Date: 10/17/2007 8:26:21 AM](https://reader033.vdocument.in/reader033/viewer/2022051919/600b22d87ab4dc1c21580e68/html5/thumbnails/15.jpg)
6. ModScan Software
Slide 15 of 23
• Need to know register map• ModScan trial version have limited com time
GEZC Service SchoolLonWork / Modbus
![Page 16: ATS Communication Overview · Microsoft PowerPoint - ATS Communication Intro R1_1 Author: 208019930 Created Date: 10/17/2007 8:26:21 AM](https://reader033.vdocument.in/reader033/viewer/2022051919/600b22d87ab4dc1c21580e68/html5/thumbnails/16.jpg)
7. EnerVista ViewPoint
Slide 16 of 23
GEZC P/N: EnerVista O&M manual: http://www.geindustrial.com/products/manuals/enervista/EVVPmon510.pdfTrial Version can be downloaded at: http://www.geindustrial.com/multilin/enervista/viewpoint/monitoring.htm
GEZC Service SchoolLonWork / Modbus
![Page 17: ATS Communication Overview · Microsoft PowerPoint - ATS Communication Intro R1_1 Author: 208019930 Created Date: 10/17/2007 8:26:21 AM](https://reader033.vdocument.in/reader033/viewer/2022051919/600b22d87ab4dc1c21580e68/html5/thumbnails/17.jpg)
7. EnerVista ViewPoint
Slide 17 of 23
Step 1: Create a device name and intended COM settings (depends on the dominant equipment).Step 2: From the field “Device Type”, select OTHERS. Step 3: From the field “Order Code”, enter MX150 or MX250.Step 4: From the field “Version”, select 5.4x or 6.0x.
GEZC Service SchoolLonWork / Modbus
![Page 18: ATS Communication Overview · Microsoft PowerPoint - ATS Communication Intro R1_1 Author: 208019930 Created Date: 10/17/2007 8:26:21 AM](https://reader033.vdocument.in/reader033/viewer/2022051919/600b22d87ab4dc1c21580e68/html5/thumbnails/18.jpg)
8. Modbus Protocol
Slide 18 of 23
• Supported Modicon functions• 01 -- Coils Read• 03 -- Registers Read• 05 -- Coil Write Single• 06 -- Register Write Single• 15 -- Coil Write Multiple• 16 -- Register Write Multiple
• Query and Response• Handshaking• Exception response• Fn -- 81, 83
GEZC Service SchoolLonWork / Modbus
![Page 19: ATS Communication Overview · Microsoft PowerPoint - ATS Communication Intro R1_1 Author: 208019930 Created Date: 10/17/2007 8:26:21 AM](https://reader033.vdocument.in/reader033/viewer/2022051919/600b22d87ab4dc1c21580e68/html5/thumbnails/19.jpg)
9. Repeater / Opto-Isolator (50W-1225)
Slide 19 of 23
• Optically isolated• Repeater• Support 2-or-4 wires (half duplex and full duplex)• Allows grounding both @ master and slave devices -- No ground loop issue• Product description Link -- http://www.bb-elec.com/product_family.asp?FamilyId=1• Datasheet link -- http://www.bb-elec.com/bb-elec/literature/485OP_2004ds.pdf
GEZC Service SchoolLonWork / Modbus
![Page 20: ATS Communication Overview · Microsoft PowerPoint - ATS Communication Intro R1_1 Author: 208019930 Created Date: 10/17/2007 8:26:21 AM](https://reader033.vdocument.in/reader033/viewer/2022051919/600b22d87ab4dc1c21580e68/html5/thumbnails/20.jpg)
9. Repeater / Opto-Isolator (50W-1225)
Slide 20 of 23GEZC Service School
Data In (A)
Data In (B)
Data Out (A)
Data Out (B)
Signal Gnd
PROT Gnd
Ground
+12VDC
B&BModel: 485OP
RS485 to RS485 Optical Isolator/Repeater
Data In (A)
Data In (B)
Data Out (B)
Signal Gnd
PROT Gnd
RS485 twisted pair(from PLC or PC)
Data Out (A)
(-)(+)
Cable gnd
shield
ModbusAssy
A
B
Connect to MX
chassis ground
J4
1
3
+12V (Output)400mA max.
Circuit Gnd
MX150/250 Controller
Length of cable shall be less than 1 foot to prevent transients pick up from adjacent power line
Wiring Diagram for 485OP Connection
LonWork / Modbus
![Page 21: ATS Communication Overview · Microsoft PowerPoint - ATS Communication Intro R1_1 Author: 208019930 Created Date: 10/17/2007 8:26:21 AM](https://reader033.vdocument.in/reader033/viewer/2022051919/600b22d87ab4dc1c21580e68/html5/thumbnails/21.jpg)
10. Troubleshooting
Slide 21 of 23
Technique of Troubleshooting
• Make sure Network option is ON• For MX150/250 -- can be set in user menu• For MX200 – Must be set in factory mode
GEZC Service SchoolLonWork / Modbus
![Page 22: ATS Communication Overview · Microsoft PowerPoint - ATS Communication Intro R1_1 Author: 208019930 Created Date: 10/17/2007 8:26:21 AM](https://reader033.vdocument.in/reader033/viewer/2022051919/600b22d87ab4dc1c21580e68/html5/thumbnails/22.jpg)
10. Troubleshooting
Slide 22 of 23
Technique of Troubleshooting
• Make sure cable is less than 3000ftOtherwise add repeater.
• Perform local communication1 master – to – 1 slave device
• Perform global communicationa. Configuration via 50P-1111b. EnerVista:
b.1 – Setupb.2 – Plug-n-play
• Have spare (good) devices(I.e. Converter, Modbus card)
GEZC Service SchoolLonWork / Modbus
![Page 23: ATS Communication Overview · Microsoft PowerPoint - ATS Communication Intro R1_1 Author: 208019930 Created Date: 10/17/2007 8:26:21 AM](https://reader033.vdocument.in/reader033/viewer/2022051919/600b22d87ab4dc1c21580e68/html5/thumbnails/23.jpg)
11. Q&A
Slide 23 of 23
• Terminating Resistor – For noise cancellation
• Noise issue due to EMI effect (I.e. Motor drive)
• Typically chassis ground one (master) end of shield but not both.(use Belden shielded pair)
• Network length –• up to 3000 feet• More than 3000 feet will need a repeater
• Need to understand the register map
• Modbus’ connection is polarity specific
• LonWork’s connection is non-polarity specific
• Conversion of Half-to-full duplex or vice versa: Use 50W-1225