Technical Note 427_01 ©Psiber Data Pte Ltd, 2012 _____________________________________________________________________________________ _____________________________________________________________________________________ Psiber Data Pte Ltd www.psiberdata.com Automatic Labeling Schemes in WireXpert WireXpert has a built-in customizable system for convenient and accurate Labeling of the files storing the results of testing at complex locations such as campuses with multiple buildings, floors, rooms and panels. You can configure WireXpert to automatically generate File Labels or enter them manually. Note: This feature is available from software version 4.2.7 onwards. To setup the automatic Labeling scheme, go to Test Settings and select “Label Source”. This will bring you to the “Cable Label Source” screen.

Upload: others

Post on 25-May-2022

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Automatic Labeling Schemes in WireXpert

Technical Note 427_01 ©Psiber Data Pte Ltd, 2012 _____________________________________________________________________________________

_____________________________________________________________________________________ Psiber Data Pte Ltd

www.psiberdata.com

Automatic Labeling Schemes in WireXpert WireXpert has a built-in customizable system for convenient and accurate Labeling of the files storing the results of testing at complex locations such as campuses with multiple buildings, floors, rooms and panels. You can configure WireXpert to automatically generate File Labels or enter them manually. Note: This feature is available from software version 4.2.7 onwards. To setup the automatic Labeling scheme, go to Test Settings and select “Label Source”. This will bring you to the “Cable Label Source” screen.

Page 2: Automatic Labeling Schemes in WireXpert

Technical Note 427_01 ©Psiber Data Pte Ltd, 2012 _____________________________________________________________________________________

_____________________________________________________________________________________ Psiber Data Pte Ltd

www.psiberdata.com

The “Cable Label Source” screen shows a list of options for generating the file names, from (top-down) manual, to simple automatic generation, and more complex automatic Labeling schemes. The current Labeling scheme is also illustrated at the bottom of the screen (in the screenshot below, “None” appears because the current option is manual input).

To use a Simple Cable Label, select “Simple Auto-Increment Labels”.

Page 3: Automatic Labeling Schemes in WireXpert

Technical Note 427_01 ©Psiber Data Pte Ltd, 2012 _____________________________________________________________________________________

_____________________________________________________________________________________ Psiber Data Pte Ltd

www.psiberdata.com

Configuring Simple Cable Label Scheme You will be first prompted to enter a Label Name. The Label Name is fixed for all the files and can be a mix of letters and symbols. For example, in the screenshot below, “A” is used as the Label Name.

Click “” when done entering the Label Name.

Page 4: Automatic Labeling Schemes in WireXpert

Technical Note 427_01 ©Psiber Data Pte Ltd, 2012 _____________________________________________________________________________________

_____________________________________________________________________________________ Psiber Data Pte Ltd

www.psiberdata.com

In the next screen, you can edit the Start/End Values, which specify the range of numbers which will be appended to the filenames, for example, 1-9999. These numbers will be used to differentiate the filenames, and can be used to represent Autotests at different times/locations. After editing, click “ok”. For the Simple Cable Labeling scheme, WireXpert automatically adds a dash “-” between the Label name and the Label number. With these specifications, the filenames will be generated as “A-1”, “A-2”, … “A-9999”.

Click the tick icon at the bottom right to confirm this as the Labeling scheme.

Page 5: Automatic Labeling Schemes in WireXpert

Technical Note 427_01 ©Psiber Data Pte Ltd, 2012 _____________________________________________________________________________________

_____________________________________________________________________________________ Psiber Data Pte Ltd

www.psiberdata.com

To check that the Labeling scheme has been properly set, at the Test Settings Page, “Label Source” should now show “Simple Labels”, and at the Label Source Page, “Current Label” should appear as “A-1”.

If Autosave is on, a “Save Result” popup will appear after an Autotest showing you the name of the autosaved file.

Page 6: Automatic Labeling Schemes in WireXpert

Technical Note 427_01 ©Psiber Data Pte Ltd, 2012 _____________________________________________________________________________________

_____________________________________________________________________________________ Psiber Data Pte Ltd

www.psiberdata.com

After a series of tests, to see the list of saved files, press the Data button on WireXpert.

Page 7: Automatic Labeling Schemes in WireXpert

Technical Note 427_01 ©Psiber Data Pte Ltd, 2012 _____________________________________________________________________________________

_____________________________________________________________________________________ Psiber Data Pte Ltd

www.psiberdata.com

You can then see a list of most recently saved Autotest files.

Page 8: Automatic Labeling Schemes in WireXpert

Technical Note 427_01 ©Psiber Data Pte Ltd, 2012 _____________________________________________________________________________________

_____________________________________________________________________________________ Psiber Data Pte Ltd

www.psiberdata.com

Modifying Labels during testing While all Labels for all files can be automatically generated according to the Labeling scheme, it is possible to make some manual adjustments. Midway in the process of testing, you may skip a range of numbers and let the numbering continue from a manually input value. In order to do this, Autosave must first be turned off. When Autosave is off, a save icon will appear at the bottom right of the screen after an Autotest. Click on the save icon.

The Edit Label Sequence page will appear, where you can manually edit the name of the current Label. “Current Label” shows the default Label for the current test result (A-5). You may edit the

Page 9: Automatic Labeling Schemes in WireXpert

Technical Note 427_01 ©Psiber Data Pte Ltd, 2012 _____________________________________________________________________________________

_____________________________________________________________________________________ Psiber Data Pte Ltd

www.psiberdata.com

default Label in terms of both the prefix and the position. Note that entering a new position will also restart the numbering of future files from the new number that you enter. For example, if we edit the position to “100”, in the next Autotest, the default Label position will become 101, as shown below. Note the Current Label appears as “A-101”.

Page 10: Automatic Labeling Schemes in WireXpert

Technical Note 427_01 ©Psiber Data Pte Ltd, 2012 _____________________________________________________________________________________

_____________________________________________________________________________________ Psiber Data Pte Ltd

www.psiberdata.com

After subsequent tests, without further manual changes, the resulting file list will appear as such:

Page 11: Automatic Labeling Schemes in WireXpert

Technical Note 427_01 ©Psiber Data Pte Ltd, 2012 _____________________________________________________________________________________

_____________________________________________________________________________________ Psiber Data Pte Ltd

www.psiberdata.com

Configuring a TIA 606A Class 1 Labeling Scheme From the Cable Label Source Page, select “Class 1”.

Page 12: Automatic Labeling Schemes in WireXpert

Technical Note 427_01 ©Psiber Data Pte Ltd, 2012 _____________________________________________________________________________________

_____________________________________________________________________________________ Psiber Data Pte Ltd

www.psiberdata.com

In the Class 1 Horizontal Link page that appears, there are 4 tabs: “Floor”, “Telecom Room”, “Panel” and “Port/Position” which describe 4 variables which will appear in the file Label. The variables can be letters or numbers. Telecom Room and Panel are denoted by letters, which will be incremented according to alphabetical order, and you can change the start and end values to other letters (but not numbers). At each of the 4 tabs, you can edit the start/end values for the variables. Click “” once you are done with each variable, to proceed to the next variable. At any point, you may click the return icon (circle arrow) to quit . When you reach the last tab, Port/Position, click the tick icon to confirm all your inputs and implement the Labeling scheme.

Page 13: Automatic Labeling Schemes in WireXpert

Technical Note 427_01 ©Psiber Data Pte Ltd, 2012 _____________________________________________________________________________________

_____________________________________________________________________________________ Psiber Data Pte Ltd

www.psiberdata.com

With these settings, the Current Label will be set to “1A-A1”.

Page 14: Automatic Labeling Schemes in WireXpert

Technical Note 427_01 ©Psiber Data Pte Ltd, 2012 _____________________________________________________________________________________

_____________________________________________________________________________________ Psiber Data Pte Ltd

www.psiberdata.com

A series of Autotests will now generate the following file names:

Page 15: Automatic Labeling Schemes in WireXpert

Technical Note 427_01 ©Psiber Data Pte Ltd, 2012 _____________________________________________________________________________________

_____________________________________________________________________________________ Psiber Data Pte Ltd

www.psiberdata.com

For this Labeling scheme, when Autosave is off, the Edit Label Sequence page that appears before saving the Autotest file will allow you to edit all the 4 variables: “Floor”, “Telecom Room”, “Panel” and “Position”.

Page 16: Automatic Labeling Schemes in WireXpert

Technical Note 427_01 ©Psiber Data Pte Ltd, 2012 _____________________________________________________________________________________

_____________________________________________________________________________________ Psiber Data Pte Ltd

www.psiberdata.com

Configuring a TIA 606A Class 2 (Single Building Horizontal Link) Labeling Scheme From the Cable Label Source Page, select “Class 2: Single Building Horizontal Link”.

Page 17: Automatic Labeling Schemes in WireXpert

Technical Note 427_01 ©Psiber Data Pte Ltd, 2012 _____________________________________________________________________________________

_____________________________________________________________________________________ Psiber Data Pte Ltd

www.psiberdata.com

The following 4 tabs will appear: “Floor”, “Telecom Room”, “Panel”, and “Port/Position”.

Page 18: Automatic Labeling Schemes in WireXpert

Technical Note 427_01 ©Psiber Data Pte Ltd, 2012 _____________________________________________________________________________________

_____________________________________________________________________________________ Psiber Data Pte Ltd

www.psiberdata.com

Click the tick icon. With these settings, the Current Label will be set to “1A-A1”.

Page 19: Automatic Labeling Schemes in WireXpert

Technical Note 427_01 ©Psiber Data Pte Ltd, 2012 _____________________________________________________________________________________

_____________________________________________________________________________________ Psiber Data Pte Ltd

www.psiberdata.com

A series of Autotests will now generate the following file names:

Page 20: Automatic Labeling Schemes in WireXpert

Technical Note 427_01 ©Psiber Data Pte Ltd, 2012 _____________________________________________________________________________________

_____________________________________________________________________________________ Psiber Data Pte Ltd

www.psiberdata.com

For this Labeling scheme, when Autosave is off, the Edit Label Sequence page that appears before saving the Autotest file will allow you to edit all the 4 variables: “Floor”, “Telecom Room”, “Panel” and “Position”.

Page 21: Automatic Labeling Schemes in WireXpert

Technical Note 427_01 ©Psiber Data Pte Ltd, 2012 _____________________________________________________________________________________

_____________________________________________________________________________________ Psiber Data Pte Ltd

www.psiberdata.com

Configuring a TIA 606A Class 2 (Single Building Backbone cable) Labeling Scheme From the Cable Label Source Page, select “Class 2: Single Building Backbone cable”.

Page 22: Automatic Labeling Schemes in WireXpert

Technical Note 427_01 ©Psiber Data Pte Ltd, 2012 _____________________________________________________________________________________

_____________________________________________________________________________________ Psiber Data Pte Ltd

www.psiberdata.com

The following 4 tabs will appear: “Telecom Room 1”, “Telecom Room 2”, “Backbone Cable” and “Cable”.

Page 23: Automatic Labeling Schemes in WireXpert

Technical Note 427_01 ©Psiber Data Pte Ltd, 2012 _____________________________________________________________________________________

_____________________________________________________________________________________ Psiber Data Pte Ltd

www.psiberdata.com

Click the tick icon. With these settings, the Current Label will be set to “1A/2B-1.1”.

Page 24: Automatic Labeling Schemes in WireXpert

Technical Note 427_01 ©Psiber Data Pte Ltd, 2012 _____________________________________________________________________________________

_____________________________________________________________________________________ Psiber Data Pte Ltd

www.psiberdata.com

A series of Autotests will now generate the following file names:

Page 25: Automatic Labeling Schemes in WireXpert

Technical Note 427_01 ©Psiber Data Pte Ltd, 2012 _____________________________________________________________________________________

_____________________________________________________________________________________ Psiber Data Pte Ltd

www.psiberdata.com

For this Labeling scheme, when Autosave is off, the Edit Label Sequence page that appears before saving the Autotest file will allow you to edit only the following fields: “Backbone Cable” and “Cable”.

Page 26: Automatic Labeling Schemes in WireXpert

Technical Note 427_01 ©Psiber Data Pte Ltd, 2012 _____________________________________________________________________________________

_____________________________________________________________________________________ Psiber Data Pte Ltd

www.psiberdata.com

Configuring a TIA 606A Class 3 (Campus Backbone cable) Labeling Scheme From the Cable Label Source Page, select “Class 3: Campus Backbone cable”.

Page 27: Automatic Labeling Schemes in WireXpert

Technical Note 427_01 ©Psiber Data Pte Ltd, 2012 _____________________________________________________________________________________

_____________________________________________________________________________________ Psiber Data Pte Ltd

www.psiberdata.com

The following 4 tabs will appear “Location 1”, “Location 2”, “Backbone Cable”, and “Cable”. For each location, 3 variables: the building name, floor and room can be specified.

Page 28: Automatic Labeling Schemes in WireXpert

Technical Note 427_01 ©Psiber Data Pte Ltd, 2012 _____________________________________________________________________________________

_____________________________________________________________________________________ Psiber Data Pte Ltd

www.psiberdata.com

Click the tick icon. With these settings, the Current Label will be set to “A-1A/y-1Z-1.1”. A series of Autotests will now generate the following file names:

Page 29: Automatic Labeling Schemes in WireXpert

Technical Note 427_01 ©Psiber Data Pte Ltd, 2012 _____________________________________________________________________________________

_____________________________________________________________________________________ Psiber Data Pte Ltd

www.psiberdata.com

Page 30: Automatic Labeling Schemes in WireXpert

Technical Note 427_01 ©Psiber Data Pte Ltd, 2012 _____________________________________________________________________________________

_____________________________________________________________________________________ Psiber Data Pte Ltd

www.psiberdata.com

For this Labeling scheme, when Autosave is off, the Edit Label Sequence page that appears before saving the Autotest file will allow you to edit only the following fields: “Backbone Cable” and “Cable”.

Page 31: Automatic Labeling Schemes in WireXpert

Technical Note 427_01 ©Psiber Data Pte Ltd, 2012 _____________________________________________________________________________________

_____________________________________________________________________________________ Psiber Data Pte Ltd

www.psiberdata.com

Configuring a Customized Hierarchical Cable Labeling Scheme From the Cable Label Source Page, select “Customized hierarchical cable Labels”. This Labeling scheme allows you to specify the largest number of Labeling variables.

Page 32: Automatic Labeling Schemes in WireXpert

Technical Note 427_01 ©Psiber Data Pte Ltd, 2012 _____________________________________________________________________________________

_____________________________________________________________________________________ Psiber Data Pte Ltd

www.psiberdata.com

At the Customized Hierarchical Cable Labels page, there are many options to customize the Label. First, you can specify the Label prefix (limited to two characters), which will be fixed for all the Labels. Then, there are 6 available variables: Building, Floor, Telecom Room, Rack, Panel, Port/Position. You can tick/untick the variables you want to use in the Labels. The building name can be a mix of letters and numbers, but for the other 5 variables, you have to choose between using letters or numbers to describe each variable. Note: In the screen, “1-9” does not mean the numbers are limited to 1-9, but only means that you are choosing numbers instead of letters.

For illustration, we select all 6 variables. Click “”.

Page 33: Automatic Labeling Schemes in WireXpert

Technical Note 427_01 ©Psiber Data Pte Ltd, 2012 _____________________________________________________________________________________

_____________________________________________________________________________________ Psiber Data Pte Ltd

www.psiberdata.com

The tabs that appear thereafter are based on the variables which have been selected.

Page 34: Automatic Labeling Schemes in WireXpert

Technical Note 427_01 ©Psiber Data Pte Ltd, 2012 _____________________________________________________________________________________

_____________________________________________________________________________________ Psiber Data Pte Ltd

www.psiberdata.com

Page 35: Automatic Labeling Schemes in WireXpert

Technical Note 427_01 ©Psiber Data Pte Ltd, 2012 _____________________________________________________________________________________

_____________________________________________________________________________________ Psiber Data Pte Ltd

www.psiberdata.com

Page 36: Automatic Labeling Schemes in WireXpert

Technical Note 427_01 ©Psiber Data Pte Ltd, 2012 _____________________________________________________________________________________

_____________________________________________________________________________________ Psiber Data Pte Ltd

www.psiberdata.com

After inputting all the start/end values, click “”.

Page 37: Automatic Labeling Schemes in WireXpert

Technical Note 427_01 ©Psiber Data Pte Ltd, 2012 _____________________________________________________________________________________

_____________________________________________________________________________________ Psiber Data Pte Ltd

www.psiberdata.com

Separator Settings The next screen allows you to choose the separators between the variables in the Labels. The symbols you can use as separators are shown in the screenshot below.

Click the tick icon to confirm all these settings and set them as your Labeling scheme. With these settings, the Current Label will be set to “PR+BL7.A-1.X.Z.A”.

Page 38: Automatic Labeling Schemes in WireXpert

Technical Note 427_01 ©Psiber Data Pte Ltd, 2012 _____________________________________________________________________________________

_____________________________________________________________________________________ Psiber Data Pte Ltd

www.psiberdata.com

A series of Autotests will now generate the following file names:

Page 39: Automatic Labeling Schemes in WireXpert

Technical Note 427_01 ©Psiber Data Pte Ltd, 2012 _____________________________________________________________________________________

_____________________________________________________________________________________ Psiber Data Pte Ltd

www.psiberdata.com

For this Labeling scheme, when Autosave is off, the Edit Label Sequence page that appears before saving the Autotest file will allow you to edit only 5 of the variables: “Floor”, “Telecom Room”, “Rack”, “Panel”, “Port/Position”.