Journal of Electrical and Electronics Engineering Research Vol. 3(6), pp. 108-120, August 2011 Available online at http://www.academicjournals.org/jeeer ISSN – 2141 – 2367 ©2011 Academic Journals Full Length Research Paper Automatic meter reading (AMR) based distribution security monitoring and distribution-supervisory control and data acquisition (D-SCADA) control T. Ananthapadmanabha, A. D. Kulkarni, Madhvaraja, and A. P. Suma Department of Electrical and Electronics Engineering, NIE, Mysore, India. Accepted 24 July, 2011 Application of automatic meter reading (AMR) system is presently used for e-billing and e-monitoring. The power system of the future will incorporate advanced monitoring and control system that improve operations and system reliability. The concept presented in this paper includes installation of automatic meters in intermediate points of distribution system to monitor the load of the system and to control the enhancement function of the D-SCADA. The AMR modeling was designed and used for testing 11 KV practical distribution system of Mysore, Karnataka, India. The algorithm was designed for AMR based D-SCADA control for peak load and off peak load periods. MATLAB-Simulink and NI LabVIEW software is used for simulation. Key words: Algorithm, network applications, output data, voltage regulation, load voltage. INTRODUCTION In today’s competitive world, the power and energy sector of any country plays a major role in the growth of domestic, industrial, agricultural, telecommunication, education and public service sectors. At present the Karnataka Power Transport Corporation Limited (KPTCL) is using the AMR in transmission side for the purpose of e-billing and e-monitoring. The SCADA security monitoring control system is also implemented in transmission sector through VSAT communication. But in the case of distribution in Karnataka region, automation is not currently used for security monitoring and control. Hence, it is suggested to install the automatic meters at intermediate points of distribution feeder. By this monitoring and control of distribution system is achieved *Corresponding author. E-mail: [email protected]. Abbreviations: AMR, Automatic meter recording; D-SCADA, distribution-supervisory control and data acquisition; GSM, global system mobile; VSAT, very small aperture terminal; RTU, remote terminal unit; PLC, programmable logic controllers; IED, intelligent electronic devices; VR, voltage regulation; PMU, phasor measuring unit. by means of interfacing the AMR data into the D-SCADA system. The AMR data of the 11 KV feeder at different locations can be transmitted through global system mobile (GSM) Rodney et al., 2007; Zheng, 2010) communication network to the distribution control centre. Then, these data can be interfaced with SCADA system, which controls the entire distribution system with reliable and secured operations and it also keeps away from the abnormal conditions. The AMR can measure the active, reactive and apparent powers of consumer load. It also measures the power factor, rms values of line and phase voltages, line and phase currents, with their angles respectively.Some of the open standard protocols for networking of energy meters like SNMP, MODBUS, DLMS/COSEM, TCP/IP etc.., are used and implemented in LabVIEW virtual instrumentation environment (Santosh and Jayaprakash, 2008). The Automatic Meter Reading and Control System (AMR) can read the both online and offline data logging and storage. These AMR’s are widely used because of the cost effectiveness, security, load monitoring options, load curve monitoring and analysis, outage management (Sridharan and Schulz, 2001). Supervisory control and data acquisition system or

Upload: others

Post on 15-Nov-2021

15 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Automatic meter reading (AMR) based distribution security

Journal of Electrical and Electronics Engineering Research Vol. 3(6), pp. 108-120, August 2011 Available online at http://www.academicjournals.org/jeeer ISSN – 2141 – 2367 ©2011 Academic Journals Full Length Research Paper

Automatic meter reading (AMR) based distribution security monitoring and distribution-supervisory control and data acquisition (D-SCADA) control

T. Ananthapadmanabha, A. D. Kulkarni, Madhvaraja, and A. P. Suma

Department of Electrical and Electronics Engineering, NIE, Mysore, India.

Accepted 24 July, 2011

Application of automatic meter reading (AMR) system is presently used for e-billing and e-monitoring. The power system of the future will incorporate advanced monitoring and control system that improve operations and system reliability. The concept presented in this paper includes installation of automatic meters in intermediate points of distribution system to monitor the load of the system and to control the enhancement function of the D-SCADA. The AMR modeling was designed and used for testing 11 KV practical distribution system of Mysore, Karnataka, India. The algorithm was designed for AMR based D-SCADA control for peak load and off peak load periods. MATLAB-Simulink and NI LabVIEW software is used for simulation. Key words: Algorithm, network applications, output data, voltage regulation, load voltage.

INTRODUCTION In today’s competitive world, the power and energy sector of any country plays a major role in the growth of domestic, industrial, agricultural, telecommunication, education and public service sectors.

At present the Karnataka Power Transport Corporation Limited (KPTCL) is using the AMR in transmission side for the purpose of e-billing and e-monitoring. The SCADA security monitoring control system is also implemented in transmission sector through VSAT communication. But in the case of distribution in Karnataka region, automation is not currently used for security monitoring and control. Hence, it is suggested to install the automatic meters at intermediate points of distribution feeder. By this monitoring and control of distribution system is achieved *Corresponding author. E-mail: [email protected]. Abbreviations: AMR, Automatic meter recording; D-SCADA, distribution-supervisory control and data acquisition; GSM, global system mobile; VSAT, very small aperture terminal; RTU, remote terminal unit; PLC, programmable logic controllers; IED, intelligent electronic devices; VR, voltage regulation; PMU, phasor measuring unit.

by means of interfacing the AMR data into the D-SCADA system.

The AMR data of the 11 KV feeder at different locations can be transmitted through global system mobile (GSM) Rodney et al., 2007; Zheng, 2010) communication network to the distribution control centre. Then, these data can be interfaced with SCADA system, which controls the entire distribution system with reliable and secured operations and it also keeps away from the abnormal conditions. The AMR can measure the active, reactive and apparent powers of consumer load. It also measures the power factor, rms values of line and phase voltages, line and phase currents, with their angles respectively.Some of the open standard protocols for networking of energy meters like SNMP, MODBUS, DLMS/COSEM, TCP/IP etc.., are used and implemented in LabVIEW virtual instrumentation environment (Santosh and Jayaprakash, 2008). The Automatic Meter Reading and Control System (AMR) can read the both online and offline data logging and storage. These AMR’s are widely used because of the cost effectiveness, security, load monitoring options, load curve monitoring and analysis, outage management (Sridharan and Schulz, 2001).

Supervisory control and data acquisition system or

Page 2: Automatic meter reading (AMR) based distribution security

SCADA refers to the combination of telemetry and data acquisition (www.abb.com/networkmanagement). SCADA includes the collecting of the information via a RTU (remote terminal unit), PLCs (programmable logic controllers) and IEDs (intelligent electronic devices), transferring it back to the central site, carrying out any necessary analysis and control and then displaying that information on a number of operator screens or displays.Three of the most important parts of a SCADA system is master station, remote terminal (RTU, PLC, IED) and the communication between them.

DSCADA (Ha et al., 2009) is a set of technologies for providing remote monitoring and control of equipment located in distribution substations and out on the distribution feeders themselves. SCADA is a basic building block upon which smart distribution is based. DSCADA provides the ability to monitor the distribution system components in real-time. Smart distribution applications use the monitoring and control capabilities provided by DSCADA to determine steps needed to optimize the performance of the distribution system. The main purpose of the DSCADA system is to continuously monitor the loading, status, and performance of equipment located on distribution feeders. Under normal conditions, the system periodically acquires real-time values of current and voltage at various strategic measurement points and the open/closed status of all monitored switches (Lee and Shin, 2009).

This paper includes advanced AMR along with the synchronised phasor measuring unit (PMU) block (Narendra and Weekes, 2008).. Hence it is used to measure the magnitude and phase angle of the voltage and currents directly from the PMU and this can be further used for study of state of the system security monitoring and control. The applications of PMU are synchrophasor capability in motor protection, AGC / SIPS analysis, capacitor bank performance, analysis of load shedding schemes, distance relay performance during small disturbances etc (Mark et al., 2007). The AMR modeling was designed which measures all the output values of electrical quantities at different buses of distribution system (Appendix 2). The algorithm was designed for AMR based distribution security monitoring and D-SCADA control. During the peak load and off peak load periods, the voltage drop problems in distribution systems are considered and these can be monitored by AMR and the system can be controlled by D-SCADA through capacitor switching. The objective is to control the system from security violations through the proposed algorithm.

A test environment is implemented and the results are obtained for 11 KV practical distribution system of Mysore city, Karnataka, India. MATLAB-sim power system tool box is used for the simulation of AMR design and load flow calculations has been performed for the test system and the algorithm was programmed and simulated in NI

Ananthapadmanabha et al. 109 LabVIEW software effectively. SYSTEM UNDER TEST The infrastructure of power system distribution network of Mysore, Karnataka was tested for 11 KV distribution network of the Chamundipuram sub division Industrial feeder 11D6. The case study of the system was simulated in Matlab simulink sim power system.

Figure 1 shows the single line diagram of the Chamundipuram sub division industrial feeder 11D6, distribution network of Mysore city. The total capacity of the feeder is 6339 KVA and it consists of 34 distribution transformers (11KV/440V), 11 HT consumers 1.78 MW and the 34 LT consumers 4.57 MW of connected load. This feeder comes under 66/11 KV south master unit sub station (MUSS), more details are shown in the Appendix 1. Thermal loading is considered based on standard conductors like coyote, rabbit, weasel etc. SYSTEM DESCRIPTION D-SCADA functions D-SCADA offers the following major functions; (a) SCADA, real-time monitoring and control. (b) Advanced network applications including network modeling. (c) Outage management including crew and resource management. (d) Work management. SCADA, real-time monitoring and control offers full SCADA functionality including data acquisition, device and sequence control, alarms, events management and geographic world maps etc. Advanced network applications provide the major functions such as, network state estimation (real time load calibration), load flow calculations, short circuit calculations, optimal feeder reconfiguration, loss minimization (MVAR control), load management, feeder voltage control, load switching tracing and dynamic line coloring, fault location, isolation and system restoration and automatic switching plan generation. The outage management functions are trouble call entry and management, manual or automated call service, feed back to customers, fault localization/inference engines, restoration prioritization and follow-up, outage reporting, outage statistics and indices, outage causes and equipment faults, customer outage notification and history. Crew and resource management functions include scheduling (time and capabilities), crew tracking (GPS tracking), dispatching and assignment, optimal route planning, follow-up and reports and mobile crew data communication. Work management includes tagging and clearances, insertion of jumpers and generators, insertion of temporary line cuts and grounding switches, operation step planning including reversal (back out) function, validation simulation scheduling, distribution of work orders, execution and follow-up. AMR design The advanced AMR includes the phasor measuring unit (PMU) block. The vital use of AMR is to provide the data of magnitude of phase and line voltage, phase and line current and their angles in degrees. It also measures the KW, KVA, KVAR, PF etc. The same data is used for analysis of energy losses in distribution system. Figure 2 shows the AMR measurements. It consists of AMR model

Page 3: Automatic meter reading (AMR) based distribution security

110 J. Electrical Electron. Eng. Res.

Figure 1. Single line diagram of the Chamundipuram sub division Industrial feeder 11D6, distribution network of Mysore city.

B1 to B5 OUTPUTS

Outputs 1

AMR

AMRMODEL1

P (MW)

Q (Mv ar)

Phase Voltages Va,Vb,Vc

Phase Voltages angles Va,Vb,Vc

Phase Currents Ia,Ib,Ic

Phase Currents angles Ia,Ib,Ic

Line Voltages VAB,VBC,VCA

Line currents Iab,Ibc,Ica

Apparant power

Power f actor

Figure 2. AMR Measurements.

Page 4: Automatic meter reading (AMR) based distribution security

Ananthapadmanabha et al. 111

10

p f

9

Apparant power

8

I line

7

V line

6

I angle

5

I

4

V angle

3

V

2

Q

1

P

In1

In2

Out1

apparant power

In1

In2

In3

In4

In5

Out1

Out2

Subsystem1

In1

In2

In3

In4

In5

Out1

Out2

Subsystem

U Y

U Y

Iabc_B4

Vabc_B1

Iabc_B1

Vabc_B5

Iabc_B5

Vabc_B3

Vabc_B2

Iabc_B3

Vabc_B4

Iabc_B2

2/3

-K-

-K-

-K-

100

Divide

Vabc

Iabc

PQ

3-PhaseActive & Reactive Power

(Phasor Type)4

Vabc

Iabc

PQ

3-PhaseActive & Reactive Power

(Phasor Type)3

Vabc

Iabc

PQ

3-PhaseActive & Reactive Power

(Phasor Type)2

Vabc

Iabc

PQ

3-PhaseActive & Reactive Power

(Phasor Type)1

Vabc

Iabc

PQ

3-PhaseActive & Reactive Power

(Phasor Type)

Figure 3. AMR Simulink model.

and output display block. It measures the values of the above mentioned parameters of buses 1 to 5. Automatic meters are connected to the monitoring and control centre through suitable communication (GSM) equipment.

This powerful AMR system is designed to support interfacing to the D-SCADA. By taking the values of phase to ground (per unit) voltage Vabc and current Iabc at individual busses of three phase 11 KV distribution line, a three phase active and reactive power measurement block of phasor type. which receives the three phase bus voltages Vabc and currents Iabc and calculate the active power (P) and reactive power (Q) values. Converting the obtained per unit values of P and Q in to the base values and connecting the ports to the output terminals 1 and 2. The phase and line voltages can be

directly read from received signals Vabc and Iabc and then convert them into per unit to base values and calculate line and phase voltages and currents.

The Vabc and Iabc are in complex form, hence it must be converted into polar form using complex to magnitude/angle conversion block. The obtained angles of respective voltage and current values are in radians and then converted into degrees. Apparent power and power factor can be calculated by using obtained values of P and Q.

Figure 3 shows the model of AMR, consisting of five units- each unit measuring the data of five busses. The output ports of the AMR are connected to the output blocks consisting the display blocks and scopes to read the output data. Figure 4 shows the PMU

Page 5: Automatic meter reading (AMR) based distribution security

112 J. Electrical Electron. Eng. Res.

2Out2

1Out1

-K-

rad-deg5

-K-

rad-deg4

-K-

rad-deg3-K-

rad-deg2

-K-

rad-deg

-K-

pu->V4

-K-

pu->V3

-K-

pu->V2

-K-

pu->V1

-K-

pu->V

|u| u

|u| u

|u| u

|u| u

|u| u

5In5

4In4

3In3

2In2

1In1

Figure 4. PMU Simulink model.

simulink model and which consists of voltage /current and with their angle measurement block.

Mathematical equations used for AMR modeling are: 1. Active power (P) : 2. Reactive power (Q) : 3. Apparent Power (S) : or

4. Power factor (pf) :

5. Voltage Regulation (VR):

PROPOSED ALGORITHM Here the development procedure of methodology is illustrated. The overall concept has been represented in Figure 5. It gives the algorithm for AMR based distribution security monitoring and D-SCADA Control. In this algorithm the focus is on two security violations - one is peak load period usually from 6 to 10 PM and the other is off peak load period during night between 10 PM and 6 in the morning. During peak load period, the voltage at the far end will be reduced and the voltage regulation is poor. Hence to improve the voltage profile and voltage regulation at far end, auto switching of the capacitor banks are necessary in the distribution line (Ellithy et al., 2008). This will improve the voltage profile, voltage regulation at the far end, minimizing the losses and balancing the load. The algorithm is as follows:

Step 1: Read the system data and close all the tie switches and perform the power flow. Step 2: If the system is under normal condition, display the green light, else display red light and give signal to the alarms and buzzers. Step 3: If the system has any abnormalities then violation of the security constraints like V and I, exceeding or limiting values will be determined by the smart meter output data. Step 4: List out the number of security violations and send the priority signal. Step 5: The received priority signal is checked for the type of security violations, and then calculate the voltage regulation. Step 6: Condition checking is done for the voltage regulation (VR) in acceptable limits (0 to 5%). If the limits are crossed, then the security violations are described as two ways. One is peak load period (VR � 5%) and another is off peak load period (VR � 0%). Step 7: The capacitor bank has to be switched on for peak load and switched off for off peak load automatically. Step 8: Run the power flow and repeat the step 5 to 6 until the VR is in acceptable limits (0 to 5%). Then the program has to realize the system to be under normal condition and it must indicate the green light signal, then the program has to be terminated. Figure 6 shows the process flow diagram of the overall simulation part. The MATLAB output can be manually entered into the LabVIEW to simulate the proposed algorithm. RESULTS AND DISCUSSION The MATLAB simulation results of the test system shows

Page 6: Automatic meter reading (AMR) based distribution security

Ananthapadmanabha et al. 113

Figure 5. AMR based distribution security monitoring and D-SCADA control algorithm.

the AMR measurements for different cases in Appendix 2. These results are manually entered as an input to the LabVIEW and algorithm was simulated and the security monitoring and control can be achieved by displaying red and green indication during peak and off peak load periods respectively. Case 1: It refers to the system to be under normal load condition, the voltage drop at the far end due to normal loading within the acceptable limit. Hence the green light is indicated in the control room according to the algorithm. Case 2: It refers to the system to be under peak load condition, the voltage drop at the far end due to peak loading exceeding the acceptable limit. Hence the red light is indicated in the control room according to the

algorithm. And also it sends the signal to the capacitor bank to switch on its position helping to improve the voltage profile at the far end.

A sudden fall in peak load, when the capacitor is connected in the line causes and increase in the value of the voltage above the limits, harming the insulation of the cables, machines etc. Hence it is devised to switch off the capacitor bank as shown in algorithm. These results can be analysed from Table 1 showing the calculated values of power consumption of the load, no load voltage V0, on load voltage VL, voltage regulation VR, size of capacitor bank in KVAR and power factor.

Figures 7 and 8 shows the simulation of AMR based distribution security monitoring and D-SCADA control algorithm respectively in LabVIEW software.

The online monitoring display includes the load switches,

Page 7: Automatic meter reading (AMR) based distribution security

114 J. Electrical Electron. Eng. Res.

Figure 6. Process flow diagram.

Table 1. Test system result analysis.

S. No Condition Load (MW)

V0 (KV) VL (KV) VR

(%) C

(KVAR) P.F Status of the system and control

action

1 Normal 5.346 11 10.54 4.18 ---- 0.904 System is stable 2 Peak load 9.591 11 10.31 6.27 ---- 0.901 Switch ON the CB 3 Peak load 9.191 11 10.51 4.45 800 0.995 Voltage and VR is improved 4 Fall in peak load 5.659 11 10.86 1.27 800 1 Switch OFF the CB 5 Back to normal 5.346 11 10.54 4.18 ---- 0.904 System is stable

indicators, measurements and load curve, status capacitor bank switching etc. In Figure 8 red light indicates that the system is under peak load condition. Conclusion This paper illustrates an algorithm for AMR based distribution security monitoring and D-SCADA control.

This technique is one of the most reliable and easily applicable in distribution systems. The utilization of AMR is the advanced technology for accurate measurements and theft control and is very helpful to achieve the objective in security operation of the power system. The test system is simulated in the MATLAB 7.8 version / SIMULINK and LabVIEW effectively. This AMR also containing PMU which directly measures the angles of the voltage and currents will be helpful to implement for and security monitoring and control of D-SCADA system.

Page 8: Automatic meter reading (AMR) based distribution security

Ananthapadmanabha et al. 115

Figure 7. Programming diagram for proposed algoritham in LabVIEW.

Figure 8. Results obtained from LabVIEW.

Page 9: Automatic meter reading (AMR) based distribution security

116 J. Electrical Electron. Eng. Res. REFERENCES Ellithy K, Al-Hinai A, Moosa A (2008). Optimal Shunt Capacitors

Allocation in Distribution Networks Using Genetic Algorithm- Practical Case Study. Int. J. Innov. Energy Syst. Power, 3(1).

Lee Ha. BN, Shin SWCH (2009). Development of intelligent distribution automation system.” Trans. Dist. Conf. Expos. Asia Pac., pp. 1-4.

Mark A, Rich H, Multilin GE (2007). Application of Phasor Measurement Units for Disturbance Recording.” www.gedigitalenergy.com/smartgrid/Aug07/PMU_disturbance_recording.

Narendra K, Weekes T (2008). Phasor Measurement Unit (PMU) Communication Experience in a Utility Environment” CIGRE Canada Conference on Power Systems. Winnipeg, pp. 19-21.

Network Manager SCADA/ DMS Distribution Network Management.” www.abb.com/networkmanagement.

Rodney Tan HG, Lee CH, Mok Young VH (2007). Automatic Power Meter Reading System Using GSM Network.” Int. Power Eng. Conf. (IPEC), pp. 465-469.

Santosh SC, Jayaprakash S (2008). An Open Standard Protocol for

Networking of Energy Meters.” IEEE Trans. On Power Deliv., 23(4): 1749-1753.

Sridharan K, Schulz NN (2001). Outage Management through AMR Systems Using an Intelligent Data Filter.” IEEE Trans. Power Deliv., 16(4): 669-675.

Zheng W (2010). Design and Implementation on Wireless Power meter System based on GSM Network.” Int. Conf. 2010 Comput., Mechatronics, Control Electron. Eng., (CMCE), 2: 76-79.

Page 10: Automatic meter reading (AMR) based distribution security

Ananthapadmanabha et al. 117

APPENDIX 1

MONITORING AND

CONTROL CENTRE

1.Ranjani11D601

2.R.V. Chemicals

11D602

3. Sidvin11D603

5. Kumar11D605

6. Water Supply11D606

33. John T. Mantooran

11D633

7. BasanthTiles

11D607

8. ChanukyaKalyanamantapa

11D608

9. Choudeswari11D609

South MUSS 66/11KV

10. Mysore Millers11D610

11. Surya Battery11D611

12. Rajarajeshwari11D612

13. Symphony11D613

14.Chamundeswari Oil11D614

15. Adichunchanagiri11D615

16. Muneshwara nagara11D616

17.Shaneshwara11D617

18.Saraswthi 11D618

21.Silver tone 11D621 22. New Lucas

11D622

20. Telephone Exchange

11D620

19.Chamundi Metals 11D619

25. Indavara11D625

24.Srinivas 11D624

23. Hifame11D623

26. TVS11D626

27. Harishchandra11D627

28. Income Tax11D628

29. Ambedkar11D629

30. MC Nagendra11D630

31. Sterling Theater11D631

32. Saraswathi Apartment -1

11D632

34 Saraswathi Apartment -2

11D634

Phasors

powergui

A B C

cap3

A B C

cap2

A B C

cap

������ ����

MONITORING AND

CONTROL CENTRE

Subsystem

A

B

C

Substation

A B C

Peak load

L9_0.167

L8_0.092KML7_0.207KM1L5_0.288KM

L4_0.446KM

L3_0.248 KML2_0.238 KML1_1.094KM L15_1KM

L14_0.395KM

L12_0.778KML11_0.495KML10_0.411KM

ABC

HT 275KW

A B C HT 27419.77 KW

A B C HT 24650.85 KW

A

BC

HT 23884.75KW

A B CHT 231140.68KW

A B C HT 23033.90 KW

A B C HT -56282.49KWA B C HT -399

70.62KW

A B CHT -32956.50KW

A B C HT -273250KWA B CHT - 55

225.99KW

A B C

a b c B9

A B C

a b c B8

A

B

C

a

b

c

B7

A

B

C

a

b

c

B6

A B C

a b c B5

A

B

C

a

b

c

B4

A

B

C

a

b

c

B3

A

B

C

a

b

c

B2

A

B

C

a

b

c

B15

A B C

a b cB14

A

B

C

a

b

c

B13

A

B

C

a

b

c

B12

A

B

C

a

b

c

B11

A B C

a b c B10

ABC

95.24KW

A B C

90KW

A B C

a b c n2

9. 250 KVA. 11KV/433V.

A B C

84.10KW

A

BC

83.62KW

A B C

a b c n2

8. 100 KVA. 11KV/433V

AB

C

73.15KW

A B C

a b c n2

7. 250 KVA. 11KV/433V.

A

BC

63.10.KW

A

B

C

a

b

c

n2

6. 100 KVA .11KV/433V

A B C

5KW

A B C

51.96 KW

A

B

C

a

b

c

n2

5. 100 KVA 11KV / 433V

A

BC

46KW

A B C

41.18KW� � �

� � �

A B C

397.67KWA B C

390.77KW

A B C

365.86KW

ABC

36.57.KW

A B C

35KW

A B C

34.86KW

A B C

34.06KW

A

B

C

a

b

c

n234. 250 KVA.

11KV/433V

A B C

336.38KW

A B C

a b c n2

33. 63 KVA 11KV/433V

A B C

a b c n2

32. 250 KVA. 11KV/433V

A B C

a b c n2

31. 63 KVA 11KV/433V

A B C

a b c n2

30. 100 KVA. 11KV/433V

A B C

a b c n2

3. 250 KVA 11KV/433V

� � �

� � �

A B C

297.61KW

A B C

a b c n2

29. 100 KVA. 11KV/433V

A B C

a b c n2

28. 250 KVA. 11KV/433V

A B C

279.19KW

A B C

a b c n2

27. 100 KVA. 11KV/433V

A B C

a b c n2

26. 100 KVA. 11KV/433V

A B C

256.15KW

A

B

C

a

b

c

n225. 250 KVA.

11KV/433V

A B C

24KW

A B C

a b c n2

24. 250 KVA. 11KV/433V

A B C

24 KW

A B C

a b cn

2

23. 500 KVA 11KV/433V1

ABC

222.64KW

AB

C

220 KW

A B C

22.39KW

A B C

a b c n2

22. 100 KVA. 11KV/433V

A B C

213.63KW

A B C

a b c n2

21. 250 KVA. 11KV/433V

AB

C

203.91KW

A B C

a b c n2

20. 100 KVA. 11KV/433V

A B C

a b c n2

2. 500 KVA 11KV/433V

� � �

� � �

A

B

C

a

b

c

n2

19. 250 KVA. 11KV/433V

A B C

a b c n2

18. 250 KVA. 11KV/433V

A B C

a b c n2

17. 100 KVA. 11KV/433V

A B C

a b c n2

16. 100 KVA. 11KV/433V

A B C

150.75KW

A B C

a b c n2

15. 63 KVA 11KV/433V

A

B

C

a

b

c

n2

14. 100 KVA 11KV / 433V

A B C

139.1KW

A

B

C

a

b

c

n2

13. 100 KVA .11KV/433V

A B C

122.11KW

A B C

12.36KW

A

B

C

a

b

c

n2

12. 100 KVA 11KV / 433V

A

BC

116.81KW

A

B

C

a

b

c

n2

11. 250 KVA .11KV/433V

A

B

C

a

b

c

n2

10. 250 KVA 11KV / 433V

A B C

a b c n2

1. 100 KVA 11KV/433V

� � �

� � �

Figure 1. Distribution system network of Mysore City, Karnataka, India. Chamundipuram sub division industrial feeder 11d6, MATLAB simulink test system model.

Table 1. Load data details of distribution transformer center substation.

S. No. Location of Transformer DTC code Capacity [KVA] Connected load

KW HP Total load [KW] 1 Ranjani 11D601 100 11.38 97.48 84.10 2 R .V. Chemicals 11D602 500 84.09 173.64 213.63 3 Sidwin 11D603 250 27.95 305.92 256.15 4 Chamundi feeds 11D604 250 14.68 65.25 63.35 5 Kumar 11D605 100 12 96 83.62 6 Water Supply 11D606 100 3.42 8 9.388 7 Basanth tiles 11D607 250 32.06 159.11 150.75 8 Chanukya Choultry 11D608 100 30.38 6 34.86 9 Choudeshwari 11D609 250 21.79 134.49 122.11 10 Mysore millers 11D610 250 6.28 119.25 95.24 11 Surya battery 11D611 250 14.47 281.4 222.64 12 Rajrajeshwari 11D612 100 1 96.75 73.15 13 Symphony 11D613 100 3 45 36.57 14 Chamundeshwari 11D614 100 1.24 60 46 15 Adichuncnchanagiri 11D615 63 12.36 0 12.36 16 Muneshwara nagara 11D616 100 76.2 18.5 90 17 Shaneshwara 11D617 250 51.96 0 51.96 18 Saraswathi 11D618 250 61.99 291.95 279.19 19 Chamundi metals 11D619 250 8.58 145.09 116.81 20 Telephone exchange 11D620 100 34.06 0 34.06 21 Silver tone 11D621 250 38.4 346.82 297.61 22 New lucas 11D622 100 5 0 5 23 Hifame 11D623 500 45.75 389.57 336.38 24 Srinivas 11D624 250 341.53 66 390.77

Page 11: Automatic meter reading (AMR) based distribution security

118 J. Electrical Electron. Eng. Res.

Table 1. Cont.

25 Indavara 11D625 250 42.7 216.07 203.89 26 TVS 11D626 100 0 30.02 22.39 27 Harishchandra 11D627 100 175.79 297.41 397.67 28 Income tax 11D628 250 139.1 0 139.10 29 Ambedkar 11D629 100 35 0 35 30 MC Nagendra 11D630 100 41.18 0 41.18 31 Sterling theater 11D631 63 332.24 45 365.86 32 Saraswathi apartment 1 11D632 250 24 0 24 33 John T. Manthooran 11D633 63 16 0 16 34 Saraswathi apartment 2 11D634 250 220 0 220 Total 11D6 6339 1965.58 3494.72 4570.788

Table 2. HT load details of the feeder 11D6.

S. No. R .R. No KVA KW 1 HT246 90 50.85 2 HT329 100 56.50 3 HT273 250 141.24 4 HT231 249 140.68 5 HT238 150 84.75 6 HT230 60 33.90 7 HT275 1200 677.97 8 HT55 400 225.99 9 HT56 500 282.49 10 HT399 125 70.62 11 HT274 35 19.77

Total 3159.50 1784.76

Table 3. Industrial feeder (11D6) conductors and line length details.

Length of overhead line distribution 9.313 KM Distribution Type of conductor Length [km] 3 wire Coyote 2.889 3 wire Rabbit 6.087 3 wire Weasel 0.338

Length of underground cable 0.214KM Type of conductor Diameter Length [km] UG 3.95 mt 0.241 Length of trunk line (mt) 2849 No. of tapping lines 28 Tapping lines (mt) 6705

Tapping Length Tapping Length Tapping Length 1 234 11 34 21 12 2 424 12 14 22 2 3 8 13 338 23 329 4 94 14 3672 24 31 5 21 15 25 25 4 6 190 16 24 26 53

Page 12: Automatic meter reading (AMR) based distribution security

Ananthapadmanabha et al. 119

Table 3. Contd.

7 87 17 98 27 20 8 384 18 297 28 43 9 22 19 176

10 13 20 58

APPENDIX 2 Results Case 1: Under normal condition Total load = 5.346 MW, No load Voltage = 11 KV, Line Voltage at end point = 10.54 KV, Voltage regulation = 4.18%

Phase Voltages (V) Phase Voltages Phase Currents (A) Phase Currents Line Voltages (V) Line Voltages Va Vb Vc Angles (Deg) Ia Ib Ic Angles (Deg) Vab Vbc Vca Angles (Deg) B1 B2 B3 B1 B2 B3 B1 B2 B3 B1 B2 B3 B1 B2 B3 B1 B2 B3 B4 B5 B4 B5 B4 B5 B4 B5 B4 B5 B4 B5

Figure 1. AMR output data of buses 1 to 5 of case 1.

Page 13: Automatic meter reading (AMR) based distribution security

120 J. Electrical Electron. Eng. Res. Case 2: Under the peak load condition Total load = 9.591 MW, No load voltage = 11 KV, Line voltage at end point = 10.31 KV, Voltage regulation = 6.27%.

Phase Voltages (V) Phase Voltages Phase Currents (A) Phase Currents Line Voltages (V) Line Voltages Va Vb Vc Angles (Deg) Ia Ib Ic Angles (Deg) Vab Vbc Vca Angles (Deg) B1 B2 B3 B1 B2 B3 B1 B2 B3 B1 B2 B3 B1 B2 B3 B1 B2 B3 B4 B5 B4 B5 B4 B5 B4 B5 B4 B5 B4 B5

Figure 2. AMR output data of buses 1 to 5 of case 2.