Description Operation The ATS-10 provides the mains voltage monitoring and automatic transfer switching. In the event of a mains voltage failure, the remote start relay output is energized and the unit automatically transfers the load from the mains to the generator. Microprocessor technology allows exact measurement, set point adjustment and timing functions with the parameters to be simply programmed and displayed from the front panel. The ATS-10 automatic transfer switch can detect failure of any phase of the mains supply. If at least one of the mains phase voltages goes outside set limits, the unit operates as follows: - The Mains Voltage Okay led turns from green to red. The mains contactor output is deenergized and the green Mains Contactor Closed led is extinguished. - The remote start output is energised after the Remote Start Delay parameter has expired. The generator start module receives this signal and initiates the engine start. - If the Unit Usage Type parameter (P00) is selected as 0 (Type-1); When the generator voltage is within set limits, the yellow Generator Running led will illuminate. The unit will allow the generating set to run without load until the Engine Heating Period parameter is expired. After this time, If the Unit Usage Type parameter (P00) is selected as 1 (Type-2); When the Engine running signal is present, the yellow Generator Running led will illuminate. The unit will allow the generating set to run without load until the Load gen. signal is present. If this signal is present, - The generator contactor output will be energized a when the Generator Contactor Delay parameter is expired. - If the mains voltage return to within limits, the Mains Voltage Okay led will turn to green and the unit waits for the Mains Return delay parameter for the mains voltage stabilization. - When the Mains Return Delay parameter is expired, the yellow Generator Contactor Closed led is extinguished and the generator contactor output is deenergized. Then the green Mains Contactor Closed led will start blinking and then the unit will wait for the Mains contactor Delay parameter. - When the Mains contactor Delay parameter is expired, the green Mains Contactor Closed led will illuminate steadily and the mains contactor output is energized. Then the remote start output is deenergized. - The unit is ready for a new mains failure. The ATS-10 has got a TEST mode feature. This mode allows the generating set to be tested without taking the load. This mode is also called Emergency backup mode which keeps the generating set running and makes a quick transfer if a mains failure occurs. In this mode, The remote start output will be energized but no load transfer will take place unless the occurrence of a mains failure. If a mains failure occurs, the load will be transferred to the generating set. If the mains voltage return to within limits and the Mains Return Delay parameter is expired, the load will be transferred to the mains, but the generating set will be kept running. The remote start output will only deenergized when the Test mode is cancelled. the yellow Generator Contactor Closed led will start blinking and the unit wait for the Generator Contactor Delay parameter. the yellow Generator Contactor Closed led will start blinking and the unit wait for the Generator Contactor Delay parameter. nd the yellow Generator Contactor Closed led will illuminate steadily 1 Automatic Transfer Switch, 72x72 DIN Size ATS-10 Automatic Transfer Switch 72 x 72 DIN Size

Upload: others

Post on 14-Apr-2020

12 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Automatic Transfer Switch, 72x72 DIN Sizedmpcontrol.mx/images/productosemko/switch de... · Automatic Transfer Switch, 72x72 DIN Size Specifications Equipment Use Electrical control

Description

Operation

The ATS-10 provides the mains voltage monitoring and automatic transfer switching. In the event of a mains voltage failure, the remote start relay output is energized and the unit automatically transfers the load from the mains to the generator. Microprocessor technology allows exact measurement, set point adjustment and timing functions with the parameters to be simply programmed and displayed from the front panel.

The ATS-10 automatic transfer switch can detect failure of any phase of the mains supply. If at least one of the mains phase voltages goes outside set limits, the unit operates as follows:

- The Mains Voltage Okay led turns from green to red. The mains contactor output is deenergized and the green Mains Contactor Closed led is extinguished.

- The remote start output is energised after the Remote Start Delay parameter has expired. The generatorstart module receives this signal and initiates the engine start.

- If the Unit Usage Type parameter (P00) is selected as 0 (Type-1); When the generator voltage is within set limits, the yellow Generator Running led will illuminate. The unit will allow the generating set to run without load until the Engine Heating Period parameter is expired. After this time,

If the Unit Usage Type parameter (P00) is selected as 1 (Type-2); When the Engine running signal is present, the yellow Generator Running led will illuminate. The unit will allow the generating set to run without load until the Load gen. signal is present. If this signal is present,

- The generator contactor output will be energized a when the Generator Contactor Delay parameter is expired.

- If the mains voltage return to within limits, the Mains Voltage Okay led will turn to green and the unit waits for the Mains Return delay parameter for the mains voltage stabilization.

- When the Mains Return Delay parameter is expired, the yellow Generator Contactor Closed led is extinguished and the generator contactor output is deenergized. Then the green Mains Contactor Closed led will start blinking and then the unit will wait for the Mains contactor Delay parameter.

- When the Mains contactor Delay parameter is expired, the green Mains Contactor Closed led will illuminate steadily and the mains contactor output is energized. Then the remote start output is deenergized.

- The unit is ready for a new mains failure.

The ATS-10 has got a TEST mode feature. This mode allows the generating set to be tested without taking the load. This mode is also called Emergency backup mode which keeps the generating set running and makes a quick transfer if a mains failure occurs.In this mode, The remote start output will be energized but no load transfer will take place unless the occurrence of a mains failure. If a mains failure occurs, the load will be transferred to the generating set. If the mains voltage return to within limits and the Mains Return Delay parameter is expired, the load will be transferred to the mains, but the generating set will be kept running. The remote start output will only deenergized when the Test mode is cancelled.

the yellow Generator Contactor Closed led will start blinking and the unit wait for the Generator Contactor Delay parameter.

the yellow Generator Contactor Closed led will start blinking and the unit wait for the Generator Contactor Delay parameter.

nd the yellow Generator Contactor Closed led will illuminate steadily

1

Automatic Transfer Switch, 72x72 DIN Size

ATS-10Automatic Transfer Switch

72 x 72 DIN Size

Page 2: Automatic Transfer Switch, 72x72 DIN Sizedmpcontrol.mx/images/productosemko/switch de... · Automatic Transfer Switch, 72x72 DIN Size Specifications Equipment Use Electrical control

2

Automatic Transfer Switch, 72x72 DIN Size

Specifications

Equipment Use Electrical control equipment for generating sets

Housing & Mounting 72mmx72mmx95mm (including connectors) DIN43700 plastic housing for panel mounting

Panel Cut-out 69mmx69mm

Protection NEMA4X (IP65 at front panel, IP20 at rear side)

Weight Approximately 0.27 kg

Environmental Rating Standard, indoor at an altitude of less then 2000 meters with non-condensing humidity

Operating / Storage Temperature -25ºC to +70ºC / -40ºC to +85ºC

Operating / Storage Humidity 90% max. (Non-condensing)

Installation Over Voltage Cat. II appliances, portable equipment

Pollution Degree II, Normal office or workplace, non-conductive pollution

Mode of Operation Continuous

EMC EN-61000-6-4, EMC generic emission standard for industrial equipment

EN-61000-6-2, EMC generic immunity standard for industrial equipment

Electrical Safety EN-61010-1, safety requirements for electrical equipment for measurement, control and

laboratory use

Battery Supply Voltage(Z) 8-32 VZ max. Operating current is 240 mA

Cranking Dropouts Battery voltage can be 0VZ for max. 100msn during cranking (battery voltage should be

at least nominal voltage before cranking)

Mains Voltage Measurement

35-300VL-NVRMS (@15.6-99.9 Hz). Accuracy: 1% FS. Resolution : 1VGenerator Voltage Measurement

35-300VL-NVRMS (@15.6-99.9 Hz). Accuracy: 1% FS. Resolution : 1V

Display 4 Digits, 7 segments LED display showing :Mains Voltage (Phase-Phase and Phase-Neutral)Alternator Voltage. ( )If the Unit Usage Type parameter (P00) is selected as 0 (Type-1)Program Parameters

Status Indicators TEST Mode LED

Mains Contactor Closed LEDGenerator Contactor Closed LED

Contact Sensing Inputs Load Generator Signal (NO)Engine Running Signal (NO)

Relay Outputs Remote Start Relay (1NO+1NC. 12A@32V Z)Mains Contactor Relay (1NC. 5A@250V V)

Generator Contactor Relay (1NO. 5A@250V V)

Mains Volgage Okay LEDGenerator Running LED

PROG Mode LED

Page 3: Automatic Transfer Switch, 72x72 DIN Sizedmpcontrol.mx/images/productosemko/switch de... · Automatic Transfer Switch, 72x72 DIN Size Specifications Equipment Use Electrical control

3

Automatic Transfer Switch, 72x72 DIN Size

Maximum 15mm / 0.590 inch

83.5 mm / 3.287 inch11.5mm / 0.452 inch72mm

72

mm

N AG - TE S

Dimensions

Panel Cut-Out

VL12 GEN V.VL23 VL31

TESTPROG

TEST

ATS-10

69

mm

/ 2

.72

in

ch

69mm / 2.72 inch

Page 4: Automatic Transfer Switch, 72x72 DIN Sizedmpcontrol.mx/images/productosemko/switch de... · Automatic Transfer Switch, 72x72 DIN Size Specifications Equipment Use Electrical control

ATS-10 Parameters List

Front View Terminal Connections

4

Automatic Transfer Switch, 72x72 DIN Size

VL12 GEN V.VL23 VL31

TESTPROG

TEST

ATS-10

12 13 14 15 16 17 18 19

MA

INS

N

MA

INS

L1

MA

INS

L2

MA

INS

L3

GE

N. N

GE

N. L

1

MA

INS

RE

LA

Y

GE

N. R

EL

AY

1 2 3 4 5 10 11

- B

AT

+ B

AT

EN

GIN

E R

UN

.IN

PU

T

LO

AD

GE

N.

INP

UT

12 A @220VV P/N : ATS-10

RE

MO

TE

STA

RT

OU

T

NCNOCÖ

2 X 5 A@220VV

+ +

Type - 1 (P00 = 0): When “Generator Voltage” detected by ATS-10Parameters List

No

P03

P09

P01

P02

Definition of Parameter

Mains Voltage Connection Level

Mains Voltage Disconnection Level

Mains Voltage Upper Limit

Alternator Voltage Lower LimitAlternator Voltage Upper Limit

Min

60

60

60

6060

Max

600

600

600

600600

Default

320

300

440

320440

Unit

VV

VV

VV

VVVV

P00 Unit Usage Type 0 1 0

P10

P07 Remote Start Delay 0 9999 0 sec

P05 Generator Contactor Delay 0.1 25.0 1.0 secP06 Mains Contactor Delay 0.1 25.0 1.0 sec

P04 Mains Return Delay 0 9999 30 sec

P08 Engine Heating Period 0 250 10 sec

Type - 2 (P00 = 1): When “Load Generator Logic Input” detected by ATS-10Parameters List

No

P03

P01

P02

Definition of Parameter

Mains Voltage Connection Level

Mains Voltage Disconnection Level

Mains Voltage Upper Limit

Min

60

60

60

Max

600

600

600

Default

320

300

440

Unit

VV

VV

VV

P00 0 1 1

P07 Remote Start Delay 0 9999 0 sec

P05 Generator Contactor Delay 0.1 25.0 1.0 secP06 Mains Contactor Delay 0.1 25.0 1.0 sec

P04 Mains Return Delay 0 9999 30 sec

Unit Usage Type

+ B

AT

OR

- B

AT

P11 0 9999 0Password

P11 0 9999 0Password

Page 5: Automatic Transfer Switch, 72x72 DIN Sizedmpcontrol.mx/images/productosemko/switch de... · Automatic Transfer Switch, 72x72 DIN Size Specifications Equipment Use Electrical control

5

Automatic Transfer Switch, 72x72 DIN Size

Three Phase Connection Schematic For Type - 1 (P00 = 0)

MAINS

MAINS CONTACTOR GENERATOR CONTACTOR

LOAD

GEN. RELAYMAINS RELAY

FU

SE

-5

FU

SE

-4

FU

SE

-3

FU

SE

-2

1512

L1 L1

L1

N N

N

L2 L2

L2

L3 L3

L3

14 13 18 17 1619

FU

SE

-1B

AT

TE

RY +

-BA

T

+B

AT

BATTERY NEGATIVE MUST BE GROUNDED

1 2 3 4 5

1

MEASUREMENTCIRCUIT

MEASUREMENTCIRCUIT

12A@220VV

5A@250VV 5A@250VV

c

1c

REMOTESTART

NO NC

NOTE: If single phase sensing is required the single phase can be fed intoall three phase inputs.

+BAT OR -BAT

10 11

NOT CONNECTED NOT CONNECTED

GENERATOR

MAINS

MAINS CONTACTOR GENERATOR CONTACTOR

LOAD

GENERATOR

GEN. RELAYMAINS RELAY

FU

SE

-5

FU

SE

-4

FU

SE

-3

FU

SE

-2

1512

L1 L1

L1

N N

N

L2 L2

L2

L3 L3

L3

14 13 18 1719

FU

SE

-1B

AT

TE

RY +

-BA

T

+B

AT

BATTERY NEGATIVE MUST BE GROUNDED

1 2 3 4 5 10

1

MEASUREMENTCIRCUIT

12A@220VV

5A@250VV 5A@250VV

c

cThe fuses should be as follows:FUSE-1FUSE-2, FUSE-3 1FUSE-4, FUSE-5

1A. TA. T

1A. T

1c

1- Connect the unit as shown in the appropriate diagram above. Be sure to connect the battery supply the right way round and battery negative should be grounded. The connectors can be unplugged from the rear of the unit to facilitate connection.

REMOTESTART

+B

AT

LO

AD

GE

NE

RA

TO

R IN

PU

T

11

+B

AT

NO NC

EN

GIN

E R

UN

NIN

G IN

PU

TO

PT

ION

AL

: U

SIN

G F

OR

GE

N. R

UN

NIN

G L

ED

16

NOT CONNECTED

+BAT OR -BAT

Three Phase Connection Schematic For Type - 2 (P00 = 1)NOTE: If single phase sensing is required the single phase can be fed intoall three phase inputs.

Page 6: Automatic Transfer Switch, 72x72 DIN Sizedmpcontrol.mx/images/productosemko/switch de... · Automatic Transfer Switch, 72x72 DIN Size Specifications Equipment Use Electrical control

Easy Access Diagram to Programming Parameters

Product Code

ATS-10 Automatic Transfer Switch, 72mmx72mmx95mm Size

i

6

The Programming mode must be entered only while the mains voltage okay and the load supplied from mains.

Automatic Transfer Switch, 72x72 DIN Size

Press the Enter button to confirm the password. If it’s correct, P00 is displayed. If the password is incorrect, the unit will drop out of program mode.

°F°F°F °F°F°F

Press the increment button.

Enter password with increment and decrement buttons.

°F°F°F

°F°F°F

Press the increment button to access to the parameter value.

Change the parameter value with increment and decrement buttons.

Press Enter button to confirm the changed value and access to the following parameter. On this way you can access to theall parameters.

°F°F°F °F°F°F°F°F°F

When the button is pressed for 10 seconds, password is asked for accessing to the parameters.

Press button for accessing to the passwordentering screen

Operation screen

Note: If the PROG button is pressed or if no buttons are pressed for a period of 2 minutes, the unit will return to the normal operation screen.

Operator password

PROG

TEST

PROG

TEST

PROG

TEST

PROG

TEST

PROG

TEST

PROG

TEST

PROG

TEST

Note: If Enter button is pressed and the password parameter is zero, pass screen is ignored and p 00 screen is shown.

It is your responsibility if this equipment is used in a manner not specified in this instruction manual.

Page 7: Automatic Transfer Switch, 72x72 DIN Sizedmpcontrol.mx/images/productosemko/switch de... · Automatic Transfer Switch, 72x72 DIN Size Specifications Equipment Use Electrical control
Page 8: Automatic Transfer Switch, 72x72 DIN Sizedmpcontrol.mx/images/productosemko/switch de... · Automatic Transfer Switch, 72x72 DIN Size Specifications Equipment Use Electrical control