Description
Operation
The ATS-10 provides the mains voltage monitoring and automatic transfer switching. In the event of a mains voltage failure, the remote start relay output is energized and the unit automatically transfers the load from the mains to the generator. Microprocessor technology allows exact measurement, set point adjustment and timing functions with the parameters to be simply programmed and displayed from the front panel.
The ATS-10 automatic transfer switch can detect failure of any phase of the mains supply. If at least one of the mains phase voltages goes outside set limits, the unit operates as follows:
- The Mains Voltage Okay led turns from green to red. The mains contactor output is deenergized and the green Mains Contactor Closed led is extinguished.
- The remote start output is energised after the Remote Start Delay parameter has expired. The generatorstart module receives this signal and initiates the engine start.
- If the Unit Usage Type parameter (P00) is selected as 0 (Type-1); When the generator voltage is within set limits, the yellow Generator Running led will illuminate. The unit will allow the generating set to run without load until the Engine Heating Period parameter is expired. After this time,
If the Unit Usage Type parameter (P00) is selected as 1 (Type-2); When the Engine running signal is present, the yellow Generator Running led will illuminate. The unit will allow the generating set to run without load until the Load gen. signal is present. If this signal is present,
- The generator contactor output will be energized a when the Generator Contactor Delay parameter is expired.
- If the mains voltage return to within limits, the Mains Voltage Okay led will turn to green and the unit waits for the Mains Return delay parameter for the mains voltage stabilization.
- When the Mains Return Delay parameter is expired, the yellow Generator Contactor Closed led is extinguished and the generator contactor output is deenergized. Then the green Mains Contactor Closed led will start blinking and then the unit will wait for the Mains contactor Delay parameter.
- When the Mains contactor Delay parameter is expired, the green Mains Contactor Closed led will illuminate steadily and the mains contactor output is energized. Then the remote start output is deenergized.
- The unit is ready for a new mains failure.
The ATS-10 has got a TEST mode feature. This mode allows the generating set to be tested without taking the load. This mode is also called Emergency backup mode which keeps the generating set running and makes a quick transfer if a mains failure occurs.In this mode, The remote start output will be energized but no load transfer will take place unless the occurrence of a mains failure. If a mains failure occurs, the load will be transferred to the generating set. If the mains voltage return to within limits and the Mains Return Delay parameter is expired, the load will be transferred to the mains, but the generating set will be kept running. The remote start output will only deenergized when the Test mode is cancelled.
the yellow Generator Contactor Closed led will start blinking and the unit wait for the Generator Contactor Delay parameter.
the yellow Generator Contactor Closed led will start blinking and the unit wait for the Generator Contactor Delay parameter.
nd the yellow Generator Contactor Closed led will illuminate steadily
1
Automatic Transfer Switch, 72x72 DIN Size
ATS-10Automatic Transfer Switch
72 x 72 DIN Size
2
Automatic Transfer Switch, 72x72 DIN Size
Specifications
Equipment Use Electrical control equipment for generating sets
Housing & Mounting 72mmx72mmx95mm (including connectors) DIN43700 plastic housing for panel mounting
Panel Cut-out 69mmx69mm
Protection NEMA4X (IP65 at front panel, IP20 at rear side)
Weight Approximately 0.27 kg
Environmental Rating Standard, indoor at an altitude of less then 2000 meters with non-condensing humidity
Operating / Storage Temperature -25ºC to +70ºC / -40ºC to +85ºC
Operating / Storage Humidity 90% max. (Non-condensing)
Installation Over Voltage Cat. II appliances, portable equipment
Pollution Degree II, Normal office or workplace, non-conductive pollution
Mode of Operation Continuous
EMC EN-61000-6-4, EMC generic emission standard for industrial equipment
EN-61000-6-2, EMC generic immunity standard for industrial equipment
Electrical Safety EN-61010-1, safety requirements for electrical equipment for measurement, control and
laboratory use
Battery Supply Voltage(Z) 8-32 VZ max. Operating current is 240 mA
Cranking Dropouts Battery voltage can be 0VZ for max. 100msn during cranking (battery voltage should be
at least nominal voltage before cranking)
Mains Voltage Measurement
35-300VL-NVRMS (@15.6-99.9 Hz). Accuracy: 1% FS. Resolution : 1VGenerator Voltage Measurement
35-300VL-NVRMS (@15.6-99.9 Hz). Accuracy: 1% FS. Resolution : 1V
Display 4 Digits, 7 segments LED display showing :Mains Voltage (Phase-Phase and Phase-Neutral)Alternator Voltage. ( )If the Unit Usage Type parameter (P00) is selected as 0 (Type-1)Program Parameters
Status Indicators TEST Mode LED
Mains Contactor Closed LEDGenerator Contactor Closed LED
Contact Sensing Inputs Load Generator Signal (NO)Engine Running Signal (NO)
Relay Outputs Remote Start Relay (1NO+1NC. 12A@32V Z)Mains Contactor Relay (1NC. 5A@250V V)
Generator Contactor Relay (1NO. 5A@250V V)
Mains Volgage Okay LEDGenerator Running LED
PROG Mode LED
3
Automatic Transfer Switch, 72x72 DIN Size
Maximum 15mm / 0.590 inch
83.5 mm / 3.287 inch11.5mm / 0.452 inch72mm
72
mm
N AG - TE S
Dimensions
Panel Cut-Out
VL12 GEN V.VL23 VL31
TESTPROG
TEST
ATS-10
69
mm
/ 2
.72
in
ch
69mm / 2.72 inch
ATS-10 Parameters List
Front View Terminal Connections
4
Automatic Transfer Switch, 72x72 DIN Size
VL12 GEN V.VL23 VL31
TESTPROG
TEST
ATS-10
12 13 14 15 16 17 18 19
MA
INS
N
MA
INS
L1
MA
INS
L2
MA
INS
L3
GE
N. N
GE
N. L
1
MA
INS
RE
LA
Y
GE
N. R
EL
AY
1 2 3 4 5 10 11
- B
AT
+ B
AT
EN
GIN
E R
UN
.IN
PU
T
LO
AD
GE
N.
INP
UT
12 A @220VV P/N : ATS-10
RE
MO
TE
STA
RT
OU
T
NCNOCÖ
2 X 5 A@220VV
+ +
Type - 1 (P00 = 0): When “Generator Voltage” detected by ATS-10Parameters List
No
P03
P09
P01
P02
Definition of Parameter
Mains Voltage Connection Level
Mains Voltage Disconnection Level
Mains Voltage Upper Limit
Alternator Voltage Lower LimitAlternator Voltage Upper Limit
Min
60
60
60
6060
Max
600
600
600
600600
Default
320
300
440
320440
Unit
VV
VV
VV
VVVV
P00 Unit Usage Type 0 1 0
P10
P07 Remote Start Delay 0 9999 0 sec
P05 Generator Contactor Delay 0.1 25.0 1.0 secP06 Mains Contactor Delay 0.1 25.0 1.0 sec
P04 Mains Return Delay 0 9999 30 sec
P08 Engine Heating Period 0 250 10 sec
Type - 2 (P00 = 1): When “Load Generator Logic Input” detected by ATS-10Parameters List
No
P03
P01
P02
Definition of Parameter
Mains Voltage Connection Level
Mains Voltage Disconnection Level
Mains Voltage Upper Limit
Min
60
60
60
Max
600
600
600
Default
320
300
440
Unit
VV
VV
VV
P00 0 1 1
P07 Remote Start Delay 0 9999 0 sec
P05 Generator Contactor Delay 0.1 25.0 1.0 secP06 Mains Contactor Delay 0.1 25.0 1.0 sec
P04 Mains Return Delay 0 9999 30 sec
Unit Usage Type
+ B
AT
OR
- B
AT
P11 0 9999 0Password
P11 0 9999 0Password
5
Automatic Transfer Switch, 72x72 DIN Size
Three Phase Connection Schematic For Type - 1 (P00 = 0)
MAINS
MAINS CONTACTOR GENERATOR CONTACTOR
LOAD
GEN. RELAYMAINS RELAY
FU
SE
-5
FU
SE
-4
FU
SE
-3
FU
SE
-2
1512
L1 L1
L1
N N
N
L2 L2
L2
L3 L3
L3
14 13 18 17 1619
FU
SE
-1B
AT
TE
RY +
-BA
T
+B
AT
BATTERY NEGATIVE MUST BE GROUNDED
1 2 3 4 5
1
MEASUREMENTCIRCUIT
MEASUREMENTCIRCUIT
12A@220VV
5A@250VV 5A@250VV
c
1c
REMOTESTART
NO NC
NOTE: If single phase sensing is required the single phase can be fed intoall three phase inputs.
+BAT OR -BAT
10 11
NOT CONNECTED NOT CONNECTED
GENERATOR
MAINS
MAINS CONTACTOR GENERATOR CONTACTOR
LOAD
GENERATOR
GEN. RELAYMAINS RELAY
FU
SE
-5
FU
SE
-4
FU
SE
-3
FU
SE
-2
1512
L1 L1
L1
N N
N
L2 L2
L2
L3 L3
L3
14 13 18 1719
FU
SE
-1B
AT
TE
RY +
-BA
T
+B
AT
BATTERY NEGATIVE MUST BE GROUNDED
1 2 3 4 5 10
1
MEASUREMENTCIRCUIT
12A@220VV
5A@250VV 5A@250VV
c
cThe fuses should be as follows:FUSE-1FUSE-2, FUSE-3 1FUSE-4, FUSE-5
1A. TA. T
1A. T
1c
1- Connect the unit as shown in the appropriate diagram above. Be sure to connect the battery supply the right way round and battery negative should be grounded. The connectors can be unplugged from the rear of the unit to facilitate connection.
REMOTESTART
+B
AT
LO
AD
GE
NE
RA
TO
R IN
PU
T
11
+B
AT
NO NC
EN
GIN
E R
UN
NIN
G IN
PU
TO
PT
ION
AL
: U
SIN
G F
OR
GE
N. R
UN
NIN
G L
ED
16
NOT CONNECTED
+BAT OR -BAT
Three Phase Connection Schematic For Type - 2 (P00 = 1)NOTE: If single phase sensing is required the single phase can be fed intoall three phase inputs.
Easy Access Diagram to Programming Parameters
Product Code
ATS-10 Automatic Transfer Switch, 72mmx72mmx95mm Size
i
6
The Programming mode must be entered only while the mains voltage okay and the load supplied from mains.
Automatic Transfer Switch, 72x72 DIN Size
Press the Enter button to confirm the password. If it’s correct, P00 is displayed. If the password is incorrect, the unit will drop out of program mode.
°F°F°F °F°F°F
Press the increment button.
Enter password with increment and decrement buttons.
°F°F°F
°F°F°F
Press the increment button to access to the parameter value.
Change the parameter value with increment and decrement buttons.
Press Enter button to confirm the changed value and access to the following parameter. On this way you can access to theall parameters.
°F°F°F °F°F°F°F°F°F
When the button is pressed for 10 seconds, password is asked for accessing to the parameters.
Press button for accessing to the passwordentering screen
Operation screen
Note: If the PROG button is pressed or if no buttons are pressed for a period of 2 minutes, the unit will return to the normal operation screen.
Operator password
PROG
TEST
PROG
TEST
PROG
TEST
PROG
TEST
PROG
TEST
PROG
TEST
PROG
TEST
Note: If Enter button is pressed and the password parameter is zero, pass screen is ignored and p 00 screen is shown.
It is your responsibility if this equipment is used in a manner not specified in this instruction manual.