ATS-34 Ver1.0 AUTOMATIC TRANSFER SWITCH CONTROLLER FOR DUAL GENERATORS WITH REDUNDANT SYSTEM OPERATOR’S MANUAL

Upload: ngodan

Post on 14-Mar-2018

226 views

Category:

Documents


1 download

TRANSCRIPT

ATS-34 Ver1.0

AUTOMATIC TRANSFER SWITCHCONTROLLER FOR DUAL GENERATORS

WITH REDUNDANT SYSTEM OPERATOR’S MANUAL

ATS-34Automatic Transfer Switch

______________________________________________________________________________________

2

TABLE OF CONTENTS

Section Page

SECTOIN 1: INTRODUCTION 1.1 Preliminary Comments and Safety Precautions .............................................................................. 3 1.2 Product Overview............................................................................................................................. 3 1.3 Functions / Features ........................................................................................................................ 3

SECTOIN 2: OPERATION PANEL 2.1 General ............................................................................................................................................ 4 2.2 Display Window................................................................................................................................ 4 2.3 Operate Touch Buttons.................................................................................................................... 5 2.4 Panel LED Outputs .......................................................................................................................... 6

SECTOIN 3: OPERATION 3.1 General ............................................................................................................................................ 7 3.2 AUTO Mode ..................................................................................................................................... 7 3.3 OFF Mode ........................................................................................................................................ 7 3.4 Bypass Mode ................................................................................................................................... 7 3.5 Programming Instruction.................................................................................................................. 7 3.6 Remote Communication Instruction................................................................................................. 8 3.7 Voltage Adjustment .......................................................................................................................... 9 3.8 Line by Line Programming Table ................................................................................................... 10 3.9 Specification Summary .................................................................................................................. 11

SECTOIN 4: INSTALLATION INSTRUCTIONS 4.1 General .......................................................................................................................................... 11 4.2 Panel Cut-Out ............................................................................................................................... 11 4.3 Unit Dimensions ........................................................................................................................... 12 4.4 Installation Reference .................................................................................................................... 12

SECTOIN 5: TYPICAL WIRING

ATS-34 Automatic Transfer Switch

______________________________________________________________________________________

3

SECTOIN 1: INTRODUCTION 1.1 Preliminary Comments and Safety

Precautions

This document covers installation, operation and maintenance of the ATS-34 Automatic Transfer Switch Controller. This manual is for the use of authorized and qualified personnel only.

WARNING

High voltage can kill.

1.2 Product Overview

The ATS-34 controls the second ATS in a redundant emergency ATS system that works with two backup Gensets. A redundant ATS system consists of two ATS, the first ATS being a standard ATS (Normal-Emergency) that triggers the second ATS (GEN-1 – GEN-2) by using the ATS-34 control. This second ATS control selects which backup generator is the first to run and in the case of a fail start or a breakdown restores power by switching to a second generator. This line circuit illustrated how it works.

Genset-1 Genset-2

Load

Mains

ATSController

ControllerATS-34

Remote StartATS-1

ATS-2

The ATS-34 Controller provides programming flexibility for the two backup generators. Therefore, the ATS switch operates properly through a series of sensing and timing functions.

ATS-34 controller allows you to control the generator duty cycle and alternate operation of the two generators.

The ATS-34 control unit features:

● Microprocessor based with touch screen ● Compact with easy to understand LED display. ● Programmable for cycle-mode or fix-mode displays

for 3-phase and 1-phase voltages and frequencies. ● All programming and operations are done from

the front screen interface. ● Monitors over and under voltages for both

primary and secondary generators ● Monitor over and under frequencies on both

generators. ● Dry-contact alarm for transfer fail and

over-cranking ● Manual forced-bypass ● Compatible with almost all ATS switches ● Optional USB / RS485 / Ethernet remote (mobile

proxy) communication functions. ● Program on-site or from remote (mobile) device

(PC, Smart Phone). ● Auto-saved settings (memory preserved

throughout all power disconnects and resets) ● Front panel display provides source status and

fail alarm indications.

ATS-34Automatic Transfer Switch

______________________________________________________________________________________

4

1.3 Functions / Features

The primary function of ATS-34 controller is to monitor power sources and provide the necessary intelligence to operate a seamless and automatic transfer of load between two generators.

1.3.1 Operational Simplicity

The design of the ATS-34 PLC simplifies routine operation and programming.

1.3.2 Standard Features

All logic settings for different ATS’s are preprogrammed and stored in its non-volatile random-access memory (NVRAM), this memory retains its information when power is turned off. Some features and set points are user adjustable.

Feature 1: Generator Duty Cycle – start attempts settings

You can program the ATS-34 to switch the lead generator duty by time or start-run attempts. When the working generator times out, or runs a number of times the ATS-34 starts the next generator and makes this one the lead generator. (See lines 3 & 4)

Adjustable Duty Time range: 0 to 250 Hours or

Adjustable start attempts 1 to 10

Feature 2: Transferring Time Delay

The ATS-34 controller provides a time delay when transferring from one generator to the other. Countdown begins when the standby source becomes available. (See line 5)

Adjustable time delay range: 0 to 250 sec

Feature 3: Time Delay Engine Cool-down

Controller permits the generator to run unloaded (cool down) after transferring to the other generator. Countdown starts when the transfer is completed. (See line 6)

Adjustable time delay range: 0 to 250 sec

Feature 4: Time Delay OFF Position Time Delay on OFF stops the switch in the center OFF position (completely disconnected) before transferring to the other generator. (See line 7)

Adjustable time delay range: 0 to 99 sec

Feature 5: Under / Over voltage Sensing

The controller monitors the output voltage for both generators. You can set the working voltage window on lines 8, 9, 10, 11, 15, & 16

Adjustable Over voltage range: 110VAC to 520VAC

Adjustable Under voltage range: 80VAC to 470VAC

Feature 6: Under / Over frequency Sensing The controller also monitors the Hertz for each generator. (See line 12, 13, 14, 18, & 19)

Adjustable Over frequency range: 51Hz to 75Hz

Adjustable Under frequency range: 40Hz to 59Hz

SECTOIN 2: OPERATION PANEL 2.1 General Familiarize yourself with ATS-34 hardware:

● The Front Display Window ● The Touch Buttons ● Panel LEDs Display

2.2 Display Window

The ATS-34 controller has a four-digit, seven-segment display panel to monitor all parameters, settings and messages.

Presenting different actions on the display window:

● Dual generator voltage / Duty time / Parameter display ● Time delay countdown display ● Program setting parameter display

2.3 Operate Touch Buttons The front panel supports five sensitive capacitive touch and release buttons.

ATS-34 Automatic Transfer Switch

______________________________________________________________________________________

5

Using the buttons on the control ICON DESCRIPTION

Increase/Selection Touch Button ● Press to increase value ● Press to select voltage

AUTO Touch Button ● Press to engage AUTO ● Press to reset alarm

OFF Touch Button ● Press OFF ● Press to enter program mode

Bypass Touch Button ● Press to force a transfer

Decrease/Selection Touch Button ● Press to decrease value ● Press for Volt / Duty / Freq display

2.3.1 Increase (▲) Button

When the ATS-34 controller is in AUTO, each touch of the up arrow (▲) changes the display to the next phase voltage reading.

When in programming mode, each touch of the Increase (▲) key scrolls through all available parameters. When touching and releasing the increase (▲) button, the displayed parameter changes and increases in single units. The Increase (▲) button will continue to scroll when held down.

2.3.2 Decrease (▼) Button

Under AUTO operate status; each touch of the decrease (▼) button will change the real parameter display between voltage, duty time, and frequency.

When in programming mode, each touch of the decrease (▼) key will scroll through all available parameters. When touching and releasing the decrease (▼) button, the displayed parameter changes and decreased by one value at a time. The decrease (▼) button will continue to scroll if it is pressed and held down.

2.3.3 Auto Key

When selecting the AUTO key, the ATS-34 runs in automatic mode, lighting the LED under AUTO. The controller automatically starts the generator, transfer and retransfers from source to source as commanded by the preprogrammed settings.

In AUTO, all anomalies are accompanied by its matching alarm output; make sure all failures are corrected before touching the auto key to reset the alarm signal.

WARNING

When any failure occurs at its duty time, the controller will shut down the engine, sound an alarm output and switch to the other generator. The failed engine will not start again unless the user manually resets the alarm output by touching the AUTO key.

2.3.4 Bypass Function Button

The Bypass button provides for a manual override of pre-programmed functions. When the ATS-34 is in AUTO, touching the Bypass key ignores the current timers and setting, and the controller will force-start the second generator and transfer the switch from the current working generator to the second generator. The Bypass function can be activated only in AUTO.

LEDs status under Bypass mode

2.3.5 OFF Key

Touching the OFF key, turns the ATS-34 OFF engaging a flashing red LED instantly disabling all functions.

However, in program mode, touching the off button allows the user to change to the next program line to set new parameters using the decrease (▼) or increase (▲) button.

ATS-34Automatic Transfer Switch

______________________________________________________________________________________

6

2.4 Panel LED Outputs

Eight individual red LEDs and four blue LEDs bars are lit when performing or indicating a specific function.

Information concerning the LEDs output

Power available display for G1 and G2

GEN-1 Over Voltage

GEN-1 Under Voltage

GEN-1 Over Frequency

GEN-1 Under Frequency

GEN-2 Over Voltage

GEN-2 Under Voltage

GEN-2 Over Frequency

GEN-2 Under Frequency

GEN-1 Transfer Failure

GEN-2 Transfer Failure

ATS-34 Automatic Transfer Switch

______________________________________________________________________________________

7

GEN-1 Fail to Start

GEN-2 Fail to Start

SECTOIN 3: OPERATION

3.1 General

This section describes the operation and functions of the ATS-34 controller. It is divided into four main categories:

● Automatic mode ● OFF mode ● Bypass mode ● Programming mode

The use of each operation under each category will be explained in this section. It is assumed that prior sections are understood, and the operator has a basic understanding of the hardware.

3.2 Auto Mode

The AUTO mode of the ATS-34 controller provides for automatic start, stop, and transfer and retransfers from source to source as dictated by the programmed values.

The ATS-34 constantly monitors the condition of both generators providing the intelligence for transfer operations.

3.3 OFF Mode

In OFF the ATS-34 disables all the transfers and protection functions, the display window and all the LEDs are turned off.

Both remote start signals are also disabled in OFF and the ATS cannot transfer the load to any source automatically.

However, in program mode, touching the off button allows the user to change the program line table and set the selected parameter using decrease (▼) or increase (▲) button.

3.4 Bypass Mode

If the ATS-34 is running in AUTO, pressing the bypass button ignores its current duties and force starts the next generator, and transfers power from this generator to the other. If the second generator fails to start or its voltage and frequency does not become available, the controller keeps the load connected to the working generator and triggers an alarm.

Activate the Bypass only when in AUTO.

3.5 Programming Instruction The controller is fully programmable from the front faceplate.

To get into programming, set the control-to OFF and press and hold the OFF button for 4 seconds. The word “Vr1.0” appears on the display window for 2 seconds, indicating the software version.

Now you are ready to start the line-by-line programming sequence. Press the OFF key to advance to the next programming line. To change each parameter, press the increase (▲) or the decrease (▼) keys. When pressing and releasing the increase (▲) or decrease (▼) key, the displayed parameter can be increased or decreased by one unit. The Increase (▲) or decrease (▼) will continue to scroll if it is pressed and not released.

Always press the “OFF” button to advance to the next programming line or until the word “End” appears on the screen. Note: To end and exit at any time, simply hold the “OFF” key for 4 seconds.

If you make an error or need to return to factory settings; stay in or reenter programming mode and simultaneously hold the AUTO keys for 4 seconds, until the word “Au.Po” appears on the display confirming all settings are reset to factory. (See line by line programming table for ATS-34 factory settings).

ATS-34Automatic Transfer Switch

______________________________________________________________________________________

8

3.6 Remote Communication Instruction You can monitor and control the two gen-set on a remote PC using the optional USB / RS485 / Ethernet remote communication modules.

WARNING A remote start signal can activate the ATS-34 and the engines can start at anytime without warning. Place a “Danger” warning sign next to each generator, stating that this generator can start at anytime!” also install a warning buzzer or a flash light. Unexpected engine starts can result in serious injury or death. When performing service or maintenance, always disconnect the remote start signal input.

A free App enables the customer to remotely monitor and operate the ATS or generators via portable mobile device. Operating software currently available for Apple iOS5.1 system or above and Android operating system. Free software can be downloaded from App Store or Google Play by simply keying in “Kutai” and hit search.

KCU-01 – USB communication module

KCU-02 – RS-485 communications module

KCU-03 – Ethernet communications module

The corresponding program settings for ATS-34 installed with KCU-XX module includes line [22], [23] and [24]. Programming line [22] is a must. When Line [22] is set to "00", then the remote monitoring software is restricted to read information only whereas remote command is strictly forbidden.

If KCU-02 - RS485 communication module is installed, additional program setting on lines [23] and [25] are needed.

WARNING ATS-34 with KCU-02 module constitutes a closed LAN network. Each controller address can be set from 1 to 99 and not to be repeated. Same transmission rate is a must !!

For more detail, information refers to the KCU-XX user manual.

The installation for the KCU-XX communication module on the ATS-34 controller is fairly simple.

Step 1: Remove cover on the back of the ATS-34.

Step 2: Plug in tighten the screw on the KCU-XX module to the ATS-34 PCB.

ATS-34 Automatic Transfer Switch

______________________________________________________________________________________

9

3.7 Voltage Adjustment (If Needed)

The ATS-34 module is factory tested and fully calibrated. Nevertheless, if you need to modify any voltage reading, follow these procedures.

Step 1:Manually start the primary and standby generators.

Step 2:Enter Program mode and set the program line [21] to (01). “VAdJ” will appear on the display window.

Step 3:Select the desired phase you wish to re-calibrate by pressing the OFF key.

EX. GEN-1 Phase L12 Calibration

EX. GEN-2 Phase L23 Calibration

Step 4:Use a calibrated voltmeter as a reference to recalibrate the ATS-34 voltage readings.

Step 5:Using the increase (▲) and decrease (▼) keys to change the voltage value as appears on your meter.

Step 6:Always press the “OFF” button to advance to the next phase calibration or until the word “End” appears on the screen. To immediately end programming, simply hold the “OFF” key at any time for four seconds to exit program.

End Programming Display

Step 7: If the screen displays “FAIL”, then the calibration is invalid. Touch the OFF key to reset this alarm and repeat from Step 1 again.

Calibration Failure

ATS-34Automatic Transfer Switch

______________________________________________________________________________________

10

ATS-34 Automatic Transfer Switch

______________________________________________________________________________________

11

3.8 Line by Line Programming Table

LINE DISCRIPTION VALUE FACTORY SETTING

1 Is this ATS operating in 1 phase or 3 phases? 00 1Ø 01 3Ø 01

2 Select Switch type See drawing on the back of this manual for different switch types then make your selection

00) MCCB BTS type ATS (Single motor) 01) Mot type ATS (Dual motors) 02) Air circuit breaker (ACB) 03) Double throw type (Single coil) 04) Double throw type (Dual coils) 05) Kutai TS-XXX type ATS

00

3

Select the lead generator. Gen 1 or Gen 2 Or let the controller select the lead generator & switch the lead by run time on duty cycle or by starts & run attempts

00 G1 Leading 01 G2 Leading 02 Alternate lead Gen by run time hours 03 Alternate lead Gen by starts & run attempts

02

4

Do not alternate the gen, but to switch only if the lead gen fails.(00) Alternate both generators by run time on duty cycle or by the number of starts & run. In any position the backup gen will always pickup the load if the lead gen fails

*Do not alternate generators ---Set to 00 *Change lead gen by run time on duty cycle---Set 01 to 250 Hr gen run time then switch. *Change lead by starts -- 01 to 10 starts after that switch

168Hr 10

5 Time delay load transfer 00 to 250 sec 10sec 6 Time delay engine cool-down 00 to 250 sec 30sec 7 Time delay ATS in CENTER-OFF position 00 to 99 sec 5sec 8 GEN-1 over voltage setting 11 to 50 ( 110V to 520V ) 25 (250V) 9 GEN-1 under voltage setting 08 to 47 ( 80V to 470V ) 18 (180V)

10 Time delay if there is a problem with GEN-1 voltage output

00 to 99sec ( 00 = Without voltage monitor function )

10sec

11 GEN-1 over frequency setting 51 to 75Hz 65Hz 12 GEN-1 under frequency setting 40 to 59Hz 55Hz

13 Time delay if there is a problem with GEN-1 frequency output

00 to 99sec ( 00 = Without frequency monitor function )

10sec

14 GEN-2 over voltage setting 11 to 50 ( 110V to 520V ) 25 (250V) 15 GEN-2 under voltage setting 8 to 47 ( 80V to 470V ) 18 (180V)

16 Time delay if there is a problem with GEN-2 voltage output

00 to 99sec ( 00 = Without voltage monitor function )

10sec

17 GEN-2 over frequency setting 51 to 75Hz 65Hz 18 GEN-2 under frequency setting 40 to 59Hz 55Hz

19 Time delay if there is a problem with GEN-2 frequency output

00 to 99sec ( 00 = Without frequency monitor function )

10sec

20 Display mode setting 00 Cyclic mode 01 Fix mode 00 21 Do you want to calibrate voltage reading? 00 NO 01 YES 00

22 Accept remote switch transfer operation (Include emergency stop) 00 NO 01 YES 00

23 KCU-02 module address 00 KCU-02 module restricted 01 to 99

00

24 KCU-02 module transmission rate 01 115200 02 57600 03 38400 04 19200 05 14400 06 9600 07 4800 08 2400 09 1200

03

ATS-34Automatic Transfer Switch

______________________________________________________________________________________

12

3.9 Specification Summary PARAMETER SPECIFICATION

DC Power Supply Voltage 8 to 60VDC

AC Voltage Measurement Range 50 VAC to 510 VAC 50/60 Hz

Frequency Measurement Range 45Hz to 70Hz

Remote Start Contact 7A @ 250VAC Max

GEN-1 ON Contact 7A @ 250VAC Max

GEN-2 ON Contact 7A @ 250VAC Max

Operating Temperature -20°C to 70°C

Storage Temperature -30°C to 80°C

Operating Humidity Maximum 90% relative humidity

Weight 495 g ± 2%

SECTION 4: INSTALLATION INSTRUCTIONS

4.1 General

The designed of the ATS-34 controller is for front panel mounting.

4.2 Panel Cut-Out (All Dimensions in MM.)

ATS-34 Automatic Transfer Switch

______________________________________________________________________________________

13

4.3 Unit Dimensions (All Dimensions in MM.)

4.4 Installation Reference

Silicon waterproof seal Panel Cut-out

A T S

Metal door

Fix bracket

Screw

Screw

Fix bracket

MC

CB

TYP

EB

TSL2 LO

AD

L 1N

L3

Genset-2

L3N L1L2

ATS

-34 Control U

nit

# NLS>> G

e ner ator -1A

ux iliarySw

i tc h#E LS >> G

ener at or-2A

uxil i ar ySw

itc h

Genset-1

L3N L1L2

BROWN

ORANGE

RED

PURPLE

GREEN

BLUE

YELLOW

GRAY

WHITE

PINK

BLACK

RED/WHT

J2

J3

J5

J3

J4

J1C

on

nect

To R

emo

teStart o

n ATS

ATS-34 Automatic Transfer Switch

15

5.2 MCCB Type ATS Wiring Diagram (2P)(220VAC)

#ELS>>Generator-2 A

uxiliary Switch

#NLS>>G

enerator-1 Auxiliary Sw

itch

L2 L1G

enset-2

L1 LOA

DL2M

CC

B TY

PE

BTS

L2 L1G

enset-1

ATS

-34 Control U

nit

ATS-34 Automatic Transfer Switch

______________________________________________________________________________________

16

5.3 MOT Type ATS Wiring Diagram (3P/4P)(220VAC)

ATS

-34 Control U

nit

L2 LOA

D

L1N

L3

Genset-1

Genset-2

N L2L3 L1

A(O

n)

D(P

2)

B(O

ff)

N-M

OTO

R U

NIT

D(P2)

C(P

1)B

(Off)

A(O

n)

L3 L2N L1

E-M

OTO

R U

NITC

(P1)

MO

T TYPE B

TS#N

LS>>Generator-1 A

uxiliary Switch

#ELS>>Generator-2 A

uxiliary Switch

ATS-34 Automatic Transfer Switch

______________________________________________________________________________________

17

5.4 MOT Type ATS Wiring Diagram (2P)(220VAC)

ATS

-34 Control U

nit

#ELS>>Generator-2 A

uxiliary Switch

#NLS>>G

enerator-1 Auxiliary Sw

itchM

OT TY

PE

BTS

C(P

1)

E-M

OTO

R U

NIT

L1L2

A(O

n)B

(Off)

C(P

1)

D(P

2)

N-M

OTO

R U

NIT

B(O

ff)

D(P

2)

A(O

n)

L1L2G

enset-2G

enset-1

L1 LOA

DL2

ATS-34 Automatic Transfer Switch

______________________________________________________________________________________

18

5.5 Air Circuit Breaker Type ATS Wiring Diagram (3P/4P)(220VAC)

ATS

-34 Control U

nit

XF : ON

Coil

MX

1: Trip coil

MC

H: C

harging Alternator

L2 LOA

D

L1N

L3

Genset-2

Genset-1

L2N L3 L1

AC

B TY

PE

BTS

L3N L2 L1

ATS-34 Automatic Transfer Switch

19

5.6 Air Circuit Breaker Type ATS Wiring Diagram (2P)(220VAC)

ATS

-34 Control U

nit

L1L2

AC

B TYP

E BTS

L1L2G

enset-1G

enset-2

L1 LOADL2

MC

H: C

harging Alternator

MX

1: Trip coilX

F : ON

Coil

ATS-34 Automatic Transfer Switch

______________________________________________________________________________________

20

5.7 Single Coil Double Throw Type ATS Wiring Diagram (3P/4P)(220VAC)

#NLS>>G

enerator-1 Auxiliary Sw

itch#ELS>>G

enerator-2 Auxiliary Sw

itch

Genset-2

Genset-1

L3N

L1

LOAD

L2

L2 L1N L3

N L1L3 L2

1 CO

IL DO

UB

LE THR

OW

TYP

E

CS1

CS1

CS1

CS1

CS2

CS2

CS2

CS2

ATS

-34 Control U

nit

ATS-34 Automatic Transfer Switch

______________________________________________________________________________________

21

5.8 Single Coil Double Throw Type ATS Wiring Diagram (2P)(220VAC)

#ELS>>Generator-2 A

uxiliary Switch

#NLS>>G

enerator-1 Auxiliary Sw

itch1 C

OIL D

OU

BLE

THR

OW

TYP

E

L2 L1L1L2

L2

LOAD

L1

Genset-1

Genset-2

CS1

CS1

CS2

CS2

ATS

-34 Control U

nit

ATS-34 Automatic Transfer Switch

______________________________________________________________________________________

22

5.9 Dual Coil Double Throw Type ATS Wiring Diagram (3P/4P)(220VAC)

ATS

-34 Control U

nit

Genset-1

Genset-2

L2 LOA

D

L1N

L3

L3N L1L2

N L1L2L3

2 CO

ILS D

OU

BLE

THR

OW

TYP

E#N

LS>>Generator-1 A

uxiliary Switch

#ELS>>Generator-2 A

uxiliary Switch

CS1

CS1

CS1

CS1

CS2

CS2

CS2

CS2

ATS-34 Automatic Transfer Switch

______________________________________________________________________________________

23

5.10 Dual Coil Double Throw Type ATS Wiring Diagram (2P)(220VAC)

ATS

-34 Control U

nit

#ELS>>Generator-2 A

uxiliary Switch

#NLS>>G

enerator-1 Auxiliary Sw

itch2 C

OILS

DO

UB

LE TH

RO

W TY

PE

L2 L1L2 L1

L1 LOA

DL2

Genset-2

Genset-1

CS1

CS1

CS2

CS2

ATS-34 Automatic Transfer Switch

______________________________________________________________________________________

24

5.11 KUTAI TS-XXX Type ATS Wiring Diagram (3P/4P)(220VAC)

ATS

-34 Control U

nit

L3L1

LOA

D

L2

E2E3 E1

KU

TAI TS3P125

CN1-4

CN1-12

CN1-8

CN1-3

YELLOW

ORANGE

RED/WHITE

GRAY

CS2

CS2

CS2

CS1

CS1

CS1

CN1-2

220VC

OIL

RED

CN1-10

CN1-6

CN1-11

ELS

CN1-9

NLS

BLACK

WHITE

PINK

BLUE

N2

N3

N1

CN1-1BROWN

CN1-5GREEN

#ELS>>Generator-2 A

uxiliary Switch

#NLS>>G

enerator-1 Auxiliary Sw

itch

Genset-1

Genset-2

ATS-34 Automatic Transfer Switch

25

5.12 KUTAI TS-XXX Type ATS Wiring Diagram (2P)(220VAC)

ATS

-34 Control U

nit

#NLS>>G

enerator-1 Auxiliary Sw

itch#ELS>>G

enerator-2 Auxiliary Sw

itch

GREEN CN1-5

BROWN CN1-1

N1

N2

BLUE

PINK

BLACK

NLS

ELS

CN1-11

CN1-6

CN1-10

RED

CO

IL220VCN1-2

CS1

CS1

CS2

CS2

ORANGE CN1-3

KU

TAI TS2P125

E1E2

L2

LOA

D

L1

GRAY

YELLOW

CN1-8

CN1-4

Genset-1

Genset-2

ATS-34 Automatic Transfer Switch

______________________________________________________________________________________

26

5.13 KME WN Type and AICHI WN type ATS Wiring Diagram (3P/4P)(220VAC)

ATS

-34 Control U

nit

Genset-2

Genset-1

L3N

L1

LOA

D

L2

N

KM

E W

N TY

PE B

TSA

ICH

I WN

-TYS

TYP

E B

TS

L2L3 L1

L3N L2 L1

#NLS>>G

enerator-1 Auxiliary Sw

itch#ELS>>G

enerator-2 Auxiliary Sw

itch

CS1

CS1

CS1

CS1

CS2

CS2

CS2

CS2

ATS-34 Automatic Transfer Switch

______________________________________________________________________________________

27

5.14 KME WN Type and AICHI WN type ATS Wiring Diagram (2P)(220VAC)

ATS

-34 Control U

nit AIC

HI W

N-TY

S TY

PE

BTS

KM

E W

N TYP

E B

TS

Genset-1

L1L2

L2LO

AD

L1

Genset-2

L1L2

#NLS>>G

enerator-1 Auxiliary Sw

itch#ELS>>G

enerator-2 Auxiliary Sw

itch

CS1

CS1

CS2

CS2

ATS-34 Automatic Transfer Switch

______________________________________________________________________________________

28

5.15 SOCOMEC ATyS-3S type ATS Wiring Diagram (3P/4P)(220VAC)

ATS

-34 Control U

nit

L2 LOA

D

L1N

L3

Genset-2

Genset-1

N L3 L1L2

L3 L1L2N

SO

CO

ME

C A

TyS-3S

TYP

E B

TS

CS1

CS1

CS1

CS1

CS2

CS2

CS2

CS2

ATS-34 Automatic Transfer Switch

______________________________________________________________________________________

29

5.16 SOCOMEC ATyS-3S type ATS Wiring Diagram (2P)(220VAC)

ATS

-34 Control U

nit

SO

CO

ME

C A

TyS-3S

TYP

E B

TS

L2 L1L2 L1

Genset-1

Genset-2

L1 LOA

DL2

CS1

CS1

CS2

CS2

ATS-34 Automatic Transfer Switch

______________________________________________________________________________________

30

5.17 SOCOMEC ATyS-3e type ATS Wiring Diagram (3P/4P)(220VAC)

ATS

-34 Control U

nit

SO

CO

ME

C A

TyS-3e TY

PE

BTS

L2 LOA

D

L1N

L3

Genset-2

Genset-1

N L2 L1L3

N L1L2L3C

S1

CS1

CS1

2 SC

1SC

CS2

CS2

CS2

ATS-34 Automatic Transfer Switch

______________________________________________________________________________________

31

5.18 SOCOMEC ATyS-3e type ATS Wiring Diagram (2P)(220VAC)

ATS

-34 Control U

nit

L2 L1L1L2

Genset-1

Genset-2

L1 LOA

DL2S

OC

OM

EC

ATyS

-3e TYP

E B

TSC

S1

CS1

CS2

CS2

ATS-34 Automatic Transfer Switch

______________________________________________________________________________________

32

5.19 SOCOMEC ATyS-6 type ATS Wiring Diagram (3P/4P)(220VAC)

ATS

-34 Control U

nit

L2 LOAD

L1N

L3

Genset-2

Genset-1

L1N L3 L2L1L3 L2N

SO

CO

ME

C A

TyS-6 TY

PE

BTS

CS1

CS1

CS1

2SC

1 SC

CS2

CS2

CS2

ATS-34 Automatic Transfer Switch

______________________________________________________________________________________

33

5.20 5.20 SOCOMEC ATyS-6 type ATS Wiring Diagram (2P)(220VAC)

ATS

-34 Control U

nit

L2 LOA

D

L1N

L3

Genset-2

Genset-1

L1L3N L2L1N L2L3

SO

CO

ME

C A

TyS-6e TY

PE

BTS

CS1

CS1

CS1

2SC

1SC

CS2

CS2

CS2

ATS-34 Automatic Transfer Switch

______________________________________________________________________________________

34

5.21 SOCOMEC ATyS-6e type ATS Wiring Diagram (3P/4P)(220VAC)

ATS

-34 Control U

nit

L2 LOA

D

L1N

L3

Genset-2

Genset-1

L1L3N L2L1N L2L3

SO

CO

ME

C A

TyS-6e TY

PE

BTS

CS1

CS1

CS1

2SC

1SC

CS2

CS2

CS2

ATS-34 Automatic Transfer Switch

______________________________________________________________________________________

35

5.22 SOCOMEC ATyS-6e type ATS Wiring Diagram (2P)(220VAC)

ATS

-34 Control U

nit

SO

CO

ME

C A

TyS-6e TY

PE

BTS

L2

LOAD

L1

Genset-2

Genset-1

L1L2L1L2

CS1

CS1

CS2

CS2

ATS-34 Automatic Transfer Switch

______________________________________________________________________________________

36

5.23 MITSUBISHI MD type ATS Wiring Diagram (3P/4P)(220VAC)

ATS

-34 Control U

nit

L2 LOA

D

L1N

L3

Genset-2

Genset-1

L3N L1L2

MITSU

BISH

I MD

TYP

E B

TS

A1

E-M

OTO

R U

NIT

CB

A2

A1

BC

N-M

OTO

R U

NIT

A2

N L1L2L3

#NA

U>>G

enerator-1 Auxiliary Sw

itch#EA

U>>G

enerator-2 Auxiliary Sw

itch

ATS-34 Automatic Transfer Switch

37

5.24 MITSUBISHI MD type ATS Wiring Diagram (2P)(220VAC)

ATS

-34C

ontrol Unit

# EAU

>>Ge ne rator-2

Aux il iary

Switch

# NA

U>>G

en era tor- 1A

u xiliar ySw

it ch

L2 L1

A2 N-M

OT O

RU

NIT

CB

A1

A2

BC

E-M

OTO

RU

NIT

A1

MITS

UB

ISHI M

DTY

PE

BTS

L 2 L 1G

e nset -1G

enset-2

L 1 LOADL2

ATS-34 Automatic Transfer Switch

_

38

5.25 MERLIN GERIN MCB type ATS Wiring Diagram (3P/4P)(220VAC)

ATS

-34 Control U

nit

L2 L OA D

L 1N

L3

Gense t-2

Gens et-1

N L3 L2 L1

MC

H:C

har gingA

lterna tor

MG

MC

BTY

PE

BTS

XF : O

N C

oilM

X1: Trip coil

L2L3N L1

ATS-34 Automatic Transfer Switch

39

5.26 MERLIN GERIN MCB type ATS Wiring Diagram (2P)(220VAC)

ATS

-34 Control U

nit

L1L2

MX

1: Tripcoil

XF

:ON

Coil

MG

MC

BTY

PE

BTS

MC

H: C

hargingA

lterna tor

L1L2G

enset-1G

enset-2

L1 LOADL2

ATS-22 AUTOMATIC TRANSFER SWITCH CONTROL UNIT

______________________________________________________________________________________

40

5.27 System Voltage different From AC220V wiring Diagram

For AC380/440/480V Systemwith 220V motors controls

For AC220V Systemwith 220 V Motors controls

For AC110V control system

220V 380/440/480V

Open

To Neutral