automatic voltage regulator - sprecher-automation.com

2
www.sprecher-automaon.com SPRECON ® -E-C AVR Automac Voltage Regulator

Upload: others

Post on 09-Nov-2021

14 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Automatic Voltage Regulator - sprecher-automation.com

www.sprecher-automation.com

SPRECON®-E-C AVRAutomatic Voltage Regulator

Page 2: Automatic Voltage Regulator - sprecher-automation.com

© Sprecher Automation 2021

All content such as texts, names, configurations, images as well as layouts, designs, logos and graphics are protected by copyright or other applicable rights. Information, technical data as well as details of products or solutions are only general descriptions and do not constitute legally binding commitments. Our deliveries or services are based on customer-specific requirements and require contractual agreements. Changes, misprints, errors and all rights are reserved at all times.

Sprecher Automation GmbH (Headquarters)

Franckstrasse 514020 Linz, Austria T: +43 732 6908-0

F: +43 732 [email protected]

Austria • Germany • The Netherlands • PolandSlovakia • Switzerland • United Arab Emirates

12.1.101.26en I

AUTOMATIC VOLTAGE REGULATORTransformers with motor-driven tap

changers can be controlled with auto-

matic voltage regulators. Actuation of

the motor drive leads to a voltage change

by one tap. If the difference between ac-

tual voltage and set-point exceeds a cer-

tain limit, a regulation command (”up”,

“down”) is initiated.

SPRECON-E-C-AVR can be adapted to

customer-specific requirements to the

greatest possible extent. In addition,

automatic parallel operation of several

units is possible based on the master/fol-

lower principle or on the basis of circuit

reactive current minimisation.

The AVR unit allows five different set

point values that can be selected both

locally or remotely.

Reliable operation is guaranteed by mon-

itoring of under- and overvoltage with

automatic tap changing to the set-point

voltage, monitoring the motor drive and

the tap changer.

Setting data is stored into programmable

memory (FLASH), which ensures a back-

up in case of a voltage failure or after

a restart.

In addition to the possibility of using

the SPRECON-E-C-AVR as a connecta-

ble stand-alone device, the “automatic

voltage regulation” function can also

be implemented in a SPRECON-E-C bay

computer or a SPRECON-E-P protec-

tion device together with other control

functions.

AVR FUNCTIONS• Voltage regulation

• Definite time-delay• Inverse time-delay

• Monitoring of tap changer

• Monitoring of motor operation time

• Monitoring of tap changer limits

• Blocking in case of overvoltage, un-

dervoltage, overcurrent or too high

reactive power

• Line drop compensation (LDC)

• Z compensation

• Accelerated tap changing

• Regulator blocking

• Parallel operation of up to 6

transformers with individual

performance data

• Different modes for parallel operation

• Minimised circulating current

• Off voltage auto return

• Additional application of specific

logic programmes

Graphical Scheme of Response Time

TECHNICAL DATA (EXCERPT)PERFORMANCE CHARACTERISTICS• Voltage measurement

• Operating range: 70 -140 %

• Accuracy: 0.5 %

• Detection of tap position

• BCD code / binary code / Ghielmetti code

• Max. number of inputs/outputs per slot

• Up to 20 digital inputs 24 -220 V DC and 110-230 V AC / 50/60 Hz

• Up to 20 digital outputs 250 V AC/DC

• Up to 10 digital control outputs 250 V AC/DC

• Up to 8 analogue inputs or 4 outputs 0 to ±20 mA/0 to ±10 V

• Up to 8 PT100 inputs for 2-wire or 4-wire circuit

• Up to 8 measurement inputs

• 1 A / 2 A / 5 A or 10

• 50-130 V

• 50 Hz

• Power supply

• 24-60 V DC or 110-250 V DC and 110-230 V AC / 50/60 Hz

COMMUNICATION PROTOCOLS• IEC 60870-5-101/-103/-104

• IEC 61850 GOOSE for cross-communication

• IEC61850 Sampled Values for operation in digital substations

• HSR/PRP

COMMUNICATION INTERFACES• LAN

• 2x Ethernet 10/100 Mbit/s (RJ45) or

• Ethernet switch for optical ring 2x opt. (BFOC) and 1 electr. (RJ45)

• RS232, RS422/485

• Fibre-optic

TESTSAccording to EN 55022, IEC 60255, IEC 61010, IEC 60870-2, IEC 61000-4, IEC 61000-6, CE designation

ENVIRONMENTAL CONDITIONS• Recommended temp.: -5 to +55 °C

• Limits: -25 to +70 °C (on request)

HMI CONTROL PANEL• Mountable attached or detached

• Full-graphical colour display (high resolution)

• 25 configurable LEDs (red, green, orange)

• Expandable with max. two alarm panels