automation and instrumentation systems entity (aise)
TRANSCRIPT
1 | P a g e
TECHNO – COMMERCIAL BID
SUPPLY, INSTALLATION, TESTING AND
COMMISSIONING OF ONLINE DOUBLE
CONVERSION STATIC UPS SYSTEMS
AUTOMATION AND INSTRUMENTATION SYSTEMS
ENTITY (AISE)
ISRO PROPULSION COMPLEX (IPRC) INDIAN SPACE RESEARCH ORGANISATION DEPARTMENT OF SPACE, GOVERNMENT OF INDIA
MAHENDRAGIRI 627 133, TIRUNELVELI DISTRICT,
TAMIL NADU, INDIA
2 | P a g e
INDEX Chapter No Description Page No 1.0 Supplier scope of work 4
2.0 Department scope of work 4
3.0 Standards 5
4.0 Details of UPS systems 5
5.0 Features 5 5.1 System description 5 5.2 Modes of operation 6 6.0 UPS Components & its feature 7 6.1 Rectifier 7 6.2 DC-DC Converter 7 6.3 Inverter 7 7.0 Control Display 7 7.1 Metering & Main display screen 7 7.2 Power flow indications 8 7.3 Alarms 8 7.4 Battery status indications 9 8.0 Battery Management system 9 9.0 Remote operation, monitoring & data logging 9 10.0 Control & Protections 10 10.1 System level control functions 10 10.2 Manual operating modes 10 10.3 Online battery test 11 11.0 Paralleling Panel 11 12.0 Technical specifications 11 13.0 Inspection & testing 13 13.1 Site acceptance test 13 13.2 Installation & Commissioning 14
3 | P a g e
13.3 Warranty 14 14.0 Documentation 14 15.0 Training 14 16.0 SMF VRLA Battery 15 16.1 Technical specifications 15 16.2 Type tests 15 16.3 Routine tests of battery 15 17.0 Prequalification criteria for bidders 16 18.0 List of Annexure 16 19.0 Technical compliance format 20 20.0 Comprehensive Annual Maintenance Contract 25 21.0 Price format 27 22.0 Terms and Conditions 32
4 | P a g e
1.0 Supplier scope of work
The scope includes supply, installation, testing and commissioning of
DSP based, online double conversion UPS systems of different capacities. The
UPS systems have to be commissioned at various facilities in IPRC campus. The
UPS systems are configured as standalone mode and parallel redundant mode
as listed in chapter 4.0. The scope includes,
• Valve Regulated Lead Acid (VRLA) battery banks with open battery
stands.
• Paralleling panel for each set of parallel redundant mode UPS
• Copper cabling between battery bank & UPS.
• The scope shall includes pre-shipment testing, proper packing for
transportation, deliver to IPRC stores, erection, interconnection of
battery banks, testing and commissioning.
2.0 Department scope of work:
� The power cabling and termination of cable to UPS input.
� The power cabling and terminations of cable at UPS output & paralleling panel.
� All earthing including body and Neutral.
� Isolation Transformers at input side of each UPS systems (External to UPS).
� Load required for load testing at site shall be provided.
� For remote monitoring & data logging, the PC, Ethernet cable and network switches will be provided.
5 | P a g e
3.0 Standards The UPS System shall confirm to the latest editions of codes and standards mentioned below.
a) IEC 62040-1-2-3 – Unterruptible Power Supply b) JISC 8702-1, 2 & 3 - 2009 – VRLA Battery or its equivalent
4.0 Details of UPS Systems
Sl No Capacity
Mode of Working
Qty Remarks Cable length (Mtr)
Configuration
1. 10 kVA Standalone 6 Nos. – –
Distance between
each UPS &
Battery Bank – 20
mtrs
Refer Annexure – 1 2. 20 kVA Standalone 2 Nos. – –
3. 2 × 10 kVA Parallel – Redundant
2 Sets 4 Nos. of 10kVA UPS
Refer Annexure – 2
4. 2 × 20 kVA Parallel – Redundant
2 Sets 4 Nos. of 20kVA UPS
5. 2 × 40 kVA Parallel – Redundant
4 Sets 8 Nos. of 40kVA UPS
5.0 Features 5.1 System Description
Each single UPS unit shall operate in double – conversion online mode. The system should consist of the following major components & features.
a) Solid state static PWM converters utilising IGBT
b) Solid state static PWM Inverters utilising IGBT
c) SMF,C20 rated, valve regulated lead acid battery bank (VRLA) for 20
minutes back up time at full load for individual UPS system.
d) Battery management system
e) Static bypass
f) Manual Maintenance bypass
g) Remote communications
h) Input Power Factor Corrected Converter
i) Back-feed Protection
6 | P a g e
j) Separate DSP for Rectifier, Inverter etc
k) Self diagnostics
l) Inverter circuit for synchronisation with an power source
5.2 Modes of Operation:
a) Normal Operation: The inverter shall continuously supply stable AC power to the load. The converter should be able to feed power to a fully loaded inverter as well as recharging the system with fully discharged battery simultaneously if required.
b) Battery Operation: In the event of power supply failure, the inverter shall derive the input from the system battery without any break.
c) Static Bypass: In the event of AC/inverter failure/overload, the load shall be transferred to the bypass source via the static switch without interruption of power to the load. The synchronisation of each inverter in phase and frequency with the bypass source shall be automatic. Transfer of the load back to the UPS outputs shall be automatic and manual also. During transfer, the load shall not suffer an outage or disturbance in the supply of power. To ensure transfer in complete safety, the system shall simultaneously control the static switches.
d) Maintenance bypass operation: In case of maintenance or repair has to be performed on the UPS, load shall be powered from bypass source through maintenance by pass switch. The power shall be transferred from inverter to static bypass and to maintenance bypass or vice versa without interruption by manual operation. For personnel safety during servicing or testing, this system shall be designed to isolate the UPS units while continuing to supply power to the load from the bypass AC source. Transfer to the manual bypass mode and back shall be possible without interruption to the load.
e) Parallel Redundancy operation: The units shall operate in parallel with
redundancy, with the load shared equally between the units. Redundancy shall be of the "n+1". If the total available power is insufficient, the load shall be automatically transferred, without interruption, to the bypass AC source. The UPS shall have an option that enables it to synchronize its output with other like UPS systems. The UPS shall be compatible for adding 2 more UPS’s in parallel.
7 | P a g e
f) Input Phase Reversal: The UPS System rectifier should supply the regulated D.C output even in case of input phase sequence reversal
g) Cold start (normal AC source absent): The battery of each UPS unit shall be capable of ensuring UPS start-up even if normal AC power is not available and continuing operation within the specified back-up time.
6.0 UPS Components & its Features
6 .1 Rectifier The rectifier shall be the IGBT based solid-state equipment and controls necessary to convert alternating current to regulated direct current to supply the inverter and the DC-DC converter. The rectifier shall have the following features.
6.2 DC-DC Converter
The DC-DC converter shall controls to regulate the output of the rectifier
to the levels appropriate for charging the battery and to boost the battery
voltage to the level required to operate the inverter. The DC-DC converter shall
be solid-state, capable of providing rated output power, shall be a pulse width-
modulated design and shall utilize insulated gate bipolar transistors (IGBT’s).
6.3 Inverter
The inverter shall convert direct current from the rectifier or battery via
the DC-DC converter to precise alternating current to power the load. The
inverter shall be solid-state, capable of providing rated output power; the
inverter shall be pulse-width-modulated transformer-free design and shall
utilize insulated gate bipolar transistors (IGBT’s). The inverter shall have the
following features.
7.0 Control Display 7.1 Metering & Main Display Screen
a. Input voltage, line-to-line b. Input current c. Input frequency d. Battery voltage e. Battery charging/discharging current f. Output voltage, line-to-line g. Output frequency
8 | P a g e
h. Bypass input voltage, line-to-line i. Bypass input frequency j. Load current k. % Load l. Load Real Power ( kW), total and percentage of capacity m. Load Apparent Power ( kVA), total and percentage of capacity n. Battery state of charge o. Battery voltage p. Battery charging Current q. Event Logs r. Warning Indicator s. Fault Indicator
7.2 Power Flow Indications
A power flow diagram shall graphically depict whether the load is being supplied from the inverter, bypass or battery. The status of the following components:
a. AC Input Circuit Breaker b. AC Output Circuit Breaker c. Battery Circuit Breaker d. Battery status e. Maintenance Bypass Status
7.3 Alarms
An audible alarm shall be activated when an alarm occurs. All alarms shall be displayed in text form. The following Alarm Messages shall be displayed:
a) Mains Voltage Abnormal b) Mains Under voltage c) Mains Freq. Abnormal d) Charger Fault e) Battery Reversed f) No Battery g) Parallel Comm. Fail h) Bypass failure i) Bypass Abnormal j) Inverter Asynchronous k) Unit Over Load l) System Over Load m) Bypass Phase Reversed
9 | P a g e
n) Load Sharing Fault o) Bypass Over Load
7.4 Battery Status Indicator
A battery status indicator shall display battery state of charge, the present battery voltage, total discharge time and battery time remaining during discharge. A graphical representation of the battery voltage during the discharge shall be displayed.
8.0 Battery management system The UPS shall contain a battery management system which has the following features:
a) The battery management system shall charge the batteries and the active battery charger states are constant-current (charge mode), constant-voltage (float mode) and no-charge (rest mode). The charge mode shall equalise and charge the batteries to near full capacity before entering into float mode. In float mode a constant voltage float charge shall charge the batteries until the batteries are fully charged. The battery shall be monitored in rest mode and the charge cycle shall automatically re-start should the battery voltage drop below pre-determined levels. The charging control system shall activate an alarm when the battery capacity drops below the pre-determined levels.
b) The battery management system shall provide battery backup time remaining while operating in normal mode and battery mode. Battery backup time available information shall be displayed real-time, even under changing load conditions
9.0 Remote Operation, Monitoring and Data Logging a) General: The UPS system shall have the suitable software for remote
operation, monitoring and data logging of all parameters listed in chapter 7.1 to 7.3 through Ethernet communication port. The software must to be able to give detailed information also in cases of UPS failure, in support of the failure diagnostic. The software shall be provided with the UPS to support Windows 7/8, Linux operating systems.
10 | P a g e
b) Remote operation: The UPS systems shall have the provision for remote switching (ON/OFF) through PLC/PC. The necessary feature shall be made available in the UPS.
c) Monitoring and Data Logging: The data shall be logged on remote PC with user friendly format at a probably better than sampling rate of 2 Sec. The UPS shall have all necessary features, software etc. The UPS mimic diagram graphics page shall be provided in remote PC for display of real time parameters, operations status etc. The department will provide the PC, Ethernet communication between UPS and remote PC.
d) Event recording: The UPS system software shall able to provide all event recording such as alarms, power failures, UPS faults, UPS in battery mode, bypass failures, faults etc apart from local display in UPS.
10.0 Controls 10.1 System – level control functions at UPS front panel
a. UPS/Bypass manual Transfer b. UPS/System Shutdown Commands c. Low Battery Warning (Minutes) Set point Adjustment d. Battery Float Voltage Set point Adjustment e. System Settings (Time, Date, Password) Adjustments f. Audio Silence Command g. Alarm Reset Command
10.2 Manual operating modes
a. Startup – The start up screen shall be user-interactive on the display panel in text and graphic form and provide a step-by-step guide for the user to bring the UPS on-line.
b. Load Transfers – A single button shall provide the means to transfer the load to static Bypass/maintenance bypass and back on UPS.
c. Standby mode – Provision shall be made available in the user-interactive LCD display panel to shut off UPS output power without affecting battery charging & MCBs (Input, Battery & Output).
11 | P a g e
10.3 On-Line Battery Test The UPS shall be provided with a menu-driven On-Line Battery Test feature. The test shall ensure the capability of the battery to supply power to the inverter while the load is supplied power in the normal mode. 11.0 Paralleling Panel
The supplier shall provide the wall mountable, powder coated, seven
tank surface-treated paralleling panel for each sets of parallel-redundant UPS
system with suitable rated MCB, Isolator, Change Over Switch (COS), MCCB
of make L&T/Schneider/ABB/GE/Legrend. The details of paralleling panel as
described in annexure 3.
12.0 Technical Specifications SL No
Description of parameters
Specifications Required
1. Capacity (kVA) 10 kVA 20 kVA 40 kVA 2. Power (kW) 8 kW 16 kW 32 kW
3. Acceptable only Makes
RIELLO, EMERSON, NOVATEUR (NUMERIC), APC, Hitachi HIREL ONLY
4. Technology True online, Double conversion architecture, IGBT based, controlled by DSP PWM Technology.
5. Duty Cycle Continuous
6. Isolation The isolation transformer at input side of UPS (External) will be provided by department and hence inbuilt IT is not required.
7. Input side
a. Rectifier IGBT , PWM technique, Power Factor corrected control
b. No. of Phases 3P+N+E, AC Supply c. Rated voltage 320 V – 480 V d. Rated frequency 50 Hz ±2.5 Hz e. Input Power factor ≥ 0.99 f. Input THDi ≤ 5 % at 100% Load
8. Battery stage
a. Type SMF VRLA, AGM type, C20, 12V
b. Backup time 20 Minutes for each UPS at full rated load. In case of parallel redundant configuration, each
12 | P a g e
UPS shall have 20 minutes battery backup independently. Refer drawing in annexure – 1 & 2.
c. Battery stands
Battery stand shall be suitably designed with M.S angular frame with powder coat finish. The scope includes supply, integration and installation at site. All batteries shall be positioned in up right on the stand, interconnected with all necessary cables.
d. Battery Protection There shall be a suitable MCCB Protection in battery stand in addition to protection inside the UPS.
11. Output side
a. Inverter IGBT based b. No. of phases 3P+N+G, AC supply c. Voltage 380V – 415V (Selectable) d. Voltage regulation 1% (Static), 3% (Dynamic) e. Frequency 50 Hz±0.05 Hz f. waveform Pure Sine wave g. Phase Angle
displacement accuracy Balanced loads: 120° ±1°, 100% unbalanced loads: 120°±20
k. Crest factor 3:1 l. THDv < 1 % for 100% linear load
< 5 % for 100% nonlinear load n. Cold Start Required o. Overload 125% for 30 Sec p. % ge Efficiency ≥ 92 % at 100% Load
12. Environment
a. Operating Temperature
0 – 40 deg. Centigrade
b. Ingress Protection IP 20 c. Cooling Forced Air Cooling d. Humidity Upto 95% non-condensing
e. Mounting Floor mounted & Base frame height of 300mm for easy termination of power cables.
f. Cable entry Bottom g. Noise at 1 mtr. level < 55 dB h. EMC IEC 62040 – 2 i. Safety IEC 62040 – 1 j. Design, Test Method IEC 62040 – 3 13. Bypass stage
a. Types of bypass Automatic static bypass and Manual maintenance bypass
13 | P a g e
13.0 Inspection and Testing:
The UPS shall be tested in accordance with applicable standards. The
supplier shall provide to department, a detailed test schedule and mutually
agreed test procedure for prior approval. All tests shall be witnessed by the
department representative. The manufacturer shall provide a test report to
department, incorporating measurements and results of all tests performed.
The UPS tests shall be confined to verifying the performance of the UPS unit
and related accessories. The following tests are to be carried out at
manufacturer’s factory.
1) Load test
2) Equal load sharing of all UPS
3) Verification of Auto Load transfer between UPS if one UPS fails
4) Verification of Bypass mode
5) Input Voltage & Current.
6) Input Current Distortion (THDi)
7) Input Power Factor
8) UPS Output Voltage
9) UPS Output Voltage Harmonics (THDv)
10) Voltage Regulation’
11) Efficiency
12) Mains Failure (Transfer to Batteries and back)
13) Battery Backup time
13.1 Site Acceptance Tests
All routine tests including full load test using a load bank shall be carried
out at site by the supplier. Prior to conducting such tests a detailed Test-
Schedule, Test Procedure and Test Record Format shall be prepared and
submitted by the supplier to department for approval. All test results obtained
shall be submitted in proper formats for approval.
a) Input Voltage & Current.
b) Input Current Distortion (THDi)
14 | P a g e
c) Input Power Factor
d) UPS Output Voltage
e) UPS Output Voltage Harmonics (THDv)
f) Mains Failure (Transfer to Batteries and back)
g) Load Steps (20%-100%, 100%-20%)
h) Inverter-Bypass & Bypass-Inverter Transfers
i) UPS AC Input / Output Efficiency.
j) Load Test
k) Redundancy Test
l) All UPS parameters and alarms transmission to remote monitoring
station
m) Synchronisation test between two UPS
n) Back up time
o) Remote ON/OFF
13.2 Installation & Commissioning
The UPS systems, Battery banks etc associated auxiliary systems shall be
installed and interconnected with power and control cables and earthing as per
the requirements at site. After satisfactory installation and pre-commissioning
tests, the UPS shall be commissioned.
14.0 Documentation
The following documents each 3 hard copies and one soft copy is to be provided for the UPS system, Battery and other accessories as applicable. 1) Operation & Maintenance, instruction manual. 2) Service manual with detailed power and control wiring diagram, 3) List of power and control devices used in the system with complete specifications 4) As-built control wiring diagram 5) Routine & type tests and UPS commissioning test. 6) Soft ware with License for interfacing to remote PC etc. 15.0 Training
The supplier shall provide the training to department engineers for three days at site at free of cost.
15 | P a g e
16.0 SMF VRLA BATTERY (Flame Retardant) 16.1 Technical Specifications Nominal Voltage : 12 V No of Cells : 6 Cells Rated capacity : C20 at 27 deg. C @ 1.75 V/cell Separator : AGM (Absorbent Glass Mat) Current Limit : Max 0.2C & Min 0.1C Purity of Lead : ≥ 99.80% Container : ABS (Acrylonitrile Butadiene Styrene) Ampere hour efficiency : > 95 % Watt hour efficiency : > 85 % Warranty : 3 years Make : EXIDE NXT, PANASONIC, ROCKET, SONNENCHENIN, AMARON Manufacturing Date : Three Months from the date supply 16.2 Type Tests
The supplier shall submit the following latest type test certificates,
a) Visual examination
b) Checking of dimension as per manufacturer’s drawing,
c) Capacity test
d) High rate discharge characteristics
e) Max. Permissible current
f) Test for retention of charge
g) Charge acceptance and deep discharge
h) Resistance to shock
16.3 Routine Test of Battery
a) Capacity test
b) Visual Inspection
c) Verification of Dimensions, Mass
d) Marking & Packing
17.0 Pre-Qualification Criteria
1. The UPS supplier should be either Original Equipment Manufacturer (OEM) or their authorized representative. Latest documentary evidence
16 | P a g e
from the manufacture shall be provided in case of authorised representative.
2. The supplier should have the own testing facility in their premises.
3. The UPS supplier should have support centres /support location with necessary infrastructure for carry out maintenance and also nearer to IPRC within 300kM distance, to attend the service calls.
4. The supplier if they are authorised representative, they should provide letter from manufacturer that they will support AMC & spares for 10 years.
5. List of similar capacity of 40 kVA UPS (at least 10 Nos.) supplied in Govt/Govt. Undertaking.
18.0 LIST OF ANNEUXURE Annexure – 1 : General arrangement layout of Parallel-Redundant
Annexure –2 : General arrangement drawing of standalone mode
Annexure–3 : General arrangement drawing of paralleling panel
17 | P a g e
General arrangement layout of Parallel-Redundant
ISOLATION TRANSFORMER
Rectifier Inverter
Battery Bank (20 Min)
Rectifier Inverter
Battery Bank (20 Min)
UPS 1
UPS 2415
V, 5
0 H
z A
C S
uppl
y
Paralleling Panel
OUTPUT
`SUPPLIER'S SCOPE `DEPARTMENT SCOPE`DEPARTMENT SCOPE
`DEPARTMENT SCOPE
Annexure – 1
18 | P a g e
General arrangement layout of Standalone Mode
ISOLATION TRANSFORMER
Rectifier Inverter
Battery Bank (20 Min)
UPS
415
V,
50 H
z A
C S
uppl
y
OUTPUT
Department Scope `SUPPLIER'S SCOPE
Annexure – 2
19 | P a g e
General Arrangement Drawing of Paralleling Panel
From MV Panel
UPS - 1 UPS - 2
`MCCB `MCCB
ISOLATOR ISOLATOR
Change Over Switch
TO LOADS
UP
S S
yste
ms
are
wor
king
in P
aral
lel -
Red
unda
ntM
ode
with
all
nece
ssar
y co
mm
unic
atio
n ca
bles
&ac
cess
ories
Paralleling Panel
Annexure – 3
20 | P a g e
19.0 Technical compliance format
Supplier Shall Necessarily Fill This Compliance Statement Failing Which Their
Offers Will Not Be Considered
SL No
Description of parameters
Specifications Required Compliance
1. Specify Make & Model of UPS
systems
RIELLO, EMERSON, NOVATEUR (NUMERIC), APC, Hitachi HIREL ONLY
2. Specify Make & Model of VRLA
Battery
AMARON , EXIDE NXT, PANASONIC, ROCKET, SONNENCHENIN,
3. Capacity (kVA) 10 kVA 20 kVA 40 kVA Power (kW) 8 kW 16 kW 32 kW
4. Supplier scope
of work As specified in chapter no. 1.0 of specification document.
5. Standards As specified in chapter no. 3.0 of specification document.
6. Details of UPS
Systems As specified in chapter no. 4.0 of specification document.
7. System
Description As specified in chapter no. 5.1 of specification document.
8. Modes of Operations
As specified in chapter no. 5.2 of specification document.
9. UPS
Components & features
As specified in chapter no. 6.0 of specification document.
10. Metering & main display
screen
As specified in chapter no. 7.1 of specification document.
11. Power flow indications
As specified in chapter no. 7.2 of specification document.
12. Alarms As specified in chapter no. 7.3 of specification document.
13. Battery status indicator
As specified in chapter no. 7.4 of specification document.
14. Battery
Management system
As specified in chapter no. 8.0 of specification document.
21 | P a g e
15.
Remote operation,
Monitoring & Data logging
As specified in chapter no. 9.0 of specification document.
16. System level
control function As specified in chapter no. 10.1 of specification document
17. Manual Operating modes
As specified in chapter no. 10.2 of specification document
18. On-line battery
test As specified in chapter no. 10.3 of specification document
19. Paralleling panel
As specified in chapter no. 11.0 and as per annexure 3 of specification document.
20. Technology
True online, Double conversion architecture, IGBT based, controlled by DSP PWM Technology.
21. Isolation With out in-built IT
22. Rectifier IGBT , PWM technique, Power Factor corrected control
23. No. of Phases 3P+N+E, AC Supply 24. Rated voltage 320 V – 480 V 25. Rated frequency 50Hz±2.5 Hz 26. Input Power
factor ≥ 0.99
27. Input THDi ≤ 5 % at 100% Load
28. Battery SMF VRLA, AGM type, 12V, C20
29. Backup time
20 Minutes for each UPS at full rated load. In case of parallel redundant configuration, each UPS shall have 20 minutes battery backup independently. Refer drawing in annexure – 1 & 2.
30. Battery Bank stand
Battery stand shall be suitably designed with M.S angular frame with powder coat finish. The scope includes supply, integration and installation at site. All batteries shall be positioned in up
22 | P a g e
right on the stand, interconnected with all necessary cables.
31. Battery Protection
There shall be a suitable MCCB Protection in battery stand in addition to protection inside the UPS.
32. Battery Manufactured date
3 months from the date of supply
33. Factory test certificates
Shall be supplied along batteries
34. Battery stands
Battery stand shall be suitably designed with M.S angular frame with powder coat finish. The scope includes supply, integration and installation at site. All batteries shall be positioned on the above stand, interconnected with all necessary cables and commissioned.
35. Battery Protection
There shall be a suitable Battery MCCB Protection in addition to protection inside the UPS
36. Inverter IGBT based 37. No. of phases 3P+N+G, AC supply 38. Voltage 380V – 415V (Selectable )
39. Voltage regulation
1% static, 3% dynamic load condition
40. Frequency 50 Hz±0.05Hz 41. Phase
Imbalance Balanced loads: 120° ±1° 100% unbalanced loads: 120° ± 20
42. Crest factor 3:1
43. THDV < 1 % for 100% linear load < 5 % for 100% nonlinear load
44. Overload 125% for 30 Seconds
45. % ge Efficiency
≥ 92 % at 100% Load
46. Cold start Required
47. Operating Temperature
0 – 40 deg. Centigrade
23 | P a g e
48. Ingress Protection
IP 20
49. Cooling Forced Air Cooling 50. Humidity Upto 95% non-condensing
51. Mounting Floor mounted & Base frame
height of 300mm for easy termination of power cables.
52. Cable entry Bottom 53. Noise < 55 dB 54. EMC IEC 62040 –2 55. Safety IEC 62040 –1
56. Design & test Method
IEC 62040 – 3
57. Types of bypass Automatic static bypass and Manual maintenance bypass
58. UPS Inspection & Testing at Factory
As specified in specification document of chapter no. 13.0
59. Site acceptance tests
As specified in specification document of chapter no. 13.1
60. Installation & Commissioning
As specified in specification document of chapter no. 13.2
61. UPS warranty Two Years 62. Battery
warranty Three Years
63. Battery type tests certificates
As specified in chapter no. 16.2 of specification document
64. Battery routine tests
As specified in chapter no. 16.3 of specification document
65. Pre-Qualification criteria
The UPS supplier should be either Original Equipment Manufacturer (OEM) or their authorized representative. Latest documentary evidence from the manufacture shall be provided in case of authorised representative.
The supplier should have the own testing facility in their premises.
The UPS supplier should have support centres /support location
24 | P a g e
with necessary infrastructure for carry out maintenance and also nearer to IPRC within 300kM distance, to attend the service calls. The supplier if they are authorised representative, they should provide letter from manufacturer that they will support AMC & spares for 10 years.
List of similar capacity of 40 kVA UPS (at least 10 Nos.) supplied in Govt/Govt. Undertaking
66. Acceptance of comprehensive
AMC
As specified in specification document chapter no. 20.0
67. Catalogue & Data sheets
The bidder should attach data sheet and catalogue for the Make & Model quoted for UPS and battery.
25 | P a g e
20.0 COMPREHENSIVE ANNUAL MAINTENANCE CONTRACT
20.1 PERIOD OF CONTRACT
Comprehensive annual maintenance contract for UPS systems (excluding
batteries) including supply of all spares for next 8 years after warranty period.
20.2 Machine details
Sl No
Capacity Mode of Working Quantity Remarks
1. 10 kVA Standalone 6 Nos. – – 2. 20 kVA Standalone 2 Nos. – – 3. 2 × 10 kVA Parallel – Redundant 2 Sets 4 Nos. of 10 kVA UPS 4. 2 × 20 kVA Parallel – Redundant 2 Sets 4 Nos. of 20 kVA UPS 5. 2 × 40 kVA Parallel – Redundant 4 Sets 8 Nos. of 40 kVA UPS
20.3 SCOPE OF WORK
a) Periodic Preventive maintenance, check up of the UPS system once in three
months (i.e.) four visits/year.
b) Verification of UPS output parameters, checking of back up time,
simulation of UPS in battery mode, converter mode, static bypass mode etc.
c) Apart from periodic preventive maintenance visits, all breakdown calls shall
be attended. Break down calls shall be attended and system shall be made
functional within 24 hrs.
d) All spares which are needed to replace during the breakdown shall be
replaced by the party. The cost of such all spares is included in the
comprehensive AMC.
e) All the items, cards, components etc., which are to be replaced shall be
routed always through Department stores.
26 | P a g e
f) Your service Engineer shall bring necessary software, tools and equipments
to execute the AMC.
g) Due to non availability of spares or for any reason if the UPS is not able to
make functional, the party shall provide a standby system until the repair is
completed.
h) Payment for each visit (i.e.) once in 3 months on pro rata basis will be
released after completing successful completion of AMC.
i) In case the break-down are not attended within 24 hours of intimation,
down-time compensation @ 0.5% for the annual maintenance charges per
day shall be recovered from you subject to a maximum of 5%.
j) Relocation/ shifting of equipment: Department reserves the right to relocate
the system as and when necessary within IPRC facilities.
27 | P a g e
21.0 Price format 21.1 10 kVA Standalone UPS
Sl No.
Item Description Unit Qty Unit rate
Total Taxes Freight charges, etc
Landed Cost
1.a
Supply of standalone 10kVA online double conversion UPS system with VRLA battery bank for 20 minutes backup along with accessories.
Each 6
Should not be quoted in
techno commercial bid. Should
be quoted in Price bid.
Should not be quoted in
techno commercial bid. Should
be quoted in Price bid.
Should be quoted in techno
commercial bid.
Should be quoted in techno
commercial bid.
Should not be quoted in
techno commercial bid. Should
be quoted in Price bid.
1.b Installation and commissioning of above 10kVA UPS systems along battery banks and accessories.
Each 6
1.c Comprehensive AMC for 8 years for 10 KVA UPS systems.
Each 6
28 | P a g e
21.2 20 kVA Standalone UPS
Sl No.
Item Description Unit Qty Unit rate
Total Taxes Freight charges, etc
Landed Cost
2.a
Supply of standalone 20kVA online double conversion UPS system with VRLA battery bank for 20 minutes backup along with accessories.
Each 2
Should not be quoted in
techno commercial bid. Should
be quoted in Price bid.
Should not be quoted in
techno commercial bid. Should
be quoted in Price bid.
Should be quoted in techno
commercial bid.
Should be quoted in techno
commercial bid.
Should not be quoted in
techno commercial bid. Should
be quoted in Price bid.
2.b Installation and commissioning of above 20kVA UPS systems along battery banks and accessories.
Each 2
2.c Comprehensive AMC 8 years for 20 KVA UPS systems.
Each 2
29 | P a g e
21.3 2×10 kVA Parallel-Redundant UPS
Sl No.
Item Description Unit Qty Unit rate
Total Taxes Freight charges, etc
Landed Cost
3.a
Supply of 2×10kVA (Parallel-Redundant mode) online UPS double conversion system with VRLA battery banks for 20 minutes backup along with accessories.
Set 2
Should not be quoted in techno commercial bid.
Should be quoted in Price bid.
Should not be quoted in techno commercial bid.
Should be quoted in Price bid.
Should be quoted in techno commercial bid.
Should be quoted in techno commercial bid.
Should not be quoted in techno commercial bid.
Should be quoted in Price bid.
3.b Supply of UPS paralleling panel for 2 X 10kVA UPS system. As per schematic drawing as per Annexure 3 enclosed.
Each 2
3.c
Installation and commissioning of above 2×10kVA (Parallel-Redundant mode) UPS systems along battery banks and accessories.
Set 2
3.d Installation and commissioning of above UPS paralleling panel for 2 X 10kVA UPS system.
Each 2
3.e Comprehensive AMC of 8 years for 10 KVA UPS systems.
Set 2
30 | P a g e
21.4 2×20 kVA Parallel-Redundant UPS
Sl No.
Item Description Unit Qty Unit rate
Total Taxes Freight charges, etc
Landed Cost
4.a
Supply of 2×20kVA (Parallel-Redundant mode) online UPS double conversion system with VRLA battery banks for 20 minutes backup along with accessories.
Set 2
Should not be quoted in techno commercial bid.
Should be quoted in Price bid.
Should not be quoted in techno commercial bid.
Should be quoted in Price bid.
Should be quoted in techno commercial bid.
Should be quoted in techno commercial bid.
Should not be quoted in techno commercial bid.
Should be quoted in Price bid.
4.b Supply of UPS paralleling panel for 2 X 20kVA UPS system. As per schematic drawing as per Annexure 3 enclosed.
Each 2
4.c
Installation and commissioning of above 2×20kVA (Parallel-Redundant mode) UPS systems along battery banks and accessories.
Set 2
4.d Installation and commissioning of above UPS paralleling panel for 2 X 20kVA UPS system.
Each 2
4.e Comprehensive AMC of 8 years for 20 KVA UPS systems.
Set 2
31 | P a g e
21.5 2×40 kVA Parallel-Redundant UPS
Sl No.
Item Description Unit Qty Unit rate
Total Taxes Freight charges, etc
Landed Cost
5.a
Supply of 2×40kVA (Parallel-Redundant mode) online UPS double conversion system with VRLA battery banks for 20 minutes backup along with accessories.
Set 4
Should not be quoted in techno commercial bid.
Should be quoted in Price bid.
Should not be quoted in techno commercial bid.
Should be quoted in Price bid.
Should be quoted in techno commercial bid.
Should be quoted in techno commercial bid.
Should not be quoted in techno commercial bid.
Should be quoted in Price bid.
5.b Supply of UPS paralleling panel for 2 X 40kVA UPS system. As per schematic drawing as per Annexure 3 enclosed.
Set 4
5.c
Installation and commissioning of above 2×40kVA (Parallel-Redundant mode) UPS systems along battery banks and accessories.
Set 4
5.d Installation and commissioning of above UPS paralleling panel for 2 X 40kVA UPS system.
Nos. 4
5.e Comprehensive AMC of 8 years for 40 KVA UPS systems.
Set 2
32 | P a g e
22.0 TERMS AND CONDITIONS
• The Price is firm and fixed.
• Two Part Tender: In the Techno commercial bid any technical and
commercial details shall be mentioned. Price shall not be mentioned. In
the Price bid, price shall be mentioned.
22.1 TAXES AND DUTIES
• EXCISE DUTY: We are exempted from payment of Excise Duty as per
Revenue Notification No. 10/97-CE dated 01.03.1997 as amended by
Notification No. 16/07-CE dated 01.03.2007 or as per Revenue
Notification No.64/95-CE dated 16.03.1995 as amended by Notification
No. 7/08-CE dated 01.03.2008. Necessary Certificate shall be issued as and
when required.
• We are also exempted from payment of customs duties.
• SALES TAX: Sales Tax as applicable extra. Please specify full taxes as
applicable.
• SERVICE TAX: Service Tax as applicable extra. Please specify full taxes
as applicable.
22.2 PAYMENT TERMS
The payment will be made through RTGS within 30days after receipt and
satisfactory completion of commissioning at our site.
22.3 WARRANTY
Two years from the date of commissioning of UPS System against any
manufacturing defects/bad workmanship. If any defects found during the
warranty period, the same shall be rectified / replaced free of cost.
Necessary Warranty Certificate shall be submitted at the time of
completion which shall be forming part of documents for final payment.
33 | P a g e
22.4 ANNUAL MAINTENANCE CONTRACT
Separate Order shall be issued for AMC for 8 years after the warranty
period of two years. AMC charges shall be fixed plus service tax as
applicable. Preventive maintenance shall be done once in three months.
Payment shall be made on pro-rata basis after certification by the Focal
Point and approved by DGM, DAAS. You shall attend any number of
breakdown calls free of cost during warranty as well as AMC period.
22.5 DELIVERY PLACE & PACKING
FOR MAHENDRAGIRI: All the materials and equipments shall be delivered
at IPRC, Mahendragiri.
22.6 DELIVERY / COMPLETION SCHEDULE
Schedule: The UPS system shall be commissioned including supply,
installation, testing and commissioning in 4 months time from the date of
order.
22.7 LIQUIDATED DAMAGE
Delivery, Installation and Commissioning is the essence of the Purchase
Order. In case of delay in Supply, Installation and commissioning beyond
the delivery date by the Supplier, the Supplier shall liable to pay an amount
equal to 0.5% (half percent) of total Purchase Order value per week subject
to a maximum of 10% of the total order value.
22.8 SECURITY DEPOSIT
The Supplier shall deposit an interest free amount equivalent to the 10%
(TEN PERCENT) of the total order value towards Security Deposit for the
due performance of the Purchase Order within 30 days from the date of
Purchase Order. The Security Deposit can be submitted either in the form
of (a) Demand Draft drawn in favour of Accounts Officer, IPRC, (b) Bank
Guarantee in Rs.100/- Non-judicial Stamp Paper obtained from any
Nationalized/Scheduled Bank and (c) Term Deposit Receipts duly endorsed
by the respective Banks in favour of IPRC. This security deposit shall be
returned to the Supplier only upon successful completion of all the
34 | P a g e
contractual obligations or shall be adjusted / forfeited against non-
fulfillment of any of the contractual obligations.
22.9 PERFORMANCE BANK GUARANTEE
The Supplier shall guarantee the successful and satisfactory
performance/commissioning of UPS System. As a performance security,
the SUPPIER shall furnish a performance bank guarantee (format
enclosed) from Nationalized Bank/Scheduled Bank for an amount equal to
the sum of 10% of the order value ensuring the due performance of UPS
System in accordance with all the specifications and terms specified in the
Purchase Order herein valid for 60 days beyond the warranty period. On
due performance, the performance bank guarantee shall be automatically
cancelled and returned to the Supplier within 30 days after expiry of the
Warranty period.
22.10 EXPORT LICENSE
For the goods of foreign origin, if any, the Supplier arrange export license.
22.11 FORCE MAJEURE
a. If at any time during the execution of work, the performance in whole
or in part by either party of any obligation under the work is prevented
or delayed by reasons of any war, hostility, acts of the public
enemy/terrorist, civil commotion, sabotage, fire, flood, earth quake,
epidemics, quarantine restrictions, tsunami, strikes, lock-outs, or acts of
God (hereinafter referred as Eventualities) and if notice is given by either
party to the other within 21 days from the date of occurrence thereof,
neither party shall for such eventuality be entitled to terminate the work
nor shall any party have any claim for damages against the other in
respect of such non-performance or delay in performance. The
performance under the work shall be resumed as soon as practicable
after such eventualities have come to an end and the decision of the
Department whether the performance has been resumed or not shall be
final and conclusive.
b. Provided further that if the performance in whole or in part of any
obligation under the work is prevented or delayed by such eventuality
35 | P a g e
for a period of exceeding 60 days, the Department may at their option
terminate the Contract provided also if the work is terminated under
this clause, the Department will be at liberty to take over from the
Supplier at a price fixed by the Department which shall be final, all
unused, un-damaged, and acceptable material, bought-out components
and stores in course of erection and commissioning in the possession of
the Supplier at the time of such termination of such portion thereof as
the Department may deem fit excepting such material, bought-out
components and stores as the Supplier may with the concurrence of the
Department elect to retain.
22.12 ARBITRATION
Except matters in respect of which the decision of the Department is
final as specified in the Purchase Order, any dispute, disagreement or
question arising out of or relating to or in consequence of the work or
fulfillment or the validity of the enforcement thereof which cannot be
settled mutually, shall within 30 days from the date that either party
informs the other in writing that such dispute or disagreement exists,
be referred to arbitration. The Arbitrator shall be a serving Law officer
of the rank of Joint Secretary to the Government of India and shall be
nominated by Director, IPRC. The award of the Arbitrator so appointed
shall be final and binding on the parties to this Purchase Order.
The arbitration proceedings shall be in compliance with the Arbitration
and Conciliation Act 1996. The performance under this Purchase Order
shall continue during the arbitration proceedings and no payment due
or payable by the Department will be withheld unless any such
payment is or forms part of the subject matter of the arbitration
proceedings. All expenditures towards arbitration will be equally
shared by both the parties.
22.13 JURISDICTION AND APPLICABLE LAW
The Purchase Order shall be governed by the laws of India in force. The
courts of Tirunelveli, Tamilnadu only shall have jurisdiction to deal with
and decide any legal matters or dispute whatsoever arising out of the work.