AXIS A1001 installation with 24 volt lock AXIS T8127 60 W Splitter 12/24 V DC - + High PoE Switch (802.3at) 24 volt lock 123456 3456 12 V 1234 34 12 V 3456 12 V 123456 3 4 2 4 2 4 12 V R2 R1 24 V READER I/O 1 DOOR IN 1 DOOR IN 2 LOCK AUDIO AUX READER I/O 2 READER DATA 1 READER DATA 2 RELAY | PWR DC IN > One door solution with a 24 V lock Application 1. Configure Door 1 lock for Relay Lock for Door 1 12 V Relay 2. Configure Door 1 lock Relay for Locked = Relay open Relay Relay open = Locked Relay open = Locked Relay open = Unlocked 3. Wire the RELAY|PWR connector according to the drawing AXIS Entry Manager Programming Please be sure your power supplies and relays are rated for intended purposes. Illustration does not depict cabling for reader, REX and DPS.

Upload: trinhdang

Post on 07-Feb-2018

225 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: AXIS A1001 installation with Application 24 volt lock · PDF fileAXIS A1001 installation with dual electric strikes PoE Network Switch Door Power Supply 12/24+ 12/24-oor 1 oor 2 12

AXIS A1001 installation with 24 volt lock

AXIS T8127 60 W Splitter12/24 V DC

- +

High PoE Switch (802.3at)

24 volt lock

1 2 3 4 5 6

3 4 5 612V

1 2 3 43 412

V3 4 5 612

V

1 2 3 4 5 6

3 4 2 4 2 412VR2R1 24

V

READER I/O 1

DOOR IN 1 DOOR IN 2 LOCK

AUDIOAUX READER I/O 2

READER DATA 1 READER DATA 2

RELAY | PWR

DC IN

> One door solution with a 24 V lock

Application

1. Configure Door 1 lock for Relay

Lock for Door 1 12 V Relay

2. Configure Door 1 lock Relay for Locked = Relay open

Relay Relay open = LockedRelay open = LockedRelay open = Unlocked

3. Wire the RELAY|PWR connector according to the drawing

AXIS Entry Manager Programming

Please be sure your power supplies and relays are rated for intended purposes.Illustration does not depict cabling for reader, REX and DPS.

Page 2: AXIS A1001 installation with Application 24 volt lock · PDF fileAXIS A1001 installation with dual electric strikes PoE Network Switch Door Power Supply 12/24+ 12/24-oor 1 oor 2 12

AXIS A1001 installation with dual electric strikes

PoE Network Switch

Door Power Supply

12/24+ 12/24-

Door 1 Door 2

12 volt DCElectric Strike

12/24 volt DCElectric Strike

1 2 3 4 5 6

3 4 5 612V

1 2 3 43 412

V3 4 5 612

V

1 2 3 4 5 6

3 4 2 4 2 412VR2R1 24

V

READER I/O 1

DOOR IN 1 DOOR IN 2 LOCK

AUDIOAUX READER I/O 2

READER DATA 1 READER DATA 2

RELAY | PWR

DC IN

> Simple two door solution with one door using external power

Application

1. Configure Door 1 lock for 12 V

Lock for Door 1 12V

2. Configure Door 1 lock 12 V for Locked = GND (-)

12V Fail-secureFail-secureFail-safe

3. Configure Door 2 lock for Relay

12 V Relay

4. Configure Door 2 lock Relay for Locked = Relay open

Relay Relay open = LockedRelay open = LockedRelay open = Unlocked

5. Wire the LOCK connector and the RELAY|PWR connector according to the drawing

AXIS Entry Manager Programming

Please be sure your power supplies and relays are rated for intended purposes.Illustration does not depict cabling for reader, REX and DPS. Voltage is determined by the power supply voltage out

Page 3: AXIS A1001 installation with Application 24 volt lock · PDF fileAXIS A1001 installation with dual electric strikes PoE Network Switch Door Power Supply 12/24+ 12/24-oor 1 oor 2 12

Please be sure your power supplies and relays are rated for intended purposes.Illustration does not depict cabling for reader, REX and DPS.

AXIS A1001 installation with dual locks and external power supply

Door power supply

1A 125VAC

06X12

2A 30VD

C

AZ8222-2C-6D

SSE

1 2 3 4 5 6

3 4 5 612V

1 2 3 43 412

V3 4 5 612

V

1 2 3 4 5 6

3 4 2 4

READER I/O 1

DOOR IN 1 DOOR IN 2 LOCK

AUDIOAUX READER I/O 2

READER DATA 1 READER DATA 2

PoE Switch

Relay

12/24+ 12/24- 12/24+ 12/24-

2 4

Door 1 Door 2

DC IN

12VR2R1 24

V

RELAY | PWR

12/24 volt Electric Strike

12/24 volt Electric Strike

> Two door solution with high current demand locks

> Suggested for use with existing power and relay

Application

1. Configure Door 1 lock for 12 V

Lock for Door 1 12V

2. Configure Door 1 lock 12 V for Locked = GND (-)

12V Fail-secureFail-secureFail-safe

3. Configure Door 2 lock for Relay

Lock for Door 2 12 V Relay

4. Configure Door 2 lock Relay for Locked = Relay open

Relay Relay open = LockedRelay open = LockedRelay open = Unlocked

5. Wire the LOCK connector and the RELAY|PWR connector according to the drawing

AXIS Entry Manager Programming

The AXIS A1001 lock output will connect to the separate auxiliary relay power input. 12/24 volts DC+ from a separate door power supply will connect to the C terminal of the slave relay. This transfers to the NO terminal pushing power to the lock.

Page 4: AXIS A1001 installation with Application 24 volt lock · PDF fileAXIS A1001 installation with dual electric strikes PoE Network Switch Door Power Supply 12/24+ 12/24-oor 1 oor 2 12

AXIS A1001 installation with dual magnetic locks and external power supply

Please be sure your power supplies and relays are rated for intended purposes.Illustration does not depict cabling for reader, REX and DPS.

> Two door solution with high current demand locks

> Suggested for use with existing power and relay

Application

1. Configure Door 1 lock for 12 V

Lock for Door 1 12V

2. Configure Door 1 lock 12 V for Locked = GND (-)

12V Fail-secureFail-secureFail-safe

3. Configure Door 2 lock for Relay

Lock for Door 2 12 V Relay

4. Configure Door 2 lock Relay for Locked = Relay closed

Relay Relay open = UnlockedRelay open = LockedRelay open = Unlocked

5. Wire the LOCK connector and the RELAY|PWR connector according to the drawing

AXIS Entry Manager Programming

Door power supply

1A 125VAC

06X12

2A 30VD

C

AZ8222-2C-6D

SSE

1 2 3 4 5 6

3 4 5 612V

1 2 3 43 412

V3 4 5 612

V

1 2 3 4 5 6

3 4 2 4

READER I/O 1

DOOR IN 1 DOOR IN 2 LOCK

AUDIOAUX READER I/O 2

READER DATA 1 READER DATA 2

PoE Switch

Relay

12/24+ 12/24- 12/24+ 12/24-

2 4

DC IN

12VR2R1 24

V

RELAY | PWR

Door 212/24 volt

Magnetic Lock12/24 volt

Magnetic Lock

The AXIS A1001 lock output will connect to the separate auxiliary relay power input. 12/24 volts DC+ from a separate door power supply will connect to the C terminal of the slave relay. This transfers constant power to the NC terminal pushing power to the lock.

Page 5: AXIS A1001 installation with Application 24 volt lock · PDF fileAXIS A1001 installation with dual electric strikes PoE Network Switch Door Power Supply 12/24+ 12/24-oor 1 oor 2 12

Please be sure your power supplies and relays are rated for intended purposes.Illustration does not depict cabling for reader, REX and DPS.

> Two door solution with high current demand locks

Application

AXIS Entry Manager Programming

AXIS A1001 installation with dual integrated locksets

Data out

Splitter

PoE IN

12/24+

12/24-

1A 125VAC

06X12

2A 30VD

C

AZ8222-2C-6D

SSE

Intergrated Lockset

Intergrated Lockset

Relay

Data + Power Data

PoE Switch

30 Watt Midspan

1 2 3 4 5 6

3 4 5 612V

1 2 3 43 412

V3 4 5 612

V

1 2 3 4 5 6

3 4 2 4 2 412VR2R1 24

V

READER I/O 1

DOOR IN 1 DOOR IN 2 LOCK

AUDIOAUX READER I/O 2

READER DATA 1 READER DATA 2

RELAY | PWR

Door 1

Door 2

DC IN

> AXIS T8127 60 W Splitter 12/24 V DC

High PoE Splitter

> AXIS T81B22 DC 30w Midspan 1-port> AXIS T8133 Midspan 3w 1-port> AXIS T8123-E Outdoor Midspan 30w 1-port

30 Watt Midspan options

The AXIS A1001 lock output will connect to the separate auxiliary relay power input. 12/24 volts DC+ from a separate door power supply will connect to the C terminal of the slave relay. This transfers to the NO terminal pushing power to the lock.

1. Configure Door 1 lock for 12 V

Lock for Door 1 12V

2. Configure Door 1 lock 12 V for Locked = GND (-)

12V Fail-secureFail-secureFail-safe

3. Configure Door 2 lock for Relay

12 V Relay

4. Configure Door 2 lock Relay for Locked = Relay open

Relay Relay open = LockedRelay open = LockedRelay open = Unlocked

5. Wire the LOCK connector and the RELAY|PWR connector according to the drawing

Page 6: AXIS A1001 installation with Application 24 volt lock · PDF fileAXIS A1001 installation with dual electric strikes PoE Network Switch Door Power Supply 12/24+ 12/24-oor 1 oor 2 12

Please be sure your power supplies and relays are rated for intended purposes.Illustration does not depict cabling for reader, REX and DPS.

> Solution for using relays to control devices such as HVAC, gates, and other auxiliary devices

Application

AXIS Entry Manager Programming

AXIS A1001 installation with dual external auxiliary devices

R2

Data 0utPOE IN

12/24+

12/24-

1A 125VAC

06X12

2A 30VD

C

AZ8222-2C-6D

SSE

1A 125VAC

06X12

2A 30VD

C

AZ8222-2C-6D

SSE

Splitter

Relay Relay

Energy Management

Data + Power Data

30 Watt Midspan

PoE Switch

1 2 3 4 5 6

3 4 5 612V

1 2 3 43 412

V3 4 5 612

V

1 2 3 4 5 6

3 4 2 4 2 412VR2R1 24

V

READER I/O 1

DOOR IN 1 DOOR IN 2 LOCK

AUDIOAUX READER I/O 2

READER DATA 1 READER DATA 2

RELAY | PWR

DC IN 1. Configure Door 1 lock for 12 V

Lock for Door 1 12V

2. Configure Door 1 lock 12 V for Locked = GND (-)

12V Fail-secureFail-secureFail-safe

3. Configure Door 2 lock for 12 V

Lock for Door 2 12V

4. Configure Door 2 lock 12 V for Locked = GND (-)

12V Relay open = LockedRelay open = LockedRelay open = Unlocked

5. Wire the LOCK connector according to the drawing

> AXIS T8127 60 W Splitter 12/24 V DC

High PoE Splitter

> AXIS T81B22 DC 30w Midspan 1-port> AXIS T8133 Midspan 3w 1-port> AXIS T8123-E Outdoor Midspan 30w 1-port

30 Watt Midspan options

Page 7: AXIS A1001 installation with Application 24 volt lock · PDF fileAXIS A1001 installation with dual electric strikes PoE Network Switch Door Power Supply 12/24+ 12/24-oor 1 oor 2 12

Please be sure your power supplies and relays are rated for intended purposes.Illustration does not depict cabling for reader, REX and DPS.

> Two door solution with one 12v lock and one 12 or 24v lock

Application

AXIS Entry Manager Programming

1 2 3 4 5 6

3 4 5 612V

1 2 3 43 412

V3 4 5 612

V

1 2 3 4 5 6

3 4 2 4 2 412VR2R1 24

V

READER I/O 1

DOOR IN 1 DOOR IN 2 LOCK

AUDIOAUX READER I/O 2

READER DATA 1 READER DATA 2

RELAY | PWR

DC IN

Data out

12 volt Magnetic Lock

12/24 volt Magnetic Lock

PoE in

Jumper Wire

12/24+

12/24-

Splitter

Data + Power Data

30 Watt Midspan

PoE Switch

Door 1 Door 2

AXIS A1001 installation with dual magnetic locks

Voltage is determined by the POE splitter voltage out.

1. Configure Door 1 lock for 12 V

Lock for Door 1 12V

2. Configure Door 1 lock 12 V for Locked = 12 V

12V Fail-safeFail-secureFail-safe

3. Configure Door 2 lock for Relay

Lock for Door 2 12 V Relay

4. Configure Door 2 lock Relay for Locked = Relay closed

Relay Relay open = UnlockedRelay open = LockedRelay open = Unlocked

5. Wire the LOCK connector and the RELAY|PWR connector according to the drawing

> AXIS T8127 60 W Splitter 12/24 V DC

High PoE Splitter

> AXIS T81B22 DC 30w Midspan 1-port> AXIS T8133 Midspan 3w 1-port> AXIS T8123-E Outdoor Midspan 30w 1-port

30 Watt Midspan options