Series 70Electric Actuato
-
8/6/2019 B-1016_EL_S-70_2009-10
2/12
The BraySeries 70Electric Actuator
RUGGED ElEctRicactUatoR FoRRotaRY ValVES
300 to 18,000 lb-inoUtpUt toRqUE
bry crs yersf rve suess eer u,med wh -
vve egeerg,hs rdued heSeres 70. the Seres70 feures -ff r
mdug r. ths red,rud eer ur fr rryvves devers hghy reeserve.
brys uue, usmerfredydesged cr ceer hsmy dvges ver rese
dusry sdrds udg: UL,CSAandCEcerticationof
ms us Easeofcustomereldwiring
drey he erm srwhu erferee frmher mes
Simpleanduniquemanualverrde hdwhee sysem
Lowestproleandlightestwegh ur he mrke
Simplengerorscrewdriverdjusme f rve m
ms whu erfereefrm her mes
Highlyvisiblevalvestatusdsy ms us
Externallyadjustabletravelss
Captivehousingscrews
addy, mes reurg usmer ess rereed udereh he pwerceer ver e.
loW pRoFilE, coMpact,HIGHTORQUEDESIGNThe Series 70 is by ar the mostcompact, lowest profle design o anyelectric actuator delivering compara-ble torque output. Thorough researchand many years o feld experiencehave gone into the development othis state-o-the-art actuator the
product of the future. This design o-ers the advantages o greatly reducedspace requirements, lighter weightand ease o installation and main-tenance when compared to otherelectric actuators. When mounteddirectly to Bray valves, the Series 70 isespecially compact.
SERIES70
EXtERioR FEatURES
DIRECTMOUNTINGOFTHESERiES 70 on bRaY ValVESBray actuators mount directly to Brayvalves without using any externallinkage. Field installation is simpleand misalignment is minimized. Forsanitary processing and outdoorapplications, the Bray direct mount-ing system reduces the possibility ocontamination buildup or corrosionbetween the valve and actuator. Themounting pattern complies with ISO
5211 and VDI/VDE 3845 (NAMURrecommendations). Standard rota-tion is 90 reversible. Bray can providelinkages or mounting the Series 70 toother devices requiring 90 rotation.Please consult the Bray actory orurther inormation.
The Series 70 compared to a typicalactuator, both mounted to 4" Bray valves.
Series 70 manual overridehandwheel with optional spinner.
MECHANICALTRAVELSTOPSStainless steel mechanical travelstops permit precise eld adjust-ment o actuator movement tospecic degrees o rotation. Thetravel stops are located outside thebase or easy readjustment withoutremoving the cover. Stainless steellock nuts with O-ring seals hold thetravel stops securely in place. Thetravel stops are normally set at theactory to allow 0 and 90 travel.
EXploSion pRooF EncloSUREThe Series 70 waterproo/explo-sion proo unit is UL NEMA 4,4x,7&9listed and certied to specicationsor hazardous locations. The rugged,heavy duty housing contains precisionmachined bores and fanges to meet
fame path requirements. Waterproo/ explosion proo models are currentlyavailable with 800 to 2,000 lb.-in. outputorque, continuous or intermittent duty
2
-
8/6/2019 B-1016_EL_S-70_2009-10
3/12
E
D
b
c
a
EncloSURE (a)The Series 70 waterproo unit is ULNEMA 4, 4x listed. Die-cast aluminumcover and base are high-quality poly-ester powder coated or exceptionalcorrosion, wear, impact and ultra-violetresistance
ManUal oVERRiDE (b)A manual override handwheel is stan-dard on all models to rotate the valvewithout electrical power. A yellow cau-tion stripe around the handwheel hubindicates the handwheel is engaged ormanual operation.
captiVE coVER boltS (c)The cover is attached to the base bystain-less steel bolts. When the cover isremoved the bolts are held captive inthe cover. This prevents time consumingproblems caused rom lost or misplacedbolts.
ValVE StatUS DiSplaY (D)The Series 70 eatures a highly vis-ible valve status display on most units.Prominently labeled and color coded yellow or open, red or closed thedisplay indicates valve position throughthe ull range o travel. The displaycan be seen rom almost any angle.Made o high impact, heat and chemicalresistant clear polycarbonate, this displaywithstands caustic wash down and oersexcellent corrosion protection. Potentialleak paths are eliminated since theindicator cover utilizes a static seal, nota dynamic seal.
ElEctRical cablE connEctionS(E) (o) A multi-pin, watertightcable receptacle oers ull compatibilitywith todays industrial wiring systems.Factory pre-wiring prevents errors andallows quickconnect eld installation.Cord sets with connection/fying leads
or extension cords with connectionson both ends can plug directly into thereceptacle.
conDUit EntRiES (F)
The Series 70 eatures two conduitconnections in either NPT or metricthreads. One entry is or power, oneor control wiring.
PILOTDRILLEDHOLESFORLOCA
contRol Station MoUntinG (GThe conduit entry panel has our holewhich may be easily tapped or the
installation o optional localControl Station.
F
G
3
-
8/6/2019 B-1016_EL_S-70_2009-10
4/12
CONTROL
CENTER
contRol cEntERFEatURES
toRqUE liMitinGSWITCHINGSYSTEM(o)The torque limiting switching systemconsists o two SPDT mechanicalswitches and two actory calibratedset screws. The upper cam adjuststhe torque limit in the open direc-tion, and the lower cam adjusts thetorque limit in the closed direction.
The switches independently respondto predetermined loads in both theopen and closed travel directions bysensing the movement o the wormshat, and interrupting the electricalpower to the motor. The switchesoperate at any point o actuatortravel.
clEan anD EaSYaccESS to allFiElD WiRinG anDaDJUStMEntS
Brayhasspecicallyegeered he Seres70 cr ceer frusmerfredyveee. Desged
likeajunctionbox,he Seres 70 ffersy fr he esesess ermk wrg, mdjusmes dswh s.aessres re esydded, eher efres r fers. there-fre, he me reuredforeldstart-upand
djusme s greyredued, d mee e erfrmed wh ssured esed sfey.
brys uue desg, mdu-r sysem f mes dessres, d vvefeures me es meedys dusr reuremes.
TRAVELLIMITSPDTSWITCHES
(a) Bray has provided two SPDTmechanical switches as standard.These durable, high quality switchesare mechanically isolated and electri-cally independent. The dedicated
circuits eliminate any voltage cross-over between the switches. Thisswitch combination is used or bothopen and closed positions o thevalve and requires only one cam oreach direction o valve travel. Braysdesign provides synchronicitybetween motor control and positiondisplay. Switches are easily accessiblewithout intererence rom othercomponents. Each switch is markedwith open or close labels and the
cams are color coded, green or openand red or close, eliminating the pos-sibility o making wrong adjustmentso travel limits or eld wiring errors.
AUXILIARYSWITCHES(o)Independent dry-contact SPDTmechanical switches are available toindicate travel position to remotecustomer control systems.
aUtoMatic poWERCUTOUTSWITCH(b)
The Series 70 is supplied with a SPDT
mechanical switch which cuts powerto the motor when the handwheelis engaged or manual operation.This switch also unctions as a saetyemergency shutdown device thatimmediately stops the actuatormotor even i electrical power isstill being applied to the actuator.
cERtiFicationS / appRoValS
Bray has gained UL, CSA and CE cer-tications on most intermittent andcontinuous duty actuators. These cer-
tications insure that the Series 70 hasbeen designed to the highest qual-ity requirements and most stringentsaety standards worldwide. Substan-tial resources have been invested
to assure our customers that the
Series 70 is the best actuator on themarket and will remain so.
SERiES 70 applicationSThe Series 70 is the ideal choice orprocess control applications involving: Automation and computer systems Buttery, ball, plug and other
rotary valves Dampers, switches, safety and
ow-control devices Machine and xture indexing Hostile environments demanding
excellent moisture, chemical andcorrosion resistance
Long service life and ruggedreliability
inDUStRiESBrays Series 70 Electric Actuators areused in a wide range o industries worldwide, including: Chemical, Pharmaceu-tical, Petroleum Refning and Oilfeld,Microelectronics, Pulp and Paper, Waterand Waste Water Treatment, Brewing,Food Processing, Beverages, Power,Marine, Mining, Textile and HVAC.
Torque Limit Switches shown withmounting bracket sectioned for clarity.
4
-
8/6/2019 B-1016_EL_S-70_2009-10
5/12
F
b
a
D
c
E
caMS / caM aDJUStMEnt (c)Brays patented cam design is an out-standing eature o the Series 70. Camsor each switch are infnitelyadjustableby nger touch or screwdriver with nospecial tools needed. The adjustmentknobs rotate the specially ormed cams.
Each cam is color coded the red adjust-ment knob controls the red cam (closeposition), and the green knob controlsthe green cam (open position). Standardactory setting allows 90 travel betweenopen and closed positions.
o-RinG SEal FoRWATERTIGHTENCLOSURE(F)
The large seal between the coverand base provides a waterprooseal and prevents internal corrosionThe Bray Series 70 O-ring seal is thebest design or watertight enclosureand is ar superior to commonlyused gaskets.
tERMinal blocK (D)
The actuator switches are pre-wired to
a terminal block. The block has beendesigned or ease o customer wiringwithout intererence rom other com-ponents and eatures clearly markedterminal numbers. The block has beenplaced near the two conduit entrieswith ample room or running wire leads.A wiring diagram is included inside thecover or easy reerence. The groundwire screw (E) is plated green andpositioned or easy access. With someoptional eatures Bray installs a secondterminal block or Bray actory wiring
and customer eld wiring o additionallimit switches.
HEATER(G)(o)Pre-wired to the terminal block,a sel-regulating heater preventscondensation rom collecting insidethe actuator, which could cause damage to the electrical components. Thheater is mounted below the switchplate. Heaters are ideal or use inapplications with extremely widetemperature or humidity ranges.
5
G
-
8/6/2019 B-1016_EL_S-70_2009-10
6/12
-
8/6/2019 B-1016_EL_S-70_2009-10
7/12
SElF-locKinGoUtpUt DRiVE aSSEMblYThe output drive assembly eatures asel-locking worm and worm gear drivewhich holds the valve in the desiredposition without the need or electro-mechanical braking systems.The worm shat directly drivesthe worm gear. The Worm (G)
is made o chrome-moly steeland the segmented Worm Gear(H) is a precision machinedaluminum bronze casting. Theworm gear and Output Shat(i) are one part. The outputshat is the driving memberthat positions the valve. Theworm gear drives the valve statusdisplay shat which operates theinnitely adjustable cams to limitthe electrical travel o theactuator.
MECHANICALTORQUEliMitinG SYStEM(o)
The mechanical torque limiting systemconsists o a Worm Shat, a Worm (G), aset o Torque Disc Springs (J) and aShat Groove (K) or torque limiting
switches. The torque disc springs,located on each side o the worm,
resist the linear movement othe worm shat. The worm
shat is driven against the
torque disc springs in response to out-put torque. The shat groove actuatesthe torque limiting switches, locatedabove in the Control Center, to startand stop the motor. (Please reer tothe Control Center section on page 4or description o the Torque Limit-ing Switching System). The preciselycontrolled movement o this system isthe main torque limiting element othe Series 70.
H
GJ K
b
a
c
i
7
H
c
-
8/6/2019 B-1016_EL_S-70_2009-10
8/12
MoDUlatinGactUatoR FoRpREciSion contRol oFValVE poSition
the bry Seres 70Eer aur e eued wh Serv fr reser f vve
s. the Servsss f mr-ressr redru rd d feedk em-eer ssemy, whhbothtentirelywh he sdrdSeres 70 urhusg. the rurd hs ermks fr usmereldwiring,andother
erms fr eres he -ur mes.the feedk e-meer s drve y ger se eed he ur uudrve. as vere Servs ef ser us mmu-, suh sDevene.
C
OmmaNd
CENTER
coMManD cEntERoptionSSERVo pRo opERationThe Servo Pro can be congured bythe actory or the customer to ac-cept several types o input signals,such as 4-20 mADC, 0-10 VDC, 0-5VDC or potentiometer control. Each
terminal connection and indicatoris clearly labeled to simpliy eldwiring and operation. The inputsignal electronically represents thedesiredactuator position, and theinternal eedback potentiometersignal electronically represents theactualactuator position. The
microprocessor constantly comparesthe two signals, and i a dierence isdetected, drives the actuator in theproper direction until the signals areequal. When a balance is reached, themicroprocessor turns o the actuatormotor. The worm gear then mechani-cally holds the valve in the desiredposition until the input signal is
changed again.
SpEED contRolAdjustments are congurable orboth open and closed speed controlo the actuator motor. In addition,an approach control circuit senseswhen the actuator is about to reachthe desired valve position, and pulsesthe motor to avoid overshootingthe set point.
potEntioMEtER calibRation
Calibration o the eedback potenti-ometer is done through a unique geararrangement that is easily accessibleand eliminates the need o any specialtools. A simple adjustment o Brayspatented cam drive aligns the potenti-ometer gear as easily as a travel cam.
SERVo pRo FEatURES / SpEciFicationSne:Serv s ve fr mdug serve uus duy
urs y.ne:Standard is the way the Servo is set at the actory.
Congurable means the customer, or the actory, can modiy the Servo bysetting 10 DIP switches.
POWER INPUT 24 , 120 or 24 0 VAC, 50/60 Hz(power must match motor)
POWER CONSUMPTION 2 Watts (not including actuator power)
INPUT SIGNAL Standard: 4-20 mADC 250 Ohm Input Impedance.Congurable: 0-10 VDC, 2-10 VDC, 10K Ohm or greaterpotentiometer, 0-10 VDC has 2.1 K Ohm Input Impedance
CALIBRATION Single Button Autocalibration
INDICATORS Power: Green LEDStatus: Flashing Red / Green LEDMotor: Red LED (Close), Green LED (Open)
CONTROL MODES Standard: Full Range, Direct ActingReverse Acting, Split Range
FAIL POSITION Standard: Fail Closed(Loss o Input Signal) Congurable: Fail Open
CONTROL CHARACTERISTIC Linear
DUTY CYCLE 100%
INTERNAL FEEDBACK 10K Ohm Potentiometer, gear driven
RETRANSMISSION OUTPUT Standard: 4-20 mADCCongurable: 0-5 VDC, 0-10 VDC, 2-10 VDCRetransmission Output is designed to drive an isolated250 500 Ohm resistive load.
SPEED CONTROL Standard: Full Speed (Speed Control is Disabled)Congurable: Bidirectional Independent Open andClose Trim Pots adjustment
Feedback Potentiometer Gear
8
-
8/6/2019 B-1016_EL_S-70_2009-10
9/12
FEEDbacK potEntioMEtERThe eedback potentiometer gear hasa green rib which should be alignedwith the slot on top o the cam-indica-tor shat when in the ully open posi-tion. This simple alignment ensures thepotentiometer will provide the ServoPro with continuous, accurate actuator-valve position eedback.
VoltaGE SpiKE pRotEctionVoltage spikes that can damage electri-cal equipment are very common in in-dustrial locations. Large voltage spikescan be caused by switching powerloads, such as large motor drives, at thecustomer location. The output stageTRIACs o the Servo Pro are protected
against damage rom voltage spikesby a special combination o limitswitchcircuitry metaloxidevaristor(MOV)for
transient voltage suppression zerocrossingdetection
DEVicEnEt SERVo pRoBray also oers the Series 70 with the
most advanced serial bus communica-tion Servo on the market. The BrayDeviceNet Servo Pro is ully ODVA(Open DeviceNet Vendor Association)compliant. Benets include greatlysimplied eld wiring and installation,advanced control and diagnostics inreal-time rom a remote location, andull network integration. Pleasecontact your Bray representativeor more inormation.
contRol Station (o)
Bray has designed a manual localelectrical control station that fush
mounts directly to the Series 70. TheControl Station eatures:alocaloffremotecontrolswitch anopenstopcloseswitch twolightswhichlocallyindicate
open and closed valve positionThe cover plate can be rotated inany 90 increment, allowing the customer to operate and view the statwith ease. The enclosure is aluminu
and weatherproo (NEMA 4, 4X, IP65). Additionally, the control stationhas captive cover bolts andtwo input ports available in the ol-lowing thread connections: 3/4" NPor M25. Two dierent multi-pin,watertight electrical cable connectiare also available.
Control Station
9
Servo Pro
shown
-
8/6/2019 B-1016_EL_S-70_2009-10
10/12
WatERpRooF / EXploSion pRooF EncloSURE Dimensions are in Inches [Millimeters in brackets]
Actuator
SeriesA B C D E F G H J
K
(UNC)
x B.C.
M
(UNC)
x B.C.
N P Q RWt.lbs
[kgs]
S70-708
S70-712
S70-720
12.5
[317]
8.0
[203]
3.7
[94]
7.67
[195]
2.5
[64]
2.69
[68.3]
.56
[14.2]
3/4
2.6
[66]
5/16-18x 2.76
F07
1/2-13x 4.92
F12
1.18
[30]
.87
[22]
2.01
[51]
8
[203]
34[16]
dImE
NSIONS
10
nes:1) Dimensions are in Inches,
[Millimeters in brackets].2) Handwheel Spinner
shown in drawing isavailable as an option.
3) K & M Dimensions arealso available in M8,M12, and M20.
4) N Dimension is alsoavailable with DoubleSquare (Star) drive.
KTypically4 Places
MTypically4 Places
F
B
E5.4Max Stem
Entry
D A1.25 [32]
J
Holes For#10-24 UNC[M5]
Typically .78[20]
3.00[76]
H NPT Conduit Entry 2 Places or M25
Allow 2.5 forCover Removal
R
G
1.97[50]
.47[12]
2.38
[60]
2.50[62.7]
.62[15.8]
3.05
[77.9]
Detail A2 - Output Bore
U
TS
Spinner Not shownsee note 2
C
S70-130/180S70-131/181
BAllow 3.12 [80]
For Cover Removal
Typically .78[20]
J E
.58 For Override[14] Engagement
3.00[76]
See Note 2
R
DA
G C
CLOSE
OPEN
N x Q Deep
Spinner NotShown SeeNote 2
F
TMypically
4 Places
P
H NPT Conduit Entry 2 Places or M25
KTypically4 Places
F
P
KTypically4 Places
N x Q Deep
MTypically4 Places
Spinner NotShown SeeNote 2
A
G C
.47[12]
1.97 x 2.6 Deep[50 x 66]
B
Allow 3.12 [80]For Cover Removal
Holes For#10-24 UNCor M54 Places
Typically .78[20]
1.25[32]
3.00[76]
H NPT Conduit Entry 2 Places or M20 for models 003 & 005
or M25 for models 008 065
J E
3.00[76]
See Note 2
.60 For Override[15] Engagement
D
1.60[41]
R
Detail A1 - Output Bore(Series 70-030,050, 065 Only)
WatERpRooF / EXploSion pRooF EncloSURE - S70-708 to S70-720
WatERpRooF EncloSURE - S70-130/131* anD S70-180/181*
* Utilizes spur gear
WatERpRooF EncloSURE - S70-003 to S70-065
Actuator
SeriesA B C D E F G H J
K
(UNC)
x B.C.
M
(UNC)
x B.C.
N P Q R S T UWt.lbs
[kgs]
S70-003
S70-005
7.5
[191]
5.6
[142]
3.0
[76]
5.1
[130]
1.9
[48]
1.94
[49.3]
.19
[4.8]
1/2
2.0
[51]
5/16-18x 2.76
F07
.75
[19]
.51
[13]
1.75
[44]
3.5
[89]
12
[6]
S70-008
S70-012
S70-020
10.1
[257]
7.8
[198]
3.7
[94]
6.5
[165]
2.5
[64]
2.69
[68.3]
.56
[14.2]
3/4
2.6
[66]
5/16-18x 2.76
F07
1/2-13x 4.92
F12
1.18
[30]
.87
[22]
2.20
[56]
8
[203]
28
[13]
S70-030
S70-050
S70-065
12.1[307]
9.5[241]
5.6[142]
7.2[183]
2.9[74]
3.19[81]
.56[14.2]
3/4
3.1[79]
1/2-13x 4.92F12
3/4-10x 6.50F16
See Detail A1 12[305]
48[22]
S70-130/131
S70-180/181
12.1
[307]
9.5
[241]
5.6
[142]
12.5
[317]
8.1
[206]
9.2
[234]
.56
[14.2]
3/4
8.3
[211]
1/2-13x 4.92
F12
3/4-10x 6.50
F16See Detail A2
12
[305]
6.1
[155]
12.7
[323]
8
[203]
83
[38]
WatERpRooF EncloSURE Dimensions are in Inches [Millimeters in brackets]
-
8/6/2019 B-1016_EL_S-70_2009-10
11/12
T E C H N I C a L d a T a
The duty cycle for intermittent on-off operation is 25%. The continuous duty actuator with Servo is rated for 100% modulating operation.12 VDC, 24 VDC and 3-Phase Motors are available as an option, please consult your Bray representative or the factory.
tYpical WiRinGDiaGRaMS
FIELD WIRING
FIELD WIRING
ACTUATOR
ACTUATOR
Wiring Diagrams areFor Reerence Only.
Do NOT use or feld wiring.
onoFFWith Optional Torque Limit
Switches, Auxiliary LimitSwitches and Heater
nes:1) Actuators are shown in closed position.2) Manual Override is not engaged.3) Actuators are shown with optional Heater4) All switches are Single Pole, Double Throw.5) Terminal block accepts feld wiring
from 12-22 AWG, 14-22 AWG for Servo.6) Modulating Unit: Position Feedback
Output is designed to drive an isolated
250 -500 Ohm resistive load.
MoDUlatinGServ pr
With Optional Heater
11
ActuatorSeries
TorqueOutput
lb/in[Nm]
Single Phase MotorsCurrent Rating (Amps)At All Speeds (locked
rotor)
Speed for 90 Operations
ManualOverride
GearRatio
RimPulllbs
[kgs]
Bray ValveSizes forDirect
Mounting
On-Off Intermittent Continuous:
VAC Hz Amps Optional SpeedsStandardSpeeds
On/Off MOD
S70-003300[34]
120 50/60 0.88 sec. 15 sec. 30 sec. 30+ sec.
30:1
11.4[5]
2 through 6220 50/60 0.5
S70-005500[57]
120 50/60 1.415 sec. 30 sec. 30+ sec.
30:1
19.0[9]
2 through 6220 50/60 0.6
S70-005500
[57]24 50/60 1.5 . 60 sec. 60+ sec. 30:1
19.0
[9]2 through 6
S70-008S70-708
800[90]
120 50/60 2.16 sec. 10 sec. 15 sec. 30 sec. 30+ sec.
30:1
13.0[6]
2 through 12220 50/60 0.9
S70-012S70-712
1200[136]
120 50/60 2.1 10 sec. 15 sec. 30 sec. 30+c sec.
30:1
20.0[9]
2 through 12220 50/60 0.9
S70-020S70-720
2000[226]
120 50/60 2.1 15 sec. 30 sec. 30+. sec
30:1
33.0[15]
2 through 12220 50/60 0.9
S70-0202000[226]
24 50/60 2.0 60 sec. 60+ sec. 30:133.0[15]
2 through 12
S70-0303000[339]
120 50/60 3.0 18 sec. 30 sec. 30+ sec.
30:1
33.0[15]
8 through 20220 50/60 1.4
S70-0505000[565]
120 50/60 3.0 18 sec. 30 sec. 30+ sec.
30:1
55.0[25]
8 through 20220 50/60 1.4
S70-0505000[565]
24 50/60 3.0 70 sec. 30:155.0[25]
8 through 20
S70-065 6500[735] 120 50/60 3.0 30 sec. 30+ sec. 30:1 72.0[33] 8 through 20220 50/60 1.4
S70-130S70-131
13000[1469]
120 50/60 3.090 sec. 90+ sec.
90:1
86.0[39]
12 through 22220 50/60 1.4
S70-180S70-181
18000[2034]
120 50/60 3.2125 sec. 125+ sec.
90:186.0[39]
16 through 36220 50/60 1.5
-
8/6/2019 B-1016_EL_S-70_2009-10
12/12
CONTROLSA Division of BRAY INTERNATIONAL, Inc.
13333 Westland East Blvd. Houston, Texas 77041
281.894.5454 FAX 281.894.9499 www.bray.com
2008 Bray International. All rights reserved.
B 1016 EL S/70 2009 10
SPECIFICaTIONS
The electric actuator shall becompact and lowprofle to greatlyreduce space requirements. Theactuator shall eature ease o accessto feld wiring and adjustment. Theactuator shall be built to withstandline vibration and shock withoutailure and shall bolt directly to Brayvalve mounting anges withoutusing brackets.
MotoR A single phase perman-
ent split-capacitor reversible motorwith voltages o 120 and 220 VAC50/60 Hz shall be standard. Motorinsulation shall be Class F or better.The motor shall contain a built-inUL approved automatic reset thermaloverload protector set at 275F(135C) embedded in motor wind-ings. A variety of 3-Phase 50/60 Hzand DC motors shall be availableupon request.
DUtY cYclE The duty cycle orintermittent on-o operation shall be25%. The continuous duty actuatorwith Servo shall be rated or 100%modulating operation.
SElF-locKinG oUtpUt DRiVE aSSEMblYThe actuator shall have a sel-locking output driveassembly consisting o a worm and worm gear outputdrive mechanism. The output drive assembly shall haveprecision cut multi-staged gears which will withstandlocked rotor conditions. The output drive assembly shallbe permanently lubricated at the actory and shall drivea chrome-moly steel worm which drives the compositealuminum bronze segmented worm gear / output shat.
WiRinG Actuator switches shall be pre-wired to aterminal block or ease o access and all internal wiringshall range from 12-22 AWG.
SWITCHESAll travel switches shall be Single Pole,Double Throw, Form C type, 10A at 125/250 VAC,1/2 A at 125 VDC, UL listed and CSA approved. Travel
Limit switches shall limit actuator in both the open andclosed position o valve travel.
caMS Cams or each travel limit switch shall beinfnitely adjustable by fnger touch or screw driver,as provided by Brays patented design.
conDUit EntRiES All units shall have 2 conduitentries. Conduit entries or models 003 and 005 shallbe either 1/2" NPT or M 20. Conduit entries or models008 181 shall be either 3/4" NPT or M 25.
MECHANICALTRAVELSTOPSMechanicalstainless steel travel stops shall be located outside theactuator or ease o adjustment and contain stainlesssteel lock nuts to hold the travel stops in place.O-rings provide waterproo seals. The travel stopsshall limit the actuator movement to specifc degrees
o rotation.
ManUal oVERRiDE All units shall be equippedwith an aluminum manual override handwheel torotate the valve without electrical power. The over-ride assembly shall ensure positive and ast manualoperation without the use o extra tools or levers.
EMERGENCYSHUT-OFFAn automatic powercutout switch shall be provided to cut power tothe motor when actuator handwheel is engagedor manual operation. This switch shall unction asa saety emergency shutdown device and shall beaccessible rom outside the housing.
EncloSURE The die-cast aluminum enclosureshall be certied to UL, CSA & CE waterproofstandards (NEMA 4, 4X, IP 65). Cover shall bepolyester powder coated or exceptional corrosion,wear, impact and UV resistance. The enclosure shallhave captive cover bolts, thereore preventing timeconsuming problems due to lost or misplaced bolts.A UL listed waterproof / explosion proof enclosure(NEMA 4, 4X, 7, 9) shall be available.
ValVE StatUS DiSplaY The actuator shallhave a highly visible display prominently labeled toindicate valve position throughout the ull range otravel.
tEMpERatURE RatinG Actuators shall bedesigned or temperature ranges o -40F (-40C)to +150F (65C).
optional EqUipMEntThe actuator shall be designed to include any othe ollowing accessories as an option.
toRqUE liMitinG SYStEM with 2 SPDTmechanical switches and 2 actory calibratedscrews. The worm shat shall be driven againstthe torque disc springs in response to the output
torque. The switches contact the worm shat groovein response to predetermined loads and interrupt theelectrical power to the motor. Switches shall operateat any point o actuator travel.
HEATERwith sel-regulating temperature control toprevent condensation buildup. The heater shall bepre-wired to the terminal block. Rated output is 15 Wat 24, 120 or 220 VAC.
SERVo A microprocessor controlled Servo shall beavailable or precise modulating control o valveposition in response to an analog input signal. The
Servo shall have an analog output signal proportionalto actual valve position as standard. This analog signalshall be confgurable to either current or voltage out-put. The Servo shall have voltage spike protection on allInput terminals. Independent adjustments shall be pro-vided or both open and closed Speed Control o theactuator and deadband. Input Signals: 4-20 mADC into250 Ohm, 0-10 VDC, 0-5 VDC, 10k Ohm or greaterpotentiometer. 10K Ohm Potentiometer shall be usedor internal eedback. Calibration o the Servo shall beaccomplished by pressing a single button to initiatethe calibration routine. Inputs or the control box andhandwheel, LED status indicators and self-diagnosticcapability shall also be provided.
DeviceNet Servos shall be available.
contRol Station or manual local electrical
operation o the actuator. The Control Station shallush mount to the actuator and feature a local / off /remote control switch, an openstopclose switch, andtwo lights which locally indicate open and closed valveposition. The enclosure shall be aluminum and water-proo (NEMA 4, 4X, IP 65).
DISTRIBUTOR
The Bray Series 70 Electric ActuatorsSeries 70-003/005, 008/012/020 and 70-030/050/065.
All statements, technical information, and recom-mendations in this bulletin are for general useonly. Consult Bray representatives or factory forthe specifc requirements and material selectionfor your intended application. The right to changeor modify product design or product without priornotice is reserved.