2 Back Basics Back Basics May 2010 Solution Based on Cx-3 ATC/FPT software TAB Existing AHU-1 Measurement Point Criteria On 24/7 Max Cool- ing On 24/7 Min Cooling On 24/7 Max Heat- ing TAB Tester Questions Design Actual Design Actual Design Actual 1 Mixed air plenum Flow Static pressure Velocity 7,000 cfm -0.25 in. sp 500 fpm 6,300 cfm -0.35 in. sp 450 fpm A. OK per basis of design B. OA damper D-1 open 100% C. OA damper D-1 closed creating excess static pressure drop via excess return air (RA) -ANSWER 2 After filter and before supply air fan Flow Static pressure Velocity 7,000 cfm -0.5 in. sp 500 fpm 6,300 cfm -0.45 in. sp 450 fpm A. OK per basis of design B. Filter pressure drop excessive. Issue PM work- order to replace filters C. Filter pressure drop OK at reduced total cfm -ANSWER 3 After fan and before cooling coil Flow Static pressure Velocity 7,000 cfm +1.50 in. sp 1,200 fpm 6,300 cfm +1.65 in. sp 1,080 fpm A. OK per basis of design B. OK based on reduced total supply air -ANSWER C. Supply fan needs to be re-sheaved to increase cfm 4 After cooling coil and before reheat coil Flow Static pressure Velocity 7,000 cfm +0.50 in. sp 400 fpm 6,300 cfm +0.50 in. sp 360 fpm A. OK per basis of design B. OK based on reduced total supply air -ANSWER C. Coil pressure drop excessive. Issue PM workorder to clean coil 5 After reheat coil Flow Static pressure Velocity 7,000 cfm +0.30 in. sp 600 fpm 6,300 cfm +0.35 in. sp 540 fpm A. OK per basis of design B. OK based on reduced total supply air -ANSWER C. Coil pressure drop excessive. Issue PM workorder to clean coil 6 3/4 Downstream In supply air duct Flow Static pressure Velocity 7,000 cfm -0.20 in. sp 1100 fpm 6,300 cfm -0.20 in. sp 990 fpm A. OK per basis of design B. OK based on reduced total supply air -ANSWER C. Duct static pressure drop is excessive - Issue PM workorder to clean ductwork 7 CHWR downstream of three-way V-1 valve Flow Head Temperature 48 gpm 30 ft 54˚F 48 gpm 45 ft 44˚F A. OK per basis of design B. Excessive pump head from coil C. Coil is piped backwards -ANSWER 8 CHWS upstream of three-way V-1 valve Flow Head Temperature 48 gpm 45 ft 44˚F 48 gpm 30 ft 54˚F A. OK per basis of design B. Inadequate pump head to the coil C. Coil is piped backwards -ANSWER 9 HWR downstream of three-way V-2 valve Flow Head Temperature 34 gpm 30 ft 180˚F 0 gpm 35 ft 190˚F A. OK per basis of design B. Valve to reheat coil is closed per design sequence -ANSWER C. Coil is piped backwards

Upload: sajuhere

Post on 21-Jul-2016

1 views

Category:

Documents


0 download

DESCRIPTION

B2b may

TRANSCRIPT

Page 1: b 2 b May 2010 Solutions

2Back BasicsBack BasicsMay 2010

SolutionBased on Cx-3 ATC/FPT software

TAB Existing AHU-1Measurement

PointCriteria On 24/7 Max Cool-

ingOn 24/7 Min Cooling On 24/7 Max Heat-

ingTAB Tester Questions

Design Actual Design Actual Design Actual

1Mixed air plenum

FlowStatic pressureVelocity

7,000 cfm-0.25 in. sp500 fpm

6,300 cfm-0.35 in. sp450 fpm

A. OK per basis of designB. OA damper D-1 open 100%C. OA damper D-1 closed creating excess static

pressure drop via excess return air (RA) -ANSWER

2After filter and before supply air fan

FlowStatic pressureVelocity

7,000 cfm-0.5 in. sp500 fpm

6,300 cfm-0.45 in. sp450 fpm

A. OK per basis of designB. Filter pressure drop excessive. Issue PM work-

order to replace filtersC. Filter pressure drop OK at reduced total cfm

-ANSWER

3After fan and before cooling coil

FlowStatic pressureVelocity

7,000 cfm+1.50 in. sp1,200 fpm

6,300 cfm+1.65 in. sp1,080 fpm

A. OK per basis of designB. OK based on reduced total supply air -ANSWERC. Supply fan needs to be re-sheaved to increase cfm

4After cooling coil and before reheat coil

FlowStatic pressureVelocity

7,000 cfm+0.50 in. sp400 fpm

6,300 cfm+0.50 in. sp360 fpm

A. OK per basis of designB. OK based on reduced total supply air -ANSWERC. Coil pressure drop excessive. Issue PM workorder

to clean coil

5After reheat coil

FlowStatic pressureVelocity

7,000 cfm+0.30 in. sp600 fpm

6,300 cfm+0.35 in. sp540 fpm

A. OK per basis of designB. OK based on reduced total supply air -ANSWERC. Coil pressure drop excessive. Issue PM workorder

to clean coil

63/4 Downstream In supply air duct

FlowStatic pressureVelocity

7,000 cfm-0.20 in. sp1100 fpm

6,300 cfm-0.20 in. sp990 fpm

A. OK per basis of designB. OK based on reduced total supply air -ANSWERC. Duct static pressure drop is excessive - Issue PM

workorder to clean ductwork

7CHWR downstreamof three-way V-1 valve

FlowHeadTemperature

48 gpm30 ft54˚F

48 gpm45 ft44˚F

A. OK per basis of designB. Excessive pump head from coilC. Coil is piped backwards -ANSWER

8CHWS upstream of three-way V-1 valve

FlowHeadTemperature

48 gpm45 ft44˚F

48 gpm30 ft54˚F

A. OK per basis of designB. Inadequate pump head to the coilC. Coil is piped backwards -ANSWER

9HWR downstream of three-way V-2 valve

FlowHeadTemperature

34 gpm30 ft180˚F

0 gpm35 ft190˚F

A. OK per basis of designB. Valve to reheat coil is closed per design sequence

-ANSWERC. Coil is piped backwards