b2311 en 0513 - contrive.mobi

2
CONTRIVE S.R.L. Via Enrico Fermi 18 I-24040 SUISIO (Bergamo) Tel. +39 (0)35 4948236 Fax +39 (0)35 4933759 B2311.EN / 0513 www.contrive.it THIS DEVICE SHOULD BE INSTALLED ONLY BY QUALIFIED PERSONNEL AL2-MBU Carefully read the instruction manual in its entirety and keep it safe for future reference. It is essential to know the information and comply with the instructions given in the manual to ensure the is installed, used and serviced correctly and safely. ALWAYS FOLLOW SAFETYPROCEDURES. IF THE DEVICE HAS BEEN STORED IN A COLD ENVIRONMENT, THEN CONDENSATION CAN OCCUR. BEFORE STARTING OPERATIONS, THE DEVICE MUST BE ABSOLUTELY DRY. THUS, AN ACCLIMATIZATION PERIOD OFAT LEAST THREE HOURS MUST BE OBSERVED. In order to prevent danger to life or property, it is the responsibility of the system designer to incorporate redundant protective mechanism appropriate to the risk involved. DO NOT ATTEMPT TO INSTALL, REPLACE OR PERFORM MAINTENANCE ON WHILE IT IS ENERGIZED, BEFORE REMOVING OR MOUNTING A MODULE, DISCONNECT BOTH THE POWER TO THE CONTROLLER AND THE FIELDBUS. MAKE SURE THE ENTIRE CONTROLLER IS REASSEMBLED BEFORE SWITCHING THE POWER BACK ON. DEATH OR SEVERE PERSONAL INJURY CAN RESULTFROM CONTACTWITH ENERGIZED EQUIPMENT. ALWAYS VERIFYTHATNO VOLTAGE IS PRESENTBEFORE PROCEEDING. This unit is not authorised for use as critical component in life-support devices or systems unless a specific written agreement has been given. No complex software or hardware system is perfect. Bugs are always present in a system of any size. All units are 100% functionally tested. Specifications are based on characterisation of tested sample units rather than testing over temperature and voltage each unit. Contrive disclaims all liability for damage to the fitting or to other property or persons deriving from installation, use and maintenance that have not been carried out in conformity with this instruction manual, which must always accompany the fitting. AL2-MBU The Modbus Gateway module is an optional device for Mitsubishi controllers which enables the connection to a Modbus system. The controller is considered as a slave on the Modbus network. Through the Modbus Gateway module it is possible to: • Read (and write) digital inputs • Read analog inputs • Read and write digital outputs • Read and write analog outputs • Read and write Communication Bits • Read and write Communication Words • Read system bits AL2-MBU AL2-MBU a a a a 2 2 Before attempting to use , the following original MITSUBISHI manuals should be carefully read and understood: For any information on 2 controller and its derivate products, please refer to the literature provided by MITSUBISHI and available for download at: These manuals will guide the reader in the correct programming and operation of the 2 controllers. AL2-MBU • Hardware Manual • Programming Manual • Software Manual • Communication Manual www.mitsubishi-automation.com SAFETY INFORMATION PRODUCT DESCRIPTION 2311.00.00 AL2-MBU MODBUS GATEWAY FOR AL2 Modbus® is a registered trademark of Schneider Electric. CONTRIVE RESERVES THE RIGHT TO MODIFY THE CHARACTERISTICS STATED IN THIS INSTRUCTION MANUAL AT ANY TIME AND WITHOUT PRIOR NOTICE. © COPYRIGHT 2002...2007 CONTRIVE SRL ITALY.ALL RIGHTS RESERVED. AL2-MBU Advanced Manual is available for download at: www.contrive.it USER GUIDE AL2-MBU MODBUS COMMUNICATION MODULE FOR MITSUBISHI ALPHA CONTROLLERS FITTING BUS INTERFACE DECLARATION OF CONFORMITY Company identification: Product identification: The manufacturer declare the conformity of the equipment with the provisions of the following EC Directive(s) when installed in accordance with the installation instructions : Conformance via a Technical Construction File is declared using all parts of the following standards (EMC only) : Manufacturer: Contrive, Srl Via Enrico Fermi 18 24040 Suisio Italy Brand: Contrive Equipment name: AL2-MBU Equipment type: Modbus Gateway Suisio, Italy July 26, 2007 89/336/EEC EMC Directive as amended by 93/68/EEC EN 50081-1 (1995) Electromagnetic compatibility. Generic emission standard. Part 1 : Residential, commercial and light industry. ¡ ¡ 73/23/EEC LVD Directive as amended by 93/68/EEC EN 50082-2 (1995) Electromagnetic compatibility. Generic immunity standard. Part 2 : Industrial environment. ¡ ¡ To install ake sure that there is no voltage applied to controller. . Carefully remove the factory fitted expansion port cover or special module cover. Make all the connections and settings before to install the into the cavity. Install the into the cavity, carefully placing the connector to match the counterpart in the base and the cable in the channel located on the top side. Once Modbus Gateway has been installed the connection for the cable is no longer available. Controller must be configured for AL2-MBU AL2-MBU AL2-MBU [1] [2] WARNING AL2-MBU AL2-GSM-CAB Station Address = 0 m 2 Release screw and keep 2 Replace the 2 cover taking care that there is no interference with and all connector and cables are in the correct position. \ Tighten screw to a torque of 0.4 N/m. 2 a a a a [A] AL2-MBU [A] Modbus is a serial, asynchronous protocol. The Modbus protocol does not specify the physical interface. Typical physical interfaces are RS-232 and RS-485. provides a galvanically-isolated ANSI EIA/TIA-485-A interface, designed for bidirectional data communication on balanced, multipoint bus transmission lines and is slew-limited to reduce reflections with improperly terminated lines. It's a fractional (1/8) power transceiver, allowing up to 256 transceivers on the bus. Building mixed network with classic full power (1/1) transceiver, a line repeater must be provided for each group of 32 units. The receiver inputs have a true fail-safe feature that ensures a reliable operation when the inputs are open or shorted. Current limiting and thermal shutdown features protect against output short circuits and bus contention situations that might cause excessive power dissipation. Data negative (Conductor 1 in twisted pair). Data positive (Conductor 2 in twisted pair). Ground (Conductor 3 in a three-wire system) and negative power supply Positive power supply Use shielded twisted-pair wire to connect each slave to the Modbus network, daisy- chain style. The polarity of the twisted pair is critically important. Close the jumper for the built-in bus termination if the is installed at the end of the bus otherwise the bus termination jumper must be left open. Bus termination prevents signal reflections from the bus cable ends. Provide an external power supply for the bus side. Although it’s possible to supply the bus side using the same 24V used for the controller, it’s strongly suggested to provide an independent power supply. This independent supply must be externally protected. Each will draw 2,5mA from the bus in idle mode, rising to a max of 150mA while in transmission mode. The address is set using two rotary encoding switches. The left switch is used to set the most significant character and the right switch is used to set the least significant character. Addresses can be set between 1 and 247 in hexadecimal format ranging 00 to FF. Address 0 is reserved for the broadcast address, which all slave devices on a network recognize. The figure below shows the address setting "14". Any address change will take place immediately, also when the unit is running. The supports both the RTU and ASCII protocol. Leave the jumper open to operate mode, close the jumper for mode. A valid selection is applied on power up. This cannot be modified during operation. In addition to the described setting options, some configuration can be modified via the Modbus registers. Default communication baud rate is edit Modbus Register 40101 to modify. Default parity option is edit Modbus Rgister 40102 to modify. The new parameters are applied at next power-on. AL2-MBU TERMINAL DESIGNATIONS MODBUS RS485 NETWORK BUS TERMINATION AL2-MBU , BUS SIDE POWER SUPPLY AL2-MBU ADDRESS SETTING FORMAT SETTING AL2-MBU RTU ASCII BAUD RATEAND PARITY SETTING 9600, NONE, A B - +

Upload: others

Post on 04-Feb-2022

6 views

Category:

Documents


0 download

TRANSCRIPT

CONTRIVE S.R.L.Via Enrico Fermi 18 I-24040 SUISIO (Bergamo)Tel. +39 (0)35 4948236 Fax +39 (0)35 4933759

B2311.EN / 0513 www.contrive.itTHIS DEVICE SHOULD BE INSTALLED ONLY BY QUALIFIED PERSONNEL

AL2-MBU

Carefully read the instruction manual in its entirety and keep it safe for futurereference. It is essential to know the information and comply with the instructionsgiven in the manual to ensure the is installed, used and serviced correctlyand safely.

ALWAYS FOLLOW SAFETY PROCEDURES.

IF THE DEVICE HAS BEEN STORED IN A COLD ENVIRONMENT, THENCONDENSATION CAN OCCUR. BEFORE STARTING OPERATIONS, THEDEVICE MUST BE ABSOLUTELY DRY. THUS, AN ACCLIMATIZATION PERIODOFAT LEASTTHREE HOURS MUST BE OBSERVED.

In order to prevent danger to life or property, it is the responsibility of the systemdesigner to incorporate redundant protective mechanism appropriate to the riskinvolved.

DO NOT ATTEMPT TO INSTALL, REPLACE OR PERFORM MAINTENANCE ONWHILE IT IS ENERGIZED, BEFORE REMOVING OR MOUNTING A

MODULE, DISCONNECT BOTH THE POWER TO THE CONTROLLER AND THEFIELDBUS.MAKE SURE THE ENTIRE CONTROLLER IS REASSEMBLED BEFORESWITCHING THE POWER BACK ON. DEATH OR SEVERE PERSONAL INJURYCAN RESULT FROM CONTACT WITH ENERGIZED EQUIPMENT.ALWAYS VERIFYTHAT NO VOLTAGE IS PRESENT BEFORE PROCEEDING.

This unit is not authorised for use as critical component in life-support devices orsystems unless a specific written agreement has been given.

No complex software or hardware system is perfect.Bugs are always present in a system of any size.

All units are 100% functionally tested. Specifications are based on characterisationof tested sample units rather than testing over temperature and voltage each unit.

Contrive disclaims all liability for damage to the fitting or to other property or personsderiving from installation, use and maintenance that have not been carried out inconformity with this instruction manual, which must always accompany the fitting.

AL2-MBU

The Modbus Gateway module is an optional device for Mitsubishicontrollers which enables the connection to a Modbus system.

The controller is considered as a slave on the Modbus network.

Through the Modbus Gateway module it is possible to:• Read (and write) digital inputs• Read analog inputs• Read and write digital outputs• Read and write analog outputs• Read and write Communication Bits• Read and write Communication Words• Read system bits

AL2-MBU

AL2-MBU

2

2

Before attempting to use , the following original MITSUBISHI manualsshould be carefully read and understood:

For any information on 2 controller and its derivate products, please refer to theliterature provided by MITSUBISHI and available for download at:

These manuals will guide the reader in the correct programming and operation of the

2 controllers.

AL2-MBU

• Hardware Manual• Programming Manual• Software Manual• Communication Manual

www.mitsubishi-automation.com

SAFETY INFORMATION

PRODUCT DESCRIPTION

2311.00.00 AL2-MBU MODBUS GATEWAY FOR AL2

Modbus® is a registered trademark of Schneider Electric.

CONTRIVE RESERVES THE RIGHT TO MODIFY THE CHARACTERISTICS STATEDIN THIS INSTRUCTION MANUAL AT ANY TIME AND WITHOUT PRIOR NOTICE.

© COPYRIGHT 2002...2007 CONTRIVE SRL ITALY. ALL RIGHTS RESERVED.

AL2-MBU Advanced Manual is available for download at: www.contrive.it

USER GUIDE

AL2-MBU MODBUS COMMUNICATION MODULEFOR MITSUBISHI ALPHA CONTROLLERS

FITTING BUS INTERFACE

DECLARATION OF CONFORMITY

Company identification:

Product identification:

The manufacturer declare the conformity of the equipment with the provisionsof the following EC Directive(s) when installed in accordance with theinstallation instructions :

Conformance via a Technical Construction File is declared using all parts ofthe following standards (EMC only) :

Manufacturer: Contrive, SrlVia Enrico Fermi 18 24040 Suisio Italy

Brand: ContriveEquipment name: AL2-MBUEquipment type: Modbus Gateway

Suisio, Italy July 26, 2007

89/336/EEC EMC Directive as amended by 93/68/EEC

EN 50081-1 (1995)Electromagnetic compatibility. Generic emission standard.Part 1 : Residential, commercial and light industry.

� 73/23/EEC LVD Directive as amended by 93/68/EEC

EN 50082-2 (1995)Electromagnetic compatibility. Generic immunity standard.Part 2 : Industrial environment.

To install ake surethat there is no voltage applied

to controller.

.

Carefully remove the factory

fitted expansion port coveror special module cover.

Make all the connections andsettings before to install the

into the cavity.

Install the into thecavity, carefully placing theconnec to r to match thecounterpart in the base and thecable in the channel locatedon the top side.

Once Modbus Gateway has been installed the connectionfor the cable is no longer available.

Controller must be configured for

AL2-MBU

AL2-MBU

AL2-MBU [1]

[2]

WARNING

AL2-MBUAL2-GSM-CAB

StationAddress = 0

m

2

Release screw and keep

2

Replace the 2 cover takingcare that there is nointerference withand all connector andcables are in the correctposition.

\Tighten screw to a torque of 0.4 N/m.

2

[A]

AL2-MBU

[A]

Modbus is a serial, asynchronous protocol.The Modbus protocol does not specify the physical interface.Typical physical interfaces are RS-232 and RS-485.

provides a galvanically-isolated ANSI EIA/TIA-485-A interface, designedfor bidirectional data communication on balanced, multipoint bus transmission linesand is slew-limited to reduce reflections with improperly terminated lines.It's a fractional (1/8) power transceiver, allowing up to 256 transceivers on the bus.Building mixed network with classic full power (1/1) transceiver, a line repeater mustbe provided for each group of 32 units.The receiver inputs have a true fail-safe feature that ensures a reliable operationwhen the inputs are open or shorted.Current limiting and thermal shutdown features protect against output short circuitsand bus contention situations that might cause excessive power dissipation.

Data negative (Conductor 1 in twisted pair).

Data positive (Conductor 2 in twisted pair).

Ground (Conductor 3 in a three-wire system) and negative power supply

Positive power supply

Use shielded twisted-pair wire to connect each slave to the Modbus network, daisy-chain style. The polarity of the twisted pair is critically important.

Close the jumper for the built-in bus termination if the is installed at the endof the bus otherwise the bus termination jumper must be left open.Bus termination prevents signal reflections from the bus cable ends.

Provide an external power supply for the bus side.Although it’s possible to supply thebus side using the same 24V used for the controller, it’s strongly suggested to providean independent power supply.This independent supply must be externally protected.Each will draw 2,5mA from the bus in idle mode, rising to a max of 150mAwhile in transmission mode.

The address is set using two rotary encoding switches.The left switch is used to set the most significant character and the right switch isused to set the least significant character. Addresses can be set between 1 and 247in hexadecimal format ranging 00 to FF. Address 0 is reserved for the broadcastaddress, which all slave devices on a network recognize.The figure below shows the address setting "14".Any address change will take place immediately, also when the unit is running.

The supports both the RTU andASCII protocol.Leave the jumper open to operate mode, close the jumper for mode.Avalid selection is applied on power up. This cannot be modified during operation.

In addition to the described setting options, some configuration can be modified viathe Modbus registers.Default communication baud rate is edit Modbus Register 40101 to modify.Default parity option is edit Modbus Rgister 40102 to modify.The new parameters are applied at next power-on.

AL2-MBU

TERMINAL DESIGNATIONS

MODBUS RS485 NETWORK

BUS TERMINATIONAL2-MBU

,

BUS SIDE POWER SUPPLY

AL2-MBU

ADDRESS SETTING

FORMAT SETTINGAL2-MBU

RTU ASCII

BAUD RATEAND PARITY SETTING

9600,NONE,

A

B

-

+

The following table highlights the subset of standard Modbus supported functions(the reference register addresses that the function operates on are also indicated):

responds to the master within the defined(nothing will be issued after this timeout), it uses the function code field to indicate anormal (error-free) response. A valid answer is given if at least one of read coil orregister is valid.An error is given when the whole addresses are not valid.

[1] Maximum number of registers/coils in a single request is limited to 64.

AL2-MBU AlphaXL COM TIMEOUT

Modbus functions operate on register map to monitor, configure, and control I/O.Modbus registers are organized into reference types identified by the leadingnumber of the reference address.The leading character is generally implied by the function code and omitted from theaddress specifier for a given function.The leading character also identifies the I/O data type.

ANALOG INPUTS

Up to 8 channels available, depending on thecontroller type, can be read from remote.

Function04 Read Input Register

BAUD RATE (kbit/s)

Function03 Read Holding Registers06 Preset Single Register

In addition to the described setting options,some configuration can be modified via theModbus registers.Default communication baud rate is .New parameters are applied at next power-on.

9600

COMMUNICATION WORDS

50 or 100 communication words could beoptionally assigned to CommunicationMemory. CW are associated to any bit of FBused within the program and can be read orwrite from remote.

Function03 Read Holding Registers06 Preset Single Register

ISOLATED NETWORK

MODBUS REGISTER MAP - COILS

NON-ISOLATED NETWORK

MODBUS REGISTER MAP - WORDS

MODBUS FUNCTIONS

MODBUS EXCEPTIONS

Figure below illustrates a typical configuration where three slave units are shown.The communication wires are daisy-chained from one controller RS-485 port to thenext. Power for bus side of is supplied by a power supply unit.Of course it’s possible to provide different power supplies for each orgroups of but the negative must be linked to reference ground.

Termination must be activated at the last of the network.Termination must be provided also at the first unit of the network (usually the master).

Negative power supply must be used like RS-485 reference ground, three-wireconnection is highly recommended as it improves noise immunity.

AL2-MBUAL2-MBU

AL2-MBU

AL2-MBU

Figure below illustrates a typical configuration where three slave units are shown.The communication wires are daisy-chained from one controller RS-485 port to the

next. Power for bus side of is supplied from the same power supply of 2controller.

Termination must be activated at the lastAL2-MBU of the network.Termination must be provided also at the first unit of the network (usually the master).

Negative power supply must be used like RS-485 reference ground, three-wireconnection is highly recommended as it improves noise immunity.

AL2-MBU �

Multiple controllers can be networked together using .Amaximum of 247 controllers can be connected together.Max wiring distance should not exceed 1200 m (4000 ft.) at 19,200 baud.

AL2-MBU

THE SHIELD SHOULD BE GROUNDED IN ONE PLACE ONLYGrounding the shield at multiple points will create a “ground loop” thatmay disrupt communications or cause damage to the device circuitry.

When handling modules, wear a grounded antistatic wrist strapor equivalent protection to avoid damaging electronic parts.Handle any circuit card by its faceplate and edges only; avoidtouching the printed circuit board and connector pins.

Avoid contact between any card and your clothing: ESDvoltages may exist on clothing and can still cause damage.

Place any removed component on an antistatic surface. If youplan to return a replaced part to the factory, immediately place itin a static shielding bag to avoid ESD damage to the board.

The register addresses which are not allocated to any AL2 parameter ordata set are invalid. No reads or writes are allowed for these addresses.If there is an attempt to read or write outside the parameter addresses, the

From the front panel keys or through the programming software, set :>GSM & Serial Communication Others

ADVANCED MANUAL including VLS examples available at: www.gsm-control.biz

Alpha XLSIMPLE APPLICATION CONTROLLERS ARE MANUFACTURED BY

MITSUBISHI

0 00010 0001

3 00013 0001

0 00020 0002

3 00023 0002

0 00030 0003

3 00033 0003

0 00040 0004

3 00043 0004

0 00050 0005

3 00053 0005

0 00060 0006

3 00063 0006

0 00070 0007

3 00073 0007

0 00080 0008

3 00083 0008

0 00090 0009

0 00100 0010

4 00014 0001

0 00110 0011

4 00024 0002

0 00120 0012

0 00130 0013

4 ....4 ....

4 00504 0050

4 00514 0051

4 ....4 ....

4 00994 0099

4 01004 0100

4 01014 0101

4 01024 0102

0 00140 0014

0 00150 0015

0 00160 0016

0 00170 0017

0 00180 0018

0 00190 0019

0 00500 0050

0 ....0 ....

0 00670 0067

0 00680 0068

0 00690 0069

0 ....0 ....

0 01160 0116

0 01170 0117

0 01180 0118

0 01190 0119

0 01200 0120

0 ....0 ....

0 01390 0139

0 01400 0140

0 01410 0141

1 01421 0142

1 01431 0143

1 01441 0144

1 01451 0145

1 01461 0146

1 01471 0147

1 01481 0148

1 01491 0149

1 01501 0150

1 01511 0151

1 01521 0152

1 01531 0153

1 01541 0154

1 01551 0155

1 01561 0156

1 01571 0157

1 01581 0158

1 01591 0159

1 01601 0160

1 01611 0161

1 01621 0162

1 01631 0163

1 01641 0164

O 01

AI 01

O 02

AI 02

O 03

AI 03

O 04

AI 04

O 05

AI 05

O 06

AI 06

O 07

AI 07

O 08

AI 08

O 09

EO 01

CW 01

EO 02

CW 02

EO 03

EO 04

....

CW 50

CW 51

....

CW 99

CW100

0: 1.2

0: NONE

1: 2.4

1: ODD

2: 4.8

2: EVEN

3: 9.6

4: 19.2

5: 38.4

6: 57.6

7:115.2

A 01

A 02

A 03

A 04

CB 01

CB 02

CB 03

....

CB 50

CB 51

CB 52

....

CB 99

CB100

M 01

M 02

M 03

....

M 22

M 23

M 24

I 01

I 02

I 03

I 04

I 05

I 06

I 07

I 08

I 09

I 10

I 11

I 12

I 13

I 14

I 15

EI 01

EI 02

EI 03

EI 04

E 01

E 02

E 03

E 04

MODBUS

MODBUS

AL2

AL2

OUTPUT RELAYS

Up to 9 channels available, depending on thecontroller type, can be read and/or set fromremote. When the output channel is linked toa FB it could be overwritten by controller atfurther cycle.

Function01 Read Single Coils05 Force Single Coils15 Force Multiple Coils

EXTERNAL OUTPUTS

When AL2-4EYT or AL2-4EYR expansionboards is not installed, these channels couldbe used like virtual (read and write) coils.

PARITY

Default parity is . New parameters areapplied at next power-on.

NONE

In a normal response, echoes the function code of the original query in thefunction field of the response. All function codes have their most-significant bit (msb)set to 0 (their values are below 80H).In an exception response, the slave sets the msb of the function code to 1 in thereturned response (i.e. exactly 80H higher than normal) and returns the exceptioncode in the data field.This is used by the master's application to recognize an exception response and todirect an examination of the data field for the applicable exception code.

AL2-MBU

EXCEPTION DESCRIPTION

01

02

03

04

Illegal Function The function code received in the query is notallowed or invalid.

Illegal Data Address The data address received in the query is notan allowable address for the slave or is invalid.

Illegal Data Value A value contained in the query data field is notan allowable value for the slave or is invalid.

Slave Device Failure Unrecoverable error occurred while the slavewas attempting to perform requested action.

CODE FUNCTION REFERENCE

01 (01H) 0 xxxx

02 (02H) 1 xxxx

03 (03H) 4 xxxx

04 (04H) 3 xxxx

05 (05H) 0 xxxx

06 (06H) 4 xxxx

15 (0 H) 0 xxxx

Read Coil Status [1]

Read Input Status [1]

Read Holding Registers [1]

Read Input Registers [1]

Force Single Coil

Preset Single Register

F Force Multiple Coils

ASi LINK OUTPUTS

When AL2-ASI-BD expansion board is notinstalled, these channels could be used likevirtual coils.

COMMUNICATION BITS

50 or 100 communication bits could beoptionally assigned to CommunicationMemory. CB are associated to any bit of FBused within the program and can be read orwrite from remote.

Function01 Read Single Coils05 Force Single Coils

SYSTEM BITS

Predefined system informations.Ref.: Programming Manual § 2.1.3

01 Read Single Coils

DIGITAL INPUTS

Up to 15 channels available, depending onthe controller type, can be read from remote.

Function02 Read Input Status

Could also be set from remote like any coil,but it will be overwritten by controller at furthercycle (could make a pulse).

Function05 Force Single Coils

EXTERNAL INPUTS

When AL2-4EX or AL2-4EXR expansionboards is not installed, these channels couldbe used like virtual coils.

ASi LINK INPUTS

When AL2-ASI-BD expansion board is notinstalled, these channels could be set fromremote (Function 05), thus used like coils.

LOGIC SIDE

BUS SIDE

GENERAL DATA

Interface Name AL2 Dedicated protocolPhysical layer RS232 (5V)Type of connection Miniature connectorTransmission speed 9,6 kBit/sSupply voltage 5 V DC from A2 controllerSupply current < 25 mA

Interface Name Modbus RTU/ASCIIPhysical layer ANSI TIA/EIA RS-485-A and ISO 8482: 1987(E)

Slew rate-limited driver outputsTrue fail-safe receiver inputsChatter-free power-up/power-down protectionThermal shutdown protection256 nodes on busCommon-mode transient immunity >25 kV/µs

Type of connection Screws connector4 x 1,5 mm² AWG16 single wire solid1 mm² AWG17 stranded wire flexible0,75 mm² AWG19 stranded wire with ferrules

Transmission speed 1,2 kBit/s to 115,2 kBit/sSupply voltage 8 ... 30 V DCCurrent consumption < 2.5 mA idle mode

< 250 mA transmission mode

Insulation voltage 2500 Vrms 1 minute (UL 1577)Isolation group IIIa (DIN VDE0110, 1/89)DimensionsWeight 15 gOperating temperature -40 °C ... 85 °CPermissible humidity 95 % non-condensingAir pressure 80 kPa ... 106 kPa up to 3000 m above sea levelDegree of protection IP20Mounting type Embedded

46.5 x 34.5 x 11.5 mm (W x H x D)

PRODUCT FEATURES

THE INFORMATION CONTAINED IN THIS DOCUMENT ARE SUBJECT TO CHANGEWITHOUT NOTICE. PRODUCT NAMES, CORPORATE NAMES OR TITLES USED WITHINTHIS DOCUMENT MAY BE TRADEMARKS OR REGISTERED TRADEMARKS OF OTHERCOMPANIES AND ARE MENTIONED ONLY IN AN EXPLANATORY MANNER TO THEREADERS’BENEFIT,AND WITHOUT INTENTION TO INFRINGE.

WHILE EVERY EFFORT HAS BEEN MADE TO MAKE SURE THE INFORMATION IN THISDOCUMENT IS CORRECT, CONTRIVE CAN NOT BE LIABLE FOR ANY DAMAGESWHATSOEVER FOR LOSS RELATING TO THIS DOCUMENT.

WARRANTIES

CONTRIVE GUARANTEES FOR TWO YEARS FROM THE DATE OF MANUFACTURE OFITS PRODUCT TO REPLACE, OR, AT ITS OPTION, TO REPAIR ANY PRODUCT OR PARTTHEREOF WHICH IS FOUND DEFECTIVE IN MATERIAL OR WORKMANSHIP OR WHICHOTHERWISE FAILS TO CONFORM TO THE DESCRIPTION OF ITS SALES ORDER.CONTRIVE MAKES NO WARRANTY OF MERCHANTABILITY OR ANY OTHERWARRANTY EXPRESS OR IMPLIED. IN NO EVENT SHALL CONTRIVE BE LIABLE FORCONSEQUENTIAL OR SPECIAL DAMAGES OF ANY NATURE WHICH MAY ARISE INCONNECTION WITH SUCH PRODUCTS.

THE WARRANTY DOES NOT APPLY IN CASE OF IMPROPER USE

CAUTION

4 01034 0103 Tw:1-90 AlphaXL COM TIMEOUT

Default Tw= 35 (3,5”) TP=1 (0,1”)New parameters applied at next power-on.

4 01044 0104 TP:1-90