ba444df-p profibus pa issue 2 - tr automatykaissue: 2 23rd june 2011 ba444df-p profibus pa...

26
Issue: 2 23 rd June 2011 BA444DF-P PROFIBUS PA Intrinsically safe Field mounting 8 variable Fieldbus Indicator Issue 2 ul. Lechicka 14 ; 02-156 Warszawa Fax. (+48 022) 846 50 37 [email protected] TR Automatyka Sp. z o. o. Tel. (+48 022) 886 10 16 www.trautomatyka.pl

Upload: others

Post on 24-Oct-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

  • Issue: 223rd June 2011

    BA444DF-PPROFIBUS PA

    Intrinsically safeField mounting

    8 variableFieldbus Indicator

    Issue 2

    ul. Lechicka 14 ; 02-156 Warszawa Fax. (+48 022) 846 50 37 [email protected] Automatyka Sp. z o. o. Tel. (+48 022) 886 10 16 www.trautomatyka.pl

  • 2

    1. Description1.1 Documentation

    2. Operation2.1 Error messages

    3. Intrinsic Safety Certification3.1 ATEX certificate3.2 Zones, gas groups and T rating3.3 Fieldbus connection3.4 Certification Iabel Information

    4. System Design for Hazardous Area4.1 FISCO Systems4.2 Non-FISCO Sysems

    5. Installation5.1 Location5.2 Installation procedure5.3 EMC

    6. Configuration6.1 Configuration menus6.2 Node configuration menu

    6.2.1 Enter fieldbus address6.2.2 Access code6.2.3 Change from node to listener6.2.4 Reset to node factory defaults

    6.3 Listener configuration menu6.3.1 Access6.3.2 Summary of configuration

    functions.6.4 Description of listener menu functions

    6.4.1 Scan fieldbus segment6.4.2 List configured input

    parameters.6.4.3 Enter address & display

    parameters.6.4.4 Enable selected input6.4.5 Enter source address6.4.6 Enter destination address6.4.7 Enter Index6.4.8 Decimal point position6.4.9 Configuration of bargraph6.4.10 Scale numeric display6.4.11 Access code for listener

    configuration menu.6.4.12 Change from fieldbus listener to

    fieldbus node.6.4.13 Reset to listener factory

    defaults.

    7. Maintenance7.1 Fault finding during commissioning7.2 Fault finding after commissioning7.3 Servicing7.4 Routine maintenance7.5 Guarantee7.6 Customer comments

    8. Accessories8.1 Scale and Tag marking8.2 Tag plate8.3 Pipe mounting kits

    Appendix 1ATEX dust certification

    Appendix 2FM Approval for use in the USA andcFM Approval for use in Canada.

    Appendix 3IECEx certification

    CONTENTS

    The BA444DF-P is CE marked to show compliance with the European Explosive AtmospheresDirective 94/9/EC and the European EMC Directive 20 04/108/EC

  • 3

    1. DESCRIPTIONThe BA444DF-P fieldbus indicator is anintrinsically safe, PROFIBUS PA instrument, thatmay be configured as a fieldbus node or as afieldbus listener. It can display up to eight fieldbusprocess variables on a five digit LCD and a 31segment analogue bargraph. The instrument isbus powered so no additional power supply isrequired and has PROFIBUS PA UserOrganisation approval, certificate Z01505.

    Fieldbus node configuration may be performed byeither a User PRM data download or by a DPV1configurator, and if required, the instrumentaddress may be entered via the front panel pushbuttons.

    When configured as a fieldbus listener, theBA444DF-P is not visible to the fieldbus host andcan only be configured using the push buttons onthe front of the instrument.

    Housed in a robust IP66 glass reinforced polyester(GRP) enclosure with a toughened glass window,the BA444DF-P is surface mounting, or may bepipe mounted using one of the accessory kits.

    The instrument is intrinsically safe and has beencertified by European Notified Body IntertekTesting and Certification Ltd (ITS) to the ATEXDirective 94/9/EC for use in explosive gas andcombustible dust atmospheres. ATEX dustcertification is an option – see Appendix 1.

    For use in the USA and Canada, the BA444DF-Pis available with intrinsic safety and nonincendiveFM and cFM Approval – see Appendix 2.

    For international applications, all versions of theBA444DF-P PROFIBUS PA indicator have IECExintrinsic safety approval allowing installation inexplosive gas atmospheres. IECEx dustcertification is available as an option – seeAppendix 3.

    The instrument’s communication protocol is shownon a label inside the terminal cover. The ‘-P’ ordercode suffix also indicates the protocol but is notshown on the instrument certification label.There is an alternative version of the fieldbusdisplay, order code BA444DF-F for use onFOUNDATION™ fieldbus networks.

    1.1 DocumentationThis instruction manual describes ATEX systemdesign and installation of the BA444DF-PPROFIBUS PA indicator.

    System design information for non-ATEX and dustapprovals is shown in appendices to this manual.

    2. OPERATIONThe BA444DF-P indicator can display up to eightpre-configured PROFIBUS PA process variablesdesignated in-1 to in-8. The operator can selectwhich variable is displayed using the ▼and ▲push buttons which scroll the display through theeight inputs. A numeric annunciator on the lefthand side of the display shows which of the eightinputs is currently being displayed.

    2.1 Error messages

    ‘no ConF’ No inputs have beenconfigured or are enabled.

    ‘no dAtA’ No data is being receivedwith the current configuration.

    3. INTRINSIC SAFETY CERTIFICATION

    3.1 ATEX certificateThe BA444DF-P has been issued with an EC-TypeExamination Certificate by Notified Body IntertekTesting and Certification Ltd (ITS) confirmingcompliance with the European ATEX Directive94/9/EC for Group II, Category 1 gasatmospheres, Ga Ex ia IIC T4 and for dustatmospheres Ex iaD 20 T100ºC IP66. TheBA444DF-P is also FISCO compliant. Theinstrument bears the Community Mark and, subjectto local codes of practice, may be installed in anyof the European Economic Area (EEA) membercountries. ATEX certificates are also acceptablefor installations in Switzerland.

    This manual describes ATEX installations inexplosive gas atmospheres which conform withEN 60079:Part 14 Electrical Installation inHazardous Areas. When designing systems forinstallation outside the UK, the local Code ofPractice should be consulted.

    For use in the presence of combustible dust,please refer to Appendix 1 that describes ATEXinstallations complying with EN 61241: Part 14.

  • 4

    3.2 Zones, gas groups and T ratingThe BA444DF-P has been issued with EC TypeExamination certificate ITS06ATEX25313confirming that it complies with the requirementsfor Group II Category 1G Ga Ex ia IIC T4Tamb = –40 to 70ºC specified in the ATEXDirective. When connected to a suitable certifiedsystem the BA444DF-P may be installed in:

    Zone 0 explosive gas air mixturecontinuously present.

    Zone 1 explosive gas air mixturelikely to occur in normaloperation.

    Zone 2 explosive gas air mixture notlikely to occur, and if it does willonly exist for a short time.

    Be used with gases in groups:Group A propaneGroup B ethyleneGroup C hydrogen

    Having a temperature classification of:T1 450ºCT2 300ºCT3 200ºCT4 135ºC

    At an ambient temperature between –40 & +70ºC.

    Note: minimum guaranteed operating temperatureis –20ºC.

    This allows the BA444DF-P PROFIBUS PAindicator to be installed in all Zones and to be usedwith most industrial gases.

    3.3 Fieldbus connectionThe BA444DF-P Indicator is powered and receivesdata via the H1 fieldbus, which is connected toterminals 1 and 2. These terminals are non-polarised, comply with the Fieldbus IntrinsicallySafe Concept (FISCO) defined in IEC 60079 Part27 and also have separate entity parameters asshown below:

    FISCO EntityUi = 17.5V dc 22.0V dcIi = 380mA dc 250mA dcPi = 5.32W 1.2W

    The maximum equivalent capacitance andinductance at terminals 1 & 2 is:

    Ci = 0nFLi = 8µH

    3.4 Certification Label InformationThe certification information label is fitted in arecess on the top outer surface of the enclosure. Itshows details of the ATEX certification, astatement that the instrument is a FISCO FieldDevice, plus BEKA associates name and location.IECEx approval information is also included. Thelabel for some versions of the instrument will alsocontain non-European certification information.

    The instrument serial number and year ofmanufacture are recorded on a separate labelinside the terminal compartment.

    4. SYSTEM DESIGN FOR HAZARDOUS AREAS

    4.1 FISCO SystemsThe BA444DF-P PROFIBUS PA indicator may beconnected to any ATEX certified FISCO compliantfieldbus segment, providing the segment cansupply the additional 13mA required to operate theinstrument.

    Fig 1 shows a typical fieldbus segment. To complywith FISCO requirements, the power supply,terminators, field devices and the interconnectingcables must conform with IEC60079 part 27.

    Fig 1 FISCO fieldbus system

  • 5

    4.2 Non-FISCO SystemsFor non-FISCO applications the BA444DF-PPROFIBUS PA indicator has a higher voltageentity intrinsic safety input parameter allowingconnection to a wide range of fieldbus segments.

    The BA444DF-P may be connected to anyintrinsically safe segment providing:

    The device powering the fieldbus segment isATEX certified and has output parametersequal to or less than:

    Uo = 22V dcIo = 250mA dcPo = 1.2W

    The segment can provide an additional 13mAto power the BA444DF-P PROFIBUS PAindicator.

    The equivalent internal capacitance Ci of theBA444DF-P PROFIBUS PA indicator is zero andthe equivalent internal inductance is insignificant.Therefore these BA444DF-P parameters do notneed to be considered.

    5. INSTALLATION

    5.1 LocationThe BA444DF-P PROFIBUS PA indicator ishoused in a robust IP66 glass reinforced polyester(GRP) enclosure incorporating an armoured glasswindow and stainless steel fittings. It is suitable forexterior mounting in most industrial environments,including offshore and wastewater treatmentinstallations. Please consult BEKA associates ifhigh vibration is anticipated.

    The BA444DF-P enclosure is surface mounting.Accessory kits described in sections 8.3 of thismanual enable the instrument to be mounted ontoa vertical or horizontal pipe.

    The field terminals and the two mounting holes arelocated in a separate compartment with a sealedcover allowing the instrument to be installedwithout exposing the display assembly.

    The BA444DF-P earth terminal is connected to thecarbon loaded GRP enclosure. If this enclosure isnot bolted to a post or structure connected to theplant potential equalising network, the instrument’searth terminal should be connected to thepotential equalising network as recommenced inEN 60079-14.

    The BA444DF-P enclosure is supplied with abonding plate to ensure electrical continuitybetween the three conduit / cable entries.

    5.2 Installation ProcedureFig 2 illustrates the instrument installationprocedure.

    a. Remove the instrument terminal cover byunscrewing the two captive 'A' screws.

    b. Mount the instrument on a flat surface andsecure with two M6 screws through the 'B'holes. Alternatively use one of the mountingkits described in section 8.3

    c. Remove the temporary dust seals from thethree cable entries and install the requiredglands, conduit fittings or blanking plugs.Note : The temporary dust seals fitted fortransit do not maintain the IP66 protection ofthe BA444DF-P enclosure.Cable glands, conduit fittings, blanking plugsand cables must be suitable for continuoususe at the maximum operating temperatureof the instrument.

    d. Connect the field wiring to the terminals asshown in Fig 3.

    e. Replace the instrument terminal cover andevenly tighten the two 'A' screws.

    Fig 2 BA444DF-P installation procedure

  • 6

    5.3 EMCThe BA444DF-P complies with the requirements ofthe European EMC Directive 2004/108/EC. Forspecified immunity, all wiring should be inscreened twisted pairs with the screens earthed atone point in the safe area.

    Fig 3 Dimensions and terminal connections

    6. CONFIGURATIONThe BA444DF-P 8 variable PROFIBUS PA PAindicator may be configured as a fieldbus node oras a fieldbus listener. When used as a fieldbusnode the indicator is configured via the fieldbushost although the instrument address may beentered via the front panel push buttons using themenu shown in Fig 4. For detailed nodeconditioning information please refer to the BEKAPROFIBUS PA Display – Fieldbus Interface Guidewhich may be downloaded from the BEKA websitewww.beka.co.uk

    As a fieldbus listener, the BA444DF-P is not visibleto the fieldbus host and can only be configured viathe front panel push buttons using the menushown in Fig 6.

    Throughout this manual the four BA444DF-P pushbuttons are identified P E ▼ ▲ and legendsdisplayed by the instrument are shown withininverted commas e.g. ‘CodE’ and ‘Enb’.

    6.1 Configuration menusThe configuration menus are separated into twosections, fieldbus node and fieldbus listener. Bothcontain the ‘tYPE’ function that enables transferbetween the two. Unless otherwise requestedwhen ordered, all PROFIBUS PA BA444DF-Pinstruments are supplied as a fieldbus node withdefault configuration but can easily be reconfiguredon-site.

    6.2 Node configuration menuThe node configuration menu is shown in Fig 4.Access to the menu is obtained by operating the Pand E buttons simultaneously. If the BA444DF-Pis not protected by an access code the firstparameter 'Addr’ will be displayed. If theinstrument is protected by an access code, ‘CodE’will be displayed first. Pressing P will allow thefour digit security code to be entered digit by digitusing the ▼ or ▲ button to adjust the flashing digitand P to move control to the next digit. When thecorrect code has been entered, pressing E willcause the first parameter ‘Addr’ to be displayed.If an incorrect code is entered, or no button ispressed for ten seconds, the BA444DF-P willautomatically return to the display mode.

    6.2.1 Enter fieldbus address ‘Addr’This function enables the fieldbus address of theBA444DF-P to be entered via the push buttons.Select ‘Addr’ in the node menu using the ▼ or ▲button and press P to enter the function. This willreveal the existing three digit decimal address withthe left hand digit flashing which may be changedby operating the ▼ or ▲ button. When set asrequired operating the P button will transfer controlto the next digit that may be adjusted in the sameway. When all digits are set as required operatingthe E button will enter the new address and theindicator will restart in the display mode aftercompleting the initialisation sequence. If theaddress is not changed, operating the E button willreturn the display to the ‘Addr’ prompt in the nodeconfiguration menu.

    6.2.2 Access code for configuration menu ‘CodE’Access to the node configuration menu may beprotected by a four digit security code which mustbe entered to gain access. New instruments aresupplied configured with the default code 0000which disables this protection and allowsunrestricted access to the configuration menu.

  • 7

    To enter a new access code select ‘CodE’ in thenode configuration menu by operating the ▼ or ▲button. To enter the function press P which willreveal the current access code with one digitflashing. The code may be changed using the ▼ or▲ button to adjust the flashing digit and the Pbutton to move control to the next digit. When therequired code has been selected, press E to enterthe selection and return to the ‘CodE’ prompt in theconfiguration menu. The revised access code willbe activated when the transmitter is returned to thedisplay mode.

    If the access code is lost please contact BEKAassociates.

    6.2.3 Change from node to listener ‘tYPE’This function enables the instrument to bechanged from a fieldbus node to a fieldbus listener.Select ‘tYPE’ in the node configuration menu usingthe ▼ or ▲ button. To enter the function press Pwhich will show that the instrument is configuredas a fieldbus node, to change to a fieldbus listenerpress the ▼ or ▲ button which will toggle thedisplay to ‘LStnr’ To prevent accidental changesthis request must be confirmed by operating the Pbutton and entering ‘5urE’. The instrument willdisplay ‘0000’ with the first digit flashing, using the▼ or ▲ button set the flashing digit to ‘5’ and pressthe P button to move control to the next digit whichshould be set to ‘u’. When the four letters of ‘5urE’have been entered, operating the E button willcause the instrument to restart as a fieldbuslistener in the display mode.

    CAUTIONAll the instrument’s node configurationinformation will be lost when it ischanged from a fieldbus node to afieldbus listener.

    Please refer to the quick set-up procedure in theBEKA PROFIBUS PA Display – Fieldbus InterfaceGuide.

    6.2.4 Reset the instrument to node factory defaults ‘rESEt’The BA444DF-P may be reset to the factorydefaults that are shown below:

    Security Code 0000 (disabled)Device address 126

    For each of the eight inputs:Decimal point XXX.XXBar Type LeftBar lower limit 0.0Bar Upper limit 100.0Gain 1.0Offset 0.0

    To reset the BA444DF-P select ‘rESEt’ in theconfiguration menu by operating the ▼ or ▲button. To enter the function press P which willreveal ‘0000’ with the left hand digit flashing. Toprevent accidental use of this function, ‘5urE’ mustbe entered to confirm that the instrument is to bereset.

    Using the ▼ or ▲ button set the flashing digit to ‘5’and press the P button to move control to the nextdigit which should be set to ‘u’. When the fourletters of ‘5urE’ have been entered operating the Ebutton will reset the BA444DF-P to the factorydefaults. Any existing configuration andaddresses will be lost when the instrument is reset.

    FIG 4 Node configuration menu

  • 8

    6.3 Listener configuration menuWhen used as a fieldbus listener the BA444DF-Pis not visible to the fieldbus host and can only beconfigured using the front panel push buttonsshown in Fig 3.

    The listener configuration menu is separated intothree sections, ‘SCAn’, ‘LISt’ and ‘Edit’, plus threehousekeeping functions ‘CodE’, ‘tYPE’ and ‘rESEt’as shown in Fig 6.

    ‘SCAn’ is the simplest method of configuration ifthe addresses of the data sources to be displayedby the BA444DF-P listener are not known.

    In the ‘SCAn’ function pressing the P buttoncauses the BA444DF-P listener to search thefieldbus segment to which it is connected for alldata sources. The hexadecimal deviceaddresses for each data source are displayed asshown in Fig 5.

    The ▼ and ▲ push buttons scroll the displaythrough all the data sources on the segmentshowing the source and destination address foreach one. To aid identification, operating the Pbutton will preview the value of the data at theselected addresses with a zero index i.e. the firstfive bytes in the data string. If the format of thedata is not DS-33 (status + float) ‘no dAt’ will bedisplayed. The selected source and destinationaddresses may be allocated to one of the eightBA444DF-P listener inputs in-1, to in-8. Operatingthe P button will reveal the current listener inputwhich may be changed using the ▼ or ▲ pushbutton, when set as required, operating the E pushbutton will enter the allocation. If the processvariable to be displayed is located further along thedata stream i.e. has an index greater than 5, therequired index must be entered via the index ‘ind’function in the edit sub-menu.

    A worked configuration example illustrating thisprocedure is contained in the Quick Set-up sectionof the PROFIBUS PA Interface Guide.

    Fig 5 Device Addresses

    If the source and destination addresses and indexof the process variable to be displayed by theBA444DF-P listener are known, they may bedirectly entered via the edit sub-menu. This sub-menu also provides full control of both the numericand bargraph display parameters.

  • 9

  • 10

    6.3.1 AccessAccess to the listener configuration menu isobtained by operating the P and E buttonssimultaneously. If the BA444DF-P listenerconfiguration menu is not protected by an accesscode the first parameter 'SCAn’ will be displayed.If the BA444DF-P is protected by an access code,‘CodE’ will be displayed first. Pressing P will allowthe four digit security code to be entered digit bydigit using the ▼ or ▲ button to adjust the flashingdigit and P to move control to the next digit. Whenthe correct code has been entered, pressing E willcause the first parameter ‘SCAn’ to be displayed.If an incorrect code is entered, or no button ispressed for ten seconds, the indicator willautomatically return to the display mode.

    Section 6.3.2 contains a summary of eachconfiguration function including a cross referenceto a more detailed description.

    6.3.2 Summary of listener configurationfunctions

    Instrument Summary display of function

    ‘SCAn’ Scan fieldbus segment Identifies all data sources on thefieldbus segment to which the listener isconnected and enables selected data tobe allocated to one of the eight listenerinputs in-1 to in-8.See section 6.4.1

    ‘LiSt’ List configured input parametersFor each of the eight BA444DF-Plistener inputs, in-1 to in-8 shows if theinput is enabled, Source Address,Destination Address and the Indexwhich have been allocated.Parameters can not be changed fromwithin this function.See section 6.4.2

    ‘Edit’ Enter addresses and displayparametersSub-menu which allows known fieldbusdevice addresses to be entered and alldisplay parameters adjusted for each ofthe eight fieldbus listener inputs.See section 6.4.3

    ‘Enb’ Enable selected input

    Enables each of the eightlistener inputs in-1 to in-8 tobe enabled or disabledwithout affecting anyparameters.See section 6.4.4

    ‘SrC’ Enter Source AddressAllows hexadecimal fieldbusdevice source address foreach of the eight listenerinputs in-1 to in-8 to beentered.See section 6.4.5

    ‘dSt’ Enter Destination AddressAllows hexadecimal fieldbusdevice destination address foreach listener input in-1 to in-8to be entered.See section 6.4.6

    ‘ind’ Enter IndexAllows hexadecimal index forspecified fieldbus sourceaddress to be entered foreach listener input in-1 to in-8.See section 6.4.7

    ‘dP’ Decimal point positionDefines position of displayeddecimal point for each listenerinput in-1 to in-8.See section 6.4.8

    ‘bAr’ Configuration of bargraphDefines the bargraphsjustification and the digitaldisplay at which the bargraphis zero and full scale for eachlistener input in-1 to in-8.See section 6.4.9

    ‘SCALE’ Scale numeric displayApplies zero offset and scalefactor to the numeric displayfor each listener input in-1 toin-8.See section 6.4.10

    ‘CodE’ Access code for listenerconfiguration menuEnters a four digit security accesscode for configuration menu. Defaultcode 0000 disables this function.See section 6.4.11

    ‘tYPE’ Change from listener to nodeEnables the instrument to beconditioned as a fieldbus listener or afieldbus node.See section 6.4.12

    ‘rESEt’ Reset to listener factory defaultsReturns the BA444DF-P listener tofactory defaults.See section 6.4.13

  • 11

    6.4 Description of listener menu functionsThis section contains a detailed description of eachfunction in the listener configuration menu. Itshould be read in conjunction with Fig 6.

    6.4.1 Scan fieldbus segment ‘SCAn’If the Device Addresses of a data source are notknown, the ‘SCAn’ function provides a simple wayto identify them. This function scans the fieldbussegment to which the BA444DF-P listener isconnected and identifies all the data sources. Toaid identification the value of the process variablewith a zero index i.e. the first five bytes in the datastring at the address may be pre-viewed.

    The BA444DF-P listener only supports DS-33formatted data (status+float) which is the usualformat for analogue process variables. The‘SCAn’ function will identify, irrespective of format,all data sources on the segment whose destinationaddress is five bytes long. When pre-viewed, nonDS-33 formatted data will produce a ‘no dAt’ errormessage.

    ‘SCAn’ is the first function displayed when enteringthe configuration menu, or it may be selected fromwithin the menu by operating the ▼ or ▲ button.To scan the fieldbus segment to which the listeneris connected for all data sources press P which willreveal the hexadecimal source address anddestination address of the first data source foundas shown in Fig 5. If there is more than one datasource, operating the ▼ or ▲ button will scrollthough all of them.

    If there are no data sources on the fieldbussegment the BA444DF-P listener will display‘noSrC’.

    When the source and destination addresses of adata source are displayed, to aid identification thevalue of the process variable with a zero index i.e.the first five bytes in the data string may be pre-viewed by operating the P button. If this confirmsthat it is the required address, it may be allocatedto one of the eight BA444DF-P listener inputs in-1to in-8. To select the required listener input, pressP which will display the first input in-1. Operatingthe ▼ or ▲ button will scroll the display throughthe other inputs. When the required input isdisplayed pressing E will allocate the selected datasource address to the selected input and return thedisplay to the source and destination addressesfrom which another data source address may beselected. When a data source address is allocatedto a listener input any previous allocation will beoverwritten.

    If the required process variable has an indexabove 5 i.e. it is not the first five bytes in the datastring, the required index should be entered via the‘ind’ function in the Edit sub-menu which isdescribed in section 6.4.7

    6.4.2 List configured input parameters ‘LiSt’The ‘LiSt’ function enables the Source Address,Destination Address and Index allocated to eachlistener input to be viewed without danger of itbeing accidentally changed.

    The ‘LiSt’ function may be selected from within themenu by operating ▼ or ▲ button. To enter thefunction press P which will display the listenerinput currently selected in the display mode, otherinputs may be selected using the ▼ or ▲ button.Operating the P button will cause the followingparameters for the selected input to be displayedsequentially:

    Display Explanation‘Enb :Y or N’ Input Enabled yes or no‘SrC :00’ Source Address‘dSt :00’ Destination Address‘ind :00’ Index

    The display then automatically returns to theselected BA444DF-P listener input from whereanother input may be selected.

    If one of the eight BA444DF-P Listener’s inputs in-1 to in-8 has not had a Source Address,Destination Address and Index allocated to it, ‘LiSt’will show both addresses as ‘FF’ and the index‘ind’ as ‘00’.

    6.4.3 Enter address & display parameters ‘Edit’The ‘Edit’ sub-menu may be selected from withinthe menu by operating ▼ or ▲ button. To enter thefunction press P which will display the listenerinput currently selected in the display mode, otherlistener inputs may be selected using the ▼ or ▲button. When the required input has beenselected operating the P button will enter the editsub-menu at ‘Enb’ for the selected input.

    6.4.4 Enable selected input ‘Enb’‘Enb’ turns the listener input selected in the Editfunction on or off without affecting the conditioning.To enter the function press P which will revealwhether the selected input is ‘on’ or ‘oFF’.Operating the ▼ or ▲ buttons will toggle betweenthe two conditions. When set as requiredoperating the E button will enter the selection andreturn to the ‘Enb’ prompt in the edit sub-menu.

  • 12

    6.4.5 Enter source address ‘SrC’This function allows a known fieldbus devicesource address to be entered and allocated to thelistener input selected in the edit function. To enterthe function press P which will reveal the existingtwo digit hexadecimal address with one digitflashing which may be changed by operating the ▼or ▲ button. When set as required operating theP button will transfer control to the second digitthat may be adjusted in the same way. When bothdigits are set as required operating the E buttonwill enter the selection and return to the ‘SrC’prompt in the edit sub-menu.

    6.4.6 Enter destination address ‘dSt’This function allows a known fieldbus devicedestination address to be entered and allocated tothe listener input selected in the Edit function. Toenter the function press P which will reveal theexisting two digit hexadecimal address with onedigit flashing which may be changed by operatingthe ▼ or ▲ button. When set as required operatingthe P button will transfer control to the second digitthat may be adjusted in the same way. When bothdigits are set as required operating the E buttonwill enter the selection and return to the ‘dSt’prompt in the edit sub-menu.

    6.4.7 Enter Index ‘ind’Index defines the location of the required processvariable in the data string. The ‘ind’ function allowsa known Index for the selected fieldbus SourceAddress to be entered and allocated to theBA444DF-P listener input selected in the Editfunction. The data location is manufacturer specificand can not be automatically determined; thedevice documentation should therefore beconsulted. To enter the function press P which willreveal the existing two digit hexadecimal addresswith one digit flashing which may be changed byoperating the ▼ or ▲ button. When set as requiredoperating the P button will transfer control to thesecond digit that may be adjusted in the sameway. When both digits are set as requiredoperating the E button will enter the selection andreturn to the ‘ind’ prompt in the edit sub-menu.

    6.4.8 Decimal point position ‘dP’This defines the position the decimal point in thenumeric display. To enter the function press Pwhich will reveal the existing decimal pointposition. Operating the ▼ or ▲ button will movethe decimal point to the required position, omit it,or activate all the decimal points whichautomatically provides maximum resolution in thedisplay mode irrespective of the numeric value.When positioned as required, operating the Ebutton will enter the selection and return to the ‘dP’prompt in the edit sub-menu.

    6.4.9 Configuration of bargraph display ‘bAr’This function contains three sub-functions thatenable the bargraph, justify its position and definethe relationship between the bargraph and theinstrument’s numeric display.

    Sub-function ‘b.tYPE’ enables the bargraph to beleft, centre or right justified, or to be turned off.Sub-functions ‘bArLo’ and ‘bArhi’ define thelistener’s numeric display at which the bargraphstarts and is at full scale.The ‘bAr’ function may be selected from within theedit sub-menu by operating the ▼ or ▲ button.To enter the function press P which will display the‘b.tYPE’ sub-function, pressing P again will revealthe existing bargraph justification. The ▼ or ▲button will scroll through the four options, when therequired justification is displayed, pressing E willenter the selection and return the display to the‘b.tYPE’ prompt in the edit sub-menu from which‘bArLo’ may be selected using the ▼ or ▲ button.

    ‘bArLo’ defines the listener’s numeric display atwhich the bargraph starts, to enter the functionpress P which will reveal the existing setting. Thedisplay may be changed using the ▼ or ▲ buttonto adjust the flashing digit and the P button tomove control to the next digit. When the requiredstarting display has been selected, press E toreturn to the ‘bArLo’ prompt in the edit sub-menufrom which the ‘bArHi’ function may be selected.

    ‘bArHi’ defines the listener’s numeric display atwhich the bargraph is full scale, to enter thefunction press P which will reveal the existingsetting. The display may be changed using the ▼or ▲ button to adjust the flashing digit and the Pbutton to move control to the next digit. When therequired display has been selected, press E twiceto enter the new values and return to the ‘bAr’prompt in the edit sub-menu.

    Note: If the ‘dP’ function has been set to provideautomatic maximum resolution irrespective of thedisplayed value, it may be necessary to manuallyposition the decimal point before adjusting ‘bArLo’or ‘bArHi’. This can be achieved by repeatedlyoperating the P button until the activated decimalpoint flashes, the decimal point can then bepositioned using either the ▼ or ▲ button.Pressing the P button again will return control toone of the digits.

    6.4.10 Scale numeric display ‘SCALE’A scaling factor ‘Gain’ and an offset ‘oFFSt’ maybe applied to the fieldbus process variable usingthis function, thus allowing the listener to displaythe fieldbus process variable in alternative units.

  • 13

    The ‘SCALE’ function may be selected from withinthe edit sub-menu by operating the ▼ or ▲ button.To enter the function press P which will display the‘GAin’ sub-function, pressing P again will revealthe existing gain with one digit flashing. Thisflashing digit may be changed by operating the ▼or ▲ button; when adjusted the P button will movecontrol to the next digit or to the decimal pointwhich can be positioned using the ▼ or ▲ button.When ‘GAin’ has been set to the required valueoperating the E button will enter the selection andreturn to the ‘GAin’ prompt in the sub-menu fromwhere the ‘oFFSt’ function can be selected usingthe ▼ or ▲ button.

    To enter the ‘oFFSt’ function press P which willreveal the existing offset with one digit flashing.Again the flashing digit may be changed byoperating the ▼ or ▲ button and the P button willmove control to the next digit or to the decimalpoint. When ‘oFFSt’ has been set to the requiredvalue operating the E button will enter the selectionand return to the ‘oFFSt’ prompt in the sub-menu.Three operations of the E button will return to the‘Edit’ function in the main configuration menu.

    6.4.11 Access code for listener configuration menu ‘CodE’Access to the listener configuration menu may beprotected by a four digit security code which mustbe entered to gain access. New instruments aresupplied configured with the default code 0000which disables this protection and allowsunrestricted access to the configuration menu.

    To enter a new access code select ‘CodE’ in theconfiguration menu by operating the ▼ or ▲button. To enter the function press P, this willreveal the current access code with one digitflashing. The code may be changed using the ▼ or▲ button to adjust the flashing digit and the Pbutton to move control to the next digit. When therequired code has been selected, press E to enterthe selection and return to the ‘CodE’ prompt in theconfiguration menu. The revised access code willbe activated when the transmitter is returned to thedisplay mode.

    If the access code is lost please contact BEKAassociates.

    6.4.12 Change from fieldbus listener tofieldbus node ‘tYPE’This function enables the BA444DF-P to beconditioned as a fieldbus node or as a fieldbuslistener. To change the function of the instrumentselect ‘tYPE’ in the listener configuration menuusing the ▼ or ▲ button and press P to enterwhich will show that the instrument is configuredas a fieldbus listener.

    To change to a fieldbus node press the ▼ or ▲button which will toggle the display to ‘nodE’. Toprevent accidental changes this request must beconfirmed by operating the P button and entering‘5urE’. The instrument will display ‘0000’ with thefirst digit flashing, using the ▼ or ▲ button set theflashing digit to ‘5’ and press the P button to movecontrol to the next digit which should be set to ‘u’.When the four letters of ‘5urE’ have been entered,operating the E button will result in the instrumentrestarting in the display mode as a fieldbus node.

    CAUTIONAll the instrument’s listener configurationinformation will be lost when it ischanged from a fieldbus listener to afieldbus node.

    6.4.13 Reset the listener to factory defaults ‘rESEt’The BA444DF-P listener may be reset to thefactory defaults that are shown below:

    Security Code 0000 (disabled)

    For each of the eight inputs:Decimal point XXX.XXBar Type LeftBar lower limit 0.0Bar Upper limit 100.0Gain 1.0Offset 0.0

    To reset the BA444DF-P listener select ‘rESEt’ inthe configuration menu by operating the ▼ or ▲button. To enter the function press P, this willreveal ‘0000’ with the left hand digit flashing. Toprevent accidental use of this function, ‘5urE’ mustbe entered to confirm that the instrument is to bereset.

    Using the ▼ or ▲ button set the flashing digit to ‘5’and press the P button to move control to the nextdigit which should be set to ‘u’. When the fourletters of ‘5urE’ have been entered operating the Ebutton will reset the BA444DF-P to the factorydefaults. Any existing configuration andaddresses will be lost when the listener is reset.

  • 14

    7. MAINTENANCE

    7.1 Fault finding during commissioningIf a BA444DF-P fails to function duringcommissioning the following procedure should befollowed:

    Symptom Cause Check:No Display Instrument not

    correctlyconnected or

    powered.

    9 to 22V betweenterminals 1 & 2.

    Displays‘no ConF’

    No inputs areenabled.

    Configuration ofeach input.

    Displays‘no dAtA’

    No data beingreceived with the

    currentconfiguration.

    Addresses andIndex are correct.

    That data hasDS-33 format.

    Display shows‘9.9.9.9.9’ with all

    decimal pointsflashing; allbargraphsegments

    activated andbargraph scale

    flashing.

    Valueover-range

    Configuration.and

    decimal pointposition.

    Display shows‘-9.9.9.9.9’ with

    all decimal pointsflashing; no

    bargraphsegments

    activated andbargraph scale

    flashing.

    Valueunder-range

    ConfigurationAnd

    Decimal pointposition.

    Displayalternates

    between valueand the word

    ‘bAd’. Bargraphflashes.

    Status of fieldbusvariable has a

    quality of ‘BAD’or a fault state is

    active.

    Fieldbusconfiguration.

    Bargraph scaleflashes.

    Process variableis outside the

    limits defined forthe bargraph.

    Bargraphconfiguration.

    All displaysegmentsactivated.

    Display isinitialising.

    This is normaloperation, after afew seconds themodel numberfollowed by the

    firmware versionwill be displayedprior to entering

    the displaymode.

    7.2 Fault finding after commissioning

    ENSURE PLANT SAFETY BEFORESTARTING MAINTENANCE

    Live maintenance is permitted onintrinsically safe equipment installed in ahazardous area, but only certified testequipment should be used unless a gasclearance certificate is available.

    If a BA444DF-P fails after it has beenfunctioning correctly, the table shown in section7.1 may help to identify the cause of the failure.

    If this procedure does not reveal the cause of thefault, it is recommended that the instrument isreplaced.

    7.3 ServicingWe recommend that faulty BA444DF-P PROFIBUSPA Indicators are returned to BEKA associates orto our local agent for repair.

    7.4 Routine maintenanceThe mechanical and electrical condition of theinstrument should be regularly checked. Initiallyannual inspections are recommended, but theinspection frequency should be adjusted to suit theenvironmental conditions.

    7.5 GuaranteeInstruments which fail within the guarantee periodshould be returned to BEKA associates or our localagent. It is helpful if a brief description of the faultsymptoms is provided.

    7.6 Customer commentsBEKA associates is always pleased to receivecomments from customers about our products andservices. All communications are acknowledgedand whenever possible, suggestions areimplemented.

  • 15

    8. ACCESSORIES

    8.1 Scale and tag markingBA444DF-P PROFIBUS PA Indicators are fittedwith a blank escutcheon around the liquid crystaldisplay. If specified when the instrument isordered, this can be supplied printed with units ofmeasurement and tag information, plus a scale forthe horizontal bargraph. Alternatively, informationmay be added on-site via an embossed strip, drytransfer or a permanent marker.

    To gain access to the display escutcheon removethe terminal cover by unscrewing the two 'A'screws which will reveal two concealed 'D' screws.Unscrew all four 'D' screws and carefully lift off thefront of the instrument. The location of thesescrews is shown in Fig 2.

    After adding the required legends, or fitting a newpre-printed self-adhesive escutcheon, ensure thatthe gasket is correctly positioned beforereassembling the instrument enclosure.

    8.2 Tag plateThe BA444DF-P can be supplied with a blank orcustom laser marked stainless steel plate securedby two screws to the front of the instrumentenclosure. This plate can accommodate:

    1 row of 9 alphanumeric characters 10mm high

    or 1 row of 11 alphanumeric characters 7mm high

    or 2 rows of 18 alphanumeric characters 5mm high.

    or 8 cells each containing units of measurement or identification for one of the 8 inputs.

    8.3 Pipe mounting kitsTwo pipe mounting kits are available for securingthe BA444DF-P to a horizontal or vertical pipe.

    BA392D Stainless steel bracket secured by twoworm drive hose clips for 60 to 80mmoutside diameter pipes.

    BA393 Heavy-duty stainless steel bracketsecured by a single 'V' bolt. Will clampto any pipe with an outside diameterbetween 40 and 80mm.

  • 16

    APPENDIX 1ATEX dust certification

    A1.0 ATEX dust certificationIn addition to ATEX certification permittinginstallation in explosive gas atmospheres which isdescribed in the main section of this instructionmanual, the BA444DF-P is available with optionalATEX certification permitting use in the presenceof combustible dusts. If ATEX dust certification isrequired it must be requested when the BA444DF-P PROFIBUS PA indicator is purchased.

    WARNINGBefore installing a BA444DF-PPROFIBUS PA indicator in the presenceof a combustible dust, ensure that thecertification information label, which islocated on the top of the instrument,specifies dust certification – see sectionA1.2

    A1.1 Zones and Maximum Surface TemperatureThe BA444DF-P has been ATEX certified asGroup II, Category 1D Ex iaD 20 T100oC IP66apparatus Tamb = -20 to 60oC. When installedas specified by EN 61241-14 ‘Electrical apparatusfor use in the presence of combustible dust –Selection and installation’, the BA444DF-PPROFIBUS PA indicator may be installed in:

    Zone 20 explosive atmosphere in theform of a cloud ofcombustible dust in air iscontinuously present, or forlong periods or frequently.

    Zone 21 explosive atmosphere in theform of a cloud ofcombustible dust in air islikely to occur occasionallyin normal operation.

    Zone 22 explosive atmosphere in theform of a cloud ofcombustible dust in air is notlikely to occur in normaloperation, but if it doesoccur, will only persist for ashort period.

    Be used with dusts having a Minimum IgnitionTemperature of:

    Dust cloud 150oC

    Dust layer on BA444DF-P 175oCup to 5mm thick

    Dust layer on BA444DF-P Refer toover 5mm thick. EN 61241-14

    At an ambient temperature between –20 and+60oC

    A1.2 Certification Label InformationThe certification label is fitted in a recess on thetop outer surface of the enclosure. It shows detailsof the ATEX dust certification including themaximum surface temperature and ingressprotection plus BEKA associates name andlocation. IECEx dust approval information is alsoshown, non-European certification information mayalso be included.

    The instrument serial number and date ofmanufacture are recorded on a separate labelinside the terminal compartment.

    A1.3 Installation & maintenanceThe ATEX dust certification relies on theBA444DF-P PROFIBUS PA enclosure being dust-tight. Therefore the terminal cover should only beremoved when dust can not enter the instrumentenclosure. Before replacing the terminal coverensure that the sealing gaskets are undamagedand are free from foreign bodies.

  • 17

    APPENDIX 2FM Approval for use in the USA andcFM Approval for use in Canada

    A2.0 Factory Mutual Approval

    For installations in the USA and Canada, a versionof the BA444DF-P is available with FM and cFMintrinsic safety and nonincendive approval, projectidentifications 3027031 and 3027031C. Copiesof the Certificates of Compliance are availablefrom BEKA associates sales office andwww.beka.co.uk

    The FM and cFM Approved version is identical tothe ATEX version except the three M20 x 1,5tapped cable entries are replaced by three plainunthreaded 22.25mm diameter entries. Approvedhubs and glands are listed in note 6 of IntrinsicallySafe Control Drawing CI410-12 and note 5 ofNonincendive Control Drawing CI410-13. Thecertification label on the FM and cFM Approvedversion includes ATEX gas certification informationso that the BA444DF-P PROFIBUS PA indicatormay be used in systems covered by eitherauthority.

    A2.1 Intrinsic safety approvalThe BA444DF-P is approved to FM Class 3610intrinsic safety standard for use in indoor andoutdoor hazardous (classified) locations.Installations must comply with BEKA associatesControl Drawing CI410-12, which is attached tothis Appendix, ANSI/ISA RP12.06.01 ‘Installationof Intrinsically Safe Systems for Hazardous(Classified) Locations’ and with the NationalElectrical Code ANSI/NFPA70.

    The BA444DF-P has a T4 rating at ambienttemperatures up to +70oC and may be used withthe following gases and dusts:

    Intrinsic SafetyDivision 1 or 2

    Class I Group A & B Group C Group D

    Class II Group E, F & G

    Class III

    Zone 0, 1 or 2Class 1 Group IIC Group IIB Group IIA

    Canadian installations must comply with theCanadian Electrical Code C22.2 and with BEKAassociates Control Drawing CI410-12, which isattached to this Appendix.

    The FM and cFM entity parameters are identical tothe ATEX parameters and, like the ATEXcertification, confirm that the BA444DF-P complieswith the FISCO Field Device requirementsspecified in IEC60079-27. The intrinsically safesystem shown in Fig 1 of this manual maytherefore be used for installations in the USA andCanada, providing the fieldbus power supply,terminators, Zener barriers and galvanic isolatorsare FM Approved for US installations and cFM orCSA Approved for Canadian installations. Allinstallations must comply with BEKA associatesControl Drawing CI410-12 .

    FM and cFM Approvals also allows the BA444DF-P to be connected to non-FISCO systems usingthe entity concept – see section 3.2 of this manual.

    A2.2 Nonincendive approvalThe BA444DF-P is FM Class 3611 nonincendiveapproved allowing it to be installed in Division 2indoor and outdoor hazardous (classified) locationswithout the need for Zener barriers or galvanicisolators. US installations must comply with theBEKA associates Control Drawing CI410-13, whichis attached to this Appendix, and with the NationalElectrical Code ANSI/NFPA70.

    Canadian nonincendive installations must complywith the Canadian Electrical Code C22.2 and withBEKA associates Control Drawing CI410-13, whichis attached to this Appendix.

    The FM and cFM Nonincendive Approvals alsoallow the BA444DF-P PROFIBUS PA indicator tobe connected to any appropriately certified FNICOcompliant fieldbus segment.

    The BA444DF-P has a T4 rating at ambienttemperatures up to +70ºC and may be used withthe following gases and dusts:

    NonincendiveDivision 2

    Class I Group A & B Group C Group D

    Class II Groups E, F & G

    Class III

    Zone 2Class I Group IIC Group IIB Group IIA

  • 18

  • 19

  • 20

  • 21

  • 22

  • 23

  • 24

  • 25

    APPENDIX 3IECEx Certification

    A3.0 The IECEx Certification SchemeIECEx is a global certification scheme forexplosion protected products which aims toharmonise international certification standards.For additional information about the IECExcertification scheme and to view the BEKAassociate certificates, please visit www.iecex.com

    A3.1 IECEx Certificate of Conformity for use in an explosive gas atmospheresThe BA444DF-P PROFIBUS PA indicator hasbeen issued with an IECEx Certificate ofConformity number IECEx ITS 06.0012 whichspecifies the following certification codes andmarking:

    Ex ia IIC T4 GaFISCO Field Device Ex ia IIC T4Ta = -40ºC to 70 ºC

    When connected to a certified IECEx system theBA444DF-P may be installed in:

    Zone 0 explosive gas air mixturecontinuously present.

    Zone 1 explosive gas air mixturelikely to occur in normaloperation.

    Zone 2 explosive gas air mixture notlikely to occur, and if it does willonly exist for a short time.

    Be used with gases in groups:Group A propaneGroup B ethyleneGroup C hydrogen

    Having a temperature classification of:T1 450ºCT2 300ºCT3 200ºCT4 135ºC

    At an ambient temperature between –40 and+70ºC.

    A3.1.1 Installation in an explosive gas atmosphereFor installations in gas atmospheres the BA444DF-P IECEx and ATEX certifications have identicalintrinsic safety parameters and installationrequirements. The ATEX system designrequirements described in section 5 of this manualmay therefore be used for IECEx installations in

    gas atmospheres, but the local code of practiceshould also be consulted.A3.2 IECEx Certificate of Conformity Use in presence of combustible dustsIn addition to IECEx certification permittinginstallation in explosive gas atmospheres, theBA444DF-P is available with optional IECExcertification permitting use in the presence ofcombustible dusts.

    The IECEx Certificate of Conformity specifies thefollowing certification codes and marking:

    Ex ia IIIC T100ºC Da IP66Ta = -20oC to 60 ºC

    If IECEx dust certification is required it must berequested when the BA444DF-P PROFIBUS PAindicator is purchased.

    WARNINGBefore installing a BA444DF-PPROFIBUS PA indicator in the presenceof a combustible dust, ensure that thecertification information label, which islocated on the top of the instrument,specifies dust certification - see below.

    When connected to a certified IECEx system theBA444DF-P may be installed in:

    Zone 20 explosive atmosphere in theform of a cloud ofcombustible dust in air iscontinuously present, or forlong periods or frequently.

    Zone 21 explosive atmosphere in theform of a cloud ofcombustible dust in air islikely to occur occasionallyin normal operation.

    Zone 22 explosive atmosphere in theform of a cloud ofcombustible dust in air is notlikely to occur in normaloperation, but if it doesoccur, will only persist for ashort period.

  • 26

    3.2.1 Installation in the presence of combustible dustThe IECEx dust certification relies on theBA444DF-P enclosure being dust-tight. Thereforethe terminal cover should only be removed whendust can not enter the instrument enclosure.Before replacing the terminal cover ensure that thesealing gaskets are undamaged and are free fromforeign bodies.

    The IECEx certificate may be downloaded fromwww.beka.co.uk, www.iecex.com or requestedfrom the BEKA sales office.

    A3.3 Versions of the BA444DFAll versions of the BA444DF-P PROFIBUS PAIndicator have IECEx certification. This includes:

    ATEX version for use in gas atmospheres.IECEx code Ex ia IIC T4 Ga

    FISCO Field Device Ex ia IIC T4Ta = -40ºC to 70ºoC

    ATEX version for use in gas and dustatmospheres.

    IECEx code Ex ia IIC T4 GaFISCO Field Device Ex ia IIC T4Ex ia IIIC T100oC Da IP66Ta = -20ºC to 60 ºC

    Factory Mutual Approved versionIECEx code Ex ia IIC T4 Ga

    FISCO Field Device Ex ia IIC T4Ta = -40ºC to 70ºC

    ul. Lechicka 14 ; 02-156 Warszawa Fax. (+48 022) 846 50 37 [email protected] Automatyka Sp. z o. o. Tel. (+48 022) 886 10 16 www.trautomatyka.pl