Page 1: Back to Basics: Pumping Systems...VARIABLE PRIMARY Variable flow through chiller/boiler – to a minimum. Bypass or 3-way valves to maintain min flow. Manifold the pumps to disassociate

4/29/2016

Back to Basics: Pumping Systems

1 RM ASHRAE TECH CONFERENCE

Page 2: Back to Basics: Pumping Systems...VARIABLE PRIMARY Variable flow through chiller/boiler – to a minimum. Bypass or 3-way valves to maintain min flow. Manifold the pumps to disassociate

2

AGENDA

Closed loop heating and cooling piping systems

Expansion Tanks

Pumps

Page 3: Back to Basics: Pumping Systems...VARIABLE PRIMARY Variable flow through chiller/boiler – to a minimum. Bypass or 3-way valves to maintain min flow. Manifold the pumps to disassociate

BASIC PUMPING LOOP

Nice and simple – too simple? Constant energy draw of pump? Compatibility of source and load flow and temperatures

Too low/high boiler/chiller return temp Too high radiant floor temp Too low chilled beam temp Too little chiller/boiler flow

3

Page 4: Back to Basics: Pumping Systems...VARIABLE PRIMARY Variable flow through chiller/boiler – to a minimum. Bypass or 3-way valves to maintain min flow. Manifold the pumps to disassociate

DIRECT RETURN

Simple, minimal pipe

Extreme head differences will create balancing and control difficulties

4

Page 5: Back to Basics: Pumping Systems...VARIABLE PRIMARY Variable flow through chiller/boiler – to a minimum. Bypass or 3-way valves to maintain min flow. Manifold the pumps to disassociate

REVERSE RETURN

Eliminates extreme head differences

Extra pipe – loop layouts are less extra than linear

5

Page 6: Back to Basics: Pumping Systems...VARIABLE PRIMARY Variable flow through chiller/boiler – to a minimum. Bypass or 3-way valves to maintain min flow. Manifold the pumps to disassociate

REVERSE RETURN

Loop Layout

6

Page 7: Back to Basics: Pumping Systems...VARIABLE PRIMARY Variable flow through chiller/boiler – to a minimum. Bypass or 3-way valves to maintain min flow. Manifold the pumps to disassociate

DIRECT/REVERSE RETURN

This shows multiple riser low rise.

For single riser layouts, each floor can be RR with DR risers

Can combine RR and DR for multiple loops/wings.

Minimizes pipe, maintains balance advantages

7

Page 8: Back to Basics: Pumping Systems...VARIABLE PRIMARY Variable flow through chiller/boiler – to a minimum. Bypass or 3-way valves to maintain min flow. Manifold the pumps to disassociate

OPTIONS TO REVERSE RETURN

BRANCH DP CONTROLLERS

AUTO FLOW VALVES

PRESSURE INDEPENDENT CONTROL VALVES

8

Page 9: Back to Basics: Pumping Systems...VARIABLE PRIMARY Variable flow through chiller/boiler – to a minimum. Bypass or 3-way valves to maintain min flow. Manifold the pumps to disassociate

VARIABLE PRIMARY

Variable flow through chiller/boiler – to a minimum. Bypass or 3-way valves to maintain min flow.

Manifold the pumps to disassociate pump flow from chiller/boiler staging and provide easy redundancy

Select chillers to allow both higher AND lower than normal flows

9

Page 10: Back to Basics: Pumping Systems...VARIABLE PRIMARY Variable flow through chiller/boiler – to a minimum. Bypass or 3-way valves to maintain min flow. Manifold the pumps to disassociate

PRIMARY SECONDARY - SYSTEM

Independent loops, not affected by each other

Integrates different source and load needs

Based on minimal pressure drop at decoupler

SOURCE LOAD

10

Page 11: Back to Basics: Pumping Systems...VARIABLE PRIMARY Variable flow through chiller/boiler – to a minimum. Bypass or 3-way valves to maintain min flow. Manifold the pumps to disassociate

PRIMARY SECONDARY - SYSTEM

Design load

Lots of pumps – redundancy adds even more

11

Page 12: Back to Basics: Pumping Systems...VARIABLE PRIMARY Variable flow through chiller/boiler – to a minimum. Bypass or 3-way valves to maintain min flow. Manifold the pumps to disassociate

PRIMARY SECONDARY - SYSTEM

Part load - stage chillers and pumps to keep source flow greater than load flow

Low DT syndrome forces multiple chillers to run even at plant load less than 1 chiller’s capacity.

Pump energy 12

Page 13: Back to Basics: Pumping Systems...VARIABLE PRIMARY Variable flow through chiller/boiler – to a minimum. Bypass or 3-way valves to maintain min flow. Manifold the pumps to disassociate

PRIMARY SECONDARY @ LOAD

Energy must balance

Can set up for variable or constant source flow/DT

Can set up for variable or constant load flow/DT

High source DT, low load DT

Different load supply temp than source supply temp

LOAD

SOURCE

13

Page 14: Back to Basics: Pumping Systems...VARIABLE PRIMARY Variable flow through chiller/boiler – to a minimum. Bypass or 3-way valves to maintain min flow. Manifold the pumps to disassociate

PRIMARY SECONDARY @ LOAD

Constant flow to load Load capacity changed via supply water temp Excellent for AHU preheat, 100% OA, or DOAS coil

Avoids oversizing Helps destratification Freeze protection

14

Page 15: Back to Basics: Pumping Systems...VARIABLE PRIMARY Variable flow through chiller/boiler – to a minimum. Bypass or 3-way valves to maintain min flow. Manifold the pumps to disassociate

DISTRIBUTED PRIMARY SECONDARY

Total pump HP is less than a single source pump

Very small systems – cycle/modulate zone pumps

Very large systems – Each zone is a building

15

Page 16: Back to Basics: Pumping Systems...VARIABLE PRIMARY Variable flow through chiller/boiler – to a minimum. Bypass or 3-way valves to maintain min flow. Manifold the pumps to disassociate

DISTRIBUTED PRIMARY SECONDARY

Total pump HP is less than a single source pump

Very small systems – cycle/modulate zone pumps

Very large systems – Each zone is a building

16

Page 17: Back to Basics: Pumping Systems...VARIABLE PRIMARY Variable flow through chiller/boiler – to a minimum. Bypass or 3-way valves to maintain min flow. Manifold the pumps to disassociate

Miscellaneous Pipe Layouts Single pipe loops

Old school baseboard Water source heat pumps Process cooling

Two pipe changeover Either heat or cool through same piping, and usually same coils

as well. Changeover decision Source equipment changeover

Three pipe systems Literally “old school” (was common in unit ventilator systems in

schools). Also high rise terminal systems. Huge energy waste just to save a pipe.

17

Page 18: Back to Basics: Pumping Systems...VARIABLE PRIMARY Variable flow through chiller/boiler – to a minimum. Bypass or 3-way valves to maintain min flow. Manifold the pumps to disassociate

18

Expansion Tanks

To limit the maximum pressure at weakest system component

Maintain a minimum pressure to eliminate cavitation and boiling

Provide a reference pressure (analogous to an electrical ground)

Page 19: Back to Basics: Pumping Systems...VARIABLE PRIMARY Variable flow through chiller/boiler – to a minimum. Bypass or 3-way valves to maintain min flow. Manifold the pumps to disassociate

19

Expansion Tanks

Point of no pressure change

Reference pressure for automatic fill

Isolates pump head from sensitive components

Page 20: Back to Basics: Pumping Systems...VARIABLE PRIMARY Variable flow through chiller/boiler – to a minimum. Bypass or 3-way valves to maintain min flow. Manifold the pumps to disassociate

20

Expansion Tanks

Page 21: Back to Basics: Pumping Systems...VARIABLE PRIMARY Variable flow through chiller/boiler – to a minimum. Bypass or 3-way valves to maintain min flow. Manifold the pumps to disassociate

21

Expansion Tanks

•Usually at suction of pump, downstream of generating equipment

•Only one tank per system

•Primary secondary

•Campus

•Additions

Page 22: Back to Basics: Pumping Systems...VARIABLE PRIMARY Variable flow through chiller/boiler – to a minimum. Bypass or 3-way valves to maintain min flow. Manifold the pumps to disassociate

22

Expansion Tank Sizing

Information needed: Vs=Volume of system

dL=Density of fluid at lower temperature

dH=Density of fluid at higher temperature

α=Expansion coefficient of pipe

ΔT=expected fluid temp range

Pa=Atmospheric pressure

PL=Minimum allowable pressure at tank = fill pressure

PH=Maximum allowable pressure at tank

Link to form

Page 23: Back to Basics: Pumping Systems...VARIABLE PRIMARY Variable flow through chiller/boiler – to a minimum. Bypass or 3-way valves to maintain min flow. Manifold the pumps to disassociate

23

Expansion Tank Sizing

Closed (plain steel) tank:

Vt=Vs[(dL/dH-1)-3αΔT] / [(Pa/PL)-(Pa/PH)]

Diaphragm/Bladder Tank:

Vt=Vs [(dL/dH-1)-3αΔT] / [1-(PL/PH)]

Precharge pressure equals PL

Total expanded volume (upper term) must not exceed “acceptance volume”

All pressures are absolute (atm + gauge)

MUST SPECIFY FILL/PRECHARGE (PL)

Page 24: Back to Basics: Pumping Systems...VARIABLE PRIMARY Variable flow through chiller/boiler – to a minimum. Bypass or 3-way valves to maintain min flow. Manifold the pumps to disassociate

24

Expansion Tank Sizing

Page 25: Back to Basics: Pumping Systems...VARIABLE PRIMARY Variable flow through chiller/boiler – to a minimum. Bypass or 3-way valves to maintain min flow. Manifold the pumps to disassociate

25

Expansion Tank Sizing

Effect of Glycol:

Expansion of plain water, 40o-180o

dL/dH-1 62.42/60.57 – 1 = .0305

Expansion of 30% Prop. Glycol, 40o-180o

dL/dH-1 64.47/61.92 – 1 = .0401

Glycol expands 1.35 times as much as water

Page 26: Back to Basics: Pumping Systems...VARIABLE PRIMARY Variable flow through chiller/boiler – to a minimum. Bypass or 3-way valves to maintain min flow. Manifold the pumps to disassociate

26

Diaphragm Type Tank

Bladder Type Tank

Page 27: Back to Basics: Pumping Systems...VARIABLE PRIMARY Variable flow through chiller/boiler – to a minimum. Bypass or 3-way valves to maintain min flow. Manifold the pumps to disassociate

27

Diaphragm Type Tank

Page 28: Back to Basics: Pumping Systems...VARIABLE PRIMARY Variable flow through chiller/boiler – to a minimum. Bypass or 3-way valves to maintain min flow. Manifold the pumps to disassociate

28

Bladder Type Tank

Page 29: Back to Basics: Pumping Systems...VARIABLE PRIMARY Variable flow through chiller/boiler – to a minimum. Bypass or 3-way valves to maintain min flow. Manifold the pumps to disassociate

29

Expansion Tank Sizing

Effect of location in building –Mechanical room at

bottom of building.

Page 30: Back to Basics: Pumping Systems...VARIABLE PRIMARY Variable flow through chiller/boiler – to a minimum. Bypass or 3-way valves to maintain min flow. Manifold the pumps to disassociate

30

Expansion Tank Sizing

Mechanical room on top

Page 31: Back to Basics: Pumping Systems...VARIABLE PRIMARY Variable flow through chiller/boiler – to a minimum. Bypass or 3-way valves to maintain min flow. Manifold the pumps to disassociate

ENERGY ASPECTS OF PUMPS

Always a parasitic loss in HVAC

Not doing the heat transfer, just getting it there.

Better than air

Water has a much higher energy density

BHP = (GPM*Ft. Head)/(3960*Pump Efficiency)

BTU/H =(GPM*500*DT) – Glycol affects the 500

31

GPM FACTOR

30% 40% 50%

40 DEG 484 469 444

180 DEG 446 434 423

Page 32: Back to Basics: Pumping Systems...VARIABLE PRIMARY Variable flow through chiller/boiler – to a minimum. Bypass or 3-way valves to maintain min flow. Manifold the pumps to disassociate

32

Pump/Pipe Sizing Corrections - Glycol

Page 33: Back to Basics: Pumping Systems...VARIABLE PRIMARY Variable flow through chiller/boiler – to a minimum. Bypass or 3-way valves to maintain min flow. Manifold the pumps to disassociate

33

Pump Selection

•System curve

•Best efficiency point

•Max impeller size

•Non-overloading

•VFD, constant, or ride the curve

•Future operation

•NPSH

Page 34: Back to Basics: Pumping Systems...VARIABLE PRIMARY Variable flow through chiller/boiler – to a minimum. Bypass or 3-way valves to maintain min flow. Manifold the pumps to disassociate

PUMP SELECTION

IMPELLER – VOLUTE ARRANGMENT

34

TRIMMING IMPELLER CAUSES RECIRCULATION WITHIN THE VOLUTE, REDUCING EFFICIENCY.

OPERATING TO THE RIGHT SIDE OF CURVE CAUSES HYDRODYNAMIC STALL – UNPREDICTABLE

LOW NPSH CAUSES LOCALIZED PRESSURE BELOW VAPOR PRESSURE OF FLUID

Page 35: Back to Basics: Pumping Systems...VARIABLE PRIMARY Variable flow through chiller/boiler – to a minimum. Bypass or 3-way valves to maintain min flow. Manifold the pumps to disassociate

35

Pump Selection

•Usually only an issue with hot/open systems or suction lift. •All pressures absolute (ATM + gauge)

•Vapor pressure •90o - .7 psi •180o – 7.5 psi •200o – 11.5 psi

Page 36: Back to Basics: Pumping Systems...VARIABLE PRIMARY Variable flow through chiller/boiler – to a minimum. Bypass or 3-way valves to maintain min flow. Manifold the pumps to disassociate

36

Pump Selection

NPSHA Examples

Condensate Return ( 200o atmospheric tank)

hp = 12 psia = 27.7ft hz = 4 ft

hvpa = 11.5 psia = 26.5 ft hf = 2 ft

27.7 + 4 - 26.5 - 2 = 3.2 ft

Page 37: Back to Basics: Pumping Systems...VARIABLE PRIMARY Variable flow through chiller/boiler – to a minimum. Bypass or 3-way valves to maintain min flow. Manifold the pumps to disassociate

37

Pump Selection

NPSHA Examples

Cooling Tower

hp = 12 psia = 27.7ft hz = 4 ft

hvpa = .7 psia = 1.6 ft hf = 5 ft

27.7 + 4 - 1.6 - 5 = 25.1 ft

Page 38: Back to Basics: Pumping Systems...VARIABLE PRIMARY Variable flow through chiller/boiler – to a minimum. Bypass or 3-way valves to maintain min flow. Manifold the pumps to disassociate

38

Cavitation Example

Page 39: Back to Basics: Pumping Systems...VARIABLE PRIMARY Variable flow through chiller/boiler – to a minimum. Bypass or 3-way valves to maintain min flow. Manifold the pumps to disassociate

39

Cavitation Example

Wort Cavitation

Page 40: Back to Basics: Pumping Systems...VARIABLE PRIMARY Variable flow through chiller/boiler – to a minimum. Bypass or 3-way valves to maintain min flow. Manifold the pumps to disassociate

40

Pump Selection Flat – “Riding the curve” variable volume Steep – VFD variable volume and constant volume

Page 41: Back to Basics: Pumping Systems...VARIABLE PRIMARY Variable flow through chiller/boiler – to a minimum. Bypass or 3-way valves to maintain min flow. Manifold the pumps to disassociate

41

Pump Selection

•Flattens curve (start with steep curve pumps) •Provides 70% - 80% back-up. •Check single pump operation for overloading and right end of curve operation •Use two similar pumps

Page 42: Back to Basics: Pumping Systems...VARIABLE PRIMARY Variable flow through chiller/boiler – to a minimum. Bypass or 3-way valves to maintain min flow. Manifold the pumps to disassociate

42

Pump Selection

Page 43: Back to Basics: Pumping Systems...VARIABLE PRIMARY Variable flow through chiller/boiler – to a minimum. Bypass or 3-way valves to maintain min flow. Manifold the pumps to disassociate

STUFF

Open systems

Static head

Remote sump cooling tower

NPSH

Don’t pump air

For cooling towers, “pumping gravel” sound is probably air, not cavitation.

43

Page 44: Back to Basics: Pumping Systems...VARIABLE PRIMARY Variable flow through chiller/boiler – to a minimum. Bypass or 3-way valves to maintain min flow. Manifold the pumps to disassociate

STUFF

Variable Speed Pumping in Constant Volume or Pressure applications Use of VSP as throttling valve or control valve Pressure is maintained by impeller speed, so if pressure at pump

needs to stay constant regardless of flow, may not be much advantage to VSP. Steep vs flat curves

Domestic Water Booster If dominated by friction rather than lift, VFD is appropriate.

Steam Boiler Feed Meet pressure relief setting per code at max speed, operate at

lower speed to meet operating pressure.

Remote sump cooling tower

44

Page 45: Back to Basics: Pumping Systems...VARIABLE PRIMARY Variable flow through chiller/boiler – to a minimum. Bypass or 3-way valves to maintain min flow. Manifold the pumps to disassociate

VFD WITH CONSTANT HEAD

45

Page 46: Back to Basics: Pumping Systems...VARIABLE PRIMARY Variable flow through chiller/boiler – to a minimum. Bypass or 3-way valves to maintain min flow. Manifold the pumps to disassociate

FURTHER INFORMATION

Manufacturer info (particularly high efficiency equipment)

ASHRAE PDS

GOOGLE

46