BACnet Node for WRS-2224 Scanner Interface type: MSTP over RS-485 WBI-2671 www.DouglasLightingControls.com CAUTION: Disconnect 24V of WRS-2224 BEFORE plug/unpluging this unit RS-485-VCC Connection lighting controls lighting controls 485 - 485 + ON OFF RS-485 Address Select 1 2 4 8 16 32 64 128 Status LED Start-up: 2 blinks then solid for 2sec Run time: blinking = OK, solid = problem Sum of switches set ON equals the unit's address 76,800 38,400 19,200 9,600 Baud Rate Setting V# - This node does not have a built-in end of the line termination resistor. Installer's responsibility to correctly terminate the RS-485 data bus. - Transmission Baud Rate is selectable, select appropriate baud rate for the system this node is installed to. - For information regarding BACnet object types supported, refer to product cutsheet available at Douglas web site. Transmit Receive VCC 1 2 Technical Data C-4-3,4,5,6 -System Integration, BACnet Interfaces 4.3 www.DouglasLightingControls.com WBI-2671 BACnet ® Node for Douglas Scanner The WBI-2671 is a BACnet MSTP device that allows Douglas WRS-2224 Relay Scanners to send and receive BACnet commands to or from a BAS. The WBI-2671 Node uses RS-485 networking technology that uses native BACnet MSTP protocol. Building Management Systems can configure and program from their database all of the functions inherent in the WBI-2671 and the WRS-2224. The WBI-2671 conforms to the open native BACnet variables for lighting. The WBI-2671 allows programming, control and monitoring of 5 groups. The WBI-2671 allows control and monitoring of 24 relays individually. The WBI-2671 allows control and monitoring of 5 switch inputs. The WBI-2671 allows programming, either from the WRS-2224 or the Network, of a 2- hour Time Out or a 5-minute Flick Warn. Plan View Side View 6.5" (165) 4.0" (103) 1.75" (45) 3 5 7 9 11 1 14 16 18 20 22 24 13 15 17 19 21 23 2 4 6 8 10 12 ON OVERRIDE OFF OVERRIDE SELECT MASTER SWITCH NORMAL MODE OPTIONS PROGRAM MODE WRS-2224 Relay Scanner 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 W B Sw Inputs 1 2 3 B 4 5 B Be sure to disconnect 24VAC from relay scanner before plugging or unplugging network node to scanner. Mount node to 35mm DIN rail installed in Douglas relay panel. 2.5" (64) Power The WBI-2671 Node obtains power from the host WRS-2224 Relay Scanner. CAUTION: Always disconnect 24VAC from the WRS-2224 Scanner prior to plugging/unplugging the WBI-2671 unit. Wire Type & Method WBI-2671 Nodes are connected together using a shielded single twisted pair cable in a serial loop. Conform to wiring specifications issued by the host Building Management System. Networking Technology Specification Network signal: RS-485 Transceiver. MSTP Protocol. 100K Ohm bias (120 Ohm termination recommended). BACnet Spec 9.2.2 compliant. .Up to 32 devices per segment. Baud Rates (selectable) 9,600 Baud. . d u a B 0 0 2 , 19 38,400 Baud. 76,800 Baud. Environment Environment: Indoors, stationary, non- vibrating, non-corrosive atmosphere and non-condensing humidity. Ambient temp: - 0° to +120°F (-15° to +50°C). Directions Programming directions are printed on keypad for handy user reference. Individual Output Buttons In operating mode, use buttons to switch the connected relay ON or OFF. In programming mode, use buttons to enter or remove the relay from the switch input being programmed. Override Buttons Use ON and OFF override buttons to switch relay groups. Relay Group Select Use the Input Select button to choose the relay group input 1, 2, 3, 4 or 5. The selected input will have its indicator LED ON. Inputs are momentary or maintained Douglas switches Relay Outputs 24 output terminals (12 per side) are provided for relay control. Douglas 2-wire switches can be connected in parallel to permit individual control of a relay by a switch. Select Buttons & LED's for: 1) Operating mode. 2) Program mode. 3) Flick Warn, Time Out and Flick Warn with Time Out options. PART No. SPECIFICATION DESCRIPTION DIMENSIONS & MOUNTING WBI-2671 MAC Address Select Use the binary DIP switch to set the MAC Address (0-255). Baud Rate Select Use the binary DIP switch to set the Baud Rate: -9,600 (both up) -19,200 (#1 up) -38,400 (#2 up) -76,800 (both down) WBI-2671 Node Data Signal RS-485 Transceiver GND

Upload: others

Post on 13-Mar-2020

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: BACnet Node for Douglas Scanner WBI-2671 Technical Data · 2017-10-19 · Management Control Systems that use BACnet technology. It is assumed that the BMS supports standard BACnet

BACnet Node for WRS-2224 ScannerInterface type: MSTP over RS-485 WBI-2671

www.DouglasLightingControls.com

CAUTION: Disconnect 24V of WRS-2224BEFORE plug/unpluging this unit

RS-485-VCC Connection

lighting controlslighting controls

485

-

485

+

ON

OFF

RS-485 Address Select

1248163264128

Status LEDStart-up: 2 blinks then solid for 2secRun time: blinking = OK, solid = problem

Sum of switches set ONequals the unit's address

76,80038,40019,2009,600

Baud Rate Setting

V#

- This node does not have a built-in end of the line termination resistor. Installer's responsibility to correctly terminate the RS-485 data bus.

- Transmission Baud Rate is selectable, select appropriate baud rate for the system this node is installed to.

- For information regarding BACnet object types supported, refer to product cutsheet available at Douglas web site.

Transmit Receive

VCC

1 2

Technical Data

C-4-3,4,5,6 -System Integration, BACnet

Interfaces 4.3 www.DouglasLightingControls.com

WBI-2671BACnet® Node for Douglas Scanner

The WBI-2671 is a BACnet MSTP device that allows Douglas WRS-2224 Relay Scanners to send and receive BACnet commands to or from a BAS.

The WBI-2671 Node uses RS-485 networking technology that uses native BACnet MSTP protocol.

Building Management Systems can configure and program from their database all of the functions inherent in the WBI-2671 and the WRS-2224.

The WBI-2671 conforms to the open native BACnet variables for lighting.

The WBI-2671 allows programming, control and monitoring of 5 groups.

The WBI-2671 allows control and monitoring of 24 relays individually.

The WBI-2671 allows control and monitoring of 5 switch inputs.

The WBI-2671 allows programming, either from the WRS-2224 or the Network, of a 2-hour Time Out or a 5-minute Flick Warn.

Plan ViewSideView

6.5"(165)

4.0"(103)

1.75"(45)

3

5

7

9

11

114

16

18

20

22

24

13

15

17

19

21

23

2

4

6

8

10

12

ONOVERRIDE

OFFOVERRIDE

SELECTMASTERSWITCH

NORMALMODE

OPTIONS PROGRAMMODE

WRS-2224RelayScanner

123456789101112

131415161718192021222324WB

SwInputs

123B45B

Be sure to disconnect 24VAC from relay scanner before plugging or unplugging network node to scanner.

Mount node to 35mm DIN rail installed in Douglas relay panel.

2.5"(64)

Power The WBI-2671 Node obtains power from the host WRS-2224 Relay Scanner.

CAUTION: Always disconnect 24VAC from the WRS-2224 Scanner prior to plugging/unplugging the WBI-2671 unit.

Wire Type & Method WBI-2671 Nodes are connected together using a shielded single twisted pair cable in a serial loop.

Conform to wiring specifications issued by the host Building Management System.

Networking Technology Specification Network signal:

RS-485 Transceiver. MSTP Protocol.100K Ohm bias (120 Ohm termination recommended).BACnet Spec 9.2.2 compliant..Up to 32 devices per segment.

Baud Rates (selectable) 9,600 Baud.

.duaB 002,19 38,400 Baud. 76,800 Baud.

Environment Environment: Indoors, stationary, non-vibrating, non-corrosive atmosphere and non-condensing humidity.

Ambient temp: -0° to +120°F (-15° to +50°C).

DirectionsProgramming directions are printed on keypad for handy user reference.

Individual OutputButtonsIn operating mode, use buttons to switch the connected relay ON or OFF.In programming mode, use buttons to enter or remove the relay from the switch input being programmed.

Override ButtonsUse ON and OFF override buttons to switch relay groups.

Relay Group SelectUse the Input Select button to choose the relay group input 1, 2, 3, 4 or 5.

The selected input will have its indicator LED ON.

Inputs are momentary or maintained Douglas switches

Relay Outputs24 output terminals (12 per side) are provided for relay control.

Douglas 2-wire switches can be connected in parallel to permit individual control of a relay by a switch.

Select Buttons& LED's for:1) Operating mode.2) Program mode.3) Flick Warn, Time Out

and Flick Warn with Time Out options.

PART No. SPECIFICATIONDESCRIPTION

DIMENSIONS & MOUNTING

WBI-2671

MAC Address SelectUse the binary DIP switch to set the MAC Address (0-255).

Baud Rate SelectUse the binary DIP switch to set the Baud Rate:-9,600 (both up)-19,200 (#1 up)-38,400 (#2 up)-76,800 (both down)

WBI-2671NodeData Signal

RS-485 Transceiver

GND

Page 2: BACnet Node for Douglas Scanner WBI-2671 Technical Data · 2017-10-19 · Management Control Systems that use BACnet technology. It is assumed that the BMS supports standard BACnet

EXTERNALLY CONFIGURED NETWORKS

Integrated Systems Douglas Relay Panels can be incorporated into Building

Management Control Systems that use BACnet technology. It is assumed that the BMS supports standard BACnet objects that can be used for lighting control.

The WBI-2671 Node plugs into the WRS-2224 Relay Scanner and is connected to the BACnet network.

Individual relay and groups status indicators are available on the keypad on the attached relay scanner.

Individual relay and group momentary overrides are available on the keypad on the attached relay scanner.

MAC Address and ConfigurationThe MAC Address (0-255 address range) for each WBI-2671 is set using the binary DIP switch on the WBI-2671 unit.

Transformer

BW 24VAC

Relays

3

5

7

9

11

114

16

18

20

22

24

13

15

17

19

21

23

2

4

6

8

10

12

ONOVERRIDE

OFFOVERRIDE

INPUTSELECT

NORMALMODEOPTIONS PROGRAM

MODE

123456789101112

131415161718192021222324WB

123B45B

MasterInputs

WRS-2224RelayScanner

Relays Node/Scanner Combo

CONNECTIONS OBJECT TYPES

Connect directlyto relays

LocalSwitches

Data SignalRS-485 Transceiver

StandardDouglas SwitchesMotion Control

Group SwitchInputs

WBI-2671Node

This information is provided for System Integrators who areconfiguring this device into an HVAC system.

Object TypeMulti-state input to check relay status (0 = absent, 1 = ON, 2 = OFF, 3 = defective)

Multi-state input to check device status

Multi-state input to check group programs

Multi-state input to check input configurations

Multi-state input to check to check Flick and Time Out status

Binary input to monitor group status (ON or OFF)

Binary input to monitor switch status (ON or OFF)

Binary input to monitor Flick status (Flick ON or OFF)

Multi-state output for for programming groups, switches and Flick

Binary output (read/write) for individual relay control (ON or OFF)

Binary output (read/write) for group control (ON or OFF)

Binary output (read/write) for group status control (ON or OFF)

Binary output (read/write) for Flick control (ON or OFF)

ObjectsMI0 - MI23

MI24

MI25 - MI29

MI30 - MI34

MI35 - MI39

BI0 - BI4

BI5 - BI9

BI10 - BI14

MV0 - MV4

BV0 - BV23

BV24 - BV28

BV29 - BV33

BV34 - BV38

WBI-2671 FUNCTIONS & FEATURES Activates a group (one command per group).

Reads the group status (one command per group).

Activates relays (one command per relay).

Reads 'enhanced' group status (one command per relay: 0 = Absent, 1 = ON, 2 = OFF, 3 = Defective).

Activates a group switch (changes the state, one command per switch).

Reads a group switch (monitors the state, one command per switch).

Reads the module status (version numbers and address).

Provides remote programming of the five scanner resident groups (including Flick Warn, Time Out and Flick Warn with Timeout options).

Querys programming of the five scanner resident groups (including Flick Warn, Time Out and Flick Warn with Time Out options).

Provides local programming of the five scanner resident groups (by the keypad on the attached scanner).

Technical Data

C-4-3,4,5,6 -System Integration, BACnet

www.DouglasLightingControls.comInterfaces 4.4

WBI-2671BACnet® Node for Douglas Scanner

Quantity 24

1

5

5

5

5

5

5

5

24

5

5

5

The Device ID for each WBI-2671 is set using a variable accessible via the BACnet MSTP port.