1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31 s Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) Basic documentation CM110665en_10 2015-07-31 Building Technologies

Upload: nguyendung

Post on 10-Mar-2018

238 views

Category:

Documents


4 download

TRANSCRIPT

Page 1: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

1/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

s

Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) Basic documentation

CM110665en_10 2015-07-31

Building Technologies

Page 2: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

2/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Contents

1 Desigo PX Automation Station .................................................................. 3

2 Desigo PXC3 and DXR2 Automation Stations ........................................ 33

3 Desigo CC Workstation ............................................................................ 59

4 Desigo Insight Workstation ...................................................................... 68

5 Desigo PXM20 Operator Unit ................................................................... 77

6 Desigo PXG3.M BACnet Router ............................................................... 88

7 Desigo PXG3.L BACnet Router ................................................................ 97

8 SX Open ................................................................................................... 105

Page 3: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

3/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

1 Desigo PX Automation Station

Date : Vendor name : Siemens Building Technologies (Vendor ID 7) Product name : Desigo PX automation station Product model number : PX… (see table below) BACnet protocol version : 1.12 Application software version – Firmware revision : FW=V6

1.1 Product model number

The Desigo PX automation station is a range of products based on the same software. The PICS are the same for all products listed below. The simultaneously supported Data Link Layers of a product are different and also listed.

Product Description Data Link Layer PXC00.D Modular automation station LON PXC00-E.D Modular automation station IP PXC50.D Modular automation station LON PXC50-E.D Modular automation station IP PXC100.D Modular automation station LON PXC100-E.D Modular automation station IP PXC200.D Modular automation station LON PXC200-E.D Modular automation station IP PXC12.D Compact automation station LON PXC12-E.D Compact automation station IP PXC12-T.D Compact automation station LON, PTP PXC22.D Compact automation station LON PXC22-E.D Compact automation station IP PXC22-T.D Compact automation station LON, PTP PXC36.D Compact automation station LON PXC36-E.D Compact automation station IP PXC36-T.D Compact automation station LON, PTP PXC52 Compact automation station LON PXC-NRUF Compact automation station LON PXC00-U Modular automation station LON/IP1), PTP2) PXC64-U Modular automation station LON/IP1), PTP2) PXC128-U Modular automation station LON/IP1), PTP2) PXC001.D Compact automation station LON PXC001-E.D Compact automation station IP 1) Only LON or IP possible; depends on configuration and extension modules. 2) Additional PTP for half-router function possible; depends on configuration and extension modules.

Page 4: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

4/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

1.2 Product description

The Desigo PXC is a freely configurable process unit with focus on HVAC. The process unit as a system platform can be used in the Desigo product range as a stand-alone or network device with BACnet communication.

1.3 BACnet standardized device profile (Annex L)

BACnet Advanced Workstation (B-AWS)

BACnet Operator Workstation (B-OWS)

BACnet Operator Display (B-OD)

BACnet Building Controller (B-BC)

BACnet Advanced Application Controller (B-AAC)

BACnet Application Specific Controller (B-ASC)

BACnet Smart Sensor (B-SS)

BACnet Smart Actuator (B-SA)

Page 5: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

5/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

1.4 BACnet interoperability building blocks supported (Annex K)

Data Sharing – Read Property-A DS-RP-A

Data Sharing – Read Property-B DS-RP-B

Data Sharing – Read Property Multiple-A DS-RPM-A

Data Sharing – Read Property Multiple-B DS-RPM-B

Data Sharing – Write Property-A DS-WP-A

Data Sharing – Write Property-B DS-WP-B

Data Sharing – Write Property Multiple-A DS-WPM-A

Data Sharing – Write Property Multiple-B DS-WPM-B

Data Sharing – Change of Value -A DS-COV-A

Data Sharing – Change of Value -B DS-COV-B

Data Sharing – Change of Value Property -A DS-COVP-A

Data Sharing – Change of Value Property -B DS-COVP-B

Data Sharing – Change of Value-Unsolicited-A DS-COVU-A

Data Sharing – Change of Value-Unsolicited-B DS-COVU-B

Data Sharing – View-A DS-V-A

Data Sharing – Advanced View-A DS-AV-A

Data Sharing – Modify-A DS-M-A

Data Sharing – Advanced Modify-A DS-AM-A

Alarm and Event – Notification-A AE-N-A

Alarm and Event – Notification Internal-B AE-N-I-B

Alarm and Event – Notification External-B AE-N-E-B

Alarm and Event – ACK-A AE-ACK-A

Alarm and Event – ACK-B AE-ACK-B

Alarm and Event – Alarm Summary-B AE-ASUM-B

Alarm and Event – Enrollment Summary-B AE-ESUM-B

Alarm and Event – Information-B AE-INFO-B

Alarm and Event – Life Safety-A AE-LS-A

Alarm and Event – Life Safety-B AE-LS-B

Alarm and Event – View Notifications-A AE-VN-A

Alarm and Event – Advanced View Notifications-A AE-AVN-A

Alarm and Event – View and Modify-A AE-VM-A

Alarm and Event – Advanced View and Modify-A AE-AVM-A

Alarm and Event – Alarm Summary View-A AE-AS-A

Alarm and Event – Event Log View-A AE-ELV-A

Alarm and Event – Event Log View and Modify-A AE-ELVM-A

Alarm and Event – Event Log Internal-B AE-EL-I-B

Alarm and Event – Event Log External-B AE-EL-E-B

Data sharing

Alarm and event management

Page 6: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

6/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Historical/Deprecated BIBBs Alarm and Event – Alarm Summary-A AE-ASUM-A

Alarm and Event – Enrollment Summary-A AE-ESUM-A

Alarm and Event – Information-A AE-INFO-A

Scheduling – Internal-B SCHED-I-B

Scheduling – External-B SCHED-E-B

Scheduling – Advanced View Modify-A SCHED-AVM-A

Scheduling – View Modify-A SCHED-VM-A

Scheduling – Weekly Schedule-A SCHED-WS-A

Scheduling – Weekly Schedule Internal-B SCHED-WS-I-B

Scheduling – Readable-B SCHED-R-B

Historical/Deprecated BIBBs Scheduling – A SCHED-A

Trending – Viewing and Modifying Trends-A T-VMT-A

Trending – Viewing and Modifying Internal-B T-VMT-I-B

Trending – Viewing and Modifying External-B T-VMT-E-B

Trending – Viewing and Modifying Multiple Values-A T-VMMV-A

Trending – Viewing and Modifying Multiple Values Internal-B T-VMMV-I-B

Trending – Viewing and Modifying Multiple Values External -B T-VMMV-E-B

Trending – Automated Multiple Value Retrieval-A T-AMVR-A

Trending – Automated Multiple Value Retrieval-B T-AMVR-B

Trending – View-A T-V-A

Trending – Advanced View and Modify-A T-AVM-A

Trending – Archival-A T-A-A

Trending – Automated Trend Retrieval-A T-ATR-A

Trending – Automated Trend Retrieval-B T-ATR-B

Historical/Deprecated BIBBs Trending – Viewing and Modifying Trends-A T-VMT-A

Trending – Viewing and Modifying Multiple Values-A T-VMMV-A

Device Management – Dynamic Device Binding-A DM-DDB-A

Device Management – Dynamic Device Binding-B DM-DDB-B

Device Management – Dynamic Object Binding-A DM-DOB-A

Device Management – Dynamic Object Binding-B DM-DOB-B

Device Management – Device Communication Control-A DM-DCC-A

Device Management – Device Communication Control-B DM-DCC-B

Device Management – Text Message-A DM-TM-A

Device Management – Text Message-B DM-TM-B

Device Management – Time Synchronization-A DM-TS-A

Device Management – Time Synchronization-B DM-TS-B

Device Management – UTC Time Synchronization-A DM-UTC-A

Device Management – UTC Time Synchronization-B DM-UTC-B

Alarm and event management

Scheduling

Trending

Device management

Page 7: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

7/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Device Management – Reinitialize Device-A DM-RD-A

Device Management – Reinitialize Device-B DM-RD-B

Device Management – Backup and Restore-A DM-BR-A

Device Management – Backup and Restore-B DM-BR-B

Device Management – Restart-A DM-R-A

Device Management – Restart-B DM-R-B

Device Management – List Manipulation-A DM-LM-A

Device Management – List Manipulation-B DM-LM-B

Device Management – Object Creation and Deletion-A DM-OCD-A

Device Management – Object Creation and Deletion-B DM-OCD-B

Device Management – Virtual Terminal-A DM-VT-A

Device Management – Virtual Terminal-B DM-VT-B

Device Management – Automatic Network Mapping-A DM-ANM-A

Device Management – Automatic Device Mapping-A DM-ADM-A

Device Management – Automatic Time Synchronization-A DM-ATS-A

Device Management – Manual Time Synchronization-A DM-MTS-A

Historical/Deprecated BIBBs Device Management – Private Transfer-A DM-PT-A

Device Management – Private Transfer-B DM-PT-B

Network Management – Connection Establishment-A NM-CE-A1)

Network Management – Connection Establishment-B NM-CE-B2)

Network Management – Router Configuration-A NM-RC-A

Network Management – Router Configuration-B NM-RC-B 1) establish connection only 2) if product supports PTP

Device management

Network management

Page 8: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

8/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

1.5 Standard object types supported

Object type Supported Can be created dynamically

Can be deleted dynamically

Analog Input Analog Output Analog Value Binary Input Binary Output Binary Value Calendar Command Device Event Enrollment File Group Loop Multi-State Input Multi-State Output Notification Class Program Schedule Averaging Multi-State Value Trend Log Life-Safety-Point Life-Safety-Zone Accumulator Pulse-Converter Event Log Global Group Trend Log Multiple Load Control Structured-View Access Door (unassigned) Access Credential Access Point Access Rights Access User Access Zone Credential Data Input Network Security Bitstring Value Characterstring Value

Page 9: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

9/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Object type Supported Can be created dynamically

Can be deleted dynamically

Date Pattern Value Date Value Datetime Pattern Value Datetime Value Integer Value Large Analog Value Octetstring Value Positive Integer Value Time Pattern Value Time Value

Page 10: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

10/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Notes on the specification of the following object types:

Writable properties are read only if they are under program control.

Variants of object types (different set of properties) are possible in the case of value objects (e.g. Analog Value). The variants are distinguished by the object tag. The object tag is listed as additional information in the EDE file.

Properties supported Readable/

Writable Range restrictions

Object_Identifier R Object_Name R Object_Type R Present_Value R Description W Device_Type R Status_Flags R Event_State R Reliability R Out_Of_Service W Update_Interval R Units R Min_Pres_Value R Max_Pres_Value R Resolution R COV_Increment W 0.000001...3.402822e+038 Time_Delay W 0…65535 Notification_Class W High_Limit W Low_Limit W Deadband W 0...maxReal Limit_Enable W Event_Enable W Acked_Transitions R Notify_Type W Event_Time_Stamps R Profile_Name R Event_Message_Texts R

Details

Analog Input

Page 11: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

11/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Properties supported Readable/ Writable

Range restrictions

Object_Identifier R Object_Name R Object_Type R Present_Value W Description W Device_Type R Status_Flags R Event_State R Reliability R Out_Of_Service W Units R Min_Pres_Value R Max_Pres_Value R Resolution R Priority_Array R Relinquish_Default W COV_Increment W 0.000001...3.402822e+038 Time_Delay W 0…65535 Notification_Class W High_Limit W Low_Limit W Deadband W 0...maxReal Limit_Enable W Event_Enable W Acked_Transitions R Notify_Type W Event_Time_Stamps R Profile_Name R Event_Message_Texts R

Analog Output

Page 12: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

12/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Properties supported Readable/ Writable

Range restrictions

Object_Identifier R Object_Name R Object_Type R Present_Value W Description W Status_Flags R Event_State R Reliability R Out_Of_Service W Units R Priority_Array R Relinquish_Default W COV_Increment W 0.000001...3.402822e+038 Time_Delay W 0…65535 Notification_Class W High_Limit W Low_Limit W Deadband W 0...maxReal Limit_Enable W Event_Enable W Acked_Transitions R Notify_Type W Event_Time_Stamps R Profile_Name R Event_Message_Texts R

Analog Value

Page 13: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

13/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Properties supported Readable/ Writable

Range restrictions

Object_Identifier R

Object_Name R

Object_Type R

Present_Value R

Description W

Device_Type R

Status_Flags R

Event_State R

Reliability R

Out_Of_Service W

Polarity W

Inactive_Text R

Active_Text R

Change_Of_State_Time R

Change_Of_State_Count W

Time_Of_State_Count_Reset R

Elapsed_Active_Time W

Time_Of_Active_Time_Reset R

Time_Delay W 0…65535

Notification_Class W

Alarm_Value W

Event_Enable W

Acked_Transitions R

Notify_Type W

Event_Time_Stamps R

Profile_Name R

Event_Message_Texts R

Binary Input

Page 14: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

14/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Properties supported Readable/ Writable

Range restrictions

Object_Identifier R

Object_Name R

Object_Type R

Present_Value W

Description W

Device_Type R

Status_Flags R

Event_State R

Reliability R

Out_Of_Service W

Polarity W

Inactive_Text R

Active_Text R

Change_Of_State_Time R

Change_Of_State_Count W

Time_Of_State_Count_Reset R

Elapsed_Active_Time W

Time_Of_Active_Time_Reset R

Minimum_Off_Time W 0…65535

Minimum_On_Time W 0…65535

Priority_Array R

Relinquish_Default W

Time_Delay W 0…65535

Notification_Class W

Feedback_Value R

Event_Enable W

Acked_Transitions R

Notify_Type W

Event_Time_Stamps R

Profile_Name R

Event_Message_Texts R

Binary Output

Page 15: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

15/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Properties supported Readable/ Writable

Range restrictions

Object_Identifier R

Object_Name R

Object_Type R

Present_Value W

Description W

Status_Flags R

Event_State R

Reliability R

Out_Of_Service W

Inactive_Text R

Active_Text R

Change_Of_State_Time R

Change_Of_State_Count W

Time_Of_State_Count_Reset R

Elapsed_Active_Time W

Time_Of_Active_Time_Reset R

Minimum_Off_Time W 0…65535

Minimum_On_Time W 0…65535

Priority_Array R

Relinquish_Default W

Time_Delay W 0…65535

Notification_Class W

Alarm_Value W

Event_Enable W

Acked_Transitions R

Notify_Type W

Event_Time_Stamps R

Profile_Name R

Event_Message_Texts R

Binary Value

Page 16: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

16/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Properties supported Readable/ Writable

Range restrictions

Object_Identifier R

Object_Name R

Object_Type R

Description W

Present_Value R

Date_List W Max. 30

Profile_Name R Properties supported Readable/

Writable Range restrictions

Object_Identifier R

Object_Name R

Object_Type R

Description W

Present_Value W 0…15

In_Process R

All_Writes_Successful R

Action R

Action_Text R

Profile_Name R

Calendar

Command

Page 17: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

17/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Properties supported Readable/ Writable

Range restrictions

Object_Identifier R

Object_Name R

Object_Type R

System_Status R

Vendor_Name R

Vendor_Identifier R

Model_Name R

Firmware_Revision R

Application_Software_Version R

Location R

Description W

Protocol_Version R

Protocol_Revision R

Protocol_Services_Supported R

Protocol_Object_Types_Supported R

Object_List R

Structured_Object_List R

Max_APDU_Length_Accepted R

Segmentation_Supported R

Max_Segments_Accepted R

VT_Classes_Supported

Active_VT_Sessions

Local_Time R

Local_Date R

UTC_Offset W -780…780

Daylight_Savings_Status R

APDU_Segment_Timeout R

APDU_Timeout R

Number_Of_APDU_Retries R

List_Of_Session_Keys

Time_Synchronization_Recipients W

Max_Master

Max_Info_Frames

Device_Address_Binding R

Database_Revision R

Configuration_Files R

Last_Restore_Time R

Backup_Failure_Timeout W 0...65535

Backup_Preparation_Time R

Restore_Preparation_Time R

Restore_Completion_Time R

Backup_And_Restore_State R

Active_COV_Subscriptions R

Slave_Proxy_Enable

Manual_Slave_Adress_Binding

Device

Page 18: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

18/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Properties supported Readable/ Writable

Range restrictions

Auto_Slave_Discovery

Slave_Address_Binding

Last_Restart_Reason R

Time_Of_Device_Restart R

Restart_Notification_Recipients W

UTC_Time_Synchronization_Recipients W

Time_Synchronization_Interval W

Align_Intervals W

Interval_Offset W

Profile_Name R

Properties supported Readable/ Writable

Range restrictions

Object_Identifier R

Object_Name R

Object_Type R

Description W

Event_Type R

Notify_Type W

Event_Parameters W

Object_Property_Reference W

Event_State R

Event_Enable W

Acked_Transitions R

Notification_Class W

Event_Time_Stamps R

Profile_Name R

Event_Message_Texts R Properties supported Readable/

Writable Range restrictions

Object_Identifier R

Object_Name R

Object_Type R

Description W

File_Type R

File_Size R

Modification_Date R

Archive W

Read_Only R

File_Access_Method R

Record_Count

Profile_Name R

Event Enrollment

File

Page 19: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

19/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Properties supported Readable/ Writable

Range restrictions

Object_Identifier R

Object_Name R

Object_Type R

Present_Value R

Description W

Status_Flags R

Event_State R

Reliability R

Out_Of_Service W

Update_Interval R

Output_Units R

Manipulated_Variable_Reference R

Controlled_Variable_Reference R

Controlled_Variable_Value R

Controlled_Variable_Units R

Setpoint_Reference R

Setpoint W -50...150

Action W

Proportional_Constant W 0…3.402822e+038 / res.: 1

Proportional_Constant_Units R

Integral_Constant W 0…65535 / res.: 1

Integral_Constant_Units R

Derivative_Constant W 0…65535 / res.: 1

Derivative_Constant_Units R

Bias W -50...150

Maximum_Output W 50...150

Minimum_Output W 50...150

Priority_For_Writing R

COV_Increment W 0.000001...3.402822e+038

Time_Delay W 0…65535

Notification_Class W

Error_Limit W

Deadband W 0…(Error_Limit / 2)

Event_Enable W

Acked_Transitions R

Notify_Type W

Event_Time_Stamps R

Profile_Name R

Event_Message_Texts R

Loop

Page 20: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

20/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Properties supported Readable/ Writable

Range restrictions

Object_Identifier R

Object_Name R

Object_Type R

Present_Value R

Description W

Device_Type R

Status_Flags R

Event_State R

Reliability R

Out_Of_Service W

Number_Of_States R

State_Text R

Time_Delay W 0...65535

Notification_Class W

Alarm_Values W Max. 16

Fault_Values R

Event_Enable W

Acked_Transitions R

Notify_Type W

Event_Time_Stamps R

Profile_Name R

Event_Message_Texts R

Multistate Input

Page 21: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

21/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Properties supported Readable/ Writable

Range restrictions

Object_Identifier R

Object_Name R

Object_Type R

Present_Value W 1…Number_Of_States

Description W

Device_Type R

Status_Flags R

Event_State R

Reliability R

Out_Of_Service W

Number_Of_States R

State_Text R

Priority_Array R

Relinquish_Default W 1…Number_Of_States

Time_Delay W 0...65535

Notification_Class W

Feedback_Value R

Event_Enable W

Acked_Transitions R

Notify_Type W

Event_Time_Stamps R

Profile_Name R

Event_Message_Texts R

Multistate Output

Page 22: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

22/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Properties supported Readable/ Writable

Range restrictions

Object_Identifier R

Object_Name R

Object_Type R

Present_Value W 1…Number_Of_States

Description W

Status_Flags R

Event_State R

Reliability R

Out_Of_Service W

Number_Of_States R

State_Text R

Priority_Array R

Relinquish_Default W 1…Number_Of_States

Time_Delay W 0...65535

Notification_Class W

Alarm_Values W Max. 16

Fault_Values R

Event_Enable W

Acked_Transitions R

Notify_Type W

Event_Time_Stamps R

Profile_Name R

Event_Message_Texts R

Multistate Value

Page 23: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

23/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Properties supported Readable/ Writable

Range restrictions

Object_Identifier R

Object_Name R

Object_Type R

Description W

Notification_Class R

Priority W

Ack_Required W

Recipient_List W Max. 20

Profile_Name R

Properties supported Readable/ Writable

Range restrictions

Object_Identifier R

Object_Name R

Object_Type R

Present_Value R

Description W

Effective_Period W

Weekly_Schedule W Max. 10 per day

Exception_Schedule W Max. 20

Schedule_Default W

List_Of_Object_Property_References W

Priority_For_Writing W

Status_Flags R

Reliability R

Out_Of_Service W

Profile_Name R

Notification Class

Schedule

Page 24: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

24/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Properties supported Readable/ Writable

Range restrictions

Object_Identifier R Object_Name R Object_Type R Program_State R Program_Change W Reason_For_Halt R Description_Of_Halt R Program_Location R Description W Instance_Of R Status_Flags R Reliability R Out_Of_Service R Profile_Name R

Program

Page 25: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

25/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Properties supported Readable/ Writable

Range restrictions

Object_Identifier R Object_Name R Object_Type R Description W Enable W Start_Time W Stop_Time W Log_DeviceObjectProperty W Log_Interval W 0; 1 sec…720 h COV_Resubscription_Interval W 60…86400 Client_COV_Increment W 0…maxReal Stop_When_Full W Buffer_Size W 0…5000 Log_Buffer R Record_Count W 0…0 Total_Record_Count R Notification_Threshold W 0…5000 Records_Since_Notification R Last_Notify_Record R Event_State R Notification_Class W Event_Enable W Acked_Transitions R Notify_Type W Event_Time_Stamps R Profile_Name R Logging_Type W Align_Intervals W Interval_Offset W Trigger W Status_Flags R Reliability R Event_Message_Texts R

Trend Log

Page 26: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

26/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Properties supported Readable/ Writable

Range restrictions

Object_Identifier R Object_Name R Object_Type R Present_Value R Description R Device_Type R Status_Flags R Event_State R Reliability R Out_Of_Service W Scale W Units W Prescale W Max_Pres_Value R Value_Change_Time R Value_Before_Change R Value_Set W Logging_Record R Logging_Object R Pulse_Rate R High_Limit W Low_Limit W Limit_Monitoring_Interval W 0…65535 Notification_Class W Time_Delay W 0…65535 Limit_Enable W Event_Enable W Acked_Transitions R Notify_Type W Event_Time_Stamps R Event_Message_Texts R Profile_Name R

Accumulator

Page 27: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

27/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Properties supported Readable/ Writable

Range restrictions

Object_Identifier R Object_Name R Object_Type R Description W Present_Value R Input_Reference R Status_Flags R Event_State R Reliability R Out_Of_Service W Units R Scale_Factor W Adjust_Value W Count R Update_Time R Count_Change_Time R Count_Before_Change R COV_Increment W 0.000001...3.402822e+038 COV_Period W 0...65535 Notification_Class W Time_Delay W 0...65535 High_Limit W Low_Limit W Deadband W 0…maxReal Limit_Enable W Event_Enable W Acked_Transitions R Notify_Type W Event_Time_Stamps R Profile_Name R Event_Message_Texts R

Pulse-Converter

Page 28: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

28/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Properties supported Readable/ Writable

Range restrictions

Object_Identifier R

Object_Name R

Object_Type R

Description W

Status_Flags R

Event_State R

Reliability R

Enable W

Start_Time W

Stop_Time W

Stop_When_Full W

Buffer_Size W 0…120

Log_Buffer R

Record_Count W 0…0

Total_Record_Count R

Notification_Threshold W 0…120

Records_Since_Notification R

Last_Notify_Record R

Notification_Class W

Event_Enable W

Acked_Transitions R

Notify_Type W

Event_Time_Stamps R

Profile_Name R

Event_Message_Texts R

Event-Log

Page 29: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

29/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Properties supported Readable/ Writable

Range restrictions

Object_Identifier R Object_Name R Object_Type R Description W Status_Flags R Event_State R Reliability R Enable W Start_Time W Stop_Time W Log_DeviceObjectProperty W Logging_Type W Log_Interval W 0; 1 sec…720 h Align_Intervals W Interval_Offset W Trigger W Stop_When_Full W Buffer_Size W 0…5000 Log_Buffer R Record_Count W 0…0 Total_Record_Count R Notification_Threshold W 0…5000 Records_Since_Notification R Last_Notify_Record R Notification_Class W Event_Enable W Acked_Transitions R Notify_Type W Event_Time_Stamps R Profile_Name R Event_Message_Texts R

Trend Log Multiple

Page 30: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

30/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Properties supported Readable/ Writable

Range restrictions

Object_Identifier R

Object_Name R

Object_Type R

Description R

Present_Value R

State_Description R

Status_Flags R

Event_State R

Reliability R

Requested_Shed_Level W

Start_Time W

Shed_Duration W

Duty_Window W

Enable W

Full_Duty_Baseline R

Expected_Shed_Level R

Actual_Shed_Level R

Shed_Levels W

Shed_Levels_Descriptions W

Notification_Class W

Time_Delay W 1…65535

Event_Enable W

Acked_Transitions R

Notify_Type W

Event_Time_Stamps R

Profile_Name R

Event_Message_Texts R Properties supported Readable/

Writable Range restrictions

Object_Identifier R

Object_Name R

Object_Type R

Description R

Node_Type R

Node_Subtype R

Subordinate_List R

Subordinate_Annotations R

Profile_Name R

Load Control

Structured View

Page 31: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

31/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

1.6 Segmentation capability

Able to transmit segmented messages Window size 4

Able to receive segmented messages Window size 4

1.7 Data Link Layer options

The supported Data Link Layers of a product are listed with the product model number.

BACnet IP, (Annex J)

BACnet IP, (Annex J), Foreign Device

ISO 8802-3, Ethernet (Clause 7)

ANSI/ATA 878.1, 2.5 Mb. ARCNET (Clause 8)

ANSI/ATA 878.1, RS-485 ARCNET (Clause 8), baud rate(s)

MS/TP master (Clause 9), baud rate(s)

MS/TP slave (Clause 9), baud rate(s)

Point-To-Point, EIA 232 (Clause 10), baud rate(s) : 38400

Point-To-Point, modem, (Clause 10), baud rate(s) : 38400

LonTalk, (Clause 11), medium : TP/FT-10

Other

1.8 Device address binding

Is static device binding supported? Yes No

1.9 Networking options

Router, Clause 6 (remote management functionality/BACnet PTP)

Annex H, BACnet Tunnelling Router over IP

BACnet/IP Broadcast Management Device (BBMD) 1)

Number of BDT entries: 50 Number of FDT entries: 50

Does the BBMD support registrations by foreign devices? Yes No 1) if product supports IP

Page 32: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

32/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

1.10 Character sets supported

Indicating support for multiple character sets does not imply that they can all be supported simultaneously.

UTF-8 IBM / Microsoft DBCS ISO 8859-1

ISO 10646 (UCS-2) ISO 10646 (UCS-4) JIS C 6226

Page 33: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

33/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

2 Desigo PXC3 and DXR2 Automation Stations

Date : 1 May 2015 Vendor name : Siemens Building Technologies (Vendor ID 7) Product name : Desigo PXC3 and DXR2 Automation Stations Product model number : PXC3 and DXR2 BACnet protocol version : 1:13 Application software version : TBD Firmware revision : TBD

2.1 Product model number

The Desigo PXC3 and DXR2 Automation stations are a range of products based on the same software. The PICS are the same for all products listed below:

PXC3.E72 Modular automation station IP PXC3.E72-100A Modular automation station IP PXC3.E72A Modular automation station IP PXC3.E72A-100A Modular automation station IP PXC3.E75 Modular automation station IP PXC3.E75-100A Modular automation station IP PXC3.E75A Modular automation station IP PXC3.E75A-100A Modular automation station IP DXR2.E18 Modular automation station IP DXR2.E12P Modular automation station IP DXR2.E10 Modular automation station IP DXR2.E09 Modular automation station IP DXR2.E09T Modular automation station IP DXR2.M11 Modular automation station MSTP DXR2.M18 Modular automation station MSTP DXR2.M12P Modular automation station MSTP DXR2.M10 Modular automation station MSTP DXR2.M09 Modular automation station MSTP DXR2.M09T Modular automation station MSTP

2.2 Product description

The Desigo PXC3 and DXR2 is a freely configurable process unit. The process unit as a system platform can be used in the Desigo product range as a stand-alone or network device with BACnet communication.

2.3 BACnet standardized device profile (Annex L)

The Desigo PXC3 automation station is a range of products based on the same software. The PICS are the same for all products listed below.

Page 34: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

34/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

2.4 BACnet standardized device profile (Annex L)

BACnet Advanced Workstation (B-AWS)

BACnet Operator Workstation (B-OWS)

BACnet Operator Display (B-OD)

BACnet Building Controller (B-BC)

BACnet Advanced Application Controller (B-AAC)

BACnet Application Specific Controller (B-ASC)

BACnet Smart Sensor (B-SS)

BACnet Smart Actuator (B-SA)

Page 35: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

35/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

2.5 BACnet interoperability building blocks supported (Annex K)

Data Sharing – Read Property-A DS-RP-A

Data Sharing – Read Property-B DS-RP-B

Data Sharing – Read Property Multiple-A DS-RPM-A

Data Sharing – Read Property Multiple-B DS-RPM-B

Data Sharing – Write Property-A DS-WP-A

Data Sharing – Write Property-B DS-WP-B

Data Sharing – Write Property Multiple-A DS-WPM-A

Data Sharing – Write Property Multiple-B DS-WPM-B

Data Sharing – Change of Value -A DS-COV-A

Data Sharing – Change of Value -B DS-COV-B

Data Sharing – Change of Value Property -A DS-COVP-A

Data Sharing – Change of Value Property -B DS-COVP-B

Data Sharing – Change of Value-Unsolicited-A DS-COVU-A

Data Sharing – Change of Value-Unsolicited-B DS-COVU-B

Data Sharing – View-A DS-V-A

Data Sharing – Advanced View-A DS-AV-A

Data Sharing – Modify-A DS-M-A

Data Sharing – Advanced Modify-A DS-AM-A

Alarm and Event – Notification-A AE-N-A

Alarm and Event – Notification Internal-B AE-N-I-B

Alarm and Event – Notification External-B AE-N-E-B

Alarm and Event – ACK-A AE-ACK-A

Alarm and Event – ACK-B AE-ACK-B

Alarm and Event – Alarm Summary-B AE-ASUM-B

Alarm and Event – Enrollment Summary-B AE-ESUM-B

Alarm and Event – Information-B AE-INFO-B

Alarm and Event – Life Safety-A AE-LS-A

Alarm and Event – Life Safety-B AE-LS-B

Alarm and Event – View Notifications-A AE-VN-A

Alarm and Event – Advanced View Notifications-A AE-AVN-A

Alarm and Event – View and Modify-A AE-VM-A

Alarm and Event – Advanced View and Modify-A AE-AVM-A

Alarm and Event – Alarm Summary View-A AE-AS-A

Alarm and Event – Event Log View-A AE-ELV-A

Alarm and Event – Event Log View and Modify-A AE-ELVM-A

Alarm and Event – Event Log Internal-B AE-EL-I-B

Alarm and Event – Event Log External-B AE-EL-E-B

Data sharing

Alarm and event management

Page 36: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

36/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Historical/Deprecated BIBBs Alarm and Event – Alarm Summary-A AE-ASUM-A

Alarm and Event – Enrollment Summary-A AE-ESUM-A

Alarm and Event – Information-A AE-INFO-A

Scheduling – Internal-B SCHED-I-B

Scheduling – External-B SCHED-E-B

Scheduling – Advanced View Modify-A SCHED-AVM-A

Scheduling – View Modify-A SCHED-VM-A

Scheduling – Weekly Schedule-A SCHED-WS-A

Scheduling – Weekly Schedule Internal-B SCHED-WS-I-B

Scheduling – Readable-B SCHED-R-B

Historical/Deprecated BIBBs Scheduling – A SCHED-A

Trending – Viewing and Modifying Trends-A T-VMT-A

Trending – Viewing and Modifying Internal-B T-VMT-I-B

Trending – Viewing and Modifying External-B T-VMT-E-B

Trending – Viewing and Modifying Multiple Values-A T-VMMV-A

Trending – Viewing and Modifying Multiple Values Internal-B T-VMMV-I-B

Trending – Viewing and Modifying Multiple Values External -B T-VMMV-E-B

Trending – Automated Multiple Value Retrieval-A T-AMVR-A

Trending – Automated Multiple Value Retrieval-B T-AMVR-B

Trending – View-A T-V-A

Trending – Advanced View and Modify-A T-AVM-A

Trending – Archival-A T-A-A

Trending – Automated Trend Retrieval-A T-ATR-A

Trending – Automated Trend Retrieval-B T-ATR-B

Historical/Deprecated BIBBs Trending – Viewing and Modifying Trends-A T-VMT-A

Trending – Viewing and Modifying Multiple Values-A T-VMMV-A

Device Management – Dynamic Device Binding-A DM-DDB-A

Device Management – Dynamic Device Binding-B DM-DDB-B

Device Management – Dynamic Object Binding-A DM-DOB-A

Device Management – Dynamic Object Binding-B DM-DOB-B

Device Management – Device Communication Control-A DM-DCC-A

Device Management – Device Communication Control-B DM-DCC-B

Device Management – Private Transfer-A DM-PT-A

Device Management – Private Transfer-B DM-PT-B

Device Management – Text Message-A DM-TM-A

Device Management – Text Message-B DM-TM-B

Device Management – Time Synchronization-A DM-TS-A

Device Management – Time Synchronization-B DM-TS-B

Alarm and event management

Scheduling

Trending

Device management

Page 37: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

37/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Device Management – UTC Time Synchronization-A DM-UTC-A

Device Management – UTC Time Synchronization-B DM-UTC-B

Device Management – Reinitialize Device-A DM-RD-A

Device Management – Reinitialize Device-B DM-RD-B

Device Management – Backup and Restore-A DM-BR-A

Device Management – Backup and Restore-B DM-BR-B

Device Management – Restart-A DM-R-A

Device Management – Restart-B DM-R-B

Device Management – List Manipulation-A DM-LM-A

Device Management – List Manipulation-B DM-LM-B

Device Management – Object Creation and Deletion-A DM-OCD-A

Device Management – Object Creation and Deletion-B DM-OCD-B

Device Management – Virtual Terminal-A DM-VT-A

Device Management – Virtual Terminal-B DM-VT-B

Device Management – Automatic Network Mapping-A DM-ANM-A

Device Management – Automatic Device Mapping-A DM-ADM-A

Device Management – Automatic Time Synchronization-A DM-ATS-A

Device Management – Manual Time Synchronization-A DM-MTS-A

Network Management – Connection Establishment-A NM-CE-A

Network Management – Connection Establishment-B NM-CE-B

Network Management – Router Configuration-A NM-RC-A

Network Management – Router Configuration-B NM-RC-B

Device management

Network management

Page 38: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

38/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

2.6 Standard object types supported

Object type Supported Can be created dynamically

Can be deleted dynamically

Analog Input

Analog Output

Analog Value

Binary Input

Binary Output

Binary Value

Calendar

Command

Device

Event Enrollment

File

Group

Loop

Multi-State Input

Multi-State Output

Notification Class

Program

Schedule

Averaging

Multi-State Value

Trend Log

Life-Safety-Point

Life-Safety-Zone

Accumulator

Pulse-Converter

Event Log

Global Group

Trend Log Multiple

Load Control

Structured-View

Access Door

(unassigned)

Access Credential

Access Point

Access Rights

Access User

Access Zone

Credential Data Input

Network Security

Bitstring Value

Characterstring Value

Page 39: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

39/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Object type Supported Can be created dynamically

Can be deleted dynamically

Date Pattern Value Date Value Datetime Pattern Value Datetime Value Integer Value Large Analog Value Octetstring Value Positive Integer Value Time Pattern Value Time Value

Page 40: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

40/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Properties Supported Readable/ Writable

Range restrictions

Object_Identifier R Object_Name W Object_Type R Present_Value W Description W Device_Type W Status_Flags R Event_State R Reliability W Out_Of_Service W Update_Interval Units W Min_Pres_Value W Max_Pres_Value W Resolution W COV_Increment W Time_Delay Notification_Class High_Limit Low_Limit Deadband Limit_Enable Event_Enable Acked_Transitions Notify_Type Event_Time_Stamps Profile_Name R

Analog Input

Page 41: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

41/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Properties Supported Readable/ Writable

Range restrictions

Object_Identifier R Object_Name W Object_Type R Present_Value W Description W Device_Type W Status_Flags R Event_State R Reliability W Out_Of_Service W Update_Interval Units W Min_Pres_Value W Max_Pres_Value W Resolution W Priority_Array R Relinquish_Default W COV_Increment W Time_Delay Notification_Class High_Limit Low_Limit Deadband Limit_Enable Event_Enable Acked_Transitions Notify_Type Event_Time_Stamps Profile_Name R

Analog Output

Page 42: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

42/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Properties Supported Readable/ Writable

Range restrictions

Object_Identifier R Object_Name W Object_Type R Present_Value W Description W Status_Flags R Event_State R Reliability W Out_Of_Service W Units W Priority_Array R Relinquish_Default W COV_Increment W Time_Delay Notification_Class High_Limit Low_Limit Deadband Limit_Enable Event_Enable Acked_Transitions Notify_Type Event_Time_Stamps Profile_Name R

Analog Value

Page 43: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

43/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Properties Supported Readable/ Writable

Range restrictions

Object_Identifier R

Object_Name W

Object_Type R

Present_Value W

Description W

Device_Type W

Status_Flags R

Event_State R

Reliability W

Out_Of_Service W

Polarity W

Inactive_Text W

Active_Text W

Change_Of_State_Time

Change_Of_State_Count

Time_Of_State_Count_Reset

Elapsed_Active_Time

Time_Of_Active_Time_Reset

Time_Delay

Notification_Class

Alarm_Value

Event_Enable

Acked_Transitions

Notify_Type

Event_Time_Stamps

Profile_Name W

Binary Input

Page 44: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

44/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Properties Supported Readable/ Writable

Range restrictions

Object_Identifier R

Object_Name W

Object_Type R

Present_Value W

Description W

Device_Type W

Status_Flags R

Event_State R

Reliability W

Out_Of_Service W

Polarity W

Inactive_Text W

Active_Text W Change_Of_State_Time Change_Of_State_Count Time_Of_State_Count_Reset Elapsed_Active_Time Time_Of_Active_Time_Reset Minimum_Off_Time Minimum_On_Time Priority_Array R

Relinquish_Default W Time_Delay Notification_Class Feedback_Value Event_Enable Acked_Transitions Notify_Type Event_Time_Stamps Profile_Name R

Binary Output

Page 45: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

45/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Properties supported Readable/ Writable

Range restrictions

Object_Identifier R

Object_Name W

Object_Type R

Present_Value W

Description W

Status_Flags R

Event_State R

Reliability W

Out_Of_Service W

Inactive_Text W

Active_Text W

Change_Of_State_Time

Change_Of_State_Count

Time_Of_State_Count_Reset

Elapsed_Active_Time

Time_Of_Active_Time_Reset

Minimum_Off_Time

Minimum_On_Time

Priority_Array R

Relinquish_Default W

Time_Delay

Notification_Class

Alarm_Value

Event_Enable

Acked_Transitions

Notify_Type

Event_Time_Stamps

Profile_Name R

Binary Value

Page 46: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

46/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Properties supported Readable/ Writable

Range restrictions

Object_Identifier R

Object_Name W

Object_Type R

Description W

Present_Value W

In_Process R

All_Writes_Successful R

Action W

Action_Text W

Profile_Name R

Command

Page 47: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

47/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Properties supported Readable/ Writable

Range restrictions

Object_Identifier R

Object_Name R

Object_Type R

System_Status R

Vendor_Name R

Vendor_Identifier R

Model_Name R

Firmware_Revision R

Application_Software_Version R

Location W

Description W

Protocol_Version R

Protocol_Revision R

Protocol_Services_Supported R

Protocol_Object_Types_Supported R

Object_List R

Structured_Object_List R

Max_APDU_Length_Accepted R

Segmentation_Supported R

Max_Segments_Accepted R

VT_Classes_Supported

Active_VT_Sessions

Local_Time R

Local_Date R

UTC_Offset R

Daylight_Savings_Status R

APDU_Segment_Timeout R

APDU_Timeout R

Number_Of_APDU_Retries R

List_Of_Session_Keys

Time_Synchronization_Recipients

Max_Master R

Max_Info_Frames R

Device_Address_Binding R

Database_Revision R

Configuration_Files R

Last_Restore_Time R

Backup_Failure_Timeout W

Backup_Preparation_Time R

Restore_Preparation_Time R

Restore_Completion_Time R

Backup_And_Restore_State R

Active_COV_Subscriptions R

Slave_Proxy_Enable W

Manual_Slave_Adress_Binding W

Device

Page 48: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

48/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Properties supported Readable/ Writable

Range restrictions

Auto_Slave_Discovery W

Slave_Address_Binding R

Last_Restart_Reason R

Time_Of_Device_Restart R

Restart_Notification_Recipients W

UTC_Time_Synchronization_Recipients

Time_Synchronization_Interval

Align_Intervals

Interval_Offset

Profile_Name R

Properties supported Readable/ Writable

Range restrictions

Object_Identifier R Object_Name W Object_Type R Description W Event_Type R Event_Parameters W Notify_Type W Object_Property_Reference W

Event_State R

Event_Enable W

Event_Detection_Enable W

Acked_Transitions R

Time_Delay_Normal W

Notification_Class W

Event_Time_Stamps R

Event_Message_Texts R

Event_Message_Texts_Config W

Event_Algorithm_Inhibit W

Status_Flags R

Reliability R

Profile_Name R

Event Enrollment

Page 49: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

49/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Properties supported Readable/ Writable

Range restrictions

Object_Identifier R Object_Name W Object_Type R Description W File_Type R File_Size W Modification_Date R Archive W Read_Only R File_Access_Method R Profile_Name R

File

Page 50: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

50/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Properties supported Readable/ Writable

Range restrictions

Object_Identifier R Object_Name W Object_Type R Present_Value W Description W

Status_Flags R

Event_State R

Reliability W Out_Of_Service W

Output_Units W

Manipulated_Variable_Reference R Controlled_Variable_Reference R

Controlled_Variable_Value R Controlled_Variable_Units W Setpoint_Reference R Setpoint R Action R Proportional_Constant W Proportional_Constant_Units W Integral_Constant W Integral_Constant_Units W Derivative_Constant W Derivative_Constant_Units W

Bias W Maximum_Output W Minimum_Output W

Priority_For_Writing R

COV_Increment W

Profile_Name R

Loop

Page 51: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

51/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Properties supported Readable/ Writable

Range restrictions

Object_Identifier R Object_Name W Object_Type R Present_Value W Description W

Device_Type W

Status_Flags R

Event_State R

Reliability W

Out_Of_Service W

Number_Of_States R

State_Text W Profile_Name R

Multistate Input

Page 52: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

52/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Properties supported Readable/ Writable

Range restrictions

Object_Identifier R Object_Name W Object_Type R Present_Value W Description W

Device_Type W

Status_Flags R

Event_State R

Reliability W

Out_Of_Service W

Priority_Array R

Relinquish_Default W

Number_Of_States R

State_Text W Profile_Name R

Multistate Output

Page 53: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

53/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Properties supported Readable/ Writable

Range restrictions

Object_Identifier R Object_Name W Object_Type R Present_Value W Description W

Status_Flags R

Event_State R

Reliability R

Out_Of_Service W

Priority_Array R

Relinquish_Default W

Number_Of_States R

State_Text W Profile_Name R

Properties supported Readable/ Writable

Range restrictions

Object_Identifier R Object_Name W Object_Type R Description W

Notification_Class R

Priority W

Ack_Required W

Recipient_List W Profile_Name R

Multistate Value

Notification Class

Page 54: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

54/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Properties supported Readable/ Writable

Range restrictions

Object_Identifier R Object_Name W Object_Type R Program_State R Program_Change W

Reason_For_Halt R

Description_Of_Halt R Description W

Status_Flags R

Reliability R

Out_Of_Service R Profile_Name R

Program

Page 55: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

55/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Properties supported Readable/ Writable

Range restrictions

Object_Identifier R Object_Name W Object_Type R Description W

Enable W

Start_Time W

Stop_Time W

Log_DeviceObjectProperty W Log_Interval W Stop_When_Full W Buffer_Size W Log_Buffer R Record_Count W Total_Record_Count R Notification_Threshold W Records_Since_Notification R Last_Notify_Record R Event_State R Notification_Class W Event_Enable W Acked_Transitions R Notify_Type R Event_Time_Stamps R Logging_Type W Align_Intervals W Interval_Offset W COV_Resubscription_Interval R Reliability R Status_Flags R

Profile_Name R

Trend Log

Page 56: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

56/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Properties supported Readable/ Writable

Range restrictions

Object_Identifier R Object_Name W Object_Type R Description W

Status_Flags R

Event_State R

Reliability R

Enable W

Start_Time W

Stop_Time W Stop_When_Full W Buffer_Size W Log_Buffer R Record_Count W Total_Record_Count R Notification_Threshold W Records_Since_Notification R Last_Notify_Record R Notification_Class W Event_Enable W Acked_Transitions R Notify_Type R Event_Time_Stamps R Profile_Name R

Event-Log

Page 57: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

57/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Properties supported Readable/ Writable

Range restrictions

Object_Identifier R Object_Name W Object_Type R Description W Node_Type R Node_Subtype W Subordinate_List W Subordinate_Annotations W Profile_Name R

2.7 Segmentation capability

Able to transmit segmented messages Window size 32

Able to receive segmented messages Window size 32

2.8 Data Link Layer options

The simultaneously supported Data Link Layers of a product are listed with the product model number.

BACnet IP, (Annex J)

BACnet IP, (Annex J), Foreign Device

ISO 8802-3, Ethernet (Clause 7)

ANSI/ATA 878.1, 2.5 Mb. ARCNET (Clause 8)

ANSI/ATA 878.1, RS-485 ARCNET (Clause 8), baud rate(s)

MS/TP master (Clause 9), baud rate(s) : 9600 : 19200 : 38400 : 76800 : 115200

MS/TP slave (Clause 9), baud rate(s)

Point-To-Point, EIA 232 (Clause 10), baud rate(s) : 38400

Point-To-Point, modem, (Clause 10), baud rate(s) : 38400

LonTalk, (Clause 11), medium : TP/FT-10

Other

2.9 Device address binding

Is static device binding supported? Yes No

Structured View

Page 58: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

58/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

2.10 Networking options

Router, Clause 6 (remote management functionality/BACnet PTP)

Annex H, BACnet Tunnelling Router over IP

BACnet/IP Broadcast Management Device (BBMD)

Number of BDT entries: Number of FDT entries:

Does the BBMD support registrations by foreign devices? Yes No

2.11 Character sets supported

Indicating support for multiple character sets does not imply that they can all be supported simultaneously.

UTF-8 (or ANSI X3.4) IBM / Microsoft DBCS ISO 8859-1

ISO 10646 (UCS-2) ISO 10646 (UCS-4) JIS C 6226

Page 59: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

59/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

3 Desigo CC Workstation

Date : October 6, 2014 Vendor name : Siemens Building Technologies (Vendor ID 7) Product name : Desigo CC Workstation Product model number : 2.1 BACnet protocol version : 1.13 Application software version : 2.1 Firmware revision : n/a

3.1 Product description

Desigo CC from Siemens is an integration platform for managing facility systems and enterprise applications. Optimized as an extension of the powerful APOGEE automation system, Desigo CC allows full building operation as well as complete system configuration from the convenience of a standard web browser, from a dedicated console for mission-critical applications, or from a Windows Desktop App for optimal mobile performance. Users find the workflow driven interface, designed around role-based profiles and flexible user-defined views, easy to learn and easy to use as it grows with their expertise. Desigo CC is built on building automation, fire safety, security, video, and IT standards, and provides the application support necessary for automating intelligent control and providing actionable information. 3.2 BACnet standardized device profile (Annex L)

BACnet Advanced Workstation (B-AWS)

BACnet Operator Workstation (B-OWS)

BACnet Operator Display (B-OD)

BACnet Building Controller (B-BC)

BACnet Advanced Application Controller (B-AAC)

BACnet Application Specific Controller (B-ASC)

BACnet Smart Sensor (B-SS)

BACnet Smart Actuator (B-SA)

Page 60: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

60/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

3.3 BACnet interoperability building blocks supported (Annex K)

Data Sharing – ReadProperty-A DS-RP-A

Data Sharing – ReadProperty-B DS-RP-B

Data Sharing – ReadPropertyMultiple-A DS-RPM-A

Data Sharing – ReadPropertyMultiple-B DS-RPM-B

Data Sharing – WriteProperty-A DS-WP-A

Data Sharing – WriteProperty-B DS-WP-B

Data Sharing – WritePropertyMultiple-A DS-WPM-A

Data Sharing – WritePropertyMultiple-B DS-WPM-B

Data Sharing – ChangeofValue -A DS-COV-A

Data Sharing – ChangeofValue -B DS-COV-B

Data Sharing – ChangeofValueProperty -A DS-COVP-A

Data Sharing – ChangeofValueProperty -B DS-COVP-B

Data Sharing – View-A DS-V-A

Data Sharing – Advanced View-A DS-AV-A

Data Sharing – Modify-A DS-M-A

Data Sharing – Advanced Modify-A DS-AM-A

Alarm and Event – Notification-A AE-N-A

Alarm and Event – Notification Internal-B AE-N-I-B

Alarm and Event – Notification External-B AE-N-E-B

Alarm and Event – ACK-A AE-ACK-A

Alarm and Event – ACK-B AE-ACK-B

Alarm and Event – Alarm Summary-B AE-ASUM-B

Alarm and Event – Enrollment Summary-B AE-ESUM-B

Alarm and Event – Information-B AE-INFO-B

Alarm and Event – LifeSafety-A AE-LS-A

Alarm and Event – LifeSafety-B AE-LS-B

Alarm and Event – View Notifications-A AE-VN-A

Alarm and Event – Advanced View Notifications-A AE-AVN-A

Alarm and Event – View and Modify-A AE-VM-A

Alarm and Event – Advanced View and Modify-A AE-AVM-A

Alarm and Event – Alarm Summary View-A AE-AS-A

Alarm and Event – Event Log View-A AE-ELV-A

Alarm and Event – Event Log View and Modify-A AE-ELVM-A

Alarm and Event – Event Log-Internal-B AE-EL-I-B

Alarm and Event – Event Log-External-B AE-EL-E-B

Data sharing

Alarm and event management

Page 61: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

61/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Historical/Deprecated BIBBs Alarm and Event – Alarm Summary-A AE-ASUM-A

Alarm and Event – Enrollment Summary-A AE-ESUM-A

Alarm and Event – Information-A AE-INFO-A

Scheduling – Internal-B SCHED-I-B

Scheduling – External-B SCHED-E-B

Scheduling – View Modify-A SCHED-VM-A

Scheduling – Advanced View Modify-A SCHED-AVM-A

Scheduling – Weekly Schedule-A SCHED-WS-A

Scheduling – Weekly Schedule Internal-B SCHED-WS-I-B

Scheduling – Readable-B SCHED-R-B

Historical/Deprecated BIBBs Scheduling – A SCHED-A Trending – Viewing and Modifying Trends Internal-B T-VMT-I-B

Trending – Viewing and Modifying Trends External-B T-VMT-E-B

Trending – Viewing and Modifying Multiple Values Internal-B T-VMMV-I-B

Trending – Viewing and Modifying Multiple Values External-B T-VMMV-E-B

Trending – Automated Multiple Value Retrieval-A T-AMVR-A

Trending – Automated Multiple Value Retrieval-B T-AMVR-B

Trending – View-A T-V-A

Trending – Advanced View and Modify-A T-AVM-A

Trending – Archival-A T-A-A

Trending – Automated Trend Retrieval-A T-ATR-A

Trending – Automated Trend Retrieval-B T-ATR-B

Historical/Deprecated BIBBs Trending – Viewing and Modifying Trends-A T-VMT-A

Trending – Viewing and Modifying Multiple Values-A T-VMMV-A

Device Management – Dynamic Device Binding-A DM-DDB-A

Device Management – Dynamic Device Binding-B DM-DDB-B

Device Management – Dynamic Object Binding-A DM-DOB-A

Device Management – Dynamic Object Binding-B DM-DOB-B

Device Management – DeviceCommunicationControl-A DM-DCC-A

Device Management – DeviceCommunicationControl-B DM-DCC-B

Device Management – Private Transfer-A DM-PT-A

Device Management – Private Transfer-B DM-PT-B

Device Management – Text Message-A DM-TM-A

Device Management – Text Message-B DM-TM-B

Device Management – TimeSynchronization-A DM-TS-A

Alarm and event management

Scheduling

Trending

Device management

Page 62: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

62/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Device Management – TimeSynchronization-B DM-TS-B

Device Management – UTCTimeSynchronization-A DM-UTC-A

Device Management – UTCTimeSynchronization-B DM-UTC-B

Device Management – ReinitializeDevice-A DM-RD-A

Device Management – ReinitializeDevice-B DM-RD-B

Device Management – Backup and Restore-A DM-BR-A

Device Management – Backup and Restore-B DM-BR-B

Device Management – Restart-A DM-R-A

Device Management – Restart-B DM-R-B

Device Management – List Manipulation-A DM-LM-A

Device Management – List Manipulation-B DM-LM-B

Device Management – Object Creation and Deletion-A DM-OCD-A

Device Management – Object Creation and Deletion-B DM-OCD-B

Device Management – Virtual Terminal-A DM-VT-A

Device Management – Virtual Terminal-B DM-VT-B

Device Management – Automatic Network Mapping-A DM-ANM-A

Device Management – Automatic Device Mapping-A DM-ADM-A

Device Management – Automatic Time Synchronization-A DM-ATS-A

Device Management – Manual Time Synchronization-A DM-MTS-A

Network Management – Connection Establishment-A NM-CE-A

Network Management – Connection Establishment-B NM-CE-B

Network Management – Router Configuration-A NM-RC-A

Network Management – Router Configuration-B NM-RC-B

Device management

Network management

Page 63: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

63/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

3.4 Standard object types supported

Only the device object is supported.

Properties monitor modify Object_Identifier

Object_Name

Object_Type

System_Status

Vendor_Name

Vendor_Identifier

Model_Name

Firmware_Revision

Application_Software_Version

Location

Description

Protocol_Version

Protocol_Revision

Protocol_Services_Supported

Protocol_Object_Types_Supported

Object_List

Structured_Object_List

Max_APDU_Length_Accepted

Segmentation_Supported

Max_Segments_Accepted

VT_Classes_Supported

Active_VT_Sessions

Local_Time

Local_Date

UTC_Offset

Daylight_Savings_Status

APDU_Segment_Timeout

APDU_Timeout

Number_Of_APDU_Retries

List_Of_Session_Keys

Time_Synchronization_Recipients

Max_Master

Max_Info_Frames

Device_Address_Binding

Database_Revision

Configuration_Files

Last_Restore_Time

Backup_Failure_Timeout

Active_COV_Subscriptions

Slave_Proxy_Enable

Manual_Slave_Adress_Binding

Auto_Slave_Discovery

Device

Page 64: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

64/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Properties monitor modify Slave_Address_Binding

Last_Restart_Reason

Time_Of_Device_Restart

Restart_Notification_Recipients

UTC_Time_Synchronization_Recipients

Time_Synchronization_Interval

Align_Intervals

Interval_Offset

Serial_Number

Property_List

Profile_Name

Page 65: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

65/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

3.5 Client supported object types Object type Supported Can be created

dynamically Can be deleted dynamically

Analog Input

Analog Output

Analog Value

Binary Input

Binary Output

Binary Value

Calendar

Command

Device

Event Enrollment

File

Group

Loop

Multi-State Input

Multi-State Output

Notification Class

Program

Schedule

Averaging

Multi-State Value

Trend Log

Life-Safety-Point

Life-Safety-Zone

Accumulator

Pulse-Converter

Event Log

Global Group

Trend Log Multiple

Load Control

Structured-View

Access Door

Access Credential

Access Point

Access Rights

Access User

Access Zone

Credential Data Input

Network Security

Bitstring Value

Characterstring Value

Page 66: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

66/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Object type Supported Can be created dynamically

Can be deleted dynamically

Date Pattern Value Date Value Datetime Pattern Value Datetime Value Integer Value Large Analog Value Octetstring Value Positive Integer Value Time Pattern Value Time Value Notification Forwarder Alert Enrollment Channel

Lighting Output

Page 67: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

67/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

3.6 Segmentation capability

Able to transmit segmented messages Window size 32

Able to receive segmented messages Window size 32

3.7 Data Link Layer options

BACnet IP, (Annex J)

BACnet IP, (Annex J), Foreign Device

ISO 8802-3, Ethernet (Clause 7)

ANSI/ATA 878.1, 2.5 Mb. ARCNET (Clause 8)

ANSI/ATA 878.1, RS-485 ARCNET (Clause 8), baud rate(s)

MS/TP master (Clause 9), baud rate(s)

MS/TP slave (Clause 9), baud rate(s)

Point-To-Point, EIA 232 (Clause 10), baud rate(s) : Max. 38400

Point-To-Point, modem, (Clause 10), baud rate(s) : Max. 38400

LonTalk, (Clause 11), medium: : TP/FT-10

Other

3.8 Device address binding

Is static device binding supported? Yes No

3.9 Networking options

Router, Clause 6

Annex H, BACnet Tunnelling Router over IP

BACnet/IP Broadcast Management Device (BBMD)

Does the BBMD support registrations by Foreign Devices? Yes No

3.10 Character sets supported

Indicating support for multiple character sets does not imply that they can all be supported simultaneously.

UTF-8 IBM / Microsoft DBCS ISO 8859-1

ISO 10646 (UCS-2) ISO 10646 (UCS-4) JIS C 6226

Page 68: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

68/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

4 Desigo Insight Workstation

Date : Vendor name : Siemens Building Technologies (Vendor ID 7) Product name : Desigo Insight Workstation Product model number : - BACnet protocol version : 1.13 Application software version : - Firmware revision : INSIGHT Rel 6

4.1 Product description

Desigo Insight is the BACnet management station for the Desigo system. Desigo Insight is represented in the network as a BACnet device, which contains a device object only. 4.2 BACnet standardized device profile (Annex L)

BACnet Advanced Workstation (B-AWS)

BACnet Operator Workstation (B-OWS)

BACnet Operator Display (B-OD)

BACnet Building Controller (B-BC)

BACnet Advanced Application Controller (B-AAC)

BACnet Application Specific Controller (B-ASC)

BACnet Smart Sensor (B-SS)

BACnet Smart Actuator (B-SA)

Page 69: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

69/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

4.3 BACnet interoperability building blocks supported (Annex K)

Data Sharing – ReadProperty-A DS-RP-A

Data Sharing – ReadProperty-B DS-RP-B

Data Sharing – ReadPropertyMultiple-A DS-RPM-A

Data Sharing – ReadPropertyMultiple-B DS-RPM-B

Data Sharing – WriteProperty-A DS-WP-A

Data Sharing – WriteProperty-B DS-WP-B

Data Sharing – WritePropertyMultiple-A DS-WPM-A

Data Sharing – WritePropertyMultiple-B DS-WPM-B

Data Sharing – ChangeofValue-A DS-COV-A

Data Sharing – ChangeofValue-B DS-COV-B

Data Sharing – ChangeofValueProperty-A DS-COVP-A

Data Sharing – ChangeofValueProperty-B DS-COVP-B

Data Sharing – ChangeofValue-Unsolicited-A DS-COVU-A

Data Sharing – ChangeofValue-Unsolicited-B DS-COVU-B

Data Sharing – View-A DS-V-A

Data Sharing – Advanced View-A DS-AV-A

Data Sharing – Modify-A DS-M-A

Data Sharing – Advanced Modify-A DS-AM-A

Alarm and Event – Notification-A AE-N-A

Alarm and Event – Notification Internal-B AE-N-I-B

Alarm and Event – Notification External-B AE-N-E-B

Alarm and Event – ACK-A AE-ACK-A

Alarm and Event – ACK-B AE-ACK-B

Alarm and Event – Alarm Summary-B AE-ASUM-B

Alarm and Event – Enrollment Summary-B AE-ESUM-B

Alarm and Event – Information-B AE-INFO-B

Alarm and Event – LifeSafety-A AE-LS-A

Alarm and Event – LifeSafety-B AE-LS-B

Alarm and Event – View Notifications-A AE-VN-A

Alarm and Event – Advanced View Notifications-A AE-AVN-A

Alarm and Event – View and Modify-A AE-VM-A

Alarm and Event – Advanced View and Modify-A AE-AVM-A

Alarm and Event – Alarm Summary View-A AE-AS-A

Alarm and Event – Event Log View-A AE-ELV-A

Alarm and Event – Event Log View and Modify-A AE-ELVM-A

Alarm and Event – Event Log-Internal-B AE-EL-I-B

Alarm and Event – Event Log-External-B AE-EL-E-B

Data sharing

Alarm and event management

Page 70: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

70/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Historical/Deprecated BIBBs Alarm and Event – Alarm Summary-A AE-ASUM-A

Alarm and Event – Enrollment Summary-A AE-ESUM-A

Alarm and Event – Information-A AE-INFO-A

Scheduling – Internal-B SCHED-I-B

Scheduling – External-B SCHED-E-B

Scheduling – View Modify-A SCHED-VM-A

Scheduling – Advanced View Modify-A SCHED-AVM-A

Scheduling – Weekly Schedule-A SCHED-WS-A

Scheduling – Weekly Schedule Internal-B SCHED-WS-I-B

Scheduling – Readable-B SCHED-R-B

Historical/Deprecated BIBBs Scheduling – A SCHED-A Trending – Viewing and Modifying Trends Internal-B T-VMT-I-B

Trending – Viewing and Modifying Trends External-B T-VMT-E-B

Trending – Viewing and Modifying Multiple Values Internal-B T-VMMV-I-B

Trending – Viewing and Modifying Multiple Values External-B T-VMMV-E-B

Trending – Automated Multiple Value Retrieval-A T-AMVR-A

Trending – Automated Multiple Value Retrieval-B T-AMVR-B

Trending – View-A T-V-A

Trending – Advanced View and Modify-A T-AVM-A

Trending – Archival-A T-A-A

Trending – Automated Trend Retrieval-A T-ATR-A

Trending – Automated Trend Retrieval-B T-ATR-B

Historical/Deprecated BIBBs Trending – Viewing and Modifying Trends-A T-VMT-A

Trending – Viewing and Modifying Multiple Values-A T-VMMV-A

Device Management – Dynamic Device Binding-A DM-DDB-A

Device Management – Dynamic Device Binding-B DM-DDB-B

Device Management – Dynamic Object Binding-A DM-DOB-A

Device Management – Dynamic Object Binding-B DM-DOB-B

Device Management – DeviceCommunicationControl-A DM-DCC-A

Device Management – DeviceCommunicationControl-B DM-DCC-B

Device Management – Private Transfer-A DM-PT-A

Device Management – Private Transfer-B DM-PT-B

Device Management – Text Message-A DM-TM-A

Device Management – Text Message-B DM-TM-B

Device Management – TimeSynchronization-A DM-TS-A

Alarm and event management

Scheduling

Trending

Device management

Page 71: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

71/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Device Management – TimeSynchronization-B DM-TS-B

Device Management – UTCTimeSynchronization-A DM-UTC-A

Device Management – UTCTimeSynchronization-B DM-UTC-B

Device Management – ReinitializeDevice-A DM-RD-A

Device Management – ReinitializeDevice-B DM-RD-B

Device Management – Backup and Restore-A DM-BR-A

Device Management – Backup and Restore-B DM-BR-B

Device Management – Restart-A DM-R-A

Device Management – Restart-B DM-R-B

Device Management – List Manipulation-A DM-LM-A

Device Management – List Manipulation-B DM-LM-B

Device Management – Object Creation and Deletion-A DM-OCD-A

Device Management – Object Creation and Deletion-B DM-OCD-B

Device Management – Virtual Terminal-A DM-VT-A

Device Management – Virtual Terminal-B DM-VT-B

Device Management – Automatic Network Mapping-A DM-ANM-A

Device Management – Automatic Device Mapping-A DM-ADM-A

Device Management – Automatic Time Synchronization-A DM-ATS-A

Device Management – Manual Time Synchronization-A DM-MTS-A

Network Management – Connection Establishment-A NM-CE-A

Network Management – Connection Establishment-B NM-CE-B

Network Management – Router Configuration-A NM-RC-A

Network Management – Router Configuration-B NM-RC-B

Device management

Network management

Page 72: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

72/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

4.4 Standard object types supported

Only the device object is supported.

Properties Supported Readable/ Writeable

Object_Identifier R

Object_Name R

Object_Type R

System_Status R

Vendor_Name R

Vendor_Identifier R

Model_Name R

Firmware_Revision R

Application_Software_Version R

Location R

Description R

Protocol_Version R

Protocol_Revision R

Protocol_Services_Supported R

Protocol_Object_Types_Supported R

Object_List R

Structured_Object_List R

Max_APDU_Length_Accepted R

Segmentation_Supported R

Max_Segments_Accepted R

VT_Classes_Supported R

Active_VT_Sessions R

Local_Time R

Local_Date R

UTC_Offset R

Daylight_Savings_Status R

APDU_Segment_Timeout R

APDU_Timeout R

Number_Of_APDU_Retries R

List_Of_Session_Keys R

Time_Synchronization_Recipients W

Max_Master R

Max_Info_Frames R

Device_Address_Binding R

Database_Revision R

Configuration_Files R

Last_Restore_Time R

Backup_Failure_Timeout R

Active_COV_Subscriptions R

Slave_Proxy_Enable R

Manual_Slave_Adress_Binding R

Device

Page 73: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

73/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Properties Supported Readable/ Writeable

Auto_Slave_Discovery R

Slave_Address_Binding R

Last_Restart_Reason R

Time_Of_Device_Restart R

Restart_Notification_Recipients R

UTC_Time_Synchronization_Recipients W

Time_Synchronization_Interval R

Align_Intervals R

Interval_Offset R

Serial_Number R

Profile_Name R

Page 74: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

74/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

4.5 Client supported object types Object type Supported Can be created

dynamically Can be deleted dynamically

Analog Input

Analog Output

Analog Value

Binary Input

Binary Output

Binary Value

Calendar

Command

Device

Event Enrollment

File

Group

Loop

Multi-State Input

Multi-State Output

Notification Class

Program

Schedule

Averaging

Multi-State Value

Trend Log

Life-Safety-Point

Life-Safety-Zone

Accumulator

Pulse-Converter

Event Log

Global Group

Trend Log Multiple

Load Control

Structured-View

Access Door

Access Credential

Access Point

Access Rights

Access User

Access Zone

Credential Data Input

Network Security

Bitstring Value

Characterstring Value

Page 75: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

75/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Object type Supported Can be created dynamically

Can be deleted dynamically

Date Pattern Value Date Value Datetime Pattern Value Datetime Value Integer Value Large Analog Value Octetstring Value Positive Integer Value Time Pattern Value Time Value Notification Forwarder Alert Enrollment

Page 76: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

76/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

4.6 Segmentation capability

Able to transmit segmented messages Window size 4

Able to receive segmented messages Window size 4

4.7 Data Link Layer options

BACnet IP, (Annex J)

BACnet IP, (Annex J), Foreign Device

ISO 8802-3, Ethernet (Clause 7)

ANSI/ATA 878.1, 2.5 Mb. ARCNET (Clause 8)

ANSI/ATA 878.1, RS-485 ARCNET (Clause 8), baud rate(s)

MS/TP master (Clause 9), baud rate(s)

MS/TP slave (Clause 9), baud rate(s)

Point-To-Point, EIA 232 (Clause 10), baud rate(s) : Max. 38400

Point-To-Point, modem, (Clause 10), baud rate(s) : Max. 38400

LonTalk, (Clause 11), medium: : TP/FT-10

Other

4.8 Device address binding

Is static device binding supported? Yes No

4.9 Networking options

Router, Clause 6

Annex H, BACnet Tunnelling Router over IP

BACnet/IP Broadcast Management Device (BBMD)

Does the BBMD support registrations by Foreign Devices? Yes No

4.10 Character sets supported

Indicating support for multiple character sets does not imply that they can all be supported simultaneously.

UTF-8 IBM / Microsoft DBCS ISO 8859-1

ISO 10646 (UCS-2) ISO 10646 (UCS-4) JIS C 6226

Page 77: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

77/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

5 Desigo PXM20 Operator Unit

Date : 21 June 2013 Vendor name : Siemens Building Technologies (Vendor ID 7) Product name : Desigo PX automation station Product model number : PXM20, PXM20-E BACnet protocol version : 1.12 Application software version – Firmware revision : V5.10

5.1 Product description

The Desigo PXM20 operator unit ensures the convenient display and operation of Desigo PXC automation stations via BACnet network communication. The graphics based display with clear text and direct access via the keyboard ensures a most user-friendly operation.

All values visible in the system can be displayed in accordance with the defined operator profile. Typical displays: display of current values, set point and parameter settings, maintenance and error messages, alarm lists and single alarm messages with acknowledgement option and/or reset, definition of time schedulers (7-day schedules and exception programs), plant switching, login and password inputs. An integrated common alarm message system with acoustic and visual indication is provided.

5.2 BACnet standardized device profile (Annex L)

BACnet Advanced Workstation (B-AWS)

BACnet Operator Workstation (B-OWS)

BACnet Operator Display (B-OD)

BACnet Building Controller (B-BC)

BACnet Advanced Application Controller (B-AAC)

BACnet Application Specific Controller (B-ASC)

BACnet Smart Sensor (B-SS)

BACnet Smart Actuator (B-SA)

Page 78: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

78/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

5.3 BACnet interoperability building blocks supported (Annex K)

Data Sharing – ReadProperty-A DS-RP-A

Data Sharing – ReadProperty-B DS-RP-B

Data Sharing – ReadPropertyMultiple-A DS-RPM-A

Data Sharing – ReadPropertyMultiple-B DS-RPM-B

Data Sharing – WriteProperty-A DS-WP-A

Data Sharing – WriteProperty-B DS-WP-B

Data Sharing – WritePropertyMultiple-A DS-WPM-A

Data Sharing – WritePropertyMultiple-B DS-WPM-B

Data Sharing – ChangeofValue -A DS-COV-A

Data Sharing – ChangeofValue -B DS-COV-B

Data Sharing – ChangeofValueProperty -A DS-COVP-A

Data Sharing – ChangeofValueProperty -B DS-COVP-B

Data Sharing – ChangeofValue-Unsolicited-A DS-COVU-A

Data Sharing – ChangeofValue-Unsolicited-B DS-COVU-B

Data Sharing – View-A DS-V-A

Data Sharing – Advanced View-A DS-AV-A

Data Sharing – Modify-A DS-M-A

Data Sharing – Advanced Modify-A DS-AM-A

Alarm and Event – Notification-A AE-N-A

Alarm and Event – Notification Internal-B AE-N-I-B

Alarm and Event – Notification External-B AE-N-E-B

Alarm and Event – ACK-A AE-ACK-A

Alarm and Event – ACK-B AE-ACK-B

Alarm and Event – Alarm Summary-A AE-ASUM-A

Alarm and Event – Alarm Summary-B AE-ASUM-B

Alarm and Event – Enrollment Summary-A AE-ESUM-A

Alarm and Event – Enrollment Summary-B AE-ESUM-B

Alarm and Event – Information-A AE-INFO-A

Alarm and Event – Information-B AE-INFO-B

Alarm and Event – LifeSafety-A AE-LS-A

Alarm and Event – LifeSafety-B AE-LS-B

Alarm and Event – View Notifications-A AE-VN-A

Alarm and Event – Advanced View Notifications-A AE-AVN-A

Alarm and Event – View and Modify-A AE-VM-A

Alarm and Event – Advanced View and Modify-A AE-AVM-A

Alarm and Event – Alarm Summary View-A AE-AS-A

Alarm and Event – Event Log View-A AE-ELV-A

Alarm and Event – Event Log View and Modify-A AE-ELVM-A

Alarm and Event – Event Log-Internal-B AE-EL-I-B

Alarm and Event – Event Log-External-B AE-EL-E-B

Data sharing

Alarm and event management

Page 79: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

79/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Scheduling – A SCHED-A

Scheduling – Internal-B SCHED-I-B

Scheduling – External-B SCHED-E-B

Scheduling – Advanced View Modify-A SCH-AVM-A

Scheduling – View Modify-A SCH-VM-A

Scheduling – Weekly Schedule-A SCH-WS-A

Scheduling – Weekly Schedule Internal-B SCH-WS-I-B

Scheduling – Readable-B SCH-R-B

The A device is capable to present and modify Schedule objects of the forms defined in Protocol_Revision 0 and Protocol_Revision 4.

Trending – Viewing and Modifying Trends-A T-VMT-A

Trending – Viewing and Modifying Internal-B T-VM-I-B

Trending – Viewing and Modifying External-B T-VM-E-B

Trending – Viewing and Modifying Multiple Values-A T-VMMV-A

Trending – Viewing and Modifying Multiple Values Internal-B T-VMMV-I-B

Trending – Viewing and Modifying Multiple Values External -B T-VMMV-E-B

Trending – Automated Multiple Value Retrieval-A T-AMVR-A

Trending – Automated Multiple Value Retrieval-B T-AMVR-B

Trending – View-A T-V-A

Trending – Advanced View and Modify-A T-AVM-A

Trending – Archival-A T-A-A

Trending – Automated Trend Retrieval-A T-ATR-A

Trending – Automated Trend Retrieval-B T-ATR-B

Scheduling

Trending

Page 80: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

80/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Device Management – Dynamic Device Binding-A DM-DDB-A

Device Management – Dynamic Device Binding-B DM-DDB-B

Device Management – Dynamic Object Binding-A DM-DOB-A

Device Management – Dynamic Object Binding-B DM-DOB-B

Device Management – DeviceCommunicationControl-A DM-DCC-A

Device Management – DeviceCommunicationControl-B DM-DCC-B

Device Management – Private Transfer-A DM-PT-A

Device Management – Private Transfer-B DM-PT-B

Device Management – Text Message-A DM-TM-A

Device Management – Text Message-B DM-TM-B

Device Management – TimeSynchronization-A DM-TS-A

Device Management – TimeSynchronization-B DM-TS-B

Device Management – UTCTimeSynchronization-A DM-UTC-A

Device Management – UTCTimeSynchronization-B DM-UTC-B

Device Management – ReinitializeDevice-A DM-RD-A

Device Management – ReinitializeDevice-B DM-RD-B

Device Management – Backup and Restore-A DM-BR-A

Device Management – Backup and Restore-B DM-BR-B

Device Management – Restart-A DM-R-A

Device Management – Restart-B DM-R-B

Device Management – List Manipulation-A DM-LM-A

Device Management – List Manipulation-B DM-LM-B

Device Management – Object Creation and Deletion-A DM-OCD-A

Device Management – Object Creation and Deletion-B DM-OCD-B

Device Management – Virtual Terminal-A DM-VT-A

Device Management – Virtual Terminal-B DM-VT-B

Device Management – Automatic Network Mapping-A DM-ANM-A

Device Management – Automatic Device Mapping-A DM-ADM-A

Device Management – Automatic Time Synchronization-A DM-ATS-A

Device Management – Manual Time Synchronization-A DM-MTS-A

Network Management – Connection Establishment-A NM-CE-A

Network Management – Connection Establishment-B NM-CE-B

Network Management – Router Configuration-A NM-RC-A

Network Management – Router Configuration-B NM-RC-B

Device management

Network management

Page 81: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

81/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

5.4 Standard object types supported

Object type Supported Can be created dynamically

Can be deleted dynamically

Analog Input Analog Output Analog Value Binary Input Binary Output Binary Value Calendar Command Device Event Enrollment File Group Loop Multi-State Input Multi-State Output Notification Class Program Schedule Averaging Multi-State Value Trend Log Life-Safety-Point Life-Safety-Zone Accumulator Pulse-Converter Event Log Global Group Trend Log Multiple Load Control Structured-View Access Door (unassigned) Access Credential Access Point Access Rights Access User Access Zone Credential Data Input Network Security Bitstring Value Characterstring Value

Page 82: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

82/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Object type Supported Can be created dynamically

Can be deleted dynamically

Date Pattern Value Date Value Datetime Pattern Value Datetime Value Integer Value Large Analog Value Octetstring Value Positive Integer Value Time Pattern Value Time Value

Page 83: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

83/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Properties supported Readable/ Writable

Range restrictions

Object_Identifier R

Object_Name R

Object_Type R

System_Status R

Vendor_Name R

Vendor_Identifier R

Model_Name R

Firmware_Revision R

Application_Software_Version R

Location R

Description R

Protocol_Version R

Protocol_Revision R

Protocol_Services_Supported R

Protocol_Object_Types_Supported R

Object_List

Structured_Object_List

Max_APDU_Length_Accepted R

Segmentation_Supported R

Max_Segments_Accepted R

VT_Classes_Supported

Active_VT_Sessions

Local_Time

Local_Date

UTC_Offset

Daylight_Savings_Status

APDU_Segment_Timeout R

APDU_Timeout R

Number_Of_APDU_Retries R

List_Of_Session_Keys

Time_Synchronization_Recipients

Max_Master

Max_Info_Frames

Device_Address_Binding R

Database_Revision R

Configuration_Files

Last_Restore_Time

Backup_Failure_Timeout

Active_COV_Subscriptions

Slave_Proxy_Enable

Manual_Slave_Adress_Binding

Auto_Slave_Discovery

Slave_Address_Binding

Device

Page 84: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

84/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Properties supported Readable/ Writable

Range restrictions

Last_Restart_Reason

Time_Of_Device_Restart

Restart_Notification_Recipients

UTC_Time_Synchronization_Recipients

Time_Synchronization_Interval

Align_Intervals

Interval_Offset

Profile_Name

Device

Page 85: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

85/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

5.5 Client supported object types Object type Supported Can be created

dynamically Can be deleted dynamically

Analog Input Analog Output Analog Value Binary Input Binary Output Binary Value Calendar Command Device Event Enrollment File Group Loop Multi-State Input Multi-State Output Notification Class Program Schedule Averaging Multi-State Value Trend Log Life-Safety-Point Life-Safety-Zone Accumulator Pulse-Converter Event Log Global Group Trend Log Multiple Load Control Structured-View Access Door (unassigned) Access Credential Access Point Access Rights Access User Access Zone Credential Data Input Network Security Bitstring Value Characterstring Value

Page 86: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

86/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Object type Supported Can be created dynamically

Can be deleted dynamically

Date Pattern Value Date Value Datetime Pattern Value Datetime Value Integer Value Large Analog Value Octetstring Value Positive Integer Value Time Pattern Value Time Value

Page 87: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

87/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

5.6 Segmentation capability

Able to transmit segmented messages Window size 4

Able to receive segmented messages Window size 4

5.7 Data Link Layer options

BACnet IP, (Annex J)

BACnet IP, (Annex J), Foreign Device

ISO 8802-3, Ethernet (Clause 7)

ANSI/ATA 878.1, 2.5 Mb. ARCNET (Clause 8)

ANSI/ATA 878.1, RS-485 ARCNET (Clause 8), baud rate(s)

MS/TP master (Clause 9), baud rate(s)

MS/TP slave (Clause 9), baud rate(s)

Point-To-Point, EIA 232 (Clause 10), baud rate(s) : Max. 38400

Point-To-Point, modem, (Clause 10), baud rate(s) : Max. 38400

LonTalk, (Clause 11), medium: : TP/FT-10

Other

5.8 Device address binding

Is static device binding supported? Yes No

5.9 Networking options

Router, Clause 6

Annex H, BACnet Tunnelling Router over IP

BACnet/IP Broadcast Management Device (BBMD)

Does the BBMD support registrations by Foreign Devices? Yes No

5.10 Character sets supported

Indicating support for multiple character sets does not imply that they can all be supported simultaneously.

UTF-8 IBM / Microsoft DBCS ISO 8859-1

ISO 10646 (UCS-2) ISO 10646 (UCS-4) JIS C 6226

• Outgoing character strings are communicated in the selected character set. • Incoming character strings with character sets other than ISO 8859-1 will be mapped

to ISO8859-1 internally. If the mapping is not possible, the character string is not accepted.

Note

Page 88: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

88/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

6 Desigo PXG3.M BACnet Router

Date : 21 March 2013

Vendor name : Siemens Building Technologies (Vendor ID 7)

Product name : Desigo PX BACnet Router

Product model number : PXG3.M

BACnet protocol version : 1.10 Application software version : –

Firmware revision : V5.10

6.1 Product description

The DESIGO PXG3-M BACnet router connects a BACnet MS/TP channel to a BACnet/IP network. In addition, the BACnet router supports the functionality of the BBMD (BACnet Broadcast Management Device) in order to distribute the BACnet broadcast messages across the IP routers including foreign device support. The configuration can be performed through the built-in Web server using a standard Web browser.

6.2 BACnet standardized device profile (Annex L)

BACnet Advanced Workstation (B-AWS)

BACnet Operator Workstation (B-OWS)

BACnet Operator Display (B-OD)

BACnet Building Controller (B-BC)

BACnet Advanced Application Controller (B-AAC)

BACnet Application Specific Controller (B-ASC)

BACnet Smart Sensor (B-SS)

BACnet Smart Actuator (B-SA)

Page 89: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

89/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

6.3 BACnet interoperability building blocks supported (Annex K)

Data Sharing – ReadProperty-A DS-RP-A

Data Sharing – ReadProperty-B DS-RP-B

Data Sharing – ReadPropertyMultiple-A DS-RPM-A

Data Sharing – ReadPropertyMultiple-B DS-RPM-B

Data Sharing – WriteProperty-A DS-WP-A

Data Sharing – WriteProperty-B DS-WP-B

Data Sharing – WritePropertyMultiple-A DS-WPM-A

Data Sharing – WritePropertyMultiple-B DS-WPM-B

Data Sharing – ChangeofValue -A DS-COV-A

Data Sharing – ChangeofValue -B DS-COV-B

Data Sharing – ChangeofValueProperty -A DS-COVP-A

Data Sharing – ChangeofValueProperty -B DS-COVP-B

Data Sharing – ChangeofValue-Unsolicited-A DS-COVU-A

Data Sharing – ChangeofValue-Unsolicited-B DS-COVU-B

Data Sharing – View-A DS-V-A

Data Sharing – Advanced View-A DS-AV-A

Data Sharing – Modify-A DS-M-A

Data Sharing – Advanced Modify-A DS-AM-A

DS-COV-B is not supported because the supported objects of this device do not have a primary value

Alarm and Event – Notification-A AE-N-A

Alarm and Event – Notification Internal-B AE-N-I-B

Alarm and Event – Notification External-B AE-N-E-B

Alarm and Event – ACK-A AE-ACK-A

Alarm and Event – ACK-B AE-ACK-B

Alarm and Event – Alarm Summary-A AE-ASUM-A

Alarm and Event – Alarm Summary-B AE-ASUM-B

Alarm and Event – Enrollment Summary-A AE-ESUM-A

Alarm and Event – Enrollment Summary-B AE-ESUM-B

Alarm and Event – Information-A AE-INFO-A

Alarm and Event – Information-B AE-INFO-B

Alarm and Event – LifeSafety-A AE-LS-A

Alarm and Event – LifeSafety-B AE-LS-B

Alarm and Event – View Notifications-A AE-VN-A

Alarm and Event – Advanced View Notifications-A AE-AVN-A

Alarm and Event – View and Modify-A AE-VM-A

Alarm and Event – Advanced View and Modify-A AE-AVM-A

Alarm and Event – Alarm Summary View-A AE-AS-A

Alarm and Event – Event Log View-A AE-ELV-A

Alarm and Event – Event Log View and Modify-A AE-ELVM-A

Alarm and Event – Event Log-Internal-B AE-EL-I-B

Alarm and Event – Event Log-External-B AE-EL-E-B

Data sharing

Alarm and event management

Page 90: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

90/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Scheduling – A SCHED-A

Scheduling – Internal-B SCHED-I-B

Scheduling – External-B SCHED-E-B

Scheduling – Advanced View Modify-A SCH-AVM-A

Scheduling – View Modify-A SCH-VM-A

Scheduling – Weekly Schedule-A SCH-WS-A

Scheduling – Weekly Schedule Internal-B SCH-WS-I-B

Scheduling – Readable-B SCH-R-B

Trending – Viewing and Modifying Trends-A T-VMT-A

Trending – Viewing and Modifying Internal-B T-VM-I-B

Trending – Viewing and Modifying External-B T-VM-E-B

Trending – Viewing and Modifying Multiple Values-A T-VMMV-A

Trending – Viewing and Modifying Multiple Values Internal-B T-VMMV-I-B

Trending – Viewing and Modifying Multiple Values External -B T-VMMV-E-B

Trending – Automated Multiple Value Retrieval-A T-AMVR-A

Trending – Automated Multiple Value Retrieval-B T-AMVR-B

Trending – View-A T-V-A

Trending – Advanced View and Modify-A T-AVM-A

Trending – Archival-A T-A-A

Trending – Automated Trend Retrieval-A T-ATR-A

Trending – Automated Trend Retrieval-B T-ATR-B

Scheduling

Trending

Page 91: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

91/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Device Management – Dynamic Device Binding-A DM-DDB-A

Device Management – Dynamic Device Binding-B DM-DDB-B

Device Management – Dynamic Object Binding-A DM-DOB-A

Device Management – Dynamic Object Binding-B DM-DOB-B

Device Management – DeviceCommunicationControl-A DM-DCC-A

Device Management – DeviceCommunicationControl-B DM-DCC-B

Device Management – Private Transfer-A DM-PT-A

Device Management – Private Transfer-B DM-PT-B

Device Management – Text Message-A DM-TM-A

Device Management – Text Message-B DM-TM-B

Device Management – TimeSynchronization-A DM-TS-A

Device Management – TimeSynchronization-B DM-TS-B

Device Management – UTCTimeSynchronization-A DM-UTC-A

Device Management – UTCTimeSynchronization-B DM-UTC-B

Device Management – ReinitializeDevice-A DM-RD-A

Device Management – ReinitializeDevice-B DM-RD-B

Device Management – Backup and Restore-A DM-BR-A

Device Management – Backup and Restore-B DM-BR-B

Device Management – Restart-A DM-R-A

Device Management – Restart-B DM-R-B

Device Management – List Manipulation-A DM-LM-A

Device Management – List Manipulation-B DM-LM-B

Device Management – Object Creation and Deletion-A DM-OCD-A

Device Management – Object Creation and Deletion-B DM-OCD-B

Device Management – Virtual Terminal-A DM-VT-A

Device Management – Virtual Terminal-B DM-VT-B

Device Management – Automatic Network Mapping-A DM-ANM-A

Device Management – Automatic Device Mapping-A DM-ADM-A

Device Management – Automatic Time Synchronization-A DM-ATS-A

Device Management – Manual Time Synchronization-A DM-MTS-A

Network Management – Connection Establishment-A NM-CE-A

Network Management – Connection Establishment-B NM-CE-B

Network Management – Router Configuration-A NM-RC-A

Network Management – Router Configuration-B NM-RC-B

Device management

Network management

Page 92: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

92/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

6.4 Standard object types supported

Object type Supported Can be created dynamically

Can be deleted dynamically

Analog Input Analog Output Analog Value Binary Input Binary Output Binary Value Calendar Command Device Event Enrollment File Group Loop Multi-State Input Multi-State Output Notification Class Program Schedule Averaging Multi-State Value Trend Log Life-Safety-Point Life-Safety-Zone Accumulator Pulse-Converter Event Log Global Group Trend Log Multiple Load Control Structured-View Access Door (unassigned) Access Credential Access Point Access Rights Access User Access Zone Credential Data Input Network Security Bitstring Value Characterstring Value

Page 93: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

93/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Object type Supported Can be created dynamically

Can be deleted dynamically

Date Pattern Value Date Value Datetime Pattern Value Datetime Value Integer Value Large Analog Value Octetstring Value Positive Integer Value Time Pattern Value Time Value

Page 94: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

94/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Properties supported Readable/ Writable

Range restrictions

Object_Identifier R

Object_Name R

Object_Type R

System_Status R

Vendor_Name R

Vendor_Identifier R

Model_Name R

Firmware_Revision R

Application_Software_Version R

Location W

Description W

Protocol_Version R

Protocol_Revision R

Protocol_Services_Supported R

Protocol_Object_Types_Supported R

Object_List R

Structured_Object_List

Max_APDU_Length_Accepted R

Segmentation_Supported R

Max_Segments_Accepted R

VT_Classes_Supported

Active_VT_Sessions

Local_Time R

Local_Date R

UTC_Offset R

Daylight_Savings_Status R

APDU_Segment_Timeout R

APDU_Timeout R

Number_Of_APDU_Retries R

List_Of_Session_Keys

Time_Synchronization_Recipients

Max_Master R

Max_Info_Frames R

Device_Address_Binding R

Database_Revision R

Configuration_Files R

Last_Restore_Time R

Backup_Failure_Timeout W 0…65535

Backup_Preparation_Time R

Restore_Preparation_Time R

Restore_Completion_Time R

Backup_And_Restore_State R

Active_COV_Subscriptions R

Slave_Proxy_Enable W

Device

Page 95: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

95/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Manual_Slave_Adress_Binding W

Auto_Slave_Discovery W

Slave_Address_Binding R

Last_Restart_Reason R

Time_Of_Device_Restart R

Restart_Notification_Recipients W

UTC_Time_Synchronization_Recipients

Time_Synchronization_Interval

Align_Intervals

Interval_Offset

Profile_Name R

Properties supported Readable/

Writable Range restrictions

Object_Identifier R

Object_Name W

Object_Type R

Description W

File_Type R

File_Size W

Modification_Date R

Archive W

Read_Only R

File_Access_Method R

Record_Count

Profile_Name R

Device

File

Page 96: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

96/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

6.5 Segmentation capability

Able to transmit segmented messages Window size configurable

Able to receive segmented messages Window size configurable

6.6 Data Link Layer options

BACnet IP, (Annex J)

BACnet IP, (Annex J), Foreign Device

ISO 8802-3, Ethernet (Clause 7)

ANSI/ATA 878.1, 2.5 Mb. ARCNET (Clause 8)

ANSI/ATA 878.1, RS-485 ARCNET (Clause 8), baud rate(s)

MS/TP master (Clause 9), baud rate(s) : 9600 : 19200 : 38400 : 76800 : 115200

MS/TP slave (Clause 9), baud rate(s)

Point-To-Point, EIA 232 (Clause 10), baud rate(s) :

Point-To-Point, modem, (Clause 10), baud rate(s) :

LonTalk, (Clause 11), medium:

Other

6.7 Device address binding

Is static device binding supported? Yes No

6.8 Networking options

Router, Clause 6

Annex H, BACnet Tunnelling Router over IP

BACnet/IP Broadcast Management Device (BBMD)

Does the BBMD support registrations by Foreign Devices? Yes No

6.9 Character sets supported

Indicating support for multiple character sets does not imply that they can all be supported simultaneously.

UTF-8 IBM / Microsoft DBCS ISO 8859-1

ISO 10646 (UCS-2) ISO 10646 (UCS-4) JIS C 6226

Page 97: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

97/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

7 Desigo PXG3.L BACnet Router

Date : 21 March 2013

Vendor name : Siemens Building Technologies (Vendor ID 7)

Product name : Desigo PX BACnet Router

Product model number : PXG3.L

BACnet protocol version : 1.10 Application software version : –

Firmware revision : V5.10

7.1 Product description

The DESIGO PXG3-L BACnet router connects: - a BACnet MS/TP channel to a BACnet/IP network - a BACnet MS/TP channel to a BACnet/Lon network - a BACnet/Lon network to a BACnet/IP network

In addition, the BACnet router supports the functionality of the BBMD (BACnet Broadcast Management Device) in order to distribute the BACnet broadcast messages across the IP routers including foreign device support. The configuration can be performed through the built-in Web server using a standard Web browser.

7.2 BACnet standardized device profile (Annex L)

BACnet Advanced Workstation (B-AWS)

BACnet Operator Workstation (B-OWS)

BACnet Operator Display (B-OD)

BACnet Building Controller (B-BC)

BACnet Advanced Application Controller (B-AAC)

BACnet Application Specific Controller (B-ASC)

BACnet Smart Sensor (B-SS)

BACnet Smart Actuator (B-SA)

Page 98: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

98/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

7.3 BACnet interoperability building blocks supported (Annex K)

Data Sharing – ReadProperty-A DS-RP-A

Data Sharing – ReadProperty-B DS-RP-B

Data Sharing – ReadPropertyMultiple-A DS-RPM-A

Data Sharing – ReadPropertyMultiple-B DS-RPM-B

Data Sharing – WriteProperty-A DS-WP-A

Data Sharing – WriteProperty-B DS-WP-B

Data Sharing – WritePropertyMultiple-A DS-WPM-A

Data Sharing – WritePropertyMultiple-B DS-WPM-B

Data Sharing – ChangeofValue -A DS-COV-A

Data Sharing – ChangeofValue -B DS-COV-B

Data Sharing – ChangeofValueProperty -A DS-COVP-A

Data Sharing – ChangeofValueProperty -B DS-COVP-B

Data Sharing – ChangeofValue-Unsolicited-A DS-COVU-A

Data Sharing – ChangeofValue-Unsolicited-B DS-COVU-B

Data Sharing – View-A DS-V-A

Data Sharing – Advanced View-A DS-AV-A

Data Sharing – Modify-A DS-M-A

Data Sharing – Advanced Modify-A DS-AM-A

DS-COV-B is not supported because the supported objects of this device do not have a primary value

Alarm and Event – Notification-A AE-N-A

Alarm and Event – Notification Internal-B AE-N-I-B

Alarm and Event – Notification External-B AE-N-E-B

Alarm and Event – ACK-A AE-ACK-A

Alarm and Event – ACK-B AE-ACK-B

Alarm and Event – Alarm Summary-A AE-ASUM-A

Alarm and Event – Alarm Summary-B AE-ASUM-B

Alarm and Event – Enrollment Summary-A AE-ESUM-A

Alarm and Event – Enrollment Summary-B AE-ESUM-B

Alarm and Event – Information-A AE-INFO-A

Alarm and Event – Information-B AE-INFO-B

Alarm and Event – LifeSafety-A AE-LS-A

Alarm and Event – LifeSafety-B AE-LS-B

Alarm and Event – View Notifications-A AE-VN-A

Alarm and Event – Advanced View Notifications-A AE-AVN-A

Alarm and Event – View and Modify-A AE-VM-A

Alarm and Event – Advanced View and Modify-A AE-AVM-A

Alarm and Event – Alarm Summary View-A AE-AS-A

Alarm and Event – Event Log View-A AE-ELV-A

Alarm and Event – Event Log View and Modify-A AE-ELVM-A

Alarm and Event – Event Log-Internal-B AE-EL-I-B

Alarm and Event – Event Log-External-B AE-EL-E-B

Data sharing

Alarm and event management

Page 99: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

99/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Scheduling – A SCHED-A

Scheduling – Internal-B SCHED-I-B

Scheduling – External-B SCHED-E-B

Scheduling – Advanced View Modify-A SCH-AVM-A

Scheduling – View Modify-A SCH-VM-A

Scheduling – Weekly Schedule-A SCH-WS-A

Scheduling – Weekly Schedule Internal-B SCH-WS-I-B

Scheduling – Readable-B SCH-R-B

Trending – Viewing and Modifying Trends-A T-VMT-A

Trending – Viewing and Modifying Internal-B T-VM-I-B

Trending – Viewing and Modifying External-B T-VM-E-B

Trending – Viewing and Modifying Multiple Values-A T-VMMV-A

Trending – Viewing and Modifying Multiple Values Internal-B T-VMMV-I-B

Trending – Viewing and Modifying Multiple Values External -B T-VMMV-E-B

Trending – Automated Multiple Value Retrieval-A T-AMVR-A

Trending – Automated Multiple Value Retrieval-B T-AMVR-B

Trending – View-A T-V-A

Trending – Advanced View and Modify-A T-AVM-A

Trending – Archival-A T-A-A

Trending – Automated Trend Retrieval-A T-ATR-A

Trending – Automated Trend Retrieval-B T-ATR-B

Scheduling

Trending

Page 100: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

100/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Device Management – Dynamic Device Binding-A DM-DDB-A

Device Management – Dynamic Device Binding-B DM-DDB-B

Device Management – Dynamic Object Binding-A DM-DOB-A

Device Management – Dynamic Object Binding-B DM-DOB-B

Device Management – DeviceCommunicationControl-A DM-DCC-A

Device Management – DeviceCommunicationControl-B DM-DCC-B

Device Management – Private Transfer-A DM-PT-A

Device Management – Private Transfer-B DM-PT-B

Device Management – Text Message-A DM-TM-A

Device Management – Text Message-B DM-TM-B

Device Management – TimeSynchronization-A DM-TS-A

Device Management – TimeSynchronization-B DM-TS-B

Device Management – UTCTimeSynchronization-A DM-UTC-A

Device Management – UTCTimeSynchronization-B DM-UTC-B

Device Management – ReinitializeDevice-A DM-RD-A

Device Management – ReinitializeDevice-B DM-RD-B

Device Management – Backup and Restore-A DM-BR-A

Device Management – Backup and Restore-B DM-BR-B

Device Management – Restart-A DM-R-A

Device Management – Restart-B DM-R-B

Device Management – List Manipulation-A DM-LM-A

Device Management – List Manipulation-B DM-LM-B

Device Management – Object Creation and Deletion-A DM-OCD-A

Device Management – Object Creation and Deletion-B DM-OCD-B

Device Management – Virtual Terminal-A DM-VT-A

Device Management – Virtual Terminal-B DM-VT-B

Device Management – Automatic Network Mapping-A DM-ANM-A

Device Management – Automatic Device Mapping-A DM-ADM-A

Device Management – Automatic Time Synchronization-A DM-ATS-A

Device Management – Manual Time Synchronization-A DM-MTS-A

Network Management – Connection Establishment-A NM-CE-A

Network Management – Connection Establishment-B NM-CE-B

Network Management – Router Configuration-A NM-RC-A

Network Management – Router Configuration-B NM-RC-B

Device management

Network management

Page 101: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

101/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

7.4 Standard object types supported

Object type Supported Can be created dynamically

Can be deleted dynamically

Analog Input Analog Output Analog Value Binary Input Binary Output Binary Value Calendar Command Device Event Enrollment File Group Loop Multi-State Input Multi-State Output Notification Class Program Schedule Averaging Multi-State Value Trend Log Life-Safety-Point Life-Safety-Zone Accumulator Pulse-Converter Event Log Global Group Trend Log Multiple Load Control Structured-View Access Door (unassigned) Access Credential Access Point Access Rights Access User Access Zone Credential Data Input Network Security Bitstring Value Characterstring Value

Page 102: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

102/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Object type Supported Can be created dynamically

Can be deleted dynamically

Date Pattern Value Date Value Datetime Pattern Value Datetime Value Integer Value Large Analog Value Octetstring Value Positive Integer Value Time Pattern Value Time Value

Properties supported Readable/ Writable

Range restrictions

Object_Identifier R

Object_Name R

Object_Type R

System_Status R

Vendor_Name R

Vendor_Identifier R

Model_Name R

Firmware_Revision R

Application_Software_Version R

Location W

Description W

Protocol_Version R

Protocol_Revision R

Protocol_Services_Supported R

Protocol_Object_Types_Supported R

Object_List R

Structured_Object_List

Max_APDU_Length_Accepted R

Segmentation_Supported R

Max_Segments_Accepted R

VT_Classes_Supported

Active_VT_Sessions

Local_Time R

Local_Date R

UTC_Offset R

Daylight_Savings_Status R

APDU_Segment_Timeout R

APDU_Timeout R

Number_Of_APDU_Retries R

List_Of_Session_Keys

Device

Page 103: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

103/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Properties supported Readable/ Writable

Range restrictions

Time_Synchronization_Recipients

Max_Master R

Max_Info_Frames R

Device_Address_Binding R

Database_Revision R

Configuration_Files R

Last_Restore_Time R

Backup_Failure_Timeout W 0...65535

Backup_Preparation_Time R

Restore_Preparation_Time R

Restore_Completion_Time R

Backup_And_Restore_State R

Active_COV_Subscriptions R

Slave_Proxy_Enable W

Manual_Slave_Adress_Binding W

Auto_Slave_Discovery W

Slave_Address_Binding R

Last_Restart_Reason R

Time_Of_Device_Restart R

Restart_Notification_Recipients W

UTC_Time_Synchronization_Recipients

Time_Synchronization_Interval

Align_Intervals

Interval_Offset

Profile_Name R

Properties supported Readable/ Writable

Range restrictions

Object_Identifier R

Object_Name W

Object_Type R

Description W

File_Type R

File_Size W

Modification_Date R

Archive W

Read_Only R

File_Access_Method R

Record_Count

Profile_Name R

Device

File

Page 104: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

104/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

7.5 Segmentation capability

Able to transmit segmented messages Window size configurable

Able to receive segmented messages Window size configurable

7.6 Data Link Layer options

BACnet IP, (Annex J)

BACnet IP, (Annex J), Foreign Device

ISO 8802-3, Ethernet (Clause 7)

ANSI/ATA 878.1, 2.5 Mb. ARCNET (Clause 8)

ANSI/ATA 878.1, RS-485 ARCNET (Clause 8), baud rate(s)

MS/TP master (Clause 9), baud rate(s) : 9600 : 19200 : 38400 : 76800 : 115200

MS/TP slave (Clause 9), baud rate(s)

Point-To-Point, EIA 232 (Clause 10), baud rate(s) :

Point-To-Point, modem, (Clause 10), baud rate(s)

LonTalk, (Clause 11), medium: : TP/FT-10

Other

7.7 Device address binding

Is static device binding supported? Yes No

7.8 Networking options

Router, Clause 6

Annex H, BACnet Tunnelling Router over IP

BACnet/IP Broadcast Management Device (BBMD)

Does the BBMD support registrations by Foreign Devices? Yes No

7.9 Character sets supported

Indicating support for multiple character sets does not imply that they can all be supported simultaneously.

UTF-8 IBM / Microsoft DBCS ISO 8859-1

ISO 10646 (UCS-2) ISO 10646 (UCS-4) JIS C 6226

Page 105: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

105/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

8 SX Open Date : 22 February 2012 Vendor name : Siemens Building Technologies (Vendor ID 7) Product name : Desigo SX-Open Product model number : V2.1 BACnet protocol version : 1.5 Application software version : – Firmware revision : 2.01.xx

8.1 Product description

SX Open is a generic framework to develop gateways from several field buses to BACnet in an efficient way. SX Open provides server-functionality but act as BACnet client as well for real peer-to-peer communication.

8.2 BACnet standardized device profile (Annex L)

BACnet Advanced Workstation (B-AWS)

BACnet Operator Workstation (B-OWS)

BACnet Operator Display (B-OD)

BACnet Building Controller (B-BC)

BACnet Advanced Application Controller (B-AAC)

BACnet Application Specific Controller (B-ASC)

BACnet Smart Sensor (B-SS)

BACnet Smart Actuator (B-SA)

Page 106: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

106/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

8.3 BACnet interoperability building blocks supported (Annex K)

Data Sharing – ReadProperty-A DS-RP-A

Data Sharing – ReadProperty-B DS-RP-B

Data Sharing – ReadPropertyMultiple-A DS-RPM-A

Data Sharing – ReadPropertyMultiple-B DS-RPM-B

Data Sharing – WriteProperty-A DS-WP-A

Data Sharing – WriteProperty-B DS-WP-B

Data Sharing – WritePropertyMultiple-A DS-WPM-A

Data Sharing – WritePropertyMultiple-B DS-WPM-B

Data Sharing – ChangeofValue -A DS-COV-A

Data Sharing – ChangeofValue -B DS-COV-B

Data Sharing – ChangeofValueProperty -A DS-COVP-A

Data Sharing – ChangeofValueProperty -B DS-COVP-B

Data Sharing – ChangeofValue-Unsolicited-A DS-COVU-A

Data Sharing – ChangeofValue-Unsolicited-B DS-COVU-B

Data Sharing – View-A DS-V-A

Data Sharing – Advanced View-A DS-AV-A

Data Sharing – Modify-A DS-M-A

Data Sharing – Advanced Modify-A DS-AM-A

Alarm and Event – Notification-A AE-N-A

Alarm and Event – Notification Internal-B AE-N-I-B

Alarm and Event – Notification External-B AE-N-E-B

Alarm and Event – ACK-A AE-ACK-A

Alarm and Event – ACK-B AE-ACK-B

Alarm and Event – Alarm Summary-A AE-ASUM-A

Alarm and Event – Alarm Summary-B AE-ASUM-B

Alarm and Event – Enrollment Summary-A AE-ESUM-A

Alarm and Event – Enrollment Summary-B AE-ESUM-B

Alarm and Event – Information-A AE-INFO-A

Alarm and Event – Information-B AE-INFO-B

Alarm and Event – LifeSafety-A AE-LS-A

Alarm and Event – LifeSafety-B AE-LS-B

Alarm and Event – View Notifications-A AE-VN-A

Alarm and Event – Advanced View Notifications-A AE-AVN-A

Alarm and Event – View and Modify-A AE-VM-A

Alarm and Event – Advanced View and Modify-A AE-AVM-A

Alarm and Event – Alarm Summary View-A AE-AS-A

Alarm and Event – Event Log View-A AE-ELV-A

Alarm and Event – Event Log View and Modify-A AE-ELVM-A

Alarm and Event – Event Log-Internal-B AE-EL-I-B

Alarm and Event – Event Log-External-B AE-EL-E-B

Data sharing

Alarm and event management

Page 107: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

107/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Scheduling – A SCHED-A

Scheduling – Internal-B SCHED-I-B

Scheduling – External-B SCHED-E-B

Scheduling – Advanced View Modify-A SCH-AVM-A

Scheduling – View Modify-A SCH-VM-A

Scheduling – Weekly Schedule-A SCH-WS-A

Scheduling – Weekly Schedule Internal-B SCH-WS-I-B

Scheduling – Readable-B SCH-R-B

Trending – Viewing and Modifying Trends-A T-VMT-A

Trending – Viewing and Modifying Internal-B T-VM-I-B

Trending – Viewing and Modifying External-B T-VM-E-B

Trending – Viewing and Modifying Multiple Values-A T-VMMV-A

Trending – Viewing and Modifying Multiple Values Internal-B T-VMMV-I-B

Trending – Viewing and Modifying Multiple Values External -B T-VMMV-E-B

Trending – Automated Multiple Value Retrieval-A T-AMVR-A

Trending – Automated Multiple Value Retrieval-B T-AMVR-B

Trending – View-A T-V-A

Trending – Advanced View and Modify-A T-AVM-A

Trending – Archival-A T-A-A

Trending – Automated Trend Retrieval-A T-ATR-A

Trending – Automated Trend Retrieval-B T-ATR-B

Device Management – Dynamic Device Binding-A DM-DDB-A

Device Management – Dynamic Device Binding-B DM-DDB-B

Device Management – Dynamic Object Binding-A DM-DOB-A

Device Management – Dynamic Object Binding-B DM-DOB-B

Device Management – DeviceCommunicationControl-A DM-DCC-A

Device Management – DeviceCommunicationControl-B DM-DCC-B

Device Management – Private Transfer-A DM-PT-A

Device Management – Private Transfer-B DM-PT-B

Device Management – Text Message-A DM-TM-A

Device Management – Text Message-B DM-TM-B

Device Management – TimeSynchronization-A DM-TS-A

Device Management – TimeSynchronization-B DM-TS-B

Device Management – UTCTimeSynchronization-A DM-UTC-A

Device Management – UTCTimeSynchronization-B DM-UTC-B

Device Management – ReinitializeDevice-A DM-RD-A

Device Management – ReinitializeDevice-B DM-RD-B

Device Management – Backup and Restore-A DM-BR-A

Device Management – Backup and Restore-B DM-BR-B

Scheduling

Trending

Device management

Page 108: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

108/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Device Management – Restart-A DM-R-A

Device Management – Restart-B DM-R-B

Device Management – List Manipulation-A DM-LM-A

Device Management – List Manipulation-B DM-LM-B

Device Management – Object Creation and Deletion-A DM-OCD-A

Device Management – Object Creation and Deletion-B DM-OCD-B

Device Management – Virtual Terminal-A DM-VT-A

Device Management – Virtual Terminal-B DM-VT-B

Device Management – Automatic Network Mapping-A DM-ANM-A

Device Management – Automatic Device Mapping-A DM-ADM-A

Device Management – Automatic Time Synchronization-A DM-ATS-A

Device Management – Manual Time Synchronization-A DM-MTS-A

Network Management – Connection Establishment-A NM-CE-A1)

Network Management – Connection Establishment-B NM-CE-B2)

Network Management – Router Configuration-A NM-RC-A

Network Management – Router Configuration-B NM-RC-B

Device management

Network management

Page 109: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

109/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

8.4 Standard object types supported

Object type Supported Can be created dynamically

Can be deleted dynamically

Analog Input Analog Output Analog Value Binary Input Binary Output Binary Value Calendar Command Device Event Enrollment File Group Loop Multi-State Input Multi-State Output Notification Class Program Schedule Averaging Multi-State Value Trend Log Life-Safety-Point Life-Safety-Zone Accumulator Pulse-Converter Event Log Global Group Trend Log Multiple Load Control Structured-View Access Door (unassigned) Access Credential Access Point Access Rights Access User Access Zone Credential Data Input Network Security Bitstring Value Characterstring Value

Page 110: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

110/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Object type Supported Can be created dynamically

Can be deleted dynamically

Date Pattern Value Date Value Datetime Pattern Value Datetime Value Integer Value Large Analog Value Octetstring Value Positive Integer Value Time Pattern Value Time Value

Page 111: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

111/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Properties supported Readable/ Writable

Range restrictions

Object_Identifier R Object_Name R Object_Type R Present_Value W Description R Device_Type Status_Flags R Event_State R Reliability W Out_Of_Service W Update_Interval Units R Min_Pres_Value R Max_Pres_Value R Resolution R COV_Increment W 0 ... Max_Pres_Value Time_Delay W Notification_Class W High_Limit W Min_Pres_Value ...

Max_Pres_Value and High_Limit > Low_Limit

Low_Limit W Min_Pres_Value ... Max_Pres_Value and High_Limit > Low_Limit

Deadband W 0 ... Max_Pres_Value Limit_Enable W Event_Enable W Acked_Transitions R Notify_Type W Event_Time_Stamps R Profile_Name R

Analog Input

Page 112: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

112/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Properties supported Readable/ Writable

Range restrictions

Object_Identifier R Object_Name R Object_Type R Present_Value W Description R Device_Type Status_Flags R Event_State R Reliability W Out_Of_Service W Units R Min_Pres_Value R Max_Pres_Value R Resolution R Priority_Array R Relinquish_Default W Min_Pres_Value ...

Max_Pres_Value COV_Increment R 0 ... Max_Pres_Value Time_Delay W Notification_Class W High_Limit W Min_Pres_Value ...

Max_Pres_Value and High_Limit > Low_Limit

Low_Limit W Min_Pres_Value ... Max_Pres_Value and High_Limit > Low_Limit

Deadband W 0 ... Max_Pres_Value Limit_Enable W Event_Enable W Acked_Transitions R Notify_Type W Event_Time_Stamps R Profile_Name R

Analog Output

Page 113: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

113/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Properties supported Readable/ Writable

Range restrictions

Object_Identifier R Object_Name R Object_Type R Present_Value W Description R Status_Flags R Event_State R Reliability W Out_Of_Service W Units R Priority_Array R Relinquish_Default W Min_Pres_Value ...

Max_Pres_Value COV_Increment W 0 .. Max_Pres_Value Time_Delay W Notification_Class W High_Limit W Min_Pres_Value ...

Max_Pres_Value and High_Limit > Low_Limit

Low_Limit W Min_Pres_Value ... Max_Pres_Value and High_Limit > Low_Limit

Deadband W 0 ... Max_Pres_Value Limit_Enable W Event_Enable W Acked_Transitions R Notify_Type W Event_Time_Stamps R Profile_Name R

Properties supported Readable/ Writable

Range restrictions

Object_Identifier R Object_Name R Object_Type R Present_Value W Description R Status_Flags R Event_State R Out_Of_Service R Units R COV_Increment R Profile_Name R

Analog Value

Analog Value (object tag = 300)

Page 114: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

114/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Properties supported Readable/ Writable

Range restrictions

Object_Identifier R

Object_Name R

Object_Type R

Present_Value W

Description R

Device_Type

Status_Flags R

Event_State R

Reliability W

Out_Of_Service W

Polarity W

Inactive_Text R

Active_Text R

Change_Of_State_Time R

Change_Of_State_Count W

Time_Of_State_Count_Reset R

Elapsed_Active_Time R

Time_Of_Active_Time_Reset R

Time_Delay W 0 .. 65535

Notification_Class W

Alarm_Value W

Event_Enable W

Acked_Transitions R

Notify_Type W

Event_Time_Stamps R

Profile_Name R

Binary Input

Page 115: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

115/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Properties supported Readable/ Writable

Range restrictions

Object_Identifier R

Object_Name R

Object_Type R

Present_Value W

Description R

Device_Type

Status_Flags R

Event_State R

Reliability W

Out_Of_Service W

Polarity W

Inactive_Text R

Active_Text R

Change_Of_State_Time R

Change_Of_State_Count W

Time_Of_State_Count_Reset R

Elapsed_Active_Time W

Time_Of_Active_Time_Reset R

Minimum_Off_Time W 0 .. 65535

Minimum_On_Time W 0 .. 65535

Priority_Array R

Relinquish_Default W

Time_Delay W 0 .. 65535

Notification_Class W

Feedback_Value R

Event_Enable W

Acked_Transitions R

Notify_Type W

Event_Time_Stamps R

Profile_Name R

Binary Output

Page 116: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

116/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Properties supported Readable/ Writable

Range restrictions

Object_Identifier R

Object_Name R

Object_Type R

Present_Value W

Description R

Status_Flags R

Event_State R

Reliability W

Out_Of_Service W

Inactive_Text R

Active_Text R

Change_Of_State_Time R

Change_Of_State_Count W

Time_Of_State_Count_Reset R

Elapsed_Active_Time W

Time_Of_Active_Time_Reset R

Minimum_Off_Time W 0 .. 65535

Minimum_On_Time W 0 .. 65535

Priority_Array R

Relinquish_Default W

Time_Delay W 0 .. 65535

Notification_Class W

Alarm_Value W

Event_Enable W

Acked_Transitions R

Notify_Type R

Event_Time_Stamps R

Profile_Name R Properties supported Readable/

Writable Range restrictions

Object_Identifier R

Object_Name R

Object_Type R

Present_Value W

Description R

Status_Flags R

Event_State R

Out_Of_Service R

Profile_Name R

Binary Value

Binary Value (object tag = 301)

Page 117: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

117/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Properties supported Readable/ Writable

Range restrictions

Object_Identifier R

Object_Name R

Object_Type R

Description R

Present_Value R

Date_List W Max. 20

Profile_Name R

Calendar

Page 118: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

118/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Properties supported Readable/ Writable

Range restrictions

Object_Identifier R

Object_Name R

Object_Type R

System_Status R

Vendor_Name R

Vendor_Identifier R

Model_Name R

Firmware_Revision R

Application_Software_Version R

Location R

Description R

Protocol_Version R

Protocol_Revision R

Protocol_Services_Supported R

Protocol_Object_Types_Supported R

Object_List R

Structured_Object_List

Max_APDU_Length_Accepted R

Segmentation_Supported R

Max_Segments_Accepted R

VT_Classes_Supported

Active_VT_Sessions

Local_Time R

Local_Date R

UTC_Offset R

Daylight_Savings_Status R

APDU_Segment_Timeout R

APDU_Timeout R

Number_Of_APDU_Retries R

List_Of_Session_Keys

Time_Synchronization_Recipients

Max_Master

Max_Info_Frames

Device_Address_Binding R

Database_Revision R

Configuration_Files

Last_Restore_Time

Backup_Failure_Timeout

Active_COV_Subscriptions R

Slave_Proxy_Enable

Manual_Slave_Adress_Binding

Auto_Slave_Discovery

Slave_Address_Binding

Device

Page 119: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

119/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Properties supported Readable/ Writable

Range restrictions

Last_Restart_Reason

Time_Of_Device_Restart

Restart_Notification_Recipients

UTC_Time_Synchronization_Recipients

Time_Synchronization_Interval

Align_Intervals

Interval_Offset

Profile_Name R Properties supported Readable/

Writable Range restrictions

Object_Identifier R

Object_Name R

Object_Type R

Present_Value W 1 … Number_Of_States

Description R

Device_Type R

Status_Flags R

Event_State R

Reliability W

Out_Of_Service W

Number_Of_States R

State_Text R

Time_Delay W 0 .. 65535

Notification_Class W

Alarm_Values W

Fault_Values W

Event_Enable W

Acked_Transitions R

Notify_Type W

Event_Time_Stamps R

Profile_Name R

Device

Multistate Input

Page 120: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

120/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Properties supported Readable/ Writable

Range restrictions

Object_Identifier R

Object_Name R

Object_Type R

Present_Value W 1 .. Number_Of_States

Description R

Device_Type R

Status_Flags R

Event_State R

Reliability W

Out_Of_Service W

Number_Of_States R

State_Text R

Priority_Array R

Relinquish_Default W 1 .. Number_Of_States

Time_Delay W 0 .. 65535

Notification_Class W

Feedback_Value R

Event_Enable W

Acked_Transitions R

Notify_Type W

Event_Time_Stamps R

Profile_Name R

Multistate Output

Page 121: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

121/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Properties supported Readable/ Writable

Range restrictions

Object_Identifier R

Object_Name R

Object_Type R

Present_Value W 1 .. Number_Of_States

Description R

Status_Flags R

Event_State R

Reliability W

Out_Of_Service W

Number_Of_States R

State_Text R

Priority_Array R

Relinquish_Default W 1 .. Number_Of_States

Time_Delay W 0 .. 65535

Notification_Class W

Alarm_Values W

Fault_Values W

Event_Enable W

Acked_Transitions R

Notify_Type W

Event_Time_Stamps R

Profile_Name R Properties supported Readable/

Writable Range restrictions

Object_Identifier R

Object_Name R

Object_Type R

Present_Value W 1…Number_Of_States

Description R

Status_Flags R

Event_State R

Out_Of_Service R

Number_Of_States R

Profile_Name R

Multistate Value

Multistate Value (object tag = 302)

Page 122: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

122/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Properties supported Readable/ Writable

Range restrictions

Object_Identifier R

Object_Name R

Object_Type R

Description R

Notification_Class R

Priority W

Ack_Required W

Recipient_List W Max. 20

Profile_Name R Properties supported Readable/

Writable Range restrictions

Object_Identifier R

Object_Name R

Object_Type R

Present_Value R

Description R

Effective_Period W

Weekly_Schedule W Max. 6 per day

Exception_Schedule W Max. 10, max. 4

per exception Schedule_Default W

List_Of_Object_Property_References W 1 ref

Priority_For_Writing W

Status_Flags R

Reliability W

Out_Of_Service W

Profile_Name R

Notification Class

Schedule

Page 123: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

123/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

Properties supported Readable/ Writable

Range restrictions

Object_Identifier R Object_Name R Object_Type R Description R Enable W Start_Time W Stop_Time W Log_DeviceObjectProperty R Log_Interval W COV_Resubscription_Interval W Client_COV_Increment W Stop_When_Full W Buffer_Size R Log_Buffer R Record_Count W Total_Record_Count R Notification_Threshold W Records_Since_Notification R Last_Notify_Record R Event_State R Notification_Class W Event_Enable R Acked_Transitions R Notify_Type R Event_Time_Stamps R Profile_Name R Logging_Type R Align_Intervals Interval_Offset Trigger Status_Flags R Reliability R

Trend Log

Page 124: BACnet (PICS) Protocol Implementation Conformance · PDF file1/125 Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies

124/125

Siemens Desigo™ V6.0 BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_10 Building Technologies 2015-07-31

8.5 Segmentation capability

Able to transmit segmented messages Window size 4

Able to receive segmented messages Window size 4

8.6 Data Link Layer options

BACnet IP, (Annex J)

BACnet IP, (Annex J), Foreign Device

ISO 8802-3, Ethernet (Clause 7)

ANSI/ATA 878.1, 2.5 Mb. ARCNET (Clause 8)

ANSI/ATA 878.1, RS-485 ARCNET (Clause 8), baud rate(s)

MS/TP master (Clause 9), baud rate(s)

MS/TP slave (Clause 9), baud rate(s)

Point-To-Point, EIA 232 (Clause 10), baud rate(s)

Point-To-Point, modem, (Clause 10), baud rate(s)

LonTalk, (Clause 11), medium

Other :

8.7 Device address binding

Is static device binding supported? Yes No

8.8 Networking options

Router, Clause 6 (remote management functionality/BACnet PTP)

Annex H, BACnet Tunnelling Router over IP

BACnet/IP Broadcast Management Device (BBMD)

Number of BDT entries: 10

Does the BBMD support registrations by foreign devices? Yes No

8.9 Character sets supported

Indicating support for multiple character sets does not imply that they can all be supported simultaneously.

ANSI X3.4 IBM / Microsoft DBCS ISO 8859-11)

ISO 10646 (UCS-2) ISO 10646 (UCS-4) JIS C 6226

Note