BAGHDAD MALL HEATING & COOLING LOAD CALCULATIONS & EQUIPMENT SELECTIONS November, 2012

Upload: dorukbakir

Post on 26-May-2017

212 views

Category:

Documents


0 download

TRANSCRIPT

BAGHDAD MALLHEATING & COOLING

LOAD CALCULATIONS & EQUIPMENT SELECTIONS

November, 2012

SPACE DESIGN LOAD SUMMARY Floor Winter Heating

A D i T D i T R l ti H L d S ibl L t t T t l C diti iCooling LoadSummer

Area Design Temp. Design Temp. Relative Hum. Load Sensible Latent Total Conditioning

SPACE REFERENCE & NAME [m²] [oC] oC RH% [W] [W] [W] [W] System

GR01-ENTRANCE HALL 344 20 24 50% 22900 73542 8683 82225 ALL‐AIR AHU GR03-SHOP 73 20 24 50% 1335 10028 691 10719 2P‐FCU GR02-MALL HALL 314 20 24 50% 4642 22067 7926 29993 ALL‐AIR AHU GR04-SHOP 70 20 24 50% 1297 9626 662 10288 2P‐FCU GR05-SHOP 66 20 24 50% 1247 9091 624 9715 2P‐FCU GR06-SHOP 12 20 24 50% 152 1606 114 1720 2P‐FCU GR07-SHOP 8 20 24 50% 230 1362 252 1614 2P‐FCU GR08-HYPERMARKET 1319 20 24 50% 21899 104313 6659 110972 ALL‐AIR AHU GR09-ESCAPE HALL 88 20 24 50% 2162 4970 0 4970 ALL‐AIR AHU GR10-HALL 11 20 24 50% 503 777 0 777 ALL‐AIR AHU GR12-WC MALE 20 20 24 50% 1016 1723 111 1834 ALL‐AIR AHU GR13-WC FEMALE 16 20 24 50% 593 1291 111 1402 ALL‐AIR AHU GR18-ENTRANCE HALL 61 20 24 50% 1830 6846 1540 8386 ALL‐AIR AHU GR19-MALL HALL 140 20 24 50% 4387 17384 3534 20918 ALL‐AIR AHU GR21-SHOP 56 20 24 50% 3947 22143 530 22673 2P‐FCU GR24-SHOP 5 20 24 50% 258 952 126 1078 2P‐FCU GR25-SHOP 56 20 24 50% 1459 8113 530 8643 2P‐FCU GR26-SHOP 55 20 24 50% 1107 7635 520 8155 2P‐FCU GR27-SHOP 23 20 24 50% 497 3215 218 3433 2P‐FCU GR29-HALL 14 20 24 50% 1086 1381 0 1381 ALL‐AIR AHU 101-SHOPPING HALL 1026 20 24 50% 927 58552 25898 84450 ALL‐AIR AHU 102-SHOP 60 20 24 50% 410 7551 568 8119 2P‐FCU 103-SHOP 58 20 24 50% 410 7308 549 7857 2P‐FCU 104-SHOP 47 20 24 50% 410 5971 445 6416 2P‐FCU 105-SHOP 43 20 24 50% 410 5485 407 5892 2P‐FCU 106-SHOP 41 20 24 50% 410 5242 388 5630 2P‐FCU 107-SHOP 52 20 24 50% 410 6579 492 7071 2P‐FCU 108-SHOP 50 20 24 50% 410 6336 473 6809 2P‐FCU 109-SHOP 60 20 24 50% 410 7551 568 8119 2P‐FCU 110-SHOP 42 20 24 50% 1036 6022 397 6419 2P‐FCU 111-HALL 11 20 24 50% 364 642 0 642 ALL‐AIR AHU 113-WC MALE 20 20 24 50% 763 1477 111 1588 ALL‐AIR AHU 114-WC FEMALE 16 20 24 50% 390 1094 111 1205 ALL‐AIR AHU 117-DEPARTMENT STORE 364 20 24 50% 3643 33331 3444 36775 2P‐FCU 119-SHOP 106 20 24 50% 1025 13564 1003 14567 2P‐FCU 120-SHOP 30 20 24 50% 226 3796 284 4080 2P‐FCU 121-SHOP 66 20 24 50% 410 8294 624 8918 2P‐FCU 122-SHOP 70 20 24 50% 410 8783 662 9445 2P‐FCU 123-SHOP 55 20 24 50% 410 6959 520 7479 2P‐FCU 124-SHOP 48 20 24 50% 1009 6704 454 7158 2P‐FCU 126-HALL 14 20 24 50% 778 1083 0 1083 ALL‐AIR AHU 127-SHOP 53 20 24 50% 913 7228 501 7729 2P‐FCU 128-SHOP 68 20 24 50% 564 8642 643 9285 2P‐FCU 129-KIOSK 5 20 24 50% 0 702 126 828 ALL‐AIR AHU 130-KIOSK 27 20 24 50% 0 3282 255 3537 ALL‐AIR AHU 131-KIOSK 54 20 24 50% 0 6564 511 7075 ALL‐AIR AHU 132-KIOSK 54 20 24 50% 0 6564 511 7075 ALL‐AIR AHU 133-KIOSK 27 20 24 50% 0 3282 255 3537 ALL‐AIR AHU 134-KIOSK 5 20 24 50% 0 702 126 828 ALL‐AIR AHU 135-SHOP 13 20 24 50% 130 1706 123 1829 2P‐FCU 201-SHOPPING HALL 860 20 24 50% 927 49188 21708 70896 ALL‐AIR AHU 202-SHOP 68 20 24 50% 410 8523 643 9166 2P‐FCU 203-SHOP 58 20 24 50% 410 7308 549 7857 2P‐FCU 204-SHOP 47 20 24 50% 410 5971 445 6416 2P‐FCU 205-SHOP 47 20 24 50% 410 5971 445 6416 2P‐FCU 206-SHOP 41 20 24 50% 410 5242 388 5630 2P‐FCU 207-SHOP 52 20 24 50% 410 6579 492 7071 2P‐FCU 208-SHOP 50 20 24 50% 410 6336 473 6809 2P‐FCU 209-SHOP 59 20 24 50% 410 7429 558 7987 2P‐FCU 210-SHOP 42 20 24 50% 1036 6022 397 6419 2P‐FCU 211-HALL 11 20 24 50% 364 642 0 642 ALL‐AIR AHU 213-WC MALE 20 20 24 50% 763 1477 111 1588 ALL‐AIR AHU 214-WC FEMALE 16 20 24 50% 390 1094 111 1205 ALL‐AIR AHU 217-DEPARTMENT STORE 364 20 24 50% 3643 33331 3444 36775 2P‐FCU 219-SHOP 39 20 24 50% 1025 5420 369 5789 2P‐FCU 220-SHOP 52 20 24 50% 410 6592 492 7084 2P‐FCU 221-SHOP 65 20 24 50% 410 8172 615 8787 2P‐FCU

Air System Sizing Summary for ALL AIR AHU Project Name: BAGHDAD MALL 11.17.2012 02:02

Hourly Analysis Program v.4,3 Page 1 of 1

Air System Information Air System Name .................................. ALL AIR AHU Equipment Class ........................................... CW AHU Air System Type ............................................... SZCAV

Number of zones ............................................................ 1 Floor Area .............................................................. 5535,0 m² Location .................................................... Baghdad, Iraq

Sizing Calculation Information Zone and Space Sizing Method:

Zone L/s .......................... Sum of space airflow rates Space L/s ...................... Individual peak space loads

Calculation Months ......................................... Jan to Dec Sizing Data ..................................................... Calculated

Central Cooling Coil Sizing Data

Total coil load ...................................................... 853,7 kW Sensible coil load ................................................ 769,8 kW Coil L/s at Jul 1500 ............................................. 37909 L/s Max block L/s ..................................................... 37909 L/s Sum of peak zone L/s ........................................ 37909 L/s Sensible heat ratio .............................................. 0,902 m²/kW ...................................................................... 6,5 W/m² .................................................................... 154,2 Water flow @ 5,0 °K rise ..................................... 40,86 L/s

Load occurs at .................................................... Jul 1500 OA DB / WB ..................................................... 45,0 / 22,8 °C Entering DB / WB ............................................ 29,3 / 18,4 °C Leaving DB / WB ............................................. 12,5 / 11,5 °C Coil ADP .................................................................... 10,6 °C Bypass Factor .......................................................... 0,100 Resulting RH ................................................................ 47 % Design supply temp. .................................................. 14,0 °C Zone T-stat Check .................................................. 0 of 1 OK Max zone temperature deviation ................................. 0,0 °K

Central Heating Coil Sizing Data

Max coil load ....................................................... 142,0 kW Coil L/s at Des Htg ............................................. 37909 L/s Max coil L/s ........................................................ 37909 L/s Water flow @ 20,0 °K drop .................................... 1,70 L/s

Load occurs at .................................................... Des Htg W/m² .......................................................................... 25,7 Ent. DB / Lvg DB ............................................. 17,3 / 20,4 °C

Supply Fan Sizing Data

Actual max L/s .................................................... 37909 L/s Standard L/s ....................................................... 37758 L/s Actual max L/(s-m²) ............................................... 6,85 L/(s-m²)

Fan motor BHP ...................................................... 112,98 BHP Fan motor kW .......................................................... 84,25 kW Fan static .................................................................. 1200 Pa

Return Fan Sizing Data

Actual max L/s .................................................... 37909 L/s Standard L/s ....................................................... 37758 L/s Actual max L/(s-m²) ............................................... 6,85 L/(s-m²)

Fan motor BHP ........................................................ 84,73 BHP Fan motor kW .......................................................... 63,18 kW Fan static .................................................................... 900 Pa

Outdoor Ventilation Air Data Design airflow L/s ................................................. 7448 L/s L/(s-m²) .................................................................. 1,35 L/(s-m²)

L/s/person .................................................................. 4,78 L/s/person

Air System Sizing Summary for VRV Project Name: BAGHDAD MALL 11.17.2012 02:16

Hourly Analysis Program v.4,3 Page 1 of 1

Air System Information Air System Name .................................................. VRV Equipment Class ................................................ TERM Air System Type ............................................ SPLT-FC

Number of zones ............................................................ 6 Floor Area .............................................................. 1115,0 m² Location .................................................... Baghdad, Iraq

Sizing Calculation Information Zone and Space Sizing Method:

Zone L/s .......................... Sum of space airflow rates Space L/s ...................... Individual peak space loads

Calculation Months ......................................... Jan to Dec Sizing Data ..................................................... Calculated

Cooling Coil Sizing Data

Total coil load ........................................................ 60,6 kW Sensible coil load .................................................. 60,6 kW Coil L/s at Jul 1500 ............................................... 2252 L/s Max coil L/s .......................................................... 2252 L/s Sensible heat ratio .............................................. 1,000 Water flow @ 5,0 °K rise ........................................ N/A

Load occurs at .................................................... Jul 1500 OA DB / WB ..................................................... 45,0 / 22,8 °C Entering DB / WB ............................................ 45,0 / 22,8 °C Leaving DB / WB ............................................. 22,6 / 15,7 °C Bypass Factor .......................................................... 0,100

Heating Coil Sizing Data

Max coil load ......................................................... 50,4 kW Coil L/s at Des Htg ............................................... 2252 L/s Max coil L/s .......................................................... 2252 L/s Water flow @ 20,0 °K drop ..................................... N/A

Load occurs at .................................................... Des Htg Ent. DB / Lvg DB ............................................... 0,0 / 18,6 °C

Ventilation Fan Sizing Data

Actual max L/s ...................................................... 2252 L/s Standard L/s ......................................................... 2243 L/s Actual max L/(s-m²) ............................................... 2,02 L/(s-m²)

Fan motor BHP .......................................................... 5,03 BHP Fan motor kW ............................................................ 3,75 kW Fan static .................................................................. 1000 Pa

Outdoor Ventilation Air Data Design airflow L/s ................................................. 2252 L/s L/(s-m²) .................................................................. 2,02 L/(s-m²)

L/s/person .................................................................. 6,40 L/s/person

Air System Sizing Summary for FCU Project Name: BAGHDAD MALL 11.17.2012 02:14

Hourly Analysis Program v.4,3 Page 1 of 1

Air System Information Air System Name .................................................. FCU Equipment Class ................................................ TERM Air System Type ................................................. 4P-FC

Number of zones .......................................................... 64 Floor Area .............................................................. 4196,0 m² Location .................................................... Baghdad, Iraq

Sizing Calculation Information Zone and Space Sizing Method:

Zone L/s .......................... Sum of space airflow rates Space L/s ...................... Individual peak space loads

Calculation Months ......................................... Jan to Dec Sizing Data ..................................................... Calculated

Cooling Coil Sizing Data

Total coil load ...................................................... 186,5 kW Sensible coil load ................................................ 186,5 kW Coil L/s at Jul 1500 ............................................... 7388 L/s Max coil L/s .......................................................... 7388 L/s Sensible heat ratio .............................................. 1,000 Water flow @ 5,0 °K rise ....................................... 8,93 L/s

Load occurs at .................................................... Jul 1500 OA DB / WB ..................................................... 45,0 / 22,8 °C Entering DB / WB ............................................ 45,0 / 22,8 °C Leaving DB / WB ............................................. 24,0 / 16,2 °C Bypass Factor .......................................................... 0,100

Heating Coil Sizing Data

Max coil load ....................................................... 177,7 kW Coil L/s at Des Htg ............................................... 7388 L/s Max coil L/s .......................................................... 7388 L/s Water flow @ 20,0 °K drop .................................... 2,13 L/s

Load occurs at .................................................... Des Htg Ent. DB / Lvg DB ............................................... 0,0 / 20,0 °C

Ventilation Fan Sizing Data

Actual max L/s ...................................................... 7388 L/s Standard L/s ......................................................... 7358 L/s Actual max L/(s-m²) ............................................... 1,76 L/(s-m²)

Fan motor BHP .......................................................... 0,00 BHP Fan motor kW ............................................................ 0,00 kW Fan static ........................................................................ 0 Pa

Outdoor Ventilation Air Data Design airflow L/s ................................................. 7388 L/s L/(s-m²) .................................................................. 1,76 L/(s-m²)

L/s/person .................................................................. 6,21 L/s/person

Space Design Load Summary for ALL AIR AHU Project Name: BAGHDAD MALL 11.17.2012 02:03

Hourly Analysis Program v.4,3 Page 1of40 1

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' GR01-ENTRANCE HALL '' IN ZONE '' Zone 1 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jun 1400 HEATING DATA AT DES HTG COOLING OA DB / WB 42,8 °C / 21,5 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 540 m² 36724 - 540 m² - -Wall Transmission 443 m² 1693 - 443 m² 2371 -Roof Transmission 1 m² 8 - 1 m² 11 -Window Transmission 250 m² 4218 - 250 m² 5500 -Skylight Transmission 290 m² 4893 - 290 m² 6380 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 344 m² 4025 - 344 m² 3354 -Partitions 0 m² 0 - 0 m² 0 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 6880 W 6880 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 1720 W 1720 - 0 0 -People 138 9880 8270 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 3502 413 30% 5285 0>> Total Zone Loads - 73542 8683 - 22900 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' GR01-ENTRANCE HALL '' IN ZONE '' Zone 1 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)N EXPOSURE WALL 1 0,854 - 14 - 17 WINDOW 1 250 1,100 0,280 4218 6073 5500E EXPOSURE WALL 221 0,266 - 833 - 1177W EXPOSURE WALL 221 0,266 - 846 - 1177N EXPOSURE ROOF 1 0,545 - 8 - 11 SKYLIGHT 290 1,100 0,280 4893 30651 6380

Space Design Load Summary for ALL AIR AHU Project Name: BAGHDAD MALL 11.17.2012 02:03

Hourly Analysis Program v.4,3 Page 2of40 2

TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' GR02-MALL HALL '' IN ZONE '' Zone 1 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jul 2300 HEATING DATA AT DES HTG COOLING OA DB / WB 30,6 °C / 18,5 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 43 m² 271 - 43 m² 339 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 314 m² 3674 - 314 m² 3062 -Partitions 17 m² 204 - 17 m² 170 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 6280 W 6280 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 1570 W 1570 - 0 0 -People 126 9018 7549 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 1051 377 30% 1071 0>> Total Zone Loads - 22067 7926 - 4642 0

TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' GR02-MALL HALL '' IN ZONE '' Zone 1 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)W EXPOSURE WALL 18 0,394 - 117 - 142E EXPOSURE WALL 25 0,394 - 154 - 197

Space Design Load Summary for ALL AIR AHU Project Name: BAGHDAD MALL 11.17.2012 02:03

Hourly Analysis Program v.4,3 Page 3of40 3

TABLE 1.3.A. COMPONENT LOADS FOR SPACE '' GR08-HYPERMARKET '' IN ZONE '' Zone 1 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG COOLING OA DB / WB 43,1 °C / 22,2 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 240 m² 1549 - 240 m² 2059 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 2 m² 147 - 2 m² 176 -Floor Transmission 1319 m² 15432 - 1319 m² 12860 -Partitions 175 m² 2100 - 175 m² 1750 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 52760 W 52757 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 19785 W 19784 - 0 0 -People 106 7576 6342 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 4967 317 30% 5054 0>> Total Zone Loads - 104313 6659 - 21899 0

TABLE 1.3.B. ENVELOPE LOADS FOR SPACE '' GR08-HYPERMARKET '' IN ZONE '' Zone 1 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)E EXPOSURE WALL 143 0,394 - 759 - 1124WSW EXPOSURE WALL 80 0,394 - 376 - 631W EXPOSURE WALL 18 0,854 - 414 - 304 DOOR 2 4,000 - 147 - 176

Space Design Load Summary for ALL AIR AHU Project Name: BAGHDAD MALL 11.17.2012 02:03

Hourly Analysis Program v.4,3 Page 4of40 4

TABLE 1.4.A. COMPONENT LOADS FOR SPACE '' GR09-ESCAPE HALL '' IN ZONE '' Zone 1 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Sep 1400 HEATING DATA AT DES HTG COOLING OA DB / WB 42,1 °C / 21,4 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 4 m² 736 - 4 m² - -Wall Transmission 13 m² 48 - 13 m² 104 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 4 m² 184 - 4 m² 251 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 88 m² 1027 - 88 m² 858 -Partitions 45 m² 539 - 45 m² 450 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 1760 W 1760 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 440 W 440 - 0 0 -People 0 0 0 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 237 0 30% 499 0>> Total Zone Loads - 4970 0 - 2162 0

TABLE 1.4.B. ENVELOPE LOADS FOR SPACE '' GR09-ESCAPE HALL '' IN ZONE '' Zone 1 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)S EXPOSURE WALL 13 0,394 - 48 - 104 WINDOW 1 4 3,281 0,751 184 736 251

Space Design Load Summary for ALL AIR AHU Project Name: BAGHDAD MALL 11.17.2012 02:03

Hourly Analysis Program v.4,3 Page 5of40 5

TABLE 1.5.A. COMPONENT LOADS FOR SPACE '' GR10-HALL '' IN ZONE '' Zone 1 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jun 2300 HEATING DATA AT DES HTG COOLING OA DB / WB 29,0 °C / 17,1 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 0 m² 0 - 0 m² 0 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 11 m² 129 - 11 m² 107 -Partitions 28 m² 336 - 28 m² 280 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 220 W 220 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 55 W 55 - 0 0 -People 0 0 0 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 37 0 30% 116 0>> Total Zone Loads - 777 0 - 503 0

TABLE 1.5.B. ENVELOPE LOADS FOR SPACE '' GR10-HALL '' IN ZONE '' Zone 1 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Space Design Load Summary for ALL AIR AHU Project Name: BAGHDAD MALL 11.17.2012 02:03

Hourly Analysis Program v.4,3 Page 6of40 6

TABLE 1.6.A. COMPONENT LOADS FOR SPACE '' GR12-WC MALE '' IN ZONE '' Zone 1 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jul 2300 HEATING DATA AT DES HTG COOLING OA DB / WB 30,6 °C / 18,5 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 30 m² 184 - 30 m² 237 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 20 m² 234 - 20 m² 195 -Partitions 35 m² 420 - 35 m² 350 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 300 W 300 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 300 W 300 - 0 0 -People 3 202 106 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 82 5 30% 234 0>> Total Zone Loads - 1723 111 - 1016 0

TABLE 1.6.B. ENVELOPE LOADS FOR SPACE '' GR12-WC MALE '' IN ZONE '' Zone 1 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)E EXPOSURE WALL 30 0,394 - 184 - 237

Space Design Load Summary for ALL AIR AHU Project Name: BAGHDAD MALL 11.17.2012 02:03

Hourly Analysis Program v.4,3 Page 7of40 7

TABLE 1.7.A. COMPONENT LOADS FOR SPACE '' GR13-WC FEMALE '' IN ZONE '' Zone 1 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jun 2300 HEATING DATA AT DES HTG COOLING OA DB / WB 29,0 °C / 17,1 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 0 m² 0 - 0 m² 0 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 16 m² 187 - 16 m² 156 -Partitions 30 m² 360 - 30 m² 300 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 240 W 240 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 240 W 240 - 0 0 -People 3 202 106 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 61 5 30% 137 0>> Total Zone Loads - 1291 111 - 593 0

TABLE 1.7.B. ENVELOPE LOADS FOR SPACE '' GR13-WC FEMALE '' IN ZONE '' Zone 1 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Space Design Load Summary for ALL AIR AHU Project Name: BAGHDAD MALL 11.17.2012 02:03

Hourly Analysis Program v.4,3 Page 8of40 8

TABLE 1.8.A. COMPONENT LOADS FOR SPACE '' GR18-ENTRANCE HALL '' IN ZONE '' Zone 1 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Oct 1400 HEATING DATA AT DES HTG COOLING OA DB / WB 37,3 °C / 19,0 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 9 m² 2285 - 9 m² - -Wall Transmission 27 m² 135 - 27 m² 204 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 9 m² 301 - 9 m² 609 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 61 m² 522 - 61 m² 595 -Partitions 0 m² 0 - 0 m² 0 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 1220 W 1220 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 305 W 305 - 0 0 -People 24 1752 1466 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 326 73 30% 422 0>> Total Zone Loads - 6846 1540 - 1830 0

TABLE 1.8.B. ENVELOPE LOADS FOR SPACE '' GR18-ENTRANCE HALL '' IN ZONE '' Zone 1 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)S EXPOSURE WALL 27 0,375 - 135 - 204 WINDOW 1 9 3,274 0,751 301 2285 609

Space Design Load Summary for ALL AIR AHU Project Name: BAGHDAD MALL 11.17.2012 02:03

Hourly Analysis Program v.4,3 Page 9of40 9

TABLE 1.9.A. COMPONENT LOADS FOR SPACE '' GR19-MALL HALL '' IN ZONE '' Zone 1 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Sep 1500 HEATING DATA AT DES HTG COOLING OA DB / WB 42,7 °C / 21,6 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 19 m² 6087 - 19 m² - -Wall Transmission 79 m² 504 - 79 m² 949 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 19 m² 811 - 19 m² 1061 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 140 m² 1634 - 140 m² 1365 -Partitions 0 m² 0 - 0 m² 0 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 2800 W 2800 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 700 W 700 - 0 0 -People 56 4021 3366 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 828 168 30% 1012 0>> Total Zone Loads - 17384 3534 - 4387 0

TABLE 1.9.B. ENVELOPE LOADS FOR SPACE '' GR19-MALL HALL '' IN ZONE '' Zone 1 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)S EXPOSURE WALL 19 0,598 - 122 - 221WSW EXPOSURE WALL 61 0,598 - 382 - 727 WINDOW 1 19 2,770 0,576 811 6087 1061

Space Design Load Summary for ALL AIR AHU Project Name: BAGHDAD MALL 11.17.2012 02:03

Hourly Analysis Program v.4,3 Page 10of40 10

TABLE 1.10.A. COMPONENT LOADS FOR SPACE '' GR29-HALL '' IN ZONE '' Zone 1 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jul 0000 HEATING DATA AT DES HTG COOLING OA DB / WB 29,5 °C / 18,1 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 13 m² 82 - 13 m² 99 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 14 m² 164 - 14 m² 137 -Partitions 60 m² 720 - 60 m² 600 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 280 W 280 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 70 W 70 - 0 0 -People 0 0 0 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 66 0 30% 251 0>> Total Zone Loads - 1381 0 - 1086 0

TABLE 1.10.B. ENVELOPE LOADS FOR SPACE '' GR29-HALL '' IN ZONE '' Zone 1 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)W EXPOSURE WALL 13 0,394 - 82 - 99

Space Design Load Summary for ALL AIR AHU Project Name: BAGHDAD MALL 11.17.2012 02:03

Hourly Analysis Program v.4,3 Page 11of40 11

TABLE 1.11.A. COMPONENT LOADS FOR SPACE '' 101-SHOPPING HALL '' IN ZONE '' Zone 1 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jul 2300 HEATING DATA AT DES HTG COOLING OA DB / WB 30,6 °C / 18,5 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 65 m² 408 - 65 m² 513 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 20 m² 240 - 20 m² 200 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 20520 W 20519 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 5130 W 5130 - 0 0 -People 410 29466 24665 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 2788 1233 30% 214 0>> Total Zone Loads - 58552 25898 - 927 0

TABLE 1.11.B. ENVELOPE LOADS FOR SPACE '' 101-SHOPPING HALL '' IN ZONE '' Zone 1 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)W EXPOSURE WALL 25 0,394 - 162 - 197E EXPOSURE WALL 40 0,394 - 246 - 316

Space Design Load Summary for ALL AIR AHU Project Name: BAGHDAD MALL 11.17.2012 02:03

Hourly Analysis Program v.4,3 Page 12of40 12

TABLE 1.12.A. COMPONENT LOADS FOR SPACE '' 111-HALL '' IN ZONE '' Zone 1 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jun 2300 HEATING DATA AT DES HTG COOLING OA DB / WB 29,0 °C / 17,1 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 0 m² 0 - 0 m² 0 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 28 m² 336 - 28 m² 280 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 220 W 220 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 55 W 55 - 0 0 -People 0 0 0 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 31 0 30% 84 0>> Total Zone Loads - 642 0 - 364 0

TABLE 1.12.B. ENVELOPE LOADS FOR SPACE '' 111-HALL '' IN ZONE '' Zone 1 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Space Design Load Summary for ALL AIR AHU Project Name: BAGHDAD MALL 11.17.2012 02:03

Hourly Analysis Program v.4,3 Page 13of40 13

TABLE 1.13.A. COMPONENT LOADS FOR SPACE '' 113-WC MALE '' IN ZONE '' Zone 1 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jul 2300 HEATING DATA AT DES HTG COOLING OA DB / WB 30,6 °C / 18,5 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 30 m² 184 - 30 m² 237 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 35 m² 420 - 35 m² 350 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 300 W 300 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 300 W 300 - 0 0 -People 3 202 106 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 70 5 30% 176 0>> Total Zone Loads - 1477 111 - 763 0

TABLE 1.13.B. ENVELOPE LOADS FOR SPACE '' 113-WC MALE '' IN ZONE '' Zone 1 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)E EXPOSURE WALL 30 0,394 - 184 - 237

Space Design Load Summary for ALL AIR AHU Project Name: BAGHDAD MALL 11.17.2012 02:03

Hourly Analysis Program v.4,3 Page 14of40 14

TABLE 1.14.A. COMPONENT LOADS FOR SPACE '' 114-WC FEMALE '' IN ZONE '' Zone 1 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jun 2300 HEATING DATA AT DES HTG COOLING OA DB / WB 29,0 °C / 17,1 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 0 m² 0 - 0 m² 0 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 30 m² 360 - 30 m² 300 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 240 W 240 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 240 W 240 - 0 0 -People 3 202 106 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 52 5 30% 90 0>> Total Zone Loads - 1094 111 - 390 0

TABLE 1.14.B. ENVELOPE LOADS FOR SPACE '' 114-WC FEMALE '' IN ZONE '' Zone 1 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Space Design Load Summary for ALL AIR AHU Project Name: BAGHDAD MALL 11.17.2012 02:03

Hourly Analysis Program v.4,3 Page 15of40 15

TABLE 1.15.A. COMPONENT LOADS FOR SPACE '' 126-HALL '' IN ZONE '' Zone 1 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jul 0000 HEATING DATA AT DES HTG COOLING OA DB / WB 29,5 °C / 18,1 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 13 m² 82 - 13 m² 99 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 50 m² 600 - 50 m² 500 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 280 W 280 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 70 W 70 - 0 0 -People 0 0 0 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 52 0 30% 180 0>> Total Zone Loads - 1083 0 - 778 0

TABLE 1.15.B. ENVELOPE LOADS FOR SPACE '' 126-HALL '' IN ZONE '' Zone 1 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)W EXPOSURE WALL 13 0,394 - 82 - 99

Space Design Load Summary for ALL AIR AHU Project Name: BAGHDAD MALL 11.17.2012 02:03

Hourly Analysis Program v.4,3 Page 16of40 16

TABLE 1.16.A. COMPONENT LOADS FOR SPACE '' 129-KIOSK '' IN ZONE '' Zone 1 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jan 2300 HEATING DATA AT DES HTG COOLING OA DB / WB 10,3 °C / 1,7 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 0 m² 0 - 0 m² 0 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 0 m² 0 - 0 m² 0 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 450 W 450 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 75 W 75 - 0 0 -People 2 144 120 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 33 6 30% 0 0>> Total Zone Loads - 702 126 - 0 0

TABLE 1.16.B. ENVELOPE LOADS FOR SPACE '' 129-KIOSK '' IN ZONE '' Zone 1 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Space Design Load Summary for ALL AIR AHU Project Name: BAGHDAD MALL 11.17.2012 02:03

Hourly Analysis Program v.4,3 Page 17of40 17

TABLE 1.17.A. COMPONENT LOADS FOR SPACE '' 130-KIOSK '' IN ZONE '' Zone 1 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jan 2300 HEATING DATA AT DES HTG COOLING OA DB / WB 10,3 °C / 1,7 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 0 m² 0 - 0 m² 0 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 0 m² 0 - 0 m² 0 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 2430 W 2430 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 405 W 405 - 0 0 -People 4 291 243 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 156 12 30% 0 0>> Total Zone Loads - 3282 255 - 0 0

TABLE 1.17.B. ENVELOPE LOADS FOR SPACE '' 130-KIOSK '' IN ZONE '' Zone 1 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Space Design Load Summary for ALL AIR AHU Project Name: BAGHDAD MALL 11.17.2012 02:03

Hourly Analysis Program v.4,3 Page 18of40 18

TABLE 1.18.A. COMPONENT LOADS FOR SPACE '' 131-KIOSK '' IN ZONE '' Zone 1 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jan 2300 HEATING DATA AT DES HTG COOLING OA DB / WB 10,3 °C / 1,7 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 0 m² 0 - 0 m² 0 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 0 m² 0 - 0 m² 0 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 4860 W 4860 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 810 W 810 - 0 0 -People 8 581 487 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 313 24 30% 0 0>> Total Zone Loads - 6564 511 - 0 0

TABLE 1.18.B. ENVELOPE LOADS FOR SPACE '' 131-KIOSK '' IN ZONE '' Zone 1 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Space Design Load Summary for ALL AIR AHU Project Name: BAGHDAD MALL 11.17.2012 02:03

Hourly Analysis Program v.4,3 Page 19of40 19

TABLE 1.19.A. COMPONENT LOADS FOR SPACE '' 132-KIOSK '' IN ZONE '' Zone 1 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jan 2300 HEATING DATA AT DES HTG COOLING OA DB / WB 10,3 °C / 1,7 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 0 m² 0 - 0 m² 0 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 0 m² 0 - 0 m² 0 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 4860 W 4860 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 810 W 810 - 0 0 -People 8 581 487 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 313 24 30% 0 0>> Total Zone Loads - 6564 511 - 0 0

TABLE 1.19.B. ENVELOPE LOADS FOR SPACE '' 132-KIOSK '' IN ZONE '' Zone 1 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Space Design Load Summary for ALL AIR AHU Project Name: BAGHDAD MALL 11.17.2012 02:03

Hourly Analysis Program v.4,3 Page 20of40 20

TABLE 1.20.A. COMPONENT LOADS FOR SPACE '' 133-KIOSK '' IN ZONE '' Zone 1 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jan 2300 HEATING DATA AT DES HTG COOLING OA DB / WB 10,3 °C / 1,7 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 0 m² 0 - 0 m² 0 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 0 m² 0 - 0 m² 0 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 2430 W 2430 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 405 W 405 - 0 0 -People 4 291 243 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 156 12 30% 0 0>> Total Zone Loads - 3282 255 - 0 0

TABLE 1.20.B. ENVELOPE LOADS FOR SPACE '' 133-KIOSK '' IN ZONE '' Zone 1 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Space Design Load Summary for ALL AIR AHU Project Name: BAGHDAD MALL 11.17.2012 02:03

Hourly Analysis Program v.4,3 Page 21of40 21

TABLE 1.21.A. COMPONENT LOADS FOR SPACE '' 134-KIOSK '' IN ZONE '' Zone 1 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jan 2300 HEATING DATA AT DES HTG COOLING OA DB / WB 10,3 °C / 1,7 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 0 m² 0 - 0 m² 0 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 0 m² 0 - 0 m² 0 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 450 W 450 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 75 W 75 - 0 0 -People 2 144 120 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 33 6 30% 0 0>> Total Zone Loads - 702 126 - 0 0

TABLE 1.21.B. ENVELOPE LOADS FOR SPACE '' 134-KIOSK '' IN ZONE '' Zone 1 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Space Design Load Summary for ALL AIR AHU Project Name: BAGHDAD MALL 11.17.2012 02:03

Hourly Analysis Program v.4,3 Page 22of40 22

TABLE 1.22.A. COMPONENT LOADS FOR SPACE '' 201-SHOPPING HALL '' IN ZONE '' Zone 1 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jul 2300 HEATING DATA AT DES HTG COOLING OA DB / WB 30,6 °C / 18,5 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 65 m² 408 - 65 m² 513 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 20 m² 240 - 20 m² 200 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 17200 W 17199 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 4300 W 4300 - 0 0 -People 344 24699 20674 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 2342 1034 30% 214 0>> Total Zone Loads - 49188 21708 - 927 0

TABLE 1.22.B. ENVELOPE LOADS FOR SPACE '' 201-SHOPPING HALL '' IN ZONE '' Zone 1 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)W EXPOSURE WALL 25 0,394 - 162 - 197E EXPOSURE WALL 40 0,394 - 246 - 316

Space Design Load Summary for ALL AIR AHU Project Name: BAGHDAD MALL 11.17.2012 02:03

Hourly Analysis Program v.4,3 Page 23of40 23

TABLE 1.23.A. COMPONENT LOADS FOR SPACE '' 211-HALL '' IN ZONE '' Zone 1 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jun 2300 HEATING DATA AT DES HTG COOLING OA DB / WB 29,0 °C / 17,1 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 0 m² 0 - 0 m² 0 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 28 m² 336 - 28 m² 280 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 220 W 220 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 55 W 55 - 0 0 -People 0 0 0 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 31 0 30% 84 0>> Total Zone Loads - 642 0 - 364 0

TABLE 1.23.B. ENVELOPE LOADS FOR SPACE '' 211-HALL '' IN ZONE '' Zone 1 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Space Design Load Summary for ALL AIR AHU Project Name: BAGHDAD MALL 11.17.2012 02:03

Hourly Analysis Program v.4,3 Page 24of40 24

TABLE 1.24.A. COMPONENT LOADS FOR SPACE '' 213-WC MALE '' IN ZONE '' Zone 1 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jul 2300 HEATING DATA AT DES HTG COOLING OA DB / WB 30,6 °C / 18,5 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 30 m² 184 - 30 m² 237 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 35 m² 420 - 35 m² 350 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 300 W 300 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 300 W 300 - 0 0 -People 3 202 106 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 70 5 30% 176 0>> Total Zone Loads - 1477 111 - 763 0

TABLE 1.24.B. ENVELOPE LOADS FOR SPACE '' 213-WC MALE '' IN ZONE '' Zone 1 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)E EXPOSURE WALL 30 0,394 - 184 - 237

Space Design Load Summary for ALL AIR AHU Project Name: BAGHDAD MALL 11.17.2012 02:03

Hourly Analysis Program v.4,3 Page 25of40 25

TABLE 1.25.A. COMPONENT LOADS FOR SPACE '' 214-WC FEMALE '' IN ZONE '' Zone 1 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jun 2300 HEATING DATA AT DES HTG COOLING OA DB / WB 29,0 °C / 17,1 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 0 m² 0 - 0 m² 0 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 30 m² 360 - 30 m² 300 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 240 W 240 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 240 W 240 - 0 0 -People 3 202 106 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 52 5 30% 90 0>> Total Zone Loads - 1094 111 - 390 0

TABLE 1.25.B. ENVELOPE LOADS FOR SPACE '' 214-WC FEMALE '' IN ZONE '' Zone 1 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Space Design Load Summary for ALL AIR AHU Project Name: BAGHDAD MALL 11.17.2012 02:03

Hourly Analysis Program v.4,3 Page 26of40 26

TABLE 1.26.A. COMPONENT LOADS FOR SPACE '' 226-HALL '' IN ZONE '' Zone 1 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jul 0000 HEATING DATA AT DES HTG COOLING OA DB / WB 29,5 °C / 18,1 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 13 m² 82 - 13 m² 99 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 50 m² 600 - 50 m² 500 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 280 W 280 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 70 W 70 - 0 0 -People 0 0 0 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 52 0 30% 180 0>> Total Zone Loads - 1083 0 - 778 0

TABLE 1.26.B. ENVELOPE LOADS FOR SPACE '' 226-HALL '' IN ZONE '' Zone 1 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)W EXPOSURE WALL 13 0,394 - 82 - 99

Space Design Load Summary for ALL AIR AHU Project Name: BAGHDAD MALL 11.17.2012 02:03

Hourly Analysis Program v.4,3 Page 27of40 27

TABLE 1.27.A. COMPONENT LOADS FOR SPACE '' 229-KIOSK '' IN ZONE '' Zone 1 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jan 2300 HEATING DATA AT DES HTG COOLING OA DB / WB 10,3 °C / 1,7 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 0 m² 0 - 0 m² 0 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 0 m² 0 - 0 m² 0 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 1440 W 1440 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 240 W 240 - 0 0 -People 3 215 180 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 95 9 30% 0 0>> Total Zone Loads - 1990 189 - 0 0

TABLE 1.27.B. ENVELOPE LOADS FOR SPACE '' 229-KIOSK '' IN ZONE '' Zone 1 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Space Design Load Summary for ALL AIR AHU Project Name: BAGHDAD MALL 11.17.2012 02:03

Hourly Analysis Program v.4,3 Page 28of40 28

TABLE 1.28.A. COMPONENT LOADS FOR SPACE '' 230-KIOSK '' IN ZONE '' Zone 1 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jan 2300 HEATING DATA AT DES HTG COOLING OA DB / WB 10,3 °C / 1,7 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 0 m² 0 - 0 m² 0 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 0 m² 0 - 0 m² 0 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 450 W 450 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 75 W 75 - 0 0 -People 2 144 120 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 33 6 30% 0 0>> Total Zone Loads - 702 126 - 0 0

TABLE 1.28.B. ENVELOPE LOADS FOR SPACE '' 230-KIOSK '' IN ZONE '' Zone 1 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Space Design Load Summary for ALL AIR AHU Project Name: BAGHDAD MALL 11.17.2012 02:03

Hourly Analysis Program v.4,3 Page 29of40 29

TABLE 1.29.A. COMPONENT LOADS FOR SPACE '' 231-KIOSK '' IN ZONE '' Zone 1 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jan 2300 HEATING DATA AT DES HTG COOLING OA DB / WB 10,3 °C / 1,7 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 0 m² 0 - 0 m² 0 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 0 m² 0 - 0 m² 0 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 450 W 450 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 75 W 75 - 0 0 -People 2 144 120 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 33 6 30% 0 0>> Total Zone Loads - 702 126 - 0 0

TABLE 1.29.B. ENVELOPE LOADS FOR SPACE '' 231-KIOSK '' IN ZONE '' Zone 1 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Space Design Load Summary for ALL AIR AHU Project Name: BAGHDAD MALL 11.17.2012 02:03

Hourly Analysis Program v.4,3 Page 30of40 30

TABLE 1.30.A. COMPONENT LOADS FOR SPACE '' 301-FOOD COURT '' IN ZONE '' Zone 1 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jul 1400 HEATING DATA AT DES HTG COOLING OA DB / WB 44,4 °C / 22,6 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 30 m² 10034 - 30 m² - -Wall Transmission 80 m² 365 - 80 m² 631 -Roof Transmission 266 m² 2468 - 266 m² 2901 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 30 m² 1706 - 30 m² 2006 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 15 m² 180 - 15 m² 150 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 13400 W 13399 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 3350 W 3350 - 0 0 -People 268 19242 16107 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 2537 805 30% 1707 0>> Total Zone Loads - 53282 16912 - 7396 0

TABLE 1.30.B. ENVELOPE LOADS FOR SPACE '' 301-FOOD COURT '' IN ZONE '' Zone 1 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)W EXPOSURE WALL 40 0,394 - 171 - 316E EXPOSURE WALL 40 0,394 - 194 - 316H EXPOSURE ROOF 266 0,545 - 2468 - 2901 SKYLIGHT 30 3,344 0,751 1706 10034 2006

Space Design Load Summary for ALL AIR AHU Project Name: BAGHDAD MALL 11.17.2012 02:03

Hourly Analysis Program v.4,3 Page 31of40 31

TABLE 1.31.A. COMPONENT LOADS FOR SPACE '' 302-KIOSK '' IN ZONE '' Zone 1 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jan 2300 HEATING DATA AT DES HTG COOLING OA DB / WB 10,3 °C / 1,7 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 0 m² 0 - 0 m² 0 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 0 m² 0 - 0 m² 0 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 450 W 450 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 75 W 75 - 0 0 -People 2 144 120 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 33 6 30% 0 0>> Total Zone Loads - 702 126 - 0 0

TABLE 1.31.B. ENVELOPE LOADS FOR SPACE '' 302-KIOSK '' IN ZONE '' Zone 1 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Space Design Load Summary for ALL AIR AHU Project Name: BAGHDAD MALL 11.17.2012 02:03

Hourly Analysis Program v.4,3 Page 32of40 32

TABLE 1.32.A. COMPONENT LOADS FOR SPACE '' 311-HALL '' IN ZONE '' Zone 1 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jun 2300 HEATING DATA AT DES HTG COOLING OA DB / WB 29,0 °C / 17,1 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 0 m² 0 - 0 m² 0 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 28 m² 336 - 28 m² 280 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 220 W 220 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 55 W 55 - 0 0 -People 0 0 0 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 31 0 30% 84 0>> Total Zone Loads - 642 0 - 364 0

TABLE 1.32.B. ENVELOPE LOADS FOR SPACE '' 311-HALL '' IN ZONE '' Zone 1 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Space Design Load Summary for ALL AIR AHU Project Name: BAGHDAD MALL 11.17.2012 02:03

Hourly Analysis Program v.4,3 Page 33of40 33

TABLE 1.33.A. COMPONENT LOADS FOR SPACE '' 313-WC MALE '' IN ZONE '' Zone 1 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jul 2300 HEATING DATA AT DES HTG COOLING OA DB / WB 30,6 °C / 18,5 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 30 m² 184 - 30 m² 237 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 35 m² 420 - 35 m² 350 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 300 W 300 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 300 W 300 - 0 0 -People 3 202 106 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 70 5 30% 176 0>> Total Zone Loads - 1477 111 - 763 0

TABLE 1.33.B. ENVELOPE LOADS FOR SPACE '' 313-WC MALE '' IN ZONE '' Zone 1 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)E EXPOSURE WALL 30 0,394 - 184 - 237

Space Design Load Summary for ALL AIR AHU Project Name: BAGHDAD MALL 11.17.2012 02:03

Hourly Analysis Program v.4,3 Page 34of40 34

TABLE 1.34.A. COMPONENT LOADS FOR SPACE '' 314-WC FEMALE '' IN ZONE '' Zone 1 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jun 2300 HEATING DATA AT DES HTG COOLING OA DB / WB 29,0 °C / 17,1 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 0 m² 0 - 0 m² 0 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 30 m² 360 - 30 m² 300 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 240 W 240 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 240 W 240 - 0 0 -People 3 202 106 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 52 5 30% 90 0>> Total Zone Loads - 1094 111 - 390 0

TABLE 1.34.B. ENVELOPE LOADS FOR SPACE '' 314-WC FEMALE '' IN ZONE '' Zone 1 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Space Design Load Summary for ALL AIR AHU Project Name: BAGHDAD MALL 11.17.2012 02:03

Hourly Analysis Program v.4,3 Page 35of40 35

TABLE 1.35.A. COMPONENT LOADS FOR SPACE '' 403-HALL '' IN ZONE '' Zone 1 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jul 2200 HEATING DATA AT DES HTG COOLING OA DB / WB 32,2 °C / 18,9 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 0 m² 0 - 0 m² 0 -Roof Transmission 11 m² 145 - 11 m² 120 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 28 m² 336 - 28 m² 280 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 220 W 220 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 55 W 55 - 0 0 -People 0 0 0 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 38 0 30% 120 0>> Total Zone Loads - 793 0 - 520 0

TABLE 1.35.B. ENVELOPE LOADS FOR SPACE '' 403-HALL '' IN ZONE '' Zone 1 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)H EXPOSURE ROOF 11 0,545 - 145 - 120

Space Design Load Summary for ALL AIR AHU Project Name: BAGHDAD MALL 11.17.2012 02:03

Hourly Analysis Program v.4,3 Page 36of40 36

TABLE 1.36.A. COMPONENT LOADS FOR SPACE '' 405-WC MALE '' IN ZONE '' Zone 1 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jul 2200 HEATING DATA AT DES HTG COOLING OA DB / WB 32,2 °C / 18,9 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 30 m² 183 - 30 m² 237 -Roof Transmission 20 m² 263 - 20 m² 218 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 35 m² 420 - 35 m² 350 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 300 W 300 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 300 W 300 - 0 0 -People 3 202 106 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 83 5 30% 241 0>> Total Zone Loads - 1752 111 - 1046 0

TABLE 1.36.B. ENVELOPE LOADS FOR SPACE '' 405-WC MALE '' IN ZONE '' Zone 1 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)E EXPOSURE WALL 30 0,394 - 183 - 237H EXPOSURE ROOF 20 0,545 - 263 - 218

Space Design Load Summary for ALL AIR AHU Project Name: BAGHDAD MALL 11.17.2012 02:03

Hourly Analysis Program v.4,3 Page 37of40 37

TABLE 1.37.A. COMPONENT LOADS FOR SPACE '' 406-WC FEMALE '' IN ZONE '' Zone 1 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jul 2200 HEATING DATA AT DES HTG COOLING OA DB / WB 32,2 °C / 18,9 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 0 m² 0 - 0 m² 0 -Roof Transmission 16 m² 210 - 16 m² 175 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 30 m² 360 - 30 m² 300 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 240 W 240 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 240 W 240 - 0 0 -People 3 202 106 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 63 5 30% 142 0>> Total Zone Loads - 1315 111 - 617 0

TABLE 1.37.B. ENVELOPE LOADS FOR SPACE '' 406-WC FEMALE '' IN ZONE '' Zone 1 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)H EXPOSURE ROOF 16 0,545 - 210 - 175

Space Design Load Summary for ALL AIR AHU Project Name: BAGHDAD MALL 11.17.2012 02:03

Hourly Analysis Program v.4,3 Page 38of40 38

TABLE 1.38.A. COMPONENT LOADS FOR SPACE '' 409-HALL '' IN ZONE '' Zone 1 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jul 2200 HEATING DATA AT DES HTG COOLING OA DB / WB 32,2 °C / 18,9 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 0 m² 0 - 0 m² 0 -Roof Transmission 6 m² 79 - 6 m² 65 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 10 m² 120 - 10 m² 100 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 140 W 140 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 35 W 35 - 0 0 -People 0 0 0 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 19 0 30% 50 0>> Total Zone Loads - 393 0 - 215 0

TABLE 1.38.B. ENVELOPE LOADS FOR SPACE '' 409-HALL '' IN ZONE '' Zone 1 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)H EXPOSURE ROOF 6 0,545 - 79 - 65

Space Design Load Summary for ALL AIR AHU Project Name: BAGHDAD MALL 11.17.2012 02:03

Hourly Analysis Program v.4,3 Page 39of40 39

TABLE 1.39.A. COMPONENT LOADS FOR SPACE '' 411-OFFICE HALL '' IN ZONE '' Zone 1 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG COOLING OA DB / WB 43,1 °C / 22,2 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 23 m² 1488 - 23 m² - -Wall Transmission 7 m² 31 - 7 m² 57 -Roof Transmission 189 m² 2132 - 189 m² 2062 -Window Transmission 23 m² 1260 - 23 m² 1505 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 135 m² 3293 - 135 m² 2550 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 3780 W 3780 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 945 W 945 - 0 0 -People 19 1357 1136 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 714 57 30% 1852 0>> Total Zone Loads - 14999 1193 - 8025 0

TABLE 1.39.B. ENVELOPE LOADS FOR SPACE '' 411-OFFICE HALL '' IN ZONE '' Zone 1 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)N EXPOSURE WALL 7 0,394 - 31 - 57 WINDOW 1 23 3,300 0,751 1260 1488 1505H EXPOSURE ROOF 189 0,545 - 2132 - 2062

Space Design Load Summary for ALL AIR AHU Project Name: BAGHDAD MALL 11.17.2012 02:03

Hourly Analysis Program v.4,3 Page 40of40 40

TABLE 1.40.A. COMPONENT LOADS FOR SPACE '' 415-HALL '' IN ZONE '' Zone 1 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG COOLING OA DB / WB 44,4 °C / 22,6 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 0 m² 0 - 0 m² 0 -Roof Transmission 37 m² 391 - 37 m² 404 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 80 m² 2727 - 80 m² 2000 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 740 W 740 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 185 W 185 - 0 0 -People 0 0 0 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 202 0 30% 721 0>> Total Zone Loads - 4245 0 - 3125 0

TABLE 1.40.B. ENVELOPE LOADS FOR SPACE '' 415-HALL '' IN ZONE '' Zone 1 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)H EXPOSURE ROOF 37 0,545 - 391 - 404

Space Design Load Summary for VRV Project Name: BAGHDAD MALL 11.14.2012 10:45

Hourly Analysis Program v.4,3 Page 1 of 6

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 401-PRIVATE RESTAURANT '' IN ZONE '' Zone 1 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG COOLING OA DB / WB 45,0 °C / 22,8 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 129 m² 13121 - 129 m² - -Wall Transmission 116 m² 499 - 116 m² 913 -Roof Transmission 401 m² 3963 - 401 m² 4374 -Window Transmission 129 m² 7511 - 129 m² 8527 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 270 m² 5923 - 270 m² 4500 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 18045 W 18044 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 2005 W 2005 - 0 0 -People 267 18018 9410 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 3454 471 30% 5494 0>> Total Zone Loads - 72538 9881 - 23809 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 401-PRIVATE RESTAURANT '' IN ZONE '' Zone 1 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)W EXPOSURE WALL 75 0,394 - 324 - 592N EXPOSURE WALL 24 0,394 - 96 - 192 WINDOW 1 46 3,300 0,751 2651 2720 3010E EXPOSURE WALL 13 0,394 - 64 - 101 WINDOW 1 72 3,300 0,751 4197 9546 4765S EXPOSURE WALL 4 0,394 - 15 - 28 WINDOW 1 11 3,300 0,751 663 855 752H EXPOSURE ROOF 401 0,545 - 3963 - 4374

Space Design Load Summary for VRV Project Name: BAGHDAD MALL 11.14.2012 10:45

Hourly Analysis Program v.4,3 Page 2 of 6

TABLE 2.1.A. COMPONENT LOADS FOR SPACE '' 410-OFFICE '' IN ZONE '' Zone 2 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG COOLING OA DB / WB 45,0 °C / 22,8 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 38 m² 7274 - 38 m² - -Wall Transmission 235 m² 1157 - 235 m² 2006 -Roof Transmission 360 m² 3372 - 360 m² 3927 -Window Transmission 38 m² 1868 - 38 m² 2120 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 50 m² 600 - 50 m² 500 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 9000 W 8999 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 12600 W 12599 - 0 0 -People 36 2585 2164 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 1923 108 30% 2566 0>> Total Zone Loads - 40377 2272 - 11119 0

TABLE 2.1.B. ENVELOPE LOADS FOR SPACE '' 410-OFFICE '' IN ZONE '' Zone 2 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)E EXPOSURE WALL 54 0,394 - 264 - 422 WINDOW 1 17 2,827 0,576 822 1122 933S EXPOSURE WALL 85 0,394 - 366 - 670S EXPOSURE WALL 38 0,598 - 275 - 448WSW EXPOSURE WALL 59 0,394 - 252 - 465 WINDOW 1 21 2,827 0,576 1046 6152 1187H EXPOSURE ROOF 360 0,545 - 3372 - 3927

Space Design Load Summary for VRV Project Name: BAGHDAD MALL 11.14.2012 10:45

Hourly Analysis Program v.4,3 Page 3 of 6

TABLE 3.1.A. COMPONENT LOADS FOR SPACE '' 412-OFFICE '' IN ZONE '' Zone 3 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Sep 1500 HEATING DATA AT DES HTG COOLING OA DB / WB 42,7 °C / 21,6 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 12 m² 3814 - 12 m² - -Wall Transmission 28 m² 94 - 28 m² 221 -Roof Transmission 60 m² 436 - 60 m² 654 -Window Transmission 12 m² 518 - 12 m² 678 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 0 m² 0 - 0 m² 0 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 1500 W 1500 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 2100 W 2100 - 0 0 -People 6 431 361 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 445 18 30% 466 0>> Total Zone Loads - 9337 379 - 2020 0

TABLE 3.1.B. ENVELOPE LOADS FOR SPACE '' 412-OFFICE '' IN ZONE '' Zone 3 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)WSW EXPOSURE WALL 28 0,394 - 94 - 221 WINDOW 1 12 2,827 0,576 518 3814 678H EXPOSURE ROOF 60 0,545 - 436 - 654

Space Design Load Summary for VRV Project Name: BAGHDAD MALL 11.14.2012 10:45

Hourly Analysis Program v.4,3 Page 4 of 6

TABLE 4.1.A. COMPONENT LOADS FOR SPACE '' 413-OFFICE '' IN ZONE '' Zone 4 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Sep 1500 HEATING DATA AT DES HTG COOLING OA DB / WB 42,7 °C / 21,6 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 12 m² 3814 - 12 m² - -Wall Transmission 28 m² 94 - 28 m² 221 -Roof Transmission 59 m² 428 - 59 m² 644 -Window Transmission 12 m² 518 - 12 m² 678 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 0 m² 0 - 0 m² 0 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 1475 W 1475 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 2065 W 2065 - 0 0 -People 6 431 361 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 441 18 30% 463 0>> Total Zone Loads - 9266 379 - 2006 0

TABLE 4.1.B. ENVELOPE LOADS FOR SPACE '' 413-OFFICE '' IN ZONE '' Zone 4 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)WSW EXPOSURE WALL 28 0,394 - 94 - 221 WINDOW 1 12 2,827 0,576 518 3814 678H EXPOSURE ROOF 59 0,545 - 428 - 644

Space Design Load Summary for VRV Project Name: BAGHDAD MALL 11.14.2012 10:45

Hourly Analysis Program v.4,3 Page 5 of 6

TABLE 5.1.A. COMPONENT LOADS FOR SPACE '' 414-OFFICE '' IN ZONE '' Zone 5 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Sep 1500 HEATING DATA AT DES HTG COOLING OA DB / WB 42,7 °C / 21,6 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 12 m² 3814 - 12 m² - -Wall Transmission 28 m² 94 - 28 m² 221 -Roof Transmission 59 m² 428 - 59 m² 644 -Window Transmission 12 m² 518 - 12 m² 678 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 0 m² 0 - 0 m² 0 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 1475 W 1475 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 2065 W 2065 - 0 0 -People 6 431 361 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 441 18 30% 463 0>> Total Zone Loads - 9266 379 - 2006 0

TABLE 5.1.B. ENVELOPE LOADS FOR SPACE '' 414-OFFICE '' IN ZONE '' Zone 5 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)WSW EXPOSURE WALL 28 0,394 - 94 - 221 WINDOW 1 12 2,827 0,576 518 3814 678H EXPOSURE ROOF 59 0,545 - 428 - 644

Space Design Load Summary for VRV Project Name: BAGHDAD MALL 11.14.2012 10:45

Hourly Analysis Program v.4,3 Page 6 of 6

TABLE 6.1.A. COMPONENT LOADS FOR SPACE '' 416-KITCHEN '' IN ZONE '' Zone 6 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jul 2200 HEATING DATA AT DES HTG COOLING OA DB / WB 32,2 °C / 18,9 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 28,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 80 m² 380 - 80 m² 631 -Roof Transmission 159 m² 1745 - 159 m² 1734 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 0 m² 0 - 0 m² 0 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 3060 W 3060 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 30600 W 30599 - 0 0 -People 15 1231 1187 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 1851 59 30% 710 0>> Total Zone Loads - 38866 1246 - 3075 0

TABLE 6.1.B. ENVELOPE LOADS FOR SPACE '' 416-KITCHEN '' IN ZONE '' Zone 6 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)WSW EXPOSURE WALL 35 0,394 - 165 - 276W EXPOSURE WALL 45 0,394 - 215 - 355H EXPOSURE ROOF 159 0,545 - 1745 - 1734

Space Design Load Summary for FCU Project Name: BAGHDAD MALL 11.13.2012 Prepared by: bjk 11:36

Hourly Analysis Program v.4,3 Page 1of64 1

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' GR03-SHOP '' IN ZONE '' Zone 1 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jul 2300 HEATING DATA AT DES HTG COOLING OA DB / WB 30,6 °C / 18,5 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 40 m² 246 - 40 m² 316 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 73 m² 854 - 73 m² 712 -Partitions 0 m² 0 - 0 m² 0 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 6570 W 6570 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 1095 W 1095 - 0 0 -People 11 786 658 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 478 33 30% 308 0>> Total Zone Loads - 10028 691 - 1335 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' GR03-SHOP '' IN ZONE '' Zone 1 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)E EXPOSURE WALL 40 0,394 - 246 - 316

Space Design Load Summary for FCU Project Name: BAGHDAD MALL 11.13.2012 Prepared by: bjk 11:36

Hourly Analysis Program v.4,3 Page 2of64 2

TABLE 2.1.A. COMPONENT LOADS FOR SPACE '' GR04-SHOP '' IN ZONE '' Zone 2 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jul 2300 HEATING DATA AT DES HTG COOLING OA DB / WB 30,6 °C / 18,5 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 40 m² 246 - 40 m² 316 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 70 m² 819 - 70 m² 683 -Partitions 0 m² 0 - 0 m² 0 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 6300 W 6300 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 1050 W 1050 - 0 0 -People 10 754 631 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 458 32 30% 299 0>> Total Zone Loads - 9626 662 - 1297 0

TABLE 2.1.B. ENVELOPE LOADS FOR SPACE '' GR04-SHOP '' IN ZONE '' Zone 2 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)E EXPOSURE WALL 40 0,394 - 246 - 316

Space Design Load Summary for FCU Project Name: BAGHDAD MALL 11.13.2012 Prepared by: bjk 11:36

Hourly Analysis Program v.4,3 Page 3of64 3

TABLE 3.1.A. COMPONENT LOADS FOR SPACE '' GR05-SHOP '' IN ZONE '' Zone 3 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jul 2300 HEATING DATA AT DES HTG COOLING OA DB / WB 30,6 °C / 18,5 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 40 m² 246 - 40 m² 316 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 66 m² 772 - 66 m² 644 -Partitions 0 m² 0 - 0 m² 0 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 5940 W 5940 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 990 W 990 - 0 0 -People 10 710 595 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 433 30 30% 288 0>> Total Zone Loads - 9091 624 - 1247 0

TABLE 3.1.B. ENVELOPE LOADS FOR SPACE '' GR05-SHOP '' IN ZONE '' Zone 3 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)E EXPOSURE WALL 40 0,394 - 246 - 316

Space Design Load Summary for FCU Project Name: BAGHDAD MALL 11.13.2012 Prepared by: bjk 11:36

Hourly Analysis Program v.4,3 Page 4of64 4

TABLE 4.1.A. COMPONENT LOADS FOR SPACE '' GR06-SHOP '' IN ZONE '' Zone 4 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jun 2300 HEATING DATA AT DES HTG COOLING OA DB / WB 29,0 °C / 17,1 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 0 m² 0 - 0 m² 0 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 12 m² 140 - 12 m² 117 -Partitions 0 m² 0 - 0 m² 0 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 1080 W 1080 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 180 W 180 - 0 0 -People 2 129 108 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 76 5 30% 35 0>> Total Zone Loads - 1606 114 - 152 0

TABLE 4.1.B. ENVELOPE LOADS FOR SPACE '' GR06-SHOP '' IN ZONE '' Zone 4 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Space Design Load Summary for FCU Project Name: BAGHDAD MALL 11.13.2012 Prepared by: bjk 11:36

Hourly Analysis Program v.4,3 Page 5of64 5

TABLE 5.1.A. COMPONENT LOADS FOR SPACE '' GR07-SHOP '' IN ZONE '' Zone 5 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jul 2300 HEATING DATA AT DES HTG COOLING OA DB / WB 30,6 °C / 18,5 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 13 m² 77 - 13 m² 99 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 8 m² 94 - 8 m² 78 -Partitions 0 m² 0 - 0 m² 0 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 720 W 720 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 120 W 120 - 0 0 -People 4 287 240 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 65 12 30% 53 0>> Total Zone Loads - 1362 252 - 230 0

TABLE 5.1.B. ENVELOPE LOADS FOR SPACE '' GR07-SHOP '' IN ZONE '' Zone 5 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)E EXPOSURE WALL 13 0,394 - 77 - 99

Space Design Load Summary for FCU Project Name: BAGHDAD MALL 11.13.2012 Prepared by: bjk 11:36

Hourly Analysis Program v.4,3 Page 6of64 6

TABLE 6.1.A. COMPONENT LOADS FOR SPACE '' GR21-SHOP '' IN ZONE '' Zone 6 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Sep 1500 HEATING DATA AT DES HTG COOLING OA DB / WB 42,7 °C / 21,6 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 38 m² 12174 - 38 m² - -Wall Transmission 47 m² 156 - 47 m² 368 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 38 m² 1622 - 38 m² 2122 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 56 m² 654 - 56 m² 546 -Partitions 0 m² 0 - 0 m² 0 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 5040 W 5040 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 840 W 840 - 0 0 -People 8 603 505 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 1054 25 30% 911 0>> Total Zone Loads - 22143 530 - 3947 0

TABLE 6.1.B. ENVELOPE LOADS FOR SPACE '' GR21-SHOP '' IN ZONE '' Zone 6 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)WSW EXPOSURE WALL 47 0,394 - 156 - 368 WINDOW 1 38 2,770 0,576 1622 12174 2122

Space Design Load Summary for FCU Project Name: BAGHDAD MALL 11.13.2012 Prepared by: bjk 11:36

Hourly Analysis Program v.4,3 Page 7of64 7

TABLE 7.1.A. COMPONENT LOADS FOR SPACE '' GR24-SHOP '' IN ZONE '' Zone 7 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jun 2300 HEATING DATA AT DES HTG COOLING OA DB / WB 29,0 °C / 17,1 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 0 m² 0 - 0 m² 0 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 5 m² 58 - 5 m² 49 -Partitions 15 m² 180 - 15 m² 150 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 450 W 450 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 75 W 75 - 0 0 -People 2 144 120 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 45 6 30% 60 0>> Total Zone Loads - 952 126 - 258 0

TABLE 7.1.B. ENVELOPE LOADS FOR SPACE '' GR24-SHOP '' IN ZONE '' Zone 7 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Space Design Load Summary for FCU Project Name: BAGHDAD MALL 11.13.2012 Prepared by: bjk 11:36

Hourly Analysis Program v.4,3 Page 8of64 8

TABLE 8.1.A. COMPONENT LOADS FOR SPACE '' GR25-SHOP '' IN ZONE '' Zone 8 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jul 0000 HEATING DATA AT DES HTG COOLING OA DB / WB 29,5 °C / 18,1 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 35 m² 229 - 35 m² 276 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 56 m² 655 - 56 m² 546 -Partitions 30 m² 360 - 30 m² 300 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 5040 W 5040 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 840 W 840 - 0 0 -People 8 603 505 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 386 25 30% 337 0>> Total Zone Loads - 8113 530 - 1459 0

TABLE 8.1.B. ENVELOPE LOADS FOR SPACE '' GR25-SHOP '' IN ZONE '' Zone 8 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)W EXPOSURE WALL 35 0,394 - 229 - 276

Space Design Load Summary for FCU Project Name: BAGHDAD MALL 11.13.2012 Prepared by: bjk 11:36

Hourly Analysis Program v.4,3 Page 9of64 9

TABLE 9.1.A. COMPONENT LOADS FOR SPACE '' GR26-SHOP '' IN ZONE '' Zone 9 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jul 0000 HEATING DATA AT DES HTG COOLING OA DB / WB 29,5 °C / 18,1 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 40 m² 262 - 40 m² 316 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 55 m² 643 - 55 m² 536 -Partitions 0 m² 0 - 0 m² 0 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 4950 W 4950 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 825 W 825 - 0 0 -People 8 592 496 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 364 25 30% 256 0>> Total Zone Loads - 7635 520 - 1107 0

TABLE 9.1.B. ENVELOPE LOADS FOR SPACE '' GR26-SHOP '' IN ZONE '' Zone 9 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)W EXPOSURE WALL 40 0,394 - 262 - 316

Space Design Load Summary for FCU Project Name: BAGHDAD MALL 11.13.2012 Prepared by: bjk 11:36

Hourly Analysis Program v.4,3 Page 10of64 10

TABLE 10.1.A. COMPONENT LOADS FOR SPACE '' GR27-SHOP '' IN ZONE '' Zone 10 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jul 0000 HEATING DATA AT DES HTG COOLING OA DB / WB 29,5 °C / 18,1 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 20 m² 131 - 20 m² 158 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 23 m² 269 - 23 m² 224 -Partitions 0 m² 0 - 0 m² 0 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 2070 W 2070 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 345 W 345 - 0 0 -People 3 248 207 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 153 10 30% 115 0>> Total Zone Loads - 3215 218 - 497 0

TABLE 10.1.B. ENVELOPE LOADS FOR SPACE '' GR27-SHOP '' IN ZONE '' Zone 10 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)W EXPOSURE WALL 20 0,394 - 131 - 158

Space Design Load Summary for FCU Project Name: BAGHDAD MALL 11.13.2012 Prepared by: bjk 11:36

Hourly Analysis Program v.4,3 Page 11of64 11

TABLE 11.1.A. COMPONENT LOADS FOR SPACE '' 102-SHOP '' IN ZONE '' Zone 11 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jul 2300 HEATING DATA AT DES HTG COOLING OA DB / WB 30,6 °C / 18,5 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 40 m² 246 - 40 m² 316 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 0 m² 0 - 0 m² 0 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 5400 W 5400 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 900 W 900 - 0 0 -People 9 646 541 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 360 27 30% 95 0>> Total Zone Loads - 7551 568 - 410 0

TABLE 11.1.B. ENVELOPE LOADS FOR SPACE '' 102-SHOP '' IN ZONE '' Zone 11 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)E EXPOSURE WALL 40 0,394 - 246 - 316

Space Design Load Summary for FCU Project Name: BAGHDAD MALL 11.13.2012 Prepared by: bjk 11:36

Hourly Analysis Program v.4,3 Page 12of64 12

TABLE 12.1.A. COMPONENT LOADS FOR SPACE '' 103-SHOP '' IN ZONE '' Zone 12 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jul 2300 HEATING DATA AT DES HTG COOLING OA DB / WB 30,6 °C / 18,5 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 40 m² 246 - 40 m² 316 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 0 m² 0 - 0 m² 0 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 5220 W 5220 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 870 W 870 - 0 0 -People 9 624 523 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 348 26 30% 95 0>> Total Zone Loads - 7308 549 - 410 0

TABLE 12.1.B. ENVELOPE LOADS FOR SPACE '' 103-SHOP '' IN ZONE '' Zone 12 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)E EXPOSURE WALL 40 0,394 - 246 - 316

Space Design Load Summary for FCU Project Name: BAGHDAD MALL 11.13.2012 Prepared by: bjk 11:36

Hourly Analysis Program v.4,3 Page 13of64 13

TABLE 13.1.A. COMPONENT LOADS FOR SPACE '' 104-SHOP '' IN ZONE '' Zone 13 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jul 2300 HEATING DATA AT DES HTG COOLING OA DB / WB 30,6 °C / 18,5 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 40 m² 246 - 40 m² 316 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 0 m² 0 - 0 m² 0 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 4230 W 4230 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 705 W 705 - 0 0 -People 7 506 423 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 284 21 30% 95 0>> Total Zone Loads - 5971 445 - 410 0

TABLE 13.1.B. ENVELOPE LOADS FOR SPACE '' 104-SHOP '' IN ZONE '' Zone 13 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)E EXPOSURE WALL 40 0,394 - 246 - 316

Space Design Load Summary for FCU Project Name: BAGHDAD MALL 11.13.2012 Prepared by: bjk 11:36

Hourly Analysis Program v.4,3 Page 14of64 14

TABLE 14.1.A. COMPONENT LOADS FOR SPACE '' 105-SHOP '' IN ZONE '' Zone 14 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jul 2300 HEATING DATA AT DES HTG COOLING OA DB / WB 30,6 °C / 18,5 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 40 m² 246 - 40 m² 316 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 0 m² 0 - 0 m² 0 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 3870 W 3870 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 645 W 645 - 0 0 -People 6 463 387 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 261 19 30% 95 0>> Total Zone Loads - 5485 407 - 410 0

TABLE 14.1.B. ENVELOPE LOADS FOR SPACE '' 105-SHOP '' IN ZONE '' Zone 14 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)E EXPOSURE WALL 40 0,394 - 246 - 316

Space Design Load Summary for FCU Project Name: BAGHDAD MALL 11.13.2012 Prepared by: bjk 11:36

Hourly Analysis Program v.4,3 Page 15of64 15

TABLE 15.1.A. COMPONENT LOADS FOR SPACE '' 106-SHOP '' IN ZONE '' Zone 15 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jul 2300 HEATING DATA AT DES HTG COOLING OA DB / WB 30,6 °C / 18,5 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 40 m² 246 - 40 m² 316 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 0 m² 0 - 0 m² 0 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 3690 W 3690 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 615 W 615 - 0 0 -People 6 441 369 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 250 18 30% 95 0>> Total Zone Loads - 5242 388 - 410 0

TABLE 15.1.B. ENVELOPE LOADS FOR SPACE '' 106-SHOP '' IN ZONE '' Zone 15 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)E EXPOSURE WALL 40 0,394 - 246 - 316

Space Design Load Summary for FCU Project Name: BAGHDAD MALL 11.13.2012 Prepared by: bjk 11:36

Hourly Analysis Program v.4,3 Page 16of64 16

TABLE 16.1.A. COMPONENT LOADS FOR SPACE '' 107-SHOP '' IN ZONE '' Zone 16 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jul 2300 HEATING DATA AT DES HTG COOLING OA DB / WB 30,6 °C / 18,5 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 40 m² 246 - 40 m² 316 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 0 m² 0 - 0 m² 0 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 4680 W 4680 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 780 W 780 - 0 0 -People 8 560 469 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 313 23 30% 95 0>> Total Zone Loads - 6579 492 - 410 0

TABLE 16.1.B. ENVELOPE LOADS FOR SPACE '' 107-SHOP '' IN ZONE '' Zone 16 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)E EXPOSURE WALL 40 0,394 - 246 - 316

Space Design Load Summary for FCU Project Name: BAGHDAD MALL 11.13.2012 Prepared by: bjk 11:36

Hourly Analysis Program v.4,3 Page 17of64 17

TABLE 17.1.A. COMPONENT LOADS FOR SPACE '' 108-SHOP '' IN ZONE '' Zone 17 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jul 2300 HEATING DATA AT DES HTG COOLING OA DB / WB 30,6 °C / 18,5 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 40 m² 246 - 40 m² 316 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 0 m² 0 - 0 m² 0 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 4500 W 4500 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 750 W 750 - 0 0 -People 7 538 451 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 302 23 30% 95 0>> Total Zone Loads - 6336 473 - 410 0

TABLE 17.1.B. ENVELOPE LOADS FOR SPACE '' 108-SHOP '' IN ZONE '' Zone 17 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)E EXPOSURE WALL 40 0,394 - 246 - 316

Space Design Load Summary for FCU Project Name: BAGHDAD MALL 11.13.2012 Prepared by: bjk 11:36

Hourly Analysis Program v.4,3 Page 18of64 18

TABLE 18.1.A. COMPONENT LOADS FOR SPACE '' 109-SHOP '' IN ZONE '' Zone 18 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jul 2300 HEATING DATA AT DES HTG COOLING OA DB / WB 30,6 °C / 18,5 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 40 m² 246 - 40 m² 316 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 0 m² 0 - 0 m² 0 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 5400 W 5400 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 900 W 900 - 0 0 -People 9 646 541 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 360 27 30% 95 0>> Total Zone Loads - 7551 568 - 410 0

TABLE 18.1.B. ENVELOPE LOADS FOR SPACE '' 109-SHOP '' IN ZONE '' Zone 18 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)E EXPOSURE WALL 40 0,394 - 246 - 316

Space Design Load Summary for FCU Project Name: BAGHDAD MALL 11.13.2012 Prepared by: bjk 11:36

Hourly Analysis Program v.4,3 Page 19of64 19

TABLE 19.1.A. COMPONENT LOADS FOR SPACE '' 110-SHOP '' IN ZONE '' Zone 19 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jul 2300 HEATING DATA AT DES HTG COOLING OA DB / WB 30,6 °C / 18,5 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 25 m² 154 - 25 m² 197 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 60 m² 720 - 60 m² 600 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 3780 W 3780 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 630 W 630 - 0 0 -People 6 452 378 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 287 19 30% 239 0>> Total Zone Loads - 6022 397 - 1036 0

TABLE 19.1.B. ENVELOPE LOADS FOR SPACE '' 110-SHOP '' IN ZONE '' Zone 19 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)E EXPOSURE WALL 25 0,394 - 154 - 197

Space Design Load Summary for FCU Project Name: BAGHDAD MALL 11.13.2012 Prepared by: bjk 11:36

Hourly Analysis Program v.4,3 Page 20of64 20

TABLE 20.1.A. COMPONENT LOADS FOR SPACE '' 117-DEPARTMENT STORE '' IN ZONE '' Zone 20 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Aug 0000 HEATING DATA AT DES HTG COOLING OA DB / WB 29,5 °C / 18,1 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 273 m² 1748 - 273 m² 2302 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 50 m² 600 - 50 m² 500 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 20020 W 20018 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 5460 W 5460 - 0 0 -People 55 3918 3280 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 1587 164 30% 841 0>> Total Zone Loads - 33331 3444 - 3643 0

TABLE 20.1.B. ENVELOPE LOADS FOR SPACE '' 117-DEPARTMENT STORE '' IN ZONE '' Zone 20 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)E EXPOSURE WALL 70 0,394 - 425 - 552S EXPOSURE WALL 85 0,394 - 508 - 670S EXPOSURE WALL 38 0,598 - 297 - 448WSW EXPOSURE WALL 80 0,394 - 518 - 631

Space Design Load Summary for FCU Project Name: BAGHDAD MALL 11.13.2012 Prepared by: bjk 11:36

Hourly Analysis Program v.4,3 Page 21of64 21

TABLE 21.1.A. COMPONENT LOADS FOR SPACE '' 119-SHOP '' IN ZONE '' Zone 21 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Aug 0000 HEATING DATA AT DES HTG COOLING OA DB / WB 29,5 °C / 18,1 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 100 m² 648 - 100 m² 789 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 0 m² 0 - 0 m² 0 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 9540 W 9539 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 1590 W 1590 - 0 0 -People 16 1141 955 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 646 48 30% 237 0>> Total Zone Loads - 13564 1003 - 1025 0

TABLE 21.1.B. ENVELOPE LOADS FOR SPACE '' 119-SHOP '' IN ZONE '' Zone 21 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)WSW EXPOSURE WALL 100 0,394 - 648 - 789

Space Design Load Summary for FCU Project Name: BAGHDAD MALL 11.13.2012 Prepared by: bjk 11:36

Hourly Analysis Program v.4,3 Page 22of64 22

TABLE 22.1.A. COMPONENT LOADS FOR SPACE '' 120-SHOP '' IN ZONE '' Zone 22 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Aug 0000 HEATING DATA AT DES HTG COOLING OA DB / WB 29,5 °C / 18,1 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 22 m² 142 - 22 m² 174 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 0 m² 0 - 0 m² 0 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 2700 W 2700 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 450 W 450 - 0 0 -People 4 323 270 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 181 14 30% 52 0>> Total Zone Loads - 3796 284 - 226 0

TABLE 22.1.B. ENVELOPE LOADS FOR SPACE '' 120-SHOP '' IN ZONE '' Zone 22 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)WSW EXPOSURE WALL 22 0,394 - 142 - 174

Space Design Load Summary for FCU Project Name: BAGHDAD MALL 11.13.2012 Prepared by: bjk 11:36

Hourly Analysis Program v.4,3 Page 23of64 23

TABLE 23.1.A. COMPONENT LOADS FOR SPACE '' 121-SHOP '' IN ZONE '' Zone 23 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Aug 0000 HEATING DATA AT DES HTG COOLING OA DB / WB 29,5 °C / 18,1 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 40 m² 259 - 40 m² 316 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 0 m² 0 - 0 m² 0 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 5940 W 5939 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 990 W 990 - 0 0 -People 10 710 595 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 395 30 30% 95 0>> Total Zone Loads - 8294 624 - 410 0

TABLE 23.1.B. ENVELOPE LOADS FOR SPACE '' 121-SHOP '' IN ZONE '' Zone 23 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)WSW EXPOSURE WALL 40 0,394 - 259 - 316

Space Design Load Summary for FCU Project Name: BAGHDAD MALL 11.13.2012 Prepared by: bjk 11:36

Hourly Analysis Program v.4,3 Page 24of64 24

TABLE 24.1.A. COMPONENT LOADS FOR SPACE '' 122-SHOP '' IN ZONE '' Zone 24 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jul 0000 HEATING DATA AT DES HTG COOLING OA DB / WB 29,5 °C / 18,1 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 40 m² 262 - 40 m² 316 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 0 m² 0 - 0 m² 0 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 6300 W 6299 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 1050 W 1050 - 0 0 -People 10 753 631 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 418 32 30% 95 0>> Total Zone Loads - 8783 662 - 410 0

TABLE 24.1.B. ENVELOPE LOADS FOR SPACE '' 122-SHOP '' IN ZONE '' Zone 24 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)W EXPOSURE WALL 40 0,394 - 262 - 316

Space Design Load Summary for FCU Project Name: BAGHDAD MALL 11.13.2012 Prepared by: bjk 11:36

Hourly Analysis Program v.4,3 Page 25of64 25

TABLE 25.1.A. COMPONENT LOADS FOR SPACE '' 123-SHOP '' IN ZONE '' Zone 25 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jul 0000 HEATING DATA AT DES HTG COOLING OA DB / WB 29,5 °C / 18,1 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 40 m² 262 - 40 m² 316 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 0 m² 0 - 0 m² 0 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 4950 W 4950 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 825 W 825 - 0 0 -People 8 592 496 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 331 25 30% 95 0>> Total Zone Loads - 6959 520 - 410 0

TABLE 25.1.B. ENVELOPE LOADS FOR SPACE '' 123-SHOP '' IN ZONE '' Zone 25 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)W EXPOSURE WALL 40 0,394 - 262 - 316

Space Design Load Summary for FCU Project Name: BAGHDAD MALL 11.13.2012 Prepared by: bjk 11:36

Hourly Analysis Program v.4,3 Page 26of64 26

TABLE 26.1.A. COMPONENT LOADS FOR SPACE '' 124-SHOP '' IN ZONE '' Zone 26 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jul 0000 HEATING DATA AT DES HTG COOLING OA DB / WB 29,5 °C / 18,1 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 35 m² 229 - 35 m² 276 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 50 m² 600 - 50 m² 500 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 4320 W 4320 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 720 W 720 - 0 0 -People 7 517 433 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 319 22 30% 233 0>> Total Zone Loads - 6704 454 - 1009 0

TABLE 26.1.B. ENVELOPE LOADS FOR SPACE '' 124-SHOP '' IN ZONE '' Zone 26 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)W EXPOSURE WALL 35 0,394 - 229 - 276

Space Design Load Summary for FCU Project Name: BAGHDAD MALL 11.13.2012 Prepared by: bjk 11:36

Hourly Analysis Program v.4,3 Page 27of64 27

TABLE 27.1.A. COMPONENT LOADS FOR SPACE '' 127-SHOP '' IN ZONE '' Zone 27 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jul 0000 HEATING DATA AT DES HTG COOLING OA DB / WB 29,5 °C / 18,1 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 32 m² 209 - 32 m² 252 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 45 m² 540 - 45 m² 450 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 4770 W 4770 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 795 W 795 - 0 0 -People 8 571 478 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 344 24 30% 211 0>> Total Zone Loads - 7228 501 - 913 0

TABLE 27.1.B. ENVELOPE LOADS FOR SPACE '' 127-SHOP '' IN ZONE '' Zone 27 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)W EXPOSURE WALL 32 0,394 - 209 - 252

Space Design Load Summary for FCU Project Name: BAGHDAD MALL 11.13.2012 Prepared by: bjk 11:36

Hourly Analysis Program v.4,3 Page 28of64 28

TABLE 28.1.A. COMPONENT LOADS FOR SPACE '' 128-SHOP '' IN ZONE '' Zone 28 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jul 0000 HEATING DATA AT DES HTG COOLING OA DB / WB 29,5 °C / 18,1 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 55 m² 360 - 55 m² 434 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 0 m² 0 - 0 m² 0 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 6120 W 6119 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 1020 W 1020 - 0 0 -People 10 732 613 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 412 31 30% 130 0>> Total Zone Loads - 8642 643 - 564 0

TABLE 28.1.B. ENVELOPE LOADS FOR SPACE '' 128-SHOP '' IN ZONE '' Zone 28 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)W EXPOSURE WALL 55 0,394 - 360 - 434

Space Design Load Summary for FCU Project Name: BAGHDAD MALL 11.13.2012 Prepared by: bjk 11:36

Hourly Analysis Program v.4,3 Page 29of64 29

TABLE 29.1.A. COMPONENT LOADS FOR SPACE '' 135-SHOP '' IN ZONE '' Zone 29 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jun 2300 HEATING DATA AT DES HTG COOLING OA DB / WB 29,0 °C / 17,1 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 0 m² 0 - 0 m² 0 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 10 m² 120 - 10 m² 100 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 1170 W 1170 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 195 W 195 - 0 0 -People 2 140 117 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 81 6 30% 30 0>> Total Zone Loads - 1706 123 - 130 0

TABLE 29.1.B. ENVELOPE LOADS FOR SPACE '' 135-SHOP '' IN ZONE '' Zone 29 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Space Design Load Summary for FCU Project Name: BAGHDAD MALL 11.13.2012 Prepared by: bjk 11:36

Hourly Analysis Program v.4,3 Page 30of64 30

TABLE 30.1.A. COMPONENT LOADS FOR SPACE '' 202-SHOP '' IN ZONE '' Zone 30 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jul 2300 HEATING DATA AT DES HTG COOLING OA DB / WB 30,6 °C / 18,5 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 40 m² 246 - 40 m² 316 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 0 m² 0 - 0 m² 0 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 6120 W 6120 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 1020 W 1020 - 0 0 -People 10 732 613 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 406 31 30% 95 0>> Total Zone Loads - 8523 643 - 410 0

TABLE 30.1.B. ENVELOPE LOADS FOR SPACE '' 202-SHOP '' IN ZONE '' Zone 30 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)E EXPOSURE WALL 40 0,394 - 246 - 316

Space Design Load Summary for FCU Project Name: BAGHDAD MALL 11.13.2012 Prepared by: bjk 11:36

Hourly Analysis Program v.4,3 Page 31of64 31

TABLE 31.1.A. COMPONENT LOADS FOR SPACE '' 203-SHOP '' IN ZONE '' Zone 31 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jul 2300 HEATING DATA AT DES HTG COOLING OA DB / WB 30,6 °C / 18,5 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 40 m² 246 - 40 m² 316 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 0 m² 0 - 0 m² 0 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 5220 W 5220 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 870 W 870 - 0 0 -People 9 624 523 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 348 26 30% 95 0>> Total Zone Loads - 7308 549 - 410 0

TABLE 31.1.B. ENVELOPE LOADS FOR SPACE '' 203-SHOP '' IN ZONE '' Zone 31 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)E EXPOSURE WALL 40 0,394 - 246 - 316

Space Design Load Summary for FCU Project Name: BAGHDAD MALL 11.13.2012 Prepared by: bjk 11:36

Hourly Analysis Program v.4,3 Page 32of64 32

TABLE 32.1.A. COMPONENT LOADS FOR SPACE '' 204-SHOP '' IN ZONE '' Zone 32 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jul 2300 HEATING DATA AT DES HTG COOLING OA DB / WB 30,6 °C / 18,5 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 40 m² 246 - 40 m² 316 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 0 m² 0 - 0 m² 0 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 4230 W 4230 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 705 W 705 - 0 0 -People 7 506 423 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 284 21 30% 95 0>> Total Zone Loads - 5971 445 - 410 0

TABLE 32.1.B. ENVELOPE LOADS FOR SPACE '' 204-SHOP '' IN ZONE '' Zone 32 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)E EXPOSURE WALL 40 0,394 - 246 - 316

Space Design Load Summary for FCU Project Name: BAGHDAD MALL 11.13.2012 Prepared by: bjk 11:36

Hourly Analysis Program v.4,3 Page 33of64 33

TABLE 33.1.A. COMPONENT LOADS FOR SPACE '' 205-SHOP '' IN ZONE '' Zone 33 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jul 2300 HEATING DATA AT DES HTG COOLING OA DB / WB 30,6 °C / 18,5 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 40 m² 246 - 40 m² 316 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 0 m² 0 - 0 m² 0 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 4230 W 4230 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 705 W 705 - 0 0 -People 7 506 423 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 284 21 30% 95 0>> Total Zone Loads - 5971 445 - 410 0

TABLE 33.1.B. ENVELOPE LOADS FOR SPACE '' 205-SHOP '' IN ZONE '' Zone 33 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)E EXPOSURE WALL 40 0,394 - 246 - 316

Space Design Load Summary for FCU Project Name: BAGHDAD MALL 11.13.2012 Prepared by: bjk 11:36

Hourly Analysis Program v.4,3 Page 34of64 34

TABLE 34.1.A. COMPONENT LOADS FOR SPACE '' 206-SHOP '' IN ZONE '' Zone 34 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jul 2300 HEATING DATA AT DES HTG COOLING OA DB / WB 30,6 °C / 18,5 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 40 m² 246 - 40 m² 316 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 0 m² 0 - 0 m² 0 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 3690 W 3690 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 615 W 615 - 0 0 -People 6 441 369 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 250 18 30% 95 0>> Total Zone Loads - 5242 388 - 410 0

TABLE 34.1.B. ENVELOPE LOADS FOR SPACE '' 206-SHOP '' IN ZONE '' Zone 34 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)E EXPOSURE WALL 40 0,394 - 246 - 316

Space Design Load Summary for FCU Project Name: BAGHDAD MALL 11.13.2012 Prepared by: bjk 11:36

Hourly Analysis Program v.4,3 Page 35of64 35

TABLE 35.1.A. COMPONENT LOADS FOR SPACE '' 207-SHOP '' IN ZONE '' Zone 35 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jul 2300 HEATING DATA AT DES HTG COOLING OA DB / WB 30,6 °C / 18,5 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 40 m² 246 - 40 m² 316 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 0 m² 0 - 0 m² 0 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 4680 W 4680 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 780 W 780 - 0 0 -People 8 560 469 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 313 23 30% 95 0>> Total Zone Loads - 6579 492 - 410 0

TABLE 35.1.B. ENVELOPE LOADS FOR SPACE '' 207-SHOP '' IN ZONE '' Zone 35 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)E EXPOSURE WALL 40 0,394 - 246 - 316

Space Design Load Summary for FCU Project Name: BAGHDAD MALL 11.13.2012 Prepared by: bjk 11:36

Hourly Analysis Program v.4,3 Page 36of64 36

TABLE 36.1.A. COMPONENT LOADS FOR SPACE '' 208-SHOP '' IN ZONE '' Zone 36 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jul 2300 HEATING DATA AT DES HTG COOLING OA DB / WB 30,6 °C / 18,5 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 40 m² 246 - 40 m² 316 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 0 m² 0 - 0 m² 0 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 4500 W 4500 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 750 W 750 - 0 0 -People 7 538 451 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 302 23 30% 95 0>> Total Zone Loads - 6336 473 - 410 0

TABLE 36.1.B. ENVELOPE LOADS FOR SPACE '' 208-SHOP '' IN ZONE '' Zone 36 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)E EXPOSURE WALL 40 0,394 - 246 - 316

Space Design Load Summary for FCU Project Name: BAGHDAD MALL 11.13.2012 Prepared by: bjk 11:36

Hourly Analysis Program v.4,3 Page 37of64 37

TABLE 37.1.A. COMPONENT LOADS FOR SPACE '' 209-SHOP '' IN ZONE '' Zone 37 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jul 2300 HEATING DATA AT DES HTG COOLING OA DB / WB 30,6 °C / 18,5 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 40 m² 246 - 40 m² 316 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 0 m² 0 - 0 m² 0 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 5310 W 5310 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 885 W 885 - 0 0 -People 9 635 532 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 354 27 30% 95 0>> Total Zone Loads - 7429 558 - 410 0

TABLE 37.1.B. ENVELOPE LOADS FOR SPACE '' 209-SHOP '' IN ZONE '' Zone 37 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)E EXPOSURE WALL 40 0,394 - 246 - 316

Space Design Load Summary for FCU Project Name: BAGHDAD MALL 11.13.2012 Prepared by: bjk 11:36

Hourly Analysis Program v.4,3 Page 38of64 38

TABLE 38.1.A. COMPONENT LOADS FOR SPACE '' 210-SHOP '' IN ZONE '' Zone 38 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jul 2300 HEATING DATA AT DES HTG COOLING OA DB / WB 30,6 °C / 18,5 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 25 m² 154 - 25 m² 197 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 60 m² 720 - 60 m² 600 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 3780 W 3780 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 630 W 630 - 0 0 -People 6 452 378 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 287 19 30% 239 0>> Total Zone Loads - 6022 397 - 1036 0

TABLE 38.1.B. ENVELOPE LOADS FOR SPACE '' 210-SHOP '' IN ZONE '' Zone 38 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)E EXPOSURE WALL 25 0,394 - 154 - 197

Space Design Load Summary for FCU Project Name: BAGHDAD MALL 11.13.2012 Prepared by: bjk 11:36

Hourly Analysis Program v.4,3 Page 39of64 39

TABLE 39.1.A. COMPONENT LOADS FOR SPACE '' 217-DEPARTMENT STORE '' IN ZONE '' Zone 39 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Aug 0000 HEATING DATA AT DES HTG COOLING OA DB / WB 29,5 °C / 18,1 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 273 m² 1748 - 273 m² 2302 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 50 m² 600 - 50 m² 500 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 20020 W 20018 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 5460 W 5460 - 0 0 -People 55 3918 3280 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 1587 164 30% 841 0>> Total Zone Loads - 33331 3444 - 3643 0

TABLE 39.1.B. ENVELOPE LOADS FOR SPACE '' 217-DEPARTMENT STORE '' IN ZONE '' Zone 39 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)E EXPOSURE WALL 70 0,394 - 425 - 552S EXPOSURE WALL 85 0,394 - 508 - 670S EXPOSURE WALL 38 0,598 - 297 - 448WSW EXPOSURE WALL 80 0,394 - 518 - 631

Space Design Load Summary for FCU Project Name: BAGHDAD MALL 11.13.2012 Prepared by: bjk 11:36

Hourly Analysis Program v.4,3 Page 40of64 40

TABLE 40.1.A. COMPONENT LOADS FOR SPACE '' 219-SHOP '' IN ZONE '' Zone 40 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Aug 0000 HEATING DATA AT DES HTG COOLING OA DB / WB 29,5 °C / 18,1 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 100 m² 648 - 100 m² 789 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 0 m² 0 - 0 m² 0 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 3510 W 3510 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 585 W 585 - 0 0 -People 6 420 351 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 258 18 30% 237 0>> Total Zone Loads - 5420 369 - 1025 0

TABLE 40.1.B. ENVELOPE LOADS FOR SPACE '' 219-SHOP '' IN ZONE '' Zone 40 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)WSW EXPOSURE WALL 100 0,394 - 648 - 789

Space Design Load Summary for FCU Project Name: BAGHDAD MALL 11.13.2012 Prepared by: bjk 11:36

Hourly Analysis Program v.4,3 Page 41of64 41

TABLE 41.1.A. COMPONENT LOADS FOR SPACE '' 220-SHOP '' IN ZONE '' Zone 41 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Aug 0000 HEATING DATA AT DES HTG COOLING OA DB / WB 29,5 °C / 18,1 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 40 m² 259 - 40 m² 316 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 0 m² 0 - 0 m² 0 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 4680 W 4680 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 780 W 780 - 0 0 -People 8 560 469 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 314 23 30% 95 0>> Total Zone Loads - 6592 492 - 410 0

TABLE 41.1.B. ENVELOPE LOADS FOR SPACE '' 220-SHOP '' IN ZONE '' Zone 41 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)WSW EXPOSURE WALL 40 0,394 - 259 - 316

Space Design Load Summary for FCU Project Name: BAGHDAD MALL 11.13.2012 Prepared by: bjk 11:36

Hourly Analysis Program v.4,3 Page 42of64 42

TABLE 42.1.A. COMPONENT LOADS FOR SPACE '' 221-SHOP '' IN ZONE '' Zone 42 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Aug 0000 HEATING DATA AT DES HTG COOLING OA DB / WB 29,5 °C / 18,1 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 40 m² 259 - 40 m² 316 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 0 m² 0 - 0 m² 0 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 5850 W 5849 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 975 W 975 - 0 0 -People 10 700 586 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 389 29 30% 95 0>> Total Zone Loads - 8172 615 - 410 0

TABLE 42.1.B. ENVELOPE LOADS FOR SPACE '' 221-SHOP '' IN ZONE '' Zone 42 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)WSW EXPOSURE WALL 40 0,394 - 259 - 316

Space Design Load Summary for FCU Project Name: BAGHDAD MALL 11.13.2012 Prepared by: bjk 11:36

Hourly Analysis Program v.4,3 Page 43of64 43

TABLE 43.1.A. COMPONENT LOADS FOR SPACE '' 222-SHOP '' IN ZONE '' Zone 43 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jul 0000 HEATING DATA AT DES HTG COOLING OA DB / WB 29,5 °C / 18,1 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 40 m² 262 - 40 m² 316 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 0 m² 0 - 0 m² 0 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 6300 W 6299 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 1050 W 1050 - 0 0 -People 10 753 631 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 418 32 30% 95 0>> Total Zone Loads - 8783 662 - 410 0

TABLE 43.1.B. ENVELOPE LOADS FOR SPACE '' 222-SHOP '' IN ZONE '' Zone 43 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)W EXPOSURE WALL 40 0,394 - 262 - 316

Space Design Load Summary for FCU Project Name: BAGHDAD MALL 11.13.2012 Prepared by: bjk 11:36

Hourly Analysis Program v.4,3 Page 44of64 44

TABLE 44.1.A. COMPONENT LOADS FOR SPACE '' 223-SHOP '' IN ZONE '' Zone 44 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jul 0000 HEATING DATA AT DES HTG COOLING OA DB / WB 29,5 °C / 18,1 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 40 m² 262 - 40 m² 316 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 0 m² 0 - 0 m² 0 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 4950 W 4950 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 825 W 825 - 0 0 -People 8 592 496 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 331 25 30% 95 0>> Total Zone Loads - 6959 520 - 410 0

TABLE 44.1.B. ENVELOPE LOADS FOR SPACE '' 223-SHOP '' IN ZONE '' Zone 44 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)W EXPOSURE WALL 40 0,394 - 262 - 316

Space Design Load Summary for FCU Project Name: BAGHDAD MALL 11.13.2012 Prepared by: bjk 11:36

Hourly Analysis Program v.4,3 Page 45of64 45

TABLE 45.1.A. COMPONENT LOADS FOR SPACE '' 224-SHOP '' IN ZONE '' Zone 45 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jul 0000 HEATING DATA AT DES HTG COOLING OA DB / WB 29,5 °C / 18,1 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 35 m² 229 - 35 m² 276 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 50 m² 600 - 50 m² 500 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 4320 W 4320 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 720 W 720 - 0 0 -People 7 517 433 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 319 22 30% 233 0>> Total Zone Loads - 6704 454 - 1009 0

TABLE 45.1.B. ENVELOPE LOADS FOR SPACE '' 224-SHOP '' IN ZONE '' Zone 45 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)W EXPOSURE WALL 35 0,394 - 229 - 276

Space Design Load Summary for FCU Project Name: BAGHDAD MALL 11.13.2012 Prepared by: bjk 11:36

Hourly Analysis Program v.4,3 Page 46of64 46

TABLE 46.1.A. COMPONENT LOADS FOR SPACE '' 227-SHOP '' IN ZONE '' Zone 46 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jul 0000 HEATING DATA AT DES HTG COOLING OA DB / WB 29,5 °C / 18,1 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 32 m² 209 - 32 m² 252 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 45 m² 540 - 45 m² 450 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 4770 W 4770 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 795 W 795 - 0 0 -People 8 571 478 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 344 24 30% 211 0>> Total Zone Loads - 7228 501 - 913 0

TABLE 46.1.B. ENVELOPE LOADS FOR SPACE '' 227-SHOP '' IN ZONE '' Zone 46 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)W EXPOSURE WALL 32 0,394 - 209 - 252

Space Design Load Summary for FCU Project Name: BAGHDAD MALL 11.13.2012 Prepared by: bjk 11:36

Hourly Analysis Program v.4,3 Page 47of64 47

TABLE 47.1.A. COMPONENT LOADS FOR SPACE '' 228-CAFE '' IN ZONE '' Zone 47 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jul 0000 HEATING DATA AT DES HTG COOLING OA DB / WB 29,5 °C / 18,1 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 55 m² 360 - 55 m² 434 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 0 m² 0 - 0 m² 0 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 3195 W 3195 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 355 W 355 - 0 0 -People 71 4785 2499 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 435 125 30% 130 0>> Total Zone Loads - 9129 2624 - 564 0

TABLE 47.1.B. ENVELOPE LOADS FOR SPACE '' 228-CAFE '' IN ZONE '' Zone 47 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)W EXPOSURE WALL 55 0,394 - 360 - 434

Space Design Load Summary for FCU Project Name: BAGHDAD MALL 11.13.2012 Prepared by: bjk 11:36

Hourly Analysis Program v.4,3 Page 48of64 48

TABLE 48.1.A. COMPONENT LOADS FOR SPACE '' 232-SHOP '' IN ZONE '' Zone 48 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jun 2300 HEATING DATA AT DES HTG COOLING OA DB / WB 29,0 °C / 17,1 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 0 m² 0 - 0 m² 0 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 10 m² 120 - 10 m² 100 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 1170 W 1170 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 195 W 195 - 0 0 -People 2 140 117 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 81 6 30% 30 0>> Total Zone Loads - 1706 123 - 130 0

TABLE 48.1.B. ENVELOPE LOADS FOR SPACE '' 232-SHOP '' IN ZONE '' Zone 48 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Space Design Load Summary for FCU Project Name: BAGHDAD MALL 11.13.2012 Prepared by: bjk 11:36

Hourly Analysis Program v.4,3 Page 49of64 49

TABLE 49.1.A. COMPONENT LOADS FOR SPACE '' 303-RESTAURANT '' IN ZONE '' Zone 49 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jul 2200 HEATING DATA AT DES HTG COOLING OA DB / WB 32,2 °C / 18,9 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 80 m² 488 - 80 m² 631 -Roof Transmission 120 m² 1579 - 120 m² 1309 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 0 m² 0 - 0 m² 0 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 5400 W 5400 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 600 W 600 - 0 0 -People 80 5392 2816 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 673 141 30% 582 0>> Total Zone Loads - 14131 2957 - 2522 0

TABLE 49.1.B. ENVELOPE LOADS FOR SPACE '' 303-RESTAURANT '' IN ZONE '' Zone 49 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)E EXPOSURE WALL 80 0,394 - 488 - 631H EXPOSURE ROOF 120 0,545 - 1579 - 1309

Space Design Load Summary for FCU Project Name: BAGHDAD MALL 11.13.2012 Prepared by: bjk 11:36

Hourly Analysis Program v.4,3 Page 50of64 50

TABLE 50.1.A. COMPONENT LOADS FOR SPACE '' 304-CAFE '' IN ZONE '' Zone 50 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jul 2200 HEATING DATA AT DES HTG COOLING OA DB / WB 32,2 °C / 18,9 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 40 m² 244 - 40 m² 316 -Roof Transmission 34 m² 447 - 34 m² 371 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 0 m² 0 - 0 m² 0 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 1530 W 1530 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 170 W 170 - 0 0 -People 34 2292 1197 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 234 60 30% 206 0>> Total Zone Loads - 4917 1257 - 892 0

TABLE 50.1.B. ENVELOPE LOADS FOR SPACE '' 304-CAFE '' IN ZONE '' Zone 50 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)E EXPOSURE WALL 40 0,394 - 244 - 316H EXPOSURE ROOF 34 0,545 - 447 - 371

Space Design Load Summary for FCU Project Name: BAGHDAD MALL 11.13.2012 Prepared by: bjk 11:36

Hourly Analysis Program v.4,3 Page 51of64 51

TABLE 51.1.A. COMPONENT LOADS FOR SPACE '' 305-CAFE '' IN ZONE '' Zone 51 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jul 2200 HEATING DATA AT DES HTG COOLING OA DB / WB 32,2 °C / 18,9 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 40 m² 244 - 40 m² 316 -Roof Transmission 34 m² 447 - 34 m² 371 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 0 m² 0 - 0 m² 0 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 1620 W 1620 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 180 W 180 - 0 0 -People 36 2426 1267 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 246 63 30% 206 0>> Total Zone Loads - 5163 1331 - 892 0

TABLE 51.1.B. ENVELOPE LOADS FOR SPACE '' 305-CAFE '' IN ZONE '' Zone 51 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)E EXPOSURE WALL 40 0,394 - 244 - 316H EXPOSURE ROOF 34 0,545 - 447 - 371

Space Design Load Summary for FCU Project Name: BAGHDAD MALL 11.13.2012 Prepared by: bjk 11:36

Hourly Analysis Program v.4,3 Page 52of64 52

TABLE 52.1.A. COMPONENT LOADS FOR SPACE '' 306-CAFE '' IN ZONE '' Zone 52 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jul 2200 HEATING DATA AT DES HTG COOLING OA DB / WB 32,2 °C / 18,9 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 40 m² 244 - 40 m² 316 -Roof Transmission 34 m² 447 - 34 m² 371 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 0 m² 0 - 0 m² 0 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 1530 W 1530 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 170 W 170 - 0 0 -People 34 2292 1197 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 234 60 30% 206 0>> Total Zone Loads - 4917 1257 - 892 0

TABLE 52.1.B. ENVELOPE LOADS FOR SPACE '' 306-CAFE '' IN ZONE '' Zone 52 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)E EXPOSURE WALL 40 0,394 - 244 - 316H EXPOSURE ROOF 34 0,545 - 447 - 371

Space Design Load Summary for FCU Project Name: BAGHDAD MALL 11.13.2012 Prepared by: bjk 11:36

Hourly Analysis Program v.4,3 Page 53of64 53

TABLE 53.1.A. COMPONENT LOADS FOR SPACE '' 307-CAFE '' IN ZONE '' Zone 53 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jul 2200 HEATING DATA AT DES HTG COOLING OA DB / WB 32,2 °C / 18,9 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 40 m² 244 - 40 m² 316 -Roof Transmission 34 m² 447 - 34 m² 371 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 0 m² 0 - 0 m² 0 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 1980 W 1980 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 220 W 220 - 0 0 -People 44 2966 1549 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 293 77 30% 206 0>> Total Zone Loads - 6150 1626 - 892 0

TABLE 53.1.B. ENVELOPE LOADS FOR SPACE '' 307-CAFE '' IN ZONE '' Zone 53 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)E EXPOSURE WALL 40 0,394 - 244 - 316H EXPOSURE ROOF 34 0,545 - 447 - 371

Space Design Load Summary for FCU Project Name: BAGHDAD MALL 11.13.2012 Prepared by: bjk 11:36

Hourly Analysis Program v.4,3 Page 54of64 54

TABLE 54.1.A. COMPONENT LOADS FOR SPACE '' 308-SHOP '' IN ZONE '' Zone 54 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jul 2200 HEATING DATA AT DES HTG COOLING OA DB / WB 32,2 °C / 18,9 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 40 m² 244 - 40 m² 316 -Roof Transmission 43 m² 566 - 43 m² 469 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 0 m² 0 - 0 m² 0 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 3870 W 3870 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 645 W 645 - 0 0 -People 6 463 387 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 289 19 30% 235 0>> Total Zone Loads - 6077 407 - 1020 0

TABLE 54.1.B. ENVELOPE LOADS FOR SPACE '' 308-SHOP '' IN ZONE '' Zone 54 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)E EXPOSURE WALL 40 0,394 - 244 - 316H EXPOSURE ROOF 43 0,545 - 566 - 469

Space Design Load Summary for FCU Project Name: BAGHDAD MALL 11.13.2012 Prepared by: bjk 11:36

Hourly Analysis Program v.4,3 Page 55of64 55

TABLE 55.1.A. COMPONENT LOADS FOR SPACE '' 309-SHOP '' IN ZONE '' Zone 55 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jul 2200 HEATING DATA AT DES HTG COOLING OA DB / WB 32,2 °C / 18,9 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 40 m² 244 - 40 m² 316 -Roof Transmission 43 m² 566 - 43 m² 469 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 0 m² 0 - 0 m² 0 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 4680 W 4680 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 780 W 780 - 0 0 -People 8 560 469 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 341 23 30% 235 0>> Total Zone Loads - 7171 492 - 1020 0

TABLE 55.1.B. ENVELOPE LOADS FOR SPACE '' 309-SHOP '' IN ZONE '' Zone 55 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)E EXPOSURE WALL 40 0,394 - 244 - 316H EXPOSURE ROOF 43 0,545 - 566 - 469

Space Design Load Summary for FCU Project Name: BAGHDAD MALL 11.13.2012 Prepared by: bjk 11:36

Hourly Analysis Program v.4,3 Page 56of64 56

TABLE 56.1.A. COMPONENT LOADS FOR SPACE '' 310-SHOP '' IN ZONE '' Zone 56 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jul 2200 HEATING DATA AT DES HTG COOLING OA DB / WB 32,2 °C / 18,9 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 25 m² 153 - 25 m² 197 -Roof Transmission 36 m² 474 - 36 m² 393 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 60 m² 720 - 60 m² 600 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 3240 W 3240 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 540 W 540 - 0 0 -People 5 388 324 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 276 16 30% 357 0>> Total Zone Loads - 5789 341 - 1547 0

TABLE 56.1.B. ENVELOPE LOADS FOR SPACE '' 310-SHOP '' IN ZONE '' Zone 56 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)E EXPOSURE WALL 25 0,394 - 153 - 197H EXPOSURE ROOF 36 0,545 - 474 - 393

Space Design Load Summary for FCU Project Name: BAGHDAD MALL 11.13.2012 Prepared by: bjk 11:36

Hourly Analysis Program v.4,3 Page 57of64 57

TABLE 57.1.A. COMPONENT LOADS FOR SPACE '' 317-ENTERTAINMENT '' IN ZONE '' Zone 57 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Aug 0000 HEATING DATA AT DES HTG COOLING OA DB / WB 29,5 °C / 18,1 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 273 m² 1748 - 273 m² 2302 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 50 m² 600 - 50 m² 500 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 9100 W 9099 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 12740 W 12739 - 0 0 -People 243 16355 8542 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 2027 427 30% 841 0>> Total Zone Loads - 42568 8969 - 3643 0

TABLE 57.1.B. ENVELOPE LOADS FOR SPACE '' 317-ENTERTAINMENT '' IN ZONE '' Zone 57 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)E EXPOSURE WALL 70 0,394 - 425 - 552S EXPOSURE WALL 85 0,394 - 508 - 670S EXPOSURE WALL 38 0,598 - 297 - 448WSW EXPOSURE WALL 80 0,394 - 518 - 631

Space Design Load Summary for FCU Project Name: BAGHDAD MALL 11.13.2012 Prepared by: bjk 11:36

Hourly Analysis Program v.4,3 Page 58of64 58

TABLE 58.1.A. COMPONENT LOADS FOR SPACE '' 319-SHOP '' IN ZONE '' Zone 58 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Aug 0000 HEATING DATA AT DES HTG COOLING OA DB / WB 29,5 °C / 18,1 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 100 m² 648 - 100 m² 789 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 0 m² 0 - 0 m² 0 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 3510 W 3510 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 585 W 585 - 0 0 -People 6 420 351 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 258 18 30% 237 0>> Total Zone Loads - 5420 369 - 1025 0

TABLE 58.1.B. ENVELOPE LOADS FOR SPACE '' 319-SHOP '' IN ZONE '' Zone 58 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)WSW EXPOSURE WALL 100 0,394 - 648 - 789

Space Design Load Summary for FCU Project Name: BAGHDAD MALL 11.13.2012 Prepared by: bjk 11:36

Hourly Analysis Program v.4,3 Page 59of64 59

TABLE 59.1.A. COMPONENT LOADS FOR SPACE '' 320-SHOP '' IN ZONE '' Zone 59 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Aug 0000 HEATING DATA AT DES HTG COOLING OA DB / WB 29,5 °C / 18,1 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 40 m² 259 - 40 m² 316 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 0 m² 0 - 0 m² 0 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 4320 W 4320 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 720 W 720 - 0 0 -People 7 517 433 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 291 22 30% 95 0>> Total Zone Loads - 6106 454 - 410 0

TABLE 59.1.B. ENVELOPE LOADS FOR SPACE '' 320-SHOP '' IN ZONE '' Zone 59 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)WSW EXPOSURE WALL 40 0,394 - 259 - 316

Space Design Load Summary for FCU Project Name: BAGHDAD MALL 11.13.2012 Prepared by: bjk 11:36

Hourly Analysis Program v.4,3 Page 60of64 60

TABLE 60.1.A. COMPONENT LOADS FOR SPACE '' 321-SHOP '' IN ZONE '' Zone 60 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Aug 0000 HEATING DATA AT DES HTG COOLING OA DB / WB 29,5 °C / 18,1 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 40 m² 259 - 40 m² 316 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 0 m² 0 - 0 m² 0 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 5220 W 5220 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 870 W 870 - 0 0 -People 9 624 523 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 349 26 30% 95 0>> Total Zone Loads - 7322 549 - 410 0

TABLE 60.1.B. ENVELOPE LOADS FOR SPACE '' 321-SHOP '' IN ZONE '' Zone 60 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)WSW EXPOSURE WALL 40 0,394 - 259 - 316

Space Design Load Summary for FCU Project Name: BAGHDAD MALL 11.13.2012 Prepared by: bjk 11:36

Hourly Analysis Program v.4,3 Page 61of64 61

TABLE 61.1.A. COMPONENT LOADS FOR SPACE '' 322-RESTAURANT '' IN ZONE '' Zone 61 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jul 0000 HEATING DATA AT DES HTG COOLING OA DB / WB 29,5 °C / 18,1 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 40 m² 262 - 40 m² 316 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 20 m² 240 - 20 m² 200 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 2790 W 2790 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 310 W 310 - 0 0 -People 41 2786 1455 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 319 73 30% 155 0>> Total Zone Loads - 6706 1528 - 670 0

TABLE 61.1.B. ENVELOPE LOADS FOR SPACE '' 322-RESTAURANT '' IN ZONE '' Zone 61 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)W EXPOSURE WALL 40 0,394 - 262 - 316

Space Design Load Summary for FCU Project Name: BAGHDAD MALL 11.13.2012 Prepared by: bjk 11:36

Hourly Analysis Program v.4,3 Page 62of64 62

TABLE 62.1.A. COMPONENT LOADS FOR SPACE '' 324-PRIVATE RESTAURANT '' IN ZONE '' Zone 62 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jul 0000 HEATING DATA AT DES HTG COOLING OA DB / WB 29,5 °C / 18,1 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 75 m² 490 - 75 m² 592 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 30 m² 360 - 30 m² 300 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 3150 W 3150 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 350 W 350 - 0 0 -People 47 3145 1643 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 375 82 30% 267 0>> Total Zone Loads - 7870 1725 - 1159 0

TABLE 62.1.B. ENVELOPE LOADS FOR SPACE '' 324-PRIVATE RESTAURANT '' IN ZONE '' Zone 62 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)W EXPOSURE WALL 75 0,394 - 490 - 592

Space Design Load Summary for FCU Project Name: BAGHDAD MALL 11.13.2012 Prepared by: bjk 11:36

Hourly Analysis Program v.4,3 Page 63of64 63

TABLE 63.1.A. COMPONENT LOADS FOR SPACE '' 327-RESTAURANT '' IN ZONE '' Zone 63 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jul 0000 HEATING DATA AT DES HTG COOLING OA DB / WB 29,5 °C / 18,1 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 75 m² 490 - 75 m² 592 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 45 m² 540 - 45 m² 450 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 4455 W 4455 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 495 W 495 - 0 0 -People 66 4448 2323 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 521 116 30% 312 0>> Total Zone Loads - 10950 2439 - 1354 0

TABLE 63.1.B. ENVELOPE LOADS FOR SPACE '' 327-RESTAURANT '' IN ZONE '' Zone 63 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)W EXPOSURE WALL 75 0,394 - 490 - 592

Space Design Load Summary for FCU Project Name: BAGHDAD MALL 11.13.2012 Prepared by: bjk 11:36

Hourly Analysis Program v.4,3 Page 64of64 64

TABLE 64.1.A. COMPONENT LOADS FOR SPACE '' 329-SHOP '' IN ZONE '' Zone 64 ''

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jun 2300 HEATING DATA AT DES HTG COOLING OA DB / WB 29,0 °C / 17,1 °C HEATING OA DB / WB 0,0 °C / -2,8 °C OCCUPIED T-STAT 24,0 °C OCCUPIED T-STAT 20,0 °C Sensible Latent Sensible LatentSPACE LOADS Details (W) (W) Details (W) (W)Window & Skylight Solar Loads 0 m² 0 - 0 m² - -Wall Transmission 0 m² 0 - 0 m² 0 -Roof Transmission 0 m² 0 - 0 m² 0 -Window Transmission 0 m² 0 - 0 m² 0 -Skylight Transmission 0 m² 0 - 0 m² 0 -Door Loads 0 m² 0 - 0 m² 0 -Floor Transmission 0 m² 0 - 0 m² 0 -Partitions 10 m² 120 - 10 m² 100 -Ceiling 0 m² 0 - 0 m² 0 -Overhead Lighting 1170 W 1170 - 0 0 -Task Lighting 0 W 0 - 0 0 -Electric Equipment 195 W 195 - 0 0 -People 2 140 117 0 0 0Infiltration - 0 0 - 0 0Miscellaneous - 0 0 - 0 0Safety Factor 5% / 5% 81 6 30% 30 0>> Total Zone Loads - 1706 123 - 130 0

TABLE 64.1.B. ENVELOPE LOADS FOR SPACE '' 329-SHOP '' IN ZONE '' Zone 64 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 1 of 98 1

101-SHOPPING HALL 1. General Details: Floor Area ......................................................... 1026,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage .................. RETAIL: Mall common area OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,30 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 20,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................. 2,50 m²/person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ................................................................. 5,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

W 25,0 0 0 0

E 40,0 0 0 0 3.1. Construction Types for Exposure W Wall Type ................................................................... OW-03 3.2. Construction Types for Exposure E Wall Type ................................................................... OW-03 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 ACH Design Heating ...................................................... 0,00 ACH Energy Analysis .................................................... 0,00 ACH Infiltration occurs at all hours. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: 7.1. 1st Partition Details: Partition Type ........................................ Wall Partition Area ....................................................................... 20,0 m² U-Value ............................................................... 2,000 W/(m²-°K) Uncondit. Space Max Temp .................................. 30,0 °C Ambient at Space Max Temp ................................ 24,0 °C Uncondit. Space Min Temp ................................... 15,0 °C Ambient at Space Min Temp ................................. 20,0 °C

7.2. 2nd Partition Details: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 2 of 98 2

102-SHOP 1. General Details: Floor Area ............................................................. 60,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ........................................ RETAIL: Sales OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,60 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 90,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................. 6,67 m²/person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 15,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

E 40,0 0 0 0 3.1. Construction Types for Exposure E Wall Type ................................................................... OW-03 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 3 of 98 3

103-SHOP 1. General Details: Floor Area ............................................................. 58,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ........................................ RETAIL: Sales OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,60 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 90,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................. 6,67 m²/person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 15,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

E 40,0 0 0 0 3.1. Construction Types for Exposure E Wall Type ................................................................... OW-03 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 4 of 98 4

104-SHOP 1. General Details: Floor Area ............................................................. 47,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ........................................ RETAIL: Sales OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,60 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 90,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................. 6,67 m²/person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 15,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

E 40,0 0 0 0 3.1. Construction Types for Exposure E Wall Type ................................................................... OW-03 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 5 of 98 5

105-SHOP 1. General Details: Floor Area ............................................................. 43,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ........................................ RETAIL: Sales OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,60 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 90,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................. 6,67 m²/person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 15,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

E 40,0 0 0 0 3.1. Construction Types for Exposure E Wall Type ................................................................... OW-03 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 6 of 98 6

106-SHOP 1. General Details: Floor Area ............................................................. 41,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ........................................ RETAIL: Sales OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,60 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 90,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................. 6,67 m²/person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 15,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

E 40,0 0 0 0 3.1. Construction Types for Exposure E Wall Type ................................................................... OW-03 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 7 of 98 7

107-SHOP 1. General Details: Floor Area ............................................................. 52,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ........................................ RETAIL: Sales OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,60 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 90,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................. 6,67 m²/person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 15,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

E 40,0 0 0 0 3.1. Construction Types for Exposure E Wall Type ................................................................... OW-03 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 8 of 98 8

108-SHOP 1. General Details: Floor Area ............................................................. 50,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ........................................ RETAIL: Sales OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,60 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 90,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................. 6,67 m²/person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 15,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

E 40,0 0 0 0 3.1. Construction Types for Exposure E Wall Type ................................................................... OW-03 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 9 of 98 9

109-SHOP 1. General Details: Floor Area ............................................................. 60,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ........................................ RETAIL: Sales OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,60 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 90,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................. 6,67 m²/person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 15,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

E 40,0 0 0 0 3.1. Construction Types for Exposure E Wall Type ................................................................... OW-03 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 10 of 98 10

110-SHOP 1. General Details: Floor Area ............................................................. 42,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ........................................ RETAIL: Sales OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,60 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 90,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................. 6,67 m²/person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 15,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

E 25,0 0 0 0 3.1. Construction Types for Exposure E Wall Type ................................................................... OW-03 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: 7.1. 1st Partition Details: Partition Type ........................................ Wall Partition Area ....................................................................... 60,0 m² U-Value ............................................................... 2,000 W/(m²-°K) Uncondit. Space Max Temp .................................. 30,0 °C Ambient at Space Max Temp ................................ 24,0 °C Uncondit. Space Min Temp ................................... 15,0 °C Ambient at Space Min Temp ................................. 20,0 °C

7.2. 2nd Partition Details: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 11 of 98 11

111-HALL 1. General Details: Floor Area ............................................................. 11,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage .............................. GENERAL: Corridor OA Requirement 1 .................................................. 0,0 L/s/person OA Requirement 2 ................................................ 0,30 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 20,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................... 0,0 Person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule .............................................................. None

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ................................................................. 5,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors: (No Wall, Window, Door data). 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 ACH Design Heating ...................................................... 0,00 ACH Energy Analysis .................................................... 0,00 ACH Infiltration occurs at all hours. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: 7.1. 1st Partition Details: Partition Type ........................................ Wall Partition Area ....................................................................... 28,0 m² U-Value ............................................................... 2,000 W/(m²-°K) Uncondit. Space Max Temp .................................. 30,0 °C Ambient at Space Max Temp ................................ 24,0 °C Uncondit. Space Min Temp ................................... 15,0 °C Ambient at Space Min Temp ................................. 20,0 °C

7.2. 2nd Partition Details: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 12 of 98 12

113-WC MALE 1. General Details: Floor Area ............................................................. 20,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage .......................................... User-Defined OA Requirement 1 .................................................. 0,0 L/s OA Requirement 2 .................................................. 0,0 L/s Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 15,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................... 3,0 People Activity Level ........................................ Seated at Rest Sensible ................................................................. 67,4 W/person Latent ..................................................................... 35,2 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 15,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

E 30,0 0 0 0 3.1. Construction Types for Exposure E Wall Type ................................................................... OW-03 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 ACH Design Heating ...................................................... 0,00 ACH Energy Analysis .................................................... 0,00 ACH Infiltration occurs at all hours. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: 7.1. 1st Partition Details: Partition Type ........................................ Wall Partition Area ....................................................................... 35,0 m² U-Value ............................................................... 2,000 W/(m²-°K) Uncondit. Space Max Temp .................................. 30,0 °C Ambient at Space Max Temp ................................ 24,0 °C Uncondit. Space Min Temp ................................... 15,0 °C Ambient at Space Min Temp ................................. 20,0 °C

7.2. 2nd Partition Details: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 13 of 98 13

114-WC FEMALE 1. General Details: Floor Area ............................................................. 16,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage .......................................... User-Defined OA Requirement 1 .................................................. 0,0 L/s OA Requirement 2 .................................................. 0,0 L/s Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 15,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................... 3,0 People Activity Level ........................................ Seated at Rest Sensible ................................................................. 67,4 W/person Latent ..................................................................... 35,2 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 15,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors: (No Wall, Window, Door data). 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 ACH Design Heating ...................................................... 0,00 ACH Energy Analysis .................................................... 0,00 ACH Infiltration occurs at all hours. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: 7.1. 1st Partition Details: Partition Type ........................................ Wall Partition Area ....................................................................... 30,0 m² U-Value ............................................................... 2,000 W/(m²-°K) Uncondit. Space Max Temp .................................. 30,0 °C Ambient at Space Max Temp ................................ 24,0 °C Uncondit. Space Min Temp ................................... 15,0 °C Ambient at Space Min Temp ................................. 20,0 °C

7.2. 2nd Partition Details: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 14 of 98 14

117-DEPARTMENT STORE 1. General Details: Floor Area ........................................................... 364,0 m² Avg. Ceiling Height .................................................. 6,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ........................................ RETAIL: Sales OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,60 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 55,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................. 6,67 m²/person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 15,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

E 70,0 0 0 0

S 85,0 0 0 0

S 37,5 0 0 0

WSW 80,0 0 0 0 3.1. Construction Types for Exposure E Wall Type ................................................................... OW-03 3.2. Construction Types for Exposure S Wall Type ................................................................... OW-03' 3.3. Construction Types for Exposure S Wall Type ................................................................... OW-04 3.4. Construction Types for Exposure WSW Wall Type ................................................................... OW-03 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: 7.1. 1st Partition Details: Partition Type ........................................ Wall Partition Area ....................................................................... 50,0 m² U-Value ............................................................... 2,000 W/(m²-°K) Uncondit. Space Max Temp .................................. 30,0 °C Ambient at Space Max Temp ................................ 24,0 °C Uncondit. Space Min Temp ................................... 15,0 °C

Ambient at Space Min Temp ................................. 20,0 °C

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 15 of 98 15

7.2. 2nd Partition Details: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 16 of 98 16

119-SHOP 1. General Details: Floor Area ........................................................... 106,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ........................................ RETAIL: Sales OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,60 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 90,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................. 6,67 m²/person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 15,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

WSW 100,0 0 0 0 3.1. Construction Types for Exposure WSW Wall Type ................................................................... OW-03 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 17 of 98 17

120-SHOP 1. General Details: Floor Area ............................................................. 30,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ........................................ RETAIL: Sales OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,60 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 90,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................. 6,67 m²/person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 15,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

WSW 22,0 0 0 0 3.1. Construction Types for Exposure WSW Wall Type ................................................................... OW-03 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 18 of 98 18

121-SHOP 1. General Details: Floor Area ............................................................. 66,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ........................................ RETAIL: Sales OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,60 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 90,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................. 6,67 m²/person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 15,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

WSW 40,0 0 0 0 3.1. Construction Types for Exposure WSW Wall Type ................................................................... OW-03 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 19 of 98 19

122-SHOP 1. General Details: Floor Area ............................................................. 70,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ........................................ RETAIL: Sales OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,60 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 90,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................. 6,67 m²/person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 15,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

W 40,0 0 0 0 3.1. Construction Types for Exposure W Wall Type ................................................................... OW-03 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 20 of 98 20

123-SHOP 1. General Details: Floor Area ............................................................. 55,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ........................................ RETAIL: Sales OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,60 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 90,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................. 6,67 m²/person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 15,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

W 40,0 0 0 0 3.1. Construction Types for Exposure W Wall Type ................................................................... OW-03 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 21 of 98 21

124-SHOP 1. General Details: Floor Area ............................................................. 48,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ........................................ RETAIL: Sales OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,60 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 90,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................. 6,67 m²/person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 15,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

W 35,0 0 0 0 3.1. Construction Types for Exposure W Wall Type ................................................................... OW-03 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: 7.1. 1st Partition Details: Partition Type ........................................ Wall Partition Area ....................................................................... 50,0 m² U-Value ............................................................... 2,000 W/(m²-°K) Uncondit. Space Max Temp .................................. 30,0 °C Ambient at Space Max Temp ................................ 24,0 °C Uncondit. Space Min Temp ................................... 15,0 °C Ambient at Space Min Temp ................................. 20,0 °C

7.2. 2nd Partition Details: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 22 of 98 22

126-HALL 1. General Details: Floor Area ............................................................. 14,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage .............................. GENERAL: Corridor OA Requirement 1 .................................................. 0,0 L/s/person OA Requirement 2 ................................................ 0,30 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 20,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................... 0,0 Person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule .............................................................. None

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ................................................................. 5,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

W 12,5 0 0 0 3.1. Construction Types for Exposure W Wall Type ................................................................... OW-03 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 ACH Design Heating ...................................................... 0,00 ACH Energy Analysis .................................................... 0,00 ACH Infiltration occurs at all hours. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: 7.1. 1st Partition Details: Partition Type ........................................ Wall Partition Area ....................................................................... 50,0 m² U-Value ............................................................... 2,000 W/(m²-°K) Uncondit. Space Max Temp .................................. 30,0 °C Ambient at Space Max Temp ................................ 24,0 °C Uncondit. Space Min Temp ................................... 15,0 °C Ambient at Space Min Temp ................................. 20,0 °C

7.2. 2nd Partition Details: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 23 of 98 23

127-SHOP 1. General Details: Floor Area ............................................................. 53,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ........................................ RETAIL: Sales OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,60 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 90,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................. 6,67 m²/person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 15,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

W 32,0 0 0 0 3.1. Construction Types for Exposure W Wall Type ................................................................... OW-03 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: 7.1. 1st Partition Details: Partition Type ........................................ Wall Partition Area ....................................................................... 45,0 m² U-Value ............................................................... 2,000 W/(m²-°K) Uncondit. Space Max Temp .................................. 30,0 °C Ambient at Space Max Temp ................................ 24,0 °C Uncondit. Space Min Temp ................................... 15,0 °C Ambient at Space Min Temp ................................. 20,0 °C

7.2. 2nd Partition Details: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 24 of 98 24

128-SHOP 1. General Details: Floor Area ............................................................. 68,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ........................................ RETAIL: Sales OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,60 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 90,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................. 6,67 m²/person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 15,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

W 55,0 0 0 0 3.1. Construction Types for Exposure W Wall Type ................................................................... OW-03 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 25 of 98 25

129-KIOSK 1. General Details: Floor Area ............................................................... 5,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ........................................ RETAIL: Sales OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,60 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 90,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................... 2,0 People Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 15,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors: (No Wall, Window, Door data). 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 26 of 98 26

130-KIOSK 1. General Details: Floor Area ............................................................. 27,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ........................................ RETAIL: Sales OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,60 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 90,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................. 6,67 m²/person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 15,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors: (No Wall, Window, Door data). 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 27 of 98 27

131-KIOSK 1. General Details: Floor Area ............................................................. 54,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ........................................ RETAIL: Sales OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,60 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 90,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................. 6,67 m²/person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 15,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors: (No Wall, Window, Door data). 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 28 of 98 28

132-KIOSK 1. General Details: Floor Area ............................................................. 54,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ........................................ RETAIL: Sales OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,60 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 90,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................. 6,67 m²/person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 15,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors: (No Wall, Window, Door data). 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 29 of 98 29

133-KIOSK 1. General Details: Floor Area ............................................................. 27,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ........................................ RETAIL: Sales OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,60 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 90,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................. 6,67 m²/person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 15,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors: (No Wall, Window, Door data). 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 30 of 98 30

134-KIOSK 1. General Details: Floor Area ............................................................... 5,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ........................................ RETAIL: Sales OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,60 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 90,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................... 2,0 People Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 15,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors: (No Wall, Window, Door data). 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 31 of 98 31

135-SHOP 1. General Details: Floor Area ............................................................. 13,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ........................................ RETAIL: Sales OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,60 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 90,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................. 6,67 m²/person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 15,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors: (No Wall, Window, Door data). 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: 7.1. 1st Partition Details: Partition Type ........................................ Wall Partition Area ....................................................................... 10,0 m² U-Value ............................................................... 2,000 W/(m²-°K) Uncondit. Space Max Temp .................................. 30,0 °C Ambient at Space Max Temp ................................ 24,0 °C Uncondit. Space Min Temp ................................... 15,0 °C Ambient at Space Min Temp ................................. 20,0 °C

7.2. 2nd Partition Details: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 32 of 98 32

201-SHOPPING HALL 1. General Details: Floor Area ........................................................... 860,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage .................. RETAIL: Mall common area OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,30 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 20,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................. 2,50 m²/person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ................................................................. 5,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

W 25,0 0 0 0

E 40,0 0 0 0 3.1. Construction Types for Exposure W Wall Type ................................................................... OW-03 3.2. Construction Types for Exposure E Wall Type ................................................................... OW-03 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 ACH Design Heating ...................................................... 0,00 ACH Energy Analysis .................................................... 0,00 ACH Infiltration occurs at all hours. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: 7.1. 1st Partition Details: Partition Type ........................................ Wall Partition Area ....................................................................... 20,0 m² U-Value ............................................................... 2,000 W/(m²-°K) Uncondit. Space Max Temp .................................. 30,0 °C Ambient at Space Max Temp ................................ 24,0 °C Uncondit. Space Min Temp ................................... 15,0 °C Ambient at Space Min Temp ................................. 20,0 °C

7.2. 2nd Partition Details: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 33 of 98 33

202-SHOP 1. General Details: Floor Area ............................................................. 68,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ........................................ RETAIL: Sales OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,60 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 90,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................. 6,67 m²/person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 15,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

E 40,0 0 0 0 3.1. Construction Types for Exposure E Wall Type ................................................................... OW-03 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 34 of 98 34

203-SHOP 1. General Details: Floor Area ............................................................. 58,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ........................................ RETAIL: Sales OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,60 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 90,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................. 6,67 m²/person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 15,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

E 40,0 0 0 0 3.1. Construction Types for Exposure E Wall Type ................................................................... OW-03 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 35 of 98 35

204-SHOP 1. General Details: Floor Area ............................................................. 47,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ........................................ RETAIL: Sales OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,60 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 90,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................. 6,67 m²/person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 15,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

E 40,0 0 0 0 3.1. Construction Types for Exposure E Wall Type ................................................................... OW-03 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 36 of 98 36

205-SHOP 1. General Details: Floor Area ............................................................. 47,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ........................................ RETAIL: Sales OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,60 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 90,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................. 6,67 m²/person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 15,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

E 40,0 0 0 0 3.1. Construction Types for Exposure E Wall Type ................................................................... OW-03 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 37 of 98 37

206-SHOP 1. General Details: Floor Area ............................................................. 41,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ........................................ RETAIL: Sales OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,60 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 90,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................. 6,67 m²/person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 15,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

E 40,0 0 0 0 3.1. Construction Types for Exposure E Wall Type ................................................................... OW-03 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 38 of 98 38

207-SHOP 1. General Details: Floor Area ............................................................. 52,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ........................................ RETAIL: Sales OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,60 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 90,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................. 6,67 m²/person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 15,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

E 40,0 0 0 0 3.1. Construction Types for Exposure E Wall Type ................................................................... OW-03 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 39 of 98 39

208-SHOP 1. General Details: Floor Area ............................................................. 50,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ........................................ RETAIL: Sales OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,60 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 90,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................. 6,67 m²/person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 15,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

E 40,0 0 0 0 3.1. Construction Types for Exposure E Wall Type ................................................................... OW-03 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 40 of 98 40

209-SHOP 1. General Details: Floor Area ............................................................. 59,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ........................................ RETAIL: Sales OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,60 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 90,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................. 6,67 m²/person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 15,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

E 40,0 0 0 0 3.1. Construction Types for Exposure E Wall Type ................................................................... OW-03 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 41 of 98 41

210-SHOP 1. General Details: Floor Area ............................................................. 42,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ........................................ RETAIL: Sales OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,60 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 90,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................. 6,67 m²/person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 15,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

E 25,0 0 0 0 3.1. Construction Types for Exposure E Wall Type ................................................................... OW-03 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: 7.1. 1st Partition Details: Partition Type ........................................ Wall Partition Area ....................................................................... 60,0 m² U-Value ............................................................... 2,000 W/(m²-°K) Uncondit. Space Max Temp .................................. 30,0 °C Ambient at Space Max Temp ................................ 24,0 °C Uncondit. Space Min Temp ................................... 15,0 °C Ambient at Space Min Temp ................................. 20,0 °C

7.2. 2nd Partition Details: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 42 of 98 42

211-HALL 1. General Details: Floor Area ............................................................. 11,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage .............................. GENERAL: Corridor OA Requirement 1 .................................................. 0,0 L/s/person OA Requirement 2 ................................................ 0,30 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 20,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................... 0,0 Person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule .............................................................. None

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ................................................................. 5,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors: (No Wall, Window, Door data). 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 ACH Design Heating ...................................................... 0,00 ACH Energy Analysis .................................................... 0,00 ACH Infiltration occurs at all hours. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: 7.1. 1st Partition Details: Partition Type ........................................ Wall Partition Area ....................................................................... 28,0 m² U-Value ............................................................... 2,000 W/(m²-°K) Uncondit. Space Max Temp .................................. 30,0 °C Ambient at Space Max Temp ................................ 24,0 °C Uncondit. Space Min Temp ................................... 15,0 °C Ambient at Space Min Temp ................................. 20,0 °C

7.2. 2nd Partition Details: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 43 of 98 43

213-WC MALE 1. General Details: Floor Area ............................................................. 20,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage .......................................... User-Defined OA Requirement 1 .................................................. 0,0 L/s OA Requirement 2 .................................................. 0,0 L/s Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 15,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................... 3,0 People Activity Level ........................................ Seated at Rest Sensible ................................................................. 67,4 W/person Latent ..................................................................... 35,2 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 15,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

E 30,0 0 0 0 3.1. Construction Types for Exposure E Wall Type ................................................................... OW-03 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 ACH Design Heating ...................................................... 0,00 ACH Energy Analysis .................................................... 0,00 ACH Infiltration occurs at all hours. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: 7.1. 1st Partition Details: Partition Type ........................................ Wall Partition Area ....................................................................... 35,0 m² U-Value ............................................................... 2,000 W/(m²-°K) Uncondit. Space Max Temp .................................. 30,0 °C Ambient at Space Max Temp ................................ 24,0 °C Uncondit. Space Min Temp ................................... 15,0 °C Ambient at Space Min Temp ................................. 20,0 °C

7.2. 2nd Partition Details: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 44 of 98 44

214-WC FEMALE 1. General Details: Floor Area ............................................................. 16,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage .......................................... User-Defined OA Requirement 1 .................................................. 0,0 L/s OA Requirement 2 .................................................. 0,0 L/s Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 15,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................... 3,0 People Activity Level ........................................ Seated at Rest Sensible ................................................................. 67,4 W/person Latent ..................................................................... 35,2 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 15,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors: (No Wall, Window, Door data). 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 ACH Design Heating ...................................................... 0,00 ACH Energy Analysis .................................................... 0,00 ACH Infiltration occurs at all hours. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: 7.1. 1st Partition Details: Partition Type ........................................ Wall Partition Area ....................................................................... 30,0 m² U-Value ............................................................... 2,000 W/(m²-°K) Uncondit. Space Max Temp .................................. 30,0 °C Ambient at Space Max Temp ................................ 24,0 °C Uncondit. Space Min Temp ................................... 15,0 °C Ambient at Space Min Temp ................................. 20,0 °C

7.2. 2nd Partition Details: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 45 of 98 45

217-DEPARTMENT STORE 1. General Details: Floor Area ........................................................... 364,0 m² Avg. Ceiling Height .................................................. 6,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ........................................ RETAIL: Sales OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,60 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 55,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................. 6,67 m²/person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 15,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

E 70,0 0 0 0

S 85,0 0 0 0

S 37,5 0 0 0

WSW 80,0 0 0 0 3.1. Construction Types for Exposure E Wall Type ................................................................... OW-03 3.2. Construction Types for Exposure S Wall Type ................................................................... OW-03' 3.3. Construction Types for Exposure S Wall Type ................................................................... OW-04 3.4. Construction Types for Exposure WSW Wall Type ................................................................... OW-03 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: 7.1. 1st Partition Details: Partition Type ........................................ Wall Partition Area ....................................................................... 50,0 m² U-Value ............................................................... 2,000 W/(m²-°K) Uncondit. Space Max Temp .................................. 30,0 °C Ambient at Space Max Temp ................................ 24,0 °C Uncondit. Space Min Temp ................................... 15,0 °C

Ambient at Space Min Temp ................................. 20,0 °C

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 46 of 98 46

7.2. 2nd Partition Details: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 47 of 98 47

219-SHOP 1. General Details: Floor Area ............................................................. 39,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ........................................ RETAIL: Sales OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,60 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 90,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................. 6,67 m²/person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 15,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

WSW 100,0 0 0 0 3.1. Construction Types for Exposure WSW Wall Type ................................................................... OW-03 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 48 of 98 48

220-SHOP 1. General Details: Floor Area ............................................................. 52,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ........................................ RETAIL: Sales OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,60 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 90,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................. 6,67 m²/person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 15,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

WSW 40,0 0 0 0 3.1. Construction Types for Exposure WSW Wall Type ................................................................... OW-03 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 49 of 98 49

221-SHOP 1. General Details: Floor Area ............................................................. 65,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ........................................ RETAIL: Sales OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,60 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 90,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................. 6,67 m²/person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 15,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

WSW 40,0 0 0 0 3.1. Construction Types for Exposure WSW Wall Type ................................................................... OW-03 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 50 of 98 50

222-SHOP 1. General Details: Floor Area ............................................................. 70,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ........................................ RETAIL: Sales OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,60 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 90,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................. 6,67 m²/person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 15,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

W 40,0 0 0 0 3.1. Construction Types for Exposure W Wall Type ................................................................... OW-03 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 51 of 98 51

223-SHOP 1. General Details: Floor Area ............................................................. 55,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ........................................ RETAIL: Sales OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,60 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 90,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................. 6,67 m²/person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 15,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

W 40,0 0 0 0 3.1. Construction Types for Exposure W Wall Type ................................................................... OW-03 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 52 of 98 52

224-SHOP 1. General Details: Floor Area ............................................................. 48,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ........................................ RETAIL: Sales OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,60 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 90,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................. 6,67 m²/person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 15,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

W 35,0 0 0 0 3.1. Construction Types for Exposure W Wall Type ................................................................... OW-03 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: 7.1. 1st Partition Details: Partition Type ........................................ Wall Partition Area ....................................................................... 50,0 m² U-Value ............................................................... 2,000 W/(m²-°K) Uncondit. Space Max Temp .................................. 30,0 °C Ambient at Space Max Temp ................................ 24,0 °C Uncondit. Space Min Temp ................................... 15,0 °C Ambient at Space Min Temp ................................. 20,0 °C

7.2. 2nd Partition Details: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 53 of 98 53

226-HALL 1. General Details: Floor Area ............................................................. 14,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage .............................. GENERAL: Corridor OA Requirement 1 .................................................. 0,0 L/s/person OA Requirement 2 ................................................ 0,30 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 20,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................... 0,0 Person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule .............................................................. None

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ................................................................. 5,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

W 12,5 0 0 0 3.1. Construction Types for Exposure W Wall Type ................................................................... OW-03 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 ACH Design Heating ...................................................... 0,00 ACH Energy Analysis .................................................... 0,00 ACH Infiltration occurs at all hours. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: 7.1. 1st Partition Details: Partition Type ........................................ Wall Partition Area ....................................................................... 50,0 m² U-Value ............................................................... 2,000 W/(m²-°K) Uncondit. Space Max Temp .................................. 30,0 °C Ambient at Space Max Temp ................................ 24,0 °C Uncondit. Space Min Temp ................................... 15,0 °C Ambient at Space Min Temp ................................. 20,0 °C

7.2. 2nd Partition Details: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 54 of 98 54

227-SHOP 1. General Details: Floor Area ............................................................. 53,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ........................................ RETAIL: Sales OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,60 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 90,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................. 6,67 m²/person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 15,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

W 32,0 0 0 0 3.1. Construction Types for Exposure W Wall Type ................................................................... OW-03 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: 7.1. 1st Partition Details: Partition Type ........................................ Wall Partition Area ....................................................................... 45,0 m² U-Value ............................................................... 2,000 W/(m²-°K) Uncondit. Space Max Temp .................................. 30,0 °C Ambient at Space Max Temp ................................ 24,0 °C Uncondit. Space Min Temp ................................... 15,0 °C Ambient at Space Min Temp ................................. 20,0 °C

7.2. 2nd Partition Details: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 55 of 98 55

228-CAFE 1. General Details: Floor Area ............................................................. 71,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ... FOOD SERVICE: Cafeteria/fast food OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,90 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 45,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................. 1,00 m²/person Activity Level ........................................ Seated at Rest Sensible ................................................................. 67,4 W/person Latent ..................................................................... 35,2 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule ...................................................... Electricity Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ................................................................. 5,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

W 55,0 0 0 0 3.1. Construction Types for Exposure W Wall Type ................................................................... OW-03 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 56 of 98 56

229-KIOSK 1. General Details: Floor Area ............................................................. 16,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ........................................ RETAIL: Sales OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,60 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 90,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................... 3,0 People Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 15,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors: (No Wall, Window, Door data). 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 57 of 98 57

230-KIOSK 1. General Details: Floor Area ............................................................... 5,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ........................................ RETAIL: Sales OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,60 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 90,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................... 2,0 People Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 15,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors: (No Wall, Window, Door data). 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 58 of 98 58

231-KIOSK 1. General Details: Floor Area ............................................................... 5,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ........................................ RETAIL: Sales OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,60 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 90,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................... 2,0 People Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 15,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors: (No Wall, Window, Door data). 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 59 of 98 59

232-SHOP 1. General Details: Floor Area ............................................................. 13,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ........................................ RETAIL: Sales OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,60 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 90,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................. 6,67 m²/person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 15,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors: (No Wall, Window, Door data). 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: 7.1. 1st Partition Details: Partition Type ........................................ Wall Partition Area ....................................................................... 10,0 m² U-Value ............................................................... 2,000 W/(m²-°K) Uncondit. Space Max Temp .................................. 30,0 °C Ambient at Space Max Temp ................................ 24,0 °C Uncondit. Space Min Temp ................................... 15,0 °C Ambient at Space Min Temp ................................. 20,0 °C

7.2. 2nd Partition Details: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 60 of 98 60

301-FOOD COURT 1. General Details: Floor Area ........................................................... 670,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage .................. RETAIL: Mall common area OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,30 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 20,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................. 2,50 m²/person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ................................................................. 5,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

W 40,0 0 0 0

E 40,0 0 0 0 3.1. Construction Types for Exposure W Wall Type ................................................................... OW-03 3.2. Construction Types for Exposure E Wall Type ................................................................... OW-03 4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.

H 296,0 0 30 4.1. Construction Types for Exposure H Roof Type ....................................................................... Roof Skylight Type ........................................................ SKYLIGHT 5. Infiltration: Design Cooling ...................................................... 0,00 ACH Design Heating ...................................................... 0,00 ACH Energy Analysis .................................................... 0,00 ACH Infiltration occurs at all hours. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: 7.1. 1st Partition Details: Partition Type ........................................ Wall Partition Area ....................................................................... 15,0 m² U-Value ............................................................... 2,000 W/(m²-°K) Uncondit. Space Max Temp .................................. 30,0 °C Ambient at Space Max Temp ................................ 24,0 °C Uncondit. Space Min Temp ................................... 15,0 °C Ambient at Space Min Temp ................................. 20,0 °C

7.2. 2nd Partition Details: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 61 of 98 61

302-KIOSK 1. General Details: Floor Area ............................................................... 5,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ........................................ RETAIL: Sales OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,60 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 90,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................... 2,0 People Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 15,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors: (No Wall, Window, Door data). 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 62 of 98 62

303-RESTAURANT 1. General Details: Floor Area ........................................................... 120,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage FOOD SERVICE: Restaurant dining room OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,90 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 45,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................. 1,50 m²/person Activity Level ........................................ Seated at Rest Sensible ................................................................. 67,4 W/person Latent ..................................................................... 35,2 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule ...................................................... Electricity Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ................................................................. 5,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

E 80,0 0 0 0 3.1. Construction Types for Exposure E Wall Type ................................................................... OW-03 4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.

H 120,0 0 0 4.1. Construction Types for Exposure H Roof Type ....................................................................... Roof 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 63 of 98 63

304-CAFE 1. General Details: Floor Area ............................................................. 34,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ... FOOD SERVICE: Cafeteria/fast food OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,90 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 45,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................. 1,00 m²/person Activity Level ........................................ Seated at Rest Sensible ................................................................. 67,4 W/person Latent ..................................................................... 35,2 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule ...................................................... Electricity Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ................................................................. 5,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

E 40,0 0 0 0 3.1. Construction Types for Exposure E Wall Type ................................................................... OW-03 4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.

H 34,0 0 0 4.1. Construction Types for Exposure H Roof Type ....................................................................... Roof 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 64 of 98 64

305-CAFE 1. General Details: Floor Area ............................................................. 36,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ... FOOD SERVICE: Cafeteria/fast food OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,90 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 45,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................. 1,00 m²/person Activity Level ........................................ Seated at Rest Sensible ................................................................. 67,4 W/person Latent ..................................................................... 35,2 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule ...................................................... Electricity Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ................................................................. 5,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

E 40,0 0 0 0 3.1. Construction Types for Exposure E Wall Type ................................................................... OW-03 4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.

H 34,0 0 0 4.1. Construction Types for Exposure H Roof Type ....................................................................... Roof 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 65 of 98 65

306-CAFE 1. General Details: Floor Area ............................................................. 34,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ... FOOD SERVICE: Cafeteria/fast food OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,90 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 45,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................. 1,00 m²/person Activity Level ........................................ Seated at Rest Sensible ................................................................. 67,4 W/person Latent ..................................................................... 35,2 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule ...................................................... Electricity Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ................................................................. 5,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

E 40,0 0 0 0 3.1. Construction Types for Exposure E Wall Type ................................................................... OW-03 4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.

H 34,0 0 0 4.1. Construction Types for Exposure H Roof Type ....................................................................... Roof 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 66 of 98 66

307-CAFE 1. General Details: Floor Area ............................................................. 44,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ... FOOD SERVICE: Cafeteria/fast food OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,90 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 45,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................. 1,00 m²/person Activity Level ........................................ Seated at Rest Sensible ................................................................. 67,4 W/person Latent ..................................................................... 35,2 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule ...................................................... Electricity Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ................................................................. 5,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

E 40,0 0 0 0 3.1. Construction Types for Exposure E Wall Type ................................................................... OW-03 4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.

H 34,0 0 0 4.1. Construction Types for Exposure H Roof Type ....................................................................... Roof 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 67 of 98 67

308-SHOP 1. General Details: Floor Area ............................................................. 43,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ........................................ RETAIL: Sales OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,60 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 90,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................. 6,67 m²/person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 15,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

E 40,0 0 0 0 3.1. Construction Types for Exposure E Wall Type ................................................................... OW-03 4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.

H 43,0 0 0 4.1. Construction Types for Exposure H Roof Type ....................................................................... Roof 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 68 of 98 68

309-SHOP 1. General Details: Floor Area ............................................................. 52,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ........................................ RETAIL: Sales OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,60 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 90,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................. 6,67 m²/person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 15,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

E 40,0 0 0 0 3.1. Construction Types for Exposure E Wall Type ................................................................... OW-03 4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.

H 43,0 0 0 4.1. Construction Types for Exposure H Roof Type ....................................................................... Roof 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 69 of 98 69

310-SHOP 1. General Details: Floor Area ............................................................. 36,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ........................................ RETAIL: Sales OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,60 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 90,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................. 6,67 m²/person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 15,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

E 25,0 0 0 0 3.1. Construction Types for Exposure E Wall Type ................................................................... OW-03 4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.

H 36,0 0 0 4.1. Construction Types for Exposure H Roof Type ....................................................................... Roof 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: 7.1. 1st Partition Details: Partition Type ........................................ Wall Partition Area ....................................................................... 60,0 m² U-Value ............................................................... 2,000 W/(m²-°K) Uncondit. Space Max Temp .................................. 30,0 °C Ambient at Space Max Temp ................................ 24,0 °C Uncondit. Space Min Temp ................................... 15,0 °C Ambient at Space Min Temp ................................. 20,0 °C

7.2. 2nd Partition Details: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 70 of 98 70

311-HALL 1. General Details: Floor Area ............................................................. 11,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage .............................. GENERAL: Corridor OA Requirement 1 .................................................. 0,0 L/s/person OA Requirement 2 ................................................ 0,30 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 20,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................... 0,0 Person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule .............................................................. None

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ................................................................. 5,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors: (No Wall, Window, Door data). 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 ACH Design Heating ...................................................... 0,00 ACH Energy Analysis .................................................... 0,00 ACH Infiltration occurs at all hours. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: 7.1. 1st Partition Details: Partition Type ........................................ Wall Partition Area ....................................................................... 28,0 m² U-Value ............................................................... 2,000 W/(m²-°K) Uncondit. Space Max Temp .................................. 30,0 °C Ambient at Space Max Temp ................................ 24,0 °C Uncondit. Space Min Temp ................................... 15,0 °C Ambient at Space Min Temp ................................. 20,0 °C

7.2. 2nd Partition Details: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 71 of 98 71

313-WC MALE 1. General Details: Floor Area ............................................................. 20,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage .......................................... User-Defined OA Requirement 1 .................................................. 0,0 L/s OA Requirement 2 .................................................. 0,0 L/s Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 15,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................... 3,0 People Activity Level ........................................ Seated at Rest Sensible ................................................................. 67,4 W/person Latent ..................................................................... 35,2 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 15,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

E 30,0 0 0 0 3.1. Construction Types for Exposure E Wall Type ................................................................... OW-03 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 ACH Design Heating ...................................................... 0,00 ACH Energy Analysis .................................................... 0,00 ACH Infiltration occurs at all hours. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: 7.1. 1st Partition Details: Partition Type ........................................ Wall Partition Area ....................................................................... 35,0 m² U-Value ............................................................... 2,000 W/(m²-°K) Uncondit. Space Max Temp .................................. 30,0 °C Ambient at Space Max Temp ................................ 24,0 °C Uncondit. Space Min Temp ................................... 15,0 °C Ambient at Space Min Temp ................................. 20,0 °C

7.2. 2nd Partition Details: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 72 of 98 72

314-WC FEMALE 1. General Details: Floor Area ............................................................. 16,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage .......................................... User-Defined OA Requirement 1 .................................................. 0,0 L/s OA Requirement 2 .................................................. 0,0 L/s Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 15,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................... 3,0 People Activity Level ........................................ Seated at Rest Sensible ................................................................. 67,4 W/person Latent ..................................................................... 35,2 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 15,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors: (No Wall, Window, Door data). 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 ACH Design Heating ...................................................... 0,00 ACH Energy Analysis .................................................... 0,00 ACH Infiltration occurs at all hours. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: 7.1. 1st Partition Details: Partition Type ........................................ Wall Partition Area ....................................................................... 30,0 m² U-Value ............................................................... 2,000 W/(m²-°K) Uncondit. Space Max Temp .................................. 30,0 °C Ambient at Space Max Temp ................................ 24,0 °C Uncondit. Space Min Temp ................................... 15,0 °C Ambient at Space Min Temp ................................. 20,0 °C

7.2. 2nd Partition Details: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 73 of 98 73

317-ENTERTAINMENT 1. General Details: Floor Area ........................................................... 364,0 m² Avg. Ceiling Height .................................................. 6,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ......................... SPORTS: Stage, studio OA Requirement 1 .................................................. 5,0 L/s/person OA Requirement 2 ................................................ 0,30 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 25,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................. 1,50 m²/person Activity Level ........................................ Seated at Rest Sensible ................................................................. 67,4 W/person Latent ..................................................................... 35,2 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 35,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

E 70,0 0 0 0

S 85,0 0 0 0

S 37,5 0 0 0

WSW 80,0 0 0 0 3.1. Construction Types for Exposure E Wall Type ................................................................... OW-03 3.2. Construction Types for Exposure S Wall Type ................................................................... OW-03' 3.3. Construction Types for Exposure S Wall Type ................................................................... OW-04 3.4. Construction Types for Exposure WSW Wall Type ................................................................... OW-03 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: 7.1. 1st Partition Details: Partition Type ........................................ Wall Partition Area ....................................................................... 50,0 m² U-Value ............................................................... 2,000 W/(m²-°K) Uncondit. Space Max Temp .................................. 30,0 °C Ambient at Space Max Temp ................................ 24,0 °C Uncondit. Space Min Temp ................................... 15,0 °C

Ambient at Space Min Temp ................................. 20,0 °C

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 74 of 98 74

7.2. 2nd Partition Details: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 75 of 98 75

319-SHOP 1. General Details: Floor Area ............................................................. 39,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ........................................ RETAIL: Sales OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,60 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 90,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................. 6,67 m²/person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 15,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

WSW 100,0 0 0 0 3.1. Construction Types for Exposure WSW Wall Type ................................................................... OW-03 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 76 of 98 76

320-SHOP 1. General Details: Floor Area ............................................................. 48,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ........................................ RETAIL: Sales OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,60 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 90,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................. 6,67 m²/person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 15,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

WSW 40,0 0 0 0 3.1. Construction Types for Exposure WSW Wall Type ................................................................... OW-03 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 77 of 98 77

321-SHOP 1. General Details: Floor Area ............................................................. 58,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ........................................ RETAIL: Sales OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,60 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 90,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................. 6,67 m²/person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 15,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

WSW 40,0 0 0 0 3.1. Construction Types for Exposure WSW Wall Type ................................................................... OW-03 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 78 of 98 78

322-RESTAURANT 1. General Details: Floor Area ............................................................. 62,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage FOOD SERVICE: Restaurant dining room OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,90 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 45,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................. 1,50 m²/person Activity Level ........................................ Seated at Rest Sensible ................................................................. 67,4 W/person Latent ..................................................................... 35,2 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule ...................................................... Electricity Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ................................................................. 5,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

W 40,0 0 0 0 3.1. Construction Types for Exposure W Wall Type ................................................................... OW-03 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: 7.1. 1st Partition Details: Partition Type ........................................ Wall Partition Area ....................................................................... 20,0 m² U-Value ............................................................... 2,000 W/(m²-°K) Uncondit. Space Max Temp .................................. 30,0 °C Ambient at Space Max Temp ................................ 24,0 °C Uncondit. Space Min Temp ................................... 15,0 °C Ambient at Space Min Temp ................................. 20,0 °C

7.2. 2nd Partition Details: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 79 of 98 79

324-PRIVATE RESTAURANT 1. General Details: Floor Area ............................................................. 70,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage FOOD SERVICE: Restaurant dining room OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,90 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 45,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................. 1,50 m²/person Activity Level ........................................ Seated at Rest Sensible ................................................................. 67,4 W/person Latent ..................................................................... 35,2 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule ...................................................... Electricity Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ................................................................. 5,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

W 75,0 0 0 0 3.1. Construction Types for Exposure W Wall Type ................................................................... OW-03 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: 7.1. 1st Partition Details: Partition Type ........................................ Wall Partition Area ....................................................................... 30,0 m² U-Value ............................................................... 2,000 W/(m²-°K) Uncondit. Space Max Temp .................................. 30,0 °C Ambient at Space Max Temp ................................ 24,0 °C Uncondit. Space Min Temp ................................... 15,0 °C Ambient at Space Min Temp ................................. 20,0 °C

7.2. 2nd Partition Details: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 80 of 98 80

326-HALL 1. General Details: Floor Area ............................................................. 14,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage .............................. GENERAL: Corridor OA Requirement 1 .................................................. 0,0 L/s/person OA Requirement 2 ................................................ 0,30 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 20,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................... 0,0 Person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule .............................................................. None

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ................................................................. 5,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

W 12,5 0 0 0 3.1. Construction Types for Exposure W Wall Type ................................................................... OW-03 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 ACH Design Heating ...................................................... 0,00 ACH Energy Analysis .................................................... 0,00 ACH Infiltration occurs at all hours. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: 7.1. 1st Partition Details: Partition Type ........................................ Wall Partition Area ....................................................................... 50,0 m² U-Value ............................................................... 2,000 W/(m²-°K) Uncondit. Space Max Temp .................................. 30,0 °C Ambient at Space Max Temp ................................ 24,0 °C Uncondit. Space Min Temp ................................... 15,0 °C Ambient at Space Min Temp ................................. 20,0 °C

7.2. 2nd Partition Details: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 81 of 98 81

327-RESTAURANT 1. General Details: Floor Area ............................................................. 99,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage FOOD SERVICE: Restaurant dining room OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,90 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 45,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................. 1,50 m²/person Activity Level ........................................ Seated at Rest Sensible ................................................................. 67,4 W/person Latent ..................................................................... 35,2 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule ...................................................... Electricity Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ................................................................. 5,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

W 75,0 0 0 0 3.1. Construction Types for Exposure W Wall Type ................................................................... OW-03 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: 7.1. 1st Partition Details: Partition Type ........................................ Wall Partition Area ....................................................................... 45,0 m² U-Value ............................................................... 2,000 W/(m²-°K) Uncondit. Space Max Temp .................................. 30,0 °C Ambient at Space Max Temp ................................ 24,0 °C Uncondit. Space Min Temp ................................... 15,0 °C Ambient at Space Min Temp ................................. 20,0 °C

7.2. 2nd Partition Details: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 82 of 98 82

328-KIOSK 1. General Details: Floor Area ............................................................... 5,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ........................................ RETAIL: Sales OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,60 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 90,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................... 2,0 People Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 15,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors: (No Wall, Window, Door data). 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 83 of 98 83

329-SHOP 1. General Details: Floor Area ............................................................. 13,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ........................................ RETAIL: Sales OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,60 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 90,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................. 6,67 m²/person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 15,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors: (No Wall, Window, Door data). 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: 7.1. 1st Partition Details: Partition Type ........................................ Wall Partition Area ....................................................................... 10,0 m² U-Value ............................................................... 2,000 W/(m²-°K) Uncondit. Space Max Temp .................................. 30,0 °C Ambient at Space Max Temp ................................ 24,0 °C Uncondit. Space Min Temp ................................... 15,0 °C Ambient at Space Min Temp ................................. 20,0 °C

7.2. 2nd Partition Details: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 84 of 98 84

330-SHOPPING HALL 1. General Details: Floor Area ........................................................... 398,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage .................. RETAIL: Mall common area OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,30 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 20,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................. 2,50 m²/person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ................................................................. 5,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors: (No Wall, Window, Door data). 4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.

H 78,0 0 0 4.1. Construction Types for Exposure H Roof Type ....................................................................... Roof 5. Infiltration: Design Cooling ...................................................... 0,00 ACH Design Heating ...................................................... 0,00 ACH Energy Analysis .................................................... 0,00 ACH Infiltration occurs at all hours. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: 7.1. 1st Partition Details: Partition Type ........................................ Wall Partition Area ....................................................................... 18,0 m² U-Value ............................................................... 2,000 W/(m²-°K) Uncondit. Space Max Temp .................................. 30,0 °C Ambient at Space Max Temp ................................ 24,0 °C Uncondit. Space Min Temp ................................... 15,0 °C Ambient at Space Min Temp ................................. 20,0 °C

7.2. 2nd Partition Details: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 85 of 98 85

401-PRIVATE RESTAURANT 1. General Details: Floor Area ........................................................... 424,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage FOOD SERVICE: Restaurant dining room OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,90 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 45,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................. 1,50 m²/person Activity Level ........................................ Seated at Rest Sensible ................................................................. 67,4 W/person Latent ..................................................................... 35,2 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule ...................................................... Electricity Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ................................................................. 5,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

W 75,0 0 0 0

N 70,0 12 0 0

E 85,0 19 0 0

S 15,0 3 0 0 3.1. Construction Types for Exposure W Wall Type ................................................................... OW-03 3.2. Construction Types for Exposure N Wall Type ................................................................... OW-03 1st Window Type ....................................... WIN-1.00X3.80 m 3.3. Construction Types for Exposure E Wall Type ................................................................... OW-03 1st Window Type ....................................... WIN-1.00X3.80 m 3.4. Construction Types for Exposure S Wall Type ................................................................... OW-03 1st Window Type ....................................... WIN-1.00X3.80 m 4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.

H 437,0 0 0 4.1. Construction Types for Exposure H Roof Type ....................................................................... Roof 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off.

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 86 of 98 86

6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: 7.1. 1st Partition Details: Partition Type ........................................ Wall Partition Area ..................................................................... 150,0 m² U-Value ............................................................... 2,000 W/(m²-°K) Uncondit. Space Max Temp .................................. 30,0 °C Ambient at Space Max Temp ................................ 24,0 °C Uncondit. Space Min Temp ................................... 15,0 °C Ambient at Space Min Temp ................................. 20,0 °C

7.2. 2nd Partition Details: Partition Type ........................................ Wall Partition Area ..................................................................... 120,0 m² U-Value ................................................................ 2,500 W/(m²-°K) Uncondit. Space Max Temp .................................. 40,0 °C Ambient at Space Max Temp ................................ 45,0 °C Uncondit. Space Min Temp ................................... 10,0 °C Ambient at Space Min Temp ................................... 0,0 °C

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 87 of 98 87

403-HALL 1. General Details: Floor Area ............................................................. 11,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage .............................. GENERAL: Corridor OA Requirement 1 .................................................. 0,0 L/s/person OA Requirement 2 ................................................ 0,30 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 20,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................... 0,0 Person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule .............................................................. None

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ................................................................. 5,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors: (No Wall, Window, Door data). 4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.

H 11,0 0 0 4.1. Construction Types for Exposure H Roof Type ....................................................................... Roof 5. Infiltration: Design Cooling ...................................................... 0,00 ACH Design Heating ...................................................... 0,00 ACH Energy Analysis .................................................... 0,00 ACH Infiltration occurs at all hours. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: 7.1. 1st Partition Details: Partition Type ........................................ Wall Partition Area ....................................................................... 28,0 m² U-Value ............................................................... 2,000 W/(m²-°K) Uncondit. Space Max Temp .................................. 30,0 °C Ambient at Space Max Temp ................................ 24,0 °C Uncondit. Space Min Temp ................................... 15,0 °C Ambient at Space Min Temp ................................. 20,0 °C

7.2. 2nd Partition Details: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 88 of 98 88

405-WC MALE 1. General Details: Floor Area ............................................................. 20,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage .......................................... User-Defined OA Requirement 1 .................................................. 0,0 L/s OA Requirement 2 .................................................. 0,0 L/s Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 15,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................... 3,0 People Activity Level ........................................ Seated at Rest Sensible ................................................................. 67,4 W/person Latent ..................................................................... 35,2 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 15,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

E 30,0 0 0 0 3.1. Construction Types for Exposure E Wall Type ................................................................... OW-03 4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.

H 20,0 0 0 4.1. Construction Types for Exposure H Roof Type ....................................................................... Roof 5. Infiltration: Design Cooling ...................................................... 0,00 ACH Design Heating ...................................................... 0,00 ACH Energy Analysis .................................................... 0,00 ACH Infiltration occurs at all hours. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: 7.1. 1st Partition Details: Partition Type ........................................ Wall Partition Area ....................................................................... 35,0 m² U-Value ............................................................... 2,000 W/(m²-°K) Uncondit. Space Max Temp .................................. 30,0 °C Ambient at Space Max Temp ................................ 24,0 °C Uncondit. Space Min Temp ................................... 15,0 °C Ambient at Space Min Temp ................................. 20,0 °C

7.2. 2nd Partition Details: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 89 of 98 89

406-WC FEMALE 1. General Details: Floor Area ............................................................. 16,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage .......................................... User-Defined OA Requirement 1 .................................................. 0,0 L/s OA Requirement 2 .................................................. 0,0 L/s Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 15,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................... 3,0 People Activity Level ........................................ Seated at Rest Sensible ................................................................. 67,4 W/person Latent ..................................................................... 35,2 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 15,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors: (No Wall, Window, Door data). 4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.

H 16,0 0 0 4.1. Construction Types for Exposure H Roof Type ....................................................................... Roof 5. Infiltration: Design Cooling ...................................................... 0,00 ACH Design Heating ...................................................... 0,00 ACH Energy Analysis .................................................... 0,00 ACH Infiltration occurs at all hours. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: 7.1. 1st Partition Details: Partition Type ........................................ Wall Partition Area ....................................................................... 30,0 m² U-Value ............................................................... 2,000 W/(m²-°K) Uncondit. Space Max Temp .................................. 30,0 °C Ambient at Space Max Temp ................................ 24,0 °C Uncondit. Space Min Temp ................................... 15,0 °C Ambient at Space Min Temp ................................. 20,0 °C

7.2. 2nd Partition Details: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 90 of 98 90

409-HALL 1. General Details: Floor Area ............................................................... 7,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage .............................. GENERAL: Corridor OA Requirement 1 .................................................. 0,0 L/s/person OA Requirement 2 ................................................ 0,30 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 20,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................... 0,0 Person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule .............................................................. None

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ................................................................. 5,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors: (No Wall, Window, Door data). 4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.

H 6,0 0 0 4.1. Construction Types for Exposure H Roof Type ....................................................................... Roof 5. Infiltration: Design Cooling ...................................................... 0,00 ACH Design Heating ...................................................... 0,00 ACH Energy Analysis .................................................... 0,00 ACH Infiltration occurs at all hours. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: 7.1. 1st Partition Details: Partition Type ........................................ Wall Partition Area ....................................................................... 10,0 m² U-Value ............................................................... 2,000 W/(m²-°K) Uncondit. Space Max Temp .................................. 30,0 °C Ambient at Space Max Temp ................................ 24,0 °C Uncondit. Space Min Temp ................................... 15,0 °C Ambient at Space Min Temp ................................. 20,0 °C

7.2. 2nd Partition Details: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 91 of 98 91

410-OFFICE 1. General Details: Floor Area ........................................................... 360,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ........................... OFFICE: Office space OA Requirement 1 .................................................. 2,5 L/s/person OA Requirement 2 ................................................ 0,30 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 25,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ........................................................... 10,00 m²/person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 35,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

E 70,0 11 0 0

S 85,0 0 0 0

S 37,5 0 0 0

WSW 80,0 14 0 0 3.1. Construction Types for Exposure E Wall Type ................................................................... OW-03 1st Window Type ........................................ WIN-1.00X1.50m 3.2. Construction Types for Exposure S Wall Type ................................................................... OW-03' 3.3. Construction Types for Exposure S Wall Type ................................................................... OW-04 3.4. Construction Types for Exposure WSW Wall Type ................................................................... OW-03 1st Window Type ........................................ WIN-1.00X1.50m 4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.

H 360,0 0 0 4.1. Construction Types for Exposure H Roof Type ....................................................................... Roof 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off.

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 92 of 98 92

6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: 7.1. 1st Partition Details: Partition Type ........................................ Wall Partition Area ....................................................................... 50,0 m² U-Value ............................................................... 2,000 W/(m²-°K) Uncondit. Space Max Temp .................................. 30,0 °C Ambient at Space Max Temp ................................ 24,0 °C Uncondit. Space Min Temp ................................... 15,0 °C Ambient at Space Min Temp ................................. 20,0 °C

7.2. 2nd Partition Details: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 93 of 98 93

411-OFFICE HALL 1. General Details: Floor Area ........................................................... 189,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage .................... OFFICE: Main entry lobby OA Requirement 1 .................................................. 2,5 L/s/person OA Requirement 2 ................................................ 0,30 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 20,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ........................................................... 10,00 m²/person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ................................................................. 5,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

N 30,0 6 0 0 3.1. Construction Types for Exposure N Wall Type ................................................................... OW-03 1st Window Type ....................................... WIN-1.00X3.80 m 4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.

H 189,0 0 0 4.1. Construction Types for Exposure H Roof Type ....................................................................... Roof 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: 7.1. 1st Partition Details: Partition Type ........................................ Wall Partition Area ....................................................................... 55,0 m² U-Value ............................................................... 2,000 W/(m²-°K) Uncondit. Space Max Temp .................................. 30,0 °C Ambient at Space Max Temp ................................ 24,0 °C Uncondit. Space Min Temp ................................... 15,0 °C Ambient at Space Min Temp ................................. 20,0 °C

7.2. 2nd Partition Details: Partition Type ........................................ Wall Partition Area ....................................................................... 80,0 m² U-Value ................................................................ 2,500 W/(m²-°K) Uncondit. Space Max Temp .................................. 40,0 °C Ambient at Space Max Temp ................................ 45,0 °C Uncondit. Space Min Temp ................................... 10,0 °C Ambient at Space Min Temp ................................... 0,0 °C

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 94 of 98 94

412-OFFICE 1. General Details: Floor Area ............................................................. 60,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ........................... OFFICE: Office space OA Requirement 1 .................................................. 2,5 L/s/person OA Requirement 2 ................................................ 0,30 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 25,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ........................................................... 10,00 m²/person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 35,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

WSW 40,0 8 0 0 3.1. Construction Types for Exposure WSW Wall Type ................................................................... OW-03 1st Window Type ........................................ WIN-1.00X1.50m 4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.

H 60,0 0 0 4.1. Construction Types for Exposure H Roof Type ....................................................................... Roof 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 95 of 98 95

413-OFFICE 1. General Details: Floor Area ............................................................. 59,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ........................... OFFICE: Office space OA Requirement 1 .................................................. 2,5 L/s/person OA Requirement 2 ................................................ 0,30 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 25,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................... 6,0 People Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 35,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

WSW 40,0 8 0 0 3.1. Construction Types for Exposure WSW Wall Type ................................................................... OW-03 1st Window Type ........................................ WIN-1.00X1.50m 4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.

H 59,0 0 0 4.1. Construction Types for Exposure H Roof Type ....................................................................... Roof 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 96 of 98 96

414-OFFICE 1. General Details: Floor Area ............................................................. 59,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ........................... OFFICE: Office space OA Requirement 1 .................................................. 2,5 L/s/person OA Requirement 2 ................................................ 0,30 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 25,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................... 6,0 People Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 35,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

WSW 40,0 8 0 0 3.1. Construction Types for Exposure WSW Wall Type ................................................................... OW-03 1st Window Type ........................................ WIN-1.00X1.50m 4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.

H 59,0 0 0 4.1. Construction Types for Exposure H Roof Type ....................................................................... Roof 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 97 of 98 97

415-HALL 1. General Details: Floor Area ............................................................. 37,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage .............................. GENERAL: Corridor OA Requirement 1 .................................................. 0,0 L/s/person OA Requirement 2 ................................................ 0,30 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 20,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................... 0,0 Person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule .............................................................. None

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ................................................................. 5,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors: (No Wall, Window, Door data). 4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.

H 37,0 0 0 4.1. Construction Types for Exposure H Roof Type ....................................................................... Roof 5. Infiltration: Design Cooling ...................................................... 0,00 ACH Design Heating ...................................................... 0,00 ACH Energy Analysis .................................................... 0,00 ACH Infiltration occurs at all hours. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: 7.1. 1st Partition Details: Partition Type ........................................ Wall Partition Area ....................................................................... 80,0 m² U-Value ............................................................... 2,500 W/(m²-°K) Uncondit. Space Max Temp .................................. 40,0 °C Ambient at Space Max Temp ................................ 45,0 °C Uncondit. Space Min Temp ................................... 10,0 °C Ambient at Space Min Temp ................................... 0,0 °C

7.2. 2nd Partition Details: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:06

Hourly Analysis Program v.4,3 Page 98 of 98 98

416-KITCHEN 1. General Details: Floor Area ........................................................... 153,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage .......................................... User-Defined OA Requirement 1 .............................................. 500,0 L/s OA Requirement 2 ................................................ 0,00 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 20,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................. 15,0 People Activity Level ..................................... Sedentary Work Sensible ................................................................. 82,1 W/person Latent ..................................................................... 79,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................. 200,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

WSW 35,0 0 0 0

W 45,0 0 0 0 3.1. Construction Types for Exposure WSW Wall Type ................................................................... OW-03 3.2. Construction Types for Exposure W Wall Type ................................................................... OW-03 4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.

H 159,0 0 0 4.1. Construction Types for Exposure H Roof Type ....................................................................... Roof 5. Infiltration: Design Cooling ...................................................... 0,00 ACH Design Heating ...................................................... 0,00 ACH Energy Analysis .................................................... 0,00 ACH Infiltration occurs at all hours. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:05

Hourly Analysis Program v.4,3 Page 1 of 24

GR01-ENTRANCE HALL 1. General Details: Floor Area ........................................................... 344,0 m² Avg. Ceiling Height ................................................ 16,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage .................. RETAIL: Mall common area OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,30 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 20,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................. 2,50 m²/person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ................................................................. 5,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

N 251,0 1 0 0

E 221,0 0 0 0

W 221,0 0 0 0 3.1. Construction Types for Exposure N Wall Type ................................................................... OW-01 1st Window Type ....................................... WIN-20.0x12.5 m 3.2. Construction Types for Exposure E Wall Type ................................................................... OW-02 3.3. Construction Types for Exposure W Wall Type ................................................................... OW-02 4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.

N 291,0 33 1 4.1. Construction Types for Exposure N Roof Type ....................................................................... Roof Skylight Type ............................................. WIN-20.0x14.5 m 5. Infiltration: Design Cooling ...................................................... 0,00 ACH Design Heating ...................................................... 0,00 ACH Energy Analysis .................................................... 0,00 ACH Infiltration occurs at all hours.

Space Input Data BAGHDAD MALL 11.22.2012 02:05

Hourly Analysis Program v.4,3 Page 2 of 24

6. Floors: Type .................. Floor Above Unconditioned Space Floor Area ........................................................... 344,0 m² Total Floor U-Value ............................................. 1,950 W/(m²-°K) Unconditioned Space Max Temp. ......................... 30,0 °C Ambient at Space Max Temp. ............................... 24,0 °C Unconditioned Space Min Temp. .......................... 15,0 °C Ambient at Space Min Temp. ................................ 20,0 °C 7. Partitions: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:05

Hourly Analysis Program v.4,3 Page 3 of 24

GR02-MALL HALL 1. General Details: Floor Area ........................................................... 314,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage .................. RETAIL: Mall common area OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,30 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 20,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................. 2,50 m²/person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ................................................................. 5,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

W 18,0 0 0 0

E 25,0 0 0 0 3.1. Construction Types for Exposure W Wall Type ................................................................... OW-03 3.2. Construction Types for Exposure E Wall Type ................................................................... OW-03 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 ACH Design Heating ...................................................... 0,00 ACH Energy Analysis .................................................... 0,00 ACH Infiltration occurs at all hours. 6. Floors: Type .................. Floor Above Unconditioned Space Floor Area ........................................................... 314,0 m² Total Floor U-Value ............................................. 1,950 W/(m²-°K) Unconditioned Space Max Temp. ......................... 30,0 °C Ambient at Space Max Temp. ............................... 24,0 °C Unconditioned Space Min Temp. .......................... 15,0 °C Ambient at Space Min Temp. ................................ 20,0 °C 7. Partitions: 7.1. 1st Partition Details: Partition Type ........................................ Wall Partition Area ....................................................................... 17,0 m² U-Value ............................................................... 2,000 W/(m²-°K) Uncondit. Space Max Temp .................................. 30,0 °C Ambient at Space Max Temp ................................ 24,0 °C Uncondit. Space Min Temp ................................... 15,0 °C Ambient at Space Min Temp ................................. 20,0 °C

7.2. 2nd Partition Details: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:05

Hourly Analysis Program v.4,3 Page 4 of 24

GR03-SHOP 1. General Details: Floor Area ............................................................. 73,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ........................................ RETAIL: Sales OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,60 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 90,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................. 6,67 m²/person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 15,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

E 40,0 0 0 0 3.1. Construction Types for Exposure E Wall Type ................................................................... OW-03 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type .................. Floor Above Unconditioned Space Floor Area ............................................................. 73,0 m² Total Floor U-Value ............................................. 1,950 W/(m²-°K) Unconditioned Space Max Temp. ......................... 30,0 °C Ambient at Space Max Temp. ............................... 24,0 °C Unconditioned Space Min Temp. .......................... 15,0 °C Ambient at Space Min Temp. ................................ 20,0 °C 7. Partitions: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:05

Hourly Analysis Program v.4,3 Page 5 of 24

GR04-SHOP 1. General Details: Floor Area ............................................................. 70,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ........................................ RETAIL: Sales OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,60 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 90,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................. 6,67 m²/person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 15,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

E 40,0 0 0 0 3.1. Construction Types for Exposure E Wall Type ................................................................... OW-03 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type .................. Floor Above Unconditioned Space Floor Area ............................................................. 70,0 m² Total Floor U-Value ............................................. 1,950 W/(m²-°K) Unconditioned Space Max Temp. ......................... 30,0 °C Ambient at Space Max Temp. ............................... 24,0 °C Unconditioned Space Min Temp. .......................... 15,0 °C Ambient at Space Min Temp. ................................ 20,0 °C 7. Partitions: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:05

Hourly Analysis Program v.4,3 Page 6 of 24

GR05-SHOP 1. General Details: Floor Area ............................................................. 66,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ........................................ RETAIL: Sales OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,60 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 90,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................. 6,67 m²/person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 15,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

E 40,0 0 0 0 3.1. Construction Types for Exposure E Wall Type ................................................................... OW-03 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type .................. Floor Above Unconditioned Space Floor Area ............................................................. 66,0 m² Total Floor U-Value ............................................. 1,950 W/(m²-°K) Unconditioned Space Max Temp. ......................... 30,0 °C Ambient at Space Max Temp. ............................... 24,0 °C Unconditioned Space Min Temp. .......................... 15,0 °C Ambient at Space Min Temp. ................................ 20,0 °C 7. Partitions: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:05

Hourly Analysis Program v.4,3 Page 7 of 24

GR06-SHOP 1. General Details: Floor Area ............................................................. 12,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ........................................ RETAIL: Sales OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,60 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 90,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................. 6,67 m²/person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 15,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors: (No Wall, Window, Door data). 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type .................. Floor Above Unconditioned Space Floor Area ............................................................. 12,0 m² Total Floor U-Value ............................................. 1,950 W/(m²-°K) Unconditioned Space Max Temp. ......................... 30,0 °C Ambient at Space Max Temp. ............................... 24,0 °C Unconditioned Space Min Temp. .......................... 15,0 °C Ambient at Space Min Temp. ................................ 20,0 °C 7. Partitions: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:05

Hourly Analysis Program v.4,3 Page 8 of 24

GR07-SHOP 1. General Details: Floor Area ............................................................... 8,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ........................................ RETAIL: Sales OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,60 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 90,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................. 2,00 m²/person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 15,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

E 12,5 0 0 0 3.1. Construction Types for Exposure E Wall Type ................................................................... OW-03 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type .................. Floor Above Unconditioned Space Floor Area ............................................................... 8,0 m² Total Floor U-Value ............................................. 1,950 W/(m²-°K) Unconditioned Space Max Temp. ......................... 30,0 °C Ambient at Space Max Temp. ............................... 24,0 °C Unconditioned Space Min Temp. .......................... 15,0 °C Ambient at Space Min Temp. ................................ 20,0 °C 7. Partitions: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:05

Hourly Analysis Program v.4,3 Page 9 of 24

GR08-HYPERMARKET 1. General Details: Floor Area ......................................................... 1319,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ........................... RETAIL: Supermarket OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,30 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 40,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ........................................................... 12,50 m²/person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 15,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

E 142,5 0 0 0

WSW 80,0 0 0 0

W 20,0 0 0 1 3.1. Construction Types for Exposure E Wall Type ................................................................... OW-03 3.2. Construction Types for Exposure WSW Wall Type ................................................................... OW-03 3.3. Construction Types for Exposure W Wall Type ................................................................... OW-01 Door Type .................................................. D5 Service Door 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type .................. Floor Above Unconditioned Space Floor Area ......................................................... 1319,0 m² Total Floor U-Value ............................................. 1,950 W/(m²-°K) Unconditioned Space Max Temp. ......................... 30,0 °C Ambient at Space Max Temp. ............................... 24,0 °C Unconditioned Space Min Temp. .......................... 15,0 °C Ambient at Space Min Temp. ................................ 20,0 °C 7. Partitions: 7.1. 1st Partition Details: Partition Type ........................................ Wall Partition Area ..................................................................... 175,0 m² U-Value ............................................................... 2,000 W/(m²-°K) Uncondit. Space Max Temp .................................. 30,0 °C Ambient at Space Max Temp ................................ 24,0 °C

Uncondit. Space Min Temp ................................... 15,0 °C Ambient at Space Min Temp ................................. 20,0 °C

Space Input Data BAGHDAD MALL 11.22.2012 02:05

Hourly Analysis Program v.4,3 Page 10 of 24

7.2. 2nd Partition Details: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:05

Hourly Analysis Program v.4,3 Page 11 of 24

GR09-ESCAPE HALL 1. General Details: Floor Area ............................................................. 88,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage .............................. GENERAL: Corridor OA Requirement 1 .................................................. 0,0 L/s/person OA Requirement 2 ................................................ 0,30 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 20,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................... 0,0 Person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule .............................................................. None

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ................................................................. 5,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

S 17,0 1 0 0 3.1. Construction Types for Exposure S Wall Type ................................................................... OW-03' 1st Window Type ....................................... WIN-1.74x2.20 m 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 ACH Design Heating ...................................................... 0,00 ACH Energy Analysis .................................................... 0,00 ACH Infiltration occurs at all hours. 6. Floors: Type .................. Floor Above Unconditioned Space Floor Area ............................................................. 88,0 m² Total Floor U-Value ............................................. 1,950 W/(m²-°K) Unconditioned Space Max Temp. ......................... 30,0 °C Ambient at Space Max Temp. ............................... 24,0 °C Unconditioned Space Min Temp. .......................... 15,0 °C Ambient at Space Min Temp. ................................ 20,0 °C 7. Partitions: 7.1. 1st Partition Details: Partition Type ........................................ Wall Partition Area ....................................................................... 45,0 m² U-Value ............................................................... 2,000 W/(m²-°K) Uncondit. Space Max Temp .................................. 30,0 °C Ambient at Space Max Temp ................................ 24,0 °C Uncondit. Space Min Temp ................................... 15,0 °C Ambient at Space Min Temp ................................. 20,0 °C

7.2. 2nd Partition Details: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:05

Hourly Analysis Program v.4,3 Page 12 of 24

GR10-HALL 1. General Details: Floor Area ............................................................. 11,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage .............................. GENERAL: Corridor OA Requirement 1 .................................................. 0,0 L/s/person OA Requirement 2 ................................................ 0,30 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 20,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................... 0,0 Person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule .............................................................. None

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ................................................................. 5,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors: (No Wall, Window, Door data). 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 ACH Design Heating ...................................................... 0,00 ACH Energy Analysis .................................................... 0,00 ACH Infiltration occurs at all hours. 6. Floors: Type .................. Floor Above Unconditioned Space Floor Area ............................................................. 11,0 m² Total Floor U-Value ............................................. 1,950 W/(m²-°K) Unconditioned Space Max Temp. ......................... 30,0 °C Ambient at Space Max Temp. ............................... 24,0 °C Unconditioned Space Min Temp. .......................... 15,0 °C Ambient at Space Min Temp. ................................ 20,0 °C 7. Partitions: 7.1. 1st Partition Details: Partition Type ........................................ Wall Partition Area ....................................................................... 28,0 m² U-Value ............................................................... 2,000 W/(m²-°K) Uncondit. Space Max Temp .................................. 30,0 °C Ambient at Space Max Temp ................................ 24,0 °C Uncondit. Space Min Temp ................................... 15,0 °C Ambient at Space Min Temp ................................. 20,0 °C

7.2. 2nd Partition Details: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:05

Hourly Analysis Program v.4,3 Page 13 of 24

GR12-WC MALE 1. General Details: Floor Area ............................................................. 20,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage .......................................... User-Defined OA Requirement 1 .................................................. 0,0 L/s OA Requirement 2 .................................................. 0,0 L/s Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 15,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................... 3,0 People Activity Level ........................................ Seated at Rest Sensible ................................................................. 67,4 W/person Latent ..................................................................... 35,2 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 15,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

E 30,0 0 0 0 3.1. Construction Types for Exposure E Wall Type ................................................................... OW-03 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 ACH Design Heating ...................................................... 0,00 ACH Energy Analysis .................................................... 0,00 ACH Infiltration occurs at all hours. 6. Floors: Type .................. Floor Above Unconditioned Space Floor Area ............................................................. 20,0 m² Total Floor U-Value ............................................. 1,950 W/(m²-°K) Unconditioned Space Max Temp. ......................... 30,0 °C Ambient at Space Max Temp. ............................... 24,0 °C Unconditioned Space Min Temp. .......................... 15,0 °C Ambient at Space Min Temp. ................................ 20,0 °C 7. Partitions: 7.1. 1st Partition Details: Partition Type ........................................ Wall Partition Area ....................................................................... 35,0 m² U-Value ............................................................... 2,000 W/(m²-°K) Uncondit. Space Max Temp .................................. 30,0 °C Ambient at Space Max Temp ................................ 24,0 °C Uncondit. Space Min Temp ................................... 15,0 °C Ambient at Space Min Temp ................................. 20,0 °C

7.2. 2nd Partition Details: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:05

Hourly Analysis Program v.4,3 Page 14 of 24

GR13-WC FEMALE 1. General Details: Floor Area ............................................................. 16,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage .......................................... User-Defined OA Requirement 1 .................................................. 0,0 L/s OA Requirement 2 .................................................. 0,0 L/s Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 15,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................... 3,0 People Activity Level ........................................ Seated at Rest Sensible ................................................................. 67,4 W/person Latent ..................................................................... 35,2 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 15,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors: (No Wall, Window, Door data). 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 ACH Design Heating ...................................................... 0,00 ACH Energy Analysis .................................................... 0,00 ACH Infiltration occurs at all hours. 6. Floors: Type .................. Floor Above Unconditioned Space Floor Area ............................................................. 16,0 m² Total Floor U-Value ............................................. 1,950 W/(m²-°K) Unconditioned Space Max Temp. ......................... 30,0 °C Ambient at Space Max Temp. ............................... 24,0 °C Unconditioned Space Min Temp. .......................... 15,0 °C Ambient at Space Min Temp. ................................ 20,0 °C 7. Partitions: 7.1. 1st Partition Details: Partition Type ........................................ Wall Partition Area ....................................................................... 30,0 m² U-Value ............................................................... 2,000 W/(m²-°K) Uncondit. Space Max Temp .................................. 30,0 °C Ambient at Space Max Temp ................................ 24,0 °C Uncondit. Space Min Temp ................................... 15,0 °C Ambient at Space Min Temp ................................. 20,0 °C

7.2. 2nd Partition Details: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:05

Hourly Analysis Program v.4,3 Page 15 of 24

GR16-OFFICE 1. General Details: Floor Area ............................................................. 36,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ........................... OFFICE: Office space OA Requirement 1 .................................................. 2,5 L/s/person OA Requirement 2 ................................................ 0,30 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 25,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ........................................................... 10,00 m²/person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 35,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

E 26,5 0 0 0 3.1. Construction Types for Exposure E Wall Type ................................................................... OW-03 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type .................. Floor Above Unconditioned Space Floor Area ............................................................. 36,0 m² Total Floor U-Value ............................................. 1,950 W/(m²-°K) Unconditioned Space Max Temp. ......................... 24,0 °C Ambient at Space Max Temp. ............................... 30,0 °C Unconditioned Space Min Temp. .......................... 20,0 °C Ambient at Space Min Temp. ................................ 15,0 °C 7. Partitions: 7.1. 1st Partition Details: Partition Type ........................................ Wall Partition Area ....................................................................... 38,0 m² U-Value ............................................................... 2,000 W/(m²-°K) Uncondit. Space Max Temp .................................. 30,0 °C Ambient at Space Max Temp ................................ 24,0 °C Uncondit. Space Min Temp ................................... 15,0 °C Ambient at Space Min Temp ................................. 20,0 °C

7.2. 2nd Partition Details: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:05

Hourly Analysis Program v.4,3 Page 16 of 24

GR17-OFFICE 1. General Details: Floor Area ............................................................. 51,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ........................... OFFICE: Office space OA Requirement 1 .................................................. 2,5 L/s/person OA Requirement 2 ................................................ 0,30 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 25,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ........................................................... 10,00 m²/person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 35,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

E 40,0 0 0 0

S 22,0 0 0 0

S 13,0 0 0 0 3.1. Construction Types for Exposure E Wall Type ................................................................... OW-03 3.2. Construction Types for Exposure S Wall Type ................................................................... OW-03' 3.3. Construction Types for Exposure S Wall Type ................................................................... OW-04 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type .................. Floor Above Unconditioned Space Floor Area ............................................................. 51,0 m² Total Floor U-Value ............................................. 1,950 W/(m²-°K) Unconditioned Space Max Temp. ......................... 24,0 °C Ambient at Space Max Temp. ............................... 30,0 °C Unconditioned Space Min Temp. .......................... 20,0 °C Ambient at Space Min Temp. ................................ 15,0 °C 7. Partitions: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:05

Hourly Analysis Program v.4,3 Page 17 of 24

GR18-ENTRANCE HALL 1. General Details: Floor Area ............................................................. 61,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage .................. RETAIL: Mall common area OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,30 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 20,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................. 2,50 m²/person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ................................................................. 5,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

S 36,5 2 0 0 3.1. Construction Types for Exposure S Wall Type ................................................................... OW-05 1st Window Type ....................................... WIN-1.86x2.50 m 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 ACH Design Heating ...................................................... 0,00 ACH Energy Analysis .................................................... 0,00 ACH Infiltration occurs at all hours. 6. Floors: Type .................. Floor Above Unconditioned Space Floor Area ............................................................. 61,0 m² Total Floor U-Value ............................................. 1,950 W/(m²-°K) Unconditioned Space Max Temp. ......................... 30,0 °C Ambient at Space Max Temp. ............................... 24,0 °C Unconditioned Space Min Temp. .......................... 15,0 °C Ambient at Space Min Temp. ................................ 20,0 °C 7. Partitions: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:05

Hourly Analysis Program v.4,3 Page 18 of 24

GR19-MALL HALL 1. General Details: Floor Area ........................................................... 140,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage .................. RETAIL: Mall common area OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,30 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 20,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................. 2,50 m²/person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ................................................................. 5,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

S 18,5 0 0 0

WSW 80,0 1 0 0 3.1. Construction Types for Exposure S Wall Type ................................................................... OW-04 3.2. Construction Types for Exposure WSW Wall Type ................................................................... OW-04 1st Window Type ....................................... WIN-6.72x2.85 m 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 ACH Design Heating ...................................................... 0,00 ACH Energy Analysis .................................................... 0,00 ACH Infiltration occurs at all hours. 6. Floors: Type .................. Floor Above Unconditioned Space Floor Area ........................................................... 140,0 m² Total Floor U-Value ............................................. 1,950 W/(m²-°K) Unconditioned Space Max Temp. ......................... 30,0 °C Ambient at Space Max Temp. ............................... 24,0 °C Unconditioned Space Min Temp. .......................... 15,0 °C Ambient at Space Min Temp. ................................ 20,0 °C 7. Partitions: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:05

Hourly Analysis Program v.4,3 Page 19 of 24

GR21-SHOP 1. General Details: Floor Area ............................................................. 56,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ........................................ RETAIL: Sales OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,60 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 90,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................. 6,67 m²/person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 15,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

WSW 85,0 2 0 0 3.1. Construction Types for Exposure WSW Wall Type ................................................................... OW-03 1st Window Type ....................................... WIN-6.72x2.85 m 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type .................. Floor Above Unconditioned Space Floor Area ............................................................. 56,0 m² Total Floor U-Value ............................................. 1,950 W/(m²-°K) Unconditioned Space Max Temp. ......................... 30,0 °C Ambient at Space Max Temp. ............................... 24,0 °C Unconditioned Space Min Temp. .......................... 15,0 °C Ambient at Space Min Temp. ................................ 20,0 °C 7. Partitions: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:05

Hourly Analysis Program v.4,3 Page 20 of 24

GR24-SHOP 1. General Details: Floor Area ............................................................... 5,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ........................................ RETAIL: Sales OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,60 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 90,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................... 2,0 People Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 15,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors: (No Wall, Window, Door data). 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type .................. Floor Above Unconditioned Space Floor Area ............................................................... 5,0 m² Total Floor U-Value ............................................. 1,950 W/(m²-°K) Unconditioned Space Max Temp. ......................... 30,0 °C Ambient at Space Max Temp. ............................... 24,0 °C Unconditioned Space Min Temp. .......................... 15,0 °C Ambient at Space Min Temp. ................................ 20,0 °C 7. Partitions: 7.1. 1st Partition Details: Partition Type ........................................ Wall Partition Area ....................................................................... 15,0 m² U-Value ............................................................... 2,000 W/(m²-°K) Uncondit. Space Max Temp .................................. 30,0 °C Ambient at Space Max Temp ................................ 24,0 °C Uncondit. Space Min Temp ................................... 15,0 °C Ambient at Space Min Temp ................................. 20,0 °C

7.2. 2nd Partition Details: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:05

Hourly Analysis Program v.4,3 Page 21 of 24

GR25-SHOP 1. General Details: Floor Area ............................................................. 56,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ........................................ RETAIL: Sales OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,60 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 90,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................. 6,67 m²/person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 15,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

W 35,0 0 0 0 3.1. Construction Types for Exposure W Wall Type ................................................................... OW-03 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type .................. Floor Above Unconditioned Space Floor Area ............................................................. 56,0 m² Total Floor U-Value ............................................. 1,950 W/(m²-°K) Unconditioned Space Max Temp. ......................... 30,0 °C Ambient at Space Max Temp. ............................... 24,0 °C Unconditioned Space Min Temp. .......................... 15,0 °C Ambient at Space Min Temp. ................................ 20,0 °C 7. Partitions: 7.1. 1st Partition Details: Partition Type ........................................ Wall Partition Area ....................................................................... 30,0 m² U-Value ............................................................... 2,000 W/(m²-°K) Uncondit. Space Max Temp .................................. 30,0 °C Ambient at Space Max Temp ................................ 24,0 °C Uncondit. Space Min Temp ................................... 15,0 °C Ambient at Space Min Temp ................................. 20,0 °C

7.2. 2nd Partition Details: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:05

Hourly Analysis Program v.4,3 Page 22 of 24

GR26-SHOP 1. General Details: Floor Area ............................................................. 55,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ........................................ RETAIL: Sales OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,60 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 90,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................. 6,67 m²/person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 15,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

W 40,0 0 0 0 3.1. Construction Types for Exposure W Wall Type ................................................................... OW-03 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type .................. Floor Above Unconditioned Space Floor Area ............................................................. 55,0 m² Total Floor U-Value ............................................. 1,950 W/(m²-°K) Unconditioned Space Max Temp. ......................... 30,0 °C Ambient at Space Max Temp. ............................... 24,0 °C Unconditioned Space Min Temp. .......................... 15,0 °C Ambient at Space Min Temp. ................................ 20,0 °C 7. Partitions: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:05

Hourly Analysis Program v.4,3 Page 23 of 24

GR27-SHOP 1. General Details: Floor Area ............................................................. 23,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ........................................ RETAIL: Sales OA Requirement 1 .................................................. 3,8 L/s/person OA Requirement 2 ................................................ 0,60 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 90,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................. 6,67 m²/person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule ................................................... Occupancy

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ............................................................... 15,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

W 20,0 0 0 0 3.1. Construction Types for Exposure W Wall Type ................................................................... OW-03 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 L/s Design Heating ...................................................... 0,00 L/s Energy Analysis .................................................... 0,00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type .................. Floor Above Unconditioned Space Floor Area ............................................................. 23,0 m² Total Floor U-Value ............................................. 1,950 W/(m²-°K) Unconditioned Space Max Temp. ......................... 30,0 °C Ambient at Space Max Temp. ............................... 24,0 °C Unconditioned Space Min Temp. .......................... 15,0 °C Ambient at Space Min Temp. ................................ 20,0 °C 7. Partitions: (No partition data).

Space Input Data BAGHDAD MALL 11.22.2012 02:05

Hourly Analysis Program v.4,3 Page 24 of 24

GR29-HALL 1. General Details: Floor Area ............................................................. 14,0 m² Avg. Ceiling Height .................................................. 5,0 m Building Weight ................................................... 341,8 kg/m² 1.1. OA Ventilation Requirements: Space Usage .............................. GENERAL: Corridor OA Requirement 1 .................................................. 0,0 L/s/person OA Requirement 2 ................................................ 0,30 L/(s-m²) Space Usage Defaults .......... ASHRAE Std 62.1-2004 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 20,00 W/m² Ballast Multiplier .................................................... 1,00 Schedule ..................................................... Electricity

2.4. People: Occupancy ............................................................... 0,0 Person Activity Level ............................................. Office Work Sensible ................................................................. 71,8 W/person Latent ..................................................................... 60,1 W/person Schedule .............................................................. None

2.2. Task Lighting: Wattage ................................................................. 0,00 W/m² Schedule ............................................................. None

2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None

2.3. Electrical Equipment: Wattage ................................................................. 5,00 W/m² Schedule ..................................................... Electricity 3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.

W 12,5 0 0 0 3.1. Construction Types for Exposure W Wall Type ................................................................... OW-03 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0,00 ACH Design Heating ...................................................... 0,00 ACH Energy Analysis .................................................... 0,00 ACH Infiltration occurs at all hours. 6. Floors: Type .................. Floor Above Unconditioned Space Floor Area ............................................................. 14,0 m² Total Floor U-Value ............................................. 1,950 W/(m²-°K) Unconditioned Space Max Temp. ......................... 30,0 °C Ambient at Space Max Temp. ............................... 24,0 °C Unconditioned Space Min Temp. .......................... 15,0 °C Ambient at Space Min Temp. ................................ 20,0 °C 7. Partitions: 7.1. 1st Partition Details: Partition Type ........................................ Wall Partition Area ....................................................................... 60,0 m² U-Value ............................................................... 2,000 W/(m²-°K) Uncondit. Space Max Temp .................................. 30,0 °C Ambient at Space Max Temp ................................ 24,0 °C Uncondit. Space Min Temp ................................... 15,0 °C Ambient at Space Min Temp ................................. 20,0 °C

7.2. 2nd Partition Details: (No partition data).

Door Constructions BAGHDAD MALL 11.22.2012 02:04

Hourly Analysis Program v.4,3 Page 1 of 1

D5 Service Door Door Details: Gross Area .............................................................. 2,2 m² Door U-Value ...................................................... 4,000 W/(m²-°K) Glass Details: Glass Area .............................................................. 0,0 m² Glass U-Value ..................................................... 3,293 W/(m²-°K) Glass Shade Coefficient ...................................... 0,880 Glass Shaded All Day? ....................................... Hayir

Window Constructions BAGHDAD MALL 11.22.2012 02:04

Hourly Analysis Program v.4,3 Page 1 of 3

SKYLIGHT Window Details: Detailed Input ........................................................ Evet Height .................................................................... 1,00 m Width ..................................................................... 1,00 m Frame Type .............. Aluminum with thermal breaks Internal Shade Type ............................................ None Overall U-Value ................................................... 3,344 W/(m²-°K) Overall Shade Coefficient ................................... 0,751 Glass Details: Gap Type ........................................ 13 mm Air Space

Glazing Glass Type Transmissivity Reflectivity Absorptivity

Outer Glazing 6mm clear 0,792 0,079 0,129

Glazing #2 6mm clear 0,792 0,079 0,129

Glazing #3 not used 1,000 0,000 0,000 WIN-1.00X1.50m Window Details: Detailed Input ........................................................ Evet Height .................................................................... 1,50 m Width ..................................................................... 1,00 m Frame Type .............. Aluminum with thermal breaks Internal Shade Type ......... Venetian Blinds - Medium Overall U-Value ................................................... 2,827 W/(m²-°K) Overall Shade Coefficient ................................... 0,576 Glass Details: Gap Type ........................................ 13 mm Air Space

Glazing Glass Type Transmissivity Reflectivity Absorptivity

Outer Glazing 6mm clear 0,792 0,079 0,129

Glazing #2 6mm clear 0,792 0,079 0,129

Glazing #3 not used 1,000 0,000 0,000 WIN-1.00X3.80 m Window Details: Detailed Input ........................................................ Evet Height .................................................................... 3,80 m Width ..................................................................... 1,00 m Frame Type .............. Aluminum with thermal breaks Internal Shade Type ............................................ None Overall U-Value ................................................... 3,300 W/(m²-°K) Overall Shade Coefficient ................................... 0,751 Glass Details: Gap Type ........................................ 13 mm Air Space

Glazing Glass Type Transmissivity Reflectivity Absorptivity

Outer Glazing 6mm clear 0,792 0,079 0,129

Glazing #2 6mm clear 0,792 0,079 0,129

Glazing #3 not used 1,000 0,000 0,000

Window Constructions BAGHDAD MALL 11.22.2012 02:04

Hourly Analysis Program v.4,3 Page 2 of 3

WIN-1.74x2.20 m Window Details: Detailed Input ........................................................ Evet Height .................................................................... 2,20 m Width ..................................................................... 1,74 m Frame Type .............. Aluminum with thermal breaks Internal Shade Type ............................................ None Overall U-Value ................................................... 3,281 W/(m²-°K) Overall Shade Coefficient ................................... 0,751 Glass Details: Gap Type ........................................ 13 mm Air Space

Glazing Glass Type Transmissivity Reflectivity Absorptivity

Outer Glazing 6mm clear 0,792 0,079 0,129

Glazing #2 6mm clear 0,792 0,079 0,129

Glazing #3 not used 1,000 0,000 0,000 WIN-1.86x2.50 m Window Details: Detailed Input ........................................................ Evet Height .................................................................... 2,50 m Width ..................................................................... 1,86 m Frame Type .............. Aluminum with thermal breaks Internal Shade Type ............................................ None Overall U-Value ................................................... 3,274 W/(m²-°K) Overall Shade Coefficient ................................... 0,751 Glass Details: Gap Type ........................................ 13 mm Air Space

Glazing Glass Type Transmissivity Reflectivity Absorptivity

Outer Glazing 6mm clear 0,792 0,079 0,129

Glazing #2 6mm clear 0,792 0,079 0,129

Glazing #3 not used 1,000 0,000 0,000 WIN-20.0x12.5 m Window Details: Detailed Input ...................................................... Hayir Height .................................................................. 12,50 m Width ................................................................... 20,00 m Overall U-Value ................................................... 1,100 W/(m²-°K) Overall Shade Coefficient ................................... 0,280 WIN-20.0x14.5 m Window Details: Detailed Input ...................................................... Hayir Height .................................................................. 14,50 m Width ................................................................... 20,00 m Overall U-Value ................................................... 1,100 W/(m²-°K) Overall Shade Coefficient ................................... 0,280

Window Constructions BAGHDAD MALL 11.22.2012 02:04

Hourly Analysis Program v.4,3 Page 3 of 3

WIN-6.72x2.85 m Window Details: Detailed Input ........................................................ Evet Height .................................................................... 2,85 m Width ..................................................................... 6,72 m Frame Type .............. Aluminum with thermal breaks Internal Shade Type ......... Venetian Blinds - Medium Overall U-Value ................................................... 2,770 W/(m²-°K) Overall Shade Coefficient ................................... 0,576 Glass Details: Gap Type ........................................ 13 mm Air Space

Glazing Glass Type Transmissivity Reflectivity Absorptivity

Outer Glazing 6mm clear 0,792 0,079 0,129

Glazing #2 6mm clear 0,792 0,079 0,129

Glazing #3 not used 1,000 0,000 0,000

Roof Constructions BAGHDAD MALL 11.22.2012 02:04

Hourly Analysis Program v.4,3 Page 1 of 1

Roof Roof Details Outside Surface Color .......................................... Dark Absorptivity .......................................................... 0,900 Overall U-Value ................................................... 0,545 W/(m²-°K) Roof Layers Details (Inside to Outside)

Thickness Density Specific Ht. R-Value Weight Layers mm kg/m³ kJ / (kg - °K) (m²-°K)/W kg/m² Inside surface resistance 0,000 0,0 0,00 0,13000 0,0 Stucco 50,000 1858,1 0,84 0,03600 92,9 XPS insulation 60,000 16,0 0,84 1,50000 1,0 220mm HW concrete 220,000 2242,6 0,84 0,10450 493,4 Stucco 20,000 1858,1 0,84 0,02300 37,2 Outside surface resistance 0,000 0,0 0,00 0,04000 0,0

Totals 350,000 - 1,83350 624,4

Wall Constructions BAGHDAD MALL 11.22.2012 02:03

Hourly Analysis Program v.4,3 Page 1 of 2

OW-01 Wall Details Outside Surface Color ......................................... Light Absorptivity .......................................................... 0,450 Overall U-Value ................................................... 0,854 W/(m²-°K) Wall Layers Details (Inside to Outside)

Thickness Density Specific Ht. R-Value Weight Layers mm kg/m³ kJ / (kg - °K) (m²-°K)/W kg/m² Inside surface resistance 0,000 0,0 0,00 0,13000 0,0 Rockwool 40,000 16,0 0,92 1,00000 0,6 Steel deck 20,000 7833,0 0,50 0,00044 156,7 Outside surface resistance 0,000 0,0 0,00 0,04000 0,0

Totals 60,000 - 1,17044 157,3 OW-02 Wall Details Outside Surface Color ......................................... Light Absorptivity .......................................................... 0,450 Overall U-Value ................................................... 0,266 W/(m²-°K) Wall Layers Details (Inside to Outside)

Thickness Density Specific Ht. R-Value Weight Layers mm kg/m³ kJ / (kg - °K) (m²-°K)/W kg/m² Inside surface resistance 0,000 0,0 0,00 0,13000 0,0 25mm stucco 25,400 1858,1 0,84 0,03519 47,2 200mm LW concrete block 200,000 608,7 0,84 1,05260 121,7 Air space 100,000 0,0 0,00 0,16026 0,0 200 mm LW concrete block 200,000 608,7 0,84 1,05260 121,7 XPS insulation 50,000 16,0 0,92 1,25000 0,8 25mm stucco 25,400 1858,1 0,84 0,03519 47,2 Outside surface resistance 0,000 0,0 0,00 0,04000 0,0

Totals 600,800 - 3,75585 338,7 OW-03 Wall Details Outside Surface Color ......................................... Light Absorptivity .......................................................... 0,450 Overall U-Value ................................................... 0,394 W/(m²-°K) Wall Layers Details (Inside to Outside)

Thickness Density Specific Ht. R-Value Weight Layers mm kg/m³ kJ / (kg - °K) (m²-°K)/W kg/m² Inside surface resistance 0,000 0,0 0,00 0,13000 0,0 25mm stucco 25,400 1858,1 0,84 0,03519 47,2 200 mm LW concrete block 200,000 608,7 0,84 1,05260 121,7 XPS insulation 50,000 16,0 0,92 1,25000 0,8 20mm stucco 20,000 1858,1 0,84 0,02771 37,2 Outside surface resistance 0,000 0,0 0,00 0,04000 0,0

Totals 295,400 - 2,53550 206,9

Wall Constructions BAGHDAD MALL 11.22.2012 02:03

Hourly Analysis Program v.4,3 Page 2 of 2

OW-03' Wall Details Outside Surface Color ......................................... Light Absorptivity .......................................................... 0,450 Overall U-Value ................................................... 0,394 W/(m²-°K) Wall Layers Details (Inside to Outside)

Thickness Density Specific Ht. R-Value Weight Layers mm kg/m³ kJ / (kg - °K) (m²-°K)/W kg/m² Inside surface resistance 0,000 0,0 0,00 0,13000 0,0 25mm stucco 25,400 1858,1 0,84 0,03519 47,2 200 mm LW concrete block 200,000 608,7 0,84 1,05260 121,7 XPS insulation 50,000 16,0 0,92 1,25000 0,8 20mm stucco 20,000 1858,1 0,84 0,02771 37,2 Outside surface resistance 0,000 0,0 0,00 0,04000 0,0

Totals 295,400 - 2,53550 206,9 OW-04 Wall Details Outside Surface Color ......................................... Light Absorptivity .......................................................... 0,450 Overall U-Value ................................................... 0,598 W/(m²-°K) Wall Layers Details (Inside to Outside)

Thickness Density Specific Ht. R-Value Weight Layers mm kg/m³ kJ / (kg - °K) (m²-°K)/W kg/m² Inside surface resistance 0,000 0,0 0,00 0,13000 0,0 25mm stucco 25,000 1858,1 0,84 0,03464 46,5 400mm HW concrete 400,000 2242,6 0,84 0,19050 897,0 XPS insulation 50,000 16,0 0,92 1,25000 0,8 20mm stucco 20,000 1858,1 0,84 0,02771 37,2 Outside surface resistance 0,000 0,0 0,00 0,04000 0,0

Totals 495,000 - 1,67285 981,5 OW-05 Wall Details Outside Surface Color ......................................... Light Absorptivity .......................................................... 0,450 Overall U-Value ................................................... 0,375 W/(m²-°K) Wall Layers Details (Inside to Outside)

Thickness Density Specific Ht. R-Value Weight Layers mm kg/m³ kJ / (kg - °K) (m²-°K)/W kg/m² Inside surface resistance 0,000 0,0 0,00 0,13000 0,0 XPS insulation 50,000 16,0 0,92 1,25000 0,8 fiber cement board 20,000 800,9 1,09 0,12426 16,0 Rockwool 40,000 16,0 0,84 1,00000 0,6 fiber cement board 20,000 800,9 1,09 0,12426 16,0 Outside surface resistance 0,000 0,0 0,00 0,04000 0,0

Totals 130,000 - 2,66851 33,5

Design Weather Parameters & MSHGs BAGHDAD MALL 11.22.2012 02:02

Hourly Analysis Program v.4,3 Page 1 of 1

Design Parameters: City Name ........................................................................................................ Baghdad Location .................................................................................................................... Iraq Latitude ..................................................................................................................... 33,3 Deg. Longitude ................................................................................................................. -44,6 Deg. Elevation ................................................................................................................... 33,8 m Summer Design Dry-Bulb ......................................................................................... 45,0 °C Summer Coincident Wet-Bulb .................................................................................. 22,8 °C Summer Daily Range ............................................................................................... 18,9 °K Winter Design Dry-Bulb .............................................................................................. 0,0 °C Winter Design Wet-Bulb ............................................................................................ -2,8 °C Atmospheric Clearness Number ............................................................................... 1,00 Average Ground Reflectance ................................................................................... 0,20 Soil Conductivity ..................................................................................................... 1,385 W/(m-°K) Local Time Zone (GMT +/- N hours) .......................................................................... -3,0 hours Consider Daylight Savings Time ............................................................................ Hayir Simulation Weather Data .................................................................................. noneN/A Current Data is ..................................................................... 1993 ASHRAE Handbook Design Cooling Months .............................................................. January to December Design Day Maximum Solar Heat Gains (The MSHG values are expressed in W/m² )

Month N NNE NE ENE E ESE SE SSE SJanuary 72,1 72,1 74,6 329,2 531,6 709,3 785,3 796,5 781,8February 84,6 84,6 188,0 456,8 650,5 749,4 787,8 743,4 706,7March 97,8 103,5 356,0 549,4 710,1 761,8 718,6 627,0 568,4April 110,7 226,2 472,3 633,4 697,6 695,9 592,9 454,4 377,9May 119,8 332,2 537,3 663,5 690,2 630,0 498,0 326,2 247,2June 155,4 366,0 558,8 665,5 672,5 599,3 451,3 272,4 202,9July 123,1 335,1 533,4 648,2 666,4 619,2 480,6 316,0 241,4August 116,0 233,6 460,3 607,3 677,5 672,4 569,7 440,3 366,1September 101,2 101,2 335,8 530,8 665,8 729,0 684,7 603,8 552,7October 87,1 87,1 204,2 424,8 619,9 737,3 754,2 715,9 686,7November 73,1 73,1 86,3 307,4 542,4 685,3 778,4 784,6 770,1December 66,1 66,1 66,1 272,5 489,2 672,8 773,0 802,7 791,4Month SSW SW WSW W WNW NW NNW HOR MultJanuary 796,2 790,9 700,5 552,2 309,3 87,7 72,1 532,4 1,00February 736,3 777,2 765,5 640,1 449,3 209,8 84,6 664,5 1,00March 620,8 714,0 761,8 692,2 568,9 354,1 97,8 777,6 1,00April 454,1 593,4 695,6 698,6 633,7 472,1 226,9 838,9 1,00May 324,8 496,7 631,8 687,3 663,0 538,9 328,3 862,8 1,00June 274,4 452,8 596,2 676,3 665,9 556,2 368,7 863,3 1,00July 317,7 485,9 612,7 677,9 651,5 528,3 335,5 853,2 1,00August 438,5 572,8 670,3 674,4 612,8 459,1 226,3 823,8 1,00September 607,7 691,3 726,8 675,1 521,1 333,7 101,2 750,7 1,00October 721,2 761,3 723,9 624,4 439,7 179,8 87,1 651,8 1,00November 784,4 772,4 697,1 522,2 323,8 74,7 73,1 528,9 1,00December 802,8 773,6 672,0 490,8 272,0 66,1 66,1 469,8 1,00

Mult. = User-defined solar multiplier factor.

HEATING&COOLING SYSTEM CIRCULATION PUMPS

BOILER CIRCULATION PUMP [CP‐01&02]Boiler capacity : 445 kW

Water Inlet temp. : 60 oC

Water Outlet temp. : 80 oCQuantity : 1 duty+ 1 standby pumpFlow : 19 1 m3/hFlow : 19,1 m3/hHead : 40 kPaPower : 0,4 kW

CHILLER CIRCULATION PUMPS [CP‐03&04, CP‐05&06]Chiller capacity : 850 kW

Water Inlet temp. : 12 oCp

Water Outlet temp. : 7 oCQuantity : 1 duty+ 1 standby pump per chillerFlow : 146,2 m3/hHead : 150 kPaPower : 11 kW

FCU CIRCULATION PUMPS [CP‐07,08,09]Total FCU capacity : 584 kW

Water Inlet temp. : 12 oC

Water Outlet temp. : 7 oCQuantity : 2 duty pumps+ 1 standby pumpFlow 50 2 m3/hFlow : 50,2 m3/hHead : 200 kPaPower : 5,5 kW

AHU  HEATING CIRCULATION PUMPS [CP‐10&11]Total FCU capacity : 389 kWTotal FCU capacity : 389 kW

Water Inlet temp. : 60 oC

Water Outlet temp. : 80 oCQuantity : 1 duty pumps+ 1 standby pumpFlow : 16,7 m3/hHead : 170 kPaPower : 5,5 kW

AHU  COOLING CIRCULATION PUMPS [CP‐12,13,14,15,16]Total FCU capacity : 1102 kW

Water Inlet temp : 12 oCWater Inlet temp. : 12 C

Water Outlet temp. : 7 oCQuantity : 4 duty pumps+ 1 standby pumpFlow : 47,4 m3/hHead : 180 kPaPower : 5,5 kW

OIL TANK HEAT EXCAHNGER CIRCULATION PUMPS [CP‐17&18]Total FCU capacity : 1 kW

Water Inlet temp. : 60 oC

Water Outlet temp. : 80 oCQuantity : 1 duty pumps+ 1 standby pumpFlow : 0,043 M3/hHead : 80 kPaPower : 0,1 kW

HEATING SYSTEM EXPANSION VESSELS SIZING

BOILER EXPANSION VESSEL [EV-01]

BOILER WATER CAPACITY 174 L

WATER VOLUME IN PIPES 131 lt

TOTAL 305 lt

Sytem Water Volume Va = 305 lt

Expansion factor of water heated from 10oC to 80oC n = 2,86

Safety valve set point psv = 2,5 bar

Static pressure pst = 0,3 bar

Min. operating pressure po = pst + 0,2 = 0,5 bar

Max. operating pressure pe = psv - 0,5 = 2 bar

Expanded water volume Ve=(Va*n)/100 = 8,71 L

V (V *0 )/100min water volume in vessel Vv=(Va*0,5)/100 = 1,52 L

Vessel volume V = Ve + Vv = 10,23 L

Pressure factor Df = ((pe+1)-(po+1))/(pe+1) = 0,500

Nominal Vessel Volume Vn = V / Df = 20,46 L

Selected Vessel Vn = 50 L

SECONDARY HEATING SYSTEM EXPANSION VESSEL [EV-02]

FCU SYSTEM WATER CONTENT 56 x 7 L/kW 392 L

AHU SYSTEM WATER CONTENT 389 x 7 L/kW 2.723 L

TOTAL 3.115 L

Sytem Water Content Va = 3.115 lt

Expansion factor of water heated from 10oC to 80oC n = 2,86

Safety valve set point psv = 2,5 bar

Static pressure pst = 0,3 bar

Min. operating pressure po = pst + 0,2 = 0,5 bar

Max. operating pressure pe = psv - 0,5 = 2 bar

Expanded water volume Ve=(Va*n)/100 = 89,09 L

min water volume in vessel Vv=(Va*0,5)/100 = 15,58 L

Vessel volume V = Ve + Vv = 104,66 L

Pressure factor Df = ((pe+1)-(po+1))/(pe+1) = 0,500

Nominal Vessel Volume Vn = V / Df = 209,33 L

Selected Vessel Vn = 300 L

COOLING SYSTEM CONTRACTION VESSELS SIZING

CHILLER CONRACTION VESSEL [EV-03&EV-04]

CHILLER WATER CAPACITY 251 L

WATER VOLUME IN PIPES 1.020 lt

TOTAL 1.271 L

Sytem Water Content Va = 1.271 lt

Expansion factor of water heated from 10oC to 40oC n = 0,79

Safety valve set point psv = 2,5 bar

Static pressure pst = 0,3 bar

Min. operating pressure po = pst + 0,2 = 0,5 bar

Max. operating pressure pe = psv - 0,5 = 2 bar

Expanded water volume Ve=(Va*n)/100 = 10,04 L

V (V *0 )/100min water volume in vessel Vv=(Va*0,5)/100 = 6,36 L

Vessel volume V = Ve + Vv = 16,40 L

Pressure factor Df = ((pe+1)-(po+1))/(pe+1) = 0,500

Nominal Vessel Volume Vn = V / Df = 32,79 L

Selected Vessel Vn = 50 L

SECONDARY HEATING SYSTEM EXPANSION VESSEL [EV-05]

FCU SYSTEM WATER CONTENT 584 x 7 L/kW 4.088 L

AHU SYSTEM WATER CONTENT 1.102 x 7 L/kW 7.714 L

TOTAL 11.802 L

Sytem Water Content Va = 11.802 lt

Expansion factor of water heated from 10oC to 80oC n = 0,79

Safety valve set point psv = 2,5 bar

Static pressure pst = 0,3 bar

Min. operating pressure po = pst + 0,2 = 0,5 bar

Max. operating pressure pe = psv - 0,5 = 2 bar

Expanded water volume Ve=(Va*n)/100 = 93,24 L

min water volume in vessel Vv=(Va*0,5)/100 = 59,01 L

Vessel volume V = Ve + Vv = 152,25 L

Pressure factor Df = ((pe+1)-(po+1))/(pe+1) = 0,500

Nominal Vessel Volume Vn = V / Df = 304,49 L

Selected Vessel Vn = 500 L

BOILER CAPACITY CALCULATION:

TOTAL FCU HEATING LOAD : 56,3 kW

TOTAL ALL AIR AHU HEATING COIL LOAD : 142 kW

TOTAL FRESH AIR AHU HEAT. COIL LOAD: + 247,1 kW

445,4 kW

Selected Boiler Specifications [CB-01]

Type : Cast Iron Sectional Boiler

Quantity : 1 unit

Heating Capacity : 445 kW @ 80 C Water Outlet Temperature

Working Pressure : 6 bar

Pressure Drop Flue Gas Side : 2.40 mbar

Oil Burner Capacity [BR-01]

Qburner = Qboiler /ηboiler

Qboiler= kW

ηboiler =Qburner= kW

Vburner= 50,1 kg/h fuel-oil = 55 l/h fuel/oilP min= 3 mbar

445

484

0,92

CHILLER CAPACITY CALCULATION:

TOTAL FCU COOLING LOAD : 584,0 kW

TOTAL ALL AIR AHU COOLING COIL LOAD : 854,0 kW

TOTAL FRESH AIR AHU COOL. COIL LOAD: + 248,0 kW

1.686,0 kW

Selected Chiller Specifications [CH-01&CH-02]

Type : Air cooled Chiller with Screw Compressors

Quantity : 2 units

Cooling Capacity : 850 kW

Evaporator Water Temperatures : 7/12 C

Outdoor Air Temperature : 45 C

Refrigerant : R134A

Power Input : 330 kW

ReferenceHeating Capacity

[W]

Sensible Cooling Capacity[W]

Total Cooling Capacity[W]

Air Flow[m3/h]

Sound Pressure[NR]

FC1 3.010 1.920 2.260 455 29FC2 3.960 2.530 3.080 580 28FC3 3.870 3.070 3.710 690 29FC4 4.940 4.640 5.480 1070 31FC5 10.600 6.930 8.100 1700 39FC6 12.700 8.880 10.100 2225 36

ReferenceHeating Capacity

[kW]

Sensible Cooling Capacity[kW]

Total Cooling Capacity[kW]

Air Flow[m3/h]

VRV 1 2,5 1,8 2,2 540

VRV 2 3,1 2,1 2,8 570

VRV 3 4 2,8 3,5 690

VRV 4 4,9 3,7 4,4 900

VRV 5 6,2 4,4 5,5 1260

VRV 6 7,9 5,3 7,1 1620

VRV 7 9,9 7,2 8,8 1680

VRV 8 12,4 9,3 11,1 2280

2‐PIPE FAN‐COIL UNITS SCHEDULE

The given values are calculated with the following conditions:Medium speed air flow, 40 Pa fan external pressure,24/17 C DB/WB design temperatures, 7/12 C water inlet/outlet temperatures in summer,20 C DB/WB design temperature, 55/35 C water inlet/outlet temperatures in winter.

VRV INDOOR UNITS SCHEDULE

The given values are calculated with the following conditions:Medium speed air flow, 40 Pa fan external pressure,24/17 C DB/WB design temperatures, 45 C outdoor temperature in summer,20 C DB/WB design temperature, 0 C outdoor temperature in winter.

222-SHOP 70 20 24 50% 410 8783 662 9445 2P‐FCU 223-SHOP 55 20 24 50% 410 6959 520 7479 2P‐FCU 224-SHOP 48 20 24 50% 1009 6704 454 7158 2P‐FCU 226-HALL 14 20 24 50% 778 1083 0 1083 ALL‐AIR AHU 227-SHOP 53 20 24 50% 913 7228 501 7729 2P‐FCU 228-CAFE 71 20 24 50% 564 9129 2624 11753 2P‐FCU 229-KIOSK 16 20 24 50% 0 1990 189 2179 ALL‐AIR AHU 230-KIOSK 5 20 24 50% 0 702 126 828 ALL‐AIR AHU 231-KIOSK 5 20 24 50% 0 702 126 828 ALL‐AIR AHU 232-SHOP 13 20 24 50% 130 1706 123 1829 2P‐FCU 301-FOOD COURT 670 20 24 50% 7396 53282 16912 70194 ALL‐AIR AHU 302-KIOSK 5 20 24 50% 0 702 126 828 ALL‐AIR AHU 303-RESTAURANT 120 20 24 50% 2522 14131 2957 17088 2P‐FCU 304-CAFE 34 20 24 50% 892 4917 1257 6174 2P‐FCU 305-CAFE 36 20 24 50% 892 5163 1331 6494 2P‐FCU 306-CAFE 34 20 24 50% 892 4917 1257 6174 2P‐FCU 307-CAFE 44 20 24 50% 892 6150 1626 7776 2P‐FCU 308-SHOP 43 20 24 50% 1020 6077 407 6484 2P‐FCU 309-SHOP 52 20 24 50% 1020 7171 492 7663 2P‐FCU 310-SHOP 36 20 24 50% 1547 5789 341 6130 2P‐FCU 311-HALL 11 20 24 50% 364 642 0 642 ALL‐AIR AHU 313-WC MALE 20 20 24 50% 763 1477 111 1588 ALL‐AIR AHU 314-WC FEMALE 16 20 24 50% 390 1094 111 1205 ALL‐AIR AHU 317-ENTERTAINMENT 364 20 24 50% 3643 42568 8969 51537 2P‐FCU 319-SHOP 39 20 24 50% 1025 5420 369 5789 2P‐FCU 320-SHOP 48 20 24 50% 410 6106 454 6560 2P‐FCU 321-SHOP 58 20 24 50% 410 7322 549 7871 2P‐FCU 322-RESTAURANT 62 20 24 50% 670 6706 1528 8234 2P‐FCU 324-PRIVATE RESTAURANT 70 20 24 50% 1159 7870 1725 9595 2P‐FCU 327-RESTAURANT 99 20 24 50% 1354 10950 2439 13389 2P‐FCU 329-SHOP 13 20 24 50% 130 1706 123 1829 2P‐FCU 401-PRIVATE RESTAURANT 424 20 24 50% 24320 75204 10447 85651 VRV 403-HALL 11 20 24 50% 520 793 0 793 ALL‐AIR AHU 405-WC MALE 20 20 24 50% 1046 1752 111 1863 ALL‐AIR AHU 406-WC FEMALE 16 20 24 50% 617 1315 111 1426 ALL‐AIR AHU 409-HALL 7 20 24 50% 215 393 0 393 ALL‐AIR AHU 410-OFFICE 360 20 24 50% 11119 40377 2272 42649 VRV 411-OFFICE HALL 189 20 24 50% 8025 14999 1193 16192 ALL‐AIR AHU 412-OFFICE 60 20 24 50% 2020 9337 379 9716 VRV 413-OFFICE 59 20 24 50% 2006 9266 379 9645 VRV 414-OFFICE 59 20 24 50% 2006 9266 379 9645 VRV 415-HALL 37 20 24 50% 3125 4245 0 4245 ALL‐AIR AHU 416-KITCHEN 153 20 28 55% 2901 38866 1246 40112 VRV

2 PIPE FAN COIL UNIT SELECTION2-PIPE FAN COIL UNIT SELECTION

Space Floor Heating Heating Sens Total

Reference & Name Area Sensible Latent Total Load FCU Reference Load Load Load

(m²) [W] [W] [W] [W] Adet (W) (W) (W)

GR03-SHOP 73 10028 691 10719 1335 2 FC5 668 5014 5360

GR04-SHOP 70 9626 662 10288 1297 2 FC5 649 4813 5144

GR05-SHOP 66 9091 624 9715 1247 2 FC4 624 4546 4858

GR06-SHOP 12 1606 114 1720 152 1 FC1 152 1606 1720

Cooling Load

Space Fan-coil unit

GR07-SHOP 8 1362 252 1614 230 1 FC1 230 1362 1614

GR21-SHOP 56 22143 530 22673 3947 3 FC6 1316 7381 7558 GR24-SHOP 5 952 126 1078 258 1 FC1 258 952 1078

GR25-SHOP 56 8113 530 8643 1459 2 FC4 730 4057 4322

GR26-SHOP 55 7635 520 8155 1107 2 FC4 554 3818 4078

GR27-SHOP 23 3215 218 3433 497 1 FC4 497 3215 3433

102-SHOP 60 7551 568 8119 410 2 FC4 205 3776 4060

103-SHOP 58 7308 549 7857 410 2 FC4 205 3654 3929

104-SHOP 47 5971 445 6416 410 2 FC3 205 2986 3208

105 SHOP 43 5485 407 5892 410 2 FC3 205 2743 2946 105-SHOP 43 5485 407 5892 410 2 FC3 205 2743 2946 106-SHOP 41 5242 388 5630 410 2 FC3 205 2621 2815

107-SHOP 52 6579 492 7071 410 2 FC4 205 3290 3536

108-SHOP 50 6336 473 6809 410 2 FC4 205 3168 3405

109-SHOP 60 7551 568 8119 410 2 FC4 205 3776 4060

110-SHOP 42 6022 397 6419 1036 2 FC3 518 3011 3210

117-DEPARTMENT STORE 364 33331 3444 36775 3643 10 FC4 364 3333 3678

119-SHOP 106 13564 1003 14567 1025 3 FC4 342 4521 4856

120-SHOP 30 3796 284 4080 226 1 FC4 226 3796 4080

121 SHOP 66 8294 624 8918 410 2 FC4 205 4147 4459 121-SHOP 66 8294 624 8918 410 2 FC4 205 4147 4459

122-SHOP 70 8783 662 9445 410 2 FC4 205 4392 4723

123-SHOP 55 6959 520 7479 410 2 FC4 205 3480 3740

124-SHOP 48 6704 454 7158 1009 2 FC4 505 3352 3579

127-SHOP 53 7228 501 7729 913 2 FC4 457 3614 3865

128-SHOP 68 8642 643 9285 564 2 FC4 282 4321 4643

135-SHOP 13 1706 123 1829 130 1 FC1 130 1706 1829

202-SHOP 68 8523 643 9166 410 2 FC4 205 4262 4583

203-SHOP 58 7308 549 7857 410 2 FC4 205 3654 3929

204-SHOP 47 5971 445 6416 410 2 FC3 205 2986 3208 204 SHOP 47 5971 445 6416 410 2 FC3 205 2986 3208

205-SHOP 47 5971 445 6416 410 2 FC3 205 2986 3208

206-SHOP 41 5242 388 5630 410 2 FC3 205 2621 2815

207-SHOP 52 6579 492 7071 410 2 FC4 205 3290 3536

208-SHOP 50 6336 473 6809 410 2 FC4 205 3168 3405

209-SHOP 59 7429 558 7987 410 2 FC4 205 3715 3994

210-SHOP 42 6022 397 6419 1036 2 FC3 518 3011 3210

217-DEPARTMENT STORE 364 33331 3444 36775 3643 10 FC4 364 3333 3678

219-SHOP 39 5420 369 5789 1025 1 FC5 1025 5420 5789

220-SHOP 52 6592 492 7084 410 2 FC4 205 3296 3542

221-SHOP 65 8172 615 8787 410 2 FC4 205 4086 4394

222-SHOP 70 8783 662 9445 410 2 FC4 205 4392 4723

223-SHOP 55 6959 520 7479 410 2 FC4 205 3480 3740

224-SHOP 48 6704 454 7158 1009 2 FC4 505 3352 3579

227-SHOP 53 7228 501 7729 913 2 FC4 457 3614 3865

228-CAFE 71 9129 2624 11753 564 2 FC4 282 4565 5877

232-SHOP 13 1706 123 1829 130 1 FC1 130 1706 1829

303-RESTAURANT 120 14131 2957 17088 2522 3 FC5 841 4710 5696

304-CAFE 34 4917 1257 6174 892 1 FC5 892 4917 6174

305-CAFE 36 5163 1331 6494 892 1 FC5 892 5163 6494

306-CAFE 34 4917 1257 6174 892 1 FC5 892 4917 6174

307-CAFE 44 6150 1626 7776 892 2 FC4 446 3075 3888

308-SHOP 43 6077 407 6484 1020 2 FC3 510 3039 3242

309-SHOP 52 7171 492 7663 1020 2 FC4 510 3586 3832

310-SHOP 36 5789 341 6130 1547 1 FC5 1547 5789 6130

317-ENTERTAINMENT 364 42568 8969 51537 3643 10 FC4 364 4257 5154

319-SHOP 39 5420 369 5789 1025 1 FC5 1025 5420 5789

320-SHOP 48 6106 454 6560 410 2 FC3 205 3053 3280

321-SHOP 58 7322 549 7871 410 2 FC4 205 3661 3936

322-RESTAURANT 62 6706 1528 8234 670 2 FC4 335 3353 4117

324-PRIVATE RESTAURANT 70 7870 1725 9595 1159 2 FC4 580 3935 4798

327-RESTAURANT 99 10950 2439 13389 1354 3 FC4 451 3650 44633 FC4 329-SHOP 13 1706 123 1829 130 1 FC1 130 1706 1829