basic lines-protection.ppt
TRANSCRIPT
-
8/20/2019 Basic Lines-Protection.ppt
1/31
Distance Relays
Introduction
1. The impedance relays also called distance relays areemployed to provide protection to transmission lines.
2. They are comparatively simple to apply, operate with
extremely high speed, and both primary and backupprotection features are inherent in them.
3. The impedance relay is made to respond to theimpedance between the relay location and the point
where fault is incident
4. The impedance is proportional to the distance to thefault, hence the name distance relay
-
8/20/2019 Basic Lines-Protection.ppt
2/31
!istance "elaying #rinciple
1. $ distance relay compares the currents and voltages at therelaying point with %urrent providing the operating tor&ue and thevoltage provides the restraining tor&ue. 'n other words animpedance relay is a voltage restrained overcurrent relay, also
%alled under impedance relay
2. (ince the operating characteristics of the relay depend upon theratio of voltage and current and the phase angle between them,their characteristics can be best represented on an ")*
diagram where both +' ratio and the phase angle can be plottedin terms of an impedance "-*.
-
8/20/2019 Basic Lines-Protection.ppt
3/31
Types of !istance "elays
1. 'mpedance relay
2. "eactance relay
3. /ho relay
4. /odified impedance relay
-
8/20/2019 Basic Lines-Protection.ppt
4/31
-
8/20/2019 Basic Lines-Protection.ppt
5/31
-
8/20/2019 Basic Lines-Protection.ppt
6/31
-
8/20/2019 Basic Lines-Protection.ppt
7/31
1. (ince the distance relays are fed from the secondaries of line %Ts andbus #Tsline %+Ts, the line parameters are to be converted intosecondary values to set the relay as per re&uirements
2. 0sec 0pri'mpedance ratio
where 'mpedance ratio #.T."atio%.T."atio
3. or the lines, the impedance in 5hms per 6/ is approximately asunder7)))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))6+ 01 02 8ine $ngle
)))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))132 6+ 9.4 :9 to;9!eg.229 6+ 9.4 ;9 to
-
8/20/2019 Basic Lines-Protection.ppt
8/31
-
8/20/2019 Basic Lines-Protection.ppt
9/31
0ones "eactance Time
)))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))
0one ) 1 of 08 instantaneous
0one ) 2 199> of 08 - 49)=9> of 0(8 9.3 to9.4sec
0one ) 3 199> of 08 - 129> of 0(8 9.:to9. of 08 - 129> of 088 9.? to1.=sec
)))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))where 08 #ositive se&uence impedance of line to be protected.
0(8 #ositive se&uence impedance of adacent shortest line.
088 #ositive se&uence impedance of adacent longest line
-
8/20/2019 Basic Lines-Protection.ppt
10/31
/ain eatures in !istance (cheme
1. (tarters.
2. /easuring units.
3. Timers
4. $uxiliary relays
-
8/20/2019 Basic Lines-Protection.ppt
11/31
Additional Features in distance schemes
1. #ower (wing blocking relay
2. +T fuse failure relay.
3. (witch onto fault relay
4. ault locator
=. $uto) reclosing scheme.
:. %arrier communication scheme
-
8/20/2019 Basic Lines-Protection.ppt
12/31
Factors affecting distance relay operation
1. ault resistance.
2. 'nfeed effect.
3. @ranching)off effect.
4. 8oad encroachment
-
8/20/2019 Basic Lines-Protection.ppt
13/31
eeder #rotection
1 5ver %urrent #rotectiona Time delayed non directional =1
b Time delayed directional :;
c 'nstantaneous =9
2 Around 5ver %urrent #rotection
a Time delayed non directional =1B
b Time delayed directional :;B
c 'nstantaneous =9B
-
8/20/2019 Basic Lines-Protection.ppt
14/31
Instantaneous (50) protection
C Dsed for detecting high magnitude fault current
C (ame time delay regardless of fault magnitude or distance
C %o)ordination with down stream section cannot be maintained.
-
8/20/2019 Basic Lines-Protection.ppt
15/31
#rotection for 3 #hase (ystem
a Three 5ver %urrent 5ne
Earth %urrent relayb Two 5ver %urrent 5ne Earth
%urrent relay
Ia
Ib
Ic
In=Ia+Ib+Ic
Ia
Ib
Ic
In=Ia+Ib+Ic
-
8/20/2019 Basic Lines-Protection.ppt
16/31
E 5% 5% 5%
Earth ault
E 5% 5%
-
8/20/2019 Basic Lines-Protection.ppt
17/31
E 5% 5%
#hase ault
5%E 5% 5%
-
8/20/2019 Basic Lines-Protection.ppt
18/31
!irectional #rotection
B d f !i i l % l
-
8/20/2019 Basic Lines-Protection.ppt
19/31
Beed for !irectional %ontrol
Aenerally re&uired if current can flow in both
directions through a relay locatione.g. #arallel feeder circuits
"ing /ain %ircuits
2.1 9.=9.? 9.11.31.;
B d f !i ti l % t l
-
8/20/2019 Basic Lines-Protection.ppt
20/31
Beed for !irectional %ontrol
Aenerally re&uired if current can flow in both
directions through a relay locatione.g. #arallel feeder circuits
"ing /ain %ircuits
rading has no! been lost "
2.1 9.=9.? 9.11.31.;
B d f !i ti l % t l
-
8/20/2019 Basic Lines-Protection.ppt
21/31
Beed for !irectional %ontrolAenerally re&uired if current can flow in both
directions through a relay locatione.g. #arallel feeder circuits
"ing /ain %ircuits
Relays operate for current flo! in direction indicated
(#ypical operating times sho!n)
9.? 9.19.= 9.?9.=9.1
"i / i %i it
-
8/20/2019 Basic Lines-Protection.ppt
22/31
"ing /ain %ircuitFith ring closed 7
@oth load and fault current may flow in either
direction along feeder circuits
Thus, directional relays are re&uired
Bote7 !irectional relays look into the feeder
Beed to establish setting philosophy
=1 :;
=1
8oad
:; :;
8oad
:;:; :;
8oad
"i / i %i it
-
8/20/2019 Basic Lines-Protection.ppt
23/31
"ing /ain %ircuit$rocedure %
&' pen ring at A
rade % A' *' D' ' ,'
-' pen ring at A'
rade % A , D *
#ypical operating times sho!n'
.ote % Relays ,/ / D/ * may be nondirectional'
1.39.1
9.1 9.?9.=
9.?
9.=
@
$
@
E E
$
1.;
!
!
1.;
1.3
% %
"i ( t ith T (
-
8/20/2019 Basic Lines-Protection.ppt
24/31
"ing (ystem with Two (ources
!iscrimination between all relays is not possible due to different re&uirements
under different ring operating conditions.
or 1 7) @G must operate before $G
or 2 7) @G must operate after $G
.ot
ompatible}
@ @ % %
! !
F&
@
F-
$
$
"i ( t ith T (
-
8/20/2019 Basic Lines-Protection.ppt
25/31
"ing (ystem with Two (ources
5ption 1
Trip least important source instantaneously then treat as normal ring main.5ption 2
it pilot wire protection to circuit $ ) @ and consider as common source
busbar.
$
@
5ption 15ption 15ption 1
5ption 2 5ption 2
=9
#F #F
# ll l d
-
8/20/2019 Basic Lines-Protection.ppt
26/31
#arallel eeders
Bon)!irectional "elays 7)
H%onventional AradingI 7)
Arade J$G with J%G
and Arade J@G with J!G
"elays J$G and J@G have
the same setting.
=1
=1
$
!
8oad
=1 @
=1 %
$ K @
% K !
ault level
at JG
5 p e r a t i n g T i m e
# ll l d
-
8/20/2019 Basic Lines-Protection.ppt
27/31
#arallel eeders
%onsider fault on one feeder 7)
"elays J%G and J!G see the same fault current
I2. $s J%G and J!G have similar settings bothfeeders will be tripped.
=1 $ =1%
=1 @ =1!
85$!
I& + I-I1
I2
# ll l d
-
8/20/2019 Basic Lines-Protection.ppt
28/31
#arallel eeders
(olution7) !irectional %ontrol at J%G andJ!G
"elay J!G does not operate due to currentflow in the reverse direction.
=1 $ :;%
=1 @ :;!
85$!
I& + I-I1
I2
#arallel eeders
-
8/20/2019 Basic Lines-Protection.ppt
29/31
#arallel eeders
(etting philosophy for directional relays
8oad current always flows in Jnon)operateG
direction. $ny current flow in JoperateG direction is
indicative of a fault condition.
=1 $ :;
E
=1 @ :;
%
!
8oad
=1
-
8/20/2019 Basic Lines-Protection.ppt
30/31
#arallel eeders
Dsually, relays are set 7)
) =9> of full load current note thermal
rating
) '!/T rather than !T
) /inimum T./.(. 9.1
#arallel eeders $pplication Bote
-
8/20/2019 Basic Lines-Protection.ppt
31/31
#arallel eeders ) $pplication Bote
#
@
@
!
!
8oad
8oad
If1
$ %
If1If22 If2
@%
!
Ifmax
$
Arade $ with @ with %
at If 1single feeder in service
Arade @ with ! at If 3'f 1upper feeder open at #
Arade $ with @ at If 2both feeders in service
) check that sufficient margin exists forbus fault at L when relay $ sees total
fault current If 2, but relay @ sees only
If 22.
If&
If-
/
/ /argin/
/
L