basic transformer protection

26
GE Digital Energy GE Digital Energy GE Digital Energy GE Digital Energy Transformer basics and more…

Upload: atan-b-atan

Post on 29-Dec-2015

58 views

Category:

Documents


4 download

TRANSCRIPT

Page 1: Basic Transformer Protection

GE Digital EnergyGE Digital EnergyGE Digital EnergyGE Digital Energy

Transformer basics and more…

Page 2: Basic Transformer Protection

Transformer Basic & More…Transformer Basic & More…Transformer Basic & More…Transformer Basic & More…

Power Transformer as an expensive device

Page 3: Basic Transformer Protection

Transformer Basic & More…Transformer Basic & More…Transformer Basic & More…Transformer Basic & More…

Power Transformer Name Plate

Page 4: Basic Transformer Protection

Generator Step- Up

transformers

Step- Down transmission

substationtransformers

Distribution substation

transformer

Transformer Basic & More…Transformer Basic & More…Transformer Basic & More…Transformer Basic & More…

Distribution transforme

r

Location

Page 5: Basic Transformer Protection

Transformer types• Generator Step-Up (GSU) transformer

• Transmission step down transformer

• Distribution substation transformer

• Distribution small transformers

• Autotransformers

Transformer Basic & More…Transformer Basic & More…Transformer Basic & More…Transformer Basic & More…

• Voltage regulating transformers

• Scott transformers

• Reactors

• Split-Phase autotransformers

Page 6: Basic Transformer Protection

GENERATOR STEP- UP (GSU) TRANSFORMERS

52

52

GSU xfmr

Transformer Basic & More…Transformer Basic & More…Transformer Basic & More…Transformer Basic & More…

• 1300 MVA

• 343 ±2x1.9% / 25 kV

• 60 Hz

• 3-phase

Aux. xfmr

Page 7: Basic Transformer Protection

STEP- DOWN DISTRIBUTION SUBSTATION TRANSFORMER

Transformer Basic & More…Transformer Basic & More…Transformer Basic & More…Transformer Basic & More…

• 24 MVA

• 138 / 13.8 kV

• 60 Hz

• 3-phase

• FOA

Page 8: Basic Transformer Protection

AUTOTRANSFORMER

Transformer Basic & More…Transformer Basic & More…Transformer Basic & More…Transformer Basic & More…

1000 MVA

346 ±17x3.66 kV / 225 kV

60 Hz

3-phase

OA/FA/FA (self-cooled/ forced air cooled)

Page 9: Basic Transformer Protection

100kVA, 14.4kV/240V/120V

100kVA, 14.4kV/347VPole-Mount

Single-phase

transformers

500kVA, 14.4kV/600VPlatform-Mount

SMALL DISTRIBUTION TRANSFORMERS

Transformer Basic & More…Transformer Basic & More…Transformer Basic & More…Transformer Basic & More…

45kVA, 24.94kV/480V3-phase Pole Mount

14.4kV/240V/120VMini-Pad

Pole-Mount

Three-phase

transformers

Up to 300kVAPrim. voltage - up to 36kV3-phase substation installation

Platform-Mount

2 MVA, 13.8/600kVPad - Mount

Page 10: Basic Transformer Protection

Transformer componentsTransformer Basic & More…Transformer Basic & More…Transformer Basic & More…Transformer Basic & More…

Page 11: Basic Transformer Protection

Transformer components – cooling system

Transformer Basic & More…Transformer Basic & More…Transformer Basic & More…Transformer Basic & More…

OIL PUMPCOOLING FANS

Page 12: Basic Transformer Protection

Transformer components – tap changer

TAP-CHANGER

Transformer Basic & More…Transformer Basic & More…Transformer Basic & More…Transformer Basic & More…

Page 13: Basic Transformer Protection

BUCHHOLZ RELAY

Transformer components –Buchholtz relayTransformer Basic & More…Transformer Basic & More…Transformer Basic & More…Transformer Basic & More…

Page 14: Basic Transformer Protection

SUDDEN PRESSURE

RELAY

Transformer components – gas pressure relayTransformer Basic & More…Transformer Basic & More…Transformer Basic & More…Transformer Basic & More…

CHANGE PRESSURE RELEIF

DEVICE

Page 15: Basic Transformer Protection

Winding connections and phase shiftTransformer Basic & More…Transformer Basic & More…Transformer Basic & More…Transformer Basic & More…

Page 16: Basic Transformer Protection

Transformer electric parameters - relations

Transformer Basic & More…Transformer Basic & More…Transformer Basic & More…Transformer Basic & More…

SSSPPP PIVIVP === **

S

P

P

S

P

S

I

I

N

N

V

V==

Page 17: Basic Transformer Protection

Transformer losses

copper losses -I 2 R

Transformer Basic & More…Transformer Basic & More…Transformer Basic & More…Transformer Basic & More…

Stray loss -stray capacitance and leakage inductance lossesApparent loss –loss due to magnetizing current in the primary winding

Iron loss –loss due to varying flux in the core( hysteresis and eddy losses)

- hysteresis loss

Page 18: Basic Transformer Protection

Transformer inrush

The steady state flux

lags the voltage by

90° degrees

Transformer Basic & More…Transformer Basic & More…Transformer Basic & More…Transformer Basic & More…

The flux builds up from zero, when the voltage is applied at zero crossing, and can reach 2 times the maximum flux. The magnetizing current becomes even higher, if the transformer is energized at zero point of the voltage wave, and there is residual flux

As the flux builds,

the exciting

current grows with

the flux.

Page 19: Basic Transformer Protection

Transformer faults and detection

• EXTERNAL FAULTS

– Overloads

– Overvoltage

– Underfrequency

– External system short circuits

• INTERNAL FAULTS

– Incipient faults

• Overheating

• Over-fluxing

• Overpressure

– Active faults

Transformer Basic & More…Transformer Basic & More…Transformer Basic & More…Transformer Basic & More…

– Active faults

• Short circuit in wye-connected

windings

• Short circuits in delta windings

• Phase-to-phase faults

• Turn-to-turn faults

• Core faults

• Tank faults

Page 20: Basic Transformer Protection

External faults:

OVERLOADSOVERLOADSOVERLOADSOVERLOADSIn most cases, no protection is provided, but an alarm is used to

warn the operating personnel of the conditions. A TOC

protection with definite time delay can be set.

OVERVOLTAGEOVERVOLTAGEOVERVOLTAGEOVERVOLTAGEIt can be either due to short-term transient conditions, or long

term power frequency conditions. Transient over-voltages,

cause end-turn stresses and possible breakdown. The conditions

are detected by Volts/HertzVolts/HertzVolts/HertzVolts/Hertz protection.

Transformer Basic & More…Transformer Basic & More…Transformer Basic & More…Transformer Basic & More…

UNDERFREQUENCYUNDERFREQUENCYUNDERFREQUENCYUNDERFREQUENCY

Under-frequency is caused by some system disturbances

resulting in unbalance between generation and load. This low

frequency creates overfluxing in the transformer core, leading to

overheat. Volts/HertzVolts/HertzVolts/HertzVolts/Hertz protection is used with typically 1.1 pu

pickup ratio setting.

EXTERNAL SYSTEM SHORT EXTERNAL SYSTEM SHORT EXTERNAL SYSTEM SHORT EXTERNAL SYSTEM SHORT CIRCUITSCIRCUITSCIRCUITSCIRCUITS

Large external fault currents can cause high mechanical stress

in the transformer windings, with the maximum stress occurring

during the first cycle. The transformers are not protected during

such external conditions. It is a matter of transformer design,

and application, to deal with these conditions.

Page 21: Basic Transformer Protection

Incipient transformer internal faults

OVERHEATINGOVERHEATINGOVERHEATINGOVERHEATING

Caused by:

• poor internal connections, in either electric or magnetic circuit

• loss of coolant due to leakage

• blockage of coolant flow

• loss of fans or pumps

Buchholtz relay and thermal elements protections such as Hottest

Spot temperature, Aging Factor and Loss of Life are normally used

Transformer Basic & More…Transformer Basic & More…Transformer Basic & More…Transformer Basic & More…

Continuous overfluxing can gradually lead to isolation breakdown. The detection is provided by Volts/Hertz Volts/Hertz Volts/Hertz Volts/Hertz protection

OVERFLUXINGOVERFLUXINGOVERFLUXINGOVERFLUXING

OVERPRESSUREOVERPRESSUREOVERPRESSUREOVERPRESSURE

Overpressure in the transformer tank occurs due to released gases that accompany localized heating. An example is the turn-to-turn fault, that can burn slowly, releasing bubbles of gases, which increase the pressure. Sudden Pressure relay, or Buchholtz relay

Page 22: Basic Transformer Protection

Protection elements

Transformer Basic & More…Transformer Basic & More…Transformer Basic & More…Transformer Basic & More…

Page 23: Basic Transformer Protection

Active internal faults detected by 87T protection

* ** *

D/Y30

WYE connectionWYE connection

I1 prim I2 prim

T60

T60

Phase-to-phase faults

Three-phase faults

Ground faults

Core faults

Tank faults

Transformer Basic & More…Transformer Basic & More…Transformer Basic & More…Transformer Basic & More…

i1 sec

i2 sec

T60

DIFFERENTIAL SIGNAL:

I DIFF. = I1COMP + I2COMP

RESTRAINING SIGNAL:

I RESTR. = max ( |I1COMP| , | I2COMP|)

Id, pu

Ir, pu

Min. PKP

B 1 B 2

S 1

S 2

Page 24: Basic Transformer Protection

T60 BIASED DIFFERENTIAL(TRIP/NO TRIP DECISION)

Id > PKP

YES

Ir < B1 Id/Ir%>S1YES

NO

NO

NO TRIP

Transformer Basic & More…Transformer Basic & More…Transformer Basic & More…Transformer Basic & More…

NO

B1 < Ir < B2 YES

NO

Ir > B2

Id/Ir, % >S2 YES TRIP

Id/Ir,% >S1&S2

YES

NO

NO

YES

Page 25: Basic Transformer Protection

Restricted Ground Fault protection

� Fast detection of winding ground faults� Very secure performance on external ground faults� Configurable pickup, slope, and time delay

Transformer Basic & More…Transformer Basic & More…Transformer Basic & More…Transformer Basic & More…

Igd, pu

I = max( IR1, IR2, IR0 ), pu

Min. PKP

S lope

gIIIgdρρ

+= 03)2,1,0max( IRIRIRIgr =

Page 26: Basic Transformer Protection

Questions

Transformer Basic & More…Transformer Basic & More…Transformer Basic & More…Transformer Basic & More…