basics of electrical testing poster en - hioki usa · e voltage drop small small current vr a/d...
TRANSCRIPT
![Page 1: Basics of Electrical Testing poster EN - Hioki USA · E Voltage drop Small Small current Vr A/D Digital display 8 8 8 8 Basics of Electrical Testing Inquiries Magnetic flux from secondary](https://reader034.vdocument.in/reader034/viewer/2022050300/5f69bb5694e18e1ba8645f4a/html5/thumbnails/1.jpg)
E
VoltagedropSmall S
mall
currentVr
A/D
Digitaldisplay
8 8 8 8
Basics of Electrical Testing www.hioki.com
Inquiries
Magneticflux fromsecondarycurrent
Output
Measuredconductor
Shuntresistance
Magnetic
core
Magnetic flux frommeasured current
Secondarycurrent
Feedbackwinding
Measuredcurrent
Hall element AMP
MEASURESW
LR6 x 4
OFF
ON
AI
V=Rx×I
Rx=V/I
S(P)electrode
E electrode
HIOKI Calibration Certificate
HIOKI Data Sheet
H(C)electrode
ICurrent meter
Voltmeter
AC power
V
Measuring Instrument(Device under test)
Magnitude
Value
Input 10VCalibrated value 10.000 00V
Standard Instrument
Relationship
Verify
Intermediatestandards
Comparativestandards
Appliedstandards
National Instituteof Advanced
Industrial Scienceand Technology
Nationallyrecognizedstandards
MULTI-PRODUCTCALIBRATOR
FLUKE 5520A
POWER HiTESTER
HIOKI 3332
National Instituteof Information
and CommunicationsTechnology
Japan Electric MetersInspection Corporation
ManufacturerFLUKE
ManufacturerClarke-Hess
TelecomEngineering
Center
STANDARDRESISTANCE
FLUKE742A-1, 742A-10k
CALIBRATORFLUKE 5700A
AMPLIFIERFLUKE 5725A
STANDARDRESISTOR
AlphaElectronics Corp.
CSR
STANDARDRESISTOR
YOKOGAWA2792, 2794
CURRENTTRANSFORMER
TOKYOSEIDENCTS8-1(50A/5A)
CURRENTSHUNT
100Ω, 1kΩ
HIOKI
ACMEASUREMENT
STANDARD
FLUKE5790A
CURRENTSHUNT
FLUKEA40,A40A
DIGITALPHASEMETER
Clarke-Hess6000A
UNIVERSALCOUNTER
ADVANTESTTR5830D
MULTIMETER
HP/Agilent 3458A
A
Water will not flow.
Differencein water level
High +
BAT
Voltage (V)
Low −
ElectricPotential
Resistance (R)
Current
Waterflow
B A
B
Current (I)
current
DC (Direct Current) is the flow of electric charge in one direction.
Excessive overvoltage (impulse voltage) may also appear on power lines. The opening and closing of solenoid valves or loads at plants may cause high voltage spikes. Furthermore, since the wave peak value may be 10 times the power supply voltage or more in the case of inductive loads, etc., the IEC standard provides a correlation between the nominal system voltage (power supply line voltage), overvoltage level, and measurement category as an indication of transient overvoltage.
AC (Alternating Current) is electric charge that periodically varies in terms of direction and magnitude. A typical AC waveform is a sine wave, and commercial power supply is made of sinusoidal AC voltage signals.
Instantaneous : Level that occurs instantaneouslyMaximum and Minimum : The highest and lowest values Peak-to-Peak : Difference between the maximum and minimumAverage : Average of the instantaneous values that occur in half a cycleRoot Mean Square (RMS or True RMS) : Energy that is converted to a DC-equivalent valueFrequency : The number of times a point on a wave passes a fixed reference point in one second
In the average rectifying method, average values are measured using an internal circuit. The average values are multiplied by the sine wave’s waveform ratio of 1.11 and then converted to RMS values. In the RMS method, RMS values are measured using an internal circuit. With this method, even distorted waveforms can be properly displayed as RMS values.
Example: A crest factor 3 measuring instrument may not be able to accurately measure a waveform with crest factor of 3 or more with respect to the range. It is necessary to change the range or to use an instrument with a higher crest factor.
Example AC Waveforms
Voltagedrop
Large LargecurrentVr
Max
Max: 141.4V
Min: -141.4V
Full waverectified(×1.11)
LPF MEANValue
DC
Peak-to-Peak
Based on the IEC61010-1 international standard concerningthe safety requirements for electrical equipment formeasurement, control, and laboratory use
Drop connection
Service dropDistributionpanel
Distributionpanel
Fixedinstallation
Outlet OutletTransformer
Power meter
Min
Sine Square
Sawtooth Triangular
Pulse Distorted
Example DC Waveforms
Direct Ripple Pulsating
Peak-to-Peak: 282.8VAverage
Average: 90V
RMS: 100V
Example: 100V Commercial Power Supply
High surge voltages often occur when a solenoid valve opens and closes. The example above shows almost a 1000V surge on a 100V AC line.
When a current flows, a magnetic field is generated concentrically. The magnitude of the magnetic field is proportional to the magnitude of the current. The direction of the magnetic field is the direction in which a screw is tightened if the direction of movement of the screw and the direction of current are matched. This law is called "Ampère's right-hand grip rule".
Input impedance : lowInstrument loss : largeExternal noise : low susceptibility
Example of Overvoltage atOpen/Close of Solenoid Valve
Ampère's right-hand grip rule
Resistance measurement circuit of an analog meter
A current clamp meter measures the voltage across a detection shunt resistor from the winding that forms the coil, the magnetic core that raises the sensitivity of the magnetic field, and the shunt resistor for measuring the induced current. The signal generated in the conductor is then calculated into current by the meter’s internal circuit and displayed.
For DC current, measurement is performed using a Hall element, whereby an induced current is generated by the change in magnetic field, and that magnetic field is proportional to the magnitude of the current to be measured.
Note) DC cannot be measured with a clamp tester dedicated for AC signals
Structure of a current clamp meter Insulation resistance is measured in order to ensure the safety of electrical equipment / parts and electrical facilities etc.1. Insulation between charged and non-charged parts → possible ground fault and electric shock if
insulation breakdown occurs2. Insulation between two or more charged parts → possible short circuit if breakdown occursThe higher the insulation resistance, the greater the effect.
Effective for TN earthing systems only 1. The voltage transducer injects a
defined voltage into the multi-grounded system.
2. From the defined voltage and measured current, the total circuit loop resistance is calculated in the following equation
IEEE 43-2013:Recommended Practice for Testing Insulation Resistance of Electric Machinery Typically referenced for motor maintenance, etc.
Objective
BS 7671: 200817th Edition of the IET Wiring Regulations
Switch from the transmission circuit, boost with a transformer to apply a high voltage, then measure the current and convert it to a resistance value.
Measurement principleThe accuracy and tolerance described in the product specifications are given in terms of rdg., f.s., and dgt. Measurement uncertainty is often defined, and the uncertainty limit is obtained from these values.
(1) f.s. (full scale: maximum displayed value, maximum scale, scale length)Generally, f.s. represents the range value currently used, and for analog displays, the maximum deflection of the needle.
(2) rdg. (reading: read value, displayed value, indicated value)Refers to the value actually being measured, i.e., the value that is currently indicated or displayed by the measuring instrument.
(3) dgt. (digit: resolution)Refers to the least significant digit of the digital display, i.e., the lowest digit in the displayed value, located at the far right of a string.
Calibration is the work to verify the relationship between values that is indicated by a meter or measurement system, to the true values provided by a given standard, standard sample, or other defined equipment
Calibration requirements stipulated byISO9001:2008:
7.6 Control of monitoring and measuring equipmenta) be calibrated or verified, or both, at
specified intervals, or prior to use, againstmeasurement standards traceable to international or national measurement standards; where no such standards exist, the basis used for calibration or verification shall be recorded
A data sheet is a document that describes the calibration and judgment results. It provides the indicated value for the input of each range, and a PASS if that value is within tolerance.
Traceability is the ability to link to national standards through a chain of seamless calibrations.
Accuracy specifications: ±1.0%rdg.±3dgt. (300V range)Measurement range: 300.0VMeasured value: 100V(A) Reading uncertainty: ±1.0% of 100.0V → 99.0 to 101.0V(B) Digit uncertainty: ±3dgt. → ±0.3VTotal uncertainty limits (range of true value) (A+B) = 98.7V to 101.3V
Digital Measuring Instruments
Example 1: Measuring voltage using the Hioki 3281 Clamp Meter
Accuracy specifications: ±0.2%rdg.±0.1%f.s. (voltage range)Measurement range: 300.0VMeasured value: 100V(A) Reading uncertainty: ±0.2% of 100.0V → 99.8 to 100.2V(B) Full scale uncertainty: ±0.1 f.s. → ±0.3V (300V x 0.001)Total uncertainty limits (range of true value) (A+B) = 99.5V to 100.5V
Example 2: Measuring voltage using the Hioki 3169 Clamp On Power Meter
How an earth resistance tester measures
Measurement Method : Clamp method
Voltage from the AC power supply is applied between the H(C) electrode and the E electrode, and the resulting AC current I is measured. In addition, an AC voltmeter is used to measure the voltage V between the S(P) electrode flowing with current and the E electrode. Earth resistance Rx of the E electrode is then calculated from the measured current and voltage.
Magnitude and values change as time passes (aging)
Earthing refers to the work of connecting the electric path to the ground. The ground is a stable potential, made possible by connecting the ground to an electric circuit. Earthing plays many roles, such as securing the outer case of equipment, the neutral point of an electric circuit, and the reference potential of electronic or communication devices.
What is earthing?
• Telecommunication and electronic equipment: to countermeasure electromagnetic waves, noise, and communication issues
• Building electrical equipment: to prevent electric shock• Lightning protection• Balance of potentialThe lower the earth resistance value, the greater the effect.
Main objectives
Measuring Leakage Current
When the magnetic field changes, a current is induced in the coil through which it penetrates. The magnitude of the current is determined by the magnetic fluctuation. By measuring the induced current, the magnitude of the magnetic field is known as it flows in the conductor, making it possible to measure the current at that time.
Measurement principle of current testing
Example of Damage due to Misuse of Tester
CAT II
Ohm’s Law
Average Rectified Method
True RMS Method
Comparing Distorted Current Values Such as Inverter Signals
Voltage = Current × ResistanceCAT III
CAT IV
Full waverectified Sq Avg √ LPF RMS
Value
RMS Processing IC
Average methodcurrent clamp
Max. value
RMS value
True RMS methodcurrent clamp
DC
Crest Factor (CF) =RMS
Max Value (Peak)
Always conduct zero adjustment when measuring resistance. (Mechanical and electrical zero adjustment) Situations where voltage is being applied is hazardous so separation is critical.
Connect to the circuit in parallel.
In order to measure without effects from wiring or contact resistance, use the 4-wire measurement method in place of the 2-wire method
Earthing Systems (TN, TT and IT)The resistance of copper wire changes according to the surrounding temperature.
Rt = Rt0 ×{ 1 + αt0 × (t - t0) }
RtRt0t0tαt0
Actually tested resistance [Ω]Compensated resistance [Ω]Reference temperature [°C]Current ambient temperature [°C]Temperature coefficient at t0
:::::
By using a temperature-compensated resistance meter, you can automatically capture the temperature-converted resistance value.
Current clamp meters are roughly classified into those that measure load current, leakage current, direct current, as well as wide frequency band meters. If only measuring load current, basically clamping 1 line is sufficient. Current clamp meters only measure 1 line at a time.
When measuring leakage current, two wires may be clamped simultaneously. Leakage current is current that flows to the ground through the insulation resistance of the load, and can be several tens of μA if many loads are connected. By using a clamp meter, the minute difference flowing in both directions can be detected and identified as leakage current.
The currents of the two go- and return- lines are in the opposite direction, and a magnetic field of the same magnitude is generated. Therefore, since the two magnetic fields cancel each other out, the fields become zero when summed. In short, zero is displayed when the two wires are clamped at the same time.
The UK standard required for distributionConfirm the standard/requirement of your country.
Analog Input impedance : highInstrument loss : smallExternal noise : high susceptibility
Digital
Serial connection to circuitPower line must be cut
Minute current direction Load current direction
Direct wiringmethod
Serial connection to circuitNo need to cut power line
High voltage:100 V AC
Allowablecurrent:158mA
Allowablecurrent:
50μA
10A(1/4W resistance)
Rs = 10Ω rv = 5kΩ Damage due toovercurrent
Approx. 63x overcurrent
20mAApprox. 400x overcurrent
The tip of the test lead also melted due to the shorted current.
-1000V
+1000V
0
Compensate
Magnetic field
Current
Current generateddue to fluctuating
magnetic field
current
Insulationresistance
Leakagecurrent
The Hioki DT4280 Series is designedwith a terminal shutter system toprevent erroneous connections.
CAT IV 600 V / CAT III 1000 V
Rt
Resistance
Rt0
t0 t Temperature
Oscillatingcircuit
Oscillatingcontrolcircuit
1,200
1,000
800
600
400
200100
00 0.025 0.05 0.1 0.125 0.25 0.5
Measured resistance [MΩ]
Measurement terminal voltage characteristics (Hioki IR4000 series)
1000V1000V
500V500V
250V250V125V125V50V50V
Mea
sure
men
t ter
min
al v
olta
ge [V
]
1 20 100 2,000 ∞
Select HVrange
R valuedisplay
Currentdetection
LINE
V → IV
detection
Boost
I1
I2
(DC
Voltage)
Resistance under test
25V25V
■ 3-pole methodMeasured resistance = Rx[Ω]
■ 2-pole method (simple method)Measured resistance = Rx + Ro [Ω]
10m 10m
Rx
C P E E P C
Minimum 5m
RxRo
E C
300.0 V range
0.1 V is the least significant digitin the 300.0 V range
Measuring 100V on the 300 V range
Measuring in the 300.0 V range
Displayedmeasured value
Max.displayed
value
Measuredvalue
calibration timetraceability
Resolution
Pin Tip
Sleeve
Nationalstandards
ReferenceTraceability Appliedstandards
Equipmentunder
calibration
300600
1000
Rated voltage toground [V] CAT II CAT III
Recommended Impulse Withstand VoltageCAT IV
250040006000
400060008000
60008000
12000
2-wire method 4-wire method
r1 r3 r4
I
r2
Constantcurrent power
Voltmeter
r1 E
I
r2
Resistance Ro
Non-chargedpart
Powersupply
LL
E E
Ground
Insulatedpart
Powersupply
Charged part
Charged partCharged partInsulated part
EARTH
MagnitudeValue
Time
High precision instruments generally exhibit little change over time
Low precision instruments generally exhibitlarge change over time
Electricity can be likened to the flow of water.
Waveforms that include harmonic and other components are converted to RMS values and displayed. RMS = Root Mean Squared
Crest factor is the ratio of a waveform's peak value to its RMS value.
In the specifications of an RMS measuring instrument, its crest factor is defined. This value represents the type of waveform that can be measured.
Primary electrical circuits in equipment connected to an AC electrical outlet by a power cord
Primary electrical circuits of heavy equipment (fixed installations) connected directly to the distribution panel, and feeders from the distribution panel to outlets
The circuit from the service drop to the service entrance, and to the power meter and primary overcurrent protection device (distribution panel)
When reading an instrument's specifications, a voltage value will follow the measurement category, such as in “CATIII 600V” . This means that the instrument can measure up to 600V in a CAT III environment.
400V was mistakenly input while in the resistance function. The resistance function carried a 250V protective circuit.
Example: mA range (analog tester)
The resistance range was used to test the voltage in this 200V electrical panel, causing severe damage.
Use the pin sleeves at the tips to prevent short-circuit accidents.
Clampmethod
Constantcurrent power
Voltmeter
Resistance Ro
Rectification
& S
moothing
Magnitude
Value
Nominal circuit voltage (AC) Test voltage (DC) Minimum resistance
0 V to 50 V 250 V 0.5 MΩ
50 V to 500 V 500 V 1 MΩ
500 V to 1000 V 1000 V 1 MΩ
Rated voltage (AC) Insulation resistance test voltage (DC)
< 1000 500
1000 to 2500 500 to 1000
2500 to 5000 1000 to 2500
50001 to 12000 2500 to 5000
> 12000 5000 to 10000
Rx R1 R2 R3 R4
Assuming a pure sinusoidal waveform with no distortions (at a single frequency), waveforms are converted to RMS values and displayed. Distorted waveforms will result in measurement values with large errors.
Measurement principle ofan earth resistance tester
*The True RMS method can measure even distorted waveforms correctly
Rx +Many R are connected.
=+R1
1 +R21
1
+R31 ...
R41 I
V Rx =IV
TN-S system
TN-C system
Consumer
Generator / Transformer L1L2L3N
Earth
PE
Consumer
Generator / Transformer L1L2L3PEN
Earth
Consumer
Generator / Transformer L1L2L3
Earth
IT system
Consumer
L1L2L3N
Earth
PE
TT system
Consumer
Generator / Transformer L1L2L3N
Earth Earth
Grid and customer are connected to the different earth independently.
Grid is not connected to the earth.Safe against leakage.
Connected to the common earth through grid.
Generator / Transformer TN-C-S system
-
0
+
I I I I I
1 cycle
-
0
+
I=0 I=0 I=0I I
Zero Adjustment
Rx
Tester Equipment under test
Always separate
Electricity in Terms of Water Flow
What is DC ?
What is AC ?
Describing AC Signal
Average Rectified vs RMS •1
Average Rectified vs RMS •2
What is Crest Factor ?
Measurement Category •1
Measurement Category •2
Measurement Category •3
Do Not Input Voltageto the Current Measurement Circuit
Do Not Input Voltageto the Resistance Measurement Circuit
Safety Standards for Test Probes
Voltage Testing
Current Testing
Measurement Principle of Current Clamp Meters •1
Measurement Principle of Current Clamp Meters •2
How to Measure Using Current Clamp Meters •1
How to Measure Using Current Clamp Meters •2
Resistance Testing
Low Resistance Testing •1
Low Resistance Testing •2
Insulation Resistance Testing •1
Insulation Resistance Testing •2
Insulation Resistance Testing •3
Insulation Resistance Testing •4
Earth Resistance Testing •1
Earth Resistance Testing •2
Earth Resistance Testing •3
Earth Resistance Testing •4
Earth Resistance Testing •5
How to Calculate Accuracy •1
How to Calculate Accuracy •2
What is Calibration ?
Why is Calibration Necessary ?
What is a Data Sheet/Test Report ?
What are Reference Instruments ?
Measurement Category and Rated Voltageto Ground Indication
Basics of Electricity Measurement Basics Accuracy & Calibration