battery fault transfer fault charger fault emergency lamp ...€¦ · one blink on/pause battery...
TRANSCRIPT
TROUBLE SHOOTING•“EXIT” legend does not illuminate • Check wiringconnections.
•Emergency circuit does not work • Batteriesareshippedunchargedanddisconnected.Connectpowerpackleadsandchargebeforetesting. • Makesurechargerboardisproperlyseated. • Checkwiringconnections.
MAINTENANCESignsshouldbetestedandmaintainedinaccordancewithNationalElectricalCodeandNFPA101LifeSafetyCoderequirements.Itisrecommendedthatemergencyexitsignsbetestedfor30secondsonceamonthandfor90minutesonceayear.
RECYCLING INFORMATION Allthermoplasticpartsarerecyclable.Allcartonscontainrecycledmaterials.Pleaserecycleresponsibly.
NOTICE:Emergency model exit signs contain rechargeable nickel-cadmium batteries which must be recycled or disposed of properly.
LX SeriesThermoplastic LED Exit Sign
Installation, Operation and Maintainance Instructions
Hubbell Lighting, Inc. Life Safety Products • www.dual-lite.comCopyright©HubbellLighting,Inc.,AllRightsReserved•Specificationssubjecttochangewithoutnotice.•PrintedinU.S.A. 93028841B 6/10
IMPORTANT SAFEGUARDSWhenusingelectricalequipment,basicsafetyprecautionsshouldalwaysbefollowedincludingthefollowing.
READ AND FOLLOW ALL SAFETY INSTRUCTIONS 1.Donotuseoutdoors. 2.Donotletpowersupplycordstouchhotsurfaces. 3.Donotmountneargasorelectricheaters. 4.Equipmentshouldbemountedinlocationsandatheightswhereitwillnotreadilybesubjecttotamperingby unauthorizedpersonnel. 5.Theuseofaccessoryequipmentnotauthorizedbythemanufacturermaycauseanunsafecondition. 6.Donotusethisequipmentforotherthanitsintendedpurpose. 7.Servicingofthisequipmentshouldbeperformedbyqualifiedservicepersonnel. 8.Testcycling:theLifeSafetyCode(NFPA101)requirestestingofemergencyexitsignsonceamonthfora minimumof30secondsandonceayearforaminimumof90minutes.
INSTALLER: •SEE UNIT LABEL FOR ADDITIONAL MODEL SPECIFICATIONS
•SAVE THESE INSTRUCTIONS FOR USE BY OWNER/OCCUPANT
WARNING–ThisproductcontainschemicalsknowntotheStateofCaliforniatocausecancer,birthdefectsand/orotherreproductiveharm.Thoroughlywashhandsafterinstalling,handling,cleaning,orotherwisetouchingthisproduct.
93028961
OPERATION“ACON”LEDisiluminatedwhenACpowerispresent.NOTE:AllmodelsaresuppliedwithanACLockoutcircuit,whichpreventsthe“EXIT”legendfromilluminatingwhenthebatteryisconnectedandnoACpowerispresent.NOTE:AllmodelsaresuppliedwithaLowVoltageDisconnectcircuit,whichpreventsdamagetothebatteryfromdeepdischargeduringprolongedemergencyoperation.NOTE:Batteriesareoftenshippedinadischargedstate–thisisnormal.Thebatterywillrequirecharging.Allowseveralhoursofchargebeforetestingtheunit.
ModelsWithSPECTRON®Self-Testing/Self-DiagnosticCircuitryModelsequippedwiththeSpectronself-testing/self-diagnosticelectronicssystemprovide:
■ Visual indication of AC power status ■ Visual indication of self-diagnostic test cycle —Visual indication of any unit malfunctions including— ■ Battery fault ■ Transfer Fault ■ Charger fault ■ Emergency Lamp faultSpectron equipped units also include:Brownoutprotection:unitwillautomaticallytransfertoemergencyoperationupondetectionoflowACpower(approximately80%ofnominalline).TimeDelayRetransfer:uponreturnofnormalACpower,unitwillremainintheemergencymodeforanadditional15minutestoallowACpowertostabilize.
LED Status IndicatorAbicolorLED(green/red)isprovidedonthecontrolpanelofallmodelsequippedwiththeSpectronoption.
Red Status Indicator Code Description
OneblinkON/pause Batterynotconnected
TwoblinksON/pause Batteryfault
ThreeblinksON/pause Chargerfault
FourblinksON/pause Transfercircuitfault
FiveblinksON/pause EmergencyLampfault
Automatic TestsTheunitwillautomaticallyinitiateaself-test/self-diagnosticcyclebasedonthefollowingtable:
Testing Period Duration of Test
Onceamonth 1minute
Onceevery6months Alternating:30minutesor60minutes
Manual TestsUsingtheunittestswitch,userscaninitiatedifferentdurationtestcyclesbasedonthefollowingtable:
Initiating Action Test Cycle
Presstestswitchonce 1minute
Presstestswitchtwice 90minutes
Pressingthetestswitchatanytimeafteratestcyclehasbeguncancelstheremainderofthetestandreturnstheunittonormaloperation.
RedServiceAlertIndicatorUndernormaloperatingconditions,theredServiceAlertIndicatorwillremain“off”.IntheeventtheSpectroncontrollerdetectsamalfunction,theredServiceAlertIndicatorwillblinkata1Hz.rate,basedonthefollowingtable:
GreenOperatingStatusIndicatorThegreenOperatingStatusIndicatorservesasbothanACpowerandaself-testindicator.Duringnormaloperation,thegreenOperatingStatusIndicatorwillbeilluminated,indicatingthepresenceofACpower.Duringallautomaticormanualself-testcycles,thegreenOperatingStatusIndicatorwillblinkata1Hz.rate.
MAINTENANCE
930289619302896393029014930290199302902593029029
END MOUNT Makeconnectionsusingquickconnectorsprovidedandinsertconnectorsincaptureslots.(SeedetailA)
IMPORTANT:Routewiresthroughtopopeningincanopyforeaseofwiring.
Usepre-tinnedpigtailleadsprovidedforACinputtosign.
ACtransformer.120VAC-connectblackandwhiteleads277VAC-connectredandwhiteleads
Storeunusedleadintransformercompartment.
*Foremergencymodels- plug2-pinbattery connectorintoPCboard.
Chargerboardand
batterypack.(Emergencymodelsonly*)
93029014
Routewiresinchannelasshown.
INSTALLATION INSTRUCTIONS
IMPORTANT:Optionconnectionwiresmustberunbeforesignhousingisattachedtocanopy.FIRE ALARM PANEL (-FAP) OPTIONFAPoptionconnectsto24voltACorDC(purplewires).FlashRate:.5secondson,.5secondsoff.DC REMOTE (-DC) OPTION DCRemoteoptionconnectsto6-24voltDC[yellow(–),blue(+)].FLASHER MODULE (-FM) OPTION EmergencyModeFlashRate:.5secondson,.5secondsoff.AUDUBLE/FLASHER MODULE (-AF) OPTION EmergencyModeBeep/FlashRate:.5secondson,.5secondsoff.
Connectoptionwires(-FAPor-DC)togreyconnectoronoptionboard.
Routewiresthroughtransformercompartmentandoutcanopyorbackplate.
93029029
DUAL CIRCUIT (-2C) OPTION
Dual-circuittransformersecondarywiresconnecttoinputconnectoronoptionboard.
Connectdual-circuitprimarytransformerwirestoutilitysource.120VAC-connectblackandwhiteleads.277VAC-connectredandwhiteleads.
93029025
WALL MOUNT
Routewiresinchannelasshown.
Storeunusedleadintransformercompartment.
Makeconnectionsusingquickconnectorsprovidedandinsertconnectorsincaptureslots.(SeedetailA)
Selectappropriateknockoutsforwallbox.
ACtransformer.120VAC-connectblackandwhiteleads.277VAC-connectredandwhiteleads
Usepre-tinnedpigtailleadsprovidedforACinputtosign.
Chargerboardand
batterypack.(Emergencymodelsonly*)
*Foremergencymodels- plug2-pinbattery connectorintoPCboard.
93028963
CEILING MOUNT
ACtransformer.120VAC-connectblackandwhiteleads.277VAC-connectredandwhiteleads
Usepre-tinnedpigtailleadsprovidedforACinputtosign.
Routewiresthroughlargeholeatsnap.
Makeconnectionsusingquickconnectorsprovidedandinsertconnectorsincaptureslots.(SeedetailA)
Routewiresinchannelasshown.
Storeunusedleadsintransformercompartment.
Chargerboardand
batterypack.(Emergencymodelsonly*)
IMPORTANT: Routewiresthroughtopopeningincanopyforeaseofwiring.
*Foremergencymodels- plug2-pinbattery connectorintoPCboard.
93029019
93029019