battery range summary · the genesis td battery range, comprises of three 12v batteries with...
TRANSCRIPT
![Page 1: Battery Range Summary · The Genesis TD battery range, comprises of three 12V batteries with capacity sizes from 50 to 150Ah and features a front terminal design ... 10 hr rate 8](https://reader035.vdocument.in/reader035/viewer/2022070907/5f81282cfa05c44e265a5e23/html5/thumbnails/1.jpg)
The Genesis® TD range of Valve Regulated Lead Acid (VRLA) front
terminal batteries has been designed to offer competitive solutions
for the global telecommunications and Information Technology
markets.
Genesis TD batteries incorporate selected design features for the
costconscious user, while retaining superior performance by weight
and volume, increased flexibility of installation and reduced
maintenance.
The Genesis TD battery range, comprises of three 12V batteries with
capacity sizes from 50 to 150Ah and features a front terminal design
for much easier installation. Terminal connectors are positioned at
the front of the cabinet. With no overhead access required, the
space between shelves can be reduced. The convenient front
terminal design saves valuable time through easier access.
Features and Benefits
Capacity range from 50 - 150Ah
12V batteries
Optimized for telecommunications applications
Front terminal design
Flame retardant UL94 V-0 container and lid
Visit us at www.enersys.comRESERVEPOWER Publication No: AS-TD-RS-001 - October 2013
Battery Range Summary
Telecommunications
TD
![Page 2: Battery Range Summary · The Genesis TD battery range, comprises of three 12V batteries with capacity sizes from 50 to 150Ah and features a front terminal design ... 10 hr rate 8](https://reader035.vdocument.in/reader035/viewer/2022070907/5f81282cfa05c44e265a5e23/html5/thumbnails/2.jpg)
General Specifications
Battery Terminal Layouts TerminalDetail Typical
12TD50F 6 12 50 58 277 106 222 17.212TD100F4 6 12 100 124 394 111 286 32.412TD150F 6 12 150 177 551 115 288 46.0
Nominal Capacity (Ah) Dimensions
10 hr rate 8 hr rateNumber Nominal to 1.80Vpc to 1.75Vpc Length Width Height Typical Weight
Cell Type of Cells Voltage @ 77°F (25ºC) @ 77°F (25ºC) mm mm mm kg
12TD50F 12TD100F4
12TD150FL ± 2 mm (.080 inches)
*L ± 1 mm (.040 inches)
Construction• Positive plates designed to extendservice life
• Separators constructed in low resistanceAbsorbed Glass Mat (AGM)
• Container and lid fabricated in toughABS UL94 flame retardant material
• Terminals manufactured with brassinserts for maximum conductivity andhighcompression grommet for long life
• Self-regulating pressure relief valveprevents ingress of atmospheric oxygen
Installation and Operation• The Genesis® TD battery range isdesigned for installation in outdoorcabinets or telecom standard racks
• Genesis TD batteries should be installedon their base
• Recommended charging voltages at77°F (25°C):Float use: 2.275 ± 0.02VpcCycle use: 2.45 ± 0.05Vpc
• Operating temperature:5ºF (-15ºC) to 113ºF (45ºC)Recommended temperature:68ºF (20ºC) to 77ºF (25ºC)
Standards• The management systems governingthe manufacture of this product areISO 9001:2008 and ISO 14001:2004certified
www.enersys.com Publication No: AS-TD-RS-001 - October 2013
EnerSys World Headquarters 2366 Bernville Road, Reading, PA 19605, USA Tel: +1-610-208-1991 / +1-800-538-3627
EnerSys EMEA EH Europe GmbH, Löwenstrasse 32, 8001 Zurich, Switzerland Tel: +41 44 215 7410
EnerSys Asia 152 Beach Road, Gateway East Building #11-03, Singapore 189721 Tel: +65 6508 1780© 2013 EnerSys. All rights reserved.Trademarks and logos are the property of EnerSys® and its affiliates unless otherwise noted.Subject to revisions without prior notice. E.&O.E.