BCGCA3004B. Construct Wall Framing. Wall Framing. Building Code of Australia states that All timber framing is to be done in accordance with AS 1682 This is an all encompassing standard which details the allowable construction methods. Wall Frame Members. - PowerPoint PPT Presentation

TRANSCRIPT

Page 1: BCGCA3004B

BCGCA3004BConstruct Wall Framing

Page 2: BCGCA3004B
Page 3: BCGCA3004B

Wall Framing

• Building Code of Australia states that

• All timber framing is to be done in accordance with AS 1682

• This is an all encompassing standard which details the allowable construction methods

Page 4: BCGCA3004B

Wall Frame Members

• Parts of a frame perform specific functions- supporting live & dead loads- resist Racking Forces- resist Overturning Forces- resist Sliding Forces- resist Uplift Forces -Most members provide a face to accept linings (this means that member sizes may be limited)

Page 5: BCGCA3004B

• Timbers Generally Used- Radiata Pine- Oregon (Douglas Fir)- Various Hardwood Species

• Various combinations of -timbers, -engineered wood products-materials such as steel

may be used WHY?

Page 6: BCGCA3004B

Structural Steel

Radiata Pine Studs

Engineered Timber (LVL) Lintels

Galvanized Steel Strap Bracing

Engineered Timber (I Beams) Deep Joists

Page 7: BCGCA3004B

• Other more exotic Timbers such as Cypress Pine may be used.

-Why?

Page 8: BCGCA3004B

Wall Frames• Frames are classified into 2 categories1. Load Bearing – They are structural frames, they

transfer loads from roof or upper floor to the supporting floor frame. They can be either external or internal walls.

2. Non Load Bearing –- do not support any structural loads.- They support their own weight- Non structural loads doors and frame, kitchen cupboards, driers etc. - support some live loads eg Doors closing.

Therefore there are some minimum requirements for theses AS 1684.2 cl 6.3.5

Page 9: BCGCA3004B

AS 1684.2 cl 6.3.5

Page 10: BCGCA3004B

Basic Frame Components

Refer page 187 TAFE Guide

Page 11: BCGCA3004B

Refer AS1684.2 cl 6.1.2

Page 12: BCGCA3004B

Frame Member Functions

Plates

•Horizontal members that form the top & bottom of the frame.•Bottom plate is usually 50mm for unseasoned timber 45mm for seasoned.•Top plate is usually the same section size as bottom plate.•For trussed roof top plates will be 75mm for unseasoned and 70mm for seasoned•Top plate may be made up by 2 x 38 (35)•Thicker top plates means that trusses or upper floor joists do not need to be placed direct over a stud

Page 13: BCGCA3004B
Page 14: BCGCA3004B

Plates AS 1684.2 cl 6.2.2

Page 15: BCGCA3004B

Studs• Vertical members placed between the plates• The set the wall height• Studs in external frames resist Wind Loads• Generally Stud sizes are 75mm or 100mm wide by

50mm or 38mm in unseasoned timbers and70mm or 90mm wide by 35mm or 45mm in seasoned timbers.

• Required Stud sizes can be found in AS 1684.2 Supplements

Page 16: BCGCA3004B

Studs Continued• Several Different types of Studs

- Common- Door & Window- Secondary Jamb Studs- Jack & Short

Page 17: BCGCA3004B

Trimmers

• Horizontal members fixed between window studs and door studs.

• Referred to as Sill or Head trimmers• Usually of the same section size bottom plates• Openings wider than 1800mm require

trimmers as specified in AS 1684.2 cl6.3.6.6 & table 6.3

Page 18: BCGCA3004B

Trimming Studs•Run from Trimmers to Plates•Used to block out Narrow Lintel•Where use in conjunction with Lintel they may take structural loads •Must be same depth as wall frame to accept finishes•May also be referred to as “Jack”, “Soldier”, or “Short” studs

Page 19: BCGCA3004B

Noggins

•Horizontal Member cut between studs to keep them - straight- evenly spaced- prevent twisting- allows studs to carry higher load- Maximum spacing 1350mm, there walls upto 2700mm require only 1 row of noggins

Page 20: BCGCA3004B

Noggins AS 1684.2 cl 6.2.1.5

Page 21: BCGCA3004B
Page 22: BCGCA3004B

Blocking

• Placed at intersections of wall frames• Normally 3 Blocks per intersection

Page 23: BCGCA3004B

Blocking AS1684.2

Page 24: BCGCA3004B

Lintels

• Also referred to as a Head• Horizontal Load Bearing Member between Studs• Purpose is to transfer loads to side of openings• May be made of many materials

- Timber- Engineered Timbers- Structural Steel or Cold Rolled Steel Sections

Page 25: BCGCA3004B
Page 26: BCGCA3004B
Page 27: BCGCA3004B

Bracing

• Provide lateral stability of Walls• Provide resistance against racking forces

induced direct wind loads• Provide resistance to Roof loads induced onto

top plates.

Page 28: BCGCA3004B

Bracing Methods

Timber Bracing – 50 to 75 mm x 19 to 25mm checked into and nailed flush into face of studs.

Braces must be installed in opposing pairs in external bracing walls.

This method is virtually never used today.

Rated 0.8 kN/m

Page 29: BCGCA3004B

Types of Bracing

Perforated Metal Bracing- Installed in similar method as timber brace with a saw cut into the plates and studs.

The brace is then nailed flush onto the studs and plates.Braces must be installed in opposing pairs in external walls.

Rated 0.8 kN/m

Page 30: BCGCA3004B
Page 31: BCGCA3004B

Types of Bracing

Page 32: BCGCA3004B
Page 33: BCGCA3004B

Types of Bracing

Flat Metal or Hoop Iron Bracing• 19mm Wide x 0.8mm• Zincalume• Two braces are fixed in

opposite directions• Fitted with Compression

Clamps

• Rated 1.5kN/m

Page 34: BCGCA3004B
Page 35: BCGCA3004B
Page 36: BCGCA3004B
Page 37: BCGCA3004B

Types of BracingSheet Bracing• Structural Plywood (Must be Stamped)• Hardboard (Masonite)• Fibre Cement• Resists Strong Wind Loads• Can be used on Narrow Panels – Why?• Usually on external walls in cavity – Why? • Minimum 7mm (Not Necessarily Correct)• Must be nailed off as per AS 1684.2 • Plate Steel can be used in High Wind Load Areas

Page 38: BCGCA3004B
Page 39: BCGCA3004B

Bracing AS 1684.2

Page 40: BCGCA3004B
Page 41: BCGCA3004B
Page 42: BCGCA3004B
Page 43: BCGCA3004B
Page 44: BCGCA3004B
Page 45: BCGCA3004B
Page 46: BCGCA3004B
Page 47: BCGCA3004B

Location of Bracing• AS 1684 cl 8.3.6.6 states

– Bracing should be evenly distributed and be provided in both directions

– Should be placed initially at corners

Page 48: BCGCA3004B
Page 49: BCGCA3004B

Spacing of Bracing Walls

• AS 1684.2 Cl 8.3.6.7 states– For Single Storey Building or Upper Storey of

Double Storey Buildings– Maximum distance between bracing wall shall be

9000mm for Wind Classifications up to N2

Page 50: BCGCA3004B
Page 51: BCGCA3004B
Page 52: BCGCA3004B
Page 53: BCGCA3004B
Page 54: BCGCA3004B
Page 55: BCGCA3004B
Page 56: BCGCA3004B
Page 57: BCGCA3004B
Page 58: BCGCA3004B
Page 59: BCGCA3004B
Page 60: BCGCA3004B
Page 61: BCGCA3004B
Page 62: BCGCA3004B

Plan & Prepare For Wall Framing

• Stress Grading of Individual Wall Frame Members

• Seasoned Or Unseasoned

Page 63: BCGCA3004B

Stress Grading

• Refers to the Timbers Strength• Timber must be able to withstand stress loads

placed on them.• Overloading may cause straining or failure• 3 types of stress

CompressiveTensileShear

Note Torsional Stress is not discussed

Page 64: BCGCA3004B
Page 65: BCGCA3004B
Page 66: BCGCA3004B

Stress Grading• Members Sizes will be determined for span

tables• Generally for Residential Construction sizes will

not be specified by designers

• Why?• Architect will not want to take responsibility• Engineer will want to charge extra to do this and • Why would a client want to pay for something

that he can get done for nothing

Page 67: BCGCA3004B

Stress Grading

• Why are members generally specified on Commercial projects

• AS 1684.2 Residential Timber Framed Construction Guide

Page 68: BCGCA3004B
Page 69: BCGCA3004B

AS 1684.2 Limitations1.4.4 The Maximum number of storey's of timber shall not exceed 2

1.4.5 The maximum width of a building shall 16 000mm, Note, if you use AS1684.2 simplified max width = 12 000mm

1.4.6 The maximum wall height shall be 3000mm excluding gable ends

1.4.7 The maximum roof pitch shall be 35 degrees

Page 70: BCGCA3004B
Page 71: BCGCA3004B

Structural pine grading A3P has announced that it will not proceed with the introduction of Structural Pine (SP) grading as previously planned.

Continuing contact with A3P members, timber merchants, truss and frame fabricators, designers and specifiers has indicated the introduction cannot be achieved without major disruption and unacceptable burden to industry.

Page 72: BCGCA3004B

Ordering Timber

• Timber is ordered in lineal metersmay be priced in cubic meters

• Increments of 300mm• Lengths over 3600mm are charged at higher rate• Timber should be ordered as required

- avoid unnecessary exposure to weather- affecting cash flows- theft- storage

Page 73: BCGCA3004B

Material Storage

• Timber should be stored on gluts

• This allows for airflow• Care should be taken

in stack sizes • Stacks can be

strapped for safety

Page 74: BCGCA3004B

Storage of Materials

• Timber should be stored as close as possible to work area

Page 75: BCGCA3004B
Page 76: BCGCA3004B
Page 77: BCGCA3004B
Page 78: BCGCA3004B
Page 79: BCGCA3004B
Page 80: BCGCA3004B
Page 81: BCGCA3004B

What is a Concentrated Load ?

Page 82: BCGCA3004B
Page 83: BCGCA3004B
Page 84: BCGCA3004B

Frame Construction

• Plates• The size of plates will depend on

1. Floor Joist Spacing2. Rafter / Truss Spacing3. Stud Spacing4. Single or Double Storey5. Stress Grade of Timber6. Roof Load Width ?

Page 85: BCGCA3004B

Roof Load Width (RLW)

Page 86: BCGCA3004B

Plates• Seasoned timbers are dressed therefore

trenching not required• Rough Sawn Timbers such as Oregon,

Hardwood require trenching.• Housing of plates for studs provides a

constant thickness• Trenching keeps Top & Bottom plates parallel• Restrains Unseasoned Studs from twisting

Page 87: BCGCA3004B

• Trenching usually appox 10 mm

• Trenching depth is not critical but what is left on is.

• Top Plates fully supported on masonary walls will be sized based on a 300mm spacing

Page 88: BCGCA3004B
Page 89: BCGCA3004B
Page 90: BCGCA3004B

Top Plates AS 1684.2

• cl 6.3.4. states that may be a minimum of 35 mm if1. not required to resist uplift forces (i.e trusses are nominally fixed and

2. Trusses or Rafters are located directly above studs or within 1.5 times the depth of the plate from the stud.

Page 91: BCGCA3004B

Joining of Plates

• Where plates are butt jointed they may be joined using a connector plate.

Page 92: BCGCA3004B

Joining of Plates

• Plates may be Scarfed or Lapped jointed.• Theses are time consuming and rarely used

Page 93: BCGCA3004B

Calculate Plate Lengths

• During Fabrication Top & Bottom Plates are the same length

• Plates should be as long as possible• Consider manpower available to stand frames• Remember Top Plate must be continuous

Page 94: BCGCA3004B
Page 95: BCGCA3004B

StudsStud Sizes are determined by1.Stress Grade2.Stud Spacing3.Rafter/ Truss spacing4.Wall Height5.Roof Load Width6.AS 1684.2 tables only specify 450mm or

600mm spacing. These are the most common spacing's

Page 96: BCGCA3004B

Stud SpacingStud Spacing Determined by1.Stress Grade2.Stud Spacing3.Rafter/ Truss spacing4.Wall Height5.Roof Load Width and6.If applicable External Sheeting Joints (ie Blue

Board etc)

Page 97: BCGCA3004B

Studs

• Not all external sheeting require critical stud placement

• Check with manufactures manual as to requirements

• Generally studs should be aligned with the internal face.

Page 98: BCGCA3004B

Harditek (Blue Board)

Page 99: BCGCA3004B

Studs• Stud sizes are determined from tables in AS

1684.2

Page 100: BCGCA3004B
Page 101: BCGCA3004B

Calculating Stud Length

• Finished Floor to Ceiling govern stud length• Minimum Habitable Room is 2400mm Clear• Floor Finishes

1. Carpet 20mm2. Timber Flooring 40mm (Depending on Batten)

• Ceilings1. 10mm Plasterboard2. 13mm Plasterboard

Page 102: BCGCA3004B

Calculating Stud Length

• Double Storey building may have FFL (Finished Floor Level).

• Allowance must be made for structural members

• Most Importantly Determine if there are any height restrictions

• Type of Roof Will affect Stud Heights

Page 103: BCGCA3004B

Top & Bottom Plates = 90 x 45 F5

Step 1 – Determine Floor & CeilingFloor Carpet = 20mmCeiling Gyprock = 13mm

Step 2 – Calculate Stud Length

Minimum Clearance = 2400mm Plus Flooring = 20mmPlus Ceiling = 20mm

Wall Height = 2440mmless Wall Plates = 90mm

Stud Length = 2350mm

Page 104: BCGCA3004B

Ground Floor

First Floor

Ground Fl Finish = Timber (40mm)First Floor = Carpet (20mm)Upper Level Joists = 200 x 50 F5Top & Bottom Plates = 90 x 45

Step 1- Determine SFL (Structural Floor Level)SFL First Floor = 28.950 (FFL First Fl)

-20 (Carpet) SFL= 28.930

SFL Ground Fl = 26.200 (FFL Gnd) - 40 (Timber)

SFL = 26.160Step 2 – Calculate Height Difference

SFL First Floor = 28.930 –SFL Ground Fl = 26.180Height Difference = 2.750

Page 105: BCGCA3004B

Step 3 – Structural Elements

Height Diff = 2.750Less Flooring = 0.017Less Floor Joist = 0.200Less T & B Plate = 0.090

Stud Length = 2.443Ground Floor

First Floor

Page 106: BCGCA3004B

Carpet Both Floors (20mm) Ceilings 10mm Plasterboard (Allow 20mm)Dimensions are clear measurementsLower level plates Upper Level PlatesBottom Plate = 90 x 35 F5 Bottom Plate = 90 x 45 F5Top Plate = 90 x 45 F5 Top Plate = 90 x 70 F5

Page 107: BCGCA3004B

Straightening of Studs

Page 108: BCGCA3004B
Page 109: BCGCA3004B

Calculating Door Heights

• On Concrete Slab• Using a standard 2040mm x 820mm • Allow 22mm for Carpet (17mm + 5mm)• 2040 mm Door Height• 2mm Clearance between Door & Jamb• 20mm for Jamb• 10mm Clearance between Jamb & Head• 15mm Clearance between Jamb & Lintel• Total = 2094mm Say 2100mm

Page 110: BCGCA3004B

Calculation of Door Width

Page 111: BCGCA3004B

Calculation of Window

•Check with manufacturer if windows are not on site•Generally at same height of doors•Check on elevations for window heights•15mm Clearance between Jamb & Lintel•Allow 10mm under sill

Page 112: BCGCA3004B

Window Width

•Care should be taken when setting out to brick bond!•Client may want window to line up with internal fitting •Client may want window dead center of room

Page 113: BCGCA3004B
Page 114: BCGCA3004B
Page 115: BCGCA3004B
Page 116: BCGCA3004B

Lintels

Page 117: BCGCA3004B
Page 118: BCGCA3004B
Page 119: BCGCA3004B
Page 120: BCGCA3004B
Page 121: BCGCA3004B

Construct Wall Frames

• Number Wall Frames• Clock Wise Direction• Internal Walls Left to Right• Top To Bottom

Page 122: BCGCA3004B

Setting Out Plates

• Confirm Dimensions of Slab/ SubfloorSelect Suitable Timber & Cut to LengthTack TogetherMark Appropriate ID Number on Plate

• Mark Required Studs – In Following OrderEnd StudsWall Intersections

Page 123: BCGCA3004B

Setting Out Plates

• If required prepare a storey rod with the appropriate markings (ie Horizontal & Vertical Bond)

• Set out position of window and doors studs remembering to allow for required jamb studs

• If required adjust position to match brickbond• Set out Common Studs, Jack Studs at required

spacing

Page 124: BCGCA3004B

Preparing Studs

• Use Storey Rod (Pattern Stud) to cut required studs

• Mark and check out window and door studs

Page 125: BCGCA3004B

Wall Frame Assembly

What are Advantages & Disadvantages of Prefabricated Wall Frames?

Page 126: BCGCA3004B

Assembling Wall Frames

Page 127: BCGCA3004B
Page 128: BCGCA3004B
Page 129: BCGCA3004B
Page 130: BCGCA3004B
Page 131: BCGCA3004B
Page 132: BCGCA3004B

Frame Erection

Page 133: BCGCA3004B
Page 134: BCGCA3004B
Page 135: BCGCA3004B
Page 136: BCGCA3004B
Page 137: BCGCA3004B

Nominal Fixings For Bottom Plates AS 1684.2

Page 138: BCGCA3004B
Page 139: BCGCA3004B
Page 140: BCGCA3004B
Page 141: BCGCA3004B
Page 142: BCGCA3004B
Page 143: BCGCA3004B

Bracing