bd01 system (40 a - 160 a) - · pdf filedescription bd01 system (40 a - 160 a) 4/4 siemens lv...

42
Siemens LV 70 · 2004 4/2 System overview 4/4 Description 4/7 Engineering Selection and ordering data 4/12 Straight trunking units, feeder units 4/13 Tap-off units for international use 4/19 Ancillary equipment units for international use 4/21 Tap-off units for Belgium 4/22 Ancillary equipment units for Belgium 4/23 Tap-off units for Denmark 4/24 Ancillary equipment units for Denmark 4/25 Tap-off units for Great Britain 4/27 Tap-off units for France 4/28 Tap-off units for Switzerland 4/28 Ancillary equipment units for Switzerland 4/29 Flexible junction unit, accessories 4/30 Technical data Dimension drawings 4/33 Straight trunking units, junction units 4/34 Feeder units 4/35 Tap-off units 4/40 Ancillary equipment units 4/41 Ancillary equipment units, accessories 4/42 Accessories BD01 System (40 A - 160 A)

Upload: dinhquynh

Post on 06-Mar-2018

218 views

Category:

Documents


4 download

TRANSCRIPT

Siemens LV 70 · 2004

4/2 System overview

4/4 Description

4/7 Engineering

Selection and ordering data4/12 Straight trunking units, feeder units4/13 Tap-off units for international use4/19 Ancillary equipment units

for international use4/21 Tap-off units for Belgium4/22 Ancillary equipment units for Belgium4/23 Tap-off units for Denmark4/24 Ancillary equipment units for Denmark4/25 Tap-off units for Great Britain4/27 Tap-off units for France4/28 Tap-off units for Switzerland4/28 Ancillary equipment units

for Switzerland4/29 Flexible junction unit, accessories

4/30 Technical data

Dimension drawings4/33 Straight trunking units, junction units 4/34 Feeder units4/35 Tap-off units4/40 Ancillary equipment units4/41 Ancillary equipment units, accessories4/42 Accessories

BD01 System (40 A - 160 A)

System Overview

Siemens LV 70 · 20044/2

BD01 System (40 A - 160 A)

4

6

3

1

2

4

4

4

5

System Overview

Siemens LV 70 · 2004 4/3

BD01 System (40 A - 160 A)

4

1 Straight trunking units5-conductor systemDegree of protection IP542 or 3 tap-off points at1m spacing4 or 6 tap-off points at0.5 m spacing2 m and 3 m lengths

a Page 4/12

2 Junction unitFlexible junction unit

a Page 4/29

3 Ancillary equipment unitsFor 4 or 8 MWWith or without component mounting unitWith or without sockets fitted

a Page 4/19

4 Tap-off unitsUp to 63 AWith components fitted or for installationof customer’s componentsFor 3, 4 or 8 MWWith or without component mounting unit

a Page 4/13

5 AccessoriesFixing and suspensionCoding set

a Page 4/29

6 Feeder unitsUniversal feeder unit

a Page 4/12

DescriptionBD01 System (40 A - 160 A)

Siemens LV 70 · 20044/4

4

• Type-tested low-voltage switchgear and controlgear assembly (TTA) to IEC/EN 60 439-1 and -2

• Flexible power supply• Junction units for changes in direction• Quick, straightforward planning• Time-saving assembly• Reliable mechanical and electrical connection technology• High level of stability, low weight• Positive opening and closing of the tap-off points• Versatile tap-off units• Few basic elements• Modular system reduces stock holding• High degree of protection to IP54 with tap-off points at sides and bottom for ex-

treme ambient conditions, otherwise IP50.

Trunking units are available in 2 m and 3 m lengths. They consist of a galvanized metal housing with a light grey (RAL 7035) paint finish and contain four busbars for L1, L2, L3 and N (aluminium conductors; copper for 160 A; silver-plated copper pick-up and connection contacts).The housing of the trunking unit also serves as PE conductor.Five current ratings are available in only one frame size: 40 A, 63 A, 100 A, 125 A and 160 A.The tap-off points are arranged on one side at intervals of 0.5 m or 1 m. The 2 m lengths have two or four tap-off points, the 3 m lengths three or six.

The tap-off points are touch-proof. They are opened automatically by the tap-off units and close by themselves when the tap-off units are removed.

Assembly of the trunking units, also with end flanges and feeder units, is fast and inherently secure. The trunking unit or end flange is simply inserted in the lower housing of the clamp terminal. Once the upper part of the clamp terminal or end flange, or the feeder unit is fitted, a secure connection is established by tightening the four screws. The PE path is established automatically when the housings are connected.An expansion compensation mechanism is built into the clamp terminal.

These flanges provide protection against direct contact at the ends of the busbar run.They are suitable for use with all BD01 systems.Two end flanges are supplied as standard with each feeder unit.

The junction units, which consist of flexible conductors, are available in versions for 100 A and 160 A and in lengths of 0.5 m and 1 m.The flexible junction units enable the direction of the busbar run to be changed as required. The 0.5 m version is recommanded for right angles, the 1 m version for fitting around obstacles or for adapting to variations in height.

Feeder units are available in two versions for 100 A and 160 A.They can be used as:

• Entry feeder units

• End feeder units

Features

Trunking units

Connections

L1L2L3N

PE

End flanges

Junction units

Feeder units

DescriptionBD01 System (40 A - 160 A)

Siemens LV 70 · 2004 4/5

4

• Centre feed

Two end flanges are included as standard with each unit.M32, M40 and M50 cable entries are possible from the four sides. For 160 A, an M63 cable gland can be fitted in a side. Plastic cable glands strain reliefmust be used (not included as standard).

Common features:• Insulated enclosure• Partially transparent cover for protective elements• Power pick-up via silver-plated horseshoe contacts• Reliable prevention of incorrect mounting• Cable entry is from one side only (use plastic cable glands with strain relief, not

included as standard).• The tap-off unit must first be removed from the trunking before it can be opened

and the cable can be connected.

Tap-off units with components fitted• One size for 1 cylinder fuse (10 38 mm), phase assignment L1, L2 or L3 freely

selectable• One size for 3 cylinder fuses (10 38 mm)• One size with 3 MW

(1 MW = 18 mm; MW = modular width)

Various versions with fuse bases, miniature circuit-breakers, Schuko and CEE sockets up to and including 32 A.

Tap-off units for free assignment• One size with 3 MW; can be operated from outside through flap incorporated in

cover (1 MW = 18 mm; MW = modular width).• Installation of devices (e.g. miniature circuit-breakers) in accordance with

DIN 43 871 possible up to and including 32 A.

Common features:• The enclosure is made from anodized aluminium and insulating material at both

ends.• A top-hat rail is built-in for component mounting.• Power pick-up via silver-plated horseshoe contacts• The tap-off unit can only be fitted to or removed from the tap-off point with its

cover open (contacts retracted).• Reliable prevention of incorrect mounting• Cable entry is possible from three directions (use plastic cable glands with strain

relief; not included as standard).• Can be combined with ancillary equipment units for additional functions.

Tap-off units with components fitted• Two sizes with 4 and 8 MW respectively (1 MW = 18 mm)• Various versions with fuse bases, miniature circuit-breakers, Schuko and

CEE sockets up to and including 63 A.• Versions with fitted miniature circuit-breaker have a component mounting unit.

Tap-off units for free assignment• Two sizes with 4 and eight 8 MW respectively (1 MW = 18 mm)• With or without component mounting unit for external operation (two sizes with

4 and 8 space units respectively)• Installation of devices (e.g. miniature circuit-breakers) in accordance with

DIN 43 871 possible up to and including 63 A.

Insulated tap-off units

Aluminium tap-off units

DescriptionBD01 System (40 A - 160 A)

Siemens LV 70 · 20044/6

4

Common features:• The enclosure is made from anodized aluminium and insulating material at both

ends.• Cable entry is possible from four sides (use plastic cable glands with strain relief;

not included as standard).• Can be combined with tap-off or feeder units• A top-hat rail is built-in for component mounting.• Two sizes with 4 and 8 MW respectively (1 MW = 18 mm; MW = modular width)• With or without Schuko or CEE sockets• With or without component mounting units for external operation

(two sizes with 4 and 8 MW respectively)• Installation of devices (e.g. fuse bases) in accordance with DIN 43 871 possible

up to and including 35 A.

Universal fixing bracketThe universal fixing bracket can be used for wall and ceiling mounting.The maximum fixing interval at normal mechanical loads is 3 m for edgewise and 1.5 m for flat mounting.At higher mechanical loads (e.g. pulling of plugs), an intermediate support with an additional fixing bracket at the trunking unit is recommended.Once the fixing point is decided, the tabs on the fixing bracket are pushed in to fix the trunking run.

Suspension bracketUse this bracket for suspension of flat-mounted trunking runs, and for increased mechanical rigidity fit it at the trunking unit connection points.

Fixing bracketThis bracket can be used for wall, ceiling and suspension mounting of the system. It can be fitted at any point of the trunking unit.The maximum fixing interval at normal mechanical loads is 3 m for edgewise and 1.5 m for flat mounting.At higher mechanical loads (e.g. pulling of plugs), an intermediate support with an additional fixing bracket at the trunking unit is recommended.

CodingThe systems can be coded for different frequencies or voltages. For this purpose, the BD01-K coding set can be fitted by the user to the installed system at each tap-off point. Four coding positions are possible.

Tap-off units can be coded on site by adapting the front face.

SealingEvery tap-off point on the trunking unit can be sealed.Feeder, junction, tap-off and ancillary equipment units can be made sealable with additional components (please enquire).

Cable glandsFor the feeder, tap-off and ancillary equipment units, use plastic cable glands with strain relief (not included as standard).

TerminalsWe recommend the use of Weidmüller or Phoenix screw terminals for the N and PE conductor connections in tap-off and ancillary equipment units.

Ancillary equipment units

Accessories

EngineeringBD01 System (40 A - 160 A)

Siemens LV 70 · 2004 4/7

4

Specimen text for tenders

Item Quantity Description Unit price Amount

... m Busbar trunking system (see Appendix for diagram)

• As “type-tested low-voltage switchgear and controlgear assembly” (TTA) to IEC/EN 60 439-1 and -2

• Rated current, corresponds with therm. rated current at max. +40 °C and +35 °C average over 24 h, for indoor installation

• Rated insulation voltage Ui = 400 V AC, 400 V DC;overvoltage category/pollution degree III/3

• Operational voltage ... V, ... Hz

• Rated peak withstand current of busbar trunking system,... kA tested to IEC/EN 60 439-1

• Degree of protection IP54 with tap-off points at sides and bottom, otherwise IP50

• 5-conductor system: L1, L2, L3, N, PE

• Busbars: silver-plated Cu connection and pick-up contacts; Al or Cu conductors; supported by insulated busbar supports

• Trunking units steel enclosed, galvanized and with paint finish; Colour: light grey, RAL 7035

• Busbar connection via clamp terminal with built-in expansion compensation

• Tap-off points: on one side, every 0.5 m or 1 m

• Supplied ready for connection, with all assembly parts

• Made by Siemens

• Type BD01-...

Consisting of:

EngineeringBD01 System (40 A - 160 A)

Siemens LV 70 · 20044/8

4

Wall or ceiling mounting with BD01-B

0.15 m

3 m

0.15 m

0.10

m

EngineeringBD01 System (40 A - 160 A)

Siemens LV 70 · 2004 4/9

4

Suspension using BD01-BAP (at connection points)

Fixing examples using BD01-B and BD01-BA

3 m=<

1.5 m

3 m

EngineeringBD01 System (40 A - 160 A)

Siemens LV 70 · 20044/10

4

• Installation flat or edgewise, horizontal or vertical, quantity, type and approximate ratings of prospective loads, cos ϕ

• Utilization factor and rated diversity factor = reduction factor α• If data are not available, use only the rated diversity factor• Feeding transformers (short-circuit current)• Nature of the installation site (dimensions, construction of the building,

transport paths, cellar)• Routing of supply lines from other power sources• Crane operation in installation area?• Special requirements

The operational current is calculated using the following formula:

If no data are available about the actual currents occurring simultaneously, the following table to IEC/EN 60 439-1 applies:

A system can be protected against short circuit alone, by fitting low-voltage h.b.c. fuses (gL) into the incoming supply; the fuse size to be appropriate for the prospective short-circuit current at the point of installation.

Due to their high response threshold (1.3 – 1.6 times rated current) and their long rupturing times at small overcurrents, fuses are not suitable for overload protection. The following can be used:

The prospective network short-circuit current and the let-through characteristic of the switches must be taken into account in each case.

Required details

Operational current

Iops = Operational current (A)Pinst = Installed power (kW)

α = Reduction factor

b = Supply factorb = 1 = Single end feedb = ½ = Double end feed

Ue = Rated operational voltage (V)cos ϕ = Power factor

Number of main circuits Rated diversity factor α

2 and 34 and 56 to 9 inclusive10 or more

0.90.80.70.6

Iops = Pinstx a x b x 103

3x Ux cos v

Short-circuit protection

Overcurrent protective devices for overload and short-circuit protection

System Overcurrent protective devices

Icc = 15 kA Icc = 25 kA

BD01-40 FAZ-3-B40 NZM7-40S

BD01-63 FAZ-3-B63 NZM7-63S

BD01-100 – NZM7-100S

BD01-125 – NZM7-125S

BD01-160 – NZM7-160S

Notes Icc = Rated conditional short-circuit current of the busbar trunking system and its outgoing circuits when protected by circuit-breakers.

EngineeringBD01 System (40 A - 160 A)

Siemens LV 70 · 2004 4/11

4

(Load distribution factor a = 1)

Temperature characteristic of BD01 systems

For long busbar runs, it may be necessary to calculate the voltage drop.

Factor “a” used in the equation for calculating the voltage drop is dependent on the load distribution.

Voltage drop at rated current

0.4 0.5 0.6 0.7 0.8 0.9 1

40 A

63 A

125 A

160 A

100 A

30

28

26

24

22

20

18

16

14

12

10

DU (V/100 m)

cos v

-5

130

120

110

100

90

80

70

5 15 25 35 45 55 65

Rated current (%)

Ambient temperature °C(average over 24 hours)

Voltage drop

∆U = Voltage drop (V)IB = Operational current (A)l = Length (m)a = Load distribution factorR = Ohmic resistance R20 (mΩ/m)X = Inductive reactance X20 (mΩ/m)cos ϕ = Power factor

Load distribution Factor a

Supply at AOne tap-off at B 1

Supply at ATap-off at B, C, D, E 0.5

Supply at ATap-off at B, C 0.25

Supply at ATap-off at B, C, D, E 0.125

Supply at ATap-off at C, D, E, F 0.25

DU = ax 3x IBx lx (Rx cos v + Xx sin v)x 10–3 (V)

AB

AEDCB

CAB

CEADB

A BFEDC

Selection and ordering dataTrunking Units, Feeder Units

Siemens LV 70 · 20044/12

BD01 System (40 A - 160 A)

4

Type PriceSee Price List

Rated current

Length Tap-off points

Tap-off point spacing

Article no. PS*

IeA m m

Straight trunking units

• Sheet steel housing• Can be coded• RAL 7035 (light grey)

40 3 6 0.5 BD01-40-3-0,5034253

1 unit

3 1 BD01-40-3-1233551

40 2 4 0.5 BD01-40-2-0,5034254

2 1 BD01-40-2-1233552

63 3 6 0.5 BD01-63-3-0,5034255

3 1 BD01-63-3-1233553

63 2 4 0.5 BD01-63-2-0,5034256

2 1 BD01-63-2-1233555

100 3 6 0.5 BD01-100-3-0,5034257

3 1 BD01-100-3-1233556

100 2 4 0.5 BD01-100-2-0,5034258

2 1 BD01-100-2-1233557

125 3 6 0.5 BD01-125-3-0,5090163

3 1 BD01-125-3-12335559

125 2 4 0.5 BD01-125-2-0,5090161

2 1 BD01-125-2-1233560

160 3 6 0.5 BD01-160-3-0,5090164

3 1 BD01-160-3-1233563

160 2 4 0.5 BD01-160-2-0,5090162

2 1 BD01-160-2-1233567

Type PriceSee PriceList

NotesCable cross-section

Rated current Article no. PS*

mm2IeA

Feeder units

• With 2 end flanges• Insulated housing. Can be fitted at all connection terminals

and the busbar run ends• Can be combined with BD01-GK... ancillary equipment units a Page 4/196 cable entries from 4 sides; 50 100 BD01-E

0342591 unit Use M32, 40, 50 plastic

cable glands with strain relief (not inclu-ded as standard).

Cable entry from 2 sides; 95 160 BD01-160-E090165

1 unit Use M63 plastic cable glands with strain relief(not included as standard).

* This quantity or a multiple thereof can be ordered.

Selection and ordering dataTap-Off Units for International Use

Siemens LV 70 · 2004 4/13

BD01 System (40 A - 160 A)

4

Type PriceSee Price List

NotesRated current

Rated operational voltage

Article no. PS*

IeA

UeV

Tap-off units (size 01)Fuse base• For one 10 x 38 mm cylinder fuse

16 400 BD01-AK01X/ZS087483

1 unit Fuse cartridges are not included as standard.Use plastic cable glands with strain relief (not included as standard)

Tap-off units (size 02)Fuse base• For three 10 x 38 mm cylinder fuses

32 400 BD01-AK02X/ZS3085090

1 unit

With component mounting unitWith 3-pole 16 A miniature circuit-breaker, characteristic B

16 400 BD01-AK02M0/A163085089

1 unit

With one 5-pole 16 ACEE socket

16 400 BD01-AK02M0/CEE165A163085092

1 unit

With 3-pole 32 A miniature circuit-breaker, characteristic C

32 400 BD01-AK02M0/A323085094

1 unit

* This quantity or a multiple thereof can be ordered.

Selection and ordering dataTap-Off Units for International Use

Siemens LV 70 · 20044/14

BD01 System (40 A - 160 A)

4

Type PriceSee Price List

NotesRated current

Rated operational voltage

Article no. PS*

IeA

UeV

Tap-off units (size 02)With component mounting unit Gauge ring/gauge screw, fuse cartridge

and screw cap are not included as standard.Use plastic cable glands with strain relief (not included as standard)

With 1-pole 16 A miniaturecircuit-breaker, characteristic B

With two Schuko sockets 16 A

16 230 BD01-AK02M0/2SD163A161085096

1 unit

With one 3-pole 16 ACEE socket

16 230 BD01-AK02M0/CEE163A161090170

1 unit

With 1-pole 16 A miniature circuit-breaker, characteristic B and 2-pole 16 A/30 mA RCCB with two 16 A Schuko sockets

16 230 BD01-AK02M0/2SD163FIA161090168

1 unit

With 1-pole 1 x D01 fuse baseWith two Schuko sockets 16 A 16 230 BD01-AK02M0/

2SD163S14085095

1 unit

With one 3-pole 16 ACEE socket

16 230 BD01-AK02M0/CEE163S14090169

1 unit

Freely assignable• (Pv max. 13 W)• 3 MW• Built-in top-hat rail

32 400 BD01-AK02M0/F085093

1 unit

* This quantity or a multiple thereof can be ordered.

Selection and ordering dataTap-Off Units for International Use

Siemens LV 70 · 2004 4/15

BD01 System (40 A - 160 A)

4

Type PriceSee Price List

NotesRated current

Rated operational voltage

Article no. PS*

IeA

UeV

Tap-off units (size 1)With 3-pole D01 fuse base• One 3 x D01 fuse base

16 400 BD01-AK1X/S14034264

1 unit Gauge ring/gauge screw, fuse cartridge and screw cap are not included as standard.Use plastic cable glands with strain relief (not included as standard)

With 3-pole D02 fuse base• One 3 x D02 fuse base

35 400 BD01-AK1X/S18034265

1 unit

With 1-pole D01 fuse baseWith two 16 A Schuko sockets 16 230 BD01-AK1X/

2SD163S14034268

1 unit

With one 3-pole 16 ACEE socket

16 230 BD01-AK1X/CEE163S14034270

1 unit

With 1-pole 16 A miniature circuit-breaker, characteristic B

With two 16 A Schuko sockets 16 230 BD01-AK1X/2SD163A161034269

1 unit

With one 3-pole 16 ACEE socket

16 230 BD01-AK1X/CEE163A161034271

1 unit

* This quantity or a multiple thereof can be ordered.

Selection and ordering dataTap-Off Units for International Use

Siemens LV 70 · 20044/16

BD01 System (40 A - 160 A)

4

Type PriceSee Price List

NotesRated current

Rated operational voltage

Article no. PS*

IeA

UeV

Tap-off units (size 1)Freely assignable• (Pv max. 13 W)• 4 MW• Built-in top-hat rail

35 400 BD01-AK1X/F034272

1 unit Gauge ring/gauge screw, fuse cartridge and screw cap are not included as standard.Use plastic cable glands with strain relief (not included as standard)

With component mounting unitWith three 1-pole 10 A miniature circuit-breakers, characteristic B

10 400 BD01-AK1M1/A101203098

1 unit

With three 1-pole 16 A miniature circuit-breakers, characteristic B

16 400 BD01-AK1M1/A161034266

With 3-pole 32 A miniature circuit-breaker, characteristic C

32 400 BD01-AK1M1/A323034267

Freely assignable• (Pv max. 13 W) • 4 MW• Built-in top-hat rail

35 400 BD01-AK1M1/F034273

* This quantity or a multiple thereof can be ordered.

Selection and ordering dataTap-Off Units for International Use

Siemens LV 70 · 2004 4/17

BD01 System (40 A - 160 A)

4

Type PriceSee Price List

NotesRated current

Rated operational voltage

Article no. PS*

IeA

UeV

Tap-off units (size 2)With 3-pole S27 fuse base

25 400 BD01-AK2X/S27034274

1 unit Gauge ring/gauge screw, fuse cartridge and screw cap are not included as standard.Use plastic cable glands with strain relief (not included as standard)

With 3-pole S27 fuse base

63 400 BD01-AK2X/S33233568

• Gauge screw system With 3-pole S27 fuse base

25 400 BD01-AK2X/S27/FORMP034275

With 3-pole S33 fuse base

63 400 BD01-AK2X/S33/FORMP233569

With two 1-pole D01 fuse bases• Four 16 A Schuko sockets

16 230 BD01-AK2X/4SD163S14034277

With three 1-pole D01 fuse bases• One 5-pole 16 A CEE sok-

ket

16 400 BD01-AK2X/CEE165S14034279

With three 1-pole D02 fuse bases• One 5-pole 32 A CEE sok-

ket

32 400 BD01-AK2X/CEE325S18034281

With two 1-pole 16 A miniature circuit-breakers, characteristic B• Four 16 A Schuko sockets

16 230 BD01-AK2X/4SD163A161034278

* This quantity or a multiple thereof can be ordered.

Selection and ordering dataTap-Off Units for International Use

Siemens LV 70 · 20044/18

BD01 System (40 A - 160 A)

4

Type PriceSee Price List

NotesPower Rated

currentRated operational voltage

Article no. PS*

Pv max.W

IeA

UeV

Tap-off units (size 2)Freely assignable• 8 MW• Built-in top-hat rail

16 35 400 BD01-AK2X/F034283

1 unit Gauge ring/gauge screw, fuse car-tridge and screw cap are not included as standard.Use plastic cable glands with strain relief (not included as standard)

22,5 63 400 BD01-AK2HX/F233570

1 unit

With component mounting unitWith 1-pole 16 A miniature circuit-breaker, B characteristic, and 2-pole 16 A/30 mA RCCBs• Two Schuko sockets

16 230 BD01-AK2M1/2SD163FIA161034276

1 unit

With 3-pole 16 A miniature circuit-breaker, C characteristic• One 5-pole 16 A CEE socket

16 400 BD01-AK2M1/CEE165A163034280

With 3-pole 32 A miniature circuit-breaker, C characteristic• One 5-pole 32 A CEE socket

32 400 BD01-AK2M1/CEE325A323034282

Freely assignable• 8 MW• Built-in top-hat rail

16 35 400 BD01-AK2M2/F034284

22,5 63 400 BD01-AK2HM2/F233571

* This quantity or a multiple thereof can be ordered.

Selection and ordering dataAncillary Equipment Units for International Use

Siemens LV 70 · 2004 4/19

BD01 System (40 A - 160 A)

4

Type PriceSee Price List

NotesArticle no. PS*

Ancillary equipment units (size 1)

Pv max. 13 W; Ue max. 400 VFreely assignable4 MWBuilt-in top-hat rail• For overvoltage protection• For remote control/remote switching• For PLCs• For electronic control equipment• For PKZ 0, etc.

BD01-GK1X/F034285

1 unit Including M50 cable grommet and screws for connecting the enclosure.Use plastic cable glands with strain relief (not included as standard)

With component mounting unit Freely assignable4 MWBuilt-in top-hat rail• For remote control/remote switching• For PLCs• For electronic control equipment• For PKZ 0 etc.

(With hinged flap to allow operator access to fitted components,e.g. miniature circuit-breakers)

BD01-GK1M1/F034286

1 unit

With four 16 A Schuko sockets BD01-GK1X/4SD163034287

1 unit

* This quantity or a multiple thereof can be ordered.

Selection and ordering dataAncillary Equipment Units for International Use

Siemens LV 70 · 20044/20

BD01 System (40 A - 160 A)

4

Type PriceSee Price List

NotesArticle no. PS*

Ancillary equipment units (size 2)

Pv max. 16 W; Ue max. 400 VFreely assignable8 MWBuilt-in top-hat rail• For overvoltage protection• For remote control/remote switching• For PLCs• For electronic control equipment• For PKZ 0 etc.

BD01-GK2X/F034288

1 unit Include M50 cable grommet and screws for connecting the enclosure.Use plastic cable glands with strain relief (not included as standard)

With component mounting unit Freely assignable8 MWBuilt-in top-hat rail• For remote control/remote switching• For PLCs• For electronic control equipment• For PKZ 0 etc.

(With hinged flap to allow operator access to fitted components, e.g. miniature circuit-breakers)

BD01-GK2M2/F034289

1 unit

With two 16 A Schuko sockets and one 5-pole 16 A CEE socket

BD01-GK2X/2SD163CEE165034291

With one 3-pole 16 A CEE socket and one 5-pole 16 A CEE socket

BD01-GK2X/CEE163CEE165034290

* This quantity or a multiple thereof can be ordered.

Selection and ordering dataTap-Off Units for Belgium

Siemens LV 70 · 2004 4/21

BD01 System (40 A - 160 A)

4

Type PriceSee Price List

NotesRated current

Rated operational voltage

Article no. PS*

IeA

UeV

Tap-off units (size 1)With 2-pole 16 A miniature circuit-breaker, C characteristic

Use plastic cable glands with strain relief (not included as standard)

With two 16 A sockets 16 230 BD01-AK1X/2PC163A162203115

1 unit

With one 3-pole 16 ACEE socket

16 230 BD01-AK1X/CEE163A162203114

1 unit

With component mounting unit

With 1-pole 16 A miniaturecircuit-breaker, C characteristic

16 230 BD01-AK1M1/A161/1203106

1 unit

With 2-pole 16 A miniaturecircuit-breaker, C characteristic

16 230 BD01-AK1M1/A162203110

With 3-pole 16 A miniaturecircuit-breaker, C characteristic

16 400 BD01-AK1M1/A163203107

With 3-pole and N 16 A miniaturecircuit-breaker, C characteristic

16 400 BD01-AK1M1/A163N203111

With 1-pole 20 A miniaturecircuit-breaker, C characteristic

20 230 BD01-AK1M1/A201203108

With 2-pole 20 A miniaturecircuit-breaker, C characteristic

20 230 BD01-AK1M1/A202203112

With 3-pole 20 A miniaturecircuit-breaker, C characteristic

20 400 BD01-AK1M1/A203203109

With 3-pole and N 20 A miniaturecircuit-breaker, C characteristic

20 400 BD01-AK1M1/A203N203113

* This quantity or a multiple thereof can be ordered.

Selection and ordering dataTap-Off Units, Ancillary Equipment Units for Belgium

Siemens LV 70 · 20044/22

BD01 System (40 A - 160 A)

4

Type PriceSee Price List

NotesRated current

Rated operational voltage

Article no. PS*

IeA

UeV

Tap-off units (size 2)With two 2-pole 16 A miniature circuit-breakers, B characteristicWith four 16 A sockets

16 230 BD01-AK2X/4PC163A162203116

1 unit M50 cable grommets and screws for connecting the enclosure are included as standard with ancillary equipment units.Use plastic cable glands with strain relief (not included as standard)

Ancillary equipment units (size 1)

Pv max. 13 W; Ue max. 400 VWith four 16 A sockets

BD01-GK1X/4PC163203117

1 unit

* This quantity or a multiple thereof can be ordered.

Selection and ordering dataTap-Off Units for Denmark

Siemens LV 70 · 2004 4/23

BD01 System (40 A - 160 A)

4

Type PriceSee Price List

NotesRated current

Rated operational voltage

Article no. PS*

IeA

UeV

Tap-off units (size 1)With 1-pole D01 fuse base• With two 10 A sockets

13 230 BD01-AK1X/2DKS103S14203099

1 unit Gauge ring/gauge screw, fuse cartridge and screw cap not included as standard with tap-off units.Use plastic cable glands with strain relief (not included as standard)

With 1-pole 13 A miniaturecircuit-breaker, C characteristic• With two 10 A sockets

13 230 BD01-AK1X/2DKS103A131203100

1 unit

Tap-off units (size 2)With two 1-pole D01 fuse bases• Four 10 A sockets

13 230 BD01-AK2X/4DKS103S14203102

1 unit

With two 1-pole 13 A miniature circuit-breakers, C characteristic• Four 10 A sockets

13 230 BD01-AK2X/4DKS103A131203103

1 unit

With component mounting unitWith 1-pole 13 A miniature circuit-breaker, C characteristic,and 2-pole 16 A/30 mA RCCB• Two 10 A sockets

13 230 BD01-AK2M1/2DKS103FIA131203101

1 unit

* This quantity or a multiple thereof can be ordered.

Selection and ordering dataAncillary Equipment Units for Denmark

Siemens LV 70 · 20044/24

BD01 System (40 A - 160 A)

4

Type PriceSee Price List

NotesArticle no. PS*

Ancillary equipment units (size 1)

Pv max. 13 W; Ue max. 400 V• With four 10 A sockets

BD01-GK1X/4DKS103203104

1 unit M50 cable grommets and screws for connecting the enclosure are included as standard with ancillary equipment units.Use plastic cable glands with strain relief (not included as standard)

Ancillary equipment units (size 2)

Pv max. 16 W; Ue max. 400 V• With two 10 A sockets

and one 5-pole 16 A CEE socket

BD01-GK2X/2DKS103CEE165203105

1 unit

* This quantity or a multiple thereof can be ordered.

Selection and ordering dataTap-Off Units for Great Britain

Siemens LV 70 · 2004 4/25

BD01 System (40 A - 160 A)

4

Type PriceSee Price List

NotesRated current

Rated operational voltage

Article no. PS*

IeA

UeV

Tap-off units (size 1)With 1-pole NNS-32 fuse base• One NNS-32 fuse base

32 230 BD01-AK1X/GB321203119

1 unit Fuse links are not included as standard.Use plastic cable glands with strain relief (not included as standard)

With 3-pole NNS-32 fuse base• One 3 x NNS-32 fuse base

32 400 BD01-AK1X/GB323203120

With 1-pole NNS-32 fuse base• With 2 13 A BS1363 sockets

13 230 BD01-AK1X/2BS133GB131203121

With 1-pole 13 A miniature circuit-breaker, B characteristic• With two 13 A BS1363 sockets

13 230 BD01-AK1X/2BS133A131203122

With component mounting unitWith three 1-pole 32 A miniature circuit-breakers, C characteristic

32 400 BD01-AK1M1/A321203118

* This quantity or a multiple thereof can be ordered.

Selection and ordering dataTap-Off Units for Great Britain

Siemens LV 70 · 20044/26

BD01 System (40 A - 160 A)

4

Type PriceSee Price List

NotesRated current

Rated operational voltage

Article no. PS*

IeA

UeV

Tap-off units (size 2)With three 1-pole NNS-32 fuse bases• One 5-pole 16 A CEE socket

16 400 BD01-AK2X/CEE165GB163203124

1 unit Fuse links are not included as standard.Use plastic cable glands with strain relief (not included as standard)

With three 1-pole NNS-32 fuse bases• One 5-pole 32 A CEE socket

32 400 BD01-AK2X/CEE325GB323203125

With component mounting unitWith 1-pole 13 A miniature circuit-breaker, B characteristic, and 2-pole 16 A/30 mA RCCB• One 13 A BS1363 socket

13 230 BD01-AK2M1/BS133FIA131203123

* This quantity or a multiple thereof can be ordered.

Selection and ordering dataTap-Off Units for France

Siemens LV 70 · 2004 4/27

BD01 System (40 A - 160 A)

4

Type PriceSee Price List

NotesRated current

Rated operational voltage

Article no. PS*

IeA

UeV

Tap-off units (size 2)With 3-pole SP51 fuse base• For three 14x 51 mm

cylinder fuses

32 400 BD01-AK2X/F1451203126

1 unit Fuse cartridges are not included as standard.Use plastic cable glands with strain relief (not included as standard)

With component mounting unitWith 2-pole 16 A miniaturecircuit-breaker, B characteristic, and2-pole 40 A/30 mA residual-current protective module• Two 16 A sockets

16 230 BD01-AK2M1/2PCUTE16AFI40214821

1 unit

* This quantity or a multiple thereof can be ordered.

Selection and ordering dataTap-Off Units, Ancillary Equipment Units for Switzerland

Siemens LV 70 · 20044/28

BD01 System (40 A - 160 A)

4

Type PriceSee Price List

NotesRated current

Rated operational voltage

Article no. PS*

IeA

UeV

Tap-off units (size 1)With 3-pole 10 A miniature circuit-breaker, B characteristic• One 5-pole 10 A socket, type 15

10 400 BD01-AK1X/15A103203128

1 unit M50 cable grommets and screws for connecting the enclosure are included as standard with ancillary equipment units.Use plastic cable glands with strain relief (not included as standard)

With 1-pole 10 A miniature circuit-breakers, B characteristic• Two 3-pole 10 A sockets, type 13

10 230 BD01-AK1X/2X13A101203130

1 unit

With 1-pole 16 A miniature circuit-breaker, B characteristic• Two 3-pole 10 A sockets, type 13

16 230 BD01-AK1X/2X13A161203129

1 unit

Tap-off units (size 2)With two 1-pole 16 A miniaturecircuit-breakers, B characteristic• Four 3-pole 10 A sockets, type 13

16 230 BD01-AK2X/4X13A161203132

1 unit

With component mounting unitWith 1-pole 16 A miniature circuit-breaker, B characteristic, and 2-po-le 16 A/30 mA RCCB• Two 3-pole 10 A sockets, type 13

16 230 BD01-AK2M1/2X13FIA161203131

1 unit

Ancillary equipment units (size 1)

Pv max. 13 W; Ue max. 400 V• Two 5-pole 10 A sockets, type 15

BD01-GK1X/2X15203133

1 unit

* This quantity or a multiple thereof can be ordered.

Selection and ordering dataJunction Units, Accessories

Siemens LV 70 · 2004 4/29

BD01 System (40 A - 160 A)

4

Type PriceSee Price List

Rated current

Length Article no. PS*

IeA m

Junction units

Flexible100 0.5 BD01-R1

0342601 unit

100 1 BD01-R2034261

160 0.5 BD01-160-R1090166

160 1 BD01-160-R2090167

Type PricSee Price List

Article no. PS*

AccessoriesUniversal fixing bracket BD01-B

0342621 unit

Fixing bracket BD01-BA081945

Suspension bracket• For suspension by cable or chain• At the connecting point

BD01-BAP203522

. Coding set4 coding positions

BD01-K034263

10 units

* This quantity or a multiple thereof can be ordered.

Technical Data

Siemens LV 70 · 20044/30

BD01 System (40 A - 160 A)

4

BD01-40 BD01-63 BD01-100

Current pathsRated insulation voltage Ui V AC/DC 400/400 400/400 400/400Overvoltage category/pollution degree

III/3 III/3 III/3

Rated operational voltage Ue V AC 400 400 400Frequency Hz 50 – 60 50 – 60 50 – 60Rated current Ieq therm. rated current at max. 40 °C and35 °C average over 24 hours

A 40 63 100

Impedance of conductors at 50 Hzand 20°C busbar temperature

Resistance R20 mO/m 3.960 1.936 0.938Reactance X20 mO/m 0.280 0.324 0.286Impedance Z20 mO/m 3.970 1.968 0.994

Impedance of conductors under fault conditions

AC resistance RF mO/m 5.991 4.128 2.841Reactance XF mO/m 1.396 1.248 1.186Impedance ZF mO/m 6.151 4.312 3.078

“Null” impedance tested to IEC 60 909, VDE 0102Resistance R0 Phase to N mO/m 15.904 7.911 4.115Reactance X0 Phase to N mO/m 2.128 2.058 1.797Impedance Z0 Phase to N mO/m 16.045 8.175 4.490Resistance R0 Phase to PE mO/m 10.086 8.565 6.648Reactance X0 Phase to PE mO/m 2.909 3.338 3.067Impedance Z0 Phase to PE mO/m 10.498 9.183 7.322

Short-circuit ratingRated peak withstand current Ipk kA 2.55 6.30 15.30Rated short-time withstand current Icw (t = 1 s) kA 0.58 1.15 2.50

Rated short-time withstand current Icw (t = 0.1 s) kA 1.70 4.20 9.00

Number of active conductors 4 4 4Conductor cross-section

L1, L2, L3 mm2 7.9 15.7 34.1N mm2 7.9 15.7 34.1PE (housing) q Cu mm2 20.0 20.0 20.0

Conductor material Al Al AlMax. interval between trunking unit supportsat normal mechanical load

Edgewise,flatflat withBD01-BAP

mmm

31.53

31.53

31.53

Combustive energy kWh/m 0.76 0.76 0.76

Tap-off unitsRated operational voltage Ue V 230 or 400Rated current Ie Max. A 63Switching capacity of the built-in switch-disconnector toIEC/EN 60 947-3 at 400 V

AC-20B

Technical Data

Siemens LV 70 · 2004 4/31

BD01 System (40 A - 160 A)

4

BD01-125 BD01-160 General technical data

400/400 400/400 Standards IEC/EN 60 439-1 and -2

Climatic proofing Damp heat, constant, to IEC 60 068-2-78Damp heat, cyclical, to IEC 60 068-2-30

Ambient temperatureMin./Max. °C −5/+40

Degree of protection IP54, IEC/EN 60 529Edgewise; tap-off points at the side; Flat; tap-off points at the bottomIP50Flat; tap-off points at the top

Mounting position Edgewise; tap-off points at the side; Flat; tap-off points at the bottom

Weights a Annex

Dimensions a Page 4/33

Material

Trunking units Galvanized, painted sheet steel

Busbars Al or Cu; Pick-up and connection contacts:Cu, silver-plated

Overload and short-circuit protectionBusbar trunking systems must be protected against overload and short circuits. Fuses and miniature circuit-breakers must be selected so that the admissible current carrying capacity corresponding with the ambient conditions is not exceeded. For overload and short-circuit protection, we recommend the use of motor-protective or standard circuit-breakers.

III/3 III/3

400 40050 – 60 50 – 60125 160

0.910 0.5780.300 0.2731.000 0.642

2.420 2.1890.940 0.9732.600 2.395

3.810 3.1671.630 1.6564.140 3.5745.430 5.3432.320 2.3555.910 5.839

15.30 15.302.50 2.50

9.00 9.00

4 4

34.1 34.134.1 34.120.0 20.0Al Cu31.53

31.53

0.76 0.76

Technical Data

Siemens LV 70 · 20044/32

BD01 System (40 A - 160 A)

4

Terminal capacities

Designation Type L1, L2, L3 N PEMin.mm2

Max. mm2

Min.mm2

Max. mm2

Min.mm2

Max. mm2

Feeder units BD01-E 6 (e, m) 50 (m) 6 (e, m) 50 (m) 6 (e, m) 50 (m)BD01-160-E 25 (m) 95 (m) 25 (m) 95 (m) 16 (m) 50 (m)

Tap-off units BD01-AK01X/ZS 0.75 (f, st) 10 (f, so, st) 0.75 (f, st) 10 (f, so, st) 0.75 (f, st) 10 (f, so, st)BD01-AK02X/ZS3 0.75 (f, st) 10 (f, so, st) 0.75 (f, st) 10 (f, so, st) 0.75 (f, st) 10 (f, so, st)BD01-AK02M0/A163 0.75 (so, st) 16 (so) 0.75 (f, st) 10 (f, so, st) 0.75 (f, st) 10 (f, so, st)BD01-AK02M0/A323 0.75 (so, st) 16 (so) 0.75 (f, st) 10 (f, so, st) 0.75 (f, st) 10 (f, so, st)BD01-AK1M1/A101 0.75 (so, st) 16 (so) 0.75 (so, f) 2.5 (so, f) 0.75 (so, f) 2.5 (so, f)BD01-AK1M1/A161 0.75 (so, st) 16 (so) 0.75 (so, f) 2.5 (so, f) 0.75 (so, f) 2.5 (so, f)BD01-AK1M1/A321 0.75 (so, st) 16 (so) 0.75 (so, f) 2.5 (so, f) 0.75 (so, f) 2.5 (so, f)BD01-AK1M1/A... 0.75 (so, st) 16 (so) 0.75 (f, st) 10 (f, so, st) 0.75 (so, st) 16 (so)BD01-AK1M1/A...N 0.75 (so, st) 16 (so) 0.75 (so, st) 16 (so) 0.75 (so, st) 16 (so)BD01-AK1X/S14 0.5 (f, st) 4 (so) 0.75 (f, st) 10 (f, so, st) 0.75 (so, st) 16 (so)BD01-AK1X/S18 0.5 (f, st) 16 (f, so, st) 0.75 (f, st) 10 (f, so, st) 0.75 (so, st) 16 (so)BD01-AK1X/GB... 0.75 (so, st) 16 (so) 0.75 (f, st) 10 (f, so, st) 0.75 (so, st) 16 (so)BD01-AK2X/F1451 0.75 (so, st) 16 (so) 0.75 (f, st) 10 (f, so, st) 0.75 (so, st) 16 (so)BD01-AK2X/S27 0.75 (f, st) 10 (f, so, st) 0.75 (f, st) 10 (f, so, st) 0.75 (so, st) 16 (so)BD01-AK2HX/S33 1.5 (f, st) 25 (f, so, st) 0.75 (f, st) 10 (f, so, st) 0.75 (so, st) 16 (so, st)

Notes so = solid, st = stranded, f = flexible with ferrule

Dimension drawingsStraight Trunking Units, Junction Units

Siemens LV 70 · 2004 4/33

BD01 System (40 A - 160 A)

4

Straight trunking units

BD01-...

Flexible junction units

BD01(...)-R.

l 57.5

50

5.5

25

90 77

57

125 4.5

250 a

5.5

n 125×

n a×

l a Number of tap-off points2000 500 4

1000 23000 500 6

1000 3

57.5 l

5092

l1

R 100

316

316

Type I I1 I2BD01-...-R1 500 165 316BD01-...-R2 1000 665 –

Dimension drawingsFeeder Units

Siemens LV 70 · 20044/34

BD01 System (40 A - 160 A)

4

Feeder units

BD01-E

BD01-160-E

170

104

1115

0

260

34.5

132

27

53

9

158

o 5.3

90

45

M32, M40, M50

20260

130

150

104

a

a

M63

End flange

Dimension drawingsTap-Off Units

Siemens LV 70 · 2004 4/35

BD01 System (40 A - 160 A)

4

Tap-off units

BD01-AK01X/ZS BD01-AK02X/ZS3

BD01-AK02M0/A163BD01-AK02M0/A323BD01-AK02M0/F

BD01-AK02M0/2SD163S14BD01-AK02M0/2SD163A161BD01-AK02M0/2SD163FIA161

77.5

100

116

10066

M25

77.5

200

100

116

14.5

9476

M25

70

200

26.526.7

118.

2

Dimension drawingsTap-Off Units

Siemens LV 70 · 20044/36

BD01 System (40 A - 160 A)

4

Tap-off units

BD01-AK02M0/CEE163S14BD01-AK02M0/CEE163A161

BD01-AK02M0/CEE165A163

100200

116

105

70

52

9094

38.5

200

105

100

116

70

52

102

94

38.5

Dimension drawingsTap-Off Units

Siemens LV 70 · 2004 4/37

BD01 System (40 A - 160 A)

4

Tap-off units

BD01-AK1X/S...BD01-AK1X/GB...BD01-AK1X/F

BD01-AK1M1/A...BD01-AK1M1/F

BD01-AK1X/2SD...BD01-AK1X/2BS...BD01-AK1X/2DKS...BD01-AK1X/2PC...BD01-AK1X/2X13...

BD01-AK1X/CEE163...BD01-AK1X/15...

Notes · · · · · · · Usable component fitting space

150

160

195

100

100 22.5

80

40 27

112

135

292

85

12

M25, 32, 40, 50

90

77

13 63

68

52

75.5

90

Dimension drawingsTap-Off Units

Siemens LV 70 · 20044/38

BD01 System (40 A - 160 A)

4

Tap-off units

BD01-AK2X/F..., BD01-AK2HX/F...BD01-AK2X/S..., BD01-AK2X/F...

BD01-AK2M2/FBD01-AK2HM2/F

BD01-AK2X/4SD..., BD01-AK2X/4DKS...BD01-AK2X/4PC..., BD01-AK2X/4X13...

Notes · · · · · · · Usable component fitting space

150

160

100

112

12

85

362

265

200

80

40 27

205

22.5

M25, 32, 40, 50

160

77 13

63

130

68

Dimension drawingsTap-Off Units

Siemens LV 70 · 2004 4/39

BD01 System (40 A - 160 A)

4

Tap-off units

BD01-AK2M1/BS...BD01-AK2M1/2SD...BD01-AK2M1/2DKS...BD01-AK2M1/2PC...BD01-AK2M1/2X13...

BD01-AK2M1/CEE165... BD01-AK2X/CEE165...

BD01-AK2M1/CEE325... BD01-AK2X/CEE325...

90

13

68

52

105

72.5

52

72.5

72.5

132

62

72.5

Dimension drawingsAncillary Equipment Units

Siemens LV 70 · 20044/40

BD01 System (40 A - 160 A)

4

Ancillary equipment units

BD01-GK1X/F BD01-GK1M1/F BD01-GK1X/4DKS103BD01-GK1X/4PC163BD01-GK1X/4SD163BD01-GK1X/2X15

BD01-GK2X/F BD01-GK2M2/F

Notes · · · · · · · Usable component fitting space

175

135

100

150

160

M25, 32, 40, 50

77

90

13

63

60.5

124.5

112

12

85

80

40

27

205

150

160

100

245

M25, 32, 40, 50

112

12142

150

160

245

77

Dimension drawingsAncillary Equipment Units, Accessories

Siemens LV 70 · 2004 4/41

BD01 System (40 A - 160 A)

4

Ancillary equipment units

BD01-GK2X/2SD163CEE165BD01-GK2X/2DKS103CEE165

BD01-GK2X/CEE163CEE165

Fixing brackets

BD01-B BD01-BA

105

84

179

13

52 63

70

174

52

75

103

25

112

132

105.5

27.5

4.5

∅ 9

50 115

135

15

27.5

10 10

49.5

52

59

91

10

10

∅ 9

Dimension drawingsAccessories

Siemens LV 70 · 20044/42

BD01 System (40 A - 160 A)

4

Suspension bracket

BD01-BAP

230 30

60

73

9

92

250

200

150

12

13

40

48