Siemens LV 70 · 2004
4/2 System overview
4/4 Description
4/7 Engineering
Selection and ordering data4/12 Straight trunking units, feeder units4/13 Tap-off units for international use4/19 Ancillary equipment units
for international use4/21 Tap-off units for Belgium4/22 Ancillary equipment units for Belgium4/23 Tap-off units for Denmark4/24 Ancillary equipment units for Denmark4/25 Tap-off units for Great Britain4/27 Tap-off units for France4/28 Tap-off units for Switzerland4/28 Ancillary equipment units
for Switzerland4/29 Flexible junction unit, accessories
4/30 Technical data
Dimension drawings4/33 Straight trunking units, junction units 4/34 Feeder units4/35 Tap-off units4/40 Ancillary equipment units4/41 Ancillary equipment units, accessories4/42 Accessories
BD01 System (40 A - 160 A)
System Overview
Siemens LV 70 · 2004 4/3
BD01 System (40 A - 160 A)
4
1 Straight trunking units5-conductor systemDegree of protection IP542 or 3 tap-off points at1m spacing4 or 6 tap-off points at0.5 m spacing2 m and 3 m lengths
a Page 4/12
2 Junction unitFlexible junction unit
a Page 4/29
3 Ancillary equipment unitsFor 4 or 8 MWWith or without component mounting unitWith or without sockets fitted
a Page 4/19
4 Tap-off unitsUp to 63 AWith components fitted or for installationof customer’s componentsFor 3, 4 or 8 MWWith or without component mounting unit
a Page 4/13
5 AccessoriesFixing and suspensionCoding set
a Page 4/29
6 Feeder unitsUniversal feeder unit
a Page 4/12
DescriptionBD01 System (40 A - 160 A)
Siemens LV 70 · 20044/4
4
• Type-tested low-voltage switchgear and controlgear assembly (TTA) to IEC/EN 60 439-1 and -2
• Flexible power supply• Junction units for changes in direction• Quick, straightforward planning• Time-saving assembly• Reliable mechanical and electrical connection technology• High level of stability, low weight• Positive opening and closing of the tap-off points• Versatile tap-off units• Few basic elements• Modular system reduces stock holding• High degree of protection to IP54 with tap-off points at sides and bottom for ex-
treme ambient conditions, otherwise IP50.
Trunking units are available in 2 m and 3 m lengths. They consist of a galvanized metal housing with a light grey (RAL 7035) paint finish and contain four busbars for L1, L2, L3 and N (aluminium conductors; copper for 160 A; silver-plated copper pick-up and connection contacts).The housing of the trunking unit also serves as PE conductor.Five current ratings are available in only one frame size: 40 A, 63 A, 100 A, 125 A and 160 A.The tap-off points are arranged on one side at intervals of 0.5 m or 1 m. The 2 m lengths have two or four tap-off points, the 3 m lengths three or six.
The tap-off points are touch-proof. They are opened automatically by the tap-off units and close by themselves when the tap-off units are removed.
Assembly of the trunking units, also with end flanges and feeder units, is fast and inherently secure. The trunking unit or end flange is simply inserted in the lower housing of the clamp terminal. Once the upper part of the clamp terminal or end flange, or the feeder unit is fitted, a secure connection is established by tightening the four screws. The PE path is established automatically when the housings are connected.An expansion compensation mechanism is built into the clamp terminal.
These flanges provide protection against direct contact at the ends of the busbar run.They are suitable for use with all BD01 systems.Two end flanges are supplied as standard with each feeder unit.
The junction units, which consist of flexible conductors, are available in versions for 100 A and 160 A and in lengths of 0.5 m and 1 m.The flexible junction units enable the direction of the busbar run to be changed as required. The 0.5 m version is recommanded for right angles, the 1 m version for fitting around obstacles or for adapting to variations in height.
Feeder units are available in two versions for 100 A and 160 A.They can be used as:
• Entry feeder units
• End feeder units
Features
Trunking units
Connections
L1L2L3N
PE
End flanges
Junction units
Feeder units
DescriptionBD01 System (40 A - 160 A)
Siemens LV 70 · 2004 4/5
4
• Centre feed
Two end flanges are included as standard with each unit.M32, M40 and M50 cable entries are possible from the four sides. For 160 A, an M63 cable gland can be fitted in a side. Plastic cable glands strain reliefmust be used (not included as standard).
Common features:• Insulated enclosure• Partially transparent cover for protective elements• Power pick-up via silver-plated horseshoe contacts• Reliable prevention of incorrect mounting• Cable entry is from one side only (use plastic cable glands with strain relief, not
included as standard).• The tap-off unit must first be removed from the trunking before it can be opened
and the cable can be connected.
Tap-off units with components fitted• One size for 1 cylinder fuse (10 38 mm), phase assignment L1, L2 or L3 freely
selectable• One size for 3 cylinder fuses (10 38 mm)• One size with 3 MW
(1 MW = 18 mm; MW = modular width)
Various versions with fuse bases, miniature circuit-breakers, Schuko and CEE sockets up to and including 32 A.
Tap-off units for free assignment• One size with 3 MW; can be operated from outside through flap incorporated in
cover (1 MW = 18 mm; MW = modular width).• Installation of devices (e.g. miniature circuit-breakers) in accordance with
DIN 43 871 possible up to and including 32 A.
Common features:• The enclosure is made from anodized aluminium and insulating material at both
ends.• A top-hat rail is built-in for component mounting.• Power pick-up via silver-plated horseshoe contacts• The tap-off unit can only be fitted to or removed from the tap-off point with its
cover open (contacts retracted).• Reliable prevention of incorrect mounting• Cable entry is possible from three directions (use plastic cable glands with strain
relief; not included as standard).• Can be combined with ancillary equipment units for additional functions.
Tap-off units with components fitted• Two sizes with 4 and 8 MW respectively (1 MW = 18 mm)• Various versions with fuse bases, miniature circuit-breakers, Schuko and
CEE sockets up to and including 63 A.• Versions with fitted miniature circuit-breaker have a component mounting unit.
Tap-off units for free assignment• Two sizes with 4 and eight 8 MW respectively (1 MW = 18 mm)• With or without component mounting unit for external operation (two sizes with
4 and 8 space units respectively)• Installation of devices (e.g. miniature circuit-breakers) in accordance with
DIN 43 871 possible up to and including 63 A.
Insulated tap-off units
Aluminium tap-off units
DescriptionBD01 System (40 A - 160 A)
Siemens LV 70 · 20044/6
4
Common features:• The enclosure is made from anodized aluminium and insulating material at both
ends.• Cable entry is possible from four sides (use plastic cable glands with strain relief;
not included as standard).• Can be combined with tap-off or feeder units• A top-hat rail is built-in for component mounting.• Two sizes with 4 and 8 MW respectively (1 MW = 18 mm; MW = modular width)• With or without Schuko or CEE sockets• With or without component mounting units for external operation
(two sizes with 4 and 8 MW respectively)• Installation of devices (e.g. fuse bases) in accordance with DIN 43 871 possible
up to and including 35 A.
Universal fixing bracketThe universal fixing bracket can be used for wall and ceiling mounting.The maximum fixing interval at normal mechanical loads is 3 m for edgewise and 1.5 m for flat mounting.At higher mechanical loads (e.g. pulling of plugs), an intermediate support with an additional fixing bracket at the trunking unit is recommended.Once the fixing point is decided, the tabs on the fixing bracket are pushed in to fix the trunking run.
Suspension bracketUse this bracket for suspension of flat-mounted trunking runs, and for increased mechanical rigidity fit it at the trunking unit connection points.
Fixing bracketThis bracket can be used for wall, ceiling and suspension mounting of the system. It can be fitted at any point of the trunking unit.The maximum fixing interval at normal mechanical loads is 3 m for edgewise and 1.5 m for flat mounting.At higher mechanical loads (e.g. pulling of plugs), an intermediate support with an additional fixing bracket at the trunking unit is recommended.
CodingThe systems can be coded for different frequencies or voltages. For this purpose, the BD01-K coding set can be fitted by the user to the installed system at each tap-off point. Four coding positions are possible.
Tap-off units can be coded on site by adapting the front face.
SealingEvery tap-off point on the trunking unit can be sealed.Feeder, junction, tap-off and ancillary equipment units can be made sealable with additional components (please enquire).
Cable glandsFor the feeder, tap-off and ancillary equipment units, use plastic cable glands with strain relief (not included as standard).
TerminalsWe recommend the use of Weidmüller or Phoenix screw terminals for the N and PE conductor connections in tap-off and ancillary equipment units.
Ancillary equipment units
Accessories
EngineeringBD01 System (40 A - 160 A)
Siemens LV 70 · 2004 4/7
4
Specimen text for tenders
Item Quantity Description Unit price Amount
... m Busbar trunking system (see Appendix for diagram)
• As “type-tested low-voltage switchgear and controlgear assembly” (TTA) to IEC/EN 60 439-1 and -2
• Rated current, corresponds with therm. rated current at max. +40 °C and +35 °C average over 24 h, for indoor installation
• Rated insulation voltage Ui = 400 V AC, 400 V DC;overvoltage category/pollution degree III/3
• Operational voltage ... V, ... Hz
• Rated peak withstand current of busbar trunking system,... kA tested to IEC/EN 60 439-1
• Degree of protection IP54 with tap-off points at sides and bottom, otherwise IP50
• 5-conductor system: L1, L2, L3, N, PE
• Busbars: silver-plated Cu connection and pick-up contacts; Al or Cu conductors; supported by insulated busbar supports
• Trunking units steel enclosed, galvanized and with paint finish; Colour: light grey, RAL 7035
• Busbar connection via clamp terminal with built-in expansion compensation
• Tap-off points: on one side, every 0.5 m or 1 m
• Supplied ready for connection, with all assembly parts
• Made by Siemens
• Type BD01-...
Consisting of:
EngineeringBD01 System (40 A - 160 A)
Siemens LV 70 · 20044/8
4
Wall or ceiling mounting with BD01-B
0.15 m
3 m
0.15 m
0.10
m
EngineeringBD01 System (40 A - 160 A)
Siemens LV 70 · 2004 4/9
4
Suspension using BD01-BAP (at connection points)
Fixing examples using BD01-B and BD01-BA
3 m=<
1.5 m
3 m
EngineeringBD01 System (40 A - 160 A)
Siemens LV 70 · 20044/10
4
• Installation flat or edgewise, horizontal or vertical, quantity, type and approximate ratings of prospective loads, cos ϕ
• Utilization factor and rated diversity factor = reduction factor α• If data are not available, use only the rated diversity factor• Feeding transformers (short-circuit current)• Nature of the installation site (dimensions, construction of the building,
transport paths, cellar)• Routing of supply lines from other power sources• Crane operation in installation area?• Special requirements
The operational current is calculated using the following formula:
If no data are available about the actual currents occurring simultaneously, the following table to IEC/EN 60 439-1 applies:
A system can be protected against short circuit alone, by fitting low-voltage h.b.c. fuses (gL) into the incoming supply; the fuse size to be appropriate for the prospective short-circuit current at the point of installation.
Due to their high response threshold (1.3 – 1.6 times rated current) and their long rupturing times at small overcurrents, fuses are not suitable for overload protection. The following can be used:
The prospective network short-circuit current and the let-through characteristic of the switches must be taken into account in each case.
Required details
Operational current
Iops = Operational current (A)Pinst = Installed power (kW)
α = Reduction factor
b = Supply factorb = 1 = Single end feedb = ½ = Double end feed
Ue = Rated operational voltage (V)cos ϕ = Power factor
Number of main circuits Rated diversity factor α
2 and 34 and 56 to 9 inclusive10 or more
0.90.80.70.6
Iops = Pinstx a x b x 103
3x Ux cos v
Short-circuit protection
Overcurrent protective devices for overload and short-circuit protection
System Overcurrent protective devices
Icc = 15 kA Icc = 25 kA
BD01-40 FAZ-3-B40 NZM7-40S
BD01-63 FAZ-3-B63 NZM7-63S
BD01-100 – NZM7-100S
BD01-125 – NZM7-125S
BD01-160 – NZM7-160S
Notes Icc = Rated conditional short-circuit current of the busbar trunking system and its outgoing circuits when protected by circuit-breakers.
EngineeringBD01 System (40 A - 160 A)
Siemens LV 70 · 2004 4/11
4
(Load distribution factor a = 1)
Temperature characteristic of BD01 systems
For long busbar runs, it may be necessary to calculate the voltage drop.
Factor “a” used in the equation for calculating the voltage drop is dependent on the load distribution.
Voltage drop at rated current
0.4 0.5 0.6 0.7 0.8 0.9 1
40 A
63 A
125 A
160 A
100 A
30
28
26
24
22
20
18
16
14
12
10
DU (V/100 m)
cos v
-5
130
120
110
100
90
80
70
5 15 25 35 45 55 65
Rated current (%)
Ambient temperature °C(average over 24 hours)
Voltage drop
∆U = Voltage drop (V)IB = Operational current (A)l = Length (m)a = Load distribution factorR = Ohmic resistance R20 (mΩ/m)X = Inductive reactance X20 (mΩ/m)cos ϕ = Power factor
Load distribution Factor a
Supply at AOne tap-off at B 1
Supply at ATap-off at B, C, D, E 0.5
Supply at ATap-off at B, C 0.25
Supply at ATap-off at B, C, D, E 0.125
Supply at ATap-off at C, D, E, F 0.25
DU = ax 3x IBx lx (Rx cos v + Xx sin v)x 10–3 (V)
AB
AEDCB
CAB
CEADB
A BFEDC
Selection and ordering dataTrunking Units, Feeder Units
Siemens LV 70 · 20044/12
BD01 System (40 A - 160 A)
4
Type PriceSee Price List
Rated current
Length Tap-off points
Tap-off point spacing
Article no. PS*
IeA m m
Straight trunking units
• Sheet steel housing• Can be coded• RAL 7035 (light grey)
40 3 6 0.5 BD01-40-3-0,5034253
1 unit
3 1 BD01-40-3-1233551
40 2 4 0.5 BD01-40-2-0,5034254
2 1 BD01-40-2-1233552
63 3 6 0.5 BD01-63-3-0,5034255
3 1 BD01-63-3-1233553
63 2 4 0.5 BD01-63-2-0,5034256
2 1 BD01-63-2-1233555
100 3 6 0.5 BD01-100-3-0,5034257
3 1 BD01-100-3-1233556
100 2 4 0.5 BD01-100-2-0,5034258
2 1 BD01-100-2-1233557
125 3 6 0.5 BD01-125-3-0,5090163
3 1 BD01-125-3-12335559
125 2 4 0.5 BD01-125-2-0,5090161
2 1 BD01-125-2-1233560
160 3 6 0.5 BD01-160-3-0,5090164
3 1 BD01-160-3-1233563
160 2 4 0.5 BD01-160-2-0,5090162
2 1 BD01-160-2-1233567
Type PriceSee PriceList
NotesCable cross-section
Rated current Article no. PS*
mm2IeA
Feeder units
• With 2 end flanges• Insulated housing. Can be fitted at all connection terminals
and the busbar run ends• Can be combined with BD01-GK... ancillary equipment units a Page 4/196 cable entries from 4 sides; 50 100 BD01-E
0342591 unit Use M32, 40, 50 plastic
cable glands with strain relief (not inclu-ded as standard).
Cable entry from 2 sides; 95 160 BD01-160-E090165
1 unit Use M63 plastic cable glands with strain relief(not included as standard).
* This quantity or a multiple thereof can be ordered.
Selection and ordering dataTap-Off Units for International Use
Siemens LV 70 · 2004 4/13
BD01 System (40 A - 160 A)
4
Type PriceSee Price List
NotesRated current
Rated operational voltage
Article no. PS*
IeA
UeV
Tap-off units (size 01)Fuse base• For one 10 x 38 mm cylinder fuse
16 400 BD01-AK01X/ZS087483
1 unit Fuse cartridges are not included as standard.Use plastic cable glands with strain relief (not included as standard)
Tap-off units (size 02)Fuse base• For three 10 x 38 mm cylinder fuses
32 400 BD01-AK02X/ZS3085090
1 unit
With component mounting unitWith 3-pole 16 A miniature circuit-breaker, characteristic B
16 400 BD01-AK02M0/A163085089
1 unit
With one 5-pole 16 ACEE socket
16 400 BD01-AK02M0/CEE165A163085092
1 unit
With 3-pole 32 A miniature circuit-breaker, characteristic C
32 400 BD01-AK02M0/A323085094
1 unit
* This quantity or a multiple thereof can be ordered.
Selection and ordering dataTap-Off Units for International Use
Siemens LV 70 · 20044/14
BD01 System (40 A - 160 A)
4
Type PriceSee Price List
NotesRated current
Rated operational voltage
Article no. PS*
IeA
UeV
Tap-off units (size 02)With component mounting unit Gauge ring/gauge screw, fuse cartridge
and screw cap are not included as standard.Use plastic cable glands with strain relief (not included as standard)
With 1-pole 16 A miniaturecircuit-breaker, characteristic B
With two Schuko sockets 16 A
16 230 BD01-AK02M0/2SD163A161085096
1 unit
With one 3-pole 16 ACEE socket
16 230 BD01-AK02M0/CEE163A161090170
1 unit
With 1-pole 16 A miniature circuit-breaker, characteristic B and 2-pole 16 A/30 mA RCCB with two 16 A Schuko sockets
16 230 BD01-AK02M0/2SD163FIA161090168
1 unit
With 1-pole 1 x D01 fuse baseWith two Schuko sockets 16 A 16 230 BD01-AK02M0/
2SD163S14085095
1 unit
With one 3-pole 16 ACEE socket
16 230 BD01-AK02M0/CEE163S14090169
1 unit
Freely assignable• (Pv max. 13 W)• 3 MW• Built-in top-hat rail
32 400 BD01-AK02M0/F085093
1 unit
* This quantity or a multiple thereof can be ordered.
Selection and ordering dataTap-Off Units for International Use
Siemens LV 70 · 2004 4/15
BD01 System (40 A - 160 A)
4
Type PriceSee Price List
NotesRated current
Rated operational voltage
Article no. PS*
IeA
UeV
Tap-off units (size 1)With 3-pole D01 fuse base• One 3 x D01 fuse base
16 400 BD01-AK1X/S14034264
1 unit Gauge ring/gauge screw, fuse cartridge and screw cap are not included as standard.Use plastic cable glands with strain relief (not included as standard)
With 3-pole D02 fuse base• One 3 x D02 fuse base
35 400 BD01-AK1X/S18034265
1 unit
With 1-pole D01 fuse baseWith two 16 A Schuko sockets 16 230 BD01-AK1X/
2SD163S14034268
1 unit
With one 3-pole 16 ACEE socket
16 230 BD01-AK1X/CEE163S14034270
1 unit
With 1-pole 16 A miniature circuit-breaker, characteristic B
With two 16 A Schuko sockets 16 230 BD01-AK1X/2SD163A161034269
1 unit
With one 3-pole 16 ACEE socket
16 230 BD01-AK1X/CEE163A161034271
1 unit
* This quantity or a multiple thereof can be ordered.
Selection and ordering dataTap-Off Units for International Use
Siemens LV 70 · 20044/16
BD01 System (40 A - 160 A)
4
Type PriceSee Price List
NotesRated current
Rated operational voltage
Article no. PS*
IeA
UeV
Tap-off units (size 1)Freely assignable• (Pv max. 13 W)• 4 MW• Built-in top-hat rail
35 400 BD01-AK1X/F034272
1 unit Gauge ring/gauge screw, fuse cartridge and screw cap are not included as standard.Use plastic cable glands with strain relief (not included as standard)
With component mounting unitWith three 1-pole 10 A miniature circuit-breakers, characteristic B
10 400 BD01-AK1M1/A101203098
1 unit
With three 1-pole 16 A miniature circuit-breakers, characteristic B
16 400 BD01-AK1M1/A161034266
With 3-pole 32 A miniature circuit-breaker, characteristic C
32 400 BD01-AK1M1/A323034267
Freely assignable• (Pv max. 13 W) • 4 MW• Built-in top-hat rail
35 400 BD01-AK1M1/F034273
* This quantity or a multiple thereof can be ordered.
Selection and ordering dataTap-Off Units for International Use
Siemens LV 70 · 2004 4/17
BD01 System (40 A - 160 A)
4
Type PriceSee Price List
NotesRated current
Rated operational voltage
Article no. PS*
IeA
UeV
Tap-off units (size 2)With 3-pole S27 fuse base
25 400 BD01-AK2X/S27034274
1 unit Gauge ring/gauge screw, fuse cartridge and screw cap are not included as standard.Use plastic cable glands with strain relief (not included as standard)
With 3-pole S27 fuse base
63 400 BD01-AK2X/S33233568
• Gauge screw system With 3-pole S27 fuse base
25 400 BD01-AK2X/S27/FORMP034275
With 3-pole S33 fuse base
63 400 BD01-AK2X/S33/FORMP233569
With two 1-pole D01 fuse bases• Four 16 A Schuko sockets
16 230 BD01-AK2X/4SD163S14034277
With three 1-pole D01 fuse bases• One 5-pole 16 A CEE sok-
ket
16 400 BD01-AK2X/CEE165S14034279
With three 1-pole D02 fuse bases• One 5-pole 32 A CEE sok-
ket
32 400 BD01-AK2X/CEE325S18034281
With two 1-pole 16 A miniature circuit-breakers, characteristic B• Four 16 A Schuko sockets
16 230 BD01-AK2X/4SD163A161034278
* This quantity or a multiple thereof can be ordered.
Selection and ordering dataTap-Off Units for International Use
Siemens LV 70 · 20044/18
BD01 System (40 A - 160 A)
4
Type PriceSee Price List
NotesPower Rated
currentRated operational voltage
Article no. PS*
Pv max.W
IeA
UeV
Tap-off units (size 2)Freely assignable• 8 MW• Built-in top-hat rail
16 35 400 BD01-AK2X/F034283
1 unit Gauge ring/gauge screw, fuse car-tridge and screw cap are not included as standard.Use plastic cable glands with strain relief (not included as standard)
22,5 63 400 BD01-AK2HX/F233570
1 unit
With component mounting unitWith 1-pole 16 A miniature circuit-breaker, B characteristic, and 2-pole 16 A/30 mA RCCBs• Two Schuko sockets
16 230 BD01-AK2M1/2SD163FIA161034276
1 unit
With 3-pole 16 A miniature circuit-breaker, C characteristic• One 5-pole 16 A CEE socket
16 400 BD01-AK2M1/CEE165A163034280
With 3-pole 32 A miniature circuit-breaker, C characteristic• One 5-pole 32 A CEE socket
32 400 BD01-AK2M1/CEE325A323034282
Freely assignable• 8 MW• Built-in top-hat rail
16 35 400 BD01-AK2M2/F034284
22,5 63 400 BD01-AK2HM2/F233571
* This quantity or a multiple thereof can be ordered.
Selection and ordering dataAncillary Equipment Units for International Use
Siemens LV 70 · 2004 4/19
BD01 System (40 A - 160 A)
4
Type PriceSee Price List
NotesArticle no. PS*
Ancillary equipment units (size 1)
Pv max. 13 W; Ue max. 400 VFreely assignable4 MWBuilt-in top-hat rail• For overvoltage protection• For remote control/remote switching• For PLCs• For electronic control equipment• For PKZ 0, etc.
BD01-GK1X/F034285
1 unit Including M50 cable grommet and screws for connecting the enclosure.Use plastic cable glands with strain relief (not included as standard)
With component mounting unit Freely assignable4 MWBuilt-in top-hat rail• For remote control/remote switching• For PLCs• For electronic control equipment• For PKZ 0 etc.
(With hinged flap to allow operator access to fitted components,e.g. miniature circuit-breakers)
BD01-GK1M1/F034286
1 unit
With four 16 A Schuko sockets BD01-GK1X/4SD163034287
1 unit
* This quantity or a multiple thereof can be ordered.
Selection and ordering dataAncillary Equipment Units for International Use
Siemens LV 70 · 20044/20
BD01 System (40 A - 160 A)
4
Type PriceSee Price List
NotesArticle no. PS*
Ancillary equipment units (size 2)
Pv max. 16 W; Ue max. 400 VFreely assignable8 MWBuilt-in top-hat rail• For overvoltage protection• For remote control/remote switching• For PLCs• For electronic control equipment• For PKZ 0 etc.
BD01-GK2X/F034288
1 unit Include M50 cable grommet and screws for connecting the enclosure.Use plastic cable glands with strain relief (not included as standard)
With component mounting unit Freely assignable8 MWBuilt-in top-hat rail• For remote control/remote switching• For PLCs• For electronic control equipment• For PKZ 0 etc.
(With hinged flap to allow operator access to fitted components, e.g. miniature circuit-breakers)
BD01-GK2M2/F034289
1 unit
With two 16 A Schuko sockets and one 5-pole 16 A CEE socket
BD01-GK2X/2SD163CEE165034291
With one 3-pole 16 A CEE socket and one 5-pole 16 A CEE socket
BD01-GK2X/CEE163CEE165034290
* This quantity or a multiple thereof can be ordered.
Selection and ordering dataTap-Off Units for Belgium
Siemens LV 70 · 2004 4/21
BD01 System (40 A - 160 A)
4
Type PriceSee Price List
NotesRated current
Rated operational voltage
Article no. PS*
IeA
UeV
Tap-off units (size 1)With 2-pole 16 A miniature circuit-breaker, C characteristic
Use plastic cable glands with strain relief (not included as standard)
With two 16 A sockets 16 230 BD01-AK1X/2PC163A162203115
1 unit
With one 3-pole 16 ACEE socket
16 230 BD01-AK1X/CEE163A162203114
1 unit
With component mounting unit
With 1-pole 16 A miniaturecircuit-breaker, C characteristic
16 230 BD01-AK1M1/A161/1203106
1 unit
With 2-pole 16 A miniaturecircuit-breaker, C characteristic
16 230 BD01-AK1M1/A162203110
With 3-pole 16 A miniaturecircuit-breaker, C characteristic
16 400 BD01-AK1M1/A163203107
With 3-pole and N 16 A miniaturecircuit-breaker, C characteristic
16 400 BD01-AK1M1/A163N203111
With 1-pole 20 A miniaturecircuit-breaker, C characteristic
20 230 BD01-AK1M1/A201203108
With 2-pole 20 A miniaturecircuit-breaker, C characteristic
20 230 BD01-AK1M1/A202203112
With 3-pole 20 A miniaturecircuit-breaker, C characteristic
20 400 BD01-AK1M1/A203203109
With 3-pole and N 20 A miniaturecircuit-breaker, C characteristic
20 400 BD01-AK1M1/A203N203113
* This quantity or a multiple thereof can be ordered.
Selection and ordering dataTap-Off Units, Ancillary Equipment Units for Belgium
Siemens LV 70 · 20044/22
BD01 System (40 A - 160 A)
4
Type PriceSee Price List
NotesRated current
Rated operational voltage
Article no. PS*
IeA
UeV
Tap-off units (size 2)With two 2-pole 16 A miniature circuit-breakers, B characteristicWith four 16 A sockets
16 230 BD01-AK2X/4PC163A162203116
1 unit M50 cable grommets and screws for connecting the enclosure are included as standard with ancillary equipment units.Use plastic cable glands with strain relief (not included as standard)
Ancillary equipment units (size 1)
Pv max. 13 W; Ue max. 400 VWith four 16 A sockets
BD01-GK1X/4PC163203117
1 unit
* This quantity or a multiple thereof can be ordered.
Selection and ordering dataTap-Off Units for Denmark
Siemens LV 70 · 2004 4/23
BD01 System (40 A - 160 A)
4
Type PriceSee Price List
NotesRated current
Rated operational voltage
Article no. PS*
IeA
UeV
Tap-off units (size 1)With 1-pole D01 fuse base• With two 10 A sockets
13 230 BD01-AK1X/2DKS103S14203099
1 unit Gauge ring/gauge screw, fuse cartridge and screw cap not included as standard with tap-off units.Use plastic cable glands with strain relief (not included as standard)
With 1-pole 13 A miniaturecircuit-breaker, C characteristic• With two 10 A sockets
13 230 BD01-AK1X/2DKS103A131203100
1 unit
Tap-off units (size 2)With two 1-pole D01 fuse bases• Four 10 A sockets
13 230 BD01-AK2X/4DKS103S14203102
1 unit
With two 1-pole 13 A miniature circuit-breakers, C characteristic• Four 10 A sockets
13 230 BD01-AK2X/4DKS103A131203103
1 unit
With component mounting unitWith 1-pole 13 A miniature circuit-breaker, C characteristic,and 2-pole 16 A/30 mA RCCB• Two 10 A sockets
13 230 BD01-AK2M1/2DKS103FIA131203101
1 unit
* This quantity or a multiple thereof can be ordered.
Selection and ordering dataAncillary Equipment Units for Denmark
Siemens LV 70 · 20044/24
BD01 System (40 A - 160 A)
4
Type PriceSee Price List
NotesArticle no. PS*
Ancillary equipment units (size 1)
Pv max. 13 W; Ue max. 400 V• With four 10 A sockets
BD01-GK1X/4DKS103203104
1 unit M50 cable grommets and screws for connecting the enclosure are included as standard with ancillary equipment units.Use plastic cable glands with strain relief (not included as standard)
Ancillary equipment units (size 2)
Pv max. 16 W; Ue max. 400 V• With two 10 A sockets
and one 5-pole 16 A CEE socket
BD01-GK2X/2DKS103CEE165203105
1 unit
* This quantity or a multiple thereof can be ordered.
Selection and ordering dataTap-Off Units for Great Britain
Siemens LV 70 · 2004 4/25
BD01 System (40 A - 160 A)
4
Type PriceSee Price List
NotesRated current
Rated operational voltage
Article no. PS*
IeA
UeV
Tap-off units (size 1)With 1-pole NNS-32 fuse base• One NNS-32 fuse base
32 230 BD01-AK1X/GB321203119
1 unit Fuse links are not included as standard.Use plastic cable glands with strain relief (not included as standard)
With 3-pole NNS-32 fuse base• One 3 x NNS-32 fuse base
32 400 BD01-AK1X/GB323203120
With 1-pole NNS-32 fuse base• With 2 13 A BS1363 sockets
13 230 BD01-AK1X/2BS133GB131203121
With 1-pole 13 A miniature circuit-breaker, B characteristic• With two 13 A BS1363 sockets
13 230 BD01-AK1X/2BS133A131203122
With component mounting unitWith three 1-pole 32 A miniature circuit-breakers, C characteristic
32 400 BD01-AK1M1/A321203118
* This quantity or a multiple thereof can be ordered.
Selection and ordering dataTap-Off Units for Great Britain
Siemens LV 70 · 20044/26
BD01 System (40 A - 160 A)
4
Type PriceSee Price List
NotesRated current
Rated operational voltage
Article no. PS*
IeA
UeV
Tap-off units (size 2)With three 1-pole NNS-32 fuse bases• One 5-pole 16 A CEE socket
16 400 BD01-AK2X/CEE165GB163203124
1 unit Fuse links are not included as standard.Use plastic cable glands with strain relief (not included as standard)
With three 1-pole NNS-32 fuse bases• One 5-pole 32 A CEE socket
32 400 BD01-AK2X/CEE325GB323203125
With component mounting unitWith 1-pole 13 A miniature circuit-breaker, B characteristic, and 2-pole 16 A/30 mA RCCB• One 13 A BS1363 socket
13 230 BD01-AK2M1/BS133FIA131203123
* This quantity or a multiple thereof can be ordered.
Selection and ordering dataTap-Off Units for France
Siemens LV 70 · 2004 4/27
BD01 System (40 A - 160 A)
4
Type PriceSee Price List
NotesRated current
Rated operational voltage
Article no. PS*
IeA
UeV
Tap-off units (size 2)With 3-pole SP51 fuse base• For three 14x 51 mm
cylinder fuses
32 400 BD01-AK2X/F1451203126
1 unit Fuse cartridges are not included as standard.Use plastic cable glands with strain relief (not included as standard)
With component mounting unitWith 2-pole 16 A miniaturecircuit-breaker, B characteristic, and2-pole 40 A/30 mA residual-current protective module• Two 16 A sockets
16 230 BD01-AK2M1/2PCUTE16AFI40214821
1 unit
* This quantity or a multiple thereof can be ordered.
Selection and ordering dataTap-Off Units, Ancillary Equipment Units for Switzerland
Siemens LV 70 · 20044/28
BD01 System (40 A - 160 A)
4
Type PriceSee Price List
NotesRated current
Rated operational voltage
Article no. PS*
IeA
UeV
Tap-off units (size 1)With 3-pole 10 A miniature circuit-breaker, B characteristic• One 5-pole 10 A socket, type 15
10 400 BD01-AK1X/15A103203128
1 unit M50 cable grommets and screws for connecting the enclosure are included as standard with ancillary equipment units.Use plastic cable glands with strain relief (not included as standard)
With 1-pole 10 A miniature circuit-breakers, B characteristic• Two 3-pole 10 A sockets, type 13
10 230 BD01-AK1X/2X13A101203130
1 unit
With 1-pole 16 A miniature circuit-breaker, B characteristic• Two 3-pole 10 A sockets, type 13
16 230 BD01-AK1X/2X13A161203129
1 unit
Tap-off units (size 2)With two 1-pole 16 A miniaturecircuit-breakers, B characteristic• Four 3-pole 10 A sockets, type 13
16 230 BD01-AK2X/4X13A161203132
1 unit
With component mounting unitWith 1-pole 16 A miniature circuit-breaker, B characteristic, and 2-po-le 16 A/30 mA RCCB• Two 3-pole 10 A sockets, type 13
16 230 BD01-AK2M1/2X13FIA161203131
1 unit
Ancillary equipment units (size 1)
Pv max. 13 W; Ue max. 400 V• Two 5-pole 10 A sockets, type 15
BD01-GK1X/2X15203133
1 unit
* This quantity or a multiple thereof can be ordered.
Selection and ordering dataJunction Units, Accessories
Siemens LV 70 · 2004 4/29
BD01 System (40 A - 160 A)
4
Type PriceSee Price List
Rated current
Length Article no. PS*
IeA m
Junction units
Flexible100 0.5 BD01-R1
0342601 unit
100 1 BD01-R2034261
160 0.5 BD01-160-R1090166
160 1 BD01-160-R2090167
Type PricSee Price List
Article no. PS*
AccessoriesUniversal fixing bracket BD01-B
0342621 unit
Fixing bracket BD01-BA081945
Suspension bracket• For suspension by cable or chain• At the connecting point
BD01-BAP203522
. Coding set4 coding positions
BD01-K034263
10 units
* This quantity or a multiple thereof can be ordered.
Technical Data
Siemens LV 70 · 20044/30
BD01 System (40 A - 160 A)
4
BD01-40 BD01-63 BD01-100
Current pathsRated insulation voltage Ui V AC/DC 400/400 400/400 400/400Overvoltage category/pollution degree
III/3 III/3 III/3
Rated operational voltage Ue V AC 400 400 400Frequency Hz 50 – 60 50 – 60 50 – 60Rated current Ieq therm. rated current at max. 40 °C and35 °C average over 24 hours
A 40 63 100
Impedance of conductors at 50 Hzand 20°C busbar temperature
Resistance R20 mO/m 3.960 1.936 0.938Reactance X20 mO/m 0.280 0.324 0.286Impedance Z20 mO/m 3.970 1.968 0.994
Impedance of conductors under fault conditions
AC resistance RF mO/m 5.991 4.128 2.841Reactance XF mO/m 1.396 1.248 1.186Impedance ZF mO/m 6.151 4.312 3.078
“Null” impedance tested to IEC 60 909, VDE 0102Resistance R0 Phase to N mO/m 15.904 7.911 4.115Reactance X0 Phase to N mO/m 2.128 2.058 1.797Impedance Z0 Phase to N mO/m 16.045 8.175 4.490Resistance R0 Phase to PE mO/m 10.086 8.565 6.648Reactance X0 Phase to PE mO/m 2.909 3.338 3.067Impedance Z0 Phase to PE mO/m 10.498 9.183 7.322
Short-circuit ratingRated peak withstand current Ipk kA 2.55 6.30 15.30Rated short-time withstand current Icw (t = 1 s) kA 0.58 1.15 2.50
Rated short-time withstand current Icw (t = 0.1 s) kA 1.70 4.20 9.00
Number of active conductors 4 4 4Conductor cross-section
L1, L2, L3 mm2 7.9 15.7 34.1N mm2 7.9 15.7 34.1PE (housing) q Cu mm2 20.0 20.0 20.0
Conductor material Al Al AlMax. interval between trunking unit supportsat normal mechanical load
Edgewise,flatflat withBD01-BAP
mmm
31.53
31.53
31.53
Combustive energy kWh/m 0.76 0.76 0.76
Tap-off unitsRated operational voltage Ue V 230 or 400Rated current Ie Max. A 63Switching capacity of the built-in switch-disconnector toIEC/EN 60 947-3 at 400 V
AC-20B
Technical Data
Siemens LV 70 · 2004 4/31
BD01 System (40 A - 160 A)
4
BD01-125 BD01-160 General technical data
400/400 400/400 Standards IEC/EN 60 439-1 and -2
Climatic proofing Damp heat, constant, to IEC 60 068-2-78Damp heat, cyclical, to IEC 60 068-2-30
Ambient temperatureMin./Max. °C −5/+40
Degree of protection IP54, IEC/EN 60 529Edgewise; tap-off points at the side; Flat; tap-off points at the bottomIP50Flat; tap-off points at the top
Mounting position Edgewise; tap-off points at the side; Flat; tap-off points at the bottom
Weights a Annex
Dimensions a Page 4/33
Material
Trunking units Galvanized, painted sheet steel
Busbars Al or Cu; Pick-up and connection contacts:Cu, silver-plated
Overload and short-circuit protectionBusbar trunking systems must be protected against overload and short circuits. Fuses and miniature circuit-breakers must be selected so that the admissible current carrying capacity corresponding with the ambient conditions is not exceeded. For overload and short-circuit protection, we recommend the use of motor-protective or standard circuit-breakers.
III/3 III/3
400 40050 – 60 50 – 60125 160
0.910 0.5780.300 0.2731.000 0.642
2.420 2.1890.940 0.9732.600 2.395
3.810 3.1671.630 1.6564.140 3.5745.430 5.3432.320 2.3555.910 5.839
15.30 15.302.50 2.50
9.00 9.00
4 4
34.1 34.134.1 34.120.0 20.0Al Cu31.53
31.53
0.76 0.76
Technical Data
Siemens LV 70 · 20044/32
BD01 System (40 A - 160 A)
4
Terminal capacities
Designation Type L1, L2, L3 N PEMin.mm2
Max. mm2
Min.mm2
Max. mm2
Min.mm2
Max. mm2
Feeder units BD01-E 6 (e, m) 50 (m) 6 (e, m) 50 (m) 6 (e, m) 50 (m)BD01-160-E 25 (m) 95 (m) 25 (m) 95 (m) 16 (m) 50 (m)
Tap-off units BD01-AK01X/ZS 0.75 (f, st) 10 (f, so, st) 0.75 (f, st) 10 (f, so, st) 0.75 (f, st) 10 (f, so, st)BD01-AK02X/ZS3 0.75 (f, st) 10 (f, so, st) 0.75 (f, st) 10 (f, so, st) 0.75 (f, st) 10 (f, so, st)BD01-AK02M0/A163 0.75 (so, st) 16 (so) 0.75 (f, st) 10 (f, so, st) 0.75 (f, st) 10 (f, so, st)BD01-AK02M0/A323 0.75 (so, st) 16 (so) 0.75 (f, st) 10 (f, so, st) 0.75 (f, st) 10 (f, so, st)BD01-AK1M1/A101 0.75 (so, st) 16 (so) 0.75 (so, f) 2.5 (so, f) 0.75 (so, f) 2.5 (so, f)BD01-AK1M1/A161 0.75 (so, st) 16 (so) 0.75 (so, f) 2.5 (so, f) 0.75 (so, f) 2.5 (so, f)BD01-AK1M1/A321 0.75 (so, st) 16 (so) 0.75 (so, f) 2.5 (so, f) 0.75 (so, f) 2.5 (so, f)BD01-AK1M1/A... 0.75 (so, st) 16 (so) 0.75 (f, st) 10 (f, so, st) 0.75 (so, st) 16 (so)BD01-AK1M1/A...N 0.75 (so, st) 16 (so) 0.75 (so, st) 16 (so) 0.75 (so, st) 16 (so)BD01-AK1X/S14 0.5 (f, st) 4 (so) 0.75 (f, st) 10 (f, so, st) 0.75 (so, st) 16 (so)BD01-AK1X/S18 0.5 (f, st) 16 (f, so, st) 0.75 (f, st) 10 (f, so, st) 0.75 (so, st) 16 (so)BD01-AK1X/GB... 0.75 (so, st) 16 (so) 0.75 (f, st) 10 (f, so, st) 0.75 (so, st) 16 (so)BD01-AK2X/F1451 0.75 (so, st) 16 (so) 0.75 (f, st) 10 (f, so, st) 0.75 (so, st) 16 (so)BD01-AK2X/S27 0.75 (f, st) 10 (f, so, st) 0.75 (f, st) 10 (f, so, st) 0.75 (so, st) 16 (so)BD01-AK2HX/S33 1.5 (f, st) 25 (f, so, st) 0.75 (f, st) 10 (f, so, st) 0.75 (so, st) 16 (so, st)
Notes so = solid, st = stranded, f = flexible with ferrule
Dimension drawingsStraight Trunking Units, Junction Units
Siemens LV 70 · 2004 4/33
BD01 System (40 A - 160 A)
4
Straight trunking units
BD01-...
Flexible junction units
BD01(...)-R.
l 57.5
50
5.5
25
90 77
57
125 4.5
250 a
5.5
n 125×
n a×
l a Number of tap-off points2000 500 4
1000 23000 500 6
1000 3
57.5 l
5092
l1
R 100
316
316
Type I I1 I2BD01-...-R1 500 165 316BD01-...-R2 1000 665 –
Dimension drawingsFeeder Units
Siemens LV 70 · 20044/34
BD01 System (40 A - 160 A)
4
Feeder units
BD01-E
BD01-160-E
170
104
1115
0
260
34.5
132
27
53
9
158
o 5.3
90
45
M32, M40, M50
20260
130
150
104
a
a
M63
End flange
Dimension drawingsTap-Off Units
Siemens LV 70 · 2004 4/35
BD01 System (40 A - 160 A)
4
Tap-off units
BD01-AK01X/ZS BD01-AK02X/ZS3
BD01-AK02M0/A163BD01-AK02M0/A323BD01-AK02M0/F
BD01-AK02M0/2SD163S14BD01-AK02M0/2SD163A161BD01-AK02M0/2SD163FIA161
77.5
100
116
10066
M25
77.5
200
100
116
14.5
9476
M25
70
200
26.526.7
118.
2
Dimension drawingsTap-Off Units
Siemens LV 70 · 20044/36
BD01 System (40 A - 160 A)
4
Tap-off units
BD01-AK02M0/CEE163S14BD01-AK02M0/CEE163A161
BD01-AK02M0/CEE165A163
100200
116
105
70
52
9094
38.5
200
105
100
116
70
52
102
94
38.5
Dimension drawingsTap-Off Units
Siemens LV 70 · 2004 4/37
BD01 System (40 A - 160 A)
4
Tap-off units
BD01-AK1X/S...BD01-AK1X/GB...BD01-AK1X/F
BD01-AK1M1/A...BD01-AK1M1/F
BD01-AK1X/2SD...BD01-AK1X/2BS...BD01-AK1X/2DKS...BD01-AK1X/2PC...BD01-AK1X/2X13...
BD01-AK1X/CEE163...BD01-AK1X/15...
Notes · · · · · · · Usable component fitting space
150
160
195
100
100 22.5
80
40 27
112
135
292
85
12
M25, 32, 40, 50
90
77
13 63
68
52
75.5
90
Dimension drawingsTap-Off Units
Siemens LV 70 · 20044/38
BD01 System (40 A - 160 A)
4
Tap-off units
BD01-AK2X/F..., BD01-AK2HX/F...BD01-AK2X/S..., BD01-AK2X/F...
BD01-AK2M2/FBD01-AK2HM2/F
BD01-AK2X/4SD..., BD01-AK2X/4DKS...BD01-AK2X/4PC..., BD01-AK2X/4X13...
Notes · · · · · · · Usable component fitting space
150
160
100
112
12
85
362
265
200
80
40 27
205
22.5
M25, 32, 40, 50
160
77 13
63
130
68
Dimension drawingsTap-Off Units
Siemens LV 70 · 2004 4/39
BD01 System (40 A - 160 A)
4
Tap-off units
BD01-AK2M1/BS...BD01-AK2M1/2SD...BD01-AK2M1/2DKS...BD01-AK2M1/2PC...BD01-AK2M1/2X13...
BD01-AK2M1/CEE165... BD01-AK2X/CEE165...
BD01-AK2M1/CEE325... BD01-AK2X/CEE325...
90
13
68
52
105
72.5
52
72.5
72.5
132
62
72.5
Dimension drawingsAncillary Equipment Units
Siemens LV 70 · 20044/40
BD01 System (40 A - 160 A)
4
Ancillary equipment units
BD01-GK1X/F BD01-GK1M1/F BD01-GK1X/4DKS103BD01-GK1X/4PC163BD01-GK1X/4SD163BD01-GK1X/2X15
BD01-GK2X/F BD01-GK2M2/F
Notes · · · · · · · Usable component fitting space
175
135
100
150
160
M25, 32, 40, 50
77
90
13
63
60.5
124.5
112
12
85
80
40
27
205
150
160
100
245
M25, 32, 40, 50
112
12142
150
160
245
77
Dimension drawingsAncillary Equipment Units, Accessories
Siemens LV 70 · 2004 4/41
BD01 System (40 A - 160 A)
4
Ancillary equipment units
BD01-GK2X/2SD163CEE165BD01-GK2X/2DKS103CEE165
BD01-GK2X/CEE163CEE165
Fixing brackets
BD01-B BD01-BA
105
84
179
13
52 63
70
174
52
75
103
25
112
132
105.5
27.5
4.5
∅ 9
50 115
135
15
27.5
10 10
49.5
52
59
91
10
10
∅ 9