behavior of a damaged prestressed concrete bridge repaired

754
Behavior of a Damaged Prestressed Concrete Bridge Repaired with Fiber-Reinforced Polymer Reinforcement by Wesley Oliver Bullock A thesis submitted to the Graduate Faculty of Auburn University in partial fulfillment of the requirements for the Degree of Master of Science Auburn, Alabama December 12, 2011 Keywords: fiber-reinforced polymer, FRP, effective debonding strain, cracking, crack-opening displacement, repair Copyright 2011 by Wesley Oliver Bullock Approved by Robert W. Barnes, Chair, James J. Mallett Associate Professor of Civil Engineering Anton K. Schindler, Associate Professor of Civil Engineering Justin D. Marshall, Assistant Professor of Civil Engineering

Upload: others

Post on 29-Dec-2021

4 views

Category:

Documents


0 download

TRANSCRIPT

Behavior of a Damaged Prestressed Concrete Bridge

Repaired with Fiber-Reinforced Polymer Reinforcement

by

Wesley Oliver Bullock

A thesis submitted to the Graduate Faculty of

Auburn University

in partial fulfillment of the

requirements for the Degree of

Master of Science

Auburn, Alabama

December 12, 2011

Keywords: fiber-reinforced polymer, FRP, effective debonding strain, cracking,

crack-opening displacement, repair

Copyright 2011 by Wesley Oliver Bullock

Approved by

Robert W. Barnes, Chair, James J. Mallett Associate Professor of Civil Engineering

Anton K. Schindler, Associate Professor of Civil Engineering

Justin D. Marshall, Assistant Professor of Civil Engineering

ii

0BAbstract

After the construction of elevated portions of I-565 in Huntsville, Alabama, cracks

were discovered in numerous prestressed concrete bulb-tee bridge girders that were

constructed to exhibit continuous behavior in response to post-construction loads.

Previous investigations conducted by Alabama Department of Transportation (ALDOT)

and Auburn University Highway Research Center (AUHRC) personnel resulted in

determinations that the cracking was a result of restrained thermal deformations and

inadequate reinforcement details, and that the cracking compromised the strength of the

girder end regions. A wet lay-up fiber-reinforced polymer (FRP) repair scheme was

proposed to address the deficiency. To assess the efficacy of the FRP repair solution,

load testing and finite element model (FEM) analyses were conducted for pre- and post-

repair conditions of Northbound Spans 10 and 11. Pre-repair testing was conducted on

June 1 and 2, 2005. The FRP reinforcement system was installed in December 2007.

Post-repair testing was conducted on May 25 and 26, 2010.

Post-repair testing included controlled truck loading as well as the monitoring of

structural response to diurnal thermal conditions. Analysis of pre- and post-repair results

indicated that the efficacy of the repair solution could not be assessed with direct

comparisons between pre- and post-repair measurements due to unforeseen unintentional

support conditions that were in effect during the pre-repair testing. Direct analysis of

post-repair behavior indicated that the structure exhibits continuity degradation in

iii

response to heavy truck loads and should be considered simply supported for

conservative strength-limit-state design. Analysis of responses to thermal conditions

indicated the FRP reinforcement exhibits behavior that can be accurately estimated with

simplified analysis of linear temperature gradient effects on restrained girders. Based on

conditions observed after more than 2 years in service, the installed FRP reinforcement

system was determined to be performing appropriately.

Based on the experimental observations, a design procedure was developed for FRP

repair of similar structures with damaged regions near continuous ends of prestressed

concrete bridge girders in accordance with AASHTO LRFD Bridge Design

Specifications and the recommendations of ACI 440.2R-08. The design procedure was

formulated to provide the girder end regions with adequate strength-limit-state resistance

for the combined effects of shear and flexure, as well as to provide adequate performance

under service loads—including the effects of daily temperature variations. A design

example is presented.

iv

1BAcknowledgments

Wesley Oliver Bullock, son of Edwin H. and Lynne D. Bullock, was born in

Birmingham, Alabama on March 22, 1985. In May of 2008, he received a Bachelor of

Science in Civil Engineering from Auburn University in Auburn, Alabama. He entered

the Graduate School at Auburn University in August of 2008 in pursuit of his Master of

Science in Civil Engineering. Edwin and Lynne Bullock cannot be thanked enough for

all of their mental, physical, financial, and emotional support throughout the entirety of

this education.

The author would like to thank the numerous people that have had an influence on the

completion of this research. He would especially like to thank his graduate advisor and

committee chair, Dr. Robert Barnes, for years of guidance and instruction, which

included countless hours devoted to this project. The author would also like to thank his

committee members, Dr. Anton Schindler and Dr. Justin Marshall, for their review of this

work and their constructive comments. There were also many other people who

specifically contributed to the success of the bridge testing process. These contributors

include Will Minton, Sam Keske, Tom Hadzor, Mr. Billy Wilson, Dr. Paul Ziehl, and

assisting ALDOT personnel. Everyone’s contributions are greatly appreciated.

The author would also like to thank all family and friends who have provided

encouragement over the years. Special thanks are due to Mom, Dad, and Blair, whose

unwavering patience and love have been truly inspirational.

v

2BTable of Contents

0HAbstract ............................................................................................................................... 946Hii

1HAcknowledgments.............................................................................................................. 947Hiv

2HList of Tables .................................................................................................................... 948Hxv

3HList of Figures ................................................................................................................. 949Hxxii

4HChapter 1: Introduction ...................................................................................................... 950H1

5H1.1 Project Overview .................................................................................................. 951H1

6H1.2 Need for Research ................................................................................................ 952H3

7H1.3 Objective and Scope ............................................................................................. 953H6

8H1.4 Thesis Organization .............................................................................................. 954H6

9HChapter 2: History of the Bridge Structure and Associated Research ............................... 955H8

10H2.1 Introduction .......................................................................................................... 956H8

11H2.2 Bridge Construction .............................................................................................. 957H8

12H2.3 Structural Geometry and Material Properties ....................................................... 958H9

13H2.3.1 Spans Investigated .......................................................................................... 959H9

14H2.3.2 Girder Types ................................................................................................. 960H12

15H2.3.3 Prestressing Strands ...................................................................................... 961H14

16H2.3.4 Shear Reinforcement .................................................................................... 962H18

17H2.3.5 Continuity Reinforcement ............................................................................ 963H23

18H2.3.6 Bridge Deck .................................................................................................. 964H26

vi

19H2.4 Unexpected Cracking ......................................................................................... 965H29

20H2.4.1 Crack Locations ............................................................................................ 966H29

21H2.4.2 Previous Repairs and Safety Measures ......................................................... 967H33

22H2.4.3 Causes for Cracking ..................................................................................... 968H37

23H2.4.4 Ramifications of Cracking ............................................................................ 969H41

24H2.5 Bridge Behavior Analysis ................................................................................... 970H42

25H2.5.1 Behavior Types Considered ......................................................................... 971H43

26H2.5.2 Analysis Methods ......................................................................................... 972H43

27H2.6 Design of External Fiber-Reinforced Polymer

Strengthening System ......................................................................................... 973H50

28H2.7 Load Tests Prior to FRP Reinforcement Installation ......................................... 974H54

29H2.7.1 Instrumentation for Pre-Repair Load Testing ............................................... 975H55

30H2.7.2 Procedures for Pre-Repair Load Testing ...................................................... 976H55

31H2.7.3 Results of Pre-Repair Load Testing ............................................................. 977H56

32H2.8 Finite-Element Analysis of Bridge Behavior ..................................................... 978H57

33H2.8.1 Uncracked Model ......................................................................................... 979H58

34H2.8.2 Cracked Model ............................................................................................. 980H58

35H2.8.3 Cracked-with-Reinforcement Model ............................................................ 981H59

36H2.8.4 Pre-Repair Model ......................................................................................... 982H59

37H2.8.5 Post-Repair Model ........................................................................................ 983H60

38H2.9 Installation of External FRP Reinforcement ...................................................... 984H60

39H2.9.1 Surface Preparation ...................................................................................... 985H61

40H2.9.2 Adhesion Testing .......................................................................................... 986H64

vii

41H2.9.3 Tensile Testing ............................................................................................. 987H66

42H2.9.4 FRP Fabric Installation Procedures .............................................................. 988H67

43H2.9.5 Painting of Installed FRP Reinforcement ..................................................... 989H72

44H2.9.6 FRP Reinforcement Installation Timeline .................................................... 990H74

45H2.10 Current Research ................................................................................................ 991H77

46HChapter 3: Bridge Instrumentation................................................................................... 992H78

47H3.1 Introduction ........................................................................................................ 993H78

48H3.2 Instrumentation Overview .................................................................................. 994H78

49H3.3 Crack-Opening Displacement Gages ................................................................. 995H81

50H3.3.1 COD Gage Locations ................................................................................... 996H83

51H3.3.2 COD Gage Installation ................................................................................. 997H83

52H3.4 Deflectometers .................................................................................................... 998H86

53H3.4.1 Deflectometer Locations .............................................................................. 999H87

54H3.4.2 Deflectometer Installation ............................................................................ 1000H89

55H3.5 Strain Gages ........................................................................................................ 1001H92

56H3.5.1 Strain Gage Locations .................................................................................. 1002H93

57H3.5.2 Concrete Strain Gages ................................................................................ 1003H106

58H3.5.3 FRP Strain Gages ....................................................................................... 1004H107

59H3.5.4 Strain Gage Installation .............................................................................. 1005H108

60H3.6 Data Acquisition System .................................................................................. 1006H116

61H3.7 Sensor Notation ................................................................................................ 1007H117

62HChapter 4: Bridge Testing Procedures ........................................................................... 1008H119

63H4.1 Introduction ...................................................................................................... 1009H119

viii

64H4.2 Traffic Control .................................................................................................. 1010H119

65H4.3 Load Testing Trucks ......................................................................................... 1011H120

66H4.3.1 Load Truck Block Configurations .............................................................. 1012H125

67H4.3.2 Resultant Force Comparisons—Pre- and Post-Repair ............................... 1013H130

68H4.3.3 Night 1—AE Preloading—LC-6.5 ............................................................. 1014H132

69H4.3.4 Night 2—AE Loading and Multiposition Load Test—LC-6 ..................... 1015H132

70H4.3.5 Truck Weight Limits .................................................................................. 1016H133

71H4.4 Load Testing Traverse Lanes and Stop Positions ............................................. 1017H133

72H4.4.1 Traverse Lanes ............................................................................................ 1018H134

73H4.4.2 Stop Positions ............................................................................................. 1019H136

74H4.5 Acoustic Emissions Load Testing .................................................................... 1020H139

75H4.6 Bridge Monitoring ............................................................................................ 1021H142

76H4.6.1 Weather Conditions during Pre-Repair Testing ......................................... 1022H142

77H4.6.2 Weather Conditions during Post-Repair Testing ........................................ 1023H143

78H4.7 Multiposition Load Testing .............................................................................. 1024H145

79H4.8 Superposition Testing ....................................................................................... 1025H146

80H4.9 Data Reduction and Analysis ........................................................................... 1026H149

81HChapter 5: Results and Discussion ................................................................................. 1027H151

82H5.1 Introduction ...................................................................................................... 1028H151

83H5.2 Bearing Pad Effects .......................................................................................... 1029H152

84H5.3 Bridge Response to Truck Loads—Post-Repair ............................................... 1030H158

85H5.3.1 Response to Different Horizontal Truck Alignments ................................. 1031H158

86H5.3.2 Indications of Damage to Instrumented Girders ........................................ 1032H163

ix

87H5.3.3 Post-Repair Continuity Behavior Assessment ............................................ 1033H181

88H5.3.4 Linear-Elastic Behavior .............................................................................. 1034H209

89H5.3.5 Relationship between Truck Position and FRP Tensile Demand ............... 1035H220

90H5.4 Bridge Response to Ambient Thermal Conditions ........................................... 1036H229

91H5.4.1 Theoretical Response to Ambient Thermal Conditions ............................. 1037H230

92H5.4.2 Measured Responses to Ambient Thermal Conditions .............................. 1038H247

93H5.5 Performance of FRP Reinforcement ................................................................ 1039H287

94H5.6 Conclusions ...................................................................................................... 1040H287

95HChapter 6: FRP Reinforcement Design.......................................................................... 1041H291

96H6.1 Introduction ...................................................................................................... 1042H291

97H6.2 Necessity of FRP Reinforcement ..................................................................... 1043H292

98H6.3 FRP Reinforcement Product Selection ............................................................. 1044H292

99H6.4 Strength-Limit-State Design ............................................................................. 1045H295

100H6.4.1 Critical Cross-Section Locations ................................................................ 1046H296

101H6.4.2 Critical Load Conditions ............................................................................ 1047H296

102H6.4.3 Strength-Limit-State Temperature Demands ............................................. 1048H298

103H6.4.4 Material Properties ..................................................................................... 1049H298

104H6.4.5 Dimensional Properties .............................................................................. 1050H302

105H6.4.6 Initial Estimate of Required FRP Layers .................................................... 1051H305

106H6.4.7 Vertical Shear Strength Resistance ............................................................ 1052H307

107H6.4.8 Tensile Strength .......................................................................................... 1053H314

108H6.4.9 Check Strengths of Each Location with Equal Layers of FRP .................. 1054H316

109H6.5 Length of FRP Reinforcement Installation ....................................................... 1055H317

x

110H6.6 Anchorage ......................................................................................................... 1056H318

111H6.7 Service Limit State ........................................................................................... 1057H320

112H6.8 Design Summary .............................................................................................. 1058H322

113H6.9 Installation Recommendations ......................................................................... 1059H322

114H6.9.1 Preparing for Installation ............................................................................ 1060H323

115H6.9.2 FRP Reinforcement Installation ................................................................. 1061H326

116HChapter 7: Summary and Conclusions ........................................................................... 1062H330

117H7.1 Project Summary .............................................................................................. 1063H330

118H7.2 Conclusions ...................................................................................................... 1064H333

119H7.2.1 FRP Reinforcement Installation ................................................................. 1065H333

120H7.2.2 Observed Responses to Truck Loads ......................................................... 1066H333

121H7.2.3 Theoretical Responses to Ambient Thermal Conditions ............................ 1067H335

122H7.2.4 Observed Responses to Ambient Thermal Conditions ............................... 1068H335

123H7.2.5 Performance of FRP Reinforcement .......................................................... 1069H337

124H7.2.6 FRP Design Recommendations .................................................................. 1070H337

125H7.2.7 FRP Reinforcement Installation Recommendations .................................. 1071H338

126HChapter 8: Recommendations ........................................................................................ 1072H340

127H8.1 Design of FRP Reinforcement Repair Solutions .............................................. 1073H340

128H8.2 Installation of FRP Reinforcement Systems ..................................................... 1074H341

129H8.3 Northbound Spans 10 and 11 of I-565 ............................................................. 1075H341

130H8.4 Recommendations for Further Research .......................................................... 1076H343

131H8.4.1 In-Service Load Testing ............................................................................. 1077H343

132H8.4.2 In-Service Bridge Monitoring .................................................................... 1078H344

xi

133H8.4.3 Laboratory Testing ..................................................................................... 1079H344

134HReferences ....................................................................................................................... 1080H347

135HAppendix A: Abbreviations and Notation ..................................................................... 1081H352

136HAppendix B: Multiposition Load Test—Graphical Results ........................................... 1082H356

137HB.1 Lane A .............................................................................................................. 1083H357

138HB.1.1 Crack-Opening Displacements ................................................................... 1084H357

139HB.1.2 Deflections .................................................................................................. 1085H362

140HB.1.3 Cross-Section Strains .................................................................................. 1086H367

141HB.1.4 Bottom-Fiber Strains—Both Girders ......................................................... 1087H407

142HB.2 Lane C .............................................................................................................. 1088H422

143HB.2.1 Crack-Opening Displacements ................................................................... 1089H422

144HB.2.2 Deflections .................................................................................................. 1090H427

145HB.2.3 Cross-Section Strains .................................................................................. 1091H432

146HB.2.4 Bottom-Fiber Strains—Both Girders ......................................................... 1092H472

147HAppendix C: Multiposition Load Test—Measurements ................................................ 1093H487

148HC.1 Lane A .............................................................................................................. 1094H488

149HC.2 Lane C .............................................................................................................. 1095H498

150HAppendix D: Bridge Monitoring—Graphical Results ................................................... 1096H508

151HD.1 Crack-Opening Displacements ......................................................................... 1097H509

152HD.2 Deflections ........................................................................................................ 1098H510

153HD.3 Bottom-Fiber Strains ........................................................................................ 1099H511

154HD.4 Bottom-Fiber Strains and Crack-Opening Displacements ............................... 1100H514

155HAppendix E: Bridge Monitoring Measurements ............................................................ 1101H516

xii

156HE.1 Crack-Opening Displacements ......................................................................... 1102H517

157HE.2 Deflections ........................................................................................................ 1103H518

158HE.3 Cross-Section Strains ........................................................................................ 1104H520

159HE.4 Bottom-Fiber Strains ........................................................................................ 1105H528

160HE.5 FRP Strains ....................................................................................................... 1106H532

161HAppendix F: Bridge Monitoring—Measurement Adjustments ..................................... 1107H535

162HF.1 Inconsistent Measurements .............................................................................. 1108H535

163HF.2 Deflectometer Behavior .................................................................................... 1109H535

164HF.3 Deflection Adjustments .................................................................................... 1110H536

165HF.4 Graphical Presentations of Deflection Adjustments ......................................... 1111H537

166HF.4.1 Original Deflections—Girders 7 and 8 ....................................................... 1112H537

167HF.4.2 Adjusted Deflections of Girder 7 in Span 10 ............................................. 1113H538

168HF.4.3 Adjusted Deflections of Girder 7 in Span 11 ............................................. 1114H541

169HF.4.4 Adjusted Deflections of Girder 8 in Span 10 ............................................. 1115H544

170HF.4.5 Adjusted Deflections of Girder 8 in Span 11 ............................................. 1116H547

171HF.4.6 Final Adjusted Deflections—Girders 7 and 8 ............................................ 1117H550

172HF.5 Strain Measurement Adjustments ..................................................................... 1118H551

173HAppendix G: Superposition—Graphical Results ........................................................... 1119H553

174HG.1 Crack-Opening Displacements ......................................................................... 1120H554

175HG.2 Deflections ........................................................................................................ 1121H558

176HG.3 Bottom-Fiber Strains ........................................................................................ 1122H562

177HAppendix H: Superposition—Measurements ................................................................ 1123H566

178HAppendix I: AE Static Positions—Graphical Results .................................................... 1124H571

xiii

179HI.1 Crack-Opening Displacements ......................................................................... 1125H572

180HI.2 Deflections ........................................................................................................ 1126H577

181HI.3 Bottom-Fiber Strains ........................................................................................ 1127H582

182HI.3.1 Bottom-Fiber Strains—Girder 7 ................................................................. 1128H587

183HI.3.2 Bottom-Fiber Strains—Girder 8 ................................................................. 1129H592

184HAppendix J: AE Static Positions—Measurements ......................................................... 1130H597

185HAppendix K: False Support Bearing Pad Effects During Load Testing ........................ 1131H610

186HK.1 Installation of False Supports with Bearing Pads ............................................. 1132H610

187HK.2 Pre-Repair Bearing Pad Conditions .................................................................. 1133H613

188HK.3 Bearing Pad Removal during FRP Installation ................................................ 1134H614

189HK.4 Post-Repair Bearing Pad Conditions ................................................................ 1135H618

190HK.5 Analysis of Numerical Results ......................................................................... 1136H618

191HK.5.1 Deflections—Multiposition Load Testing .................................................. 1137H618

192HK.5.2 Crack-Opening Displacements—Multiposition Load Testing ................... 1138H623

193HK.5.3 Surface Strains ............................................................................................ 1139H628

194HK.5.4 Superposition Deflections .......................................................................... 1140H636

195HK.6 Bearing Pad Effects .......................................................................................... 1141H639

196HAppendix L: Data Acquisition Channel Layout ............................................................ 1142H640

197HAppendix M: Strain Gage Installation Procedure—FRP Reinforcement ...................... 1143H644

198HAppendix N: FRP Reinforcement Design Example ...................................................... 1144H652

199HN.1 Introduction ...................................................................................................... 1145H652

200HN.2 Product Selection .............................................................................................. 1146H652

201HN.3 Strength-Limit-State Design ............................................................................. 1147H652

xiv

202HN.3.1 Critical Cross-Section Locations ................................................................ 1148H653

203HN.3.2 Critical Load Conditions ............................................................................ 1149H658

204HN.3.3 Material Properties ..................................................................................... 1150H662

205HN.3.4 Dimensional Properties .............................................................................. 1151H664

206HN.3.5 Initial Estimate of Required FRP Layers .................................................... 1152H671

207HN.3.6 Shear Strength Check—Three Layers ........................................................ 1153H674

208HN.3.7 Shear Strength—Five Layers ..................................................................... 1154H682

209HN.4 Extent of FRP Installation ................................................................................ 1155H695

210HN.5 Anchorage ......................................................................................................... 1156H698

211HN.6 Service-Limit-State Verification ...................................................................... 1157H698

212HN.7 Design Summary .............................................................................................. 1158H699

213HN.8 Installation Recommendations ......................................................................... 1159H700

214HN.9 Comparison of Design Recommendation and Previously Installed FRP ......... 1160H700

215HN.10 Varying Modulus of Elasticity for FRP Reinforcement ................................... 1161H703

xv

3BList of Tables

216HTable 2.1: Stirrup mild steel bar details (ALDOT 1988; Swenson 2003) ................ 1162H21

217HTable 2.2: Summary of cracking in prestressed concrete girders made

continuous for live loads (ALDOT 1994) ............................................... 1163H33

218HTable 2.3: Weather during FRP reinforcement installation (NOAA 2008) ............. 1164H74

219HTable 3.1: COD gage locations ................................................................................. 1165H83

220HTable 3.2: Deflectometer locations ........................................................................... 1166H89

221HTable 3.3: Strain-gaged cross sections ..................................................................... 1167H95

222HTable 3.4: Strain gage locations within cross section ............................................. 1168H101

223HTable 4.1: Load truck weight distributions—pre-repair ......................................... 1169H126

224HTable 4.2: Load truck weight distributions—post-repair ....................................... 1170H127

225HTable 4.3: Comparison of unconventional load truck weight distributions ........... 1171H127

226HTable 4.4: Resultant force comparisons—ST-6400—LC-6 ................................... 1172H130

227HTable 4.5: Resultant force comparisons—ST-6400—LC-6.5 ................................ 1173H130

228HTable 4.6: Resultant force comparisons—ST-6902 and ST-6538—LC-6 ............. 1174H131

229HTable 4.7: Resultant force comparisons—ST-6902 and ST-6538—LC-6.5 .......... 1175H131

230HTable 4.8: Stop position locations .......................................................................... 1176H137

231HTable 4.9: Weather during pre-repair bridge testing (NOAA 2005) ...................... 1177H143

xvi

232HTable 4.10: Weather during post-repair bridge testing (NOAA 2010) ..................... 1178H144

233HTable 4.11: Temperatures measured during bridge monitoring (NOAA 2010) ....... 1179H144

234HTable 5.1: Bearing pad effects—crack-opening displacements ............................. 1180H157

235HTable 5.2: Midspan truck positions—deflections ................................................... 1181H162

236HTable 5.3: AE truck positions—crack-opening displacements .............................. 1182H167

237HTable 5.4: AE truck positions—bottom-fiber strains—Girder 7 ............................ 1183H173

238HTable 5.5: AE truck positions—bottom-fiber strains—Girder 8 ............................ 1184H174

239HTable 5.6: Midspan truck positions—deflections ................................................... 1185H185

240HTable 5.7: Midspan truck positions—bottom-fiber strains—Girder 7 ................... 1186H191

241HTable 5.8: Midspan truck positions—bottom-fiber strains—Girder 8 ................... 1187H192

242HTable 5.9: Damaged region truck positions—bottom-fiber strains—Girder 7 ....... 1188H196

243HTable 5.10: Damaged region truck positions—bottom-fiber strains—Girder 8 ....... 1189H197

244HTable 5.13: Midspan truck positions—maximum crack closures ............................ 1190H203

245HTable 5.14: Damaged region truck positions—maximum crack openings .............. 1191H207

246HTable 5.15: Superposition—deflections ................................................................... 1192H211

247HTable 5.16: Superposition—maximum crack closures ............................................. 1193H213

248HTable 5.17: Superposition—bottom-fiber strains—Girder 7 .................................... 1194H217

249HTable 5.18: Superposition—bottom-fiber strains—Girder 8 .................................... 1195H218

250HTable 5.19: FRP tensile demand—bottom-fiber strains—Span 11 truck positions . 1196H228

251HTable 5.20: Crack openings—Span 11 truck positions ............................................ 1197H228

252HTable 5.21: Temperatures measured during bridge monitoring (NOAA 2010) ....... 1198H248

xvii

253HTable 5.22: Maximum upward deflections—thermal conditions ............................. 1199H251

254HTable 5.23: Maximum upward deflections—post-repair ......................................... 1200H252

255HTable 5.24: Deflections—ambient thermal conditions ............................................. 1201H256

256HTable 5.25: Maximum bottom-fiber tensile strains—Girder 7—

thermal conditions ................................................................................. 1202H260

257HTable 5.26: Maximum bottom-fiber tensile strains—Girder 8—

thermal conditions ................................................................................. 1203H261

258HTable 5.27: Maximum bottom-fiber tensile strains—Girder 7 ................................. 1204H262

259HTable 5.28: Maximum bottom-fiber tensile strains—Girder 8 ................................. 1205H263

260HTable 5.29: Bottom-fiber strains—Girder 7—ambient thermal conditions ............. 1206H267

261HTable 5.30: Bottom-fiber strains—Girder 8—ambient thermal conditions ............. 1207H268

262HTable 5.31: Maximum crack openings—thermal conditions ................................... 1208H281

263HTable 5.32: Maximum crack openings—thermal and load truck conditions ........... 1209H281

264HTable 5.33: Crack-opening displacements—ambient thermal conditions ................ 1210H282

265HTable 5.34: Crack openings and bottom-fiber strains—thermal conditions ............. 1211H285

266HTable C.1: Lane A—crack-opening displacements ................................................. 1212H488

267HTable C.2: Lane A—deflections .............................................................................. 1213H489

268HTable C.3: Lane A—cross-section strains—Girder 7—Span 10 ............................ 1214H490

269HTable C.4: Lane A—cross-section strains—Girder 7—Span 11 ............................ 1215H491

270HTable C.5: Lane A—cross-section strains—Girder 8—Span 10 ............................ 1216H492

271HTable C.6: Lane A—cross-section strains—Girder 8—Span 11 ............................ 1217H493

272HTable C.7: Lane A—bottom-fiber strains—Girder 7 .............................................. 1218H494

xviii

273HTable C.8: Lane A—bottom-fiber strains—Girder 8 .............................................. 1219H495

274HTable C.9: Lane A—FRP strains—Girder 7 ........................................................... 1220H496

275HTable C.10: Lane A—FRP strains—Girder 8 ........................................................... 1221H497

276HTable C.11: Lane C—crack-opening displacements ................................................. 1222H498

277HTable C.12: Lane C—deflections .............................................................................. 1223H499

278HTable C.13: Lane C—cross-section strains—Girder 7—Span 10 ............................. 1224H500

279HTable C.14: Lane C—cross-section strains—Girder 7—Span 11 ............................. 1225H501

280HTable C.15: Lane C—cross-section strains—Girder 8—Span 10 ............................. 1226H502

281HTable C.16: Lane C—cross-section strains—Girder 8—Span 11 ............................. 1227H503

282HTable C.17: Lane C—bottom-fiber strains—Girder 7 .............................................. 1228H504

283HTable C.18: Lane C—bottom-fiber strains—Girder 8 .............................................. 1229H505

284HTable C.19: Lane C—FRP strains—Girder 7 ........................................................... 1230H506

285HTable C.20: Lane C—FRP strains—Girder 8 ........................................................... 1231H507

286HTable E.1: Bridge monitoring—crack-opening displacements ............................... 1232H517

287HTable E.2: Bridge monitoring—deflections—Girder 7 .......................................... 1233H518

288HTable E.3: Bridge monitoring—deflections—Girder 8 .......................................... 1234H519

289HTable E.4: Bridge monitoring—strains—Girder 7—Section 1 .............................. 1235H520

290HTable E.5: Bridge monitoring—strains—Girder 7—Section 2 .............................. 1236H521

291HTable E.6: Bridge monitoring—strains—Girder 7—Section 3 .............................. 1237H522

292HTable E.7: Bridge monitoring—strains—Girder 7—Section 4 .............................. 1238H523

293HTable E.8: Bridge monitoring—strains—Girder 8—Section 1 .............................. 1239H524

xix

294HTable E.9: Bridge monitoring—strains—Girder 8—Section 2 .............................. 1240H525

295HTable E.10: Bridge monitoring—strains—Girder 8—Section 3 .............................. 1241H526

296HTable E.11: Bridge monitoring—strains—Girder 8—Section 4 .............................. 1242H527

297HTable E.12: Bridge monitoring—bottom-fiber strains—Girder 7 ............................ 1243H528

298HTable E.13: Bridge monitoring—bottom-fiber strains—Girder 8 ............................ 1244H530

299HTable E.14: Bridge monitoring—FRP strains—Girder 7 ......................................... 1245H532

300HTable E.15: Bridge monitoring—FRP strains—Girder 8 ......................................... 1246H533

301HTable H.1: Superposition—crack-opening displacements ...................................... 1247H567

302HTable H.2: Superposition—deflections ................................................................... 1248H568

303HTable H.3: Superposition—bottom-fiber strains—Girder 7 .................................... 1249H569

304HTable H.4: Superposition—bottom-fiber strains—Girder 8 .................................... 1250H570

305HTable J.1: AE static positions—crack-opening displacements .............................. 1251H600

306HTable J.2: AE static positions—deflections ........................................................... 1252H601

307HTable J.3: AE static positions—cross-section strains—Girder 7—Span 10 .......... 1253H602

308HTable J.4: AE static positions—cross-section strains—Girder 7—Span 11 .......... 1254H603

309HTable J.5: AE static positions—cross-section strains—Girder 8—Span 10 .......... 1255H604

310HTable J.6: AE static positions—cross-section strains—Girder 8—Span 11 .......... 1256H605

311HTable J.7: AE static positions—bottom-fiber strains—Girder 7 ............................ 1257H606

312HTable J.8: AE static positions—bottom-fiber strains—Girder 8 ............................ 1258H607

313HTable J.9: AE static positions—FRP strains—Girder 7 ......................................... 1259H608

314HTable J.10: AE static positions—FRP strains—Girder 8 ......................................... 1260H609

xx

315HTable K.1: Deflections—A1 .................................................................................... 1261H619

316HTable K.2: Deflections—A9 .................................................................................... 1262H620

317HTable K.3: Deflections—C1 .................................................................................... 1263H621

318HTable K.4: Deflections—C9 .................................................................................... 1264H622

319HTable K.5: Bearing pad effects—crack-opening displacements ............................. 1265H627

320HTable K.6: Deflections—superposition—A1 and A9 ............................................. 1266H637

321HTable K.7: Deflections—superposition—A1 + A9 ................................................. 1267H638

322HTable L.1: Data acquisition channels—crack-opening displacement gages ........... 1268H641

323HTable L.2: Data acquisition channels—deflectometers .......................................... 1269H641

324HTable L.3: Data acquisition channels—strain gages—Span 10 .............................. 1270H642

325HTable L.4: Data acquisition channels—strain gages—Span 11 .............................. 1271H643

326HTable N.1: Critical cross-section locations .............................................................. 1272H653

327HTable N.2: Critical load conditions ......................................................................... 1273H659

328HTable N.3: Material properties ................................................................................ 1274H663

329HTable N.4: Cross-section dimensional properties .................................................... 1275H664

330HTable N.5: Reinforcement dimensional properties .................................................. 1276H666

331HTable N.6: Initial estimate for minimum area of FRP required .............................. 1277H672

332HTable N.7: Initial estimate for minimum layers of FRP required ............................ 1278H673

333HTable N.8: Effective FRP debonding strain—three layers ...................................... 1279H675

334HTable N.9: Effective shear depth—three layers ...................................................... 1280H677

335HTable N.10: Net longitudinal tensile strain—three layers ....................................... 1281H679

xxi

336HTable N.11: Layers required satisfying net longitudinal tensile strain ...................... 1282H681

337HTable N.12: Effective FRP debonding strain—five layers ........................................ 1283H683

338HTable N.13: Effective shear depth—five layers ........................................................ 1284H684

339HTable N.14: Net longitudinal tensile strain—five layers ........................................... 1285H685

340HTable N.15: Vertical shear strength—concrete—five layers .................................... 1286H687

341HTable N.16: Vertical shear strength—vertical reinforcement—five layers ............... 1287H688

342HTable N.17: Nominal shear strength—five layers ..................................................... 1288H689

343HTable N.18: Vertical shear strength verification—five layers ................................... 1289H690

344HTable N.19: Longitudinal tension strength—five layers ........................................... 1290H691

345HTable N.20: Longitudinal tension demand—five layers ........................................... 1291H692

346HTable N.21: Longitudinal tension strength verification—five layers ........................ 1292H693

347HTable N.22: Comparisons of strength and demand—five layers .............................. 1293H694

xxii

4BList of Figures

348HFigure 1.1: Elevated spans of I-565 in Huntsville, Alabama ....................................... 1294H1

349HFigure 1.2: Northbound Bent 11 of I-565 in Huntsville, Alabama .............................. 1295H2

350HFigure 1.3: Cracked pre-tensioned bulb-tee girders of I-565 (Barnes et al. 2006) ...... 1296H2

351HFigure 1.4: Girder 9 of Northbound Spans 10 and 11—repaired ................................ 1297H5

352HFigure 1.5: Girders 7, 8, and 9 of Northbound Span 10—repaired ............................. 1298H5

353HFigure 2.1: Plan view of the two-span continuous unit (ALDOT 1988) ................... 1299H10

354HFigure 2.2: Elevation view of the two-span continuous unit (ALDOT 1988) ........... 1300H10

355HFigure 2.3: Detailed plan view of the two-span continuous unit (ALDOT 1988) ..... 1301H11

356HFigure 2.4: Cross section of a typical BT-54 girder (ALDOT 1988; Swenson 2003) 1302H13

357HFigure 2.5: Prestressed strand pattern near girder end

(ALDOT 1988; Swenson 2003) .............................................................. 1303H14

358HFigure 2.6: Prestressed strand pattern near girder midpoint

(ALDOT 1988; Swenson 2003) .............................................................. 1304H15

359HFigure 2.7: Prestressed strand profile (Swenson 2003) ............................................. 1305H17

360HFigure 2.8: Vertical shear reinforcement near girder end

(ALDOT 1988; Swenson 2003) .............................................................. 1306H19

361HFigure 2.9: Vertical shear reinforcement near girder midpoint

(ALDOT 1988; Swenson 2003) .............................................................. 1307H20

xxiii

362HFigure 2.10: Location and spacing of vertical shear reinforcement

(ALDOT 1988; Swenson 2003) .............................................................. 1308H22

363HFigure 2.11: Continuity reinforcement—continuity diaphragm detail

(ALDOT 1988; Swenson 2003) .............................................................. 1309H24

364HFigure 2.12: Continuity reinforcement of a typical BT-54 cross section

(ALDOT 1988; Swenson 2003) .............................................................. 1310H25

365HFigure 2.13: Cross section view of deck slab reinforcement over an exterior girder

(ALDOT 1988; Swenson 2003) .............................................................. 1311H27

366HFigure 2.14: Cross section view of deck slab reinforcement over an interior girder

(ALDOT 1988; Swenson 2003) .............................................................. 1312H28

367HFigure 2.15: Portion of I-565 containing cracked bridge girders (Swenson 2003) ..... 1313H30

368HFigure 2.16: Cracking pattern in end region of precast girder (Barnes et al. 2006) .... 1314H31

369HFigure 2.17: Cracked pre-tensioned bulb-tee girders (Barnes et al. 2006) .................. 1315H31

370HFigure 2.18: Typical diaphragm face crack (Swenson 2003) ...................................... 1316H32

371HFigure 2.19: Typical diaphragm end crack (Swenson 2003) ....................................... 1317H32

372HFigure 2.20: Cracks injected with epoxy (Fason 2009) ............................................... 1318H35

373HFigure 2.21: Steel frame false supports (Fason 2009) ................................................. 1319H35

374HFigure 2.22: False support bearing pad with gap between pad and girder

(Fason 2009) ............................................................................................ 1320H36

375HFigure 2.23: False support bearing pad in contact with girder (Fason 2009) .............. 1321H36

376HFigure 2.24: Cracked girder with continuity reinforcement details

(Barnes et al. 2006) ................................................................................. 1322H40

377HFigure 2.25: Typical strut-and-tie model (Swenson 2003) .......................................... 1323H47

xxiv

378HFigure 2.25: Longitudinal configuration profile for FRP (Barnes et al. 2006) ............ 1324H52

379HFigure 2.26: Cross-sectional configuration of FRP near diaphragm

(Swenson 2003) ....................................................................................... 1325H53

380HFigure 2.27: Cross-sectional configuration of FRP beyond bearing pad

(Swenson 2003) ....................................................................................... 1326H53

381HFigure 2.28: Surface cleaning—final removal of dust and debris ............................... 1327H61

382HFigure 2.29: Use of saw for bearing pad removal ........................................................ 1328H62

383HFigure 2.30: Use of torch for bearing pad removal ...................................................... 1329H63

384HFigure 2.31: Successful removal of bearing pad .......................................................... 1330H63

385HFigure 2.32: Bearing pad after forceful removal ......................................................... 1331H64

386HFigure 2.33: Adhesion test equipment (Swenson 2007) .............................................. 1332H65

387HFigure 2.34: Performance of on-site adhesion test ....................................................... 1333H65

388HFigure 2.35: Preparation of sample for tension testing ................................................ 1334H66

389HFigure 2.36: Representative sample for tension testing ............................................... 1335H67

390HFigure 2.37: Cutting strips of FRP fabric ..................................................................... 1336H68

391HFigure 2.38: Epoxy saturation of FRP fabric ............................................................... 1337H68

392HFigure 2.39: Applying epoxy to girder surface before FRP fabric installation ........... 1338H69

393HFigure 2.40: Installation of first layer of FRP fabric ................................................... 1339H69

394HFigure 2.41: Four layers of installed FRP fabric .......................................................... 1340H70

395HFigure 2.42: FRP installation sequence–first layer ...................................................... 1341H70

396HFigure 2.43: FRP installation sequence—second layer ............................................... 1342H71

397HFigure 2.44: FRP installation sequence—third layer ................................................... 1343H72

xxv

398HFigure 2.45: FRP installation sequence—fourth layer ................................................. 1344H72

399HFigure 2.46: Painting of FRP reinforcement ................................................................ 1345H73

400HFigure 2.47: Painted FRP reinforcement of Span 10 ................................................... 1346H73

401HFigure 3.1: Instrumentation overview ........................................................................ 1347H80

402HFigure 3.2: Crack-opening displacement gage (TML 2011) ..................................... 1348H82

403HFigure 3.3: Anchor blocks for COD gage installation (Fason 2009) ......................... 1349H84

404HFigure 3.4: COD gage attached to anchor blocks ...................................................... 1350H85

405HFigure 3.5: Typical deflectometer .............................................................................. 1351H86

406HFigure 3.6: Deflectometer locations—Girder Line 7 ................................................. 1352H88

407HFigure 3.7: Deflectometer locations—Girder Line 8 ................................................. 1353H88

408HFigure 3.8: Girder attachment point for deflectometer wire ...................................... 1354H90

409HFigure 3.9: Deflectometer aluminum bar—pre-bent with adjusted turnbuckle ......... 1355H91

410HFigure 3.10: Deflectometer area—Span 11 ................................................................. 1356H92

411HFigure 3.11: Strain gage cross section locations .......................................................... 1357H94

412HFigure 3.12: Strain gage locations—Girder 7—Section 1 ........................................... 1358H96

413HFigure 3.13: Strain gage locations—Girder 7—Section 2 ........................................... 1359H96

414HFigure 3.14: Strain gage locations—Girder 7—Section 3 ........................................... 1360H97

415HFigure 3.15: Strain gage locations—Girder 7—Section 4 ........................................... 1361H97

416HFigure 3.16: Strain gage locations—Girder 8—Section 1 ........................................... 1362H98

417HFigure 3.17: Strain gage locations—Girder 8—Section 2 ........................................... 1363H98

418HFigure 3.18: Strain gage locations—Girder 8—Section 3 ........................................... 1364H99

xxvi

419HFigure 3.19: Strain gage locations—Girder 8—Section 4 ........................................... 1365H99

420HFigure 3.20: Strain gage locations—Girders 7 and 8—Section 5 .............................. 1366H100

421HFigure 3.21: Strain gage locations—Girders 7 and 8—Sections 6, 7, and 8 ............. 1367H100

422HFigure 3.22: Strain gage locations—CRACK ............................................................ 1368H101

423HFigure 3.23: Surface-mounted strain gage—concrete (Fason 2009) ......................... 1369H107

424HFigure 3.25: Strain gage installation—applying degreaser to gage location ............. 1370H109

425HFigure 3.26: Strain gage installation—removal of surface irregularities ................... 1371H110

426HFigure 3.27: Strain gage installation—initial surface cleaning .................................. 1372H110

427HFigure 3.28: Strain gage installation—clean surface prepared for solid epoxy ......... 1373H111

428HFigure 3.29: Strain gage installation—application of solid epoxy ............................ 1374H112

429HFigure 3.30: Strain gage installation—epoxy surface ................................................ 1375H112

430HFigure 3.31: Strain gage installation—gage application with thin epoxy .................. 1376H114

431HFigure 3.32: Strain gage installation—gage applied to FRP reinforcement .............. 1377H114

432HFigure 3.33: Strain gage installation—rubber coating for moisture protection ......... 1378H115

433HFigure 3.34: Strain gage installation—mastic tape for mechanical protection .......... 1379H116

434HFigure 3.35: Data acquisition hardware ..................................................................... 1380H117

435HFigure 4.1: ST-6400 (standard load truck) ............................................................... 1381H121

436HFigure 4.2: ST-6902 (pre-repair unconventional truck) ........................................... 1382H122

437HFigure 4.3: ST-6538 (post-repair replacement for

pre-repair unconventional truck) ........................................................... 1383H122

438HFigure 4.4: Footprint of ALDOT load testing trucks (ST-6400 and ST-6538) ....... 1384H123

xxvii

439HFigure 4.5: Footprint of ALDOT tool trailer truck (ST-6902) ................................. 1385H124

440HFigure 4.6: LC-6.5 block configuration—post-repair ST-6400 ............................... 1386H128

441HFigure 4.7: LC-6 block configuration—post-repair ST-6400 .................................. 1387H128

442HFigure 4.8: LC-6.5 block configuration—post-repair ST-6538 ............................... 1388H129

443HFigure 4.9: LC-6 block configuration—post-repair ST-6538 .................................. 1389H129

444HFigure 4.10: Traverse lanes and stop positions—overhead photo ............................. 1390H134

445HFigure 4.11: Lane A—Horizontal truck positioning (multiposition test) .................. 1391H135

446HFigure 4.12: Lane C—Horizontal truck positioning (multiposition and AE tests) .... 1392H135

447HFigure 4.13: Stop position locations .......................................................................... 1393H138

448HFigure 4.14: Acoustic emissions test—stop position locations ................................. 1394H140

449HFigure 4.15: Superposition test—horizontal lane positioning ................................... 1395H147

450HFigure 4.16: Superposition test—stop position locations .......................................... 1396H148

451HFigure 5.1: Crack-opening displacements—pre- and post-repair—A4 ................... 1397H154

452HFigure 5.2: Crack-opening displacements—pre- and post-repair—A7 ................... 1398H155

453HFigure 5.3: Crack-opening displacements—pre- and post-repair—C4 ................... 1399H155

454HFigure 5.4: Crack-opening displacements—pre- and post-repair—C7 ................... 1400H156

455HFigure 5.5: Lane A—horizontal truck positioning ................................................... 1401H159

456HFigure 5.6: Lane C—horizontal truck positioning ................................................... 1402H159

457HFigure 5.7: Deflections—A1 .................................................................................... 1403H160

458HFigure 5.8: Deflections—A9 .................................................................................... 1404H160

459HFigure 5.9: Deflections—C1 .................................................................................... 1405H161

xxviii

460HFigure 5.10: Deflections—C9 .................................................................................... 1406H161

461HFigure 5.11: AE Span 10 truck position—crack-opening displacements—LC-6.5 ... 1407H164

462HFigure 5.12: AE Span 11 truck position—crack-opening displacements—LC-6.5 ... 1408H165

463HFigure 5.13: AE Span 10 truck position—crack-opening displacements—LC-6 ...... 1409H165

464HFigure 5.14: AE Span 11 truck position—crack-opening displacements—LC-6 ...... 1410H166

465HFigure 5.15: AE Span 10 truck position—bottom-fiber strains—LC-6.5 ................. 1411H170

466HFigure 5.16: AE Span 11 truck position—bottom-fiber strains—LC-6.5 ................. 1412H171

467HFigure 5.17: AE Span 10 truck position—bottom-fiber strains—LC-6 .................... 1413H171

468HFigure 5.18: AE Span 11 truck position—bottom-fiber strains—LC-6 .................... 1414H172

469HFigure 5.19: COD and bottom-fiber strain comparisons—LC-6.5—AE Span 10 ..... 1415H177

470HFigure 5.20: COD and bottom-fiber strain comparisons—LC-6.5—AE Span 11 ..... 1416H177

471HFigure 5.21: COD and bottom-fiber strain comparisons—LC-6—AE Span 10 ........ 1417H178

472HFigure 5.22: COD and bottom-fiber strain comparisons—LC-6—AE Span 11 ........ 1418H178

473HFigure 5.23: Deflections—A1 .................................................................................... 1419H182

474HFigure 5.24: Deflections—A9 .................................................................................... 1420H183

475HFigure 5.25: Deflections—C1 .................................................................................... 1421H183

476HFigure 5.26: Deflections—C9 .................................................................................... 1422H184

477HFigure 5.27: Deflections—post-repair—measurements and predictions—A9 .......... 1423H186

478HFigure 5.28: Deflections—post-repair—measurements and predictions—C9 .......... 1424H187

479HFigure 5.29: Bottom-fiber strain—A1 ....................................................................... 1425H188

480HFigure 5.30: Bottom-fiber strain—A9 ....................................................................... 1426H189

xxix

481HFigure 5.31: Bottom-fiber strain—C1 ........................................................................ 1427H189

482HFigure 5.32: Bottom-fiber strain—C9 ........................................................................ 1428H190

483HFigure 5.33: Bottom-fiber strain—A4 ....................................................................... 1429H194

484HFigure 5.34: Bottom-fiber strain—A7 ....................................................................... 1430H194

485HFigure 5.35: Bottom-fiber strain—C4 ........................................................................ 1431H195

486HFigure 5.36: Bottom-fiber strain—C7 ........................................................................ 1432H195

487HFigure 5.37: Bottom-fiber strain—post-repair—measurements and predictions—

A7 .......................................................................................................... 1433H198

488HFigure 5.38: Bottom-fiber strain—post-repair—measurements and predictions—

A9 .......................................................................................................... 1434H199

489HFigure 5.39: Bottom-fiber strain—post-repair—measurements and predictions—

C7 .......................................................................................................... 1435H199

490HFigure 5.40: Bottom-fiber strain—post-repair—measurements and predictions—

C9 .......................................................................................................... 1436H200

491HFigure 5.41: Midspan truck positions—crack-opening displacements—A1 ............. 1437H201

492HFigure 5.42: Midspan truck positions—crack-opening displacements—A9 ............. 1438H202

493HFigure 5.43: Midspan truck positions—crack-opening displacements—C1 ............. 1439H202

494HFigure 5.44: Midspan truck positions—crack-opening displacements—C9 ............. 1440H203

495HFigure 5.45: Damaged region truck positions—crack-opening displacements—A4 1441H205

496HFigure 5.46: Damaged region truck positions—crack-opening displacements—A7 1442H205

497HFigure 5.47: Damaged section truck positions—crack-opening displacements—C4 1443H206

498HFigure 5.48: Damaged region truck positions—crack-opening displacements—C7 . 1444H206

xxx

499HFigure 5.49: Superposition—deflections—predicted and measured ......................... 1445H210

500HFigure 5.50: Superposition—crack-opening displacements—

predicted and measured ......................................................................... 1446H213

501HFigure 5.51: Superposition—bottom-fiber strains—predicted and measured ........... 1447H216

502HFigure 5.52: Longitudinal truck positions—C6 ......................................................... 1448H221

503HFigure 5.53: Longitudinal truck positions—AE LC-6 Span 11 and C7 .................... 1449H222

504HFigure 5.54: Longitudinal truck positions—C8 ......................................................... 1450H223

505HFigure 5.55: Bottom-fiber strains—C6 ...................................................................... 1451H225

506HFigure 5.56: Bottom-fiber strains—AE LC-6 Span 11 .............................................. 1452H226

507HFigure 5.57: Bottom-fiber strains—C7 ...................................................................... 1453H226

508HFigure 5.58: Bottom-fiber strains—C8 ...................................................................... 1454H227

509HFigure 5.59: Linear temperature gradient .................................................................. 1455H230

510HFigure 5.60: Two-span continuous structure subjected to linear thermal gradient .... 1456H231

511HFigure 5.61: Expected deformations—two theoretical load conditions ..................... 1457H232

512HFigure 5.62: Moment diagrams—two theoretical load conditions ............................ 1458H234

513HFigure 5.63: Curvature diagrams—two theoretical load conditions .......................... 1459H235

514HFigure 5.64: Curvature due to temperature gradient with restraint ............................ 1460H239

515HFigure 5.65: Moment due to temperature gradient with restraint .............................. 1461H240

516HFigure 5.66: Shear due to temperature gradient with restraint ................................... 1462H242

517HFigure 5.67: Bottom-fiber strain due to temperature gradient with restraint ............. 1463H243

518HFigure 5.68: Bottom-fiber stress due to temperature gradient with restraint ............. 1464H244

xxxi

519HFigure 5.69: Deflections due to temperature gradient with restraint ......................... 1465H246

520HFigure 5.70: Deflections—normal traffic—twenty-four hours—Girder 7 ................ 1466H249

521HFigure 5.71: Deflections—normal traffic—twenty-four hours—Girder 8 ................ 1467H250

522HFigure 5.72: Deflections—8:30 a.m. .......................................................................... 1468H254

523HFigure 5.73: Deflections—4:30 p.m. ......................................................................... 1469H254

524HFigure 5.74: Deflections—8:30 p.m. ......................................................................... 1470H255

525HFigure 5.75: Deflections—2:30 a.m. .......................................................................... 1471H255

526HFigure 5.76: Bottom-fiber strains—Girder 7—within 80 in. from diaphragm .......... 1472H257

527HFigure 5.77: Bottom-fiber strains—Girder 7—beyond 80 in. from diaphragm ........ 1473H258

528HFigure 5.78: Bottom-fiber strains—Girder 8—within 80 in. from diaphragm .......... 1474H258

529HFigure 5.79: Bottom-fiber strains—Girder 8—beyond 80 in. from diaphragm ........ 1475H259

530HFigure 5.80: Bottom-fiber strains—8:30 a.m. ............................................................ 1476H265

531HFigure 5.81: Bottom-fiber strains—4:30 p.m. ........................................................... 1477H265

532HFigure 5.82: Bottom-fiber strains—8:30 p.m. ........................................................... 1478H266

533HFigure 5.83: Bottom-fiber strains—2:30 a.m. ............................................................ 1479H266

534HFigure 5.84: Bottom-fiber strains—concrete—Girder 7—6:30 a.m. ......................... 1480H269

535HFigure 5.85: Bottom-fiber strains—concrete—Girder 7—4:30 p.m. ........................ 1481H270

536HFigure 5.86: Bottom-fiber strains—concrete—Girder 7—8:30 p.m. ........................ 1482H270

537HFigure 5.87: Bottom-fiber strains—concrete—Girder 7—2:30 a.m. ......................... 1483H271

538HFigure 5.88: Bottom-fiber strains—concrete—Girder 8—6:30 a.m. ......................... 1484H271

539HFigure 5.89: Bottom-fiber strains—concrete—Girder 8—4:30 p.m. ........................ 1485H272

xxxii

540HFigure 5.90: Bottom-fiber strains—concrete—Girder 8—8:30 p.m. ........................ 1486H272

541HFigure 5.91: Bottom-fiber strains—concrete—Girder 8—2:30 a.m. ......................... 1487H273

542HFigure 5.92: Bottom-fiber strains—damaged region—8:30 a.m. .............................. 1488H275

543HFigure 5.93: Bottom-fiber strains—damaged region—4:30 p.m. .............................. 1489H276

544HFigure 5.94: Bottom-fiber strains—damaged region—8:30 p.m. .............................. 1490H276

545HFigure 5.95: Bottom-fiber strains—damaged region—2:30 a.m. .............................. 1491H277

546HFigure 5.96: Crack-opening displacements—normal traffic—twenty-four hours ..... 1492H280

547HFigure 5.97: Bottom-fiber strain and COD—thermal conditions—Girder 7—

Span 10 .................................................................................................. 1493H283

548HFigure 5.98: Bottom-fiber strain and COD—thermal conditions—Girder 7—

Span 11 .................................................................................................. 1494H284

549HFigure 5.99: Bottom-fiber strain and COD—thermal conditions—Girder 8—

Span 10 .................................................................................................. 1495H284

550HFigure 5.100: Bottom-fiber strain and COD—thermal conditions—Girder 8—

Span 11 .................................................................................................. 1496H285

551HFigure 6.1: Cross-sectional configuration of FRP—near diaphragm

(Swenson 2003) ..................................................................................... 1497H304

552HFigure 6.2: Cross-sectional configuration of FRP—typical (Swenson 2003) ......... 1498H304

553HFigure 6.3: Simplified model for initial estimate of FRP requirement .................... 1499H305

554HFigure 6.4: FRP fan anchorage system (Niemitz et al. 2010) .................................. 1500H319

555HFigure B.1: Crack-opening displacements—A1 ....................................................... 1501H357

556HFigure B.2: Crack-opening displacements—A2 ....................................................... 1502H358

557HFigure B.3: Crack-opening displacements—A3 ....................................................... 1503H358

xxxiii

558HFigure B.4: Crack-opening displacements—A4 ....................................................... 1504H359

559HFigure B.5: Crack-opening displacements—A5 ....................................................... 1505H359

560HFigure B.6: Crack-opening displacements—A6 ....................................................... 1506H360

561HFigure B.7: Crack-opening displacements—A7 ....................................................... 1507H360

562HFigure B.8: Crack-opening displacements—A8 ....................................................... 1508H361

563HFigure B.9: Crack-opening displacements—A9 ....................................................... 1509H361

564HFigure B.10: Deflections—A1 .................................................................................... 1510H362

565HFigure B.11: Deflections—A2 .................................................................................... 1511H363

566HFigure B.12: Deflections—A3 .................................................................................... 1512H363

567HFigure B.13: Deflections—A4 .................................................................................... 1513H364

568HFigure B.14: Deflections—A5 .................................................................................... 1514H364

569HFigure B.15: Deflections—A6 .................................................................................... 1515H365

570HFigure B.16: Deflections—A7 .................................................................................... 1516H365

571HFigure B.17: Deflections—A8 .................................................................................... 1517H366

572HFigure B.18: Deflections—A9 .................................................................................... 1518H366

573HFigure B.19: Strains—Girder 7—Section 1—A1 ....................................................... 1519H367

574HFigure B.20: Strains—Girder 7—Section 1—A2 ....................................................... 1520H368

575HFigure B.21: Strains—Girder 7—Section 1—A3 ....................................................... 1521H368

576HFigure B.22: Strains—Girder 7—Section 1—A4 ....................................................... 1522H369

577HFigure B.23: Strains—Girder 7—Section 1—A5 ....................................................... 1523H369

578HFigure B.24: Strains—Girder 7—Section 1—A6 ....................................................... 1524H370

xxxiv

579HFigure B.25: Strains—Girder 7—Section 1—A7 ....................................................... 1525H370

580HFigure B.26: Strains—Girder 7—Section 1—A8 ....................................................... 1526H371

581HFigure B.27: Strains—Girder 7—Section 1—A9 ....................................................... 1527H371

582HFigure B.28: Strains—Girder 7—Section 2—A1 ....................................................... 1528H372

583HFigure B.29: Strains—Girder 7—Section 2—A2 ....................................................... 1529H373

584HFigure B.30: Strains—Girder 7—Section 2—A3 ....................................................... 1530H373

585HFigure B.31: Strains—Girder 7—Section 2—A4 ....................................................... 1531H374

586HFigure B.32: Strains—Girder 7—Section 2—A5 ....................................................... 1532H374

587HFigure B.33: Strains—Girder 7—Section 2—A6 ....................................................... 1533H375

588HFigure B.34: Strains—Girder 7—Section 2—A7 ....................................................... 1534H375

589HFigure B.35: Strains—Girder 7—Section 2—A8 ....................................................... 1535H376

590HFigure B.36: Strains—Girder 7—Section 2—A9 ....................................................... 1536H376

591HFigure B.37: Strains—Girder 7—Section 3—A1 ....................................................... 1537H377

592HFigure B.38: Strains—Girder 7—Section 3—A2 ....................................................... 1538H378

593HFigure B.39: Strains—Girder 7—Section 3—A3 ....................................................... 1539H378

594HFigure B.40: Strains—Girder 7—Section 3—A4 ....................................................... 1540H379

595HFigure B.41: Strains—Girder 7—Section 3—A5 ....................................................... 1541H379

596HFigure B.42: Strains—Girder 7—Section 3—A6 ....................................................... 1542H380

597HFigure B.43: Strains—Girder 7—Section 3—A7 ....................................................... 1543H380

598HFigure B.44: Strains—Girder 7—Section 3—A8 ....................................................... 1544H381

599HFigure B.45: Strains—Girder 7—Section 3—A9 ....................................................... 1545H381

xxxv

600HFigure B.46: Strains—Girder 7—Section 4—A1 ....................................................... 1546H382

601HFigure B.47: Strains—Girder 7—Section 4—A2 ....................................................... 1547H383

602HFigure B.48: Strains—Girder 7—Section 4—A3 ....................................................... 1548H383

603HFigure B.49: Strains—Girder 7—Section 4—A4 ....................................................... 1549H384

604HFigure B.50: Strains—Girder 7—Section 4—A5 ....................................................... 1550H384

605HFigure B.51: Strains—Girder 7—Section 4—A6 ....................................................... 1551H385

606HFigure B.52: Strains—Girder 7—Section 4—A7 ....................................................... 1552H385

607HFigure B.53: Strains—Girder 7—Section 4—A8 ....................................................... 1553H386

608HFigure B.54: Strains—Girder 7—Section 4—A9 ....................................................... 1554H386

609HFigure B.55: Strains—Girder 8—Section 1—A1 ....................................................... 1555H387

610HFigure B.56: Strains—Girder 8—Section 1—A2 ....................................................... 1556H388

611HFigure B.57: Strains—Girder 8—Section 1—A3 ....................................................... 1557H388

612HFigure B.58: Strains—Girder 8—Section 1—A4 ....................................................... 1558H389

613HFigure B.59: Strains—Girder 8—Section 1—A5 ....................................................... 1559H389

614HFigure B.60: Strains—Girder 8—Section 1—A6 ....................................................... 1560H390

615HFigure B.61: Strains—Girder 8—Section 1—A7 ....................................................... 1561H390

616HFigure B.62: Strains—Girder 8—Section 1—A8 ....................................................... 1562H391

617HFigure B.63: Strains—Girder 8—Section 1—A9 ....................................................... 1563H391

618HFigure B.64: Strains—Girder 8—Section 2—A1 ....................................................... 1564H392

619HFigure B.65: Strains—Girder 8—Section 2—A2 ....................................................... 1565H393

620HFigure B.66: Strains—Girder 8—Section 2—A3 ....................................................... 1566H393

xxxvi

621HFigure B.67: Strains—Girder 8—Section 2—A4 ....................................................... 1567H394

622HFigure B.68: Strains—Girder 8—Section 2—A5 ....................................................... 1568H394

623HFigure B.69: Strains—Girder 8—Section 2—A6 ....................................................... 1569H395

624HFigure B.70: Strains—Girder 8—Section 2—A7 ....................................................... 1570H395

625HFigure B.71: Strains—Girder 8—Section 2—A8 ....................................................... 1571H396

626HFigure B.72: Strains—Girder 8—Section 2—A9 ....................................................... 1572H396

627HFigure B.73: Strains—Girder 8—Section 3—A1 ....................................................... 1573H397

628HFigure B.74: Strains—Girder 8—Section 3—A2 ....................................................... 1574H398

629HFigure B.75: Strains—Girder 8—Section 3—A3 ....................................................... 1575H398

630HFigure B.76: Strains—Girder 8—Section 3—A4 ....................................................... 1576H399

631HFigure B.77: Strains—Girder 8—Section 3—A5 ....................................................... 1577H399

632HFigure B.78: Strains—Girder 8—Section 3—A6 ....................................................... 1578H400

633HFigure B.79: Strains—Girder 8—Section 3—A7 ....................................................... 1579H400

634HFigure B.80: Strains—Girder 8—Section 3—A8 ....................................................... 1580H401

635HFigure B.81: Strains—Girder 8—Section 3—A9 ....................................................... 1581H401

636HFigure B.82: Strains—Girder 8—Section 4—A1 ....................................................... 1582H402

637HFigure B.83: Strains—Girder 8—Section 4—A2 ....................................................... 1583H403

638HFigure B.84: Strains—Girder 8—Section 4—A3 ....................................................... 1584H403

639HFigure B.85: Strains—Girder 8—Section 4—A4 ....................................................... 1585H404

640HFigure B.86: Strains—Girder 8—Section 4—A5 ....................................................... 1586H404

641HFigure B.87: Strains—Girder 8—Section 4—A6 ....................................................... 1587H405

xxxvii

642HFigure B.88: Strains—Girder 8—Section 4—A7 ....................................................... 1588H405

643HFigure B.89: Strains—Girder 8—Section 4—A8 ....................................................... 1589H406

644HFigure B.90: Strains—Girder 8—Section 4—A9 ....................................................... 1590H406

645HFigure B.91: Bottom-fiber strains—A1 ...................................................................... 1591H407

646HFigure B.92: Bottom-fiber strains—A2 ...................................................................... 1592H408

647HFigure B.93: Bottom-fiber strains—A3 ...................................................................... 1593H408

648HFigure B.94: Bottom-fiber strains—A4 ...................................................................... 1594H409

649HFigure B.95: Bottom-fiber strains—A5 ...................................................................... 1595H409

650HFigure B.96: Bottom-fiber strains—A6 ...................................................................... 1596H410

651HFigure B.97: Bottom-fiber strains—A7 ...................................................................... 1597H410

652HFigure B.98: Bottom-fiber strains—A8 ...................................................................... 1598H411

653HFigure B.99: Bottom-fiber strains—A9 ...................................................................... 1599H411

654HFigure B.100: Bottom-fiber strains—Girder 7—A1 .................................................... 1600H412

655HFigure B.101: Bottom-fiber strains—Girder 7—A2 .................................................... 1601H413

656HFigure B.102: Bottom-fiber strains—Girder 7—A3 .................................................... 1602H413

657HFigure B.103: Bottom-fiber strains—Girder 7—A4 .................................................... 1603H414

658HFigure B.104: Bottom-fiber strains—Girder 7—A5 .................................................... 1604H414

659HFigure B.105: Bottom-fiber strains—Girder 7—A6 .................................................... 1605H415

660HFigure B.106: Bottom-fiber strains—Girder 7—A7 .................................................... 1606H415

661HFigure B.107: Bottom-fiber strains—Girder 7—A8 .................................................... 1607H416

662HFigure B.108: Bottom-fiber strains—Girder 7—A9 .................................................... 1608H416

xxxviii

663HFigure B.109: Bottom-fiber strains—Girder 8—A1 .................................................... 1609H417

664HFigure B.110: Bottom-fiber strains—Girder 8—A2 .................................................... 1610H418

665HFigure B.111: Bottom-fiber strains—Girder 8—A3 .................................................... 1611H418

666HFigure B.112: Bottom-fiber strains—Girder 8—A4 .................................................... 1612H419

667HFigure B.113: Bottom-fiber strains—Girder 8—A5 .................................................... 1613H419

668HFigure B.114: Bottom-fiber strains—Girder 8—A6 .................................................... 1614H420

669HFigure B.115: Bottom-fiber strains—Girder 8—A7 .................................................... 1615H420

670HFigure B.116: Bottom-fiber strains—Girder 8—A8 .................................................... 1616H421

671HFigure B.117: Bottom-fiber strains—Girder 8—A9 .................................................... 1617H421

672HFigure B.118: Crack-opening displacements—C1 ....................................................... 1618H422

673HFigure B.119: Crack-opening displacements—C2 ....................................................... 1619H423

674HFigure B.120: Crack-opening displacements—C3 ....................................................... 1620H423

675HFigure B.121: Crack-opening displacements—C4 ....................................................... 1621H424

676HFigure B.122: Crack-opening displacements—C5 ....................................................... 1622H424

677HFigure B.123: Crack-opening displacements—C6 ....................................................... 1623H425

678HFigure B.124: Crack-opening displacements—C7 ....................................................... 1624H425

679HFigure B.125: Crack-opening displacements—C8 ....................................................... 1625H426

680HFigure B.126: Crack-opening displacements—C9 ....................................................... 1626H426

681HFigure B.127: Deflections—C1 .................................................................................... 1627H427

682HFigure B.128: Deflections—C2 .................................................................................... 1628H428

683HFigure B.129: Deflections—C3 .................................................................................... 1629H428

xxxix

684HFigure B.130: Deflections—C4 .................................................................................... 1630H429

685HFigure B.131: Deflections—C5 .................................................................................... 1631H429

686HFigure B.132: Deflections—C6 .................................................................................... 1632H430

687HFigure B.133: Deflections—C7 .................................................................................... 1633H430

688HFigure B.134: Deflections—C8 .................................................................................... 1634H431

689HFigure B.135: Deflections—C9 .................................................................................... 1635H431

690HFigure B.136: Strains—Girder 7—Section 1—C1 ....................................................... 1636H432

691HFigure B.137: Strains—Girder 7—Section 1—C2 ....................................................... 1637H433

692HFigure B.138: Strains—Girder 7—Section 1—C3 ....................................................... 1638H433

693HFigure B.139: Strains—Girder 7—Section 1—C4 ....................................................... 1639H434

694HFigure B.140: Strains—Girder 7—Section 1—C5 ....................................................... 1640H434

695HFigure B.141: Strains—Girder 7—Section 1—C6 ....................................................... 1641H435

696HFigure B.142: Strains—Girder 7—Section 1—C7 ....................................................... 1642H435

697HFigure B.143: Strains—Girder 7—Section 1—C8 ....................................................... 1643H436

698HFigure B.144: Strains—Girder 7—Section 1—C9 ....................................................... 1644H436

699HFigure B.145: Strains—Girder 7—Section 2—C1 ....................................................... 1645H437

700HFigure B.146: Strains—Girder 7—Section 2—C2 ....................................................... 1646H438

701HFigure B.147: Strains—Girder 7—Section 2—C3 ....................................................... 1647H438

702HFigure B.148: Strains—Girder 7—Section 2—C4 ....................................................... 1648H439

703HFigure B.149: Strains—Girder 7—Section 2—C5 ....................................................... 1649H439

704HFigure B.150: Strains—Girder 7—Section 2—C6 ....................................................... 1650H440

xl

705HFigure B.151: Strains—Girder 7—Section 2—C7 ....................................................... 1651H440

706HFigure B.152: Strains—Girder 7—Section 2—C8 ....................................................... 1652H441

707HFigure B.153: Strains—Girder 7—Section 2—C9 ....................................................... 1653H441

708HFigure B.154: Strains—Girder 7—Section 3—C1 ....................................................... 1654H442

709HFigure B.155: Strains—Girder 7—Section 3—C2 ....................................................... 1655H443

710HFigure B.156: Strains—Girder 7—Section 3—C3 ....................................................... 1656H443

711HFigure B.157: Strains—Girder 7—Section 3—C4 ....................................................... 1657H444

712HFigure B.158: Strains—Girder 7—Section 3—C5 ....................................................... 1658H444

713HFigure B.159: Strains—Girder 7—Section 3—C6 ....................................................... 1659H445

714HFigure B.160: Strains—Girder 7—Section 3—C7 ....................................................... 1660H445

715HFigure B.161: Strains—Girder 7—Section 3—C8 ....................................................... 1661H446

716HFigure B.162: Strains—Girder 7—Section 3—C9 ....................................................... 1662H446

717HFigure B.163: Strains—Girder 7—Section 4—C1 ....................................................... 1663H447

718HFigure B.164: Strains—Girder 7—Section 4—C2 ....................................................... 1664H448

719HFigure B.165: Strains—Girder 7—Section 4—C3 ....................................................... 1665H448

720HFigure B.166: Strains—Girder 7—Section 4—C4 ....................................................... 1666H449

721HFigure B.167: Strains—Girder 7—Section 4—C5 ....................................................... 1667H449

722HFigure B.168: Strains—Girder 7—Section 4—C6 ....................................................... 1668H450

723HFigure B.169: Strains—Girder 7—Section 4—C7 ....................................................... 1669H450

724HFigure B.170: Strains—Girder 7—Section 4—C8 ....................................................... 1670H451

725HFigure B.171: Strains—Girder 7—Section 4—C9 ....................................................... 1671H451

xli

726HFigure B.172: Strains—Girder 8—Section 1—C1 ....................................................... 1672H452

727HFigure B.173: Strains—Girder 8—Section 1—C2 ....................................................... 1673H453

728HFigure B.174: Strains—Girder 8—Section 1—C3 ....................................................... 1674H453

729HFigure B.175: Strains—Girder 8—Section 1—C4 ....................................................... 1675H454

730HFigure B.176: Strains—Girder8—Section 1—C5 ........................................................ 1676H454

731HFigure B.177: Strains—Girder 8—Section 1—C6 ....................................................... 1677H455

732HFigure B.178: Strains—Girder 8—Section 1—C7 ....................................................... 1678H455

733HFigure B.179: Strains—Girder 8—Section 1—C8 ....................................................... 1679H456

734HFigure B.180: Strains—Girder 8—Section 1—C9 ....................................................... 1680H456

735HFigure B.181: Strains—Girder 8—Section 2—C1 ....................................................... 1681H457

736HFigure B.182: Strains—Girder 8—Section 2—C2 ....................................................... 1682H458

737HFigure B.183: Strains—Girder 8—Section 2—C3 ....................................................... 1683H458

738HFigure B.184: Strains—Girder 8—Section 2—C4 ....................................................... 1684H459

739HFigure B.185: Strains—Girder 8—Section 2—C5 ....................................................... 1685H459

740HFigure B.186: Strains—Girder 8—Section 2—C6 ....................................................... 1686H460

741HFigure B.187: Strains—Girder 8—Section 2—C7 ....................................................... 1687H460

742HFigure B.188: Strains—Girder 8—Section 2—C8 ....................................................... 1688H461

743HFigure B.189: Strains—Girder 8—Section 2—C9 ....................................................... 1689H461

744HFigure B.190: Strains—Girder 8—Section 3—C1 ....................................................... 1690H462

745HFigure B.191: Strains—Girder 8—Section 3—C2 ....................................................... 1691H463

746HFigure B.192: Strains—Girder 8—Section 3—C3 ....................................................... 1692H463

xlii

747HFigure B.193: Strains—Girder 8—Section 3—C4 ....................................................... 1693H464

748HFigure B.194: Strains—Girder 8—Section 3—C5 ....................................................... 1694H464

749HFigure B.195: Strains—Girder 8—Section 3—C6 ....................................................... 1695H465

750HFigure B.196: Strains—Girder 8—Section 3—C7 ....................................................... 1696H465

751HFigure B.197: Strains—Girder 8—Section 3—C8 ....................................................... 1697H466

752HFigure B.198: Strains—Girder 8—Section 3—C9 ....................................................... 1698H466

753HFigure B.199: Strains—Girder 8—Section 4—C1 ....................................................... 1699H467

754HFigure B.200: Strains—Girder 8—Section 4—C2 ....................................................... 1700H468

755HFigure B.201: Strains—Girder 8—Section 4—C3 ....................................................... 1701H468

756HFigure B.202: Strains—Girder 8—Section 4—C4 ....................................................... 1702H469

757HFigure B.203: Strains—Girder 8—Section 4—C5 ....................................................... 1703H469

758HFigure B.204: Strains—Girder 8—Section 4—C6 ....................................................... 1704H470

759HFigure B.205: Strains—Girder 8—Section 4—C7 ....................................................... 1705H470

760HFigure B.206: Strains—Girder 8—Section 4—C8 ....................................................... 1706H471

761HFigure B.207: Strains—Girder 8—Section 4—C9 ....................................................... 1707H471

762HFigure B.208: Bottom-fiber strains—C1 ...................................................................... 1708H472

763HFigure B.209: Bottom-fiber strains—C2 ...................................................................... 1709H473

764HFigure B.210: Bottom-fiber strains—C3 ...................................................................... 1710H473

765HFigure B.211: Bottom-fiber strains—C4 ...................................................................... 1711H474

766HFigure B.212: Bottom-fiber strains—C5 ...................................................................... 1712H474

767HFigure B.213: Bottom-fiber strains—C6 ...................................................................... 1713H475

xliii

768HFigure B.214: Bottom-fiber strains—C7 ...................................................................... 1714H475

769HFigure B.215: Bottom-fiber strains—C8 ...................................................................... 1715H476

770HFigure B.216: Bottom-fiber strains—C9 ...................................................................... 1716H476

771HFigure B.217: Bottom-fiber strains—Girder 7—C1 ..................................................... 1717H477

772HFigure B.218: Bottom-fiber strains—Girder 7—C2 ..................................................... 1718H478

773HFigure B.219: Bottom-fiber strains—Girder 7—C3 ..................................................... 1719H478

774HFigure B.220: Bottom-fiber strains—Girder 7—C4 ..................................................... 1720H479

775HFigure B.221: Bottom-fiber strains—Girder 7—C5 ..................................................... 1721H479

776HFigure B.222: Bottom-fiber strains—Girder 7—C6 ..................................................... 1722H480

777HFigure B.223: Bottom-fiber strains—Girder 7—C7 ..................................................... 1723H480

778HFigure B.224: Bottom-fiber strains—Girder 7—C8 ..................................................... 1724H481

779HFigure B.225: Bottom-fiber strains—Girder 7—C9 ..................................................... 1725H481

780HFigure B.226: Bottom-fiber strains—Girder 8—C1 ..................................................... 1726H482

781HFigure B.227: Bottom-fiber strains—Girder 8—C2 ..................................................... 1727H483

782HFigure B.228: Bottom-fiber strains—Girder 8—C3 ..................................................... 1728H483

783HFigure B.229: Bottom-fiber strains—Girder 8—C4 ..................................................... 1729H484

784HFigure B.230: Bottom-fiber strains—Girder 8—C5 ..................................................... 1730H484

785HFigure B.231: Bottom-fiber strains—Girder 8—C6 ..................................................... 1731H485

786HFigure B.232: Bottom-fiber strains—Girder 8—C7 ..................................................... 1732H485

787HFigure B.233: Bottom-fiber strains—Girder 8—C8 ..................................................... 1733H486

788HFigure B.234: Bottom-fiber strains—Girder 8—C9 ..................................................... 1734H486

xliv

789HFigure D.1: Crack-opening displacements—24 hrs .................................................. 1735H509

790HFigure D.2: Deflections—24 hrs—Girder 7 ............................................................. 1736H510

791HFigure D.3: Deflections—24 hrs—Girder 8 ............................................................. 1737H510

792HFigure D.4: Bottom-fiber strains—24 hrs—Girder 7—

within 80 in. from diaphragm ................................................................ 1738H511

793HFigure D.5: Bottom-fiber strains—24 hrs—Girder 7—

beyond 80 in. from diaphragm .............................................................. 1739H511

794HFigure D.6: Bottom-fiber strains—24 hrs—Girder 8—

within 80 in. from diaphragm ................................................................ 1740H512

795HFigure D.7: Bottom-fiber strains—24 hrs—Girder 8—

beyond 80 in. from diaphragm .............................................................. 1741H512

796HFigure D.8: Bottom-fiber strains—24 hrs—FRP near crack locations ..................... 1742H513

797HFigure D.9: Bottom-fiber strain and COD—24 hrs—Girder 7—Span 10 ................ 1743H514

798HFigure D.10: Bottom-fiber strain and COD—24 hrs—Girder 7—Span 11 ................ 1744H514

799HFigure D.11: Bottom-fiber strain and COD—24 hrs—Girder 8—Span 10 ................ 1745H515

800HFigure D.12: Bottom-fiber strain and COD—24 hrs—Girder 8—Span 11 ................ 1746H515

801HFigure F.1: Original deflection results—Girder 7 .................................................... 1747H537

802HFigure F.2: Original deflection results—Girder 8 .................................................... 1748H538

803HFigure F.3: Original deflection results—Girder 7—Span 10 ................................... 1749H538

804HFigure F.4: Adjusted deflection results—D7_10_A ................................................ 1750H539

805HFigure F.5: Adjusted deflection results—D7_10_B ................................................. 1751H539

806HFigure F.6: Adjusted deflection results—Girder 7—Span 10 .................................. 1752H540

xlv

807HFigure F.7: Final deflection results—Girder 7—Span 10 ........................................ 1753H540

808HFigure F.8: Original deflection results—Girder 7—Span 11 ................................... 1754H541

809HFigure F.9: Adjusted deflection results—D7_11_C ................................................. 1755H541

810HFigure F.10: Adjusted deflection results—D7_11_D ................................................ 1756H542

811HFigure F.11: Adjusted deflection results—D7_11_E ................................................. 1757H542

812HFigure F.12: Adjusted deflection results—D7_11_F ................................................. 1758H543

813HFigure F.13: Adjusted deflection results—Girder 7—Span 11 .................................. 1759H543

814HFigure F.14: Final deflection results—Girder 7—Span 11 ........................................ 1760H544

815HFigure F.15: Original deflection results—Girder 8—Span 10 ................................... 1761H544

816HFigure F.16: Adjusted deflection results—D8_10_A ................................................ 1762H545

817HFigure F.17: Adjusted deflection results—D8_10_B ................................................. 1763H545

818HFigure F.18: Adjusted deflection results—Girder 8—Span 10 .................................. 1764H546

819HFigure F.19: Final deflection results—Girder 8—Span 10 ........................................ 1765H546

820HFigure F.20: Original deflection results—Girder 8—Span 11 ................................... 1766H547

821HFigure F.21: Adjusted deflection results—D8_11_C ................................................. 1767H547

822HFigure F.22: Adjusted deflection results—D8_11_D ................................................ 1768H548

823HFigure F.23: Adjusted deflection results—D8_11_E ................................................. 1769H548

824HFigure F.24: Adjusted deflection results—D8_11_F ................................................. 1770H549

825HFigure F.25: Adjusted deflection results—Girder 8—Span 11 .................................. 1771H549

826HFigure F.26: Final deflection results—Girder 8—Span 11 ........................................ 1772H550

827HFigure F.27: Final deflection results—Girder 7 ......................................................... 1773H550

xlvi

828HFigure F.28: Final deflection results—Girder 8 ......................................................... 1774H551

829HFigure F.29: Crack location FRP strain measurements—original F8_10_CK .......... 1775H552

830HFigure F.30: Crack location FRP strain measurements—adjusted F8_10_CK .......... 1776H552

831HFigure G.1: Crack-opening displacements—A1 (east) ............................................. 1777H554

832HFigure G.2: Crack-opening displacements—A9 (east) ............................................. 1778H555

833HFigure G.3: Crack-opening displacements—A1 (east) + A9 (east) .......................... 1779H555

834HFigure G.4: Crack-opening displacements—superposition—actual and predicted .. 1780H556

835HFigure G.5: COD—superposition—actual and predicted—Girder 7 ....................... 1781H556

836HFigure G.6: COD—superposition—actual and predicted—Girder 8 ....................... 1782H557

837HFigure G.7: Deflections—A1 (east) .......................................................................... 1783H558

838HFigure G.8: Deflections—A9 (east) .......................................................................... 1784H559

839HFigure G.9: Deflections—A1 (east) + A9 (east) ....................................................... 1785H559

840HFigure G.10: Deflections—superposition—actual and predicted ............................... 1786H560

841HFigure G.11: Deflections—superposition—actual and predicted—Girder 7 ............. 1787H560

842HFigure G.12: Deflections—superposition—actual and predicted—Girder 8 ............. 1788H561

843HFigure G.13: Bottom-fiber strains—A1 (east) ............................................................ 1789H562

844HFigure G.14: Bottom-fiber strains—A9 (east) ............................................................ 1790H563

845HFigure G.15: Bottom-fiber strains—A1 (east) + A9 (east) ......................................... 1791H563

846HFigure G.16: Bottom-fiber strains—superposition—actual and predicted ................. 1792H564

847HFigure G.17: Bottom-fiber strains—superposition—actual and predicted—Girder 7 1793H564

848HFigure G.18: Bottom-fiber strains—superposition—actual and predicted—Girder 8 1794H565

xlvii

849HFigure I.1: Crack-opening displacements—LC 6.5—AE Span 10 (east) ............... 1795H572

850HFigure I.2: Crack-opening displacements—LC 6.5—AE Span 10 (both) .............. 1796H573

851HFigure I.3: Crack-opening displacements—LC 6.5—AE Span 11 (east) ............... 1797H573

852HFigure I.4: Crack-opening displacements—LC 6.5—AE Span 11 (both) .............. 1798H574

853HFigure I.5: Crack-opening displacements—LC 6—AE Span 10 (east) .................. 1799H574

854HFigure I.6: Crack-opening displacements—LC 6—AE Span 10 (both) ................. 1800H575

855HFigure I.7: Crack-opening displacements—LC 6—AE Span 11 (east) .................. 1801H575

856HFigure I.8: Crack-opening displacements—LC 6—AE Span 11 (both) ................. 1802H576

857HFigure I.9: Deflections—LC 6.5—AE Span 10 (east) ............................................ 1803H577

858HFigure I.10: Deflections—LC 6.5—AE Span 10 (both) ........................................... 1804H578

859HFigure I.11: Deflections—LC 6.5—AE Span 11 (east) ............................................ 1805H578

860HFigure I.12: Deflections—LC 6.5—AE Span 11 (both) ........................................... 1806H579

861HFigure I.13: Deflections—LC 6—AE Span 10 (east) ............................................... 1807H579

862HFigure I.14: Deflections—LC 6—AE Span 10 (both) .............................................. 1808H580

863HFigure I.15: Deflections—LC 6—AE Span 11 (east) ............................................... 1809H580

864HFigure I.16: Deflections—LC 6—AE Span 11 (both) .............................................. 1810H581

865HFigure I.17: Bottom-fiber strains—LC 6.5—AE Span 10 (east) .............................. 1811H582

866HFigure I.18: Bottom-fiber strains—LC 6.5—AE Span 10 (both) ............................. 1812H583

867HFigure I.19: Bottom-fiber strains—LC 6.5—AE Span 11 (east) .............................. 1813H583

868HFigure I.20: Bottom-fiber strains—LC 6.5—AE Span 11 (both) ............................. 1814H584

869HFigure I.21: Bottom-fiber strains—LC 6—AE Span 10 (east) ................................. 1815H584

xlviii

870HFigure I.22: Bottom-fiber strains—LC 6—AE Span 10 (both) ................................ 1816H585

871HFigure I.23: Bottom-fiber strains—LC 6—AE Span 11 (east) ................................. 1817H585

872HFigure I.24: Bottom-fiber strains—LC 6—AE Span 11 (both) ................................ 1818H586

873HFigure I.25: Bottom-fiber strains—Girder 7—LC 6.5—AE Span 10 (east) ............. 1819H587

874HFigure I.26: Bottom-fiber strains—Girder 7—LC 6.5—AE Span 10 (both) ............ 1820H588

875HFigure I.27: Bottom-fiber strains—Girder 7—LC 6.5—AE Span 11 (east) ............. 1821H588

876HFigure I.28: Bottom-fiber strains—Girder 7—LC 6.5—AE Span 11 (both) ............ 1822H589

877HFigure I.29: Bottom-fiber strains—Girder 7—LC 6—AE Span 10 (east) ................ 1823H589

878HFigure I.30: Bottom-fiber strains—Girder 7—LC 6—AE Span 10 (both) ............... 1824H590

879HFigure I.31: Bottom-fiber strains—Girder 7—LC 6—AE Span 11 (east) ................ 1825H590

880HFigure I.32: Bottom-fiber strains—Girder 7—LC 6—AE Span 11 (both) ............... 1826H591

881HFigure I.33: Bottom-fiber strains—Girder 8—LC 6.5—AE Span 10 (east) ............. 1827H592

882HFigure I.34: Bottom-fiber strains—Girder 8—LC 6.5—AE Span 10 (both) ............ 1828H593

883HFigure I.35: Bottom-fiber strains—Girder 8—LC 6.5—AE Span 11 (east) ............. 1829H593

884HFigure I.36: Bottom-fiber strains—Girder 8—LC 6.5—AE Span 11 (both) ............ 1830H594

885HFigure I.37: Bottom-fiber strains—Girder 8—LC 6—AE Span 10 (east) ................ 1831H594

886HFigure I.38: Bottom-fiber strains—Girder 8—LC 6—AE Span 10 (both) ............... 1832H595

887HFigure I.39: Bottom-fiber strains—Girder 8—LC 6—AE Span 11 (east) ................ 1833H595

888HFigure I.40: Bottom-fiber strains—Girder 8—LC 6—AE Span 11 (both) ............... 1834H596

889HFigure J.1: Transverse load position—AE testing—Lane C—east truck ................ 1835H598

890HFigure J.2: Transverse load position—AE testing—Lane C—both trucks ............. 1836H598

xlix

891HFigure K.1: Steel frame false supports ...................................................................... 1837H610

892HFigure K.2: Bearing pad between false support and exterior girder ......................... 1838H611

893HFigure K.3: Bearing pad location with space between the

bearing pad and girder ........................................................................... 1839H612

894HFigure K.4: Bearing pad location without space between the

bearing pad and girder ........................................................................... 1840H612

895HFigure K.5: Bearing pad in contact with girder during pre-repair testing ................ 1841H613

896HFigure K.6: Use of reciprocating saw during bearing pad removal .......................... 1842H615

897HFigure K.7: Use of propane torch during bearing pad removal ................................ 1843H616

898HFigure K.8: Successful removal of bearing pad ........................................................ 1844H617

899HFigure K.9: Bearing pad after forceful removal ....................................................... 1845H617

900HFigure K.10: Deflections—A1 .................................................................................... 1846H619

901HFigure K.11: Deflections—A9 .................................................................................... 1847H620

902HFigure K.12: Deflections—C1 .................................................................................... 1848H621

903HFigure K.13: Deflections—C9 .................................................................................... 1849H622

904HFigure K.14: Crack-opening displacements—pre- and post-repair—A4 ................... 1850H624

905HFigure K.15: Crack-opening displacements—pre- and post-repair—A7 ................... 1851H625

906HFigure K.16: Crack-opening displacements—pre- and post-repair—C4 ................... 1852H625

907HFigure K.17: Crack-opening displacements—pre- and post-repair—C7 ................... 1853H626

908HFigure K.18: Bottom-fiber strain—A4 ....................................................................... 1854H629

909HFigure K.19: Strain profile—Girder 7—Section 1—A4 ............................................ 1855H629

910HFigure K.20: Strain profile—Girder 8—Section 1—A4 ............................................ 1856H630

l

911HFigure K.21: Bottom-fiber strain—C4 ........................................................................ 1857H631

912HFigure K.22: Strain profile—Girder 7—Section 1—C4 ............................................. 1858H631

913HFigure K.23: Strain profile—Girder 8—Section 1—C4 ............................................. 1859H632

914HFigure K.24: Bottom-fiber strain—A7 ....................................................................... 1860H633

915HFigure K.25: Strain profile—Girder 7—Section 4—A7 ............................................ 1861H633

916HFigure K.26: Strain profile—Girder 8—Section 4—A7 ............................................ 1862H634

917HFigure K.27: Bottom-fiber strain—C7 ........................................................................ 1863H635

918HFigure K.28: Strain profile—Girder 7—Section 4—C7 ............................................. 1864H635

919HFigure K.29: Strain profile—Girder 8—Section 4—C7 ............................................. 1865H636

920HFigure K.30: Deflections—superposition—A1 and A9 ............................................. 1866H637

921HFigure K.31: Deflections—superposition—A1 + A9 ................................................. 1867H638

922HFigure M.1: Strain gage installation—applying degreaser to gage location ............. 1868H646

923HFigure M.2: Strain gage installation—removal of surface irregularities ................... 1869H646

924HFigure M.3: Strain gage installation—initial surface cleaning .................................. 1870H647

925HFigure M.4: Strain gage installation—clean surface prepared for solid epoxy ......... 1871H647

926HFigure M.5: Strain gage installation—application of solid epoxy ............................ 1872H648

927HFigure M.6: Strain gage installation—epoxy surface ................................................ 1873H648

928HFigure M.7: Strain gage installation—rubber coating for moisture protection ......... 1874H649

929HFigure M.8: Strain gage installation—mastic tape for mechanical protection .......... 1875H649

930HFigure M.9: Strain gage installation—gage application with thin epoxy .................. 1876H650

931HFigure M.10: Strain gage installation—gage applied to FRP reinforcement .............. 1877H650

li

932HFigure M.11: Strain gage installation—rubber coating for moisture protection ......... 1878H651

933HFigure M.12: Strain gage installation—mastic tape for mechanical protection .......... 1879H651

934HFigure N.1: Cracked girder with continuity reinforcement details

(Barnes et al. 2006) ............................................................................... 1880H654

935HFigure N.2: Longitudinal configuration profile for FRP

(adapted from Barnes et al. 2006) ......................................................... 1881H655

936HFigure N.3: Cross-sectional configuration of FRP—near diaphragm

(Swenson 2003) ..................................................................................... 1882H656

937HFigure N.4: Cross-sectional configuration of FRP—typical (Swenson 2003) ......... 1883H657

938HFigure N.5: Factored shear demand—simply supported (Swenson 2003) ............... 1884H660

939HFigure N.6: Factored moment demand—simply supported (Swenson 2003) .......... 1885H661

940HFigure N.7: Typical girder-deck composite cross section ........................................ 1886H665

941HFigure N.8: Continuity reinforcement—typical BT-54 cross section

(ALDOT 1988; Swenson 2003) ............................................................ 1887H667

942HFigure N.9: Cross-sectional configuration of FRP—near diaphragm

(Swenson 2003) ..................................................................................... 1888H668

943HFigure N.10: Cross-sectional configuration of FRP—typical (Swenson 2003) ......... 1889H669

944HFigure N.11: Vertical shear reinforcement—location and spacing

(ALDOT 1988; Swenson 2003) ............................................................ 1890H670

945HFigure N.12: Longitudinal configuration profile for

five-layer FRP reinforcement system .................................................... 1891H697

1

Chapter 1

5BINTRODUCTION

1.1 28BPROJECT OVERVIEW

Spans of the elevated portion of interstate highway I-565 in Huntsville, Alabama were

constructed to be multi-span continuous structures for post-construction loads. Elevated

portions of the interstate are shown in Figures 1892H1.1 and 1893H1.2. In 1992, shortly after

construction was completed, large and unexpected cracks were discovered at the

continuous end of many prestressed concrete bulb-tee girders within these spans.

Cracking of two adjacent prestressed concrete girders of I-565 is shown in Figure 1894H1.3.

Figure 1.1: Elevated spans of I-565 in Huntsville, Alabama

2

Figure 1.2: Northbound Bent 11 of I-565 in Huntsville, Alabama

Figure 1.3: Cracked pre-tensioned bulb-tee girders of I-565 (Barnes et al. 2006)

Bottom Flange Cracking

3

The Alabama Department of Transportation (ALDOT) installed false supports under

damaged girders to safely allow for the investigation of the cause of damage and to

determine potential repair solutions, while preventing catastrophic collapse in case of

further deterioration of bridge girders.

Previous investigations conducted by Alabama Department of Transportation

(ALDOT) and Auburn University Highway Research Center (AUHRC) personnel

resulted in determinations that the cracking was a result of restrained thermal

deformations and inadequate reinforcement details, and that the cracking compromised

the strength of the girder end regions (ALDOT 1994; Gao 2003; Swenson 2003). An

externally bonded wet lay-up fiber-reinforced polymer (FRP) repair scheme was

proposed to repair damaged regions and address the perceived strength deficiency

(Swenson 2003). Analysis of pre- and post-repair structural responses to service-level

truck loads was recommended to assess the efficacy of this repair system.

Post-repair bridge testing and resulting conclusions are documented in this thesis.

Conclusions supported by post-repair bridge testing have been used to evaluate in-service

performance of the FRP reinforcement system and to propose design recommendations

for repair of conditions similar to those of the damaged spans of I-565 using FRP.

1.2 29BNEED FOR RESEARCH

Many states have bridge structures that contain spans that were constructed to be multi-

span continuous structures for post-construction loads. The National Cooperative

Highway Research Program (NCHRP) published a report titled Connection of Simple-

Span Precast Concrete Girders for Continuity (NCHRP Report 519) that investigated

some of the different continuous-for-live-load connections used in various states

4

(Miller et al. 2004). The damaged girders of I-565 in Huntsville, Alabama are reviewed

within NCHRP Report 519, which states that very few multi-span continuous bridge

structures exhibit significant cracking similar to what was observed on the Alabama

bridge structures. However, NCHRP Report 519 does state that various respondents to

their survey indicated difficulties associated with the positive bending moment continuity

reinforcement during girder fabrication and bridge construction.

Although NCHRP Report 519 suggests that the damage observed in the Alabama

bridge girders is unique, Auburn University researchers have had several conversations

with transportation officials and consulting engineers from around the United States that

indicate otherwise. NCHRP Report 519 also stated that Alabama bridge structures

continued to perform as designed (Miller et al. 2004). However, this continued

performance is with respect to service conditions and not with respect to the strength-

limit-state.

Bridge structures exhibiting damage conditions similar to those observed in the

damaged spans of I-565 in Huntsville may adequately resist service loads, but repairs

may be necessary to ensure safety for a design overload event, without requiring

complete reconstruction. It is desirable to develop a repair solution for these conditions

that would require minimal traffic disruption and delay during repair. The proposed FRP

reinforcement system, which was installed on Northbound Spans 10 and 11 of I-565 in

Huntsville in December of 2007, provides an unobtrusive repair solution, but this solution

required verification through testing before further implementation could confidently be

recommended. Girders repaired with FRP reinforcement are shown in Figures 1895H1.4 and

1896H1.5.

5

Figure 1.4: Girder 9 of Northbound Spans 10 and 11—repaired

Figure 1.5: Girders 7, 8, and 9 of Northbound Span 10—repaired

6

1.3 30BOBJECTIVE AND SCOPE

The main objective of the research presented in this thesis is to verify that an FRP

reinforcement system is a viable solution for the repair of multi-span continuous

structures that exhibit damage at the continuous end of girders. The specific objectives of

this research include

1. Performing post-repair load tests and comparing measured post-repair bridge

behavior to the bridge behavior observed during pre-repair load tests,

2. Monitoring bridge behavior during a twenty-four hour time period to observe

bridge behavior in response to a change in ambient thermal conditions,

3. Verifying the effectiveness of the FRP reinforcement system in response to

truck loads and ambient thermal conditions, and

4. Developing a design procedure for utilizing FRP reinforcement to repair

bridge structures prone to conditions similar to those observed in the

investigated spans of I-565.

Post-repair bridge testing was conducted in late spring of 2010, and was followed by an

analysis of the observed sensor measurements to satisfy these objectives.

1.4 31BTHESIS ORGANIZATION

A summary of the project background and previous research is presented in Chapter 2 of

this thesis. The project background includes construction details and the cause and

location of damage that was observed soon after the completion of construction.

Previous research includes analyses that assisted with the design of an FRP reinforcement

system, analysis of load testing measurements before the installation of the repair system,

and the development of a finite-element model that was used to analyze modeled bridge

7

behavior before and after the installation of FRP reinforcement. The chapter concludes

with a summary of the FRP reinforcement installation process.

Chapter 3 contains a discussion of the bridge instrumentation details. This discussion

includes the locations and installation procedures for bridge testing sensors. The sensors

installed include deflectometers, crack-opening displacement gages, and surface-mounted

strain gages.

Chapter 4 contains a detailed explanation of bridge testing procedures. The load

testing procedures include truck weights and stop positions. The procedures for

monitoring bridge behavior for a twenty-four hour period are also discussed.

Chapter 5 contains a presentation of the results of analysis following the post-repair

bridge testing. This analysis includes comparisons of pre- and post-repair support

conditions and post-repair behavior. Theoretical analysis of the behavior of a two-span

continuous bridge structure in response to ambient thermal conditions is presented. The

measured behavior in response to thermal conditions observed during bridge monitoring

is also presented.

Chapter 6 includes a recommended design procedure for implementation of this

repair solution on similar bridge structures that exhibit similar damage. An example of

the design procedure is presented in Appendix N. The example is a redesign of an FRP

reinforcement system for the investigated bridge structure using the same FRP material

that has already been installed.

Chapter 7 includes a summary of conclusions supported by the thesis research, and

Chapter 8 is a discussion of recommendations for further research and the installation of

similar repair systems for similar conditions.

8

Chapter 2

6BHISTORY OF THE BRIDGE STRUCTURE AND ASSOCIATED RESEARCH

2.1 32BINTRODUCTION

An elevated portion of Interstate Highway 565 in Huntsville, Alabama, consists of bridge

structures with spans that were constructed to be continuous for live loads. Shortly after

construction, inspectors discovered unexpected cracks in concrete girders near the

interior supports of several continuous spans. These cracks have been further

investigated, and varying repair techniques have been proposed and implemented. This

chapter summarizes the history of the bridge structure, previous mitigation techniques

and bridge-response analysis methods, and the currently implemented fiber-reinforced

polymer strengthening system.

2.2 33BBRIDGE CONSTRUCTION

The elevated I-565 bridge structures were erected during a five-part construction project.

Construction of the bridge structures began in January of 1988 and was completed in

March of 1991 (ALDOT 1994). The elevated spans consist of either steel or prestressed

concrete bulb-tee girders supporting a cast-in-place composite reinforced concrete (RC)

deck. The deck and cast-in-place continuity diaphragms result in simply supported

precast girders acting as two-, three-, or four-span units made continuous for live load to

preclude durability problems associated with open joints (Swenson 2003).

9

2.3 34BSTRUCTURAL GEOMETRY AND MATERIAL PROPERTIES

Specific bridge structures of I-565 in Huntsville were selected to be the main focus of

research efforts. The selected structures are two-span structures that were constructed to

be fully continuous for live loads. These spans consist of similar girder types,

reinforcement details, and continuous bridge decks. Structural geometry and material

property details discussed in this section are presented by ALDOT (1988).

2.3.1 119BSPANS INVESTIGATED

Northbound Spans 4 and 5 were the focus of research efforts that have been reported by

Swenson (2003) and Gao (2003) of the Auburn University Highway Research Center

(AUHRC). These spans each contain nine prestressed concrete bulb-tee girders, and

form a two-span continuous structure with span lengths of 98.29 ft and a radius of

horizontal curvature of about 1950 ft. The length of each span is measured along the

curved centerline of the bridge deck from the centerline of the interior bent to the joint at

the simply supported end of the span.

Northbound Spans 10 and 11 were selected for further research. These spans are

more ideal than Spans 4 and 5 for testing bridge response to service-level truck loads and

thermal conditions because they have zero horizontal curvature. Spans 10 and 11 have

span lengths of 100 ft. Plan and elevation views of Northbound Spans 10 and 11 are

shown in Figures 1897H2.1–1898H2.3.

10

Figure 2.1: Plan view of the two-span continuous unit (ALDOT 1988)

Figure 2.2: Elevation view of the two-span continuous unit (ALDOT 1988)

Span 10 Span 11

Span 10 Span 11

11

Figure 2.3: Detailed plan view of the two-span continuous unit (ALDOT 1988)

Span 10 Span 11

12

2.3.2 120BGIRDER TYPES

Over the length of the elevated portion of I-565, different prestressed concrete girder

types were used within different spans. These girder types include AASHTO girders

(Types I, III, and IV) and bulb-tee girders (BT-54 and BT-63). The AASHTO girders

were prevalent in the original design, but bulb-tee girders were suggested for a majority

of spans during a value engineering redesign of the bridge structures. The final design

consisted of 246 AASHTO girders, 796 BT-63 girders, and 1292 BT-54 girders

(ALDOT 1994). The two-span continuous structure selected for bridge response testing

(Spans 10 and 11) was constructed with BT-54 girders that, over time, exhibited cracking

near their continuous ends. The dimensions of a typical BT-54 girder are shown in

1899HFigure 2.4.

13

Figure 2.4: Cross section of a typical BT-54 girder (ALDOT 1988; Swenson 2003)

Cross-Section Properties

A = 659 in.2

I = 268080 in.4

h = 54 in.

yt = 26.37 in.

3.5‖

2‖ 2‖

36‖

4.5‖

6‖

26‖

42‖

18‖

10‖

2‖

¾‖ chamfer

54‖ 6‖

14

2.3.3 121BPRESTRESSING STRANDS

Each BT-54 girder in the studied spans was reinforced with a total of thirty-eight

prestressing strands during girder fabrication. The strand pattern at each girder end and

midpoint can be seen in Figures 1900H2.5 and 1901H2.6 respectively.

Figure 2.5: Prestressed strand pattern near girder end (ALDOT 1988; Swenson 2003)

3 @ 2‖

2.5‖

5 @ 2‖ 5 @ 2‖

5 @ 2‖

2 @ 1.125‖

8‖ 8‖

2‖

5‖

3‖

Fully bonded strand (0.5‖ Special)

Debonded strand (48‖ debond length, 0.5‖ Special)

Debonded strand (168‖ debond length, 0.5‖ Special)

Fully bonded strand (7/16‖)

15

Figure 2.6: Prestressed strand pattern near girder midpoint

(ALDOT 1988; Swenson 2003)

Thirty-four of the thirty-eight strands are 0.5 in. special, low-relaxation, prestressing

strands that were jacked to a stress of 202.5 ksi during girder fabrication. The remaining

four strands are 7/16 in. diameter, low-relaxation, prestressing strands that were jacked to

a stress of 69.6 ksi during girder fabrication. Due to the low prestressing force, the

7/16 in. strands are assumed to not contribute to the shear or flexural capacity of the

structure (Swenson 2003).

Fully bonded strand (0.5‖ Special)

2 @ 1.125‖

6 @ 2‖

5 @ 2‖ 5 @ 2‖ 2 @ 3‖

8‖ 8‖

2‖

5‖

Fully bonded strand (7/16‖)

2.5‖

16

Six of the thirty-four 0.5 in. special strands were harped during girder fabrication.

The hold-down points for harped strands are 120 in. from the girder midpoint. The

harped strands have a constant eccentricity between hold-down points. The strand profile

typical of the investigated BT-54 girders can be seen in 1902HFigure 2.7.

The other twenty-eight 0.5 in. special strands have a constant eccentricity along the

entire length of each girder. Twelve of the strands with constant eccentricity are partially

debonded. Ten of these strands are partially debonded for a length of 48 in. from the

girder end, and the remaining two strands are partially debonded for a length of 168 in.

from the girder end (ALDOT 1988).

17

Figure 2.7: Prestressed strand profile (Swenson 2003)

120‖

Girder Midpoint

18

2.3.4 122BSHEAR REINFORCEMENT

The vertical shear reinforcement for each girder consists of stirrups cast into each girder

during fabrication. These stirrups are composed of multiple pieces of mild steel

reinforcement. The stirrups near the girder ends have a different steel bar arrangement

compared to the stirrups near midspan as shown in Figures 1903H2.8 and 1904H2.9 respectively. The

details of the different mild steel bars used to make the stirrups can be seen in 1905HTable 2.1.

The spacing of vertical shear reinforcement varies from 3.5 in. near the girder ends to

12 in. near the girder midpoint. The size of stirrup bars also varies. Vertical legs of

stirrups within 24 ft of the girder midpoint are size #4 rebar. The remaining stirrups

outside of this middle region have vertical legs that are size #5 rebar. The location and

spacing of the vertical shear reinforcement along a typical BT-54 girder can be seen in

1906HFigure 2.10 (ALDOT 1988).

19

Figure 2.8: Vertical shear reinforcement near girder end (ALDOT 1988; Swenson 2003)

Fully bonded strand (0.5‖ Special)

Debonded strand (48‖ debond length, 0.5‖ Special)

Debonded strand (168‖ debond length, 0.5‖ Special)

Fully bonded strand

(7/16‖)

MK-351 stirrup,

1.50‖ cover

MK-553 stirrup,

2.125‖ cover

MK-451 stirrup,

1.25‖ cover MK-352 stirrup,

1.125‖ cover

20

Figure 2.9: Vertical shear reinforcement near girder midpoint

(ALDOT 1988; Swenson 2003)

Fully bonded strand

(7/16‖)

MK-451 stirrup,

1.25‖ cover MK-352 stirrup,

1.125‖ cover

MK-452 stirrup,

2.25‖ cover

MK-452 stirrup,

1.75‖ cover

Fully bonded strand (0.5‖ Special)

21

Table 2.1: Stirrup mild steel bar details (ALDOT 1988; Swenson 2003)

Designation Bar Size Location Shape

MK-351 #3 Lower Flange

MK-352 #3 Upper Flange/

Web

MK-451 #4 Upper Flange

MK-452 #4 Web

MK-553 #5 Web

1 in. = 25.4 mm

23.25‖

11‖ 11‖

39.5‖

12‖

58.38‖

6‖

5.75‖

14‖

24.2°

57.13‖

6‖

12‖

22

Figure 2.10: Location and spacing of vertical shear reinforcement (ALDOT 1988; Swenson 2003)

4 spaces

@ 3.5 in.

7 spaces

@ 6 in.

Spaces to midspan

@ 12 in.

-- All stirrups within 24 ft of midspan are #4 bars (MK-452) @ 12 in. spacing.

All other stirrups are #5 bars (MK-553), spaced as shown above.

1.5 in. clear spacing at girder end

23

2.3.5 123BCONTINUITY REINFORCEMENT

During girder fabrication, eight mild steel bent bars were cast into each girder end that

would be made continuous for live loads. These mild steel bars act as positive bending

moment reinforcement. The bent bars are size #6 rebar with dimensions as shown in

1907HFigure 2.11. The locations of the bars within a typical BT-54 cross section are shown in

1908HFigure 2.12.

Each steel bar has a total length of 61 in. Each bar is bent to form a 90-degree hook

with leg lengths of 12 in. and 49 in. During girder fabrication, the longer leg of each bar

was embedded 41 in. within the girder end. During bridge construction, the remaining

20 in. of each bar were cast into the cast-in-place continuity diaphragm. Each bar

extended 8 in. into the continuity diaphragm, and then extended 12 in. vertically within

the continuity diaphragm.

24

Figure 2.11: Continuity reinforcement—continuity diaphragm detail

(ALDOT 1988; Swenson 2003)

8‖

MK-651 bent bar detail

49‖

12‖

3‖

C L

Black – 9‖ x 24.5‖ x ¾‖

Elastomeric Bearing Pad

Checked – ¾‖ Premolded

Bituminous Filler

¾‖ diameter dowel,

21‖ long

MK-651 bent bar

(8 per girder end

made continuous)

25

Figure 2.12: Continuity reinforcement of a typical BT-54 cross section

(ALDOT 1988; Swenson 2003)

2‖

3.5‖

5‖

1.75‖

3‖ 6‖ 6‖ 4‖ 7‖

4‖ 19.5‖

14‖

1.75‖

Mild Steel Bent Bar (3/4‖ diameter)

26

2.3.6 124BBRIDGE DECK

The bridge deck for Spans 10 and 11 was constructed to be one continuous slab of cast-

in-place reinforced concrete. The bridge deck has a consistent thickness of 6.5 in. and an

additional ―build up depth‖ over each girder that varies from 3 in. near the support to

1 in. near midspan. Mild steel reinforcing bars were cast into the slab during construction

to provide reinforcement in the longitudinal and transverse directions. The longitudinal

reinforcement resists tension forces in the deck slab induced by shear and acts as negative

bending moment reinforcement for the bridge structure. The transverse deck

reinforcement does not contribute to the calculated shear or flexural capacity of the

structure (Swenson 2003).

The longitudinal reinforcement within a typical deck slab cross section over an

exterior girder can be seen in 1909HFigure 2.13, and the reinforcement within a deck slab cross

section over an interior girder is shown in 1910HFigure 2.14. The size #7 bars are only

continuous over the interior support, and not continuous throughout the entire two-span

structure. The size #7 bars extend a minimum of 15 ft from the centerline of the

continuity diaphragm, and some of the size #7 bars extend an additional 10 ft. All other

longitudinal reinforcement is continuous throughout both spans.

The slab was also designed to act compositely with the prestressed bridge girders.

During girder fabrication, the stirrups that were cast into each girder were long enough to

protrude from the top surface of the girder. The top surface of each girder was also

roughened during girder fabrication. During construction, the protruding stirrups were

cast into the cast-in-place deck slab. The stirrups and roughened girder surfaces promote

composite behavior between the deck slab and bridge girders.

27

Figure 2.13: Cross section view of deck slab reinforcement over an exterior girder (ALDOT 1988; Swenson 2003)

Transverse deck reinforcement

#5 bars both top and bottom

1‖ clear cover on bottom of composite

slab (typical)

#5 Bars, Bottom of Slab (E1)

#4 Bars, Bottom of Slab (D3) #4 Bars, Top of Slab

(D1) #7 Bars, Top of Slab (F1 and F2)

#7 Bars, Bottom of Slab (F3 and F4)

2‖ clear cover on top of composite

slab (typical)

28

Figure 2.14: Cross section view of deck slab reinforcement over an interior girder (ALDOT 1988; Swenson 2003)

Transverse deck reinforcement #5 bars

both top and bottom

1‖ clear cover on bottom of composite

slab (typical)

#5 Bars, Bottom of Slab (E1)

#4 Bars, Bottom of Slab (D3)

#4 Bars, Top of Slab

(D1) #7 Bars, Top of Slab (F1 and F2)

#7 Bars, Bottom of Slab (F3 and F4)

2‖ clear cover on top of composite

slab (typical)

29

2.4 35BUNEXPECTED CRACKING

Hairline cracks in many of the prestressed bulb-tee girder ends made continuous for live

loads were discovered during a routine inspection in 1992. The occurrence of hairline

cracks is not uncommon in prestressed concrete girders at an early age, and is not

necessarily a cause for serious concern, but the presence of early-age cracking did justify

further evaluation. In 1994, a second inspection revealed that many of the hairline cracks

had propagated and widened (ALDOT 1994). Some cracks had extended through the

bottom flange, into the web, and as far as the intersection of the web and upper flange.

Typical crack widths ranged from 0.002 in. (0.05mm) to 0.25 in. (6 mm)

(Swenson 2003).

2.4.1 125BCRACK LOCATIONS

Cracked girders were found at ten different sites between Eighth Street and Oakwood

Avenue (ALDOT 1994). The portion of I-565 containing cracked bridge girders is

illustrated in 1911HFigure 2.15. The pattern of cracking found in one BT-54 girder of Span 5 is

illustrated in 1912HFigure 2.16. The inclined web cracks were limited to approximately 0.06 in.

(1.5 mm) due to the transverse reinforcement that the cracks intersected. The vertical

bottom-flange cracks only crossed the longitudinal prestressed strands and crack widths

were not controlled by transverse reinforcement. Some of the larger bottom-flange

cracks with widths up to 0.25 in. (6 mm) were visible from the ground in 1994, as shown

in 1913HFigure 1.3.

The 1994 investigation also resulted in the discovery of continuity diaphragm

cracking. The two types of cracks present in some of the continuity diaphragms were

face cracks and end cracks. An example of a typical continuity diaphragm face crack can

30

be seen in 1914HFigure 2.18, and an example of a typical diaphragm end crack can be seen in

1915HFigure 2.19. Approximately 57 percent of bents supporting bulb-tee girders contain

diaphragm face cracks, and roughly 85 percent of bent contain diaphragm end cracks.

All interior bents in two-span continuous structures constructed with BT-54 girders

exhibit diaphragm end cracks (ALDOT 1994).

Figure 2.15: Portion of I-565 containing cracked bridge girders (Swenson 2003)

Pratt Ave.

Oakwood Ave.

Holmes Ave.

8th Street

Portion of I-565 containing

bridges with cracked girders

N

Clinton Ave.

I-565 231/431

31

Figure 2.16: Cracking pattern in end region of precast girder (Barnes et al. 2006)

Figure 2.17: Cracked pre-tensioned bulb-tee girders (Barnes et al. 2006)

Crack Pattern

Girder 5—Span 5—West Face

Precast BT-54 girder

Cast-in-place deck

Cast-in-place

continuity diaphragm

1 ft 2 ft 3 ft 4 ft 5 ft 6 ft 7 ft 8 ft

32

Figure 2.18: Typical diaphragm face crack (Swenson 2003)

Figure 2.19: Typical diaphragm end crack (Swenson 2003)

33

Due to the 1994 discovery that cracks were widening over time, a survey

encompassing all of the Huntsville I-565 prestressed concrete bridge girders was

conducted to locate cracks and document their size. For each girder type, the total

number of girders was recorded as well as the number of girders associated with girder or

diaphragm cracking. It was determined that typical AASHTO I-shaped girders exhibited

no cracking, and that damaged regions were only found where bulb-tee girders were

made continuous for live loads. It was also concluded that eighty-five percent of the

bents supporting continuous ends of bulb-tee girders exhibited continuity-diaphragm end

cracks (ALDOT 1994). The results of the girder survey performed by ALDOT personnel

are shown in 1916HTable 2.2.

Table 2.2: Summary of cracking in prestressed concrete girders made

continuous for live loads (ALDOT 1994)

BT-54 Girders BT-63 Girders

AASHTO

Types I, III, IV

Girders

No. of

Girders

No. of

Cracked

Girders

No. of

Girders

No. of

Cracked

Girders

No. of

Girders

No. of

Cracked

Girders

Mainline 732 33 656 9 72 0

Ramp 560 24 140 8 174 0

Total 1292 57 796 17 246 0

2.4.2 126BPREVIOUS REPAIRS AND SAFETY MEASURES

The severity of the cracks required immediate attention, and ALDOT personnel

responded to the situation accordingly. The initial repair technique involved injecting the

cracks with a structural epoxy, as shown in 1917HFigure 2.20, in an attempt to seal existing

cracks and prevent future crack growth. However, new cracks often formed near the

34

epoxy-injected cracks, and many epoxy-injected cracks reopened, indicating that this

repair technique was ineffective. Other safety measures had to be implemented before a

more effective repair method could be determined.

Steel frame false supports, as shown in 1918HFigure 2.21, were installed near all bents that

were associated with girders containing cracked end regions. The false supports were

positioned slightly beyond the cracked regions. The false supports were also installed

with clearance of roughly 1 in. between the top of the false support and the bottom of the

girder. Elastomeric bearing pads were installed between the false supports and each

girder bottom to allow the false supports to carry loads, if necessary, while limiting

impact forces that could result in damage to the girders or false supports. Although the

bearing pads were installed to limit impact-related damage, it was undesirable for bearing

pads to remain in contact with bridge girders. An installed bearing pad with proper space

between the pad and girder is shown in 1919HFigure 2.22. A bearing pad that is in contact with

a girder and transferring loads through the false support is shown in 1920HFigure 2.23.

35

Figure 2.20: Cracks injected with epoxy (Fason 2009)

Figure 2.21: Steel frame false supports (Fason 2009)

36

Figure 2.22: False support bearing pad with gap between pad and girder (Fason 2009)

Figure 2.23: False support bearing pad in contact with girder (Fason 2009)

37

2.4.3 127BCAUSES FOR CRACKING

After conducting initial repairs and safety measures, the affected bridges were monitored

to determine what caused the severe cracking. Ningyu Gao (2003) of Auburn University

analyzed an interior BT-54 girder line of a typical two-span continuous portion of the

elevated I-565 bridge structure in search of a cause for the extensive cracking. Gao

calculated stresses in the girder, deck slab, and continuity diaphragm while considering

construction sequence, time-dependent effects, and temperature distribution. The

primary focus of the analysis was identifying the cause of positive bending moments near

the continuous ends of the girders.

2.4.3.1 4338BCONSTRUCTION SEQUENCE

The construction sequence is related to the age of the girder when the deck and the

diaphragm are cast. It was concluded with further investigation of the Huntsville I-565

bridge structure that the staged casting of the bridge deck and diaphragms was not

performed in the order originally specified in the contract documents (ALDOT 1988).

Previous research (Ma et al. 1998) has shown that the amount of time between diaphragm

and deck casting can significantly affect the behavior of this type of bridge system.

Gao (2003) concluded from a step-by-step analysis that the actual construction sequence

did result in slightly smaller bottom-flange compressive stresses near the continuity

diaphragm when compared to the stresses expected following the specified construction

sequence. However, the difference between the two stresses was not large enough to be a

likely cause of the observed tensile cracking.

38

2.4.3.2 4339BTIME-DEPENDENT EFFECTS

Time-dependent effects that could potentially cause cracking in the restrained girder ends

include creep due to prestress forces and concrete shrinkage. The creep and shrinkage

could cause enough of a member length change to induce a positive moment at the

restrained girder end. However, Gao (2003) concluded that time-dependent effects are

not large enough to be the primary cause of cracking—especially considering the early

age at which the cracking occurred.

2.4.3.3 4340BTEMPERATURE EFFECTS

Ambient thermal conditions can result in temperature variations between the top of the

bridge deck and the bottom of the girders. This temperature distribution can result in an

upward deflection known as ―sun cambering‖ in spans constructed to be continuous for

live loads. This upward deflection due to temperature has the potential to induce bottom-

flange tensile stresses associated with positive bending moments near the continuity

diaphragm. It has been concluded that the relevant design standards used to design the

I-565 bridge structures did not supply sufficient information regarding stresses due to

temperature gradients (Barnes et al. 2006).

ALDOT personnel recorded temperature data at several different times during the

investigation. The worst-case temperature gradient recorded occurred at 14:15 CST on

May 19, 1994. An ambient temperature of 64.8° F (18.2° C) was reported. The deck

surface reportedly had a temperature of 95.7° F (35.4° C), while the temperature at the

bottom of a girder was 52.0° F (11.1° C), which resulted in a temperature difference of

43.7° F (24.3° C) (ALDOT 1994).

39

Ambient, deck, and girder temperatures were only monitored for a few days, and it is

unlikely that these temperatures represent the worst load scenario related to temperature

distributions that the bridge has experienced in its lifetime. The temperature difference of

43.7° F (24.3° C) measured for the bridge structure in Huntsville, Alabama is less than

the maximum temperature difference of 48.6° F (27.0° C) calculated by Potgieter and

Gamble (1989) for a bridge structure in Nashville, Tennessee (the city nearest to

Huntsville, Alabama within the scope of their report). It is feasible for the ambient

temperature in Huntsville to exceed 100° F (38° C) during an extreme event on a sunny

summer day, which would likely result in a greater temperature difference than the

difference that resulted from the ambient temperature of 64.8° F (18.2° C) measured on

May 19, 1994. Due to direct sun exposure, an increased ambient temperature will likely

have a greater effect on a deck surface than a girder bottom, resulting in an increased

temperature difference that induces tensile stresses of greater magnitude near the

continuity diaphragm (Gao 2003).

2.4.3.4 4341BINTERNAL REINFORCEMENT DETAILS

The bottom-flange flexural cracking near the continuous ends of these girders is reported

to be associated with positive bending moments related to restrained forces of thermal

load conditions. The maximum positive bending moment due to thermal load conditions

would occur at the continuity diaphragm, which explains the diaphragm face and end

cracks, but in some cases the cracks do not correspond with the point of maximum

moment. Along multiple concrete girders, cracking has been observed to originate at

distances from the continuity diaphragm that are similar to other origins of cracking on

other girders. The internal reinforcement details for the BT-54 girders of I-565 were

40

investigated to determine if localized stress concentrations could explain the similar crack

locations (Barnes et al. 2006).

Prestressing strand debonding and continuity reinforcement details discussed in

Sections 1921H2.3.3 and 1922H2.3.5 have an effect on the positive bending moment capacity near the

continuity diaphragm. The continuity reinforcement length of 41 in. and the debonded

length of 48 in. for more than one-third of the strands have been superimposed with the

crack pattern observed at Girder 5 of Span 5, as shown in Figure 1923H2.24.

Figure 2.24: Cracked girder with continuity reinforcement details (Barnes et al. 2006)

7 in.

41 in.

Crack Pattern

Girder 5—Span 5—West Face

Precast BT-54 girder

Cast-in-place deck

Cast-in-place

continuity diaphragm

1 ft 2 ft 3 ft 4 ft 5 ft 6 ft 7 ft 8 ft

Continuity Reinforcement

Size #6 Rebar

12 of 28 bottom-flange

prestressed strands are

debonded at least 48 in.

41

During a critical thermal event, bottom-flange tensile stresses could be induced near

the continuity diaphragm along the girder. The debonded strands result in cross sections

with a relatively weak positive moment bending capacity compared to the midspan cross

sections. Due to relatively weak cross sections for a distance of 48 in. and local stress

concentrations that can occur near the continuity reinforcement termination point at

41 in., cross sections near the continuity reinforcement termination location are likely

points of origin for flexural cracking in response to positive moment bending.

2.4.4 128BRAMIFICATIONS OF CRACKING

Cracking within the anchorage zone of prestressed strands has the potential to reduce the

effective prestress force, which consequently reduces the shear and flexural capacities of

the girder. Cracks that remain open after the initiating event are an indication of inelastic

behavior at the cracked cross section. This inelastic behavior could be caused by strands

either yielding or slipping at the crack locations.

Yielding of prestressed strands at a crack location is one type of failure that results in

a reduction of effective prestress force. Inelastic behavior caused by strand yielding

results in permanent elongation of the strand, allowing crack widths to remain open after

crack inducing loads are removed. A portion of the strain in the prestressing strand

would be lost, which would result in a reduction of the effective prestressing force

transferred to the end region of the girder.

In order for yielding to occur, yield level stresses must be developed in the

prestressed strand at the crack location. This requires that the strands be adequately

anchored on both sides of the crack. Swenson (2003) calculated the development length

of a 0.5 in. special prestressing strand to be 80 in. in accordance with Article 5.11.4.2 of

42

the AASHTO LRFD Bridge Design Specifications (2002). Swenson also noted that the

typical cracking in the I-565 girders occurs within 41 in. of the continuous girder end.

Since the strands are only anchored a distance roughly half of the full development length

before the crack location, development of yielding stresses in the prestressing strands is

not likely.

Slipping of prestressed strands at the crack location also results in the reduction of the

effective prestress force transferred to the end region of a girder. Adequately developed

prestressed strands result in concrete compressive stresses which increase shear capacity.

Strand slip due to a lack of effective anchorage reduces pre-compression effects and may

also result in girders with insufficient resistance to shear forces in the girder end region.

Swenson (2003) determined that the theoretical total slip resulting if all prestressing

force was lost corresponded to the range of crack widths present in the I-565 girders.

Swenson concluded that the prestressing strands slipped as a result of the cracks and that

it is appropriate and conservative to assume that the prestressing force in the strands has

been completely lost between each crack location and girder end. Visual inspection of

the girders in 2010 indicated that the girder end regions have experienced much less

camber curvature over time than the rest of the span. This agrees with Swenson’s

contention that much of the effective prestress in the end regions has been lost.

2.5 36BBRIDGE BEHAVIOR ANALYSIS

Swenson (2003) used analytical methods to determine if the prestressed bulb-tee girders

have strength deficiencies. Different girder behaviors and analysis methods were

considered. The results of this analysis were taken into consideration during the design

43

of an externally bonded fiber-reinforced polymer (FRP) reinforcement repair method.

Bridge behavior analysis from Swenson (2003) is summarized in this section.

2.5.1 129BBEHAVIOR TYPES CONSIDERED

The two-span structures of I-565 were designed to behave as fully continuous structures

for live loads. However, three possible girder behavior types were considered during

analysis. The two-span structures have been analyzed as behaving as either

Two simply-supported spans with no continuity at the interior support,

One fully continuous structure, as originally constructed, or

A two-span continuous structure with internal hinge behavior at crack

locations.

2.5.2 130BANALYSIS METHODS

The three possible bridge behaviors were evaluated with three analysis methods. The

three analysis methods include

Elastic structural analysis,

Sectional model analysis, and

Strut-and-tie model analysis.

Factored ultimate shear and moment envelopes for both interior and exterior girders were

determined with elastic structural analysis. Shear and moment capacities of a typical

cracked BT-54 girder were determined with sectional model analysis. The calculated

capacities were then compared to the factored ultimate shear and moment envelopes to

determine the location and magnitude of strength deficiencies. The forces transferred

through the prestressed strands and future externally bonded fiber-reinforced polymer

44

(FRP) reinforcement were determined with strut-and-tie model analysis. An adequate

FRP reinforcement design was formulated based on the resistance force required of the

FRP at the crack location.

2.5.2.1 4342BELASTIC STRUCTURAL ANALYSIS—UNFACTORED DEMANDS

Elastic structural analysis of the two-span structure was conducted using structural

analysis software. Shear and bending moment reactions in response to unfactored live

loads were determined for each of the three behavior type models. Analysis of the simply

supported model resulted in

A maximum positive bending moment of around 26,000 kip-in. at midspan,

A maximum shear force of roughly 96 kips at the supports, and

No negative moments.

Analysis of the two-span fully continuous model resulted in

A maximum shear force of roughly 87 kips at the non-continuous support,

A maximum shear force of roughly 105 kips at the interior support,

A maximum positive bending moment of roughly 19,200 kip-in. nearly

500 in. from the non-continuous end, and

A maximum negative moment of roughly 22,000 kip-in. at the interior

support.

Analysis of the two-span continuous model with an internal hinge resulted in reactions

that were bounded in magnitude by the other two models. These reactions include

a less severe maximum shear force at the interior support compared to both the simply

supported and fully continuous model, less severe maximum positive moment compared

45

to the simply supported model, and a less severe maximum negative moment at the

interior support compared to the continuous model. Due to distribution factors calculated

for the two-span continuous bridge structure, the live load effects for ultimate shear

demand are more severe for interior girders than exterior, and the live load effects for

ultimate moment demand are more severe for exterior girders.

2.5.2.2 4343BSECTIONAL MODEL ANALYSIS—STRENGTH CAPACITIES

Strength capacities for a typical cracked BT-54 girder were determined with sectional

model analysis. The strength capacities were compared to the factored ultimate load

demands determined for each type of behavior. The actual behavior may be more similar

to the behavior expected of the continuous model with an internal hinge at the crack

location, but the factored load demands of both the simply-supported and continuous

bridge behavior were satisfied when designing a repair method for the strength

deficiencies.

Simply supported behavior was determined to control the factored ultimate shear

demand, exceeding the shear capacity of a typical cracked BT-54 girder by as much as

49 kips for an interior girder and 4 kips for an exterior girder.

Simply supported behavior was determined to control the factored ultimate positive

moment demand, exceeding the positive moment capacity of a typical cracked BT-54

girder for cross sections located between the cracked cross section and the interior

support. Due to the assumption that the prestressed strands have slipped and the prestress

force has been lost, a strength reduction factor of 0.90 for flexure in non-prestressed

concrete members was applied in accordance with Article 5.5.4.2.1 of the AASHTO

LRFD.

46

Continuous behavior was determined to control the factored ultimate negative

moment demand, exceeding the negative moment capacity of a typical cracked BT-54

girder. The negative moment capacity at the continuous end of a typical exterior girder

was determined to be deficient for a length of 48 in. from the interior support.

Simply supported behavior was determined to control the longitudinal reinforcement

capacity calculated in accordance with Article 5.8.3.5 of AASHTO LRFD (2002). The

longitudinal reinforcement capacity provided was determined to be unsatisfactory over a

length of 14 in. from the exterior support and over a length of 64 in. from the interior

support. The longitudinal reinforcement at the cracked end was determined to be

insufficient for a length of roughly 20 in. beyond the typical crack location within the

two-span bridge structure.

2.5.2.3 4344BSTRUT-AND-TIE ANALYSIS—FLOW OF FORCES

Forces within a BT-54 girder with external reinforcement added to the bottom flange

were determined with strut-and-tie model analysis. A typical strut-and-tie model is

presented in 1924HFigure 2.25.

47

Figure 2.25: Typical strut-and-tie model (Swenson 2003)

48

Three separate models (A, B, and C) were produced to analyze the flow of forces within

one girder for each of the three prospective bridge behavior conditions. Specific ties

within the strut-and-tie models represent forces required to be carried by the longitudinal

reinforcement. During the design of an external reinforcement repair method, the tensile

capacity of the longitudinal reinforcement should satisfy the factored ultimate tensile

force demand along the entire length of each tie.

Model A represents a simply supported girder with FRP reinforcement. Load

configurations were examined to produce maximum shear and positive moment effects at

the assumed cracked cross section. The maximum factored ultimate tensile force

expected in the FRP reinforcement was 255 kips and the tensile force expected in

prestressing strands at the same distance from the interior support was 300 kips. As the

distance from the interior support increased, the tensile force expected in the FRP

reinforcement decreased and the force expected in the prestressing strands increased.

The element representing the FRP reinforcement furthest from the interior support

expected a factored ultimate tensile force of 62 kips and the element representing the

prestressing strands at that same distance from the interior support expected a tensile

force of 491 kips. The expected factored ultimate tensile force in the element

representing the prestressing strands following the curtailment of the FRP reinforcement

was 631 kips.

Model B represents a girder that is part of a two-span structure made fully continuous

for live loads. Load configurations were examined to produce maximum shear effects at

the assumed cracked cross section. The ties representing the longitudinal tensile

reinforcement were primarily in compression near the cracked cross section. None of the

49

ties representing the FRP reinforcement were expected to be in tension. The element

representing the FRP reinforcement furthest from the interior support expected a factored

ultimate compressive force of 9 kips and the element representing the prestressing strands

at that same distance from the interior support expected a tensile force of 150 kips. The

expected factored ultimate tensile force in the element representing the prestressing

strands following the curtailment of the FRP reinforcement was 344 kips.

Model C represents a girder that is part of a two-span structure made continuous for

live loads, but contains an internal hinge representing a cracked cross section. Load

configurations were examined to produce maximum shear effects at the assumed cracked

cross section. The flow of forces in Model C were similar to the simply supported model

(Model A), but the tensile forces expected in the longitudinal reinforcement decreased in

magnitude. The maximum factored ultimate tensile force expected in the FRP

reinforcement was 140 kips and the tensile force expected in prestressing strands at the

same distance from the interior support was 189 kips. As the distance from the interior

support increased, the tensile force expected in the FRP reinforcement decreased and the

force expected in the prestressing strands increased. The element representing the FRP

reinforcement furthest from the interior support expected a factored ultimate tensile force

of 35 kips and the element representing the prestressing strands at that same distance

from the interior support expected a tensile force of 294 kips. The expected factored

ultimate tensile force in the element representing the prestressing strands following the

curtailment of the FRP reinforcement was 552 kips.

It was determined that the simply supported model (Model A) should control the

required tensile capacity of the longitudinal reinforcement including the prestressing

50

strands and external FRP reinforcement. Although the structure may not be purely

simply supported, the girders should be strengthened to dependably resist factored

ultimate loads for all three potential behavior types.

Longitudinal reinforcement tensile forces must be fully developed at the end of the tie

closest to the support. For the tie extending from the nodal zone at the interior support

(Member 1), the tensile force must be developed at the point where the centroid of the

reinforcement extends beyond the extended nodal zone (ACI Committee 318 2002).

During the design of an FRP reinforcement repair method, the FRP reinforcement forces

were considered fully developed at the inside face of the bearing pad.

2.6 37BDESIGN OF EXTERNAL FIBER-REINFORCED POLYMER STRENGTHENING SYSTEM

Four FRP-reinforcement repair designs were presented by Swenson (2003). The FRP

reinforcement systems were designed to either correct strength deficiencies that have

resulted from cracking, or prevent strength deficiencies from occurring. Three

complementary objectives were considered during the design of potential strengthening

systems. Two objectives were to provide adequate positive bending resistance, as well as

adequate shear resistance, regardless of continuity conditions. The other objective was to

shift future cracking, associated with the restrained deformations of time- and

temperature-dependent effects, to a more acceptable location at the face of, or within, the

continuity diaphragm.

The FRP reinforcement selected for the design of potential repair systems was the

Tyfo SCH-41 composite manufactured by Fyfe Co. This product is a wet lay-up system

comprised of Tyfo SCH-41 reinforcing fabric and Tyfo S epoxy. Tyfo SCH-41

reinforcing fabric is comprised of unidirectional carbon fibers backed with a glass veil to

51

increase and support fabric stability during installation. Tyfo S epoxy is a two-part

adhesive used to both saturate the composite fabric and bond the fabric to the concrete.

The repair solution recommended by Swenson (2003) was a 4-ply FRP system

applied near the continuity diaphragm along the bottom flange of every girder, even those

which are uncracked. The longitudinal and cross sectional configurations of the

recommended 4-ply FRP system are shown in Figures 1925H2.26–1926H2.28.

52

Figure 2.26: Longitudinal configuration profile for FRP (Barnes et al. 2006)

6.5 in.

130 in.

3 @ 6 in.

Four plies of wet layup,

CFRP fabric

53

Figure 2.27: Cross-sectional configuration of FRP near diaphragm (Swenson 2003)

Figure 2.28: Cross-sectional configuration of FRP beyond bearing pad (Swenson 2003)

6.5‖

Inside face of

bearing pad

Face of continuity

diaphragm

B

B

Section B

Total effective width of

FRP reinforcement

bonded to girder = 58 in.

3‖

21‖

21‖

6.5‖

A

A

Section A

Total effective width of

FRP reinforcement

bonded to girder = 30 in.

Bearing pad

3‖

Inside face of

bearing pad

Face of continuity

diaphragm

54

The FRP system terminates at a distance of 130 in. from the face of the continuity

diaphragm. Only the first installed layer of FRP extends the full 130 in. from the

diaphragm. Each subsequently installed layer terminates 6 in. earlier than the previous

layer to allow for the gradual transfer of forces into the FRP and to minimize stress

concentrations at the termination points. FRP applied to the bottom surface of the flange

cannot extend to the continuity diaphragm because of the girder bearing; instead it

extends to roughly 10 in. from the face of the diaphragm, and terminates within 1 in. of

the bearing pad.

2.7 38BLOAD TESTS PRIOR TO FRP REINFORCEMENT INSTALLATION

Load tests scheduled to be performed before and after installation of the FRP system

were planned to quantify the effectiveness of the FRP reinforcement. The pre-repair load

tests were conducted on the nights of May 31, and June 1, 2005. Specific girders were

instrumented to document responses to various load conditions. Two ALDOT load

trucks were positioned to apply loads to the bridge structure at designated locations.

General behavior of the damaged bridge structure was analyzed with measured responses

to the pre-repair load tests. Detailed documentation of the instrumentation, procedures,

and results of pre-repair testing has been reported by Fason (2009) and is summarized in

this section.

The instrumentation and procedure of the pre-repair testing were similar to those of

the post-repair testing documented in this thesis. Specific details regarding the setup and

execution of post-repair testing can be found in Chapters 3 and 4 of this thesis.

55

2.7.1 131BINSTRUMENTATION FOR PRE-REPAIR LOAD TESTING

Prior to pre-repair testing, Girders 7 and 8 of Northbound Spans 10 and 11were

instrumented with sensors designated to measure girder responses to varying load

conditions. The installed sensors include

Crack opening displacement (COD) gages,

Deflectometers, and

Surface-mounted strain gages.

A total of four COD gages, one per instrumented girder, were installed. Each COD gage

was installed near the continuity diaphragm to span a single crack that extends into the

web on each instrumented girder. A total of twelve deflectometers were positioned

underneath the instrumented girders. A total of fifty-six surface-mounted strain gages

were installed on the concrete surface of the instrumented girders. Eight cross sections

contain gages at varying heights within the cross section, while eight other cross sections

have only one concrete gage on the bottom surface of the bottom flange.

Sensor installation procedures prior to pre-repair testing have been described by

Fason (2009). The majority of these sensors were maintained for post-repair testing, and

specific post-repair sensor instrumentation details from can be found in Chapter 3 of this

thesis.

2.7.2 132BPROCEDURES FOR PRE-REPAIR LOAD TESTING

Three distinct horizontal truck alignments represented load truck traverse lanes. Each

traverse lane contained nine stop positions. Load trucks were held at stop positions long

enough for sensors to measure girder response.

56

The first night of testing was dedicated to acoustic emissions testing. Analysis of the

measurements from the acoustic emissions sensors do not fall within the scope of this

thesis, but the sensors installed for static load testing did measure girder responses to the

static truck positions of the acoustic emissions test.

The second night of testing included a repeat of the acoustic emissions test followed

by static load testing at all stop positions. Each stop position was recorded three times to

allow for averaging and elimination of outliers. Static load testing concluded with a

superposition test.

Pre-repair testing procedures have been reported by Fason (2009). The majority of

these load tests were repeated during post-repair testing, and specific details of post-

repair load testing procedures can be found in Chapter 4 of this thesis.

2.7.3 133BRESULTS OF PRE-REPAIR LOAD TESTING

The overall bridge behavior was analyzed following the pre-repair tests. Fason (2009)

determined that the girders were not acting as simply supported girders, which was the

worst-case behavior selected by Swenson for design of the FRP system. It was also

determined that, at the time of the pre-repair load tests, the girders were not behaving as

though they were hinged at the crack locations. It was noted by Fason that crack sizes

observed during testing were visibly not as large as the crack sizes observed during

sensor installation.

The superposition test was conducted to assess if the damaged bridge structure

exhibited linear elastic behavior. It was determined that the deflections measured during

superposition testing indicated that the bridge was exhibiting responses similar to linear-

elastic behavior. Although the overall bridge behavior was considered to be linear-

57

elastic, there were some discrepancies with the localized measurements of the crack-

opening devices and strain gages. The cracks within the girders were observed to be

behaving similar to a nonlinear spring, with the stiffness factor increasing as the

deflection increased and crack openings decreased.

The influence of the false supports on bridge behavior during the pre-repair tests was

also reported. A strain gage installed on one column of the false supports measured a

small compressive strain during normal traffic conditions, which indicated that the false

supports were providing some actual support during normal traffic conditions. Strains

measured near the bent during superposition testing were also reportedly affected by the

presence of the false supports. When only one span was loaded, the false supports under

that span seemed to carry significant load, reducing the strain measured at the bent.

When both spans were loaded simultaneously, the continuity effects that promote an

upward deflection of the opposite span allowed for the false supports under each span to

carry fewer loads individually.

It was concluded by Fason (2009) that direct comparisons between pre- and post-

repair measured responses would not be independently indicative of the effectiveness of

the FRP repair. This was based on the assumption that the weather conditions during

post-repair testing could be more conducive to wider crack openings immediately prior to

load testing, and the fact that the false support bearing pads would be removed during the

installation of the FRP reinforcement.

2.8 39B FINITE-ELEMENT ANALYSIS OF BRIDGE BEHAVIOR

Shapiro (2007) used ABAQUS/CAE to develop a finite element model (FEM) to

represent the elevated two-span section of I-565 being investigated. Information

58

regarding FEM development including: element selection, member geometry, material

properties, support conditions, member connections, and load application has been

detailed by Shapiro (2007). Once the fundamental model was created, the model was

refined in three stages. Load test results were used to verify and refine the model as

necessary. The final stage of the refinement process became the pre-repair condition

model. Once a pre-repair model was established, the FRP reinforcement was then added

to provide expected results for the post-repair load tests. The unintended support prvided

by the false supports was not considered in the model development. A summary of the

finite-element model analysis presented by Shapiro (2007) is discussed in this section.

2.8.1 134BUNCRACKED MODEL

The first stage of model refinement assumes an ideal scenario of uncracked girders.

When compared to the pre-repair load test results, the Uncracked model results generally

exhibit more compression (or less tension) strain on the bottom surface of the bottom

flange than observed during testing. This discrepancy was even more evident at the cross

sections near the cracked region, especially comparing results associated with midspan

loadings. The Uncracked model overestimates the continuity of the cracked girder-

system.

2.8.2 135BCRACKED MODEL

The second stage of model refinement incorporated ABAQUS seams within the model to

represent existing cracks. The resulting Cracked model represents a worst-case scenario

of no reinforcement contribution at crack locations. The seams cut through the concrete

and steel as if the steel has fractured at the crack locations or the bond between the steel

and the concrete has deteriorated to the extent that no stresses can be transferred from the

59

concrete to the steel. As a result, the model suggests that no bending moment is

developed near the crack locations. The load test results are more complicated and do not

reflect the zero strain behavior suggested by the Cracked model results.

2.8.3 136BCRACKED-WITH-REINFORCEMENT MODEL

The Cracked model was refined by accounting for the presence of steel at the cracked

cross sections. A Cracked-with-Reinforcement model was developed by adding two

groups of reinforcing steel to represent the draped and undraped prestressing strands.

Although this reinforcement was added, no attempt was made to apply a prestressing

force to the model since it was considered unlikely that the prestress force would be

effective at the cracked sections. The Cracked-with-Reinforcement model results fell

between those of the Uncracked and Cracked models, better resembling the pre-repair

load test results.

2.8.4 137BPRE-REPAIR MODEL

Through further analysis it was suggested that the Cracked-with-Reinforcement model

could be refined by adding seams in the model to represents cracks at the face of the

continuity diaphragm. The addition of seams at the face of the continuity diaphragm

yielded results that best resembled the pre-repair load test results. This refined model

became the Pre-Repair model to officially compare analytical results to experimental

load test results. This model was also refined by modeling the addition of the FRP

reinforcement to estimate the post-repair behavior of the bridge structure.

60

2.8.5 138BPOST-REPAIR MODEL

The wet lay-up FRP reinforcement was modeled to behave as a laminate, or thin plate.

The FRP reinforcement material properties were modeled as both isotropic and laminar.

The isotropic material exhibits the same properties in all directions. The laminar material

acts as a simplified form of an orthotropic material, which differentiates material

properties in principal or perpendicular directions to each other. Shapiro (2007)

concluded that the laminar representation of the FRP material more accurately modeled

the orthotropic properties of the FRP reinforcement selected to be installed. The laminate

FRP reinforcement was added to the Pre-Repair model to create a Post-Repair model for

comparison with the results of the post-repair load tests.

2.9 40BINSTALLATION OF EXTERNAL FRP REINFORCEMENT

FRP reinforcement installation, which took place during December of 2007, was

performed in accordance with the ALDOT Special Provision regarding the use of fiber

reinforced polymer for girder repair. The on-site activities taking place from

December 11, through December 19, 2007 were documented by Jiangong Xu for the

AUHRC. Xu, an Auburn Univeristy research assistant at the time of the installation

process, documented activities including

Surface preparation,

Adhesion testing of Tyfo S epoxy on concrete surface,

Preparation of FRP-composite samples for tensile testing

Procedures of FRP reinforcement installation process, and

Painting of the FRP reinforcement that concluded installation.

61

2.9.1 139BSURFACE PREPARATION

Prior to FRP fabric installation, the contractor was required to prepare the surface to

ensure adequate contact between the FRP and concrete. Surface preparation procedures

were conducted in accordance with the ALDOT Special Provision regarding the use of

fiber-reinforced polymer reinforcement for girder repair. Surface preparation techniques

included surface grinding of irregularities such as excess crack-injected epoxy, surface

patching of unacceptable voids and depressions, light surface roughening for improved

bond quality, and final surface cleaning to remove dust and all other bond-inhibiting

material. The use of compressed air for final cleaning is shown in 1927HFigure 2.29.

Figure 2.29: Surface cleaning—final removal of dust and debris

Girder preparation also involved the removal of the false support bearing pads. These

bearing pads inhibited FRP installation to the bottom of the girder at false-support

62

locations. The bearing pads under Span 11 were, in general, more difficult to remove

than the bearing pads under Span 10. Initially, the contractor attempted to remove each

bearing pad by punching it out of place using a chisel and hammer. When a bearing pad

was under enough pressure to prevent removal, the contractor then used a reciprocating

saw on the pad to alleviate some of that pressure, as shown in 1928HFigure 2.30. In some

cases, saw cutting alone was not effective at alleviating enough pressure for successful

bearing pad removal. In these cases, a propane torch was used to soften the rubber and

allow for a more effective sawing process, which is shown in 1929HFigure 2.31. After

successful pressure alleviation, the bearing pad was removed using the initial chisel-and-

hammer removal method, as shown in 1930HFigure 2.32. An example of a bearing pad that

required extensive removal efforts is shown in 1931HFigure 2.33.

Figure 2.30: Use of saw for bearing pad removal

63

Figure 2.31: Use of torch for bearing pad removal

Figure 2.32: Successful removal of bearing pad

64

Figure 2.33: Bearing pad after forceful removal

2.9.2 140BADHESION TESTING

Tyfo S saturant epoxy manufactured by Fyfe Co. was used throughout the FRP

installation. Adhesion testing of the Tyfo S epoxy on the concrete surface was required

to ensure that the bond strength of the epoxy exceeded the tensile strength of the

concrete. The adhesion tests were conducted in accordance with the requirements given

in ASTM D4541. Detailed description of the ASTM D4541 adhesion testing procedure

has been reported by Swenson (2007). A minimum of three tests were required for each

day in which FRP reinforcement was installed, and a minimum of one test was required

per 500 square feet of installed FRP reinforcement. Adhesion testing equipment is shown

in a laboratory setting in Figure 1932H2.34. On-site adhesion testing is shown in Figure 1933H2.35.

65

Figure 2.34: Adhesion test equipment (Swenson 2007)

Figure 2.35: Performance of on-site adhesion test

66

2.9.3 141BTENSILE TESTING

Tensile testing of FRP reinforcement samples was required to ensure the quality of the

FRP reinforcement installed. A minimum of two testing samples were required for each

day that FRP reinforcement was installed. A testing sample, prepared as shown in

Figures 1934H2.36 and 1935H2.37, was to consist of two 12 in. by 12 in. panels representative of the

four-layer FRP and epoxy composite. However, the contractor fabricated each panel with

only two plies of fabric, interpreting this as ―representative‖ of the four-ply system. The

samples were sent to a testing laboratory accredited in accordance with ISO/IEC 17025.

The required testing procedures are presented in ASTM D3039. The tensile strength,

ultimate tensile strain, and tensile modulus of elasticity were tested in a minimum of five

sample batches.

Figure 2.36: Preparation of sample for tension testing

67

Figure 2.37: Representative sample for tension testing

2.9.4 142BFRP FABRIC INSTALLATION PROCEDURES

The FRP reinforcement repair consisted of four layers of FRP fabric. Due to the width of

FRP fabric required to wrap around a typical bottom flange, three FRP fabric sheets were

necessary per layer of installation. Two of the fabric sheets were of equal width and the

third fabric sheet was narrower.

Each sheet of FRP fabric was cut to size and then saturated with epoxy. The typical

fabric cutting and epoxy saturation procedures are shown in Figures 1936H2.38 and 1937H2.39.

Epoxy was also applied to the surface of the girders prior to application of the first layer

of FRP fabric, as shown in Figure 1938H2.40. The first layer of FRP fabric was then installed

as shown in Figure 1939H2.41. Successive layers of FRP and epoxy were then applied, and an

example of a typical four-layer installation is shown in Figure 1940H2.42.

68

Figure 2.38: Cutting strips of FRP fabric

Figure 2.39: Epoxy saturation of FRP fabric

69

Figure 2.40: Applying epoxy to girder surface before FRP fabric installation

Figure 2.41: Installation of first layer of FRP fabric

70

Figure 2.42: Four layers of installed FRP fabric

2.9.4.1 4345BFRP FABRIC INSTALLATION—FIRST LAYER

The installation sequence for the first layer of FRP fabric is illustrated in 1941HFigure 2.43.

The two wider strips were installed beginning at the joint of the web and top of bottom

flange on their respective faces of the girder and wrapped around to extend partially

along the bottom of the bottom flange. The narrower strip was applied along the

centerline of the bottom of the bottom flange of the girder to fill the gap between the

termination points of the two wider FRP fabric sheets.

Figure 2.43: FRP installation sequence–first layer

71

2.9.4.2 4346BFRP FABRIC INSTALLATION—SECOND LAYER

The installation sequence for the second layer of FRP fabric is illustrated in 1942HFigure 2.44.

The narrow sheet was applied at the joint of the web and top of bottom flange on one face

of the girder. One of the wide sheets was applied beginning at the edge of the narrow

sheet and overlapped the centerline of the girder on the bottom flange. The remaining

wide sheet began at the termination of the first wide sheet and wrapped around the

bottom flange to terminate at the joint of the web and top of the bottom flange.

Figure 2.44: FRP installation sequence—second layer

2.9.4.3 4347BFRP FABRIC INSTALLATION—THIRD LAYER

The third layer was similar to the second layer, but the installation began with the narrow

sheet being applied to the face of the girder opposite of the narrow sheet in the second

layer. The sheets were arranged in this opposing pattern so that fabric of the third layer

overlapped the seams in the second layer. The installation sequence for the third layer of

FRP fabric is presented in 1943HFigure 2.45.

72

Figure 2.45: FRP installation sequence—third layer

2.9.4.4 4348BFRP FABRIC INSTALLATION—FOURTH LAYER

The fourth layer pattern was identical to the symmetric first layer pattern. The

installation sequence for the fourth layer of FRP fabric is presented in 1944HFigure 2.46.

Figure 2.46: FRP installation sequence—fourth layer

2.9.5 143BPAINTING OF INSTALLED FRP REINFORCEMENT

After the epoxy of the FRP reinforcement sufficiently cured, the FRP surface was painted

using Masonry, Stucco, and Brick Paint manufactured by Behr. This white acrylic latex

paint was used to further protect the reinforcement from ultraviolet rays and weather-

related distress over time. The paint was sprayed onto the FRP surface as shown in

Figure 1945H2.47, and the finished girders of Span 10 are shown in Figure 1946H2.48.

73

Figure 2.47: Painting of FRP reinforcement

Figure 2.48: Painted FRP reinforcement of Span 10

74

2.9.6 144BFRP REINFORCEMENT INSTALLATION TIMELINE

FRP installation activities occurred between Tuesday, December 11, and Wednesday,

December 19, 2007. The weather conditions reported at the Huntsville International

Airport for these dates are presented in 1947HTable 2.3. A summary of the FRP reinforcement

installation activities that were conducted each day is presented in this section based on

documentation provided by an Auburn University researcher.

Table 2.3: Weather during FRP reinforcement installation (NOAA 2008)

Date Minimum

Temperature

(°F)

Maximum

Temperature

(°F)

Mean

Temperature

(°F)

Precipitation

(in.)

Dec. 11, 2007 56 77 67 0.00

Dec. 12, 2007 56 71 64 0.00

Dec. 13, 2007 47 69 58 0.05

Dec. 14, 2007 39 51 45 0.00

Dec. 15, 2007 40 69 55 0.08

Dec. 16, 2007 28 43 36 T

Dec. 17, 2007 23 48 36 0.00

Dec. 18, 2007 27 54 41 T

Dec. 19, 2007 44 54 49 T

Note: T = Trace precipitation amount (between 0.00 and 0.01 in.)

2.9.6.1 4349BDECEMBER 11, 2007

FRP reinforcement was installed on Girder 9 of Span 10 on Tuesday, December 11,

2007, which was the first day of installation. The first layer of FRP took close to 1 hour

to install. Installation of all four FRP layers was completed in roughly 2.5 hours. A

tensile testing sample was prepared before beginning the installation process.

75

2.9.6.2 4350BDECEMBER 12, 2007

FRP reinforcement was installed on Girders 8, 7, and 6 of Span 10 on Wednesday,

December 12, 2007. FRP installation was completed in roughly 1.5 hours for Girder 8,

1.25 hours for Girder 7, and 2hours for Girder 6. It was also documented that, before

beginning installation, an adhesion test was performed and a tensile testing sample was

prepared.

2.9.6.3 4351BDECEMBER 13, 2007

The 0.05 in. of precipitation noted for Thursday, December 13, 2007 in 1948HTable 2.3

reportedly accumulated between the hours of 5:00 a.m and 2:00 p.m. CST (NOAA 2008).

This weather and resulting moisture conditions were not conducive to proper FRP

installation, and the contractor decided to focus efforts on surface preparation.

2.9.6.4 4352BDECEMBER 14, 2007

FRP reinforcement was installed on Girders 5, 4, 3, and 2 of Span 10 on Friday,

December 14, 2007. FRP installation was completed in roughly 1 hour for Girder 5,

1 hour for Girder 4, 1.5 hours for Girder 3, and 1 hour for Girder 2. It was again

documented that, before beginning installation, an adhesion test was performed and a

tensile testing sample was prepared.

2.9.6.5 4353BDECEMBER 15, 2007

The forceful removal of Span 11 bearing pads began on Saturday, December 15, 2007.

Complete removal of all Span 11 bearing pads was unsuccessful.

2.9.6.6 4354BDECEMBER 16, 2007

No work was documented by the AUHRC for Sunday, December 16, 2007

76

2.9.6.7 4355BDECEMBER 17, 2007

Span 11 bearing pad removal continued on Monday, December 17, 2007.

2.9.6.8 4356BDECEMBER 18, 2007

FRP reinforcement was installed on Girders 9, 8, 7, 6, and 5 of Span 11 on Tuesday,

December 18, 2007. FRP installation was completed in roughly 1 hour for Girder 9,

1 hour for Girder 8, and 2 hours for Girder 7, 1 hour for Girder 6, and 1hour for Girder 5.

It was documented that another tensile testing sample was prepared before beginning

installation.

2.9.6.9 4357BDECEMBER 19, 2007

The contractor began painting installed FRP fabric on Wednesday, December 19, 2007.

Girders 9–2 of Span 10 were painted before beginning other FRP installation. FRP

reinforcement was installed on Girder 1 of Span 10 and Girder 1 of Span 11. FRP

installation was completed in roughly 2 hours for Girder 1 of Span 10 and 1 hour for

Girder 1 of Span 11. These girders were painted immediately following FRP installation.

It was also documented that a tensile testing sample was prepared, before beginning

installation.

2.9.6.10 4358BAFTER DECEMBER 19, 2007

FRP installation activities performed after Wednesday, December 19, 2007 were not

documented by AUHRC personnel. The remaining activities included FRP installation

on Girders 4, 3, and 2 of Span 11 and the painting of installed FRP fabric on Girders 9–2

of Span 11.

77

2.10 41BCURRENT RESEARCH

Post-repair testing was required to gauge the effectiveness of the FRP reinforcement

repair. The FRP material installed on the instrumented girders was inspected for signs of

delamination prior to testing, and no significant signs of bond failure were observed for

the repair that had been in service for more than 2 years at the time of post-repair testing.

Also, additional strain gages were installed to measure the response of the FRP material

during testing. The bridge structure was then subjected to load tests similar to those

conducted prior to the repair. The instrumentation, procedure, and results of post-repair

testing are presented in subsequent chapters of this thesis.

78

Chapter 3

7BBRIDGE INSTRUMENTATION

3.1 42BINTRODUCTION

Northbound Spans 10 and 11 were instrumented with sensors to quantify bridge behavior

and the response of selected girders during specific loading scenarios. The desired

quantifiable responses included the opening or closing of cracks within a girder web,

girder deflections, and girder surface strains of concrete and FRP reinforcement. Sensor

locations and installation procedures are discussed in this chapter.

3.2 43BINSTRUMENTATION OVERVIEW

Girders 7 and 8 in Spans 10 and 11 exhibited significant cracking at their continuous ends

and were selected for instrumentation. Two girders per span were heavily instrumented

rather than installing fewer sensors per girder for all nine girders per span. Another

factor leading to the selection of Girders 7 and 8 was the need to keep one lane open to

vehicular traffic during load testing. These girders are the second and third interior

girders from the east edge of the bridge, which allowed the west lane to remain open

without significant effect on test results. The exterior girder (Girder 9) was not chosen

because of anticipated analytical complications related to the proximity of the west

barrier rail (Fason 2009).

79

The instruments installed on each girder included crack-opening displacement (COD)

gages, deflectometers, and surface-mounted strain gages installed on concrete and FRP

reinforcement. A total of seventy-two sensors were installed. Four sensors were COD

gages: each straddled one crack per instrumented girder. Twelve sensors were

deflectometers placed along the ground directly underneath the instrumented girders to

measure deflections at incremental distances from the continuity diaphragm. The

remaining fifty-six sensors were surface-mounted strain gages installed along the

instrumented girders. Eight cross sections, four on each girder line, were instrumented

with surface-mounted strain gages at different girder heights to allow for strain profile

analysis. Bottom-fiber strain gages were installed at eight different locations along each

girder line. An overview of the instrumentation locations per girder line is illustrated in

Figure 1949H3.1.

80

Figure 3.1: Instrumentation overview

Legend:

Crack-Opening Displacement Gage

Deflectometer

Cross Section Gaged for Strain Profile

Bottom-Fiber Strain Gage

False Support False Support

Bent 10

Simple

Support

Span 11

Bent 11

Continuity

Diaphragm

Span 10

Bent 12

Simple

Support

81

A data acquisition system was used to collect sensor measurements during testing.

The data acquisition system had seventy-two 350-ohm channels available. The COD

gages were full-bridge sensors, and the deflectometers and strain gages were quarter-

bridge sensors. Four-wire configurations were used for the full-bridge sensors. Three-

wire configurations were used with the quarter-bridge sensors to reduce lead-wire

temperature effects (Fason 2009).

3.3 44BCRACK-OPENING DISPLACEMENT GAGES

Crack-opening displacement (COD) gages were installed to measure the opening or

closing deformations of one crack per instrumented girder. Each COD gage was attached

to anchor blocks that were installed on either side of the crack using an epoxy. The type

of COD gage selected for testing is capable of measuring crack openings or closures of

up to 2 mm (0.08 in.). The COD gages are full-bridge instruments that were calibrated

prior to testing. A diagram of the specific model of COD gage used for the pre- and post-

repair tests can be seen in 1950HFigure 3.2.

82

Note: dimensions are shown as mm

Figure 3.2: Crack-opening displacement gage (TML 2011)

35

30

70

50 (gauge length)

12

4.5 diam.

PI-2-50

83

3.3.1 145BCOD GAGE LOCATIONS

Four crack-opening displacement gages (A–D) were installed prior to the pre-repair load

tests. The specific COD gage locations can be seen in 1951HTable 3.1. Each COD gage was

installed to span a significant crack in a girder web near the girder’s continuous end. The

anchor blocks for each COD gage location were installed three inches above the joint of

the bottom-flange and the web. The COD gage installed on Girder 8 of Span 10 was

located on the west face of the girder. The other COD gages were located on the east

face of their respective girders.

Each COD gage was installed in the same respective location for pre- and post-repair

testing. During analysis each gage was referenced according to installed location rather

than COD ID.

Table 3.1: COD gage locations

Span

Girder

Distance from Continuity

Diaphragm Centerline

(in.)

Girder

Face

(east/west)

COD

ID

(A–D)

10 7 50 east C

8 40 west A

11 7 48 east D

8 56 east B

3.3.2 146BCOD GAGE INSTALLATION

Prior to pre-repair testing, two anchor blocks were attached to the surface of each

instrumented girder using a 5-minute epoxy. A photo of installed anchor blocks can be

seen in 1952HFigure 3.3.

84

Figure 3.3: Anchor blocks for COD gage installation (Fason 2009)

To provide consistent initial distances between anchor blocks, a reference bar was

mechanically attached with screws to the anchor blocks prior to installation. The

reference bar had a distance of 50.0 mm (1.97 in.) between mechanical attachment points.

The anchor blocks were then attached to the concrete girder surface using the 5-minute

epoxy. After the epoxy set, the reference bar was removed and a COD gage was

mechanically attached to the anchor blocks (Fason 2009).

Following the conclusion of pre-repair testing, the COD gages were detached from

their respective anchor blocks and safely stored until reinstalled for post-repair testing.

The only COD gage installation required prior to the post-repair tests was the mechanical

attachment of the COD gages to their respective anchor blocks that remained installed

after pre-repair testing. Each COD gage was located in the same respective location and

85

was connected to the data acquisition system using the same respective 4-wire cable from

the pre-repair tests. A photo of a COD gage attached to anchor blocks can be seen in

1953HFigure 3.4.

Figure 3.4: COD gage attached to anchor blocks

86

3.4 45BDEFLECTOMETERS

Deflectometers were used to measure bottom-fiber girder deflections, due to different

load conditions, at specific points along each instrumented girder. A picture of a typical

deflectometer used during bridge testing can be seen in 1954HFigure 3.5.

Figure 3.5: Typical deflectometer

Each deflectometer was positioned under the bridge girder at the ground level and

connected to the underside of the bridge girder using a wire. The wire length was

adjusted to ensure the aluminum bar of the deflectometer remains bent with the bottom of

the bar in tension throughout the bridge testing. As the bridge girder deflected downward

or upward at the deflectometer location, the flexural tension in the cantilevered aluminum

bar was relieved or amplified respectively. A single quarter-bridge surface-mounted

strain gage on the underside of the aluminum bar was used to measure the flexural strain.

A decrease in tension resulted in a negative strain that represents a downward deflection

87

in the bridge and an increase in tension resulted in a positive strain that represents an

upward deflection. As long as the aluminum bar is not bent past its proportional limit,

there is a linear relationship between the strain and deflection. The strain-to-deflection

conversion factors for all deflectometers were calibrated before and after testing.

3.4.1 147BDEFLECTOMETER LOCATIONS

Twelve deflectometers were installed at the same respective locations for pre- and post-

repair testing. The deflectometer positions along each girder line are illustrated in

Figures 1955H3.6 and 1956H3.7. The specific deflectometer locations for the bridge testing are

presented in 1957HTable 3.2.

Six deflectometers were assigned to each girder line. Along each girder line, two

deflectometers were installed under Span 10, and four deflectometers were installed

under Span 11 at the locations shown in Figures 1958H3.6 and 1959H3.7.

The individual deflectometers have identification labels A–L. However, the notation

used to distinguish between deflectometer locations during analysis and reporting

consists of the girder (7 or 8), span (10 or 11), and girder line location (A–F).

88

Figure 3.6: Deflectometer locations—Girder Line 7

Figure 3.7: Deflectometer locations—Girder Line 8

D

DEFL: F

Midspan

Deflectometer Attachment Point

158”

Midspan

Bent 11

150” 150” 150” 308” 300” A

DEFL: L

B

DEFL: K

C

DEFL: E

E

DEFL: G

F

DEFL: H

Span 11 Span 10

Girder Line 8

D

DEFL: B

Midspan

Deflectometer Attachment Point

158”

Midspan

Bent 11

150” 150” 150” 308” 300” A

DEFL: J

B

DEFL: I

C

DEFL: A

E

DEFL: C

F

DEFL: D

Span 11 Span 10

Girder Line 7

89

Table 3.2: Deflectometer locations

Span

Girder

Distance from Continuity

Diaphragm Centerline

(in.)

Girder Line

Location

(A–F)

DEFL

ID

(A–L)

10

7 608 A J

308 B I

8 608 A L

308 B K

11

7

158 C A

308 D B

458 E C

608 F D

8

158 C E

308 D F

458 E G

608 F H

3.4.2 148BDEFLECTOMETER INSTALLATION

Deflectometers were constructed and installed prior to the pre-repair tests in 2005.

Information regarding the construction and installation of deflectometers prior to the pre-

repair tests has been reported by Fason (2009). Each deflectometer was installed in the

same location for both pre- and post-repair testing. Each deflectometer used the same

4-wire cable to connect to the data acquisition system for both pre- and post-repair

testing.

Prior to the pre-repair tests, deflectometer attachment points were installed to the

underside of the bottom-flange at the desired locations along each instrumented girder.

A picture of a typical attachment point is shown in 1960HFigure 3.8.

90

Figure 3.8: Girder attachment point for deflectometer wire

The attachment points consist of an epoxy-mounted bracket of two metal plates

connected with two metal bars. Metal wire was used to connect each attachment point to

its respective deflectometer on the ground directly beneath the attachment point. For the

pre-repair tests, the metal wires were tied directly to the attachment points. For the post-

repair tests, metal S-hooks were used to connect the metal wires to their respective

attachment points, allowing for easier wire installation and detachment.

A turnbuckle was attached to each wire at the ground level to allow for wire length

adjustment while pre-bending each deflectometer aluminum bar. Each turnbuckle was

attached to an eye-hook at the end of the corresponding deflectometer aluminum bar.

Some of the turnbuckles used during the post-repair tests required an additional s-hook to

connect to the of the aluminum bar. Each turnbuckle was adjusted until the vertical

distance between the tip of the pre-bent aluminum bar and the base of the deflectometer

91

was roughly 4 inches. A picture of an adjusted turnbuckle and pre-bent aluminum bar

can be seen in 1961HFigure 3.9.

Figure 3.9: Deflectometer aluminum bar—pre-bent with adjusted turnbuckle

Plywood boards were used to level and stabilize each deflectometer as much as

possible. Each deflectometer was then connected to the data acquisition system using the

same 4-wire cable from the pre-repair tests. Since the deflectometers were at the ground

level throughout the testing, it was important to deter accidental human interference. All

deflectometer wires were marked with flagging at eye level, and the deflectometer areas

under Spans 10 and 11 were marked with a perimeter of flagging. Movement through the

deflectometer areas was avoided as much as possible. A photo of the deflectometer area

under Span 11 is shown in 1962HFigure 3.10.

92

Figure 3.10: Deflectometer area—Span 11

3.5 46BSTRAIN GAGES

Surface-mounted strain gages were installed to monitor material strains in response to

different loading conditions. Electrical-resistance strain gages were mounted directly to

structural material including concrete and FRP reinforcement at different locations along

each instrumented girder. The majority of the strain gages were installed near the

93

continuity diaphragm to allow for better analysis of the bridge behavior near the support.

Prior to the pre-repair tests, strain gages were installed on the concrete at specified

locations. Prior to the post-repair tests, strain gages were installed on the FRP

reinforcement at specified locations. The FRP reinforcement strain gages allowed for

analysis of the forces carried by the FRP reinforcement due to specific loading

conditions, and the analysis of the transfer of stresses from the concrete to the FRP

reinforcement. The gage locations, gage types, and installation procedures for the

surface-mounted strain gages are discussed in Sections 3.5.1–3.5.4.

3.5.1 149BSTRAIN GAGE LOCATIONS

Fifty-six surface-mounted strain gages were installed for bridge testing. An illustration

of the strain gage cross section locations along one girder line can be seen in 1963HFigure 3.11.

The specific locations of the strain gage cross sections and the amount of gages in each

cross section are provided in 1964HTable 3.3. Illustrations of the post-repair strain gage

locations within each cross section can be seen in Figures 1965H3.12–1966H3.22. The potential gage

locations within a cross section are detailed in 1967HTable 3.4.

94

Notes: Dimensions shown are from the centerline of the continuity diaphragm.

Cracks shown are meant only to illustrate the typical crack zone and

do not represent actual crack locations.

Figure 3.11: Strain gage cross section locations

CRACK CRACK

13 in. 75 in.

75 in. 13 in.

Cross

Section

1

Cross

Section

2

Cross

Section

3

Cross

Section

4

Span 10 Span 11

Cross Sections 6, 7, and 8 are

equally spaced at distances of

273 in., 441 in., and 609 in.

respectively from the center

of the continuity diaphragm

105 in.

Cross

Section

5

95

Table 3.3: Strain-gaged cross sections

Span

Girder

Cross

Section

Distance from

Continuity Diaphragm

Centerline

(in.)

No. of

Concrete

Strain

Gages

No. of

FRP

Strain

Gages

Total

Gages

10

7

1 75 4 1 5

CRACK 47 – 1 1

2 13 4 1 5

8

1 75 4 2 6

CRACK 41 – 1 1

2 13 3 2 5

11

7

3 13 5 0 5

CRACK 47 – 1 1

4 75 4 1 5

5 105 1 1 2

6 273 1 – 1

7 441 1 – 1

8 609 1 – 1

8

3 13 3 2 5

CRACK 52 – 1 1

4 75 4 2 6

5 105 1 1 2

6 273 1 – 1

7 441 1 – 1

8 609 1 – 1

Total Gages 39 17 56

96

Figure 3.12: Strain gage locations—Girder 7—Section 1

Figure 3.13: Strain gage locations—Girder 7—Section 2

4.5‖

Z

V

X W

Y

— Concrete Strain Gage

— FRP Strain Gage

— Discontinued Gage

36‖

6‖

26‖

42‖

FRP

54‖

3‖

3‖

3‖

18‖

West East

West East

4.5‖

V

X W

Y

— Concrete Strain Gage

— FRP Strain Gage

— Discontinued Gage

36‖

6‖

26‖

42‖

FRP

54‖

3‖

3‖

3‖

18‖

M

97

Figure 3.14: Strain gage locations—Girder 7—Section 3

Figure 3.15: Strain gage locations—Girder 7—Section 4

4.5‖

V

X W

Y

— Concrete Strain Gage

— FRP Strain Gage

— Discontinued Gage

36‖

6‖

26‖

42‖

FRP

54‖

3‖

3‖

3‖

18‖

M

West East

4.5‖

Z

V

X W

Y

— Concrete Strain Gage

— FRP Strain Gage

— Discontinued Gage

36‖

6‖

26‖

42‖

FRP

54‖

3‖

3‖

3‖

18‖ 36

West East

98

Figure 3.16: Strain gage locations—Girder 8—Section 1

Figure 3.17: Strain gage locations—Girder 8—Section 2

4.5‖

Z

V

X W

Y

— Concrete Strain Gage

— FRP Strain Gage

— Discontinued Gage

36‖

6‖

26‖

42‖

FRP

54‖

3‖

3‖

3‖

18‖

West East

4.5‖

V

X W

Y

— Concrete Strain Gage

— FRP Strain Gage

— Discontinued Gage

36‖

6‖

26‖

42‖

FRP

54‖

3‖

3‖

3‖

18‖

M

West East

99

Figure 3.18: Strain gage locations—Girder 8—Section 3

Figure 3.19: Strain gage locations—Girder 8—Section 4

4.5‖

V

X W

Y

— Concrete Strain Gage

— FRP Strain Gage

— Discontinued Gage

36‖

6‖

26‖

42‖

FRP

54‖

3‖

3‖

3‖

18‖

M

36

West East

West East

4.5‖

Z

V

X W

Y

— Concrete Strain Gage

— FRP Strain Gage

— Discontinued Gage

36‖

6‖

26‖

42‖

FRP

54‖

3‖

3‖

3‖

18‖

100

Figure 3.20: Strain gage locations—Girders 7 and 8—Section 5

Figure 3.21: Strain gage locations—Girders 7 and 8—Sections 6, 7, and 8

West East

4.5‖

— Concrete Strain Gage

— FRP Strain Gage

— Discontinued Gage

36‖

6‖

26‖

42‖

54‖

M

36

4.5‖

— Concrete Strain Gage

— FRP Strain Gage

— Discontinued Gage

36‖

6‖

26‖

42‖

FRP

M

36

West East 54‖

101

Figure 3.22: Strain gage locations—CRACK

Table 3.4: Strain gage locations within cross section

Location

Notation

Distance from

Bottom of

Bottom-Flange

(in.) Location Description

Girder

Face

F 43.5 Top of Web West

V 28.5 Middle of Web West

W 13.5 Bottom of Web West

X 13.5 Bottom of Web East

Y 3 Side of Bottom Flange West

Z 3 Side of Bottom Flange East

M 0 Bottom of Bottom Flange Bottom

CK 0 Bottom of Bottom Flange Bottom

Note: The gage location at the top of the web (Location F) was discontinued

for post-repair testing

West East

4.5‖

CK

— Concrete Strain Gage

— FRP Strain Gage

— Discontinued Gage

36‖

6‖

26‖

42‖

FRP

54‖

36

102

Strain gage instrumentation was concentrated in the end regions of Girders 7 and 8

near the continuity diaphragm between Spans 10 and 11. Strain gages were installed at

various girder heights at two main cross sections on each instrumented girder. One cross

section in each girder is located near the face of the continuity diaphragm, while the other

cross section is located just beyond the cracked region. The two girders in Span 11 also

contain strain gages along the bottom of the girders at different locations out to midspan.

The strain gages at the end region cross sections allow for the analysis of localized

behaviors around the cracked regions of each girder. The strain gages along the bottom

of each girder allow for analysis of overall girder behavior.

3.5.1.1 4359BCROSS SECTION LOCATIONS

There are a total of ten cross sections on each girder line that contain strain gages.

Span 10 girders contain three strain-gaged cross sections. Two cross sections in Span 10

are instrumented for strain profile analysis, and one cross section consists of an FRP

strain gage on the bottom of the girder at the primary crack location. The two Span 10

cross sections instrumented for strain profile analysis are located at distances of 75 in.

(Cross Section 1) and 13 in. (Cross Section 2) from the center of the continuity

diaphragm. The gages at these cross sections are installed at different heights on both

faces of the girder. The cross section containing an FRP strain gage at the primary crack

location is located between Cross Section 1 and Cross Section 2 for both girders. The

crack section FRP strain gages are located at distances of 47 in. and 41 in. from the

continuity diaphragm on Girders 7 and 8 respectively.

The Span 11 girders contain seven strain-gaged cross sections. Two cross sections in

Span 11 are instrumented for strain profile analysis, and five cross sections contain strain

103

gages located on the bottom of the girder. One of the cross sections with a bottom-fiber

strain gage is located at the primary crack location on each girder. The other four cross

sections with bottom-fiber strain gages are equally spaced out to midspan from just

beyond the false support. The two Span 11 cross sections instrumented for strain profile

analysis are located at distances of 13 in. (Cross Section 3) and 75 in. (Cross Section 4)

from the center of the continuity diaphragm. The gages at these cross sections are

installed at different heights on both faces of the girder. The cross section containing an

FRP strain gage at the primary crack location is located between Cross Section 3 and

Cross Section 4 for both girders. The crack section FRP strain gages are located at

distances of 47 in. and 52 in. from the continuity diaphragm on Girders 7 and 8

respectively. The first of the four equally spaced bottom-fiber strain gages is located at a

distance of 105 in. (Cross Section 5) from the center of the continuity diaphragm. The

other three locations are then equally spaced out to midspan at distances of 273 in.

(Cross Section 6), 441 in. (Cross Section 7), and 609 in. (Cross Section 7) from the center

of the continuity diaphragm. Cross Section 5 contains two strain gages, a concrete strain

gage and an FRP strain gage at the same overlaying location. Cross Sections 6, 7, and 8

only contain one concrete strain gage each on the bottom of the girder.

There were some inconsistencies concerning the pre-repair strain gage cross section

locations that resulted in a slightly different installation location for the post-repair FRP

strain gages considered to be a companion with a previously installed concrete strain

gage. The concrete strain gages average the surface strain measured over their entire

length (2.4 in. [60 mm]), but were installed placing one edge of the gage at the reported

cross section location from the face of the continuity diaphragm. The FRP strain gages

104

(1/4 in. [6 mm]) were installed with the center of the gage at the previously reported cross

section location. This resulted in the location of the average measured strain for concrete

gages to be roughly 1 in. (25 mm) different compared to the location of the average

measured strain of FRP strain gages at the same cross section. For the purpose of gage

notation, concrete strain gages and FRP strain gages are still considered to be in the same

cross sections, but the locations of the average strain for each gage are reported when

tabulating and graphically illustrating results.

3.5.1.2 4360BGAGE LOCATIONS WITHIN A TYPICAL CROSS SECTION

For each gaged cross section, there are seven different potential gage locations. The gage

locations are as follows: top of the web at 3 in. below the joint of the top flange and web

on the west face (discontinued for post-repair tests), middle of the web at 18 in. above the

joint of the bottom-flange and web on the west face (Location V), bottom of web at 3 in.

above the joint of the bottom-flange and web on the west face (W) and east face (X), side

of bottom flange at 3 in. below the top edge of the side of the bottom flange on the west

face (Y) and east face (Z), and center of the underside of the bottom flange at 13 in. from

the side of the bottom flange (M or CK). Concrete surface strain gages were installed at

the following locations: V, W, X, Y, Z, and M. After applying the FRP reinforcement,

FRP surface strain gages were installed at the following locations: Y, Z, M, and CK.

3.5.1.3 4361BDISCONTINUED, ADDITIONAL, AND REPLACEMENT GAGES

Every available channel of the data acquisition system was employed during the pre-

repair tests. In order to install and record strain gages at desired locations on the FRP, it

was necessary to discontinue some concrete strain gages from the pre-repair tests. For

the pre-repair tests, there was a concrete strain gage installed 3 in. below the joint of the

105

web and top flange at Cross Sections 1–4 on both girder lines. After analysis of the pre-

repair results, it was recommended to discontinue the eight concrete strain gages located

near the top of the web of Cross Sections 1–4 on both girder lines, and to replace them

with FRP strain gages at bottom-fiber locations of Cross Sections 4 and 5 on both girder

lines and at the main crack location of each instrumented girder (Shapiro 2007).

Some of the concrete strain gages from the pre-repair tests that were at desirable

girder height locations were unfortunately no longer functioning at the time of the post-

repair tests. Concrete strain gages were installed at the same girder height location to

replace nonfunctioning concrete strain gages that were accessible, but other

nonfunctioning concrete strain gages had been covered by the FRP reinforcement and had

to be discontinued for the post-repair tests. Where nonfunctioning concrete strain gages

covered by the FRP reinforcement were discontinued, FRP strain gages were installed at

the same location for the post-repair tests and assigned the same channel and 3-wire cable

assigned to the respective pre-repair concrete strain gage. Two nonfunctioning concrete

strain gages were accessible and replaced with another concrete strain gage. Nine

nonfunctioning concrete strain gages were inaccessible and replaced with FRP strain

gages.

106

3.5.2 150BCONCRETE STRAIN GAGES

Prior to pre-repair testing, strain gages were installed on the concrete surface of girders.

Prior to post-repair testing, strain gages were only installed on the concrete surface to

replace a previously installed strain gage that was no longer functioning properly. Strain

gages installed on a concrete surface must have a greater gage length than strain gages on

other material surfaces due to the heterogeneous properties of concrete. Longer gage

lengths allow for an averaging effect that includes strains in the aggregate and the

surrounding mortar. It is suggested that strain gages installed on concrete surfaces should

be several times longer than the largest coarse aggregate material used during production

of the concrete (Vishay 2010). The strain gages installed on the concrete surfaces prior to

the pre-repair tests were 60 mm (2.4 in.) quarter-bridge gages with a resistance of 350 Ω

(MFLA-60•350-1L). A photo of an installed concrete surface strain gage before the

application of weather protection can be seen in 1968HFigure 3.23.

107

Figure 3.23: Surface-mounted strain gage—concrete (Fason 2009)

3.5.3 151BFRP STRAIN GAGES

Strain gages were installed on the FRP reinforcement to correspond with previously

installed concrete gages or previously noted concrete crack locations. The gages located

on the FRP reinforcement did not require as long of a gage length as the concrete surface

strain gages, because the FRP strain gages average strains along fibers of similar material

composition. The strain gages installed on the FRP reinforcement were 6 mm (1/4 in.)

quarter-bridge gages with a resistance of 350 Ω (FLA-6-350-11-1LT). A photo of an

installed FRP reinforcement strain gage before the application of weather protection can

be seen in 1969HFigure 3.24.

108

Figure 3.24: Surface-mounted strain gage—FRP reinforcement

3.5.4 152BSTRAIN GAGE INSTALLATION

The concrete strain gages were installed prior to the pre-repair tests using the installation

procedure noted by Fason (2009). Any nonfunctioning concrete gages were replaced

with new concrete gages prior to the post-repair tests in accordance with the same

procedure.

FRP reinforcement strain gages were installed using a modified procedure suited for

the composite material. The strain gage installation procedure for the FRP reinforcement

consisted of five main processes: initial surface preparation, smoothing the gaging

surface with solids-epoxy, surface preparation for gage application, gage installation, and

gage protection. The main difference between the strain gage installation procedures for

concrete and FRP reinforcement is the surface preparation required for each material.

Also, due to the fact that an FRP strain gage was one-tenth the length of a concrete strain

109

gage, it was possible to use a quick-setting gaging epoxy. A step-by-step strain gage

installation procedure for the FRP composite material is presented in Appendix M.

Pictures illustrating portions of the FRP strain gage installation procedure can be seen in

Figures 1970H3.25–1971H3.34.

Initial surface preparation required the removal of paint, excess epoxy remaining

from the FRP installation, and other irregularities on the FRP surface. After initial

location of the gaging area, degreaser was applied to the area to initiate the surface

preparation. A wire brush, an electric grinder, sand-paper, and compressed air were used

to assist with initial surface preparation. Photographs of initial surface preparation

procedures are shown in Figures 1972H3.25–1973H3.28.

Figure 3.25: Strain gage installation—applying degreaser to gage location

110

Figure 3.26: Strain gage installation—removal of surface irregularities

Figure 3.27: Strain gage installation—initial surface cleaning

111

Figure 3.28: Strain gage installation—clean surface prepared for solid epoxy

The FRP reinforcement is composed of woven fibers, creating an uneven surface

which is not ideal for strain gage application. The exposed FRP fibers were further

cleaned using isopropyl alcohol and gauze. After cleaning the FRP surface, a solids-

epoxy mixture (PC-7) was applied to level the surface. The epoxy was not meant to

completely cover the FRP and was only applied to fill small voids near the final gage

location. Photographs of surface leveling are shown in Figures 1974H3.29 and 1975H3.30.

112

Figure 3.29: Strain gage installation—application of solid epoxy

Figure 3.30: Strain gage installation—epoxy surface

113

The gage location was cleaned again after the solids-epoxy mixture was allowed to

cure. Sand-paper and isopropyl alcohol were used to clean the gage location with added

solids-epoxy. Following another surface cleaning, the gage location was treated with a

cleaning agent (Vishay M-Prep A–Conditioner) and neutralizer (Vishay M-Prep 5A–

Neutralizer). After thoroughly cleaning the surface, a heat gun was used to dry the gage

location. Once the surface was clean and dry, it was prepared for gage installation.

The gage application procedures are very similar for the FRP and concrete strain

gages. Due to their shorter gage length, the FRP strain gages were easier to install than

concrete strain gages. A clean acrylic plate was used to apply a strip of tape to the back

of each gage. The tape was smoothly applied to the gage without creating any air

bubbles. The gage and tape were then carefully removed from the acrylic plate and taped

in position at the gage location. Once in position, the gage and tape were carefully peeled

back from the gaging surface to reveal the underside of the strain gage. A catalyst

(Vishay 200 Catalyst-C) was then applied to the underside of the strain gage in one

stroke, and allowed to dry. A small amount of gaging epoxy (Vishay M-Bond 200) was

then applied just behind the gage location towards the peeled-back gage and tape. The

peeled-back gage and tape were then applied to the gage location. While applying the

gage and tape, a thin layer of gaging epoxy was spread under the gage and tape for the

entire length of the gage location. Pressure was applied to the gage and tape for at least

one minute, allowing the gaging epoxy to set. After removing pressure and waiting a few

more minutes, the tape was very carefully removed from the back of the gage.

Photographs of an installed FRP strain gage are shown in Figures 1976H3.31 and 1977H3.32.

114

Figure 3.31: Strain gage installation—gage application with thin epoxy

Figure 3.32: Strain gage installation—gage applied to FRP reinforcement

115

Following the application of each gage, moisture and mechanical protection was

applied in order to increase the durability of the gage. A liquid rubber coating was

applied to the gage and surrounding surface to act as moisture protection. After the

rubber coating dried, a strip of mastic tape was applied to provide mechanical protection.

The mastic tape strip was long enough to provide some support for the pre-attached lead

wires extending from the gage to a terminal strip mounted on the girder, adding

protection against the wires detaching from the gage due to unexpected tension.

Photographs of an FRP strain gage with installed protection are shown in Figures 1978H3.33

and 1979H3.34.

Figure 3.33: Strain gage installation—rubber coating for moisture protection

116

Figure 3.34: Strain gage installation—mastic tape for mechanical protection

3.6 47BDATA ACQUISITION SYSTEM

A total of seventy-two sensors were attached to a data acquisition system, and each

sensor was assigned a specific channel. An Optim Megadac® data acquisition system

recorded measurements corresponding with each sensor at a rate of either 60 or 120 scans

per second. A picture of the data acquisition system used during bridge testing can be

seen in 1980HFigure 3.35.

117

Figure 3.35: Data acquisition hardware

3.7 48BSENSOR NOTATION

For data acquisition and analysis purposes, each sensor was assigned unique

identification. The notation for sensor identification incorporated the instrument type,

girder number, span number, and instrument location. The instrument type was assigned

the following notation: CO for crack-opening displacement gage, D for deflectometer,

S for concrete surface strain gage, and F for FRP reinforcement surface strain gage.

Immediately following the instrument type, a number is used to represent the girder line

(7 or 8) for the instrument. Following the girder line notation and an underscore, another

number is used to represent the span (10 or 11) containing the instrument. Following the

span notation and another underscore, the instrument location notation concludes the

sensor identification.

118

The different sensor types require different instrument location notation. The COD

gage locations are only indicated by the girder number and span number and do not

require additional gage location notation. The twelve deflectometers require six location

designations per girder line. The notation selected for these six deflectometer locations

range from A through F, with A located at the midspan of Span 10 and F located at the

midspan of Span 11. Figures and tables detailing these deflectometer locations can be

seen in Section 1981H3.4.1. Strain gage location notation is derived by cross section and then

the location on the girder within that specific cross section. The cross section notation is

indicated by a number (1–8). The potential concrete surface strain gage locations within

a cross section are indicated by letters (V, W, X, Y, Z, and M). Similarly, the potential

FRP reinforcement surface strain gage locations within a cross section are indicated by

letters (Y, Z, M, and CK). Figures and tables detailing these strain gage locations can be

seen in Section 1982H3.5.1. The data acquisition channel layout assigned to the seventy-two

sensors can be seen in Appendix L. The following are examples of the data acquisition

sensor identification for each instrument type:

CO8_10 - Crack Opening Displacement Gage

Girder Line 8, Span 10

D8_11_F - Deflectometer

Girder Line 8, Span 11, Location F

S7_10_1V - Concrete Surface Strain Gage

Girder Line 7, Span 10, Cross Section 1, Gage Location V

F7_10_1M - FRP Reinforcement Strain Gage

Girder Line 7, Span 10, Cross Section 1, Gage Location M

119

Chapter 4

8BBRIDGE TESTING PROCEDURES

4.1 49BINTRODUCTION

Bridge testing was conducted to analyze the behavior of the damaged bridge after

installed FRP reinforcement had been in service for more than 2 years. This testing took

place over two nights. The first night of load testing included the designation of truck

traverse lanes and stop positions, and the completion of the first phase of acoustic

emissions (AE) testing. Immediately following the first night of load testing, sensor

measurements were monitored at fifteen-minute intervals between the two nights of

testing to investigate the bridge response to diurnal thermal conditions. The second night

of load testing included the second phase of acoustic emissions testing, multiposition load

testing, and a superposition load test. Details and procedures of the post-repair bridge

testing are discussed within this chapter. Full details of the post-repair acoustic emissions

testing have been reported by Hadzor (2011).

4.2 50BTRAFFIC CONTROL

The instrumented spans of I-565 in Huntsville support four lanes of northbound traffic.

During pre-repair load testing, it was determined that traffic traveling in the far west lane

of the northbound bridge had a minimal influence on readings taken from the east side of

the bridge (Fason 2009). Girders 7 and 8, the instrumented girders, are located on the

120

east side of the northbound bridge. It was decided that leaving the west lane of traffic

open during testing would be acceptable as long as measurements were collected during

times of minimal traffic interference. In order to provide a safe working environment

during the overnight testing hours, ALDOT officially closed the three east lanes with

standard lane closure procedures including placement of safety cones and adequate

warning signs. The lanes were closed for a distance long enough to provide the load

trucks space with which to maneuver once clear of the spans being tested, Northbound

Spans 10 and 11.

The effect of traffic control on normal traffic flow demands was also considered.

Previously collected traffic volume data was analyzed to determine that the best period

for lane closures was between 11 p.m. and 4 a.m. daily. This time frame also coincides

with optimal load testing circumstances due to relatively steady-state atmospheric

conditions. ALDOT began closing the three east lanes at 11 p.m. and the lanes were

re-opened to normal traffic before 4 a.m. each night of load testing.

4.3 51BLOAD TESTING TRUCKS

Two trucks were used to load the bridge for testing purposes. For the pre-repair tests, one

of the standard load test trucks was out of service and replaced immediately prior to

testing with a nonstandard truck. The replacement truck used during pre-repair testing

was an ALDOT tool trailer truck (ST-6902). The other truck used during the pre-repair

tests was a standard ALDOT load test truck (ST-6400).

To maintain consistent test conditions for the post-repair testing, it was suggested that

both trucks used during pre-repair testing continue their roles as load test trucks for the

post-repair tests. The standard truck (ST-6400) did continue its role as a load test truck,

121

but the replacement truck (ST-6902) was no longer available at the time of post-repair

testing. Another standard ALDOT load test truck (ST-6538) was chosen to replace the

tool trailer truck (ST-6902) for post-repair testing. The ST-6538 truck has the same

footprint as the ST-6400 truck. Photos of the three different ALDOT trucks can be seen

in Figures 1983H4.1, 1984H4.2, and 1985H4.3. The footprints of the different ALDOT trucks can be seen in

Figures 1986H4.4 and 1987H4.5.

Figure 4.1: ST-6400 (standard load truck)

122

Figure 4.2: ST-6902 (pre-repair unconventional truck)

Figure 4.3: ST-6538 (post-repair replacement for pre-repair unconventional truck)

123

Figure 4.4: Footprint of ALDOT load testing trucks (ST-6400 and ST-6538)

97.25 in.

96 in.

13.5 in.

75 in.

279 i

n.

22.25 in.

222 in

.

13.5 in.

22.25 in.

124

Figure 4.5: Footprint of ALDOT tool trailer truck (ST-6902)

21.5 in. 21.5 in.

95.5 in.

12.5 in.

73.5 in.

280.5

in. 2

27 in

.

12.5 in.

94 in.

125

4.3.1 153BLOAD TRUCK BLOCK CONFIGURATIONS

The first night of testing consisted of a nonstandard ALDOT load test block configuration

for the acoustic emissions pre-load tests. This AE pre-load block configuration was titled

LC-6.5. The weights of the load trucks were decreased for the second night of testing by

loading the trucks with a standard ALDOT load truck block configuration titled LC-6.

Load trucks were originally intended to be loaded with identical block configurations

during testing, but the bed of the pre-repair replacement truck (ST-6902) extended further

beyond the back axle in comparison to the bed of the standard truck (ST-6400), which

resulted in slightly different weight distributions. Prior to pre-repair testing, an attempt

was made to rearrange the blocks on the replacement truck to compensate for the

different truck dimensions. However, the resulting weight distributions were not

accurately determined until after the completion of the pre-repair testing, when the truck

weights for the pre-repair block configurations were measured at ALDOT headquarters in

Montgomery, Alabama. The measured weight distributions of each truck for the LC-6.5

and LC-6 pre-repair load conditions can be seen in 1988HTable 4.1.

126

Table 4.1: Load truck weight distributions—pre-repair

Axle Group Tires

ST-6400 ST-6902

LC-6.5

(lbs)

LC-6

(lbs)

LC-6.5

(lbs)

LC-6

(lbs)

Front Left Single 11500 10750 7575 7850

Right Single 11500 10900 7200 7450

Rear 1 Left Double 19450 18900 20300 19350

Right Double 19150 18350 19500 18750

Rear 2 Left Double 18000 17200 19450 18600

Right Double 17850 17500 20150 19250

Total Weight (lbs) 97450 93600 94175 91250

The load truck block configurations for the post-repair load tests were designed to

replicate the measured weight distributions from the pre-repair load tests. The block

configurations for the standard load truck (ST-6400) remained the same, but the block

configurations for the standard load truck (ST-6538) that replaced the unconventional

truck (ST-6902) had to be modified. Blocks were moved appropriately to best match the

magnitude and location of the resultant loads measured after the conclusion of pre-repair

testing. The weight distributions for the post-repair tests were measured before

conducting any post-repair testing. The recorded weight distributions of each truck for

the LC-6 and LC-6.5 post-repair load conditions can be seen in Table 1989H4.2.

127

Table 4.2: Load truck weight distributions—post-repair

Axle Group Tires

ST-6400 ST-6538

LC-6.5

(lbs)

LC-6

(lbs)

LC-6.5

(lbs)

LC-6

(lbs)

Front Left Single 10950 10800 8150 7750

Right Single 11600 11000 7950 8100

Rear 1 Left Double 18050 17500 20200 19200

Right Double 19300 18600 19300 18400

Rear 2 Left Double 18000 17250 20450 19850

Right Double 19100 18750 18650 17700

Total Weight (lbs) 97000 93900 94700 91000

A comparison of the weight distributions for the unconventional pre-repair truck

(ST-6902) and its post-repair standard load truck replacement (ST-6538) with modified

block configurations can be seen in 1990HTable 4.3. The post-repair block configurations are

shown in Figures 1991H4.6–1992H4.9. For all block configurations, each axle load is illustrated with

a solid line, and the net resultant truck load is illustrated with a dashed line.

Table 4.3: Comparison of unconventional load truck weight distributions

Axle Group Tires

ST-6902

(pre-repair)

ST-6538

(post-repair)

LC-6.5

(lbs)

LC-6

(lbs)

LC-6.5

(lbs)

LC-6

(lbs)

Front Left Single 7575 7850 8150 7750

Right Single 7200 7450 7950 8100

Rear 1 Left Double 20300 19350 20200 19200

Right Double 19500 18750 19300 18400

Rear 2 Left Double 19450 18600 20450 19850

Right Double 20150 19250 18650 17700

Total Weight (lbs) 94175 91250 94700 91000

128

Figure 4.6: LC-6.5 block configuration—post-repair ST-6400

Figure 4.7: LC-6 block configuration—post-repair ST-6400

Side

View

Top Layer = 12 Blocks

36.0 kips 36.1 kips 21.8 kips 93.9 kips

29.7 in.

Bottom Layer = 16 Blocks (Full)

Top

View

Side

View

Top Layer = 14 Blocks

37.1 kips 37.4 kips 97.0 kips

22.6 kips

29.8 in.

Bottom Layer = 16 Blocks (Full)

Top

View

Resultant Force

Front Axle

Resultant Force

129

Figure 4.8: LC-6.5 block configuration—post-repair ST-6538

Figure 4.9: LC-6 block configuration—post-repair ST-6538

Side

View

Top Layer = 6 Blocks

Top

View

37.6 kips 37.6 kips 15.9 kips 91.0 kips

15.1 in.

Middle Layer = 9 Blocks

Bottom Layer = 12 Blocks

Side

View

Top Layer = 8 Blocks

39.1 kips 39.5 kips 16.1 kips 94.7 kips

14.2 in.

Middle Layer = 9 Blocks

Bottom Layer = 12 Blocks

Top

View

Front Axle

Resultant Force

Front Axle

Resultant Force

130

4.3.2 154BRESULTANT FORCE COMPARISONS—PRE- AND POST-REPAIR

As previously mentioned, the resultant force for each load truck was monitored when

modifying the post-repair block configurations. The magnitude and location of the

resultant forces varied for the consistent load truck (ST-6400) with consistent block

configurations, as shown in Tables 1993H4.4 and 1994H4.5.

Table 4.4: Resultant force comparisons—ST-6400—LC-6

Load Configuration

LC-6

Total Weight

(kips)

Resultant Location

from middle axle

(in.)

from rear axle

(in.)

Pre-Repair

(ST-6400) 93.6 30.2 87.2

Post-Repair

(ST-6400) 93.9 29.7 86.7

Difference 0.3 -0.5 -0.5

Table 4.5: Resultant force comparisons—ST-6400—LC-6.5

Load Configuration

LC-6.5

Total Weight

(kips)

Resultant Location

from middle axle

(in.)

from rear axle

(in.)

Pre-Repair

(ST-6400) 97.4 31.4 88.4

Post-Repair

(ST-6400) 97.0 29.8 86.8

Difference -0.4 -1.6 -1.6

131

The change in the location and magnitude of the resultant force for the two

inconsistent load trucks are shown in Tables 1995H4.6 and 1996H4.7.

Table 4.6: Resultant force comparisons—ST-6902 and ST-6538—LC-6

Load Configuration

LC-6

Total Weight

(kips)

Resultant Location

from middle axle

(in.)

from rear axle

(in.)

Pre-Repair

(ST-6902) 91.2 15.9 69.4

Post-Repair

(ST-6538) 91.0 15.1 72.1

Difference -0.2 -0.8 2.7

Table 4.7: Resultant force comparisons—ST-6902 and ST-6538—LC-6.5

Load Configuration

LC-6.5

Total Weight

(kips)

Resultant Location

from middle axle

(in.)

from rear axle

(in.)

Pre-Repair

(ST-6902) 94.2 13.1 66.6

Post-Repair

(ST-6538) 94.7 14.2 71.2

Difference 0.5 1.1 4.6

132

After modifying the block configurations for the replacement truck (ST-6538), the

magnitude of the resultant force exhibited similar magnitudes of variation compared to

those of the consistent load truck (ST-6400). The location of the resultant force exhibited

similar variation when measured from the middle axle, but, due to the change in truck

dimensions, the location of the resultant exhibited larger variations when measured from

the rear axle. Each truck was positioned based on its middle axle for all tests except the

acoustic emissions tests, in which each truck was positioned based on its rear axle. These

slight variations of magnitude and location of resultant forces were considered negligible

based on the scale of the load testing.

4.3.3 155BNIGHT 1—AE PRELOADING—LC-6.5

The acoustic emissions pre-load test was designed to apply a heavier load than the bridge

had ever experienced in service. The load combination LC-6.5 was designed to be

slightly heavier than the standard ALDOT load test combination LC-6 and to induce load

effects approximately 10–15 percent larger than those corresponding to service limit state

design. The purpose of this heavier load scenario was to activate any existing cracks.

More information regarding the acoustic emissions test procedure can be found in

Section 1997H4.5. The post-repair LC-6.5 block configurations for load test trucks ST-6400

and ST-6538 can be seen in Figures 4.6 and 4.8 respectively.

4.3.4 156BNIGHT 2—AE LOADING AND MULTIPOSITION LOAD TEST—LC-6

The second night of load testing included a repeat of the acoustic emissions tests using

the lighter load combination, LC-6. Due to the decreased truck weights relative to the

first night, no new crack initiation was expected, but existing cracks were expected to

open and close. Following the completion of the acoustic emissions testing,

133

multiposition load tests were conducted with the same LC-6 block configurations. More

information regarding the multiposition load test procedure can be found in Section 1998H4.7.

The post-repair LC-6 block configurations for load test trucks ST-6400 and ST-6538 can

be seen in Figures 4.7 and 4.9 respectively.

4.3.5 157BTRUCK WEIGHT LIMITS

The load combinations used during the load tests were heavier than any truck legally

allowed on Alabama highways. Fason (2009) stated that the maximum total weight of

any legal truck is 84 kips for a six-axle truck (3S3_AL). The maximum total weight of a

legal truck with a similar footprint to ALDOT load test trucks is 75 kips for a tri-axle

dump truck. The total weight of a single ALDOT load test truck used during post-repair

and pre-repair testing ranged from 91to 97 kips.

4.4 52BLOAD TESTING TRAVERSE LANES AND STOP POSITIONS

Specific load testing lanes and stop positions were required to consistently provide

known truck positions during testing. Information regarding the detailed locations of

these lines can be found in Sections 1999H4.4.1 and 2000H4.4.2. The load truck traverse lanes and

stop positions were painted on the driving surface of the bridge after traffic control

allowed for a safe work environment. An overhead photo of the painted lines

representing traverse lanes and stop positions can be seen in 2001HFigure 4.10.

134

Figure 4.10: Traverse lanes and stop positions—overhead photo

4.4.1 158BTRAVERSE LANES

During pre-repair testing, three load lane configurations were designed to apply specific

load scenarios to each girder of interest. Each load lane required two traverse lines, one

for the east truck and one for the west truck. For the pre-repair multiposition load testing,

the conventional load test truck (ST-6400) was always the east truck, while the

unconventional load test truck (ST-6902) was always the west truck. The three load

truck traverse lanes were titled Lanes A, B, and C. Lane A centered the west wheel

group of the east truck directly over Girder 7. Lane B centered the east wheel group of

the west truck directly over Girder 7. Lane C centered the west wheel group of the east

truck directly over Girder 8. After analysis of the pre-repair load test results, it was

determined that Lanes A and C yielded the most useful results for determining bridge

response (Fason 2009). Thus, only these two lane configurations were utilized during

135

post-repair load testing. The truck wheel positions of Lanes A and C are shown in

Figures 2002H4.11 and 2003H4.12 respectively.

Figure 4.11: Lane A—Horizontal truck positioning (multiposition test)

Figure 4.12: Lane C—Horizontal truck positioning (multiposition and AE tests)

40.5‖ 96‖

Cast-in-place

concrete barrier

64’ - 0‖

70’ - 9‖

6.5‖

Girder 7 Girder 8

73.5‖ 75‖ 49‖

ST-6538 ST-6400

AASHTO BT-54 Girders

40.5‖ 96‖ AASHTO BT-54 Girders

Cast-in-place

concrete barrier

64’ - 0‖

70’ - 9‖

6.5‖

Girder 7 Girder 8

73.5‖ 75‖ 49‖

ST-6538 ST-6400

136

For the post-repair load testing, Lane C was traversed for the acoustic emissions and

multiposition load tests, and Lane A was only traversed during the multiposition load

test. ST-6400 retained its role as the east load truck, while ST-6538 replaced ST-6902 as

the west load truck during the post-repair static load tests. To better distinguish between

the two lanes, different colored paint was used to indicate the north-south traverse lanes.

Orange paint indicated Lane A, and yellow paint indicated Lane C.

4.4.2 159BSTOP POSITIONS

Prior to pre-repair testing, nine stop positions along each traverse lane were designated to

provide consistent stationary truck positions for repeated data collection. The nine stop

positions range from the midspan of Span 10 to the midspan of Span 11. These

longitudinal stop positions are illustrated in 2004HFigure 4.13. Five stop positions are located

on Span 10, while four stop positions are located on Span 11. Descriptions of the nine

stop position locations relative to the centerline of the continuity diaphragm can be seen

in 2005HTable 4.8. Yellow lines were painted in the east-west direction across all north-south

traverse lines to indicate the nine stop positions. For acoustic emissions tests, the load

trucks were stopped when their back axle was aligned with the desired east-west stop

position line. For the multiposition load tests, the load trucks were stopped when their

middle axle was aligned with the desired stop position line.

137

Table 4.8: Stop position locations

Stop Position Position Description

Distance from Center

of Continuity

Diaphragm

[middle axle]

(in.)

1 middle axle—midspan of span 10 -600

2 front axle—cross section 1 -291

3 front axle—cross section 4 -151

4 middle axle—cross section 1 -70

5 rear axle—cross section 1 -12

6 middle axle—cross section 4 70

7 rear axle—cross section 4 128

8 middle axle—quarter-span of span 11 300

9 middle axle—midspan of span 11 600

138

Figure 4.13: Stop position locations

Legend:

Stop Position

Centerline of Continuity Diaphragm

600‖ 600‖

12‖

Bent 10

Simple

Support

Span 11

Bent 11

Continuity

Diaphragm

Span 10

Bent 12

Simple

Support

9 8

7 6 5 4 3 2 1

291‖ 300‖

151‖ 128‖

70‖ 70‖

False Support False Support

139

4.5 53BACOUSTIC EMISSIONS LOAD TESTING

The acoustic emissions testing and analysis do not fall within the scope of this thesis.

Hadzor (2011) has reported the details and results of this testing. Although the AE

results are not presented in this thesis, data were collected from the static load test

instruments to assist with the AE testing analysis. Measurements from all of the static

load test sensors (strain gages, deflectometers, and COD gages) were recorded during the

AE testing.

AE testing took place both nights. The first night of AE testing began later in the

night due to the time allotted for painting the lines designating load truck lanes and stop

position. With no load trucks and minimal traffic on Spans 10 and 11, all of the static

load test instrument channels were balanced (zeroed) before beginning the first night of

AE testing. The channels were not rebalanced for the remainder of the post-repair load

tests.

The acoustic emission test procedures were consistent for the pre- and post-repair

tests. The AE testing began when baseline data were collected to represent the zero-load

condition. Both load trucks then backed down traverse Lane C until their back axles

reached the desired stop positions. The two AE stop positions are illustrated in

Figure 2006H4.14. The back axles aligned with Stop Position C4 for Span 10 testing, and

aligned with Stop Position C6 for Span 11 testing.

140

Figure 4.14: Acoustic emissions test—stop position locations

70‖ 70‖

Bent 10

Simple

Support

Span 11

Bent 11

Continuity

Diaphragm

Span 10

Bent 12

Simple

Support

6 4

ST-6400 (east)

ST-6538 (west)

ST-6400 (east)

ST-6538 (west)

Legend:

Stop Position

Centerline of Continuity Diaphragm

False Support False Support

141

Span 10 was the first span tested during both nights of AE testing. Span 10 AE

testing began once both trucks were aligned with their respective Lane C traverse lines on

Span 9. The east truck (ST-6400) was slowly driven backward along Lane C in Span 10

until the back axle reached Stop Position C4. Once the east truck was in position, it was

held in position for six minutes. While the truck was held in position, a short time

interval of measurements from the static load test sensors was recorded. The west truck

(ST-6538) was then slowly backed along Span 10 until its back axle also reached

Stop Position C4. Both trucks were then held in position for another six minutes, and

static load test measurements were recorded. The trucks were then simultaneously driven

forward off of Span 10 and onto Span 9. The west lane that was open to normal traffic

was used to transport the trucks from Span 9 to Span 12 for the second round of AE

testing.

Span 11 AE testing began once both trucks were in position on Span 12, and another

baseline reading was recorded to represent the current zero-load condition. The east truck

(ST-6400) was backed onto Span 11 until its back axle reach Stop Position C6, and held

in position for six minutes. Static load test measurements were recorded while ST-6400

was held in position. The west truck (ST-6538) was then backed into position, and both

trucks were held in position for six minutes. Static load test measurements were recorded

with both trucks held in position. Both trucks then simultaneously drove forward off of

Span 11 and onto Span 12 to conclude the AE testing.

The acoustic emissions test procedure was completed twice during both the pre- and

post-repair tests. The first night of acoustic emissions testing was conducted with the

142

heavier LC-6.5 block configurations, and the second night of testing was conducted with

the LC-6 block configurations.

4.6 54BBRIDGE MONITORING

The instrumented girders were monitored over the course of one twenty-four hour time

period to allow for analysis of bridge behavior due to temperature change during a typical

late-spring day/night cycle. After the completion of the first night of acoustic emissions

testing, sensor measurements were recorded every fifteen minutes. Due to increased

traffic volume and no lane closures during the day, at least ten seconds of measurements

were recorded at a rate of sixty scans per second to provide more data for analysis at each

fifteen-minute interval. The raw data was then reduced by selecting the most time-frames

that yielded the most consistent measurements with minimal electrical noise and as close

to a zero traffic loading condition as possible. These fifteen-minute recording intervals

were continued until the beginning of the second night of load testing. The baseline set

of measurements for the first night of AE testing is considered to exhibit the baseline

conditions for all of the bridge monitoring measurements.

4.6.1 160BWEATHER CONDITIONS DURING PRE-REPAIR TESTING

Bridge monitoring was not conducted during the pre-repair load tests of 2005, but it is

still pertinent to compare the weather conditions during both the pre- and post-repair load

tests. Fason (2009) stated that the weather conditions during the pre-repair tests included

significant cloud cover and rain. These pre-repair conditions were not conducive to

temperature variations throughout the day. It was noted that cracks in the girders were

visibly smaller on the days surrounding the pre-repair tests than on earlier days when

sensors were installed (Fason 2009).

143

Weather data collected at the Huntsville International Airport for the days

encompassing pre-repair testing is presented in 2007HTable 4.9.

Table 4.9: Weather during pre-repair bridge testing (NOAA 2005)

Date Minimum

Temperature

(°F)

Maximum

Temperature

(°F)

Mean

Temperature

(°F)

Precipitation

(in.)

May 31, 2005 61 77 69 0.02

June 1, 2005 63 70 67 0.93

June 2, 2005 63 81 72 0.04

4.6.2 161BWEATHER CONDITIONS DURING POST-REPAIR TESTING

The weather conditions for the days surrounding the post-repair load tests in 2010 were

conducive to temperature variations throughout the day. On these days, there was little to

no cloud cover and no rain, which resulted in significantly higher maximum temperatures

for the days surrounding the post-repair tests when compared to the maximum

temperatures for the days surrounding the pre-repair tests. Even though the maximum

post-repair temperatures were greater than the maximum pre-repair temperatures, the

minimum post-repair temperatures at night, which is when load testing was conducted,

were similar to the minimum pre-repair temperatures. Weather data collected at the

Huntsville International Airport for the days encompassing post-repair testing are

presented in 2008HTable 4.10.

144

Table 4.10: Weather during post-repair bridge testing (NOAA 2010)

Date Minimum

Temperature

(°F)

Maximum

Temperature

(°F)

Mean

Temperature

(°F)

Precipitation

(in.)

May 24, 2010 67 94 81 0.00

May 25, 2010 68 85 77 0.00

May 26, 2010 66 90 78 0.26

Note: Precipitation on May 26 accumulated after the conclusion of post-repair testing

The post-repair weather conditions were favorable for the desired analysis of structural

behavior in response to large temperature variations experienced during a daily cycle.

Temperatures measured at the Huntsville International Airport every three hours during

post-repair bridge monitoring are presented in 2009HTable 4.11. Sunrise reportedly occurred at

4:38 a.m., and sunset reportedly occurred at 6:50 p.m. on May 25, 2010. (NOAA 2010)

Table 4.11: Temperatures measured during bridge monitoring (NOAA 2010)

Date Time

(CST)

Temperature

(°F)

May 25, 2010

12:00 a.m. 72

3:00 a.m. 71

6:00 a.m. 71

9:00 a.m. 78

12:00 p.m. 80

3:00 p.m. 84

6:00 p.m. 82

9:00 p.m. 75

May 26, 2010 12:00 a.m. 70

3:00 a.m. 66

145

4.7 55BMULTIPOSITION LOAD TESTING

Multiposition load tests were conducted for the pre-repair condition on June 2, 2005, and

were repeated for the post-repair condition on May 25, 2010. Lanes A, B, and C were

sequentially traversed during the pre-repair tests, but only Lanes A and C were traversed

during the post-repair tests. Load trucks simultaneously traversed northbound, keeping

the driver-side tires aligned with their respective lane line, and stopped at designated stop

positions for a time interval long enough for steady measurements to be recorded.

A baseline representing the zero-load condition was established by collecting

measurements while no trucks were on the instrumented spans. The trucks stopped at

each of the nine stop positions along each traverse lane long enough to allow for

measurements to be recorded at a rate of 120 scans per second for a minimum of three

seconds without traffic interference. Lane C was traversed three times consecutively, and

the trucks stopped at all nine stop positions during each traverse. This process was then

repeated for Lane A.

Every sensor was measured and recorded three times for each stop position. The data

collected were organized according to the traverse lane, stop position, and round of

testing, for example C3—Round 2. The measurements for each sensor from each of the

three traverse rounds were averaged, with the option of eliminating an outlier, to establish

one reported measurement for each sensor with respect to each stop position load

condition.

146

The following list describes the step-by-step procedure for the multiposition load testing:

1. While on Span 9, align both trucks with the lines necessary to traverse Lane C

2. Record data for three seconds to establish a baseline for the current conditions

3. Drive both trucks to Position 1 and record data for three seconds

4. Repeat Step 3 for Positions 2–9.

5. Drive trucks back to their starting positions on Span 9 and record another baseline

6. Repeat Steps 3 and 4 to complete a second round of testing

7. Drive trucks back to their starting positions on Span 9 and record a third baseline

8. Repeat Steps 3 and 4 to complete a third round of testing

9. Drive trucks back to Span 9 and realign with traverse Lane A

10. Repeat Steps 2–8 to complete all testing for Lane A

4.8 56BSUPERPOSITION TESTING

After the last round of static load testing, a supplemental static load test was conducted to

analyze the bridge behavior with respect to the superposition of load effects. Load trucks

were aligned along the east line of Lane A as shown in 2010HFigure 4.15. Measurements were

collected while both trucks were off of the instrumented spans to establish a baseline for

the current zero-load condition. ST-6400 was driven to Stop Position A9 and held in

position long enough for sensor measurements to be collected without traffic interference.

With ST-6400 still holding at Stop Position A9, ST-6538 was driven to Stop Position A1.

Both trucks were held in position for measurements representing the effects of the

combined loading. ST-6400 was then driven off of Span 11 and onto Span 12 while

ST-6538 was held in position for measurements representing a single-truck loading at

147

Stop Position A1. The stop position locations for the superposition test are illustrated in

2011HFigure 4.16. Only one round of superposition testing was completed.

During analysis, the results of the two single-truck load scenarios can be added

together and compared to the results of the load scenario with both trucks simultaneously

at their respective stop positions. Theoretically, if the overall bridge behavior is linear-

elastic throughout the loading range, for each sensor the sum of the results from the two

single-truck loadings should equal the result from the dual-truck loading.

Figure 4.15: Superposition test—horizontal lane positioning

40.5‖ 96‖ AASHTO BT-54 Girders

Cast-in-place

concrete barrier

64’ – 0‖

70’ – 9‖

6.5‖

Girder 7 Girder 8

75‖

ST-6400 (Span 11)

ST-6538 (Span 10)

148

Figure 4.16: Superposition test—stop position locations

Bent 10

Simple

Support

Span 11

Bent 11

Continuity

Diaphragm

Span 10

Bent 12

Simple

Support

Legend:

Stop Position

Centerline of Continuity Diaphragm

9 1

600‖ 600‖

ST-6538

ST-6400

False Support False Support

149

4.9 57BDATA REDUCTION AND ANALYSIS

For analysis purposes, a single numerical result for each sensor was desired for each

recorded event. Even though data collection occurred during static loading conditions,

every sensor experienced some variance during each recording interval. This variance

seems to be mainly related to electrical noise, but could also be associated with physical

effects related to normal traffic loads or lingering dynamic loads resulting from moving

load trucks into position. For the static load tests, only one lane was open to normal

traffic and recorded events were only affected by electrical noise and potentially the

dissipation of dynamic loads associated with moving the load trucks into position.

During bridge monitoring, all lanes were open to normal traffic and some recorded events

correlated with traffic events. Due to increased variable traffic loading, bridge

monitoring data collection required an increased recording window to allow for the

identification of a suitable traffic-free time interval. Selective data reduction was

implemented to reduce effects the inconsistencies might have on the final reported results

for all post-repair tests.

During data collection, a separate raw data file was created for each recording

interval. Raw data files were organized according to their respective tests and load

conditions. Initial data analysis included plotting the raw data measurements over time.

These raw data plots were inspected, and reduced time intervals exhibiting relatively

consistent behavior were selected for further data analysis. Each reduced time interval

was then plotted for each sensor, and a slightly more reduced time interval was then

selected to represent even more consistent data. The average numerical result for each

sensor over this more consistent time interval was recorded for further analysis. For

150

each recorded event, average values for up to three consistent time intervals were

recorded for each sensor. These average values were then averaged together to represent

a single numerical result for each sensor relative to each recorded event.

During initial data analysis it was determined that certain sensors were more likely

than others to exhibit inconsistent raw data. Sensors judged to be more vulnerable to

inconsistencies included the following:

D7_11_F (Deflectometer—Girder 7—Span 11—Location F [Midspan])

S8_11_3W (Concrete Strain Gage—Girder 8—Span 11—Section 3—Location W)

F8_11_4M (FRP Strain Gage—Girder 8—Span 11—Section 4—Location M)

For each recorded event, the least consistent sensors were used to efficiently identify the

reduced time intervals to be analyzed for all sensors. The majority of the sensors were

consistent enough that results rounded to an appropriate precision remained constant

regardless of the time intervals selected during data reduction.

151

Chapter 5

9BRESULTS AND DISCUSSION

5.1 58BINTRODUCTION

During post-repair testing of Northbound Spans 10 and 11 of I-565 in Huntsville,

Alabama, structural behaviors were measured in response to varying load-truck positions

as well as varying ambient thermal effects during normal traffic conditions. Pre- and

post-repair measured responses to truck loads were analyzed to address the suspicion that

contact between girders and false support bearing pads—which were present during pre-

repair testing but removed prior to FRP installation—had an effect on pre-repair

structural behavior, thus making direct comparison between pre- and post-repair behavior

inappropriate for assessing the effectiveness of the FRP repair (Fason 2009). Post-repair

behavioral responses were analyzed independent of pre-repair measured responses to

specifically assess structural behavior observed during post-repair testing. Post-repair

measured responses to service-level truck loads were also compared to post-repair

structural behavior predicted using finite-element modeling (FEM) techniques

(Shapiro 2007). In addition to analyzing behavioral responses to truck loads, theoretical

and measured responses to varying ambient thermal conditions were analyzed to assess

the effects of temperature-induced loading on the instrumented girders.

Measurements from pre-repair testing have been reported by Fason (2009). Predicted

responses to post-repair testing have been reported by Shapiro (2007). Reported post-

152

repair measurements are presented within the appendices of this thesis. The analysis of

specific measurements and theoretical behavior predictions is discussed within this

chapter.

5.2 59BBEARING PAD EFFECTS

Inconsistent structural conditions during pre- and post-repair testing could impact the

ability to assess the effectiveness of an installed repair solution using direct comparisons

of pre- and post-repair measured behavior. Variable conditions that could affect the

ability to directly relate behavioral changes measured between pre- and post-repair

testing to the performance of a repair solution include

Different temperature gradients during pre- and post-repair testing,

Different temperature gradients during pre-repair testing and installation of

the repair,

Additional damage occurring between pre-repair testing and installation of the

repair, and

Addition or removal of load-bearing support conditions between pre- and

post-repair testing.

Of these variable conditions, adding or subtracting support conditions would have the

most apparent effect on bridge behavior measured in response to load testing. For this

reason, it is important to determine if the steel false supports installed slightly beyond the

damaged regions of Spans 10 and 11 were acting as load-bearing supports during testing.

Elastomeric bearing pads were located on top of the false supports prior to pre-repair

testing of the bridge structure. These bearing pads were supposed to be removed prior to

153

the first day of pre-repair testing, but complete removal of all pads was unsuccessful

because some of the girders were in contact with the bearing pads. The bearing pads

under Span 10 were easier to remove than the bearing pads under Span 11. Under

Span 10, the bearing pad corresponding to Girder 8 was completely removed, and the

bearing pad corresponding to Girder 7 was partially removed. The bearing pads

corresponding to Girders 7 and 8 of Span 11 could not be removed prior to the pre-repair

tests. All of the false-support bearing pads were finally removed during the FRP

installation process, so they were not present during post-repair testing.

Following pre-repair testing, it was noted by Fason (2009) that the remaining bearing

pads likely allowed some of the load to be transmitted through the false supports rather

than spanning to the bents. Fason also reported that, due to the pre-repair bearing pad

effects, direct comparisons between pre- and post-repair measurements may not be

indicative of the effectiveness of the FRP repair. For this reason, post-repair

measurements were analyzed to check whether these bearing pads had enough of an

impact on the pre-repair measurements that the effectiveness of the repair could not be

accurately assessed by direct comparison of measurements from pre- and post-repair

testing.

Multiple comparisons were made to assess the pre-repair bearing pad effects. These

comparisons include deflections, crack-opening displacements, and strains measured in

response to different load-truck positions. A summary of bearing pad conditions and

comparisons of pre-and post-repair measurements are presented in 2012HAppendix K of this

thesis.

154

The comparison of crack-opening displacements from the pre- and post-repair tests in

response to the same truck positions is one behavior that indicates that the bearing pads

had a significant effect on the pre-repair measurements. Stop positions that resulted in

crack openings were analyzed. Stop position locations are described in Section 2013H4.4 of

this thesis. During both the pre- and post-repair tests, Stop Position 4 had the greatest

effect on the Span 10 crack openings, and Stop Position 7 had the greatest effect on the

Span 11 crack openings. The pre- and post-repair crack-opening displacement

measurements for Stop Positions A4, A7, C4, and C7 are presented in Figures 2014H5.1–2015H5.4

and 2016HTable 5.1. The arrows in the figures represent the position of the wheel loads on the

bridge.

Figure 5.1: Crack-opening displacements—pre- and post-repair—A4

-0.05

-0.04

-0.03

-0.02

-0.01

0.00

0.01

0.02

0.03

0.04

0.05

-300 -250 -200 -150 -100 -50 0 50 100 150 200 250 300

Cra

ck-O

pen

ing

Dis

pla

cem

ent

(mm

)

Distance from Center of Continuity Diaphragm (in.)

G7 (Pre-Repair)

G8 (Pre-Repair)

G7 (Post-Repair)

G8 (Post-Repair)

155

Figure 5.2: Crack-opening displacements—pre- and post-repair—A7

Figure 5.3: Crack-opening displacements—pre- and post-repair—C4

-0.05

-0.04

-0.03

-0.02

-0.01

0.00

0.01

0.02

0.03

0.04

0.05

-300 -250 -200 -150 -100 -50 0 50 100 150 200 250 300

Cra

ck-O

pen

ing

Dis

pla

cem

ent

(mm

)

Distance from Center of Continuity Diaphragm (in.)

G7 (Pre-Repair)

G8 (Pre-Repair)

G7 (Post-Repair)

G8 (Post-Repair)

-0.05

-0.04

-0.03

-0.02

-0.01

0.00

0.01

0.02

0.03

0.04

0.05

-300 -250 -200 -150 -100 -50 0 50 100 150 200 250 300

Cra

ck-O

pen

ing D

isp

lace

men

t (m

m)

Distance from Center of Continuity Diaphragm (in.)

G7 (Pre-Repair)

G8 (Pre-Repair)

G7 (Post-Repair)

G8 (Post-Repair)

156

Figure 5.4: Crack-opening displacements—pre- and post-repair—C7

-0.05

-0.04

-0.03

-0.02

-0.01

0.00

0.01

0.02

0.03

0.04

0.05

-300 -250 -200 -150 -100 -50 0 50 100 150 200 250 300

Cra

ck-O

pen

ing

Dis

pla

cem

ent

(mm

)

Distance from Center of Continuity Diaphragm (in.)

G7 (Pre-Repair)

G8 (Pre-Repair)

G7 (Post-Repair)

G8 (Post-Repair)

157

Table 5.1: Bearing pad effects—crack-opening displacements

Girder Span

Pre-

or

Post-

Repair

Crack-Opening Displacement

(mm)

– closing

+ opening

A4 A7 C4 C7

7

10 Pre- 0.021 -0.010 0.019 -0.010

Post- 0.024 -0.008 0.022 -0.009

11 Pre- -0.008 0.019 -0.008 0.020

Post- -0.003 0.041 -0.006 0.039

8

10 Pre- -0.003 -0.005 -0.004 -0.008

Post- -0.004 -0.005 -0.005 -0.008

11 Pre- -0.003 0.004 -0.004 0.010

Post- -0.002 0.018 -0.004 0.032

Notes: Measurements presented in bold represent the crack openings with the

greatest difference between pre- and post-repair testing

1 in. = 25.4 mm

The crack-opening displacements measured in Span 10 were similar for both pre- and

post-repair testing, but the crack-opening displacements measured in Span 11 in response

to the Stop Position 7 load condition of the post-repair test increased in comparison to the

crack-opening displacements measured in response to the same load condition during

pre-repair testing. This behavior corresponds with the Span 10 bearing pads being

partially removed prior to pre-repair testing, and the Span 11 bearing pads being under

enough pressure to prevent any removal prior to pre-repair testing. It is apparent that

girder contact with the false support bearing pads under Span 11 resulted in additional

158

support conditions that affected pre-repair measurements. This conclusion is further

supported by the other comparisons that are located in 2017HAppendix K.

Due to the apparent effects that the bearing pads had on the pre-repair tests, direct

comparisons of the pre- and post-repair measured behavior cannot be used to accurately

gauge the effectiveness of the FRP repair. Analysis of the post-repair measurements,

independent of the pre-repair measurements, is required to assess the post-repair behavior

of the overall structure and the FRP reinforcement.

5.3 60BBRIDGE RESPONSE TO TRUCK LOADS—POST-REPAIR

Sensor measurements in response to different load-truck static positions were analyzed to

assess bridge behavior in response to applied gravity loads. These assessments include:

girder-line responses to different horizontal truck alignments, signs of damage exhibited

by sensor measurements, continuity behavior, and linear-elastic behavior of both the

overall structure and the damaged sections.

5.3.1 162BRESPONSE TO DIFFERENT HORIZONTAL TRUCK ALIGNMENTS

The horizontal truck alignments for the two traverse lanes had an effect on the measured

responses. Lane A aligns the west wheels of the east truck with Girder 7 and the east

wheels of the east truck nearly align with Girder 8, while the west truck straddles

Girder 6. Lane C aligns the west wheels of the east truck with Girder 8 while the west

truck straddles Girder 7. These horizontal truck alignments are illustrated in Figures 2018H5.5

and 2019H5.6.

159

Figure 5.5: Lane A—horizontal truck positioning

Figure 5.6: Lane C—horizontal truck positioning

Girder deflections measured in response to trucks positioned at midspan were

analyzed to assess the effects that the two horizontal truck alignments had on the two

instrumented girder lines during load testing. Deflection measurements from midspan

truck positions of post-repair testing are presented in Figures 2020H5.7–2021H5.10 and 2022HTable 5.2.

40.5‖ 96‖

Cast-in-place

concrete barrier

64’ - 0‖

70’ - 9‖

6.5‖

Girder 7 Girder 8

73.5‖ 75‖ 49‖

ST-6538 ST-6400

AASHTO BT-54 Girders

40.5‖ 96‖ AASHTO BT-54 Girders

Cast-in-place

concrete barrier

64’ - 0‖

70’ - 9‖

6.5‖

Girder 7 Girder 8

73.5‖ 75‖ 49‖

ST-6538 ST-6400

160

Figure 5.7: Deflections—A1

Figure 5.8: Deflections—A9

-0.4

-0.3

-0.2

-0.1

0.0

0.1

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er D

efle

ctio

n (

in.)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

-0.4

-0.3

-0.2

-0.1

0.0

0.1

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er D

efle

ctio

n (

in.)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

161

Figure 5.9: Deflections—C1

Figure 5.10: Deflections—C9

-0.4

-0.3

-0.2

-0.1

0.0

0.1

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er D

efle

ctio

n (

in.)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

-0.4

-0.3

-0.2

-0.1

0.0

0.1

-900 -700 -500 -300 -100 100 300 500 700 900

Bo

tto

m-F

iber

Def

lect

ion

(in

.)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

162

Table 5.2: Midspan truck positions—deflections

Girder Span

Location

from

continuity

diaphragm

at

Bent 11

Deflections

(in.)

– downward

+ upward

A1 A9 C1 C9

7

10 midspan -0.32 0.04 -0.29 0.04

quarterspan -0.22 0.04 -0.20 0.03

11 quarterspan 0.04 -0.22 0.04 -0.21

midspan 0.05 -0.33 0.04 -0.31

8

10 midspan -0.26 0.04 -0.35 0.05

quarterspan -0.17 0.03 -0.22 0.04

11 quarterspan 0.04 -0.17 0.04 -0.24

midspan 0.04 -0.25 0.05 -0.35

Note: Measurements presented in bold represent the maximum downward

deflection per sensor location during all post-repair static load tests

The deflections measured while traversing Lane A resulted in greater deflections,

upward and downward, for Girder 7 than for Girder 8. The deflections measured while

traversing Lane C resulted in greater deflections, upward and downward, for Girder 8

than for Girder 7. The difference between deflection measurements for both traverse

lanes was more significant for Girder 8 deflections than for Girder 7 deflections.

The Girder 8 downward deflections at quarterspan and midspan increased by

approximately 30–40 percent when comparing the deflections due to the midspan truck

positions aligned with Lane C to the deflections resulting from the midspan truck

positions aligned with Lane A. Conversely, the Girder 7 downward deflections at

163

quarterspan and midspan increased by only 5–10 percent when comparing the deflections

due to the midspan truck positions aligned with Lane A to the deflections resulting from

the midspan truck positions aligned with Lane C.

Load trucks aligned with Lane A have the greatest effect on Girder 7. Load trucks

aligned with Lane C have the greatest effect on Girder 8. The Girder 8 deflections due to

the Lane C midspan alignments were greater than the Girder 7 deflections due to the

Lane A midspan alignments. Due to producing absolute maximum deflections in

response to truck loads, the Lane C horizontal truck alignment resulted in better overall

results for the analysis of the behavior of the instrumented girders.

5.3.2 163BINDICATIONS OF DAMAGE TO INSTRUMENTED GIRDERS

Crack-opening displacements and bottom-fiber strains measured during acoustic

emissions (AE) testing were analyzed to assess damage indicated by the two spans when

subjected to identical load conditions mirrored about the centerline of the continuity

diaphragm. Information regarding the procedures and truck positions of the post-repair

AE tests is presented in Section 2023H4.5 of this thesis.

Analysis of the post-repair acoustic emissions measurements obtained using the AE

sensors is not within the scope of this thesis. The post-repair AE analysis of the AE

sensor measurements is reported by Hadzor (2011). Crack-opening displacements and

surface strains measured in response to the post-repair AE static positions are presented

graphically in Appendix G and in tabular format in Appendix H of this thesis.

5.3.2.1 4362BCRACK-OPENING DISPLACEMENTS

Crack-opening displacement magnitude in response to a specific load can be considered a

measured indication of the relative degree of damage to a specific cross section. Crack-

164

opening displacement measurements in response to the AE static positions were analyzed

to compare the current amount of damage exhibited by the instrumented girders in

response to the identical AE load conditions applied to both spans. The crack-opening

displacement measurements from the post-repair AE static positions with both trucks in

position can be seen in Figures 2024H5.11–2025H5.14 and 2026HTable 5.3.

Figure 5.11: AE Span 10 truck position—crack-opening displacements—LC-6.5

-0.05

-0.04

-0.03

-0.02

-0.01

0.00

0.01

0.02

0.03

0.04

0.05

-900 -700 -500 -300 -100 100 300 500 700 900

Cra

ck-O

pen

ing D

isp

lace

men

t (m

m)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

165

Figure 5.12: AE Span 11 truck position—crack-opening displacements—LC-6.5

Figure 5.13: AE Span 10 truck position—crack-opening displacements—LC-6

-0.05

-0.04

-0.03

-0.02

-0.01

0.00

0.01

0.02

0.03

0.04

0.05

-900 -700 -500 -300 -100 100 300 500 700 900

Cra

ck-O

pen

ing D

isp

lace

men

t (m

m)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

-0.05

-0.04

-0.03

-0.02

-0.01

0.00

0.01

0.02

0.03

0.04

0.05

-900 -700 -500 -300 -100 100 300 500 700 900

Cra

ck-O

pen

ing D

isp

lace

men

t (m

m)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

166

Figure 5.14: AE Span 11 truck position—crack-opening displacements—LC-6

-0.05

-0.04

-0.03

-0.02

-0.01

0.00

0.01

0.02

0.03

0.04

0.05

-900 -700 -500 -300 -100 100 300 500 700 900

Cra

ck-O

pen

ing D

isp

lace

men

t (m

m)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

167

Table 5.3: AE truck positions—crack-opening displacements

Girder Span

Crack Opening Displacement

(mm)

– closing

+ opening

LC-6.5 LC-6

Span Span

10 11 10 11

7 10 0.024 -0.013 0.023 -0.014

11 -0.021 0.047 -0.021 0.044

8 10 -0.010 -0.010 -0.010 -0.010

11 -0.019 0.038 -0.019 0.040

Notes: Measurements presented in bold represent the maximum crack

opening per gage for the AE truck positions

1 in. = 25.4 mm

A maximum crack opening of 0.047 mm (1.83 x 10-3

in.) was measured by the COD

gage on the east face of Girder 7 in Span 11 in response to the AE Span 11 static position.

A maximum crack closure of 0.021 mm (0.84 x 10-3

in.) was measured by the same COD

gage on the east face of Girder 7 in Span 11 but in response to the Span 10 static position.

The COD gage on the west face of Girder 8 in Span 10 did not measure a crack opening

due to any of the AE static positions.

5.3.2.2 4363BCRACK-OPENING DISPLACEMENT OBSERVATIONS

The crack openings measured on the instrumented girders of Span 11 due to the Span 11

static position were of greater magnitude than the Span 10 crack openings due to the

Span 10 static position. Similarly, the crack closures measured on the instrumented

168

girders of Span 11 due to the Span 10 static position were of greater magnitude than the

Span 10 crack closures due to the Span 11 static position. In response to trucks with

consistent load-block configurations, the maximum range of crack-opening

displacements on an instrumented Span 11 crack was 0.068 mm (2.67 x 10-3

in.)

measured by the COD gage on Girder 7 of Span 11. The maximum range of crack-

opening displacements on an instrumented Span 10 crack was 0.037 mm (1.47 x 10-3

in.)

measured by the COD gage on Girder 7 of Span 10.

The crack-opening displacements measured for the instrumented crack on Girder 8 of

Span 10 exhibited behavior that was inconsistent with the other three instrumented

cracks. Fason (2009) also noted that, during the pre-repair AE static position

measurements, the COD gage installed on the west face of Girder 8 in Span 10 exhibited

different behavior when compared to the other COD gages installed on the east face of

the other instrumented girders. During the pre-repair AE tests, the COD gage on Girder 8

of Span 10 did not exhibit crack openings due to the Span 10 static position, and all other

COD gages did exhibit crack opening due to the static position of their respective span.

Fason reported that the possible reasons for this difference were either due to the failure

to remove all false support bearing pads prior to pre-repair testing or out-of-plane

bending that resulted in different behavior on the west face of the girder than on the east

face.

Even after the successful removal of all bearing pads, the post-repair AE static

position crack-opening displacements for the COD gage of Girder 8 in Span 10 exhibited

behavior similar to the behavior indicated by the pre-repair AE static position

measurements. The COD gage on Girder 8 of Span 10 still did not exhibit a crack

169

opening due to any of the AE static positions, but in response to the Span 11 static

position the COD gage on Girder 8 of Span 10 did exhibit closures similar to those

observed by the COD gage on Girder 7 of Span 10.

Similar behavior measured at the COD gage location on Girder 8 of Span 10 during

both pre- and post-repair AE testing is an indication that the pre-repair crack-opening

displacement behavior measured at this location was related to something other than the

bearing pad under Girder 8 of Span 10 being the only bearing pad completely removed

prior to pre-repair testing. If the complete removal of only one bearing pad is not the

reason for the COD gage on Girder 8 of Span 10 to behave differently, then the gage may

be measuring a response to out-of-plane bending as suggested by Fason (2009).

As stated previously, a lack of significant cracking on the east face of Girder 8 in

Span 10 influenced the decision to install the COD gage on the west face of Girder 8,

which is the opposite girder face compared to the installation of the other three COD

gages. The instrumented crack also did not extend completely through the thickness of

the web, which could influence out-of-plane bending behavior being measured at the

COD gage location. In addition to the potential response to out-of-plane bending, it is

possible that the girder is behaving uniquely simply because it is less damaged than the

other instrumented girders.

5.3.2.3 4364BBOTTOM-FIBER STRAINS

The bottom-fiber strains measured within 105 in. of the centerline of the continuity

diaphragm in response to the post-repair AE static positions were also analyzed to

compare the signs of damage exhibited by each instrumented girder. The bottom-fiber

170

strain measurements from the AE static positions are presented in Figures 2027H5.15–2028H5.18 and

Tables 2029H5.4 and 2030H5.5.

Figure 5.15: AE Span 10 truck position—bottom-fiber strains—LC-6.5

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bo

tto

m-F

iber

Str

ain

(x

10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G8 - Concrete

G7 - FRP

G8 - FRP

171

Figure 5.16: AE Span 11 truck position—bottom-fiber strains—LC-6.5

Figure 5.17: AE Span 10 truck position—bottom-fiber strains—LC-6

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er S

train

(x10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G8 - Concrete

G7 - FRP

G8 - FRP

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er S

train

(x1

0-6

in./

in.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G8 - Concrete

G7 - FRP

G8 - FRP

172

Figure 5.18: AE Span 11 truck position—bottom-fiber strains—LC-6

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er S

train

(x1

0-6

in./

in.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G8 - Concrete

G7 - FRP

G8 - FRP

173

Table 5.4: AE truck positions—bottom-fiber strains—Girder 7

Span

164BDistance

from

center of

continuity

diaphragm

(in.)

– Span 10

+ Span 11

165BLocation

Description

166BBottom-Fiber Strain

(x10-6

in./in.)

– compressive

+ tensile

LC-6.5 LC-6

Span Span

10 11 10 11

10 167B-74 FRP 24 -9 23 -9

168B-47 169BFRP-Crack 96 -70 92 -74

11

170B47 171BFRP-Crack -93 140 -87 130

172B74 173BFRP -11 28 -10 28

174B104 175BFRP -7 30 -8 25

176B105 177BConcrete -10 28 -13 35

178B273 179BConcrete -13 38 -5 38

180B441 181BConcrete -19 30 0 30

182B609 183BConcrete -26 22 6 20

Note: Measurements presented in bold represent the maximum tensile strains

per gage for the AE truck positions

174

Table 5.5: AE truck positions—bottom-fiber strains—Girder 8

Span

184BDistance

from

center of

continuity

diaphragm

(in.)

– Span 10

+ Span 11

185BLocation

Description

186BBottom-Fiber Strain

(x10-6

in./in.)

– compressive

+ tensile

LC-6.5 LC-6

Span Span

10 11 10 11

10

187B-75 Concrete 20 -16 28 -14

188B-74 189BFRP 19 -10 19 -10

190B-41 191BFRP-Crack 117 -125 106 -120

11

192B52 193BFRP-Crack -87 69 -81 71

194B74 195BFRP -21 55 -20 59

196B75 197BConcrete -40 136 -44 148

198B104 199BFRP -13 34 -14 34

200B105 201BConcrete -10 34 -14 34

202B273 203BConcrete -16 49 -6 47

204B441 205BConcrete -22 42 0 41

206B609 207BConcrete 4 24 -7 22

Note: Measurements presented in bold represent the maximum tensile strains

per gage for the AE truck positions

5.3.2.3.1 CONCRETE BEYOND PRIMARY CRACK LOCATIONS

A maximum bottom-fiber concrete tensile strain of 148 x 10-6

in./in. was measured 75 in.

from the center of the continuity diaphragm on Girder 8 of Span 11 due to the Span 11

static truck position. A maximum bottom-fiber concrete compressive strain of

44 x 10-6

in./in. was measured 75 in. from the center of the continuity diaphragm on

Girder 8 of Span 11 in response to the Span 10 static position.

175

5.3.2.3.2 FRP REINFORCEMENT BEYOND PRIMARY CRACK LOCATIONS

Disregarding the FRP reinforcement strain gages assigned to crack locations, a maximum

bottom-fiber FRP reinforcement tensile strain of 59 x 10-6

in./in. was measured 74 in.

from the center of the continuity diaphragm on Girder 8 of Span 11 in response to the

Span 11 static position. A maximum bottom-fiber FRP reinforcement compressive

strain of 21 x 10-6

in./in. was measured 74 in. from the center of the continuity diaphragm

on Girder 8 of Span 11 in response to the Span 10 static position.

5.3.2.3.3 FRP REINFORCEMENT NEAR PRIMARY CRACK LOCATIONS

A maximum bottom-fiber near-crack FRP reinforcement tensile strain of 140 x 10-6

in./in.

was measured 47 in. from the center of the continuity diaphragm at the crack on Girder 7

of Span 11 in response to the Span 11 static position. A maximum bottom-fiber near-

crack FRP reinforcement compressive strain of 125 x 10-6

in./in. was measured 41 in.

from the center of the continuity diaphragm at the crack on Girder 8 of Span 10 in

response to the Span 11 static position.

5.3.2.4 4365BBOTTOM-FIBER STRAIN OBSERVATIONS

In response to the AE static positions, the FRP strain gage installed at the crack location

of Girder 7 in Span 11 measured tensile and compressive strains of greater magnitude

than the strains measured at the gage installed at the crack location of Girder 7 in

Span 10. The FRP strain gage installed at the crack location of Girder 8 in Span 10

measured strains of greater magnitude than the strains measured at the gage installed at

the crack location of Girder 8 in Span 11. The magnitudes of strain measured at the FRP

gage corresponding with the crack location on Girder 8 of Span 11 were not consistent

with the magnitudes of strain measured at the crack locations of the other girders. Also,

176

the concrete strain gage on Girder 8 of Span 11 located 75 in. from the continuity

diaphragm measured tensile strains similar to the tensile strains measured at the FRP

corresponding with the crack locations of the other girders.

When considering the FRP strain measurements representing strains measured at the

crack location, it is possible that the FRP strain gages may have been installed at varying

proximities to the actual cracks. This variation is due to the inability to accurately locate

each crack through the FRP reinforcement during strain gage installation. Based on the

difference between the FRP strain measurements at the crack location on Girder 8 of

Span 11 and the measurements at the other crack locations, it is possible that the FRP

strain gage at the crack location on Girder 8 of Span 11 was installed the least accurately

with respect to the actual crack location.

5.3.2.5 4366BCOD AND BOTTOM-FIBER STRAIN COMPARISONS

Theoretically, the bottom-fiber strain measured at the crack location of a girder should be

related to the crack-opening displacement measured at the instrumented crack of that

same girder. The crack-opening displacements and near-crack bottom-fiber strains

measured during the AE static positions are presented for graphical comparison in

Figures 2031H5.19–2032H5.22.

177

Figure 5.19: COD and bottom-fiber strain comparisons—LC-6.5—AE Span 10

Figure 5.20: COD and bottom-fiber strain comparisons—LC-6.5—AE Span 11

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-0.06

-0.05

-0.04

-0.03

-0.02

-0.01

0.00

0.01

0.02

0.03

0.04

0.05

-400 -300 -200 -100 0 100 200 300 400

Bott

om

-Fib

er S

train

(x1

0-6

in./in

.)

Cra

ck-O

pen

ing D

isp

lace

men

t (m

m)

Distance from Center of Continuity Diaphragm (in)

Girder 7 - COD

Girder 8 - COD

Girder 7 - FRP Strain

Girder 8 - FRP Strain

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-0.06

-0.05

-0.04

-0.03

-0.02

-0.01

0.00

0.01

0.02

0.03

0.04

0.05

-400 -300 -200 -100 0 100 200 300 400

Bo

tto

m-F

iber

Str

ain

(x

10

-6 in

./in

.)

Cra

ck-O

pen

ing

Dis

pla

cem

ent

(mm

)

Distance from Center of Continuity Diaphragm (in)

Girder 7 - COD

Girder 8 - COD

Girder 7 - FRP Strain

Girder 8 - FRP Strain

178

Figure 5.21: COD and bottom-fiber strain comparisons—LC-6—AE Span 10

Figure 5.22: COD and bottom-fiber strain comparisons—LC-6—AE Span 11

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-0.06

-0.05

-0.04

-0.03

-0.02

-0.01

0.00

0.01

0.02

0.03

0.04

0.05

-400 -300 -200 -100 0 100 200 300 400

Bo

tto

m-F

iber

Str

ain

(x

10

-6 in

./in

.)

Cra

ck-O

pen

ing

Dis

pla

cem

ent

(mm

)

Distance from Center of Continuity Diaphragm (in)

Girder 7 - COD

Girder 8 - COD

Girder 7 - FRP Strain

Girder 8 - FRP Strain

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-0.06

-0.05

-0.04

-0.03

-0.02

-0.01

0.00

0.01

0.02

0.03

0.04

0.05

-400 -300 -200 -100 0 100 200 300 400

Bo

tto

m-F

iber

Str

ain

(x

10

-6 in

./in

.)

Cra

ck-O

pen

ing

Dis

pla

cem

ent

(mm

)

Distance from Center of Continuity Diaphragm (in)

Girder 7 - COD

Girder 8 - COD

Girder 7 - FRP Strain

Girder 8 - FRP Strain

179

The COD and near-crack bottom-fiber strain measurements of Girder 8 in Span 10

exhibited contradicting behavior. Crack closure was measured in response to the Span 10

load condition while a near-crack bottom-fiber tensile strain was measured. The tensile

strain measured at the Girder 8-Span 10 near-crack strain gage location was similar to the

tensile strain measured at the Girder 7-Span 10 near-crack strain gage location in

response to the same Span 10 load condition. The difference between the Girder 8-

Span 10 COD gage and the Girder 7-Span 10 COD gage is that the COD gages are

installed on opposite girder faces. The combination of similar bottom-fiber strain

behavior and conflicting crack-opening displacement behavior for the Girder 8-Span 10

COD gage supports the conclusion that out-of-plane bending behavior has an effect on

crack-opening displacements measured during live-load testing—particularly when a

wheel load is placed very close to the girder cross section under investigation.

The crack-opening displacement behavior of Girder 8 in Span 11 was similar to the

bottom-fiber strain behavior at the crack location of the same girder. Tensile strains were

measured when crack-openings were observed, and compressive strains were measured

when crack closures were observed. However, the relationship between the bottom-fiber

strain and crack-opening displacement for Girder 8-Span 11 was not similar to the

relationships observed in Girder 7-Span 11 and Girder 7-Span 10. The bottom-fiber

strain gage on Girder 8 of Span 11 measured less tensile strain relative to a respective

crack opening when compared to the other two girders. In response to the load

conditions resulting in the maximum crack openings for each COD gage, the ratio of

crack opening to the near-crack bottom-fiber FRP strain was 250 mm (10 in.) for

Girder 7-Span 10, 330 mm (13 in.) for Girder 7-Span 11, and 570 mm (22 in.) for

180

Girder 8-Span 11. These three ratios are an indication that the relationship between crack

opening and bottom-fiber tensile strain varies for each damaged region.

One constant for each damaged section is the location of the COD gage within the

height of the girder. The distances from the continuity diaphragm are also similar for the

damaged section COD and bottom-fiber strain gages. Due to the strain gage application

process, one potential difference between each damaged section is the proximity of the

bottom-fiber FRP strain gage to the actual crack location. Ideally the FRP strain gage

would be installed to straddle the underlying crack in the structural concrete, but the

inability to accurately locate cracks underneath the installed FRP reinforcement may have

resulted in strain gages being applied near cracks rather than directly at the crack

location.

Theoretically, the further a strain gage varies from the actual crack location, the more

the tensile strain measured by that strain gage will decrease relative to the measured crack

opening. This is because the gage is in a region where the tension is shared between the

concrete and FRP, rather than carried solely by the FRP. This theoretical behavior

supports the earlier conclusion that the Girder 8-Span 11 near-crack bottom-fiber strain

gage was not installed at the desired crack location as accurately as the bottom-fiber

strain gages installed at the crack locations of Girder 7 in both Spans 10 and 11.

5.3.2.6 4367BDAMAGE INDICATION CONCLUSIONS

Crack-openings and bottom-fiber tension strains measured in response to AE static

positions are indications of damage exhibited by the instrumented girders. The

relationships between crack-opening displacement and near-crack bottom-fiber strain

supports the conclusion that the installation of the Girder 8-Span 10 COD gage on the

181

opposite face of the girder compared to the other COD gages has an effect on the COD

measurements, which is likely attributable to out-of-plane bending as suggested by

Fason (2009). These relationships also support the conclusion that the near-crack

bottom-fiber strain gage of Girder 8-Span 11 was not accurately installed at the location

of the underlying crack.

5.3.3 208BPOST-REPAIR CONTINUITY BEHAVIOR ASSESSMENT

Deflections, bottom-fiber strains, and crack-opening displacements were analyzed in

response to multiposition load testing to assess the post-repair continuity behavior of the

bridge structure. During this continuity assessment, sensor measurements were analyzed

in response to live-load static positions at different specified distances from the continuity

diaphragm. Details regarding the different truck position locations are given in

Section 2033H4.4. Post-repair deflections, bottom-fiber strains, and crack-opening

displacements measured in response to the eighteen multiposition load test truck

positions (A1–A9 and C1–C9) are presented graphically in 2034HAppendix B and in tabular

format in 2035HAppendix C of this thesis.

Sensor measurements were also compared to responses predicted using an FEM

model of the bridge structure, which was modeled as a continuous structure with an

internal hinge representing a primary crack location. Structural responses to four load

truck positions (A7, A9, C7, and C9) were predicted using an FEM model of the post-

repair bridge structure. Graphical presentations of the predicted responses are presented

by Shapiro (2007).

182

5.3.3.1 4368BDEFLECTIONS

Deflections measured during post-repair multiposition load testing exhibit continuous

behavior for the bridge structure. This behavior is evident due to the upward deflections

measured within the non-loaded span. The maximum deflections were measured in

response to the midspan load conditions. The deflections measured in response to load

trucks traversing Lanes A and C and stopping at the midspan stop positions

(Stop Positions 1 and 9) are presented graphically in Figures 2036H5.23–2037H5.26. The summary of

deflection measurements due to the midspan static positions is presented in Table 2038H5.6.

Figure 5.23: Deflections—A1

-0.4

-0.3

-0.2

-0.1

0.0

0.1

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er D

efle

ctio

n (

in.)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

183

Figure 5.24: Deflections—A9

Figure 5.25: Deflections—C1

-0.4

-0.3

-0.2

-0.1

0.0

0.1

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er D

efle

ctio

n (

in.)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

-0.4

-0.3

-0.2

-0.1

0.0

0.1

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er D

efle

ctio

n (

in.)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

184

Figure 5.26: Deflections—C9

-0.4

-0.3

-0.2

-0.1

0.0

0.1

-900 -700 -500 -300 -100 100 300 500 700 900

Bo

tto

m-F

iber

Def

lect

ion

(in

.)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

185

Table 5.6: Midspan truck positions—deflections

Girder Span

Location

from

continuity

diaphragm

at

Bent 11

Deflections

(in.)

– downward

+ upward

A1 A9 C1 C9

7

10 midspan -0.32 0.04 -0.29 0.04

quarterspan -0.22 0.04 -0.20 0.03

11 quarterspan 0.04 -0.22 0.04 -0.21

midspan 0.05 -0.33 0.04 -0.31

8

10 midspan -0.26 0.04 -0.35 0.05

quarterspan -0.17 0.03 -0.22 0.04

11 quarterspan 0.04 -0.17 0.04 -0.24

midspan 0.04 -0.25 0.05 -0.35

Note: Measurements presented in bold represent the maximum downward

deflection per sensor location during the post-repair multiposition

load tests

The Span 10 midspan load condition (Stop Position 1) caused downward deflections

at Span 10 (loaded span) deflectometer locations, and upward deflections at Span 11

(non-loaded span) deflectometer locations. Similarly, the Span 11 midspan load

condition (Stop Position 9) caused downward deflections in Span 11 and upward

deflections in Span 10.

A maximum downward deflection of 0.35 in. was measured at the midspan location

of Span 11 due to the Span 11 midspan load condition. A maximum upward deflection

of 0.05 in. was measured at three different locations due to separate load conditions. The

upward deflections due to live loads are an indicator that partial continuity has been

preserved.

186

The continuous behavior indicated by the post-repair deflection measurements was

compared to the predicted behavior of the FEM model provided by Shapiro (2007). The

post-repair model was constructed to be a continuous structure with an internal hinge

representing the typical crack location observed on damaged BT-54 girders of I-565.

Comparisons between the measured and predicted behavior are illustrated in Figures 2039H5.27

and 2040H5.28.

Figure 5.27: Deflections—post-repair—measurements and predictions—A9

-0.40

-0.35

-0.30

-0.25

-0.20

-0.15

-0.10

-0.05

0.00

0.05

0.10

-800 -600 -400 -200 0 200 400 600 800

Bott

om

-Fib

er D

efle

ctio

n (

in.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Measured

G8 - Measured

G7 Model - Post-Repair

G8 Model - Post-Repair

187

Figure 5.28: Deflections—post-repair—measurements and predictions—C9

Post-repair deflection measurements are an indication that the modeled post-repair

structure exhibits more apparent stiffness and continuity than the actual post-repair

structure. The downward deflections measured in the loaded span were greater than the

downward deflections predicted. The upward deflections measured in the non-loaded

span were less than the upward deflections predicted.

Although the upward deflections measured during the post-repair static load test are

signs of continuity, it is evident that the structure is no longer behaving fully continuous

under live loads. The damaged sections have an effect on the bridge behavior that, when

modeling the structure, could not be accurately accounted for with a seam acting as an

internal hinge. The post-repair structure exhibits less continuity behavior in response to

-0.40

-0.35

-0.30

-0.25

-0.20

-0.15

-0.10

-0.05

0.00

0.05

0.10

-800 -600 -400 -200 0 200 400 600 800

Bott

om

-Fib

er D

efle

ctio

n (

in.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Measured

G8 - Measured

G7 Model - Post-Repair

G8 Model - Post-Repair

188

live loads than indicated by the post-repair FEM model, which was already modeled to be

less continuous than originally constructed.

5.3.3.2 4369BBOTTOM-FIBER STRAINS

Bottom-fiber compressive strains measured near the continuity diaphragm in response to

live loads are an indicator of continuous behavior. Maximum measured compressive

strains were located at the FRP reinforcement near crack locations in response to midspan

load conditions. Bottom-fiber strains measured in response to midspan load conditions of

Lanes A and C are presented graphically in Figures 2041H5.29–2042H5.32. The summary of bottom-

fiber strains measured in response to midspan load conditions is presented in Tables 2043H5.7

and 2044H5.8.

Figure 5.29: Bottom-fiber strain—A1

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bo

tto

m-F

iber

Str

ain

(x

10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G8 - Concrete

G7 - FRP

G8 - FRP

189

Figure 5.30: Bottom-fiber strain—A9

Figure 5.31: Bottom-fiber strain—C1

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er S

train

(x10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G8 - Concrete

G7 - FRP

G8 - FRP

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bo

tto

m-F

iber

Str

ain

(x

10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G8 - Concrete

G7 - FRP

G8 - FRP

190

Figure 5.32: Bottom-fiber strain—C9

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bo

tto

m-F

iber

Str

ain

(x

10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G8 - Concrete

G7 - FRP

G8 - FRP

191

Table 5.7: Midspan truck positions—bottom-fiber strains—Girder 7

Span

209BDistance

from

center of

continuity

diaphragm

(in.)

– Span 10

+ Span 11

210BLocation

Description

211BBottom-Fiber Strain

(x10-6

in./in.)

– compressive

+ tensile

A1 A9 C1 C9

10 212B-74 FRP 213B-9 214B-19 215B-6 216B-17

217B-47 218BFRP-Crack 219B-87 220B-132 221B-67 222B-122

11

223B47 224BFRP-Crack 225B-148 226B-93 227B-132 228B-82

229B74 230BFRP 231B-21 232B-9 233B-18 234B-8

235B104 236BFRP 237B-18 238B-5 239B-16 240B-4

241B105 242BConcrete 243B-20 244B-5 245B-17 246B-4

247B273 248BConcrete 249B-19 250B35 251B-18 252B34

253B441 254BConcrete 255B-14 256B75 257B-12 258B71

259B609 260BConcrete 261B-8 262B75 263B-9 264B105

Note: Measurements presented in bold represent the maximum compressive strains

per gage for the multiposition load test truck positions

192

Table 5.8: Midspan truck positions—bottom-fiber strains—Girder 8

Span

265BDistance

from

center of

continuity

diaphragm

(in.)

– Span 10

+ Span 11

266BLocation

Description

267BBottom-Fiber Strain

(x10-6

in./in.)

– compressive

+ tensile

A1 A9 C1 C9

10

268B-75 Concrete -11 269B-17 -15 270B-27

271B-74 272BFRP 273B-4 274B-11 275B-10 276B-17

277B-41 278BFRP-Crack 279B-104 280B-139 281B-165 282B-222

11

283B52 284BFRP-Crack 285B-65 286B-44 287B-100 288B-67

289B74 290BFRP 291B-23 292B-6 293B-31 294B-13

295B75 296BConcrete 297B-39 298B-7 299B-56 300B-23

301B104 302BFRP 303B-20 304B-4 305B-29 306B-12

307B105 308BConcrete 309B-18 310B-5 311B-26 312B-11

313B273 314BConcrete 315B-15 316B26 317B-20 318B38

319B441 320BConcrete 321B-11 322B61 323B-16 324B87

325B609 326BConcrete 327B-8 328B75 329B-10 330B113

Note: Measurements presented in bold represent the maximum compressive strains

per gage for the post-repair multiposition load test truck positions

193

The maximum bottom-fiber compressive strain measured during the post-repair static

load test was 222 x 10-6

in./in. at the FRP reinforcement near the crack location of

Girder 8 in Span 10 due to the Lane C midspan static position of Span 11. This bottom-

fiber compressive response in the non-loaded span is a sign of continuous behavior.

Bottom-fiber tensile strains measured near the continuity diaphragm that are of

greater magnitude than tensile strains measured further from the continuity diaphragm are

an indicator that the structure is not behaving as a fully continuous structure for live loads

as originally constructed. The local behaviors of the damaged sections have an effect on

the continuity of the bridge structure. The maximum bottom-fiber tensile strains were

measured near the crack-locations in response to the positioning of loads near the

damaged regions, which resulted in significant shear demand within the damaged region

and positive bending moment at respective bottom-fiber crack locations. Bottom-fiber

strains measured in response to four load conditions (A4, A7, C4, and C7) positioning

trucks near the damaged regions are presented in Figures 2045H5.33–2046H5.36. The summary of

bottom-fiber strains measured in response to these load conditions with trucks near the

damaged sections is presented in Tables 2047H5.9 and 2048H5.10

194

Figure 5.33: Bottom-fiber strain—A4

Figure 5.34: Bottom-fiber strain—A7

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er S

train

(x10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G8 - Concrete

G7 - FRP

G8 - FRP

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er S

train

(x10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G8 - Concrete

G7 - FRP

G8 - FRP

195

Figure 5.35: Bottom-fiber strain—C4

Figure 5.36: Bottom-fiber strain—C7

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er S

train

(x10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G8 - Concrete

G7 - FRP

G8 - FRP

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er S

train

(x10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G8 - Concrete

G7 - FRP

G8 - FRP

196

Table 5.9: Damaged region truck positions—bottom-fiber strains—Girder 7

Span

331BDistance

from

center of

continuity

diaphragm

(in.)

– Span 10

+ Span 11

332BLocation

Description

333BBottom-Fiber Strain

(x10-6

in./in.)

– compressive

+ tensile

A4 A7 C4 C7

10 334B-74 FRP 23 -9 22 -8

335B-47 336BFRP-Crack 108 -60 95 -60

11

337B47 338BFRP-Crack -25 128 -34 116

339B74 340BFRP 0 28 -2 25

341B104 342BFRP 2 29 0 27

343B105 344BConcrete 3 32 1 28

345B273 346BConcrete 4 42 3 37

347B441 348BConcrete 4 36 2 31

349B609 350BConcrete 1 16 3 24

Note: Measurements presented in bold represent the maximum tensile strains

per gage for the post-repair multiposition load test truck positions

197

Table 5.10: Damaged region truck positions—bottom-fiber strains—Girder 8

Span

351BDistance

from

center of

continuity

diaphragm

(in.)

– Span 10

+ Span 11

352BLocation

Description

353BBottom-Fiber Strain

(x10-6

in./in.)

– compressive

+ tensile

A4 A7 C4 C7

10

354B-75 Concrete 13 -9 23 -14

355B-74 356BFRP 10 -6 16 -9

357B-41 358BFRP-Crack 53 -71 113 -108

11

359B52 360BFRP-Crack -17 27 -30 56

361B74 362BFRP -4 58 -4 121

363B75 364BConcrete -1 25 -2 52

365B104 366BFRP 1 20 1 32

367B105 368BConcrete 1 22 1 32

369B273 370BConcrete 3 28 7 46

371B441 372BConcrete 2 27 3 39

373B609 374BConcrete 1 16 2 24

Note: Measurements presented in bold represent the maximum tensile strains

per gage for the post-repair multiposition load test truck positions

198

The maximum bottom-fiber tensile strain measured in response to the eighteen post-

repair traversing-load-test truck positions was 128 x 10-6

in./in. near the crack location

47 in. from the continuity diaphragm along Girder 7 of Span 11 in response to trucks

aligned with Lane A and positioned near the damaged section (A7). A bottom-fiber

tensile strain of 28 x 10-6

in./in. was measured 74 in. from the continuity diaphragm along

the same girder and in response to the same load condition. This bottom-fiber tensile

response near the continuity diaphragm is a sign of local behavior that decreases the

overall continuity of the bridge structure.

Measured bottom-fiber strains have also been compared to strains predicted by the

post-repair model provided by Shapiro. The comparisons between measured and

predicted bottom-fiber strains are illustrated in Figures 2049H5.37–2050H5.40.

Figure 5.37: Bottom-fiber strain—post-repair—measurements and predictions—A7

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-100 0 100 200 300 400 500 600 700

Bo

tto

m-F

iber

Str

ain

(x

10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 Concrete - Measured

G8 Concrete - Measured

G7 FRP - Measured

G8 FRP - Measured

G7 Model - Post-Repair

G8 Model - Post-Repair

199

Figure 5.38: Bottom-fiber strain—post-repair—measurements and predictions—A9

Figure 5.39: Bottom-fiber strain—post-repair—measurements and predictions—C7

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-100 0 100 200 300 400 500 600 700

Bo

tto

m-F

iber

Str

ain

(x

10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 Concrete - Measured

G8 Concrete - Measured

G7 FRP - Measured

G8 FRP - Measured

G7 Model - Post-Repair

G8 Model - Post-Repair

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-100 0 100 200 300 400 500 600 700

Bo

tto

m-F

iber

Str

ain

(x

10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 Concrete - Measured

G8 Concrete - Measured

G7 FRP - Measured

G8 FRP - Measured

G7 Model - Post-Repair

G8 Model - Post-Repair

200

Figure 5.40: Bottom-fiber strain—post-repair—measurements and predictions—C9

Bottom-fiber strains measured beyond the damaged regions were similar to the

predicted strains, but they were slightly more tensile. This is an indicator that the bridge

structure is behaving continuously, but with slightly less apparent stiffness than modeled.

The measured bottom-fiber strains near the damaged region were not similar to the

predicted strains. When the trucks were positioned near the damaged regions of Span 11,

the bottom-fiber strains measured near the crack locations of Span 11 were more tensile

than predicted. When the trucks were positioned near midspan of Span 11, the bottom-

fiber strains measured near the crack locations of Span 10 were more compressive than

predicted.

Although bottom-fiber strains measured during the post-repair static load test exhibit

some continuity, it is evident that the structure is no longer behaving as if fully

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-100 0 100 200 300 400 500 600 700

Bo

tto

m-F

iber

Str

ain

(x

10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 Concrete - Measured

G8 Concrete - Measured

G7 FRP - Measured

G8 FRP - Measured

G7 Model - Post-Repair

G8 Model - Post-Repair

201

continuous for post-construction loads. The damaged sections have an effect on the

bridge behavior that could not be accurately modeled. This damaged section behavior

results in the instrumented girders exhibiting less apparent stiffness than assumed by the

post-repair FEM model developed by Shapiro (2007).

5.3.3.3 4370BCRACK BEHAVIOR

Crack closures measured near the continuity diaphragm, particularly within a non-loaded

span, are an indicator of continuous behavior. The maximum post-repair crack closures

were measured in response to the midspan load conditions. Crack-opening displacements

measured in response to four midspan load conditions (A1, C1, A9 and C9) are presented

graphically in Figures 2051H5.41–2052H5.44. The summary of crack-opening displacements

measured in response to the four midspan load conditions is presented in 2053HTable 5.11.

Figure 5.41: Midspan truck positions—crack-opening displacements—A1

-0.05

-0.04

-0.03

-0.02

-0.01

0.00

0.01

0.02

0.03

0.04

0.05

-900 -700 -500 -300 -100 100 300 500 700 900

Cra

ck-O

pen

ing D

isp

lace

men

t (m

m)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

202

Figure 5.42: Midspan truck positions—crack-opening displacements—A9

Figure 5.43: Midspan truck positions—crack-opening displacements—C1

-0.05

-0.04

-0.03

-0.02

-0.01

0.00

0.01

0.02

0.03

0.04

0.05

-900 -700 -500 -300 -100 100 300 500 700 900

Cra

ck-O

pen

ing D

isp

lace

men

t (m

m)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

-0.05

-0.04

-0.03

-0.02

-0.01

0.00

0.01

0.02

0.03

0.04

0.05

-900 -700 -500 -300 -100 100 300 500 700 900

Cra

ck-O

pen

ing

Dis

pla

cem

ent

(mm

)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

203

Figure 5.44: Midspan truck positions—crack-opening displacements—C9

Table 5.11: Midspan truck positions—maximum crack closures

Girder Span

Crack-Opening Displacement

(mm)

– closing

+ opening

A1 A9 C1 C9

7 10 -0.008 -0.016 -0.003 -0.017

11 -0.027 -0.014 -0.025 -0.008

8 10 -0.011 -0.009 -0.016 -0.015

11 -0.013 -0.005 -0.020 -0.007

Notes: Measurements presented in bold represent the maximum crack closure

per gage measured during the post-repair multiposition load tests

1 in. = 25.4 mm

-0.05

-0.04

-0.03

-0.02

-0.01

0.00

0.01

0.02

0.03

0.04

0.05

-900 -700 -500 -300 -100 100 300 500 700 900

Cra

ck-O

pen

ing D

isp

lace

men

t (m

m)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

204

Crack closures were measured at all of the COD gage locations in response to all four

midspan truck positions of the post-repair traversing load test. The maximum crack

closure measured during the post-repair traversing load test was 0.027 mm

(1.08 x 10-3

in.) at the crack location of Girder 7 in Span 11 in response to the Lane A

midspan load condition of Span 10 (A1). The maximum crack closure of Span 10 was

0.017 mm (0.65 x 10-3

in.) at the crack location of Girder 7 in response to the Lane C

midspan load condition of Span 11 (C9). Crack closures measured at damaged regions of

both spans in response to midspan truck positions are signs of continuous behavior being

partially preserved as well as decreased local apparent stiffness.

Midspan load conditions were the only load conditions of the post-repair static load

test that did not result in the measurement of at least one crack opening. Maximum crack

openings were measured in response to truck positions near gaged crack locations, which

are the truck positions that cause the greatest shear demand within the damaged region.

Crack-opening displacements measured in response to load trucks positioned near gaged

damaged regions are presented graphically in Figures 2054H5.45–2055H5.48. The summary of crack-

opening displacements measured in response to load trucks positioned near gaged

damaged regions is presented in 2056HTable 5.12.

205

Figure 5.45: Damaged region truck positions—crack-opening displacements—A4

Figure 5.46: Damaged region truck positions—crack-opening displacements—A7

-0.05

-0.04

-0.03

-0.02

-0.01

0.00

0.01

0.02

0.03

0.04

0.05

-900 -700 -500 -300 -100 100 300 500 700 900

Cra

ck-O

pen

ing D

isp

lace

men

t (m

m)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

-0.05

-0.04

-0.03

-0.02

-0.01

0.00

0.01

0.02

0.03

0.04

0.05

-900 -700 -500 -300 -100 100 300 500 700 900

Cra

ck-O

pen

ing D

isp

lace

men

t (m

m)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

206

Figure 5.47: Damaged section truck positions—crack-opening displacements—C4

Figure 5.48: Damaged region truck positions—crack-opening displacements—C7

-0.05

-0.04

-0.03

-0.02

-0.01

0.00

0.01

0.02

0.03

0.04

0.05

-900 -700 -500 -300 -100 100 300 500 700 900

Cra

ck-O

pen

ing D

isp

lace

men

t (m

m)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

-0.05

-0.04

-0.03

-0.02

-0.01

0.00

0.01

0.02

0.03

0.04

0.05

-900 -700 -500 -300 -100 100 300 500 700 900

Cra

ck-O

pen

ing D

isp

lace

men

t (m

m)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

207

Table 5.12: Damaged region truck positions—maximum crack openings

Girder Span

Crack-Opening Displacement

(mm)

– closing

+ opening

A4 A7 C4 C7

7 10 0.024 -0.008 0.022 -0.009

11 -0.003 0.041 -0.006 0.039

8 10 -0.004 -0.005 -0.005 -0.008

11 -0.002 0.018 -0.004 0.032

Notes: Measurements presented in bold represent the maximum crack opening

measured per gage during the post-repair multiposition load tests

1 in. = 25.4 mm

The maximum crack opening measured during the post-repair traversing load test was

0.041 mm (1.62 x 10-3

in.) at the crack location of Girder 7 in Span 11 in response to the

Lane A load condition with trucks near the Span 11 damaged sections (A7). The

maximum Span 10 crack opening measured was 0.024 mm (0.95 x 10-3

in.) at the crack

location of Girder 7 in Span 10 in response to the Lane A load condition with trucks near

the Span 10 damaged sections (A4). Crack openings measured within a loaded span are

also signs of decreased apparent stiffness within damaged regions.

The COD gage installed on the west face of Girder 8 in Span 10 did not measure a

crack opening in response to any of the traversing-load-test stop positions. For the COD

gage of Girder 8 in Span 10, the maximum crack opening (least crack closure) measured

during the traversing load test was a closure of 0.002 mm (0.07 x 10-3

in.) in response to

trucks being aligned with Lane C and positioned near the continuity diaphragm (C5).

208

As stated previously, the COD gage on Girder 8 in Span 10 was installed on the

opposite face of the girder compared to the other COD gages and likely does not

accurately represent behavior similar to what is being measured by the other COD gages.

This different behavior for the crack-opening displacement measurements of Girder 8 in

Span 10 is likely due to out-of-plane bending as noted by Fason (2009).

Regardless of the cause of behavior for the COD gage on Girder 8 of Span 10, the

crack-opening displacements measured at the other three crack locations are indications

that the bridge structure is exhibiting overall continuous behavior that cannot be

considered fully continuous for post-construction loads due to the local behavior of

damaged regions.

5.3.3.4 4371BCONTINUITY BEHAVIOR CONCLUSIONS

Upward deflections of non-loaded spans during post-repair testing are indications that

continuity in response to post-construction loads has been partially preserved for the

bridge structure. However, further analysis of post-repair deflection measurements and

model predictions has provided evidence that the structure is behaving less continuously

in response to post-construction loads than assumed by the post-repair FEM model,

which was already modeled to be less continuous than originally constructed.

Compressive strains measured within non-loaded spans during post-repair testing are

additional indications that continuity is partially preserved for the bridge structure.

However, tensile strains measured near the continuity diaphragm in loaded spans are

additional indications that the structure is not behaving as a fully continuous structure in

response to live loads as originally constructed.

209

Crack closures measured within non-loaded spans during post-repair testing are

additional indications that continuity has been partially preserved for the bridge structure.

However, crack openings measured within loaded spans are additional indications that

the structure is not behaving as a fully continuous structure in response to live loads as

originally constructed.

Based on the behaviors observed within damaged regions as well as the decrease in

apparent stiffness and continuity compared to the post-repair FEM model, it is

appropriate to assume that increased damage may further reduce the apparent stiffness

and continuity behavior of the bridge structure. It is recommended to assume complete

degradation of continuity in response to strength-limit-state demands. Thus, an

assumption of simply supported girder behavior is recommended for the design of repair

solutions for bridge structures containing girders with damage at continuous ends.

Decreased continuity behavior will decrease the shear demand, but will also decrease the

shear resistance provided by negative bending moments.

5.3.4 375BLINEAR-ELASTIC BEHAVIOR

Superposition test measurements were analyzed to assess if the bridge structure is

exhibiting linear-elastic behavior. During analysis, general behavior of the bridge

structure and local behavior of the damaged sections were considered. Bridge responses

were measured while two load-test trucks were independently positioned at midspan

locations of both spans. Bridge responses were also measured while the load-test trucks

were simultaneously positioned at those same respective locations. More details

regarding superposition test procedures are given in Section 2057H4.8 of this thesis.

210

Theoretically, a structure exhibits linear-elastic behavior if the sum of the measured

responses representing both trucks at their respective positions independently is equal to

the actual measured response representing both trucks at their respective positions

simultaneously. The measurements for the post-repair superposition test can be found

presented graphically in 2058HAppendix G and in a tabular format in 2059HAppendix H of this thesis.

5.3.4.1 4372BLINEAR-ELASTIC BEHAVIOR ASSESSMENT—TWO-SPAN STRUCTURE

Deflections measured during the post-repair superposition test were analyzed to assess

the general behavior of the bridge structure. The predicted and measured superposition

deflections are illustrated in 2060HFigure 5.49. The differences between the predicted and

measured superposition deflections are presented in 2061HTable 5.13.

Figure 5.49: Superposition—deflections—predicted and measured

-0.20

-0.15

-0.10

-0.05

0.00

0.05

-800 -600 -400 -200 0 200 400 600 800

Bott

om

-Fib

er D

efle

ctio

n (

in.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Predicted

G8 - Predicted

G7 - Measured

G8 - Measured

211

Table 5.13: Superposition—deflections

Girder Span

Location

from

Bent 11

Superposition

Deflections

(in.)

– downward

+ upward

Difference

(Pred.–Meas.)

Predicted

(A1 + A9)

Measured

(A1 & A9) in. %

7

10 midspan 376B-0.16 377B-0.16 378B0.00 379B0

quarterspan 380B-0.12 381B-0.11 382B-0.01 383B-9

11 quarterspan 384B-0.11 385B-0.10 386B-0.01 387B-10

midspan 388B-0.17 389B-0.16 390B-0.01 391B-6

8

10 midspan 392B-0.16 393B-0.15 394B-0.01 395B-7

quarterspan 396B-0.10 397B-0.09 398B-0.01 399B-10

11 quarterspan 400B-0.11 401B-0.10 402B-0.01 403B-10

midspan 404B-0.16 405B-0.15 406B-0.01 407B-7

Note: Percent difference is reported as a percentage of the measured superposition

The superposition deflection measurements from the post-repair test were consistent

for all sensor locations. The actual simultaneously positioned load condition resulted in

downward deflections for all sensors that were of less magnitude than the summation of

the deflections measured in response to the trucks positioned independently. The average

difference was approximately 0.01 in. and the average percentage difference from the

measured superposition was less than 10 percent. These relatively small differences

between measured and predicted deflections are an indication that overall the bridge

structure exhibited nearly linear-elastic behavior during the post-repair superposition test.

212

5.3.4.2 4373BLINEAR-ELASTIC BEHAVIOR ASSESSMENT—DAMAGED REGIONS

Crack-opening displacements and bottom-fiber strains measured during the post-repair

superposition test were analyzed to assess the local behavior of the damaged regions.

Damaged region behavior can be assessed by analyzing the crack-opening displacement

behavior in response to the superposition test. Cracked region behavior can be also be

assessed by comparing near-crack bottom-fiber strain behavior to bottom-fiber strain

behavior observed further from the primary crack location. The relationship between

near-crack bottom-fiber strain behavior and crack-opening displacement behavior can

also be analyzed to further support conclusions regarding the behavior of the damaged

regions and previously stated conclusions regarding damage comparisons and continuity

behavior.

5.3.4.2.1 CRACK-OPENING DISPLACEMENTS

The predicted and measured superposition crack-opening displacements are illustrated in

2062HFigure 5.50. The differences between the predicted and measured superposition crack-

opening displacements are presented in 2063HTable 5.14.

213

Figure 5.50: Superposition—crack-opening displacements—predicted and measured

Table 5.14: Superposition—maximum crack closures

Girder Span

Superposition

Crack-Opening Displacement

(mm)

– closing

+ opening

Difference

(Pred.–Meas.)

Predicted

(A1 + A9)

Measured

(A1 & A9) mm %

7 10 408B-0.011 409B-0.014 410B0.003 411B21

11 412B-0.018 413B-0.024 414B0.006 415B25

8 10 416B-0.014 417B-0.015 418B0.001 419B7

11 420B-0.010 421B-0.012 422B0.002 423B17

Notes: Percent difference is reported as a percentage of the measured superposition

1 in. = 25.4 mm

-0.03

-0.02

-0.01

0.00

0.01

0.02

-100 -80 -60 -40 -20 0 20 40 60 80 100

Cra

ck-O

pen

ing

Dis

pla

cem

ent

(mm

)

Distance from Center of Continuity Diaphragm (in.)

G7 - Predicted

G8 - Predicted

G7 - Measured

G8 - Measured

214

Each instrumented crack experienced closure due to all of the superposition-test load

conditions. The crack closures measured in response to the combined load condition

(A1 and A9) were greater in magnitude than the crack closures predicted by

superposition (A1 + A9). The maximum difference between the measured and predicted

superposition crack closures was 0.006 mm (0.27 x 10-3

in.) at the crack on the east face

of Girder 7 in Span 11. This difference resulted in a percentage difference from the

measured superposition of 25 percent. The average difference between the measured and

predicted crack closures for all four crack locations was 0.003 mm (0.14 x 10-3

in.), and

the average percentage difference was 18 percent of the measured result.

The magnitudes of the differences and percentage differences between measured and

predicted crack closures during the post-repair superposition test indicate that the

principle of superposition is not valid in the cracked regions. Therefore, crack locations

are exhibiting nonlinear behavior. As previously noted, the location of the COD gage on

Girder 8-Span 10 likely had an effect on the crack-opening displacement measurements

making this gage less reliable for comparison. The damaged region of Girder 7 in Span

11 exhibited the apparent least linear behavior. The damaged region of Girder 8 in Span

10 exhibited the most apparent linear behavior. These varying degrees of linear behavior

can be related to varying degrees of damage within each girder.

Nonlinear behavior exhibited by measured crack closures is possibly associated with

the presence of multiple cracks surrounding the instrumented crack locations. Load

conditions that result in closure of a gaged crack will likely also result in closure of

smaller neighboring cracks. As smaller neighboring cracks close, the local cross-

sectional area of the concrete effectively transmitting compression is increased. Due to

215

the increased local effective compression zone, the application of additional loads that

would result in closure of a gaged crack, if applied independently, will result in additional

crack closure of greater magnitude than the closure in response to the independent load

condition. This neighboring crack closure explanation, as the possible cause of nonlinear

behavior, is supported by the observation that the trucks positioned simultaneously

produced crack closures that were measured to be of greater magnitude than the

summation of the measured crack closures in response to the trucks positioned

independently.

5.3.4.2.2 BOTTOM-FIBER STRAINS

The predicted and measured superposition bottom-fiber strain measurements are

presented in 2064HFigure 5.51. The differences between the predicted and measured

superposition bottom-fiber strain measurements are presented in Tables 2065H5.15 and 2066H5.16.

216

Figure 5.51: Superposition—bottom-fiber strains—predicted and measured

-210

-180

-150

-120

-90

-60

-30

0

30

60

90

-100 0 100 200 300 400 500 600 700 800

Bo

tto

m-F

iber

Str

ain

(x1

0-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Predicted

G8 - Predicted

G7 - Measured

G8 - Measured

217

Table 5.15: Superposition—bottom-fiber strains—Girder 7

Span

424BDistance

from

center of

continuity

diaphragm

(in.)

– Span 10

+ Span 11

425BLocation

Description

426BSuperposition

427BBottom-Fiber Strain

(x10-6

in./in.)

– compressive

+ tensile

Difference

(Pred.–Meas.)

Predicted

(A1 + A9)

Measured

(A1 & A9)

x10-6

in./in. %

10 428B-74 FRP 429B-10 430B-17 431B7 432B41

433B-47 434BFRP-Crack 435B-94 436B-134 437B40 438B30

11

439B47 440BFRP-Crack 441B-107 442B-149 443B42 444B28

445B74 446BFRP 447B-13 448B-19 449B6 450B32

451B104 452BFRP 453B-8 454B-14 455B6 456B40

457B105 458BConcrete 459B-12 460B-17 461B5 462B29

463B273 464BConcrete 465B11 466B7 467B4 468B60

469B441 470BConcrete 471B35 472B34 473B1 474B3

475B609 476BConcrete 477B60 478B60 479B0 480B0

Note: Percent difference is reported as a percentage of the measured superposition

218

Table 5.16: Superposition—bottom-fiber strains—Girder 8

Span

481BDistance

from

center of

continuity

diaphragm

(in.)

– Span 10

+ Span 11

482BLocation

Description

483BSuperposition

484BBottom-Fiber Strain

(x10-6

in./in.)

– compressive

+ tensile

Difference

(Pred.–Meas.)

Predicted

(A1 + A9)

Measured

(A1 & A9)

x10-6

in./in. %

10

485B-75 Concrete 486B-18 487B-24 488B6 489B25

490B-74 491BFRP 492B-11 493B-15 494B4 495B27

496B-41 497BFRP-Crack 498B-166 499B-204 500B38 501B19

11

502B52 503BFRP-Crack 504B-73 505B-85 506B12 507B14

508B74 509BFRP 510B-16 511B-24 512B8 513B33

514B75 515BConcrete 516B-30 517B-41 518B11 519B27

520B104 521BFRP 522B-13 523B-19 524B6 525B32

526B105 527BConcrete 528B-15 529B-20 530B5 531B25

532B273 533BConcrete 534B10 535B7 536B3 537B40

538B441 539BConcrete 540B37 541B36 542B1 543B3

544B609 545BConcrete 546B52 547B50 548B2 549B4

Note: Percent difference is reported as a percentage of the measured superposition

219

All of the bottom-fiber strain gages measured compressive strains in response to the

individual Span 10 load condition (A1 east). In response to the individual Span 11 load

condition (A9 east), the bottom-fiber gages within 8 ft from the face of the continuity

diaphragm measured compressive strains, and the remaining strain gages out to midspan

measured tensile strains. The maximum compressive strains were measured by the

bottom-fiber strain gages installed on the FRP at the assumed underlying crack location

on each girder.

The maximum compressive strain measured in response to the superposition-test

Span 10 truck position (A1) was 73 x 10-6

in./in. at the strain gage installed on the FRP

corresponding with the primary crack location of Girder 8 in Span 10. The maximum

compressive strain measured in response to the Span 11 truck position (A9) was

93 x 10-6

in./in. at the same crack location strain gage of Girder 8 in Span 10.

The differences between predicted and measured superposition strains were observed

to be of greater magnitude at the FRP near the primary crack locations. A maximum

difference of 42 x 10-6

in./in. was observed at the FRP strain gage installed near the crack

location on Girder 7 of Span 11. From this difference, it is evident that the damaged

region of Girder 7 in Span 11 exhibits the least apparent linear behavior of the four

instrumented damaged regions.

5.3.4.3 4374BLINEAR-ELASTIC BEHAVIOR CONCLUSIONS

Deflections measured during the superposition test provide evidence that the overall

bridge structure exhibits behavior that is nearly linear elastic under truck loads.

However, the bottom-fiber strain and crack-opening displacement measurements from the

220

superposition test indicate that the damaged regions exhibit a localized nonlinear

response to truck loads.

5.3.5 550BRELATIONSHIP BETWEEN TRUCK POSITION AND FRP TENSILE DEMAND

The FRP tensile demand was analyzed in response to each truck position of post-repair

testing. Analysis of bottom-fiber strains measured in response to four of the Span 11

truck positions provides evidence for determining critical truck positions. The four truck

positions selected for further analysis include C6, C7, C8, and the Span 11 static position

of AE testing, which are illustrated in Figures 2067H5.52–2068H5.54.

221

Figure 5.52: Longitudinal truck positions—C6

Legend:

Stop Position

Centerline of Continuity Diaphragm

Bent 10

Simple

Support

Span 11

Bent 11

Continuity

Diaphragm

Span 10

Bent 12

Simple

Support

7 6

128‖

70‖

False Support False Support

ST-6400 (east)

ST-6538 (west)

8

300‖

222

Figure 5.53: Longitudinal truck positions—AE LC-6 Span 11 and C7

Legend:

Stop Position

Centerline of Continuity Diaphragm

Bent 10

Simple

Support

Span 11

Bent 11

Continuity

Diaphragm

Span 10

Bent 12

Simple

Support

7 6

128‖

70‖

False Support False Support

ST-6400 (east)

ST-6538 (west)

8

300‖

223

Figure 5.54: Longitudinal truck positions—C8

Legend:

Stop Position

Centerline of Continuity Diaphragm

Bent 10

Simple

Support

Span 11

Bent 11

Continuity

Diaphragm

Span 10

Bent 12

Simple

Support

7 6

128‖

70‖

False Support False Support

ST-6400 (east)

ST-6538 (west)

8

300‖

224

When the trucks are at Static Position C6, the back axles of each truck straddle the

damaged region. The middle axle is positioned 70 in. from the center of the continuity

diaphragm, and the rear axle is approximately 13 in. from the center of the diaphragm, as

shown in 2069HFigure 5.52. The distance between the rear axle and middle axle is 57 in. for

the standard ALDOT load truck.

The Span 11 static position of the AE tests is similar to Static Position C7 of the

multiposition load-tests. These stop positions are similar enough to be presented as one

stop position, as shown in 2070HFigure 5.53, however, there is a slight difference between the

two truck positions. Truck positioning for AE testing was based on aligning the rear

axle, and truck positioning for the multiposition tests was based on aligning the middle

axle. For the AE Span 11 static position, the rear axle is positioned 70 in. from the center

of the continuity diaphragm, and the middle axle is approximately 127 in. from the center

of the diaphragm. When the trucks are at Static Position C7, the middle axle is

positioned 128 in. from the center of the continuity diaphragm, and the rear axle is

approximately 71 in. from the center of the diaphragm.

When the trucks are at Static Position C8, all truck axles are beyond the damaged

region. The middle axle is positioned 300 in. from the center of the continuity

diaphragm, and the rear axle is approximately 243 in. from the center of the diaphragm,

as shown in 2071HFigure 5.54.

These four static positions were tested with the LC-6 load truck block configurations

of the second night of bridge testing. The bottom-fiber strains measured in response to

these four truck position are presented in Figures 2072H5.55–2073H5.58. To indicate the FRP tensile

demand, the Span 11 bottom-fiber FRP strains have been presented in Table 2074H5.17. To

225

further support FRP tensile demand conclusions, crack openings measured in response to

the same four truck positions have been presented in Table 2075H5.18.

Figure 5.55: Bottom-fiber strains—C6

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er S

train

(x10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G8 - Concrete

G7 - FRP

G8 - FRP

226

Figure 5.56: Bottom-fiber strains—AE LC-6 Span 11

Figure 5.57: Bottom-fiber strains—C7

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bo

tto

m-F

iber

Str

ain

(x

10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G8 - Concrete

G7 - FRP

G8 - FRP

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er S

train

(x10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G8 - Concrete

G7 - FRP

G8 - FRP

227

Figure 5.58: Bottom-fiber strains—C8

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er S

train

(x10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G8 - Concrete

G7 - FRP

G8 - FRP

228

Table 5.17: FRP tensile demand—bottom-fiber strains—Span 11 truck positions

Girder

551BDistance

from

center of

continuity

diaphragm

(in.)

– Span 10

+ Span 11

552BLocation

Description

553BBottom-Fiber Strain

(x10-6

in./in.)

– compressive

+ tensile

C6

AE

LC-6

Span 11

C7 C8

7

554B47 555BFRP-Crack 76 130 116 -8

556B74 557BFRP 14 28 25 7

558B104 559BFRP 12 25 28 12

8

560B52 561BFRP-Crack 44 71 56 -21

562B74 563BFRP 26 59 52 14

564B104 565BFRP 26 34 32 10

Note: Measurements presented in bold represent the maximum tensile strains

per gage for all truck positions

Table 5.18: Crack openings—Span 11 truck positions

Girder

566BDistance

from

center of

continuity

diaphragm

(in.)

– Span 10

+ Span 11

Crack-Opening Displacement

(mm)

– closing

+ opening

C6

AE

LC-6

Span 11

C7 C8

7 567B48 0.020 0.044 0.039 0.015

8 568B56 0.017 0.040 0.032 0.011

Notes: Measurements presented in bold represent the maximum crack opening

per gage for all truck positions

1 in. = 25.4 mm

229

The Span 11 static position of the AE test and the C7 static position of the

multiposition test resulted in similar FRP tensile strains of greater magnitude than the

other truck positions. When comparing all static truck positions, the positioning of axles

near the primary crack location, but without straddling the crack location, resulted in the

larger measured FRP tensile demand in response to truck loads. This corresponds to the

truck position that generates the largest shear demand on the damaged cross section. The

Span 11 static position of the AE test also resulted in crack openings of greater

magnitude compared to the other truck positions, which further supports the conclusion

that these stop positions were the most critical truck positions observed during post-repair

bridge testing.

Truck positions resulting in the greatest FRP tensile demand correspond with truck

positions resulting in the greatest shear demand at damaged regions. Analysis procedures

for determining maximum shear force demand for a girder should be used to determine

the load effects and design forces for FRP repair of damaged continuous girder ends.

5.4 61BBRIDGE RESPONSE TO AMBIENT THERMAL CONDITIONS

It has been previously reported (Gao 2003) that initial cracking of I-565 concrete bulb-tee

girders was more likely due to thermal gradients than traffic loads. During post-repair

testing, sensor measurements were monitored for twenty-four hours of normal traffic

conditions to assess structural behavior in response to ambient thermal conditions. These

assessments include continuity behavior of the bridge structure, confirmation that thermal

gradient loading is responsible for initial cracking, and confirmation of other conclusions

supported by static live load analysis. Before the presentation of bridge monitoring

measurements, theoretical bridge behavior is discussed for a two-span continuous

230

structure subjected to a linear thermal gradient. The measured responses to ambient

temperature will then be compared to theoretical responses to ambient temperature and

previously discussed measured responses to truck loads.

5.4.1 569BTHEORETICAL RESPONSE TO AMBIENT THERMAL CONDITIONS

The theoretical temperature gradient along a typical cross-section height (h) is assumed to

be linearly decreasing from the top-fiber of the bridge deck to the bottom-fiber of a

typical girder. This linear temperature gradient results in a positive temperature

difference (Th) when subtracting the temperature at the top of the bridge deck from the

temperature at the bottom of a typical girder. The formula for the temperature difference

is presented as Equation 2076H5.1. The formula for the change in temperature difference

(Th)) between two points in time is presented as Equation 2077H5.2. A linear temperature

gradient example is illustrated in 2078HFigure 5.59.

Th = Ttop – Tbottom Eq. 5.1

Th) = (Th)2 – (Th)1 Eq. 5.2

Figure 5.59: Linear temperature gradient

h

Tbottom

Ttop

Th = Ttop – Tbottom

231

The bridge structure was also considered to be acting as originally constructed, fully

continuous for post-construction loads. A theoretical two-span continuous structure

subjected to a thermal load effects is illustrated in 2079HFigure 5.60. The structure consists of

two identical span lengths (L). The exterior supports (A and C) represent simple

supports, and the interior support (B) represents the continuity achieved by a typical

continuity diaphragm.

Figure 5.60: Two-span continuous structure subjected to linear thermal gradient

After initial cracking, it is likely that the bridge structure does not exhibit fully

continuous behavior, but theoretical analysis as a fully continuous structure will allow for

conservative estimations of bottom-fiber strains that may lead to initial cracking of

uncracked girders. Theoretical bottom-fiber FRP strains expected within a damaged

region should be considered during the design of an FRP reinforcement repair.

L L

A C B

232

5.4.1.1 4375BSTRUCTURAL ANALYSIS

During analysis, the vertical restraint of the interior support was treated as a redundant

support condition to determine the theoretical behavior of the two-span indeterminate

structure. The resulting simply-supported structure was subjected to two separate load

conditions as shown in 2080HFigure 5.61.

Figure 5.61: Expected deformations—two theoretical load conditions

The first load condition consists of a linear thermal gradient without restraint from the

interior support. The second load condition consists of a vertical force (P) representing

the restraining force that had been removed from the first load condition. The theoretical

deformations, moments, and curvatures were determined for both of the two simply

supported load conditions. These theoretical behaviors are mirrored about the interior

support (B). For the purpose of defining behavior with respect to location within a span,

behavior functions will originate at the interior support. Location within the span (x) will

be defined as equal to zero at Support B and equal to L at Support C.

x

+

L L L

P

2

1

L

Thermal displacement with no mid-bridge restraint Restraining force at Support B

A C B A C B

x

233

5.4.1.1.1 DEFORMATIONS

The expected deformations () of the two load conditions are also illustrated in

Figure 2081H5.61. The mid-bridge deformation results from thermal conditions without

restraint at the interior supportThe mid-bridge deformation results from application

of a theoretical restraining force at the location of the theoretically removed interior

supportAs indicated in Equation 2082H5.3, the summation of the two resulting deflections at

the interior support must be equal to zero to match the support conditions of the actual

bridge.

1 + 2 = 0 Eq. 5.3

5.4.1.1.2 BENDING MOMENTS

Bending moment (M) diagrams for the two load conditions of the simply supported

structure are presented in 2083HFigure 5.62. Although the thermal gradient load condition

results in deformation, the simply supported structure does not develop bending moments

along the length of the structure due to unrestrained linear thermal gradient alone. The

restraining force load condition does result in a linear function of bending moment. The

yet-to-be-determined restraining force (P) and span length have an effect on the bending

moment function with a maximum moment of PL/2 at the mid-bridge location and zero

moment at the simple supports. The bending moment function for Span BC in response

to the restraining force applied at Support B is presented as Equation 2084H5.4.

234

Figure 5.62: Moment diagrams—two theoretical load conditions

Eq. 5.4

5.4.1.1.3 CURVATURES

Curvature diagrams for the two theoretical load conditions of the simply supported

structure are presented in 2085HFigure 5.63.

The curvature due to a linear temperature gradient with no restraint is consistent

along the length of the structure. This curvature is also referred to as the temperature-

gradient curvature . The temperature-gradient curvature is a function of the

coefficient of thermal expansion (T), temperature difference (Th) from the top of the

deck to the bottom of a typical girder, and the typical cross-section height (h) including

the height of the deck. The relationship used to calculate is presented as Equation 2086H5.5.

The curvature function due to an unrestrained response to thermal conditions is presented

as Equation 2087H5.6.

+

M +

M

Restraining force at Support B

Simply supported

Max moment at B = [P(2L)/4]

L L L

L

+

Thermal displacement with no mid-bridge restraint

Simply supported

No restraint

No moment

A C B A C B

x x

235

Figure 5.63: Curvature diagrams—two theoretical load conditions

Eq. 5.5

Eq. 5.6

The curvature due to the restraining force is presented in terms of the moment

due to the restraining force and cross-section properties. It is assumed that the modulus

of elasticity (E) and the moment of inertia (I) are constant along the length of the bridge.

The basic function for the curvature due to the restraining force is presented as

Equation 2088H5.7. This curvature function has also been presented in terms of the moment

function variables including the restraint force (P) as shown in Equation 2089H5.8

+

+

Restraining force at Support B

L L L

L

+

Thermal displacement with no mid-bridge restraint

A C B A C B

x x

236

Eq. 5.7

Eq. 5.8

5.4.1.1.4 RESTRAINT FORCE AT INTERIOR SUPPORT

The theory of consistent deformations was used to determine the theoretical restraint

force at B. The theoretical mid-bridge deformations were determined in terms of

variables within the curvature and moment functions. The formulas for the theoretical

mid-bridge deflections 1 and 2 are shown as Equations 2090H5.9 and 2091H5.10 respectively.

Eq. 5.9

Eq. 5.10

The restraint force is a function of the same properties used to define the moments

and curvatures resulting from the two theoretical load conditions. The deflections 1 and

2 were substituted into the consistent deformations relationship presented as

Equation 2092H5.3, and the resulting formula is shown as Equation 2093H5.11. This formula was

then manipulated to solve for the restraint force P in terms of the other variables as shown

in Equation 2094H5.12.

237

Eq. 5.11

Eq. 5.12

5.4.1.2 4376BEXPECTED BEHAVIOR

The expected behavior of the two-span continuous structure can be determined by

superimposing the behaviors of the simply supported structure resulting from the

temperature gradient and restraint force load conditions. The expected response

characteristics are presented as functions of the distance (x) from the interior support.

The behaviors presented include the net curvature ( ), bending moment (M), shear force

(V), bottom-fiber strain ( ), and bottom-fiber stress ( ). The bottom-fiber strains are

computed from the curvatures, and the shear forces and bottom-fiber stresses are derived

from the bending moments. The bottom-fiber strains and stresses are also a function of

the distance (ybot) from the cross section centroid to the bottom fiber.

5.4.1.2.1 CURVATURE

The formula for the expected net curvature presented as Equation 2095H5.13 is derived by

superimposing the previously defined curvature functions of the two theoretical load

conditions. The curvature ( ) due to a temperature gradient without restraint is

presented as Equation 2096H5.14. The restraint force variable (P) within the curvature function

presented as Equation 2097H5.8, which represents the curvature due to the restraint force

associated with temperature effects that restrained at the interior support, can be

238

substituted with the restraint force formula defined as Equation 2098H5.12. The resulting

curvature ( ) due to the restraint force is presented as Equation 2099H5.15.

Eq. 5.13

Eq. 5.14

Eq. 5.15

The curvature functions defined in Equations 2100H5.14 and 2101H5.15 can be superimposed to

determine the expected net curvature function due to a linear temperature gradient with

restraint at the interior support, which is presented as Equation 2102H5.16.

Eq. 5.16

The expected net curvature function can then be simplified by condensing the

temperature gradient curvature variables into one term as shown in Equation 2103H5.17, where

is the curvature due to unrestrained temperature gradient defined in Equation 2104H5.5.

Eq. 5.17

239

The curvature function can then be solved to determine that the expected point of zero

curvature is located a distance of one third the span length from the interior support as

shown in Equation 2105H5.18.

Eq. 5.18

An illustration of the expected curvature as a function of the distance from the interior

support is presented in 2106HFigure 5.64. The curvatures expected at the interior and exterior

supports are also provided within this figure.

Figure 5.64: Curvature due to temperature gradient with restraint

5.4.1.2.2 BENDING MOMENT

The bending moment is a function of the restraint force developed. The restraint force

(P) within the bending moment function presented as Equation 2107H5.4 can be substituted

with the restraint force defined as Equation 2108H5.12. The resulting function for bending

moment that results from the restraint force is presented as Equation 2109H5.19, and represents

the expected moment due to a linear temperature gradient with restraint at the interior

+

L/3 L/3

L L

A C B

x

240

support in a two-span continuous beam. The expected moment function can then be

simplified by condensing the temperature gradient curvature variables into one term as

shown in Equation 2110H5.20. An illustration of the expected moment as a function of the

distance from the interior support is presented in 2111HFigure 5.65. The moment expected at

the interior support is also provided within this figure.

Eq. 5.19

Eq. 5.20

Figure 5.65: Moment due to temperature gradient with restraint

+

L L

A C B

x

241

5.4.1.2.3 SHEAR FORCE

The shear force function is a constant value with opposing direction of action on either

side of the interior support. The shear force is computed from the slope of the moment

function as shown in Equation 2112H5.21. The formula for the maximum bending moment,

which is expected at the interior support as shown in 2113HFigure 5.65, is defined as

Equation 2114H5.22. Substituting the formula for the maximum expected moment into the

shear force function shown in Equation 2115H5.21 provides the expanded shear force formula

presented as Equation 2116H5.23. The expected shear force function can then be simplified by

condensing the temperature gradient curvature variables into one term as shown in

Equation 2117H5.24. An illustration of the expected shear force as a function of the distance

from the interior support is presented in 2118HFigure 5.66.

Eq. 5.21

Eq. 5.22

Eq. 5.23

Eq. 5.24

242

Figure 5.66: Shear due to temperature gradient with restraint

5.4.1.2.4 BOTTOM-FIBER STRAIN—UNCRACKED CROSS SECTIONS

The bottom-fiber strain function of the theoretically uncracked structure is derived from

the curvature function using the distance from the centroid of a typical uncracked cross

section to the bottom of the girder. The basic bottom-fiber strain function formula is

shown as Equation 2119H5.25. The expected curvature function of Equation 2120H5.16 can be

substituted into the basic bottom-fiber strain function to provide the expanded bottom-

fiber strain function presented as Equation 2121H5.26. The expected bottom-fiber strain

function can then be simplified by condensing the temperature gradient curvature

variables into one term as shown in Equation 2122H5.27. An illustration of the expected

bottom-fiber strain as a function of the distance from the interior support is presented in

Figure 2123H5.67.

Eq. 5.25

Eq. 5.26

+

L L

A C B

x

243

Eq. 5.27

Figure 5.67: Bottom-fiber strain due to temperature gradient with restraint

5.4.1.2.5 BOTTOM-FIBER STRESS—UNCRACKED CROSS SECTION

The bottom-fiber stress function of the theoretically uncracked structure is derived from

the moment function, the distance from the centroid of a typical uncracked cross section

to the bottom of the girder, and the moment of inertia. The basic bottom-fiber stress

function formula is shown as Equation 2124H5.28. The expected moment function of

Equation 2125H5.19 can be substituted into the basic bottom-fiber stress function to provide the

expanded bottom-fiber stress function presented as Equation 2126H5.29. The expected bottom-

fiber stress function can then be simplified by condensing the temperature gradient

curvature variables into one term as shown in Equation 2127H5.30. An illustration of the

expected shear force as a function of the distance from the interior support is presented in

2128HFigure 5.68. The bottom-fiber stress is not proportional to the bottom-fiber strain

because a portion of the total strain is due to stress-independent thermal changes.

+

L/3 L/3

L L

A C B

x

244

Eq. 5.28

Eq. 5.29

Eq. 5.30

Figure 5.68: Bottom-fiber stress due to temperature gradient with restraint

5.4.1.2.6 BOTTOM-FIBER STRAIN—CRACKED CROSS SECTION—FRP

The theoretical uncracked concrete behavior presented is not applicable for the local

behavior at damaged sections selected for potential FRP repair. The damaged cross

section must be considered cracked during analysis to determine the bottom-fiber FRP

strain expected in response to temperature effects.

Assuming the cross section to be cracked eliminates the theoretical bottom-fiber

strain due to a temperature gradient without restraint at the interior support. However,

there is still an FRP strain expected due to an unrestrained temperature change. This FRP

strain is associated with the ambient temperature at the FRP location at two different

+

L L

A C B

x

245

times. The difference between these two temperatures results in a temperature change

(TFRP) that can be multiplied by the longitudinal coefficient of thermal expansion

(FRP) specified for the repair material. The formula for the FRP strain expected in

response to unrestrained temperature change in the FRP material is presented as

Equation 2129H5.31. This strain component is stress-independent.

Eq. 5.31

The FRP must also undergo the stress-dependent bottom-fiber strain due to the

restraint force associated with a linear temperature gradient applied to the entire two-span

continuous structure. This strain is based on the theoretical curvature due to the restraint

force load condition, which corresponds to the bending moment that results from this

restraint. This theoretical curvature has been previously defined as Equation 2130H5.15. The

basic formula for the strain expected due to curvature has been previously defined as

Equation 2131H5.25, and is associated with the distance (ybot) from the centroid of the cross

section to the bottom of the girder. The distance (ycr,bot) from the centroid of a cracked

section to the bottom of the girder of a cracked section is of greater magnitude than the

distance from centroid of an uncracked section to the bottom of the girder, which results

in an increase of expected strain due to the cracked nature of the cross section. The

formula for the FRP strain expected due to the restraint force is presented as

Equation 2132H5.32. This formula can also be presented with the distance from the centroid to

the bottom fiber and the girder height considered a ratio as presented in Equation 2133H5.33.

246

Eq. 5.32

Eq. 5.33

The bottom-fiber strain functions defined in Equations 2134H5.31 and 2135H5.33 can be

superimposed to determine the expected FRP strain due to ambient temperature effects

with restraint at the interior support, which is presented as Equation 2136H5.34.

Eq. 5.34

5.4.1.2.7 DEFLECTION

The expected displacement of a two-span continuous structure due to a linear temperature

gradient is illustrated in 2137HFigure 5.69. Inflection points are expected at the previously

defined points of zero curvature located a distance of one third of the span length from

the interior support.

Figure 5.69: Deflections due to temperature gradient with restraint

Inflection Points

( )

L/3 L/3

L L

A C B

247

5.4.2 570BMEASURED RESPONSES TO AMBIENT THERMAL CONDITIONS

Bridge monitoring measurements were analyzed to assess the post-repair behavior of the

instrumented girders for twenty-four hours. The temperature and weather conditions

during bridge monitoring were ideal for observing the bridge behavior in response to a

near worst-case thermal gradient load condition for the geographic bridge location. The

bridge monitoring measurements can be compared to the measured responses to truck

placement and can also be related to the theoretical behavior of a continuous structure

subjected to a linear thermal gradient.

All bridge monitoring measurements are relative to initial conditions measured at

2:30 a.m. on the first night of bridge testing. These initial conditions are not necessarily

equal to the initial conditions observed during the static load tests on the second night of

testing, but are similar enough to allow for approximate comparisons of magnitude for

measured responses to load truck placement and ambient thermal conditions. The bridge

monitoring measurements are presented graphically in 2138HAppendix D and in tabular format

in 2139HAppendix E of this thesis.

For the purpose of analyzing the change in deflection and bottom-fiber strain profiles,

four specific times were selected based on the observation of measured responses for all

sensor types. The times selected were 6:30 a.m., 4:30 p.m., 8:30 p.m., and 2:30 a.m.

Measurements at 6:30 a.m. represent responses measured just before the thermal

conditions begin to rapidly change at dawn. Measurements at 4:30 p.m. represent a near-

maximum response to thermal conditions. Measurements at 8:30 p.m. represent

responses measured while the bridge deck was cooling down after sunset. Measurements

248

at 2:30 a.m. represent responses measured at the conclusion of the twenty-four hour

period.

The post-repair weather conditions were favorable for the desired analysis of

structural behavior in response to large temperature variations experienced during a daily

cycle. Temperatures measured at the Huntsville International Airport every three hours

during post-repair bridge monitoring are presented in 2140HTable 5.19. Sunrise reportedly

occurred at 4:38 a.m., and sunset reportedly occurred at 6:50 p.m. on May 25, 2010.

(NOAA 2010)

Table 5.19: Temperatures measured during bridge monitoring (NOAA 2010)

Date Time

(CST)

Temperature

(°F)

May 25, 2010

12:00 a.m. 72

3:00 a.m. 71

6:00 a.m. 71

9:00 a.m. 78

12:00 p.m. 80

3:00 p.m. 84

6:00 p.m. 82

9:00 p.m. 75

May 26, 2010 12:00 a.m. 70

3:00 a.m. 66

249

5.4.2.1 4377BDEFLECTIONS

Deflection measurements in response to ambient thermal conditions are relative to initial

conditions at 2:30 a.m. on the first night of bridge testing. Positive deflection

measurements indicate upward deflections compared to initial conditions, and negative

deflection measurements indicate downward deflections compared to initial conditions.

The deflections measured in response to thermal conditions are presented in Tables E2141H.2

and E2142H.3. Graphical presentations of the midspan and quarterspan deflections measured

during the twenty-four hour period are shown in Figures 2143H5.70 and 2144H5.71.

Figure 5.70: Deflections—normal traffic—twenty-four hours—Girder 7

-0.2

-0.1

0.0

0.1

0.2

0.3

0.4

0.5

2:30 5/25 6:30 5/25 10:30 5/25 14:30 5/25 18:30 5/25 22:30 5/25 2:30 5/26

Bo

tto

m-F

iber

Def

lect

ion

(in

.)

Time of Day (hr:min month/day)

G7 - SP10 - Midspan

G7 - SP10 - Q. Span

G7 - SP11 - Q. Span

G7 - SP11 - Midspan

250

Figure 5.71: Deflections—normal traffic—twenty-four hours—Girder 8

5.4.2.1.1 MAXIMUM UPWARD DEFLECTIONS

The upward deflections measured in response to ambient thermal conditions were

compared to the upward deflections measured in response to truck loads. The maximum

upward deflections at midspan and quarterspan due to thermal conditions are presented in

2145HTable 5.20. These maximum upward deflections due to thermal conditions are compared

to the maximum upward deflections due to truck loads as shown in Table 2146H5.21.

-0.2

-0.1

0.0

0.1

0.2

0.3

0.4

0.5

2:30 5/25 6:30 5/25 10:30 5/25 14:30 5/25 18:30 5/25 22:30 5/25 2:30 5/26

Bo

tto

m-F

iber

Def

lect

ion

(in

.)

Time of Day (hr:min month/day)

G8 - SP10 - Midspan

G8 - SP10 - Q. Span

G8 - SP11 - Q. Span

G8 - SP11 - Midspan

251

Table 5.20: Maximum upward deflections—thermal conditions

Girder Span

Location

from

continuity

diaphragm

at

Bent 11

Deflection

(in.)

Time Measured

(hr:min a.m./p.m.)

7

10 midspan 571B0.41 572B3:30 p.m.

quarterspan 573B0.38 574B4:30 p.m.

11 quarterspan 575B0.36 576B4:30 p.m.

midspan 577B0.39 578B4:30 p.m.

8

10 midspan 579B0.49 580B3:30 p.m.

quarterspan 581B0.40 582B2:30 p.m.

11 quarterspan 583B0.37 584B2:30 p.m.

midspan 585B0.40 586B2:30 p.m.

252

Table 5.21: Maximum upward deflections—post-repair

Girder Span

Location

from

continuity

diaphragm

at

Bent 11

Maximum

Upward

Deflection

(in.)

Thermal

Conditions

Load Truck

Conditions

7

10 midspan 587B0.41 588B0.04

quarterspan 589B0.38 590B0.04

11 quarterspan 591B0.36 592B0.04

midspan 593B0.39 594B0.05

8

10 midspan 595B0.49 596B0.05

quarterspan 597B0.40 598B0.04

11 quarterspan 599B0.37 600B0.04

midspan 601B0.40 602B0.05

NCHRP Report 519 (Miller et al. 2004) indicates that a maximum camber of 0.41 in.

at midspan was observed in response to solar effects during ALDOT bridge testing

(ALDOT 1994). The maximum upward deflections were observed at the time of day

when the thermal gradient would be reaching its peak. A maximum upward deflection of

0.49 in. was measured at roughly 3:30 p.m. by the midspan deflectometer of Girder 8 in

Span 10, and the other three midspan sensors measured maximum upward deflections of

0.39 in., 0.40 in., and 0.41 in. The magnitudes of the maximum midspan upward

deflections for each instrumented girder—disregarding Girder 8-Span 10—were very

similar to the maximum upward deflection measured by ALDOT in 1994.

253

The maximum upward deflection measured due to any load truck position during

post-repair bridge testing was 0.05 in. at the midspan locations of three of the four

girders. These maximum upward deflections measured during bridge testing were all in

response to the midspan truck position in the opposite span. The maximum midspan and

quarterspan upward deflections measured in response to thermal condition are

approximately ten times greater than the maximum upward deflections measured in

response to service-level truck loads.

5.4.2.1.2 DEFLECTED SHAPE—MEASURED AND THEORETICAL

Measured deflections were illustrated to observe the change in deflected shape due to

ambient thermal conditions. The deflections measured at 6:30 a.m., 4:30 p.m., 8:30 p.m.

and 2:30 a.m. are presented graphically in Figures 2147H5.72–2148H5.75. A summary of the midspan

and quarterspan deflections measured at these times is presented in Table 2149H5.22.

254

Figure 5.72: Deflections—8:30 a.m.

Figure 5.73: Deflections—4:30 p.m.

-0.20

-0.10

0.00

0.10

0.20

0.30

0.40

0.50

-700 -500 -300 -100 100 300 500 700

Bott

om

-Fib

er D

efle

ctio

n (

in.)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

-0.20

-0.10

0.00

0.10

0.20

0.30

0.40

0.50

-700 -500 -300 -100 100 300 500 700

Bott

om

-Fib

er D

efle

ctio

n (

in.)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

255

Figure 5.74: Deflections—8:30 p.m.

Figure 5.75: Deflections—2:30 a.m.

-0.20

-0.10

0.00

0.10

0.20

0.30

0.40

0.50

-700 -500 -300 -100 100 300 500 700

Bott

om

-Fib

er D

efle

ctio

n (

in.)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

-0.20

-0.10

0.00

0.10

0.20

0.30

0.40

0.50

-700 -500 -300 -100 100 300 500 700

Bott

om

-Fib

er D

efle

ctio

n (

in.)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

256

Table 5.22: Deflections—ambient thermal conditions

Girder Span

Location

from

continuity

diaphragm

at

Bent 11

Deflections

(in.)

– downward

+ upward

6:30

a.m.

4:30

p.m.

8:30

p.m.

2:30

a.m.

7

10 midspan -0.11 0.41 0.13 -0.14

quarterspan -0.08 0.37 0.11 -0.11

11 quarterspan -0.07 0.34 0.34 -0.05

midspan -0.10 0.39 0.39 -0.05

8

10 midspan -0.03 0.48 0.25 0.01

quarterspan -0.01 0.38 0.20 0.01

11 quarterspan -0.06 0.34 0.17 -0.06

midspan -0.02 0.37 0.16 -0.08

The deflections measured at 4:30 p.m. and 8:30 p.m. result in deflected shapes that

are similar to the deflected shape expected of a continuous structure subjected to a

thermal gradient as shown in 2150HFigure 5.69. However, additional measured deflections

would be useful for providing clearer evidence of an inflection point in response to

restrained thermal effects.

5.4.2.2 4378BBOTTOM-FIBER STRAINS

Strain measurements in response to ambient thermal conditions are relative to initial

conditions at 2:30 a.m. on the first night of bridge testing. Positive strains measurements

indicate elongation relative to the initial conditions, and negative strain measurements

257

indicate relative contraction. The bottom-fiber strains measured due to thermal

conditions are presented in Tables E 2151H.12 and E 2152H.13. Graphical presentations of the bottom-

fiber strains measured during the twenty-four hour period are shown in Figures 2153H5.76–

2154H5.79.

Figure 5.76: Bottom-fiber strains—Girder 7—within 80 in. from diaphragm

-200

-100

0

100

200

300

400

500

600

2:30 5/25 6:30 5/25 10:30 5/25 14:30 5/25 18:30 5/25 22:30 5/25 2:30 5/26

Bo

tto

m-F

iber

Str

ain

(x

10

-6 in

./in

.)

Time of Day (hr:min month/day)

F7_10_1M

F7_10_CK

F7_11_CK

F7_11_4M

258

Figure 5.77: Bottom-fiber strains—Girder 7—beyond 80 in. from diaphragm

Figure 5.78: Bottom-fiber strains—Girder 8—within 80 in. from diaphragm

-100

-75

-50

-25

0

25

50

2:30 5/25 6:30 5/25 10:30 5/25 14:30 5/25 18:30 5/25 22:30 5/25 2:30 5/26

Bo

tto

m-F

iber

Str

ain

(x

10

-6 in

./in

.)

Time of Day (hr:min month/day)

S7_11_5M

F7_11_5M

S7_11_6M

S7_11_7M

S7_11_8M

-200

-100

0

100

200

300

400

500

600

2:30 5/25 6:30 5/25 10:30 5/25 14:30 5/25 18:30 5/25 22:30 5/25 2:30 5/26

Bo

tto

m-F

iber

Str

ain

(x

10

-6 in

./in

.)

Time of Day (hr:min month/day)

S8_10_1MF8_10_1MF8_10_CKF8_11_CKS8_11_4MF8_11_4M

259

Figure 5.79: Bottom-fiber strains—Girder 8—beyond 80 in. from diaphragm

5.4.2.2.1 MAXIMUM BOTTOM-FIBER TENSILE STRAINS

The maximum bottom-fiber tensile strains measured in response to ambient thermal

conditions were compared to the maximum bottom-fiber tensile strains measured in

response to truck loads. The bottom-fiber strain gages in Span 11 beyond 105 in. from

the center of the continuity diaphragm did not measure significant tensile strains due to

ambient thermal conditions compared to the other bottom-fiber strain gages. The

maximum bottom-fiber tensile strains measured by gages located 105 in. from the

continuity diaphragm or closer in response to ambient thermal conditions are presented in

Tables 2155H5.23 and 2156H5.24. These maximum tensile strains measured in response to thermal

conditions are compared to the maximum bottom-fiber tensile strains measured in

response to truck loads as shown in Tables 2157H5.25 and 2158H5.26.

-100

-75

-50

-25

0

25

50

2:30 5/25 6:30 5/25 10:30 5/25 14:30 5/25 18:30 5/25 22:30 5/25 2:30 5/26

Bo

tto

m-F

iber

Str

ain

(x

10

-6 in

./in

.)

Time of Day (hr:min month/day)

S8_11_5M

F8_11_5M

S8_11_6M

S8_11_7M

S8_11_8M

260

Table 5.23: Maximum bottom-fiber tensile strains—Girder 7—thermal conditions

Span

603BDistance

from

center of

continuity

diaphragm

(in.)

– Span 10

+ Span 11

604BLocation

Description

605BBottom-Fiber Strain

(x10-6

in./in.)

– compressive

+ tensile

Time Measured

(hr:min a.m./p.m.)

10 606B-74 FRP 607B38 608B4:30 p.m.

609B-47 610BFRP-Crack 611B387 612B4:30 p.m.

11

613B47 614BFRP-Crack 615B504 616B3:30 p.m.

617B74 618BFRP 619B46 620B4:30 p.m.

621B104 622BFRP 623B27 624B6:30 p.m.

625B105 626BConcrete 627B33 628B6:30 p.m.

261

Table 5.24: Maximum bottom-fiber tensile strains—Girder 8—thermal conditions

Span

629BDistance

from

center of

continuity

diaphragm

(in.)

– Span 10

+ Span 11

630BLocation

Description

631BBottom-Fiber Strain

(x10-6

in./in.)

– compressive

+ tensile

Time Measured

(hr:min a.m./p.m.)

10

632B-75 Concrete 633B25 634B4:30 p.m.

635B-74 636BFRP 637B16 638B3:30 p.m.

639B-41 640BFRP-Crack 641B404 642B4:30 p.m.

11

643B52 644BFRP-Crack 645B251 646B4:30 p.m.

647B74 648BFRP 649B101 650B4:30 p.m.

651B75 652BConcrete 653B297 654B4:30 p.m.

655B104 656BFRP 657B27 658B6:30 p.m.

659B105 660BConcrete 661B37 662B5:30 p.m.

262

Table 5.25: Maximum bottom-fiber tensile strains—Girder 7

Span

663BDistance

from

center of

continuity

diaphragm

(in.)

– Span 10

+ Span 11

664BLocation

Description

665BMaximum

666BBottom-Fiber

667BTensile Strain

(x10-6

in./in.)

Thermal

Conditions

Load Truck

Conditions

10 668B-74 FRP 669B38 670B24

671B-47 672BFRP-Crack 673B387 674B108

11

675B47 676BFRP-Crack 677B504 678B140

679B74 680BFRP 681B46 682B28

683B104 684BFRP 685B27 686B32

687B105 688BConcrete 689B33 690B35

263

Table 5.26: Maximum bottom-fiber tensile strains—Girder 8

Span

691BDistance

from

center of

continuity

diaphragm

(in.)

– Span 10

+ Span 11

692BLocation

Description

693BMaximum

694BBottom-Fiber

695BTensile Strain

(x10-6

in./in.)

Thermal

Conditions

Load Truck

Conditions

10

696B-75 Concrete 697B25 698B28

699B-74 700BFRP 701B16 702B19

703B-41 704BFRP-Crack 705B404 706B117

11

707B52 708BFRP-Crack 709B251 710B71

711B74 712BFRP 713B101 714B59

715B75 716BConcrete 717B297 718B148

719B104 720BFRP 721B27 722B34

723B105 724BConcrete 725B37 726B34

The maximum bottom-fiber tensile strains were observed at the time of day when the

thermal gradient would be reaching its peak. A maximum bottom-fiber tensile strain of

504 x 10-6

in./in. was measured at roughly 3:30 p.m. by the near-crack bottom-fiber FRP

strain gage on Girder 7 in Span 11.

The maximum bottom-fiber tensile strain measured in response to any load truck

position during post-repair bridge testing was 148 x 10-6

in./in. at the bottom-fiber

concrete strain gage located 75 in. from the center of the continuity diaphragm along

Girder 8 in Span 11. The majority of the maximum bottom-fiber tensile strains in

response to truck loads were associated with the AE static positions. Compared to the

264

maximum bottom-fiber strains in response to truck loads, the maximum bottom-fiber

tensile strains due to thermal conditions are more significantly increased for the gages

installed on the FRP near the crack locations than at any other gage location. Overall

comparisons of maximum bottom-fiber tensile strains due to thermal loads versus truck

loads clearly indicate that the ambient thermal conditions at the time of the post-repair

bridge testing resulted in greater tension demand on the damaged regions than any of the

load truck conditions. These measured bottom-fiber strains support the conclusion that

restraint of ambient thermal conditions was the cause of initial cracking.

5.4.2.2.2 STRAIN PROFILE—MEASURED AND THEORETICAL

The bottom-fiber strain measurements were illustrated to observe the bottom-fiber strain

profile along the length of the bridge structure due to ambient thermal conditions at

different times throughout the twenty-four hour period. The bottom-fiber strains

measured at 6:30 a.m., 4:30 p.m., 8:30 p.m. and 2:30 a.m. are presented graphically in

Figures 2159H5.80–2160H5.83. A summary of these bottom-fiber strain measurements are presented

in Tables 2161H5.27 and 2162H5.28.

265

Figure 5.80: Bottom-fiber strains—8:30 a.m.

Figure 5.81: Bottom-fiber strains—4:30 p.m.

-100

0

100

200

300

400

500

600

-700 -500 -300 -100 100 300 500 700

Bo

tto

m-F

iber

Str

ain

(x

10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G8 - Concrete

G7 - FRP

G8 - FRP

-100

0

100

200

300

400

500

600

-700 -500 -300 -100 100 300 500 700

Bo

tto

m-F

iber

Str

ain

(x

10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G8 - Concrete

G7 - FRP

G8 - FRP

266

Figure 5.82: Bottom-fiber strains—8:30 p.m.

Figure 5.83: Bottom-fiber strains—2:30 a.m.

-100

0

100

200

300

400

500

600

-700 -500 -300 -100 100 300 500 700

Bo

tto

m-F

iber

Str

ain

(x

10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G8 - Concrete

G7 - FRP

G8 - FRP

-100

0

100

200

300

400

500

600

-700 -500 -300 -100 100 300 500 700

Bo

tto

m-F

iber

Str

ain

(x

10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G8 - Concrete

G7 - FRP

G8 - FRP

267

Table 5.27: Bottom-fiber strains—Girder 7—ambient thermal conditions

Span

727BDistance

from

center of

continuity

diaphragm

(in.)

– Span 10

+ Span 11

728BLocation

Description

729BBottom-Fiber Strain

(x10-6

in./in.)

– compressive

+ tensile

6:30

a.m.

4:30

p.m.

8:30

p.m.

2:30

a.m.

10 730B-74 FRP 731B-1 732B38 733B20 734B1

735B-47 736BFRP-Crack 737B-78 738B387 739B185 740B-39

11

741B47 742BFRP-Crack 743B-79 744B502 745B233 746B-28

747B74 748BFRP 749B-6 750B46 751B23 752B6

753B104 754BFRP 755B0 756B25 757B17 758B7

759B105 760BConcrete 761B-12 762B31 763B15 764B-11

765B273 766BConcrete 767B-16 768B7 769B0 770B-11

771B441 772BConcrete 773B-24 774B-14 775B-19 776B-27

777B609 778BConcrete 779B-22 780B-56 781B-52 782B-50

268

Table 5.28: Bottom-fiber strains—Girder 8—ambient thermal conditions

Span

783BDistance

from

center of

continuity

diaphragm

(in.)

– Span 10

+ Span 11

784BLocation

Description

785BBottom-Fiber Strain

(x10-6

in./in.)

– compressive

+ tensile

6:30

a.m.

4:30

p.m.

8:30

p.m.

2:30

a.m.

10

786B-75 Concrete -20 787B25 9 788B-18

789B-74 790BFRP 791B-1 792B15 793B8 794B-1

795B-41 796BFRP-Crack 797B-111 798B404 799B190 800B-86

11

801B52 802BFRP-Crack 803B-69 804B251 805B126 806B-36

807B74 808BFRP 809B-9 810B101 811B41 812B-8

813B75 814BConcrete 815B-36 816B297 817B116 818B-20

819B104 820BFRP 821B-5 822B24 823B17 824B0

825B105 826BConcrete 827B-11 828B37 829B23 830B-9

831B273 832BConcrete 833B-21 834B7 835B-2 836B-21

837B441 838BConcrete 839B-28 840B-9 841B-18 842B-28

843B609 844BConcrete 845B1 846B14 847B12 848B1

269

To allow for better comparison between measured bottom-fiber strains and theoretical

bottom-fiber strains of a continuous uncracked structure, the bottom-fiber concrete strains

for each girder line are also presented at the same previously mentioned times, but

independent of the other bottom-fiber strain measurements. The bottom-fiber concrete

strains for Girder Line 7 are presented in Figures 2163H5.84–2164H5.87, and the bottom-fiber

concrete strains for Girder Line 8 are presented in Figures 2165H5.88–2166H5.91. The slopes of

linear trend lines for the more reliable concrete strain gages in Span 11 beyond the

damaged zone have been noted in each figure. These slopes indicate that during service

conditions the structure experiences larger differences of bottom-fiber strain along a

girder line during times associated with larger temperature gradients. This behavior is

another indication that the bridge structure is exhibiting continuous behavior.

Figure 5.84: Bottom-fiber strains—concrete—Girder 7—6:30 a.m.

-100

-80

-60

-40

-20

0

20

40

60

80

100

-700 -500 -300 -100 100 300 500 700

Bo

tto

m-F

iber

Str

ain

(x

10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

Slope: –0.02 x10-6 (in./in)/in.

270

Figure 5.85: Bottom-fiber strains—concrete—Girder 7—4:30 p.m.

Figure 5.86: Bottom-fiber strains—concrete—Girder 7—8:30 p.m.

-100

-80

-60

-40

-20

0

20

40

60

80

100

-700 -500 -300 -100 100 300 500 700

Bo

tto

m-F

iber

Str

ain

(x

10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

Slope: –0.17 x10-6 (in./in)/in.

-100

-80

-60

-40

-20

0

20

40

60

80

100

-700 -500 -300 -100 100 300 500 700

Bo

tto

m-F

iber

Str

ain

(x

10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

Slope: –0.13 x10-6 (in./in)/in.

271

Figure 5.87: Bottom-fiber strains—concrete—Girder 7—2:30 a.m.

Figure 5.88: Bottom-fiber strains—concrete—Girder 8—6:30 a.m.

-100

-80

-60

-40

-20

0

20

40

60

80

100

-700 -500 -300 -100 100 300 500 700

Bo

tto

m-F

iber

Str

ain

(x

10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

Slope: –0.08 x10-6 (in./in)/in.

-100

-80

-60

-40

-20

0

20

40

60

80

100

-700 -500 -300 -100 100 300 500 700

Bo

tto

m-F

iber

Str

ain

(x

10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G8 - Concrete

Slope: –0.05 x10-6 (in./in)/in.

272

Figure 5.89: Bottom-fiber strains—concrete—Girder 8—4:30 p.m.

Figure 5.90: Bottom-fiber strains—concrete—Girder 8—8:30 p.m.

-100

-80

-60

-40

-20

0

20

40

60

80

100

-700 -500 -300 -100 100 300 500 700

Bott

om

-Fib

er S

train

(x10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G8 - Concrete

Slope: –0.13 x10-6 (in./in)/in.

-100

-80

-60

-40

-20

0

20

40

60

80

100

-700 -500 -300 -100 100 300 500 700

Bott

om

-Fib

er S

train

(x10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G8 - Concrete

Slope: –0.12 x10-6 (in./in)/in.

273

Figure 5.91: Bottom-fiber strains—concrete—Girder 8—2:30 a.m.

The trend line slopes can also be compared to the slope of the theoretical bottom-fiber

strain profile presented in Figure 2167H5.67. The formula for this theoretical slope is presented

as Equation 2168H5.35. Values for the formula variables, and the slope of the bottom-fiber

strain profile expected due to these conditions, are presented following the equation. The

temperature variation ) from the top of the deck to the bottom of a typical girder

is assumed to be 44 °F, which was reported for ALDOT bridge testing (ALDOT 1994)

with a maximum measured upward deflection similar to the maximum upward

deflections measured during post-repair bridge monitoring. Also, the ALDOT bridge

testing (May 19, 1994) and post-repair bridge monitoring (May 25, 2010) were conducted

at a similar time of the year.

-100

-80

-60

-40

-20

0

20

40

60

80

100

-700 -500 -300 -100 100 300 500 700

Bott

om

-Fib

er S

train

(x10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G8 - Concrete

Slope: –0.06 x10-6 (in./in)/in.

274

Eq. 5.35

The slope of the bottom-fiber strain profile expected due to these conditions is

-0.24 x 10-6

(in./in.)/in., which is similar to the -0.17 x 10-6

(in./in.)/in. slope of the

measured strain profile for Girder 7 in Span 11 at 4:30 p.m. as presented in Figure 2169H5.85.

The slope of the measured strain profile is less steep than the slope of the theoretical

strain profile, which could be an indication that the girder is not exhibiting fully

continuous behavior as theoretically assumed, or that the actual temperature gradient was

less than the estimated value. This decrease in continuity exhibited by the slope of the

measured strain profile is likely due to the local behavior of the damaged region.

The bottom-fiber strains near the damaged region are shown to be greater than the

strains projected by trend lines associated with concrete strains beyond the damaged

region. These near damage zone bottom-fiber strains are presented in Figures 2170H5.92–2171H5.95.

The magnitudes of the bottom-fiber tensile strains measured within the damaged region at

275

4:30 p.m. as shown in 2172HFigure 5.93 are an indication that the ambient thermal conditions

have a significant effect on the damaged regions.

Figure 5.92: Bottom-fiber strains—damaged region—8:30 a.m.

-100

0

100

200

300

400

500

600

-120 -80 -40 0 40 80 120

Bott

om

-Fib

er S

train

(x1

0-6

in./

in.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G8 - Concrete

G7 - FRP

G8 - FRP

276

Figure 5.93: Bottom-fiber strains—damaged region—4:30 p.m.

Figure 5.94: Bottom-fiber strains—damaged region—8:30 p.m.

-100

0

100

200

300

400

500

600

-120 -80 -40 0 40 80 120

Bott

om

-Fib

er S

train

(x10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G8 - Concrete

G7 - FRP

G8 - FRP

-100

0

100

200

300

400

500

600

-120 -80 -40 0 40 80 120

Bott

om

-Fib

er S

train

(x10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G8 - Concrete

G7 - FRP

G8 - FRP

277

Figure 5.95: Bottom-fiber strains—damaged region—2:30 a.m.

The force resisted by the FRP at a cracked cross section must make up for the

decreased flexural stiffness of the cracked section. The formula for the theoretical

bottom-fiber FRP strain expected due to thermal conditions is presented as Equation 2173H5.34.

The typical crack location observed at the continuous ends of the investigated girders

is less than 4 percent of the respective span length. Due to the variation of crack location

from the continuous end of the girder, it is conservative to assume that the ratio between

the crack location and span length is nearly equal to zero. Also, due to the previously

reported assumption that prestressing strands are considered to have slipped at a typical

crack location, it is conservative to assume that the ratio between the distance from the

cracked section neutral axis to the bottom of the girder and the overall height of the cross

section is only slightly less than one—as would be expected in a cross section that is

-100

0

100

200

300

400

500

600

-120 -80 -40 0 40 80 120

Bott

om

-Fib

er S

train

(x10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G8 - Concrete

G7 - FRP

G8 - FRP

278

lightly reinforced with a wide compression flange. Based on these assumptions, the

formula for the theoretical bottom-fiber FRP strain expected due to thermal conditions

can be simplified as presented in Equation 2174H5.36.

Eq. 5.36

Values for the formula variables, and the bottom-fiber strain expected due to these

conditions, are presented following this paragraph. The concrete thermal properties

remain the same as previously presented. The longitudinal coefficient of thermal

expansion of the FRP ( ) is approximately 3.6 x 10-6

(in./in.)/°F according to the

manufacturer (Fyfe 2010). An FRP temperature variation (TFRP) of 30 °F is assumed

based on the range of maximum and minimum ambient temperatures reported for the

days encompassing post-repair testing (NOAA 2010).

279

The bottom-fiber FRP strain expected due to these conditions is a tensile strain of

510 x 10-6

in./in., which is similar to the maximum tensile strains measured at the crack

locations as presented in Tables 2175H5.23 and 2176H5.24. These similar tensile strains support the

conclusion that this simplified analysis of structural response to a linear temperature

gradient can be used to establish the tensile strain that must be resisted on a regular basis

by an FRP repair system.

5.4.2.3 4379BCRACK-OPENING DISPLACEMENTS

Crack-opening displacements in response to ambient thermal conditions are relative to

initial conditions at 2:30 a.m. on the first night of bridge testing. Positive crack-opening

displacement measurements indicate crack openings compared to the initial conditions,

and negative crack-opening displacement measurements indicate crack closures

compared to the initial conditions. The crack-opening displacements measured in

280

response to ambient thermal conditions are presented in Table E 2177H.1. Graphical

presentations of these crack-opening displacements are shown in 2178HFigure 5.96.

Figure 5.96: Crack-opening displacements—normal traffic—twenty-four hours

5.4.2.3.1 MAXIMUM CRACK OPENINGS

The maximum crack openings measured in response to ambient thermal conditions have

been compared to the maximum crack openings measured in response to truck loads.

The maximum crack openings in response to ambient thermal conditions are presented in

2179HTable 5.29. These maximum crack openings measured in response to thermal conditions

are compared to the maximum crack openings measured in response to truck loads as

shown in 2180HTable 5.30.

-0.05

0.00

0.05

0.10

0.15

0.20

2:30 5/25 6:30 5/25 10:30 5/25 14:30 5/25 18:30 5/25 22:30 5/25 2:30 5/26

Cra

ck-O

pen

ing D

isp

lace

men

t (m

m)

Time of Day (hr:min month/day)

CO7_10

CO8_10

CO7_11

CO8_11

281

Table 5.29: Maximum crack openings—thermal conditions

Girder Span

Crack-Opening

Displacement

(mm)

– closing

+ opening

Time Measured

(hr:min a.m./p.m.)

7 10 849B0.109 850B3:30 p.m.

11 851B0.169 852B3:30 p.m.

8 10 853B0.077 854B3:30 p.m.

11 855B0.122 856B4:30 p.m.

Note: 1 in. = 25.4 mm

Table 5.30: Maximum crack openings—thermal and load truck conditions

Girder Span

Maximum

Crack Opening

(mm)

– closing

+ opening

Thermal

Conditions

Load Truck

Conditions

7 10 857B0.109 858B0.024

11 859B0.169 860B0.047

8 10 861B0.077 862B-0.002

11 863B0.122 864B0.040

Note: 1 in. = 25.4 mm

282

Table 5.31: Crack-opening displacements—ambient thermal conditions

Girder Span

Crack-Opening Displacement

(mm)

– closing

+ opening

6:30

a.m.

4:30

p.m.

8:30

p.m.

2:30

a.m.

7 10 -0.014 0.108 0.049 -0.006

11 -0.022 0.168 0.078 -0.009

8 10 -0.014 0.076 0.029 -0.007

11 -0.014 0.122 0.060 -0.004

Note: 1 in. = 25.4 mm

The maximum crack openings measured in response to thermal conditions were

observed around the time of day when the thermal gradient would be expected to peak.

A maximum crack opening of 0.169 mm (6.66 x 10-3

in.) was measured at roughly

3:30 p.m. by the COD gage on the east face of Girder 7 in Span 11. The maximum crack

opening measured in response to any load truck position during post-repair bridge testing

was 0.047 mm (1.83 x 10-3

in.) at the same COD gage location on Girder 7 of Span 11 in

response to the AE Span 11 static position. All of the COD gages measured crack

openings of greater magnitude in response to thermal conditions compared to crack

openings due to truck loads.

The COD gage on Girder 8 of Span 10 did not measure a crack opening in response

to any of the static truck positions, but this same gage measured a crack opening of

0.077 mm (3.02 x 10-3

in.) due to ambient thermal conditions at roughly 3:30 p.m. The

crack openings measured due to thermal conditions by the COD gage on Girder 8 of

283

Span 10 are another indication that crack initiation or propagation is more likely due to

extreme thermal conditions than oversized truck loads. These crack openings also

support the static load test conclusion that out-of-plane bending had an effect on the COD

measurements of this COD gage in response to truck loads. This is due to the fact that

thermal conditions are less likely to produce out-of-plane bending in an interior girder

than a wheel load placed on the bridge deck.

5.4.2.3.2 CRACK OPENINGS AND NEAR-CRACK FRP TENSILE STRAINS

The crack-opening displacement measurements and near-crack bottom-fiber FRP strain

measurements in response to ambient thermal conditions allow for analysis of gage

performance. The crack-opening displacement and FRP strain relationship for the crack

location of each instrumented girder has been presented in Figures 2181H5.97–2182H5.100. The

measurements for each sensor at 4:30 p.m. have been presented in 2183HTable 5.32.

Figure 5.97: Bottom-fiber strain and COD—thermal conditions—Girder 7—Span 10

-0.06

-0.03

0.00

0.03

0.06

0.09

0.12

0.15

0.18

-200

-100

0

100

200

300

400

500

600

2:30 5/25 6:30 5/25 10:30 5/25 14:30 5/25 18:30 5/25 22:30 5/25 2:30 5/26

Cra

ck-O

pen

ing D

isp

lace

men

t (m

m)

Bo

tto

m-F

iber

Str

ain

(x

10

-6 in

./in

.)

Time of Day (hr:min month/day)

F7_10_CK

CO7_10

-0.03

-0.06

284

Figure 5.98: Bottom-fiber strain and COD—thermal conditions—Girder 7—Span 11

Figure 5.99: Bottom-fiber strain and COD—thermal conditions—Girder 8—Span 10

-0.06

-0.03

0.00

0.03

0.06

0.09

0.12

0.15

0.18

-200

-100

0

100

200

300

400

500

600

2:30 5/25 6:30 5/25 10:30 5/25 14:30 5/25 18:30 5/25 22:30 5/25 2:30 5/26

Cra

ck-O

pen

ing D

isp

lace

men

t (m

m)

Bo

tto

m-F

iber

Str

ain

(x

10

-6 in

./in

.)

Time of Day (hr:min month/day)

F7_11_CK

CO7_11

-0.03

-0.06

-0.06

-0.03

0.00

0.03

0.06

0.09

0.12

0.15

0.18

-200

-100

0

100

200

300

400

500

600

2:30 5/25 6:30 5/25 10:30 5/25 14:30 5/25 18:30 5/25 22:30 5/25 2:30 5/26

Cra

ck-O

pen

ing D

isp

lace

men

t (m

m)

Bo

tto

m-F

iber

Str

ain

(x

10

-6 in

./in

.)

Time of Day (hr:min month/day)

F8_10_CK

CO8_10

-0.03

-0.06

285

Figure 5.100: Bottom-fiber strain and COD—thermal conditions—Girder 8—Span 11

Table 5.32: Crack openings and bottom-fiber strains—thermal conditions

Girder Span

Thermal Conditions

4:30 p.m.

Crack Opening

(mm)

865BBottom-Fiber Strain

(x10-6

in./in.)

7 10 866B0.108 867B387

11 868B0.168 869B502

8 10 870B0.076 871B404

11 872B0.122 873B251

Note: 1 in. = 25.4 mm

-0.06

-0.03

0.00

0.03

0.06

0.09

0.12

0.15

0.18

-200

-100

0

100

200

300

400

500

600

2:30 5/25 6:30 5/25 10:30 5/25 14:30 5/25 18:30 5/25 22:30 5/25 2:30 5/26

Cra

ck-O

pen

ing D

isp

lace

men

t (m

m)

Bo

tto

m-F

iber

Str

ain

(x

10

-6 in

./in

.)

Time of Day (hr:min month/day)

F8_11_CK

CO8_11

-0.03

-0.06

286

Due to the previous conclusion that Girder 7 sensors provide the most reliable

measurements, the crack-opening displacements and FRP strains have been presented

using scales that provided the best graphical comparisons between the Girder 7 sensors.

As previously discussed, the Girder 8-Span 10 COD gage measured crack openings in

response to ambient thermal conditions but not in response to truck loads. Although the

measured behavior at this gage location is more similar to the other gages in response to

ambient temperature than it was in response to truck loads, the COD and FRP strain

relationship is not similar to the relationships observed at the Girder 7 crack locations of

both instrumented spans. The FRP strain measurements for Girder 8 of Span 10 were

similar to the FRP strain measurements for Girder 7 of Span 10, but the COD

measurements for the two girders were not similar under the same conditions. The

smaller magnitude of the Girder 8-Span 10 COD measurements can be associated with

the fact that cracks within the girder web are only present on the west face. The

relationship observed in 2184HFigure 5.99 supports the previous conclusions that the

performance of the COD gage on Girder 8 of Span 10 has been affected by the presence

of cracks only on the west face of the girder web resulting in different cross sectional

behavior compared to the other instrumented damaged regions and also requiring that the

COD gage be installed on an opposite girder face compared to the other COD gages.

The FRP strains measured at the crack location of Girder 8 in Span 11 were

consistently the least tensile of the four instrumented girders. This behavior is not

consistent with the crack-opening displacements measured by the COD gage on the same

girder. The relationship shown in 2185HFigure 5.100 between the COD measurements and the

bottom-fiber FRP strain measurements at the crack location of Girder 8-Span 11 supports

287

the previous conclusion that the bottom-fiber FRP strain gage assigned to that crack

location was not accurately installed as close to the actual underlying crack location as

the other FRP strain gages assigned to their respective crack locations.

5.5 62BPERFORMANCE OF FRP REINFORCEMENT

At the time of post-repair testing in May 2010, the FRP reinforcement installed in

December 2007 had been in service for more than 2 years. Most importantly, the FRP

reinforcement system had been subjected to two summer cycles and likely experienced

varying temperature gradients similar to the thermal conditions that reportedly caused

initial cracking. At the time of post-repair testing, the bridge structure did not exhibit

additional severe cracking of structural concrete or debonding/deterioration of FRP

reinforcement bonded to the concrete surface. During post-repair testing, stress-induced

tensile strains were measured on the surface of the FRP reinforcement in response to

truck loads and daily temperature variations. The FRP reinforcement was installed to

provide tension resistance to limit additional damage without debonding and becoming

ineffective. It is apparent that the FRP installed on Northbound Spans 10 and 11 of I-565

is providing tension resistance without debonding, and that it would be appropriate to

recommend a design procedure for the repair of prestressed bridge girders that exhibit

damage near continuous ends using FRP reinforcement.

5.6 63BCONCLUSIONS

Analysis of the post-repair measurements in response to truck loads confirmed that

contact between false support bearing pads and bridge girders during pre-repair testing

resulted in additional load-bearing support conditions that affected behavior observed

during pre-repair testing. It is evident that comparisons between pre- and post-repair

288

structural behavior measured during testing are not useful for assessing the efficacy of the

FRP reinforcement repair.

Post-repair measurements in response to truck loads confirmed that, although

extensive cracking near the continuous ends of girders has occurred, the bridge structure

exhibits continuous behavior. However, it is also evident that damaged regions exhibit

local nonlinear behavior preventing the bridge structure from behaving as a fully

continuous two-span structure under live loads as originally constructed. When

designing similar FRP repair systems, the bridge should be considered to consist of

simply-supported girders with complete loss of continuity at the interior support in

response to strength-limit-state demands.

Post-repair measurements in response to various truck positions confirmed that the

most critical load conditions for crack openings and FRP tensile demand were those that

correspond with the greatest shear demand within the damaged region. Design-critical

loading configurations for the damaged regions coincide with truck positions that result

in the maximum shear force at the most damaged regions. Analysis procedures for

determining the maximum shear force demand for a simply girder should be used to

determine the load effects and design forces for FRP repair of girders with damaged

continuous ends.

Analysis of the post-repair measurements in response to ambient thermal conditions

supports the previously documented conclusion that restraint of temperature-induced

deformations was the cause of initial cracking near the continuous ends of the I-565

bridge girders. Upward deflections measured in response to ambient thermal conditions

289

during post-repair bridge monitoring were similar to upward deflections measured in

response to solar effects during an ALDOT investigation of the same spans in 1994.

Linear profiles of bottom-fiber concrete strains measured beyond the primary crack

location of damaged regions were similar to the theoretical linear profiles expected of a

fully continuous structure in response to the restraint of thermal deformations. The slope

of the bottom-fiber strain profiles were less than theoretically expected of a fully

continuous structure subjected to a linear temperature gradient similar to the gradient

measured by ALDOT in 1994, which is an indication that either the structure is not

exhibiting fully continuous behavior or the temperature gradient was less than

theoretically assumed.

Post-repair measurements in response to thermal conditions also provide evidence

that the typical daily strain range experienced by the FRP reinforcement at a primary

crack location is similar to the theoretical behavior expected in response to a linear

temperature gradient similar to the gradient measured by ALDOT in 1994.

Simplified linear temperature gradient analysis can be used to effectively estimate the

tensile strain that an FRP repair system must resist due to daily temperature variations.

This theoretical strain behavior in response to thermal conditions should be considered

when selecting a specific FRP reinforcement system for repair.

After more than 2 years of service, the repaired bridge structure did not exhibit

additional severe cracking of structural concrete or debonding/deterioration of FRP

reinforcement bonded to the concrete surface. It is apparent that the FRP installed on

Northbound Spans 10 and 11 of I-565 is providing tension resistance without debonding,

and that it would be appropriate to recommend a design procedure for the repair of

290

prestressed bridge girders that exhibit damage near continuous ends using FRP

reinforcement.

291

Chapter 6

10BFRP REINFORCEMENT DESIGN

6.1 64BINTRODUCTION

Behavioral observations from bridge testing were used to formulate FRP reinforcement

design recommendations for repairing damaged regions similar to the continuous ends of

girders in Northbound Spans 10 and 11 of I-565 in Huntsville, Alabama. These

recommendations include parameters for selecting appropriate FRP reinforcement

products, determining critical cross-section locations and critical load conditions,

determining an amount of reinforcement required to satisfy strength-limit-state demands,

and, if necessary, selecting appropriate solutions for providing supplementary anchorage.

Design recommendations for an FRP reinforcement solution (similar to the repair system

discussed in this thesis) intended for the repair of damaged multi-span bridge structures

constructed to be continuous for post-construction loads (similar to the bridge structure

discussed in this thesis) are presented in this chapter. An example of the design

procedure, considering the investigated I-565 bridge structure and FRP reinforcement

product selected by the Auburn University Highway Research Center (AUHRC), is

presented in 2186HAppendix N of this thesis.

292

6.2 65BNECESSITY OF FRP REINFORCEMENT

The conditions investigated within the scope of this thesis include girder cracking at the

continuous ends of bridge structures that were constructed to be continuous for post-

construction loads. As discussed in Chapter 2 of this thesis, this cracking is attributable

to inadequate detailing of reinforcement to account for positive bending moment

demands associated with ambient temperature conditions (Gao 2003). The primary

inadequate detail is the premature termination of positive bending moment continuity

reinforcement within the girder. If large cracks have been observed to intersect

prestressed strands, it has been determined that it is no longer appropriate to assume that

these strands provide significant precompression stresses or act as effective longitudinal

reinforcement for positive bending moment resistance between the crack location and the

face of the continuity diaphragm—particularly under strength-limit-state demands. Thus,

additional longitudinal reinforcement is required to satisfy shear- and flexure-dependent

ultimate strength demands that were previously dependent upon the performance of these

prestressed strands.

6.3 66BFRP REINFORCEMENT PRODUCT SELECTION

A manufacturer of FRP reinforcement must be able to confidently recommend the

selected FRP product for bridge girder reinforcement. Recommendations for determining

qualifying FRP reinforcement products are presented by the American Concrete Institute

(ACI) Committee 440.2R-08 Guide for the Design and Construction of Externally

Bonded FRP Systems for Strengthening Concrete Structures (ACI Committee 440 2008),

referred to as ACI 440.2R-08 from this point forward. Product selection

recommendations are also presented by the National Cooperative Highway Research

293

Program (NCHRP) Report 655 Recommended Guide Specification for the Design of

Externally Bonded FRP Systems for the Repair and Strengthening of Concrete Bridge

Elements (Zureick et al. 2010), referred to as NCHRP Report 655 from this point

forward.

Material properties should be reported for the cured composite material of FRP fibers

and adhesive. The tension failure strain (fu) and Young’s modulus of elasticity (Ef)

should be reported by the manufacturer as determined in accordance with ASTM D3039.

The glass transition temperature (Tg) should be reported in accordance with

ASTM D4065.

For design purposes, these properties should take into account material degradation

due to prolonged environmental exposure. It is recommended that the durability of an

FRP product be tested for conditions that are consistent with the environment of the

installation location. Conditions that could have an effect on durability include

Freeze-thaw cycling,

Hot-wet cycling,

Alkaline immersion,

Ultraviolet exposure,

Dry heat, and

Salt water exposure.

If the material properties documented by the manufacturer do not account for durability

effects, then an environmental reduction factor (CE) must be applied in accordance with

ACI 440.2R-08.

294

To account for fatigue associated with service life environmental exposure, tensile

properties reported by the manufacturer should be adjusted in accordance with provisions

presented in Section 9.4 of ACI 440.2R-08. Young’s modulus of elasticity is typically

unaffected by environmental conditions, because the design tensile strength and design

rupture strain are both modified by the same reduction coefficient for environmental

exposure (ACI Committee 440 2008).

According to ACI 440.2R-08, of all types of FRP composites for infrastructure

applications, carbon FRP (CFRP) is the least prone to fatigue failure. The fatigue

strength at ultimate strength is relatively unaffected by environmental conditions, unless

the resin or fiber/resin interface is substantially degraded by environmental exposure.

According to NCHRP Report 655, the tension failure strain should be documented at

greater than 0.85 percent after environmental effects. NCHRP Report 655 also

recommends that the glass transition temperature should represent a temperature more

than 40 °F warmer than the maximum design temperature (Tmax,design) expected at the

geographic location of the bridge structure. This maximum design temperature is defined

in Article 3.12.2.2 of the American Association of State Highway and Transportation

Officials LRFD Bridge Design Specification (AASHTO 2010), referred to as AASHTO

LRFD from this point forward.

To assess the feasibility of an FRP repair system, it is recommended to assume FRP

material properties similar to those of the FRP material installed on the girders of

Northbound Spans 10 and 11 of I-565. However, it is permissible to design a repair

system with other FRP products that are recommended by the manufacturer for the

reinforcement of bridge girders. Potential FRP reinforcement products must have

295

documented material properties obtained through testing. Additional testing may be

required to verify these documented properties if the designer or bridge owner is

unfamiliar with the product.

6.4 67BSTRENGTH-LIMIT-STATE DESIGN

After selecting an FRP reinforcement product with confirmed acceptable material

properties, the amount of reinforcement required to satisfy strength-limit-state demands

can be determined. For the purpose of this discussion, strength-limit-state capacities and

demands are determined in accordance with AASHTO LRFD; however, another

framework of consistent analysis and design procedures could be utilized at the discretion

of the bridge owner—as long as each of the relevant failure modes are adequately

addressed.

Strength-limit-state capacities must be modified to include the effects of longitudinal

FRP reinforcement. Limiting behavior expected of FRP reinforcement is determined in

accordance with provisions presented by ACI 440.2R-08.

FRP reinforcement design requirements are determined according to the minimum

tensile capacity required of the net flexural reinforcement in response to strength-limit-

state demands. Strength-limit-state design includes the determination of

Critical cross-section locations,

Critical load conditions for those locations,

Material properties of the existing structure and FRP reinforcement,

Cross-section dimensions,

Reinforcement dimensions at each critical location,

Shear strength after reinforcement,

296

Tension strength of longitudinal reinforcement,

Length of FRP installation, and

Supplemental anchorage solution necessity.

The subsequent sections of this chapter detail this strength design process. An

example of the FRP reinforcement design process is presented in 2187HAppendix N of this

thesis. This example refers to the conditions of the investigated bridge structures of

Northbound Spans 10 and 11 of I-565 in Huntsville, Alabama.

6.4.1 874BCRITICAL CROSS-SECTION LOCATIONS

Critical cross-section locations are those that are associated with support conditions or

reinforcement transition points within a damaged or potentially damaged region.

Reinforcement transitions occur where the cross-sectional area of longitudinal

reinforcement area changes due to the addition or termination of reinforcement.

Reinforcement details that result in these changes in reinforcement area include the

termination of mild steel reinforcement, partial debonding of strands during girder

fabrication, and changes in FRP widths that can be installed due to obstructions.

Reinforcement transitions also occur where the spacing of vertical reinforcement

changes.

6.4.2 875BCRITICAL LOAD CONDITIONS

Load testing has provided evidence that damaged end regions of bridge structures

constructed to be fully continuous for post-construction loads exhibit partially continuous

behavior, but not fully continuous behavior, in response to service-level truck loads.

When determining strength-limit-state demands, it is conservative and appropriate to

297

assume that a multi-span structure constructed to be continuous for post-construction

loads will consist of independent simply supported spans near failure. This assumption

results in a safe estimate of tensile demand in the bottom flange. As a bridge structure

becomes less continuous there is a decrease in tensile demand associated with shear, but

there is also a reduction of tensile resistance provided by negative bending moments near

the interior support.

Load testing has also provided evidence that the most critical load conditions

controlling FRP reinforcement performance are those that correspond to maximum shear

demand within the damaged end regions. The strength limit state for maximum shear

demand, along with the corresponding bending moment demand, at a critical location will

control the tension requirements of an FRP reinforcement repair solution.

Strength-limit-state tension demand is determined by assuming the bridge structure

exhibits simply supported behavior near failure and applying a combination of dead- and

live-load effects to the structure. Impact force effects that are normally associated with

behavior near open bridge joints may be appropriately reduced or neglected at the

discretion of the bridge owner when assessing damaged regions located near continuous

support conditions (where there is no open joint). Strength-limit-state demands at critical

cross-section locations of the assumed simply supported bridge structure can be

determined in accordance with AASHTO LRFD or another framework of consistent

analysis and design procedures at the discretion of the bridge owner. All demands

associated with simply supported behavior assumption should be satisfied along the

entire length of the girder. This includes shear and bending moment demands at

midspan.

298

6.4.3 876BSTRENGTH-LIMIT-STATE TEMPERATURE DEMANDS

Temperature demands do not need to be considered in conjunction with other strength-

limit-state demands. The FRP reinforcement repair has been conservatively designed to

strengthen girders that have experienced complete continuity degradation and exhibit

simply supported behavior in response to live loads. After the degradation of continuity

behavior, thermal effects are no longer restrained and do not result in stress-induced

strains. If the continuity remains partially effective, temperature effects will be restrained

and result in stress-induced strain, but the tension demands on the FRP in response to

truck loads will be decreased by a greater magnitude than the additional tension demands

related to these stress-induced thermal strains. It is thus appropriate to disregard thermal

effects during strength-limit-state design.

6.4.4 877BMATERIAL PROPERTIES

During the design process it is important to know specific material properties. The

materials that will have an effect on the repair system design include the girder concrete,

deck concrete, longitudinal steel continuity reinforcement, vertical steel shear

reinforcement (stirrups), and the selected FRP reinforcement.

6.4.4.1 4380BCONCRETE

The 28-day design compressive strength (f’c) of the concrete placed during girder

fabrication and deck placement is required to determine post-repair strength capacities.

Due to the thickness and effective width (b) of the bridge deck, the compression zone for

providing nominal bending moment resistance will be located within the bridge deck.

For this reason, the concrete strength of the bridge deck affects the strength for bending

moment resistance—although only slightly for typical bridge girders. When determining

299

the nominal strength for shear resistance (Vn), the effective concrete is located in the

girder web between the compression and tension zones. For this reason, the concrete

strength of the girder controls nominal strength for shear resistance.

For design purposes, the typical concrete strengths are considered to range from 3 ksi

to 8 ksi. Although higher strength concretes may be utilized for prestressed girders, it is

recommended that these higher concrete strengths be taken no higher than 8 ksi during

the design of an FRP reinforcement system (Zureick et al. 2010).

6.4.4.2 4381BSTEEL REINFORCEMENT

The material properties of steel reinforcement installed during girder fabrication are also

required for strength design. It is undesirable for an FRP failure to occur before the steel

reinforcement yields. For this reason, the design yield strength (fy) of both the

longitudinal and vertical steel reinforcement should be known.

6.4.4.3 4382BFRP REINFORCEMENT

The material properties of the FRP composite material (fabric and cured epoxy) also have

an effect on strength design. The tensile modulus of elasticity (Ef) and nominal one-layer

laminate thickness (tf,n) of the composite material are required to be presented in product

specifications provided by the manufacturer.

FRP reinforcement does not exhibit yielding behavior similar to steel, but rather

exhibits brittle failure modes, typically associated with debonding from the concrete.

The FRP strain must be conservatively limited to prevent this failure mode because FRP

debonding represents an undesirable failure of reinforcement instantaneously becoming

ineffective at the debonded location. Thus, the effective debonding strain (εfe) of

laminate FRP reinforcement must be limited during strength design based on the

300

debonding strain (εfd), development length (Ldf), bonded length provided (Lb), and an

appropriate upper limit debonding strain.

The debonding strain (εfd) is contingent upon other material properties including

concrete strength, FRP modulus of elasticity, the thickness of one layer of laminate, and

the total number of layers (n) installed at a specific location. A formula for the strain

level at which an FRP laminate may debond from a concrete substrate—even if ample

bonded length is provided on either side of the critical section—is presented as

Equation 2188H6.1, as proposed by ACI 440.2R-08.

– Eq. 6.1

The bond capacity of FRP reinforcement is developed over a critical length (Ldf) from

termination points. This development length of the reinforcement has an effect on the

expected debonding strain, and is based on the same material properties of the concrete

and FRP reinforcement. A formula for the development length of FRP reinforcement is

presented as Equation 2189H6.2, as proposed by ACI 440.2R-08 (in.–lb units) based on the

formula proposed by Teng et al. (2003) (SI units).

– Eq. 6.2

If the bonded length (Lb) between a termination point and a critical location is less

than the required development length, the expected debonding strain at the critical

location must be reduced. Although a reduction factor for inadequate development

length is not presented by ACI 440.2R-08, a reduction factor is presented by the source of

the development length formula (Teng et al. 2003). A strain reduction factor (βL) for

301

locations where the available bonded length is less than the required development length

is presented as Equation 2190H6.3.

Eq. 6.3

L is equal to 1 for locations where the bonded length exceeds the required development

length. Equation 2191H6.3 describes the development of FRP bond capacity as a half sine

curve that reaches full development at Ldf. Past published literature suggests that

supplemental anchorage can be provided to decrease the required development length at

locations of inadequate bonded length; however, the effectiveness of proposed anchorage

methods should be experimentally tested prior to installation.

Debonding of FRP reinforcement can occur at intermediate crack locations along the

length of the reinforced region. Thus, the effective FRP strain at all locations should be

limited regardless of expected bond capacities or known effectiveness of supplemental

anchorage. A maximum effective debonding strain of 0.004 in./in. (0.4%) is proposed by

ACI 440.2R-08.

The formula for determining the limiting effective debonding strain (εfe) of laminate

FRP reinforcement during strength design is based on the debonding strain (εfd), bonded

length reduction factor (βL), and an upper limit debonding strain (0.004 in./in.), as shown

in Equation 2192H6.4.

– Eq. 6.4

302

6.4.5 878BDIMENSIONAL PROPERTIES

Details of the cross-section dimensions and reinforcement dimensions at critical cross-

section locations are required for strength design of an FRP reinforced system.

6.4.5.1 4383BCROSS-SECTION DIMENSIONS

Cross-section dimensions are dependent upon the girder type and construction methods.

If the structure is constructed for composite behavior between the girders and the bridge

deck, then an effective width and total height of the bridge deck is included in the cross-

section dimensions. The required cross-section dimensions include total height (h), web

width (bv), and compression zone width (b).

6.4.5.2 4384BREINFORCEMENT DIMENSIONS

Reinforcement dimensions are dependent upon the reinforcement type, size, amount, and

location. The types of reinforcement include longitudinal steel, FRP reinforcement, and

vertical steel.

6.4.5.2.1 LONGITUDINAL STEEL REINFORCEMENT

Longitudinal steel reinforcement includes any mild steel reinforcement or prestressed

steel strands installed during girder fabrication. The area of reinforcement (As and Aps)

and the location of the centroid (ys and yps) of each reinforcement type should be known

for ultimate-strength design.

Prestressed strands are conservatively and appropriately considered to be ineffective

for tension and shear resistance between the face of the diaphragm and damaged regions.

Thus, prestressed strand dimensions are only applicable beyond the damaged region.

303

Mild steel installed as continuity reinforcement remains effective for tension

resistance between the face of the diaphragm and damaged regions. Although continuity

reinforcement is typically installed throughout the girder height, it is conservative to

simply consider only the reinforcement located in the tension flange during ultimate-

strength design. Consideration of the continuity reinforcement in the flange is

complicated by uncertainty about whether or not this reinforcement yields prior to failure

of the FRP reinforcement.

6.4.5.2.2 FRP REINFORCEMENT

The dimensions of the tension flange control the dimensions of the FRP reinforcement.

The width of FRP reinforcement (bf) and the location of the centroid (yf) are required for

ultimate-strength design.

Sheets of FRP fabric are applied as continuous sheets of reinforcement along the

entire length of the repair system. The end regions of continuous sheets of reinforcement

are shaped appropriately to account for interference of supports. At support locations

where the bottom of the girder rests on a bearing pad, FRP reinforcement cannot be

installed along the bottom of the girder, as shown in 2193HFigure 6.1. Wherever possible, FRP

reinforcement should be installed to wrap around the entire perimeter of the tension

flange, as shown in 2194HFigure 6.2. The FRP should be installed so that the primary fibers are

parallel to the girder axis and can provide effective tension reinforcement to the bottom

flange.

304

Figure 6.1: Cross-sectional configuration of FRP—near diaphragm (Swenson 2003)

Figure 6.2: Cross-sectional configuration of FRP—typical (Swenson 2003)

6.5‖

Inside face of

bearing pad

Face of continuity

diaphragm

B

B

Section B

Total effective width of

FRP reinforcement

bonded to girder = 58 in.

3‖

21‖

21‖

6.5‖

A

A

Section A

Total effective width of

FRP reinforcement

bonded to girder = 30 in.

Bearing pad

3‖

Inside face of

bearing pad

Face of continuity

diaphragm

305

6.4.5.2.3 VERTICAL STEEL REINFORCEMENT

Vertical steel reinforcement includes any steel stirrups installed during girder fabrication.

The area of reinforcement (Av) and the reinforcement spacing (s) for the region

surrounding a critical cross-section location are required for ultimate-strength design.

6.4.6 879BINITIAL ESTIMATE OF REQUIRED FRP LAYERS

To begin designing an FRP reinforcement solution that satisfies ultimate-strength

demand, an initial estimate of the FRP thickness is required. This initial thickness can be

estimated with a simplified assumption that the longitudinal tension demand (T) is equal

to the maximum factored shear demand (Vu). A simplified model for the transfer of

forces is shown in 2195HFigure 6.3.

Figure 6.3: Simplified model for initial estimate of FRP requirement

During ultimate-strength design of an FRP reinforcement repair, it is desirable for

steel reinforcement to yield before the FRP reinforcement reaches an effective debonding

stress (ffe) associated with FRP failure. Typical steel with a yield stress of 60 ksi yields at

C

T

R

Vu

T = Asfy + Afffe

306

a strain of roughly 0.002 in./in., thus, an initial estimate of an FRP effective debonding

strain (εfe,min) of 0.003 in./in. at failure is appropriate for the initial estimation of FRP

required.

The simplified formula for tension resistance required is presented as Equation 2196H6.5.

Eq. 6.5

The tension capacity that should satisfy the simplified tension demand is shown as

Equation 2197H6.6.

Eq. 6.6

If there is no steel reinforcement, the FRP thickness must satisfy the entire tension

demand for that cross section. The tension capacity, reduced by an appropriate resistance

factor (ϕ) of 0.9, must be greater than the tension demand, as shown in Equation 2198H6.7.

Eq. 6.7

The formula for the estimated minimum FRP thickness required (tf,req) can then be

derived from Equations 2199H6.5–2200H6.7, which is presented as Equation 2201H6.8.

Eq. 6.8

The angle θ is not yet known at this stage of the design process. However, values of

cot(θ) will typically range from 1.0 to 1.5. The designer should begin the process by

selecting a trial value in this range.

307

The minimum thickness required should be determined for critical cross-section

locations. The greatest required thickness of these locations will control the initial FRP

thickness estimated for the entire reinforcement system. The number of layers (n) of FRP

required is determined based on the manufacturer specified nominal thickness (tf,n) per

layer of FRP laminate, as shown in Equation 2202H6.9.

Eq. 6.9

FRP reinforcement is applied as long continuous sheets of fabric. The number of

layers required to satisfy the maximum thickness requirement of critical locations will

control the initially estimated thickness of reinforcement.

6.4.7 880BVERTICAL SHEAR STRENGTH RESISTANCE

Although longitudinal FRP reinforcement does not directly provide additional vertical

strength resistance, the additional reinforcement does allow for an increase of the vertical

shear strength resistance provided by the concrete and vertical steel reinforcement. The

additional reinforcement results in an increase of the nominal strength for bending

moment resistance (Mn), an increase of the effective shear depth (dv) of the cross section,

a decrease of the net longitudinal tensile strain (εs) expected in response to design load

conditions, and a decrease of the expected angle of inclination for shear cracking (θ),

which leads to an increase in the nominal vertical shear strength (Vn) provided by the

concrete and vertical steel reinforcement.

308

6.4.7.1 4385BNOMINAL STRENGTH FOR BENDING MOMENT RESISTANCE

The nominal strength for bending moment resistance can be determining in accordance

with typical design provisions. Additional terms may be appropriately included to

account for the effects of the FRP reinforcement. When determining the nominal

strength for bending moment resistance, the standard Whitney uniform compression

block theory may not accurately represent the compression block behavior of the repaired

structure. This is due to the failure mode of the structure being controlled by an FRP

debonding failure instead of a concrete crushing failure. Although the Whitney

compression block theory may not accurately represent the actual cross-section

compressive stress distribution, this simplified theory can reasonably be applied for cross

sections with relatively low positive bending moment demands, such as the end regions

of bridge girders. Formulas used to calculate nominal bending moment resistance are

presented in Equations 2203H6.10–2204H6.13.

Eq. 6.10

Eq. 6.11

Eq. 6.12

Eq. 6.13

309

Because the deck provides a very wide compression flange for positive-moment

resistance in bridge girders, the flexural strength is relatively insensitive to the assumed

compressive stress distribution.

6.4.7.2 4386BEFFECTIVE SHEAR DEPTH

The effective shear depth (dv) for each critical cross-section location is the greatest of

three values calculated in accordance with Article 5.8.2.9 of AASHTO LRFD.

One effective shear depth value is dependent upon the nominal bending moment

resistance and the tensile forces at failure. It is appropriate to assume that FRP

reinforcement failure occurs due to reaching the FRP effective debonding strain after the

steel yields but before the compression-zone concrete crushes. This effective shear depth

is calculated as the distance between the centroid of the compression zone and the

location of the net tensile force, as shown in Equation 2205H6.14.

Eq. 6.14

The second effective shear depth value is ninety percent of the depth (de) from the top

of the cross section to the location of the net tensile stress, as shown in Equations 2206H6.15

and 2207H6.16.

Eq. 6.15

Eq. 6.16

The third effective shear depth value is seventy-two-percent of the total height (h) of

the cross section, as shown in Equation 2208H6.17.

310

Eq. 6.17

The maximum of these three effective shear depths controls design in accordance

with AASHTO LRFD provisions. However, the larger of the two values that do not

require the calculation of the nominal bending moment capacity can be used for

simplicity if desired.

6.4.7.3 4387BNET TENSION STRAIN

In order to prevent FRP debonding failure under the combined influence of flexure and

shear, the net longitudinal tension strain (s) corresponding to the nominal strength for

shear resistance must not exceed the effective debonding strain limit for the FRP

reinforcement. The net longitudinal tension strain can be calculated in accordance with

Article 5.8.3.4 of AASHTO LRFD, modified to include FRP effects, as shown in

Equation 2209H6.18.

Eq. 6.18

Terms associated with strength provided by prestressed strands (Vp, Apfpo, and ApsEp)

have been disregarded from the AASHTO formula based on the unknown effectiveness

of prestressed strands within damaged regions.

When determining the net longitudinal tension strain, the factored bending moment

demand corresponding to the maximum factored shear demand must not be taken less

than the theoretical bending moment resulting from the factored shear demand being

applied a distance equal to the effective shear depth from the critical location. The

311

factored bending moment demand of the net tension strain equation is considered to be

the greater of these two bending moment demands, as shown in Equation 2210H6.19.

Eq. 6.19

If the net tension strain calculated in response to the factored demands for shear

strength exceeds the effective debonding strain of the FRP reinforcement, more layers of

FRP may be required to satisfy demand. The effective FRP strain can be substituted into

the net tension strain equation, which can then be rearranged to solve for the number of

layers of FRP required to satisfy the net tension strain demands in response to factored

demands for shear strength, as shown in Equation 2211H6.20.

Eq. 6.20

If additional layers are required to satisfy the net tension demand, the net tension

strain must be recalculated with the appropriate number of layers before continuing to

check vertical shear strength.

6.4.7.4 4388BDIAGONAL SHEAR CRACK PARAMETERS

After determining an appropriate net tension strain in response to factored shear strength

demands, the vertical shear strength can be determined. The net tension strain dictates

parameters associated with diagonal shear cracking, which have an effect on vertical

shear strength provided by concrete and vertical steel reinforcement. These parameters

are calculated in accordance with Article 5.8.3.4 of AASHTO LRFD.

312

The ability of diagonally cracked concrete to transmit tension and shear is related to

the net tension strain. The AASHTO LRFD formula for the factor () applied to the

concrete shear strength is presented as Equation 2212H6.21.

Eq. 6.21

The angle of inclination () of diagonal shear cracking has an effect on the amount of

vertical shear resistance provided by transverse steel reinforcement (stirrups) within a

region of shear cracking. The AASHTO LRFD formula for this angle of inclination is

presented as Equation 2213H6.22.

Eq. 6.22

6.4.7.5 4389BCOMPONENTS OF VERTICAL SHEAR STRENGTH

The nominal vertical shear strength consists of both concrete and steel components of

shear resistance. These concrete and steel components of vertical shear strength are

calculated in accordance with Article 5.8.3.3 of AASHTO LRFD.

The shear strength (Vc) provided by the concrete is dependent upon the design

strength of the girder concrete (f ’c), the effective shear depth (dv), the width of girder web

(bv), and the net tension strain shear strength factor (). The formula for the shear

strength provided by the concrete, calculated in accordance with the general procedure of

Article 5.8.3.4.2 of AASHTO LRFD, is presented as Equation 2214H6.23.

313

– Eq. 6.23

The shear strength (Vs) provided by the vertical steel reinforcement is dependent

upon the amount of vertical steel reinforcement intersecting a diagonal shear crack. The

factors affecting the shear strength include the effective shear depth (dv), the angle of

inclination (), the spacing of reinforcement (s), the area of intersecting reinforcement

(Av) within one typical cross section containing vertical reinforcement, and the

assumption that the vertical reinforcement reaches a yield stress (fy) in response to

ultimate strength demands. The formula for the shear strength provided by vertical steel

reinforcement, calculated in accordance with the general procedure of Article 5.8.3.4.2

of AASHTO LRFD, is presented as Equation 2215H6.24.

Eq. 6.24

6.4.7.6 4390BNOMINAL VERTICAL SHEAR STRENGTH

The combined shear strengths provided by the concrete and vertical steel reinforcement

represents the nominal vertical shear strength, as shown in Equation 2216H6.25.

Eq. 6.25

An upper limit is applied to the nominal vertical shear strength, in accordance with

Article 5.8.3.3 of AASHTO LRFD, to ensure that the vertical steel reinforcement yields

prior to concrete crushing. This upper limit nominal shear strength formula is presented

as Equation 2217H6.26.

314

Eq. 6.26

6.4.7.7 4391BFACTORED STRENGTH FOR RESISTING SHEAR DEMAND

The resistance factor for the shear strength of normal weight reinforced concrete,

presented in Article 5.5.4.2 of AASHTO LRFD, reduces the nominal vertical shear

strength to be compared to the factored shear demand. To satisfy ultimate strength

design, the factored shear strength (ϕVn) must be greater than the factored shear demand

(Vu), as shown in Equation 2218H6.27.

Eq. 6.27

Additional longitudinal FRP reinforcement may increase the net tension strength in

response to shear demands, but will not greatly improve the nominal vertical shear

strength of critical cross-section locations. Thus, if the vertical shear strength does not

satisfy the vertical shear demand, an additional repair solution is necessary to provide

additional vertical shear strength. FRP reinforcement solutions for providing additional

vertical shear strength have been proposed by ACI Committee 440 and the NCHRP;

however, an additional repair solution for vertical shear reinforcement is not within the

scope of this thesis.

6.4.8 881BTENSILE STRENGTH

The combined demands of flexure and shear induce tension forces that must be resisted

by the flexural tension region of the cross section. It is conservative and appropriate to

assume that the concrete does not provide any tensile strength after cracking, and that all

315

tension demand must be satisfied with tension capacity provided by longitudinal

reinforcement. To determine the tension strength provided, Article 5.8.3.5 of AASHTO

LRFD may be modified with additional terms that account for resistance capacity

provided by externally bonded FRP reinforcement.

6.4.8.1 4392BNOMINAL STRENGTH FOR RESISTING TENSION

The nominal strength for resisting tension is provided by longitudinal reinforcement at

the flexural tension region of the cross section. Based on the typical difference in

modulus of elasticity for steel and laminate FRP, it is appropriate to assume that the steel

will yield before the FRP reaches an effective debonding strain limit. It is also

appropriate to assume that the effective debonding strain limit for the FRP will be

reached before concrete crushes. Thus, the nominal strength for resisting tension (Tn,prov)

is limited by the area of longitudinal steel that yields and the area of FRP that is

appropriately assumed to provide tension resistance until reaching the effective stress

limit, as shown in Equation 2219H6.28.

Eq. 6.28

6.4.8.2 4393BFACTORED TENSION DEMAND

The factored tension demand (Tn,req) in response to ultimate-strength demand is based on

the maximum factored shear and corresponding bending moment demands at the critical

location. The formula for required tension capacity, presented in Article 5.8.3.5 of

AASHTO LRFD, applies the individual resistance factors for flexure (ϕf) and shear (ϕv),

respectively, to compute the increased demand that corresponds to simultaneous

316

attainment of the nominal strengths in flexure and shear on the cross section rather than

applying a single tension resistance factor to reduce the computed tensile capacity, as

shown in Equation 2220H6.29.

Eq. 6.29

Vertical shear resistance provided by vertical reinforcement reduces the demand on

longitudinal reinforcement due to the diagonal nature of the critical flexure-shear crack.

However, AASHTO LRFD limits the contribution of the vertical shear resistance (Vs) to

no more than the factored vertical shear demand, as shown in Equation 2221H6.30.

Eq. 6.30

Because the shear and flexure resistance factors have already been applied to

determine the required nominal tension capacity, it is appropriate to not apply a reduction

factor to the nominal strength for tension resistance when checking for satisfaction of the

nominal tension capacity, as shown in Equation 2222H6.31.

Eq. 6.31

6.4.9 882BCHECK STRENGTHS OF EACH LOCATION WITH EQUAL LAYERS OF FRP

FRP reinforcement systems are installed with continuous sheets of FRP fabric. As the

number of FRP layers increases, the required development length increases and the

limiting effective strain (to prevent debonding) decreases. For this reason, the

performance at critical locations must be checked with the maximum number of layers

317

required of any other location, particularly with respect to net tension strain in response

to shear demands.

6.5 68BLENGTH OF FRP REINFORCEMENT INSTALLATION

As previously mentioned, the FRP reinforcement is installed as continuous sheets of

fabric that originate at the face of the continuity diaphragm and terminate beyond the

damaged region. When determining the length of reinforcement required, the original

reinforcement details of girder fabrication should be considered. The FRP reinforcement

should extend far enough along the girder so that forces can be transferred through the

concrete into the fully developed prestressing reinforcement beyond the damaged region.

For this reason, it is recommended that the FRP reinforcement extend (a) beyond the

debonded length of strands by a minimum distance equal to the development length of

the prestressed strands and (b) beyond any existing bottom flange cracks by the same

minimum distance.

According to AASHTO LRFD design provisions, the development length (d) for the

prestressed strands is dependent upon the stress required to provide the nominal flexural

or tension strength and the effective stress in the strands after accounting for time-

dependent losses. Considering typical values for these parameters, a conservative

approximation of the development length being equal to 180 strand diameters is

appropriate for determining the length of FRP reinforcement required. This

approximation is presented as Equation 2223H6.32.

Eq. 6.32

318

It is also recommended that the termination of the FRP reinforcement layers be

stepped down to prevent stress concentrations at the reinforcement termination location.

ACI 440.2R-08 recommends that each layer be terminated 6 in. earlier than the

underlying layer. When determining the recommended lengths of each layer of FRP

reinforcement, the initial (longest) layer of reinforcement should be designed to extend

the recommended distance mentioned previously.

6.6 69BANCHORAGE

The length of adequately bonded reinforcement between a termination location and

critical cross-section location directly affects performance of the reinforcement system.

Adequate stress transfer is required to limit stress concentrations that could result in bond

failure of the reinforcement system. Wherever possible, the FRP reinforcement should

(a) extend beyond the point where it is no longer required for strength and (b) have a

bonded length adequate to develop the effective FRP strain required at each critical

section.

Additional anchorage should be considered for regions that do not allow for desired

bonded lengths. There are various methods for providing additional anchorage to

increase the stress capacity at end regions with short bonded lengths; however, more

research of anchorage performance is recommended before selecting a specific anchorage

method to be implemented.

Recent research indicates that carbon fiber anchors may be useful for providing

supplemental anchorage at end regions (Ceroni and Pecce 2010; Niemitz et al. 2010;

Orton et al. 2008). These anchors, which are depicted in 2224HFigure 6.4, include FRP strips

that are bundles at one end and free at the other.

319

Figure 6.4: FRP fan anchorage system (Niemitz et al. 2010)

The bundled ends of the FRP strips are installed into a hole drilled into the structural

concrete. The free ends of the FRP strips are fanned out onto the first installed layer of

uncured FRP reinforcement. Epoxy is applied inside the drilled hole as well as on the

fanned FRP strips. Subsequent layers of reinforcement can then be installed on top of the

fanned FRP strips. The use of multiple smaller anchors to cover a large area is suggested

(Orton et al. 2008).

Research indicates that it is safe to estimate a debonding strength increase of about

25 percent for FRP reinforcement solutions that utilize this fanned FRP anchorage system

(Ceroni and Pecce 2010). However, until further research can be conducted to verify

anchorage performance in conjunction with wrapped FRP systems installed on in-service

320

bridge girders, it is recommended that the maximum FRP strain at all locations be limited

to be conservative and appropriate for regions of relatively short bonded lengths. It is

uncertain whether the depth of concrete cover available in these girders is adequate to

fully develop this type of anchor.

The amount of damage exhibited at the time of the repair is another factor that must

be considered during the determination of an acceptable strain capacity. FRP

reinforcement has the potential to debond due to behavior exhibited at existing crack

locations. These debonding conditions due to crack behavior include failure at one

specific crack location and failure of a shortened bonded region between two crack

locations. Additional anchorage provided by transverse wrapping of FRP reinforcement

around the bottom flange may be beneficial at locations of excessive cracking that has

extended through the bottom chord of the tension flange prior to repair. Additional

testing is required to verify this supplemental anchorage method.

6.7 70BSERVICE LIMIT STATE

Bridge testing has provided evidence that supports the conclusion that the structure

maintains some continuous behavior for service load conditions. Before any repair

methods had been implemented, a review of the I-565 bridge structures presented in

NCHRP Report 519 stated that the damaged bridge structures continued to perform as

designed (Miller et al. 2004). The strength-limit-state design assumption of simply

supported bridge behavior at failure is an even more conservative assumption for the

service limit state. After a bridge structure has been repaired to satisfy the strength-limit-

state demands, assuming simply supported behavior, the service-limit-state demands

321

should be appropriately satisfied with the same reinforcement, assuming any partial

continuity exists.

During post-repair testing, FRP tensile strains measured in response to ambient

thermal conditions were observed to be of greater magnitude than FRP tensile strains

measured in response to truck loads. The strains measured in response to ambient

temperature conditions were greater than the strains in response to truck loads because of

the non-stress-induced strain exhibited by the FRP material in response to ambient

temperature. Only the stress-induced strain associated with thermal conditions will have

an effect on service conditions of the structure.

To determine a critical diurnal strain range, it is conservative and appropriate to

assume that the two-span structure exhibits fully continuous behavior in response to

ambient thermal conditions. The formula for the tension-flange FRP strain expected in

response to ambient thermal conditions is presented as Equation 2225H5.36 in Section 2226H5.4.2.2.2.

The strain associated with the unrestrained expansion of FRP material due to thermal

conditions is not considered a stress-induced strain; however, the strain associated with

restraint of the temperature differential between the top of the deck and bottom of the

girder does induce stress-related strain in the FRP reinforcement. This stress-induced

strain, based on a change in temperature differential ([Th]) and the appropriate

concrete coefficient of thermal expansion (T), represents the FRP strain that must be

accounted for in response to diurnal ambient thermal conditions. The limiting effective

debonding strain of the FRP reinforcement shall exceed the stress-induced FRP

strain demand in response to thermal conditions, as shown in Equation 2227H6.33.

322

Eq. 6.33

6.8 71BDESIGN SUMMARY

An FRP reinforcement system that appropriately satisfies all design requirements may be

summarized after completing the design procedure. The design summary should include

the

Name of the FRP reinforcement product,

Assumed FRP material properties,

Fiber orientation in the installed FRP,

Number of layers required to satisfy ultimate strength demands,

Distance that each layer must extend,

Verification that service demands are satisfied, and

Assessment of supplemental anchorage requirements.

6.9 72BINSTALLATION RECOMMENDATIONS

An FRP reinforcement system that satisfies design requirements must be appropriately

installed to ensure that the assumed FRP reinforcement conditions remain valid.

Installation must be performed by skilled professionals that have experience following

the installation guidelines of the manufacturer for the selected FRP reinforcement

product. Before the FRP reinforcement can be installed, the structural substrate and

surface must be prepared for the installation process. After the substrate and surface are

prepared, the FRP reinforcement can then be appropriately installed. Specific installation

recommendations are presented in this section.

323

6.9.1 883BPREPARING FOR INSTALLATION

Prior to installation, preparation procedures must be performed in accordance with

manufacturer specifications. In addition to manufacturer guidelines, there are some

standard procedures that must be performed that may not be specifically recommended

by the manufacturer. These procedures include specific details with regard to crack

injection and surface preparation.

6.9.1.1 4394BADHESION TESTING

Prior to beginning surface preparation for installation, it is important to test the strength

of the structural concrete that the FRP reinforcement will be bonded to during

installation. Adhesion testing of the FRP reinforcement epoxy on the concrete surface is

required to ensure that the bond strength of the epoxy exceeds the tensile strength of the

concrete. Adhesion testing should be conducted in accordance with the requirements

given in ASTM D4541 (2009).

6.9.1.2 4395BCRACK INJECTION

Existing cracks should be injected with structural epoxy shortly prior to the installation of

FRP reinforcement. To minimize the possibility of new cracks forming prior to

installation, it is important to schedule the FRP installation for a time of day or year with

minimal temperature-induced stresses that could result in crack re-formation.

Cracks that are 0.01 in. (0.3 mm) and wider can adversely affect FRP reinforcement

performance, as stated by ACI 440.2R-08. The specific concern for this project is the

actual attainment of the computed concrete contribution (Vc) to the vertical shear

strength. The computation of Vc is based on an assumption that shear can be resisted

along the diagonal crack face due to aggregate interlock. This may not be true for overly

324

large crack widths. Thus, it is recommended that wide cracks be pressure injected with

structural epoxy prior to FRP installation. It is also recommended that smaller cracks be

resin injected or sealed to prevent corrosion of existing steel, especially on exterior

girders which are more exposed to aggressive environmental conditions. All crack

injection procedures are recommended to be performed in accordance with the general

procedures for epoxy injection presented by ACI Committee 224.1R-07 Causes,

Evaluation, and Repair of Cracks in Concrete Structures, referred to as ACI 224.1R-07

(ACI Committee 224 2007). The procedures presented by ACI 224.1R-07 include

Cleaning the crack,

Sealing the crack to prevent epoxy contained during injection,

Installation of entry and venting ports,

Mixing structural epoxy,

Pressure injecting the epoxy, and

Removing the surface seals after the epoxy has cured.

6.9.1.3 4396BSURFACE PREPARATION AND PROFILING

After the structural epoxy that has been injected into wide cracks has cured, the surface

must be prepared for installation. FRP installation recommendations of ACI 440.2R-08

state that surfaces must be prepared for adequate bonding conditions in accordance with

the recommendations of ACI Committee 546 Concrete Repair Guide, referred to as

ACI 546R-04 (ACI Committee 546 2004), and International Concrete Repair Institute

(ICRI) Committee 310 Guide for Surface Preparation for the Repair of Deteriorated

Concrete Resulting from Reinforcing Steel Corrosion, referred to as ICRI 310.1R-2008,

formerly ICRI 03730 (ICRI Committee 310 2008). Surface preparation specifications of

325

the NCHRP Report 609 Recommended Construction Specifications and Process Control

Manual for Repair and Retrofit of Concrete Structures Using Bonded FRP Composites,

referred to as NCHRP Report 609, also recommend consulting with ACI 546R-04 and

ICRI 310.1R-2008 for assuring proper surface preparation (Mirmiran et al. 2008).

General guidelines for surface preparation include the clearing of all irregularities,

unevenness, and sharp protrusions in the surface profile. It is recommended by NCHRP

Report 609 that these obstructions be grinded away to a smooth surface with less than

1/32 in. deviation. Any excess epoxy or sealer from the crack injection process should

also be removed to provide a smooth surface.

It is recommended by ACI 440.2R-08 that all corners be rounded or chamfered to a

minimum radius of 0.5 in. during surface preparation. The rounding of corners helps to

prevent stress concentrations in the FRP system and voids from forming between the FRP

system and the concrete. This stipulation is not critical for applications such as the

damage girders in this study in which the primary fiber orientation is parallel to the girder

corners. It is also recommended that corners that have been roughened during the

rounding process be smoothed with putty prior to installation.

After the removal of obstructions, the surface must be profiled to remove any

remaining unevenness in the surface. Surface profiling guidelines are presented by

ACI 546R-04 and ICRI 310.1R-2008. It is recommended by NCHRP Report 609 to

smooth any remaining bug holes, depressions, protrusions, and roughened corners using

putty made of epoxy resin mortar, or polymer cement mortar, with a cured strength

greater than the strength of the original concrete. It is also recommended that the

326

patching material be cured for a minimum of 7 days prior to installation of the FRP

reinforcement system.

To complete surface preparation, the bonding surface should be appropriately

cleaned. NCHRP Report 609 states that surface cleaning includes the removal of all

bond-inhibiting material such as dust, curing compounds, or paint coatings.

After completing surface cleaning, the moisture content of the surfaces must be

checked. ACI 440.2R-08 states that the clean bonding surfaces must be as dry as

recommended by the FRP system manufacturer to ensure appropriate resin penetration.

The moisture content can be evaluated in accordance with the requirements of ACI

Committee 503 Standard Specifications for Repairing Concrete with Epoxy Mortars,

referred to as ACI 503.4-92 (ACI Committee 503 1992).

6.9.2 884BFRP REINFORCEMENT INSTALLATION

Installation of the FRP reinforcement system should be conducted in accordance with

manufacturer specifications. General guidelines for the installation of FRP reinforcement

systems are also presented by ACI 440.2R-08 and NCHRP Report 609.

6.9.2.1 4397BEPOXY SATURATION

Due to the large surface area available for bonding around the perimeter of the girder

bottom flange, a wet-layup FRP reinforcement system is recommended for this

application. Wet-layup systems consist of dry FRP fabrics that are saturated with epoxy

during installation. The epoxy of the FRP reinforcement system should be mixed in

accordance with manufacturer specifications, which should include recommended batch

sizes, mixture ratios, mixing methods, mixing times, and pot-life limits

(ACI Committee 440 2008). The epoxy should be applied uniformly on the concrete

327

surface where the FRP is to be installed. The sheets of FRP fabric may also be saturated

prior to installation. Immediately following surface saturation, the first layer of FRP

reinforcement should be installed. Successive layers of epoxy and FRP should be

installed before the previously installed layers have cured (ACI Committee 440 2008).

6.9.2.2 4398BAPPLICATION OF FRP REINFORCEMENT

Prior to epoxy saturation, the sheets of dry FRP fabric should be cut to size, which

includes cutting different lengths for different layers, and modifying one end to

appropriately account for support conditions. FRP fabric materials should be handled in

accordance with manufacturer recommendations. Installers should ensure that the fabric

is cut and installed so that the primary fiber orientation matches the direction stipulated

on the contract drawings. Any signs of kinks, folds, or other forms of severe waviness

should be reported appropriately (ACI Committee 440 2008). The sequence of

installation should be documented prior to installation. If multiple sheets are required

within each layer, then fabric installation sequences should be designed to prevent the

alignment of seams in successive layers. FRP reinforcement should be applied without

entrapping air between the fabric and concrete surface or successive layers of fabric.

Any entrapped air should be released along the reinforcement in the direction parallel to

the fibers, and should never be rolled perpendicular to the fiber direction

(Mirmiran et al. 2008)

6.9.2.3 4399BPROTECTIVE COATING

Protective coatings should be applied to cured FRP reinforcement systems for improved

durability from environmental conditions, impact, fire, or vandalism. The protective

coating must be approved by the manufacturer and may be a polymer-modified portland

328

cement coating, or a polymer-based latex coating, with a final appearance that matches,

within reason, the color and texture of the adjacent concrete (Mirmiran et al. 2008).

6.9.2.4 4400BQUALITY CONTROL TESTING AND INSPECTION

The FRP reinforcement system and protective coating should be tested and inspected

during and after FRP installation according to ACI 440.2R-08, NCHRP Report 609, and

manufacturer recommendations. Topics of concern during inspections include

Representative tensile strength of FRP reinforcement samples,

Weather conditions such as temperature and humidity,

Surface temperature of the concrete,

Widths of cracks not injected with epoxy, and the

Location and size of any delaminations or air voids.

The tensile strength of a representative sample of the installed FRP reinforcement

system should be tested in accordance with the procedures of ASTM D3039 (2008). The

definition of a representative sample of FRP reinforcement for tensile testing should be

discussed and agreed upon prior to installation. The tension modulus of elasticity of the

FRP reinforcement affects the effective debonding strength of the installed repair system.

Supplemental anchorage may be recommended for FRP reinforcement materials that are

determined to have a tension modulus of elasticity greater than assumed during design.

FRP systems should finally be evaluated and accepted based on conformance or

nonconformance with the design drawings and specifications of the designer and

manufacturer. It is recommended that the selected installation contractor be qualified by

the FRP and epoxy manufacturer.

329

330

Chapter 7

11BSUMMARY AND CONCLUSIONS

7.1 73BPROJECT SUMMARY

Construction of the elevated portion of I-565 in Huntsville, Alabama began in January of

1988. The elevated highway is composed of simply supported steel or prestressed

concrete girders that were constructed to act as two-, three-, and four-span continuous

structures in response to post-construction loads. The elevated highway was completed

on March 27, 1991. In 1992, Alabama Department of Transportation (ALDOT) bridge

inspectors discovered large and unexpected cracks at the continuous end of many

prestressed concrete bulb-tee girders.

Analysis conducted by Gao (2003) of Auburn University confirmed ALDOT’s

suspicion that the damage was a result of the daily variation in temperature gradient

between the top of the bridge deck and the bottom of the concrete bridge girders.

Warmer temperatures of the bridge deck in relation to the bottom of bridge girders results

in upward deflections of the bridge spans, a behavior known as ―sun cambering.‖ Due to

restraint of these temperature-induced deformations at the continuous ends of girders,

substantial positive bending moments formed near these girder ends. Gao (2003) also

identified the contribution of the positive bending moment continuity reinforcement

details to the severity of the cracking.

331

Swenson (2003) of Auburn University examined how the cracks could affect bridge

performance. It was determined that the prestressed strands at the cracked girder ends are

likely inadequately developed as a result of cracking and may not provide dependable

shear and flexural resistance in these regions. Swenson designed a fiber-reinforced

polymer (FRP) reinforcement system to provide additional longitudinal reinforcement at

the damaged regions that would supply additional tension resistance and strengthen the

damaged girders.

In late spring of 2005, prior to installation of the recommended FRP reinforcement

system, Auburn University researchers measured behavioral bridge responses to service-

level truck loads. Four girders (Girders 7 and 8 of Northbound Spans 10 and 11) were

instrumented to measure deflections, crack-opening displacements, and surface strains of

the concrete during load testing (Fason 2009).

Following the pre-repair load testing, a finite-element model (FEM) of the

instrumented bridge structure was created for further analysis of the structural behavior of

the bridge in response to modeled load conditions. Measurements from the pre-repair

load tests were used to refine the pre-repair model. After the pre-repair model was

finalized, the recommended FRP reinforcement system was added to the model to allow

for analysis of the predicted post-repair behavior of the structure (Shapiro 2007).

In December of 2007, the recommended FRP reinforcement system was installed on

the eighteen girders of Northbound Spans 10 and 11. The project plans and

specifications were developed through the collaborative efforts of the Auburn University

Highway Research Center (AUHRC) and ALDOT.

332

This thesis includes the details of the post-repair performance monitoring and load

testing of the bridge conducted in the late spring of 2010. The majority of the sensors

used during the pre-repair load tests were maintained for post-repair testing, and

additional strain gages were installed on the surface of the FRP reinforcement. In

addition to repeating the pre-repair load testing procedures, the sensors measuring bridge

behavior were also monitored for roughly 24 hours to allow for analysis of the post-repair

structure’s behavioral response to a daily cycle in ambient thermal conditions.

Initially, the post-repair bridge behavior was compared to the behavior observed

during pre-repair testing. It was determined that, due to inconsistent support conditions

between pre- and post-repair testing, comparisons between the pre- and post-repair

measurements in response to truck loads are not appropriate for assessing the efficacy of

the repair system. Thus, the post-repair bridge test results were analyzed independently

to gain insight into the post-repair structural performance.

It was determined that an FRP reinforcement system is an effective repair solution for

damage conditions similar to those observed for the girders of I-565. An updated and

simplified FRP-strengthening design procedure that synthesizes the AASHTO LRFD

bridge design specifications and the FRP-strengthening recommendations of ACI

Committee 440 was developed. This procedure is explained to facilitate application to

FRP repair solutions for bridge structures that exhibit damage at the continuous end of

concrete girders. A design example was developed for the FRP strengthening of girders

in Northbound Spans 10 and 11 using the material properties of the FRP reinforcement

used for this project. Recommendations are also provided for appropriate installation of

an FRP reinforcement repair solution.

333

7.2 74BCONCLUSIONS

Conclusions stated within this thesis include AUHRC findings related to:

The FRP reinforcement installation process that occurred in December 2007,

Measured responses to service-level truck loads,

Theoretical responses to ambient thermal conditions,

Measured responses to ambient thermal conditions,

Performance of FRP reinforcement installed in December 2007, and

Design recommendations for the repair of other bridge structures exhibiting

damaged regions at the continuous ends of prestressed concrete girders.

7.2.1 885BFRP REINFORCEMENT INSTALLATION

The installation process in December 2007 indicated that plans and procedures

should be explicitly discussed with the contractor on site before beginning the

reinforcement installation process.

Proper quality control testing procedures should be discussed and monitored.

The contractor became noticeably more efficient with the installation process,

consistently installing four layers of FRP reinforcement in roughly one hour

during the repair of the second of the two spans.

7.2.2 886BOBSERVED RESPONSES TO TRUCK LOADS

Contact between false support bearing pads and bridge girders during pre-

repair testing resulted in additional load-bearing support conditions that

affected structural behavior observed during pre-repair testing.

334

Because of differences in support conditions, comparisons between pre- and

post-repair structural behavior measured during testing are not useful for

assessing the efficacy of the FRP reinforcement repair.

The crack closures measured at the COD gage on Girder 8 of Span 10 during

both pre- and post-repair load testing are an indication of potential out-of-

plane bending behavior in response to truck loads.

The post-repair structure exhibited an even greater loss of continuity in

response to live loads than indicated by the post-repair FEM model, which

was modeled to be less continuous than the original undamaged structure.

The overall bridge structure exhibited a nearly linear elastic response to

midspan truck positions during superposition testing.

The damaged regions of the bridge structure exhibited a localized nonlinear

response to midspan truck positions during superposition testing.

The magnitude of damage exhibited at a cracked region near the continuous

end of a concrete girder was observed to relate to the degree of continuity

degradation indicated for that girder line in response to live loads.

It is appropriate to assume that the bridge structure would exhibit simply

supported girder behavior in response to strength-limit-state design loads that

control the design of repair solutions.

Truck positions that induced the greatest shear demand on damaged regions

resulted in greatest measured FRP tensile demands.

335

Strength-limit-state demands for damaged regions should be determined in

accordance with AASHTO LRFD or another framework of consistent analysis

and design procedures at the discretion of the bridge owner.

7.2.3 887BTHEORETICAL RESPONSES TO AMBIENT THERMAL CONDITIONS

For design purposes, it is appropriate to assume that a bridge structure with

damaged continuous girder ends repaired with FRP reinforcement exhibits

fully continuous behavior in response to ambient thermal conditions.

The stress-induced strain expected in FRP reinforcement installed to repair

damaged continuous ends of multi-span continuous girder systems is

primarily a function of the structural concrete coefficient of thermal

expansion, height of the girder-deck composite cross section, variation of

temperature gradient conditions, and distance from the continuity diaphragm

to the damaged region.

For design purposes, it is conservative and simple to assume that the girder

stresses in the damaged region are approximately the same as the stresses at

the adjacent continuous support.

7.2.4 888BOBSERVED RESPONSES TO AMBIENT THERMAL CONDITIONS

Upward deflections measured in response to ambient thermal conditions

during post-repair bridge monitoring were similar to upward deflections

measured in response to solar effects during an ALDOT investigation of the

same spans in 1994.

336

Linear profiles of bottom-fiber concrete strains measured beyond damaged

regions indicate the bridge structure exhibited some preservation of

continuous behavior in response to thermal effects.

The slope of bottom-fiber concrete strain profiles were less than theoretically

expected of a fully continuous structure subjected to a linear temperature

gradient similar to the gradient measured by ALDOT in 1994, which indicates

that either the structure is not exhibiting fully continuous behavior or the

actual temperature gradient was less than theoretically assumed.

Maximum bottom-fiber FRP strains measured at crack locations in response to

thermal conditions were similar to the bottom-fiber FRP strain estimated in

response to the linear temperature gradient measured by ALDOT in 1994.

Simplified linear temperature gradient analysis can be used to effectively

estimate the tensile strain that an FRP repair system must resist due to daily

temperature fluctuations.

Ambient thermal conditions resulted in damaged region crack-opening

displacements and FRP surface strains roughly 3–4.5 times greater than

maximum respective measurements in response to service-level truck loads.

Comparisons of structural responses to thermal gradient effects and truck

loads support the conclusion that temperature effects caused initial cracking.

337

7.2.5 889BPERFORMANCE OF FRP REINFORCEMENT

The FRP reinforcement was observed to carry tension forces and effectively

serve as additional longitudinal reinforcement to service-level truck loads and

ambient thermal conditions.

During post-repair testing, the repair system had been in service for more than

2 years without exhibiting signs of debonding or other deterioration.

No additional signs of severe cracking were observed at the repaired region

since the installation of the FRP reinforcement.

The installed FRP reinforcement does not satisfy the design procedure

presented in Chapter 6 of this thesis, but the strength deficiency is less than

5 percent (on the basis of AASHTO LRFD strength-limit-state design loads).

The FRP reinforcement that has already been installed is acceptable, but

future design and installation should conform to guidelines and procedures

discussed in Chapter 6 of this thesis.

7.2.6 890BFRP DESIGN RECOMMENDATIONS

FRP reinforcement product can be selected for bridge girder repair using

guidelines presented by ACI 440.2R-08 and NCHRP Report 655.

FRP reinforcement systems can be designed to resist strength-limit-state

demands determined in accordance with AASHTO LRFD bridge design

specifications—or other strength-limit-state demands at the discretion of the

bridge owner.

338

Designed repair solutions should satisfy strength-limit-state demands at all

locations of (FRP or internal) reinforcement transitions assuming simply

supported girder behavior.

Debonding failure of FRP reinforcement systems due to tension strains

expected in response to combined shear and bending moment demands has

been observed to control the design of FRP reinforcement repair solutions.

A simplified formula (ld = 180db) for approximating prestressed strand

development lengths that begin at or beyond damaged regions has been

proposed as a guideline for determining the extent of FRP reinforcement.

Solutions for providing supplemental anchorage at locations of short available

bonded length require further research before they can be recommended.

Temperature demands do not need to be considered in conjunction with

strength-limit-state demands because temperature-induced deformations are

no longer restrained once the structure transitions to the simply supported

behavior recommended for strength-limit-state design.

7.2.7 891BFRP REINFORCEMENT INSTALLATION RECOMMENDATIONS

The contractor should have experience following the guidelines of the

manufacturer for the selected FRP and epoxy reinforcement product.

Existing cracks should be injected with structural epoxy prior to installation of

FRP reinforcement.

339

Structural substrates should be appropriately prepared for adequate bonding of

the FRP reinforcement to the concrete surface for the entire length installed.

Protective coatings should be applied to cured FRP reinforcement systems for

improved durability.

Quality control testing and inspections should be conducted during and

following the installation process to ensure proper installation.

340

Chapter 8

12BRECOMMENDATIONS

8.1 75BDESIGN OF FRP REINFORCEMENT REPAIR SOLUTIONS

FRP reinforcement can be utilized for the repair of prestressed concrete bridge girders

with damage conditions near continuous ends, similar to the damage observed near the

continuous ends of girders within Northbound Spans 10 and 11 of I-565 in Huntsville,

Alabama. The design procedure presented in Chapter 6 of this thesis has been

formulated in accordance with specifications of AASHTO LRFD, NCHRP Report 655

(Zureick et al. 2010), and ACI 440.2R-08.

An FRP reinforcement system designed in accordance with the guidelines presented

in this thesis provides adequate tension reinforcement for the resistance of strength-limit-

state demands of combined shear and flexure. The FRP repair solution also provides

resistance to the tension stresses induced by daily temperature variations on the

continuous structure. The design procedure detailed in this thesis includes guidelines for

the determination of

An appropriate FRP reinforcement product,

Critical cross-section locations,

Critical load conditions for those locations,

Material and dimensional properties at those locations,

341

Layers of FRP reinforcement required to satisfy strength demands, and

Length of FRP reinforcement required for appropriate development of

prestressed strands.

8.2 76BINSTALLATION OF FRP REINFORCEMENT SYSTEMS

FRP reinforcement installation procedures should be performed in accordance with the

specifications of the manufacturer. Guidelines presented in Chapter 6 of this thesis for

ensuring proper FRP reinforcement installation include guidelines that are also presented

in NCHRP Report 609 (Miller et al. 2008) and ACI 440.2R-08. These guidelines include

recommended procedures for

Crack injection,

Surface preparation,

FRP reinforcement installation, and

Quality control inspection and testing.

8.3 77BNORTHBOUND SPANS 10 AND 11 OF I-565

The FRP reinforcement system installed on Northbound Spans 10 and 11 of I-565 in

December 2007 was designed by Auburn University researchers (Swenson 2003). The

FRP reinforcement was designed to resist tension forces that were predicted with strut-

and-tie models. The reinforcement system was also designed in accordance with the

effective debonding strain (εfe) specifications presented by ACI 440.2R-02, which have

since been updated to reflect the findings of more recent research as presented by

ACI 440.2R-08.

342

The design procedure presented in Chapter 6 of this thesis has been formulated in

accordance with AASHTO LRFD specifications (AASHTO 2010) and the updated

effective debonding strain specifications of ACI 440.2R-08. An updated FRP

reinforcement system design example is presented in Appendix N of this thesis.

The FRP reinforcement systems that were installed on Spans 10 and 11 in

December 2007 do not satisfy the updated design recommendation, but installation of an

additional layer of reinforcement may not be absolutely necessary. The limiting effective

debonding strain (εfe < 0.004 in./in.) controls the recommendation of 5 layers of

reinforcement instead of 4 layers. The current installation of 4 layers satisfies strength

requirements at the interior face of the bearing pad, but results in a strength deficiency of

less than 5 percent at the termination of the continuity reinforcement in response to

factored shear demand.

The installed 4 layers of reinforcement nearly satisfy the requirements of the updated

design recommendations of this thesis. The small computed strength deficiency is based

on full strength-limit-state AASHTO LRFD design loads for new construction in

conjunction with the conservative limiting effective debonding strain of the FRP

reinforcement. The length of FRP reinforcement currently installed allows for adequate

development of prestressed strands beyond the primary crack locations in these particular

spans. It is unknown if an additionally installed fifth layer of reinforcement would

perform as expected when bonded to previously installed FRP reinforcement that has

been fully cured. Surface preparation procedures required for proper installation of

additional FRP reinforcement may also be detrimental to the integrity of the existing FRP

reinforcement. Whether or not the computed strength discrepancy justifies the cost,

343

effort, and uncertainty associated with installation of an additional layer of FRP in

Spans 10 and 11 is a decision best left to the discretion of ALDOT after consideration of

these factors in light of the department’s established maintenance philosophy. On the

other hand, FRP reinforcement configurations for new repairs should be designed to

satisfy the design recommendations proposed within this thesis.

8.4 78BRECOMMENDATIONS FOR FURTHER RESEARCH

Further research would be beneficial to provide a better understanding of the behavioral

responses observed during the testing of Northbound Spans 10 and 11. Further testing is

also recommended to gain a better understanding of the performance of FRP composite

material as a reinforcement solution.

8.4.1 892BIN-SERVICE LOAD TESTING

Truck positions that resulted in large shear demand at the damaged region resulted in

significant reinforcement tension demand. Future load testing of structures that exhibit

damage regions similar to those of Spans 10 and 11 should focus on these high shear

demand truck positions. Superposition testing should also be conducted with truck

positions that result in significant damaged-region tension demand.

For future pre- and post-repair testing of in-service bridge structures, it is

recommended that variables which may have an effect on bridge behavior during testing

be limited to allow for more appropriate comparisons of pre- and post-repair measured

bridge behavior. Variables observed during the research discussed within this thesis that

had an effect on the ability to assess the efficacy of the installed FRP reinforcement

repair system by directly comparing pre- and post-repair measurements include

344

False supports that were unintentionally load-bearing supports during pre-

repair testing but were not load-bearing supports during post-repair testing,

Weather conditions that resulted in significantly cooler ambient temperatures

during pre-repair testing compared to the temperatures of post-repair testing,

Vehicles with different dimensions that required modifications to load block

configurations during both pre- and post-repair testing,

Time elapsed between pre-repair testing and reinforcement installation, and

Time elapsed between reinforcement installation and post-repair testing.

8.4.2 893BIN-SERVICE BRIDGE MONITORING

Bridge monitoring provided information that supports the conclusion that temperature

effects are the primary cause of cracking observed in damaged regions near continuous

ends of prestressed concrete bridge girders. For future in-service load testing of pre- and

post-repair conditions of bridge structures, it is recommended that bridge monitoring be

conducted during the days encompassing both the pre- and post-repair in-service load

testing. It is also recommended that bridge monitoring be conducted for more than one

daily cycle during both pre- and post-repair testing. Additionally, it is recommended to

measure ambient, deck, and girder temperatures during future bridge monitoring tests.

8.4.3 894BLABORATORY TESTING

The limiting effective debonding strain (εfe < 0.004 in./in.) specified by ACI 440.2R-08 is

a conservative assumption that has been observed to frequently control the amount of

FRP required when executing the design procedure recommended in Chapter 6 of this

thesis. This conservative assumption is recommended until further testing can validate

345

that higher effective debonding strains can be achieved consistently and concervatively.

Controlled laboratory testing of longitudinal FRP reinforcement system that wraps

around the tension flange at one end of a simply supported girder could provide insight

into the actual performance of this repair system near failure (strength limit state)

conditions. This testing would require that a girder sustain ―controlled‖ damage near one

end of the girder before installing the FRP reinforcement.

Laboratory-controlled testing of solutions for providing additional FRP reinforcement

anchorage for locations of short bonded length between critical cross-section locations

and FRP reinforcement termination is recommended before permitting the installation of

FRP reinforcement systems that require supplemental anchorage.

The design effective debonding strain in areas of short bonded lengths is a function of

the design modulus of elascticity of the composite FRP reinforcement. For design

purposes, it is recommended to assume the design modulus of elasticity of the composite

FRP reinforcement product reported by the manufacturer; however, testing of

representative samples may indicate that the installed product exhibits more stiffness than

originally assumed during design. To better understand the ramifications of this issue,

laboratory testing is recommended to assess the effective debonding strain for FRP

reinforcement products with varying stiffnesses determined in accordance with the

procedures (ASTM D3039 2008) recommended for testing representative samples of

installed FRP reinforcement systems.

Further testing of FRP reinforcement is recommended to better understand the

performance of this composite material; however, the design procedure recommended in

this thesis provides appropriately conservative specifications for the design of repair

346

solutions similar to the reinforcement systems installed to repair the damaged girders of

Northbound Spans 10 and 11 of I-565 in Huntsville, Alabama.

347

13BREFERENCES

AASHTO. 2002. AASHTO LRFD Bridge design specifications: Customary U.S. Units.

Second Edition. Washington, D.C.: American Association of State Highway and

Transportation Officials (AASHTO).

AASHTO. 2010. AASHTO LRFD Bridge design specifications: Customary U.S. Units.

Fifth Edition. Washington, D.C.: American Association of State Highway and

Transportation Officials (AASHTO).

ACI Committee 224. 2007. Causes, evaluation, and repair of cracks in concrete

structures. ACI 224.1R-07. Farmington Hills, MI: American Concrete Institute

(ACI).

ACI Committee 318. 2002. Building code requirements for structural concrete and

commentary. ACI 318R-02. Farmington Hills, MI: American Concrete Institute

(ACI).

ACI Committee 318. 2008. Building code requirements for structural concrete and

commentary. ACI 318-08. Farmington Hills, MI: American Concrete Institute (ACI).

ACI Committee 440. 2008. Guide for the design and construction of externally bonded

FRP systems for strengthening concrete structures. ACI 440.2R-08.

Farmington Hills, MI: American Concrete Institute (ACI).

ACI Committee 503. 1992. Standard specifications for repairing concrete with epoxy

mortars. ACI 503.4-92. Farmington Hills, MI: American Concrete Institute (ACI).

348

ACI Committee 546. 2004. Concrete repair guide. ACI 546R-04. Farmington Hills, MI:

American Concrete Institute (ACI).

Alabama Department of Transportation (ALDOT). 1988. Construction plans for Project

ID-565-5(21)358. Montgomery, AL: Alabama Department of Transportation

(ALDOT).

Alabama Department of Transportation (ALDOT). 1994. Cracks in precast prestressed

bulb tee girders on Structure No.’s I-565-45-11.5 A. and B. on I-565 in Huntsville,

Alabama. Report and attachments (A–L). Montgomery, AL: Alabama Department of

Transportation (ALDOT).

ASTM Standard D3039. 2008. Test method for tensile properties of polymer matrix

composite materials. ASTM D3039-08. West Conshohocken, PA: ASTM

International.

ASTM Standard D4065. 2006. Practice for plastics: dynamic mechanical properties:

determination and report of procedures. ASTM D4065-06. West Conshohocken, PA:

ASTM International.

ASTM Standard D4541. 2009. Standard test method for pull-off strength of coatings

using portable adhesion testers. ASTM D4541-09. West Conshohocken, PA: ASTM

International.

Barnes, R. W., K. S. Swenson, N. Gao, A. K. Schindler, and W. E. Fason. 2006.

Cracking and repair of prestressed concrete bridge girders made continuous for live

loads. In the Proceedings of Structural Faults and Repair, Eleventh International

Conference: Edinburgh, Scotland. 13–15 June 2006.

Ceroni, F. and M. Pecce. 2010. Evaluation of bond strength in concrete elements

externally reinforced with CFRP sheets and anchoring devices. ASCE Journal of

Composites for Construction 14 (5): 521–530.

Fason, W. E. 2009. Static load testing of a damaged, continuous prestressed concrete

bridge. M.S. thesis. Auburn, AL: Auburn University.

349

Fyfe Co. Tyfo Fiberwrap Systems. 2010. Tyfo SCH-41 Composite using Tyfo S Epoxy

data sheet. San Diego, CA: Fyfe Co. LLC.

Gao, N. 2003. Investigation of cracking in prestressed girders made continuous for live

load. M.S. thesis. Auburn, AL: Auburn University.

Hadzor, T. J. 2011. Acoustic emission testing of repaired prestressed concrete bridge

girders. M.S. thesis. Auburn, AL: Auburn University.

ICRI Committee 310. 2008. Guide for surface preparation for the repair of deteriorated

concrete resulting from reinforcing steel corrosion. ICRI 310.1R-2008.

Farmington Hills, MI: International Concrete Repair Institute (ICRI).

ISO/IEC Technical Committee. 2005. General requirements for the competence of testing

and calibration laboratories (ISO/IEC 17025). Geneva, Switzerland: International

Organization for Standardization (ISO) and International Electrotechnical

Commission (IEC).

Ma, Z., X. Huo, M. K. Tadros, and M. Baishya. 1998. Restraint moments in

precast/prestressed concrete continuous bridges. PCI Journal 43 (6): 40–57.

Miller, R. A., R. Castrodale, A. Mirmiran, and M. Hastak. 2004. Connection of simple-

span precast concrete girders for continuity. NCHRP Report 519. Washington, D.C.:

Transportation Research Board (TRB).

Mirmiran, A., M. Shahawy, A. Nanni, V. Karbhari, and B. Yalim, and A. S. Kalayci.

2008. Recommended construction specifications and process control manual for

repair and retrofit of concrete structures using bonded FRP composites.

NCHRP Report 609. Washington, D.C.: Transportation Research Board (TRB).

National Oceanic and Atmospheric Administration (NOAA). 2005a.

Local Climatological Data: Huntsville, AL: May 2005. Rocket Center, WV:

National Climatic Data Center (NCDC).

350

National Oceanic and Atmospheric Administration (NOAA). 2005b.

Local Climatological Data: Huntsville, AL: June 2005. Rocket Center, WV:

National Climatic Data Center (NCDC).

National Oceanic and Atmospheric Administration (NOAA). 2008. Local Climatological

Data: Huntsville, AL: December 2007. Rocket Center, WV: National Climatic Data

Center (NCDC).

National Oceanic and Atmospheric Administration (NOAA). 2010. Local Climatological

Data: Huntsville, AL: May 2010. Rocket Center, WV: National Climatic Data Center

(NCDC).

Niemitz, C. W., R. James, and S. F. Breña. 2010. Experimental behavior of carbon fiber-

reinforced polymer (CFRP) sheets attached to concrete surfaces using CRFP anchors.

ASCE Journal of Composites for Construction 14 (2): 185–194.

Orton, S. L., J. O. Jirsa, and O. Bayrak. 2008. Design considerations of carbon fiber

anchors. ASCE Journal of Composites for Construction 12 (6): 608–616.

Potgieter, I. C. and W. L. Gamble. 1989. Nonlinear temperature distributions in bridges at

different locations in the United States. PCI Journal 34 (4): 80–103.

Shapiro, K. A. 2007. Finite-element modeling of a damaged prestressed concrete bridge.

M.S. thesis. Auburn, AL: Auburn University.

Swenson, K. S. 2003. Feasibility of externally bonded FRP reinforcement for repair of

cracked prestressed concrete girders. M.S. thesis. Auburn, AL: Auburn University.

Swenson, K. S. and R. W. Barnes. 2007. Feasibility of externally bonded FRP

reinforcement for repair of cracked prestressed concrete girders, I-565, Huntsville

Alabama. Report IR-07-02. Auburn, AL: Auburn University Highway Research

Center (AUHRC).

Teng, J. G., J. F. Chen, S. T. Smith, and L. Lam. 2002. FRP-strengthened RC structures.

Chichester, West Sussex, UK: John Wiley and Sons.

351

Teng, J. G., S. T. Smith, J. Yao, and J.F. Chen. 2003. Intermediate crack induced

debonding in RC beams and slabs. Construction and Building Materials 17 (6-7):

447–462.

TML. 2011. PI displacement transducer data sheet. TML manual: strain gauge-type

transducers. TML Pam E-701B. Tokyo, Japan: TML Tokyo Sokki Kenkyujo Co.,

Ltd.

Vishay Precision Group. 2010. Strain gage selection: criteria, procedures, and

recommendations. Tech Note TN-505-4. Raleigh, NC. Vishay Precision Group.

Zureick, A.-H., B. R. Ellingwood, A. S. Nowak, D. R. Mertz, and T. C. Triantafillou.

2010. Recommended guide specification for the design of externally bonded FRP

systems for repair and strengthening of concrete bridge elements. NCHRP Report

655. Washington, D.C.: Transportation Research Board (TRB).

352

Appendix A

14BABBREVIATIONS AND NOTATION

AASHTO American Association of State Highway and Transportation Officials

ACI American Concrete Institute

AE acoustic emissions

ALDOT Alabama Department of Transportation

ASTM American Society for Testing and Materials

AUHRC Auburn University Highway Research Center

BT bulb-tee

CFRP carbon fiber-reinforced polymer

ERSG electrical-resistance strain gauge

FEM finite-element modeling

FRP fiber-reinforced polymer

I-565 Interstate Highway 565

ICRI International Concrete Repair Institute

IEC International Electrotechnical Commission

ISO International Organization for Standardization

LRFD load and resistance factor design

NCDC National Climatic Data Center

NCHRP National Cooperative Highway Research Program

NOAA National Oceanic and Atmospheric Administration

PCI Precast/Prestressed Concrete Institute

RC reinforced concrete

TRB Transportation Research Board

353

a depth of compression zone

A area

Af area of FRP reinforcement

Aps area of prestressed strand reinforcement

As area of steel reinforcement

Av area of vertical steel reinforcement

b width of compression zone

bf width (perimeter) of FRP reinforcement

bv width of girder web

CE environmental reduction factor for composites

de effective depth from top of cross section

df depth to centroid of FRP reinforcement

ds depth to centroid of longitudinal steel reinforcement

dv effective shear depth

E modulus of elasticity

Ef modulus of elasticity—FRP reinforcement

Ep modulus of elasticity—prestressed strand

Es modulus of elasticity—steel reinforcement

f’c design compressive strength of concrete

fbot stress at the bottom of the cross section

ffe effective debonding stress of FRP reinforcement system

fpo modulus of elasticity of prestressing strands multiplied by the

locked-in difference in strain between the prestressing strands and

the surrounding concrete

fy tension yield strength

h height of the cross section

I moment of inertia of the cross section

L span length

Lb bonded length of FRP reinforcement

d development length of prestressed strand

Lfd development length of FRP reinforcement

354

M bending moment demand

Mn nominal bending moment capacity

Mu factored bending moment demand

n layers of FRP-epoxy composite

P restraint force due to thermal gradient

s spacing of reinforcement

T temperature; tension demand

Tbot temperature of girder bottom flange

tf thickness of one layer of FRP fabric

tf,n nominal thickness of one layer of FRP-epoxy composite

Tg glass transition temperature

Tmax,design maximum design temperature based on geographic location

Tn,prov nominal longitudinal tension capacity provided

Tn,req nominal longitudinal tension capacity required

Ttop temperature of bridge deck

Th temperature gradient—difference between Ttop and Tbot

Th) change in temperature gradient with respect to time

V shear demand

Vc shear capacity provided by concrete

Vn nominal shear capacity

Vp shear capacity provided by prestressed reinforcement

Vs shear capacity provided by steel reinforcement

Vu factored shear demand

x distance along girder from continuous support

yt distance from neutral axis to the top of the cross section

ybot distance from neutral axis to the bottom of the cross section

ycr,bot distance from cracked section neutral axis to the

bottom of the cross section

yf location of centroid of FRP reinforcement

yps location of centroid of prestressed strand reinforcement

ys location of centroid of steel reinforcement

355

T coefficient of thermal expansion—concrete

FRP coefficient of thermal expansion—FRP

factor relating effect of longitudinal strain on the shear capacity,

as indicated by the ability of diagonally cracked concrete to

transmit tension

L effective debonding strain reduction factor for locations of short

bonded length

deflection

fd debonding strain of FRP reinforcement system

fe effective debonding strain of FRP reinforcement system

fu tension failure strain of FRP

s strain in FRP due to thermal expansion

T,FRP strain in FRP due to thermal expansion

Ø curvature

ØT curvature in response to unrestrained temperature gradient effects

ϕ resistance factor

ϕf resistance factor for flexure

ϕv resistance factor for shear

θ angle of inclination for shear cracking

356

Appendix B

15BMULTIPOSITION LOAD TEST—GRAPHICAL RESULTS

357

B.1 79BLANE A

B.1.1 895BCRACK-OPENING DISPLACEMENTS

Figure B.1: Crack-opening displacements—A1

-0.05

-0.04

-0.03

-0.02

-0.01

0.00

0.01

0.02

0.03

0.04

0.05

-900 -700 -500 -300 -100 100 300 500 700 900

Cra

ck-O

pen

ing

Dis

pla

cem

ent

(mm

)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

358

Figure B.2: Crack-opening displacements—A2

Figure B.3: Crack-opening displacements—A3

-0.05

-0.04

-0.03

-0.02

-0.01

0.00

0.01

0.02

0.03

0.04

0.05

-900 -700 -500 -300 -100 100 300 500 700 900

Cra

ck-O

pen

ing

Dis

pla

cem

ent

(mm

)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

-0.05

-0.04

-0.03

-0.02

-0.01

0.00

0.01

0.02

0.03

0.04

0.05

-900 -700 -500 -300 -100 100 300 500 700 900

Cra

ck-O

pen

ing

Dis

pla

cem

ent

(mm

)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

359

Figure B.4: Crack-opening displacements—A4

Figure B.5: Crack-opening displacements—A5

-0.05

-0.04

-0.03

-0.02

-0.01

0.00

0.01

0.02

0.03

0.04

0.05

-900 -700 -500 -300 -100 100 300 500 700 900

Cra

ck-O

pen

ing

Dis

pla

cem

ent

(mm

)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

-0.05

-0.04

-0.03

-0.02

-0.01

0.00

0.01

0.02

0.03

0.04

0.05

-900 -700 -500 -300 -100 100 300 500 700 900

Cra

ck-O

pen

ing

Dis

pla

cem

ent

(mm

)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

360

Figure B.6: Crack-opening displacements—A6

Figure B.7: Crack-opening displacements—A7

-0.05

-0.04

-0.03

-0.02

-0.01

0.00

0.01

0.02

0.03

0.04

0.05

-900 -700 -500 -300 -100 100 300 500 700 900

Cra

ck-O

pen

ing

Dis

pla

cem

ent

(mm

)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

-0.05

-0.04

-0.03

-0.02

-0.01

0.00

0.01

0.02

0.03

0.04

0.05

-900 -700 -500 -300 -100 100 300 500 700 900

Cra

ck-O

pen

ing

Dis

pla

cem

ent

(mm

)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

361

Figure B.8: Crack-opening displacements—A8

Figure B.9: Crack-opening displacements—A9

-0.05

-0.04

-0.03

-0.02

-0.01

0.00

0.01

0.02

0.03

0.04

0.05

-900 -700 -500 -300 -100 100 300 500 700 900

Cra

ck-O

pen

ing

Dis

pla

cem

ent

(mm

)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

-0.05

-0.04

-0.03

-0.02

-0.01

0.00

0.01

0.02

0.03

0.04

0.05

-900 -700 -500 -300 -100 100 300 500 700 900

Cra

ck-O

pen

ing

Dis

pla

cem

ent

(mm

)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

362

B.1.2 896BDEFLECTIONS

Figure B.10: Deflections—A1

-0.4

-0.3

-0.2

-0.1

0.0

0.1

-900 -700 -500 -300 -100 100 300 500 700 900

Bo

tto

m-F

iber

Def

lect

ion

(in

.)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

363

Figure B.11: Deflections—A2

Figure B.12: Deflections—A3

-0.4

-0.3

-0.2

-0.1

0.0

0.1

-900 -700 -500 -300 -100 100 300 500 700 900

Bo

tto

m-F

iber

Def

lect

ion

(in

.)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

-0.4

-0.3

-0.2

-0.1

0.0

0.1

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er D

efle

ctio

n (

in.)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

364

Figure B.13: Deflections—A4

Figure B.14: Deflections—A5

-0.4

-0.3

-0.2

-0.1

0.0

0.1

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er D

efle

ctio

n (

in.)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

-0.4

-0.3

-0.2

-0.1

0.0

0.1

-900 -700 -500 -300 -100 100 300 500 700 900

Bo

tto

m-F

iber

Def

lect

ion

(in

.)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

365

Figure B.15: Deflections—A6

Figure B.16: Deflections—A7

-0.4

-0.3

-0.2

-0.1

0.0

0.1

-900 -700 -500 -300 -100 100 300 500 700 900

Bo

tto

m-F

iber

Def

lect

ion

(in

.)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

-0.4

-0.3

-0.2

-0.1

0.0

0.1

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er D

efle

ctio

n (

in.)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

366

Figure B.17: Deflections—A8

Figure B.18: Deflections—A9

-0.4

-0.3

-0.2

-0.1

0.0

0.1

-900 -700 -500 -300 -100 100 300 500 700 900

Bo

tto

m-F

iber

Def

lect

ion

(in

.)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

-0.4

-0.3

-0.2

-0.1

0.0

0.1

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er D

efle

ctio

n (

in.)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

367

B.1.3 897BCROSS-SECTION STRAINS

B.1.3.1 4401BCROSS-SECTION STRAINS—GIRDER 7

B.1.3.1.1 STRAINS—GIRDER 7—CROSS SECTION 1

Figure B.19: Strains—Girder 7—Section 1—A1

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

368

Figure B.20: Strains—Girder 7—Section 1—A2

Figure B.21: Strains—Girder 7—Section 1—A3

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

369

Figure B.22: Strains—Girder 7—Section 1—A4

Figure B.23: Strains—Girder 7—Section 1—A5

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

370

Figure B.24: Strains—Girder 7—Section 1—A6

Figure B.25: Strains—Girder 7—Section 1—A7

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

371

Figure B.26: Strains—Girder 7—Section 1—A8

Figure B.27: Strains—Girder 7—Section 1—A9

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

372

B.1.3.1.2 STRAINS—GIRDER 7—CROSS SECTION 2

Figure B.28: Strains—Girder 7—Section 2—A1

0

5

10

15

20

25

30

-160 -140 -120 -100 -80 -60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bott

om

of

Gir

der

(in

.)

Strain (x10-6 in./in.)

Concrete

FRP

373

Figure B.29: Strains—Girder 7—Section 2—A2

Figure B.30: Strains—Girder 7—Section 2—A3

0

5

10

15

20

25

30

-160 -140 -120 -100 -80 -60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bott

om

of

Gir

der

(in

.)

Strain (x10-6 in./in.)

Concrete

FRP

0

5

10

15

20

25

30

-160 -140 -120 -100 -80 -60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bott

om

of

Gir

der

(in

.)

Strain (x10-6 in./in.)

Concrete

FRP

374

Figure B.31: Strains—Girder 7—Section 2—A4

Figure B.32: Strains—Girder 7—Section 2—A5

0

5

10

15

20

25

30

-160 -140 -120 -100 -80 -60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bott

om

of

Gir

der

(in

.)

Strain (x10-6 in./in.)

Concrete

FRP

0

5

10

15

20

25

30

-160 -140 -120 -100 -80 -60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bott

om

of

Gir

der

(in

.)

Strain (x10-6 in./in.)

Concrete

FRP

375

Figure B.33: Strains—Girder 7—Section 2—A6

Figure B.34: Strains—Girder 7—Section 2—A7

0

5

10

15

20

25

30

-160 -140 -120 -100 -80 -60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bott

om

of

Gir

der

(in

.)

Strain (x10-6 in./in.)

Concrete

FRP

0

5

10

15

20

25

30

-160 -140 -120 -100 -80 -60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bott

om

of

Gir

der

(in

.)

Strain (x10-6 in./in.)

Concrete

FRP

376

Figure B.35: Strains—Girder 7—Section 2—A8

Figure B.36: Strains—Girder 7—Section 2—A9

0

5

10

15

20

25

30

-160 -140 -120 -100 -80 -60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bott

om

of

Gir

der

(in

.)

Strain (x10-6 in./in.)

Concrete

FRP

0

5

10

15

20

25

30

-160 -140 -120 -100 -80 -60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bott

om

of

Gir

der

(in

.)

Strain (x10-6 in./in.)

Concrete

FRP

377

B.1.3.1.3 STRAINS—GIRDER 7—CROSS SECTION 3

Figure B.37: Strains—Girder 7—Section 3—A1

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

378

Figure B.38: Strains—Girder 7—Section 3—A2

Figure B.39: Strains—Girder 7—Section 3—A3

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

379

Figure B.40: Strains—Girder 7—Section 3—A4

Figure B.41: Strains—Girder 7—Section 3—A5

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

380

Figure B.42: Strains—Girder 7—Section 3—A6

Figure B.43: Strains—Girder 7—Section 3—A7

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

381

Figure B.44: Strains—Girder 7—Section 3—A8

Figure B.45: Strains—Girder 7—Section 3—A9

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

382

B.1.3.1.4 STRAINS—GIRDER 7—CROSS SECTION 4

Figure B.46: Strains—Girder 7—Section 4—A1

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

383

Figure B.47: Strains—Girder 7—Section 4—A2

Figure B.48: Strains—Girder 7—Section 4—A3

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bott

om

of

Gir

der

(in

.)

Strain (x10-6 in./in.)

Concrete

FRP

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bott

om

of

Gir

der

(in

.)

Strain (x10-6 in./in.)

Concrete

FRP

384

Figure B.49: Strains—Girder 7—Section 4—A4

Figure B.50: Strains—Girder 7—Section 4—A5

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bott

om

of

Gir

der

(in

.)

Strain (x10-6 in./in.)

Concrete

FRP

385

Figure B.51: Strains—Girder 7—Section 4—A6

Figure B.52: Strains—Girder 7—Section 4—A7

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bott

om

of

Gir

der

(in

.)

Strain (x10-6 in./in.)

Concrete

FRP

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

386

Figure B.53: Strains—Girder 7—Section 4—A8

Figure B.54: Strains—Girder 7—Section 4—A9

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

387

B.1.3.2 4402BCROSS-SECTION STRAINS—GIRDER 8

B.1.3.2.1 STRAINS—GIRDER 8—CROSS SECTION 1

Figure B.55: Strains—Girder 8—Section 1—A1

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

388

Figure B.56: Strains—Girder 8—Section 1—A2

Figure B.57: Strains—Girder 8—Section 1—A3

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

389

Figure B.58: Strains—Girder 8—Section 1—A4

Figure B.59: Strains—Girder 8—Section 1—A5

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

390

Figure B.60: Strains—Girder 8—Section 1—A6

Figure B.61: Strains—Girder 8—Section 1—A7

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

391

Figure B.62: Strains—Girder 8—Section 1—A8

Figure B.63: Strains—Girder 8—Section 1—A9

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

392

B.1.3.2.2 STRAINS—GIRDER 8—CROSS SECTION 2

Figure B.64: Strains—Girder 8—Section 2—A1

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

393

Figure B.65: Strains—Girder 8—Section 2—A2

Figure B.66: Strains—Girder 8—Section 2—A3

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

394

Figure B.67: Strains—Girder 8—Section 2—A4

Figure B.68: Strains—Girder 8—Section 2—A5

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

395

Figure B.69: Strains—Girder 8—Section 2—A6

Figure B.70: Strains—Girder 8—Section 2—A7

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

396

Figure B.71: Strains—Girder 8—Section 2—A8

Figure B.72: Strains—Girder 8—Section 2—A9

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

397

B.1.3.2.3 STRAINS—GIRDER 8—CROSS SECTION 3

Figure B.73: Strains—Girder 8—Section 3—A1

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

398

Figure B.74: Strains—Girder 8—Section 3—A2

Figure B.75: Strains—Girder 8—Section 3—A3

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

399

Figure B.76: Strains—Girder 8—Section 3—A4

Figure B.77: Strains—Girder 8—Section 3—A5

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

400

Figure B.78: Strains—Girder 8—Section 3—A6

Figure B.79: Strains—Girder 8—Section 3—A7

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

401

Figure B.80: Strains—Girder 8—Section 3—A8

Figure B.81: Strains—Girder 8—Section 3—A9

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

402

B.1.3.2.4 STRAINS—GIRDER 8—CROSS SECTION 4

Figure B.82: Strains—Girder 8—Section 4—A1

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

403

Figure B.83: Strains—Girder 8—Section 4—A2

Figure B.84: Strains—Girder 8—Section 4—A3

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

404

Figure B.85: Strains—Girder 8—Section 4—A4

Figure B.86: Strains—Girder 8—Section 4—A5

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

405

Figure B.87: Strains—Girder 8—Section 4—A6

Figure B.88: Strains—Girder 8—Section 4—A7

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

406

Figure B.89: Strains—Girder 8—Section 4—A8

Figure B.90: Strains—Girder 8—Section 4—A9

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

407

B.1.4 898BBOTTOM-FIBER STRAINS—BOTH GIRDERS

Figure B.91: Bottom-fiber strains—A1

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bo

tto

m-F

iber

Str

ain

(x

10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G8 - Concrete

G7 - FRP

G8 - FRP

408

Figure B.92: Bottom-fiber strains—A2

Figure B.93: Bottom-fiber strains—A3

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er S

train

(x10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G8 - Concrete

G7 - FRP

G8 - FRP

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er S

train

(x10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G8 - Concrete

G7 - FRP

G8 - FRP

409

Figure B.94: Bottom-fiber strains—A4

Figure B.95: Bottom-fiber strains—A5

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er S

train

(x10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G8 - Concrete

G7 - FRP

G8 - FRP

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er S

train

(x10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G8 - Concrete

G7 - FRP

G8 - FRP

410

Figure B.96: Bottom-fiber strains—A6

Figure B.97: Bottom-fiber strains—A7

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er S

train

(x10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G8 - Concrete

G7 - FRP

G8 - FRP

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bo

tto

m-F

iber

Str

ain

(x

10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G8 - Concrete

G7 - FRP

G8 - FRP

411

Figure B.98: Bottom-fiber strains—A8

Figure B.99: Bottom-fiber strains—A9

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er S

train

(x10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G8 - Concrete

G7 - FRP

G8 - FRP

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er S

train

(x10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G8 - Concrete

G7 - FRP

G8 - FRP

412

B.1.4.1 4403BBOTTOM-FIBER STRAINS—GIRDER 7

Figure B.100: Bottom-fiber strains—Girder 7—A1

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bo

tto

m-F

iber

Str

ain

(x

10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G7 - FRP

413

Figure B.101: Bottom-fiber strains—Girder 7—A2

Figure B.102: Bottom-fiber strains—Girder 7—A3

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er S

train

(x10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G7 - FRP

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er S

train

(x10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G7 - FRP

414

Figure B.103: Bottom-fiber strains—Girder 7—A4

Figure B.104: Bottom-fiber strains—Girder 7—A5

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bo

tto

m-F

iber

Str

ain

(x

10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G7 - FRP

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er S

train

(x10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G7 - FRP

415

Figure B.105: Bottom-fiber strains—Girder 7—A6

Figure B.106: Bottom-fiber strains—Girder 7—A7

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er S

train

(x10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G7 - FRP

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bo

tto

m-F

iber

Str

ain

(x

10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G7 - FRP

416

Figure B.107: Bottom-fiber strains—Girder 7—A8

Figure B.108: Bottom-fiber strains—Girder 7—A9

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er S

train

(x10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G7 - FRP

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er S

train

(x10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G7 - FRP

417

B.1.4.2 4404BBOTTOM-FIBER STRAINS—GIRDER 8

Figure B.109: Bottom-fiber strains—Girder 8—A1

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bo

tto

m-F

iber

Str

ain

(x

10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G8 - Concrete

G8 - FRP

418

Figure B.110: Bottom-fiber strains—Girder 8—A2

Figure B.111: Bottom-fiber strains—Girder 8—A3

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er S

train

(x10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G8 - Concrete

G8 - FRP

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er S

train

(x10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G8 - Concrete

G8 - FRP

419

Figure B.112: Bottom-fiber strains—Girder 8—A4

Figure B.113: Bottom-fiber strains—Girder 8—A5

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bo

tto

m-F

iber

Str

ain

(x

10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G8 - Concrete

G8 - FRP

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er S

train

(x10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G8 - Concrete

G8 - FRP

420

Figure B.114: Bottom-fiber strains—Girder 8—A6

Figure B.115: Bottom-fiber strains—Girder 8—A7

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er S

train

(x10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G8 - Concrete

G8 - FRP

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bo

tto

m-F

iber

Str

ain

(x

10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G8 - Concrete

G8 - FRP

421

Figure B.116: Bottom-fiber strains—Girder 8—A8

Figure B.117: Bottom-fiber strains—Girder 8—A9

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er S

train

(x10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G8 - Concrete

G8 - FRP

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er S

train

(x10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G8 - Concrete

G8 - FRP

422

B.2 80BLANE C

B.2.1 899BCRACK-OPENING DISPLACEMENTS

Figure B.118: Crack-opening displacements—C1

-0.05

-0.04

-0.03

-0.02

-0.01

0.00

0.01

0.02

0.03

0.04

0.05

-900 -700 -500 -300 -100 100 300 500 700 900

Cra

ck-O

pen

ing

Dis

pla

cem

ent

(mm

)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

423

Figure B.119: Crack-opening displacements—C2

Figure B.120: Crack-opening displacements—C3

-0.05

-0.04

-0.03

-0.02

-0.01

0.00

0.01

0.02

0.03

0.04

0.05

-900 -700 -500 -300 -100 100 300 500 700 900

Cra

ck-O

pen

ing D

isp

lace

men

t (m

m)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

-0.05

-0.04

-0.03

-0.02

-0.01

0.00

0.01

0.02

0.03

0.04

0.05

-900 -700 -500 -300 -100 100 300 500 700 900

Cra

ck-O

pen

ing D

isp

lace

men

t (m

m)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

424

Figure B.121: Crack-opening displacements—C4

Figure B.122: Crack-opening displacements—C5

-0.05

-0.04

-0.03

-0.02

-0.01

0.00

0.01

0.02

0.03

0.04

0.05

-900 -700 -500 -300 -100 100 300 500 700 900

Cra

ck-O

pen

ing D

isp

lace

men

t (m

m)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

-0.05

-0.04

-0.03

-0.02

-0.01

0.00

0.01

0.02

0.03

0.04

0.05

-900 -700 -500 -300 -100 100 300 500 700 900

Cra

ck-O

pen

ing

Dis

pla

cem

ent

(mm

)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

425

Figure B.123: Crack-opening displacements—C6

Figure B.124: Crack-opening displacements—C7

-0.05

-0.04

-0.03

-0.02

-0.01

0.00

0.01

0.02

0.03

0.04

0.05

-900 -700 -500 -300 -100 100 300 500 700 900

Cra

ck-O

pen

ing

Dis

pla

cem

ent

(mm

)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

-0.05

-0.04

-0.03

-0.02

-0.01

0.00

0.01

0.02

0.03

0.04

0.05

-900 -700 -500 -300 -100 100 300 500 700 900

Cra

ck-O

pen

ing

Dis

pla

cem

ent

(mm

)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

426

Figure B.125: Crack-opening displacements—C8

Figure B.126: Crack-opening displacements—C9

-0.05

-0.04

-0.03

-0.02

-0.01

0.00

0.01

0.02

0.03

0.04

0.05

-900 -700 -500 -300 -100 100 300 500 700 900

Cra

ck-O

pen

ing D

isp

lace

men

t (m

m)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

-0.05

-0.04

-0.03

-0.02

-0.01

0.00

0.01

0.02

0.03

0.04

0.05

-900 -700 -500 -300 -100 100 300 500 700 900

Cra

ck-O

pen

ing D

isp

lace

men

t (m

m)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

427

B.2.2 900BDEFLECTIONS

Figure B.127: Deflections—C1

-0.4

-0.3

-0.2

-0.1

0.0

0.1

-900 -700 -500 -300 -100 100 300 500 700 900

Bo

tto

m-F

iber

Def

lect

ion

(in

.)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

428

Figure B.128: Deflections—C2

Figure B.129: Deflections—C3

-0.4

-0.3

-0.2

-0.1

0.0

0.1

-900 -700 -500 -300 -100 100 300 500 700 900

Bo

tto

m-F

iber

Def

lect

ion

(in

.)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

-0.4

-0.3

-0.2

-0.1

0.0

0.1

-900 -700 -500 -300 -100 100 300 500 700 900

Bo

tto

m-F

iber

Def

lect

ion

(in

.)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

429

Figure B.130: Deflections—C4

Figure B.131: Deflections—C5

-0.4

-0.3

-0.2

-0.1

0.0

0.1

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er D

efle

ctio

n (

in.)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

-0.4

-0.3

-0.2

-0.1

0.0

0.1

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er D

efle

ctio

n (

in.)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

430

Figure B.132: Deflections—C6

Figure B.133: Deflections—C7

-0.4

-0.3

-0.2

-0.1

0.0

0.1

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er D

efle

ctio

n (

in.)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

-0.4

-0.3

-0.2

-0.1

0.0

0.1

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er D

efle

ctio

n (

in.)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

431

Figure B.134: Deflections—C8

Figure B.135: Deflections—C9

-0.4

-0.3

-0.2

-0.1

0.0

0.1

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er D

efle

ctio

n (

in.)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

-0.4

-0.3

-0.2

-0.1

0.0

0.1

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er D

efle

ctio

n (

in.)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

432

B.2.3 901BCROSS-SECTION STRAINS

B.2.3.1 4405BCROSS-SECTION STRAINS—GIRDER 7

B.2.3.1.1 STRAINS—GIRDER 7—CROSS SECTION 1

Figure B.136: Strains—Girder 7—Section 1—C1

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bott

om

of

Gir

der

(in

.)

Strain (x10-6 in./in.)

Concrete

FRP

433

Figure B.137: Strains—Girder 7—Section 1—C2

Figure B.138: Strains—Girder 7—Section 1—C3

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

434

Figure B.139: Strains—Girder 7—Section 1—C4

Figure B.140: Strains—Girder 7—Section 1—C5

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

435

Figure B.141: Strains—Girder 7—Section 1—C6

Figure B.142: Strains—Girder 7—Section 1—C7

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

436

Figure B.143: Strains—Girder 7—Section 1—C8

Figure B.144: Strains—Girder 7—Section 1—C9

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

437

B.2.3.1.2 STRAINS—GIRDER 7—CROSS SECTION 2

Figure B.145: Strains—Girder 7—Section 2—C1

0

5

10

15

20

25

30

-160 -140 -120 -100 -80 -60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

438

Figure B.146: Strains—Girder 7—Section 2—C2

Figure B.147: Strains—Girder 7—Section 2—C3

0

5

10

15

20

25

30

-160 -140 -120 -100 -80 -60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

0

5

10

15

20

25

30

-160 -140 -120 -100 -80 -60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

439

Figure B.148: Strains—Girder 7—Section 2—C4

Figure B.149: Strains—Girder 7—Section 2—C5

0

5

10

15

20

25

30

-160 -140 -120 -100 -80 -60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

0

5

10

15

20

25

30

-160 -140 -120 -100 -80 -60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

440

Figure B.150: Strains—Girder 7—Section 2—C6

Figure B.151: Strains—Girder 7—Section 2—C7

0

5

10

15

20

25

30

-160 -140 -120 -100 -80 -60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

0

5

10

15

20

25

30

-160 -140 -120 -100 -80 -60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

441

Figure B.152: Strains—Girder 7—Section 2—C8

Figure B.153: Strains—Girder 7—Section 2—C9

0

5

10

15

20

25

30

-160 -140 -120 -100 -80 -60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

0

5

10

15

20

25

30

-160 -140 -120 -100 -80 -60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

442

B.2.3.1.3 STRAINS—GIRDER 7—CROSS SECTION 3

Figure B.154: Strains—Girder 7—Section 3—C1

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

443

Figure B.155: Strains—Girder 7—Section 3—C2

Figure B.156: Strains—Girder 7—Section 3—C3

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

444

Figure B.157: Strains—Girder 7—Section 3—C4

Figure B.158: Strains—Girder 7—Section 3—C5

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

445

Figure B.159: Strains—Girder 7—Section 3—C6

Figure B.160: Strains—Girder 7—Section 3—C7

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

446

Figure B.161: Strains—Girder 7—Section 3—C8

Figure B.162: Strains—Girder 7—Section 3—C9

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

447

B.2.3.1.4 STRAINS—GIRDER 7—CROSS SECTION 4

Figure B.163: Strains—Girder 7—Section 4—C1

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

448

Figure B.164: Strains—Girder 7—Section 4—C2

Figure B.165: Strains—Girder 7—Section 4—C3

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

449

Figure B.166: Strains—Girder 7—Section 4—C4

Figure B.167: Strains—Girder 7—Section 4—C5

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

450

Figure B.168: Strains—Girder 7—Section 4—C6

Figure B.169: Strains—Girder 7—Section 4—C7

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

451

Figure B.170: Strains—Girder 7—Section 4—C8

Figure B.171: Strains—Girder 7—Section 4—C9

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

452

B.2.3.2 4406BCROSS-SECTION STRAINS—GIRDER 8

B.2.3.2.1 STRAINS—GIRDER 8—CROSS SECTION 1

Figure B.172: Strains—Girder 8—Section 1—C1

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bott

om

of

Gir

der

(in

.)

Strain (x10-6 in./in.)

Concrete

FRP

453

Figure B.173: Strains—Girder 8—Section 1—C2

Figure B.174: Strains—Girder 8—Section 1—C3

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

454

Figure B.175: Strains—Girder 8—Section 1—C4

Figure B.176: Strains—Girder8—Section 1—C5

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

455

Figure B.177: Strains—Girder 8—Section 1—C6

Figure B.178: Strains—Girder 8—Section 1—C7

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bott

om

of

Gir

der

(in

.)

Strain (x10-6 in./in.)

Concrete

FRP

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bott

om

of

Gir

der

(in

.)

Strain (x10-6 in./in.)

Concrete

FRP

456

Figure B.179: Strains—Girder 8—Section 1—C8

Figure B.180: Strains—Girder 8—Section 1—C9

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

ttom

of

Gir

der

(in

.)

Strain (x10-6 in./in.)

Concrete

FRP

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

457

B.2.3.2.2 STRAINS—GIRDER 8—CROSS SECTION 2

Figure B.181: Strains—Girder 8—Section 2—C1

0

5

10

15

20

25

30

-100 -80 -60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bott

om

of

Gir

der

(in

.)

Strain (x10-6 in./in.)

Concrete

FRP

458

Figure B.182: Strains—Girder 8—Section 2—C2

Figure B.183: Strains—Girder 8—Section 2—C3

0

5

10

15

20

25

30

-100 -80 -60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

0

5

10

15

20

25

30

-100 -80 -60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

459

Figure B.184: Strains—Girder 8—Section 2—C4

Figure B.185: Strains—Girder 8—Section 2—C5

0

5

10

15

20

25

30

-100 -80 -60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

0

5

10

15

20

25

30

-100 -80 -60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

460

Figure B.186: Strains—Girder 8—Section 2—C6

Figure B.187: Strains—Girder 8—Section 2—C7

0

5

10

15

20

25

30

-100 -80 -60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

0

5

10

15

20

25

30

-100 -80 -60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

461

Figure B.188: Strains—Girder 8—Section 2—C8

Figure B.189: Strains—Girder 8—Section 2—C9

0

5

10

15

20

25

30

-100 -80 -60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

0

5

10

15

20

25

30

-100 -80 -60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

462

B.2.3.2.3 STRAINS—GIRDER 8—CROSS SECTION 3

Figure B.190: Strains—Girder 8—Section 3—C1

0

5

10

15

20

25

30

-80 -60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bott

om

of

Gir

der

(in

.)

Strain (x10-6 in./in.)

Concrete

FRP

463

Figure B.191: Strains—Girder 8—Section 3—C2

Figure B.192: Strains—Girder 8—Section 3—C3

0

5

10

15

20

25

30

-80 -60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

0

5

10

15

20

25

30

-80 -60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

464

Figure B.193: Strains—Girder 8—Section 3—C4

Figure B.194: Strains—Girder 8—Section 3—C5

0

5

10

15

20

25

30

-80 -60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

0

5

10

15

20

25

30

-80 -60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

465

Figure B.195: Strains—Girder 8—Section 3—C6

Figure B.196: Strains—Girder 8—Section 3—C7

0

5

10

15

20

25

30

-80 -60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

0

5

10

15

20

25

30

-80 -60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

466

Figure B.197: Strains—Girder 8—Section 3—C8

Figure B.198: Strains—Girder 8—Section 3—C9

0

5

10

15

20

25

30

-80 -60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

0

5

10

15

20

25

30

-80 -60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

467

B.2.3.2.4 STRAINS—GIRDER 8—CROSS SECTION 4

Figure B.199: Strains—Girder 8—Section 4—C1

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60 80 100 120 140

Hei

gh

t fr

om

Bott

om

of

Gir

der

(in

.)

Strain (x10-6 in./in.)

Concrete

FRP

468

Figure B.200: Strains—Girder 8—Section 4—C2

Figure B.201: Strains—Girder 8—Section 4—C3

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60 80 100 120 140

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60 80 100 120 140

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

469

Figure B.202: Strains—Girder 8—Section 4—C4

Figure B.203: Strains—Girder 8—Section 4—C5

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60 80 100 120 140

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60 80 100 120 140

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

470

Figure B.204: Strains—Girder 8—Section 4—C6

Figure B.205: Strains—Girder 8—Section 4—C7

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60 80 100 120 140

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60 80 100 120 140

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

471

Figure B.206: Strains—Girder 8—Section 4—C8

Figure B.207: Strains—Girder 8—Section 4—C9

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60 80 100 120 140

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60 80 100 120 140

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete

FRP

472

B.2.4 902BBOTTOM-FIBER STRAINS—BOTH GIRDERS

Figure B.208: Bottom-fiber strains—C1

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er S

train

(x10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G8 - Concrete

G7 - FRP

G8 - FRP

473

Figure B.209: Bottom-fiber strains—C2

Figure B.210: Bottom-fiber strains—C3

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er S

train

(x10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G8 - Concrete

G7 - FRP

G8 - FRP

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er S

train

(x10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G8 - Concrete

G7 - FRP

G8 - FRP

474

Figure B.211: Bottom-fiber strains—C4

Figure B.212: Bottom-fiber strains—C5

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bo

tto

m-F

iber

Str

ain

(x

10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G8 - Concrete

G7 - FRP

G8 - FRP

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er S

train

(x10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G8 - Concrete

G7 - FRP

G8 - FRP

475

Figure B.213: Bottom-fiber strains—C6

Figure B.214: Bottom-fiber strains—C7

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er S

train

(x10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G8 - Concrete

G7 - FRP

G8 - FRP

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er S

train

(x10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G8 - Concrete

G7 - FRP

G8 - FRP

476

Figure B.215: Bottom-fiber strains—C8

Figure B.216: Bottom-fiber strains—C9

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er S

train

(x10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G8 - Concrete

G7 - FRP

G8 - FRP

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er S

train

(x10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G8 - Concrete

G7 - FRP

G8 - FRP

477

B.2.4.1 4407BBOTTOM-FIBER STRAINS—GIRDER 7

Figure B.217: Bottom-fiber strains—Girder 7—C1

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er S

train

(x10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G7 - FRP

478

Figure B.218: Bottom-fiber strains—Girder 7—C2

Figure B.219: Bottom-fiber strains—Girder 7—C3

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er S

train

(x10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G7 - FRP

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er S

train

(x10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G7 - FRP

479

Figure B.220: Bottom-fiber strains—Girder 7—C4

Figure B.221: Bottom-fiber strains—Girder 7—C5

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bo

tto

m-F

iber

Str

ain

(x

10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G7 - FRP

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er S

train

(x10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G7 - FRP

480

Figure B.222: Bottom-fiber strains—Girder 7—C6

Figure B.223: Bottom-fiber strains—Girder 7—C7

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er S

train

(x10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G7 - FRP

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er S

train

(x10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G7 - FRP

481

Figure B.224: Bottom-fiber strains—Girder 7—C8

Figure B.225: Bottom-fiber strains—Girder 7—C9

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er S

train

(x10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G7 - FRP

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er S

train

(x10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G7 - FRP

482

B.2.4.2 4408BBOTTOM-FIBER STRAINS—GIRDER 8

Figure B.226: Bottom-fiber strains—Girder 8—C1

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er S

train

(x10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G8 - Concrete

G8 - FRP

483

Figure B.227: Bottom-fiber strains—Girder 8—C2

Figure B.228: Bottom-fiber strains—Girder 8—C3

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er S

train

(x10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G8 - Concrete

G8 - FRP

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er S

train

(x10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G8 - Concrete

G8 - FRP

484

Figure B.229: Bottom-fiber strains—Girder 8—C4

Figure B.230: Bottom-fiber strains—Girder 8—C5

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bo

tto

m-F

iber

Str

ain

(x

10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G8 - Concrete

G8 - FRP

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er S

train

(x10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G8 - Concrete

G8 - FRP

485

Figure B.231: Bottom-fiber strains—Girder 8—C6

Figure B.232: Bottom-fiber strains—Girder 8—C7

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er S

train

(x10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G8 - Concrete

G8 - FRP

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er S

train

(x10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G8 - Concrete

G8 - FRP

486

Figure B.233: Bottom-fiber strains—Girder 8—C8

Figure B.234: Bottom-fiber strains—Girder 8—C9

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er S

train

(x10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G8 - Concrete

G8 - FRP

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er S

train

(x10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G8 - Concrete

G8 - FRP

487

Appendix C

16BMULTIPOSITION LOAD TEST—MEASUREMENTS

488

C.1 81BLANE A

The following tables represent measurements from the multiposition load test due to traversing Lane A

Table C.1: Lane A—crack-opening displacements

Girder 903BGage

904BHeight

from

bottom of

girder

(in.)

905BDistance from

center of

continuity

diaphragm

(in.)

– Span 10

+ Span 11

906BCrack-Opening Displacement

(mm)

– closing

+ opening

907BA1 908BA2 909BA3 910BA4 911BA5 912BA6 913BA7 914BA8 915BA9

916B7

917BCO7_10 918B13.5 919B-50 -0.008 0.010 920B0.016 921B0.024 922B0.014 923B-0.005 924B-0.008 925B-0.015 926B-0.016

927BCO7_11 928B13.5 929B48 930B-0.027 931B-0.023 932B-0.005 933B-0.003 934B-0.003 935B0.022 936B0.041 937B0.012 938B-0.014

939B8

940BCO8_10 941B13.5 942B-40 943B-0.011 944B-0.009 945B-0.006 946B-0.004 947B-0.002 948B-0.004 949B-0.005 950B-0.008 951B-0.009

952BCO8_11 953B13.5 954B56 955B-0.013 956B-0.011 957B-0.004 958B-0.002 959B-0.001 960B0.010 961B0.018 962B0.005 963B-0.005

489

Table C.2: Lane A—deflections

Girder 964BGage

965BHeight

from

bottom of

girder

(in.)

966BDistance from

center of

continuity

diaphragm

(in.)

– Span 10

+ Span 11

967BDeflection

(in.)

– downward

+ upward

968BA1 969BA2 970BA3 971BA4 972BA5 973BA6 974BA7 975BA8 976BA9

977B7

978BD7_10_A 979Bn/a 980B-608 -0.32 -0.20 981B-0.11 982B-0.06 983B-0.02 984B0.01 985B0.02 986B0.04 987B0.04

988BD7_10_B 989Bn/a 990B-308 991B-0.22 992B-0.18 993B-0.11 994B-0.07 995B-0.03 996B0.00 997B0.01 998B0.03 999B0.04

1000BD7_11_C 1001Bn/a 1002B158 1003B0.02 1004B0.01 1005B0.00 1006B-0.02 1007B-0.03 1008B-0.05 1009B-0.08 1010B-0.12 1011B-0.12

1012BD7_11_D 1013Bn/a 1014B308 1015B0.04 1016B0.03 1017B0.00 1018B-0.02 1019B-0.04 1020B-0.07 1021B-0.11 1022B-0.20 1023B-0.22

1024BD7_11_E 1025Bn/a 1026B458 1027B0.05 1028B0.03 1029B0.01 1030B-0.02 1031B0.03 1032B-0.08 1033B-0.12 1034B-0.22 1035B-0.29

1036BD7_11_F 1037Bn/a 1038B608 1039B0.05 1040B0.03 1041B0.01 1042B-0.01 1043B-0.03 1044B-0.07 1045B-0.11 1046B-0.22 1047B-0.33

1048B8

1049BD8_10_A 1050Bn/a 1051B-608 1052B-0.26 1053B-0.16 1054B-0.09 1055B-0.05 1056B-0.02 1057B0.01 1058B0.02 1059B0.04 1060B0.04

1061BD8_10_B 1062Bn/a 1063B-308 1064B-0.17 1065B-0.13 1066B-0.08 1067B-0.05 1068B-0.02 1069B0.00 1070B0.01 1071B0.03 1072B0.03

1073BD8_11_C 1074Bn/a 1075B158 1076B0.02 1077B0.01 1078B0.00 1079B-0.01 1080B-0.02 1081B-0.04 1082B-0.06 1083B-0.09 1084B-0.09

1085BD8_11_D 1086Bn/a 1087B308 1088B0.04 1089B0.03 1090B0.00 1091B-0.01 1092B-0.03 1093B-0.06 1094B-0.08 1095B-0.15 1096B-0.17

1097BD8_11_E 1098Bn/a 1099B458 1100B0.04 1101B0.03 1102B0.01 1103B-0.01 1104B-0.03 1105B-0.06 1106B-0.09 1107B-0.18 1108B-0.23

1109BD8_11_F 1110Bn/a 1111B608 1112B0.04 1113B0.03 1114B0.01 1115B-0.01 1116B-0.02 1117B-0.06 1118B-0.09 1119B-0.17 1120B-0.25

490

Table C.3: Lane A—cross-section strains—Girder 7—Span 10

Section 1121BGage

1122BHeight

from

bottom of

girder

(in.)

1123BDistance from

center of

continuity

diaphragm

(in.)

– Span 10

+ Span 11

1124BStrain

(x10-6

in./in.)

– compressive

+ tensile

1125BA1 1126BA2 1127BA3 1128BA4 1129BA5 1130BA6 1131BA7 1132BA8 1133BA9

1134BGir

der

7

1135BCro

ss S

ecti

on

1136B1

1137BS7_10_1V 1138B28.5 1139B-75 -6 2 1140B3 1141B5 1142B3 1143B-2 1144B-3 1145B-6 1146B-6

1147BS7_10_1W 1148B13.5 1149B-75 1150B-7 1151B4 1152B7 1153B10 1154B4 1155B-4 1156B-6 1157B-11 1158B-12

1159BS7_10_1X 1160B13.5 1161B-75 1162B-6 1163B5 1164B8 1165B11 1166B5 1167B-4 1168B-6 1169B-11 1170B-12

1171BS7_10_1Y 1172B3.0 1173B-75 1174B-11 1175B7 1176B14 1177B18 1178B8 1179B-6 1180B-9 1181B-19 1182B-20

1183BF7_10_1M 1184B0.0 1185B-74 1186B-9 1187B11 1188B16 1189B23 1190B13 1191B-6 1192B-9 1193B-18 1194B-19

1195BGir

der

7

1196BCro

ss S

ecti

on

1197B2

1198BS7_10_2V 1199B28.5 1200B-13 1201B2 1202B3 1203B3 1204B3 1205B3 1206B1 1207B-1 1208B-4 1209B-5

1210BS7_10_2W 1211B13.5 1212B-13 1213B0 1214B-1 1215B-1 1216B-3 1217B-1 1218B1 1219B0 1220B-4 1221B-4

1222BS7_10_2X 1223B13.5 1224B-13 1225B6 1226B4 1227B3 1228B0 1229B2 1230B2 1231B1 1232B-1 1233B-2

1234BS7_10_2Y 1235B3.0 1236B-13 1237B-157 1238B-135 1239B-91 1240B-49 1241B-27 1242B-46 1243B-64 1244B-127 1245B-131

1246BF7_10_2Z 1247B3.0 1248B-14 1249B-39 1250B-27 1251B-16 1252B-7 1253B-3 1254B-12 1255B-17 1256B-29 1257B-27

491

Table C.4: Lane A—cross-section strains—Girder 7—Span 11

Section 1258BGage

1259BHeight

from

bottom of

girder

(in.)

1260BDistance from

center of

continuity

diaphragm

(in.)

– Span 10

+ Span 11

1261BStrain

(x10-6

in./in.)

– compressive

+ tensile

1262BA1 1263BA2 1264BA3 1265BA4 1266BA5 1267BA6 1268BA7 1269BA8 1270BA9

1271BGir

der

7

1272BCro

ss S

ecti

on

1273B3

1274BS7_11_3V 1275B28.5 1276B13 -7 -4 1277B-3 1278B-1 1279B0 1280B1 1281B-2 1282B-2 1283B-2

1284BS7_11_3W 1285B13.5 1286B13 1287B-17 1288B-10 1289B0 1290B4 1291B7 1292B12 1293B9 1294B2 1295B-2

1296BS7_11_3X 1297B13.5 1298B13 1299B-8 1300B-2 1301B1 1302B4 1303B7 1304B6 1305B2 1306B4 1307B4

1308BS7_11_3Y 1309B3.0 1310B13 1311B-11 1312B-8 1313B-5 1314B-7 1315B-2 1316B-3 1317B-6 1318B-15 1319B-17

1320BS7_11_3Z 1321B3.0 1322B13 1323B-10 1324B-8 1325B-6 1326B-5 1327B-4 1328B-6 1329B-9 1330B-13 1331B-11

1332BGir

der

7

1333BCro

ss S

ecti

on

1334B4

1335BS7_11_4V 1336B28.5 1337B75 1338B-2 1339B-1 1340B0 1341B-2 1342B-2 1343B-2 1344B-5 1345B-8 1346B-6

1347BS7_11_4W 1348B13.5 1349B75 1350B-10 1351B-7 1352B-3 1353B-1 1354B-1 1355B4 1356B5 1357B-3 1358B-8

1359BS7_11_4X 1360B13.5 1361B75 1362B-11 1363B-8 1364B-2 1365B-1 1366B-1 1367B5 1368B6 1369B-2 1370B-8

1371BS7_11_4Y 1372B3.0 1373B75 1374B-17 1375B-13 1376B-2 1377B0 1378B1 1379B13 1380B22 1381B6 1382B-8

1383BF7_11_4M 1384B0.0 1385B74 1386B-21 1387B-16 1388B-3 1389B0 1390B1 1391B17 1392B28 1393B8 1394B9

492

Table C.5: Lane A—cross-section strains—Girder 8—Span 10

Section 1395BGage

1396BHeight

from

bottom of

girder

(in.)

1397BDistance from

center of

continuity

diaphragm

(in.)

– Span 10

+ Span 11

1398BStrain

(x10-6

in./in.)

– compressive

+ tensile

1399BA1 1400BA2 1401BA3 1402BA4 1403BA5 1404BA6 1405BA7 1406BA8 1407BA9

1408BGir

der

8

1409BCro

ss S

ecti

on

1410B1

1411BS8_10_1V 1412B28.5 1413B-75 -5 -2 1414B-1 1415B0 1416B0 1417B-3 1418B-3 1419B-5 1420B-6

1421BS8_10_1W 1422B13.5 1423B-75 1424B-7 1425B1 1426B3 1427B5 1428B2 1429B-4 1430B-6 1431B-11 1432B-12

1433BS8_10_1X 1434B13.5 1435B-75 1436B-9 1437B1 1438B3 1439B7 1440B4 1441B-4 1442B-7 1443B-12 1444B-12

1445BF8_10_1Y 1446B3.0 1447B-74 1448B-5 1449B1 1450B2 1451B3 1452B1 1453B-3 1454B-4 1455B-8 1456B-8

1457BS8_10_1M 1458B0.0 1459B-75 1460B-11 1461B4 1462B7 1463B13 1464B7 1465B-6 1466B-9 1467B-16 1468B-17

1469BF8_10_1M 1470B0.0 1471B-74 1472B-4 1473B5 1474B6 1475B10 1476B5 1477B-4 1478B-6 1479B-11 1480B-11

1481BGir

der

8

1482BCro

ss S

ecti

on

1483B2

1484BS8_10_2V 1485B28.5 1486B-13 1487B0 1488B1 1489B1 1490B1 1491B2 1492B0 1493B-1 1494B-3 1495B-4

1496BS8_10_2W 1497B13.5 1498B-13 1499B2 1500B4 1501B3 1502B3 1503B2 1504B-1 1505B-2 1506B-7 1507B-9

1508BS8_10_2X 1509B13.5 1510B-13 1511B4 1512B6 1513B5 1514B3 1515B4 1516B1 1517B-2 1518B-6 1519B-8

1520BF8_10_2Y 1521B3.0 1522B-14 1523B-32 1524B-21 1525B-14 1526B-10 1527B-7 1528B-14 1529B-18 1530B-28 1531B-30

1532BF8_10_2Z 1533B3.0 1534B-14 1535B-28 1536B-19 1537B-11 1538B-5 1539B-2 1540B-4 1541B-8 1542B-13 1543B-13

493

Table C.6: Lane A—cross-section strains—Girder 8—Span 11

Section 1544BGage

1545BHeight

from

bottom of

girder

(in.)

1546BDistance from

center of

continuity

diaphragm

(in.)

– Span 10

+ Span 11

1547BStrain

(x10-6

in./in.)

– compressive

+ tensile

1548BA1 1549BA2 1550BA3 1551BA4 1552BA5 1553BA6 1554BA7 1555BA8 1556BA9

1557BGir

der

8

1558BCro

ss S

ecti

on

1559B3

1560BS8_11_3V 1561B28.5 1562B13 -42 -35 1563B-26 1564B-22 1565B-17 1566B-13 1567B-17 1568B-26 1569B-32

1570BS8_11_3W 1571B13.5 1572B13 1573B-18 1574B-10 1575B-5 1576B-1 1577B1 1578B0 1579B-3 1580B-6 1581B-7

1582BS8_11_3X 1583B13.5 1584B13 1585B-31 1586B-21 1587B-5 1588B-2 1589B2 1590B15 1591B17 1592B-1 1593B-14

1594BF8_11_3Y 1595B3.0 1596B14 1597B-33 1598B-25 1599B-15 1600B-11 1601B-7 1602B-2 1603B-5 1604B-15 1605B-22

1606BF8_11_3Z 1607B3.0 1608B14 1609B-28 1610B-22 1611B-17 1612B-15 1613B-12 1614B-12 1615B-22 1616B-48 1617B-49

1618BGir

der

8

1619BCro

ss S

ecti

on

1620B4

1621BS8_11_4V 1622B28.5 1623B75 1624B-4 1625B-2 1626B-2 1627B-4 1628B-4 1629B-5 1630B-12 1631B-16 1632B-12

1633BS8_11_4W 1634B13.5 1635B75 1636B-11 1637B-8 1638B-4 1639B-3 1640B-2 1641B0 1642B-2 1643B-8 1644B-12

1645BS8_11_4X 1646B13.5 1647B75 1648B-9 1649B-16 1650B-2 1651B-3 1652B-1 1653B3 1654B2 1655B-2 1656B-5

1657BF8_11_4Y 1658B3.0 1659B74 1660B-11 1661B-8 1662B-3 1663B-1 1664B0 1665B4 1666B6 1667B1 1668B-5

1669BS8_11_4M 1670B0.0 1671B75 1672B-39 1673B-32 1674B-11 1675B-4 1676B-1 1677B27 1678B58 1679B26 1680B-7

1681BF8_11_4M 1682B0.0 1683B74 1684B-23 1685B-18 1686B-6 1687B-1 1688B0 1689B14 1690B25 1691B9 1692B-6

494

Table C.7: Lane A—bottom-fiber strains—Girder 7

Span 1693BGage

1694BHeight

from

bottom of

girder

(in.)

1695BDistance from

center of

continuity

diaphragm

(in.)

– Span 10

+ Span 11

1696BStrain

(x10-6

in./in.)

– compressive

+ tensile

1697BA1 1698BA2 1699BA3 1700BA4 1701BA5 1702BA6 1703BA7 1704BA8 1705BA9

1706B10

1707BF7_10_1M 1708B0 1709B-74 -9 11 1710B16 1711B23 1712B13 1713B-6 1714B-9 1715B-18 1716B-19

1717BF7_10_CK 1718B0 1719B-47 1720B-87 1721B21 1722B58 1723B108 1724B73 1725B-33 1726B-60 1727B-125 1728B-132

1729B11

1730BF7_11_CK 1731B0 1732B47 1733B-148 1734B-119 1735B-36 1736B-25 1737B-13 1738B90 1739B128 1740B-8 1741B-93

1742BF7_11_4M 1743B0 1744B74 1745B-21 1746B-16 1747B-3 1748B0 1749B1 1750B17 1751B28 1752B8 1753B-9

1754BF7_11_5M 1755B0 1756B104 1757B-20 1758B-15 1759B-3 1760B3 1761B3 1762B17 1763B32 1764B14 1765B-5

1766BS7_11_5M 1767B0 1768B105 1769B-18 1770B-15 1771B-3 1772B2 1773B3 1774B15 1775B29 1776B13 1777B-5

1778BS7_11_6M 1779B0 1780B273 1781B-19 1782B-15 1783B-6 1784B4 1785B12 1786B30 1787B42 1788B84 1789B35

1790BS7_11_7M 1791B0 1792B441 1793B-14 1794B-11 1795B-3 1796B4 1797B9 1798B22 1799B36 1800B69 1801B75

1802BS7_11_8M 1803B0 1804B609 1805B-8 1806B-6 1807B-3 1808B1 1809B4 1810B10 1811B16 1812B40 1813B75

495

Table C.8: Lane A—bottom-fiber strains—Girder 8

Span 1814BGage

1815BHeight

from

bottom of

girder

(in.)

1816BDistance from

center of

continuity

diaphragm

(in.)

– Span 10

+ Span 11

1817BStrain

(x10-6

in./in.)

– compressive

+ tensile

1818BA1 1819BA2 1820BA3 1821BA4 1822BA5 1823BA6 1824BA7 1825BA8 1826BA9

1827B10

1828BS8_10_1M 1829B0 1830B-75 -11 4 1831B7 1832B13 1833B7 1834B-6 1835B-9 1836B-16 1837B-17

1838BF8_10_1M 1839B0 1840B-74 1841B-4 1842B5 1843B6 1844B10 1845B5 1846B-4 1847B-6 1848B-11 1849B-11

1850BF8_10_CK 1851B0 1852B-41 1853B-104 1854B-17 1855B8 1856B53 1857B41 1858B-42 1859B-71 1860B-126 1861B-139

1862B11

1863BF8_11_CK 1864B0 1865B52 1866B-65 1867B-51 1868B-21 1869B-17 1870B-10 1871B21 1872B27 1873B-18 1874B-44

1875BF8_11_4M 1876B0 1877B74 1878B-23 1879B-18 1880B-6 1881B-1 1882B0 1883B14 1884B25 1885B9 1886B-6

1887BS8_11_4M 1888B0 1889B75 1890B-39 1891B-32 1892B-11 1893B-4 1894B-1 1895B27 1896B58 1897B26 1898B-7

1899BF8_11_5M 1900B0 1901B104 1902B-20 1903B-14 1904B-3 1905B1 1906B2 1907B11 1908B22 1909B9 1910B-4

1911BS8_11_5M 1912B0 1913B105 1914B-18 1915B-14 1916B-4 1917B1 1918B1 1919B10 1920B20 1921B7 1922B-5

1923BS8_11_6M 1924B0 1925B273 1926B-15 1927B-11 1928B-4 1929B3 1930B9 1931B21 1932B28 1933B56 1934B26

1935BS8_11_7M 1936B0 1937B441 1938B-11 1939B-8 1940B-3 1941B2 1942B6 1943B17 1944B27 1945B54 1946B61

1947BS8_11_8M 1948B0 1949B609 1950B-8 1951B-6 1952B-3 1953B1 1954B4 1955B10 1956B16 1957B40 1958B75

496

Table C.9: Lane A—FRP strains—Girder 7

Span 1959BGage

1960BHeight

from

bottom of

girder

(in.)

1961BDistance from

center of

continuity

diaphragm

(in.)

– Span 10

+ Span 11

1962BStrain

(x10-6

in./in.)

– compressive

+ tensile

1963BA1 1964BA2 1965BA3 1966BA4 1967BA5 1968BA6 1969BA7 1970BA8 1971BA9

1972B10

1973BF7_10_1M 1974B0 1975B-74 -9 11 1976B16 1977B23 1978B13 1979B-6 1980B-9 1981B-18 1982B-19

1983BF7_10_CK 1984B0 1985B-47 1986B-87 1987B21 1988B58 1989B108 1990B73 1991B-33 1992B-60 1993B-125 1994B-132

1995BF7_10_2Z 1996B3 1997B-13 1998B-39 1999B-27 2000B-16 2001B-7 2002B-3 2003B-12 2004B-17 2005B-29 2006B-27

2007B11

2008BF7_11_CK 2009B0 2010B47 2011B-148 2012B-119 2013B-36 2014B-25 2015B-13 2016B90 2017B128 2018B-8 2019B-93

2020BF7_11_4M 2021B0 2022B74 2023B-21 2024B-16 2025B-3 2026B0 2027B1 2028B17 2029B28 2030B8 2031B-9

2032BF7_11_5M 2033B0 2034B104 2035B-20 2036B-15 2037B-3 2038B3 2039B3 2040B17 2041B32 2042B14 2043B-5

497

Table C.10: Lane A—FRP strains—Girder 8

Span 2044BGage

2045BHeight

from

bottom of

girder

(in.)

2046BDistance from

center of

continuity

diaphragm

(in.)

– Span 10

+ Span 11

2047BStrain

(x10-6

in./in.)

– compressive

+ tensile

2048BA1 2049BA2 2050BA3 2051BA4 2052BA5 2053BA6 2054BA7 2055BA8 2056BA9

2057B10

2058BF8_10_1Y 2059B3 2060B-74 2061B-5 2062B1 2063B2 2064B3 2065B1 2066B-3 2067B-4 2068B-8 2069B-8

2070BF8_10_1M 2071B0 2072B-74 2073B-4 2074B5 2075B6 2076B10 2077B5 2078B-4 2079B-6 2080B-11 2081B-11

2082BF8_10_CK 2083B0 2084B-41 2085B-104 2086B-17 2087B8 2088B53 2089B41 2090B-42 2091B-71 2092B-126 2093B-139

2094BF8_10_2Y 2095B3 2096B-14 2097B-32 2098B-21 2099B-14 2100B-10 2101B-7 2102B-14 2103B-18 2104B-28 2105B-30

2106BF8_10_2Z 2107B3 2108B-14 2109B-28 2110B-19 2111B-11 2112B-5 2113B-2 2114B-4 2115B-8 2116B-13 2117B-13

2118B11

2119BF8_11_3Y 2120B3 2121B14 2122B-33 2123B-25 2124B-15 2125B-11 2126B-7 2127B-2 2128B-5 2129B-15 2130B-22

2131BF8_11_3Z 2132B3 2133B14 2134B-28 2135B-22 2136B-17 2137B-15 2138B-12 2139B-12 2140B-22 2141B-48 2142B-49

2143BF8_11_CK 2144B0 2145B52 2146B-65 2147B-51 2148B-21 2149B-17 2150B-10 2151B21 2152B27 2153B-18 2154B-44

2155BF8_11_4Y 2156B3 2157B74 2158B-11 2159B-8 2160B-3 2161B-1 2162B0 2163B4 2164B6 2165B1 2166B-5

2167BF8_11_4M 2168B0 2169B74 2170B-23 2171B-18 2172B-6 2173B-1 2174B0 2175B14 2176B25 2177B9 2178B-6

2179BF8_11_5M 2180B0 2181B104 2182B-20 2183B-14 2184B-3 2185B1 2186B2 2187B11 2188B22 2189B9 2190B-4

498

C.2 82BLANE C

The following tables represent measurements from the multiposition load test due to traversing Lane C.

Table C.11: Lane C—crack-opening displacements

Girder 2191BGage

2192BHeight

from

bottom of

girder

(in.)

2193BDistance from

center of

continuity

diaphragm

(in.)

– Span 10

+ Span 11

2194BCrack-Opening Displacement

(mm)

– closing

+ opening

2195BC1 2196BC2 2197BC3 2198BC4 2199BC5 2200BC6 2201BC7 2202BC8 2203BC9

2204B7

2205BCO7_10 2206B13.5 2207B-50 -0.003 0.010 2208B0.016 2209B0.022 2210B0.011 2211B-0.006 2212B-0.009 2213B-0.015 2214B-0.017

2215BCO7_11 2216B13.5 2217B48 2218B-0.025 2219B-0.022 2220B-0.008 2221B-0.006 2222B-0.004 2223B0.020 2224B0.039 2225B0.015 2226B-0.008

2227B8

2228BCO8_10 2229B13.5 2230B-40 2231B-0.016 2232B-0.013 2233B-0.008 2234B-0.005 2235B-0.002 2236B-0.005 2237B-0.008 2238B-0.015 2239B-0.015

2240BCO8_11 2241B13.5 2242B56 2243B-0.020 2244B-0.018 2245B-0.007 2246B-0.004 2247B-0.002 2248B0.017 2249B0.032 2250B0.011 2251B-0.007

499

Table C.12: Lane C—deflections

Girder 2252BGage

2253BHeight

from

bottom of

girder

(in.)

2254BDistance from

center of

continuity

diaphragm

(in.)

– Span 10

+ Span 11

2255BDeflection

(in.)

– downward

+ upward

2256BC1 2257BC2 2258BC3 2259BC4 2260BC5 2261BC6 2262BC7 2263BC8 2264BC9

2265B7

2266BD7_10_A 2267Bn/a 2268B-608 -0.29 -0.18 2269B-0.10 2270B-0.05 2271B-0.02 2272B0.01 2273B0.02 2274B0.03 2275B0.04

2276BD7_10_B 2277Bn/a 2278B-308 2279B-0.20 2280B-0.17 2281B-0.10 2282B-0.06 2283B-0.03 2284B0.00 2285B0.01 2286B0.03 2287B0.03

2288BD7_11_C 2289Bn/a 2290B158 2291B0.02 2292B0.01 2293B0.00 2294B-0.02 2295B-0.02 2296B-0.05 2297B-0.07 2298B-0.11 2299B-0.11

2300BD7_11_D 2301Bn/a 2302B308 2303B0.04 2304B0.03 2305B0.00 2306B-0.02 2307B-0.03 2308B-0.07 2309B-0.10 2310B-0.19 2311B-0.21

2312BD7_11_E 2313Bn/a 2314B458 2315B0.04 2316B0.03 2317B0.00 2318B-0.02 2319B-0.03 2320B-0.07 2321B-0.11 2322B-0.21 2323B-0.27

2324BD7_11_F 2325Bn/a 2326B608 2327B0.04 2328B0.03 2329B0.00 2330B-0.02 2331B-0.03 2332B-0.07 2333B-0.11 2334B-0.22 2335B-0.31

2336B8

2337BD8_10_A 2338Bn/a 2339B-608 2340B-0.35 2341B-0.21 2342B-0.12 2343B-0.06 2344B-0.02 2345B0.01 2346B0.02 2347B0.04 2348B0.05

2349BD8_10_B 2350Bn/a 2351B-308 2352B-0.22 2353B-0.18 2354B-0.11 2355B-0.06 2356B-0.03 2357B0.01 2358B0.02 2359B0.04 2360B0.04

2361BD8_11_C 2362Bn/a 2363B158 2364B0.03 2365B0.02 2366B0.00 2367B-0.02 2368B-0.03 2369B-0.05 2370B-0.08 2371B-0.13 2372B-0.13

2373BD8_11_D 2374Bn/a 2375B308 2376B0.04 2377B0.03 2378B0.00 2379B-0.02 2380B-0.04 2381B-0.08 2382B-0.12 2383B-0.22 2384B-0.24

2385BD8_11_E 2386Bn/a 2387B458 2388B0.05 2389B0.03 2390B0.01 2391B-0.02 2392B-0.04 2393B-0.09 2394B-0.13 2395B-0.26 2396B-0.33

2397BD8_11_F 2398Bn/a 2399B608 2400B0.05 2401B0.04 2402B0.01 2403B-0.02 2404B-0.03 2405B-0.08 2406B-0.12 2407B-0.25 2408B-0.35

500

Table C.13: Lane C—cross-section strains—Girder 7—Span 10

Section 2409BGage

2410BHeight

from

bottom of

girder

(in.)

2411BDistance from

center of

continuity

diaphragm

(in.)

– Span 10

+ Span 11

2412BStrain

(x10-6

in./in.)

– compressive

+ tensile

2413BC1 2414BC2 2415BC3 2416BC4 2417BC5 2418BC6 2419BC7 2420BC8 2421BC9

2422BGir

der

7

2423BCro

ss S

ecti

on

2424B1

2425BS7_10_1V 2426B28.5 2427B-75 -4 1 2428B2 2429B4 2430B2 2431B-4 2432B-3 2433B-5 2434B-6

2435BS7_10_1W 2436B13.5 2437B-75 2438B-5 2439B4 2440B8 2441B9 2442B4 2443B-4 2444B-5 2445B-10 2446B-11

2447BS7_10_1X 2448B13.5 2449B-75 2450B-5 2451B3 2452B7 2453B9 2454B4 2455B-4 2456B-5 2457B-9 2458B-10

2459BS7_10_1Y 2460B3.0 2461B-75 2462B-8 2463B7 2464B15 2465B18 2466B7 2467B-6 2468B-9 2469B-17 2470B-18

2471BF7_10_1M 2472B0.0 2473B-74 2474B-6 2475B9 2476B15 2477B22 2478B11 2479B-5 2480B-8 2481B-16 2482B-17

2483BGir

der

7

2484BCro

ss S

ecti

on

2485B2

2486BS7_10_2V 2487B28.5 2488B-13 2489B2 2490B3 2491B2 2492B2 2493B2 2494B1 2495B-1 2496B-3 2497B-4

2498BS7_10_2W 2499B13.5 2500B-13 2501B2 2502B2 2503B1 2504B-1 2505B-1 2506B1 2507B0 2508B-3 2509B-4

2510BS7_10_2X 2511B13.5 2512B-13 2513B4 2514B2 2515B1 2516B-1 2517B1 2518B2 2519B1 2520B-1 2521B-2

2522BS7_10_2Y 2523B3.0 2524B-13 2525B-154 2526B-135 2527B-87 2528B-45 2529B-24 2530B-37 2531B-47 2532B-99 2533B-105

2534BF7_10_2Z 2535B3.0 2536B-14 2537B-18 2538B-9 2539B-6 2540B-2 2541B0 2542B-10 2543B-16 2544B-28 2545B-27

501

Table C.14: Lane C—cross-section strains—Girder 7—Span 11

Section 2546BGage

2547BHeight

from

bottom of

girder

(in.)

2548BDistance from

center of

continuity

diaphragm

(in.)

– Span 10

+ Span 11

2549BStrain

(x10-6

in./in.)

– compressive

+ tensile

2550BC1 2551BC2 2552BC3 2553BC4 2554BC5 2555BC6 2556BC7 2557BC8 2558BC9

2559BGir

der

7

2560BCro

ss S

ecti

on

2561B3

2562BS7_11_3V 2563B28.5 2564B13 -7 -5 2565B-3 2566B-2 2567B0 2568B0 2569B-3 2570B-3 2571B-2

2572BS7_11_3W 2573B13.5 2574B13 2575B-14 2576B-8 2577B-1 2578B2 2579B6 2580B9 2581B7 2582B1 2583B-2

2584BS7_11_3X 2585B13.5 2586B13 2587B-7 2588B-3 2589B-1 2590B2 2591B6 2592B4 2593B0 2594B2 2595B3

2596BS7_11_3Y 2597B3.0 2598B13 2599B-11 2600B-9 2601B-6 2602B-5 2603B-6 2604B-6 2605B-9 2606B-17 2607B-20

2608BS7_11_3Z 2609B3.0 2610B13 2611B-11 2612B-9 2613B-6 2614B-5 2615B-3 2616B-3 2617B-5 2618B-6 2619B-7

2620BGir

der

7

2621BCro

ss S

ecti

on

2622B4

2623BS7_11_4V 2624B28.5 2625B75 2626B-2 2627B-2 2628B0 2629B-1 2630B-1 2631B0 2632B-3 2633B-5 2634B-4

2635BS7_11_4W 2636B13.5 2637B75 2638B-9 2639B-7 2640B-2 2641B-2 2642B-1 2643B4 2644B6 2645B-1 2646B-6

2647BS7_11_4X 2648B13.5 2649B75 2650B-9 2651B-7 2652B-3 2653B-3 2654B-2 2655B3 2656B4 2657B-3 2658B-8

2659BS7_11_4Y 2660B3.0 2661B75 2662B-15 2663B-12 2664B-3 2665B0 2666B1 2667B13 2668B23 2669B8 2670B-6

2671BF7_11_4M 2672B0.0 2673B74 2674B-18 2675B-14 2676B-4 2677B-2 2678B-1 2679B14 2680B25 2681B7 2682B-8

502

Table C.15: Lane C—cross-section strains—Girder 8—Span 10

Section 2683BGage

2684BHeight

from

bottom of

girder

(in.)

2685BDistance from

center of

continuity

diaphragm

(in.)

– Span 10

+ Span 11

2686BStrain

(x10-6

in./in.)

– compressive

+ tensile

2687BC1 2688BC2 2689BC3 2690BC4 2691BC5 2692BC6 2693BC7 2694BC8 2695BC9

2696BGir

der

8

2697BCro

ss S

ecti

on

2698B1

2699BS8_10_1V 2700B28.5 2701B-75 -10 -3 2702B0 2703B3 2704B1 2705B-4 2706B-5 2707B-9 2708B-10

2709BS8_10_1W 2710B13.5 2711B-75 2712B-13 2713B1 2714B7 2715B10 2716B4 2717B-6 2718B-10 2719B-18 2720B-19

2721BS8_10_1X 2722B13.5 2723B-75 2724B-14 2725B0 2726B6 2727B11 2728B5 2729B-6 2730B-10 2731B-18 2732B-19

2733BF8_10_1Y 2734B3.0 2735B-74 2736B-9 2737B2 2738B8 2739B10 2740B5 2741B-4 2742B-7 2743B-13 2744B-14

2745BS8_10_1M 2746B0.0 2747B-75 2748B-15 2749B7 2750B14 2751B23 2752B11 2753B-9 2754B-14 2755B-25 2756B-27

2757BF8_10_1M 2758B0.0 2759B-74 2760B-10 2761B5 2762B10 2763B16 2764B9 2765B-5 2766B-9 2767B-16 2768B-17

2769BGir

der

8

2770BCro

ss S

ecti

on

2771B2

2772BS8_10_2V 2773B28.5 2774B-13 2775B0 2776B2 2777B2 2778B3 2779B3 2780B0 2781B-2 2782B-5 2783B-6

2784BS8_10_2W 2785B13.5 2786B-13 2787B1 2788B5 2789B5 2790B5 2791B4 2792B-1 2793B-4 2794B-12 2795B-15

2796BS8_10_2X 2797B13.5 2798B-13 2799B4 2800B6 2801B6 2802B4 2803B6 2804B2 2805B-2 2806B-10 2807B-12

2808BF8_10_2Y 2809B3.0 2810B-14 2811B-74 2812B-51 2813B-30 2814B-19 2815B-10 2816B-19 2817B-26 2818B-47 2819B-46

2820BF8_10_2Z 2821B3.0 2822B-14 2823B-26 2824B-18 2825B-10 2826B-4 2827B0 2828B-5 2829B-12 2830B-23 2831B-23

503

Table C.16: Lane C—cross-section strains—Girder 8—Span 11

Section 2832BGage

2833BHeight

from

bottom of

girder

(in.)

2834BDistance from

center of

continuity

diaphragm

(in.)

– Span 10

+ Span 11

2835BStrain

(x10-6

in./in.)

– compressive

+ tensile

2836BC1 2837BC2 2838BC3 2839BC4 2840BC5 2841BC6 2842BC7 2843BC8 2844BC9

2845BGir

der

8

2846BCro

ss S

ecti

on

2847B3

2848BS8_11_3V 2849B28.5 2850B13 -65 -57 2851B-43 2852B-36 2853B-27 2854B-17 2855B-25 2856B-42 2857B-51

2858BS8_11_3W 2859B13.5 2860B13 2861B-27 2862B-18 2863B-9 2864B-3 2865B2 2866B1 2867B-7 2868B-15 2869B-16

2870BS8_11_3X 2871B13.5 2872B13 2873B-54 2874B-40 2875B-9 2876B-3 2877B5 2878B25 2879B28 2880B-2 2881B-22

2882BF8_11_3Y 2883B3.0 2884B14 2885B-45 2886B-38 2887B-23 2888B-17 2889B-11 2890B-5 2891B-14 2892B-45 2893B-54

2894BF8_11_3Z 2895B3.0 2896B14 2897B-44 2898B-37 2899B-25 2900B-22 2901B-15 2902B-11 2903B-25 2904B-53 2905B-53

2906BGir

der

8

2907BCro

ss S

ecti

on

2908B4

2909BS8_11_4V 2910B28.5 2911B75 2912B-6 2913B-5 2914B-3 2915B-6 2916B-5 2917B-6 2918B-17 2919B-23 2920B-16

2921BS8_11_4W 2922B13.5 2923B75 2924B-17 2925B-13 2926B-5 2927B-4 2928B-2 2929B3 2930B2 2931B-11 2932B-16

2933BS8_11_4X 2934B13.5 2935B75 2936B-12 2937B-9 2938B-3 2939B-4 2940B-2 2941B1 2942B-2 2943B-11 2944B-14

2945BF8_11_4Y 2946B3.0 2947B74 2948B-16 2949B-12 2950B-3 2951B-1 2952B0 2953B10 2954B17 2955B0 2956B-10

2957BS8_11_4M 2958B0.0 2959B75 2960B-56 2961B-48 2962B-13 2963B-4 2964B2 2965B56 2966B121 2967B32 2968B-23

2969BF8_11_4M 2970B0.0 2971B74 2972B-31 2973B-25 2974B-6 2975B-2 2976B1 2977B26 2978B52 2979B14 2980B-13

504

Table C.17: Lane C—bottom-fiber strains—Girder 7

Span 2981BGage

2982BHeight

from

bottom of

girder

(in.)

2983BDistance from

center of

continuity

diaphragm

(in.)

– Span 10

+ Span 11

2984BStrain

(x10-6

in./in.)

– compressive

+ tensile

2985BC1 2986BC2 2987BC3 2988BC4 2989BC5 2990BC6 2991BC7 2992BC8 2993BC9

2994B10

2995BF7_10_1M 2996B0 2997B-74 -6 9 2998B15 2999B22 3000B11 3001B-5 3002B-8 3003B-16 3004B-17

3005BF7_10_CK 3006B0 3007B-47 3008B-67 3009B14 3010B51 3011B95 3012B59 3013B-37 3014B-60 3015B-115 3016B-122

3017B11

3018BF7_11_CK 3019B0 3020B47 3021B-132 3022B-110 3023B-46 3024B-34 3025B-21 3026B76 3027B116 3028B-8 3029B-82

3030BF7_11_4M 3031B0 3032B74 3033B-18 3034B-14 3035B-4 3036B-2 3037B-1 3038B14 3039B25 3040B7 3041B-8

3042BF7_11_5M 3043B0 3044B104 3045B-17 3046B-13 3047B-4 3048B1 3049B0 3050B12 3051B28 3052B12 3053B-4

3054BS7_11_5M 3055B0 3056B105 3057B-16 3058B-13 3059B-4 3060B0 3061B1 3062B14 3063B27 3064B12 3065B-4

3066BS7_11_6M 3067B0 3068B273 3069B-18 3070B-14 3071B-5 3072B3 3073B10 3074B25 3075B37 3076B79 3077B34

3078BS7_11_7M 3079B0 3080B441 3081B-12 3082B-11 3083B-4 3084B2 3085B7 3086B14 3087B31 3088B63 3089B71

3090BS7_11_8M 3091B0 3092B609 3093B-9 3094B-8 3095B-2 3096B3 3097B7 3098B15 3099B24 3100B52 3101B105

505

Table C.18: Lane C—bottom-fiber strains—Girder 8

Span 3102BGage

3103BHeight

from

bottom of

girder

(in.)

3104BDistance from

center of

continuity

diaphragm

(in.)

– Span 10

+ Span 11

3105BStrain

(x10-6

in./in.)

– compressive

+ tensile

3106BC1 3107BC2 3108BC3 3109BC4 3110BC5 3111BC6 3112BC7 3113BC8 3114BC9

3115B10

3116BS8_10_1M 3117B0 3118B-75 -15 7 3119B14 3120B23 3121B11 3122B-9 3123B-14 3124B-25 3125B-27

3126BF8_10_1M 3127B0 3128B-74 3129B-10 3130B5 3131B10 3132B16 3133B9 3134B-5 3135B-9 3136B-16 3137B-17

3138BF8_10_CK 3139B0 3140B-41 3141B-165 3142B-30 3143B32 3144B113 3145B82 3146B-58 3147B-108 3148B-211 3149B-222

3150B11

3151BF8_11_CK 3152B0 3153B52 3154B-100 3155B-87 3156B-38 3157B-30 3158B-18 3159B44 3160B56 3161B-21 3162B-67

3163BF8_11_4M 3164B0 3165B74 3166B-31 3167B-25 3168B-6 3169B-2 3170B1 3171B26 3172B52 3173B14 3174B-13

3175BS8_11_4M 3176B0 3177B75 3178B-56 3179B-48 3180B-13 3181B-4 3182B2 3183B56 3184B121 3185B32 3186B-23

3187BF8_11_5M 3188B0 3189B104 3190B-29 3191B-22 3192B-4 3193B1 3194B1 3195B16 3196B32 3197B10 3198B-12

3199BS8_11_5M 3200B0 3201B105 3202B-26 3203B-21 3204B-5 3205B1 3206B2 3207B17 3208B32 3209B10 3210B-11

3211BS8_11_6M 3212B0 3213B273 3214B-20 3215B-16 3216B-4 3217B7 3218B16 3219B34 3220B46 3221B91 3222B38

3223BS8_11_7M 3224B0 3225B441 3226B-16 3227B-13 3228B-4 3229B3 3230B9 3231B23 3232B39 3233B82 3234B87

3235BS8_11_8M 3236B0 3237B609 3238B-10 3239B-7 3240B-2 3241B2 3242B6 3243B14 3244B24 3245B58 3246B113

506

Table C.19: Lane C—FRP strains—Girder 7

Span 3247BGage

3248BHeight

from

bottom of

girder

(in.)

3249BDistance from

center of

continuity

diaphragm

(in.)

– Span 10

+ Span 11

3250BStrain

(x10-6

in./in.)

– compressive

+ tensile

3251BC1 3252BC2 3253BC3 3254BC4 3255BC5 3256BC6 3257BC7 3258BC8 3259BC9

3260B10

3261BF7_10_1M 3262B0 3263B-74 -6 9 3264B15 3265B22 3266B11 3267B-5 3268B-8 3269B-16 3270B-17

3271BF7_10_CK 3272B0 3273B-47 3274B-67 3275B14 3276B51 3277B95 3278B59 3279B-37 3280B-60 3281B-115 3282B-122

3283BF7_10_2Z 3284B3 3285B-14 3286B-18 3287B-9 3288B-6 3289B-2 3290B0 3291B-10 3292B-16 3293B-28 3294B-27

3295B11

3296BF7_11_CK 3297B0 3298B47 3299B-132 3300B-110 3301B-46 3302B-34 3303B-21 3304B76 3305B116 3306B-8 3307B-82

3308BF7_11_4M 3309B0 3310B74 3311B-18 3312B-14 3313B-4 3314B-2 3315B-1 3316B14 3317B25 3318B7 3319B-8

3320BF7_11_5M 3321B0 3322B104 3323B-17 3324B-13 3325B-4 3326B1 3327B0 3328B12 3329B28 3330B12 3331B-4

507

Table C.20: Lane C—FRP strains—Girder 8

Span 3332BGage

3333BHeight

from

bottom of

girder

(in.)

3334BDistance from

center of

continuity

diaphragm

(in.)

– Span 10

+ Span 11

3335BStrain

(x10-6

in./in.)

– compressive

+ tensile

3336BC1 3337BC2 3338BC3 3339BC4 3340BC5 3341BC6 3342BC7 3343BC8 3344BC9

3345B10

3346BF8_10_1Y 3347B3 3348B-74 3349B-9 3350B2 3351B8 3352B10 3353B5 3354B-4 3355B-7 3356B-13 3357B-14

3358BF8_10_1M 3359B0 3360B-74 3361B-10 3362B5 3363B10 3364B16 3365B9 3366B-5 3367B-9 3368B-16 3369B-17

3370BF8_10_CK 3371B0 3372B-41 3373B-165 3374B-30 3375B32 3376B113 3377B82 3378B-58 3379B-108 3380B-211 3381B-222

3382BF8_10_2Y 3383B3 3384B-14 3385B-74 3386B-51 3387B-30 3388B-19 3389B-10 3390B-19 3391B-26 3392B-47 3393B-46

3394BF8_10_2Z 3395B3 3396B-14 3397B-26 3398B-18 3399B-10 3400B-4 3401B0 3402B-5 3403B-12 3404B-23 3405B-23

3406B11

3407BF8_11_3Y 3408B3 3409B14 3410B-45 3411B-38 3412B-23 3413B-17 3414B-11 3415B-5 3416B-14 3417B-45 3418B-54

3419BF8_11_3Z 3420B3 3421B14 3422B-44 3423B-37 3424B-25 3425B-22 3426B-15 3427B-11 3428B-25 3429B-53 3430B-53

3431BF8_11_CK 3432B0 3433B52 3434B-100 3435B-87 3436B-38 3437B-30 3438B-18 3439B44 3440B56 3441B-21 3442B-67

3443BF8_11_4Y 3444B3 3445B74 3446B-16 3447B-12 3448B-3 3449B-1 3450B0 3451B10 3452B17 3453B0 3454B-10

3455BF8_11_4M 3456B0 3457B74 3458B-31 3459B-25 3460B-6 3461B-2 3462B1 3463B26 3464B52 3465B14 3466B-13

3467BF8_11_5M 3468B0 3469B104 3470B-29 3471B-22 3472B-4 3473B1 3474B1 3475B16 3476B32 3477B10 3478B-12

508

Appendix D

17BBRIDGE MONITORING—GRAPHICAL RESULTS

509

D.1 83BCRACK-OPENING DISPLACEMENTS

Figure D.1: Crack-opening displacements—24 hrs

-0.05

0.00

0.05

0.10

0.15

0.20

2:30 5/25 6:30 5/25 10:30 5/25 14:30 5/25 18:30 5/25 22:30 5/25 2:30 5/26

Cra

ck-O

pen

ing D

isp

lace

men

t (m

m)

Time of Day (hr:min month/day)

CO7_10

CO8_10

CO7_11

CO8_11

510

D.2 84BDEFLECTIONS

Figure D.2: Deflections—24 hrs—Girder 7

Figure D.3: Deflections—24 hrs—Girder 8

-0.2

-0.1

0.0

0.1

0.2

0.3

0.4

0.5

2:30 5/25 6:30 5/25 10:30 5/25 14:30 5/25 18:30 5/25 22:30 5/25 2:30 5/26

Bo

tto

m-F

iber

Def

lect

ion

(in

.)

Time of Day (hr:min month/day)

G7 - SP10 - Midspan

G7 - SP10 - Q. Span

G7 - SP11 - Q. Span

G7 - SP11 - Midspan

-0.2

-0.1

0.0

0.1

0.2

0.3

0.4

0.5

2:30 5/25 6:30 5/25 10:30 5/25 14:30 5/25 18:30 5/25 22:30 5/25 2:30 5/26

Bo

tto

m-F

iber

Def

lect

ion

(in

.)

Time of Day (hr:min month/day)

G8 - SP10 - Midspan

G8 - SP10 - Q. Span

G8 - SP11 - Q. Span

G8 - SP11 - Midspan

511

D.3 85BBOTTOM-FIBER STRAINS

Figure D.4: Bottom-fiber strains—24 hrs—Girder 7—within 80 in. from diaphragm

Figure D.5: Bottom-fiber strains—24 hrs—Girder 7—beyond 80 in. from diaphragm

-200

-100

0

100

200

300

400

500

600

2:30 5/25 6:30 5/25 10:30 5/25 14:30 5/25 18:30 5/25 22:30 5/25 2:30 5/26

Bo

tto

m-F

iber

Str

ain

(x

10

-6 in

./in

.)

Time of Day (hr:min month/day)

F7_10_1M

F7_10_CK

F7_11_CK

F7_11_4M

-100

-75

-50

-25

0

25

50

2:30 5/25 6:30 5/25 10:30 5/25 14:30 5/25 18:30 5/25 22:30 5/25 2:30 5/26

Bo

tto

m-F

iber

Str

ain

(x

10

-6 in

./in

.)

Time of Day (hr:min month/day)

S7_11_5M

F7_11_5M

S7_11_6M

S7_11_7M

S7_11_8M

512

Figure D.6: Bottom-fiber strains—24 hrs—Girder 8—within 80 in. from diaphragm

Figure D.7: Bottom-fiber strains—24 hrs—Girder 8—beyond 80 in. from diaphragm

-200

-100

0

100

200

300

400

500

600

2:30 5/25 6:30 5/25 10:30 5/25 14:30 5/25 18:30 5/25 22:30 5/25 2:30 5/26

Bo

tto

m-F

iber

Str

ain

(x

10

-6 in

./in

.)

Time of Day (hr:min month/day)

S8_10_1MF8_10_1MF8_10_CKF8_11_CKS8_11_4MF8_11_4M

-100

-75

-50

-25

0

25

50

2:30 5/25 6:30 5/25 10:30 5/25 14:30 5/25 18:30 5/25 22:30 5/25 2:30 5/26

Bo

tto

m-F

iber

Str

ain

(x

10

-6 in

./in

.)

Time of Day (hr:min month/day)

S8_11_5M

F8_11_5M

S8_11_6M

S8_11_7M

S8_11_8M

513

Figure D.8: Bottom-fiber strains—24 hrs—FRP near crack locations

-200

-100

0

100

200

300

400

500

600

2:30 5/25 6:30 5/25 10:30 5/25 14:30 5/25 18:30 5/25 22:30 5/25 2:30 5/26

Str

ain

(x10

-6in

./in

.)

Time of Day (hr:min month/day)

F7_10_CK

F7_11_CK

F8_10_CK

F8_11_CK

514

D.4 86BBOTTOM-FIBER STRAINS AND CRACK-OPENING DISPLACEMENTS

Figure D.9: Bottom-fiber strain and COD—24 hrs—Girder 7—Span 10

Figure D.10: Bottom-fiber strain and COD—24 hrs—Girder 7—Span 11

-0.06

-0.03

0.00

0.03

0.06

0.09

0.12

0.15

0.18

-200

-100

0

100

200

300

400

500

600

2:30 5/25 6:30 5/25 10:30 5/25 14:30 5/25 18:30 5/25 22:30 5/25 2:30 5/26

Cra

ck-O

pen

ing D

isp

lace

men

t (m

m)

Bo

tto

m-F

iber

Str

ain

(x

10

-6 in

./in

.)

Time of Day (hr:min month/day)

F7_10_CK

CO7_10

-0.03

-0.06

-0.06

-0.03

0.00

0.03

0.06

0.09

0.12

0.15

0.18

-200

-100

0

100

200

300

400

500

600

2:30 5/25 6:30 5/25 10:30 5/25 14:30 5/25 18:30 5/25 22:30 5/25 2:30 5/26

Cra

ck-O

pen

ing D

isp

lace

men

t (m

m)

Bo

tto

m-F

iber

Str

ain

(x

10

-6 in

./in

.)

Time of Day (hr:min month/day)

F7_11_CK

CO7_11

-0.03

-0.06

515

Figure D.11: Bottom-fiber strain and COD—24 hrs—Girder 8—Span 10

Figure D.12: Bottom-fiber strain and COD—24 hrs—Girder 8—Span 11

-0.06

-0.03

0.00

0.03

0.06

0.09

0.12

0.15

0.18

-200

-100

0

100

200

300

400

500

600

2:30 5/25 6:30 5/25 10:30 5/25 14:30 5/25 18:30 5/25 22:30 5/25 2:30 5/26

Cra

ck-O

pen

ing D

isp

lace

men

t (m

m)

Bo

tto

m-F

iber

Str

ain

(x

10

-6 in

./in

.)

Time of Day (hr:min month/day)

F8_10_CK

CO8_10

-0.03

-0.06

-0.06

-0.03

0.00

0.03

0.06

0.09

0.12

0.15

0.18

-200

-100

0

100

200

300

400

500

600

2:30 5/25 6:30 5/25 10:30 5/25 14:30 5/25 18:30 5/25 22:30 5/25 2:30 5/26

Cra

ck-O

pen

ing D

isp

lace

men

t (m

m)

Bo

tto

m-F

iber

Str

ain

(x

10

-6 in

./in

.)

Time of Day (hr:min month/day)

F8_11_CK

CO8_11

-0.03

-0.06

516

Appendix E

18BBRIDGE MONITORING MEASUREMENTS

517

E.1 87BCRACK-OPENING DISPLACEMENTS

Table E.1: Bridge monitoring—crack-opening displacements

Girder 7 Girder 8

CO

7_

10

CO

7_

11

CO

8_

10

CO

8_

11

Ht. from girder base (in.) 13.5 13.5 13.5 13.5

Dist. from center of cont. dia. (in.) -50 48 -40 56

Units mm

Date Time

5/25/2010

2:30 0.000 0.000 0.000 0.000

3:30 -0.009 -0.008 -0.009 -0.007

4:30 -0.011 -0.013 -0.011 -0.010

5:30 -0.012 -0.018 -0.012 -0.012

6:30 -0.014 -0.022 -0.014 -0.014

7:30 -0.014 -0.020 -0.013 -0.013

8:30 -0.009 -0.011 -0.009 -0.009

9:30 0.000 0.008 -0.002 0.001

10:30 0.013 0.029 0.006 0.014

11:30 0.024 0.046 0.013 0.027

12:30 0.049 0.082 0.031 0.051

13:30 0.079 0.127 0.055 0.083

14:30 0.101 0.159 0.072 0.108

15:30 0.109 0.169 0.077 0.120

16:30 0.108 0.168 0.076 0.122

17:30 0.101 0.158 0.070 0.118

18:30 0.086 0.134 0.058 0.102

19:15 0.071 0.114 0.047 0.088

20:30 0.049 0.078 0.029 0.060

21:30 0.033 0.055 0.019 0.041

22:30 0.023 0.037 0.013 0.028

23:00 0.017 0.028 0.009 0.021

5/26/2010

0:50 0.004 0.006 0.003 0.008

1:30 0.002 -0.005 -0.003 -0.002

2:30 -0.006 -0.009 -0.007 -0.004

518

E.2 88BDEFLECTIONS

Table E.2: Bridge monitoring—deflections—Girder 7

Span 10 Span 11

D7

_1

0_

A

D7

_1

0_

B

D7

_1

1_

C

D7

_1

1_

D

D7

_1

1_

E

D7

_1

1_

F

Ht. from girder base (in.) n/a n/a n/a n/a n/a n/a

Dist. from center of cont. dia. (in.) -608 -308 158 308 458 608

Units in.

Date Time

5/25/2010

2:30 0.00 0.00 0.00 0.00 0.00 0.00

3:30 -0.04 -0.03 -0.03 -0.04 -0.04 -0.04

4:30 -0.07 -0.04 0.00 -0.04 -0.04 -0.13

5:30 -0.10 -0.07 -0.01 -0.06 -0.06 -0.10

6:30 -0.11 -0.08 -0.01 -0.07 -0.09 -0.10

7:30 0.00 0.00 0.00 -0.02 0.00 -0.07

8:30 0.00 0.00 0.00 0.00 0.00 0.00

9:30 0.00 0.00 0.00 0.00 0.00 0.00

10:30 0.00 0.00 0.00 0.00 0.00 0.00

11:30 0.21 0.18 0.17 0.00 0.17 0.17

12:30 0.26 0.22 0.19 0.23 0.21 0.21

13:30 0.34 0.31 0.23 0.28 0.28 0.29

14:30 0.39 0.35 0.27 0.32 0.34 0.35

15:30 0.41 0.38 0.29 0.35 0.36 0.38

16:30 0.41 0.37 0.28 0.34 0.38 0.39

17:30 0.37 0.35 0.26 0.32 0.35 0.37

18:30 0.30 0.28 0.23 0.30 0.30 0.32

19:15 0.24 0.21 0.19 0.26 0.24 0.26

20:30 0.13 0.11 0.13 0.19 0.16 0.18

21:30 0.07 0.06 0.09 0.14 0.10 0.12

22:30 0.02 0.01 0.06 0.09 0.06 0.09

23:00 0.00 0.00 0.05 0.08 0.04 0.08

5/26/2010

0:50 -0.07 -0.06 -0.02 0.00 -0.05 0.00

1:30 -0.10 -0.09 -0.04 -0.02 -0.07 -0.03

2:30 -0.14 -0.11 -0.06 -0.05 -0.10 -0.05

519

Table E.3: Bridge monitoring—deflections—Girder 8

Span 10 Span 11

D8

_1

0_

A

D8

_1

0_

B

D8

_1

1_C

D8

_1

1_

D

D8

_1

1_

E

D8

_1

1_

F

Ht. from girder base (in.) n/a n/a n/a n/a n/a n/a

Dist. from center of cont. dia. (in.) -608 -308 158 308 458 608

Units in.

Date Time

5/25/2010

2:30 0.00 0.00 0.00 0.00 0.00 0.00

3:30 -0.04 -0.02 -0.03 -0.03 -0.03 -0.04

4:30 -0.06 -0.05 -0.03 -0.08 -0.04 -0.08

5:30 -0.08 -0.06 -0.05 -0.07 -0.02 -0.05

6:30 -0.03 -0.01 -0.06 -0.06 0.00 -0.02

7:30 0.00 0.00 -0.03 -0.03 0.02 0.00

8:30 0.00 0.00 0.00 0.00 0.00 0.00

9:30 0.00 0.00 0.00 0.00 0.00 0.00

10:30 0.00 0.00 0.00 0.00 0.00 0.00

11:30 0.00 0.00 0.00 0.00 0.00 0.00

12:30 0.37 0.36 0.17 0.30 0.32 0.33

13:30 0.42 0.38 0.20 0.33 0.36 0.37

14:30 0.46 0.40 0.22 0.37 0.39 0.40

15:30 0.49 0.39 0.22 0.36 0.39 0.40

16:30 0.48 0.38 0.22 0.34 0.36 0.37

17:30 0.45 0.36 0.20 0.32 0.34 0.35

18:30 0.44 0.36 0.18 0.30 0.28 0.28

19:15 0.37 0.29 0.16 0.26 0.23 0.24

20:30 0.25 0.20 0.10 0.17 0.17 0.16

21:30 0.20 0.16 0.06 0.09 0.11 0.12

22:30 0.14 0.12 0.03 0.05 0.07 0.06

23:00 0.13 0.10 0.03 0.04 0.06 0.05

5/26/2010

0:50 0.06 0.04 -0.04 -0.02 -0.03 -0.03

1:30 0.04 0.02 -0.06 -0.04 -0.05 -0.06

2:30 0.01 0.01 -0.08 -0.06 -0.08 -0.08

520

E.3 89BCROSS-SECTION STRAINS

Table E.4: Bridge monitoring—strains—Girder 7—Section 1

S7

_1

0_

1V

S7

_1

0_

1W

S7

_1

0_

1X

S7

_1

0_

1Y

F7_

10

_1

M

Ht. from girder base (in.) 28.5 13.5 13.5 3.0 0.0

Dist. from center of cont. dia. (in.) -75 -75 -75 -75 -74

Units x10-6 in/in

Date Time

5/25/2010

2:30 0 0 0 0 0

3:30 -1 0 0 -3 0

4:30 -5 -3 -1 -1 0

5:30 -8 -6 -2 -4 2

6:30 -10 -9 -4 -9 -1

7:30 -10 -9 -4 -9 -1

8:30 -6 -7 -3 -9 -1

9:30 0 -3 0 -5 0

10:30 4 0 4 2 5

11:30 6 3 6 4 9

12:30 11 9 10 15 16

13:30 17 17 17 27 27

14:30 24 25 23 39 35

15:30 24 26 25 41 38

16:30 24 26 26 40 38

17:30 23 24 24 36 34

18:30 20 20 21 30 30

19:15 17 16 18 24 23

20:30 14 11 14 18 20

21:30 10 7 12 11 15

22:30 6 4 10 7 12

23:00 4 2 7 6 9

5/26/2010

0:50 -2 -4 0 -1 3

1:30 -3 -4 0 -3 3

2:30 -5 -6 -1 -3 1

521

Table E.5: Bridge monitoring—strains—Girder 7—Section 2

S7

_1

0_

2V

S7

_1

0_

2W

S7

_1

0_

2X

S7

_1

0_

2Y

F7_

10

_2

Z

Ht. from girder base (in.) 28.5 13.5 13.5 3.0 3.0

Dist. from center of cont. dia. (in.) -13 -13 -13 -13 -14

Units x10-6 in/in

Date Time

5/25/2010

2:30 0 0 0 0 0

3:30 -1 -1 0 -67 -4

4:30 -3 -2 5 -79 -5

5:30 -4 8 8 -90 -6

6:30 -7 5 13 -109 -7

7:30 -7 5 16 -111 -7

8:30 -6 6 16 -90 -3

9:30 -5 7 17 5 6

10:30 -4 9 16 135 15

11:30 -4 9 15 201 20

12:30 -2 10 12 425 33

13:30 0 11 11 743 55

14:30 3 13 11 963 72

15:30 3 12 10 1039 77

16:30 3 12 10 1038 76

17:30 3 12 12 940 68

18:30 2 12 15 768 57

19:15 1 11 17 611 46

20:30 1 12 19 376 32

21:30 0 10 19 254 24

22:30 -1 9 20 169 19

23:00 -1 9 21 126 14

5/26/2010

0:50 -6 4 21 19 6

1:30 -6 5 20 -29 4

2:30 -7 4 21 -75 0

522

Table E.6: Bridge monitoring—strains—Girder 7—Section 3

S7

_1

1_

3V

S7

_1

1_

3W

S7

_1

1_

3X

S7

_1

1_

3Y

S7

_1

1_

3Z

Ht. from girder base (in.) 28.5 13.5 13.5 3.0 3.0

Dist. from center of cont. dia. (in.) 13 13 13 13 13

Units x10-6 in/in

Date Time

5/25/2010

2:30 0 0 0 0 0

3:30 -2 -6 0 -15 2

4:30 1 -6 1 -49 4

5:30 0 -6 1 -70 4

6:30 -2 -8 2 -91 1

7:30 -3 -8 1 5761 1

8:30 -4 -7 1 5296 4

9:30 -1 -3 -2 4918 4

10:30 9 3 0 4489 12

11:30 8 3 -3 3784 12

12:30 14 7 -7 3110 21

13:30 27 13 -11 2500 30

14:30 39 20 -9 2175 35

15:30 38 19 -14 2037 31

16:30 36 17 -17 1955 29

17:30 35 17 -13 1795 29

18:30 35 16 -8 1738 31

19:15 28 14 -4 1701 29

20:30 21 10 -3 1631 18

21:30 13 6 -5 1584 12

22:30 10 3 -2 1559 8

23:00 9 3 -1 1549 7

5/26/2010

0:50 2 -2 -6 1492 -3

1:30 5 -4 3 1478 5

2:30 1 -8 -2 1428 3

523

Table E.7: Bridge monitoring—strains—Girder 7—Section 4

S7

_1

1_

4V

S7

_1

1_

4W

S7

_1

1_

4X

S7

_1

1_

4Y

F7_

11

_4

M

Ht. from girder base (in.) 28.5 13.5 13.5 3.0 0.0

Dist. from center of cont. dia. (in.) 75 75 75 75 74

Units x10-6 in/in

Date Time

5/25/2010

2:30 0 0 0 0 0

3:30 -1 0 0 1 0

4:30 -3 -3 -1 -3 -2

5:30 -5 -3 -1 -4 -4

6:30 -7 -4 -4 -6 -6

7:30 -7 -5 -5 -7 -4

8:30 -4 -2 -4 -4 -4

9:30 -1 0 -1 1 1

10:30 3 5 5 7 6

11:30 5 8 6 11 11

12:30 12 16 13 24 21

13:30 19 25 21 36 34

14:30 25 35 31 50 44

15:30 25 36 29 50 46

16:30 24 35 31 48 46

17:30 22 34 29 46 43

18:30 17 29 28 40 38

19:15 15 27 24 36 32

20:30 9 20 17 25 23

21:30 5 16 12 19 16

22:30 3 12 9 16 15

23:00 2 9 7 13 12

5/26/2010

0:50 -4 0 -2 3 6

1:30 -3 1 -1 7 4

2:30 -6 -1 -4 4 6

524

Table E.8: Bridge monitoring—strains—Girder 8—Section 1

S8

_1

0_

1V

S8

_1

0_

1W

S8

_1

0_

1X

F8_

10

_1

Y

S8

_1

0_

1M

F8_

10

_1

M

Ht. from girder base (in.) 28.5 13.5 13.5 3.0 0.0 0.0

Dist. from center of cont. dia. (in.) -75 -75 -75 -74 -75 -74

Units x10-6 in/in

Date Time

5/25/2010

2:30 0 0 0 0 0 0

3:30 -2 -5 0 0 -7 1

4:30 -5 -1 -3 0 -11 1

5:30 -3 -5 -6 0 -15 0

6:30 -6 -10 -9 -1 -20 -1

7:30 -5 -12 -9 2 -17 0

8:30 0 -10 -6 0 -23 0

9:30 6 -4 0 1 -16 0

10:30 13 2 5 3 -12 0

11:30 19 6 9 4 -11 1

12:30 26 14 16 7 -4 0

13:30 36 24 25 11 9 7

14:30 43 32 34 15 22 13

15:30 44 33 35 14 24 16

16:30 44 32 35 13 25 15

17:30 44 32 35 12 23 15

18:30 40 29 31 11 21 13

19:15 37 26 28 9 19 10

20:30 30 20 21 6 9 8

21:30 24 13 15 3 0 5

22:30 20 10 12 5 1 6

23:00 17 8 9 4 0 5

5/26/2010

0:50 9 0 1 3 -14 -1

1:30 8 1 2 4 -18 -1

2:30 5 -2 -1 4 -18 -1

525

Table E.9: Bridge monitoring—strains—Girder 8—Section 2

S8

_1

0_

2V

S8

_1

0_

2W

S8

_1

0_

2X

F8_

10

_2

Y

F8_

10

_2

Z

Ht. from girder base (in.) 28.5 13.5 13.5 3.0 3.0

Dist. from center of cont. dia. (in.) -13 -13 -13 -14 -14

Units x10-6 in/in

Date Time

5/25/2010

2:30 0 0 0 0 0

3:30 -2 -2 1 -11 1

4:30 -3 -4 0 9 -1

5:30 -5 -3 0 23 -1

6:30 -5 -5 -1 43 -2

7:30 -4 -5 -1 42 -2

8:30 -3 -4 0 52 0

9:30 -1 -3 -1 69 3

10:30 1 -4 -1 84 2

11:30 2 -5 -1 90 4

12:30 5 -4 -2 125 9

13:30 8 -4 -5 167 16

14:30 11 -1 -5 202 23

15:30 10 -2 -5 210 23

16:30 10 -1 -5 208 23

17:30 10 0 -4 195 21

18:30 10 -1 -3 170 18

19:15 9 -1 -2 147 14

20:30 7 4 0 110 9

21:30 5 3 0 90 6

22:30 4 2 0 80 6

23:00 4 1 0 75 5

5/26/2010

0:50 0 -2 -1 58 4

1:30 0 -5 -1 57 3

2:30 -1 -5 1 51 3

526

Table E.10: Bridge monitoring—strains—Girder 8—Section 3

S8

_1

1_

3V

S8

_1

1_

3W

S8

_1

1_

3X

F8_

11

_3

Y

F8_

11

_3

Z

Ht. from girder base (in.) 28.5 13.5 13.5 3.0 3.0

Dist. from center of cont. dia. (in.) 13 13 13 14 14

Units x10-6 in/in

Date Time

5/25/2010

2:30 0 0 0 0 0

3:30 -21 -1 -11 -11 -13

4:30 -29 -5 -15 -18 -14

5:30 -40 -6 -17 -22 -16

6:30 -50 -8 -20 -26 -21

7:30 -52 -7 -21 -28 -21

8:30 -33 -4 -20 -18 -11

9:30 5 -3 -16 -5 -8

10:30 60 0 -9 10 5

11:30 101 2 -2 25 20

12:30 196 5 13 57 53

13:30 318 4 37 94 97

14:30 405 -2 69 119 130

15:30 430 0 84 125 140

16:30 429 2 85 126 142

17:30 409 7 83 118 132

18:30 365 8 72 101 112

19:15 320 9 65 87 91

20:30 228 7 46 57 58

21:30 167 4 34 36 35

22:30 126 1 28 22 20

23:00 109 -2 24 15 12

5/26/2010

0:50 75 -7 15 -1 3

1:30 -3 -7 -9 -9 -11

2:30 -29 -10 -19 -16 -12

527

Table E.11: Bridge monitoring—strains—Girder 8—Section 4

S8

_1

1_

4V

S8

_1

1_

4W

S8

_1

1_

4X

F8_

11

_4

Y

S8

_1

1_

4M

F8_

11

_4

M

Ht. from girder base (in.) 28.5 13.5 13.5 3.0 0.0 0.0

Dist. from center of cont. dia. (in.) 75 75 75 74 75 74

Units x10-6 in/in

Date Time

5/25/2010

2:30 0 0 0 0 0 0

3:30 -2 -1 -1 -4 -12 -4

4:30 -3 -2 0 -5 -18 -3

5:30 -4 -1 -1 -7 -25 -5

6:30 -6 -2 -3 -10 -36 -9

7:30 -6 -3 -4 -11 -39 -11

8:30 -3 -1 -4 -10 -32 -12

9:30 -1 3 -1 -7 -19 -9

10:30 3 9 6 -2 4 2

11:30 2 11 5 1 26 7

12:30 5 16 9 9 77 23

13:30 9 24 17 22 165 54

14:30 11 29 23 32 239 82

15:30 8 28 24 37 279 97

16:30 7 30 22 38 297 101

17:30 6 28 23 37 284 98

18:30 8 27 22 31 241 84

19:15 5 22 18 25 195 68

20:30 5 18 11 14 116 41

21:30 1 12 7 6 76 25

22:30 -1 9 4 1 45 14

23:00 0 7 4 0 33 10

5/26/2010

0:50 -2 -1 -2 -4 7 -1

1:30 -2 -1 0 -7 -13 -7

2:30 -5 -4 -2 -9 -20 -8

528

E.4 90BBOTTOM-FIBER STRAINS

Table E.12: Bridge monitoring—bottom-fiber strains—Girder 7

Span 10 Span 11

F7_

10

_1

M

F7_

10

_C

K

F7_

11

_C

K

F7_

11

_4

M

Ht. from girder base (in.) 0 0 0 0

Dist. from center of cont. dia. (in.) -74 -47 47 74

Units x10-6 in/in

Date Time

5/25/2010

2:30 0 0 0 0

3:30 0 -50 -37 0

4:30 0 -60 -51 -2

5:30 2 -67 -62 -4

6:30 -1 -78 -79 -6

7:30 -1 -79 -79 -4

8:30 -1 -59 -58 -4

9:30 0 -15 -3 1

10:30 5 38 65 6

11:30 9 77 116 11

12:30 16 167 228 21

13:30 27 277 368 34

14:30 35 358 475 44

15:30 38 385 504 46

16:30 38 387 502 46

17:30 34 359 466 43

18:30 30 312 401 38

19:15 23 261 340 32

20:30 20 185 233 23

21:30 15 125 160 16

22:30 12 88 112 15

23:00 9 61 84 12

5/26/2010

0:50 3 14 23 6

1:30 3 -6 -7 4

2:30 1 -39 -28 6

529

2228HTable E.12 cont.: Bridge monitoring—bottom-fiber strains—Girder 7

Span 11

S7

_1

1_

5M

F7_

11

_5

M

S7

_1

1_

6M

S7

_1

1_

7M

S7

_1

1_

8M

Ht. from girder base (in.) 0 0 0 0 0

Dist. from center of cont. dia. (in.) 105 104 273 441 609

Units x10-6 in/in

Date Time

5/25/2010

2:30 0 0 0 0 0

3:30 -2 1 -7 -16 -24

4:30 4 3 -15 -30 -38

5:30 -2 3 -16 -29 -32

6:30 -12 0 -16 -24 -22

7:30 -13 0 -15 -22 -19

8:30 -12 -5 -23 -37 -51

9:30 -11 -6 -19 -27 -34

10:30 1 -2 -20 -33 -52

11:30 -2 1 -15 -27 -45

12:30 4 4 -12 -29 -55

13:30 16 14 -4 -21 -50

14:30 19 25 2 -16 -53

15:30 25 23 5 -13 -54

16:30 31 25 7 -14 -56

17:30 27 25 9 -8 -45

18:30 33 27 4 -14 -51

19:15 20 23 6 -8 -37

20:30 15 17 0 -19 -52

21:30 14 13 0 -16 -47

22:30 -1 11 1 -11 -29

23:00 -1 9 -1 -15 -38

5/26/2010

0:50 0 7 -10 -28 -58

1:30 -11 8 -10 -29 -55

2:30 -11 7 -11 -27 -50

530

Table E.13: Bridge monitoring—bottom-fiber strains—Girder 8

Span 10 Span 11

S8

_1

0_

1M

F8_

10

_1

M

F8_

10

_C

K

F8_

11

_C

K

S8

_1

1_

4M

F8_

11

_4

M

Ht. from girder base (in.) 0 0 0 0 0 0

Dist. from center of cont. dia. (in.) -75 -74 -41 52 75 74

Units x10-6 in/in

Date Time

5/25/2010

2:30 0 0 0 0 0 0

3:30 -7 1 -43 -45 -12 -4

4:30 -11 1 -66 -52 -18 -3

5:30 -15 0 -86 -60 -25 -5

6:30 -20 -1 -111 -69 -36 -9

7:30 -17 0 -114 -71 -39 -11

8:30 -23 0 -85 -62 -32 -12

9:30 -16 0 -29 -37 -19 -9

10:30 -12 0 34 -6 4 2

11:30 -11 1 72 27 26 7

12:30 -4 0 159 82 77 23

13:30 9 7 268 156 165 54

14:30 22 13 355 215 239 82

15:30 24 16 391 244 279 97

16:30 25 15 404 251 297 101

17:30 23 15 383 241 284 98

18:30 21 13 334 213 241 84

19:15 19 10 283 185 195 68

20:30 9 8 190 126 116 41

21:30 0 5 124 85 76 25

22:30 1 6 76 57 45 14

23:00 0 5 50 43 33 10

5/26/2010

0:50 -14 -1 -13 16 7 -1

1:30 -18 -1 -47 -27 -13 -7

2:30 -18 -1 -86 -36 -20 -8

2229H

531

Table E.13 cont.: Bridge monitoring—bottom-fiber strains—Girder 8

Span 11

S8

_1

1_

5M

F8_

11

_5

M

S8

_1

1_

6M

S8

_1

1_

7M

S8

_1

1_

8M

Ht. from girder base (in.) 0 0 0 0 0

Dist. from center of cont. dia. (in.) 105 104 273 441 609

Units x10-6 in/in

Date Time

5/25/2010

2:30 0 0 0 0 0

3:30 0 -1 -10 -19 9

4:30 -1 3 -19 -35 10

5:30 -6 -1 -20 -31 5

6:30 -11 -5 -21 -28 1

7:30 -16 -8 -20 -23 0

8:30 -14 -16 -29 -40 8

9:30 -14 -18 -24 -27 1

10:30 -5 -17 -25 -33 8

11:30 -1 -10 -20 -27 5

12:30 5 -12 -17 -28 7

13:30 15 0 -8 -19 9

14:30 25 14 1 -11 11

15:30 32 18 7 -9 11

16:30 37 24 7 -9 14

17:30 37 25 10 -4 13

18:30 33 27 5 -11 13

19:15 26 22 6 -3 9

20:30 23 17 -2 -18 12

21:30 18 11 -4 -18 12

22:30 6 8 -4 -8 4

23:00 4 5 -7 -15 5

5/26/2010

0:50 -1 2 -19 -29 7

1:30 -2 1 -19 -32 6

2:30 -9 0 -21 -28 1

532

E.5 91BFRP STRAINS

Table E.14: Bridge monitoring—FRP strains—Girder 7

Span 10 Span 11

F7_

10

_1

M

F7_

10

_C

K

F7_

10

_2

Z

F7_

11

_C

K

F7_

11

_4

M

F7_

11

_5

M

Ht. from girder base (in.) 0 0 3 0 0 0

Dist. from center of cont. dia. (in.) -74 -47 -14 47 74 104

Units x10-6 in/in

Date Time

5/25/2010

2:30 0 0 0 0 0 0

3:30 0 -50 -4 -37 0 1

4:30 0 -60 -5 -51 -2 3

5:30 2 -67 -6 -62 -4 3

6:30 -1 -78 -7 -79 -6 0

7:30 -1 -79 -7 -79 -4 0

8:30 -1 -59 -3 -58 -4 -5

9:30 0 -15 6 -3 1 -6

10:30 5 38 15 65 6 -2

11:30 9 77 20 116 11 1

12:30 16 167 33 228 21 4

13:30 27 277 55 368 34 14

14:30 35 358 72 475 44 25

15:30 38 385 77 504 46 23

16:30 38 387 76 502 46 25

17:30 34 359 68 466 43 25

18:30 30 312 57 401 38 27

19:15 23 261 46 340 32 23

20:30 20 185 32 233 23 17

21:30 15 125 24 160 16 13

22:30 12 88 19 112 15 11

23:00 9 61 14 84 12 9

5/26/2010

0:50 3 14 6 23 6 7

1:30 3 -6 4 -7 4 8

2:30 1 -39 0 -28 6 7

533

Table E.15: Bridge monitoring—FRP strains—Girder 8

Span 10

F8_

10

_1

Y

F8_

10

_1

M

F8_

10

_C

K

F8_

10

_2

Y

F8_

10

_2

Z

Ht. from girder base (in.) 3 0 0 3 3

Dist. from center of cont. dia. (in.) -74 -74 -41 -14 -14

Units x10-6 in/in

Date Time

5/25/2010

2:30 0 0 0 0 0

3:30 0 1 -43 -11 1

4:30 0 1 -66 9 -1

5:30 0 0 -86 23 -1

6:30 -1 -1 -111 43 -2

7:30 2 0 -114 42 -2

8:30 0 0 -85 52 0

9:30 1 0 -29 69 3

10:30 3 0 34 84 2

11:30 4 1 72 90 4

12:30 7 0 159 125 9

13:30 11 7 268 167 16

14:30 15 13 355 202 23

15:30 14 16 391 210 23

16:30 13 15 404 208 23

17:30 12 15 383 195 21

18:30 11 13 334 170 18

19:15 9 10 283 147 14

20:30 6 8 190 110 9

21:30 3 5 124 90 6

22:30 5 6 76 80 6

23:00 4 5 50 75 5

5/26/2010

0:50 3 -1 -13 58 4

1:30 4 -1 -47 57 3

2:30 4 -1 -86 51 3 2230H

534

Table E.15 cont.: Bridge monitoring—FRP strains—Girder 8

Span 11

F8_

11

_3

Y

F8_

11

_3

Z

F8_

11

_C

K

F8_

11

_4

Y

F8_

11

_4

M

F8_

11

_5

M

Ht. from girder base (in.) 3 3 0 3 0 0

Dist. from center of cont. dia. (in.) 14 14 52 74 74 104

Units x10-6 in/in

Date Time

5/25/2010

2:30 0 0 0 0 0 0

3:30 -11 -13 -45 -4 -4 -1

4:30 -18 -14 -52 -5 -3 3

5:30 -22 -16 -60 -7 -5 -1

6:30 -26 -21 -69 -10 -9 -5

7:30 -28 -21 -71 -11 -11 -8

8:30 -18 -11 -62 -10 -12 -16

9:30 -5 -8 -37 -7 -9 -18

10:30 10 5 -6 -2 2 -17

11:30 25 20 27 1 7 -10

12:30 57 53 82 9 23 -12

13:30 94 97 156 22 54 0

14:30 119 130 215 32 82 14

15:30 125 140 244 37 97 18

16:30 126 142 251 38 101 24

17:30 118 132 241 37 98 25

18:30 101 112 213 31 84 27

19:15 87 91 185 25 68 22

20:30 57 58 126 14 41 17

21:30 36 35 85 6 25 11

22:30 22 20 57 1 14 8

23:00 15 12 43 0 10 5

5/26/2010

0:50 -1 3 16 -4 -1 2

1:30 -9 -11 -27 -7 -7 1

2:30 -16 -12 -36 -9 -8 0

535

Appendix F

19BBRIDGE MONITORING—MEASUREMENT ADJUSTMENTS

F.1 92BINCONSISTENT MEASUREMENTS

Sensors were balanced at the beginning of bridge monitoring. During the duration of the

bridge monitoring test, some of the instruments provided inconsistent measurements at

different points in time that may have had an effect on the remaining measurements.

These inconsistent measurements could be a result of electrical noise/interference or

physical effects at the sensor location. The sensors that were the most inconsistent were

the deflectometers. The bottom-fiber strain gage near the crack location of Girder 8 in

Span 10 also measured inconsistencies. During the analysis of bridge monitoring

measurements, efforts were made to decrease the effects associated with inconsistent

sensor behavior.

F.2 93BDEFLECTOMETER BEHAVIOR

The deflectometers seemed to be sensitive to temporary direct sunlight on the aluminum

bar during the sunrise hours. An example of this type of sensitivity is evident during the

morning hours plotted in 2231HFigure F.1. Unexpected physical movement of a deflectometer

could also have an effect relative to the original baseline and cause a permanent data

shift. Electrical noise or interference could have also caused a momentary or permanent

movement relative to the original baseline. Instruments not returning to a similar

536

measurement at the end of the test, in relation to either the initial measurement of that

sensor or the concluding measurements of other comparable sensors, were the primary

reason for deciding to adjust certain results. An example of this type of offset can be

readily observed in the response of Sensor D7_10_B in the early afternoon in 2232HFigure F.1.

Measurements that seemed to be inconsistent with the expected result were inspected and

adjustments were proposed and implemented when deemed appropriate.

F.3 94BDEFLECTION ADJUSTMENTS

Deflection measurements considered to be affected by deflectometers exposed to direct

sunlight were disregarded. When plotting the deflection results, a straight line was used

to connect measurements on either side of a discarded time interval during the sunrise

period when this was a particular problem.

Results that seemed to be inconsistent compared to adjacent time intervals were

disregarded and replaced with an estimated value based on the following procedure.

The estimated adjusted value was created by projecting a change in value over time from

the prior measurement. This projected change in value over time was based on the

average of two slopes bounding the time intervals to be replaced. All time intervals

following the last adjusted result maintain their original relative change in value between

time intervals. Measurements following the last adjusted measurement are shifted by the

same magnitude.

537

F.4 95BGRAPHICAL PRESENTATIONS OF DEFLECTION ADJUSTMENTS

The graphical presentations within this section, Figures F 2233H.1–F2234H.28, have been provided to

illustrate the deflection adjustments that were made during the analysis of bridge

monitoring measurements.

F.4.1 3479BORIGINAL DEFLECTIONS—GIRDERS 7 AND 8

Figure F.1: Original deflection results—Girder 7

-1.00

-0.80

-0.60

-0.40

-0.20

0.00

0.20

0.40

0.60

0.80

1.00

02:30 5/25 06:30 5/25 10:30 5/25 14:30 5/25 18:30 5/25 22:30 5/25 02:30 5/26

Defl

ecti

on

(in

)

Time of Day (hr:min month/day)

D7_10_A

D7_10_B

D7_11_C

D7_11_D

D7_11_E

D7_11_F

538

Figure F.2: Original deflection results—Girder 8

F.4.2 3480BADJUSTED DEFLECTIONS OF GIRDER 7 IN SPAN 10

Figure F.3: Original deflection results—Girder 7—Span 10

-1.00

-0.80

-0.60

-0.40

-0.20

0.00

0.20

0.40

0.60

0.80

1.00

02:30 5/25 06:30 5/25 10:30 5/25 14:30 5/25 18:30 5/25 22:30 5/25 02:30 5/26

Defl

ecti

on

(in

)

Time of Day (hr:min month/day)

D8_10_A

D8_10_B

D8_11_C

D8_11_D

D8_11_E

D8_11_F

-0.5

-0.4

-0.3

-0.2

-0.1

0.0

0.1

0.2

0.3

0.4

0.5

2:30 5/25 6:30 5/25 10:30 5/25 14:30 5/25 18:30 5/25 22:30 5/25 2:30 5/26

Defl

ecti

on

(in

.)

Time of Day (hr:min month/day)

D7_10_A

D7_10_B

539

Figure F.4: Adjusted deflection results—D7_10_A

Figure F.5: Adjusted deflection results—D7_10_B

-0.5

-0.4

-0.3

-0.2

-0.1

0.0

0.1

0.2

0.3

0.4

0.5

2:30 5/25 6:30 5/25 10:30 5/25 14:30 5/25 18:30 5/25 22:30 5/25 2:30 5/26

Defl

ecti

on

(in

.)

Time of Day (hr:min month/day)

D7_10_A (Original)

D7_10_A (Adjusted)

-0.5

-0.4

-0.3

-0.2

-0.1

0.0

0.1

0.2

0.3

0.4

0.5

2:30 5/25 6:30 5/25 10:30 5/25 14:30 5/25 18:30 5/25 22:30 5/25 2:30 5/26

Defl

ecti

on

(in

.)

Time of Day (hr:min month/day)

D7_10_B (Original)

D7_10_B (Adjusted)

540

Figure F.6: Adjusted deflection results—Girder 7—Span 10

Figure F.7: Final deflection results—Girder 7—Span 10

-0.5

-0.4

-0.3

-0.2

-0.1

0.0

0.1

0.2

0.3

0.4

0.5

2:30 5/25 6:30 5/25 10:30 5/25 14:30 5/25 18:30 5/25 22:30 5/25 2:30 5/26

Defl

ecti

on

(in

.)

Time of Day (hr:min month/day)

D7_10_A (Original)

D7_10_A (Adjusted)

D7_10_B (Original)

D7_10_B (Adjusted)

-0.2

-0.1

0.0

0.1

0.2

0.3

0.4

0.5

2:30 5/25 6:30 5/25 10:30 5/25 14:30 5/25 18:30 5/25 22:30 5/25 2:30 5/26

Defl

ecti

on

(in

.)

Time of Day (hr:min month/day)

D7_10_A (Adjusted)

D7_10_B (Adjusted)

541

F.4.3 3481BADJUSTED DEFLECTIONS OF GIRDER 7 IN SPAN 11

Figure F.8: Original deflection results—Girder 7—Span 11

Figure F.9: Adjusted deflection results—D7_11_C

-0.5

-0.4

-0.3

-0.2

-0.1

0.0

0.1

0.2

0.3

0.4

0.5

2:30 5/25 6:30 5/25 10:30 5/25 14:30 5/25 18:30 5/25 22:30 5/25 2:30 5/26

Defl

ecti

on

(in

.)

Time of Day (hr:min month/day)

D7_11_C

D7_11_D

D7_11_E

D7_11_F

-0.5

-0.4

-0.3

-0.2

-0.1

0.0

0.1

0.2

0.3

0.4

0.5

2:30 5/25 6:30 5/25 10:30 5/25 14:30 5/25 18:30 5/25 22:30 5/25 2:30 5/26

Defl

ecti

on

(in

.)

Time of Day (hr:min month/day)

D7_11_C (Original)

D7_11_C (Adjusted)

542

Figure F.10: Adjusted deflection results—D7_11_D

Figure F.11: Adjusted deflection results—D7_11_E

-0.5

-0.4

-0.3

-0.2

-0.1

0.0

0.1

0.2

0.3

0.4

0.5

2:30 5/25 6:30 5/25 10:30 5/25 14:30 5/25 18:30 5/25 22:30 5/25 2:30 5/26

Defl

ecti

on

(in

.)

Time of Day (hr:min month/day)

D7_11_D (Original)

D7_11_D (Adjusted)

-0.5

-0.4

-0.3

-0.2

-0.1

0.0

0.1

0.2

0.3

0.4

0.5

2:30 5/25 6:30 5/25 10:30 5/25 14:30 5/25 18:30 5/25 22:30 5/25 2:30 5/26

Defl

ecti

on

(in

.)

Time of Day (hr:min month/day)

D7_11_E (Original)

D7_11_E (Adjusted)

543

Figure F.12: Adjusted deflection results—D7_11_F

Figure F.13: Adjusted deflection results—Girder 7—Span 11

-0.5

-0.4

-0.3

-0.2

-0.1

0.0

0.1

0.2

0.3

0.4

0.5

2:30 5/25 6:30 5/25 10:30 5/25 14:30 5/25 18:30 5/25 22:30 5/25 2:30 5/26

Defl

ecti

on

(in

.)

Time of Day (hr:min month/day)

D7_11_F (Original)

D7_11_F (Adjusted)

-0.5

-0.4

-0.3

-0.2

-0.1

0.0

0.1

0.2

0.3

0.4

0.5

2:30 5/25 6:30 5/25 10:30 5/25 14:30 5/25 18:30 5/25 22:30 5/25 2:30 5/26

Defl

ecti

on

(in

.)

Time of Day (hr:min month/day)

D7_11_C (Original) D7_11_C (Adjusted)

D7_11_D (Original) D7_11_D (Adjusted)

D7_11_E (Original) D7_11_E (Adjusted)

D7_11_F (Original) D7_11_F (Adjusted)

544

Figure F.14: Final deflection results—Girder 7—Span 11

F.4.4 3482BADJUSTED DEFLECTIONS OF GIRDER 8 IN SPAN 10

Figure F.15: Original deflection results—Girder 8—Span 10

-0.2

-0.1

0.0

0.1

0.2

0.3

0.4

0.5

2:30 5/25 6:30 5/25 10:30 5/25 14:30 5/25 18:30 5/25 22:30 5/25 2:30 5/26

Defl

ecti

on

(in

.)

Time of Day (hr:min month/day)

D7_11_C (Adjusted)

D7_11_D (Adjusted)

D7_11_E (Adjusted)

D7_11_F (Adjusted)

-1.0

-0.8

-0.6

-0.4

-0.2

0.0

0.2

0.4

0.6

0.8

1.0

2:30 5/25 6:30 5/25 10:30 5/25 14:30 5/25 18:30 5/25 22:30 5/25 2:30 5/26

Defl

ecti

on

(in

.)

Time of Day (hr:min month/day)

D8_10_A

D8_10_B

545

Figure F.16: Adjusted deflection results—D8_10_A

Figure F.17: Adjusted deflection results—D8_10_B

-1.0

-0.8

-0.6

-0.4

-0.2

0.0

0.2

0.4

0.6

0.8

1.0

2:30 5/25 6:30 5/25 10:30 5/25 14:30 5/25 18:30 5/25 22:30 5/25 2:30 5/26

Defl

ecti

on

(in

.)

Time of Day (hr:min month/day)

D8_10_A (Original)

D8_10_A (Adjusted)

-1.0

-0.8

-0.6

-0.4

-0.2

0.0

0.2

0.4

0.6

0.8

1.0

2:30 5/25 6:30 5/25 10:30 5/25 14:30 5/25 18:30 5/25 22:30 5/25 2:30 5/26

Defl

ecti

on

(in

.)

Time of Day (hr:min month/day)

D8_10_B (Original)

D8_10_B (Adjusted)

546

Figure F.18: Adjusted deflection results—Girder 8—Span 10

Figure F.19: Final deflection results—Girder 8—Span 10

-1.0

-0.8

-0.6

-0.4

-0.2

0.0

0.2

0.4

0.6

0.8

1.0

2:30 5/25 6:30 5/25 10:30 5/25 14:30 5/25 18:30 5/25 22:30 5/25 2:30 5/26

Defl

ecti

on

(in

.)

Time of Day (hr:min month/day)

D8_10_A (Original)

D8_10_A (Adjusted)

D8_10_B (Original)

D8_10_B (Adjusted)

-0.2

-0.1

0.0

0.1

0.2

0.3

0.4

0.5

0.6

2:30 5/25 6:30 5/25 10:30 5/25 14:30 5/25 18:30 5/25 22:30 5/25 2:30 5/26

Defl

ecti

on

(in

.)

Time of Day (hr:min month/day)

D8_10_A (Adjusted)

D8_10_B (Adjusted)

547

F.4.5 3483BADJUSTED DEFLECTIONS OF GIRDER 8 IN SPAN 11

Figure F.20: Original deflection results—Girder 8—Span 11

Figure F.21: Adjusted deflection results—D8_11_C

-1.0

-0.8

-0.6

-0.4

-0.2

0.0

0.2

0.4

0.6

0.8

1.0

2:30 5/25 6:30 5/25 10:30 5/25 14:30 5/25 18:30 5/25 22:30 5/25 2:30 5/26

Defl

ecti

on

(in

.)

Time of Day (hr:min month/day)

D8_11_C

D8_11_D

D8_11_E

D8_11_F

-1.0

-0.8

-0.6

-0.4

-0.2

0.0

0.2

0.4

0.6

0.8

1.0

2:30 5/25 6:30 5/25 10:30 5/25 14:30 5/25 18:30 5/25 22:30 5/25 2:30 5/26

Defl

ecti

on

(in

.)

Time of Day (hr:min month/day)

D8_11_C (Original)

D8_11_C (Adjusted)

548

Figure F.22: Adjusted deflection results—D8_11_D

Figure F.23: Adjusted deflection results—D8_11_E

-1.0

-0.8

-0.6

-0.4

-0.2

0.0

0.2

0.4

0.6

0.8

1.0

2:30 5/25 6:30 5/25 10:30 5/25 14:30 5/25 18:30 5/25 22:30 5/25 2:30 5/26

Defl

ecti

on

(in

.)

Time of Day (hr:min month/day)

D8_11_D (Original)

D8_11_D (Adjusted)

-1.0

-0.8

-0.6

-0.4

-0.2

0.0

0.2

0.4

0.6

0.8

1.0

2:30 5/25 6:30 5/25 10:30 5/25 14:30 5/25 18:30 5/25 22:30 5/25 2:30 5/26

Defl

ecti

on

(in

.)

Time of Day (hr:min month/day)

D8_11_E (Original)

D8_11_E (Adjusted)

549

Figure F.24: Adjusted deflection results—D8_11_F

Figure F.25: Adjusted deflection results—Girder 8—Span 11

-1.0

-0.8

-0.6

-0.4

-0.2

0.0

0.2

0.4

0.6

0.8

1.0

2:30 5/25 6:30 5/25 10:30 5/25 14:30 5/25 18:30 5/25 22:30 5/25 2:30 5/26

Defl

ecti

on

(in

.)

Time of Day (hr:min month/day)

D8_11_F (Original)

D8_11_F (Adjusted)

-1.0

-0.8

-0.6

-0.4

-0.2

0.0

0.2

0.4

0.6

0.8

1.0

2:30 5/25 6:30 5/25 10:30 5/25 14:30 5/25 18:30 5/25 22:30 5/25 2:30 5/26

Defl

ecti

on

(in

.)

Time of Day (hr:min month/day)

D7_11_C (Original) D7_11_C (Adjusted)

D8_11_D (Original) D8_11_D (Adjusted)

D8_11_E (Original) D8_11_E (Adjusted)

D8_11_F (Original) D8_11_F (Adjusted)

550

Figure F.26: Final deflection results—Girder 8—Span 11

F.4.6 3484BFINAL ADJUSTED DEFLECTIONS—GIRDERS 7 AND 8

Figure F.27: Final deflection results—Girder 7

-0.2

-0.1

0.0

0.1

0.2

0.3

0.4

0.5

2:30 5/25 6:30 5/25 10:30 5/25 14:30 5/25 18:30 5/25 22:30 5/25 2:30 5/26

Defl

ecti

on

(in

.)

Time of Day (hr:min month/day)

D8_11_C (Adjusted)

D8_11_D (Adjusted)

D8_11_E (Adjusted)

D8_11_F (Adjusted)

-0.2

-0.1

0.0

0.1

0.2

0.3

0.4

0.5

2:30 5/25 6:30 5/25 10:30 5/25 14:30 5/25 18:30 5/25 22:30 5/25 2:30 5/26

Defl

ecti

on

(in

.)

Time of Day (hr:min month/day)

D7_10_A

D7_10_B

D7_11_C

D7_11_D

D7_11_E

D7_11_F

551

Figure F.28: Final deflection results—Girder 8

F.5 96BSTRAIN MEASUREMENT ADJUSTMENTS

Some of the strain gages also contained inconsistent results. Strain gages that displayed

data shifts similar to deflectometer data shifts were also investigated. For the bottom-

fiber strain gage sensors, only the measurements on the FRP at the crack location of

Girder 8 in Span 10 were adjusted. Some measurements during the early morning hours

(3:30 a.m. through 5:30 a.m.) were disregarded and estimated using the same method for

estimating deflection measurements that were inconsistent compared to adjacent

measurements. The original FRP strains measured near the crack locations are presented

in 2235HFigure F.29. The adjusted FRP strains measured near the crack location of Girder 8 in

Span 10 are presented with the other crack location FRP strains in 2236HFigure F.30.

-0.2

-0.1

0.0

0.1

0.2

0.3

0.4

0.5

2:30 5/25 6:30 5/25 10:30 5/25 14:30 5/25 18:30 5/25 22:30 5/25 2:30 5/26

Defl

ecti

on

(in

.)

Time of Day (hr:min month/day)

D8_10_A

D8_10_B

D8_11_C

D8_11_D

D8_11_E

D8_11_F

552

Figure F.29: Crack location FRP strain measurements—original F8_10_CK

Figure F.30: Crack location FRP strain measurements—adjusted F8_10_CK

-400

-300

-200

-100

0

100

200

300

400

500

600

2:30 5/25 6:30 5/25 10:30 5/25 14:30 5/25 18:30 5/25 22:30 5/25 2:30 5/26

Str

ain

(x

10

-6in

./in

.)

Time of Day (hr:min month/day)

F7_10_CK

F7_11_CK

F8_10_CK

F8_11_CK

-400

-300

-200

-100

0

100

200

300

400

500

600

2:30 5/25 6:30 5/25 10:30 5/25 14:30 5/25 18:30 5/25 22:30 5/25 2:30 5/26

Str

ain

(x10

-6in

./in

.)

Time of Day (hr:min month/day)

F7_10_CK

F7_11_CK

F8_10_CK

F8_11_CK

553

Appendix G

20BSUPERPOSITION—GRAPHICAL RESULTS

554

G.1 97BCRACK-OPENING DISPLACEMENTS

Figure G.1: Crack-opening displacements—A1 (east)

-0.03

-0.02

-0.01

0.00

0.01

0.02

-900 -700 -500 -300 -100 100 300 500 700 900

Ch

an

ge-

Op

enin

g D

isp

lace

men

t (m

m)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

7 8

555

Figure G.2: Crack-opening displacements—A9 (east)

Figure G.3: Crack-opening displacements—A1 (east) + A9 (east)

-0.03

-0.02

-0.01

0.00

0.01

0.02

-900 -700 -500 -300 -100 100 300 500 700 900

Ch

an

ge-

Op

enin

g D

isp

lace

men

t (m

m)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

7 8

-0.03

-0.02

-0.01

0.00

0.01

0.02

-900 -700 -500 -300 -100 100 300 500 700 900

Ch

an

ge-

Op

enin

g D

isp

lace

men

t (m

m)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

7 8

556

Figure G.4: Crack-opening displacements—superposition—actual and predicted

Figure G.5: COD—superposition—actual and predicted—Girder 7

-0.03

-0.02

-0.01

0.00

0.01

0.02

-900 -700 -500 -300 -100 100 300 500 700 900

Cra

ck-O

pen

ing

Dis

pla

cem

ent

(mm

)

Distance from Center of Continuity Diaphragm (in.)

G7 - Predicted

G8 - Predicted

G7 - Measured

G8 - Measured

7 8

-0.03

-0.02

-0.01

0.00

0.01

0.02

-900 -700 -500 -300 -100 100 300 500 700 900

Cra

ck-O

pen

ing

Dis

pla

cem

ent

(mm

)

Distance from Center of Continuity Diaphragm (in.)

G7 - Predicted

G7 - Measured

7 8

557

Figure G.6: COD—superposition—actual and predicted—Girder 8

-0.03

-0.02

-0.01

0.00

0.01

0.02

-900 -700 -500 -300 -100 100 300 500 700 900

Cra

ck-O

pen

ing

Dis

pla

cem

ent

(mm

)

Distance from Center of Continuity Diaphragm (in.)

G8 - Predicted

G8 - Measured

7 8

558

G.2 98BDEFLECTIONS

Figure G.7: Deflections—A1 (east)

-0.30

-0.25

-0.20

-0.15

-0.10

-0.05

0.00

0.05

0.10

-900 -700 -500 -300 -100 100 300 500 700 900

Bo

tto

m-F

iber

Def

lect

ion

(in

.)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

7 8

559

Figure G.8: Deflections—A9 (east)

Figure G.9: Deflections—A1 (east) + A9 (east)

-0.30

-0.25

-0.20

-0.15

-0.10

-0.05

0.00

0.05

0.10

-900 -700 -500 -300 -100 100 300 500 700 900

Bo

tto

m-F

iber

Def

lect

ion

(in

.)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

7 8

-0.30

-0.25

-0.20

-0.15

-0.10

-0.05

0.00

0.05

0.10

-900 -700 -500 -300 -100 100 300 500 700 900

Bo

tto

m-F

iber

Def

lect

ion

du

e to

Tru

ck L

oa

din

g (

in.)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

7 8

560

Figure G.10: Deflections—superposition—actual and predicted

Figure G.11: Deflections—superposition—actual and predicted—Girder 7

-0.30

-0.25

-0.20

-0.15

-0.10

-0.05

0.00

0.05

0.10

-900 -700 -500 -300 -100 100 300 500 700 900

Bo

tto

m-F

iber

Def

lect

ion

(in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Predicted

G8 - Predicted

G7 - Measured

G8 - Measured

7 8

-0.30

-0.25

-0.20

-0.15

-0.10

-0.05

0.00

0.05

0.10

-900 -700 -500 -300 -100 100 300 500 700 900

Bo

tto

m-F

iber

Def

lect

ion

(in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Predicted

G7 - Actual

7 8

561

Figure G.12: Deflections—superposition—actual and predicted—Girder 8

-0.30

-0.25

-0.20

-0.15

-0.10

-0.05

0.00

0.05

0.10

-900 -700 -500 -300 -100 100 300 500 700 900

Bo

tto

m-F

iber

Def

lect

ion

(in

.)

Distance from Center of Continuity Diaphragm (in.)

G8 - Predicted

G8 - Actual

7 8

562

G.3 99BBOTTOM-FIBER STRAINS

Figure G.13: Bottom-fiber strains—A1 (east)

-210

-180

-150

-120

-90

-60

-30

0

30

60

90

-900 -700 -500 -300 -100 100 300 500 700 900

Bo

tto

m-F

iber

Str

ain

(x

10

-6in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G8 - Concrete

G7 - FRP

G8 - FRP

7 8

563

Figure G.14: Bottom-fiber strains—A9 (east)

Figure G.15: Bottom-fiber strains—A1 (east) + A9 (east)

-210

-180

-150

-120

-90

-60

-30

0

30

60

90

-900 -700 -500 -300 -100 100 300 500 700 900

Bo

tto

m-F

iber

Str

ain

(x

10

-6in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G8 - Concrete

G7 - FRP

G8 - FRP

7 8

-210

-180

-150

-120

-90

-60

-30

0

30

60

90

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er S

train

(x10

-6in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G8 - Concrete

G7 - FRP

G8 - FRP

7 8

564

Figure G.16: Bottom-fiber strains—superposition—actual and predicted

Figure G.17: Bottom-fiber strains—superposition—actual and predicted—Girder 7

-210

-180

-150

-120

-90

-60

-30

0

30

60

90

-900 -700 -500 -300 -100 100 300 500 700 900

Bo

tto

m-F

iber

Str

ain

(x1

0-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Predicted

G8 - Predicted

G7 - Measured

G8 - Measured

7 8

-210

-180

-150

-120

-90

-60

-30

0

30

60

90

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er S

train

(x1

0-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Predicted

G7 - Measured

7 8

565

Figure G.18: Bottom-fiber strains—superposition—actual and predicted—Girder 8

-210

-180

-150

-120

-90

-60

-30

0

30

60

90

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er S

train

(x1

0-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G8 - Predicted

G8 - Measured

7 8

566

Appendix H

21BSUPERPOSITION—MEASUREMENTS

567

Table H.1: Superposition—crack-opening displacements

Girder 3485BGage

3486BHeight

from

bottom of

girder

(in.)

3487BDistance from

center of

continuity

diaphragm

(in.)

– Span 10

+ Span 11

3488BCrack-Opening Displacement

(mm)

– closing

+ opening

3489BLoad Position 3490BSuperposition 3491BDifference

3492B(Pred.–Meas.)

3493BA1 3494BA9 3495BPredicted

3496B(A1+A9)

3497BMeasured

3498B(A1 and A9) 3499Bmm

3500B%

3501B7

3502BCO7_10 3503B13.5 3504B-50 -0.003 -0.008 3505B-0.011 3506B-0.014 3507B0.003 3508B21

3509BCO7_11 3510B13.5 3511B48 3512B-0.013 3513B-0.005 3514B-0.018 3515B-0.024 3516B0.006 3517B25

3518B8

3519BCO8_10 3520B13.5 3521B-40 3522B-0.008 3523B-0.006 3524B-0.014 3525B-0.015 3526B0.001 3527B7

3528BCO8_11 3529B13.5 3530B56 3531B-0.007 3532B-0.003 3533B-0.010 3534B-0.012 3535B0.002 3536B17

3537B Note: Percent difference is reported as a percentage of the measured superposition

568

Table H.2: Superposition—deflections

Girder 3538BGage

3539BHeight

from

bottom

3540Bof

3541Bgirder

(in.)

3542BDistance from

center of

continuity

diaphragm

(in.)

– Span 10

+ Span 11

3543BDeflection

(in.)

– downward

+ upward

3544BLoad Position 3545BSuperposition 3546BDifference

3547B(Pred.–Meas.)

3548BA1 3549BA9 3550BPredicted

3551B(A1+A9)

3552BMeasured

3553B(A1 and A9) 3554Bin.

3555B%

3556B7

3557BD7_10_A

n/a

3558B-608 -0.18 0.02 3559B-0.16 3560B-0.16 3561B0.00 3562B0

3563BD7_10_B 3564B-308 3565B-0.13 3566B0.01 3567B-0.12 3568B-0.11 3569B-0.01 3570B-9

3571BD7_11_C 3572B158 3573B0.01 3574B-0.06 3575B-0.05 3576B-0.05 3577B0.00 3578B0

3579BD7_11_D 3580B308 3581B0.01 3582B-0.12 3583B-0.11 3584B-0.10 3585B-0.01 3586B-10

3587BD7_11_E 3588B458 3589B0.01 3590B-0.16 3591B-0.15 3592B-0.14 3593B-0.01 3594B-7

3595BD7_11_F 3596B608 3597B0.01 3598B-0.18 3599B-0.17 3600B-0.16 3601B-0.01 3602B-6

3603B8

3604BD8_10_A

n/a

3605B-608 3606B-0.18 3607B0.02 3608B-0.16 3609B-0.15 3610B-0.01 3611B-7

3612BD8_10_B 3613B-308 3614B-0.12 3615B0.02 3616B-0.10 3617B-0.09 3618B-0.01 3619B-10

3620BD8_11_C 3621B158 3622B0.01 3623B-0.07 3624B-0.06 3625B-0.05 3626B-0.01 3627B-20

3628BD8_11_D 3629B308 3630B0.01 3631B-0.12 3632B-0.11 3633B-0.10 3634B-0.01 3635B-10

3636BD8_11_E 3637B458 3638B0.01 3639B-0.17 3640B-0.16 3641B-0.14 3642B-0.02 3643B-14

3644BD8_11_F 3645B608 3646B0.01 3647B-0.17 3648B-0.16 3649B-0.15 3650B-0.01 3651B-7

Note: Percent difference is reported as a percentage of the measured superposition

569

Table H.3: Superposition—bottom-fiber strains—Girder 7

Span 3652BGage

3653BHeight

from

bottom

3654Bof

3655Bgirder

(in.)

3656BDistance from

center of

continuity

diaphragm

(in.)

– Span 10

+ Span 11

3657BStrain

(x10-6

in/in)

– compressive

+ tensile

3658BLoad Position 3659BSuperposition 3660BDifference

3661B(Pred.–Meas.)

3662BA1 3663BA9 3664BPredicted

3665B(A1+A9)

3666BMeasured

3667B(A1 and A9)

3668Bx10-6

3669Bin./in. 3670B%

3671B10

3672BF7_10_1M

0

3673B-74 -2 -8 3674B-10 3675B-17 3676B7 3677B41

3678BF7_10_CK 3679B-47 3680B-36 3681B-58 3682B-94 3683B-134 3684B40 3685B30

3686B11

3687BF7_11_CK

0

3688B47 3689B-67 3690B-40 3691B-107 3692B-149 3693B42 3694B28

3695BF7_11_4M 3696B74 3697B-8 3698B-5 3699B-13 3700B-19 3701B6 3702B32

3703BF7_11_5M 3704B104 3705B-7 3706B-1 3707B-8 3708B-14 3709B6 3710B40

3711BS7_11_5M 3712B105 3713B-9 3714B-3 3715B-12 3716B-17 3717B5 3718B29

3719BS7_11_6M 3720B273 3721B-8 3722B19 3723B11 3724B7 3725B4 3726B60

3727BS7_11_7M 3728B441 3729B-6 3730B41 3731B35 3732B34 3733B1 3734B3

3735BS7_11_8M 3736B609 3737B-5 3738B65 3739B60 3740B60 3741B0 3742B0

Note: Percent difference is reported as a percentage of the measured superposition

570

Table H.4: Superposition—bottom-fiber strains—Girder 8

Span 3743BGage

3744BHeight

from

bottom

3745Bof

3746Bgirder

(in.)

3747BDistance from

center of

continuity

diaphragm

(in.)

– Span 10

+ Span 11

3748BStrain

(x10-6

in/in)

– compressive

+ tensile

3749BLoad Position 3750BSuperposition 3751BDifference

3752B(Pred.–Meas.)

3753BA1 3754BA9 3755BPredicted

3756B(A1+A9)

3757BMeasured

3758B(A1 and A9)

3759Bx10-6

3760Bin./in. 3761B%

3762B10

3763BS8_10_1M

0

3764B-75 -6 -12 3765B-18 3766B-24 3767B6 3768B25

3769BF8_10_1M 3770B-74 3771B-3 3772B-8 3773B-11 3774B-15 3775B4 3776B27

3777BF8_10_CK 3778B-41 3779B-73 3780B-93 3781B-166 3782B-204 3783B38 3784B19

3785B11

3786BF8_11_CK

0

3787B52 3788B-44 3789B-29 3790B-73 3791B-85 3792B12 3793B14

3794BF8_11_4M 3795B74 3796B-11 3797B-5 3798B-16 3799B-24 3800B8 3801B33

3802BS8_11_4M 3803B75 3804B-25 3805B-5 3806B-30 3807B-41 3808B11 3809B27

3810BF8_11_5M 3811B104 3812B-10 3813B-3 3814B-13 3815B-19 3816B6 3817B32

3818BS8_11_5M 3819B105 3820B-11 3821B-4 3822B-15 3823B-20 3824B5 3825B25

3826BS8_11_6M 3827B273 3828B-8 3829B18 3830B10 3831B7 3832B3 3833B40

3834BS8_11_7M 3835B441 3836B-6 3837B43 3838B37 3839B36 3840B1 3841B3

3842BS8_11_8M 3843B609 3844B-4 3845B56 3846B52 3847B50 3848B2 3849B4

Note: Percent difference is reported as a percentage of the measured superposition

571

Appendix I

22BAE STATIC POSITIONS—GRAPHICAL RESULTS

572

I.1 100BCRACK-OPENING DISPLACEMENTS

Figure I.1: Crack-opening displacements—LC 6.5—AE Span 10 (east)

-0.05

-0.04

-0.03

-0.02

-0.01

0.00

0.01

0.02

0.03

0.04

0.05

-900 -700 -500 -300 -100 100 300 500 700 900

Cra

ck-O

pen

ing

Dis

pla

cem

ent

(mm

)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

7 8

573

Figure I.2: Crack-opening displacements—LC 6.5—AE Span 10 (both)

Figure I.3: Crack-opening displacements—LC 6.5—AE Span 11 (east)

-0.05

-0.04

-0.03

-0.02

-0.01

0.00

0.01

0.02

0.03

0.04

0.05

-900 -700 -500 -300 -100 100 300 500 700 900

Cra

ck-O

pen

ing D

isp

lace

men

t (m

m)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

7 8

-0.05

-0.04

-0.03

-0.02

-0.01

0.00

0.01

0.02

0.03

0.04

0.05

-900 -700 -500 -300 -100 100 300 500 700 900

Cra

ck-O

pen

ing

Dis

pla

cem

ent

(mm

)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

7 8

574

Figure I.4: Crack-opening displacements—LC 6.5—AE Span 11 (both)

Figure I.5: Crack-opening displacements—LC 6—AE Span 10 (east)

-0.05

-0.04

-0.03

-0.02

-0.01

0.00

0.01

0.02

0.03

0.04

0.05

-900 -700 -500 -300 -100 100 300 500 700 900

Cra

ck-O

pen

ing

Dis

pla

cem

ent

(mm

)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

7 8

-0.05

-0.04

-0.03

-0.02

-0.01

0.00

0.01

0.02

0.03

0.04

0.05

-900 -700 -500 -300 -100 100 300 500 700 900

Cra

ck-O

pen

ing

Dis

pla

cem

ent

(mm

)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

7 8

575

Figure I.6: Crack-opening displacements—LC 6—AE Span 10 (both)

Figure I.7: Crack-opening displacements—LC 6—AE Span 11 (east)

-0.05

-0.04

-0.03

-0.02

-0.01

0.00

0.01

0.02

0.03

0.04

0.05

-900 -700 -500 -300 -100 100 300 500 700 900

Cra

ck-O

pen

ing

Dis

pla

cem

ent

(mm

)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

7 8

-0.05

-0.04

-0.03

-0.02

-0.01

0.00

0.01

0.02

0.03

0.04

0.05

-900 -700 -500 -300 -100 100 300 500 700 900

Cra

ck-O

pen

ing

Dis

pla

cem

ent

(mm

)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

7 8

576

Figure I.8: Crack-opening displacements—LC 6—AE Span 11 (both)

-0.05

-0.04

-0.03

-0.02

-0.01

0.00

0.01

0.02

0.03

0.04

0.05

-900 -700 -500 -300 -100 100 300 500 700 900

Cra

ck-O

pen

ing

Dis

pla

cem

ent

(mm

)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

7 8

577

I.2 101BDEFLECTIONS

Figure I.9: Deflections—LC 6.5—AE Span 10 (east)

-0.4

-0.3

-0.2

-0.1

0.0

0.1

-900 -700 -500 -300 -100 100 300 500 700 900

Bo

tto

m-F

iber

Def

lect

ion

(in

.)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

7 8

578

Figure I.10: Deflections—LC 6.5—AE Span 10 (both)

Figure I.11: Deflections—LC 6.5—AE Span 11 (east)

-0.4

-0.3

-0.2

-0.1

0.0

0.1

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er D

efle

ctio

n (

in.)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

7 8

-0.4

-0.3

-0.2

-0.1

0.0

0.1

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er D

efle

ctio

n (

in.)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

7 8

579

Figure I.12: Deflections—LC 6.5—AE Span 11 (both)

Figure I.13: Deflections—LC 6—AE Span 10 (east)

-0.4

-0.3

-0.2

-0.1

0.0

0.1

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er D

efle

ctio

n (

in.)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

7 8

-0.4

-0.3

-0.2

-0.1

0.0

0.1

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er D

efle

ctio

n (

in.)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

7 8

580

Figure I.14: Deflections—LC 6—AE Span 10 (both)

Figure I.15: Deflections—LC 6—AE Span 11 (east)

-0.4

-0.3

-0.2

-0.1

0.0

0.1

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er D

efle

ctio

n (

in.)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

7 8

-0.4

-0.3

-0.2

-0.1

0.0

0.1

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er D

efle

ctio

n (

in.)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

7 8

581

Figure I.16: Deflections—LC 6—AE Span 11 (both)

-0.4

-0.3

-0.2

-0.1

0.0

0.1

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er D

efle

ctio

n (

in.)

Distance from Center of Continuity Diaphragm (in.)

Girder 7

Girder 8

7 8

582

I.3 102BBOTTOM-FIBER STRAINS

Figure I.17: Bottom-fiber strains—LC 6.5—AE Span 10 (east)

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bo

tto

m-F

iber

Str

ain

(x

10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G8 - Concrete

G7 - FRP

G8 - FRP

7 8

583

Figure I.18: Bottom-fiber strains—LC 6.5—AE Span 10 (both)

Figure I.19: Bottom-fiber strains—LC 6.5—AE Span 11 (east)

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bo

tto

m-F

iber

Str

ain

(x

10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G8 - Concrete

G7 - FRP

G8 - FRP

7 8

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bo

tto

m-F

iber

Str

ain

(x

10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G8 - Concrete

G7 - FRP

G8 - FRP

7 8

584

Figure I.20: Bottom-fiber strains—LC 6.5—AE Span 11 (both)

Figure I.21: Bottom-fiber strains—LC 6—AE Span 10 (east)

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bo

tto

m-F

iber

Str

ain

(x

10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G8 - Concrete

G7 - FRP

G8 - FRP

7 8

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bo

tto

m-F

iber

Str

ain

(x

10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G8 - Concrete

G7 - FRP

G8 - FRP

7 8

585

Figure I.22: Bottom-fiber strains—LC 6—AE Span 10 (both)

Figure I.23: Bottom-fiber strains—LC 6—AE Span 11 (east)

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bo

tto

m-F

iber

Str

ain

(x

10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G8 - Concrete

G7 - FRP

G8 - FRP

7 8

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bo

tto

m-F

iber

Str

ain

(x

10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G8 - Concrete

G7 - FRP

G8 - FRP

7 8

586

Figure I.24: Bottom-fiber strains—LC 6—AE Span 11 (both)

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bo

tto

m-F

iber

Str

ain

(x

10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G8 - Concrete

G7 - FRP

G8 - FRP

7 8

587

I.3.1 3850BBOTTOM-FIBER STRAINS—GIRDER 7

Figure I.25: Bottom-fiber strains—Girder 7—LC 6.5—AE Span 10 (east)

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er S

train

(x10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G7 - FRP

7 8

588

Figure I.26: Bottom-fiber strains—Girder 7—LC 6.5—AE Span 10 (both)

Figure I.27: Bottom-fiber strains—Girder 7—LC 6.5—AE Span 11 (east)

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er S

train

(x1

0-6

in./

in.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G7 - FRP

7 8

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er S

train

(x1

0-6

in./

in.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G7 - FRP

7 8

589

Figure I.28: Bottom-fiber strains—Girder 7—LC 6.5—AE Span 11 (both)

Figure I.29: Bottom-fiber strains—Girder 7—LC 6—AE Span 10 (east)

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er S

train

(x10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G7 - FRP

7 8

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er S

train

(x1

0-6

in./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G7 - FRP

7 8

590

Figure I.30: Bottom-fiber strains—Girder 7—LC 6—AE Span 10 (both)

Figure I.31: Bottom-fiber strains—Girder 7—LC 6—AE Span 11 (east)

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er S

train

(x1

0-6

in./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G7 - FRP

7 8

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er S

train

(x10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G7 - FRP

7 8

591

Figure I.32: Bottom-fiber strains—Girder 7—LC 6—AE Span 11 (both)

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bo

tto

m-F

iber

Str

ain

(x

10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete

G7 - FRP

7 8

592

I.3.2 3851BBOTTOM-FIBER STRAINS—GIRDER 8

Figure I.33: Bottom-fiber strains—Girder 8—LC 6.5—AE Span 10 (east)

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bo

tto

m-F

iber

Str

ain

(x

10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G8 - Concrete

G8 - FRP

7 8

593

Figure I.34: Bottom-fiber strains—Girder 8—LC 6.5—AE Span 10 (both)

Figure I.35: Bottom-fiber strains—Girder 8—LC 6.5—AE Span 11 (east)

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bo

tto

m-F

iber

Str

ain

(x

10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G8 - Concrete

G8 - FRP

7 8

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bo

tto

m-F

iber

Str

ain

(x

10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G8 - Concrete

G8 - FRP

7 8

594

Figure I.36: Bottom-fiber strains—Girder 8—LC 6.5—AE Span 11 (both)

Figure I.37: Bottom-fiber strains—Girder 8—LC 6—AE Span 10 (east)

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bo

tto

m-F

iber

Str

ain

(x

10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G8 - Concrete

G8 - FRP

7 8

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bo

tto

m-F

iber

Str

ain

(x

10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G8 - Concrete

G8 - FRP

7 8

595

Figure I.38: Bottom-fiber strains—Girder 8—LC 6—AE Span 10 (both)

Figure I.39: Bottom-fiber strains—Girder 8—LC 6—AE Span 11 (east)

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bo

tto

m-F

iber

Str

ain

(x

10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G8 - Concrete

G8 - FRP

7 8

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bo

tto

m-F

iber

Str

ain

(x

10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G8 - Concrete

G8 - FRP

7 8

596

Figure I.40: Bottom-fiber strains—Girder 8—LC 6—AE Span 11 (both)

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bo

tto

m-F

iber

Str

ain

(x

10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G8 - Concrete

G8 - FRP

7 8

597

Appendix J

23BAE STATIC POSITIONS—MEASUREMENTS

598

Figure J.1: Transverse load position—AE testing—Lane C—east truck

Figure J.2: Transverse load position—AE testing—Lane C—both trucks

40.5‖ 96‖

Cast-in-place

concrete barrier

64’ - 0‖

70’ - 9‖

6.5‖

Girder 7 Girder 8

73.5‖ 75‖ 49‖

ST-6538

west truck

ST-6400

east truck

AASHTO BT-54 Girders

40.5‖ 96‖

Cast-in-place

concrete barrier

64’ - 0‖

70’ - 9‖

6.5‖

Girder 7 Girder 8

75‖

ST-6400

east truck

AASHTO BT-54 Girders

599

Figure J.3: Longitudinal stop positions—AE testing—Spans 10 and 11

70‖ 70‖

Bent 10

Simple

Support

Span 11

Bent 11

Continuity

Diaphragm

Span 10

Bent 12

Simple

Support

6 4

Span 10 Static Position (C6)

ST-6400 (east)

ST-6538 (west)

Span 11 Static Position (C4)

ST-6400 (east)

ST-6538 (west)

Legend:

Stop Position

Centerline of Continuity Diaphragm

False Support False Support

600

Table J.1: AE static positions—crack-opening displacements

Girder 3852BGage

3853BHeight

from

bottom of

girder

(in.)

3854BDistance from

center of

continuity

diaphragm

(in.)

– Span 10

+ Span 11

3855BCrack-Opening Displacement

(mm)

– closing

+ opening

3856BAE—Night 1 (LC-6.5) 3857BAE—Night 2 (LC-6)

3858BSpan 10 Loading 3859BSpan 11 Loading 3860BSpan 10 Loading 3861BSpan 11 Loading

3862BEast

Truck 3863BBoth

Trucks

3864BEast

Truck

3865BBoth

Trucks

3866BEast

Truck

3867BBoth

Trucks

3868BEast

Truck

3869BBoth

Trucks

3870B7

3871BCO7_10 3872B13.5 3873B-50 0.002 0.024 -0.005 -0.013 0.002 0.023 -0.005 -0.014

3874BCO7_11 3875B13.5 3876B48 -0.008 -0.021 0.004 0.047 -0.008 -0.021 0.004 0.044

3877B8

3878BCO8_10 3879B13.5 3880B-40 -0.005 -0.010 -0.006 -0.010 -0.006 -0.010 -0.006 -0.010

3881BCO8_11 3882B13.5 3883B56 -0.013 -0.019 0.023 0.038 -0.013 -0.019 0.026 0.040

601

Table J.2: AE static positions—deflections

Girder 3884BGage

3885BHeight

from

bottom of

girder

(in.)

3886BDistance from

center of

continuity

diaphragm

(in.)

– Span 10

+ Span 11

3887BDeflection

(in.)

– downward

+ upward

3888BAE—Night 1 (LC-6.5) 3889BAE—Night 2 (LC-6)

3890BSpan 10 3891BSpan 11 3892BSpan 10 3893BSpan 11

3894BEast

Truck 3895BBoth

Trucks

3896BEast

Truck

3897BBoth

Trucks

3898BEast

Truck

3899BBoth

Trucks

3900BEast

Truck

3901BBoth

Trucks

3902B7

3903BD7_10_A

3904Bn/a

3905B-608 -0.06 -0.12 0.01 0.01 -0.05 -0.11 0.00 0.01

3906BD7_10_B 3907B-308 -0.05 -0.11 0.01 0.01 -0.04 -0.10 0.00 0.00

3908BD7_11_C 3909B158 -0.01 -0.01 -0.03 -0.08 0.01 0.00 -0.03 -0.07

3910BD7_11_D 3911B308 -0.01 -0.01 -0.04 -0.12 0.00 0.01 -0.05 -0.12

3912BD7_11_E 3913B458 -0.01 -0.01 -0.05 -0.12 0.00 0.01 -0.06 -0.12

3914BD7_11_F 3915B608 -0.01 -0.01 -0.05 -0.12 0.00 0.00 -0.06 -0.12

3916B8

3917BD8_10_A

3918Bn/a

3919B-608 -0.09 -0.14 0.01 0.01 -0.08 -0.13 0.00 0.01

3920BD8_10_B 3921B-308 -0.08 -0.13 0.01 0.01 -0.07 -0.12 0.00 0.01

3922BD8_11_C 3923B158 0.00 0.00 -0.05 -0.09 0.01 0.01 -0.06 -0.09

3924BD8_11_D 3925B308 -0.01 0.00 -0.08 -0.13 0.01 0.01 -0.08 -0.13

3926BD8_11_E 3927B458 -0.01 0.00 -0.08 -0.14 0.00 0.01 -0.10 -0.15

3928BD8_11_F 3929B608 -0.01 0.00 -0.07 -0.13 0.01 0.01 -0.08 -0.12

602

Table J.3: AE static positions—cross-section strains—Girder 7—Span 10

Cross

Section 3930BGage

3931BHeight

from

bottom of

girder

(in.)

3932BDistance from

center of

continuity

diaphragm

(in.)

– Span 10

+ Span 11

3933BStrain

(x10-6

in/in)

– compressive

+ tensile

3934BAE—Night 1 (LC-6.5) 3935BAE—Night 2 (LC-6)

3936BSpan 10 3937BSpan 11 3938BSpan 10 3939BSpan 11

3940BEast

Truck 3941BBoth

Trucks

3942BEast

Truck

3943BBoth

Trucks

3944BEast

Truck

3945BBoth

Trucks

3946BEast

Truck

3947BBoth

Trucks

3948BGir

der

7

3949BCro

ss S

ecti

on

3950B1

3951BS7_10_1V 3952B28.5 3953B-75 0 5 -1 -3 0 5 -2 -3

3954BS7_10_1W 3955B13.5 3956B-75 2 12 -2 -5 2 11 -3 -6

3957BS7_10_1X 3958B13.5 3959B-75 0 10 -1 -4 1 11 -2 -5

3960BS7_10_1Y 3961B3.0 3962B-75 0 21 -4 -10 2 22 -4 -8

3963BF7_10_1M 3964B0.0 3965B-74 1 24 -3 -9 3 23 -4 -9

3966BGir

der

7

3967BCro

ss S

ecti

on

3968B2

3969BS7_10_2V 3970B28.5 3971B-13 0 3 0 1 2 3 -1 -1

3972BS7_10_2W 3973B13.5 3974B-13 0 -1 1 3 8 4 -1 2

3975BS7_10_2X 3976B13.5 3977B-13 -1 -1 0 2 1 5 0 1

3978BS7_10_2Y 3979B3.0 3980B-13 -47 -108 -12 -63 -51 -107 -23 -69

3981BF7_10_2Z 3982B3.0 3983B-14 0 -4 -4 -21 1 -3 -5 -20

603

Table J.4: AE static positions—cross-section strains—Girder 7—Span 11

Cross

Section 3984BGage

3985BHeight

from

bottom of

girder

(in.)

3986BDistance from

center of

continuity

diaphragm

(in.)

– Span 10

+ Span 11

3987BStrain

(x10-6

in./in.)

– compressive

+ tensile

3988BAE—Night 1 (LC-6.5) 3989BAE—Night 2 (LC-6)

3990BSpan 10 3991BSpan 11 3992BSpan 10 3993BSpan 11

3994BEast

Truck 3995BBoth

Trucks

3996BEast

Truck

3997BBoth

Trucks

3998BEast

Truck

3999BBoth

Trucks

4000BEast

Truck

4001BBoth

Trucks

4002BGir

der

7

4003BCro

ss S

ecti

on

4004B3

4005BS7_11_3V 4006B28.5 4007B13 -4 -3 0 -5 -2 -1 -7 -7

4008BS7_11_3W 4009B13.5 4010B13 -3 -3 1 5 -4 -4 -2 3

4011BS7_11_3X 4012B13.5 4013B13 1 3 -2 -4 2 5 -6 -7

4014BS7_11_3Y 4015B3.0 4016B13 -2 -4 -3 -7 0 -5 -10 -10

4017BS7_11_3Z 4018B3.0 4019B13 -2 -3 2 -6 3 -1 -6 -7

4020BGir

der

7

4021BCro

ss S

ecti

on

4022B4

4023BS7_11_4V 4024B28.5 4025B75 0 0 -1 -3 1 1 -1 -4

4026BS7_11_4W 4027B13.5 4028B75 0 -2 1 7 0 -3 0 6

4029BS7_11_4X 4030B13.5 4031B75 -2 -4 -1 5 -1 -3 -3 4

4032BS7_11_4Y 4033B3.0 4034B75 -1 -5 4 26 0 -5 3 23

4035BF7_11_4M 4036B0.0 4037B74 -5 -11 2 28 -4 -10 3 28

604

Table J.5: AE static positions—cross-section strains—Girder 8—Span 10

Cross

Section 4038BGage

4039BHeight

from

bottom of

girder

(in.)

4040BDistance from

center of

continuity

diaphragm

(in.)

– Span 10

+ Span 11

4041BStrain

(x10-6

in./in.)

– compressive

+ tensile

4042BAE—Night 1 (LC-6.5) 4043BAE—Night 2 (LC-6)

4044BSpan 10 4045BSpan 11 4046BSpan 10 4047BSpan 11

4048BEast

Truck 4049BBoth

Trucks

4050BEast

Truck

4051BBoth

Trucks

4052BEast

Truck

4053BBoth

Trucks

4054BEast

Truck

4055BBoth

Trucks

4056BGir

der

8

4057BCro

ss S

ecti

on

4058B1

4059BS8_10_1V 4060B28.5 4061B-75 3 3 -4 -6 3 3 -5 -7

4062BS8_10_1W 4063B13.5 4064B-75 10 13 -6 -12 10 13 -8 -11

4065BS8_10_1X 4066B13.5 4067B-75 8 14 -6 -11 7 13 -7 -12

4068BF8_10_1Y 4069B3.0 4070B-74 10 11 -5 -8 11 12 -5 -7

4071BS8_10_1M 4072B0.0 4073B-75 11 20 -10 -16 16 28 -7 -14

4074BF8_10_1M 4075B0.0 4076B-74 11 19 -6 -10 11 19 -7 -10

4077BGir

der

8

4078BCro

ss S

ecti

on

4079B2

4080BS8_10_2V 4081B28.5 4082B-13 2 3 -1 -2 3 5 -2 -2

4083BS8_10_2W 4084B13.5 4085B-13 6 6 0 -1 5 7 -2 -1

4086BS8_10_2X 4087B13.5 4088B-13 5 7 0 0 5 7 0 0

4089BF8_10_2Y 4090B3.0 4091B-14 -16 -24 -14 -26 -17 -25 -16 -26

4092BF8_10_2Z 4093B3.0 4094B-14 0 -5 -6 -14 1 -4 -4 -12

605

Table J.6: AE static positions—cross-section strains—Girder 8—Span 11

Cross

Section 4095BGage

4096BHeight

from

bottom of

girder

(in.)

4097BDistance from

center of

continuity

diaphragm

(in.)

– Span 10

+ Span 11

4098BStrain

(x10-6

in/in)

– compressive

+ tensile

4099BAE—Night 1 (LC-6.5) 4100BAE—Night 2 (LC-6)

4101BSpan 10 4102BSpan 11 4103BSpan 10 4104BSpan 11

4105BEast

Truck 4106BBoth

Trucks

4107BEast

Truck

4108BBoth

Trucks

4109BEast

Truck

4110BBoth

Trucks

4111BEast

Truck

4112BBoth

Trucks

4113BGir

der

8

4114BCro

ss S

ecti

on

4115B3

4116BS8_11_3V 4117B28.5 4118B13 -76 -107 -23 -28 -71 -100 -24 -27

4119BS8_11_3W 4120B13.5 4121B13 -1 -2 -4 -6 -2 -3 -6 -6

4122BS8_11_3X 4123B13.5 4124B13 -8 -14 8 10 -5 -9 7 10

4125BF8_11_3Y 4126B3.0 4127B14 -13 -27 -11 -15 -15 -27 -10 -16

4128BF8_11_3Z 4129B3.0 4130B14 -19 -33 -3 -20 -15 -29 0 -16

4131BGir

der

8

4132BCro

ss S

ecti

on

4133B4

4134BS8_11_4V 4135B28.5 4136B75 -2 -3 -10 -19 -2 -1 -11 -19

4137BS8_11_4W 4138B13.5 4139B75 -5 -8 4 3 -4 -6 2 1

4140BS8_11_4X 4141B13.5 4142B75 -5 -7 -2 -3 -2 -3 -6 -1

4143BF8_11_4Y 4144B3.0 4145B74 -6 -8 15 16 -6 -8 13 16

4146BS8_11_4M 4147B0.0 4148B75 -27 -40 77 136 -29 -44 80 148

4149BF8_11_4M 4150B0.0 4151B74 -15 -21 34 55 -15 -20 31 59

606

Table J.7: AE static positions—bottom-fiber strains—Girder 7

Span 4152BGage

4153BHeight

from

bottom of

girder

(in.)

4154BDistance from

center of

continuity

diaphragm

(in.)

– Span 10

+ Span 11

4155BStrain

(x10-6

in/in)

– compressive

+ tensile

4156BAE—Night 1 (LC-6.5) 4157BAE—Night 2 (LC-6)

4158BSpan 10 4159BSpan 11 4160BSpan 10 4161BSpan 11

4162BEast

Truck 4163BBoth

Trucks

4164BEast

Truck

4165BBoth

Trucks

4166BEast

Truck

4167BBoth

Trucks

4168BEast

Truck

4169BBoth

Trucks

4170B10

4171BF7_10_1M 4172B0

4173B-74 1 24 -3 -9 3 23 -4 -9

4174BF7_10_CK 4175B-47 -1 96 -22 -70 0 92 -26 -74

4176B11

4177BF7_11_CK

4178B0

4179B47 -37 -93 6 140 -31 -87 1 130

4180BF7_11_4M 4181B74 -5 -11 2 28 -4 -10 3 28

4182BF7_11_5M 4183B104 -4 -7 3 30 -5 -8 -2 25

4184BS7_11_5M 4185B105 -7 -10 8 28 -8 -13 -3 35

4186BS7_11_6M 4187B273 -9 -13 10 38 -2 -5 17 38

4188BS7_11_7M 4189B441 -18 -19 11 30 0 0 25 30

4190BS7_11_8M 4191B609 -23 -26 7 22 3 6 37 20

607

Table J.8: AE static positions—bottom-fiber strains—Girder 8

Span 4192BGage

4193BHeight

from

bottom of

girder

(in.)

4194BDistance from

center of

continuity

diaphragm

(in.)

– Span 10

+ Span 11

4195BStrain

(x10-6

in/in)

– compressive

+ tensile

4196BAE—Night 1 (LC-6.5) 4197BAE—Night 2 (LC-6)

4198BSpan 10 4199BSpan 11 4200BSpan 10 4201BSpan 11

4202BEast

Truck 4203BBoth

Trucks

4204BEast

Truck

4205BBoth

Trucks

4206BEast

Truck

4207BBoth

Trucks

4208BEast

Truck

4209BBoth

Trucks

4210B10

4211BS8_10_1M

4212B0

4213B-75 11 20 -10 -16 16 28 -7 -14

4214BF8_10_1M 4215B-74 11 19 -6 -10 11 19 -7 -10

4216BF8_10_CK 4217B-41 69 117 -72 -125 63 106 -72 -120

4218B11

4219BF8_11_CK

4220B0

4221B52 -56 -87 48 69 -54 -81 52 71

4222BF8_11_4M 4223B74 -15 -21 34 55 -15 -20 31 59

4224BS8_11_4M 4225B75 -27 -40 77 136 -29 -44 80 148

4226BF8_11_5M 4227B104 -9 -13 22 34 -10 -14 21 34

4228BS8_11_5M 4229B105 -5 -10 24 34 -9 -14 16 34

4230BS8_11_6M 4231B273 -13 -16 30 49 -4 -6 36 47

4232BS8_11_7M 4233B441 -19 -22 23 42 0 0 41 41

4234BS8_11_8M 4235B609 5 4 16 24 -4 -7 4 22

608

Table J.9: AE static positions—FRP strains—Girder 7

Span 4236BGage

4237BHeight

from

bottom of

girder

(in.)

4238BDistance from

center of

continuity

diaphragm

(in.)

– Span 10

+ Span 11

4239BStrain

(x10-6

in/in)

– compressive

+ tensile

4240BAE—Night 1 (LC-6.5) 4241BAE—Night 2 (LC-6)

4242BSpan 10 4243BSpan 11 4244BSpan 10 4245BSpan 11

4246BEast

Truck 4247BBoth

Trucks

4248BEast

Truck

4249BBoth

Trucks

4250BEast

Truck

4251BBoth

Trucks

4252BEast

Truck

4253BBoth

Trucks

4254B10

4255BF7_10_1M 4256B0 4257B-74 1 24 -3 -9 3 23 -4 -9

4258BF7_10_CK 4259B0 4260B-47 -1 96 -22 -70 0 92 -26 -74

4261BF7_10_2Z 4262B3 4263B-13 0 -4 -4 -21 1 -3 -5 -20

4264B11

4265BF7_11_CK 4266B0 4267B47 -37 -93 6 140 -31 -87 1 130

4268BF7_11_4M 4269B0 4270B74 -5 -11 2 28 -4 -10 3 28

4271BF7_11_5M 4272B0 4273B104 -4 -7 3 30 -5 -8 -2 25

609

Table J.10: AE static positions—FRP strains—Girder 8

Span 4274BGage

4275BHeight

from

bottom of

girder

(in.)

4276BDistance from

center of

continuity

diaphragm

(in.)

– Span 10

+ Span 11

4277BStrain

(x10-6

in/in)

– compressive

+ tensile

4278BAE—Night 1 (LC-6.5) 4279BAE—Night 2 (LC-6)

4280BSpan 10 4281BSpan 11 4282BSpan 10 4283BSpan 11

4284BEast

Truck 4285BBoth

Trucks

4286BEast

Truck

4287BBoth

Trucks

4288BEast

Truck

4289BBoth

Trucks

4290BEast

Truck

4291BBoth

Trucks

4292B10

4293BF8_10_1Y 4294B3 4295B-74 10 11 -5 -8 11 12 -5 -7

4296BF8_10_1M 4297B0 4298B-74 11 19 -6 -10 11 19 -7 -10

4299BF8_10_CK 4300B0 4301B-41 69 117 -72 -125 63 106 -72 -120

4302BF8_10_2Y 4303B3 4304B-14 -16 -24 -14 -26 -17 -25 -16 -26

4305BF8_10_2Z 4306B3 4307B-14 0 -5 -6 -14 1 -4 -4 -12

4308B11

4309BF8_11_3Y 4310B3 4311B14 -13 -27 -11 -15 -15 -27 -10 -16

4312BF8_11_3Z 4313B3 4314B14 -19 -33 -3 -20 -15 -29 0 -16

4315BF8_11_CK 4316B0 4317B52 -56 -87 48 69 -54 -81 52 71

4318BF8_11_4Y 4319B3 4320B74 -6 -8 15 16 -6 -8 13 16

4321BF8_11_4M 4322B0 4323B74 -15 -21 34 55 -15 -20 31 59

4324BF8_11_5M 4325B0 4326B104 -9 -13 22 34 -10 -14 21 34

610

Appendix K

24BFALSE SUPPORT BEARING PAD EFFECTS DURING LOAD TESTING

K.1 103BINSTALLATION OF FALSE SUPPORTS WITH BEARING PADS

In response to the severity of cracking observed at the continuous ends of prestressed

concrete girders of I-565, ALDOT installed steel frame false supports under spans

containing damaged girders, as shown in 2237HFigure K.1. False supports were installed

within ten feet of the bents, allowing the cracked regions of damaged girders to be

contained between false supports and the nearest bent.

Figure K.1: Steel frame false supports

611

The false supports were installed to leave a gap of at least one inch between the top of

false supports and the bottom of girders before adding bearing pads. Elastomeric bearing

pads were then installed under each girder, attaching them to the tops of the false

supports, as shown in Figure K 2238H.2

Figure K.2: Bearing pad between false support and exterior girder

A small gap between the bearing pad and girder bottom remained after false support

installation. Bearing pads were installed to prevent catastrophic collapse in case of

further deterioration of the bridge girders, but it was undesirable for bearing pads to

remain in contact with bridge girders during load testing. An installed bearing pad with

space remaining between the pad and girder is shown in Figure K2239H.3. A bearing pad that

is in contact with a girder and likely transferring loads through the false support is shown

in Figure K2240H.4.

612

Figure K.3: Bearing pad location with space between the bearing pad and girder

Figure K.4: Bearing pad location without space between the bearing pad and girder

613

K.2 104BPRE-REPAIR BEARING PAD CONDITIONS

During initial test preparation, it was observed that some of the gaps between bearing

pads and false supports had closed, and bearing pads were in contact with instrumented

girders, as shown in Figure K 2241H.5. The closure of gaps between girders and false support

bearing pads was likely due to downward creep deformations of the girders or settlement

of the bridge structure.

Figure K.5: Bearing pad in contact with girder during pre-repair testing

An attempt was made to remove the bearing pads; however, initial removal attempts were

unsuccessful. A surface-mounted strain gage was attached to one column of the false

supports to determine if the false supports were supporting normal traffic loads due to the

bearing pads being in direct contact with the girders. Due to the measurement of small

614

compressive strains, it was determined that the bearing pads were transmitting some load

through the false supports during normal traffic conditions (Fason 2009).

For research purposes, it was desirable to test the bridge without additional load-

bearing supports. The removal of bearing pads was scheduled to take place on the day of

the pre-repair testing; however, the overcast weather conditions on that day were not

conducive to the upward movement expected of the girders during the warmest time of

the day in late spring. Under the overcast weather conditions, the gap between the

bearing pads and the girders was so small—in some cases non-existent—that the

complete removal of all bearing pads prior to the scheduled pre-repair tests was not

possible using the available equipment and methods. After realizing that complete

removal of all bearing pads would not be possible before conducting pre-repair load tests,

holes were drilled in the bearing pads to alleviate pressure and reduce the effective

stiffness of the pads (Fason 2009).

Fason (2009) reported that, prior to the pre-repair tests, one bearing pad was

completely removed (Girder 8 of Span 10), one half of another bearing pad was removed

(east half of Girder 7 of Span 10), and holes were drilled in the remaining bearing pads to

reduce their effective stiffness (west half of Girder 7 of Span 10, Girder 7 of Span 11, and

Girder 8 of Span 11).

The pre-repair tests were conducted without complete removal of all bearing pads.

Following the pre-repair tests, it was suggested that the presence of the bearing pads

could have had an effect on the measured bridge behavior (Fason 2009).

K.3 105BBEARING PAD REMOVAL DURING FRP INSTALLATION

The installation of the FRP reinforcement required that all bearing pads be removed.

615

These bearing pads inhibited FRP installation to the bottom of the girder at false-support

locations. The bearing pads under Span 11 were, in general, more difficult to remove

than the bearing pads under Span 10. Initially, the contractor attempted to remove each

bearing pad by punching it out of place using a chisel and hammer. When a bearing pad

was under enough pressure to prevent removal, the contractor then used a reciprocating

saw on the pad in an attempt to alleviate some of that pressure, as shown in Figure K 2242H.6.

Figure K.6: Use of reciprocating saw during bearing pad removal

In some cases, saw cutting alone was not effective at alleviating enough pressure for

successful bearing pad removal. In these cases, a propane torch was used to soften the

rubber, as shown in Figure K 2243H.7, which then allowed for a more effective sawing process.

616

Figure K.7: Use of propane torch during bearing pad removal

After successful pressure alleviation, the bearing pad was removed using the initial

chisel-and-hammer removal method, as shown in Figure K 2244H.8. An example of a bearing

pad that required forceful removal is shown in Figure K 2245H.9. Bearing pads were not

replaced following the installation of the FRP reinforcement.

617

Figure K.8: Successful removal of bearing pad

Figure K.9: Bearing pad after forceful removal

618

K.4 106BPOST-REPAIR BEARING PAD CONDITIONS

The post-repair tests were conducted without the presence of any bearing pads. Fason

(2009) indicated that direct relationships between structural behavior measured and

observed during pre-repair and post-repair load testing may be affected by the variation

of support conditions.

K.5 107BANALYSIS OF NUMERICAL RESULTS

The measurements of the pre- and post-repair tests were compared to better determine the

effects related to the presence of the bearing pads. These comparisons include:

deflections, crack opening displacements, and surface strains measured during

multiposition load testing as well as deflections measured during superposition testing.

K.5.1 4327BDEFLECTIONS—MULTIPOSITION LOAD TESTING

Truck positions resulting in maximum downward deflections measured during pre- and

post-repair multiposition load testing have been analyzed to assess whether the bearing

pads had an effect on the pre-repair support conditions and general pre-repair bridge

behavior. Pre- and post-repair deflections measured in response to four midspan truck

positions (A1, C1, A9, and C9) are shown in Figures K 2246H.10–K2247H.13. The arrows in the

figures represent the position of the wheel loads on the bridge. For each midspan truck

position, the midspan and quarterspan deflection measurements—and the differences

between pre- and post-repair testing—are presented in Tables K 2248H.1–K2249H.4. For each

midspan truck position, the table of measurements follows the figure that illustrates the

measured deflections.

619

Figure K.10: Deflections—A1

Table K.1: Deflections—A1

Span Girder

Location

(span)

Post-

Repair

(in.)

Pre-

Repair

(in.)

Diff.

(in.)

Percent

Diff.

(%)

10

7 mid -0.32 -0.31 -0.01 3

quarter -0.22 -0.20 -0.02 10

8 mid -0.26 -0.24 -0.02 8

quarter -0.17 -0.16 -0.01 6

11

7 quarter 0.04 0.05 -0.01 20

mid 0.05 0.06 -0.01 20

8 quarter 0.04 0.05 -0.01 20

mid 0.04 0.05 -0.01 20

-0.4

-0.3

-0.2

-0.1

0.0

0.1

-900 -700 -500 -300 -100 100 300 500 700 900

Bo

tto

m-F

iber

Def

lect

ion

(in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 (Pre-Repair)

G8 (Pre-Repair)

G7 (Post-Repair)

G8 (Post-Repair)

620

Figure K.11: Deflections—A9

Table K.2: Deflections—A9

Span Girder

Location

(span)

Post-

Repair

(in.)

Pre-

Repair

(in.)

Diff.

(in.)

Percent

Diff.

(%)

10

7 mid 0.04 0.05 -0.01 20

quarter 0.04 0.05 -0.01 20

8 mid 0.04 0.05 -0.01 20

quarter 0.03 0.04 -0.01 30

11

7 quarter -0.22 -0.20 -0.02 10

mid -0.33 -0.30 -0.03 10

8 quarter -0.17 -0.15 -0.02 13

mid -0.25 -0.23 -0.02 8

-0.4

-0.3

-0.2

-0.1

0.0

0.1

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er D

efle

ctio

n (

in.)

Distance from Center of Continuity Diaphragm (in.)

G7 (Pre-Repair)

G8 (Pre-Repair)

G7 (Post-Repair)

G8 (Post-Repair)

621

Figure K.12: Deflections—C1

Table K.3: Deflections—C1

Span Girder

Location

(span)

Post-

Repair

(in.)

Pre-

Repair

(in.)

Diff.

(in.)

Percent

Diff.

(%)

10

7 mid -0.29 -0.28 -0.01 4

quarter -0.20 -0.19 -0.01 5

8 mid -0.35 -0.33 -0.02 6

quarter -0.22 -0.21 -0.01 5

11

7 quarter 0.04 0.05 -0.01 20

mid 0.04 0.06 -0.02 40

8 quarter 0.04 0.06 -0.02 40

mid 0.05 0.07 -0.02 30

-0.4

-0.3

-0.2

-0.1

0.0

0.1

-900 -700 -500 -300 -100 100 300 500 700 900

Bo

tto

m-F

iber

Def

lect

ion

(in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 (Pre-Repair)

G8 (Pre-Repair)

G7 (Post-Repair)

G8 (Post-Repair)

622

Figure K.13: Deflections—C9

Table K.4: Deflections—C9

Span Girder

Location

(span)

Post-

Repair

(in.)

Pre-

Repair

(in.)

Diff.

(in.)

Percent

Diff.

(%)

10

7 mid 0.04 0.05 -0.01 20

quarter 0.03 0.05 -0.02 50

8 mid 0.05 0.06 -0.01 20

quarter 0.04 0.05 -0.01 20

11

7 quarter -0.21 -0.18 -0.03 15

mid -0.31 -0.27 -0.04 14

8 quarter -0.24 -0.21 -0.03 13

mid -0.35 -0.32 -0.03 9

-0.4

-0.3

-0.2

-0.1

0.0

0.1

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er D

efle

ctio

n (

in.)

Distance from Center of Continuity Diaphragm (in.)

Girder 7 (Pre-Repair)

Girder 8 (Pre-Repair)

Girder 7 (Post-Repair)

Girder 8 (Post-Repair)

623

During the post-repair load tests, the measured downward deflections of the loaded

span were increased while the upward deflections of the unloaded span were decreased

when compared to pre-repair measurements. This behavior could be attributed to the

false support of the loaded span acting as an active load-bearing support during the pre-

repair test but not during the post-repair test. If the false supports were acting as load-

bearing supports, the loaded span would have a shorter effective span length. The post-

repair downward deflections of the loaded span could have been larger due to an

increased effective span length causing a decrease in apparent stiffness when compared to

the pre-repair test conditions.

The post-repair upward deflections of the non-loaded span could have been smaller

due to the bent becoming the only active support during post-repair testing. If the false

support acted as an active support during pre-repair testing, that support could have

shifted the inflection point further from the main support, which could result in greater

upward deflections being measured in the non-loaded span, when compared to the post-

repair conditions that had just one true support condition at the bent.

K.5.2 4328BCRACK-OPENING DISPLACEMENTS—MULTIPOSITION LOAD TESTING

Truck positions that resulted in crack openings during pre- and post-repair multiposition

load testing were analyzed to assess bearing pad effects on pre-repair damaged region

behavior. Truck position locations are described in Section 4.4 of this thesis. During

both pre- and post-repair testing, Stop Position 4 had the greatest effect on the Span 10

crack openings, and Stop Position 7 had the greatest effect on the Span 11 crack

openings. The pre- and post-repair crack-opening displacements measured for Stop

624

Positions A4, A7, C4, and C7 are presented in Figures K2250H.14–K2251H.17 and 2252HTable K.5. The

arrows in the figures represent the position of the wheel loads on the bridge.

Figure K.14: Crack-opening displacements—pre- and post-repair—A4

-0.05

-0.04

-0.03

-0.02

-0.01

0.00

0.01

0.02

0.03

0.04

0.05

-300 -250 -200 -150 -100 -50 0 50 100 150 200 250 300

Cra

ck-O

pen

ing D

isp

lace

men

t (m

m)

Distance from Center of Continuity Diaphragm (in.)

G7 (Pre-Repair)

G8 (Pre-Repair)

G7 (Post-Repair)

G8 (Post-Repair)

625

Figure K.15: Crack-opening displacements—pre- and post-repair—A7

Figure K.16: Crack-opening displacements—pre- and post-repair—C4

-0.05

-0.04

-0.03

-0.02

-0.01

0.00

0.01

0.02

0.03

0.04

0.05

-300 -250 -200 -150 -100 -50 0 50 100 150 200 250 300

Cra

ck-O

pen

ing

Dis

pla

cem

ent

(mm

)

Distance from Center of Continuity Diaphragm (in.)

G7 (Pre-Repair)

G8 (Pre-Repair)

G7 (Post-Repair)

G8 (Post-Repair)

-0.05

-0.04

-0.03

-0.02

-0.01

0.00

0.01

0.02

0.03

0.04

0.05

-300 -250 -200 -150 -100 -50 0 50 100 150 200 250 300

Cra

ck-O

pen

ing

Dis

pla

cem

ent

(mm

)

Distance from Center of Continuity Diaphragm (in.)

G7 (Pre-Repair)

G8 (Pre-Repair)

G7 (Post-Repair)

G8 (Post-Repair)

626

Figure K.17: Crack-opening displacements—pre- and post-repair—C7

-0.05

-0.04

-0.03

-0.02

-0.01

0.00

0.01

0.02

0.03

0.04

0.05

-300 -250 -200 -150 -100 -50 0 50 100 150 200 250 300

Cra

ck-O

pen

ing D

isp

lace

men

t (m

m)

Distance from Center of Continuity Diaphragm (in.)

G7 (Pre-Repair)

G8 (Pre-Repair)

G7 (Post-Repair)

G8 (Post-Repair)

627

Table K.5: Bearing pad effects—crack-opening displacements

Girder Span

Pre-

or

Post-

Repair

Crack-Opening Displacement

(mm)

– closing

+ opening

A4 A7 C4 C7

7

10 Pre- 0.021 -0.010 0.019 -0.010

Post- 0.024 -0.008 0.022 -0.009

11 Pre- -0.008 0.019 -0.008 0.020

Post- -0.003 0.041 -0.006 0.039

8

10 Pre- -0.003 -0.005 -0.004 -0.008

Post- -0.004 -0.005 -0.005 -0.008

11 Pre- -0.003 0.004 -0.004 0.010

Post- -0.002 0.018 -0.004 0.032

Notes: Measurements presented in bold represent the crack openings with the

greatest difference between pre- and post-repair testing

1 in. = 25.4 mm

The crack-opening displacements measured in Span 10 were similar for both pre- and

post-repair testing, but the crack-opening displacements measured in Span 11 in response

to the Stop Position 7 load condition of the post-repair test increased in comparison to the

crack-opening displacements measured in response to the same load condition during

pre-repair testing. This behavior corresponds with the Span 10 bearing pads being

partially removed prior to pre-repair testing, and the Span 11 bearing pads being under

enough pressure to prevent any removal prior to pre-repair testing. It is apparent that

girder contact with the false support bearing pads under Span 11 resulted in additional

support conditions that affected pre-repair measurements.

628

K.5.3 4329BSURFACE STRAINS

Truck positions that resulted in tension strains measured within damaged regions during

pre- and post-repair multiposition load testing were analyzed to assess bearing pad effects

on pre-repair damaged region behavior. During both pre- and post-repair testing,

Stop Position 4 had the greatest effect on the Span 10 damaged region tension strains, and

Stop Position 7 had the greatest effect on the Span 11 damaged region tension strains.

The cross-section locations that contain the most sensors near the false support locations

are Section 1 in Span 10 and Section 4 in Span 11. Stop Positions A4, A7, C4, and C7 of

pre- and post-repair testing have been analyzed to assess the bearing pad effects exhibited

by bottom-fiber strains as well as strain profiles at Sections 1 and 4.

It should be noted that some of the concrete strain gages from the pre-repair tests that

were covered during the FRP repair had become defective and were discontinued for the

post-repair tests. At the locations of discontinued sensors, strain gages were installed on

the surface of the FRP reinforcement. The comparison of pre-repair concrete strains and

post-repair FRP strains may not be appropriate for analyzing bearing pad effects.

The bottom-fiber strains measured in response to truck position A4 are shown in

2253HFigure K.18. The strains measured within the Section 1 cross section of Girders 7 and 8

in response to truck position A4 are shown in Figures K 2254H.19 and K2255H.20 respectively.

629

Figure K.18: Bottom-fiber strain—A4

Figure K.19: Strain profile—Girder 7—Section 1—A4

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er S

train

(x10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete (Pre-Repair)

G8 - Concrete (Pre-Repair)

G7 - Concrete (Post-Repair)

G8 - Concrete (Post-Repair)

G7 - FRP

G8 - FRP

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete (Pre-Repair)

Concrete (Post-Repair)

FRP

630

Figure K.20: Strain profile—Girder 8—Section 1—A4

The bottom-fiber strains measured in response to truck position C4 are shown in

2256HFigure K.21. The strains measured within the Section 1 cross section of Girders 7 and 8

in response to truck position C4 are shown in Figures K 2257H.22 and K2258H.23 respectively.

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete (Pre-Repair)

Concrete (Post-Repair)

FRP

631

Figure K.21: Bottom-fiber strain—C4

Figure K.22: Strain profile—Girder 7—Section 1—C4

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bo

tto

m-F

iber

Str

ain

(x

10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete (Pre-Repair)

G8 - Concrete (Pre-Repair)

G7 - Concrete (Post-Repair)

G8 - Concrete (Post-Repair)

G7 - FRP

G8 - FRP

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bott

om

of

Gir

der

(in

.)

Strain (x10-6 in./in.)

Concrete (Pre-Repair)

Concrete (Post-Repair)

FRP

632

Figure K.23: Strain profile—Girder 8—Section 1—C4

The bottom-fiber strains measured in response to truck position A7 are shown in

2259HFigure K.24. The strains measured within the Section 4 cross section of Girders 7 and 8

in response to truck position A7 are shown in Figures K 2260H.25 and K2261H.26 respectively.

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete (Pre-Repair)

Concrete (Post-Repair)

FRP

633

Figure K.24: Bottom-fiber strain—A7

Figure K.25: Strain profile—Girder 7—Section 4—A7

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bo

tto

m-F

iber

Str

ain

(x

10

-6 in

./in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete (Pre-Repair)

G8 - Concrete (Pre-Repair)

G7 - Concrete (Post-Repair)

G8 - Concrete (Post-Repair)

G7 - FRP

G8 - FRP

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bott

om

of

Gir

der

(in

.)

Strain (x10-6 in./in.)

Concrete (Pre-Repair)

Concrete (Post-Repair)

FRP

634

Figure K.26: Strain profile—Girder 8—Section 4—A7

The bottom-fiber strains measured in response to truck position C7 are shown in

2262HFigure K.27. The strains measured within the Section 4 cross section of Girders 7 and 8

in response to truck position C7 are shown in Figures K 2263H.28 and K2264H.29 respectively.

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete (Pre-Repair)

Concrete (Post-Repair)

FRP

635

Figure K.27: Bottom-fiber strain—C7

Figure K.28: Strain profile—Girder 7—Section 4—C7

-240

-200

-160

-120

-80

-40

0

40

80

120

160

200

-900 -700 -500 -300 -100 100 300 500 700 900

Bott

om

-Fib

er S

train

(x1

0-6

in./

in.)

Distance from Center of Continuity Diaphragm (in.)

G7 - Concrete (Pre-Repair)

G8 - Concrete (Pre-Repair)

G7 - Concrete (Post-Repair)

G8 - Concrete (Post-Repair)

G7 - FRP

G8 - FRP

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete (Pre-Repair)

Concrete (Post-Repair)

FRP

636

Figure K.29: Strain profile—Girder 8—Section 4—C7

When comparing the pre- and post-repair test measurements, sensors located near the

bottom of Section 4 cross sections experienced a greater increased tension demand during

post-repair testing in response to truck positions A7 and C7 (Span 11—load scenarios)

than the sensors located near the bottom of Section 1 cross sections experienced in

response to truck positions A4 and C4 (Span 10—load scenarios).

K.5.4 4330BSUPERPOSITION DEFLECTIONS

Pre-and post-repair superposition deflection measurements have also been analyzed to

assess whether the bearing pads had an effect on pre-repair bridge behavior. Measured

superposition deflections (A1 and A9) are shown in 2265HFigure K.30 and 2266HTable K.6.

Predicted superposition deflections (A1 + A9) are shown in 2267HFigure K.31 and 2268HTable K.7

0

5

10

15

20

25

30

-60 -40 -20 0 20 40 60 80 100 120 140

Hei

gh

t fr

om

Bo

tto

m o

f G

ird

er (

in.)

Strain (x10-6 in./in.)

Concrete (Pre-Repair)

Concrete (Post-Repair)

FRP

637

Figure K.30: Deflections—superposition—A1 and A9

Table K.6: Deflections—superposition—A1 and A9

Span Girder

Location

from

Bent 11

Post-

Repair

(in.)

Pre-

Repair

(in.)

Diff.

(in.)

Percent

Diff.

(%)

10

7 midspan -0.16 -0.14 -0.02 13

quarterspan -0.11 -0.09 -0.02 20

8 midspan -0.15 -0.13 -0.02 14

quarterspan -0.09 -0.08 -0.01 10

11

7 quarterspan -0.10 -0.08 -0.02 22

midspan -0.16 -0.13 -0.03 21

8 quarterspan -0.10 -0.08 -0.02 22

midspan -0.15 -0.13 -0.02 14

-0.30

-0.25

-0.20

-0.15

-0.10

-0.05

0.00

0.05

0.10

-900 -700 -500 -300 -100 100 300 500 700 900

Bo

tto

m-F

iber

Def

lect

ion

(in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 (Pre-Repair)

G8 (Pre-Repair)

G7 (Post-Repair)

G8 (Post-Repair)

7 8

638

Figure K.31: Deflections—superposition—A1 + A9

Table K.7: Deflections—superposition—A1 + A9

Span Girder

Location

from

Bent 11

Post-

Repair

(in.)

Pre-

Repair

(in.)

Diff.

(in.)

Percent

Diff.

(%)

10

7 midspan -0.16 -0.14 -0.02 13

quarterspan -0.12 -0.09 -0.03 30

8 midspan -0.16 -0.13 -0.03 21

quarterspan -0.10 -0.08 -0.02 20

11

7 quarterspan -0.11 -0.09 -0.02 20

midspan -0.17 -0.13 -0.04 27

8 quarterspan -0.11 -0.08 -0.03 30

midspan -0.16 -0.13 -0.03 21

-0.30

-0.25

-0.20

-0.15

-0.10

-0.05

0.00

0.05

0.10

-900 -700 -500 -300 -100 100 300 500 700 900

Bo

tto

m-F

iber

Def

lect

ion

(in

.)

Distance from Center of Continuity Diaphragm (in.)

G7 (Pre-Repair)

G8 (Pre-Repair)

G7 (Post-Repair)

G8 (Post-Repair)

7 8

639

Greater downward deflections were measured for all of the post-repair measured

superposition deflections compared to the pre-repair measurements. These greater

deflections support the conclusion that a decrease in apparent stiffness was observed

during the post-repair tests. The measured superposition deflections of Span 11 were

observed to result in greater differences between pre- and post-repair measurements

compared to Span 10 deflections. This behavior further supports the conclusion that the

bearing pad conditions of Span 11 had a greater effect on pre-repair bridge behavior than

the bearing pad conditions of Span 10.

K.6 108BBEARING PAD EFFECTS

The bearing pads that remained in place during the pre-repair tests appear to have

increased the apparent stiffness of the bridge structure during pre-repair testing. Span 10

bearing pads were removed with some success prior to pre-repair testing, but Span 11

bearing pads were not removed and only had holes drilled into them to reduce effective

stiffness. All bearing pads were removed during the FRP reinforcement installation

process and were not replaced prior to post-repair testing.

During comparison of pre- and post-repair measurements, the Span 10 truck positions

were observed to result in more similar pre- and post-repair measurements than the

Span 11 truck positions. Increased deflections, crack opening displacements, and

bottom-fiber tensile strains indicate a decrease in apparent stiffness between conducting

pre-repair and post-repair testing. For these reasons, direct comparisons of pre-repair and

post-repair behavior are not useful to accurately gauge the effectiveness of the FRP

repair.

640

Appendix L

25BDATA ACQUISITION CHANNEL LAYOUT

641

Table L.1: Data acquisition channels—crack-opening displacement gages

MEGADAC Information Sensor Description and Location

Channel Tag Units Type Span Girder Location

ID

COD

ID

70 CO7_10

mm COD

10 7 NA C

68 CO8_10 8 NA A

71 CO7_11 11

7 NA D

69 CO8_11 8 NA B

Notes: AD-1 808FB-1 card used with gain of 100 for all Channels (64-71)

Card set for full-bridge measurements for Channels 68-71

Table L.2: Data acquisition channels—deflectometers

MEGADAC Information Sensor Description and Location

Channel Tag Units Type Span Girder Location

ID

DEFL

ID

65 D7_10_A

in. deflectometer

10

7 A J

64 D7_10_B B I

67 D8_10_A 8

A L

66 D8_10_B B K

0 D7_11_C

11

7

C A

1 D7_11_D D B

2 D7_11_E E C

3 D7_11_F F D

4 D8_11_C

8

C E

5 D8_11_D D F

6 D8_11_E E G

7 D8_11_F F H

Notes: AD-1 808FB-1 card used with gain of 100 for all Channels (64–71)

Card set for quarter-bridge measurements for Channels 64–67

AD808QB card used with gain of 100 for all Channels (0–7)

642

Table L.3: Data acquisition channels—strain gages—Span 10

MEGADAC Information Sensor Description and Location

Channel Tag Units Type Span Girder Cross

Section

Location

ID

18 S7_10_1V

x10-6

in./in.

concrete

10

7

1

V

17 S7_10_1W concrete W

14 S7_10_1X concrete X

16 S7_10_1Y concrete Y

12 S7_10_2V concrete

2

V

11 S7_10_2W concrete W

8 S7_10_2X concrete X

10 S7_10_2Y concrete Y

9 F7_10_2Z FRP Z

30 S8_10_1V concrete

8

1

V

29 S8_10_1W concrete W

26 S8_10_1X concrete X

28 S8_10_1Y concrete Y

24 S8_10_2V concrete

2

V

23 S8_10_2W concrete W

20 S8_10_2X concrete X

22 F8_10_2Y FRP Y

21 F8_10_2Z FRP Z

15 F7_10_1M FRP 7 1 M

27 S8_10_1M concrete 8 1

M

31 F8_10_1M FRP M

13 F7_10_CK FRP–CK 7 Crack CK

19 F8_10_CK FRP–CK 8 Crack CK

Notes: Three AD808QB cards used with gain of 100 for all Channels

8–15, 16–23, and 24–31

643

Table L.4: Data acquisition channels—strain gages—Span 11

MEGADAC Information Sensor Description and Location

Channel Tag Units Type Span Girder Cross

Section

Location

ID

36 S7_11_3V

x10-6

in./in.

concrete

11

7

3

V

35 S7_11_3W concrete W

32 S7_11_3X concrete X

34 S7_11_3Y concrete Y

33 S7_11_3Z concrete Z

42 S7_11_4V concrete

4

V

41 S7_11_4W concrete W

38 S7_11_4X concrete X

40 S7_11_4Y concrete Y

48 S8_11_3V concrete

8

3

V

47 S8_11_3W concrete W

44 S8_11_3X concrete X

46 F8_11_3Y FRP Y

45 S8_11_3Z concrete Z

54 S8_11_4V concrete

4

V

53 S8_11_4W concrete W

50 S8_11_4X concrete X

52 F8_11_4Y FRP Y

25 F7_11_4M FRP

7

4 M

56 S7_11_5M concrete 5

M

39 F7_11_5M FRP M

57 S7_11_6M concrete 6 M

58 S7_11_7M concrete 7 M

59 S7_11_8M concrete 8 M

51 S8_11_4M concrete

8

4 M

49 F8_11_4M FRP M

60 S8_11_5M concrete 5

M

55 F8_11_5M FRP M

61 S8_11_6M concrete 6 M

62 S8_11_7M concrete 7 M

63 S8_11_8M concrete 8 M

37 F7_11_CK FRP–CK 7 Crack CK

43 F8_11_CK FRP–CK 8 Crack CK

Notes: Two AD884D cards used with gain of 500 for Channels 32–39 and 48–55

Two AD885D cards used with gain of 500 for Channels 40–47 and 56–63

644

Appendix M

26BSTRAIN GAGE INSTALLATION PROCEDURE—FRP REINFORCEMENT

645

Strain Gage Installation Procedure—FRP Reinforcement Composite Material

Prepare FRP Surface

1. Mark area for gage.

2. Spray gaging area with degreaser.

3. Brush area with wire brush.

4. Smooth area with grinder if needed to remove irregularities, paint, or epoxy.

5. Continue to smooth with 220 grit sandpaper.

6. Blow loose dust from surface with compressed air.

7. Rinse area with isopropyl alcohol.

8. Sand lightly with 320 grit sandpaper.

9. Blow loose dust from surface with compressed air.

10. Rinse area with isopropyl alcohol.

11. Blot area with gauze sponges.

12. Rinse area thoroughly with clean water.

13. Blot area with gauze sponges.

14. Blow loose gauze from surface with compressed air.

15. Dry surface thoroughly (warming surface with heat gun may help).

Apply 100% solids epoxy

16. Place equal portions of PC-7 A and B on a flat surface using separate tools.

17. Mix PC-7 A and B together with putty knife.

18. Apply epoxy to gaging area, work into voids, and smooth with putty knife.

19. Allow epoxy to cure.

20. Sand surface initially with 220 grit sandpaper.

21. Blow loose particles from surface with compressed air.

22. Sand smooth with 320 grit sandpaper.

23. Blow loose particles from surface with compressed air.

24. Draw layout lines for gage location.

Apply Gage to Surface

1. Apply M-Prep A Conditioner with cotton.

2. Apply M-Prep 5A Neutralizer with cotton.

3. Dry surface thoroughly (warming surface with heat gun may help).

4. Carefully mount strain gage to glass plate with Cellophane Tape.

5. Remove the tape and gage from glass plate by lifting from gage side of tape

6. Tape gage at the desired location on FRP surface.

7. Peel tape and gage back to expose back of gage until clear of desired location by ½ in.

8. Apply 200 Catalyst-C to gage with a single stroke, allow to dry 1 minute

9. Apply M-Bond 200 just behind desired gage location

10. Apply gage to FRP surface, using thumb to spread M-Bond 200 the length of the gage.

11. Apply pressure for at least 1 minute

12. Wait at least 2 minutes to remove tape.

13. After at least 1 hour, apply M-Coat B Nitrile Rubber Coating and allow to dry.

14. Apply Mastic Tape.

15. Attach wire ends to mounted terminal strips.

646

Figure M.1: Strain gage installation—applying degreaser to gage location

Figure M.2: Strain gage installation—removal of surface irregularities

647

Figure M.3: Strain gage installation—initial surface cleaning

Figure M.4: Strain gage installation—clean surface prepared for solid epoxy

648

Figure M.5: Strain gage installation—application of solid epoxy

Figure M.6: Strain gage installation—epoxy surface

649

Figure M.7: Strain gage installation—rubber coating for moisture protection

Figure M.8: Strain gage installation—mastic tape for mechanical protection

650

Figure M.9: Strain gage installation—gage application with thin epoxy

Figure M.10: Strain gage installation—gage applied to FRP reinforcement

651

Figure M.11: Strain gage installation—rubber coating for moisture protection

Figure M.12: Strain gage installation—mastic tape for mechanical protection

652

Appendix N

27BFRP REINFORCEMENT DESIGN EXAMPLE

N.1 109BINTRODUCTION

An FRP reinforcement design example is presented in this appendix based on the

material and dimensional properties of Northbound Spans 10 and 11 of I-565 and the

FRP reinforcement system proposed for girder repair.

N.2 110BPRODUCT SELECTION

The Auburn University Highway Research Center (AUHRC) selected the Tyfo SCH-41

FRP laminate material (Fyfe 2010) as the reinforcement product for the proposed repair

of Spans 10 and 11 on I-565 in Huntsville, Alabama. Material properties for this design

are based on properties documented by the manufacturer, but samples should be prepared

by the contractor responsible for the installation of the proposed reinforcement system for

further testing to verify documented product performance.

N.3 111BSTRENGTH-LIMIT-STATE DESIGN

After selecting an FRP reinforcement material, a reinforcement system can be designed

to satisfy strength limit states with that material.

Strength-limit-state capacities and demands are determined in accordance with the

American Association of State Highway and Transportation Officials LRFD Bridge

Design Specification (AASHTO 2010), referred to as AASHTO LRFD within this thesis.

653

Limiting behavior expected of FRP reinforcement is determined in accordance with

provisions presented by the American Concrete Institute (ACI) Committee 440.2R-08

Guide for the Design and Construction of Externally Bonded FRP Systems for

Strengthening Concrete Structures (ACI Committee 440 2008), referred to as

ACI 440.2R-08 within this thesis.

N.3.1 4331BCRITICAL CROSS-SECTION LOCATIONS

Critical cross sections are specified at locations of reinforcement transition. The cross-

section locations that have been determined to be the most critical within the girders of

Northbound Spans 10 and 11 of I-565 are presented in 2269HTable N.1 and 2270HFigure N.1.

Table N.1: Critical cross-section locations

Location

Reference

Critical Section

Interior Face

of

Bearing Pad

(A-A)

Termination

of

Continuity

Reinforcement

(B-B)

from

Girder End 6.5 in. 38 in.

from

Diaphragm

Centerline

14.5 in. 46 in.

654

Figure N.1: Cracked girder with continuity reinforcement details (Barnes et al. 2006)

Analysis of test measurements, crack patterns, and documented reinforcement details

provided evidence supporting the identification of two critical cross sections. The cross

sections determined to be critical for the design of an FRP reinforcement system—similar

to the FRP reinforcement system discussed in this thesis—include the cross section at the

interior face of the bearing pad and the cross section at the termination of the mild steel

continuity reinforcement.

Shear cracks within the web were observed near the interior face of the bearing pad,

and flexural cracking was observed near the termination of the continuity reinforcement,

as shown in 2271HFigure N.1. These critical cross sections have also been noted for a girder

with an overlaying illustration of an example FRP reinforcement system with unknown

number of layers and length of FRP reinforcement, as shown in 2272HFigure N.2.

A

A

B

B

7 in.

41 in.

Precast BT-54 girder

Cast-in-place deck

Cast-in-place

continuity diaphragm

1 ft 2 ft 3 ft 4 ft 5 ft 6 ft 7 ft 8 ft

Continuity Reinforcement

Size #6 Rebar

12 of 28 bottom-flange

prestressed strands are

debonded at least 48 in.

655

Figure N.2: Longitudinal configuration profile for FRP (adapted from Barnes et al. 2006)

A

A

B

B

6.5 in.

length to be determined

Number of layers

to be determined

Four plies of wet layup,

CFRP fabric

45 in.

38 in. (Region of continuity reinforcement [six 3/4 in. steel bars])

(Debonded region for 12 of 28 bottom-flange prestressed strands)

656

The end regions of continuous sheets of reinforcement must be cut appropriately to

account for support conditions. At the interior face of the bearing pad, FRP

reinforcement cannot be installed along the bottom face of the girder, as shown in

Figure N2273H.3. At the termination of the continuity reinforcement, the FRP reinforcement

can be installed to wrap around the entire perimeter of the tension flange, as shown in

2274HFigure N.4.

Figure N.3: Cross-sectional configuration of FRP—near diaphragm (Swenson 2003)

21‖

6.5‖

A

A

Section A

Total effective width of

FRP reinforcement

bonded to girder = 30 in.

Bearing pad

3‖

Inside face of

bearing pad

Face of continuity

diaphragm

657

Figure N.4: Cross-sectional configuration of FRP—typical (Swenson 2003)

The cross section at the interior face of the bearing pad at the continuity diaphragm is

located roughly 6.5 in. from the face of the diaphragm. This location is considered

critical because it is a support condition and the bearing pad obstructs the ability to install

FRP reinforcement around the entire tension flange, which also represents a

reinforcement transition location. This is also the point of maximum shear force

influence on the bottom flange of the girder.

FRP reinforcement installed between the interior face of the bearing pad and the face

of the continuity diaphragm must be modified to allow the maximum possible amount of

FRP reinforcement to extend to the face of the diaphragm. The interference from the

girder bearing results in a decrease in the width of FRP that can be considered

longitudinal reinforcement.

At the interior face of the bearing pad, it is appropriate to assume that the mild steel

continuity reinforcement is effective longitudinal reinforcement for tension resistance as

6.5‖

Inside face of

bearing pad

Face of continuity

diaphragm

B

B

Section B

Total effective width of

FRP reinforcement

bonded to girder = 58 in.

3‖

21‖

658

long as it is adequately developed on each side of the section. Due to cracked

(or potentially cracked) conditions beyond the interior face of the bearing pad, it is also

conservative and appropriate to assume that prestressed strands do not provide concrete

precompression (for concrete shear resistance) or act as effective longitudinal

reinforcement between the face of the diaphragm and the interior face of the bearing pad.

The cross section at the termination of the mild steel continuity reinforcement is

located 38 in. from the face of the diaphragm. This location is considered critical

because it represents the initiation of a region without longitudinal steel reinforcement

that can safely be considered effective for tension resistance in response to shear or

positive bending moment demands. Even if cracking is only present between this

location and the face of the diaphragm, the short distance between the cracks and this

section makes it appropriate to assume that the prestressed strands do not provide

precompression or act as effective longitudinal reinforcement at this cross-section

location also. In this example girder, the FRP is the only bonded reinforcement that can

be considered effective at this cross section.

N.3.2 4332BCRITICAL LOAD CONDITIONS

The critical load conditions are those that result in maximum factored shear demand at

the critical locations. The maximum shear demands (Vu) and the corresponding positive

bending moment demands (Mu) for both critical locations are presented in 2275HTable N.2.

659

Table N.2: Critical load conditions

Load Effect

Critical Section

Interior Face

of

Bearing Pad

(A-A)

Termination

of

Continuity

Reinforcement

(B-B)

Vu 242 kips 231 kips

Mu 1500 kip-in. 6000 kip-in.

The factored shear and moment demands were determined from graphical

presentations of shear and moment demand presented by Swenson (2003). The factored

shear demand diagram is presented in 2276HFigure N.5, and the factored moment demand

diagram is presented in 2277HFigure N.6.

660

Figure N.5: Factored shear demand—simply supported (Swenson 2003)

0

100

200

300

400

500

0 100 200 300 400 500 600 700 800 900 1000 1100

Distance from Noncontinuous Support (in.)

Sh

ear

(kip

s)

Factored Ultimate Demand N

661

Figure N.6: Factored moment demand—simply supported (Swenson 2003)

0

10000

20000

30000

40000

50000

60000

70000

80000

90000

0 100 200 300 400 500 600 700 800 900 1000 1100

Distance from Noncontinuous Support (in.)

Factored Ultimate Demand N M

om

ent

(kip

-in

)

662

The shear and moment demand diagrams present maximum shear and moment

demands that consist of factored lane and truck live load effects (including impact forces,

which could have been disregarded as previously recommended) and factored dead load

effects. It has been recommended that the moment demand correspond with the load

condition resulting in maximum shear demand; however, these moment demands

represent maximum moment demands, which are of greater magnitude than those

expected in response to the load conditions resulting in maximum shear demand at the

critical cross-section locations. It is recommended that these demands be determined

using bridge rating analysis software. Spans should be modeled as simply supported

during analysis. All demands associated with simply supported behavior assumption

should be satisfied along the entire length of the girder. This includes shear and bending

moment demands at midspan.

N.3.3 4333BMATERIAL PROPERTIES

Relevant material properties for the girder concrete, deck concrete, steel reinforcement,

and FRP reinforcement are summarized in 2278HTable N.3. These properties include concrete

design strength (f’c), longitudinal steel reinforcement modulus of elasticity (Es) and yield

stress (fy), FRP reinforcement modulus of elasticity (Ef) and nominal thickness (tf,n), and

an initial lower bound estimate of effective debonding strain (εfe,min).

663

Table N.3: Material properties

Material

Property Value

f’c

girder 6 ksi

f’c

deck 4 ksi

Es 29000 ksi

fy

longitudinal

steel

60 ksi

fy

vertical

steel

60 ksi

Ef 11900 ksi

tf,n 0.04 in.

fe,min 0.003 in./in.

The concrete and steel material properties of original design and construction have

been documented by ALDOT (1988). The FRP material properties have been

documented for the for the Tyfo SCH-41 FRP-epoxy laminate reinforcement product

(Fyfe 2011). The minimum effective debonding strain (fe,min) is not a documented

material property of the Tyfo SCH-41 product, but is an appropriate approximate value

for initial design of a carbon FRP wet-layup reinforcement system that should not debond

prior to yielding of longitudinal steel reinforcement.

664

N.3.4 4334BDIMENSIONAL PROPERTIES

Relevant dimensional properties for the typical BT-54 cross-section constructed to

behave compositely with the bridge deck are presented in 2279HTable N.4. These properties

include the effective width of the compression zone (b), width of the girder web (bv), and

height of the girder-deck composite cross section.

Table N.4: Cross section dimensional properties

Dimensional

Property Value

b 91 in.

bv 6 in.

h 64 in.

The typical BT-54 cross section constructed to behave compositely with the bridge deck

is shown in 2280HFigure N.7.

665

Figure N.7: Typical girder-deck composite cross section

3.5‖

2‖ 2‖

36‖

4.5‖

6‖

26‖

42‖

2)

18‖

10‖

2‖

¾‖ chamfer

54‖ 6‖

3.5‖

6.5‖

91‖

Cross-Section Properties

A = 1398 in.2

I = 606330 in.4

h = 64 in.

yt = 44.6 in.

b = 91 in.

bv = 6 in.

64‖

666

The cross section dimensions have been documented by ALDOT (1988). The build-up

depth between the deck and girder was documented as varying along the girder length.

The maximum build-up depth of 3.5 in. has been assumed for the end region composite

cross-sections. The effective compression zone width (b) of 91 in. has been determined

in accordance with Article 4.6.2.6 of AASHTO LRFD.

Dimensional properties for the reinforcement associated with the two critical cross-

section locations are presented in 2281HTable N.5. Reinforcement details and figures are

presented following the table.

Table N.5: Reinforcement dimensional properties

Dimensional

Property

Critical Section

Interior Face

of

Bearing Pad

(A-A)

Termination

of

Continuity

Reinforcement

(B-B)

As 2.64 in.2 0 in.

2

ys 4.17 in. —

ds 59.8 in. —

bf 30 in. 58 in.

yf 6.5 in. 3.4 in.

df 57.5 in. 60.6 in.

Lb 6.5 in. 38 in.

Av 0.62 in.2 0.62 in.

2

s 3.5 in. 6 in.

667

The mild steel continuity reinforcement details from original design and construction

have been documented by ALDOT (1988). The continuity reinforcement configuration is

shown in 2282HFigure N.8. The continuity reinforcement of the tension flange is considered to

be effective reinforcement for tension capacity. The area (As) of reinforcement located in

the tension flange is equal to 2.64 in.2, and the centroid (ys) of this reinforcement is

located 4.17 in. from the bottom of the girder, which equates to a reinforcement depth

(ds) of 59.8 in.

Figure N.8: Continuity reinforcement—typical BT-54 cross section

(ALDOT 1988; Swenson 2003)

2‖

3.5‖

5‖

1.75‖

3‖ 6‖ 6‖ 4‖ 7‖

4‖ 19.5‖

14‖

1.75‖

Mild Steel Bent Bar (3/4‖ diameter)

668

The effective widths of FRP reinforcement (bf) are representative of the repair system

designed for Northbound Spans 10 and 11 of I-565 (Swenson 2003). The FRP

reinforcement configurations are different for the two critical locations, as shown in

Figures N2283H.9 and N2284H.10.

Figure N.9: Cross-sectional configuration of FRP—near diaphragm (Swenson 2003)

21‖

6.5‖

A

A

Section A

Total effective width of

FRP reinforcement

bonded to girder = 30 in.

Bearing pad

3‖

Inside face of

bearing pad

Face of continuity

diaphragm

669

Figure N.10: Cross-sectional configuration of FRP—typical (Swenson 2003)

The FRP reinforcement configuration at the interior face of the bearing pad has an

available effective width (bf) of 30 in., and the typical configuration that wraps the

perimeter of the tension flange has an effective width of 58 in. The centroid of FRP

reinforcement (yf) at the interior face of the bearing pad is roughly 6.5 in. from the

bottom face of the girder, which equates to a reinforcement depth (df) of 57.5 in. The

bonded length (Lb) from the FRP termination at the face of the continuity diaphragm to

the face of the bearing pad is roughly 6.5 in. The centroid of the typical FRP

reinforcement configuration is roughly 3.4 in. from the bottom face of the girder, which

equates to depth of 60.6 in. The bonded length from the diaphragm is roughly 38 in.

The vertical reinforcement details vary along the length of the girder, and have been

documented by ALDOT (1988). The typical end region vertical reinforcement details are

shown in 2285HFigure N.11.

6.5‖

Inside face of

bearing pad

Face of continuity

diaphragm

B

B

Section B

Total effective width of

FRP reinforcement

bonded to girder = 58 in.

3‖

21‖

670

Figure N.11: Vertical shear reinforcement—location and spacing (ALDOT 1988; Swenson 2003)

4 spaces

@ 3.5 in.

7 spaces

@ 6 in.

Spaces to midspan

@ 12 in.

-- All stirrups within 24 ft of midspan are #4 bars (MK-452) @ 12 in. spacing.

All other stirrups are #5 bars (MK-553), spaced as shown above.

1.5 in. clear spacing at girder end

671

The area (Av) of vertical reinforcement within a representative cross section is equal

to the area of two 5/8 in. diameter bars (0.62 in.2). The stirrup spacing (s) for the region

encompassing the interior face of the bearing pad is equal to 3.5 in. on center. The stirrup

spacing for the region encompassing the termination of the continuity reinforcement is

equal to 6 in. on center.

N.3.5 4335BINITIAL ESTIMATE OF REQUIRED FRP LAYERS

An initial estimate of required FRP layers (n) is determined in accordance with the

simplified procedure presented in Section 2286H6.4.6 of this thesis. The terms associated with

determining the area of FRP reinforcement required are shown in 2287HTable N.5, which

include factored shear demand (Vu), resistance factor ( ), assumed crack inclination

angle (θ), cross-sectional area of steel reinforcement (As), yield stress of longitudinal

steel reinforcement (fy), and an effective debonding stress (ffe,min) based on the initial

lower bound estimate of effective debonding strain (εfe,min). Formulas used to determine

the required area of FRP reinforcement are shown following the table.

672

Table N.6: Initial estimate for minimum area of FRP required

Term Units

Critical Section

Interior Face

of

Bearing Pad

(A-A)

Termination

of

Continuity

Reinforcement

(B-B)

Vu kips 242 231

— 0.9 0.9

θ degrees 45 45

Tn,req kips 269 257

As in.2 2.64 0

fy ksi 60 —

ffe,min ksi 35.7 35.7

Af,req in.2 3.10 7.20

Eq. N.1

Eq. N.2

The layers of FRP reinforcement required are determined based on the effective width

(bf) of the FRP composite at the critical cross-section locations and the manufacturer

documented nominal thickness (tf,n) per layer of installed FRP reinforcement. The terms

associated with determining the layers of FRP reinforcement required are shown in

Table N2288H.7, which include FRP reinforcement width (bf), nominal per layer thickness (tf,n)

673

required area (Af,req) and required thickness (tf,req). Formulas used to determine the

required layers of FRP reinforcement are shown following the table.

Table N.7: Initial estimate for minimum layers of FRP required

Term Units

Critical Section

Interior Face

of

Bearing Pad

(A-A)

Termination

of

Continuity

Reinforcement

(B-B)

Af,req in.2 3.10 7.20

bf in. 30 58

tf,req in. 0.10 0.12

tf,n in. 0.04 0.04

n

required layers 2.5 3.0

n

whole

number

layers 2 3

Eq. N.3

Eq. N.4

The 3 layers of FRP required at the critical location corresponding with the

termination of continuity reinforcement controls the initial estimate of layers required.

674

N.3.6 4336BSHEAR STRENGTH CHECK—THREE LAYERS

The nominal shear strength (Vn) of the proposed three-layer system must be checked in

accordance with procedures presented in Section 2289H6.4.7 of this thesis. First the effective

debonding strain (εfe) of the FRP system must be checked to determine if the net tension

strain (εs) in response to ultimate strength demands is satisfied. Once the net tension

strain is satisfied, then the vertical shear strength must be checked to determine if the

factored vertical shear demand (Vu) is satisfied.

N.3.6.1 4409BLIMITING EFFECTIVE FRP DEBONDING STRAIN—THREE LAYERS

The effective FRP debonding strain (εfe) is the strain limit at which a debonding failure

may occur. It is likely that this strain limit is the controlling failure mode for this repair

system. The terms associated with determining the limiting effective FRP strain are

shown in Table N2290H.8, which include FRP modulus of elasticity (Ef), nominal thickness per

layer of reinforcement (tf,n), girder concrete design strength (f’c), FRP bonded length (Lb),

FRP development length (Ldf), bonded length reduction factor (L), and general FRP

debonding strain (fd). Formulas used to determine the effective FRP strain are shown

following the table.

675

Table N.8: Effective FRP debonding strain—three layers

Term Units

Critical Section

Interior Face

of

Bearing Pad

(A-A)

Termination

of

Continuity

Reinforcement

(B-B)

n layers 3 3

tf,n in 0.04 0.04

Ef psi 11.9 x 106 11.9 x 10

6

f’c psi 6000 6000

Lb in. 6.5 38

Ldf in. 7.74 7.74

βL – 0.97 1

εfd in./in. 0.0054 0.0054

εfe in./in. 0.0040 0.0040

Eq. N.5

Eq. N.6

Eq. N.7

Eq. N.8

676

These formulas are presented as conversions from SI units, and the terms that control

the effective debonding strain must maintain in.–lb units rather than in.–kip units to

satisfy this conversion. The maximum effective debonding strain permitted during

design is 0.004 in./in. (0.4%). This limit controls the effective debonding strain for three

layers of Tyfo SCH-41 installed on 6 ksi concrete at both critical locations.

N.3.6.2 4410BEFFECTIVE SHEAR DEPTH—THREE LAYERS

The magnitude of the net tension strain in the tension flange response to shear demand is

dependent upon the effective shear depth (dv) of the cross section. This effective shear

depth is controlled by the area of FRP reinforcement and the limiting effective stress.

The terms associated with determining the effective shear depth are shown in Table N2291H.9,

which include cross sectional nominal bending moment strength (Mn), effective depth

(de), and cross section height (h). Formulas used to determine the effective shear depth

are shown following the table.

677

Table N.9: Effective shear depth—three layers

Term Units

Critical Section

Interior Face

of

Bearing Pad

(A-A)

Termination

of

Continuity

Reinforcement

(B-B)

Mn kip-in. 19200 19900

dv,1 in. 58.1 60.1

de in. 58.6 60.6

dv,2 in. 52.8 54.5

h in. 64 64

dv,3 in. 46.1 46.1

dv in. 58.1 60.1

Note: Bold values represent maximum effective shear depth that controls design

678

Eq. N.9

Eq. N.10

Eq. N.11

Eq. N.12

Eq. N.13

Eq. N.14

Eq. N.15

Eq. N.16

The maximum effective shear depth controls design. However, the larger of the two

values that do not require the calculation of the nominal bending moment capacity can be

used for simplicity if desired.

N.3.6.3 4411BNET LONGITUDINAL TENSILE STRAIN—INITIAL ESTIMATE

The net longitudinal tensile strain (εs) is the tensile strain expected in the tension

reinforcement in response to ultimate strength shear demand. The terms associated with

determining the net longitudinal tensile strain are shown in Table N2292H.10, which include

factored shear (Vu) and bending moment (Mu) demands, effective shear depth (dv),

679

longitudinal steel reinforcement modulus of elasticity (Es) and cross sectional area (As),

and FRP reinforcement modulus of elasticity (Ef) and cross sectional area (Af). The

formula used to determine the net longitudinal tensile strain is shown following the table.

Table N.10: Net longitudinal tensile strain—three layers

Term Units

Critical Section

Interior Face

of

Bearing Pad

(A-A)

Termination

of

Continuity

Reinforcement

(B-B)

Mu kip-in 1500 6000

Vu kips 242 231

dv in. 58.1 60.1

Vudv kip-in. 14100 13900

Es ksi 29000 29000

As in.2 2.64 0

Ef ksi 11900 11900

Af in.2 3.60 6.96

εs in./in. 0.0041 0.0056

Note: Bold values represent maximum value of either Mu or Vudv

Eq. N.17

The moment demand of this formula may not be taken to be less than the product of

the shear demand multiplied by a distance equal to the effective shear depth, as shown in

680

Equation N2293H.18. The shear demand controls for this proposed repair system, as shown in

Table N 2294H.10.

Eq. N.18

This net tensile strain must be less than the limiting effective debonding strain to

proceed with design. If the net tensile strain exceeds the limiting effective debonding

strain due to inadequate development length, but is less than the effective debonding

strain permitted with adequate development length, supplemental anchorage solutions can

be used to decrease the required development length. If supplemental anchorage is

required, proposed anchorage solutions should be tested to verify desired performance.

Supplemental anchorage may be provided to decrease the required development length,

but additional anchorage cannot be considered to increase the limiting effective

debonding strain.

If the net tensile strain exceeds the limiting effective debonding strain at a critical

location with adequate development length, then additional layers of FRP reinforcement

are required. Increasing the amount of tension reinforcement will decrease the

corresponding net tensile strain. A reiteration of the design checks are then required.

N.3.6.4 4412BLAYERS REQUIRED TO SATISFY TENSILE STRAIN DEMAND

The tensile strain demand of the proposed three-layer repair system exceeds the limiting

effective debonding strain at both critical locations, which is controlled by the maximum

appropriate effective debonding strain limit of 0.004 in./in. Additional layers of FRP

reinforcement are therefore required to decrease the net tensile strain demand. The

amount of reinforcement required to satisfy the net tensile demand can be determined.

681

The terms associated with determining the layers of FRP reinforcement required to

satisfy the net longitudinal tensile strain demand are shown in Table N2295H.11. The formula

used to determine the required layers of FRP reinforcement is shown following the table.

Table N.11: Layers required satisfying net longitudinal tensile strain

Term Units

Critical Section

Interior Face

of

Bearing Pad

(A-A)

Termination

of

Continuity

Reinforcement

(B-B)

n layers 3 3

εs kip-in 0.0041 0.0056

εfe kips 0.0040 0.0040

n

required layers 3.11 4.18

n

whole

number

layers 4 5

Eq. N.19

The moment requirement presented in Equation N2296H.19 still applies. The 5 layers of

FRP required at the critical location corresponding with the termination of continuity

reinforcement controls the layers of reinforcement required along the girder end region.

682

N.3.7 4337BSHEAR STRENGTH—FIVE LAYERS

The shear strength of the proposed five-layer system must be checked. Although the

five-layer system was determined by satisfying the effective debonding strain limit of the

three-layer system, the effective debonding strain of the five-layer system must still be

checked to confirm that the net tension strain in response to strength-limit-state demands

is satisfied. If the net tension strain is satisfied, then the vertical shear strength must be

checked to determine if the factored vertical shear demand is satisfied.

N.3.7.1 4413BEFFECTIVE FRP STRAIN—FIVE LAYERS

The FRP debonding strain decreases as the number of FRP layers increases. The terms

associated with determining the limiting effective FRP strain for the five-layer system are

shown in Table N2297H.12. Formulas used to determine the effective FRP strain have been

previously presented following Table N2298H.8.

683

Table N.12: Effective FRP debonding strain—five layers

Term Units

Critical Section

Interior Face

of

Bearing Pad

(A-A)

Termination

of

Continuity

Reinforcement

(B-B)

n layers 5 5

tf,n in. 0.04 0.04

Ef psi 11.9 x 106 11.9 x 10

6

f’c psi 6000 6000

Lb in. 6.5 38

Ldf in. 9.99 9.99

βL – 0.85 1

εdf in./in. 0.0042 0.0042

εfe in./in. 0.0036 0.0040

Due to the limited bonded length between the interior face of the bearing pad and the

face of the diaphragm, the effective debonding strain at the interior face of the bearing

pad is less than the maximum limit of 0.004 in./in. that controlled the effective debonding

strain at the same location for the three-layer system.

N.3.7.2 4414BEFFECTIVE SHEAR DEPTH—FIVE LAYERS

The effective shear depth is also affected by the change in area of FRP reinforcement.

The terms associated with determining the effective shear depth for the five-layer system

684

are shown in Table N2299H.13. Formulas used to determine the effective shear depth have

been previously presented following Table N 2300H.9.

Table N.13: Effective shear depth—five layers

Term Units

Critical Section

Interior Face

of

Bearing Pad

(A-A)

Termination

of

Continuity

Reinforcement

(B-B)

Mn kip-in. 20400 33000

dv,1 in. 57.7 59.7

de in. 58.4 60.6

dv,2 in. 52.6 54.5

h in. 64 64

dv,3 in. 46.1 46.1

dv in. 57.7 59.7

Note: Bold values represent maximum effective shear depth that controls design

The shear depths at two critical locations are similar for the three- and five-layer

systems, but the increased area of reinforcement for the five-layer system did result in a

slightly decreased effective shear depth for both locations.

N.3.7.3 4415BNET LONGITUDINAL TENSILE STRAIN—FIVE LAYERS

Although the limiting effective debonding strain decreases with additional layers of FRP

reinforcement, the additional area of reinforcement also decreases the net longitudinal

strain demand in response to ultimate strength demands. The terms associated with

685

determining the net longitudinal tensile strain are shown in Table N2301H.14. The formula

used to determine the net longitudinal tensile strain has been previously presented

following Table N2302H.10.

Table N.14: Net longitudinal tensile strain—five layers

Term Units

Critical Section

Interior Face

of

Bearing Pad

(A-A)

Termination

of

Continuity

Reinforcement

(B-B)

Mu kip-in 1500 6000

Vu kips 242 231

dv in. 57.7 59.7

Vudv kip-in. 14000 13800

Es ksi 29000 29000

As in.2 2.64 0

Ef ksi 11900 11900

Af in.2 6 11.6

εs in./in. 0.0033 0.0033

Note: Bold values represent maximum value of either Mu or Vudv

At the termination of the continuity reinforcement, the net longitudinal strain demand

has decreased from 0.0056 in./in. with three layers to 0.0033 in./in. with five layers,

which satisfies the limiting effective debonding strain at the termination of the continuity

reinforcement that is still controlled by the maximum limit of 0.0040 in./in.

686

At the interior face of the bearing pad, the net longitudinal strain demand has

decreased from 0.0041 in./in. with three layers of reinforcement to 0.0033 in./in. with

five layers of reinforcement. Due to the relatively short bond length between the face of

the face of the diaphragm and the critical location, the debonding strain at the interior

face of the bearing pad required a reduction to 85 percent of the full value. This reduced

the effective debonding strain from 0.0042 in./in. to 0.0036 in./in. at this location. Even

though the effective debonding strain is reduced, the net longitudinal strain demand is

still satisfied with five layers of FRP reinforcement at the interior face of the bearing pad.

The net longitudinal strain demand is satisfied by the effective debonding strain

capacity at both critical cross-section locations.

N.3.7.4 4416BVERTICAL SHEAR STRENGTH—FIVE LAYERS

After confirming that the net longitudinal strain in response to shear demand does not

exceed the effective debonding strain, the vertical shear strength corresponding to that net

longitudinal strain can be determined. The concrete and vertical reinforcement both

provide vertical shear strength that is affected by the net longitudinal strain.

N.3.7.4.1 CONCRETE SHEAR STRENGTH

The terms associated with determining the vertical shear strength (Vc) provided by the

concrete are shown in 2303HTable N.15, which include net tension strain (s), girder web

concrete design strength (f’c) and width (bv), effective shear depth (dv), and concrete

shear capacity factor (). Formulas used to determine the vertical shear strength

provided by the concrete are shown following the table.

687

Table N.15: Vertical shear strength—concrete—five layers

Term Units

Critical Section

Interior Face

of

Bearing Pad

(A-A)

Termination

of

Continuity

Reinforcement

(B-B)

εs in./in. 0.0033 0.0033

β – 1.39 1.37

f’c ksi 6 6

bv in. 6 6

dv in. 58 59.7

Vc kips 37 38

Eq. N.20

Eq. N.21

N.3.7.4.2 VERTICAL REINFORCEMENT SHEAR STRENGTH

The terms associated with determining the vertical shear strength (Vs) provided by the

vertical reinforcement are shown in 2304HTable N.16, which includes net tension strain (s),

vertical steel reinforcement area (Av) spacing (s) and yield strength (fy), effective shear

depth (dv), and angle of crack inclination (θ). Formulas used to determine the vertical

shear strength provided by the vertical reinforcement are shown following the table.

688

Table N.16: Vertical shear strength—vertical reinforcement—five layers

Term Units

Critical Section

Interior Face

of

Bearing Pad

(A-A)

Termination

of

Continuity

Reinforcement

(B-B)

εs in./in. 0.0033 0.0033

θ degrees 40.4 40.7

Av in.2 0.62 0.62

fy ksi 60 60

s in. 3.5 6.0

dv in. 58 59.7

Vs kips 723 430

Eq. N.22

Eq. N.23

N.3.7.4.3 NOMINAL VERTICAL SHEAR STRENGTH

The terms associated with determining the nominal vertical shear strength (Vn) are shown

in 2305HTable N.17. Formulas used to determine the nominal vertical shear strength are shown

following the table.

689

Table N.17: Nominal shear strength—five layers

Term Units

Critical Section

Interior Face

of

Bearing Pad

(A-A)

Termination

of

Continuity

Reinforcement

(B-B)

Vc kips 37 38

Vs kips 723 430

Vn kips 760 468

f’c ksi 6 6

bv in. 6 6

dv in. 58 59.7

Vn,max kips 522 537

Vn kips 522 468

Note: Bold values represent the limiting value of either Vn or Vn,max

Eq. N.24

Eq. N.25

The nominal shear strength at the interior face of the bearing pad is controlled by the

limiting nominal vertical shear strength. The nominal shear strength at the termination of

the continuity reinforcement is controlled by the increased vertical reinforcement spacing

that decreases the vertical shear strength provided by the vertical reinforcement.

690

N.3.7.4.4 VERTICAL SHEAR STRENGTH VERIFICATION—FIVE LAYERS

The shear strength provided at both critical cross-section locations must satisfy the shear

demand (Vu) at those locations. A reduction factor is applied to the nominal shear

strength in accordance with AASHTO LRFD. This reduced shear strength must satisfy

the factored shear demand. The reduced shear strengths and factored shear demands for

both critical cross-section locations have been presented in 2306HTable N.18.

Table N.18: Vertical shear strength verification—five layers

Term Units

Critical Section

Interior Face

of

Bearing Pad

(A-A)

Termination

of

Continuity

Reinforcement

(B-B)

Vn kips 522 468

— 0.9 0.9

Vn kips 470 421

Vu kips 242 231

The vertical shear strength provided with the five-layer system satisfies the vertical

shear demand at both critical cross-section locations. If the vertical shear demands had

not been satisfied, additional longitudinal FRP reinforcement would likely not improve

the situation. Adding longitudinal FRP would increase the components of Vn only

slightly. If the vertical shear demands are not satisfied by a proposed longitudinal

reinforcement system, supplemental vertical reinforcement must be provided. The

691

performance of any proposed supplemental vertical reinforcement solutions should be

verified before installation.

N.3.7.5 4417BLONGITUDINAL TENSION STRENGTH PROVIDED—FIVE LAYERS

The longitudinal reinforcement must also provide longitudinal tensile strength to satisfy

longitudinal tension demand in response to combined shear and moment effects in the

girder end region. The terms associated with determining the longitudinal tensile

strength provided (Tn,prov) are shown in 2307HTable N.19. The formula used to determine the

longitudinal tensile strength is shown following the table.

Table N.19: Longitudinal tension strength—five layers

Term Units

Critical Section

Interior Face

of

Bearing Pad

(A-A)

Termination

of

Continuity

Reinforcement

(B-B)

As in.2 2.64 0

fy ksi 60 —

n layers 5 5

Af in.2 6 11.6

ffe ksi 32.3 47.6

Tn,prov kips 352 552

Eq. N.26

692

N.3.7.6 4418BLONGITUDINAL TENSION STRENGTH REQUIRED—FIVE LAYERS

The terms associated with determining the longitudinal tensile strength required (Tn,req)

are shown in 2308HTable N.20. The formula used to determine the longitudinal tensile demand

is shown following the table.

Table N.20: Longitudinal tension demand—five layers

Term Units

Critical Section

Interior Face

of

Bearing Pad

(A-A)

Termination

of

Continuity

Reinforcement

(B-B)

f – 0.9 0.9

Mu kip-in. 1500 6000

dv in. 58 59.7

v – 0.9 0.9

Vu kips 242 231

Vs kips 723 430

Vu/ v kips/in. 269 257

θ degrees 40.4 40.7

Tn,req kips 186 261

693

Eq. N.27

N.3.7.7 4419BLONGITUDINAL TENSION STRENGTH VERIFICATION—FIVE LAYERS

Reduction factors are applied to the factored longitudinal tension demand formula to

amplify the longitudinal tension demand, as shown in Equation N 2309H.27. Thus, the nominal

longitudinal tension strength does not require reduction to safely satisfy factored demand.

The nominal longitudinal tension strengths and factored longitudinal tension demands

from Tables N 2310H.19 and N2311H.20 are presented in 2312HTable N.21 for comparison.

Table N.21: Longitudinal tension strength verification—five layers

Term Units

Critical Section

Interior Face

of

Bearing Pad

(A-A)

Termination

of

Continuity

Reinforcement

(B-B)

Tn,prov kips 352 552

Tn,req kips 186 261

N.3.7.8 4420BSTRENGTH AND DEMAND COMPARISONS—FIVE LAYERS

The reinforcement system should allow the critical cross-section locations of the structure

to satisfy moment, shear, and longitudinal tension demands in response to the load

condition resulting in the maximum ultimate strength shear demands at that location. The

reinforcement system must also satisfy the shear demand without the resulting net

longitudinal tension strain exceeding the effective debonding strain limit of the

694

reinforcement system. The strengths and demands relevant to the proposed five-layer

FRP reinforcement system are presented in 2313HTable N.22 for comparison.

Table N.22: Comparisons of strength and demand—five layers

Term Units

Critical Section

Interior Face

of

Bearing Pad

(A-A)

Termination

of

Continuity

Reinforcement

(B-B)

n layers 5 5

Mn kip-in. 18400 29700

Mu kip-in. 1500 6000

εfe in./in. 0.036 0.040

εs in./in. 0.033 0.033

Vn kips 470 421

Vu kips 242 231

Tn,prov kips 352 552

Tn,req kips 186 261

Note: All of the demands are shown to be satisfied.

695

N.4 112BEXTENT OF FRP INSTALLATION

The length of FRP reinforcement to be installed is dependent upon the development of

the prestressed strands after consideration of the cracking damage, as discussed in

Section 2314H6.5 of this thesis. It is recommended to extend the FRP reinforcement along the

girder for a distance long enough to allow for full development of stresses in the

prestressed strands.

It was previously assumed that the prestressed strands are not safely considered to be

effective between the face of the end of the girder and the end of the initial region of

debonded strands. Thus, the FRP reinforcement should be extended for a distance of at

least one development length (d) of the prestressed strands from the end of the initial

region of debonded strands. The development length can be estimated using the

approximation presented as Equation 2315H6.32 in Section 2316H6.5 of this thesis, as shown below.

Eq. N.28

The end of the initial region of debonded strands is located 45 in. from the face of the

diaphragm, as shown in 2317HFigure N.2. The first (longest) layer of FRP reinforcement

installed should extend from the face of the diaphragm to a distance of 137 in. from the

face of the diaphragm.

696

Each subsequently installed layer should extend a distance 6 in. less than its

respective underlying layer, as discussed in Section 2318H6.5. Thus, the final (shortest) layer of

FRP reinforcement should extend to a distance of 113 in. from the face of the diaphragm.

These recommended lengths of FRP reinforcement for the five-layer FRP repair are

shown in 2319HFigure N.12.

697

Figure N.12: Longitudinal configuration profile for five-layer FRP reinforcement system

A

A

B

B

6.5 in.

113 in.

4 @ 6 in.

Five plies of wet layup,

CFRP fabric

Tyfo SCH-41

45 in.

38 in. (Region of continuity reinforcement [six 3/4 in. steel bars])

(Debonded region for 12 of 28 bottom-flange prestressed strands)

137 in.

698

N.5 113BANCHORAGE

The limiting effective debonding strain at the interior face of the bearing has been

reduced to reflect the bonded length available from the termination of reinforcement at

the face of the diaphragm, as shown in Table N 2320H.12. The reduced effective debonding

strain at this location still satisfies the net tension strain demand, as shown in Table N 2321H.22.

Thus, the proposed five-layer FRP reinforcement system does not require additional

anchorage at the termination of reinforcement at the face of the diaphragm.

Supplemental anchorage may still be provided to decrease the required development

length, but a proposed method for providing additional anchorage must be tested before

implementation.

N.6 114BSERVICE-LIMIT-STATE VERIFICATION

It is appropriate to assume that the bridge structure will maintain partial continuity in

response to service loads, as discussed in Section 2322H6.7 of this thesis. The assumption of

simply supported bridge behavior during strength-limit-state design results in FRP

requirements that conservatively satisfy service-limit-state demands for a bridge structure

that maintains partial continuity.

The stress-induced strain resulting from expected diurnal temperature variation must

be checked with respect to the effective debonding strain of the FRP system. The

formula for the maximum stress-induced strain expected in response to ambient

temperatures is presented as Equation 2323H6.33 in Section 2324H6.7 of this thesis. This equation is

also presented below with the values for the concrete coefficient of thermal expansion

and the maximum expected change in temperature gradient that are presented in

Section 2325H5.4.2.2.2 of this thesis.

699

Eq. N.29

in./in.

in./in.

A temperature gradient of 60 °F was selected to exceed measured temperature gradients

as well as temperature gradients recommended by AASHTO for design. The effective

debonding strain limit far exceeds the expected stress-induced FRP strain in response to

restrained ambient temperature changes.

N.7 115BDESIGN SUMMARY

The Tyfo SCH-41 FRP reinforcement product was selected for the proposed repair

solution. Five layers of this FRP reinforcement are required to satisfy ultimate strength

demands. All first installed (longest) layer must extend a distance of at least 137 in. from

the face of the diaphragm to allow for full development of stresses in prestressed strands.

It has been determined that supplemental anchorage is not necessary at the termination of

FRP reinforcement at the face of the diaphragm, but additional anchorage may be

provided to further decrease the risk of debonding failure, if an appropriate anchorage

method has been verified. Also, the minimum effective debonding strain of this five-

layer system is shown to adequately satisfy the maximum strain demand expected in

response to ambient thermal conditions.

700

N.8 116BINSTALLATION RECOMMENDATIONS

Installation of the proposed five-layer FRP reinforcement system must adhere to the

guidelines presented in Section 6.9 of this thesis. These guidelines refer to standard

procedures for surface preparation and FRP reinforcement installation. Appropriate

installation procedures are required for the effects assumed of the designed FRP

reinforcement system to remain valid.

N.9 117BCOMPARISON OF DESIGN RECOMMENDATION AND PREVIOUSLY INSTALLED FRP

An FRP reinforcement system was designed by Auburn University researchers

(Swenson 2003) for the repair of Northbound Spans 10 and 11 of I-565 in Huntsville,

Alabama—the same spans considered for the design example in this appendix. The

repair was designed to resist tension forces that were predicted with strut-and-tie models.

The reinforcement system was also designed in accordance with the effective debonding

strain (εfe) specifications of ACI 440.2R-02, which have since been updated in

ACI 440.2R-08 to reflect the findings of more recent research. The FRP reinforcement

system was installed in December 2007.

The installed FRP reinforcement consists of 4 layers of FRP, with the longest layer

extending 130 in. from the face of the continuity diaphragm. The FRP reinforcement

design presented in this appendix—for the repair of the same girders using the same FRP

reinforcement product—recommends an FRP reinforcement system consisting of 5 layers

of FRP, with the longest layer extending 137 in. from the face of the continuity

diaphragm.

The updated limiting effective debonding strain (εfe < 0.004 in./in.) of ACI 440.2R-08

is the primary reason for recommending 5 layers of reinforcement instead of the

701

previously recommended 4 layers. The longer recommended length of FRP

reinforcement is due in part to the recommendation that the FRP be extended one

prestressed strand development length (d) beyond the primary region of debonded

strands as well as beyond the previously recommended (Swenson 2003) assumed

location of primary cracking. The updated design also recommends a simplified and

appropriately conservative formula for the approximation of prestressed strand

development length beginning at or beyond damaged regions within a girder.

Although the FRP reinforcement systems that were installed on Spans 10 and 11 in

December 2007 do not satisfy the updated design recommendation, installation of an

additional layer of reinforcement may not be absolutely necessary. The limiting effective

debonding strain (εfe < 0.004 in./in.) controls the recommendation of 5 layers of

reinforcement instead of 4 layers. The current installation of 4 layers satisfies strength

requirements at the interior face of the bearing pad, but the net tension strain at the

termination of the continuity reinforcement in response to factored AASHTO LRFD

strength-limit-state shear demand is calculated to be 0.00418 in./in., which exceeds the

limiting effective debonding strain of 0.004 in./in. by less than 5 percent. At sections like

this one that are near a simple support—where there is minimal positive bending

moment—the net tension strain determined in accordance with AASHTO LRFD

specifications is a linear function of the factored shear demand. Therefore, the net

tension strain exceeding the limiting effective debonding strain by 0.00018 in./in.

represents a strength deficiency of less than 5 percent in response to factored shear

demand at the termination of the continuity reinforcement.

702

The length of FRP reinforcement has been conservatively estimated by the design

recommendation presented by Swenson (2003) and the slightly modified design

recommendation presented in this thesis. It is appropriate to assume that the prestressed

strands have slipped, but it is conservative to assume that this slip has resulted in the

complete loss of effective prestress forces between the cracked section and the end of the

girder. The simplified and appropriately conservative method for determining the

required length of FRP reinforcement in accordance with the design procedure of this

thesis is recommended for the design of FRP reinforcement systems for a general range

of bridges that have experienced or are susceptible to the type of damage exhibited in the

I-565 structures. Based on the cracking observed thus far in the life of this particular

structure, it is appropriate to assume that the lengths of FRP reinforcement currently

installed on the girders of Northbound Spans 10 and 11 are acceptable.

The installed 4 layers of reinforcement nearly satisfy the requirements of the updated

design recommendations of this thesis. The small computed strength deficiency is based

on full strength-limit-state AASHTO LRFD design loads for new construction in

conjunction with the conservative limiting effective debonding strain of the FRP

reinforcement. The length of FRP reinforcement currently installed allows for adequate

development of prestressed strands beyond the primary crack locations in these particular

spans. It is unknown if an additionally installed fifth layer of reinforcement would

perform as expected when bonded to previously installed FRP reinforcement that has

been fully cured. Surface preparation procedures required for proper installation of

additional FRP reinforcement may also be detrimental to the integrity of the existing FRP

reinforcement. Whether or not the computed strength discrepancy justifies the cost,

703

effort, and uncertainty associated with installation of an additional layer of FRP in

Spans 10 and 11 is a decision best left to the discretion of ALDOT after consideration of

these factors in light of the department’s established maintenance philosophy. On the

other hand, FRP reinforcement configurations for new repairs should be designed to

satisfy the design recommendations proposed within this thesis.

N.10 118BVARYING MODULUS OF ELASTICITY FOR FRP REINFORCEMENT

The design effective debonding strain in areas of short bonded lengths is very dependent

upon the modulus of elasticity (Ef) of the FRP reinforcement product. For design

purposes, it is recommended to assume the design modulus of elasticity of the FRP

reinforcement product reported by the manufacturer; however testing of representative

samples may indicate that the installed product exhibits more tensile stiffness than

originally assumed during design.

An increased modulus of elasticity may affect the effective debonding strain for

locations with limited bonded length. Increasing the modulus of elasticity decreases the

reinforcement debonding strain and increases the required development length. Both of

these factors independently decrease the limiting effective debonding strain of the

reinforcement system.

To better understand the ramifications of this issue, laboratory testing is

recommended to assess the effective debonding strain for FRP reinforcement products

with varying modulus of elasticity values determined in accordance with procedures

(ASTM D3039 2008) recommended for testing representative samples of installed FRP

reinforcement systems.