CALIBRATING WEIGH SCALES USING DROP TEST
Checks or calibrations with check weights cannot reproduce the actual circumstances to perfection.
Highly accurate weighing results can be achieved only by various measurements with material and
subsequent correction.
1. Note down the Feed rate (I tph) say its MA,
2. Collect material over 1 meter of Belt ( say X kg),
3. Note down time taken for 1 meter of Belt (say T sec),
4. Note down Old value of Parameter D 02 (Old)
5. Calculate Actual federate as MW = (X * 3.6)/ T.
Example:
Suppose in INTECONT its reading as MA = 5 tph and MW = 4.9 tph is calculated feed rate by means of drop test.
Also suppose D02 ( Old)= 1. Then
Enter computed value into Parameter D 02.
STEPS TO ACCESS PARAMETER DO2
Call Function Distributor
Scroll Programming function into lower display field and acknowledge
Select ENTER PAR. Function
Enter password 07734
-
Display shows title of first parameter block
Move through blocks A,B, up and down. Block letter flashes.
Select block. Parameter selected last is displayed.
Move through parameter numbers within a block.
Prepare input
Selection parameters: Value flashes. Scroll desired value into lower display field.
For left-right
Numeric values
Acknowledge input.