Page 2: Bid Publication Date: 2 / 4 / 2021

EXTG ASU-1 EXTG ASU-2

EXTG ASU-3 EXTG ASU-4

EXTG AHU-1

EXTG AHU-2

EXTG AHU-3

EXTG AHU-4

M

EXTG GAS METER

EXTG 3" GAS

EXTG 2" GAS

EXTGCU-1

EXTGCU-2

EXTGCU-3

EXTGCU-4

MD-1 MD-1

MD-1MD-1

MD-3

MD-4

MD-3

MD-3

MD-3

MD-4

MD-4

MD-4

SPECIAL NOTICE TO CONTRACTORS

1. IT IS RECOMMENDED THAT ALL CONTRACTORS BIDDING THIS PROJECT VISIT THE JOB SITEAND VERIFY THE EXISTING CONDITIONS PRIOR TO SUBMITTING THEIR BID. CONTRACTORSARE TO CAREFULLY REVIEW ALL CONSTRUCTION DOCUMENTS AND NOTE ANYDISCREPANCIES BETWEEN THE CONSTRUCTION DOCUMENTS AND THE CONDITIONSOBSERVED AT THE JOB SITE PRIOR TO SUBMISSION OF ANY BID. THE BUILDING OWNERREPRESENTATIVE MAY BE CONTACTED FOR ACCESS TO THE JOB SITE.

2. PRIOR TO CONSTRUCTION, CONTRACTORS ARE RESPONSIBLE FOR VERIFYING THELOCATION AND CONDITION OF THE FOLLOWING:

A. ALL POINTS OF CONNECTION TO BUILDING UTILITIES AND/OR SYSTEMS INCLUDING, BUTNOT LIMITED TO, GAS, WATER, SEWER, VENT, ELECTRICAL, MECHANICAL SYSTEMS,DUCTWORK, EXHAUST/OUTSIDE AIR, SECURITY, FIRE/LIFE SAFETY, DATA, AND PHONE.

B. ALL REQUIRED CONNECTIONS TO THE BUILDING STRUCTURE.

C. ALL REQUIRED BUILDING PENETRATIONS.

3. ANY DISCREPANCIES BETWEEN THE CONSTRUCTION DOCUMENTS AND THE CONDITIONSOBSERVED SHALL BE BROUGHT TO THE ATTENTION, IN WRITING, TO THE ARCHITECT AND/ORENGINEER PRIOR TO PROCEEDING WITH CONSTRUCTION.

4. REFER TO THE CONSTRUCTION DOCUMENTS FOR ALL CONTACT INFORMATION.

MECHANICAL DEMOLITION NOTES

1. EQUIPMENT, PIPING, DUCTWORK, ETC., TAGGED WITH A PRECEDING "EXTG", "EX." OR "x" AREEXISTING.

2. BEFORE COMMENCING WORK ENSURE GAS IS OFF, AND ELECTRICAL POWER IS TURNED OFFTO THE EXISTING EQUIPMENT.

3. THE MECHANICAL CONTRACTOR SHALL REMOVE ALL ITEMS INDICATED AND SHALL BERESPONSIBLE FOR THEIR DISPOSAL PER LOCAL, STATE AND FEDERAL REGULATIONS ANDPAY FOR ALL ASSOCIATED COSTS OF DISPOSAL.

4. THE MECHANICAL CONTRACTOR SHALL COORDINATE WITH THE OWNER'S REPRESENTATIVETO DETERMINE IF ANY PARTS OR EQUIPMENT ARE DESIRED TO BE KEPT BY THE OWNER. THEOWNER SHALL HAVE THE RIGHT OF FIRST REFUSAL. ANY ITEM NOT WISHED TO BE RETAINED,SHALL BE DISPOSED OF AT THE RESPONSIBILITY OF THE MECHANICAL CONTRACTOR.

5. ITEMS HATCHED SHALL BE PERMANENTLY REMOVED.

6. ITEMS CLOUDED SHALL BE TEMPORARILY REMOVED AND REUSED.

REMOVE EXISTING AIR SUPPLY UNITS (ASU'S), OUTDOOR AIR, SUPPLY AIR, RETURN AIRDUCTWORK AND FRAME. PREPARE TO TIE IN NEW ROOF TOP UNIT (RTU) AND COORDINATENEW TAPERED RTU CURBS AND CONCENTRIC DIFFUSER WITH EXISTING ASUPENETRATIONS.

REMOVE EXISTING GAS LINES LEADING TO EXISTING AHU'S AND PREPARE TO REUSE GASPIPING. INSTALL NEW GAS PIPING WHERE NEEDED FOR NEW RTU'S.

REMOVE EXISTING AIR HANDLING UNITS (AHU'S).

REMOVE EXISTING CONDENSING UNITS (CU'S).

MD-1

MD-2

DEMOLITION KEYED NOTES

ALTERNATE #1

1. EXISTING EQUIPMENT AIR HANDLING UNITS (AHU'S): EXISTING AHU'S TO REMAIN IN PLACE.COORDINATE WITH OWNER.

2. EXISTING EQUIPMENT CONDENSING UNITS (CU'S): EXISTING CU'S TO REMAIN IN PLACE.COORDINATE WITH OWNER.

MD-X

MD-3

MD-4

NOTE:LOCATE FOUR (4) NEW RTU'SDIRECTLY ABOVE EXTG UNITSTHAT ARE GOING TO BE REMOVED.

ENGR. PROJ.#

MD1

ET

20071

MEC

HAN

ICAL

DEM

OLI

TIO

NFL

OO

R P

LAN

DRAWN BY:

CHECKED BY:GLN

DATE:

SHEE

T TI

TLE:

PRO

JEC

T TI

TLE:

12-18-2020PLAN REVIEW

------------------------------------------

SHEET NUMBER

MU

LTI-P

UR

POSE

FAC

ILIT

Y

Cad

illac,

MI

Wex

ford

Cou

nty

SCALE:MECHANICAL DEMOLITION FLOOR PLAN

1/8" = 1'-0"

SCALE:KEY PLAN

NO SCALE

Page 3: Bid Publication Date: 2 / 4 / 2021

M

EXTG GAS METER

EXTG 3" GAS

EXTG 2" GAS

ROOFOPENING

76-1

/2"

81"

ROOFOPENING

76-1

/2"

81"

ROOFOPENING

76-1

/2"

81"

ROOFOPENING

76-1

/2"

81"

T

RTU-1

RTU-2

RTU-3

RTU-4

T-STATRTU-1

TT-STATRTU-3

TT-STATRTU-4

T

T-STATRTU-2

AB

C D

55"

35"

AB

C D

AB

C D

AB

C D

3.

1-1/4" GAS

1-1/4" GAS1-1/4" GAS

EXTEND 3/4" GASUP TO NEW RTU

1-1/4" GAS

4.

4.

4.

4.EXTG TRUSS (TYP.)

EXTG TRUSS (TYP.)

6'-8"

6'-8"

TRU

SS P

ANEL

PO

INT

AT T

OP

CH

OR

D(T

YP. O

F 4)

30'-8" ± (TYP. OF 4)

TRU

SS P

ANEL

PO

INT

AT T

OP

CH

OR

D(T

YP. O

F 4)

30'-8" ± (TYP. OF 4)

EXTEND 3/4" GASUP TO NEW RTU

EXTEND 3/4" GASUP TO NEW RTU

EXTEND 3/4" GASUP TO NEW RTU

ALTERNATE #2

3. ELIMINATE RTU-4 AND CAP EXISTING ROOF PENETRATION.

ALTERNATE #3

4. ADD NEEDLEPOINT IONIZATION IN EACH ROOF TOP UNIT.

OPERATING WEIGHT

2626.0 LBS

A

635.0 LB

B

515.0 LB 374.0 LB 454.0 LB

C D

CORNER WEIGHTSRTU WEIGHT*

CONCENTRICDIFFUSER WEIGHT*

388 LBS

RTU, CONCENTRICDIFFUSER, & CURB WEIGHT*

3249 LBS

ROOF CURB*

235 LBS

*ALL WEIGHTS ARE APPROXIMATE. THE ACTUALWEIGHTS ARE LISTED ON THE UNIT NAMEPLATE.

NOTE:LOCATE FOUR (4) NEW RTU'SDIRECTLY ABOVE EXTG UNITSTHAT ARE GOING TO BE REMOVED.

ENGR. PROJ.#

M1

ET

20071

MEC

HAN

ICAL

FLO

OR

PLA

N

DRAWN BY:

CHECKED BY:GLN

DATE:

SHEE

T TI

TLE:

PRO

JEC

T TI

TLE:

------------------------------------------

SHEET NUMBER

MU

LTI-P

UR

POSE

FAC

ILIT

Y

Cad

illac,

MI

Wex

ford

Cou

nty

SCALE:MECHANICAL FLOOR PLAN

1/8" = 1'-0"SCALE:KEY PLAN

NO SCALE

12-18-2020PLAN REVIEW

Page 4: Bid Publication Date: 2 / 4 / 2021

1. THE MECHANICAL CONTRACTOR SHALL SUBCONTRACT A TEST AND BALANCE CONTRACTOR TO BALANCE THE SYSTEMS DESCRIBED BELOW.2. THE BALANCING SHALL BE COMPLETED BY AN INDEPENDENT TEST AND BALANCE CONTRACTOR WHO IS NOT AN EMPLOYEE OF THE MECHANICAL

CONTRACTOR.3. PER COMPLIANCE WITH ASHRAE 90.1-2013, THE BALANCER SHALL SUBMIT AN AIR BALANCE REPORT TO THE ENGINEER AND STATE OR COUNTY

INSPECTOR.4. THE BALANCE REPORT SHALL SHOW PROOF THAT THE SYSTEM HAS BEEN BALANCED TO +/- 10% OF THE DESIGNED FLOW RATE. IT IS THE

MECHANICAL CONTRACTOR AND TEST AND BALANCER'S DUTY TO PROVIDE ACCURATE DATA, SO AREAS OF INCORRECT FLOW MAY BEDISCLOSED TO THE ENGINEER, INSPECTOR, AND OWNER.

5. ALL AIRSIDE SYSTEMS, COMPONENTS, ETC. INCLUDING SUPPLY, RETURN, OUTDOOR, AND EXHAUST AIR SYSTEMS SHALL BE BALANCED. THEBALANCER SHALL PROVIDE SHEAVES AND BELTS AS NEEDED TO PROPERLY BALANCE EQUIPMENT TO +/- 10% OF THE DESIGNED AIRFLOWS. ALLDIFFUSERS, REGISTERS, GRILLES, AND LOUVERS SHALL BE INDIVIDUALLY BALANCED AND LISTED IN THE BALANCE REPORT. ALL AIRSIDEEQUIPMENT, SUPPLY, RETURN, AND OUTDOOR AIR FLOWRATES SHALL BE LISTED IN THE BALANCE REPORT.

6. ALL HVAC MOTOR DATA INCLUDING FREQUENCY (RPM), AMP DRAW, HORSEPOWER, EXTERNAL STATIC PRESSURE, HEAD PRESSURE, ETC., SHALLBE INCLUDED IN THE BALANCE REPORT.

23 05 93

TESTING,ADJUSTING,ANDBALANCING

23 11 00

FACILITY FUELPIPING

1. GAS PIPING SHALL COMPLY WITH THE CURRENTLY ENFORCED VERSION OF THE INTERNATIONAL FUEL GAS CODE (I.F.G.C.).2. ABOVE GROUND GAS PIPING SHALL BE SCHEDULE 40, BLACK IRON WITH MALLEABLE IRON THREADED FITTINGS, SUPPORT PIPING WITH

ADJUSTABLE BAND TYPE PIPE HANGERS, EQUAL TO ITT-GRINNEL FIG. 97. INSTALL DRIP LEG WITH UNION AND VALVE AT CONNECTION TO EACHPIECE OF EQUIPMENT. GAS SHUT-OFF VALVES SHALL BE 150 PSI, NON-SHOCK WOG, BRONZE BODY, STRAIGHT CONFIGURATION, AND/OR SHALLCOMPLY WITH I.F.G.C TABLE 409.1.1 AND SHALL MEET ANSI Z21.15, CSA REQUIREMENT 3-88, ASME B16.44, ASME B16.33.

3. INSTALL AND TEST GAS PIPING IN COMPLIANCE WITH UTILITY COMPANY REGULATIONS AND THE LATEST VERSION OF THE INTERNATIONAL FUELGAS CODE, NFPA NO. 54.

23 74 00

ROOF-TOPUNITS

23 00 00

BASICMECHANICALREQUIREMENTS

1. THE MECHANICAL CONTRACTOR SHALL FURNISH AND INSTALL PACKAGED ROOF-TOP UNIT(S) AS SHOWN AND SCHEDULED. THE UNIT(S) SHALL BEINSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S SPECIFICATIONS, AND SHALL PERFORM AT THE CONDITIONS SCHEDULED.

2. THE ROOF TOP UNIT PACKAGE(S) SHALL INCLUDE:2.1. R-410A CONDENSER SECTION. SEE SCHEDULE FOR REQUIREMENTS INCLUDING

2.1.1. STAGING REQUIREMENTS2.1.2. ANTI-SHORT CYCLING TIMER (ADJ. TIMED ON AND TIMED OFF)2.1.3. LOW AMBIENT CRANK-CASE HEATER

2.2. TWO STAGE NATURAL GAS BURNER.2.3. BELT-DRIVE EVAPORATOR BLOWER2.4. 100% FULL ECONOMIZER WITH REFERENCE ENTHALPY CONTROLLER.2.5. DEMAND CONTROL VENTILATION (DCV) CONTROLLER.2.6. BAROMETRIC RELIEF DAMPER OR POWERED EXHAUST AS SCHEDULED.2.7. DIGITAL CONTROL BOARD.2.8. HINGED ACCESS DOORS.2.9. ELECTRICAL DISCONNECT (SEE ROOF TOP UNIT SCHEDULE FOR CORRECT VOLTAGE.)2.10. 115V CONVENIENCE OUTLET WITH ALL-WEATHER COVER (MAY NOT BE REQUIRED ON ALL UNITS --- SEE SCHEDULE AND DRAWINGS FOR

REQUIRED LOCATIONS.)2.11. (2) SETS OF THROW-AWAY FILTERS FOR EACH ROOF TOP UNIT.

3. THE MECHANICAL CONTRACTOR SHALL PROVIDE TWO (2) SETS OF FILTERS FOR EACH UNIT AND SHALL BE RESPONSIBLE FOR CHANGING FILTERSWITHIN TWO (2) WEEKS OF START-UP.

4. THE MECHANICAL CONTRACTOR SHALL PROVIDE A SINGLE POWER SOURCE CONNECTION DISCONNECT, AND A 15 AMP DUPLEX, WEATHERPROOFCONVENIENCE OUTLET BOX FOR EACH ROOF TOP UNIT INSTALLED.

6. MANUFACTURERS: TRANE, CARRIER, MCQUAY, YORK, AAON (NOTE THAT THESE MANUFACTURERS ARE APPROVED CONTINGENT ON MEETING THEREQUIREMENTS OF THE TOTAL RTU AND ZONE DAMPER PACKAGE INCLUDING CONTROL ACCESSORIES).

MECHANICAL SPECIFICATIONSSECTION SECTION 1. BUILDING AUTOMATION SYSTEM (BAS) SHALL BE AS INDICATED ON THE DRAWINGS AND DESCRIBED IN THESE SPECIFICATIONS. SYSTEM MUST BE

FULLY INTEGRATED AND COORDINATED WITH MECHANICAL EQUIPMENT DDC CONTROLLERS FURNISHED AND INSTALLED IN THE EQUIPMENTMANUFACTURER'S FACTORY AS SPECIFIED IN THOSE SECTIONS.

1.1. THE INTENT OF THE BAS IS TO INTEGRATE THE MECHANICAL EQUIPMENT ASSOCIATED WITH THIS PROJECT INTO ONE SYSTEM FOR GLOBALMONITORING, CONTROL, AND ALARMING.

1.2. ALL MECHANICAL EQUIPMENT THAT IS INTENDED TO BE INTEGRATED INTO THE BAS SHALL BE CONTROLLED BY CUSTOM APPLICATION ORAPPLICATION SPECIFIC CONTROLLERS THAT MEET THE INTERFACE REQUIREMENTS AS DETAILED IN THE COMMUNICATIONS SECTION OF THISSPECIFICATION.

1.3. ACCEPTABLE INSTALLERS1.3.1. TRANE1.3.2. SIEMENS

2. PROVIDE TOUCH SCREEN DISPLAY WITH MOBILE APP AND WEB UI ACCESS.3. SYSTEM COMMUNICATIONS SHALL WORK SEAMLESSLY WITH CONTROLLERS AND ROOF TOP UNITS.4. SYSTEM CONTROLLER CONFIGURATION

4.1. SYSTEM SHALL BE CAPABLE OF SETUP FROM TOUCHSCREEN INTERFACE.4.2. UNIT CONTROLLERS SHALL BE ABLE TO BE ADDRESSED BY METHODS OTHER THAN SOFTWARE IN CASES WHERE TOUCHSCREEN INTERFACE

ISSUES ARISE.

1. ALL WORK TO BE DONE AND MATERIALS FURNISHED COMPLYING WITH APPLICABLE LAWS AND REGULATIONS, INCLUDING THE 2015 MICHIGANMECHANICAL CODE (M.M.C.), ASHRAE 90.1-2013 "ENERGY STANDARDS FOR BUILDINGS EXCEPT LOW-RISE RESIDENTIAL BUILDINGS", ASHRAE62.1-2013 VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITY", 2015 INTERNATIONAL PLUMBING CODE (M.P.C.), CURRENTLY ENFORCED MICHIGANBUILDING CODE (M.B.C.), AND LOCAL, STATE, AND FEDERAL FIRE SAFETY CODES (NFPA).

2. ALL MATERIALS USED SHALL BE NEW AND UNDAMAGED.3. ALL WORK PERFORMED SHALL BE IN ACCORDANCE WITH CURRENT CONSTRUCTION INDUSTRY STANDARDS AND WORKMANSHIP.4. LABEL PIPING AND EQUIPMENT USING PROFESSIONAL MARKERS PER ASME A13.1-1996:

4.1. PROVIDE PROFESSIONAL ENGRAVED PLASTIC EQUIPMENT NAMEPLATES FOR ALL HVAC EQUIPMENT IDENTIFYING EQUIPMENT TAG ANDNUMBER. SEE PLANS FOR EQUIPMENT TAG NUMBERS (FOR EXAMPLE, B-1, P-1, AHU-1, ... ETC.)

5. FURNISH ALL ACCESS DOORS (RATED OR NON-RATED AS REQUIRED) WHERE VALVES OR EQUIPMENT ARE CONCEALED BEHIND A NON-ACCESSIBLECEILING OR WALL. FURNISH ACCESS DOORS TO GENERAL CONTRACTOR FOR INSTALLATION.

6. THE CONTRACTOR SHALL ARRANGE TO MEET AND INSTRUCT THE OWNER IN THE USE AND MAINTENANCE OF SYSTEMS AND EQUIPMENT. THISINSTRUCTION SHALL BE FOR A MINIMUM OF (4) HOURS. AN ADDITIONAL (2) HOURS OF INSTRUCTION FOR THE OWNER WILL BE GIVEN IN THEOPERATION OF THE TEMPERATURE CONTROLS BY THE INSTALLER OF THE TEMPERATURE CONTROLS.

7. ALL MANUFACTURED EQUIPMENT, ACCESSORIES AND MATERIALS SHALL BE USED AS INTENDED BY THE MANUFACTURER, IN STRICT ACCORDANCEWITH THE MANUFACTURER'S WRITTEN INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS.

8. THE CONTRACTOR SHALL PROVIDE, IN ADDITION TO ANY OTHER WARRANTIES SPECIFIED, A ONE (1) YEAR FULL LABOR AND MATERIAL WARRANTYON ALL WORKMANSHIP, MATERIAL AND EQUIPMENT FURNISHED FOR THIS PROJECT.

9. THE MECHANICAL CONTRACTOR IS RESPONSIBLE FOR LOCATING ALL OPENINGS AND REQUIRED LINTELS NEEDED FOR THE GENERALCONTRACTOR FOR THE INSTALLATION OF MECHANICAL EQUIPMENT.

10.SAWCUTS, LINTELS, HEADERS, AND STRUCTURAL MODIFICATIONS TO THE BUILDING STRUCTURE NEEDED FOR THE INSTALLATION OF MECHANICALEQUIPMENT SHALL BE APPROVED BY THE GENERAL CONTRACTOR, BEFORE INSTALLATION.

11.IN GENERAL, OPENINGS AND REQUIRED LINTELS SHALL BE PROVIDED BY THE GENERAL CONTRACTOR. THE MECHANICAL CONTRACTOR ISRESPONSIBLE FOR PROVIDING DETAILS AND TEMPLATES OF ALL OPENINGS NECESSARY FOR MECHANICAL EQUIPMENT INSTALLATION INCLUDING:HOUSING, ACCESS DOORS, INSPECTION DOORS, AND PASSAGEWAYS FOR MECHANICAL EQUIPMENT. THE MECHANICAL CONTRACTOR ISRESPONSIBLE FOR SEALING CRACKS AND FINISHING ROUGH EDGES LEFT FOLLOWING MECHANICAL INSTALLATION.

12.THE USE OF THE MECHANICAL EQUIPMENT FOR HEATING, COOLING, OR DRYING DURING CONSTRUCTION IS PROHIBITED, UNLESS APPROVED BYWRITTEN DOCUMENTATION BY THE OWNER.

13. APPROVED EQUALS: MECHANICAL EQUIPMENT MANUFACTURED BY A COMPANY OTHER THAN THAT WHICH WAS SPECIFIED IN THE SCHEDULE MAYBE SUBSTITUTED BY APPROVED SHOP DRAWINGS CONTINENT UPON MEETING THE DESIGN, APPEARANCE, AND FUNCTIONAL STANDARDSESTABLISHED BY THE ORIGINALLY SPECIFIED ITEM(S). THE MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING DIMENSIONS,CLEARANCES, ASSEMBLY, FIT, ETC. OF THE APPROVED EQUAL(S) AND THEIR AFFECT ON OTHER EQUIPMENT FIT AND OPERATION. THE MECH.CONTRACTOR IS LIABLE FOR ANY ADDED COSTS TO HIMSELF OR OTHERS CAUSED BY THE APPROVED EQUALS.

14.SUBMITTALS14.1. FURNISH SHOP DRAWINGS TO ENGINEER FOR APPROVAL PRIOR TO PLACING DELIVERY ORDERS. PROVIDE SHOP DRAWINGS OF ALL

MANUFACTURED EQUIPMENT AND MATERIALS EXCEPT PIPE, PIPE FITTINGS, AND GALVANIZED DUCTWORK.14.2. AT SUBSTANTIAL COMPLETION OF CONSTRUCTION, FURNISH AS-BUILT PLANS TO ENGINEER FOR APPROVAL. WITHIN 90 DAYS AFTER THE

DATE OF SYSTEM ACCEPTANCE, APPROVED AS-BUILT PLANS SHALL BE PROVIDED TO THE BUILDING OWNER. RECORD DRAWINGS SHALLINCLUDE, AS A MINIMUM, THE LOCATION AND PERFORMANCE DATA ON EACH PIECE OF EQUIPMENT, GENERAL CONFIGURATION OF DUCTAND PIPE DISTRIBUTION SYSTEM INCLUDING SIZES, AND THE TERMINAL AIR OR WATER DESIGN FLOW RATES.

14.3. AN OPERATING MANUAL AND MAINTENANCE MANUAL SHALL BE PROVIDED TO THE BUILDING OWNER WITHIN 90 DAYS OF SYSTEMACCEPTANCE. THESE MANUALS SHALL BE IN ACCORDANCE WITH INDUSTRY-ACCEPTED STANDARDS AND SHALL INCLUDE, AT THE MINIMUM:

14.3.1. SUBMITTAL DATA STATING EQUIPMENT SIZE AND SELECTED OPTIONS FOR EACH PIECE OF EQUIPMENT REQUIRING MAINTENANCE.14.3.2. OPERATION AND MAINTENANCE MANUALS FOR EACH PIECE OF EQUIPMENT REQUIRING MAINTENANCE. REQUIRED ROUTINE

MAINTENANCE ACTIONS SHALL BE CLEARLY IDENTIFIED.14.3.3. NAMES AND ADDRESSES OF AT LEAST ONE SERVICE AGENCY.14.3.4. HVAC CONTROLS SYSTEM MAINTENANCE AND CALIBRATION INFORMATION, INCLUDING WIRING DIAGRAMS, SCHEMATICS, AND CONTROL

SEQUENCE DESCRIPTIONS. DESIRED OR FIELD-DETERMINED SET POINTS SHALL BE PERMANENTLY RECORDED ON CONTROL DRAWINGSAT CONTROL DEVICES OR IN PROGRAMMING COMMENTS.

23 09 00

INSTRUMENTA-TION ANDCONTROL FORHVAC

NOTES:

1. DO NOT INSTALL FACTORY SUPPLIED DUCT SUPPORTS,UNLESS NOTED IN ASSEMBLY INSTRUCTIONS.

2. INSTALL CONCENTRIC DUCTWORK BEFORE SETTING A/CUNIT IN PLACE.

3. PLACE GASKET ON ALL SURFACES OF DUCT FLANGE ANDCURB.

4. ALIGN TRANE UNIT SUPPLY OPENING TO MATCH SUPPLYOPENING OF CONCENTRIC DUCT KIT.

5. FIELD BAFFLES MAY BE REQUIRED FOR BALANCING.6. FOR INSTALLATION SEE ASSEMBLY INSTRUCTIONS.

Scale: None

CONCENTRIC DIFFUSER DETAIL

DUCT SUPPORTSUPPLIED WITH CURB

INSULATED PANELSSUPPLIED WITH CURB

DO NOT INSTALL

ACCESSORY ROOF CURB

TRANSITION CURBMAKE TRANSITION PRIOR TOPENETRATION THROUGH ROOF

DROP TYPECONCENTRIC DIFFUSER

ENGR. PROJ.#

M2

ET

20071

MEC

HAN

ICAL

SC

HED

ULE

SD

ETAI

LS &

SPE

CIF

ICAT

ION

S

DRAWN BY:

CHECKED BY:GLN

DATE:

SHEE

T TI

TLE:

PRO

JEC

T TI

TLE:

------------------------------------------

SHEET NUMBER

MU

LTI-P

UR

POSE

FAC

ILIT

Y

Cad

illac,

MI

Wex

ford

Cou

nty

12-18-2020PLAN REVIEW

Page 5: Bid Publication Date: 2 / 4 / 2021

ENGR. PROJ.#20071

STR

UC

TUR

AL D

ETAI

LS

DRAWN BY:

CHECKED BY:

DATE:

SHEE

T TI

TLE:

PRO

JEC

T TI

TLE:

------------------------------------------

SHEET NUMBER

MU

LTI-P

UR

POSE

FAC

ILIT

Y

Cad

illac,

MI

Wex

ford

Cou

nty

12-18-2020PLAN REVIEW

12/18/20

Page 6: Bid Publication Date: 2 / 4 / 2021

ENGR. PROJ.#

E0

BSR

20071

ELEC

TRIC

ALSC

HED

ULE

S &

DET

AILS

DRAWN BY:

CHECKED BY:JAV

DATE:

SHEE

T TI

TLE:

PRO

JEC

T TI

TLE:

12-18-2020PLAN REVIEW

------------------------------------------

SHEET NUMBER

MU

LTI-P

UR

POSE

FAC

ILIT

Y

Cad

illac,

MI

Wex

ford

Cou

nty

ABBREVIATIONS

C/B, CB

C

EC

EF

A

DWG

EWC

GFI

GEC

AMPERES

CIRCUIT BREAKER

CONDUIT

ELECTRICAL CONTRACTOR

EXHAUST FAN

DRAWING

COOLERELECTRIC WATER

CIRCUIT INTERRUPTERGROUND FAULT

CONDUCTORGROUNDING ELECTRODE

EGC CONDUCTOREQUIPMENT GROUNDING

AFF ABOVE FINISH FLOOR

AFG ABOVE FINISH GRADE

AC ABOVE COUNTER

KCMIL THOUSAND CIRCULAR MILS

KVA KILOVOLT-AMPERES

KW KILOWATTS

MC MECHANICAL CONTRACTOR

MCB MAIN CIRCUIT BREAKER

MDP MAIN DISTRIBUTION PANEL

MLO MAIN LUG ONLY

NTS NOT TO SCALE

RGS RIGID GALVANIZED STEEL

TVSS SUPPRESSIONTRANSIENT VOLTAGE SURGE

UON UNLESS OTHERWISE NOTED

V VOLT

VFD VARIABLE FREQUENCY DRIVE

W WIRE

WP WEATHERPROOF

XFMR TRANSFORMER

WG WIREGUARD

NL NIGHT LIGHT

P PUMP

PNL PANEL

PS PRIMARY SWITCH

PT PRIMARY TRANSFORMER

ERV VENTILATORENERGY RECOVERY

EWH HEATERELECTRIC WATER

G GROUND

EMT ELECTRICAL METALLIC TUBING

PVC POLYVINYL CHLORIDE

1-21 PANEL 1, CIRCUIT 21

ETR EXISTING TO REMAIN

E-R EXISTING TO BE RELOCATED

E EXISTING TO REMAIN

TR TAMPER RESISTANT

BC BELOW COUNTER

UGRD or U/G UNDERGROUND

DF DEAD FRONT

DEVICE ON REAR SIDE OF COVER

OTHER THAN POWER ORLIGHTING CKT.'S LABELCOVERS INDICATINGSYSTEM TYPE AND ZONES.

JUNCTION BOXES (EXPOSEDOR CONCEALED ABOVE

FOR J.B.'S CONTAINING

ACCESSIBLE CEILING)

PLATE. USE PERMANANT MARKER PEN, BRADY MARKING SYSTEM OR OTHERMETHOD APPROVED BY THE ENGINEER

CKT.SLP4-13,15,17

"P.A. ZONES 4,5,&6""DATA CIRCUITS A&B""EXIT SIGNS-EMI&2""EMERG. CKTS. BPEM1-3,4"

"FIRE ALARM-ZONES 2&3"

LABEL EXAMPLES:

LABEL COVERS WITH CKT.'S

-----------

OTHER APPROVED METHOD.

SWITCH PLATESTANDARD TOGGLE

REAR SIDE

LABEL CKT. NO. OF EACH

DUPLEX RECEPTACLE

ELECTRICAL IDENTIFICATION

N-2

FRONT

OF PLATE

FRONT

PLATE

N-5

OF PLATEREAR SIDE

PERMANANT MARKER PEN ORCONTAINED WITHIN. USE

WIRE SIZE REQUIREMENTS

WIRES FOR RUNS OVER 100'-0" SHALL BE DETERMINED ON THIS

LENGTH OF RUN - FROM PANEL TO FIRST CONNECTION - FEET

NOTE:BASED ON A MAXIMUM OF 3.6-VOLT DROP (3%) ON 120V CIRCUITS.

15

20

30

#12

#12

#10

#12

#10

#10

CIRCUIT AMPS

AMPS

BRANCH

50' 60'

#10

#10

#8

#12

#10

#8

#10

#10

#8

#8

#6

#10 #10

#8

#6

90'

A MAXIMUM OF A 3% DROP ALLOWED.

70' 80' 100' 110'

#10

#8

#6

#8

#8

#6

120' 130'

EGC CONDUCTOREQUIPMENT GROUNDING SM SURFACE MOUNT

CM CEILING MOUNT

NIC NOT IN CONTRACTNEW BRANCH CIRCUIT ELECTRICAL PANEL

REFER TO SHOP DRAWINGS FOR CONNECTION REQUIREMENTS1Ø SPECIAL CONNECTION, AS NOTED

DESCRIPTIONSYMBOL NOTES

REFER TO SPECIFICATIONS AND RISER DIAGRAM ON SHEET E2 FOR DETAILS

ELECTRICAL SYMBOL LEGEND

ELECTRICAL SPECIFICATIONSSECTION

260000

BASICELECTRICALREQUIREMENTS

1. PRIOR TO SUBMITTING A PROPOSAL, BIDDER SHALL HAVE VISITED THECONSTRUCTION SITE. HE/SHE SHALL BE FAMILIAR WITH THE EXISTINGCONDITIONS UNDER WHICH HE/SHE WILL HAVE TO OPERATE AND WHICH WILLIN ANY WAY AFFECT THE WORK UNDER THIS CONTRACT. NO SUBSEQUENTALLOWANCE WILL BE MADE IN THIS CONNECTION ON BEHALF OF THECONTRACTOR FOR ANY ERROR OR NEGLIGENCE ON HIS PART.

2. ELECTRICAL WORK SHALL COMPLY WITH THE LATEST ENFORCEABLE EDITIONOF THE N.E.C., LOCAL AND STATE CODES, ORDINANCES, REGULATIONS,INCLUDING THE OCCUPATIONAL SAFETY AND HEALTH ACT (OSHA), AND ADAGUIDELINES WITH THE LOCAL CODE AUTHORITIES HAVING JURISDICTION.

3. ELECTRICAL CONTRACTOR SHALL OBTAIN ALL PERMITS, PAY ALL FEES, ANDARRANGE FOR ALL INSPECTIONS FOR HIS/HER WORK. AT THE COMPLETIONOF ELECTRICAL WORK, THE ELECTRICAL CONTRACTOR SHALL FURNISH THEOWNER WITH ALL CERTIFICATES OF FINAL INSPECTION AND APPROVALS.

4. THE CONTRACTOR SHALL EMPLOY QUALIFIED AND EXPERIENCED WORKMENFOR THIS WORK.

5. ELECTRICAL CONTRACTOR SHALL GUARANTEE ALL WORK INSTALLED UNDERHIS/HER CONTRACT TO BE FREE FROM DEFECTIVE WORKMANSHIP ANDMATERIALS FOR A PERIOD OF ONE YEAR AFTER THE ACCEPTANCE OF THEBUILDING BY THE OWNER. SHOULD DEFECTS OCCUR WITHIN THIS PERIOD,REPAIR AND/OR REPLACE DEFECTIVE ITEMS AT NO EXPENSE TO THE OWNER.

6. THE ELECTRICAL CONTRACTOR SHALL PROVIDE A MINIMUM OF ONE (1) HOUROF TRAINING AS NECESSARY TO THE OWNER ON THE ELECTRICAL EQUIPMENTAND/OR DEVICES.

7. THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL OPERATING ANDMAINTENANCE INSTRUCTION MANUALS, CERTIFICATES OF INSPECTION, TESTREPORTS, SPARE PARTS, AND RECORD DRAWINGS (AS-BUILTS) TO THEOWNER PRIOR TO CLOSEOUT. FINAL PAYMENT WILL ONLY BE MADE AFTERTHE FINAL PUNCH LIST COMPLETION AND RECEIPT OF THE ABOVE CLOSEOUTDOCUMENTATION.

8. ELECTRICAL CONTRACTOR SHALL COORDINATE LOCATIONS OF HISEQUIPMENT AND WORK WITH OTHER BUILDING TRADES TO AVOID ANYINTERFERENCES BETWEEN HIS WORK AND THE WORK OF OTHER BUILDINGTRADES. IF ANY DISCREPANCIES OCCUR, CONSULT WITH THE ENGINEERAND/OR OWNER BEFORE CONTINUING.

9. THE CONTRACTOR SHALL BE HELD FULLY RESPONSIBLE FOR THE PROPERRESTORATION OF ALL EXISTING SURFACES REQUIRING PATCHING,PLASTERING, PAINTING AND/OR REPAIR DUE TO THE INSTALLATION OFELECTRICAL WORK UNDER THE TERMS OF THIS SPECIFICATION. CLOSE ALLOPENINGS, REPAIR ALL SURFACES, ETC. AS REQUIRED.

10. CUTTING AND/OR PATCHING THAT MAY BE REQUIRED FOR THE INSTALLATIONOF THE ELECTRICAL SYSTEM(S) SHALL BE DONE AND/OR REPAIRED BY THEELECTRICAL CONTRACTOR. NO CUTTING OF THE BUILDING STRUCTURALSYSTEM SHALL BE DONE WITHOUT THE WRITTEN CONSENT OF THEOWNER/ENGINEER.

11. CERTAIN REMODELING OF ELECTRICAL FACILITIES WILL BE REQUIRED IN THEEXISTING BUILDING. EXISTING CONDUIT RUNS ARE GENERALLY NOT SHOWNALTHOUGH AN ATTEMPT HAS BEEN MADE TO SHOW SOME EXISTINGCONDITIONS FOR WHICH THE INFORMATION HAS BEEN TAKEN FROM FIELDOBSERVATIONS OF THIS PROJECT. THE DRAWINGS SHOWING LOCATIONS OFEXISTING EQUIPMENT, OUTLETS, FIXTURES, ETC., IN EXISTING AREAS AREAPPROXIMATE ONLY (FIELD VERIFY). VERIFY ALL EXISTING LOADS AND WIRING- NOTIFY THE ARCHITECT/ENGINEER IF EXISTING CONDITIONS ARE FOUNDTHAT VIOLATE INSTALLATION OR SAFETY CODES.

12.BRANCH CIRCUITS SHALL BE REUSED WHERE PRACTICAL AND SHALL, INADDITION, BE REMODELED AS REQUIRED.

13.EXISTING ELECTRICAL WIRING WHICH WILL NOT BE MADE OBSOLETE ANDWHICH WILL BE DISTURBED DUE TO CONSTRUCTION CHANGES REQUIRED BYTHIS CONTRACT SHALL BE RESTORED TO OPERATING CONDITION ASREQUIRED AND/OR DIRECTED. WHERE REQUIRED, SHOWN AND/OR DIRECTED,OUTLETS AND CONDUIT RUNS SHALL BE RELOCATED. IN SOME CASES IT MAYBE NECESSARY TO EXTEND CONDUITS AND PULL IN NEW WIRING, INSTALLJUNCTION BOXES AND SPLICE IN NEW WIRING, OR REPLACE OLD WIRING WITHNEW.

14. OUTLETS FROM WHICH FIXTURES, SWITCHES, RECEPTACLES, AND/OR OTHERELECTRICAL DEVICES ARE MOVED AND WHICH ARE NOT REPLACED ORREUSED SHALL BE REMOVED OR, IF IT IS NOT POSSIBLE TO REMOVE, HAVE ABLANK COVER PLACED ON THE OUTLET BOX. WHERE OUTLETS, BOXES, ETC.ARE COMPLETELY REMOVED, THE CONTRACTOR SHALL CUT OFF AND CAPCONDUITS AND REMOVE WIRING.

15. WHERE EXISTING CONDUIT IS TO BE ABANDONED, THE CONDUIT SHALL BEREMOVED IF IT IS EXPOSED, IN A CRAWL SPACE OR IN AN ACCESSIBLECEILING. WHERE IT IS IMPOSSIBLE TO REMOVE THE CONDUIT, IT SHALL BE CUTOFF AND CAPPED OR PLUGGED.

16. WHERE EXISTING WIRE, CONDUIT AND OUTLET BOXES ARE NO LONGER USED,REMOVE WIRE BACK TO THE POWER SOURCE AND PROVIDE BLANK COVER ONOUTLET BOX. EXPOSED CONDUIT NOT REUSED SHALL BE REMOVED.THECONTRACTOR SHALL BE HELD FULLY RESPONSIBLE FOR THE PROPERRESTORATION OF ALL EXISTING SURFACES REQUIRING PATCHING,PLASTERING, PAINTING AND/OR REPAIR DUE TO THE INSTALLATION OFELECTRICAL WORK UNDER THE TERMS OF THIS SPECIFICATION. CLOSE ALLOPENINGS, REPAIR ALL SURFACES, ETC. AS REQUIRED.

17. THE ELECTRICAL CONTRACTOR SHALL PERIODICALLY REMOVE FROM THE SITEALL DEBRIS AND RUBBISH ACCUMULATING AS A RESULT OF THE ELECTRICALINSTALLATION. UPON COMPLETION OF THE PROJECT, HE/SHE SHALL DISPOSEOF ALL DEBRIS AND RUBBISH AND SHALL LEAVE ALL AREAS CLEAN. THEINTERIORS OF ALL CABINETS, PULL BOXES, AND EQUIPMENT ENCLOSURESSHALL BE FREE OF ANY DEBRIS.

18. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS AND SHALLWORK WITH EXISTING SYSTEMS IN AN "AS FOUND" CONDITION.

19.DRAWINGS ARE DIAGRAMMATIC ONLY AND SHOW OBSERVATIONS FROMCASUAL FIELD INVESTIGATIONS AND EXISTING DRAWINGS. FIELD VERIFY ALLEXISTING CONDITIONS, DIMENSIONS AND MOUNTING LOCATIONS. NOTIFYENGINEER IF ANY DISCREPANCIES ARE FOUND THAT AFFECT THE WORK TO BEPERFORMED, PRIOR TO PROCEEDING.

20.ELECTRICAL JOINTS WILL BE PERMITTED ONLY IN JUNCTION AND OUTLETBOXES. ALL JOINTS SHALL BE FIRMLY BONDED TOGETHER AND TAPED ORSHALL BE MADE WITH MECHANICAL CONNECTORS.

21.WITHIN THIRTY (30) DAYS AFTER THE ELECTRICAL CONTRACTOR HAS BEENNOTIFIED TO PROCEED WITH THE WORK, THEY SHALL SUBMIT TO THE OWNEREIGHT (8) PRINTED AND BOUND COPIES -OR- ONE (1) ELECTRONIC COPY IN PDFFORMAT OF EACH OF THE FOLLOWING DRAWINGS AND DATA SHEETS FORREVIEW. ALL EQUIPMENT FOR WHICH SHOP DRAWINGS ARE BEINGSUBMITTED SHALL NOT BE ORDERED UNTIL APPROVED DRAWINGS HAVE BEENRETURNED. SUCH SUBMITTALS SHALL INCLUDE:

* ELECTRICAL DISTRIBUTION EQUIPMENT, INCLUDING PANELBOARDS &CIRCUIT BREAKERS

22.ELECTRICAL MATERIALS SHALL BE NEW, AND BEAR THE "UL" LABEL ORLISTING.

23.BRANCH CIRCUIT WIRE SHALL BE COPPER, RATED 75°C, MINIMUM SIZE #12AWG, AND BE:(1. TYPE 'MC', 'AC' CABLE (10 FT. MAXIMUM UNLESS OTHERWISE NOTED OR

APPROVED BY THE ARCHITECT/ENGINEER/OWNER) WHERE INSTALLED INCONCEALED LOCATIONS, OR

(2. TYPE 'NM', 'NM-B', 'NM-C' OR 'NM-S' WHERE PERMITTED BY CODE ANDINSTALLED IN CONCEALED LOCATIONS ONLY, OR

(3. TYPE "THHN", "THWN" OR "THWN-2" AND INSTALLED IN CONDUIT (EMT, FORINDOOR USE; SCHEDULE 40 PVC OR SCHEDULE 80 PVC, WHERE SUBJECTTO DAMAGE, FOR INDOOR WET LOCATIONS, AND SCHEDULE 40 PVC ORRMC FOR OUTDOOR USE, MINIMUM SIZE 1/2", OR

(4. UNLESS OTHERWISE NOTED OR REQUIRED BY CODE. EXPOSED INTERIORMOTOR CONNECTIONS SHALL BE TYPE "MC" OR "AC" CABLE OR LIQUIDTITE FLEXIBLE CONDUIT (ALL WITH A 6FT. MAXIMUM LENGTH).

(5. ALL WIRE AND CABLE SHALL BE NEW AND SHALL BE DELIVERED TOPROJECT IN UNBROKEN AND UNDAMAGED CARTONS AND/OR REELS. ALLNEW BRANCH WIRING SHALL BE COLOR CODED BY THE FOLLOWINGVOLTAGE SYSTEMS AND LABELED AT THEIR SOURCE PER 2017 NECSECTION #210.5:

(6. 120/240V-1Ø-3W : 120/208V-3Ø-4W: 277/480V-3Ø-4W :ØA - BLACK ØA - BLACK ØA - ORANGEØB - RED ØB - RED ØB - BROWNNEUTRAL - WHITE ØC - BLUE ØC - YELLOWGROUND-GREEN NEUTRAL - WHITE NEUTRAL - WHITE

GROUND-GREEN GROUND-GREEN

24.ALL CONDUIT AND JUNCTION BOXES SHALL BE APPROPRIATELY MARKED WITHTHE CIRCUITS THEY CONTAIN AND A DESIGNATION THAT IT IS CONTAININGELECTRICAL CONDUCTORS.

25.UNDERGROUND CONDUIT TO BE SCHEDULE 40 PVC OR SCHEDULE 80 PVCWHERE SUBJECT TO PHYSICAL DAMAGE.

26.FUSES SHALL BE "UL" LISTED, DUAL-ELEMENT AS MANUFACTURED BY BUSSMANCO., OR APPROVED EQUAL (200,000 AIC).

27.FIRE CAULKING REQUIRED WHERE ANY PENETRATIONS ARE MADE THROUGHFIRE RATED WALLS, BY. E.C.

28.PROVIDE AN UPDATED, AND ACCURATE PANEL SCHEDULE FOR THE EXISTINGELECTRICAL PANEL(S) THAT ARE AFFECTED BY THE WORK IN THIS PROJECT.DOCUMENT ALL CHANGES ON FINAL AS-BUILT DRAWINGS AS REQUIRED. VERIFYALL EXISTING LOADS AND WIRING - NOTIFY THE ARCHITECT/ENGINEER IFEXISTING CONDITIONS ARE FOUND THAT VIOLATE INSTALLATION OR SAFETYCODES.

29. ALL NEW EQUIPMENT (PANELS, DISCONNECTS, COMBINATIONSTARTER/DISCONNECTS, VARIABLE FREQUENCY DRIVES (VFD), ETC.)IDENTIFICATION SHALL BE DONE WITH ENGRAVED 2-PLY LAMACOID PLATESWITH 14" WHITE LETTERING ON A BLACK BACKGROUND. "DYMO" OR TAPEMARKERS MUST BE APPROVED BY OWNER AND/OR ENGINEER PRIOR TO USE.

30.E.C. SHALL COORDINATE WITH THE ELECTRIC UTILITY AND THE OWNER TOCOMPLETE DOCUMENTATION TO OBTAIN ALL AVAILABLE ENERGY INCENTIVECREDITS FOR THE OWNER.

1Ø DISCONNECT (SAFETY SWITCH)

EXISTING BRANCH CIRCUIT ELECTRICAL PANEL

EXISTING MAIN ELECTRICAL DISTRIBUTION PANEL

FIELD VERIFY

FIELD VERIFY

1Ø MOTOR CONNECTION

3Ø SPECIAL CONNECTION, AS NOTED REFER TO SHOP DRAWINGS FOR CONNECTION REQUIREMENTS

3Ø MOTOR CONNECTION

FIELD VERIFY

FIELD VERIFY

3Ø DISCONNECT (SAFETY SWITCH)

FIELD VERIFY

FIELD VERIFY

Page 7: Bid Publication Date: 2 / 4 / 2021

T

T

EXT'G CONDENSING UNIT NOTE:IT IS BELIEVED THAT EXISTING PANEL #B ISFEEDING THE EXISTING CONDENSING UNITSLOCATED AROUND THE PERIMETER OF THEEXISTING BUILDING. HOWEVER, THIS COULDNOT BE VERIFIED DURING THE DESIGN. E.C. TOCONFIRM THE ELECTRICAL SOURCE FOR THEEXISTING CONDENSING UNITS AND NOTIFYTHE ENGINEER PRIOR TO DEMOLISHING.

ENGR. PROJ.#

E1D

BSR

20071

ELEC

TRIC

AL E

QU

IPM

ENT

FLO

OR

PLA

N

DRAWN BY:

CHECKED BY:JAV

DATE:

SHEE

T TI

TLE:

PRO

JEC

T TI

TLE:

------------------------------------------

SHEET NUMBER

MU

LTI-P

UR

POSE

FAC

ILIT

Y

Cad

illac,

MI

Wex

ford

Cou

nty

SCALE:ELECTRICAL EQUIPMENT FLOOR PLAN

1/8" = 1'-0"SCALE:KEY PLAN

NO SCALE

ELECTRICAL DEMOLITION NOTES

1

FOR THE ELECTRICAL EQUIPMENT TO BE DISCONNECTED AND REMOVED, THE OWNER

DISCONNECT AND REMOVE ELECTRICAL DEVICE(S) WHICH WILL INTERFEREWITH THE DEMOLITION AND REMOVAL OF MECHANICAL EQUIPMENT, CONTROLS,AND PIPING AS DESCRIBED IN THE MECHANICAL DEMOLITION PLANS. REMOVEABANDONED CIRCUITRY (WIRING) AND CONDUIT BACK TO PANEL AND DISCARD.CAUTION!!! MAINTAIN EXISTING BUILDING EQUIPMENT AND SYSTEMS THAT ARETO REMAIN.

DISCONNECT AND REMOVE EXISTING ELECTRICAL CONNECTIONS TO THEEXISTING MECHANICAL AND/OR PLUMBING EQUIPMENT THAT IS TO BEREMOVED, AS INDICATED. ALL DISCONNECTS AND POWER DEVICES ARE TO BEREMOVED AND DISCARDED. REMOVE EXISTING CIRCUITRY (WIRING) ANDCONDUIT BACK TO PANEL OR SOURCE AND DISCARD. ALL UNUSED ABOVEGROUND CIRCUITRY (WIRING) AND CONDUIT ON THE EXTERIOR OF THEBUILDING SHALL BE DISCONNECTED AND REMOVED. EXISTING UNDERGROUNDCONDUIT SHALL BE CUT BELOW GRADE AND ABANDONED. ALL THRU-WALLPENETRATIONS SHALL BE FILLED WITH EXTERIOR RATED SILICONE SEALANT,COLOR TO MATCH EXISTING INTERIOR/EXTERIOR WALLS. PROVIDE BLANKCOVER PLATES FOR EMPTY GANG BOXES. COORDINATE ALL DISCONNECTIONSWITH THE MECHANICAL CONTRACTOR.

DISCONNECT AND REMOVE EXISTING ELECTRICAL PANEL #B1, AND ALLASSOCIATED BRANCH CIRCUITRY (WIRING) AND CONDUITS, AS SHOWN.DISCONNECT AND REMOVE EXISTING FEEDER FROM EXISTING PANEL #B, ANDIDENTIFY THE CIRCUIT BREAKER WHICH PREVIOUSLY FED PANEL #B1 AS ASPARE.

SHALL BE GIVEN THE OPPORTUNITY OF HAVING ANY OF IT TURNED OVER TO THEM.

1 1

1 1

1 1

1

1

1

1

1

1

3

3

2

2 2

2

2

22

2 2

2

2

2

2

12-18-2020PLAN REVIEW

Page 8: Bid Publication Date: 2 / 4 / 2021

T

NEWPANEL #G

T

RTU-1G-1,3,5

RTU RECEPT.FPB-10

RTU RECEPT.FPB-10

RTU RECEPT.FPB-10

RTU RECEPT.FPB-10

RTU-3G-7,9,11

RTU-4G-8,10,12

RTU-2G-2,4,6

ROOF TOP UNIT NOTE:ALL RTU'S WILL BE SUPPLIED WITH INTEGRALDISCONNECTS AND INTEGRAL CONVENIENCERECEPTACLES. COORDINATE CONNECTIONSREQUIREMENTS AND LOCATIONS WITH SHOPDRAWINGS.

ALTERNATE #2

ENGR. PROJ.#

E1P

BSR

20071

ELEC

TRIC

AL P

OW

ERFL

OO

R P

LAN

DRAWN BY:

CHECKED BY:JAV

DATE:

SHEE

T TI

TLE:

PRO

JEC

T TI

TLE:

------------------------------------------

SHEET NUMBER

MU

LTI-P

UR

POSE

FAC

ILIT

Y

Cad

illac,

MI

Wex

ford

Cou

nty

SCALE:ELECTRICAL POWER FLOOR PLAN

1/8" = 1'-0"SCALE:KEY PLAN

NO SCALE

GENERAL ELECTRICAL NOTES1. CAUTION!!!!!!!! .

E.C. SHALL VERIFY ALL ROUGH-IN ELEVATIONS, LOCATIONS AND/OR HEIGHTSOF ALL MECHANICAL AND POWERED EQUIPMENT WITH ARCHITECT/ENGINEER.FAILURE TO DO SO WILL REQUIRE E.C. TO RELOCATE RESPECTIVE ITEMS ATTHE E.C.'S EXPENSE.

2. THERE SHALL BE NO EXPOSED CONDUITS, EXCEPT IN MECHANICAL ROOMSAND FINISHED SPACES WITH EXPOSED CEILINGS. ALL EXPOSED CONDUITSHALL BE PAINTED TO MATCH ASSOCIATED SURFACE (WALL, CEILING, ETC.) INFINISHED SPACES.

3. THE ELECTRICAL CONTRACTOR SHALL COORDINATE WITH THE OWNER'SREPRESENTATIVE TO DETERMINE IF ANY PARTS OR EQUIPMENT ARE DESIREDTO BE KEPT BY THE OWNER. THE OWNER SHALL HAVE THE RIGHT OF FIRSTREFUSAL. ANY ITEM NOT WISHED TO BE RETAINED, SHALL BE DISPOSED OF ATTHE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR.

4. CIRCUITS SHOWN ON PLANS WITH AN * AFTER IT, INDICATE THE CIRCUITNUMBER FROM OLD DRAWINGS OR A TAKEOFF. E.C. IS TO VERIFY ACTUALCIRCUIT AND USE IT IF DIFFERENT THAN CIRCUIT INDICATED.

ALTERNATE #2 DESCRIPTIONTHE BASE BID SHALL INCLUDE THE INSTALLATION OF ALL FOUR (4) ROOF TOP UNITS,AS SHOWN ON THE FLOOR PLANS. ALTERNATE #2 IS A DEDUCT ALTERNATEWHEREIN ONLY THREE (3) OF THE ROOF TOP UNITS WILL BE INSTALLED. FOR THEDEDUCT PRICING, ELIMINATE ALL LABOR AND EQUIPMENT ASSOCIATED WITH THEINSTALLATION OF RTU-4, INCLUDING THE CIRCUIT BREAKER, CONDUIT ANDCIRCUITRY (WIRING) FROM NEW PANEL #G TO RTU-4.

12-18-2020PLAN REVIEW

Page 9: Bid Publication Date: 2 / 4 / 2021

ENGR. PROJ.#

E2

BSR

20071

ELEC

TRIC

ALSC

HED

ULE

S &

DET

AILS

DRAWN BY:

CHECKED BY:JAV

DATE:

SHEE

T TI

TLE:

PRO

JEC

T TI

TLE:

------------------------------------------

SHEET NUMBER

MU

LTI-P

UR

POSE

FAC

ILIT

Y

Cad

illac,

MI

Wex

ford

Cou

nty

PANEL #GNEW

400A277/480V-3Ø

NEW 400A/3P

T

DESCRIPTION

1197

AMP/CIR

13

NO.

5

POLES DESCRIPTION LOADLOAD

8

1210

AMP/ CIR

42

POLES NO.

620/1RECEPTS - RTU-1, RTU-2, RTU-3, RTU-4720

KEYNOTE

KEYNOTE

XX

X

XXXN

DESCRIPTION

1197

NEW PANEL #GAMP/CIR

13

NO.

5

POLES DESCRIPTION LOADLOAD

8

1210

AMP/ CIR

42

POLES NO.

6

400 AMPS M.L.O. 277/480V-3Ø-4W SQUARE D NF SURFACE PANEL

70/3

SPACESPACE

RTU-1 - ROOF ------

----

KEYNOTE

KEYNOTE

131517192123252729

141618202224262830

SPACESPACE

----

SPACESPACE

----

SPACESPACE

----

SPACESPACE

SPACESPACE

SPACESPACE

SPACESPACE

----

----

----

----

SPACE-- SPACE --

70/3 RTU-2 - ROOF

RTU-3 - ROOF

RTU-4 - ROOF (ALT#2)

70/3

70/3 A

KEYNOTES: A ELIMINATE CIRCUIT FOR RTU-4 AND REMOVE BREAKER FROM BID FOR ALTERNATE #2 N PROVIDE NEW CIRCUIT BREAKER IN EXISTING PANEL, SIZED AS INDICATED. X DESIGNATES EXISTING CIRCUIT BREAKERS WHICH ARE TO REMAIN. R RE-LABEL EXISTING CIRCUITS AS SPARES AND SWITCH BREAKERS TO THE OFF POSITION

TWO (2) PARALLEL RUNS OF:4#3/0, 1#3 E.G.C, 2-1/2"C

TOTAL CALCULATED LOAD:

(83.1 kVA

342.2 kVA

EXT'G ELECTRICAL SERVICE LOAD CALCULATIONS:AT PRIMARY SWITCH

PRIMARY SWITCH:

142.8 kVA

EXT'G PANEL #B

-- 75.7 AMPS

-- 40.0 AMPS)-- 100.0 AMPS)

EXT'G PANEL #FP: (33.2 kVA

-- 303.1 AMPSEXT'G 3Ø PEAK DEMAND*:+ 25% NEC FACTOR: 63.0 kVA

252.0 kVA

-- 179.2 AMPS

-- 418.2 AMPS

REMOVED LOADS:

* DENOTES PEAK DEMAND DATA OBTAINED OVER A 15-MINUTEPERIOD OF TIME FROM THE ELECTRIC UTILITY (CONSUMERS ENERGY)

0.7 kVA -- 0.8 AMPS

PARTIAL ELECTRICAL RISER DIAGRAMNO SCALE

DESCRIPTION

1197

AMP/CIR

13

NO.

5

POLES DESCRIPTION LOADLOAD

8

1210

AMP/ CIR

42

POLES NO.

6

KEYNOTE

KEYNOTE

131517192123252729

141618202224262830

31 3233 3435 3637 3839 4041 4243 4445 4647 4849 5051 5253 54

SPARE

SPARE

SPARE

SPARE

KEYNOTES: A ELIMINATE CIRCUIT FOR RTU-4 AND REMOVE BREAKER FROM BID FOR ALTERNATE #2 N PROVIDE NEW CIRCUIT BREAKER IN EXISTING PANEL, SIZED AS INDICATED. X DESIGNATES EXISTING CIRCUIT BREAKERS WHICH ARE TO REMAIN. R RE-LABEL EXISTING CIRCUITS AS SPARES AND SWITCH BREAKERS TO THE OFF POSITION

KEYNOTES: A ELIMINATE CIRCUIT FOR RTU-4 AND REMOVE BREAKER FROM BID FOR ALTERNATE #2 N PROVIDE NEW CIRCUIT BREAKER IN EXISTING PANEL, SIZED AS INDICATED. X DESIGNATES EXISTING CIRCUIT BREAKERS WHICH ARE TO REMAIN. R RE-LABEL EXISTING CIRCUITS AS SPARES AND SWITCH BREAKERS TO THE OFF POSITION

XXXXXXXXXXXX

X

X

R

R

XXXXXXXXXX

X

R

R

EXT'G PANEL #FP-BNEW PANEL #G:

ADDED LOADS:

M

NOTE:THE EXSTING #MDP CONTAINS FIVE (5) EXISTING SERVICEDISCONNECTS AND ONE (1) NEW SERVICE DISCONNECTFOR A TOTAL OF SIX (6) SERVICE DISCONNECTS. PER THE2017 NEC, THIS IS THE MAXIMUM ALLOWABLE NUMBER OFSERVICE DISCONNECTS. ALL ADDITIONAL SPACES INEXISTING #MDP SHALL BE LABELED AS "NOT USABLE".

NOTE:INCLUDE NEW PERMENANTIDENTIFICATION PLAQUES ATEACH OF THE ELECTRICALSERVICE DISCONNECTLOCATIONS (2 - TOTAL) PER2017 NEC SECTION #230.2(E)

NOT USABLE

NOT USABLE

12-18-2020PLAN REVIEW