NOTICE TO BIDDERS IFB 2018-09-003 Addendum 1 10/9/18 Central Texas Community Health Center d/b/a CommUnityCare SEHW Remodel and Renovation Clarification Plans and Drawings can be found on the following websites: BidSync - https://www.bidsync.com/community-care ESBD - http://esbd.cpa.state.tx.us/ Central Health - https://www.centralhealth.net/sdm_downloads/central-health-southeast-health- wellness-center-remodel-and-renovation/ Correction See Attachment A, Permit review comments correction/additional design information Questions in Black, Answers in RED 1. If we did not attend the mandatory Pre-Bid meeting, are we still able to submit a proposal? No, because of the two unique projects it was determined vendors could not give accurate construction quote without first seeing the site. 2. Is there an estimated budget/cost? See question 4 3. Is there an estimated start date for the work? Start date will be dependent on the fully executed agreement with the Awarded Vendor. We are hoping to start the project second week of November. 4. Is there an engineer’s estimate on the value of work for bonding purposes? For the bid bond of 5% the estimated construction value is $337,000

Upload: others

Post on 11-Nov-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: BidSync - ESBD ......Addendum S.E. Health & Wellness Center Renovations Addendum No. 1 Central Health Page 2 of 3 Austin, Texas Project No. 1826.01 Austin 811 Barton Springs Road,

NOTICE TO BIDDERS

IFB 2018-09-003 Addendum 1

10/9/18

Central Texas Community Health Center d/b/a CommUnityCare

SEHW Remodel and Renovation

Clarification Plans and Drawings can be found on the following websites:

BidSync - https://www.bidsync.com/community-care ESBD - http://esbd.cpa.state.tx.us/ Central Health - https://www.centralhealth.net/sdm_downloads/central-health-southeast-health-

wellness-center-remodel-and-renovation/ Correction See Attachment A, Permit review comments correction/additional design information Questions in Black, Answers in RED

1. If we did not attend the mandatory Pre-Bid meeting, are we still able to submit a proposal? No, because of the two unique projects it was determined vendors could not give accurate construction quote without first seeing the site.

2. Is there an estimated budget/cost? See question 4

3. Is there an estimated start date for the work? Start date will be dependent on the fully executed agreement with the Awarded Vendor. We are hoping to start the project second week of November.

4. Is there an engineer’s estimate on the value of work for bonding purposes? For the bid bond of 5% the estimated construction value is $337,000

Page 2: BidSync - ESBD ......Addendum S.E. Health & Wellness Center Renovations Addendum No. 1 Central Health Page 2 of 3 Austin, Texas Project No. 1826.01 Austin 811 Barton Springs Road,

AddendumS.E. Health & Wellness Center Renovations Addendum No. 1

Central Health Page 1 of 3

Austin, Texas

Project No. 1826.01

Austin 811 Barton Springs Road, Suite 900, Austin, Texas 78704 p: 512.478.7286 f: 512.478.7441

San Antonio 4040 Broadway, Suite 300, San Antonio, Texas 78209 p: 210.224.6032 f: 210.224.6453

Addendum No. 1

Date: September 28, 2018

S.E. Health & Wellness Center Renovations

Central Health

Austin, Texas

Notice To Bidders

A. This Addendum shall be considered part of the Construction Documents dated August 31, 2018, for the above-mentioned project, as though it had been issued at the same time and incorporated integrally therewith. Where provisions of the following supplementary data differ from those of the original Construction Documents, this Addendum shall govern and take precedence.

B. Bidders are hereby notified that they shall make necessary adjustments in their estimates on account of this Addendum. It will be construed that each bidder’s proposal is submitted

9/27/18

JAMIE BUCHANAN

92680

S

ST

ATEOF TEX

AL DI CE NS

E

PROF

ESSION LA

ENG

INEER

9.26.18 9/27/2018

ATTACHMENT A

Page 3: BidSync - ESBD ......Addendum S.E. Health & Wellness Center Renovations Addendum No. 1 Central Health Page 2 of 3 Austin, Texas Project No. 1826.01 Austin 811 Barton Springs Road,

Addendum

S.E. Health & Wellness Center Renovations Addendum No. 1

Central Health Page 2 of 3

Austin, Texas

Project No. 1826.01

Austin 811 Barton Springs Road, Suite 900, Austin, Texas 78704 p: 512.478.7286 f: 512.478.7441

San Antonio 4040 Broadway, Suite 300, San Antonio, Texas 78209 p: 210.224.6032 f: 210.224.6453

with full knowledge of all modifications and supplemental data specified herein. Please staple

in the back of your specification book.

SPECIFICATIONS

ITEM 1 Section 00 01 15 – DRAWING INDEX

A. REVISED and REISSUED as part of this Addendum.

DRAWINGS

GENERAL:

ITEM G1 Sheet G1.1 – DRAWING INDEX AND SYMBOLS

B. REVISED and REISSUED as part of this Addendum.

STRUCTURAL:

ITEM S1 Sheet XS-1 – TYPICAL TRENCH DETAIL FOR UNDER-SLAB PLUMBING LINES

A. NEW 11” x 17” sheet is ISSUED as part of this Addendum.

ELECTRICAL:

ITEM E1 Sheet E2.2 – LIGHTING DEMOLITION PLAN

A. REVISED and REISSUED as part of this Addendum.

ITEM E2 Sheet E3.1 – POWER & SPECIAL SYSTEMS PLAN

A. REVISED and REISSUED as part of this Addendum.

ITEM E3 Sheet E3.2 – LIGHTING PLANS

A. REVISED and REISSUED as part of this Addendum.

ITEM E4 Sheet E6.1 – ONE-LINE RISER DIAGRAM

A. NEW 30” x 42” sheet ISSUED as part of this Addendum.

ITEM E5 Sheet E7.1 – ELECTRICAL SCHEDULES & DETAILS

A. REVISED and REISSUED as part of this Addendum.

Page 4: BidSync - ESBD ......Addendum S.E. Health & Wellness Center Renovations Addendum No. 1 Central Health Page 2 of 3 Austin, Texas Project No. 1826.01 Austin 811 Barton Springs Road,

Addendum

S.E. Health & Wellness Center Renovations Addendum No. 1

Central Health Page 3 of 3

Austin, Texas

Project No. 1826.01

Austin 811 Barton Springs Road, Suite 900, Austin, Texas 78704 p: 512.478.7286 f: 512.478.7441

San Antonio 4040 Broadway, Suite 300, San Antonio, Texas 78209 p: 210.224.6032 f: 210.224.6453

ITEM E6 Sheet E7.2 – ELECTRICAL SCHEDULES

A. NEW 30” x 42” sheet ISSUED as part of this Addendum.

ITEM E7 Sheet E7.3 – ELECTRICAL SCHEDULES

A. NEW 30” x 42” sheet ISSUED as part of this Addendum.

ATTACHMENTS

The following Specification Sections are attached to this Addendum:

• Section 00 01 15 – DRAWING INDEX

The following drawings (11” x 17”) reflect revisions in the work and are attached to this Addendum:

• XS-1 – TYPICAL TRENCH DETAIL FOR UNDER-SLAB PLUMBING LINES

The following drawings (30” x 42”) reflect revisions in the work and are attached to this Addendum:

• G1.1 – DRAWING INDEX AND SYMBOLS

• E2.2 – LIGHTING DEMOLITION PLAN

• E3.1 – POWER & SPECIAL SYSTEMS PLAN

• E3.2 – LIGHTING PLANS

• E6.1 – ONE-LINE RISER DIAGRAM

• E7.1 – ELECTRICAL SCHEDULES & DETAILS

• E7.2 – ELECTRICAL SCHEDULES

• E7.3 – ELECTRICAL SCHEDULES

END OF ADDENDUM NO. 1

Page 5: BidSync - ESBD ......Addendum S.E. Health & Wellness Center Renovations Addendum No. 1 Central Health Page 2 of 3 Austin, Texas Project No. 1826.01 Austin 811 Barton Springs Road,

S.E. Health & Wellness Center Renovations Central Health Austin, Texas Project No. 1826.01

Drawing Index Section 00 01 15.1 of 1

H:\18\182601\3 Technical\Specifications\Div 00\00 01 15_Drawing Index.docx 9/27/2018 3:55 PM

SECTION 00 01 15 – DRAWING INDEX

GENERAL

SHEET G1.0 COVER SHEET

SHEET G1.1 DRAWING INDEX AND SYMBOLS SHEET G2.1 ADULT TAS ACCESSIBILITY LIFE SAFETY

SHEET LS1.1 LIFE SAFETY INFORMATION ARCHITECTURAL

SHEET A2.1 DEMOLITION PLANS

SHEET A3.1 FLOOR PLANS SHEET A7.1 PARTITION TYPES AND DETAILS SHEET A7.2 DETAILS SHEET A7.3 DOOR, FRAME TYPES, AND FINISH SCHEDULE SHEET A9.1 REFLECTED CEILING PLAN SHEET A9.2 ROOM FINISH PLAN SHEET A10.1 INTERIOR ELEVATIONS FIRE PROTECTION

SHEET FP1.1 FIRE PROTECTION NOTES, SYMBOLS AND FLOOR PLAN

PME

SHEET PME1.1 PME OVERALL PLANS

PLUMBING

SHEET P1.1 PLUMBING NOTES, SYMBOLS AND ABBREVIATIONS

SHEET P2.1 PLUMBING DEMOLITION PLANS SHEET P3.0 PLUMBING UNDERFLOOR PLANS SHEET P3.1 PLUMBING FLOOR PLANS SHEET P5.1 PLUMBING DETAILS MECHANICAL

SHEET M1.1 MECHANICAL NOTES, SYMBOLS, SCHEDULES & DETAILS

SHEET M2.1 MECHANICAL DUCTWORK DEMOLITION PLANS SHEET M3.1 MECHANICAL DUCTWORK PLANS ELECTRICAL

SHEET E1.1 ELECTRICAL NOTES, SYMBOLS AND ABBREVIATIONS

SHEET E2.1 POWER & SPECIAL SYSTEMS DEMOLITION PLANS SHEET E2.2 LIGHTING DEMOLITION PLANS SHEET E3.1 POWER & SPECIAL SYSTEMS PLANS SHEET E3.2 LIGHTING PLANS SHEET E6.1 ONE-LINE RISER DIAGRAM SHEET E7.1 ELECTRICAL SCHEDULES & DETAILS SHEET E7.2 ELECTRICAL SCEDULES SHEET E7.3 ELECTRICAL SCEDULES

END OF DRAWING INDEX

Page 6: BidSync - ESBD ......Addendum S.E. Health & Wellness Center Renovations Addendum No. 1 Central Health Page 2 of 3 Austin, Texas Project No. 1826.01 Austin 811 Barton Springs Road,

NOTES:

1. ADHESIVE ANCHORING SYSTEM SHALL BE HILTI "HIT-HY 200" OR SIMPSON "ACRYLIC-TIE". FOLLOW ALL MANUFACTURER'S INSTALLATION INSTRUCTIONS.

2. VAPOR RETARDER SHALL MEET THE FOLLOWING PROPERTIES:

a. 15 MIL MINIMUM THICKNESS b. MEET ASTM E 1745 CLASS A c. WATER VAPOR PERMEANCE PER ASTM E96 SHALL BE 0.01 OR LESS

3. LAP JOINTS IN VAPOR RETARDER 6" MIN. USE MANUFACTURER'S STANDARD ADHESIVE OR PRESSURE SENSITIVE TAPE FOR SEALING MEMBRANE AT SEAMS, PIPE

PENETRATIONS, TEARS, ETC.

4. PROVIDE 2-#4X2'-0" DIAGONAL BARS AT RE-ENTRANT CORNERS IN SAWCUT. PLACE AT MID-DEPTH OF SLAB.

5. SOIL REMOVED FOR SLAB TRENCH SHALL BE REPLACED AND RECOMPACTED TO A MINIMUM OF 95% STANDARD PROCTER DENSITY (ASTM D698).

6. PLACE SLAB BACK TO THICKNESS TO MATCH EXISTING WITH A MINIMUM 3,000 PSI NORMAL WEIGHT CONCRETE AND A RATIO OF 0.50 OR LESS.

7. THE CONTRACTOR SHALL ENSURE THAT TRENCHING FOR THE UTILITY LINE IS NOT OVER-EXCAVATED AND THAT NO PORTION OF THE SURROUNDING SLAB-ON-GRADE ISLEFT UNSUPPORTED.

8. CONTRACTOR SHALL PROVIDE A COLD JOINT EVERY 30 LINEAR FEET IN THE PORTION OF NEW CONCRETE SLAB THAT IS PLACED DUE TO UNDER-SLAB TRENCHING.

FULL SLAB DEPTHSAWCUT @ EACHFACE OF TRENCH

#4 @ 3" FROM EACHSIDE OF TRENCH AND16" O.C. MAX.

NEW CONCRETE SLAB -SEE NOTE 6

EQ

EQ

6"

3'-0" MAX.

AS REQ'D.

TYP.

3"

EXIST. SLAB-ON-GRADE

DRILL AND ANCHORDOWELS AS SHOWN@16" O.C. - SEE NOTE 1

PLUMBING LINE - SEE PLUMBING DRAWINGS FOR SIZE AND LOCATION

VAPOR RETARDERSEE NOTE 2

SEE ARCH'L FORVAPOR RETARDERREPAIR DETAIL

F.V

.

REF.

CLIENT

PROJECT

REV. DATE SHEET

9/2

6/2

018 3

:16:5

5 P

M

CENTRAL HEALTH - SE HEALTH & WELNESS CENTER RENOVATIONS

O'CONNELL ROBERTSON

09/26/18 XS-1

210 BARTON SPRINGS RD., SUITE 250512.474.4001AUSTIN, TEXAS 78704

TBPE FIRM F-12778

JQ + TSEN, LLC

JQT PROJECT NO:

TSEN

SCALE: 1 1/2" = 1'-0"1 TYPICAL TRENCH DETAIL FOR UNDER-SLAB PLUMBING LINES

JAMIE BUCHANAN

92680

S

ST

ATEOF TEX

A

L DI CENSE

PROF

ESSION LA

ENG

INEER

9.26.18

Page 7: BidSync - ESBD ......Addendum S.E. Health & Wellness Center Renovations Addendum No. 1 Central Health Page 2 of 3 Austin, Texas Project No. 1826.01 Austin 811 Barton Springs Road,

ABV ABOVE D DRAIN FRT FIRE RESISTANT TREATED M METER PSF POUNDS PER SQUARE FOOT TB TACK BOARD

ACOUS ACOUSTICAL DBL DOUBLE FT FOOT MAS MASONRY PSI POUNDS PER SQUARE INCH TOC TOP OF CURB

ADJ ADJUSTABLE DEMO DEMOLISH, DEMOLITION FURR FURRING MAX MAXIMUM PT PRESSURE TREATED TOSC TOP OF STRUCTURAL STEEL

AFF ABOVE FINISH FLOOR DEPT DEPARTMENT FWC FABRIC WALL COVERING MDF MEDIUM DENSITY FIBER BOARD TEL TELEPHONE

ALUM ALUMINUM DF DRINKING FOUNTAIN MED MEDIUM QT QUARRY TILE THK THICK

ALT ALTERNATE DIA or Ø DIAMETER GA GAUGE MEMB MEMBRANE QTB QUARRY TILE BASE TOB TOP OF BEAM

ANOD ANODIZED DIM DIMENSION GALV GALVANIZED MTL METAL TOP TOP OF PAVEMENT

APPROX APPROXIMATELY DIV DIVISION GB GRAB BAR MFGR MANUFACTURER RI RISER TOM TOP OF MASONRY

AWP ACOUSTICAL WALL PANEL DL DEAD LOAD GC GENERAL CONTRACTOR MH MANHOLE R RADIUS TOS TOP OF STEEL (BOTTOM OF ROOF DECK)

DN DOWN GCLU GLAZED CMU MIN MINIMUM RB RUBBER BASE TP TOILET PARTITION

BD BOARD DS DOWN SPOUT GI GALVANIZED IRON MISC MISCELLANEOUS RCP REFLECTED CEILING PLAN TV TELEVISION

BLDG BUILDING DSP DRY STAND PIPE GL GLASS MM MILLIMETER RD ROOF DRAIN TYP TYPICAL

BOT BOTTOM DTL DETAIL GLB GLASS BLOCK MO MASONRY OPENING REF REFERENCE TZ TERRAZZO

BW BOTH WAYS DWG DRAWING GMT GLASS MOSAIC TILE MOD MODULAR REFR REFRIGERATOR TZB TERRAZZO BASE

BM BENCH MARK GMTW GLASS MOSAIC TILE WALL MTD MOUNT(ED) (ING) REINF REINFORCING

E EAST GR GRADE MUL MULLION REQ REQUIRE(D) (ING) UC UNDERCUT

C CHANNEL EA EACH GYP GYPSUM REV REVISION UNO UNLESS OTHERWISE NOTED

CC CUBICAL CURTAIN EF EPOXY FLOOR GYP BD GYPSUM BOARD N NORTH RH RIGHT HAND USC UNDER SEPARATE CONTRACT

CK CORK EFB EPOXY FLOOR BASE NAT NATURAL RM ROOM(S)

CAB CABINET EJ EXPANSION JOINT HC HOLLOW CORE NIC NOT IN CONTRACT ROW RIGHT OF WAY VAR VARNISH

CB CHALK BOARD EG END GUARD HDR HEADER NO or # NUMBER RVWC RIGID VINYL WALL COVERING VB VAPOR BARRIER

CFCI CONTRACTOR FURNISH CONTRACTOR INSTALL EL ELEVATION HDW HARDWARE NOM NOMINAL VB VINYL BASE

CFOI CONTRACTOR FURNISH OWNER INSTALL ET EPOXY TERRAZZO FLOOR HDWD HARDWOOD NRC NOISE REDUCTION COEFFICIENT S SOUTH VCT VINYL COMPOSITION TILE

CFT CUBIC FOOT ETB EPOXY TERRAZZO BASE HGT HEIGHT NTS NOT TO SCALE SB SPLASH BLOCK VERT VERTICAL

CG CORNER GUARD ELECT ELECTRICAL HM HOLLOW METAL SC SOLID CORE VEST VESTIBULE

CL, CENTER LINE EM ENTRANCE MAT HORIZ HORIZONTAL OC ON CENTER SCHED SCHEDULE VT VINYL TILE

CLG CEILING EMER EMERGENCY HP HIGH POINT OD OUTSIDE DIAMETER SECT SECTION VTR VENT THROUGH ROOF

CI CAST IRON ENCL ENCLOSURE HR HANDRAIL OFD OVERFLOW ROOF DRAIN SHR SHOWER VWC VINYL WALL COVERING

CLO CLOSET EP EPOXY PAINT HVAC HEATING VENTILATION AIR CONDITIONING OFF OFFICE SIM SIMILAR

CLR CLEAR EQ EQUAL OFOI OWNER FURNISH OWNER INSTALL SPECS SPECIFICATION(S) W WEST

CMP CROWN MOLDING PAINTED EQUIP EQUIPMENT ID INSIDE DIAMETER OFCI OWNER FURNISH CONTRACTOR INSTALL SPK SPEAKER W/ WITH

CMS CROWN MOLDING STAINED EWC ELECTRIC WATER COOLER INCL INCLUDING OVH OVERHEAD SQ SQUARE WBP WOOD BASE PAINTED

CMT CERAMIC MOSAIC TILE EXP EXPANSION INSUL INSULATION OH OPPOSITE HAND SS STAINLESS STEEL WBS WOOD BASE STAINED

CMTB CERAMIC MOSAIC TILE BASE EXIST EXISTING INT INTERIOR OPNG OPENING ST STONE WC WATER CLOSET

CMTW CERAMIC MOSAIC TILE WALL EXT EXTERIOR IPS IRON PIPE SIZE OPP OPPOSITE STC STONE COUNTERTOP WD WOOD

CMU CONCRETE MASONRY UNIT STW STONE WALL WDS WOOD STAINED

CO CASED OPENING FA FIRE ALARM J JOIST P PAINT(ED) STB STONE BASE WIN WINDOW

COL COLUMN FBO FURNISHED BY OTHERS JAN JANITOR PARA PARALLEL STC STAINED CONCRETE W/O WITHOUT

CONC CONCRETE FD FLOOR DRAIN JT JOINT PBD PARTICLE BOARD STD STANDARD WP WOOD PANELING PREFINISHED

CONST CONSTRUCTION FE FIRE EXTINGUISHER PCF POUNDS PER CUBIC FOOT STL STEEL WPP WOOD PANELING PAINTED

CR FEC FIRE EXTINGUISHER CABINET KIT KITCHEN PERF PERFORATED STO STORAGE WPS WOOD PANELING STAINED

CORR

CHAIR RAIL

FFE FINISH FLOOR ELEVATION KO KNOCKOUT PERI PERIMETER STRUCT STRUCTURAL WS WATER STOP

CPT

CORRIDOR

FHC FIRE HOSE CABINET PFL POUNDS PER LINEAR FOOT SV SHEET VINYL WSCT WAINSCOT

CPTB

CARPET

FHVC FIRE HOSE VALVE CABINET L LENGTH/LONG PL PLATE SVB SHEET VINYL COVED BASE WT WEIGHT

CT

CARPET BASE

FE FINISHED END LAB LABORATORY PLAM PLASTIC LAMINATE SYM SYMMETRICAL WWF WELDED WIRE FABRIC

CTB

CERAMIC TILE

FLR FLOOR LAM LAMINATE PLAS PLASTER SYS SYSTEM

CTW

CERAMIC TILE BASE

FOC FACE OF CONCRETE LH LEFT HAND PLYWD PLYWOODCERAMIC TILE WALL

FOF FACE OF FINISH LI LINOLEUM PP PORCELAIN PAVERCTSK COUNTERSINK

FOM FACE OF MASONRY LIB LINOLEUM COVED BASE PPB PORCELAIN PAVER BASECYD CUBIC YARD

FOS FACE OF STUDS LIT LINOLEUM TILE PPW PORCELAIN PAVER WALL

FPRF FIREPROOFING LL LIVE LOAD PR PAIR

NEW CONSTRUCTION

EXISTING CONSTRUCTION

DEMOLITION

HIDDEN LINE

FIRE/SMOKE BARRIERS

1 HOUR FIRE BARRIER

SMOKE BARRIER

2 HOUR FIRE BARRIER

FIRE/SMOKE PARTITIONS

1 HOUR FIRE PARTITION

SMOKE PARTITION

FIRE WALLS

2 HOURS

3 HOURS

BRICK

CONCRETE

CONCRETE BLOCK

EARTH

INSULATION, BATT

INSULATION, RIGID

METAL

PLYWOOD

FINISH GRADE HARDWOOD

WOOD FRAMING THROUGH MEMBER

WOOD FRAMING INTERUPTED MEMBER

PARTITION TYPES

ROOM NUMBER

DOOR NUMBER

KEYNOTE

DEMOLITION NOTE

EQUIPMENT

WINDOW TAG

COLUMN GRID

ELEVATION HEIGHT

REVISION

ELEVATION

SECTION

NORTH ARROW

-

#

?#

?#

#

#

#

A.F.F.0'-0"

#

#

#

N

#

#

SIM

Austin

811 B

art

on S

pring

s Ro

ad

, Suite

900, A

ust

in, Te

xas

78704 p

: 512.4

78.7

286 f: 512.4

78.7

441

San Antonio

4040 B

roa

dw

ay, Suite

300, Sa

n A

nto

nio

, Te

xas

78209 p

: 2

10.2

24.6

032 f: 2

10.2

24.6

453

Revisions:

C:\R

evit P

roje

cts

2017\1

82601_17_C

entral_

Health_R

enovations_A

rch_C

entral_

plu

u.rvt

9/2

7/2

018 4

:55:5

2 P

2018 O

'CO

NN

ELL

RO

BERTS

ON

, IN

C.

SE HEALTH & WELLNESS CENTER RENOVATIONS

2901 M

ON

TOPO

LIS D

R, A

USTI

N, TX

78741

CEN

TRA

L H

EA

LTH

08/31/18

Project No. 1826.01CONTRACT DOCUMENTS

DRAWING INDEX ANDSYMBOLS

G1.1ARCHITECTURAL ABBREVIATIONSARCHITECTURALLINETYPES

ARCHITECTURALMATERIALS

ARCHITECTURALSYMBOLS

DRAWING INDEXGENERAL

G1.0 COVER SHEET

G1.1 DRAWING INDEX AND SYMBOLS

G2.1 ADULT TAS ACCESSIBILITY

LIFE SAFETY

LS1.1 LIFE SAFETY INFORMATION

ARCHITECTURAL

A2.1 DEMOLITION PLANS

A3.1 FLOOR PLANS

A7.1 PARTITION TYPES AND DETAILS

A7.2 DETAILS

A7.3 DOOR AND FRAME TYPES

A9.1 REFLECTED CEILING PLAN

A9.2 ROOM FINISH PLAN

A10.1 INTERIOR ELEVATIONS

FIRE PROTECTION

FP1.1 FIRE PROTECTION NOTES, SYMBOLS AND FLOOR PLAN

PME

PME1.1 PME OVERALL PLANS

PLUMBING

P1.1 PLUMBING NOTES, SYMBOLS AND ABBREVIATIONS

P2.1 PLUMBING DEMOLITION PLANS

P3.0 PLUMBING UNDERFLOOR PLANS

P3.1 PLUMBING FLOOR PLANS

P5.1 PLUMBING DETAILS

MECHANICAL

M1.1 MECHANICAL NOTES, SYMBOLS, SCHEDULES & DETAILS

M2.1 MECHANICAL DUCTWORK DEMOLITION PLANS

M3.1 MECHANICAL DUCTWORK PLANS

ELECTRICAL

E1.1 ELECTRICAL NOTES, SYMBOLS AND ABBREVIATIONS

E2.1 POWER & SPECIAL SYSTEMS DEMOLITION PLANS

E2.2 LIGHTING DEMOLITION PLANS

E3.1 POWER & SPECIAL SYSTEMS PLANS

E3.2 LIGHTING PLANS

E6.1 ONE-LINE RISER DIAGRAM

E7.1 ELECTRICAL SCHEDULES & DETAILS

E7.2 ELECTRICAL SCHEDULES

E7.3 ELECTRICAL SCHEDULES

NOTESGENERAL PROJECT

13. PROTECT ALL EXISTING FINISHES, DOOR FRAMES, EQUIPMENT ANDMATERIALS THAT ARE TO REMAIN IN PLACE. DAMAGE TO EXISTINGCOMPONENTS BY CONTRACTOR SHALL BE REPLACED WITH NEWMATERIAL OF LIKE KIND AND QUALITY THAT MATCH THE EXISTINGSTANDARDS. THE CONTRACTOR IS RESPONSIBLE FOR PREPARINGEXISTING SURFACES TO RECEIVE NEW FINISHES SCHEDULED.

14. REFER TO MECHANICAL, PLUMBING AND ELECTRICAL DRAWINGSFOR OTHER WORK.

15. ELECTRICAL AND MECHANICAL INSTALLATIONS MAY REQUIRE WORKABOVE EXISTING CEILINGS BOTH IN THE AREA OF WORK AND INADJACENT AREAS (POSSIBLY ON OTHER FLOORS). REMOVE ANDREINSTALL (OR REPLACE) CEILING TILES AND GRID AS REQUIRED.REMOVE GYPSUM BOARD AT WALLS AND CEILINGS AND REPLACE ASREQUIRED.

16. UNLESS NOTED OTHERWISE, ALL EXISTING ELECTRICAL OUTLETS &FIXTURES IN REMODELED AREAS ARE TO BE REMOVED & RETURNEDTO OWNER. SEE ELECTRICAL SHEETS FOR DEVICES & CIRCUITS TOBE REUSED.

17. ALL ITEMS AND ASSOCIATED CONNECTIONS ARE TO BE REMOVEDAND TERMINATED AT DESIGNATED POINTS. SERVICE CONNECTIONSSHALL BE SAFELY REMOVED, CAPPED OR PLUGGED IN CONFORMITYWITH LOCAL LAWS AND ORDINANCES, REQUIREMENTS OF PUBLICUTILITY COMPANIES, AND OF THE NATIONAL BOARD OF FIREUNDERWRITERS, AND IN SUCH MANNER AS NOT TO INTERFERE WITHTHE USE OF THE OCCUPIED SPACES IN THE BUILDING.

18. IF A CONDUIT OR UTILITY LINE IS CUT WHILE SLEEVING OR CUTTINGTHE SLAB OR REMOVING A PARTITION, THE CONTRACTOR ISRESPONSIBLE FOR REPAIRING IT IMMEDIATELY.

19. ANY EXISTING TO REMAIN FIREPROOFING OR FIRE ASSEMBLIESDAMAGED DURING CONSTRUCTION ARE TO BE REPAIRED TOORIGINAL FIRE PROTECTION REQUIREMENTS.

20. IMMEDIATELY SEAL ALL PENETRATIONS IN EXISTING STRUCTUREOPENED DURING DEMOLITION WITH FIRESTOPPING MATERIALAND/OR WATERPROOFING.

21. SEAL ALL PENETRATIONS, NEW AND EXISTING, ABOVE CEILINGS ATRATED FIRE WALLS IN AREAS OF WORK.

22. PROVIDE DUST PROTECTION OF ALL SUPPLY AND RETURN AIRDIFFUSERS/GRILLES, AND TO CHANGE THESE DAILY.

23. ANY / ALL CONCRETE SAW CUTTING WILL BE “WET” TO MINIMIZEDUST GENERATION.

24. CONTRACTOR TO PROVIDE VACUUM OR OTHER MEANS TO COLLECTALL WATER AND TO PREVENT ITS FLOW OUTSIDE CONSTRUCTIONAREA.

25. ALL SAW CUTTING AND OTHER HIGH NOISE ACTIVITY ASDETERMINED BY OWNER WILL BE PERFORMED OFF HOURS.

26. CONTRACTOR SHALL PHOTOGRAPH AND OTHERWISE DOCUMENTALL CONDITIONS ADJACENT TO CONSTRUCTION AREAS PRIOR TOTHE START OF WORK. PROVIDE PHOTOS TO OWNER.

27. OWNER SHALL PAY FOR OR REIMBURSE CONTRACTOR FORGENERAL BUILDING PERMIT. ALL OTHER (TRADE) PERMITS SHALL BEPAID FOR BY CONTRACTOR OR ITS SUBCONTRACTORS.

NOTESGENERAL PROJECT

1. GENERAL NOTES APPLY TO ALL SHEETS.

2. THE CONTRACTOR SHALL FURNISH ALL LABOR, MATERIALS, TOOLS,EQUIPMENT, AND RELATED ITEMS REQUIRED TO COMPLETE THEDEMOLITION WORK AS INDICATED BY THE CONTRACT DOCUMENTS.

3. CONTRACTOR TO VERIFY ALL DIMENSIONS.

4. ALL ACCESSIBLE ROUTES (OTHER THAN RAMPS) SHALL NOT EXCEEDA SLOPE OF 1:20, AND CROSS SLOPES SHALL NOT EXCEED A SLOPEOF 1:50

5. THE DRAWINGS INDICATE BUILDING CONDITIONS PER EXISTINGDRAWINGS AND ACTUAL PROJECT INVESTIGATION. THECONTRACTOR SHALL ANTICIPATE POSSIBLE SLIGHT DEVIATIONFROM THESE DRAWINGS. REFER TO ARCHITECTURAL & MEPDRAWINGS AND DETAILS FOR EXTENT OF DEMOLITION.

6. THE CONTRACTOR SHALL SUPERVISE AND DIRECT THE WORK,USING HIS BEST SKILL AND ATTENTION. HE SHALL BE SOLELYRESPONSIBLE FOR ALL MEANS, METHODS, TECHNIQUES,SEQUENCES AND PROCEDURES AND FOR COORDINATING ALLPORTIONS OF THE WORK UNDER THE CONTRACT.

7. INSTALL TEMPORARY DUST PARTITIONS WITH DOORS FORCONSTRUCTION ACCESS AROUND AREAS OF WORK SO THATOPERATIONS IN EXISTING ADJACENT AREAS REMAIN DUST FREEAND ACCESSIBLE TO BUILDING OCCUPANTS. MAINTAIN IN PLACEUNTIL COMPLETION OF CONSTRUCTION.

8. REMOVE ALL BUILDING PARTS AND/OR OTHER ITEMS TO ALLOW FORTHE INSTALLATION AND CONNECTION OF NEW WORK, COORDINATETHE WORK WITH THE HVAC, PLUMBING AND ELECTRICALDEMOLITION DRAWINGS.

9. REMOVAL OF THE BUILDING PARTS SHALL BE PERFORMED IN ASAFE, ORDERLY AND CAREFUL MANNER, WITH THE CONSIDERATIONAT ALL TIMES FOR THE SAFETY AND WELFARE OF THE OWNER,BLDG. OCCUPANTS, & PERSONNEL OF THE CONTRACTOR AND/ORSUBCONTRACTOR.

10. MAINTAIN THE UTILITIES TO OCCUPIED SPACES AT ALL TIMES.COORDINATE ANY UTILITY DOWNTIMES W/ OWNER. PROVIDE 72HOUR ADVANCE NOTICE TO THE OWNER OF INTENDED UTILITY SHUTDOWN AND/OR DISRUPTION.

11. ANY QUESTIONS CONCERNING OWNERSHIP OF SALVAGEABLEMATERIAL SHALL BE ANSWERED BY THE OWNER, OR OWNER'SREPRESENTATIVE. ALL ITEMS OTHER THAN FINISH MATERIALS TOBE REMOVED AS PART OF THIS CONTRACT ARE INDICATED WITHDASHED LINES ON DEMOLITION SHEETS. DISPOSE OF THESEMATERIALS AND ITEMS AFTER CHECKING WITH OWNER FOR ITEMSTO BE SALVAGED. SALVAGE ANY ITEMS REQUIRED TO COMPLETENEW WORK.

12. REMOVE ALL MISCELLANEOUS DEVICES AS REQUIRED TO INSTALLNEW FINISHES, INCLUDING BUT NOT LIMITED TO: PLUMBINGFIXTURES, SIGNAGE, SWITCH PLATES, TELEVISION BRACKETS, WALLOUTLET COVERS, TOILET ACCESSORIES, CORNER GUARDS, ETC.SAVE FOR REINSTALLATION AFTER COMPLETION OF FINISH WORK.

NO. DESCRIPTION DATE

1 ADDENDUM 1 09/28/18

1

1

1

9/27/18

Page 8: BidSync - ESBD ......Addendum S.E. Health & Wellness Center Renovations Addendum No. 1 Central Health Page 2 of 3 Austin, Texas Project No. 1826.01 Austin 811 Barton Springs Road,

3 3 3 3

M M

33 33

M

M M

3 3

3

M

M

M

N

TRUE NORTH

N

PLAN NORTH

104

104

104

104104

104

104

104

104

104 105

105 105

105

105

105

105

105

105

105

105

105

105

105

105

105

105105

J1-EXIST (TYP U.N.O.)

J1E-EXISTJ1E-EXIST

D1-EXIST

D1-EXIST

D1-EXIST

D1-EXIST D1-EXIST

104

104

104

104

104 104 104

104 104 104

105

D3-EXIST (TYP) D3-EXIST (TYP)

104

104

104

104

104 104 104

104 104 104

104

104 104

104 104 104

104 104

D3-EXIST

D3-EXIST

D3-EXIST

A3E-EXIST

A3-EXIST (TYP U.N.O.)

Au

stin

811 B

art

on

Sp

rin

gs

Ro

ad

, Su

ite

900, A

ust

in, Te

xas

78704 p

: 512.4

78.7

286 f:

512.4

78.7

441

Sa

n A

nto

nio

4040 B

roa

dw

ay, Su

ite

300, Sa

n A

nto

nio

, Te

xas

78209 p

: 2

10.2

24.6

032 f

: 2

10.2

24.6

453

Engineering Firm:

O'CONNELL ROBERTSON

Firm Registration No. F-2708Revisions:

C:\R

evit P

roje

cts

20

17

\18

260

1_

17_

SE

CH

W R

eno

vation

_M

EP

_C

en

tra

l_aa

nde

rso

n@

oco

nne

llrob

ert

so

n.c

om

.rvt

9/2

7/2

018

12:5

2:3

7 P

20

18

O'C

ON

NELL

RO

BER

TSO

N, IN

C.

SE

HE

AL

TH

& W

EL

LN

ES

S C

EN

TE

R R

EN

OV

AT

ION

S2901 M

ON

TOP

OLI

S D

R., A

USTI

N, TX

78741

CEN

TRA

L H

EA

LTH

08/31/18

Project No. 1826.01CONTRACT DOCUMENTS

LIGHTING DEMOLITIONPLANS

E2.2

GENERAL NOTES

1. REFER TO SHEET E1.1 FOR GENERAL ELECTRICAL NOTESTHAT SHALL APPLY TO ALL SHEETS IN THIS SET UNLESSNOTED OTHERWISE IN THE KEYED NOTES.

2. EXISTING ELECTRICAL WORK & LOCATIONS ARE TAKEN FROMAVAILABLE RECORD DOCUMENTS & SITE OBSERVATIONS.CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONSPRIOR TO CONSTRUCTION.

KEYNOTE LEGEND

104 REMOVE AND RETAIN LIGHT FIXTURES FOR RE-USE.

105 REMOVE LIGHT FIXTURES AND TURN OVER TO OWNER FORATTIC STOCK.

SCALE: 1/4" = 1'-0"1LIGHTING DEMOLITION PLAN - BLACKSTOCK CLINIC

SCALE: 1/4" = 1'-0"2LIGHTING DEMOLITION PLAN - GROUP VISIT ROOMS

SCALE: 1/4" = 1'-0"3LIGHTING DEMOLITION PLAN - CONVENIENT CARE CLINIC

NO. DESCRIPTION DATE

1 ADDENDUM 1 09/28/18

RETAIN EXISTING LIGHTING CIRCUITS AND CONTACTORS (AS APPLICABLE) FOR RE-USE

1

9/27/2018

Page 9: BidSync - ESBD ......Addendum S.E. Health & Wellness Center Renovations Addendum No. 1 Central Health Page 2 of 3 Austin, Texas Project No. 1826.01 Austin 811 Barton Springs Road,

R

R

R

E E

CR

F

R

E

CR

E

E

N

TRUE NORTH

N

PLAN NORTH

+ + ++

CIRCUIT TO EXISTING PNL 'NL1F' U.N.O.

52"

40"

52"

40"

52"

40"

52"

40"

24

2424

24

24

1616

16

16

16

18

18

18

18

2020

20

20

20

22 22

22

22

22

11

1

1

1

1

1

1

POWER CIRCUITED TO EXISTING PNL 'NL1D' U.N.O.

POWER CIRCUITED TO EXISTING PNL 'NL1C' U.N.O.

4D

4D

POWER/DATA POLE FOR WORKSTATIONS BY FURNITURE VENDOR

PROVIDE SPARE JUNCTION BOX AND 1" CONDUIT ABOVE CEILING

FOR OWNER'S FUTURE USE (COORDINATE WITH OWNER)

PROVIDE SPARE JUNCTION BOX AND 1" CONDUIT ABOVE CEILING

FOR OWNER'S FUTURE USE (COORDINATE WITH OWNER)

803

12

10

12

10

12 10 12

12 10 12

10

12

10

12

101210

9

7

9

7

9 7 9

7

9

7

+

PROVIDE TWO NEW RECEPTACLES ON THIS

WALL - COORDINATE LOCATION WITH OWNER;

CONNECT TO NEW CIRCUIT

30

36

PP

10

9

4

4

4

4

1

38 38

11

1

1

1

1

+ ++

+

++

+

+

CIRCUIT TO EXISTING PNL 'NL1B' U.N.O.

FOR UNDER-COUNTER FREEZER

POWER/DATA POLE FROM CEILING TO WITHIN PARTIAL-HEIGHT WALL FOR WORKSTATIONS

803

COORDINATE WITH TV LOCATION

PP

84"

+

PROVIDE PUSH-BUTTON DOOR RELEASE

COORDINATE POWER/DATA ROUTING AND

CONNECTION WITH OFOI FURNITURE

49

40"

52"51

51

51

51

57

55

55 55

55

55 12

12

1212 14

14

14

14

1412

59

61

63

59 61

63

59

63

67

16

16

61

63

16

16

16

18

18

18 18

18

20

20

20

20

20

22

22

2224 24 24

262626

5961

40" 40"

40"

40"40"

40"

52" 52" 52"

52"

52"

52"

CIRCUIT TO EXISTING PNL 'NL1K' U.N.O.

PROVIDE NEW DEDICATED RECEPTACLE AND CIRCUIT FOR REFRIGERATOR; COORDINATE LOCATION WITH OWNER

12

Au

stin

811 B

art

on

Sp

rin

gs

Ro

ad

, Su

ite

900, A

ust

in, Te

xas

78704 p

: 512.4

78.7

286 f:

512.4

78.7

441

Sa

n A

nto

nio

4040 B

roa

dw

ay, Su

ite

300, Sa

n A

nto

nio

, Te

xas

78209 p

: 2

10.2

24.6

032 f

: 2

10.2

24.6

453

Engineering Firm:

O'CONNELL ROBERTSON

Firm Registration No. F-2708Revisions:

C:\R

evit P

roje

cts

20

17

\18

260

1_

17_

SE

CH

W R

eno

vation

_M

EP

_C

en

tra

l_aa

nde

rso

n@

oco

nne

llrob

ert

so

n.c

om

.rvt

9/2

7/2

018

12:5

2:4

0 P

20

18

O'C

ON

NELL

RO

BER

TSO

N, IN

C.

SE

HE

AL

TH

& W

EL

LN

ES

S C

EN

TE

R R

EN

OV

AT

ION

S2901 M

ON

TOP

OLI

S D

R., A

USTI

N, TX

78741

CEN

TRA

L H

EA

LTH

08/31/18

Project No. 1826.01CONTRACT DOCUMENTS

POWER & SPECIALSYSTEMS PLANS

E3.1

KEYNOTE LEGEND

803 RE-INSTALL SALVAGED CARD READER AND TIE TO EXISTINGNEARBY SECURITY PANEL. INSTALLATION AND LABELINGSHALL MATCH EXISTING INSTALLATIONS IN BUILDING.

GENERAL NOTES

1. REFER TO SHEET E1.1 FOR GENERAL ELECTRICAL NOTESTHAT SHALL APPLY TO ALL SHEETS IN THIS SET UNLESSNOTED OTHERWISE IN THE KEYED NOTES.

2. THIS SHEET GENERALLY DEPICTS EQUIPMENT AND DEVICESFOR FLOOR LEVEL TO APPROXIMATELY 48" AFF. SEELIGHTING/CEILING SHEETS FOR ADDITIONAL DEVICESMOUNTED ABOVE THIS LEVEL.

SCALE: 1/4" = 1'-0"1POWER & SPECIAL SYSTEMS PLANS - BLACKSTOCK CLINIC

SCALE: 1/4" = 1'-0"2POWER & SPECIAL SYSTEMS PLANS - GROUP VISIT ROOMS

SCALE: 1/4" = 1'-0"3POWER & SPECIAL SYSTEMS PLANS - CONVENIENT CARE CLINIC

ALL NEW RECEPTACLES SHALL BE TAMPER-RESISTANT PER NEC 2017 REQUIREMENTS.

SCALE: 1/4" = 1'-0"4

POWER & SPECIALSYSTEMS PLANS -IMMUNIZATION

CIRCUIT NUMBERS SHOWN BASED ON RECORD DOCUMENTS - CONTRACTOR SHALL VERIFY CIRCUIT NUMBERS WITH EXISTING PANEL

DIRECTORIES. USE SPARE BREAKER CIRCUITS WHERE AVAILABLE. PROVIDE NEW 20/1

BREAKERS AS NECESSARY.

NO. DESCRIPTION DATE

1 ADDENDUM 1 09/28/18

ALL BRANCH CIRCUITS TO EXAM ROOMS AND OTHER PATIENT CARE AREAS SHALL BE PROVIDED WITH METAL RACEWAY SYSTEM OR HEALTHCARE RATED FLEX CONDUIT (HCF) PER NEC 2017 SECTION 517.13.

1

9/27/2018

Page 10: BidSync - ESBD ......Addendum S.E. Health & Wellness Center Renovations Addendum No. 1 Central Health Page 2 of 3 Austin, Texas Project No. 1826.01 Austin 811 Barton Springs Road,

M

M M

3 3

3

N

TRUE NORTH

N

PLAN NORTH

CIRCUIT TO EXISTING PNL 'NH1F' CKT #6 U.N.O.

A3

A3

A3

A3

A3

A3

A3

A3

A3

A3

802

TYP

1

POWER CIRCUITED TO EXISTING PNL 'NH1D'

CKT. #4 U.N.O.

POWER CIRCUITED TO EXISTING PNL 'NH1C' CKT. #2 U.N.O.

800

800 800 800 800

800 800 800 800

800 800

800 800

D3-EXIST (TYP)

D3-EXIST (TYP)

D3-EXIST (TYP)

1 1

1" 1"

2"

4"

3"

4"

1"

1" 4"

2"

CIRCUIT TO EXISTING PNL 'NH1B' CKT #22

U.N.O.

801

TYP

800 800

800

800 800

800

800

800

800

800

800

800

800

800

800

A3 A3 A3 A3

A3

A3

A3A3A3A3E-EXIST

A3-EXISTA3-EXIST

J1-EXIST (TYP)

A3-EXIST

A3-EXIST A3-EXIST

A3-EXIST

A3-EXIST

A3-EXIST

A3-EXIST

A3-EXISTA3-EXIST

A3-EXISTA3-EXIST

A3-EXIST

802

TYP

TIE WAITING AREA LIGHTS ONTO

EXISTING THREE-WAY CORRIDOR SWITCH

1

NEW EXAM AND WAITING LIGHTS ON EXISTING

CKT. NH2B-16, CONTACTOR LC-7 TO

MATCH EXISTING LAYOUT

1

Au

stin

811 B

art

on

Sp

rin

gs

Ro

ad

, Su

ite

900, A

ust

in, Te

xas

78704 p

: 512.4

78.7

286 f:

512.4

78.7

441

Sa

n A

nto

nio

4040 B

roa

dw

ay, Su

ite

300, Sa

n A

nto

nio

, Te

xas

78209 p

: 2

10.2

24.6

032 f

: 2

10.2

24.6

453

Engineering Firm:

O'CONNELL ROBERTSON

Firm Registration No. F-2708Revisions:

C:\R

evit P

roje

cts

20

17

\18

260

1_

17_

SE

CH

W R

eno

vation

_M

EP

_C

en

tra

l_aa

nde

rso

n@

oco

nne

llrob

ert

so

n.c

om

.rvt

9/2

7/2

018

12:5

2:4

3 P

20

18

O'C

ON

NELL

RO

BER

TSO

N, IN

C.

SE

HE

AL

TH

& W

EL

LN

ES

S C

EN

TE

R R

EN

OV

AT

ION

S2901 M

ON

TOP

OLI

S D

R., A

USTI

N, TX

78741

CEN

TRA

L H

EA

LTH

08/31/18

Project No. 1826.01CONTRACT DOCUMENTS

LIGHTING PLANS

E3.2

KEYNOTE LEGEND

800 REINSTALL SALVAGED LIGHT FIXTURE AND RECONNECT TOEXISTING LIGHTING CIRCUIT AND (IF APPLICABLE)CONTACTOR.

801 REINSTALL SALVAGED LIGHT FIXTURES FROM DEMOLISHEDWAITING AREA (REF 1/E2.2). PROVIDE PATTERN AS SHOWN;PROTRUSION DOWN FROM CEILING PER FIXTURE INDICATED(E.G. 2").

802 PROVIDE NEW TYPE 'A3' LED LIGHTING FIXTURE EQUAL TOLITHONIA MODEL '2GTL-4-60L-A12125-EZ1-LP835' SERIES TOMATCH APPEARANCE OF EXISTING ACRYLIC TROFFERFLUORESCENT FIXTURES THROUGHOUT BUILDING ASCLOSELY AS POSSIBLE. FIXTURE SHALL SUPPORT 277V.

GENERAL NOTES

1. REFER TO SHEET E1.1 FOR GENERAL ELECTRICAL NOTESTHAT SHALL APPLY TO ALL SHEETS IN THIS SET UNLESSNOTED OTHERWISE IN THE KEYED NOTES.

2. THIS SHEET GENERALLY DEPICTS EQUIPMENT AND DEVICESFOR FLOOR LEVEL TO APPROXIMATELY 48" AFF. SEELIGHTING/CEILING SHEETS FOR ADDITIONAL DEVICESMOUNTED ABOVE THIS LEVEL.

SCALE: 1/4" = 1'-0"1LIGHTING PLAN - BLACKSTOCK CLINIC

SCALE: 1/4" = 1'-0"2LIGHTING PLAN - GROUP VISIT ROOMS

SCALE: 1/4" = 1'-0"3LIGHTING PLAN - CONVENIENT CARE CLINIC

PROVIDE LIGHTING CONTROLS DEVICES AS NECESSARY TO

CONNECT TO EXISTING LIGHTING CONTROLS SYSTEMS

NO. DESCRIPTION DATE

1 ADDENDUM 1 09/28/18

9/27/2018

Page 11: BidSync - ESBD ......Addendum S.E. Health & Wellness Center Renovations Addendum No. 1 Central Health Page 2 of 3 Austin, Texas Project No. 1826.01 Austin 811 Barton Springs Road,

NH1X

DISTRIBUTION EQUIPMENT

DESIGNATIONSSYSTEM: N = NORMAL

E = EMERGENCY (NEC ART 700)

S = LEGALLY REQD STANDBY (NEC ART 701)

O = OPTIONAL STANDBY (NEC ART 702)

G = ALTERNATE SUPPLY (GENERATOR)

C = CRITICAL (NEC ART 517)

X = LIFE SAFETY (NEC ART 517)

Q = EQUIPMENT (NEC ART 517)

VOLTAGE LEVEL: H = 277/480

L = 120/208

FLOOR: M = MEZZANINE

6 = ROOF

7 = UPPER ROOF

ETC.

SUFFIX(ES) TO PROVIDE LOCATION INFORMATION OR TO

AVOID DUPLICATION.

NOTE:TRANSFORMER DESIGNATIONS SIMILAR EXCEPT "H"/"L"

VOLTAGE DESIGNATIONS OMITTED.

EXISTING AUSTIN ENERGY

PADMOUNT TRANSFORMER

~

~

TO FUTURE PVSYSTEM

DISTRIBUTION PANEL NH1E, 277/480V, 600A, 30 KAIC, (I SCA=16,114A)

NH1

MAIN SWITCHBOARD NH1A, 2000 AMPS, 277/480 VOLTS, 65 KA INTERRUPTING, NEMA 1, (CALCULATED AVAILABLE FAULT CURENT 24,442 AMPS)

DIGITALMETERING

SURGESUPPRESSION

BU

ILD

ING

ST

EE

L

WA

TE

RL

INE

GR

OU

ND

RO

DS

N1B N1C N1D N1J N1H N1K N1M N1N

N1F N1G N1L

N2BN2A

PANEL NH2A, 277/480V, 225A, 18 KAIC, (I SCA=8,508A)

N1P

N1E

2000 AMP, 277/480 VOLT

FUSED NEMA 3R BOLTED PRESSURE

SWITCH WITH GFI PROTECTION

CAPPED FOR FUTURE USE

2000 AMP, 277/480 VOLT

NEMA 3R CT ENCLOSURE AND METER

SOCKET PER AUSTIN ENERGY REQUIREMENTS.

3/0 GROUND

MDF ROOM

GRD BUS

IDF ROOM

GRD BUS

3/0 GROUND

1000 KVA TRANSFORMER,

5.3% IMPEDANCE, AVAILABLE

FAULT CURRENT 25,217 AMPS

I SCA= 24,631 AMPS

PANEL NH2B, 277/480V, 225A, 18 KAIC, (I SCA=11,000A)

F57

F56

F55

F59

F58

NL1E

120/208V

100A

10 KAIC

PNL

F02

3PNF

600A

N3R

NL1P

PNL

NH1P

PNL

F53

F51

NL2A

120/208V

100A

10 KAIC

PNL

F54

F52

NL2B

PNL

S2

F50F49F48

F47F46F45

F44F43F42

F41F40F39F38

F41F40F39F38

F36F35F34F32F31F30

F29F28F27F26F25F24F23F22

F21F20F19F18F17F16F15F14

F13F12F11F10FO9F08F07F06F05F04F03F02

F01

S1

S1

WHAV

10

AHU-3

10

AHU-2

10

AHU-1AHU-6AHU-5AHU-4

15

SHWP-2

15

SHWP-1

10

CHWP-2

10

CHWP-1

NL1F

120/208V

150A

10 KAIC

PNL

NH1F

277/480V

150A

18 KAIC

PNL

NL1G

120/208V

150A

10 KAIC

PNL

NH1G

277/480V

150A

18 KAIC

PNL

NL1H

120/208V

150A

10 KAIC

PNL

NH1H

277/480V

200A

18 KAIC

PNL

NL1L

PNL

NH1L

PNL

CH-1

NL1N

PNL

NH1N

PNL

NL1M

120/208V

150A

10 KAIC

PNL

NH1M

277/480V

150A

18 KAIC

PNL

NL1K

PNL

NH1K

PNL

NL1J

PNL

NH1J

PNL

NL1D

120/208V

150A

10 KAIC

PNL

NH1D

277/480V

150A

18 KAIC

PNL

NL1B

120/208V

225A

10 KAIC

PNL

NH1B

277/480V

225A

30 KAIC

PNL

NL1C

120/208V

150A

10 KAIC

PNL

NH1C

277/480V

150A

18 KAIC

PNL

WHWH

NEW WORK

FUTURE

EXISTING TO REMAIN

EXISTING TO BE DEMOLISHED

ONE-LINE LEGEND

CIRCUIT TAGFDR1

Au

stin

811 B

art

on

Sp

rin

gs

Ro

ad

, Su

ite

900, A

ust

in, Te

xas

78704 p

: 512.4

78.7

286 f:

512.4

78.7

441

Sa

n A

nto

nio

4040 B

roa

dw

ay, Su

ite

300, Sa

n A

nto

nio

, Te

xas

78209 p

: 2

10.2

24.6

032 f

: 2

10.2

24.6

453

Engineering Firm:

O'CONNELL ROBERTSON

Firm Registration No. F-2708Revisions:

C:\R

evit P

roje

cts

20

17

\18

260

1_

17_

SE

CH

W R

eno

vation

_M

EP

_C

en

tra

l_aa

nde

rso

n@

oco

nne

llrob

ert

so

n.c

om

.rvt

9/2

7/2

018

12:5

2:4

4 P

20

18

O'C

ON

NELL

RO

BER

TSO

N, IN

C.

SE

HE

AL

TH

& W

EL

LN

ES

S C

EN

TE

R R

EN

OV

AT

ION

S2901 M

ON

TOP

OLI

S D

R., A

USTI

N, TX

78741

CEN

TRA

L H

EA

LTH

08/31/18

Project No. 1826.01CONTRACT DOCUMENTS

ONE-LINE RISERDIAGRAM

E6.1

NO. DESCRIPTION DATE

1 ADDENDUM 1 09/28/18

1

9/27/2018

Page 12: BidSync - ESBD ......Addendum S.E. Health & Wellness Center Renovations Addendum No. 1 Central Health Page 2 of 3 Austin, Texas Project No. 1826.01 Austin 811 Barton Springs Road,

LUMINAIRE SUSPENSIONWIRES (#10 MIN) ATTACHEDTO STRUCTURE(TYP EA. CORNER)

3 TWIST MINIMUM (TYP)

FIXTURE WHIP FROMJUNCTION BOX(6FT. LONG MAX.)

LUMINAIRE.REFER TOSCHEDULE

LUMINAIRE MANUFACTURER'S EARTHQUAKECLIP, (4) PER FIXTURE AT CORNERS. ATTACHWITH SHEET METAL SCREW

ACOUSTICAL CEILING TILE(TYP)

ARCHITECTURAL CEILINGGRID

LUMINAIRE.REFER TOSCHEDULE

ON

GREEN GROUNDING

SCREW-#10-32X3/8"

TAPPED HOLE

PER SPECIFICATIONS

PHASE CONDUCTOR

CIRCUIT MARKER ON

CONDUIT

WIRE NUT

(TYPICAL)

(TYPICAL)

IN BOX

GN

G GNNSWITCHING

NOTE:

GREEN GROUND CONDUCTOR SHALL BE CONTINUOUS SO THAT REMOVAL

OF DEVICE WILL NOT INTERFERE WITH GROUND CONTINUITY.

PROVIDE A SEPARATE NEUTRAL FOR EACH CIRCUIT.

JUNCTION BOX

JUNCTION BOX

IN BOX

(TYPICAL)

(TYPICAL)

WIRE NUT

CONDUIT

CIRCUIT MARKER ON

PHASE CONDUCTOR

PER SPECIFICATIONS

TAPPED HOLE

SCREW-#10-32X3/8"

GREEN GROUNDING

1.

2.

SELF TAPPING

SELF TAPPING

OUTBOARD BALLAST

INBOARD BALLAST

1 BUTTON MOMENTARYSWITCH, HUBBELL LVS-1

RED

BLACK (COMMON)

BLUE (CONTROL)

RED

BLACK

WHITE

NEUTRAL

HOT

NE

UT

RA

L

HO

T

OUTBOARD BALLASTPOWER PACK CONTACTS RATEDFOR 20 AMPS

UVPPM POWER PACK SUPPLIES 150mA

RED

BLACK (COMMON)

BLUE (CONTROL)

RED

BLACK

WHITE

INBOARD BALLASTPOWER PACK CONTACTS RATEDFOR 20 AMPS

UVPPM POWER PACK SUPPLIES 150mA

RED (+24VDC)

RED (+24VDC)

DO NOT TIE THE LOW-VOLTAGE RED WIRE(+24VDC) TOGETHER

HOT

HUBBELL BUILDING AUTOMATION LOW VOLTAGE

SENSORS (DEVICES) REQUIRE 33mA EACH

HUBBELL BUILDING AUTOMATION OMNISERIES SENSOR WITH -RP OPTION, SEESPECIFICATIONS FOR MODEL NUMBER

GENERAL NOTES:

1. DETAIL DENOTES HUBBELL PART NUMBERS,

EQUIVALENT SYSTEM UTILIZING APPROVED EQUAL

PARTS FROM OTHER SUPPLIERS IS ACCEPTABLE.

2. DRAWING DENOTES LAYOUT WITH SINGLE SENSOR,

FOR LARGER ROOMS WITH MULTIPLE SENSORS

MODIFY DRAWING PER MANUFACTURER'S

REQUIREMENTS.

ORANGE

ORANGE 1 BUTTON MOMENTARYSWITCH, HUBBELL LVS-1

ROOM LIGHTING

CIRCUIT

2

LUMINAIRE MOUNTING

LAY-IN CEILING DETAILSCALE: NONE

1 RECEPTACLE AND SWITCH WIRING DETAIL

NOT TO SCALE

3 TYPICAL LIGHTING VACANCY CONTROLS

NOT TO SCALE

ELECTRICAL LOAD ANALYSIS - PANEL NH1B

CONNECTED LOAD

EXISTING LOAD REMOVED FROM NH1B

LIGHTS 0.9 kVA

NEW LOADS ADDED TO NH1B

LIGHTS 1.3 kVA

(DEMAND FACTOR = 100%)

NET LOAD 0.3 kVA

480/277V/3PH/4W 0.4 A

EXISTING DESIGN MAX LOAD NH1B (NOTE 1) 49.9 kVA

NEW LOADS ADDED TO NL1B

LIGHTS 0.3 kVA

NET LOAD 50.2 kVA

480/277V/3PH/4W 139.5 A

THE EXISTING 225-AMP FEEDER TO PANEL NH1B REMAINS ADEQUATE

FOR THE REVISED LOAD.

NOTES

1. FROM RECORD DOCUMENTS + 25%

ELECTRICAL LOAD ANALYSIS - PANEL NH1C

CONNECTED LOAD

EXISTING LOAD REMOVED FROM NH1C

LIGHTS 0.4 kVA

NEW LOADS ADDED TO NH1C

LIGHTS 0.3 kVA

(DEMAND FACTOR = 100%)

NET LOAD -0.1 kVA

480/277V/3PH/4W -0.1 A

LIGHTING AND RECEPTACLE LOADS REMAIN RELATIVELY UNCHANGED AS

PART OF THIS RENOVATION. THERE IS AN OVERALL NET REDUCTION IN

CONNECTED ELECTRICAL LOAD FOR THIS DISTRIBUTION PANEL AND

DOWNSTREAM PANELS.

ELECTRICAL LOAD ANALYSIS - PANEL NH1D

CONNECTED LOAD

EXISTING LOAD REMOVED FROM NH1D

LIGHTING 0.3 kVA

NEW LOADS ADDED TO NH1D

LIGHTING 0.5 kVA

(DEMAND FACTOR = 100%)

NET LOAD 0.3 kVA

480/277V/3PH/4W 0.3 A

EXISTING DESIGN MAX LOAD NH1D (NOTE 1) 36.1 kVA

NEW LOADS ADDED TO NH1D

RECEPTACLES 0.3 kVA

NET LOAD 36.4 kVA

480/277V/3PH/4W 101.1 A

THE EXISTING 150-AMP FEEDER TO PANEL NH1D REMAINS ADEQUATE

FOR THE REVISED LOAD.

NOTES

1. FROM RECORD DOCUMENTS + 25%

ELECTRICAL LOAD ANALYSIS - PANEL NH1F

CONNECTED LOAD

EXISTING LOAD REMOVED FROM NH1F

LIGHTING 0.8 kVA

NEW LOADS ADDED TO NH1F

LIGHTING 0.5 kVA

(DEMAND FACTOR = 100%)

NET LOAD -0.3 kVA

480/277V/3PH/4W -0.4 A

LIGHTING AND RECEPTACLE LOADS REMAIN RELATIVELY UNCHANGED AS

PART OF THIS RENOVATION. THERE IS AN OVERALL NET REDUCTION IN

CONNECTED ELECTRICAL LOAD FOR THIS DISTRIBUTION PANEL AND

DOWNSTREAM PANELS.

ELECTRICAL LOAD ANALYSIS - PANEL NL1B

CONNECTED LOAD

EXISTING LOAD REMOVED FROM NL1B

RECEPTACLES 3.8 kVA

NEW LOADS ADDED TO NL1B

RECEPTACLES 4.9 kVA

(DEMAND FACTOR UP TO 10 KVA = 100%)

NET LOAD 1.1 kVA

208/120V/3PH/4W 3.1 A

EXISTING DESIGN MAX LOAD NL1B (NOTE 1) 33.1 kVA

NEW LOADS ADDED TO NL1B

RECEPTACLES 1.1 kVA

NET LOAD 34.2 kVA

208/120V/3PH/4W 95.1 A

THE EXISTING 225-AMP FEEDER TO PANEL NL1B REMAINS ADEQUATE

FOR THE REVISED LOAD.

NOTES

1. FROM RECORD DOCUMENTS + 25%

ELECTRICAL LOAD ANALYSIS - PANEL NL1C

CONNECTED LOAD

EXISTING LOAD REMOVED FROM NL1C

RECEPTACLES 1.4 kVA

NEW LOADS ADDED TO NL1C

RECEPTACLES 2.7 kVA

(DEMAND FACTOR UP TO 10 KVA = 100%)

NET LOAD 1.3 kVA

208/120V/3PH/4W 3.5 A

EXISTING DESIGN MAX LOAD NL1C (NOTE 1) 21.6 kVA

NEW LOADS ADDED TO NL1C

RECEPTACLES 1.3 kVA

NET LOAD 22.9 kVA

208/120V/3PH/4W 63.6 A

THE EXISTING 150-AMP FEEDER TO PANEL NL1C REMAINS ADEQUATE

FOR THE REVISED LOAD.

NOTES

1. FROM RECORD DOCUMENTS + 25%

ELECTRICAL LOAD ANALYSIS - PANEL NL1D

CONNECTED LOAD

EXISTING LOAD REMOVED FROM NL1D

RECEPTACLES 1.1 kVA

NEW LOADS ADDED TO NL1D

RECEPTACLES 4.0 kVA

(DEMAND FACTOR UP TO 10 KVA = 100%)

NET LOAD 2.9 kVA

208/120V/3PH/4W 8.0 A

EXISTING DESIGN MAX LOAD NL1D (NOTE 1) 33.1 kVA

NEW LOADS ADDED TO NL1D

RECEPTACLES 2.9 kVA

NET LOAD 36.0 kVA

208/120V/3PH/4W 100.1 A

THE EXISTING 150-AMP FEEDER TO PANEL NL1B REMAINS ADEQUATE

FOR THE REVISED LOAD.

NOTES

1. FROM RECORD DOCUMENTS + 25%

ELECTRICAL LOAD ANALYSIS - PANEL NL1F

CONNECTED LOAD

EXISTING LOAD REMOVED FROM NL1F

RECEPTACLES 2.2 kVA

NEW LOADS ADDED TO NL1F

RECEPTACLES 4.3 kVA

(DEMAND FACTOR UP TO 10 KVA = 100%)

NET LOAD 2.2 kVA

208/120V/3PH/4W 6.0 A

EXISTING DESIGN MAX LOAD NL1F (NOTE 1) 27.0 kVA

NEW LOADS ADDED TO NL1F

RECEPTACLES 2.2 kVA

NET LOAD 29.2 kVA

208/120V/3PH/4W 81.0 A

THE EXISTING 150-AMP FEEDER TO PANEL NL1B REMAINS ADEQUATE

FOR THE REVISED LOAD.

NOTES

1. FROM RECORD DOCUMENTS + 25%

ELECTRICAL LOAD ANALYSIS - PANEL NL1K

CONNECTED LOAD

EXISTING LOAD REMOVED FROM NL1K

RECEPTACLES 0.0 kVA

NEW LOADS ADDED TO NL1K

RECEPTACLES 0.2 kVA

(DEMAND FACTOR UP TO 10 KVA = 100%)

NET LOAD 0.2 kVA

208/120V/3PH/4W 0.5 A

EXISTING DESIGN MAX LOAD NL1K (NOTE 1) 28.5 kVA

NEW LOADS ADDED TO NL1K

RECEPTACLES 0.2 kVA

NET LOAD 28.7 kVA

208/120V/3PH/4W 79.8 A

THE EXISTING 150-AMP FEEDER TO PANEL NL1K REMAINS ADEQUATE

FOR THE REVISED LOAD.

NOTES

1. FROM RECORD DOCUMENTS + 25%

1

Au

stin

811 B

art

on

Sp

rin

gs

Ro

ad

, Su

ite

900, A

ust

in, Te

xas

78704 p

: 512.4

78.7

286 f:

512.4

78.7

441

Sa

n A

nto

nio

4040 B

roa

dw

ay, Su

ite

300, Sa

n A

nto

nio

, Te

xas

78209 p

: 2

10.2

24.6

032 f

: 2

10.2

24.6

453

Engineering Firm:

O'CONNELL ROBERTSON

Firm Registration No. F-2708Revisions:

C:\R

evit P

roje

cts

20

17

\18

260

1_

17_

SE

CH

W R

eno

vation

_M

EP

_C

en

tra

l_aa

nde

rso

n@

oco

nne

llrob

ert

so

n.c

om

.rvt

9/2

7/2

018

12:5

2:4

5 P

20

18

O'C

ON

NELL

RO

BER

TSO

N, IN

C.

SE

HE

AL

TH

& W

EL

LN

ES

S C

EN

TE

R R

EN

OV

AT

ION

S2901 M

ON

TOP

OLI

S D

R., A

USTI

N, TX

78741

CEN

TRA

L H

EA

LTH

08/31/18

Project No. 1826.01CONTRACT DOCUMENTS

ELECTRICAL SCHEDULES& DETAILS

E7.1

NO. DESCRIPTION DATE

1 ADDENDUM 1 09/28/18

9/27/2018

Page 13: BidSync - ESBD ......Addendum S.E. Health & Wellness Center Renovations Addendum No. 1 Central Health Page 2 of 3 Austin, Texas Project No. 1826.01 Austin 811 Barton Springs Road,

BC PNL 277/480 V 3PH 4W 225 A MLO 30 KAIC 42 CKT NEMA 1 SURF MTD NEMA 1 1 SECT

NH1B LOCATION: FED FROM: NH1A

CKT LOAD DESCRIPTION LOAD BREAKER CIRCUITNOTES PH

NO. TYPE TRIP / POLES SIZING

1 XFMR N1B / PANEL NL1B FDR 100 / 3 3#3, #8G, 1 1/4"C A

3 B

5 C

7 SPACE ONLY A

9 SPACE ONLY B

11 SPACE ONLY C

13 SPACE ONLY A

15 SPACE ONLY B

17 SPACE ONLY C

19 SPACE ONLY A

21 SPACE ONLY B

23 SPACE ONLY C

25 SPACE ONLY A

27 SPACE ONLY B

29 SPACE ONLY C

31 SPACE ONLY A

33 SPACE ONLY B

35 SPACE ONLY C

37 SPACE ONLY A

39 SPACE ONLY B

41 SPACE ONLY C

2 LIGHTING LTG 20 / 1 1#12, #12N, #12G, 3/4"C A

4 LIGHTING LTG 20 / 1 1#12, #12N, #12G, 3/4"C B

6 LIGHTING LTG 20 / 1 1#12, #12N, #12G, 3/4"C C

8 EXTERIOR LIGHTS LTG 20 / 1 1#10, #10N, #10G, 3/4"C A

10 LTG 20 / 1 1#10, #10N, #10G, 3/4"C B

12 PARKING LOT LIGHTS LTG 30 / 1 1#8, #8N, #10G, 3/4"C C

14 LTG 30 / 1 1#8, #8N, #10G, 3/4"C A

16 LIGHTING LTG 20 / 1 1#12, #12N, #12G, 3/4"C B

18 STAIR LIGHTS LTG 20 / 1 1#12, #12N, #12G, 3/4"C C

20 SPARE 20 / 1 A

22 LIGHTING LTG 20 / 1 1#12, #12N, #12G, 3/4"C B

24 SPARE 20 / 1 C

26 SPARE 20 / 1 A

28 SPARE 20 / 1 B

30 SPARE 20 / 1 C

32 SPACE ONLY A

34 SPACE ONLY B

36 SPACE ONLY C

38 SPACE ONLY A

40 SPACE ONLY B

42 SPACE ONLY C

NOTES:

BC PNL 277/480 V 3PH 4W 150 A MLO 18 KAIC 30 CKT NEMA 1 FLUSH MTD NEMA 1 1 SECT

NH1C LOCATION: FED FROM: NH1A

CKT LOAD DESCRIPTION LOAD BREAKER CIRCUITNOTES PH

NO. TYPE TRIP / POLES SIZING

1 XFMR N1C / PANEL NL1C FDR 70 / 3 3#4, #8G, 1"C A

3 B

5 C

7 SPACE ONLY A

9 SPACE ONLY B

11 SPACE ONLY C

13 SPACE ONLY A

15 SPACE ONLY B

17 SPACE ONLY C

19 SPACE ONLY A

21 SPACE ONLY B

23 SPACE ONLY C

25 SPACE ONLY A

27 SPACE ONLY B

29 SPACE ONLY C

2 LIGHTING LTG 20 / 1 1#12, #12N, #12G, 3/4"C A

4 LIGHTING LTG 20 / 1 1#12, #12N, #12G, 3/4"C B

6 SPARE 20 / 1 C

8 SPARE 20 / 1 A

10 SPARE 20 / 1 B

12 SPARE 20 / 1 C

14 SPACE ONLY A

16 SPACE ONLY B

18 SPACE ONLY C

20 SPACE ONLY A

22 SPACE ONLY B

24 SPACE ONLY C

26 SPACE ONLY A

28 SPACE ONLY B

30 SPACE ONLY C

NOTES:

BC PNL 277/480 V 3PH 4W 150 A MLO 18 KAIC 30 CKT NEMA 1 FLUSH MTD NEMA 1 1 SECT

NH1D LOCATION: FED FROM: NH1A

CKT LOAD DESCRIPTION LOAD BREAKER CIRCUITNOTES PH

NO. TYPE TRIP / POLES SIZING

1 XFMR N1D / PANEL NL1D FDR 70 / 3 3#4, #8G, 1"C A

3 B

5 C

7 SPACE ONLY A

9 SPACE ONLY B

11 SPACE ONLY C

13 SPACE ONLY A

15 SPACE ONLY B

17 SPACE ONLY C

19 SPACE ONLY A

21 SPACE ONLY B

23 SPACE ONLY C

25 SPACE ONLY A

27 SPACE ONLY B

29 SPACE ONLY C

2 LIGHTING LTG 20 / 1 1#12, #12N, #12G, 3/4"C A

4 LIGHTING LTG 20 / 1 1#12, #12N, #12G, 3/4"C B

6 SPARE 20 / 1 C

8 SPARE 20 / 1 A

10 SPARE 20 / 1 B

12 SPARE 20 / 1 C

14 SPACE ONLY A

16 SPACE ONLY B

18 SPACE ONLY C

20 SPACE ONLY A

22 SPACE ONLY B

24 SPACE ONLY C

26 SPACE ONLY A

28 SPACE ONLY B

30 SPACE ONLY C

NOTES:

BC PNL 277/480 V 3PH 4W 150 A MLO 18 KAIC 30 CKT NEMA 1 FLUSH MTD NEMA 1 1 SECT

NH1F LOCATION: FED FROM: NH1E

CKT LOAD DESCRIPTION LOAD BREAKER CIRCUITNOTES PH

NO. TYPE TRIP / POLES SIZING

1 XFMR N1F / PANEL NL1F FDR 70 / 3 3#4, #8G, 1"C A

3 B

5 C

7 SPACE ONLY A

9 SPACE ONLY B

11 SPACE ONLY C

13 SPACE ONLY A

15 SPACE ONLY B

17 SPACE ONLY C

19 SPACE ONLY A

21 SPACE ONLY B

23 SPACE ONLY C

25 SPACE ONLY A

27 SPACE ONLY B

29 SPACE ONLY C

2 LIGHTING LTG 20 / 1 1#12, #12N, #12G, 3/4"C A

4 LIGHTING LTG 20 / 1 1#12, #12N, #12G, 3/4"C B

6 LIGHTING LTG 20 / 1 1#12, #12N, #12G, 3/4"C C

8 SPARE 20 / 1 A

10 SPARE 20 / 1 B

12 SPARE 20 / 1 C

14 SPACE ONLY A

16 SPACE ONLY B

18 SPACE ONLY C

20 SPACE ONLY A

22 SPACE ONLY B

24 SPACE ONLY C

26 SPACE ONLY A

28 SPACE ONLY B

30 SPACE ONLY C

NOTES:

BC PNL 120/208 V 3PH 4W 225 A MCB 10 KAIC 84 CKT NEMA 1 SURF MTD NEMA 1 2 SECT

NL1B LOCATION: FED FROM: NH1B

CKT LOAD DESCRIPTION LOAD BREAKER CIRCUITNOTES PH

NO. TYPE TRIP / POLES SIZING

1 INTERIOR LIGHTING CONTROL OTH 15 / 1 1#12, #12N, #12G, 3/4"C A

3 EXTERIOR LIGHTING CONTROL OTH 15 / 1 1#12, #12N, #12G, 3/4"C B

5 CU-2 A/C 40 / 2 2#8, #10G, 3/4"C C

7 A

9 CU-3 A/C 15 / 2 2#12, #12G, 3/4"C B

11 C

13 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A

15 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B

17 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C

19 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A

21 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B

23 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C

25 ACCESS CONTROL OTH 20 / 1 1#12, #12N, #12G, 3/4"C A

27 MAIN COMM ROOM UPS REC 30 / 2 2#10, #10N, #10G, 3/4"C B

29 C

31 MAIN COMM ROOM UPS REC 30 / 2 2#10, #10N, #10G, 3/4"C A

33 B

35 MAIN COMM ROOM UPS REC 30 / 2 2#10, #10N, #10G, 3/4"C C

37 A

39 TRAP PRIMER OTH 15 / 1 1#12, #12N, #12G, 3/4"C B

41 LOBBY PENDANT LIGHTING LTG 20 / 1 1#12, #12N, #12G, 3/4"C C

43 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A

45 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B

47 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C

49 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A

51 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B

53 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C

55 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A

57 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B

59 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C

61 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A

63 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B

65 SPARE 20 / 1 C

67 SPARE 20 / 1 A

69 SPARE 20 / 1 B

71 SPARE 20 / 1 C

73 SPARE 20 / 1 A

75 SPARE 20 / 1 B

77 SPARE 20 / 1 C

79 SPARE 20 / 1 A

81 SPARE 20 / 1 B

83 SPARE 20 / 1 C

2 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A

4 FIRE ALARM CONTROL PANEL OTH 20 / 1 1#12, #12N, #12G, 3/4"C B

6 CU-5 A/C 15 / 2 2#12, #12G, 3/4"C C

8 A

10 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B

12 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C

14 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A

16 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B

18 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C

20 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A

22 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B

24 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C

26 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A

28 SPACE ONLY B

30 SPACE ONLY C

32 SPACE ONLY A

34 SPACE ONLY B

36 SPACE ONLY C

38 SPACE ONLY A

40 SPACE ONLY B

42 SPACE ONLY C

44 SPACE ONLY A

46 SPACE ONLY B

48 SPACE ONLY C

50 SPACE ONLY A

52 SPACE ONLY B

54 SPACE ONLY C

56 SPACE ONLY A

58 SPACE ONLY B

60 SPACE ONLY C

62 SPACE ONLY A

64 SPACE ONLY B

66 SPACE ONLY C

68 SPACE ONLY A

70 SPACE ONLY B

72 SPACE ONLY C

74 SPACE ONLY A

76 SPACE ONLY B

78 SPACE ONLY C

80 SPACE ONLY A

82 SPACE ONLY B

84 SPACE ONLY C

NOTES:

1) PROVIDE WITH INTEGRAL SURGE SUPPRESSION

BC PNL 120/208 V 3PH 4W 150 A MCB 10 KAIC 60 CKT NEMA 1 FLUSH MTD NEMA 1 1 SECT

NL1C LOCATION: FED FROM: NH1C

CKT LOAD DESCRIPTION LOAD BREAKER CIRCUITNOTES PH

NO. TYPE TRIP / POLES SIZING

1 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A

3 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B

5 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C

7 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A

9 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B

11 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C

13 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A

15 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B

17 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C

19 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A

21 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B

23 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C

25 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A

27 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B

29 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C

31 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A

33 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B

35 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C

37 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A

39 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B

41 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C

43 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A

45 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B

47 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C

49 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A

51 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B

53 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C

55 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A

57 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B

59 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C

2 HAND DRYER OTH 20 / 1 1#12, #12N, #12G, 3/4"C A

4 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B

6 SPACE ONLY C

8 SPACE ONLY A

10 SPACE ONLY B

12 SPACE ONLY C

14 SPACE ONLY A

16 SPACE ONLY B

18 SPACE ONLY C

20 SPACE ONLY A

22 SPACE ONLY B

24 SPACE ONLY C

26 SPACE ONLY A

28 SPACE ONLY B

30 SPACE ONLY C

32 SPACE ONLY A

34 SPACE ONLY B

36 SPACE ONLY C

38 SPACE ONLY A

40 SPACE ONLY B

42 SPACE ONLY C

44 SPACE ONLY A

46 SPACE ONLY B

48 SPACE ONLY C

50 SPACE ONLY A

52 SPACE ONLY B

54 SPACE ONLY C

56 SPACE ONLY A

58 SPACE ONLY B

60 SPACE ONLY C

NOTES:

1) PROVIDE WITH INTEGRAL SURGE SUPPRESSION

BC PNL 120/208 V 3PH 4W 150 A MCB 10 KAIC 60 CKT NEMA 1 FLUSH MTD NEMA 1 1 SECT

NL1D LOCATION: FED FROM: NH1D

CKT LOAD DESCRIPTION LOAD BREAKER CIRCUITNOTES PH

NO. TYPE TRIP / POLES SIZING

1 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A

3 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B

5 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C

7 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A

9 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B

11 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C

13 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A

15 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B

17 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C

19 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A

21 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B

23 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C

25 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A

27 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B

29 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C

31 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A

33 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B

35 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C

37 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A

39 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B

41 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C

43 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A

45 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B

47 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C

49 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A

51 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B

53 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C

55 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A

57 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B

59 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C

2 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A

4 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B

6 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C

8 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A

10 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B

12 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C

14 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A

16 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B

18 IMMUN REFRIGERATOR OTH 20 / 1 1#12, #12N, #12G, 3/4"C C

20 IMMUN REFRIGERATOR OTH 20 / 1 1#12, #12N, #12G, 3/4"C A

22 IMMUN REFRIGERATOR OTH 20 / 1 1#12, #12N, #12G, 3/4"C B

24 LAB REFRIGERATOR OTH 20 / 1 1#12, #12N, #12G, 3/4"C C

26 HAND DRYER OTH 20 / 1 1#12, #12N, #12G, 3/4"C A

28 COPIER OTH 20 / 1 1#12, #12N, #12G, 3/4"C B

30 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C

32 REFRIGERATOR ALARMS 20 / 1 A

34 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B

36 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C

38 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A

40 SPARE 20 / 1 B

42 SPARE 20 / 1 C

44 SPARE 20 / 1 A

46 SPARE 20 / 1 B

48 SPACE ONLY C

50 SPACE ONLY A

52 SPACE ONLY B

54 SPACE ONLY C

56 SPACE ONLY A

58 CU-6 A/C 15 / 2 B

60 C

NOTES:

1) PROVIDE WITH INTEGRAL SURGE SUPPRESSION

PANEL SCHEDULES SHOWN BASED ON EXISTING RECORD DOCUMENT INFORMATION. CIRCUITS OUTSIDE OF HATCHED REGION ARE

NEW TO THIS PROJECT.

Au

stin

811 B

art

on

Sp

rin

gs

Ro

ad

, Su

ite

900, A

ust

in, Te

xas

78704 p

: 512.4

78.7

286 f:

512.4

78.7

441

Sa

n A

nto

nio

4040 B

roa

dw

ay, Su

ite

300, Sa

n A

nto

nio

, Te

xas

78209 p

: 2

10.2

24.6

032 f

: 2

10.2

24.6

453

Engineering Firm:

O'CONNELL ROBERTSON

Firm Registration No. F-2708Revisions:

C:\R

evit P

roje

cts

20

17

\18

260

1_

17_

SE

CH

W R

eno

vation

_M

EP

_C

en

tra

l_aa

nde

rso

n@

oco

nne

llrob

ert

so

n.c

om

.rvt

9/2

7/2

018

12:5

2:4

6 P

20

18

O'C

ON

NELL

RO

BER

TSO

N, IN

C.

SE

HE

AL

TH

& W

EL

LN

ES

S C

EN

TE

R R

EN

OV

AT

ION

S2901 M

ON

TOP

OLI

S D

R., A

USTI

N, TX

78741

CEN

TRA

L H

EA

LTH

08/31/18

Project No. 1826.01CONTRACT DOCUMENTS

ELECTRICAL SCHEDULES

E7.2

NO. DESCRIPTION DATE

1 ADDENDUM 1 09/28/18

1

9/27/2018

Page 14: BidSync - ESBD ......Addendum S.E. Health & Wellness Center Renovations Addendum No. 1 Central Health Page 2 of 3 Austin, Texas Project No. 1826.01 Austin 811 Barton Springs Road,

BC PNL 120/208 V 3PH 4W 150 A MCB 10 KAIC 60 CKT NEMA 1 FLUSH MTD NEMA 1 1 SECT

NL1F LOCATION: FED FROM: NH1F

CKT LOAD DESCRIPTION LOAD BREAKER CIRCUITNOTES PH

NO. TYPE TRIP / POLES SIZING

1 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A

3 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B

5 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C

7 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A

9 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B

11 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C

13 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A

15 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B

17 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C

19 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A

21 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B

23 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C

25 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A

27 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B

29 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C

31 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A

33 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B

35 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C

37 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A

39 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B

41 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C

43 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A

45 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B

47 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C

49 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A

51 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B

53 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C

55 COPIER OTH 20 / 1 1#12, #12N, #12G, 3/4"C A

57 EXTERIOR RECEPTACLE REC 20 / 1 1#12, #12N, #12G, 3/4"C B

59 SPARE 20 / 1 C

61 SPARE 20 / 1 A

2 HAND DRYER OTH 20 / 1 1#12, #12N, #12G, 3/4"C A

4 COMM ROOM UPS REC 30 / 2 2#10, #10N, #10G, 3/4"C B

6 C

8 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A

10 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B

12 CU-4 A/C 15 / 2 2#12, #12G, 3/4"C C

14 A

16 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B

18 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C

20 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A

22 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B

24 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C

26 SPARE 20 / 1 A

28 SPARE 20 / 1 B

30 SPARE 20 / 1 C

32 SPACE ONLY A

34 SPACE ONLY B

36 SPACE ONLY C

38 SPACE ONLY A

40 SPACE ONLY B

42 SPACE ONLY C

44 SPACE ONLY A

46 SPACE ONLY B

48 SPACE ONLY C

50 SPACE ONLY A

52 SPACE ONLY B

54 SPACE ONLY C

56 SPACE ONLY A

58 SPACE ONLY B

60 SPACE ONLY C

NOTES:

1) PROVIDE WITH INTEGRAL SURGE SUPPRESSION

BC PNL 120/208 V 3PH 4W 150 A MCB 10 KAIC 60 CKT NEMA 1 FLUSH MTD NEMA 1 1 SECT

NL1K LOCATION: FED FROM: NH1K

CKT LOAD DESCRIPTION LOAD BREAKER CIRCUITNOTES PH

NO. TYPE TRIP / POLES SIZING

1 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A

3 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B

5 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C

7 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A

9 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B

11 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C

13 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A

15 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B

17 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C

19 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A

21 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B

23 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C

25 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A

27 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B

29 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C

31 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A

33 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B

35 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C

37 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A

39 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B

41 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C

43 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A

45 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B

47 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C

49 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A

51 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B

53 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C

55 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A

57 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B

59 SPARE 20 / 1 C

2 HAND DRYER OTH 20 / 1 1#12, #12N, #12G, 3/4"C A

4 REFRIGERATOR OTH 20 / 1 1#12, #12N, #12G, 3/4"C B

6 REFRIGERATOR OTH 20 / 1 1#12, #12N, #12G, 3/4"C C

8 REFRIGERATOR OTH 20 / 1 1#12, #12N, #12G, 3/4"C A

10 TEMP ALARMS OTH 20 / 1 1#12, #12N, #12G, 3/4"C B

12 REFRIGERATOR OTH 20 / 1 1#12, #12N, #12G, 3/4"C C

14 SPARE 20 / 1 A

16 SPARE 20 / 1 B

18 SPARE 20 / 1 C

20 SPARE 20 / 1 A

22 SPARE 20 / 1 B

24 SPARE 20 / 1 C

26 SPARE 20 / 1 A

28 SPACE ONLY B

30 SPACE ONLY C

32 SPACE ONLY A

34 SPACE ONLY B

36 SPACE ONLY C

38 SPACE ONLY A

40 SPACE ONLY B

42 SPACE ONLY C

44 SPACE ONLY A

46 SPACE ONLY B

48 SPACE ONLY C

50 SPACE ONLY A

52 SPACE ONLY B

54 SPACE ONLY C

56 SPACE ONLY A

58 CU-7 A/C 15 / 2 B

60 C

NOTES:

1) PROVIDE WITH INTEGRAL SURGE SUPPRESSION

FEEDER SCHEDULEFDR

FROM TO DESCRIPTION CIRCUIT SIZINGDEMAND

NO AMPS

F01 NH1 NH1A FEED TO SWITCHBOARD NH1A 5 SETS OF: 3-600, 300N, 3/0G, 4"C 1,059.0

F02 NH1A CH-1 CHILLER CH-1 2 SETS OF: 3-350, 1/0G, 2 1/2"C 391.0

F03 NH1A NH2A PANEL NH2A 3-300, 3/0N, #3G, 2 1/2"C 75.0

F04 NH1A NH2B PANEL NH2B 3-250, 3/0N, #3G, 2 1/2"C 78.4

F05 NH1A NH1B PANEL NH1B 3-4/0, 3/0N, #4G, 2 1/2"C 48.0

F06 NH1A NH1C PANEL NH1C 3-3/0, 1/0N, #4G, 2"C 23.7

F07 NH1A NH1D PANEL NH1D 3-3/0, 1/0N, #4G, 2"C 34.7

F08 NH1A NH1J PANEL NH1J (PHASE 2) 3-3/0, 1/0N, #4G, 2"C 24.2

F09 NH1A NH1H PANEL NH1H 3-250, 2/0N, #3G, 2 1/2"C 40.6

F10 NH1A NH1K PANEL NH1K (PHASE 2) 3-3/0, 1/0N, #4G, 2"C 30.8

F11 NH1A NH1M PANEL NH1M 3-3/0, 1/0N, #4G, 2"C 50.3

F12 NH1A NH1N PANEL NH1N (PHASE 2) 3-4/0, 3/0N, #4G, 2 1/2"C 64.5

F13 NH1A NH1E DISTRIBUTION PANEL NH1E 2 SETS OF: 3-500, 250N, 1/0G, 3"C 159.3

F14 NH1B NL1B XFMR N1B / PANEL NL1B 3#3, #8G, 1 1/4"C 31.9

F15 NH1C NL1C XFMR N1C / PANEL NL1C 3#4, #8G, 1"C 20.8

F16 NH1D NL1D XFMR N1D / PANEL NL1D 3#4, #8G, 1"C 31.9

F17 NH1J NL1J XFMR N1J / PANEL NL1J (PHASE 2) 3#4, #8G, 1"C 20.8

F18 NH1H NL1H XFMR N1H / PANEL NL1H 3#4, #8G, 1"C 37.7

F19 NH1K NL1K XFMR N1K / PANEL NL1K (PHASE 2) 3#4, #8G, 1"C 27.5

F20 NH1M NL1M XFMR N1M / PANEL NL1M 3#4, #8G, 1"C 44.6

F21 NH1N NL1N XFMR N1N / PANEL NL1N (PHASE 2) 3#3, #8G, 1 1/4"C 58.8

F22 N1B NL1B XFMR SECONDARY TO 'NL1B' 3-4/0, 4/0N, #4G IN 2 1/2"

F23 N1C NL1C XFMR SECONDARY TO 'NL1C' 3-1/0, 1/0N, #6G IN 1 1/2"

F24 N1D NL1D XFMR SECONDARY TO 'NL1D' 3-1/0, 1/0N, #6G IN 1 1/2"

F25 N1J NL1J XFMR SECONDARY TO 'NL1J' 3-1/0, 1/0N, #6G IN 1 1/2"

F26 N1H NL1H XFMR SECONDARY TO 'NL1H' 3-1/0, 1/0N, #6G IN 1 1/2"

F27 N1K NL1K XFMR SECONDARY TO 'NL1K' 3-1/0, 1/0N, #6G IN 1 1/2"

F28 N1M NL1M XFMR SECONDARY TO 'NL1M' 3-1/0, 1/0N, #6G IN 1 1/2"

F29 N1N NL1N XFMR SECONDARY TO 'NL1N' 3-4/0, 4/0N, #4G IN 2 1/2"

F30 NH2A AHU-1 AHU-1 3#10, #10G, 3/4"C 15.0

F31 NH2A AHU-2 AHU-2 3#10, #10G, 3/4"C 15.0

F32 NH2A AHU-3 AHU-3 3#10, #10G, 3/4"C 15.0

F34 NH2B AHU-4 AHU-4 3#10, #10G, 3/4"C 15.0

F35 NH2B AHU-5 AHU-5 (PHASE 2) 3#10, #10G, 3/4"C 15.0

F36 NH2B AHU-6 AHU-6 (PHASE 2) 3#10, #10G, 3/4"C 15.0

F38 NH1E CHWP-1 PUMP CHWP-1 3#10, #10G, 3/4"C 14.0

F39 NH1E CHWP-2 PUMP CHWP-2 3#10, #10G, 3/4"C 14.0

F40 NH1E SHWP-1 PUMP SHWP-1 3#10, #10G, 3/4"C 21.0

F41 NH1E SHWP-2 PUMP SHWP-2 3#10, #10G, 3/4"C 21.0

F42 NH1E NH1F PANEL NH1F 3-3/0, 1/0N, #4G, 2"C 28.8

F43 NH1E NH1G PANEL NH1G 3-3/0, 1/0N, #4G, 2"C 39.0

F44 NH1E NH1L PANEL NH1L (PHASE 2) 3-3/0, 1/0N, #4G, 2"C 21.9

F45 NH1F NL1F XFMR N1F / PANEL NL1F 3#4, #8G, 1"C 26.0

F46 NH1G NL1G XFMR N1G / PANEL NL1G 3#4, #8G, 1"C 35.7

F47 NH1L NL1L XFMR N1L / PANEL NL1L (PHASE 2) 3#4, #8G, 1"C 19.0

F48 N1F NL1F XFMR SECONDARY TO 'NL1F' 3-1/0, 1/0N, #6G IN 1 1/2"

F49 N1G NL1G XFMR SECONDARY TO 'NL1G' 3-1/0, 1/0N, #6G IN 1 1/2"

F50 N1L NL1L XFMR SECONDARY TO 'NL1L' 3-1/0, 1/0N, #6G IN 1 1/2"

F51 NH2A NL2A XFMR N2A / PANEL NL2A 3#8, #10G, 3/4"C 19.5

F52 NH2B NL2B XFMR N2B / PANEL NL2B 3#8, #10G, 3/4"C 22.3

F53 N2A NL2A XFMR SECONDARY TO 'NL2A' 3#3, #3N, #8G IN 1"

F54 N2B NL2B XFMR SECONDARY TO 'NL2B' 3#3, #3N, #8G IN 1"

F55 NH1A NH1P PANEL NH1P (PHASE 2) 3-250, 2/0N, #3G, 2 1/2"C 102.1

F56 NH1P NL1P XFMR N1P / PANEL NL1P (PHASE 2) 3#4, #8G, 1"C 21.5

F57 N1P NL1P XFMR SECONDARY TO 'NL1P' 3-1/0, 1/0N, #6G IN 1 1/2"

F58 NH1E NL1E XFMR N1E / PANEL NL1E 3#8, #10G, 3/4"C 5.3

F59 N1E NL1E XFMR SECONDARY TO 'NL1E' 3#3, #3N, #8G IN 1"

S1 UTIL NH1 BUILDING SERVICE 5 SETS OF: 3-600, 300N, 3/0G, 4"C 1,224.9

S2 UTIL FUTURE PHOTO VOLTAIC SYSTEM 1 SETS OF: , 4"C

NOTES:

BC PNL 277/480 V 3PH 4W 225 A MLO 18 KAIC 42 CKT NEMA 1 SURF MTD NEMA 1 1 SECT

NH2B LOCATION: NORTH MECHANICAL ROOMFED FROM: NH1A

CKT LOAD DESCRIPTION LOAD BREAKER CIRCUITNOTES PH

NO. TYPE TRIP / POLES SIZING

1 AHU-4 MOT 30 / 3 3#10, #10G, 3/4"C A

3 B

5 C

7 AHU-5 (PHASE 2) MOT 30 / 3 3#10, #10G, 3/4"C A

9 B

11 C

13 AHU-6 (PHASE 2) MOT 30 / 3 3#10, #10G, 3/4"C A

15 B

17 C

19 SPACE ONLY A

21 SPACE ONLY B

23 SPACE ONLY C

25 SPACE ONLY A

27 SPACE ONLY B

29 SPACE ONLY C

31 SPACE ONLY A

33 SPACE ONLY B

35 SPACE ONLY C

37 SPACE ONLY A

39 SPACE ONLY B

41 SPACE ONLY C

2 XFMR N2B / PANEL NL2B FDR 50 / 3 3#8, #10G, 3/4"C A

4 B

6 C

8 LIGHTING LTG 20 / 1 1#12, #12N, #12G, 3/4"C A

10 LIGHTING LTG 20 / 1 1#12, #12N, #12G, 3/4"C B

12 LIGHTING LTG 20 / 1 1#12, #12N, #12G, 3/4"C C

14 LIGHTING LTG 20 / 1 1#12, #12N, #12G, 3/4"C A

16 LIGHTING LTG 20 / 1 1#12, #12N, #12G, 3/4"C B

18 SPACE ONLY C

20 SPACE ONLY A

22 SPACE ONLY B

24 SPACE ONLY C

26 SPACE ONLY A

28 EGRESS LIGHTS LTG 20 / 1 1#12, #12N, #12G, 3/4"C B

30 EXIT LIGHTS LTG 20 / 1 1#12, #12N, #12G, 3/4"C C

32 SPACE ONLY A

34 SPACE ONLY B

36 SPACE ONLY C

38 SPACE ONLY A

40 SPACE ONLY B

42 SPACE ONLY C

NOTES:

EXISTING RECORD DOCUMENT SCHEDULE FOR REFERENCE ONLY

PANEL SCHEDULES SHOWN BASED ON EXISTING RECORD DOCUMENT INFORMATION. CIRCUITS OUTSIDE OF HATCHED REGION ARE

NEW TO THIS PROJECT.

Au

stin

811 B

art

on

Sp

rin

gs

Ro

ad

, Su

ite

900, A

ust

in, Te

xas

78704 p

: 512.4

78.7

286 f:

512.4

78.7

441

Sa

n A

nto

nio

4040 B

roa

dw

ay, Su

ite

300, Sa

n A

nto

nio

, Te

xas

78209 p

: 2

10.2

24.6

032 f

: 2

10.2

24.6

453

Engineering Firm:

O'CONNELL ROBERTSON

Firm Registration No. F-2708Revisions:

C:\R

evit P

roje

cts

20

17

\18

260

1_

17_

SE

CH

W R

eno

vation

_M

EP

_C

en

tra

l_aa

nde

rso

n@

oco

nne

llrob

ert

so

n.c

om

.rvt

9/2

7/2

018

12:5

2:4

6 P

20

18

O'C

ON

NELL

RO

BER

TSO

N, IN

C.

SE

HE

AL

TH

& W

EL

LN

ES

S C

EN

TE

R R

EN

OV

AT

ION

S2901 M

ON

TOP

OLI

S D

R., A

USTI

N, TX

78741

CEN

TRA

L H

EA

LTH

08/31/18

Project No. 1826.01CONTRACT DOCUMENTS

ELECTRICAL SCHEDULES

E7.3

NO. DESCRIPTION DATE

1 ADDENDUM 1 09/28/18

1

9/27/2018