NOTICE TO BIDDERS
IFB 2018-09-003 Addendum 1
10/9/18
Central Texas Community Health Center d/b/a CommUnityCare
SEHW Remodel and Renovation
Clarification Plans and Drawings can be found on the following websites:
BidSync - https://www.bidsync.com/community-care ESBD - http://esbd.cpa.state.tx.us/ Central Health - https://www.centralhealth.net/sdm_downloads/central-health-southeast-health-
wellness-center-remodel-and-renovation/ Correction See Attachment A, Permit review comments correction/additional design information Questions in Black, Answers in RED
1. If we did not attend the mandatory Pre-Bid meeting, are we still able to submit a proposal? No, because of the two unique projects it was determined vendors could not give accurate construction quote without first seeing the site.
2. Is there an estimated budget/cost? See question 4
3. Is there an estimated start date for the work? Start date will be dependent on the fully executed agreement with the Awarded Vendor. We are hoping to start the project second week of November.
4. Is there an engineer’s estimate on the value of work for bonding purposes? For the bid bond of 5% the estimated construction value is $337,000
AddendumS.E. Health & Wellness Center Renovations Addendum No. 1
Central Health Page 1 of 3
Austin, Texas
Project No. 1826.01
Austin 811 Barton Springs Road, Suite 900, Austin, Texas 78704 p: 512.478.7286 f: 512.478.7441
San Antonio 4040 Broadway, Suite 300, San Antonio, Texas 78209 p: 210.224.6032 f: 210.224.6453
Addendum No. 1
Date: September 28, 2018
S.E. Health & Wellness Center Renovations
Central Health
Austin, Texas
Notice To Bidders
A. This Addendum shall be considered part of the Construction Documents dated August 31, 2018, for the above-mentioned project, as though it had been issued at the same time and incorporated integrally therewith. Where provisions of the following supplementary data differ from those of the original Construction Documents, this Addendum shall govern and take precedence.
B. Bidders are hereby notified that they shall make necessary adjustments in their estimates on account of this Addendum. It will be construed that each bidder’s proposal is submitted
9/27/18
JAMIE BUCHANAN
92680
S
ST
ATEOF TEX
AL DI CE NS
E
PROF
ESSION LA
ENG
INEER
9.26.18 9/27/2018
ATTACHMENT A
Addendum
S.E. Health & Wellness Center Renovations Addendum No. 1
Central Health Page 2 of 3
Austin, Texas
Project No. 1826.01
Austin 811 Barton Springs Road, Suite 900, Austin, Texas 78704 p: 512.478.7286 f: 512.478.7441
San Antonio 4040 Broadway, Suite 300, San Antonio, Texas 78209 p: 210.224.6032 f: 210.224.6453
with full knowledge of all modifications and supplemental data specified herein. Please staple
in the back of your specification book.
SPECIFICATIONS
ITEM 1 Section 00 01 15 – DRAWING INDEX
A. REVISED and REISSUED as part of this Addendum.
DRAWINGS
GENERAL:
ITEM G1 Sheet G1.1 – DRAWING INDEX AND SYMBOLS
B. REVISED and REISSUED as part of this Addendum.
STRUCTURAL:
ITEM S1 Sheet XS-1 – TYPICAL TRENCH DETAIL FOR UNDER-SLAB PLUMBING LINES
A. NEW 11” x 17” sheet is ISSUED as part of this Addendum.
ELECTRICAL:
ITEM E1 Sheet E2.2 – LIGHTING DEMOLITION PLAN
A. REVISED and REISSUED as part of this Addendum.
ITEM E2 Sheet E3.1 – POWER & SPECIAL SYSTEMS PLAN
A. REVISED and REISSUED as part of this Addendum.
ITEM E3 Sheet E3.2 – LIGHTING PLANS
A. REVISED and REISSUED as part of this Addendum.
ITEM E4 Sheet E6.1 – ONE-LINE RISER DIAGRAM
A. NEW 30” x 42” sheet ISSUED as part of this Addendum.
ITEM E5 Sheet E7.1 – ELECTRICAL SCHEDULES & DETAILS
A. REVISED and REISSUED as part of this Addendum.
Addendum
S.E. Health & Wellness Center Renovations Addendum No. 1
Central Health Page 3 of 3
Austin, Texas
Project No. 1826.01
Austin 811 Barton Springs Road, Suite 900, Austin, Texas 78704 p: 512.478.7286 f: 512.478.7441
San Antonio 4040 Broadway, Suite 300, San Antonio, Texas 78209 p: 210.224.6032 f: 210.224.6453
ITEM E6 Sheet E7.2 – ELECTRICAL SCHEDULES
A. NEW 30” x 42” sheet ISSUED as part of this Addendum.
ITEM E7 Sheet E7.3 – ELECTRICAL SCHEDULES
A. NEW 30” x 42” sheet ISSUED as part of this Addendum.
ATTACHMENTS
The following Specification Sections are attached to this Addendum:
• Section 00 01 15 – DRAWING INDEX
The following drawings (11” x 17”) reflect revisions in the work and are attached to this Addendum:
• XS-1 – TYPICAL TRENCH DETAIL FOR UNDER-SLAB PLUMBING LINES
The following drawings (30” x 42”) reflect revisions in the work and are attached to this Addendum:
• G1.1 – DRAWING INDEX AND SYMBOLS
• E2.2 – LIGHTING DEMOLITION PLAN
• E3.1 – POWER & SPECIAL SYSTEMS PLAN
• E3.2 – LIGHTING PLANS
• E6.1 – ONE-LINE RISER DIAGRAM
• E7.1 – ELECTRICAL SCHEDULES & DETAILS
• E7.2 – ELECTRICAL SCHEDULES
• E7.3 – ELECTRICAL SCHEDULES
END OF ADDENDUM NO. 1
S.E. Health & Wellness Center Renovations Central Health Austin, Texas Project No. 1826.01
Drawing Index Section 00 01 15.1 of 1
H:\18\182601\3 Technical\Specifications\Div 00\00 01 15_Drawing Index.docx 9/27/2018 3:55 PM
SECTION 00 01 15 – DRAWING INDEX
GENERAL
SHEET G1.0 COVER SHEET
SHEET G1.1 DRAWING INDEX AND SYMBOLS SHEET G2.1 ADULT TAS ACCESSIBILITY LIFE SAFETY
SHEET LS1.1 LIFE SAFETY INFORMATION ARCHITECTURAL
SHEET A2.1 DEMOLITION PLANS
SHEET A3.1 FLOOR PLANS SHEET A7.1 PARTITION TYPES AND DETAILS SHEET A7.2 DETAILS SHEET A7.3 DOOR, FRAME TYPES, AND FINISH SCHEDULE SHEET A9.1 REFLECTED CEILING PLAN SHEET A9.2 ROOM FINISH PLAN SHEET A10.1 INTERIOR ELEVATIONS FIRE PROTECTION
SHEET FP1.1 FIRE PROTECTION NOTES, SYMBOLS AND FLOOR PLAN
PME
SHEET PME1.1 PME OVERALL PLANS
PLUMBING
SHEET P1.1 PLUMBING NOTES, SYMBOLS AND ABBREVIATIONS
SHEET P2.1 PLUMBING DEMOLITION PLANS SHEET P3.0 PLUMBING UNDERFLOOR PLANS SHEET P3.1 PLUMBING FLOOR PLANS SHEET P5.1 PLUMBING DETAILS MECHANICAL
SHEET M1.1 MECHANICAL NOTES, SYMBOLS, SCHEDULES & DETAILS
SHEET M2.1 MECHANICAL DUCTWORK DEMOLITION PLANS SHEET M3.1 MECHANICAL DUCTWORK PLANS ELECTRICAL
SHEET E1.1 ELECTRICAL NOTES, SYMBOLS AND ABBREVIATIONS
SHEET E2.1 POWER & SPECIAL SYSTEMS DEMOLITION PLANS SHEET E2.2 LIGHTING DEMOLITION PLANS SHEET E3.1 POWER & SPECIAL SYSTEMS PLANS SHEET E3.2 LIGHTING PLANS SHEET E6.1 ONE-LINE RISER DIAGRAM SHEET E7.1 ELECTRICAL SCHEDULES & DETAILS SHEET E7.2 ELECTRICAL SCEDULES SHEET E7.3 ELECTRICAL SCEDULES
END OF DRAWING INDEX
NOTES:
1. ADHESIVE ANCHORING SYSTEM SHALL BE HILTI "HIT-HY 200" OR SIMPSON "ACRYLIC-TIE". FOLLOW ALL MANUFACTURER'S INSTALLATION INSTRUCTIONS.
2. VAPOR RETARDER SHALL MEET THE FOLLOWING PROPERTIES:
a. 15 MIL MINIMUM THICKNESS b. MEET ASTM E 1745 CLASS A c. WATER VAPOR PERMEANCE PER ASTM E96 SHALL BE 0.01 OR LESS
3. LAP JOINTS IN VAPOR RETARDER 6" MIN. USE MANUFACTURER'S STANDARD ADHESIVE OR PRESSURE SENSITIVE TAPE FOR SEALING MEMBRANE AT SEAMS, PIPE
PENETRATIONS, TEARS, ETC.
4. PROVIDE 2-#4X2'-0" DIAGONAL BARS AT RE-ENTRANT CORNERS IN SAWCUT. PLACE AT MID-DEPTH OF SLAB.
5. SOIL REMOVED FOR SLAB TRENCH SHALL BE REPLACED AND RECOMPACTED TO A MINIMUM OF 95% STANDARD PROCTER DENSITY (ASTM D698).
6. PLACE SLAB BACK TO THICKNESS TO MATCH EXISTING WITH A MINIMUM 3,000 PSI NORMAL WEIGHT CONCRETE AND A RATIO OF 0.50 OR LESS.
7. THE CONTRACTOR SHALL ENSURE THAT TRENCHING FOR THE UTILITY LINE IS NOT OVER-EXCAVATED AND THAT NO PORTION OF THE SURROUNDING SLAB-ON-GRADE ISLEFT UNSUPPORTED.
8. CONTRACTOR SHALL PROVIDE A COLD JOINT EVERY 30 LINEAR FEET IN THE PORTION OF NEW CONCRETE SLAB THAT IS PLACED DUE TO UNDER-SLAB TRENCHING.
FULL SLAB DEPTHSAWCUT @ EACHFACE OF TRENCH
#4 @ 3" FROM EACHSIDE OF TRENCH AND16" O.C. MAX.
NEW CONCRETE SLAB -SEE NOTE 6
EQ
EQ
6"
3'-0" MAX.
AS REQ'D.
TYP.
3"
EXIST. SLAB-ON-GRADE
DRILL AND ANCHORDOWELS AS SHOWN@16" O.C. - SEE NOTE 1
PLUMBING LINE - SEE PLUMBING DRAWINGS FOR SIZE AND LOCATION
VAPOR RETARDERSEE NOTE 2
SEE ARCH'L FORVAPOR RETARDERREPAIR DETAIL
F.V
.
REF.
CLIENT
PROJECT
REV. DATE SHEET
9/2
6/2
018 3
:16:5
5 P
M
CENTRAL HEALTH - SE HEALTH & WELNESS CENTER RENOVATIONS
O'CONNELL ROBERTSON
09/26/18 XS-1
210 BARTON SPRINGS RD., SUITE 250512.474.4001AUSTIN, TEXAS 78704
TBPE FIRM F-12778
JQ + TSEN, LLC
JQT PROJECT NO:
TSEN
SCALE: 1 1/2" = 1'-0"1 TYPICAL TRENCH DETAIL FOR UNDER-SLAB PLUMBING LINES
JAMIE BUCHANAN
92680
S
ST
ATEOF TEX
A
L DI CENSE
PROF
ESSION LA
ENG
INEER
9.26.18
ABV ABOVE D DRAIN FRT FIRE RESISTANT TREATED M METER PSF POUNDS PER SQUARE FOOT TB TACK BOARD
ACOUS ACOUSTICAL DBL DOUBLE FT FOOT MAS MASONRY PSI POUNDS PER SQUARE INCH TOC TOP OF CURB
ADJ ADJUSTABLE DEMO DEMOLISH, DEMOLITION FURR FURRING MAX MAXIMUM PT PRESSURE TREATED TOSC TOP OF STRUCTURAL STEEL
AFF ABOVE FINISH FLOOR DEPT DEPARTMENT FWC FABRIC WALL COVERING MDF MEDIUM DENSITY FIBER BOARD TEL TELEPHONE
ALUM ALUMINUM DF DRINKING FOUNTAIN MED MEDIUM QT QUARRY TILE THK THICK
ALT ALTERNATE DIA or Ø DIAMETER GA GAUGE MEMB MEMBRANE QTB QUARRY TILE BASE TOB TOP OF BEAM
ANOD ANODIZED DIM DIMENSION GALV GALVANIZED MTL METAL TOP TOP OF PAVEMENT
APPROX APPROXIMATELY DIV DIVISION GB GRAB BAR MFGR MANUFACTURER RI RISER TOM TOP OF MASONRY
AWP ACOUSTICAL WALL PANEL DL DEAD LOAD GC GENERAL CONTRACTOR MH MANHOLE R RADIUS TOS TOP OF STEEL (BOTTOM OF ROOF DECK)
DN DOWN GCLU GLAZED CMU MIN MINIMUM RB RUBBER BASE TP TOILET PARTITION
BD BOARD DS DOWN SPOUT GI GALVANIZED IRON MISC MISCELLANEOUS RCP REFLECTED CEILING PLAN TV TELEVISION
BLDG BUILDING DSP DRY STAND PIPE GL GLASS MM MILLIMETER RD ROOF DRAIN TYP TYPICAL
BOT BOTTOM DTL DETAIL GLB GLASS BLOCK MO MASONRY OPENING REF REFERENCE TZ TERRAZZO
BW BOTH WAYS DWG DRAWING GMT GLASS MOSAIC TILE MOD MODULAR REFR REFRIGERATOR TZB TERRAZZO BASE
BM BENCH MARK GMTW GLASS MOSAIC TILE WALL MTD MOUNT(ED) (ING) REINF REINFORCING
E EAST GR GRADE MUL MULLION REQ REQUIRE(D) (ING) UC UNDERCUT
C CHANNEL EA EACH GYP GYPSUM REV REVISION UNO UNLESS OTHERWISE NOTED
CC CUBICAL CURTAIN EF EPOXY FLOOR GYP BD GYPSUM BOARD N NORTH RH RIGHT HAND USC UNDER SEPARATE CONTRACT
CK CORK EFB EPOXY FLOOR BASE NAT NATURAL RM ROOM(S)
CAB CABINET EJ EXPANSION JOINT HC HOLLOW CORE NIC NOT IN CONTRACT ROW RIGHT OF WAY VAR VARNISH
CB CHALK BOARD EG END GUARD HDR HEADER NO or # NUMBER RVWC RIGID VINYL WALL COVERING VB VAPOR BARRIER
CFCI CONTRACTOR FURNISH CONTRACTOR INSTALL EL ELEVATION HDW HARDWARE NOM NOMINAL VB VINYL BASE
CFOI CONTRACTOR FURNISH OWNER INSTALL ET EPOXY TERRAZZO FLOOR HDWD HARDWOOD NRC NOISE REDUCTION COEFFICIENT S SOUTH VCT VINYL COMPOSITION TILE
CFT CUBIC FOOT ETB EPOXY TERRAZZO BASE HGT HEIGHT NTS NOT TO SCALE SB SPLASH BLOCK VERT VERTICAL
CG CORNER GUARD ELECT ELECTRICAL HM HOLLOW METAL SC SOLID CORE VEST VESTIBULE
CL, CENTER LINE EM ENTRANCE MAT HORIZ HORIZONTAL OC ON CENTER SCHED SCHEDULE VT VINYL TILE
CLG CEILING EMER EMERGENCY HP HIGH POINT OD OUTSIDE DIAMETER SECT SECTION VTR VENT THROUGH ROOF
CI CAST IRON ENCL ENCLOSURE HR HANDRAIL OFD OVERFLOW ROOF DRAIN SHR SHOWER VWC VINYL WALL COVERING
CLO CLOSET EP EPOXY PAINT HVAC HEATING VENTILATION AIR CONDITIONING OFF OFFICE SIM SIMILAR
CLR CLEAR EQ EQUAL OFOI OWNER FURNISH OWNER INSTALL SPECS SPECIFICATION(S) W WEST
CMP CROWN MOLDING PAINTED EQUIP EQUIPMENT ID INSIDE DIAMETER OFCI OWNER FURNISH CONTRACTOR INSTALL SPK SPEAKER W/ WITH
CMS CROWN MOLDING STAINED EWC ELECTRIC WATER COOLER INCL INCLUDING OVH OVERHEAD SQ SQUARE WBP WOOD BASE PAINTED
CMT CERAMIC MOSAIC TILE EXP EXPANSION INSUL INSULATION OH OPPOSITE HAND SS STAINLESS STEEL WBS WOOD BASE STAINED
CMTB CERAMIC MOSAIC TILE BASE EXIST EXISTING INT INTERIOR OPNG OPENING ST STONE WC WATER CLOSET
CMTW CERAMIC MOSAIC TILE WALL EXT EXTERIOR IPS IRON PIPE SIZE OPP OPPOSITE STC STONE COUNTERTOP WD WOOD
CMU CONCRETE MASONRY UNIT STW STONE WALL WDS WOOD STAINED
CO CASED OPENING FA FIRE ALARM J JOIST P PAINT(ED) STB STONE BASE WIN WINDOW
COL COLUMN FBO FURNISHED BY OTHERS JAN JANITOR PARA PARALLEL STC STAINED CONCRETE W/O WITHOUT
CONC CONCRETE FD FLOOR DRAIN JT JOINT PBD PARTICLE BOARD STD STANDARD WP WOOD PANELING PREFINISHED
CONST CONSTRUCTION FE FIRE EXTINGUISHER PCF POUNDS PER CUBIC FOOT STL STEEL WPP WOOD PANELING PAINTED
CR FEC FIRE EXTINGUISHER CABINET KIT KITCHEN PERF PERFORATED STO STORAGE WPS WOOD PANELING STAINED
CORR
CHAIR RAIL
FFE FINISH FLOOR ELEVATION KO KNOCKOUT PERI PERIMETER STRUCT STRUCTURAL WS WATER STOP
CPT
CORRIDOR
FHC FIRE HOSE CABINET PFL POUNDS PER LINEAR FOOT SV SHEET VINYL WSCT WAINSCOT
CPTB
CARPET
FHVC FIRE HOSE VALVE CABINET L LENGTH/LONG PL PLATE SVB SHEET VINYL COVED BASE WT WEIGHT
CT
CARPET BASE
FE FINISHED END LAB LABORATORY PLAM PLASTIC LAMINATE SYM SYMMETRICAL WWF WELDED WIRE FABRIC
CTB
CERAMIC TILE
FLR FLOOR LAM LAMINATE PLAS PLASTER SYS SYSTEM
CTW
CERAMIC TILE BASE
FOC FACE OF CONCRETE LH LEFT HAND PLYWD PLYWOODCERAMIC TILE WALL
FOF FACE OF FINISH LI LINOLEUM PP PORCELAIN PAVERCTSK COUNTERSINK
FOM FACE OF MASONRY LIB LINOLEUM COVED BASE PPB PORCELAIN PAVER BASECYD CUBIC YARD
FOS FACE OF STUDS LIT LINOLEUM TILE PPW PORCELAIN PAVER WALL
FPRF FIREPROOFING LL LIVE LOAD PR PAIR
NEW CONSTRUCTION
EXISTING CONSTRUCTION
DEMOLITION
HIDDEN LINE
FIRE/SMOKE BARRIERS
1 HOUR FIRE BARRIER
SMOKE BARRIER
2 HOUR FIRE BARRIER
FIRE/SMOKE PARTITIONS
1 HOUR FIRE PARTITION
SMOKE PARTITION
FIRE WALLS
2 HOURS
3 HOURS
BRICK
CONCRETE
CONCRETE BLOCK
EARTH
INSULATION, BATT
INSULATION, RIGID
METAL
PLYWOOD
FINISH GRADE HARDWOOD
WOOD FRAMING THROUGH MEMBER
WOOD FRAMING INTERUPTED MEMBER
PARTITION TYPES
ROOM NUMBER
DOOR NUMBER
KEYNOTE
DEMOLITION NOTE
EQUIPMENT
WINDOW TAG
COLUMN GRID
ELEVATION HEIGHT
REVISION
ELEVATION
SECTION
NORTH ARROW
-
#
?#
?#
#
#
#
A.F.F.0'-0"
#
#
#
N
#
#
SIM
Austin
811 B
art
on S
pring
s Ro
ad
, Suite
900, A
ust
in, Te
xas
78704 p
: 512.4
78.7
286 f: 512.4
78.7
441
San Antonio
4040 B
roa
dw
ay, Suite
300, Sa
n A
nto
nio
, Te
xas
78209 p
: 2
10.2
24.6
032 f: 2
10.2
24.6
453
Revisions:
C:\R
evit P
roje
cts
2017\1
82601_17_C
entral_
Health_R
enovations_A
rch_C
entral_
plu
u.rvt
9/2
7/2
018 4
:55:5
2 P
M©
2018 O
'CO
NN
ELL
RO
BERTS
ON
, IN
C.
SE HEALTH & WELLNESS CENTER RENOVATIONS
2901 M
ON
TOPO
LIS D
R, A
USTI
N, TX
78741
CEN
TRA
L H
EA
LTH
08/31/18
Project No. 1826.01CONTRACT DOCUMENTS
DRAWING INDEX ANDSYMBOLS
G1.1ARCHITECTURAL ABBREVIATIONSARCHITECTURALLINETYPES
ARCHITECTURALMATERIALS
ARCHITECTURALSYMBOLS
DRAWING INDEXGENERAL
G1.0 COVER SHEET
G1.1 DRAWING INDEX AND SYMBOLS
G2.1 ADULT TAS ACCESSIBILITY
LIFE SAFETY
LS1.1 LIFE SAFETY INFORMATION
ARCHITECTURAL
A2.1 DEMOLITION PLANS
A3.1 FLOOR PLANS
A7.1 PARTITION TYPES AND DETAILS
A7.2 DETAILS
A7.3 DOOR AND FRAME TYPES
A9.1 REFLECTED CEILING PLAN
A9.2 ROOM FINISH PLAN
A10.1 INTERIOR ELEVATIONS
FIRE PROTECTION
FP1.1 FIRE PROTECTION NOTES, SYMBOLS AND FLOOR PLAN
PME
PME1.1 PME OVERALL PLANS
PLUMBING
P1.1 PLUMBING NOTES, SYMBOLS AND ABBREVIATIONS
P2.1 PLUMBING DEMOLITION PLANS
P3.0 PLUMBING UNDERFLOOR PLANS
P3.1 PLUMBING FLOOR PLANS
P5.1 PLUMBING DETAILS
MECHANICAL
M1.1 MECHANICAL NOTES, SYMBOLS, SCHEDULES & DETAILS
M2.1 MECHANICAL DUCTWORK DEMOLITION PLANS
M3.1 MECHANICAL DUCTWORK PLANS
ELECTRICAL
E1.1 ELECTRICAL NOTES, SYMBOLS AND ABBREVIATIONS
E2.1 POWER & SPECIAL SYSTEMS DEMOLITION PLANS
E2.2 LIGHTING DEMOLITION PLANS
E3.1 POWER & SPECIAL SYSTEMS PLANS
E3.2 LIGHTING PLANS
E6.1 ONE-LINE RISER DIAGRAM
E7.1 ELECTRICAL SCHEDULES & DETAILS
E7.2 ELECTRICAL SCHEDULES
E7.3 ELECTRICAL SCHEDULES
NOTESGENERAL PROJECT
13. PROTECT ALL EXISTING FINISHES, DOOR FRAMES, EQUIPMENT ANDMATERIALS THAT ARE TO REMAIN IN PLACE. DAMAGE TO EXISTINGCOMPONENTS BY CONTRACTOR SHALL BE REPLACED WITH NEWMATERIAL OF LIKE KIND AND QUALITY THAT MATCH THE EXISTINGSTANDARDS. THE CONTRACTOR IS RESPONSIBLE FOR PREPARINGEXISTING SURFACES TO RECEIVE NEW FINISHES SCHEDULED.
14. REFER TO MECHANICAL, PLUMBING AND ELECTRICAL DRAWINGSFOR OTHER WORK.
15. ELECTRICAL AND MECHANICAL INSTALLATIONS MAY REQUIRE WORKABOVE EXISTING CEILINGS BOTH IN THE AREA OF WORK AND INADJACENT AREAS (POSSIBLY ON OTHER FLOORS). REMOVE ANDREINSTALL (OR REPLACE) CEILING TILES AND GRID AS REQUIRED.REMOVE GYPSUM BOARD AT WALLS AND CEILINGS AND REPLACE ASREQUIRED.
16. UNLESS NOTED OTHERWISE, ALL EXISTING ELECTRICAL OUTLETS &FIXTURES IN REMODELED AREAS ARE TO BE REMOVED & RETURNEDTO OWNER. SEE ELECTRICAL SHEETS FOR DEVICES & CIRCUITS TOBE REUSED.
17. ALL ITEMS AND ASSOCIATED CONNECTIONS ARE TO BE REMOVEDAND TERMINATED AT DESIGNATED POINTS. SERVICE CONNECTIONSSHALL BE SAFELY REMOVED, CAPPED OR PLUGGED IN CONFORMITYWITH LOCAL LAWS AND ORDINANCES, REQUIREMENTS OF PUBLICUTILITY COMPANIES, AND OF THE NATIONAL BOARD OF FIREUNDERWRITERS, AND IN SUCH MANNER AS NOT TO INTERFERE WITHTHE USE OF THE OCCUPIED SPACES IN THE BUILDING.
18. IF A CONDUIT OR UTILITY LINE IS CUT WHILE SLEEVING OR CUTTINGTHE SLAB OR REMOVING A PARTITION, THE CONTRACTOR ISRESPONSIBLE FOR REPAIRING IT IMMEDIATELY.
19. ANY EXISTING TO REMAIN FIREPROOFING OR FIRE ASSEMBLIESDAMAGED DURING CONSTRUCTION ARE TO BE REPAIRED TOORIGINAL FIRE PROTECTION REQUIREMENTS.
20. IMMEDIATELY SEAL ALL PENETRATIONS IN EXISTING STRUCTUREOPENED DURING DEMOLITION WITH FIRESTOPPING MATERIALAND/OR WATERPROOFING.
21. SEAL ALL PENETRATIONS, NEW AND EXISTING, ABOVE CEILINGS ATRATED FIRE WALLS IN AREAS OF WORK.
22. PROVIDE DUST PROTECTION OF ALL SUPPLY AND RETURN AIRDIFFUSERS/GRILLES, AND TO CHANGE THESE DAILY.
23. ANY / ALL CONCRETE SAW CUTTING WILL BE “WET” TO MINIMIZEDUST GENERATION.
24. CONTRACTOR TO PROVIDE VACUUM OR OTHER MEANS TO COLLECTALL WATER AND TO PREVENT ITS FLOW OUTSIDE CONSTRUCTIONAREA.
25. ALL SAW CUTTING AND OTHER HIGH NOISE ACTIVITY ASDETERMINED BY OWNER WILL BE PERFORMED OFF HOURS.
26. CONTRACTOR SHALL PHOTOGRAPH AND OTHERWISE DOCUMENTALL CONDITIONS ADJACENT TO CONSTRUCTION AREAS PRIOR TOTHE START OF WORK. PROVIDE PHOTOS TO OWNER.
27. OWNER SHALL PAY FOR OR REIMBURSE CONTRACTOR FORGENERAL BUILDING PERMIT. ALL OTHER (TRADE) PERMITS SHALL BEPAID FOR BY CONTRACTOR OR ITS SUBCONTRACTORS.
NOTESGENERAL PROJECT
1. GENERAL NOTES APPLY TO ALL SHEETS.
2. THE CONTRACTOR SHALL FURNISH ALL LABOR, MATERIALS, TOOLS,EQUIPMENT, AND RELATED ITEMS REQUIRED TO COMPLETE THEDEMOLITION WORK AS INDICATED BY THE CONTRACT DOCUMENTS.
3. CONTRACTOR TO VERIFY ALL DIMENSIONS.
4. ALL ACCESSIBLE ROUTES (OTHER THAN RAMPS) SHALL NOT EXCEEDA SLOPE OF 1:20, AND CROSS SLOPES SHALL NOT EXCEED A SLOPEOF 1:50
5. THE DRAWINGS INDICATE BUILDING CONDITIONS PER EXISTINGDRAWINGS AND ACTUAL PROJECT INVESTIGATION. THECONTRACTOR SHALL ANTICIPATE POSSIBLE SLIGHT DEVIATIONFROM THESE DRAWINGS. REFER TO ARCHITECTURAL & MEPDRAWINGS AND DETAILS FOR EXTENT OF DEMOLITION.
6. THE CONTRACTOR SHALL SUPERVISE AND DIRECT THE WORK,USING HIS BEST SKILL AND ATTENTION. HE SHALL BE SOLELYRESPONSIBLE FOR ALL MEANS, METHODS, TECHNIQUES,SEQUENCES AND PROCEDURES AND FOR COORDINATING ALLPORTIONS OF THE WORK UNDER THE CONTRACT.
7. INSTALL TEMPORARY DUST PARTITIONS WITH DOORS FORCONSTRUCTION ACCESS AROUND AREAS OF WORK SO THATOPERATIONS IN EXISTING ADJACENT AREAS REMAIN DUST FREEAND ACCESSIBLE TO BUILDING OCCUPANTS. MAINTAIN IN PLACEUNTIL COMPLETION OF CONSTRUCTION.
8. REMOVE ALL BUILDING PARTS AND/OR OTHER ITEMS TO ALLOW FORTHE INSTALLATION AND CONNECTION OF NEW WORK, COORDINATETHE WORK WITH THE HVAC, PLUMBING AND ELECTRICALDEMOLITION DRAWINGS.
9. REMOVAL OF THE BUILDING PARTS SHALL BE PERFORMED IN ASAFE, ORDERLY AND CAREFUL MANNER, WITH THE CONSIDERATIONAT ALL TIMES FOR THE SAFETY AND WELFARE OF THE OWNER,BLDG. OCCUPANTS, & PERSONNEL OF THE CONTRACTOR AND/ORSUBCONTRACTOR.
10. MAINTAIN THE UTILITIES TO OCCUPIED SPACES AT ALL TIMES.COORDINATE ANY UTILITY DOWNTIMES W/ OWNER. PROVIDE 72HOUR ADVANCE NOTICE TO THE OWNER OF INTENDED UTILITY SHUTDOWN AND/OR DISRUPTION.
11. ANY QUESTIONS CONCERNING OWNERSHIP OF SALVAGEABLEMATERIAL SHALL BE ANSWERED BY THE OWNER, OR OWNER'SREPRESENTATIVE. ALL ITEMS OTHER THAN FINISH MATERIALS TOBE REMOVED AS PART OF THIS CONTRACT ARE INDICATED WITHDASHED LINES ON DEMOLITION SHEETS. DISPOSE OF THESEMATERIALS AND ITEMS AFTER CHECKING WITH OWNER FOR ITEMSTO BE SALVAGED. SALVAGE ANY ITEMS REQUIRED TO COMPLETENEW WORK.
12. REMOVE ALL MISCELLANEOUS DEVICES AS REQUIRED TO INSTALLNEW FINISHES, INCLUDING BUT NOT LIMITED TO: PLUMBINGFIXTURES, SIGNAGE, SWITCH PLATES, TELEVISION BRACKETS, WALLOUTLET COVERS, TOILET ACCESSORIES, CORNER GUARDS, ETC.SAVE FOR REINSTALLATION AFTER COMPLETION OF FINISH WORK.
NO. DESCRIPTION DATE
1 ADDENDUM 1 09/28/18
1
1
1
9/27/18
3 3 3 3
M M
33 33
M
M M
3 3
3
M
M
M
N
TRUE NORTH
N
PLAN NORTH
104
104
104
104104
104
104
104
104
104 105
105 105
105
105
105
105
105
105
105
105
105
105
105
105
105
105105
J1-EXIST (TYP U.N.O.)
J1E-EXISTJ1E-EXIST
D1-EXIST
D1-EXIST
D1-EXIST
D1-EXIST D1-EXIST
104
104
104
104
104 104 104
104 104 104
105
D3-EXIST (TYP) D3-EXIST (TYP)
104
104
104
104
104 104 104
104 104 104
104
104 104
104 104 104
104 104
D3-EXIST
D3-EXIST
D3-EXIST
A3E-EXIST
A3-EXIST (TYP U.N.O.)
Au
stin
811 B
art
on
Sp
rin
gs
Ro
ad
, Su
ite
900, A
ust
in, Te
xas
78704 p
: 512.4
78.7
286 f:
512.4
78.7
441
Sa
n A
nto
nio
4040 B
roa
dw
ay, Su
ite
300, Sa
n A
nto
nio
, Te
xas
78209 p
: 2
10.2
24.6
032 f
: 2
10.2
24.6
453
Engineering Firm:
O'CONNELL ROBERTSON
Firm Registration No. F-2708Revisions:
C:\R
evit P
roje
cts
20
17
\18
260
1_
17_
SE
CH
W R
eno
vation
_M
EP
_C
en
tra
l_aa
nde
rso
n@
oco
nne
llrob
ert
so
n.c
om
.rvt
9/2
7/2
018
12:5
2:3
7 P
M©
20
18
O'C
ON
NELL
RO
BER
TSO
N, IN
C.
SE
HE
AL
TH
& W
EL
LN
ES
S C
EN
TE
R R
EN
OV
AT
ION
S2901 M
ON
TOP
OLI
S D
R., A
USTI
N, TX
78741
CEN
TRA
L H
EA
LTH
08/31/18
Project No. 1826.01CONTRACT DOCUMENTS
LIGHTING DEMOLITIONPLANS
E2.2
GENERAL NOTES
1. REFER TO SHEET E1.1 FOR GENERAL ELECTRICAL NOTESTHAT SHALL APPLY TO ALL SHEETS IN THIS SET UNLESSNOTED OTHERWISE IN THE KEYED NOTES.
2. EXISTING ELECTRICAL WORK & LOCATIONS ARE TAKEN FROMAVAILABLE RECORD DOCUMENTS & SITE OBSERVATIONS.CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONSPRIOR TO CONSTRUCTION.
KEYNOTE LEGEND
104 REMOVE AND RETAIN LIGHT FIXTURES FOR RE-USE.
105 REMOVE LIGHT FIXTURES AND TURN OVER TO OWNER FORATTIC STOCK.
SCALE: 1/4" = 1'-0"1LIGHTING DEMOLITION PLAN - BLACKSTOCK CLINIC
SCALE: 1/4" = 1'-0"2LIGHTING DEMOLITION PLAN - GROUP VISIT ROOMS
SCALE: 1/4" = 1'-0"3LIGHTING DEMOLITION PLAN - CONVENIENT CARE CLINIC
NO. DESCRIPTION DATE
1 ADDENDUM 1 09/28/18
RETAIN EXISTING LIGHTING CIRCUITS AND CONTACTORS (AS APPLICABLE) FOR RE-USE
1
9/27/2018
R
R
R
E E
CR
F
R
E
CR
E
E
N
TRUE NORTH
N
PLAN NORTH
+ + ++
CIRCUIT TO EXISTING PNL 'NL1F' U.N.O.
52"
40"
52"
40"
52"
40"
52"
40"
24
2424
24
24
1616
16
16
16
18
18
18
18
2020
20
20
20
22 22
22
22
22
11
1
1
1
1
1
1
POWER CIRCUITED TO EXISTING PNL 'NL1D' U.N.O.
POWER CIRCUITED TO EXISTING PNL 'NL1C' U.N.O.
4D
4D
POWER/DATA POLE FOR WORKSTATIONS BY FURNITURE VENDOR
PROVIDE SPARE JUNCTION BOX AND 1" CONDUIT ABOVE CEILING
FOR OWNER'S FUTURE USE (COORDINATE WITH OWNER)
PROVIDE SPARE JUNCTION BOX AND 1" CONDUIT ABOVE CEILING
FOR OWNER'S FUTURE USE (COORDINATE WITH OWNER)
803
12
10
12
10
12 10 12
12 10 12
10
12
10
12
101210
9
7
9
7
9 7 9
7
9
7
+
PROVIDE TWO NEW RECEPTACLES ON THIS
WALL - COORDINATE LOCATION WITH OWNER;
CONNECT TO NEW CIRCUIT
30
36
PP
10
9
4
4
4
4
1
38 38
11
1
1
1
1
+ ++
+
++
+
+
CIRCUIT TO EXISTING PNL 'NL1B' U.N.O.
FOR UNDER-COUNTER FREEZER
POWER/DATA POLE FROM CEILING TO WITHIN PARTIAL-HEIGHT WALL FOR WORKSTATIONS
803
COORDINATE WITH TV LOCATION
PP
84"
+
PROVIDE PUSH-BUTTON DOOR RELEASE
COORDINATE POWER/DATA ROUTING AND
CONNECTION WITH OFOI FURNITURE
49
40"
52"51
51
51
51
57
55
55 55
55
55 12
12
1212 14
14
14
14
1412
59
61
63
59 61
63
59
63
67
16
16
61
63
16
16
16
18
18
18 18
18
20
20
20
20
20
22
22
2224 24 24
262626
5961
40" 40"
40"
40"40"
40"
52" 52" 52"
52"
52"
52"
CIRCUIT TO EXISTING PNL 'NL1K' U.N.O.
PROVIDE NEW DEDICATED RECEPTACLE AND CIRCUIT FOR REFRIGERATOR; COORDINATE LOCATION WITH OWNER
12
Au
stin
811 B
art
on
Sp
rin
gs
Ro
ad
, Su
ite
900, A
ust
in, Te
xas
78704 p
: 512.4
78.7
286 f:
512.4
78.7
441
Sa
n A
nto
nio
4040 B
roa
dw
ay, Su
ite
300, Sa
n A
nto
nio
, Te
xas
78209 p
: 2
10.2
24.6
032 f
: 2
10.2
24.6
453
Engineering Firm:
O'CONNELL ROBERTSON
Firm Registration No. F-2708Revisions:
C:\R
evit P
roje
cts
20
17
\18
260
1_
17_
SE
CH
W R
eno
vation
_M
EP
_C
en
tra
l_aa
nde
rso
n@
oco
nne
llrob
ert
so
n.c
om
.rvt
9/2
7/2
018
12:5
2:4
0 P
M©
20
18
O'C
ON
NELL
RO
BER
TSO
N, IN
C.
SE
HE
AL
TH
& W
EL
LN
ES
S C
EN
TE
R R
EN
OV
AT
ION
S2901 M
ON
TOP
OLI
S D
R., A
USTI
N, TX
78741
CEN
TRA
L H
EA
LTH
08/31/18
Project No. 1826.01CONTRACT DOCUMENTS
POWER & SPECIALSYSTEMS PLANS
E3.1
KEYNOTE LEGEND
803 RE-INSTALL SALVAGED CARD READER AND TIE TO EXISTINGNEARBY SECURITY PANEL. INSTALLATION AND LABELINGSHALL MATCH EXISTING INSTALLATIONS IN BUILDING.
GENERAL NOTES
1. REFER TO SHEET E1.1 FOR GENERAL ELECTRICAL NOTESTHAT SHALL APPLY TO ALL SHEETS IN THIS SET UNLESSNOTED OTHERWISE IN THE KEYED NOTES.
2. THIS SHEET GENERALLY DEPICTS EQUIPMENT AND DEVICESFOR FLOOR LEVEL TO APPROXIMATELY 48" AFF. SEELIGHTING/CEILING SHEETS FOR ADDITIONAL DEVICESMOUNTED ABOVE THIS LEVEL.
SCALE: 1/4" = 1'-0"1POWER & SPECIAL SYSTEMS PLANS - BLACKSTOCK CLINIC
SCALE: 1/4" = 1'-0"2POWER & SPECIAL SYSTEMS PLANS - GROUP VISIT ROOMS
SCALE: 1/4" = 1'-0"3POWER & SPECIAL SYSTEMS PLANS - CONVENIENT CARE CLINIC
ALL NEW RECEPTACLES SHALL BE TAMPER-RESISTANT PER NEC 2017 REQUIREMENTS.
SCALE: 1/4" = 1'-0"4
POWER & SPECIALSYSTEMS PLANS -IMMUNIZATION
CIRCUIT NUMBERS SHOWN BASED ON RECORD DOCUMENTS - CONTRACTOR SHALL VERIFY CIRCUIT NUMBERS WITH EXISTING PANEL
DIRECTORIES. USE SPARE BREAKER CIRCUITS WHERE AVAILABLE. PROVIDE NEW 20/1
BREAKERS AS NECESSARY.
NO. DESCRIPTION DATE
1 ADDENDUM 1 09/28/18
ALL BRANCH CIRCUITS TO EXAM ROOMS AND OTHER PATIENT CARE AREAS SHALL BE PROVIDED WITH METAL RACEWAY SYSTEM OR HEALTHCARE RATED FLEX CONDUIT (HCF) PER NEC 2017 SECTION 517.13.
1
9/27/2018
M
M M
3 3
3
N
TRUE NORTH
N
PLAN NORTH
CIRCUIT TO EXISTING PNL 'NH1F' CKT #6 U.N.O.
A3
A3
A3
A3
A3
A3
A3
A3
A3
A3
802
TYP
1
POWER CIRCUITED TO EXISTING PNL 'NH1D'
CKT. #4 U.N.O.
POWER CIRCUITED TO EXISTING PNL 'NH1C' CKT. #2 U.N.O.
800
800 800 800 800
800 800 800 800
800 800
800 800
D3-EXIST (TYP)
D3-EXIST (TYP)
D3-EXIST (TYP)
1 1
1" 1"
2"
4"
3"
4"
1"
1" 4"
2"
CIRCUIT TO EXISTING PNL 'NH1B' CKT #22
U.N.O.
801
TYP
800 800
800
800 800
800
800
800
800
800
800
800
800
800
800
A3 A3 A3 A3
A3
A3
A3A3A3A3E-EXIST
A3-EXISTA3-EXIST
J1-EXIST (TYP)
A3-EXIST
A3-EXIST A3-EXIST
A3-EXIST
A3-EXIST
A3-EXIST
A3-EXIST
A3-EXISTA3-EXIST
A3-EXISTA3-EXIST
A3-EXIST
802
TYP
TIE WAITING AREA LIGHTS ONTO
EXISTING THREE-WAY CORRIDOR SWITCH
1
NEW EXAM AND WAITING LIGHTS ON EXISTING
CKT. NH2B-16, CONTACTOR LC-7 TO
MATCH EXISTING LAYOUT
1
Au
stin
811 B
art
on
Sp
rin
gs
Ro
ad
, Su
ite
900, A
ust
in, Te
xas
78704 p
: 512.4
78.7
286 f:
512.4
78.7
441
Sa
n A
nto
nio
4040 B
roa
dw
ay, Su
ite
300, Sa
n A
nto
nio
, Te
xas
78209 p
: 2
10.2
24.6
032 f
: 2
10.2
24.6
453
Engineering Firm:
O'CONNELL ROBERTSON
Firm Registration No. F-2708Revisions:
C:\R
evit P
roje
cts
20
17
\18
260
1_
17_
SE
CH
W R
eno
vation
_M
EP
_C
en
tra
l_aa
nde
rso
n@
oco
nne
llrob
ert
so
n.c
om
.rvt
9/2
7/2
018
12:5
2:4
3 P
M©
20
18
O'C
ON
NELL
RO
BER
TSO
N, IN
C.
SE
HE
AL
TH
& W
EL
LN
ES
S C
EN
TE
R R
EN
OV
AT
ION
S2901 M
ON
TOP
OLI
S D
R., A
USTI
N, TX
78741
CEN
TRA
L H
EA
LTH
08/31/18
Project No. 1826.01CONTRACT DOCUMENTS
LIGHTING PLANS
E3.2
KEYNOTE LEGEND
800 REINSTALL SALVAGED LIGHT FIXTURE AND RECONNECT TOEXISTING LIGHTING CIRCUIT AND (IF APPLICABLE)CONTACTOR.
801 REINSTALL SALVAGED LIGHT FIXTURES FROM DEMOLISHEDWAITING AREA (REF 1/E2.2). PROVIDE PATTERN AS SHOWN;PROTRUSION DOWN FROM CEILING PER FIXTURE INDICATED(E.G. 2").
802 PROVIDE NEW TYPE 'A3' LED LIGHTING FIXTURE EQUAL TOLITHONIA MODEL '2GTL-4-60L-A12125-EZ1-LP835' SERIES TOMATCH APPEARANCE OF EXISTING ACRYLIC TROFFERFLUORESCENT FIXTURES THROUGHOUT BUILDING ASCLOSELY AS POSSIBLE. FIXTURE SHALL SUPPORT 277V.
GENERAL NOTES
1. REFER TO SHEET E1.1 FOR GENERAL ELECTRICAL NOTESTHAT SHALL APPLY TO ALL SHEETS IN THIS SET UNLESSNOTED OTHERWISE IN THE KEYED NOTES.
2. THIS SHEET GENERALLY DEPICTS EQUIPMENT AND DEVICESFOR FLOOR LEVEL TO APPROXIMATELY 48" AFF. SEELIGHTING/CEILING SHEETS FOR ADDITIONAL DEVICESMOUNTED ABOVE THIS LEVEL.
SCALE: 1/4" = 1'-0"1LIGHTING PLAN - BLACKSTOCK CLINIC
SCALE: 1/4" = 1'-0"2LIGHTING PLAN - GROUP VISIT ROOMS
SCALE: 1/4" = 1'-0"3LIGHTING PLAN - CONVENIENT CARE CLINIC
PROVIDE LIGHTING CONTROLS DEVICES AS NECESSARY TO
CONNECT TO EXISTING LIGHTING CONTROLS SYSTEMS
NO. DESCRIPTION DATE
1 ADDENDUM 1 09/28/18
9/27/2018
NH1X
DISTRIBUTION EQUIPMENT
DESIGNATIONSSYSTEM: N = NORMAL
E = EMERGENCY (NEC ART 700)
S = LEGALLY REQD STANDBY (NEC ART 701)
O = OPTIONAL STANDBY (NEC ART 702)
G = ALTERNATE SUPPLY (GENERATOR)
C = CRITICAL (NEC ART 517)
X = LIFE SAFETY (NEC ART 517)
Q = EQUIPMENT (NEC ART 517)
VOLTAGE LEVEL: H = 277/480
L = 120/208
FLOOR: M = MEZZANINE
6 = ROOF
7 = UPPER ROOF
ETC.
SUFFIX(ES) TO PROVIDE LOCATION INFORMATION OR TO
AVOID DUPLICATION.
NOTE:TRANSFORMER DESIGNATIONS SIMILAR EXCEPT "H"/"L"
VOLTAGE DESIGNATIONS OMITTED.
EXISTING AUSTIN ENERGY
PADMOUNT TRANSFORMER
~
~
TO FUTURE PVSYSTEM
DISTRIBUTION PANEL NH1E, 277/480V, 600A, 30 KAIC, (I SCA=16,114A)
NH1
MAIN SWITCHBOARD NH1A, 2000 AMPS, 277/480 VOLTS, 65 KA INTERRUPTING, NEMA 1, (CALCULATED AVAILABLE FAULT CURENT 24,442 AMPS)
DIGITALMETERING
SURGESUPPRESSION
BU
ILD
ING
ST
EE
L
WA
TE
RL
INE
GR
OU
ND
RO
DS
N1B N1C N1D N1J N1H N1K N1M N1N
N1F N1G N1L
N2BN2A
PANEL NH2A, 277/480V, 225A, 18 KAIC, (I SCA=8,508A)
N1P
N1E
2000 AMP, 277/480 VOLT
FUSED NEMA 3R BOLTED PRESSURE
SWITCH WITH GFI PROTECTION
CAPPED FOR FUTURE USE
2000 AMP, 277/480 VOLT
NEMA 3R CT ENCLOSURE AND METER
SOCKET PER AUSTIN ENERGY REQUIREMENTS.
3/0 GROUND
MDF ROOM
GRD BUS
IDF ROOM
GRD BUS
3/0 GROUND
1000 KVA TRANSFORMER,
5.3% IMPEDANCE, AVAILABLE
FAULT CURRENT 25,217 AMPS
I SCA= 24,631 AMPS
PANEL NH2B, 277/480V, 225A, 18 KAIC, (I SCA=11,000A)
F57
F56
F55
F59
F58
NL1E
120/208V
100A
10 KAIC
PNL
F02
3PNF
600A
N3R
NL1P
PNL
NH1P
PNL
F53
F51
NL2A
120/208V
100A
10 KAIC
PNL
F54
F52
NL2B
PNL
S2
F50F49F48
F47F46F45
F44F43F42
F41F40F39F38
F41F40F39F38
F36F35F34F32F31F30
F29F28F27F26F25F24F23F22
F21F20F19F18F17F16F15F14
F13F12F11F10FO9F08F07F06F05F04F03F02
F01
S1
S1
WHAV
10
AHU-3
10
AHU-2
10
AHU-1AHU-6AHU-5AHU-4
15
SHWP-2
15
SHWP-1
10
CHWP-2
10
CHWP-1
NL1F
120/208V
150A
10 KAIC
PNL
NH1F
277/480V
150A
18 KAIC
PNL
NL1G
120/208V
150A
10 KAIC
PNL
NH1G
277/480V
150A
18 KAIC
PNL
NL1H
120/208V
150A
10 KAIC
PNL
NH1H
277/480V
200A
18 KAIC
PNL
NL1L
PNL
NH1L
PNL
CH-1
NL1N
PNL
NH1N
PNL
NL1M
120/208V
150A
10 KAIC
PNL
NH1M
277/480V
150A
18 KAIC
PNL
NL1K
PNL
NH1K
PNL
NL1J
PNL
NH1J
PNL
NL1D
120/208V
150A
10 KAIC
PNL
NH1D
277/480V
150A
18 KAIC
PNL
NL1B
120/208V
225A
10 KAIC
PNL
NH1B
277/480V
225A
30 KAIC
PNL
NL1C
120/208V
150A
10 KAIC
PNL
NH1C
277/480V
150A
18 KAIC
PNL
WHWH
NEW WORK
FUTURE
EXISTING TO REMAIN
EXISTING TO BE DEMOLISHED
ONE-LINE LEGEND
CIRCUIT TAGFDR1
Au
stin
811 B
art
on
Sp
rin
gs
Ro
ad
, Su
ite
900, A
ust
in, Te
xas
78704 p
: 512.4
78.7
286 f:
512.4
78.7
441
Sa
n A
nto
nio
4040 B
roa
dw
ay, Su
ite
300, Sa
n A
nto
nio
, Te
xas
78209 p
: 2
10.2
24.6
032 f
: 2
10.2
24.6
453
Engineering Firm:
O'CONNELL ROBERTSON
Firm Registration No. F-2708Revisions:
C:\R
evit P
roje
cts
20
17
\18
260
1_
17_
SE
CH
W R
eno
vation
_M
EP
_C
en
tra
l_aa
nde
rso
n@
oco
nne
llrob
ert
so
n.c
om
.rvt
9/2
7/2
018
12:5
2:4
4 P
M©
20
18
O'C
ON
NELL
RO
BER
TSO
N, IN
C.
SE
HE
AL
TH
& W
EL
LN
ES
S C
EN
TE
R R
EN
OV
AT
ION
S2901 M
ON
TOP
OLI
S D
R., A
USTI
N, TX
78741
CEN
TRA
L H
EA
LTH
08/31/18
Project No. 1826.01CONTRACT DOCUMENTS
ONE-LINE RISERDIAGRAM
E6.1
NO. DESCRIPTION DATE
1 ADDENDUM 1 09/28/18
1
9/27/2018
LUMINAIRE SUSPENSIONWIRES (#10 MIN) ATTACHEDTO STRUCTURE(TYP EA. CORNER)
3 TWIST MINIMUM (TYP)
FIXTURE WHIP FROMJUNCTION BOX(6FT. LONG MAX.)
LUMINAIRE.REFER TOSCHEDULE
LUMINAIRE MANUFACTURER'S EARTHQUAKECLIP, (4) PER FIXTURE AT CORNERS. ATTACHWITH SHEET METAL SCREW
ACOUSTICAL CEILING TILE(TYP)
ARCHITECTURAL CEILINGGRID
LUMINAIRE.REFER TOSCHEDULE
ON
GREEN GROUNDING
SCREW-#10-32X3/8"
TAPPED HOLE
PER SPECIFICATIONS
PHASE CONDUCTOR
CIRCUIT MARKER ON
CONDUIT
WIRE NUT
(TYPICAL)
(TYPICAL)
IN BOX
GN
G GNNSWITCHING
NOTE:
GREEN GROUND CONDUCTOR SHALL BE CONTINUOUS SO THAT REMOVAL
OF DEVICE WILL NOT INTERFERE WITH GROUND CONTINUITY.
PROVIDE A SEPARATE NEUTRAL FOR EACH CIRCUIT.
∅
∅
JUNCTION BOX
JUNCTION BOX
IN BOX
(TYPICAL)
(TYPICAL)
WIRE NUT
CONDUIT
CIRCUIT MARKER ON
PHASE CONDUCTOR
PER SPECIFICATIONS
TAPPED HOLE
SCREW-#10-32X3/8"
GREEN GROUNDING
1.
2.
SELF TAPPING
SELF TAPPING
OUTBOARD BALLAST
INBOARD BALLAST
1 BUTTON MOMENTARYSWITCH, HUBBELL LVS-1
RED
BLACK (COMMON)
BLUE (CONTROL)
RED
BLACK
WHITE
NEUTRAL
HOT
NE
UT
RA
L
HO
T
OUTBOARD BALLASTPOWER PACK CONTACTS RATEDFOR 20 AMPS
UVPPM POWER PACK SUPPLIES 150mA
RED
BLACK (COMMON)
BLUE (CONTROL)
RED
BLACK
WHITE
INBOARD BALLASTPOWER PACK CONTACTS RATEDFOR 20 AMPS
UVPPM POWER PACK SUPPLIES 150mA
RED (+24VDC)
RED (+24VDC)
DO NOT TIE THE LOW-VOLTAGE RED WIRE(+24VDC) TOGETHER
HOT
HUBBELL BUILDING AUTOMATION LOW VOLTAGE
SENSORS (DEVICES) REQUIRE 33mA EACH
HUBBELL BUILDING AUTOMATION OMNISERIES SENSOR WITH -RP OPTION, SEESPECIFICATIONS FOR MODEL NUMBER
GENERAL NOTES:
1. DETAIL DENOTES HUBBELL PART NUMBERS,
EQUIVALENT SYSTEM UTILIZING APPROVED EQUAL
PARTS FROM OTHER SUPPLIERS IS ACCEPTABLE.
2. DRAWING DENOTES LAYOUT WITH SINGLE SENSOR,
FOR LARGER ROOMS WITH MULTIPLE SENSORS
MODIFY DRAWING PER MANUFACTURER'S
REQUIREMENTS.
ORANGE
ORANGE 1 BUTTON MOMENTARYSWITCH, HUBBELL LVS-1
ROOM LIGHTING
CIRCUIT
2
LUMINAIRE MOUNTING
LAY-IN CEILING DETAILSCALE: NONE
1 RECEPTACLE AND SWITCH WIRING DETAIL
NOT TO SCALE
3 TYPICAL LIGHTING VACANCY CONTROLS
NOT TO SCALE
ELECTRICAL LOAD ANALYSIS - PANEL NH1B
CONNECTED LOAD
EXISTING LOAD REMOVED FROM NH1B
LIGHTS 0.9 kVA
NEW LOADS ADDED TO NH1B
LIGHTS 1.3 kVA
(DEMAND FACTOR = 100%)
NET LOAD 0.3 kVA
480/277V/3PH/4W 0.4 A
EXISTING DESIGN MAX LOAD NH1B (NOTE 1) 49.9 kVA
NEW LOADS ADDED TO NL1B
LIGHTS 0.3 kVA
NET LOAD 50.2 kVA
480/277V/3PH/4W 139.5 A
THE EXISTING 225-AMP FEEDER TO PANEL NH1B REMAINS ADEQUATE
FOR THE REVISED LOAD.
NOTES
1. FROM RECORD DOCUMENTS + 25%
ELECTRICAL LOAD ANALYSIS - PANEL NH1C
CONNECTED LOAD
EXISTING LOAD REMOVED FROM NH1C
LIGHTS 0.4 kVA
NEW LOADS ADDED TO NH1C
LIGHTS 0.3 kVA
(DEMAND FACTOR = 100%)
NET LOAD -0.1 kVA
480/277V/3PH/4W -0.1 A
LIGHTING AND RECEPTACLE LOADS REMAIN RELATIVELY UNCHANGED AS
PART OF THIS RENOVATION. THERE IS AN OVERALL NET REDUCTION IN
CONNECTED ELECTRICAL LOAD FOR THIS DISTRIBUTION PANEL AND
DOWNSTREAM PANELS.
ELECTRICAL LOAD ANALYSIS - PANEL NH1D
CONNECTED LOAD
EXISTING LOAD REMOVED FROM NH1D
LIGHTING 0.3 kVA
NEW LOADS ADDED TO NH1D
LIGHTING 0.5 kVA
(DEMAND FACTOR = 100%)
NET LOAD 0.3 kVA
480/277V/3PH/4W 0.3 A
EXISTING DESIGN MAX LOAD NH1D (NOTE 1) 36.1 kVA
NEW LOADS ADDED TO NH1D
RECEPTACLES 0.3 kVA
NET LOAD 36.4 kVA
480/277V/3PH/4W 101.1 A
THE EXISTING 150-AMP FEEDER TO PANEL NH1D REMAINS ADEQUATE
FOR THE REVISED LOAD.
NOTES
1. FROM RECORD DOCUMENTS + 25%
ELECTRICAL LOAD ANALYSIS - PANEL NH1F
CONNECTED LOAD
EXISTING LOAD REMOVED FROM NH1F
LIGHTING 0.8 kVA
NEW LOADS ADDED TO NH1F
LIGHTING 0.5 kVA
(DEMAND FACTOR = 100%)
NET LOAD -0.3 kVA
480/277V/3PH/4W -0.4 A
LIGHTING AND RECEPTACLE LOADS REMAIN RELATIVELY UNCHANGED AS
PART OF THIS RENOVATION. THERE IS AN OVERALL NET REDUCTION IN
CONNECTED ELECTRICAL LOAD FOR THIS DISTRIBUTION PANEL AND
DOWNSTREAM PANELS.
ELECTRICAL LOAD ANALYSIS - PANEL NL1B
CONNECTED LOAD
EXISTING LOAD REMOVED FROM NL1B
RECEPTACLES 3.8 kVA
NEW LOADS ADDED TO NL1B
RECEPTACLES 4.9 kVA
(DEMAND FACTOR UP TO 10 KVA = 100%)
NET LOAD 1.1 kVA
208/120V/3PH/4W 3.1 A
EXISTING DESIGN MAX LOAD NL1B (NOTE 1) 33.1 kVA
NEW LOADS ADDED TO NL1B
RECEPTACLES 1.1 kVA
NET LOAD 34.2 kVA
208/120V/3PH/4W 95.1 A
THE EXISTING 225-AMP FEEDER TO PANEL NL1B REMAINS ADEQUATE
FOR THE REVISED LOAD.
NOTES
1. FROM RECORD DOCUMENTS + 25%
ELECTRICAL LOAD ANALYSIS - PANEL NL1C
CONNECTED LOAD
EXISTING LOAD REMOVED FROM NL1C
RECEPTACLES 1.4 kVA
NEW LOADS ADDED TO NL1C
RECEPTACLES 2.7 kVA
(DEMAND FACTOR UP TO 10 KVA = 100%)
NET LOAD 1.3 kVA
208/120V/3PH/4W 3.5 A
EXISTING DESIGN MAX LOAD NL1C (NOTE 1) 21.6 kVA
NEW LOADS ADDED TO NL1C
RECEPTACLES 1.3 kVA
NET LOAD 22.9 kVA
208/120V/3PH/4W 63.6 A
THE EXISTING 150-AMP FEEDER TO PANEL NL1C REMAINS ADEQUATE
FOR THE REVISED LOAD.
NOTES
1. FROM RECORD DOCUMENTS + 25%
ELECTRICAL LOAD ANALYSIS - PANEL NL1D
CONNECTED LOAD
EXISTING LOAD REMOVED FROM NL1D
RECEPTACLES 1.1 kVA
NEW LOADS ADDED TO NL1D
RECEPTACLES 4.0 kVA
(DEMAND FACTOR UP TO 10 KVA = 100%)
NET LOAD 2.9 kVA
208/120V/3PH/4W 8.0 A
EXISTING DESIGN MAX LOAD NL1D (NOTE 1) 33.1 kVA
NEW LOADS ADDED TO NL1D
RECEPTACLES 2.9 kVA
NET LOAD 36.0 kVA
208/120V/3PH/4W 100.1 A
THE EXISTING 150-AMP FEEDER TO PANEL NL1B REMAINS ADEQUATE
FOR THE REVISED LOAD.
NOTES
1. FROM RECORD DOCUMENTS + 25%
ELECTRICAL LOAD ANALYSIS - PANEL NL1F
CONNECTED LOAD
EXISTING LOAD REMOVED FROM NL1F
RECEPTACLES 2.2 kVA
NEW LOADS ADDED TO NL1F
RECEPTACLES 4.3 kVA
(DEMAND FACTOR UP TO 10 KVA = 100%)
NET LOAD 2.2 kVA
208/120V/3PH/4W 6.0 A
EXISTING DESIGN MAX LOAD NL1F (NOTE 1) 27.0 kVA
NEW LOADS ADDED TO NL1F
RECEPTACLES 2.2 kVA
NET LOAD 29.2 kVA
208/120V/3PH/4W 81.0 A
THE EXISTING 150-AMP FEEDER TO PANEL NL1B REMAINS ADEQUATE
FOR THE REVISED LOAD.
NOTES
1. FROM RECORD DOCUMENTS + 25%
ELECTRICAL LOAD ANALYSIS - PANEL NL1K
CONNECTED LOAD
EXISTING LOAD REMOVED FROM NL1K
RECEPTACLES 0.0 kVA
NEW LOADS ADDED TO NL1K
RECEPTACLES 0.2 kVA
(DEMAND FACTOR UP TO 10 KVA = 100%)
NET LOAD 0.2 kVA
208/120V/3PH/4W 0.5 A
EXISTING DESIGN MAX LOAD NL1K (NOTE 1) 28.5 kVA
NEW LOADS ADDED TO NL1K
RECEPTACLES 0.2 kVA
NET LOAD 28.7 kVA
208/120V/3PH/4W 79.8 A
THE EXISTING 150-AMP FEEDER TO PANEL NL1K REMAINS ADEQUATE
FOR THE REVISED LOAD.
NOTES
1. FROM RECORD DOCUMENTS + 25%
1
Au
stin
811 B
art
on
Sp
rin
gs
Ro
ad
, Su
ite
900, A
ust
in, Te
xas
78704 p
: 512.4
78.7
286 f:
512.4
78.7
441
Sa
n A
nto
nio
4040 B
roa
dw
ay, Su
ite
300, Sa
n A
nto
nio
, Te
xas
78209 p
: 2
10.2
24.6
032 f
: 2
10.2
24.6
453
Engineering Firm:
O'CONNELL ROBERTSON
Firm Registration No. F-2708Revisions:
C:\R
evit P
roje
cts
20
17
\18
260
1_
17_
SE
CH
W R
eno
vation
_M
EP
_C
en
tra
l_aa
nde
rso
n@
oco
nne
llrob
ert
so
n.c
om
.rvt
9/2
7/2
018
12:5
2:4
5 P
M©
20
18
O'C
ON
NELL
RO
BER
TSO
N, IN
C.
SE
HE
AL
TH
& W
EL
LN
ES
S C
EN
TE
R R
EN
OV
AT
ION
S2901 M
ON
TOP
OLI
S D
R., A
USTI
N, TX
78741
CEN
TRA
L H
EA
LTH
08/31/18
Project No. 1826.01CONTRACT DOCUMENTS
ELECTRICAL SCHEDULES& DETAILS
E7.1
NO. DESCRIPTION DATE
1 ADDENDUM 1 09/28/18
9/27/2018
BC PNL 277/480 V 3PH 4W 225 A MLO 30 KAIC 42 CKT NEMA 1 SURF MTD NEMA 1 1 SECT
NH1B LOCATION: FED FROM: NH1A
CKT LOAD DESCRIPTION LOAD BREAKER CIRCUITNOTES PH
NO. TYPE TRIP / POLES SIZING
1 XFMR N1B / PANEL NL1B FDR 100 / 3 3#3, #8G, 1 1/4"C A
3 B
5 C
7 SPACE ONLY A
9 SPACE ONLY B
11 SPACE ONLY C
13 SPACE ONLY A
15 SPACE ONLY B
17 SPACE ONLY C
19 SPACE ONLY A
21 SPACE ONLY B
23 SPACE ONLY C
25 SPACE ONLY A
27 SPACE ONLY B
29 SPACE ONLY C
31 SPACE ONLY A
33 SPACE ONLY B
35 SPACE ONLY C
37 SPACE ONLY A
39 SPACE ONLY B
41 SPACE ONLY C
2 LIGHTING LTG 20 / 1 1#12, #12N, #12G, 3/4"C A
4 LIGHTING LTG 20 / 1 1#12, #12N, #12G, 3/4"C B
6 LIGHTING LTG 20 / 1 1#12, #12N, #12G, 3/4"C C
8 EXTERIOR LIGHTS LTG 20 / 1 1#10, #10N, #10G, 3/4"C A
10 LTG 20 / 1 1#10, #10N, #10G, 3/4"C B
12 PARKING LOT LIGHTS LTG 30 / 1 1#8, #8N, #10G, 3/4"C C
14 LTG 30 / 1 1#8, #8N, #10G, 3/4"C A
16 LIGHTING LTG 20 / 1 1#12, #12N, #12G, 3/4"C B
18 STAIR LIGHTS LTG 20 / 1 1#12, #12N, #12G, 3/4"C C
20 SPARE 20 / 1 A
22 LIGHTING LTG 20 / 1 1#12, #12N, #12G, 3/4"C B
24 SPARE 20 / 1 C
26 SPARE 20 / 1 A
28 SPARE 20 / 1 B
30 SPARE 20 / 1 C
32 SPACE ONLY A
34 SPACE ONLY B
36 SPACE ONLY C
38 SPACE ONLY A
40 SPACE ONLY B
42 SPACE ONLY C
NOTES:
BC PNL 277/480 V 3PH 4W 150 A MLO 18 KAIC 30 CKT NEMA 1 FLUSH MTD NEMA 1 1 SECT
NH1C LOCATION: FED FROM: NH1A
CKT LOAD DESCRIPTION LOAD BREAKER CIRCUITNOTES PH
NO. TYPE TRIP / POLES SIZING
1 XFMR N1C / PANEL NL1C FDR 70 / 3 3#4, #8G, 1"C A
3 B
5 C
7 SPACE ONLY A
9 SPACE ONLY B
11 SPACE ONLY C
13 SPACE ONLY A
15 SPACE ONLY B
17 SPACE ONLY C
19 SPACE ONLY A
21 SPACE ONLY B
23 SPACE ONLY C
25 SPACE ONLY A
27 SPACE ONLY B
29 SPACE ONLY C
2 LIGHTING LTG 20 / 1 1#12, #12N, #12G, 3/4"C A
4 LIGHTING LTG 20 / 1 1#12, #12N, #12G, 3/4"C B
6 SPARE 20 / 1 C
8 SPARE 20 / 1 A
10 SPARE 20 / 1 B
12 SPARE 20 / 1 C
14 SPACE ONLY A
16 SPACE ONLY B
18 SPACE ONLY C
20 SPACE ONLY A
22 SPACE ONLY B
24 SPACE ONLY C
26 SPACE ONLY A
28 SPACE ONLY B
30 SPACE ONLY C
NOTES:
BC PNL 277/480 V 3PH 4W 150 A MLO 18 KAIC 30 CKT NEMA 1 FLUSH MTD NEMA 1 1 SECT
NH1D LOCATION: FED FROM: NH1A
CKT LOAD DESCRIPTION LOAD BREAKER CIRCUITNOTES PH
NO. TYPE TRIP / POLES SIZING
1 XFMR N1D / PANEL NL1D FDR 70 / 3 3#4, #8G, 1"C A
3 B
5 C
7 SPACE ONLY A
9 SPACE ONLY B
11 SPACE ONLY C
13 SPACE ONLY A
15 SPACE ONLY B
17 SPACE ONLY C
19 SPACE ONLY A
21 SPACE ONLY B
23 SPACE ONLY C
25 SPACE ONLY A
27 SPACE ONLY B
29 SPACE ONLY C
2 LIGHTING LTG 20 / 1 1#12, #12N, #12G, 3/4"C A
4 LIGHTING LTG 20 / 1 1#12, #12N, #12G, 3/4"C B
6 SPARE 20 / 1 C
8 SPARE 20 / 1 A
10 SPARE 20 / 1 B
12 SPARE 20 / 1 C
14 SPACE ONLY A
16 SPACE ONLY B
18 SPACE ONLY C
20 SPACE ONLY A
22 SPACE ONLY B
24 SPACE ONLY C
26 SPACE ONLY A
28 SPACE ONLY B
30 SPACE ONLY C
NOTES:
BC PNL 277/480 V 3PH 4W 150 A MLO 18 KAIC 30 CKT NEMA 1 FLUSH MTD NEMA 1 1 SECT
NH1F LOCATION: FED FROM: NH1E
CKT LOAD DESCRIPTION LOAD BREAKER CIRCUITNOTES PH
NO. TYPE TRIP / POLES SIZING
1 XFMR N1F / PANEL NL1F FDR 70 / 3 3#4, #8G, 1"C A
3 B
5 C
7 SPACE ONLY A
9 SPACE ONLY B
11 SPACE ONLY C
13 SPACE ONLY A
15 SPACE ONLY B
17 SPACE ONLY C
19 SPACE ONLY A
21 SPACE ONLY B
23 SPACE ONLY C
25 SPACE ONLY A
27 SPACE ONLY B
29 SPACE ONLY C
2 LIGHTING LTG 20 / 1 1#12, #12N, #12G, 3/4"C A
4 LIGHTING LTG 20 / 1 1#12, #12N, #12G, 3/4"C B
6 LIGHTING LTG 20 / 1 1#12, #12N, #12G, 3/4"C C
8 SPARE 20 / 1 A
10 SPARE 20 / 1 B
12 SPARE 20 / 1 C
14 SPACE ONLY A
16 SPACE ONLY B
18 SPACE ONLY C
20 SPACE ONLY A
22 SPACE ONLY B
24 SPACE ONLY C
26 SPACE ONLY A
28 SPACE ONLY B
30 SPACE ONLY C
NOTES:
BC PNL 120/208 V 3PH 4W 225 A MCB 10 KAIC 84 CKT NEMA 1 SURF MTD NEMA 1 2 SECT
NL1B LOCATION: FED FROM: NH1B
CKT LOAD DESCRIPTION LOAD BREAKER CIRCUITNOTES PH
NO. TYPE TRIP / POLES SIZING
1 INTERIOR LIGHTING CONTROL OTH 15 / 1 1#12, #12N, #12G, 3/4"C A
3 EXTERIOR LIGHTING CONTROL OTH 15 / 1 1#12, #12N, #12G, 3/4"C B
5 CU-2 A/C 40 / 2 2#8, #10G, 3/4"C C
7 A
9 CU-3 A/C 15 / 2 2#12, #12G, 3/4"C B
11 C
13 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A
15 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B
17 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C
19 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A
21 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B
23 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C
25 ACCESS CONTROL OTH 20 / 1 1#12, #12N, #12G, 3/4"C A
27 MAIN COMM ROOM UPS REC 30 / 2 2#10, #10N, #10G, 3/4"C B
29 C
31 MAIN COMM ROOM UPS REC 30 / 2 2#10, #10N, #10G, 3/4"C A
33 B
35 MAIN COMM ROOM UPS REC 30 / 2 2#10, #10N, #10G, 3/4"C C
37 A
39 TRAP PRIMER OTH 15 / 1 1#12, #12N, #12G, 3/4"C B
41 LOBBY PENDANT LIGHTING LTG 20 / 1 1#12, #12N, #12G, 3/4"C C
43 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A
45 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B
47 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C
49 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A
51 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B
53 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C
55 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A
57 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B
59 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C
61 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A
63 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B
65 SPARE 20 / 1 C
67 SPARE 20 / 1 A
69 SPARE 20 / 1 B
71 SPARE 20 / 1 C
73 SPARE 20 / 1 A
75 SPARE 20 / 1 B
77 SPARE 20 / 1 C
79 SPARE 20 / 1 A
81 SPARE 20 / 1 B
83 SPARE 20 / 1 C
2 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A
4 FIRE ALARM CONTROL PANEL OTH 20 / 1 1#12, #12N, #12G, 3/4"C B
6 CU-5 A/C 15 / 2 2#12, #12G, 3/4"C C
8 A
10 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B
12 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C
14 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A
16 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B
18 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C
20 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A
22 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B
24 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C
26 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A
28 SPACE ONLY B
30 SPACE ONLY C
32 SPACE ONLY A
34 SPACE ONLY B
36 SPACE ONLY C
38 SPACE ONLY A
40 SPACE ONLY B
42 SPACE ONLY C
44 SPACE ONLY A
46 SPACE ONLY B
48 SPACE ONLY C
50 SPACE ONLY A
52 SPACE ONLY B
54 SPACE ONLY C
56 SPACE ONLY A
58 SPACE ONLY B
60 SPACE ONLY C
62 SPACE ONLY A
64 SPACE ONLY B
66 SPACE ONLY C
68 SPACE ONLY A
70 SPACE ONLY B
72 SPACE ONLY C
74 SPACE ONLY A
76 SPACE ONLY B
78 SPACE ONLY C
80 SPACE ONLY A
82 SPACE ONLY B
84 SPACE ONLY C
NOTES:
1) PROVIDE WITH INTEGRAL SURGE SUPPRESSION
BC PNL 120/208 V 3PH 4W 150 A MCB 10 KAIC 60 CKT NEMA 1 FLUSH MTD NEMA 1 1 SECT
NL1C LOCATION: FED FROM: NH1C
CKT LOAD DESCRIPTION LOAD BREAKER CIRCUITNOTES PH
NO. TYPE TRIP / POLES SIZING
1 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A
3 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B
5 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C
7 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A
9 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B
11 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C
13 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A
15 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B
17 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C
19 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A
21 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B
23 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C
25 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A
27 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B
29 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C
31 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A
33 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B
35 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C
37 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A
39 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B
41 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C
43 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A
45 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B
47 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C
49 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A
51 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B
53 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C
55 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A
57 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B
59 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C
2 HAND DRYER OTH 20 / 1 1#12, #12N, #12G, 3/4"C A
4 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B
6 SPACE ONLY C
8 SPACE ONLY A
10 SPACE ONLY B
12 SPACE ONLY C
14 SPACE ONLY A
16 SPACE ONLY B
18 SPACE ONLY C
20 SPACE ONLY A
22 SPACE ONLY B
24 SPACE ONLY C
26 SPACE ONLY A
28 SPACE ONLY B
30 SPACE ONLY C
32 SPACE ONLY A
34 SPACE ONLY B
36 SPACE ONLY C
38 SPACE ONLY A
40 SPACE ONLY B
42 SPACE ONLY C
44 SPACE ONLY A
46 SPACE ONLY B
48 SPACE ONLY C
50 SPACE ONLY A
52 SPACE ONLY B
54 SPACE ONLY C
56 SPACE ONLY A
58 SPACE ONLY B
60 SPACE ONLY C
NOTES:
1) PROVIDE WITH INTEGRAL SURGE SUPPRESSION
BC PNL 120/208 V 3PH 4W 150 A MCB 10 KAIC 60 CKT NEMA 1 FLUSH MTD NEMA 1 1 SECT
NL1D LOCATION: FED FROM: NH1D
CKT LOAD DESCRIPTION LOAD BREAKER CIRCUITNOTES PH
NO. TYPE TRIP / POLES SIZING
1 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A
3 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B
5 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C
7 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A
9 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B
11 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C
13 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A
15 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B
17 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C
19 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A
21 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B
23 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C
25 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A
27 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B
29 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C
31 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A
33 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B
35 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C
37 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A
39 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B
41 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C
43 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A
45 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B
47 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C
49 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A
51 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B
53 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C
55 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A
57 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B
59 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C
2 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A
4 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B
6 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C
8 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A
10 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B
12 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C
14 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A
16 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B
18 IMMUN REFRIGERATOR OTH 20 / 1 1#12, #12N, #12G, 3/4"C C
20 IMMUN REFRIGERATOR OTH 20 / 1 1#12, #12N, #12G, 3/4"C A
22 IMMUN REFRIGERATOR OTH 20 / 1 1#12, #12N, #12G, 3/4"C B
24 LAB REFRIGERATOR OTH 20 / 1 1#12, #12N, #12G, 3/4"C C
26 HAND DRYER OTH 20 / 1 1#12, #12N, #12G, 3/4"C A
28 COPIER OTH 20 / 1 1#12, #12N, #12G, 3/4"C B
30 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C
32 REFRIGERATOR ALARMS 20 / 1 A
34 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B
36 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C
38 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A
40 SPARE 20 / 1 B
42 SPARE 20 / 1 C
44 SPARE 20 / 1 A
46 SPARE 20 / 1 B
48 SPACE ONLY C
50 SPACE ONLY A
52 SPACE ONLY B
54 SPACE ONLY C
56 SPACE ONLY A
58 CU-6 A/C 15 / 2 B
60 C
NOTES:
1) PROVIDE WITH INTEGRAL SURGE SUPPRESSION
PANEL SCHEDULES SHOWN BASED ON EXISTING RECORD DOCUMENT INFORMATION. CIRCUITS OUTSIDE OF HATCHED REGION ARE
NEW TO THIS PROJECT.
Au
stin
811 B
art
on
Sp
rin
gs
Ro
ad
, Su
ite
900, A
ust
in, Te
xas
78704 p
: 512.4
78.7
286 f:
512.4
78.7
441
Sa
n A
nto
nio
4040 B
roa
dw
ay, Su
ite
300, Sa
n A
nto
nio
, Te
xas
78209 p
: 2
10.2
24.6
032 f
: 2
10.2
24.6
453
Engineering Firm:
O'CONNELL ROBERTSON
Firm Registration No. F-2708Revisions:
C:\R
evit P
roje
cts
20
17
\18
260
1_
17_
SE
CH
W R
eno
vation
_M
EP
_C
en
tra
l_aa
nde
rso
n@
oco
nne
llrob
ert
so
n.c
om
.rvt
9/2
7/2
018
12:5
2:4
6 P
M©
20
18
O'C
ON
NELL
RO
BER
TSO
N, IN
C.
SE
HE
AL
TH
& W
EL
LN
ES
S C
EN
TE
R R
EN
OV
AT
ION
S2901 M
ON
TOP
OLI
S D
R., A
USTI
N, TX
78741
CEN
TRA
L H
EA
LTH
08/31/18
Project No. 1826.01CONTRACT DOCUMENTS
ELECTRICAL SCHEDULES
E7.2
NO. DESCRIPTION DATE
1 ADDENDUM 1 09/28/18
1
9/27/2018
BC PNL 120/208 V 3PH 4W 150 A MCB 10 KAIC 60 CKT NEMA 1 FLUSH MTD NEMA 1 1 SECT
NL1F LOCATION: FED FROM: NH1F
CKT LOAD DESCRIPTION LOAD BREAKER CIRCUITNOTES PH
NO. TYPE TRIP / POLES SIZING
1 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A
3 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B
5 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C
7 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A
9 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B
11 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C
13 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A
15 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B
17 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C
19 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A
21 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B
23 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C
25 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A
27 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B
29 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C
31 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A
33 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B
35 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C
37 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A
39 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B
41 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C
43 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A
45 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B
47 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C
49 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A
51 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B
53 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C
55 COPIER OTH 20 / 1 1#12, #12N, #12G, 3/4"C A
57 EXTERIOR RECEPTACLE REC 20 / 1 1#12, #12N, #12G, 3/4"C B
59 SPARE 20 / 1 C
61 SPARE 20 / 1 A
2 HAND DRYER OTH 20 / 1 1#12, #12N, #12G, 3/4"C A
4 COMM ROOM UPS REC 30 / 2 2#10, #10N, #10G, 3/4"C B
6 C
8 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A
10 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B
12 CU-4 A/C 15 / 2 2#12, #12G, 3/4"C C
14 A
16 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B
18 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C
20 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A
22 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B
24 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C
26 SPARE 20 / 1 A
28 SPARE 20 / 1 B
30 SPARE 20 / 1 C
32 SPACE ONLY A
34 SPACE ONLY B
36 SPACE ONLY C
38 SPACE ONLY A
40 SPACE ONLY B
42 SPACE ONLY C
44 SPACE ONLY A
46 SPACE ONLY B
48 SPACE ONLY C
50 SPACE ONLY A
52 SPACE ONLY B
54 SPACE ONLY C
56 SPACE ONLY A
58 SPACE ONLY B
60 SPACE ONLY C
NOTES:
1) PROVIDE WITH INTEGRAL SURGE SUPPRESSION
BC PNL 120/208 V 3PH 4W 150 A MCB 10 KAIC 60 CKT NEMA 1 FLUSH MTD NEMA 1 1 SECT
NL1K LOCATION: FED FROM: NH1K
CKT LOAD DESCRIPTION LOAD BREAKER CIRCUITNOTES PH
NO. TYPE TRIP / POLES SIZING
1 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A
3 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B
5 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C
7 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A
9 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B
11 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C
13 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A
15 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B
17 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C
19 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A
21 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B
23 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C
25 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A
27 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B
29 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C
31 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A
33 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B
35 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C
37 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A
39 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B
41 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C
43 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A
45 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B
47 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C
49 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A
51 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B
53 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C C
55 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C A
57 RECEPTACLES REC 20 / 1 1#12, #12N, #12G, 3/4"C B
59 SPARE 20 / 1 C
2 HAND DRYER OTH 20 / 1 1#12, #12N, #12G, 3/4"C A
4 REFRIGERATOR OTH 20 / 1 1#12, #12N, #12G, 3/4"C B
6 REFRIGERATOR OTH 20 / 1 1#12, #12N, #12G, 3/4"C C
8 REFRIGERATOR OTH 20 / 1 1#12, #12N, #12G, 3/4"C A
10 TEMP ALARMS OTH 20 / 1 1#12, #12N, #12G, 3/4"C B
12 REFRIGERATOR OTH 20 / 1 1#12, #12N, #12G, 3/4"C C
14 SPARE 20 / 1 A
16 SPARE 20 / 1 B
18 SPARE 20 / 1 C
20 SPARE 20 / 1 A
22 SPARE 20 / 1 B
24 SPARE 20 / 1 C
26 SPARE 20 / 1 A
28 SPACE ONLY B
30 SPACE ONLY C
32 SPACE ONLY A
34 SPACE ONLY B
36 SPACE ONLY C
38 SPACE ONLY A
40 SPACE ONLY B
42 SPACE ONLY C
44 SPACE ONLY A
46 SPACE ONLY B
48 SPACE ONLY C
50 SPACE ONLY A
52 SPACE ONLY B
54 SPACE ONLY C
56 SPACE ONLY A
58 CU-7 A/C 15 / 2 B
60 C
NOTES:
1) PROVIDE WITH INTEGRAL SURGE SUPPRESSION
FEEDER SCHEDULEFDR
FROM TO DESCRIPTION CIRCUIT SIZINGDEMAND
NO AMPS
F01 NH1 NH1A FEED TO SWITCHBOARD NH1A 5 SETS OF: 3-600, 300N, 3/0G, 4"C 1,059.0
F02 NH1A CH-1 CHILLER CH-1 2 SETS OF: 3-350, 1/0G, 2 1/2"C 391.0
F03 NH1A NH2A PANEL NH2A 3-300, 3/0N, #3G, 2 1/2"C 75.0
F04 NH1A NH2B PANEL NH2B 3-250, 3/0N, #3G, 2 1/2"C 78.4
F05 NH1A NH1B PANEL NH1B 3-4/0, 3/0N, #4G, 2 1/2"C 48.0
F06 NH1A NH1C PANEL NH1C 3-3/0, 1/0N, #4G, 2"C 23.7
F07 NH1A NH1D PANEL NH1D 3-3/0, 1/0N, #4G, 2"C 34.7
F08 NH1A NH1J PANEL NH1J (PHASE 2) 3-3/0, 1/0N, #4G, 2"C 24.2
F09 NH1A NH1H PANEL NH1H 3-250, 2/0N, #3G, 2 1/2"C 40.6
F10 NH1A NH1K PANEL NH1K (PHASE 2) 3-3/0, 1/0N, #4G, 2"C 30.8
F11 NH1A NH1M PANEL NH1M 3-3/0, 1/0N, #4G, 2"C 50.3
F12 NH1A NH1N PANEL NH1N (PHASE 2) 3-4/0, 3/0N, #4G, 2 1/2"C 64.5
F13 NH1A NH1E DISTRIBUTION PANEL NH1E 2 SETS OF: 3-500, 250N, 1/0G, 3"C 159.3
F14 NH1B NL1B XFMR N1B / PANEL NL1B 3#3, #8G, 1 1/4"C 31.9
F15 NH1C NL1C XFMR N1C / PANEL NL1C 3#4, #8G, 1"C 20.8
F16 NH1D NL1D XFMR N1D / PANEL NL1D 3#4, #8G, 1"C 31.9
F17 NH1J NL1J XFMR N1J / PANEL NL1J (PHASE 2) 3#4, #8G, 1"C 20.8
F18 NH1H NL1H XFMR N1H / PANEL NL1H 3#4, #8G, 1"C 37.7
F19 NH1K NL1K XFMR N1K / PANEL NL1K (PHASE 2) 3#4, #8G, 1"C 27.5
F20 NH1M NL1M XFMR N1M / PANEL NL1M 3#4, #8G, 1"C 44.6
F21 NH1N NL1N XFMR N1N / PANEL NL1N (PHASE 2) 3#3, #8G, 1 1/4"C 58.8
F22 N1B NL1B XFMR SECONDARY TO 'NL1B' 3-4/0, 4/0N, #4G IN 2 1/2"
F23 N1C NL1C XFMR SECONDARY TO 'NL1C' 3-1/0, 1/0N, #6G IN 1 1/2"
F24 N1D NL1D XFMR SECONDARY TO 'NL1D' 3-1/0, 1/0N, #6G IN 1 1/2"
F25 N1J NL1J XFMR SECONDARY TO 'NL1J' 3-1/0, 1/0N, #6G IN 1 1/2"
F26 N1H NL1H XFMR SECONDARY TO 'NL1H' 3-1/0, 1/0N, #6G IN 1 1/2"
F27 N1K NL1K XFMR SECONDARY TO 'NL1K' 3-1/0, 1/0N, #6G IN 1 1/2"
F28 N1M NL1M XFMR SECONDARY TO 'NL1M' 3-1/0, 1/0N, #6G IN 1 1/2"
F29 N1N NL1N XFMR SECONDARY TO 'NL1N' 3-4/0, 4/0N, #4G IN 2 1/2"
F30 NH2A AHU-1 AHU-1 3#10, #10G, 3/4"C 15.0
F31 NH2A AHU-2 AHU-2 3#10, #10G, 3/4"C 15.0
F32 NH2A AHU-3 AHU-3 3#10, #10G, 3/4"C 15.0
F34 NH2B AHU-4 AHU-4 3#10, #10G, 3/4"C 15.0
F35 NH2B AHU-5 AHU-5 (PHASE 2) 3#10, #10G, 3/4"C 15.0
F36 NH2B AHU-6 AHU-6 (PHASE 2) 3#10, #10G, 3/4"C 15.0
F38 NH1E CHWP-1 PUMP CHWP-1 3#10, #10G, 3/4"C 14.0
F39 NH1E CHWP-2 PUMP CHWP-2 3#10, #10G, 3/4"C 14.0
F40 NH1E SHWP-1 PUMP SHWP-1 3#10, #10G, 3/4"C 21.0
F41 NH1E SHWP-2 PUMP SHWP-2 3#10, #10G, 3/4"C 21.0
F42 NH1E NH1F PANEL NH1F 3-3/0, 1/0N, #4G, 2"C 28.8
F43 NH1E NH1G PANEL NH1G 3-3/0, 1/0N, #4G, 2"C 39.0
F44 NH1E NH1L PANEL NH1L (PHASE 2) 3-3/0, 1/0N, #4G, 2"C 21.9
F45 NH1F NL1F XFMR N1F / PANEL NL1F 3#4, #8G, 1"C 26.0
F46 NH1G NL1G XFMR N1G / PANEL NL1G 3#4, #8G, 1"C 35.7
F47 NH1L NL1L XFMR N1L / PANEL NL1L (PHASE 2) 3#4, #8G, 1"C 19.0
F48 N1F NL1F XFMR SECONDARY TO 'NL1F' 3-1/0, 1/0N, #6G IN 1 1/2"
F49 N1G NL1G XFMR SECONDARY TO 'NL1G' 3-1/0, 1/0N, #6G IN 1 1/2"
F50 N1L NL1L XFMR SECONDARY TO 'NL1L' 3-1/0, 1/0N, #6G IN 1 1/2"
F51 NH2A NL2A XFMR N2A / PANEL NL2A 3#8, #10G, 3/4"C 19.5
F52 NH2B NL2B XFMR N2B / PANEL NL2B 3#8, #10G, 3/4"C 22.3
F53 N2A NL2A XFMR SECONDARY TO 'NL2A' 3#3, #3N, #8G IN 1"
F54 N2B NL2B XFMR SECONDARY TO 'NL2B' 3#3, #3N, #8G IN 1"
F55 NH1A NH1P PANEL NH1P (PHASE 2) 3-250, 2/0N, #3G, 2 1/2"C 102.1
F56 NH1P NL1P XFMR N1P / PANEL NL1P (PHASE 2) 3#4, #8G, 1"C 21.5
F57 N1P NL1P XFMR SECONDARY TO 'NL1P' 3-1/0, 1/0N, #6G IN 1 1/2"
F58 NH1E NL1E XFMR N1E / PANEL NL1E 3#8, #10G, 3/4"C 5.3
F59 N1E NL1E XFMR SECONDARY TO 'NL1E' 3#3, #3N, #8G IN 1"
S1 UTIL NH1 BUILDING SERVICE 5 SETS OF: 3-600, 300N, 3/0G, 4"C 1,224.9
S2 UTIL FUTURE PHOTO VOLTAIC SYSTEM 1 SETS OF: , 4"C
NOTES:
BC PNL 277/480 V 3PH 4W 225 A MLO 18 KAIC 42 CKT NEMA 1 SURF MTD NEMA 1 1 SECT
NH2B LOCATION: NORTH MECHANICAL ROOMFED FROM: NH1A
CKT LOAD DESCRIPTION LOAD BREAKER CIRCUITNOTES PH
NO. TYPE TRIP / POLES SIZING
1 AHU-4 MOT 30 / 3 3#10, #10G, 3/4"C A
3 B
5 C
7 AHU-5 (PHASE 2) MOT 30 / 3 3#10, #10G, 3/4"C A
9 B
11 C
13 AHU-6 (PHASE 2) MOT 30 / 3 3#10, #10G, 3/4"C A
15 B
17 C
19 SPACE ONLY A
21 SPACE ONLY B
23 SPACE ONLY C
25 SPACE ONLY A
27 SPACE ONLY B
29 SPACE ONLY C
31 SPACE ONLY A
33 SPACE ONLY B
35 SPACE ONLY C
37 SPACE ONLY A
39 SPACE ONLY B
41 SPACE ONLY C
2 XFMR N2B / PANEL NL2B FDR 50 / 3 3#8, #10G, 3/4"C A
4 B
6 C
8 LIGHTING LTG 20 / 1 1#12, #12N, #12G, 3/4"C A
10 LIGHTING LTG 20 / 1 1#12, #12N, #12G, 3/4"C B
12 LIGHTING LTG 20 / 1 1#12, #12N, #12G, 3/4"C C
14 LIGHTING LTG 20 / 1 1#12, #12N, #12G, 3/4"C A
16 LIGHTING LTG 20 / 1 1#12, #12N, #12G, 3/4"C B
18 SPACE ONLY C
20 SPACE ONLY A
22 SPACE ONLY B
24 SPACE ONLY C
26 SPACE ONLY A
28 EGRESS LIGHTS LTG 20 / 1 1#12, #12N, #12G, 3/4"C B
30 EXIT LIGHTS LTG 20 / 1 1#12, #12N, #12G, 3/4"C C
32 SPACE ONLY A
34 SPACE ONLY B
36 SPACE ONLY C
38 SPACE ONLY A
40 SPACE ONLY B
42 SPACE ONLY C
NOTES:
EXISTING RECORD DOCUMENT SCHEDULE FOR REFERENCE ONLY
PANEL SCHEDULES SHOWN BASED ON EXISTING RECORD DOCUMENT INFORMATION. CIRCUITS OUTSIDE OF HATCHED REGION ARE
NEW TO THIS PROJECT.
Au
stin
811 B
art
on
Sp
rin
gs
Ro
ad
, Su
ite
900, A
ust
in, Te
xas
78704 p
: 512.4
78.7
286 f:
512.4
78.7
441
Sa
n A
nto
nio
4040 B
roa
dw
ay, Su
ite
300, Sa
n A
nto
nio
, Te
xas
78209 p
: 2
10.2
24.6
032 f
: 2
10.2
24.6
453
Engineering Firm:
O'CONNELL ROBERTSON
Firm Registration No. F-2708Revisions:
C:\R
evit P
roje
cts
20
17
\18
260
1_
17_
SE
CH
W R
eno
vation
_M
EP
_C
en
tra
l_aa
nde
rso
n@
oco
nne
llrob
ert
so
n.c
om
.rvt
9/2
7/2
018
12:5
2:4
6 P
M©
20
18
O'C
ON
NELL
RO
BER
TSO
N, IN
C.
SE
HE
AL
TH
& W
EL
LN
ES
S C
EN
TE
R R
EN
OV
AT
ION
S2901 M
ON
TOP
OLI
S D
R., A
USTI
N, TX
78741
CEN
TRA
L H
EA
LTH
08/31/18
Project No. 1826.01CONTRACT DOCUMENTS
ELECTRICAL SCHEDULES
E7.3
NO. DESCRIPTION DATE
1 ADDENDUM 1 09/28/18
1
9/27/2018