DEWA / REVISED V1.2 / BRSH SS_F_DREP_M1FP_7SD5 MLFB: 7SD52215NB997HJ4 Parameter set version: V04.61.04 Device path: C:\Siemens\Digsi4\D4PROJ\Dewa\P7DI\GV\SD\00000037 Author: Creation date: 30.03.11 08:56:26 Last modified: 02.04.11 18:49:12 Operating mode: Offline Comment: Setting values in: Secondary value description P R I N T - C O N T E N T S 1 Configuration - short (column-oriented) 2 1.1 Binary inputs 2 1.2 Binary outputs 2 1.3 LEDs 2 1.4 CFC 3 1.5 System interface IEC 61850 4 SIMATIC DEWA / REVISED V1.2 / BRSH SS_F_DREP_M1FP_7SD5/7SD522 02.04.11 19:00:38 Page 1 of 10

Upload: anupam0103

Post on 18-Aug-2015

225 views

Category:

Documents


2 download

DESCRIPTION

Binary I/O List for SS

TRANSCRIPT

DEWA / REVISED V1.2 / BRSH SS_F_DREP_M1FP_7SD5MLFB:7SD52215NB997HJ 4Parameter set version:V04.61.04Device path:C:\Siemens\Digsi4\D4PROJ \Dewa\P7DI\GV\SD\00000037Author:Creation date: 30.03.11 08:56:26Last modified: 02.04.11 18:49:12Operating mode: OfflineComment:Setting values in:Secondary value descriptionP R I N T-C O N T E N T S1 Configuration - short (column-oriented) 21.1 Binary inputs 21.2 Binary outputs 21.3 LEDs 21.4 CFC 31.5 System interface IEC 61850 4SIMATIC DEWA / REVISED V1.2 / BRSH SS_F_DREP_M1FP_7SD5/7SD522 02.04.11 19:00:38Page 1 of 101 Configuration - short (column-oriented)1.1 Binary inputsBinary inputsNo. Group Information Type Configuration1 P.System Data 2 >Control & Indication Circuit DC Fail SP L2 P.System Data 2 >Main-2 Protection Fail SP L3 P.System Data 2 >CB contact (52a) - R phase SP H4 P.System Data 2 >CB contact (52a) - Y phase SP H5 P.System Data 2 >CB contact (52a) - B phase SP H6 00380 P.System Data 2 >CB aux. contact 3pole Open SP H6 00411 P.System Data 2 >CB1 aux. 3p Open (for AR, CB-Test) SP H7 P.System Data 2 >CB Open command received SP H8 Breaker Failure >CBF INITIATED BY BUSBAR PROTECTION SP H9 P.System Data 2 >VT MCB Tripped SP H10 P.System Data 2 >Trip Coil-1faulty SP H11 Remote Signals >InterTRIP SEND(IS3) - M1Reactor protn. SP H1.2 Binary outputsBO No. Group Information Type Configuration2 03229 Prot. Interface Prot Int 1: Reception of faulty data OUT U2 03230 Prot. Interface Prot Int 1: Total receiption failure OUT U2 03233 Prot. Interface Device table has inconsistent numbers OUT U2 03234 Prot. Interface Device tables are unequal OUT U2 03235 Prot. Interface Differences between common parameters OUT U2 03239 Prot. Interface Prot Int 1: Transmission delay too high OUT U2 03258 Prot. Interface ProtInt1:Permissible error rate exceeded OUT U2 03487 Diff.-Topo Equal IDs in constellation OUT U3 P.System Data 2 >VT MCB Tripped SP U3 00167 Measurem.Superv Failure: Voltage Balance OUT U3 00168 Measurem.Superv Failure: Voltage absent OUT U3 00169 Measurem.Superv VT Fuse Failure (alarm >10s) OUT U3 00170 Measurem.Superv VT Fuse Failure (alarm instantaneous) OUT U4 00511 P.System Data 2 Relay GENERAL TRIP command OUT U4 01476 Breaker Failure BF Trip T1 (local trip) -3pole OUT U4 01494 Breaker Failure BF Trip T2 (busbar trip) OUT U6 01494 Breaker Failure BF Trip T2 (busbar trip) OUT U7 01494 Breaker Failure BF Trip T2 (busbar trip) OUT U8 P.System Data 2 >Control & Indication Circuit DC Fail SP U9 00511 P.System Data 2 Relay GENERAL TRIP command OUT U9 01476 Breaker Failure BF Trip T1 (local trip) -3pole OUT U9 01494 Breaker Failure BF Trip T2 (busbar trip) OUT U10 00290 Measurem.Superv Alarm: Broken current-wire detected L1 OUT U10 00291 Measurem.Superv Alarm: Broken current-wire detected L2 OUT U10 00292 Measurem.Superv Alarm: Broken current-wire detected L3 OUT U11 01494 Breaker Failure BF Trip T2 (busbar trip) OUT U13 00051 Device Device is Operational and Protecting OUT U20 03141 Diff. Prot Diff: General TRIP OUT U20 03517 Intertrip I.Trip: General TRIP OUT U20 04435 DTT Direct Trip DTT TRIP command L123 OUT U20 01476 Breaker Failure BF Trip T1 (local trip) -3pole OUT U20 User-def. Trip Extension to CB SP U21 03141 Diff. Prot Diff: General TRIP OUT U21 03517 Intertrip I.Trip: General TRIP OUT U21 04435 DTT Direct Trip DTT TRIP command L123 OUT U21 01476 Breaker Failure BF Trip T1 (local trip) -3pole OUT U21 User-def. Trip Extension to CB SP U22 03141 Diff. Prot Diff: General TRIP OUT U22 03517 Intertrip I.Trip: General TRIP OUT U22 04435 DTT Direct Trip DTT TRIP command L123 OUT U22 01476 Breaker Failure BF Trip T1 (local trip) -3pole OUT U22 User-def. Trip Extension to CB SP USIMATIC DEWA / REVISED V1.2 / BRSH SS_F_DREP_M1FP_7SD5/7SD522 02.04.11 19:00:38Page 2 of 101.3 LEDsLEDs No. Group Information Type Configuration1 00511 P.System Data 2 Relay GENERAL TRIP command OUT L1 01476 Breaker Failure BF Trip T1 (local trip) -3pole OUT L1 01494 Breaker Failure BF Trip T2 (busbar trip) OUT L2 00503 P.System Data 2 Relay PICKUP Phase L1 OUT U2 P.System Data 2 Relay Trip L1 SP L3 00504 P.System Data 2 Relay PICKUP Phase L2 OUT U3 P.System Data 2 Relay Trip L2 SP L4 00505 P.System Data 2 Relay PICKUP Phase L3 OUT U4 P.System Data 2 Relay Trip L3 SP L5 03141 Diff. Prot Diff: General TRIP OUT L10 01494 Breaker Failure BF Trip T2 (busbar trip) OUT L11 04435 DTT Direct Trip DTT TRIP command L123 OUT L12 03229 Prot. Interface Prot Int 1: Reception of faulty data OUT U12 03230 Prot. Interface Prot Int 1: Total receiption failure OUT U12 03233 Prot. Interface Device table has inconsistent numbers OUT U12 03234 Prot. Interface Device tables are unequal OUT U12 03235 Prot. Interface Differences between common parameters OUT U12 03239 Prot. Interface Prot Int 1: Transmission delay too high OUT U12 03258 Prot. Interface ProtInt1:Permissible error rate exceeded OUT U12 03487 Diff.-Topo Equal IDs in constellation OUT U13 P.System Data 2 >VT MCB Tripped SP U13 00167 Measurem.Superv Failure: Voltage Balance OUT U13 00168 Measurem.Superv Failure: Voltage absent OUT U13 00169 Measurem.Superv VT Fuse Failure (alarm >10s) OUT U13 00170 Measurem.Superv VT Fuse Failure (alarm instantaneous) OUT U13 00290 Measurem.Superv Alarm: Broken current-wire detected L1 OUT U13 00291 Measurem.Superv Alarm: Broken current-wire detected L2 OUT U13 00292 Measurem.Superv Alarm: Broken current-wire detected L3 OUT U14 P.System Data 2 >Control & Indication Circuit DC Fail SP U1.4 CFCNo. Group Information Source Destination00016 Device >DataStop / >Stop data transmission XDevice UnlockDT / Unlock data transmission via BI XDevice Reset LED / Reset LED XDevice Brk OPENED / Breaker OPENED XDevice FdrEARTHED / Feeder EARTHED X00380 P.System Data 2 >CB 3p Open / >CB aux. contact 3pole Open X00503 P.System Data 2 Relay PICKUP L1 / Relay PICKUP Phase L1 X00504 P.System Data 2 Relay PICKUP L2 / Relay PICKUP Phase L2 X00505 P.System Data 2 Relay PICKUP L3 / Relay PICKUP Phase L3 X00511 P.System Data 2 Relay TRIP / Relay GENERAL TRIP command XP.System Data 2 >CB 52a-R / >CB contact (52a) - R phase XP.System Data 2 >CB 52a-Y / >CB contact (52a) - Y phase XP.System Data 2 >CB 52a-B / >CB contact (52a) - B phase XP.System Data 2 >L1 Trip / Relay Trip L1 XP.System Data 2 >L2 Trip / Relay Trip L2 XP.System Data 2 >L3 Trip / Relay Trip L3 XP.System Data 2 >VTMCBTR / >VT MCB Tripped XP.System Data 2 VT Prot Op / VT Protection Operated XP.System Data 2 Comms Fail / Communication Fail XP.System Data 2 ITR.Send / Intertrip Send X03141 Diff. Prot Diff. Gen. TRIP / Diff: General TRIP X03190 Diff. Prot Test Diff. / Diff: Set Teststate of Diff. protection X03517 Intertrip ITrp. Gen. TRIP / I.Trip: General TRIP XRemote Signals >DIST CS / >Distance Carrier Send XRemote Signals >IS3 Send / >InterTRIP SEND(IS3) - M1Reactor protn. XRemote Signals >DIST CR / >Distance Carrier Receive XRemote Signals >IR3 Recieved / >IR3 Rec- M1RP Trip XRemote Signals >CBF ITR send / >CBF Intertrip Send IS1 X XRemote Signals >DEF CS / >DEF Carrier Send X XRemote Signals >CBF ITR RCV / >CBF Intertrip received IR1 XSIMATIC DEWA / REVISED V1.2 / BRSH SS_F_DREP_M1FP_7SD5/7SD522 02.04.11 19:00:38Page 3 of 10No. Group Information Source DestinationRemote Signals >DEF CR / >DEF Carrier Receive X04417 DTT Direct Trip >DTT Trip L123 / >Direct Transfer Trip INPUT 3ph L123 X04435 DTT Direct Trip DTT TRIP L123 / DTT TRIP command L123 XDTT Direct Trip >ITR Recv / >Intertrip Received Indication IR1 X07104 Back-Up O/C >BLOCK O/C I>>/ >BLOCK Backup OverCurrent I>> X07191 Back-Up O/C O/C PICKUP I>>/ Backup O/C Pickup I>> X00168 Measurem.Superv Fail U absent / Failure: Voltage absent X00169 Measurem.Superv VT FuseFail>10s / VT Fuse Failure (alarm >10s) X00170 Measurem.Superv VT FuseFail / VT Fuse Failure (alarm instantaneous) X00290 Measurem.Superv Broken Iwire L1 / Alarm: Broken current-wire detected L1 X00291 Measurem.Superv Broken Iwire L2 / Alarm: Broken current-wire detected L2 X00292 Measurem.Superv Broken Iwire L3 / Alarm: Broken current-wire detected L3 XMeasurem.Superv CT Fail / CT Fail X01307 Earth Fault O/C >EF BLOCK 3I0>>/ >Earth Fault O/C Block 3I0>> X01310 Earth Fault O/C >EF InstTRIP / >Earth Fault O/C Instantaneous trip X01355 Earth Fault O/C EF 3I0>>Pickup / E/F 3I0>>PICKED UP X01369 Earth Fault O/C EF 3I0p TRIP / E/F 3I0p TRIP X01415 Breaker Failure >BF Start 3pole / >BF: External start 3pole X01476 Breaker Failure BF T1-TRIP L123 / BF Trip T1 (local trip) -3pole X01494 Breaker Failure BF T2-TRIP(bus) / BF Trip T2 (busbar trip) XBreaker Failure >BB-CBFINI / >CBF INITIATED BY BUSBAR PROTECTION X03229 Prot. Interface PI1 Data fault / Prot Int 1: Reception of faulty data X03230 Prot. Interface PI1 Datafailure / Prot Int 1: Total receiption failure X03233 Prot. Interface DT inconsistent / Device table has inconsistent numbers X03234 Prot. Interface DT unequal / Device tables are unequal X03235 Prot. Interface Par. different / Differences between common parameters X03239 Prot. Interface PI1 TD alarm / Prot Int 1: Transmission delay too high X03256 Prot. Interface PI1 unsym. / Prot.1: Delay time unsymmetry to large X03258 Prot. Interface PI1 Error / ProtInt1:Permissible error rate exceeded X03484 Diff.-Topo Logout / Local activation of Logout state X03487 Diff.-Topo Equal IDs / Equal IDs in constellation XControl Device Breaker / Breaker XControl Device Breaker / Breaker XControl Device Disc.Swit. / Disconnect Switch XControl Device Disc.Swit. / Disconnect Switch XControl Device EarthSwit / Earth Switch XControl Device EarthSwit / Earth Switch XControl Device Brk Open / Interlocking: Breaker Open XControl Device Brk Close / Interlocking: Breaker Close XControl Device Disc.Open / Interlocking: Disconnect switch Open XControl Device Disc.Close / Interlocking: Disconnect switch Close XControl Device E Sw Open / Interlocking: Earth switch Open XControl Device E Sw Cl. / Interlocking: Earth switch Close XProcess Data >Door open / >Cabinet door open XProcess Data >CB wait / >CB waiting for Spring charged X00601 Measurement IL1 =/ I L1 X00602 Measurement IL2 =/ I L2 X00603 Measurement IL3 =/ I L3 XSet Points(MV) PFControl & Indication Circuit DC Fail SP X CTRL/CIDCFLGGIO1/SPCSO1P.System Data 2 >Main-2 Protection Fail SP X CTRL/M2FAILGGIO1/SPCSO1P.System Data 2 >CB Open command received SP X CTRL/CBOPCDGGIO1/SPCSO1P.System Data 2 >Trip Coil-1faulty SP X CTRL/TC1FLTGGIO1/SPCSO1P.System Data 2 >VT MCB Tripped SP X CTRL/VTMCBTGGIO1/SPCSO1P.System Data 2 VT Protection Operated SP X CTRL/VTPROTGGIO1/SPCSO1P.System Data 2 Communication Fail SP X CTRL/COMFLTGGIO1/SPCSO1P.System Data 2 Intertrip Send SP X CTRL/ITRSDGGIO1/SPCSO103120 Diff. Prot Diff: Active OUT X PROT/PDIF1/ModPROT/PDIF1/BehPROT/PDIF2/ModPROT/PDIF2/BehPROT/PTRC3/ModPROT/PTRC3/Beh03132 Diff. Prot Diff: Fault detection OUT X PROT/PTRC3/Str03133 Diff. Prot Diff: Fault detection in phase L1 OUT X PROT/PTRC3/Str03134 Diff. Prot Diff: Fault detection in phase L2 OUT X PROT/PTRC3/Str03135 Diff. Prot Diff: Fault detection in phase L3 OUT X PROT/PTRC3/Str03136 Diff. Prot Diff: Earth fault detection OUT X PROT/PTRC3/Str03137 Diff. Prot Diff: Fault detection of I-Diff>> OUT X PROT/PDIF2/Str03139 Diff. Prot Diff: Fault detection of I-Diff> OUT X PROT/PDIF1/Str03141 Diff. Prot Diff: General TRIP OUT X X PROT/PTRC3/Op03145 Diff. Prot Diff: TRIP L123 OUT X PROT/PTRC3/Op03148 Diff. Prot Diff: Differential protection is blocked OUT X PROT/PDIF1/ModPROT/PDIF1/BehPROT/PDIF2/ModPROT/PDIF2/BehPROT/PTRC3/ModPROT/PTRC3/Beh03149 Diff. Prot Diff: Diff. protection is switched off OUT X PROT/PDIF1/ModPROT/PDIF1/BehPROT/PDIF2/ModPROT/PDIF2/BehPROT/PTRC3/ModPROT/PTRC3/Beh03176 Diff. Prot Diff: Fault detection L1 (only) OUT X PROT/PTRC3/StrA03177 Diff. Prot Diff: Fault detection L1E OUT X PROT/PTRC3/StrAG03178 Diff. Prot Diff: Fault detection L2 (only) OUT X PROT/PTRC3/StrB03179 Diff. Prot Diff: Fault detection L2E OUT X PROT/PTRC3/StrBG03180 Diff. Prot Diff: Fault detection L12 OUT X PROT/PTRC3/StrAB03181 Diff. Prot Diff: Fault detection L12E OUT X PROT/PTRC3/StrABG03182 Diff. Prot Diff: Fault detection L3 (only) OUT X PROT/PTRC3/StrC03183 Diff. Prot Diff: Fault detection L3E OUT X PROT/PTRC3/StrCG03184 Diff. Prot Diff: Fault detection L31 OUT X PROT/PTRC3/StrCA03185 Diff. Prot Diff: Fault detection L31E OUT X PROT/PTRC3/StrCAG03186 Diff. Prot Diff: Fault detection L23 OUT X PROT/PTRC3/StrBC03187 Diff. Prot Diff: Fault detection L23E OUT X PROT/PTRC3/StrBCG03188 Diff. Prot Diff: Fault detection L123 OUT X PROT/PTRC3/StrABC03189 Diff. Prot Diff: Fault detection L123E OUT X PROT/PTRC3/StrABCG03190 Diff. Prot Diff: Set Teststate of Diff. protection IntSP X PROT/PDIF1/ModPROT/PDIF1/BehPROT/PDIF1/StrPROT/PDIF1/OpPROT/PDIF2/ModPROT/PDIF2/BehPROT/PDIF2/StrPROT/PDIF2/OpPROT/PTRC3/ModPROT/PTRC3/BehSIMATIC DEWA / REVISED V1.2 / BRSH SS_F_DREP_M1FP_7SD5/7SD522 02.04.11 19:00:38Page 6 of 10No. Group Information Type Source Destination Extended Assigned IEC 61850 object (LD /LN / DO)03193 Diff. Prot Diff: Commissioning state is active OUT X PROT/PDIF1/ModPROT/PDIF1/BehPROT/PDIF1/StrPROT/PDIF1/OpPROT/PDIF2/ModPROT/PDIF2/BehPROT/PDIF2/StrPROT/PDIF2/OpPROT/PTRC3/ModPROT/PTRC3/Beh03517 Intertrip I.Trip: General TRIP OUT XRemote Signals >Distance Carrier Send SP XRemote Signals >InterTRIP SEND(IS3) - M1Reactor protn. SP XRemote Signals >Distance Carrier Receive OUT XRemote Signals >IR3 Rec- M1RP Trip OUT XRemote Signals >CBF Intertrip Send IS1 SP XRemote Signals >DEF Carrier Send SP XRemote Signals >CBF Intertrip received IR1 OUT XRemote Signals >DEF Carrier Receive OUT X04417 DTT Direct Trip >Direct Transfer Trip INPUT 3ph L123 SP X04435 DTT Direct Trip DTT TRIP command L123 OUT XDTT Direct Trip >Intertrip Received Indication IR1 SP X CTRL/ITRRECGGIO1/SPCSO107104 Back-Up O/C >BLOCK Backup OverCurrent I>> SP X PROT/PTOC3/ModPROT/PTOC3/Beh07105 Back-Up O/C >BLOCK Backup OverCurrent I> SP X PROT/PTOC2/ModPROT/PTOC2/Beh07106 Back-Up O/C >BLOCK Backup OverCurrent Ip SP X PROT/PTOC1/ModPROT/PTOC1/Beh07130 Back-Up O/C >BLOCK I-STUB SP X PROT/PTOC4/ModPROT/PTOC4/Beh07131 Back-Up O/C >Enable I-STUB-Bus function SP X PROT/PTOC4/ModPROT/PTOC4/Beh07151 Back-Up O/C Backup O/C is switched OFF OUT X PROT/PTOC1/ModPROT/PTOC1/BehPROT/PTOC2/ModPROT/PTOC2/BehPROT/PTOC3/ModPROT/PTOC3/BehPROT/PTOC4/ModPROT/PTOC4/BehPROT/PTOC9/ModPROT/PTOC9/Beh07152 Back-Up O/C Backup O/C is BLOCKED OUT X PROT/PTOC1/ModPROT/PTOC1/BehPROT/PTOC2/ModPROT/PTOC2/BehPROT/PTOC3/ModPROT/PTOC3/BehPROT/PTOC4/ModPROT/PTOC4/BehPROT/PTOC9/ModPROT/PTOC9/Beh07153 Back-Up O/C Backup O/C is ACTIVE OUT X PROT/PTOC1/ModPROT/PTOC1/BehPROT/PTOC2/ModPROT/PTOC2/BehPROT/PTOC3/ModPROT/PTOC3/BehPROT/PTOC4/ModPROT/PTOC4/BehPROT/PTOC9/ModPROT/PTOC9/Beh07191 Back-Up O/C Backup O/C Pickup I>> OUT X PROT/PTOC3/Str07192 Back-Up O/C Backup O/C Pickup I> OUT X PROT/PTOC2/Str07193 Back-Up O/C Backup O/C Pickup Ip OUT X PROT/PTOC1/Str07201 Back-Up O/C O/C I-STUB Pickup OUT X PROT/PTOC4/Str07221 Back-Up O/C Backup O/C TRIP I>> OUT X PROT/PTOC3/Op07222 Back-Up O/C Backup O/C TRIP I> OUT X PROT/PTOC2/Op07223 Back-Up O/C Backup O/C TRIP Ip OUT X PROT/PTOC1/Op07235 Back-Up O/C O/C I-STUB TRIP OUT X PROT/PTOC4/Op00161 Measurem.Superv Failure: General Current Supervision OUT X00163 Measurem.Superv Failure: Current Balance OUT XSIMATIC DEWA / REVISED V1.2 / BRSH SS_F_DREP_M1FP_7SD5/7SD522 02.04.11 19:00:38Page 7 of 10No. Group Information Type Source Destination Extended Assigned IEC 61850 object (LD /LN / DO)00164 Measurem.Superv Failure: General Voltage Supervision OUT X00167 Measurem.Superv Failure: Voltage Balance OUT X00168 Measurem.Superv Failure: Voltage absent OUT X00169 Measurem.Superv VT Fuse Failure (alarm >10s) OUT X00170 Measurem.Superv VT Fuse Failure (alarm instantaneous) OUT X00296 Measurem.Superv Current summation superv is switched OFF OUT X00290 Measurem.Superv Alarm: Broken current-wire detected L1 OUT X X PROT/PDIF3/ModPROT/PDIF3/Beh00291 Measurem.Superv Alarm: Broken current-wire detected L2 OUT X X PROT/PDIF3/ModPROT/PDIF3/Beh00292 Measurem.Superv Alarm: Broken current-wire detected L3 OUT X X PROT/PDIF3/ModPROT/PDIF3/BehMeasurem.Superv CT Fail SP X CTRL/CTFAILGGIO1/SPCSO101305 Earth Fault O/C >Earth Fault O/C Block 3I0>>> SP X PROT/PTOC7/ModPROT/PTOC7/Beh01307 Earth Fault O/C >Earth Fault O/C Block 3I0>> SP X PROT/PTOC6/ModPROT/PTOC6/Beh01308 Earth Fault O/C >Earth Fault O/C Block 3I0> SP X PROT/PTOC5/ModPROT/PTOC5/Beh01309 Earth Fault O/C >Earth Fault O/C Block 3I0p SP X PROT/PTOC8/ModPROT/PTOC8/Beh01331 Earth Fault O/C Earth fault protection is switched OFF OUT X PROT/PTOC5/ModPROT/PTOC5/BehPROT/PTOC6/ModPROT/PTOC6/BehPROT/PTOC7/ModPROT/PTOC7/BehPROT/PTOC8/ModPROT/PTOC8/Beh01332 Earth Fault O/C Earth fault protection is BLOCKED OUT X PROT/PTOC5/ModPROT/PTOC5/BehPROT/PTOC6/ModPROT/PTOC6/BehPROT/PTOC7/ModPROT/PTOC7/BehPROT/PTOC8/ModPROT/PTOC8/Beh01333 Earth Fault O/C Earth fault protection is ACTIVE OUT X PROT/PTOC5/ModPROT/PTOC5/BehPROT/PTOC6/ModPROT/PTOC6/BehPROT/PTOC7/ModPROT/PTOC7/Beh01354 Earth Fault O/C E/F 3I0>>>PICKED UP OUT X PROT/PTOC7/Str01355 Earth Fault O/C E/F 3I0>>PICKED UP OUT X PROT/PTOC6/Str01356 Earth Fault O/C E/F 3I0>PICKED UP OUT X PROT/PTOC5/Str01357 Earth Fault O/C E/F 3I0p PICKED UP OUT X PROT/PTOC8/Str01358 Earth Fault O/C E/F picked up FORWARD OUT X PROT/PTOC5/StrPROT/PTOC6/StrPROT/PTOC7/StrPROT/PTOC8/StrPROT/PTRC1/Str01359 Earth Fault O/C E/F picked up REVERSE OUT X PROT/PTOC5/StrPROT/PTOC6/StrPROT/PTOC7/StrPROT/PTOC8/StrPROT/PTRC1/Str01366 Earth Fault O/C E/F 3I0>>>TRIP OUT X PROT/PTOC7/Op01367 Earth Fault O/C E/F 3I0>>TRIP OUT X PROT/PTOC6/Op01368 Earth Fault O/C E/F 3I0>TRIP OUT X PROT/PTOC5/Op01369 Earth Fault O/C E/F 3I0p TRIP OUT X PROT/PTOC8/Op01120 Fault Locator Flt Locator: Distance [%] to fault VI X PROT/RFLO1/FltDisPrc01133 Fault Locator Fault locator setting error K0,angle(K0) OUT X PROT/RFLO1/Health01111 Fault Locator Fault locator active OUT X PROT/RFLO1/ModPROT/RFLO1/Beh01451 Breaker Failure Breaker failure is switched OFF OUT X PROT/RBRF1/ModPROT/RBRF1/Beh01452 Breaker Failure Breaker failure is BLOCKED OUT X PROT/RBRF1/ModPROT/RBRF1/Beh01461 Breaker Failure Breaker failure protection started OUT X PROT/RBRF1/Str01476 Breaker Failure BF Trip T1 (local trip) -3pole OUT X PROT/RBRF1/OpInSIMATIC DEWA / REVISED V1.2 / BRSH SS_F_DREP_M1FP_7SD5/7SD522 02.04.11 19:00:38Page 8 of 10No. Group Information Type Source Destination Extended Assigned IEC 61850 object (LD /LN / DO)01494 Breaker Failure BF Trip T2 (busbar trip) OUT X X PROT/RBRF1/OpEx03229 Prot. Interface Prot Int 1: Reception of faulty data OUT X03230 Prot. Interface Prot Int 1: Total receiption failure OUT X03233 Prot. Interface Device table has inconsistent numbers OUT X03234 Prot. Interface Device tables are unequal OUT X03235 Prot. Interface Differences between common parameters OUT X03239 Prot. Interface Prot Int 1: Transmission delay too high OUT X03258 Prot. Interface ProtInt1:Permissible error rate exceeded OUT X03487 Diff.-Topo Equal IDs in constellation OUT X03491 Diff.-Topo Relay 1 in Login state OUT X MEAS/MMXU2/ModMEAS/MMXU2/Beh03492 Diff.-Topo Relay 2 in Login state OUT X MEAS/MMXU3/ModMEAS/MMXU3/BehCntrl Authority Control Authority IntSP X CTRL/LLN0/LocControl Device Breaker CF_D12 X CTRL/Q0XCBR1CTRL/Q0CSWI1Circuit breakerQ0 OpCnt=Control Device Breaker DP X CTRL/Q0XCBR1CTRL/Q0CSWI1Circuit breakerQ0 OpCnt=Control Device Disconnect Switch CF_D2 X CTRL/Q1XSWI1CTRL/Q1CSWI1DisconnectorQ1 OpCnt=Control Device Disconnect Switch DP X CTRL/Q1XSWI1CTRL/Q1CSWI1DisconnectorQ1 OpCnt=Control Device Earth Switch CF_D2 X CTRL/Q8XSWI1CTRL/Q8CSWI1Ground switchQ8 OpCnt=Control Device Earth Switch DP X CTRL/Q8XSWI1CTRL/Q8CSWI1Ground switchQ8 OpCnt=Control Device Q2 Open/Close CF_D2 X CTRL/Q2XSWI1CTRL/Q2CSWI1DisconnectorQ2 OpCnt=Control Device Q2 Open/Close DP X CTRL/Q2XSWI1CTRL/Q2CSWI1DisconnectorQ2 OpCnt=Control Device Q9 Open/Close CF_D2 X CTRL/Q9XSWI1CTRL/Q9CSWI1DisconnectorQ9 OpCnt=Control Device Q9 Open/Close DP X CTRL/Q9XSWI1CTRL/Q9CSWI1DisconnectorQ9 OpCnt=00601 Measurement I L1 MV X MEAS/MMXU1/A00602 Measurement I L2 MV X MEAS/MMXU1/A00603 Measurement I L3 MV X MEAS/MMXU1/A00610 Measurement 3I0 (zero sequence) MV X MEAS/MMXU1/AMEAS/MSQI1/SeqA00619 Measurement I1 (positive sequence) MV X MEAS/MSQI1/SeqA00620 Measurement I2 (negative sequence) MV X MEAS/MSQI1/SeqA00644 Measurement Frequency MV X MEAS/MMXU1/Hz00621 Measurement U L1-E MV X MEAS/MMXU1/PhV00622 Measurement U L2-E MV X MEAS/MMXU1/PhV00623 Measurement U L3-E MV X MEAS/MMXU1/PhV00624 Measurement U L12 MV X MEAS/MMXU1/PPV00625 Measurement U L23 MV X MEAS/MMXU1/PPV00626 Measurement U L31 MV X MEAS/MMXU1/PPV00684 Measurement U0 (zero sequence) MV X MEAS/MSQI1/SeqV00634 Measurement U1 (positive sequence) MV X MEAS/MSQI1/SeqVSIMATIC DEWA / REVISED V1.2 / BRSH SS_F_DREP_M1FP_7SD5/7SD522 02.04.11 19:00:38Page 9 of 10No. Group Information Type Source Destination Extended Assigned IEC 61850 object (LD /LN / DO)00635 Measurement U2 (negative sequence) MV X MEAS/MSQI1/SeqV00641 Measurement P (active power) MV X MEAS/MMXU1/TotW00642 Measurement Q (reactive power) MV X MEAS/MMXU1/TotVAr00643 Measurement Power Factor MV X MEAS/MMXU1/TotPF00645 Measurement S (apparent power) MV X MEAS/MMXU1/TotVA07761 Measure relay1 Relay ID of 1. relay MV X MEAS/MMXU2/RelId07762 Measure relay1 IL1(% of Operational nominal current) MV X MEAS/MMXU2/A07763 Measure relay1 Angle IL1_rem IL1_loc MV X MEAS/MMXU2/A07764 Measure relay1 IL2(% of Operational nominal current) MV X MEAS/MMXU2/A07765 Measure relay1 Angle IL2_rem IL2_loc MV X MEAS/MMXU2/A07766 Measure relay1 IL3(% of Operational nominal current) MV X MEAS/MMXU2/A07767 Measure relay1 Angle IL3_rem IL3_loc MV X MEAS/MMXU2/AMEAS/MMXU3/A07769 Measure relay1 UL1(% of Operational nominal voltage) MV X MEAS/MMXU2/PhV07770 Measure relay1 Angle UL1_rem UL1_loc MV X MEAS/MMXU2/PhV07771 Measure relay1 UL2(% of Operational nominal voltage) MV X MEAS/MMXU2/PhV07772 Measure relay1 Angle UL2_rem UL2_loc MV X MEAS/MMXU2/PhV07773 Measure relay1 UL3(% of Operational nominal voltage) MV X MEAS/MMXU2/PhV07774 Measure relay1 Angle UL3_rem UL3_loc MV X MEAS/MMXU2/PhV07781 Measure relay2 Relay ID of 2. relay MV X MEAS/MMXU3/RelId07782 Measure relay2 IL1(% of Operational nominal current) MV X MEAS/MMXU3/A07783 Measure relay2 Angle IL1_rem IL1_loc MV X MEAS/MMXU3/A07784 Measure relay2 IL2(% of Operational nominal current) MV X MEAS/MMXU3/A07785 Measure relay2 Angle IL2_rem IL2_loc MV X MEAS/MMXU3/A07786 Measure relay2 IL3(% of Operational nominal current) MV X MEAS/MMXU3/A07787 Measure relay2 Angle IL3_rem IL3_loc MV X MEAS/MMXU3/A07789 Measure relay2 UL1(% of Operational nominal voltage) MV X MEAS/MMXU3/PhV07790 Measure relay2 Angle UL1_rem UL1_loc MV X MEAS/MMXU3/PhV07791 Measure relay2 UL2(% of Operational nominal voltage) MV X MEAS/MMXU3/PhV07792 Measure relay2 Angle UL2_rem UL2_loc MV X MEAS/MMXU3/PhV07793 Measure relay2 UL3(% of Operational nominal voltage) MV X MEAS/MMXU3/PhV07794 Measure relay2 Angle UL3_rem UL3_loc MV X MEAS/MMXU3/PhV00924 Energy Wp Forward MVMV X MEAS/MMTR1/SupWh00925 Energy Wq Forward MVMV X MEAS/MMTR1/SupVArh00928 Energy Wp Reverse MVMV X MEAS/MMTR1/DmdWh00929 Energy Wq Reverse MVMV X MEAS/MMTR1/DmdVArh01000 Statistics Number of breaker TRIP commands VI X PROT/XCBR1/OpCnt01027 Statistics Accumulation of interrupted current L1 VI X PROT/XCBR1/SumSwARs1PROT/XCBR2/SumSwARs01028 Statistics Accumulation of interrupted current L2 VI X PROT/XCBR1/SumSwARs2PROT/XCBR3/SumSwARs01029 Statistics Accumulation of interrupted current L3 VI X PROT/XCBR1/SumSwARs3PROT/XCBR4/SumSwARsSIMATIC DEWA / REVISED V1.2 / BRSH SS_F_DREP_M1FP_7SD5/7SD522 02.04.11 19:00:38Page 10 of 10