blank iec form - ulstandards.ul.com...178 between any iec publication and the corresponding national...

195
2 IEC TR 62368-2:2019 © IEC 2019 CONTENTS 1 FOREWORD ........................................................................................................................... 6 2 INTRODUCTION ..................................................................................................................... 9 3 0 Principles of this product safety standard ....................................................................... 10 4 1 Scope ............................................................................................................................ 13 5 2 Normative references ..................................................................................................... 13 6 3 Terms, definitions and abbreviations .............................................................................. 13 7 4 General requirements .................................................................................................... 16 8 5 Electrically-caused injury ............................................................................................... 23 9 6 Electrically-caused fire ................................................................................................... 70 10 7 Injury caused by hazardous substances ....................................................................... 105 11 8 Mechanically-caused injury .......................................................................................... 109 12 9 Thermal burn injury ...................................................................................................... 117 13 10 Radiation ..................................................................................................................... 127 14 Annex A Examples of equipment within the scope of this standard ................................. 134 15 Annex B Normal operating condition tests, abnormal operating condition tests and 16 single fault condition tests ................................................................................ 134 17 Annex C UV Radiation .................................................................................................... 137 18 Annex D Test generators ................................................................................................ 137 19 Annex E Test conditions for equipment containing audio amplifiers ................................ 138 20 Annex F Equipment markings, instructions, and instructional safeguards ........................ 138 21 Annex G Components ..................................................................................................... 139 22 Annex H Criteria for telephone ringing signals ................................................................ 147 23 Annex J Insulated winding wires for use without interleaved insulation ........................... 149 24 Annex K Safety interlocks ............................................................................................... 149 25 Annex L Disconnect devices ........................................................................................... 149 26 Annex M Equipment containing batteries and their protection circuits .............................. 150 27 Annex O Measurement of creepage distances and clearances ........................................ 159 28 Annex P Safeguards against conductive objects ............................................................. 160 29 Annex Q Circuits intended for interconnection with building wiring .................................. 161 30 Annex R Limited short-circuit test ................................................................................... 161 31 Annex S Tests for resistance to heat and fire .................................................................. 162 32 Annex T Mechanical strength tests ................................................................................. 163 33 Annex U Mechanical strength of CRTs and protection against the effects of 34 implosion .......................................................................................................... 164 35 Annex V Determination of accessible parts ..................................................................... 165 36 Annex X Alternative method for determing clearances for insulation in circuits 37 connected to an AC mains not exceeding 420 V peak (300 V RMS) .................. 165 38 Annex Y Construction requirements for outdoor enclosures ............................................ 166 39 Annex A (informative) Background information related to the use of SPDs ......................... 169 40 Annex B (informative) Background information related to measurement of discharges 41 Determining the R-C discharge time constant for X- and Y-capacitors .............................. 182 42 Annex C (informative) Background information related to resistance to candle flame 43 ignition ................................................................................................................................ 194 44

Upload: others

Post on 08-May-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 2 – IEC TR 62368-2:2019 © IEC 2019

CONTENTS 1

FOREWORD ........................................................................................................................... 6 2

INTRODUCTION ..................................................................................................................... 9 3

0 Principles of this product safety standard ....................................................................... 10 4

1 Scope ............................................................................................................................ 13 5

2 Normative references ..................................................................................................... 13 6

3 Terms, definitions and abbreviations .............................................................................. 13 7

4 General requirements .................................................................................................... 16 8

5 Electrically-caused injury ............................................................................................... 23 9

6 Electrically-caused fire ................................................................................................... 70 10

7 Injury caused by hazardous substances ....................................................................... 105 11

8 Mechanically-caused injury .......................................................................................... 109 12

9 Thermal burn injury ...................................................................................................... 117 13

10 Radiation ..................................................................................................................... 127 14

Annex A Examples of equipment within the scope of this standard ................................. 134 15

Annex B Normal operating condition tests, abnormal operating condition tests and 16

single fault condit ion tests ................................................................................ 134 17

Annex C UV Radiation .................................................................................................... 137 18

Annex D Test generators ................................................................................................ 137 19

Annex E Test conditions for equipment containing audio amplifiers ................................ 138 20

Annex F Equipment markings, instructions, and instructional safeguards ........................ 138 21

Annex G Components ..................................................................................................... 139 22

Annex H Criteria for telephone ringing signals ................................................................ 147 23

Annex J Insulated winding wires for use without interleaved insulation ........................... 149 24

Annex K Safety interlocks ............................................................................................... 149 25

Annex L Disconnect devices ........................................................................................... 149 26

Annex M Equipment containing batteries and their protection circuits .............................. 150 27

Annex O Measurement of creepage distances and clearances ........................................ 159 28

Annex P Safeguards against conductive objects ............................................................. 160 29

Annex Q Circuits intended for interconnection with building wiring .................................. 161 30

Annex R Limited short-circuit test ................................................................................... 161 31

Annex S Tests for resistance to heat and fire .................................................................. 162 32

Annex T Mechanical strength tests ................................................................................. 163 33

Annex U Mechanical strength of CRTs and protection against the effects of 34

implosion .......................................................................................................... 164 35

Annex V Determination of accessible parts ..................................................................... 165 36

Annex X Alternative method for determing clearances for insulation in circuits 37

connected to an AC mains not exceeding 420 V peak (300 V RMS) .................. 165 38

Annex Y Construction requirements for outdoor enclosures ............................................ 166 39

Annex A (informative) Background information related to the use of SPDs ......................... 169 40

Annex B (informative) Background information related to measurement of discharges 41

– Determining the R-C discharge time constant for X- and Y-capacitors .............................. 182 42

Annex C (informative) Background information related to resistance to candle flame 43

ignition ................................................................................................................................ 194 44

Page 2: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:2019 © IEC 2019 – 3 –

Bibliography ........................................................................................................................ 195 45

46

Figure 1 – Risk reduction as given in ISO/IEC Guide 51 ........................................................ 11 47

Figure 2 – HBSE Process Chart ............................................................................................ 12 48

Figure 3 – Protective bonding conductor as part of a safeguard ............................................ 15 49

Figure 4 – Safeguards for protecting an ordinary person ....................................................... 19 50

Figure 5 – Safeguards for protecting an instructed person .................................................... 20 51

Figure 6 – Safeguards for protecting a skilled person ............................................................ 20 52

Figure 7 – Flow chart showing the intent of the glass requirements ....................................... 22 53

Figure 8 – Conventional time/current zones of effects of AC currents (15 Hz to 100 Hz) 54

on persons for a current path corresponding to left hand to feet (see IEC/TS 60479 -55

1:2005, Figure 20) ................................................................................................................ 25 56

Figure 9 – Conventional time/current zones of effects of DC currents on persons for a 57

longitudinal upward current path (see IEC/TS 60479-1:2005, Figure 22) ............................... 26 58

Figure 10 – Illustration that limits depend on both voltage and current .................................. 27 59

Figure 11 – Illustration of working voltage ............................................................................. 39 60

Figure 12 – Illustration of transient voltages on paired conductor external circuits ................ 41 61

Figure 13 – Illustration of transient voltages on coaxial -cable external circuits ...................... 42 62

Figure 14 – Basic and reinforced insulation in Table 14 of IEC 62368-1:2018; ratio 63

reinforced to basic ................................................................................................................ 43 64

Figure 15 – Reinforced clearances according to Rule 1, Rule 2, and Table 14 ...................... 45 65

Figure 16 – Example illustrating accessible internal wi ring .................................................... 53 66

Figure 17 – Waveform on insulation without surge suppressors and no breakdown ............... 56 67

Figure 18 – Waveforms on insulation dur ing breakdown without surge suppressors .............. 57 68

Figure 19 – Waveforms on insulation with surge suppressors in operation ............................ 57 69

Figure 20 – Waveform on short-circuited surge suppressor and insulation ............................ 57 70

Figure 21 – Example for an ES2 source ................................................................................ 59 71

Figure 22 – Example for an ES3 source ................................................................................ 59 72

Figure 23 – Overview of protective conductors ...................................................................... 62 73

Figure 24 – Example of a typical touch current measuring net work ....................................... 64 74

Figure 25 – Touch current from a floating circuit ................................................................... 67 75

Figure 26 – Touch current from an earthed circuit ................................................................. 67 76

Figure 27 – Summation of touch currents in a PABX ............................................................. 68 77

Figure 28 – Possible safeguards against electrically -caused fire ........................................... 75 78

Figure 29 – Fire clause flow chart ......................................................................................... 78 79

Figure 30 – Prevent ignition flow chart .................................................................................. 83 80

Figure 31 – Control fire spread summary .............................................................................. 85 81

Figure 32 – Control fire spread PS2 ...................................................................................... 86 82

Figure 33 – Control fire spread PS3 ...................................................................................... 87 83

Figure 34 – Fire cone application to a large component ........................................................ 96 84

Figure 35 – Flowchart demonstrating the hierarchy of hazard management ........................ 108 85

Figure 36 – Model for chemical injury .................................................................................. 109 86

Figure 37 – Direction of forces to be applied ....................................................................... 114 87

Figure 38 – Model for a burn injury ..................................................................................... 117 88

Page 3: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 4 – IEC TR 62368-2:2019 © IEC 2019

Figure 39 – Model for safeguards against thermal burn injury ............................................. 119 89

Figure 40 – Model for absence of a thermal hazard ............................................................. 120 90

Figure 41 – Model for presence of a thermal hazard with a physical safeguard in place ...... 120 91

Figure 42 – Model for presence of a thermal hazard with behavioural safeguard 92

in place ............................................................................................................................... 120 93

Figure 43 – Flowchart for evaluation of Image projectors (beamers) ................................... 129 94

Figure 44 – Graphical representation of LAeq,T .................................................................. 131 95

Figure 45 – Overview of operating modes ........................................................................... 136 96

Figure 46 – Voltage-current characteristics (Typical data) ................................................... 141 97

Figure 47 – Example of IC current limiter circuit .................................................................. 145 98

Figure 48 – Current limit curves .......................................................................................... 148 99

Figure 49 – Example of a dummy battery circuit .................................................................. 158 100

Figure 50 – Example of a circuit with two power sources..................................................... 161 101

Figure A.1 – Installation has poor earthing and bonding; equipment damaged 102

(from ITU-T K.66) ................................................................................................................ 170 103

Figure A.2 – Installation has poor earthing and bonding; using main earth bar for 104

protection against lightning strike (from ITU -T K.66) ........................................................... 170 105

Figure A.3 – Installation with poor earthing and bonding, using a varistor and a GDT 106

for protection against a lightning strike ................................................................................ 171 107

Figure A.4 – Installation with poor earthing and bonding; equipment damaged (TV set) ...... 171 108

Figure A.5 – Safeguards ..................................................................................................... 172 109

Figure A.6 – Discharge stages ............................................................................................ 176 110

Figure A.7 – Holdover ......................................................................................................... 177 111

Figure A.8 – Discharge ....................................................................................................... 178 112

Figure A.9 – Characteristics ................................................................................................ 179 113

Figure A.10 – Follow on current pictures ............................................................................. 180 114

Figure B.1 – Typical EMC filter schematic ........................................................................... 182 115

Figure B.2 – 100 M oscilloscope probes ........................................................................... 184 116

Figure B.3 – Combinations of EUT resistance and capacitance for 1 -s time constant .......... 186 117

Figure B.4 – 240 V mains followed by capacitor discharge .................................................. 188 118

Figure B.5 – Time constant measurement schematic .......................................................... 189 119

Figure B.6 – Worst-case measured time constant values for 100 M and 10 M probes .... 193 120

121

Table 1 – General summary of required safeguards .............................................................. 20 122

Table 2 – Time/current zones for AC 15 Hz to 100 Hz for hand to feet pathway (see 123

IEC/TS 60479-1:2005, Table 11) ........................................................................................... 26 124

Table 3 – Time/current zones for DC for hand to feet pathway (see IEC/TS 60479 -125

1:2005, Table 13).................................................................................................................. 27 126

Table 4 – Limit values of accessible capacitance (threshold of pain) ..................................... 30 127

Table 5 – Total body resistances RT for a current path hand to hand, DC, for large 128

surface areas of contact in dry condition ............................................................................... 32 129

Table 6 – Insulation requirements for external circuits .......................................................... 42 130

Table 7 – Voltage drop across clearance and solid insulation in series ................................. 47 131

Table 8 – Examples of application of various safeguards ...................................................... 77 132

Page 4: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:2019 © IEC 2019 – 5 –

Table 9 – Basic safeguards against fire under normal operating conditions and 133

abnormal operating conditions .............................................................................................. 79 134

Table 10 – Supplementary safeguards against fire under single faul t conditions ................... 80 135

Table 11 – Method 1: Reduce the likelihood of ignition ......................................................... 82 136

Table 12 – Method 2: Control fire spread .............................................................................. 91 137

Table 13 – Fire barrier and fire enclosure flammability requirements ..................................... 98 138

Table 14 – Summary – Fire enclosure and fire barrier material requ irements ...................... 102 139

Table 15 – Control of chemical hazards .............................................................................. 107 140

Table 16 – Overview of requirements for dose-based systems ............................................ 133 141

Table 17 – Safety of batteries and their cells – requirements (expanded information on 142

documents and scope) ........................................................................................................ 152 143

Table B.1 – 100- M oscilloscope probes ........................................................................... 184 144

Table B.2 – Capacitor discharge ......................................................................................... 185 145

Table B.3 – Maximum Tmeasured values for combinations of REUT and CEUT for 146

TEUT of 1 s ........................................................................................................................ 192 147

148

149

Page 5: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 6 – IEC TR 62368-2:2019 © IEC 2019

INTERNATIONAL ELECTROTECHNICAL COMMISSION 150

____________ 151

152

AUDIO/VIDEO, INFORMATION AND 153

COMMUNICATION TECHNOLOGY EQUIPMENT – 154

155

Part 2: Explanatory information related to IEC 62368-1:2018 156

157

FOREWORD 158

1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising 159 all national electrotechnical committees (IEC National Committees). The object of IEC is to promote 160 international co-operation on all questions concer ning standardization in the electrical and electronic fields. To 161 this end and in addition to other activities, IEC publishes International Standards, Technical Specifications, 162 Technical Reports, Publicly Available Specifications (PAS) and Guides (hereafter referred to as “IEC 163 Publication(s)”). Their preparation is entrusted to technical committees; any IEC National Committee interested 164 in the subject dealt with may participate in this preparatory work. International, governmental and non -165 governmental organizations liaising with the IEC also participate in this preparation. IEC collaborates closely 166 with the International Organization for Standardization (ISO) in accordance with conditions determined by 167 agreement between the two organizations. 168

2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international 169 consensus of opinion on the relevant subjects since each technical committee has representation from all 170 interested IEC National Committees. 171

3) IEC Publicat ions have the form of recommendations for international use and are accepted by IEC National 172 Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC 173 Publications is accurate, IEC cannot be held responsibl e for the way in which they are used or for any 174 misinterpretation by any end user. 175

4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications 176 transparently to the maximum extent possible in their national a nd regional publications. Any divergence 177 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 178 the latter. 179

5) IEC itself does not provide any attestation of conformity. Independent certification bo dies provide conformity 180 assessment services and, in some areas, access to IEC marks of conformity. IEC is not responsible for any 181 services carried out by independent certification bodies. 182

6) All users should ensure that they have the latest edition of this publication. 183

7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and 184 members of its technical committees and IEC National Committees for any personal injury, property damage or 185 other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and 186 expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC 187 Publications. 188

8) Attention is drawn to the Normative referen ces cited in this publication. Use of the referenced publications is 189 indispensable for the correct application of this publication. 190

9) Attention is drawn to the possibility that some of the elements of this IEC Publication may be the subject of 191 patent rights. IEC shall not be held responsible for identifying any or all such patent rights. 192

The main task of IEC technical committees is to prepare International Standards. However, a 193

technical committee may propose the publication of a technical report when it h as collected 194

data of a different kind from that which is normally published as an International Standard, for 195

example, "state of the art". 196

IEC 62368-2, which is a Technical Report, has been prepared by IEC technical committee 197

TC 108: Safety of electronic equipment within the field of audio/video, information technology 198

and communication technology. 199

This third edition updates the second edition of IEC 62368-2 published in 2014 to take into 200

account changes made to IEC 62368-1:2014 as identified in the Foreword of 201

IEC 62368-1:2018. 202

This Technical Report is informative only. In case of a conflict between IEC 62368-1 and IEC 203

TR 62368-2, the requirements in IEC 62368-1 prevail over this Technical Report. 204

Page 6: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:2019 © IEC 2019 – 7 –

The text of this technical report is based on the following documents: 205

Enquiry draft Report on voting

108/708/DTR 108/711/RVDTR

206

Full information on the voting for the approval of this technical report can be found in the 207

report on voting indicated in the above table. 208

In this document, the following print types are used: 209

– notes/explanatory matter: in smaller roman type; 210

– tables and figures that are included in the rationale have linked fields (shaded in grey if 211

“field shading” is active); 212

– terms that are defined in IEC 62368-1: in bold type. 213

In this document, where the term (HBSDT) is used, it stands for Hazard Based Standard 214

Development Team, which is the Working Group of IEC TC 108 responsible for the 215

development and maintenance of IEC 62368-1. 216

This publication has been drafted in accordance with the ISO/IEC Direct ives, Part 2. 217

A list of all parts of the IEC 62368 series can be found, under the general title Audio/video, 218

information and communication technology equipment , on the IEC website. 219

In this document, only those subclauses from IEC 62368-1 considered to need further 220

background reference information or explanation to benefit the reader in applying the relevant 221

requirements are included. Therefore, not all numbered subclauses are cited. Unless 222

otherwise noted, all references are to clauses, subclauses, annexes, figures or tables located 223

in IEC 62368-1:2018. 224

The entries in the document may have one or two of the following subheadings in addition to 225

the Rationale statement: 226

Source – where the source is known and is a document that is accessible to the general 227

public, a reference is provided. 228

Purpose – where there is a need and when it may prove helpful to the understanding of the 229

Rationale, we have added a Purpose statement. 230

231

Page 7: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 8 – IEC TR 62368-2:2019 © IEC 2019

The committee has decided that the contents of this publication will remain unchanged u ntil 232

the stability date indicated on the IEC web site under "http://webstore.iec.ch" in the data 233

related to the specific publication. At this date, the publication will be 234

• reconfirmed, 235

• withdrawn, 236

• replaced by a revised edition, or 237

• amended. 238

239

IMPORTANT – The 'colour inside' logo on the cover page of this publication indicates that it contains colours which are considered to be useful for the correct understanding of its contents. Users should therefore print this document using a colour printer.

240

241

Page 8: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:2019 © IEC 2019 – 9 –

INTRODUCTION 242

IEC 62368-1 is based on the principles of hazard -based safety engineering, which is a 243

different way of developing and specifying safety considerations than that of the current 244

practice. While this document is different from traditional IEC safety docume nts in its 245

approach and while it is believed that IEC 62368-1 provides a number of advantages, its 246

introduction and evolution are not intended to result in significant changes to the existing 247

safety philosophy that led to the development of the safety requ irements contained in 248

IEC 60065 and IEC 60950-1. The predominant reason behind the creation of IEC 62368-1 is 249

to simplify the problems created by the merging of the technologies of ITE and CE. The 250

techniques used are novel, so a learning process is require d and experience is needed in its 251

application. Consequently, the committee recommends that this edition of the document be 252

considered as an alternative to IEC 60065 or IEC 60950-1 at least over the recommended 253

transition period. 254

255

256

Page 9: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 10 – IEC TR 62368-2:2019 © IEC 2019

AUDIO/VIDEO, INFORMATION AND 257

COMMUNICATION TECHNOLOGY EQUIPMENT – 258

259

Part 2: Explanatory information related to IEC 62368-1:2018 260

261

262

263

0 Principles of this product safety standard 264

Clause 0 is informational and provides a rationale for the normative clauses 265

of the document. 266

0.5.1 General 267

ISO/IEC Guide 51:2014, 6.3.5 states: 268

“When reducing risks the order of priority shall be as follows: 269

a) inherently safe design; 270

b) guards and protective devices; 271

c) information for end users. 272

Inherently safe design measures are the first and most imp ortant step in 273

the risk reduction process. This is because protective measures inherent to 274

the characteristics of the product or system are likely to remain effective, 275

whereas experience has shown that even well -designed guards and 276

protective devices can fail or be violated and information for use might not 277

be followed. 278

Guards and protective devices shall be used whenever an inherently safe 279

design measure does not reasonably make it possible either to remove 280

hazards or to sufficiently reduce risks. Compleme ntary protective measures 281

involving additional equipment (for example, emergency stop equipment) 282

might have to be implemented. 283

The end user has a role to play in the risk reduction procedure by 284

complying with the information provided by the designer/suppli er. However, 285

information for use shall not be a substitute for the correct application of 286

inherently safe design measures, guards or complementary protective 287

measures.” 288

In general, this principle is used in IEC 62368-1. The table below shows a 289

comparison between the hierarchy required in ISO/IEC Guide 51 and the 290

hierarchy used in IEC 62368-1:2018: 291

ISO/IEC Guide 51 IEC 62368-1

a) inherently safe design 1. inherently safe design by limiting all energy hazards to class 1

b) guards and protective devices 2. equipment safeguards

3. installation safeguards

4. personal safeguards

c) information for end users 5. behavioral safeguards

6. instructional safeguards

292

Risk assessment has been considered as part of the development of 293

IEC 62368-1 as indicated in the following from ISO/IEC Guide 51 (Figure 1) 294

in this document. See also the Hazard Based Safety Engineering (HBSE) 295

Process Flow (Figure 2) in this document that also provides additional 296

details for the above comparison. 297

Page 10: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:2019 © IEC 2019 – 11 –

298

Figure 1 – Risk reduction as given in ISO/IEC Guide 51 299

Page 11: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 12 – IEC TR 62368-2:2019 © IEC 2019

300

301

Figure 2 – HBSE Process Chart 302

0.5.7 Equipment safeguards during skilled person service conditions 303

Purpose: To explain the intent of requirements for providing safeguards against 304

involuntary reaction. 305

Rationale: By definition, a skilled person has the education and experience to identify 306

all class 3 energy sources to which he may be exposed. However, while 307

servicing one class 3 energy source in one location, a skilled person may 308

be exposed to another class 3 energy source in a different location. 309

In such a situation, either of two events is possible. First, something may 310

cause an involuntary reaction of the skilled person with the consequences 311

of contact with the class 3 energy source in the different location. Second, 312

the space in which the skilled person is located may be small and 313

cramped, and inadvertent contact with a class 3 energy source in the 314

different location may be likely. 315

In such situations, this document may require an equipment safeguard 316

solely for the protection of a skilled person while performing servicing 317

activity. 318

0.10 Thermally-caused injury (skin burn) 319

Purpose: The requirements basically address safeguards against thermal energy 320

transfer by conduction. They do not specifically address safeguards 321

against thermal energy transfer by convection or radiation. However, as the 322

temperatures from hot surfaces due to conduction are always higher than 323

the radiated or convected temperatures, these are considered to be 324

covered by the requirements against conducted energy transfer. 325

___________ 326

Met opmerkingen [RJ1]: See Brussels item 6.2.15

Page 12: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:2019 © IEC 2019 – 13 –

1 Scope 327

Purpose: To identify the purpose and applicability of this document and the 328

exclusions from the scope. 329

Rationale: The scope excludes requirements for functional safety. Functional safety is 330

addressed in IEC 61508-1. Because the scope includes computers that 331

may control safety systems, functional safety requirements would 332

necessarily include requirements for computer processes and software. 333

The requirements provided in IEC 60950-23 could be modified and added 334

to IEC 62368 as another –X document. However, because of the hazard-335

based nature of IEC 62368-1, the requirements from IEC 60950-23 have 336

been incorporated into the body of IEC 62368-1 and made more generic. 337

The intent of the addition of the IEC 60950-23 requirements is to maintain 338

the overall intent of the technical requirements from IEC 60950-23, 339

incorporate them into IEC 62368-1 following the overall format of 340

IEC 62368-1 and simplify and facilitate the application of these 341

requirements. 342

Robots traditionally are covered under the scopes of ISO documents, 343

typically maintained by ISO TC 299. ISO TC 299 has working groups for 344

personal care robots and service robots, and produces fo r example, 345

ISO 13482, Robots and robotic devices – Safety requirements for personal 346

care robots. 347

___________ 348

2 Normative references 349

The list of normative references is a list of all documents that have a 350

normative reference to it in the body of the document. As such, referenced 351

documents are indispensable for the application of this document. For 352

dated references, only the edition cited applies. For undated references, 353

the latest edition of the referenced document (including any amendments) 354

applies. 355

Recently, there were some issues with test houses that wanted to use the 356

latest edition as soon as it was published. As this creates serious problems 357

for manufacturers, since they have no chance to prepare, it was felt that a 358

reasonable transition period should be taken into account. This is in line 359

with earlier decisions taken by the SMB that allow transition periods to be 360

mentioned in the foreword of the documents. Therefore IEC TC 108 361

decided to indicate this in the introduction of the normative references 362

clause, to instruct test houses to take into account any transition period, 363

effective date or date of withdrawal established for the document. 364

These documents are referenced, in whole, in part , or as alternative 365

requirements to the requirements contained in thi s document. Their use is 366

specified, where necessary, for the application of the requirements of this 367

document. The fact that a standard is mentioned in the list does not mean 368

that compliance with the document or parts of it are required. 369

___________ 370

3 Terms, definitions and abbreviations 371

Rationale is provided for definitions that deviate from IEV definitions or 372

from Basic or Group Safety publication definitions. 373

3.3.2.1 electrical enclosure 374

Source: IEC 60050-195:1998, 195-06-13 375

Page 13: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 14 – IEC TR 62368-2:2019 © IEC 2019

Purpose: To support the concept of safeguards as used in this document. 376

Rationale: The IEV definition is modified to use the term “safeguard” in place of the 377

word “protection”. The word “safeguard” identifies a physical “thing” 378

whereas the word “protection” identifies the act of prote cting. This 379

document sets forth requirements for use of physical safeguards and 380

requirements for those safeguards. The safeguards provide “protection” 381

against injury from the equipment. 382

3.3.5.1 basic insulation 383

Source: IEC 60050-195:1998, 195-06-06 384

Purpose: To support the concept of safeguards as used in this document. 385

Rationale: The IEV definition is modified to use the term “safeguard” in place of the 386

word “protection” . The word “safeguard” identifies a physical “thing” 387

whereas the word “protection” identifies the act of protecting. This 388

document sets forth requirements for use of physical safeguards and 389

requirements for those safeguards. The safeguards provide “protection” 390

against injury from the equipment. 391

3.3.5.2 double insulation 392

Source: IEC 60050-195:1998, 195-06-08 393

Purpose: To support the concept of safeguards as used in this document. 394

Rationale: See 3.3.5.1, basic insulation. 395

3.3.5.6 solid insulation 396

Source: IEC 60050-212:2015, 212-11-02 397

3.3.5.7 supplementary insulation 398

Source: IEC 60050-195:1998, 195-06-07 399

Purpose: To support the concept of safeguards as used in this document. 400

Rationale: See 3.3.5.1, basic insulation. 401

3.3.6.9 restricted access area 402

Source: IEC 60050-195:1998, 195-04-04 403

Purpose: To use the concept of “ instructed persons” and “skilled persons” as used 404

in this document. 405

Rationale: The IEV definition is modified to use the terms “ instructed persons” and 406

“skilled persons” rather than “electrically instructed persons” and 407

“electrically skilled persons.” 408

3.3.7.7 reasonably foreseeable misuse 409

Source: ISO/IEC Guide 51:2014, 3.7 410

Rationale: Misuse depends on personal objectives, personal perception of the 411

equipment, and the possible use of the equipment (in a manner not 412

intended by the manufacturer) to accomplish those personal objectives. 413

Equipment within the scope of this document ranges from small handheld 414

equipment to large, permanently installed equipment. There is no 415

commonality among the equipment for readily predicting human behaviour 416

leading to misuse of the equipment and resultant injury. Where a possible 417

reasonably foreseeable misuse that may lead to an injury is not covered 418

by the requirements of the document, manufacturers are encouraged to 419

consider reasonably foreseeable misuse of equipment and provide 420

safeguards, as applicable, to prevent injury in the event of such misuse . 421

(Not all reasonably foreseeable misuse of equipment results in injury or 422

potential for injury.) 423

Page 14: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:2019 © IEC 2019 – 15 –

3.3.8.1 instructed person 424

Source: IEC 60050-826:2004, 826-18-02 425

Rationale: The IEV definition is modified to use the terms “energy sources”, “skilled 426

person”, and “precautionary safeguard ”. The definition is made stronger 427

by using the term “instructed” rather than “advised”. 428

3.3.8.3 skilled person 429

Source: IEC 60050-826:2004, 826-18-01 430

Rationale: The IEV definition is modified to use the phrase “to reduce the likelihood 431

of”. IEC 62368-1, in general, tends not use the word “hazard”. 432

3.3.11.9 protective bonding conductor 433

Rationale: The protective bonding conductor, is not a complete safeguard, but a 434

component part of the earthing system safeguard. The protective 435

bonding conductor provides a fault current pathway from a part (insulated 436

from ES3 by basic insulation only) to the equipment protective earthing 437

terminal, see Figure 3 in this document. 438

439

Figure 3 – Protective bonding conductor as part of a safeguard 440

The parts required to be earthed via a protective bonding conductor are 441

those that have only basic insulation between the parts and ES3, and are 442

connected to accessible parts. 443

Only the fault current pathway is required to be a protective bonding 444

conductor. Other earthing connections of accessible conductive parts 445

can be by means of a functional earth conductor to the equipment PE 446

terminal or to a protective bonding conductor. 447

3.3.14.3 prospective touch voltage 448

Source: IEC 60050-195:1998, 195-05-09 449

Purpose: To properly identify electric shock energy source voltages. 450

Rationale: The IEV definition is modified to delete “animal”. The word “pers on” is also 451

deleted as all of the requirements in the document are with respect to 452

persons. 453

3.3.14.8 working voltage 454

Source: IEC 60664-1:2007, 3.5 455

Purpose: To distinguish between RMS. working voltage and the peak of the 456

working voltage. 457

Page 15: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 16 – IEC TR 62368-2:2019 © IEC 2019

Rationale: The IEC 60664-1 definition is modified to delete “RMS”. IEC 62368-1 uses 458

both RMS. working voltage and peak of the working voltage; each term 459

is defined. 460

3.3.15.2 class II construction 461

Source: IEC 60335-1:2010, 3.3.11 462

Purpose: Although the term is not used in t he document, for completeness, it was 463

decided to retain this definition. 464

Rationale: The word “appliance” is changed to “equipment”. 465

____________ 466

4 General requirements 467

Purpose: To explain how to investigate and determine whether or not safety is 468

involved. 469

Rationale: In order to establish whether or not safety is involved, the circuits and 470

construction are investigated to determine whether the consequences of 471

possible fault conditions would lead to an injury. Safety is involved if, as a 472

result of a single fault condition, the consequences of the fault lead to a 473

risk of injury. 474

If a fault condition should lead to a risk of injury, the part, material, or 475

device whose fault was simulated may comprise a safeguard. 476

Rationale is provided for questions regarding the omission of some 477

traditional requirements appearing in other safety documents. Rationale is 478

also provided for further explanation of new concepts and requirements in 479

this document. 480

Reasonable foreseeable misuse 481

Rationale: Apart from Annex M, this document does not specifically mention 482

foreseeable misuse or abnormal operating conditions . Nevertheless, the 483

requirements of the document cover many kinds of foreseeable misuse, 484

such as covering of ventilation openings, paper jams, stalled motors, etc. 485

functional insulation 486

Rationale: This documentdoes not include requirements for functional insulation . By 487

its nature, functional insulation does not provide a safeguard function 488

against electric shock or electrically-caused fire and therefore may be 489

faulted. Obviously, not all functional insulations are faulted as this would 490

be prohibitively time-consuming. Sites for functional insulation faults 491

should be based upon physical examination of the equipment, and upon the 492

electrical schematic. 493

Note that basic insulation and reinforced insulation may also serve as 494

functional insulation , in which case the insulation is not faulted. 495

Page 16: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:2019 © IEC 2019 – 17 –

functional components 496

Rationale: This document does not include requirements for functional components. 497

By their nature, individual functional components do not provide a 498

safeguard function against electric shock, electrically -caused fire, thermal 499

injury, etc., and therefore may be candidates for fault testing. Obviously, 500

not all functional components are faulted as this would be prohibitively 501

time-consuming. Candidate components for fault testing should be based 502

upon physical examination of the equipment, upon the electrical schematic 503

diagrams, and whether a fault of that component might result in conditions 504

for electric shock, conditions for ignition and propagation of fire, conditions 505

for thermal injury, etc. 506

As with all single fault condition testing (Clause B.4), upon faulting of a 507

functional component, there shall not be any safety consequence (for 508

example, a benign consequence), or a basic safeguard, supplementary 509

safeguard , or reinforced safeguard shall remain effective. 510

In some cases, a pair of components may comprise a safeguard. If the 511

fault of one of the components in the pair is mitigated by the second 512

component, then the pair is designated as a double safeguard. For 513

example, if two diodes are employed in series to protect a battery from 514

reverse charge, then the pair comprises a double safeguard and the 515

components should be limited to the manufacturer and part number actually 516

tested. A second example is that of an X-capacitor and discharge resistor. 517

If the discharge resistor should fail open, then the X -capacitor will not be 518

discharged. Therefore, the X-capacitor value is not to exceed the ES2 limits 519

specified for a charged capacitor. Again, the two components comprise a 520

double safeguard and the values of each component are limited to values 521

for ES1 under normal operating conditions and the values for ES2 under 522

single fault conditions. 523

4.1.1 Application of requirements and acceptance of materials, components and 524

subassemblies 525

Purpose: To accept components as safeguards. 526

Rationale: This document includes requirements for safeguard components. A 527

safeguard component is a component specifically designed and 528

manufactured for both functional and safeguard parameters. Examples of 529

safeguard components are capacitors complying with IEC 60384-14 and 530

other components that comply with their related IEC component document. 531

Acceptance of components and component requirements from 532

IEC 60065 and 60950-1 533

Purpose: To accept both components and sub-assemblies investigated to the legacy 534

documents, IEC 60065 and IEC 60950-1, and components complying with 535

individual component requirements within these documents during the 536

transition period. 537

Rationale: To facilitate a smooth transition from the legacy documents IEC 60065 and 538

IEC 60950-1 to IEC 62368-1, including by the component supply chain, this 539

document allows for acceptance of both components and sub -assemblies 540

investigated to the legacy documents. Individual component requirements 541

within these documents may be used for compliance with IEC 62368-1 542

without further investigation , other than to give consideration to the 543

appropriate use of the component or sub-assembly in the end-product. 544

This means, for example, if a switch mode power supply is certified to 545

IEC 60065 or IEC 60950-1, this component can be used in equipment 546

evaluated to IEC 62368-1 without further investigation , other than to give 547

consideration to the appropriate use of the component, such as use within 548

its electrical ratings. 549

Page 17: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 18 – IEC TR 62368-2:2019 © IEC 2019

This also means, for example, since IEC 60950-1 allows for wiring and 550

cables insulated with PVC, TFE, PTFE, FEP, polychloroprene or polyimide 551

to comply with material requirements for parts within a fire enclosure 552

without need for the application of a flammability test, the same wire can be 553

used to comply with the requirements in 6.5.2 for insulation on wiring used 554

in PS2 or PS3 circuits and without the need for application of a flammability 555

test per IEC 60332 series or IEC TS 60695-11-21 as normally is required 556

by 6.5.1. 557

4.1.5 Constructions and components not specifically covered 558

For constructions not covered, consideration should be given for the 559

hierarchy of safeguards in accordance with ISO/IEC Guide 51. 560

4.1.6 Orientation during transport and use 561

See also 4.1.4 562

In general, equipment is assumed to be installed and used in accordance 563

with the manufacturer’s instructions. However, in some cases where 564

equipment may be installed by an ordinary person, it is recognized that it 565

is common practice to mount equipment as desired if screw holes are 566

provided, especially if they allow mounting to readily available brackets. 567

Hence, the exception that is added to 4.1.6. 568

Examples of the above: a piece of equipment, such as a television set or a 569

video projector, that has embedded screw mounting holes that allow it to be 570

attached to a wall or other surface through the use of commercially 571

available vertically or tilt -mountable brackets, shall also take into account 572

that the mounting surface itself may not be vertical. 573

It is also recognized that transportable equipment , by its nature, may be 574

transported in any and all orientations. 575

4.1.8 Liquids and liquid filled components (LFC) 576

The one-litre (1 l) restriction was placed in 4.1.8 since the ori gin of some of 577

the requirements in Clause G.15 came from requirements in documents 578

often applied to smaller systems. Nevertheless, such a limitation does not 579

always negate the allowed application of 4.1.8 and Clause G.15 to systems 580

with larger volumes of l iquid, but it could impact direct (automatic) 581

applicability to the larger systems. 582

4.2 Energy source classifications 583

Classification of energy sources may be done whether the source is 584

accessible or not. The requirements for parts may differ on whether the 585

part is accessible or not. 586

4.2.1 Class 1 energy source 587

A class 1 energy source is a source that is expected not to create any pain 588

or injury. Therefore, a class 1 energy source may be accessible by any 589

person. 590

Under some specific conditions of abnormal operation or single fault 591

conditions, a class 1 energy source may reach class 2 limits. However, 592

this source still remains a class 1 energy source. In this case, an 593

instructional safeguard may be required. 594

Under normal operating conditions and abnormal operating conditions, 595

the energy in a class 1 source, in contact with a body part, may be 596

detectable, but is not painful nor is it likely to cause an injury. For fire, the 597

energy in a class 1 source is not likely to cause ignition. 598

Under single fault conditions, a class 1 energy source, under contact with 599

a body part, may be painful, but is not likely to cause injury. 600

Page 18: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:2019 © IEC 2019 – 19 –

4.2.2 Class 2 energy source 601

A class 2 energy source is a source that may create pain, but which is 602

unlikely to create any serious injury. There fore, a class 2 energy source 603

may not be accessible by an ordinary person. However, a class 2 energy 604

source may be accessible by: 605

– an instructed person; and 606

– a skilled person. 607

The energy in a class 2 source, under contact with a body part, may be 608

painful, but is not likely to cause an injury. For fire, the energy in a class 2 609

source can cause ignition under some conditions. 610

4.2.3 Class 3 energy source 611

A class 3 energy source is a source that is likely to create an injury . 612

Therefore a class 3 energy source may not be accessible to an ordinary 613

person or an instructed person. A class 3 energy source may, in general, 614

be accessible to a skilled person. 615

Any source may be declared a class 3 energy source without measurement, 616

in which case all the safeguards applicable to class 3 are required. 617

The energy in a class 3 source, under contact with a body part, is capable 618

of causing injury. For fire, the energy in a class 3 source may cause ignition 619

and the spread of flame where fuel is available. 620

4.3.2 Safeguards for protection of an ordinary person 621

The required safeguards for the protection of an ordinary person are given in Figure 4. 622

623

Figure 4 – Safeguards for protecting an ordinary person 624

4.3.3 Safeguards for protection of an instructed person 625

The required safeguards for the protection of an instructed person are given in Figure 5. 626

Page 19: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 20 – IEC TR 62368-2:2019 © IEC 2019

627

Figure 5 – Safeguards for protecting an instructed person 628

4.3.4 Safeguards for protection of a skilled person 629

The required safeguards for the protection of a skilled person are given in Figure 6. 630

631

Figure 6 – Safeguards for protecting a skilled perso n 632

Table 1 in this document gives a general overview of the required number 633

of safeguards depending on the energy source and the person to whom 634

the energy source is accessible. The different clauses have requirements 635

that sometimes deviate from the general principle as given above. These 636

cases are clearly defined in the requirements sections of the document. 637

Table 1 – General summary of required safeguards 638

Person

Number of safeguards required to be interposed between an energy source and a person

Class 1 Class 2 Class3

Ordinary person 0 1 2

Instructed person 0 0 2

Skilled person 0 0 0 or 1

639

For a skilled person, there is normally no safeguard required for a class 3 640

energy source. However, if there are multiple class 3 energy sources 641

accessible or if the energy source is not obvious, a safeguard may be 642

required. 643

Page 20: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:2019 © IEC 2019 – 21 –

4.4.2 Composition of a safeguard 644

Purpose: To specify design and construction criteria for a single safeguard (basic, 645

supplementary, or reinforced) comprised of more than one element, for 646

example, a component or a device. 647

Rationale: Safeguards need not be a single, homogeneous component. Indeed, some 648

parts of this document require a single safeguard be comprised of two or 649

more elements. For example, for thin insulation, two or more layers are 650

required to qualify as supplementary insulation . Another example is 651

protective bonding and protective earthing, both of which are comprised 652

of wires, terminals, screws, etc. 653

If a safeguard is comprised of two or more elements, then the function of 654

the safeguard should not be compromised by a failure of any one element. 655

For example, if a screw attaching a protective earthing wire should 656

loosen, then the current-carrying capacity of the protective earthing circuit 657

may be compromised, making its reliability uncertain . 658

4.4.3 Safeguard robustness 659

Rationale: Safeguards should be sufficiently robust to withstand the rigors of 660

expected use throughout the equipment lifetime. Robustness requirements 661

are specified in the various clauses. 662

4.4.3.4 Impact test 663

Rationale: Stationary equipment can, in some cases, be developed for a specific 664

installation in which it is not possible for certain surfaces to be subjected to 665

an impact when installed as intended. In those cases, the impact test is not 666

necessary when the installation makes clear that the side cannot be 667

impacted. 668

4.4.3.6 Glass impact tests 669

Source: IEC 60065 670

Purpose: Verify that any glass that breaks does not cause skin -lacerating injury, or 671

expose class 3 hazards behind the glass. 672

Rationale: When it comes to glass, two hazards can be present in case the glass 673

breaks: 674

− access to sharp edges from the broken glass itself 675

− exposure of class 3 energy hazards in case the glass is used as (part of) 676

the enclosure. 677

Should the glass break during the impact test, T.9 is applied to ensure the 678

expelled fragments will be at MS2 level or less. 679

Platen glass has a long history of being exempted, because it is quite 680

obvious for people that, if broken, the broken glass is hazardous and 681

contact should be avoided. There is no known history of serious injuries 682

with this application. Platen glass is the glass that is typically used in 683

scanners, copiers, etc. Accidents are rare, probably also because they are 684

protected by an additional cover most of the time, which limits the 685

probability that an impact will occur on the glass. 686

CRTs are exempted because they have separate requirements. 687

The test value for floor standing equipment is higher because it is more 688

likely to be impacted by persons or carts and dollies at a higher force while 689

in normal use. 690

The exemption for glass below certain sizes is taken over from IEC 60065. 691

There is no good rationale to keep the exemption, other than that there are 692

no serious accidents known from the field. The HBSDT d ecided that they 693

want to keep the exemption in. 694

Page 21: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 22 – IEC TR 62368-2:2019 © IEC 2019

The flow chart in Figure 7 in this document shows the intent for the 695

requirements. 696

697

Figure 7 – Flow chart showing the intent of the glass requirements 698

4.4.3.10 Compliance criteria 699

The value of 30 g for the weight limit is chosen based on the maximum 700

dimension of a side of 50 mm. A typical piece of glass with a size of 50 mm 701

× 50 mm × 4 mm (roughly 2,80 g/cm3) would have a weight of around 30 g. 702

4.6 Fixing of conductors 703

Source: IEC 60950-1 704

Purpose: To reduce the likelihood that conductors could be displaced such that they 705

reduce the creepage distances and clearances. 706

Rationale: These requirements have been successfully used for products in the scope 707

of this document for many years. 708

4.7 Equipment for direct insertion into mains socket -outlets 709

Source: IEC 60065:2014, 15.5 710

IEC 60950-1:2013, 4.3.6 711

IEC 60335-1:2010, 22.3 712

Page 22: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:2019 © IEC 2019 – 23 –

IEC 60884-1:2013, 14.23.2 713

Purpose: Determine that equipment incorporating integr al pins for insertion into 714

mains socket-outlets does not impose undue torque on the socket -outlet 715

due to the mass and configuration of the equipment. This type of equipment 716

often is known as Direct Plug-in Equipment or Direct Plug-in Transformers. 717

Rationale: Socket outlets are required to comply with the safety requirements in 718

IEC 60884-1:2013, Plugs and socket-outlets for household and similar 719

purposes – Part 1: General requirements , including subclause 14.23.2. The 720

requirements result in socket designs wi th certain design limitations. 721

Equipment incorporating integral pins for insertion into mains socket-722

outlets is not allowed to exceed these design limitations. 723

4.9 Likelihood of fire or shock due to entry of conductive objects 724

Purpose: The purpose of this subclause is to establish opening requirements that 725

would minimize the risk of foreign conductive objects falling into the 726

equipment that could bridge parts within class 2 or class 3 circuits, or 727

between PS circuits that could result in ignition or electric shock. 728

It is considered unlikely that a person would accidentally drop something 729

that could consequently fall into the equipment at a height greater than 730

1,8 m. 731

_____________ 732

5 Electrically-caused injury 733

Purpose: Clause 5 classifies electrical energy sources and provides criteria for 734

determining the energy source class of each conductive part. The criteria 735

for energy source class include the source current -voltage characteristics, 736

duration, and capacitance. Each conductive part, whether current -carrying 737

or not, or whether earthed or not, shall be classed ES1, ES2, or ES3 with 738

respect to earth and with respect to any other simultaneously accessible 739

conductive part. 740

240 VA limit 741

IEC 62368-1 does not have requirements for a 240 VA energy hazard that 742

was previously located in 2.1.1.5 of IEC 60950-1:2013. 743

The origin/justification of the 240 VA energy hazard requirement in the 744

legacy documents was never precisely determined, and it appears the VA 745

limits may have come from a manufacturer’s specifications original ly 746

applied to exposed bus bars in mainframe computers back in the 1960 ’s 747

and concerns at the time service personnel inadvertently bridging them wit h 748

a metal part. 749

However, when IEC TC 108 started the IEC 62368-1 project the intent was 750

to take a fresh look at product safety using HBSE and only carry over a 751

legacy requirement if the safety science and HBSE justified it. After 752

considerable study by IEC TC 108, there was no support for carrying over 753

the 240 VA requirement since: 754

− the requirements were not based on any proven science or sound 755

technical basis; 756

− the 240 VA value was relatively arb itrary; and 757

− in practice the requirement was difficult to apply consistently (for 758

example, on a populated printed board or inside a switch mode power 759

supply). 760

In the meantime, there are energy limits for capacitors in Clause 5, which 761

remains a more realistic concern and which were the second set of the 762

energy hazard requirements in IEC 60950-1, the first being steady state 763

240 VA. 764

Page 23: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 24 – IEC TR 62368-2:2019 © IEC 2019

In addition, there are other requirements in IEC 62368-1 that will limit 765

exposure to high levels of power (VA), including a VA limit for LPS outputs 766

when those are required by Annex Q (for outputs connected to buil ding 767

wiring as required by 6.5.2). 768

Electric burn (eBurn) 769

Analysis of the body current generated by increasing frequency sinusoidal 770

waveforms shows that the current continues to increase with frequency. 771

The same analysis shows that the touch current, which is discounted with 772

frequency, stabilizes. 773

The following paper describes the analysis fully: ‘Touch Current 774

Comparison, Looking at IEC 60990 Measurement Circuit Performance – 775

Part 1: Electric Burn'; Peter E Perkins; IEEE PSES Product Safety 776

Engineering Newsletter, Vol 4, No 2, Nov 2008. 777

The crossover frequency is different for the startle -reaction circuit than for 778

the let go-immobilization circuit because of the separate Frequency Factor 779

body response curves related to current levels; analysis identifies the 780

crossover frequency where the eBurn current surpasses the touch current. 781

Under these conditions, a person touching the circuit will become 782

immobilized and will not be able to let go of the circuit. This crossover 783

frequency is determined in the analysis. The person contacting the circuit 784

should always be able to let go. 785

The general conditions that apply to eBurn circuits are: 786

− the eBurn limit only applies to HF sinusoidal signals; 787

− the area of contact should be limited to a small, fingertip contact 788

(~ 1cm2); 789

− the contact time should be less than 1 s; at this short contact time, it is 790

not reasonable to define different levels for various persons; 791

This requirement applies to accessible circuits that can be contacted at 792

both poles, including all grounded circuits isolated from the mains and any 793

isolated circuits where both contacts are easily available to touch. 794

A simplified application of these requirements in the documents limits the 795

accessibility of HF sinusoidal currents above a specified frequency. The 796

22 kHz and 36 kHz frequency limits are where the eBurn current crosses 797

the 5mA limit for the ES1 and ES2 measurement circuits. This will ensure 798

that the person contacting the circuit will be able to remove themselves 799

from the circuit under these conditions. 800

1 MHz limit 801

The effects of electric current on the human body are described in the 802

IEC 60479 series and the requirements in IEC 62368-1 are drawn from 803

there. The effects versus frequency are well laid out and properly 804

accounted for in these requirements . The body effects move from 805

conducted effects to surface radiofrequency burns at higher frequencies 806

approaching 100 kHz. By long-term agreement, IEC safety documents are 807

responsible for outlining the effects of current to 1 MHz, which are properly 808

measured by the techniques given herein . Above the 1 MHz level, it 809

becomes an EMC issue. Unless the current is provided as a principal action 810

of the equipment operation, electric shock evaluation should not be needed 811

above the 1 MHz level. Where it is fundamental to the equipment 's 812

operation, the high-frequency current levels shall be specially measured 813

using proper high-frequency techniques, including classifying the circuits 814

and, if necessary, appropriately protected to avoid any bodily injury. 815

Page 24: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:2019 © IEC 2019 – 25 –

5.2.1 Electrical energy source classification s 816

Source: IEC TS 60479-1:2005 and IEC 61201 817

Purpose: To define the line between hazardous and non-hazardous electrical energy 818

sources for normal operating conditions and abnormal operating 819

conditions. 820

Rationale: The effect on persons from an electric source depend s on the current 821

through the human body. The effects are described in IEC TS 60479-1. 822

IEC TS 60479-1 (see Figures 20 and 22, Tables 11 and 13); zone AC-1 and 823

zone DC-1; usually no reaction (Figure 8 and Figure 9, Table 2 and Table 3 824

in this document) is taken as values for ES1. 825

IEC TS 60479-1 (see Figures 20 and 22; Tables 11 and 13); zone AC-2 and 826

zone DC-2; usually no harmful physiological effects (see Figure 8 and 827

Figure 9, Table 2 in this document) is taken as values for ES2. 828

IEC TS 60479-1; zone AC-3 and zone DC-3; harmful physiological effects 829

may occur (see Figure 8 and Figure 9, Table 2 and Table 3 in this 830

document) is the ES3 zone. 831

832

833

Figure 8 – Conventional time/current zones of effects 834

of AC currents (15 Hz to 100 Hz) on persons for a cur rent path corresponding 835

to left hand to feet (see IEC TS 60479-1:2005, Figure 20) 836

Page 25: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 26 – IEC TR 62368-2:2019 © IEC 2019

Table 2 – Time/current zones for AC 15 Hz to 100 Hz 837

for hand to feet pathway (see IEC TS 60479-1:2005, Table 11) 838

Zones Boundaries Physiological effects

AC-1 up to 0,5 mA curve a Perception possible but usually no startle reaction

AC-2 0,5 mA up to curve b Perception and involuntary muscular contractions likely but usually no harmful electrical physiological effects

AC-3 Curve b and above Strong involuntary muscular contractions. Difficulty in breathing.

Reversible disturbances of heart function. Immobilisation may occur.

Effects increasing with current magnitude. Usually no organic damage to be expected.

AC-4a Above curve c1 Pathophysiological effects may occur such as cardiac arrest,

breathing arrest, and burns or other cellular damage. Probability of ventricular fibrillation increasing with current magnitude and time.

c1 – c

2 AC-4.1 Probability of ventricular fibrillation increasing up to about

5 %.

c2 – c

3 AC-4.2 Probability of ventricular fibrillation up to about 50 %.

Beyond curve c3 AC-4.3 Probability of ventricular fibrillation above 50 %.

a For durations of current flow below 200 ms, ventricular fibrillation is only initiated within t he vulnerable period if the relevant thresholds are surpassed. As regards ventricular fibrillation , this figure relates to the effects of current that flows in the path left hand to feet. For other current paths , the heart current factor has to be considered.

839

840

Figure 9 – Conventional time/current zones of effects of DC currents on persons for 841

a longitudinal upward current path (see IEC TS 60479-1:2005, Figure 22) 842

Page 26: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:2019 © IEC 2019 – 27 –

Table 3 – Time/current zones for DC for hand to feet pathway 843

(see IEC TS 60479-1:2005, Table 13) 844

Zones Boundaries Physiological effects

DC-1 Up to 2 mA curve a Slight pricking sensation possible when making, breaking or rapidly altering current flow.

DC-2 2 mA up to curve b Involuntary muscular contractions likely , especially when making, breaking or rapidly altering current flow , but usually no harmful electrical physiological effects

DC-3 curve b and above Strong involuntary muscular reactions and reversible disturbances of formation and conduction of impulses in the heart may occur, increasing with current magnitude and time. Usually no organic damage to be expected.

DC-4a Above curve c1 Pathophysiological effects may occur such as cardiac arrest,

breathing arrest, and burns or other cellula r damage. Probability of ventricular fibrillation increasing with current magnitude and time.

c1 – c

2 DC-4.1 Probability of ventricular fibrillation increasing up to about

5 %.

c2 – c

3 DC-4.2 Probability of ventricular fibrillation up to about 50 %.

Beyond curve c3 DC-4.3 Probability of ventricular fibrillation above 50 %.

a For durations of current flow below 200 ms, ventricular fibrillation is only initiated within the vulnerable period if the relevant thresholds are surpassed. As regards ventricu lar fibrillation, this figure relates to the effects of current which flows in the path left hand to feet and for upward current. For other current paths , the heart current factor has to be considered.

845

The seriousness of an injury increases continuously with the energy 846

transferred to the body. To demonstrate this principle Figure 8 and Figure 9 847

in this document (see IEC TS 60479-1, Figures 20 and 22) are transferred 848

into a graph: effects vs energy (see Figure 10 in this document). 849

850

Figure 10 – Illustration that limits depend on both voltage and current 851

Within the document, only the limits for Zone 1 (green) and Zone 2 (yellow) 852

will be specified. 853

Curve “a” (limit of Zone 1) will be the limit for parts accessible by an 854

ordinary person during normal use. 855

Curve “b” (limit of Zone 2) will be the limit for parts accessible by an 856

ordinary person during (or after) a single fault. 857

Page 27: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 28 – IEC TR 62368-2:2019 © IEC 2019

IEC TC 108 regarded it not to be acceptable to go to the limits of either 858

Zone 3 or 4. 859

In the document three (3) zones are described as electrical energy sources. 860

This classification is as follows: 861

– electrical energy source 1 (ES1): levels are of such a value that they do 862

not exceed curve “a” (threshold of perception) of Figure 8 and Figure 9 863

in this document (see IEC TS 60479-1:2005, Figures 20 and 22). 864

– electrical energy source 2 (ES2): levels are of such a value that they 865

exceed curve “a”, but do not exceed curve “b” (threshold of let go) of 866

Figure 8 and Figure 9 in this document (see IEC TS 60479-1:2005, 867

Figures 20 and 22). 868

– electrical energy source 3 (ES3): levels are of such a value that they 869

exceed curve “b” of Figure 8 and Figure 9 in this document (see IEC 870

TS 60479-1:2005, Figures 20 and 22). 871

5.2.2.1 General 872

When classifying a circuit or part that is not accessible, that circuit or part 873

shall be regarded as being accessible when measuring prospective touch 874

voltage and touch current. 875

5.2.2.2 Steady-state voltage and current limits 876

Table 4 Electrical energy source limits for steady-state ES1 and ES2 877

Source: IEC TS 60479-1:2005, Dalziel, Effect of Wave Form on Let -Go Currents; 878

AIEE Electrical Engineering Transactions, Dec 1943, Vol 62. 879

Rationale: The current limits of Table 4 line 1 and 2 are derived from curve a and b, 880

Figure 8 and Figure 9 in this document (see IEC TS 60479-1:2005, Figures 881

20 and 22). 882

The basis for setting limits for combined AC and DC touch current is from 883

the work of Dalziel which provides clear data for men, women and children. 884

In the current diagram (Figure 22), the AC current is always the peak value 885

(per Dalziel). In the voltage diagram (Figure 23), the 30 V AC and 50 V AC 886

points on the baseline are recognized as AC RMS values as stated in 887

Table 4. Since IEC TC 108 is working with consumer appliances, there is a 888

need to provide protection for children, who are generally considered the 889

most vulnerable category of people . The formulas of IEC 62368-1:2018, 890

Table 4 address the Dalziel investigations. 891

Under single fault conditions of a relevant basic safeguard or 892

supplementary safeguard, touch current is measured according to 5.1.2 893

of IEC 60990:2016. However, this IEC 60990 subclause references both 894

the IEC 60990 perception/reaction network (Figure 4) and the let -go 895

network (Figure 5), selection of which depends on several factors. Figure 5 896

applies to touch current limits above 2 mA RMS. IEC TC 108 has decided 897

that parts under single fault conditions of relevant basic safeguards or 898

supplementary safeguards should be measured per Figure 5 (let -go 899

immobilization network). Therefore, since 5.1.2 makes reference to both 900

Figure 4 and Figure 5, for clarification Table 4 is mentioned directly in 901

5.2.2.2. 902

Because there is usually no reaction of the human body when touching 903

ES1, access is permitted by any person (IEC TS 60479-1; zone AC-1 and 904

zone DC-1). 905

Because there may be a reaction of th e human body when touching ES2, 906

protection is required for an ordinary person. One safeguard is sufficient 907

because there are usually no harmful physiological effects when t ouching 908

ES2 (IEC TS 60479-1:2005; zone AC-2 and zone DC-2). 909

Page 28: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:2019 © IEC 2019 – 29 –

Because harmful physiological effects may occur when touching ES3, (IEC 910

TS 60479-1:2005; zone AC-3 and zone DC-3), protection is required for an 911

ordinary person and an instructed person, including after a fault of one 912

safeguard. 913

During the application of the electrical energy source limits for “combined 914

AC and DC” in Table 4, if the AC component of a superimposed AC and DC 915

energy source does not exceed 10 % of the DC energy, then the AC 916

component can be disregarded for purposes of application of Table 4. This 917

consideration is valid based on the definition of DC voltage in 3.3.14.1, 918

which allows peak-to-peak ripple not exceeding 10 % of the average value 919

to integrated into DC voltage considerations. As a result, in such cases 920

where AC does not exceed 10 % of DC, only the DC energy source limits in 921

Table 4 need be applied. 922

When measuring combined AC and DC voltages and currents, both AC and 923

DC measurements shall be made between the same points of reference. 924

Do not combine common-mode measurements with differential-mode 925

measurements. They shall be assessed separately. 926

In using Table 4, ES1 touch current measurement specifies the startle -927

reaction circuit ‘a’ intended for limits less than 2 mA RMS / 2,8 mA peak 928

and ES2 touch current specifies the let -go-immobilization circuit ‘b’ 929

intended for limits > 2 mA RMS / 2,8 mA peak. These circuits are adopted 930

from IEC 60990:2016, Clause 5. 931

Normal operating conditions of equipment for touch current testing are 932

outlined in 5.7.2 and Clause B.2 of IEC 62368-1:2018 and includes 933

operation of all operator controls. Abnormal operating conditions are 934

specified in Clause B.3 of IEC 62368-1:2018. Single fault conditions 935

(within the equipment), specified in Clause B.4 of IEC 62368-1:2018, 936

includes faults of a relevant basic safeguard or a supplementary 937

safeguard. 938

5.2.2.3 Capacitance limits 939

Table 5 Electrical energy source limits for a charged capacitor 940

Source: IEC TS 61201:2007 (Annex A) 941

Rationale: Where the energy source is a capacitor, the energy source class is 942

determined from both the charge voltage and the capacitance. The 943

capacitance limits are derived from IEC TS 61201:2007, see Table 4 in this 944

document. 945

The values for ES2 are derived from Table A .2 of IEC TS 61201:2007. 946

The values for ES1 are calculated by dividing the values from Table A .2 of 947

IEC TS 61201:2007 by two (2). 948

Page 29: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 30 – IEC TR 62368-2:2019 © IEC 2019

Table 4 – Limit values of accessible capacitance (threshold of pain) 949

U

V

C

F

U

kV

C

nF

70 42,4 1 8,0

78 10,0 2 4,0

80 3,8 5 1,6

90 1,2 10 0,8

100 0,58 20 0,4

150 0,17 40 0,2

200 0,091 60 0,133

250 0,061

300 0,041

400 0,028

500 0,018

700 0,012

950

5.2.2.4 Single pulse limits 951

Table 6 Voltage limits for single pulses 952

Rationale: The values are based on the DC current values of Table 4, assuming 953

25 mA gives a voltage of 120 V DC (body resistance of 4,8 kΩ). The lowest 954

value is taken as 120 V because, under single fault conditions, the 955

voltage of ES1 can be as high as 120 V DC without a time limit. 956

The table allows linear interpolation because the difference is considered to 957

be very small. However, the following formula may be used for a more 958

exact interpolation of the log-log based values in this table. The variable t 959

or V is the desired unknown "in between value" and either may be 960

determined when one is known: 961

22 1

1

2

1

–1

log loglog log

log logAntilog

log log

log log

t tV V

t tV

t t

t t

+

=

+

962

and 963

22 1

1

2

1

–1

log loglog log

log logAntilog

log log

log log

V Vt t

V Vt

V V

V V

+

=

+

964

where: 965

t is the time duration that is required to be determined if Upeak

voltage V is known (or t 966 is known and V needs to be determined) 967

t1 is the time duration adjacent to t corresponding to the U

peak voltage V

1 968

t2 is the time duration adjacent to t corresponding to the U

peak voltage V

2 969

V is the Upeak

voltage value that is known if time duration t is to be determined (or V is 970

required to be determined if time duration t is known) 971

V1 is the value of the voltage U

peak adjacent to V corresponding to time duration t

1 972

V2 is the value of the voltage U

peak adjacent to V corresponding to time duration t

2 973

Page 30: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:2019 © IEC 2019 – 31 –

Table 7 Current limits for single pulses 974

Source: IEC TS 60479-1:2005 975

Rationale: For ES1, the limit of single pulse should not exceed the ES1 steady-state 976

voltage limits for DC voltages. 977

For ES2, the voltage limits have been calculated by using the DC current 978

values of curve b Figure 9 in this document and the resistance values of 979

Table 10 of IEC TS 60479-1:2005, column for 5 % of the population (see 980

Table 5 in this document). 981

The current limits of single pulses in Table 7 for ES1 levels are from curve 982

a and for ES2 are from curve b of Figure 9 in this document. 983

The table allows linear interpolation because the difference is considered to 984

be very small. However, the following formula may be used for a more 985

exact interpolation of the log-log based values in this table. The variable t 986

or I is the desired unknown "in between value" and either may be 987

determined when one is known: 988

989

22 1

1

2

1

–1

log loglog log

log logAntilog

log log

log log

t tI I

t tI

t t

t t

+

=

+

990

and 991

22 1

1

2

1

–1

log loglog log

log logAntilog

log log

log log

I It t

I It

I I

I I

+

=

+

992

where: 993

t is the time duration that is required to be determined if the electric current I is 994 known (or t is known and I needs to be determined) 995

t1 is the time duration adjacent to t corresponding to the electric current I

1 996

t2 is the time duration adjacent to t corresponding to the electric current I

2 997

I is the value of the Ipeak

current that is known if time duration t is to be determined 998 (or I is required to be determined if time duration t is known) 999

I1 is the value of the I

peak adjacent to I corresponding to time duration t

1 1000

I2 is the value of the I

peak adjacent to I corresponding to time duration t

2 1001

Page 31: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 32 – IEC TR 62368-2:2019 © IEC 2019

Table 5 – Total body resistances RT for a current path hand to hand, DC, 1002

for large surface areas of contact in dry condition 1003

Touch voltage

V

Values for the total body resistance RT ()

that are not exceeded for

5 % of the

population

50 % of the

population

95 % of the

population

25

50

75

100

125

150

175

200

225

400

500

700

1 000

2 100

1 600

1 275

1 100

975

875

825

800

775

700

625

575

575

3 875

2 900

2 275

1 900

1 675

1 475

1 350

1 275

1 225

950

850

775

775

7 275

5 325

4 100

3 350

2 875

2 475

2 225

2 050

1 900

1 275

1 150

1 050

1 050

Asymptotic value 575 775 1 050

NOTE 1 Some measurements indicate that the total body resistance RT for the current path hand to foot

is somewhat lower than for a current path hand to hand (10 % to 30 %).

NOTE 2 For living persons the values of RT correspond to a duration of current flow of about 0,1 s.

For longer durations RT values may decrease (about 10 % to 20 %) and after complete rupture

of the skin RT approaches the initial body resistance Ro.

NOTE 3 Values of RT are rounded to 25 .

1004

1005

5.2.2.6 Ringing signals 1006

Source: EN 41003 1007

Purpose: To establish limits for analogue telephone network ringing signals . 1008

Rationale: For details see rationale for Annex H. Where the energy source is an 1009

analogue telephone network ringing signal as defined in Annex H, the 1010

energy source class is taken as ES2 (as in IEC 60950-1:2005, Annex M). 1011

5.2.2.7 Audio signals 1012

Source: IEC 60065:2014 1013

Purpose: To establish limits for touch voltages for audio signals . 1014

Rationale: The proposed limits for touch voltages at terminals involving audio signals 1015

that may be contacted by persons have been extracted without deviation 1016

from IEC 60065. Reference: IEC 60065:2014, 9.1.1.2 a). Under single 1017

fault conditions, 10.2 of IEC 60065:2014 does not permit an increase in 1018

acceptable touch voltage limits. 1019

Page 32: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:2019 © IEC 2019 – 33 –

The proposed limits are quantitatively larger than the accepted limits of 1020

Tables 5 and 6, but are not considered danger ous for the following 1021

reasons: 1022

– the output is measured with the load disconnected (worst case load) ; 1023

– defining the contact area of connectors and wiring is very difficult due to 1024

complex shapes. The area of contact is considered small due to the 1025

construction of the connectors; 1026

– normally, it is recommended to the user, in the instruction manual 1027

provided with the equipment, that all connections be made with the 1028

equipment in the “off” condition; 1029

– in addition to being on, the equipment would have to be pla ying some 1030

program at a high output with the load disconnected to achieve the 1031

proposed limits (although possible, highly unlikely). Historically, no 1032

known cases of injury are known for amplifiers with non -clipped output 1033

less than 71 V RMS; 1034

– the National Electrical Code (USA) permits accessible terminals with 1035

maximum output voltage of 120 V RMS. 1036

5.3.2 Accessibility to electrical energy sources and safeguards 1037

1038

What are the requirements between the non-accessible sources? 1039

Answer: None. As the enclosure is double insulated, the sources are not 1040

accessible. 1041

1042

Now there is an accessible connection. What are the requirements 1043

between the sources in this case? 1044

Page 33: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 34 – IEC TR 62368-2:2019 © IEC 2019

Answer: 1045

– Basic insulation between ES1 and ES2 1046

– Double insulation or reinforced insulation between ES1 and ES3 1047

– The insulation between ES2 and ES3 depends on the insulation 1048

between the ES1 and ES2 1049

1050

Now there are two accessible connections from independent sources. 1051

What are the requirements between the sources in this case? 1052

Answer: 1053

– According to Clause B.4, the insulation or any components between the 1054

sources need to be shorted 1055

– If one of the two ES1 sources would reach ES2 levels basic 1056

safeguard 1057

– If both ES1 sources stay within ES1 limits no safeguard (functional 1058

insulation) 1059

For outdoor equipment, lower voltage limits apply because the body 1060

impedance is reduced to half the value when subjected to wet conditions as 1061

described in IEC TS 60479-1 and IEC TS 61201. 1062

Where Class III equipment is acceptable in an indoor application , this outdoor 1063

application does not introduce additional safeguard requirements. 1064

5.3.2.2 Contact requirements 1065

Source: IEC 61140:2001, 8.1.1 1066

Purpose: Determination of accessible parts for adults and children. Tests are in 1067

IEC 62368-1:2018, Annex V. 1068

Rationale: According to Paschen’s Law, air breakdown does not occur below 1069

323 V peak or DC (at sea level). IEC 62368-1:2018 uses 420 V peak (300 V 1070

RMS) to add an additional safety margin. 1071

5.3.2.3 Compliance criteria 1072

The reason for accepting different requirements for components is because 1073

you cannot expect your supplier to make different components for each end 1074

application. 1075

5.3.2.4 Terminals for connecting stripped wire 1076

Source: IEC 60065 1077

Purpose: To prevent contact of ES2 or ES3 parts . 1078

Page 34: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:2019 © IEC 2019 – 35 –

Rationale: Accepted constructions used in the audio/video industry for many years. 1079

5.4 Insulation materials and requirements 1080

Rationale: The requirements, test methods and compliance criteria are taken from the 1081

actual outputs from IEC TC 108 MT2 (formerly WG6) as well as from IEC 1082

TC 108 MT1. 1083

– The choice and application of components shall take into account the 1084

needs for electrical, thermal and mechanical strength, frequency of the 1085

working voltage and working environment (temperature, pressure, 1086

humidity and pollution). 1087

– Components shall have the electric strength, thermal strength, 1088

mechanical strength, dimensions, and other properties as specified in 1089

the document. 1090

– Depending on the grade of safeguard (basic safeguard, 1091

supplementary safeguard, reinforced safeguard) the requirements 1092

differ. 1093

– Components complying with their component documents (for example, 1094

IEC 60384-14 for capacitances) have to be verified for their application. 1095

– The components listed in this subclause of the new document have a 1096

separation function. 1097

5.4.1.1 Insulation 1098

Source: IEC 60664-1 1099

Purpose: Provide a reliable safeguard 1100

Rationale: Solid basic insulation, supplementary insulation, and reinforced 1101

insulation shall be capable of durably withstanding electrical, mechanical, 1102

thermal, and environmental stress that may occur during the anticip ated 1103

lifetime of the equipment. 1104

Clearances and creepage distances may be divided by intervening 1105

unconnected (floating) conductive parts, such as unused contacts of a 1106

connector, provided that the sum of the individual distances meets the 1107

specified minimum requirements (see Figure O.4). 1108

5.4.1.4 Maximum operating temperatures for materials , components and systems 1109

Source: IEC 60085, IEC 60364-4-43, ISO 306, IEC 60695-10-2 1110

Rationale: Temperature limits given in Table 9: 1111

– limits for insulation materials including electrical insulation systems, 1112

including winding insulation (C lasses A, E, B, F, H, N, R and 250) are 1113

taken from IEC 60085; 1114

– limits for insulation of internal and external wiring, including power 1115

supply cords with temperature marking are those indi cated by the 1116

marking or the rating assigned by the (component) manufacturer ; 1117

– limits for insulation of internal and external wiring, including power 1118

supply cords without temperature marking of 70 °C are referenced in 1119

IEC 60364-4-43 for an ambient temperature of 25 °C; 1120

– limits for thermoplastic insulation are based on: 1121

• data from Vicat test B50 of ISO 306; 1122

• ball pressure test according to IEC 60695-10-2; 1123

• when it is clear from the examination of the physical characteristics of 1124

the material that it will meet the requirements of the ball pressure 1125

test; 1126

Page 35: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 36 – IEC TR 62368-2:2019 © IEC 2019

• experience with 125 °C value for parts in a circuit supplied from the 1127

mains. 1128

5.4.1.4.3 Compliance criteria 1129

Table 9 Temperature limits for materials, components and systems 1130

Rationale Regarding condition “a”, it has been assumed by the technical committee 1131

for many years that the thermal gradient between outer surface and inner 1132

windings will be limited to 10 °C differential as an average. As a result, the 1133

temperature limits for outer surface insulation measured via thermocouple 1134

is 10 °C lower than similar measurement with a thermocouple embedded in 1135

the winding(s), with both limits at least 5 °C less than the hot-spot 1136

temperature allowed per IEC 60085 as an additional safety factor. 1137

However, some modern transformer constructions with larger power 1138

densities may have larger thermal gradients, as may some outer surface 1139

transformer insulation thermal measurements in the equipment/system be 1140

influenced by forced cooling or similar effects. Therefore, if thermal 1141

imaging, computer modeling, or actual measurement shows a thermal 1142

gradient greater than 10 °C average between transformer surface 1143

temperature and transformer winding(s), the rise of resistance temperature 1144

measurement method and limits for an embedded thermocouple shoul d be 1145

used (for example, 100 °C maximum temperature for Class 105 (A)) for 1146

determining compliance of a transformer with Table 9 since the original 1147

assumptions do not hold true. 1148

As an example, a material rated for 124 °C using the rise of resistance 1149

method is considered suitable for classes whose temperature is lower 1150

(class with letter codes E and A) and not for classes whose temperature is 1151

higher (class with letter codes B, F, H, N, R and 250). 1152

5.4.1.5 Pollution degrees 1153

Source: IEC 60664-1 1154

Rationale: No values for PD 4 (pollution generates persistent conductivity) are 1155

included, as it is unlikely that such conditions are present when using 1156

products in the scope of the document. 1157

5.4.1.5.2 Test for pollution degree 1 environment and for an insulating compoun d 1158

The compliance check made by visual inspection applies both to single 1159

layer and multi-layer boards without the need for sectioning to check for 1160

voids, gaps, etc. 1161

5.4.1.6 Insulation in transformers with varying dimensions 1162

Source: IEC 60950-1 1163

Purpose: To consider actual working voltage along the winding of a transformer . 1164

Rationale: Description of a method to determine adequacy of solid insulation along 1165

the length of a transformer winding. 1166

5.4.1.7 Insulation in circuits generating starting pulses 1167

Source: IEC 60950-1, IEC 60664-1 1168

Purpose: To avoid insulation breakdown due to starting pulses. 1169

Rationale: This method has been successfully used for products in the scope of this 1170

document for many years. 1171

5.4.1.8 Determination of working voltage 1172

Source: IEC 60664-1:2007, 3.5; IEC 60950-1 1173

Page 36: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:2019 © IEC 2019 – 37 –

Rationale: The working voltage does not include short duration signals, such as 1174

transients. Recurring peak voltages are not included. Transient 1175

overvoltages are covered in the required withstand voltage. Ringing 1176

signals do not carry external transients. 1177

5.4.1.8.1 General 1178

Rationale: Functional insulation is not addressed in Clause 5, as it does not provide 1179

protection against electric shock. Requirements for functional insulation 1180

are covered in Clause 6, which addresses protection against electrically 1181

caused fire. 1182

Source: IEC 60664-1:2007, 3.8 1183

Rationale: In IEC 62368-1, “Circuit supplied from the mains” is used for a “primary 1184

circuit”. “Circuit isolated from the mains” is used for a “secondary circuit”. 1185

“External circuit” is defined as external to the equipment. ES1 can be 1186

external to the equipment. 1187

For an external circuit operating at ES2 level and not exiting the building, 1188

the transient is 0 V. Therefore, in this case, ringing peak voltage needs to 1189

be taken into account. 1190

5.4.1.8.2 RMS working voltage 1191

Source: IEC 60664-1:2007, 3.5 1192

Rationale: RMS working voltage is used when determining minimum creepage 1193

distance. Unless otherwise specified, working voltage is the RMS value. 1194

5.4.1.10 Thermoplastic parts on which conductive meta llic parts are directly mounted 1195

Source: ISO 306 and IEC 60695-2 series 1196

Rationale: The temperature of the thermoplastic parts under normal operating 1197

conditions shall be 15 K less than the softening temperature of a non -1198

metallic part. Supporting parts in a circuit supplied from the mains shall not 1199

be less than 125 °C. 1200

5.4.2 Clearances 1201

5.4.2.1 General requirements 1202

Source: IEC 60664-1:2007 1203

Rationale: The dimension for a clearance is determined from the required impulse 1204

withstand voltage for that clearance. This concept is taken from 1205

IEC 60664-1:2007, 5.1. In addition, clearances are affected by the largest 1206

of the determined transients. The likelihood of simultaneous occurrence of 1207

transients is very low and is not taken into account . 1208

Overvoltages and transients that may enter the equipment, and peak 1209

voltages that may be generated within the equipment, do not break down 1210

the clearance (see IEC 60664-1:2007, 5.1.5 and 5.1.6). 1211

Minimum clearances of safety components shall comply with the 1212

requirements of their appl icable component safety document. 1213

Clearances between the outer insulating surface of a connector and 1214

conductive parts at ES3 voltage level shall comply with the requirements of 1215

basic insulation only, if the connectors are fixed to the equipment, located 1216

internal to the outer electrical enclosure of the equipment, and are 1217

accessible only after removal of a sub-assembly that is required to be in 1218

place during normal operation. 1219

It is assumed that the occurrence of both factors, the sub-assembly being 1220

removed and the occurrence of a transient overvoltage , have a reduced 1221

likelihood and hazard potential. 1222

Page 37: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 38 – IEC TR 62368-2:2019 © IEC 2019

Source: IEC 60664-2 series, Application guide 1223

Rationale: The method is derived from the IEC 60664-2 series, Application guide. 1224

Example:

Assuming: – an SMPS power supply, – connection to the AC mains, – a peak of the working voltage (PWV) of 800 V, – frequencies above and below 30 kHz, – reinforced clearances required, – temporary overvoltages: 2 000 V Procedure 1: Table 10 requires 2,54 mm Table 11 requires 0,44 mm Result is 2,54 mm

NOTE All PWV below 1 200 V have clearance requirements less than 3 mm for both Table 10 and Table 11

Procedure 2: Transients (OVC 2): 2 500 V RWV = 2 500 V Table 14 requires 3,0 mm The required ES test voltage according to Table 15 is 4,67 KV Result is 3,0 mm or ES test at 4,67 KV

Final result: – 3,0 mm or – ES test at 4,67 KV and 2,54 mm ATTENTION:

For a product with connection to coax cable, different values are to be used since a different transient and required withstand voltage is required.

Page 38: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:2019 © IEC 2019 – 39 –

1225

5.4.2.2 Procedure 1 for determining clearance 1226

Rationale: Related to the first dash of 5.4.2.2, it is noted that an example of a cause of 1227

determination of the peak value of steady state voltages that are below the 1228

peak voltage of the mains includes, for example, a determination in 1229

accordance with the 2nd and 3rd dash of 5.4.2.3.3 where filtering is in 1230

place to lower expected peak voltages. 1231

Similarly, related to the second dash of 5.4.2.2, an example of this case 1232

where the recurring peak voltage is limited to 1,1 times the mains voltage 1233

may be use of certain forms of surge protection devices that reduce 1234

overvoltage category. 1235

Peak of the working voltage versus recurring peak voltage. 1236

There has been some discussion between the two terms. The peak of the 1237

working voltage is the peak value of the waveform that occurs each cycle, 1238

and therefore is considered to be a part of the working voltage. 1239

A recurring peak voltage is a peak that does not occur at each cycle of the 1240

waveform, but that reoccurs at a certain interval, usually at a lower 1241

frequency than the waveform frequency. 1242

Figure 11 in this document gives an example of a waveform where the 1243

recurring peak voltage occurs every two cycles of the main waveform . 1244

1245

Figure 11 – Illustration of working voltage 1246

Table 10 Minimum clearances for voltages with frequencies up to 30 kHz 1247

Rationale: IEC TC 108 noted that, if the rules of IEC 60664-1 are followed, for 1248

reinforced clearance, some values were more than double the 1249

requirements for basic insulation. IEC TC 108 felt that this should not be 1250

the case and decided to limit the requirement for reinforced insulation to 1251

twice the value of basic insulation, thereby deviating from IEC 60664-1. 1252

In addition, normal rounding rules were applied to the values in the table. 1253

5.4.2.3.2.2 Determining AC mains transient voltages 1254

Source: IEC 60664-1:2007, 4.3.3.3 1255

Rationale: Table 12 is derived from Table F.1 of IEC 60664-1:2007. 1256

The term used in IEC 60664-1 is ‘rated impulse voltage’. Products covered 1257

by IEC 62368-1 are also exposed to transients from external circuits, and 1258

therefore another term is needed, to show the different source. 1259

Page 39: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 40 – IEC TR 62368-2:2019 © IEC 2019

Outdoor equipment that is part of the building installation, or that may be 1260

subject to transient overvoltages exceeding those for Overvoltage 1261

Category II, shall be designed for Overvoltage Category III or IV, unless 1262

additional protection is to be provided internally or externally to the 1263

equipment. In this case, the installation instructions shall state the need for 1264

such additional protection. 1265

5.4.2.3.2.3 Determining DC mains transient voltages 1266

Rationale: Transient overvoltages are attenuated by the capacitive filtering. 1267

5.4.2.3.2.4 Determining external circuit transient voltages 1268

Source: ITU-T K.21 1269

Rationale: Transients have an influence on circuits and insulation, therefore transients 1270

on external circuits need to be taken into account. Transients are needed 1271

only for the dimensioning safeguards. Transients should not be used for 1272

the classification of energy sources (ES1, ES2, etc.). 1273

It is expected that external circuits receive a transient voltage of 1,5 kV 1274

peak with a waveform of 10/700s from sources outside the building. 1275

The expected transient is independent from the application (telecom; LAN 1276

or other). Therefore, it is assumed that for all kinds of applications the 1277

same transient appears. The value 1,5 kV 10/700s is taken from ITU-T 1278

K.21. 1279

It is expected that external circuits using earthed coaxial cable receive no 1280

transients that have to be taken into account from sources outside the 1281

building. 1282

Because of the earthed shield of the coaxial cable , a possible transient on 1283

the outside cable will be reduced at the earthed shield at the building 1284

entrance of the cable. 1285

It is expected that for external circuits within the same building no 1286

transients have to be taken into account. 1287

The transients for an interface are defined with respect to the terminals 1288

where the voltage is defined. For the majority of cases, the relevant 1289

voltages are common (Uc) and differential mode (Ud) voltages at the 1290

interface. For hand-held parts or other parts in extended contact with the 1291

human body, such as a telephone hand set, the voltage with respect to 1292

local earth (Uce) may be relevant. Figure 12 in this document shows the 1293

definition of the various voltages for paired -conductor interface. 1294

The transients for coaxial cable interfaces are between the centre 1295

conductor and shield (Ud) of the cable if the shield is earthed at the 1296

equipment. If the shield is isolated from earth at the equipment, then the 1297

shield-to-earth voltage (Us) is important. Earthing of the shield can consist 1298

of connection of the shield to the protective earthing, functional earth 1299

inside or immediately outside the equipment. It is assumed that all earths 1300

are bonded together. Figure 13 in this document shows the definition of the 1301

various voltages for coaxial-cable interfaces. 1302

An overview of insulation requirements is given in Table 6 in this document. 1303

Page 40: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:2019 © IEC 2019 – 41 –

1304

1305

1306

Figure 12 – Illustration of transient voltages on paired conductor external circuits 1307

Page 41: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 42 – IEC TR 62368-2:2019 © IEC 2019

1308

1309

Figure 13 – Illustration of transient voltages on coaxial -cable external circuits 1310

Table 6 – Insulation requirements for external circuits 1311

External Circuit under consideration

Insulation Requirement

ES1 earthed None None

ES1 unearthed Separation (to floating metal parts and other floating ES1 circuits)

Electric strength test (using Table 15) between unearthed ES1 and other unearthed ES1 and floating parts

ES2 Basic insulation (to ES1 and metal parts)

Clearances; creepage distance; and solid insulation and by electric strength test (using Table 15) between ES2 and ES1 and metal parts

ES3 Double insulation or reinforced insulation (to ES1, ES2 and metal parts)

Clearances; creepage distance; and solid insulation requirements including electric strength test (using Table 15)

1312

Table 13 External circuit transient voltages 1313

Rationale: When the DC power distribution system is located outside the building, 1314

transient over-voltages can be expected. Transients are not present if the 1315

DC power system is connected to protective earthing and is located 1316

entirely within a single building. 1317

5.4.2.3.2.5 Determining transient voltage levels by measurement 1318

Source: Test method is taken from IEC 60950-1:2013, Annex G. 1319

5.4.2.3.4 Determining clearances using required withstand voltage 1320

Source: IEC 60664-1:2007, Table F.2 Case A (inhomogeneous field) and Case B 1321

(homogeneous field) 1322

Page 42: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:2019 © IEC 2019 – 43 –

Rationale: Values in Table 14 are taken from IEC 60664-1:2007 Table F.2 Case A 1323

(inhomogeneous field) and Case B (homogeneous field) and include explicit 1324

values for reinforced insulation . Clearances for reinforced insulation 1325

have been calculated in accordance with 5.1.6 of IEC 60664-1:2007. For 1326

reinforced insulation 5.1.6 states clearance shall be to the corresponding 1327

rated impulse voltage that is one step higher for voltages in the preferred 1328

series. For voltages that are not in the preferred series, the clearance 1329

should be based on 160 % of the required withstand voltage for basic 1330

insulation. 1331

When determining the required withstand voltage, interpolation should be 1332

allowed when the internal repetitive peak voltages are higher than the 1333

mains peak voltages, or if the required withstand voltage is above the 1334

mains transient voltage values. 1335

No values for PD 4 (pollution generates persistent conductivity) are 1336

included, as it is unlikely that such conditions are present when using 1337

products in the scope of the document. 1338

Table 14 Minimum clearances using required withstand voltage 1339

Rationale: IEC 62368-1 follows the rules and requirements of IEC basic safety 1340

publications, one of which is the IEC 60664 series. IEC 60664-1 specifies 1341

clearances for basic insulation and supplementary insulation. 1342

Clearances for reinforced insulation are not specified. Instead, 5.1.6 1343

specifies the rules for determining the reinforced clearances. 1344

The reinforced clearances in Table 14 have a varying slope, and include a 1345

“discontinuity”. The values of Table 14 are shown in Figure 14 in this 1346

document. 1347

1348

Figure 14 – Basic and reinforced insulation in Table 14 of IEC 62368-1:2018; 1349

ratio reinforced to basic 1350

Page 43: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 44 – IEC TR 62368-2:2019 © IEC 2019

The brown line, reinforced clearance, is not a constant slope as is the 1351

yellow line, basic clearance. The ratio of reinforced to basic (blue line) 1352

varies from a maximum of 2:1 to a minimum of 1,49:1. Physically, this is not 1353

reasonable; the ratio should be nearly constant. 1354

In IEC 60664-1:2007, the values for basic insulation are given in Table 1355

F.2. No values are given for reinforced insulation. Table F.2 refers to 1356

5.1.6 for reinforced insulation. 1357

Rule 1, preferred series impulse withstand voltages 1358

Subclause 5.1.6 of IEC 60664-1:2007 states: 1359

“With respect to impulse voltages, clearances of reinforced insulation 1360

shall be dimensioned as specified in Table F.2 corresponding to the rated 1361

impulse voltage but one step higher in the preferred series of values in 1362

4.2.3 than that specified for basic insulation.” 1363

NOTE 1 IEC 62368-1 uses the term “required withstand voltage” instead of the 1364 IEC 60664-1 term “required impulse withstand voltage.” 1365

NOTE 2 IEC 62368-1 uses the term “mains transient voltage” instead of the IEC 60664-1 1366 term “rated impulse voltage.” 1367

The preferred series of values of rated impulse voltage acco rding to 4.2.3 1368

of IEC 60664-1:2007 is: 330 V, 500 V, 800 V, 1 500 V, 2 500 V, 4 000 V, 6 1369

000 V, 8 000 V, 12 000 V 1370

Applying Rule 1, the reinforced clearance (inhomogeneous field, pollution 1371

degree 2, Table F.2) for: 1372

– 330 V would be the basic insulation clearance for 500 V: 0,2 mm 1373

– 500 V would be the basic insulation clearance for 800 V: 0,2 mm 1374

– 800 V would be the basic insulation clearance for 1 500 V: 0,5 mm 1375

– 1 500 V would be the basic insulation clearance for 2 500 V: 1,5 mm 1376

– 2 500 V would be the basic insulation clearance for 4 000 V: 3,0 mm 1377

– 4 000 V would be the basic insulation clearance for 6 000 V: 5,5 mm 1378

– 6 000 V would be the basic insulation clearance for 8 000 V: 8,0 mm 1379

– 8 000 V would be the basic insulation clearance for 12 000 V: 14 mm 1380

– 12 000 V is indeterminate because there is no preferred voltage above 1381

12 000 volts. 1382

Rule 2, 160 % of impulse withstand voltages other than the preferred 1383

series 1384

With regard to non-mains circuits, subclause 5.1.6 of IEC 60664-1:2007 1385

states: 1386

“If the impulse withstand voltage required for basic insulation according to 1387

4.3.3.4.2 is other than a value taken from the preferred series, reinforced 1388

insulation shall be dimensioned to withstand 160 % of the value required 1389

for basic insulation.” 1390

The impulse withstand voltages other than the preferred series (in 1391

IEC 60664-1:2007, Table F.2) are: 400 V, 600 V, 1 200 V, 2 000 V, 3 000 1392

V, 10 000 V, and all voltages above 12 000 V. 1393

Applying Rule 2, the reinforced clearance (inhomogeneous field, pollution 1394

degree 2, Table F.2) for: 1395

400 V x 1,6 = 640 V interpolated to 0,20 mm. 1396

Since 640 V is not in the list, the reinforced insulation is determined by 1397

interpolation. Interpolation yields the reinforced clearance as 0,2 mm. 1398

Page 44: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:2019 © IEC 2019 – 45 –

Applying Rule 2 to the impulse withstand voltag es in Table F.2 that are not 1399

in the preferred series: 1400

– 400 V × 1,6 = 640 V interpolated to 0,20 mm 1401

– 600 V × 1,6 = 960 V interpolated to 0,24 mm 1402

– 1 200 V × 1,6 = 1 920 V interpolated to 0,92 mm 1403

– 2 000 V × 1,6 = 1 320 V interpolated to 2,2 mm 1404

– 3 000 V × 1,6 = 4 800 V interpolated to 3,8 mm 1405

– 10 000 V × 1,6 = 13 000 V interpolated to 19,4 mm 1406

– 15 000 V to 100 000 V × 1,6 and interpolated according to the rule. 1407

Clearance differences for Rules 1 and 2 1408

The two rules, Rule 1 for impulse withstand voltages o f the preferred 1409

series, and Rule 2 for impulse withstand voltages other than the preferred 1410

series, yield different clearances for the same voltages. These differences 1411

occur because the slope, mm/kV, of the two methods is slightly different. 1412

The slope for Rule 1 is not constant. The slope for Rule 2 is nearly 1413

constant. Figure 15 in this document illustrates the differences between 1414

Rule 1, Rule 2 and Table 14 of IEC 62368-1:2018. 1415

1416

Figure 15 – Reinforced clearances according to Rule 1, Rule 2 , and Table 14 1417

If the two values for Rules 1 and 2 are combined into one set of values, the 1418

values are the same as in existing Table 14 (the brown line in Figure 14 1419

and Figure 15 in this document). According to IEC 60664-1:2007, 5.1.6, 1420

only the impulse withstand voltages “other than a value taken from the 1421

preferred series…” are subject to the 160 % rule. Therefore, the 1422

clearances jump from Rule 1 criteria to Rule 2 criteria and back again. This 1423

yields the radical slope changes of the Table 14 reinforced clearances 1424

(brown) line. 1425

Rule 1

Rule 2

Basic insulation

Table 15

Page 45: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 46 – IEC TR 62368-2:2019 © IEC 2019

Physically, the expected reinforced insulation clearances should be a 1426

constant proportion of the basic insulation clearances. However, the 1427

proportion between steps of Rule 1 (preferred series of impulse withstand 1428

voltages) are: 1429

– 330 V to 500 V: 1,52 1430

– 500 V to 800 V: 1,60 1431

– 800 V to 1 500 V: 1,88 1432

– 1 500 V to 2 500 V: 1,67 1433

– 2 500 V to 4 000 V: 1,60 1434

– 4 000 V to 6 000 V: 1,50 1435

– 6 000 V to 8 000 V: 1,33 1436

– 8 000 V to 12 000 V: 1,50 1437

Average proportion, 330 to 12 000: 1,57 1438

For Rule 2, all of the clearances for reinforced insulation are based on 1439

exactly 1,6 times the non-preferred series impulse withstand voltage for 1440

basic insulation. 1441

The two rules applied in accordance with 5.1.6 of IEC 60664-1:2007 result 1442

in the variable slope of the clearance requirements for reinforced 1443

insulation of IEC 62368-1. 1444

IEC TC 108 noted that, if the rules of IEC 60664-1 are followed, for 1445

clearances for reinforced insulation , some values were more than double 1446

the requirements for basic insulation. IEC TC 108 felt that this should not 1447

be the case and decided to limit the requirement for reinforced insulation 1448

to twice the value of basic insulation, thereby deviating from IEC 60664-1. 1449

In addition, normal rounding rules were applied to the values in the table. 1450

5.4.2.4 Determining the adequacy of a clearance using an electric strength test 1451

Source: IEC 60664-1:2007, Table F.5 1452

Purpose: Tests are carried out by either impulse voltage or AC voltage with the 1453

values of Table 15. 1454

Rationale: The impulse test voltages in Table 15 are taken from IEC 60664-1:2007, 1455

Table F.5. The calculation for the AC RMS. values as well as the DC values 1456

are based on the values given in Table A.1 of IEC 60664-1:2007 (see 1457

Table 7 in this document for further explanation). 1458

This test is not suited for homogenous fields. This is for an actual design 1459

that is within the limits of the homogenous and inhomogeneous field. 1460

Calculations for the voltage drop across an air gap during the electric 1461

strength test may be rounded up to the next higher 0,1 mm increment. In 1462

case the calculated value is higher than the value in the next row, the next 1463

row may be used. 1464

Enamel Material: Most commonly used material is polyester resin or 1465

polyester 1466

Dielectric constant for Polyester: 5 (can vary) 1467

Dielectric constant for air: 1 1468

Formula used for calculation (voltage divides inversely proportional to the 1469

dielectric constant) 1470

Transient = 2 500 V = 2 500 ( thickness of enamel / 5 + air gap / 1) = 2 500 1471

(0,04 / 5 + 2 / 1 for 2 mm air gap) = 2 500 (0,008 + 2) = (10 V across 1472

enamel + 2 490 V across air gap) 1473

Page 46: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:2019 © IEC 2019 – 47 –

Related to condition a of Table 15, although U is any required withstand 1474

voltage higher than 12,0 kV, there is an exception when using Table F.5 of 1475

IEC 60664-1:2007. 1476

Table 7 – Voltage drop across clearance and solid insulation in seri es 1477

Enamel thickness

mm

Air gap

mm

Transient on 240 V system

Transient voltage

across air gap

Transient voltage across enamel

Peak impulse

test voltage for

2 500 V peak

transient from

Table 16

Test voltage

across air gap

Test voltage across enamel

Material: Polyester, dielectric constant = 5

0,04 2 2 500 2 490 10 2 950 12 2 938

0,04 1 2 500 2 480 20 2 950 24 2 926

0,04 0,6 2 500 2 467 33 2 950 39 2 911

For 2 500 V peak impulse (transient for 230 V system), the homogenous field distanc e is 0,6 mm (from Table A.1 of IEC 60664-1:2007). Our test voltage for 2 500 V peak is 2 950 V peak from Table 15. This means that a minimum distance of 0,79 mm through homogenous field needs to be maintained to pass the 2 950 V impulse test.

This gives us a margin of (0,19 /0,6) 100 = 3,2 %. In actual practice, the distance will be higher as it is not a true homogenous field. Therefore, we do not need to verify compliance with Table 14. We are always on the conservative side.

Material: Polyamide, dielectric constant = 2,5

0,04 2 2 500 2 480 20 2 950 23 2 927

0,04 1 2 500 2 460 40 2 950 46 2 904

0,04 0,6 2 500 2 435 65 2 950 76 2 874

For 2 500 V peak impulse (transient for 230 V system), the homogenous field distance is 0,6 mm (from Table A.1 of IEC 60664-1:2007). Our test voltage for 2 500 V peak is 2 950 V peak from Table 15. This means that a minimum distance of 0,78 mm through homogenous field needs to be maintained to pass the 2 950 V impulse test.

This gives us a margin of (0,18/0,6) 100 = 3,0 %. In actual practice, the distance will be higher , as it is not a true homogenous field. Therefore, we do not need to verify compliance with Table 14. We are always on the consevative side.

1478

5.4.2.5 Multiplication factors for altitudes higher than 2 000 m above sea level 1479

Source: IEC 60664-1:2007, curve number 2 for case A using impulse test. 1480

Purpose: Test is carried out by either impulse voltage or AC voltage with the values 1481

of Table 16 and the multiplication factors for altitudes higher than 2 000 m. 1482

Rationale: Table 16 is developed using Figure A.1 of IEC 60664-1:2007, curve number 1483

2 for case A using impulse test. 1484

5.4.2.6 Compliance criteria 1485

Source: IEC 60664-1:2007, 5.1.1 1486

Rationale: IEC 62368-1:2018, Annex O figures are similar/identical to figures in 1487

IEC 60664-1:2007. 1488

Tests of IEC 62368-1:2018, Annex T simulate the occurrence of mechanical 1489

forces: 1490

– 10 N applied to components and parts that may be touched during 1491

operation or servicing. Simulates the accidental contact with a finger or 1492

part of the hand; 1493

– 30 N applied to internal enclosures and barriers that are accessible to 1494

ordinary persons. Simulates accidental contact of part of the hand ; 1495

Page 47: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 48 – IEC TR 62368-2:2019 © IEC 2019

– 100 N applied to external enclosures of transportable equipment and 1496

handheld equipment. Simulates expected force applied durin g use or 1497

movement; 1498

– 250 N applied to external enclosures (except those covered in T.4). 1499

Simulates expected force applied by a body part to the surface of the 1500

equipment. It is not expected that such forces will be applied to the 1501

bottom surface of heavy equipment ( 18 kg). 1502

During the force tests metal surfaces shall not come into contact with parts 1503

at ES2 or ES3 voltage. 1504

5.4.3 Creepage distances 1505

Source: IEC 60664-1:2007, 3.3 1506

Purpose: To prevent flashover along a surface or breakdown of the insulation. 1507

Rationale: Preserve safeguard integrity. 1508

In IEC 60664-1:2007, Table F.4 columns 2 and 3 for printed wiring boards 1509

are deleted, as there is no rationale for the very small creepage distances 1510

for printed wiring in columns 2 and 3 (the only rationale is that it is in the 1511

basic safety publication IEC 60664-1). 1512

However, there is no rationale why the creepage distances are different 1513

for printed wiring boards and other isolation material under the same 1514

condition (same PD and same CTI) . 1515

Moreover the creepage distances for printed boards in columns 2 and 3 1516

are in conflict with the requirements in G.13.3 (Coated printed boards). 1517

Consequently the values for voltages up to 455 V in Table G.16 were 1518

replaced. 1519

Creepage distances between the outer insulating surface of a connect or 1520

and conductive parts at ES3 voltage level shall comply with the 1521

requirements of basic insulation only, if the connectors are fixed to the 1522

equipment, located internal to the outer electrical enclosure of the 1523

equipment, and are accessible only after removal of a sub-assembly which 1524

is required to be in place during normal operation. 1525

It is assumed that the occurrence of both factors, the sub -assembly being 1526

removed, and the occurrence of a transient overvoltage have a reduced 1527

likelihood and hazard potential. 1528

5.4.3.2 Test method 1529

Source: IEC 60664-1:2007, 3.2 1530

Purpose: Measurement of creepage distance. 1531

Rationale: To preserve safeguard integrity after mechanical tests . 1532

Annex O figures are similar/identical to figures in IEC 60950-1 and 1533

IEC 60664-1. 1534

Tests of Annex T simulate the occurrence of mechanical forces: 1535

– 10 N applied to components and parts that are likely to be touched by a 1536

skilled person during servicing, where displacement of the part reduces 1537

the creepage distance. Simulates the accidental contact wi th a finger or 1538

part of the hand. 1539

– 30 N applied to internal enclosures and barriers that are accessible to 1540

ordinary persons. Simulates accidental contact of part of the hand. 1541

– 100 N applied to external enclosures of transportable equipment and 1542

hand-held equipment. Simulates expected force applied during use or 1543

movement. 1544

Page 48: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:2019 © IEC 2019 – 49 –

– 250 N applied to external enclosures (except those covered in T.4). 1545

Simulates expected force when leaning against the equipment surface. It 1546

is not expected that such forces will be applie d to the bottom surface of 1547

heavy equipment ( 18 kg). 1548

Creepage distances are measured after performing the force tests of 1549

Annex T. 1550

5.4.3.3 Material group and CTI 1551

Source: IEC 60112 1552

Rationale: Classification as given in IEC 60112. 1553

5.4.3.4 Compliance criteria 1554

Source: IEC 60664-1:2007, Table F.4; IEC 60664-4 for frequencies above 30 kHz 1555

Rationale: Values in Table 17 are the same as in Table F.4 of IEC 60664-1:2007. 1556

Values in Table 18 are the same as in Table 2 of IEC 60664-4:2005 and 1557

are used for frequencies up to 400 kHz . 1558

5.4.4 Solid insulation 1559

Source: IEC 60950-1, IEC 60664-1 1560

Purpose: To prevent breakdown of the solid insulation. 1561

Rationale: To preserve safeguards integrity. 1562

Exclusion of solvent based enamel coatings for safety insulations are 1563

based on field experience. However, with the advent of n ewer insulation 1564

materials those materials may be acceptable in the future when passing the 1565

adequate tests. 1566

Except for printed boards (see G.13), the solid insulation shall meet the 1567

requirements of 5.4.4.4 to 5.4.4.7 as applicable. 1568

5.4.4.2 Minimum distance through insulation 1569

Source: IEC 60950-1:2005 1570

Purpose: Minimum distance through insulation of 0,4 mm for supplementary 1571

insulation and reinforced insulation. 1572

Rationale: Some (very) old documents required for single insulations 2 mm dti 1573

(distance through insulation) for reinforced insulation and 1 mm for 1574

supplementary insulation. If this insulation served also as outer 1575

enclosure for Class II equipment, it had to be mechanically robust, which 1576

was tested with a hammer blow of 0,5 Nm. 1577

The wire documents did not distinguish between grades of insulation, and 1578

required 0,4 mm for PVC insulation material. This value was considered 1579

adequate to protect against electric shock when touching the insulation if it 1580

was broken. This concept was also introduced in VDE 0860 (w hich evolved 1581

into IEC 60065), where the 0,4 mm value was discussed first. For IT 1582

products this value was first only accepted for in accessible insulations. 1583

The VDE document for telecom equipment (VDE 0804) did not include any 1584

thickness requirements, but the insulation had to be adequate for the 1585

application. 1586

The document VDE 0730 for household equipment with electric motors 1587

introduced in 1976 the requirement of an insulation thickness of 0,5 mm 1588

between input and output windings of a transformer. This was i ntroduced 1589

by former colleagues from IBM and Siemens (against the position of the 1590

people from the transformer committee). 1591

Page 49: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 50 – IEC TR 62368-2:2019 © IEC 2019

Also VDE 0110 (Insulation Coordination, which evolved into the IEC 60664 1592

series) contained a minimum insulation thickness of 0,5 mm fo r 250 V 1593

supply voltage, to cover the effect of insulation breakage. 1594

These 0,5 mm then evolved into 0,4 mm (in IEC 60950-1), with the 1595

reference to VDE 0860 (IEC 60065), where this value was already in use. 1596

It is interesting to note that the 0,31 mm which is derived from Table 2A of 1597

IEC 60950-1, has also a relation to the 0,4 mm. 0,31 mm is the minimum 1598

value of the average insulation thickness of 0,4 mm, according to experts 1599

from the wire manufacturers. 1600

5.4.4.3 Insulating compound forming solid insulation 1601

Source: IEC 60950-1 1602

Purpose: Minimum distance through insulation of 0,4 mm for supplementary 1603

insulation and reinforced insulation. 1604

Rationale: The same distance through insulation requirements as for solid insulation 1605

apply (see 5.4.4.2). Insulation is subjected to thermal cycling (see 1606

5.4.1.5.3), humidity test (see 5.4.8) and electric strength test (see 5.4.9). 1607

Insulation is inspected for cracks and voids . 1608

5.4.4.4 Solid insulation in semiconductor devices 1609

Source: IEC 60950-1, UL 1577 1610

Purpose: No minimum thickness requirements for the solid insulation. 1611

Rationale: – type test ing of 5.4.9.1 (electric strength testing at 160 % of the normal 1612

value after thermal cycling and humidity conditioning), and routine 1613

electric strength test of 5.4.9.2 has been used for many years, especially 1614

in North America. 1615

– refers to G.12, which references IEC 60747-5-5. 1616

5.4.4.5 Insulating compound forming cemented joints 1617

Source: IEC 60950-1 1618

Rationale: a) The distances along the path comply with PD 2 requirements 1619

irrespective of the joint; 1620

b) applies if protected to generate PD 1 environment ; 1621

c) applies if treated like solid insulation environment, no clearances and 1622

creepage distances apply; 1623

d) is not applied to printed boards, when the board temperature is below 1624

90 °C, as the risk for board delaminating at lower temperatures is 1625

considered low. 1626

Optocouplers are excluded from the requirements of this subclause, 1627

because the document requires optocouplers to comply with 1628

IEC 60747-5-5, which sufficiently covers cemented joints . 1629

Page 50: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:2019 © IEC 2019 – 51 –

5.4.4.6.1 General requirements 1630

Source: IEC 60950-1, IEC 61558-1:2005 1631

Rationale: No dimensional or constructional requirements for insulation in thin sheet 1632

material used as basic insulation, is aligned to the requirements of 1633

IEC 61558-1. 1634

Two or more layers with no minimum thickness are required for 1635

supplementary insulation or reinforced insulation , provided they are 1636

protected against external mechanical influences. 1637

Each layer is qualified for the full voltage for supplementary insulation or 1638

reinforced insulation. 1639

The requirements are based on extensive tests performed on thin sheet 1640

material by manufacturers and test houses involved in IEC TC 74 (now IEC 1641

TC 108) work. 1642

5.4.4.6.2 Separable thin sheet material 1643

Source: IEC 60950-1 1644

Rationale: For two layers, test each layer with the electric strength test of 5.4.9 for the 1645

applicable insulation grade. For three layers, test all combinations of two 1646

layers together with the electric strength test of 5.4.9 for the applicable 1647

insulation grade. 1648

Each layer is qualified for the full voltage for supplementary insulation or 1649

reinforced insulation. 1650

The requirements are based on extensive tests performed on thin sheet 1651

material by manufacturers and test houses involved in IEC TC 74 (now IEC 1652

TC 108) work. 1653

5.4.4.6.3 Non-separable thin sheet material 1654

Source: IEC 60950-1 1655

Rationale: For testing non-separable layers, all the layers are to have the same 1656

material and thickness. If not, samples of different materials are tested as 1657

given in 5.4.4.6.2 for separable layers. When testing non-separable layers, 1658

the principle used is the same as for separable layers. 1659

When testing two separable layers, each layer is tested for the required 1660

test voltage. Two layers get tested for two times the required test voltage 1661

as each layer is tested for the required test voltage. When testing two non -1662

separable layers, the total test voltage remain s the same, for example, two 1663

times the required test voltage. Therefore, two non -separable layers are 1664

tested at 200 % of the required test voltage. 1665

When testing three separable layers, every combination of two layers is 1666

tested for the required test voltage. Therefore, a single layer gets tested for 1667

half the required test voltage and three layers are tested for 150 % of the 1668

required test voltage. 1669

5.4.4.6.4 Standard test procedure for non-separable thin sheet material 1670

Source: IEC 60950-1 1671

Rationale: Test voltage 200 % of Utest if two layers are used. 1672

Test voltage 150 % of Utest if three or more layers are used. 1673

See the rationale in 5.4.4.6.3. The procedure can be applied to both 1674

separable and non-separable layers as long as the material and material 1675

thickness is same for all the layers. 1676

Page 51: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 52 – IEC TR 62368-2:2019 © IEC 2019

5.4.4.6.5 Mandrel test 1677

Source: IEC 61558-1:2005, 26.3.3; IEC 60950-1:2013; IEC 60065:2011 1678

Purpose: This test should detect a break of the inner layer of non-separated foils. 1679

Rationale: This test procedure is taken from IEC 61558-1, 26.3.3, and the test voltage 1680

is 150 % Utest, or 5 kV RMS., whatever is greater. 1681

5.4.4.7 Solid insulation in wound components 1682

Source: IEC 60950-1, IEC 61558-1 1683

Purpose: To identify constructional requirements of insulation of winding wires and 1684

insulation between windings . 1685

Rationale: Requirements have been used in IEC 60950-1 for many years and are 1686

aligned to IEC 61558-1. 1687

Planar transformers are not considered wound components and have to 1688

comply with G.13. 1689

5.4.4.9 Solid insulation requirements at frequencies higher than 30 kHz 1690

Source: IEC 60664-4:2005 1691

Purpose: To identify requirements for solid insulation that is exposed to voltages at 1692

frequencies above 30 kHz. 1693

Rationale: The requirements are taken from the data presented in Annex C of 1694

IEC 60664-4:2005. Testing of solid insulation can be performed at line 1695

frequency as detailed in 6.2 of IEC 60664-4:2005. 1696

In general, the breakdown electric field strength of insulation can be 1697

determined according to IEC 60243-1 (Electrical strength of insulating 1698

materials−Test methods−Part 1) as referred from 5.3.2.2.1 of IEC 60664-1699

1:2007 (see below). 1700

5.3.2.2.1 Frequency of the voltage 1701

The electric strength is greatly influenced by the frequency of the applied 1702

voltage. Dielectric heating and the probability of thermal instability increase 1703

approximately in proportion to the frequency. The breakdown field strength 1704

of insulation having a thickness of 3 mm when measured at power 1705

frequency according to IEC 60243-1 is between 10 kV/mm and 40 kV/mm. 1706

Increasing the frequency will reduce the electric strength of most insulating 1707

materials. 1708

NOTE The influence of frequencies greater than 30 kHz on the electric strength is 1709 described in IEC 60664-4. 1710

Table 20 shows the electric field strength for some commonly used 1711

materials. These values are related to a frequency of 50/60 Hz. 1712

Table 21, which is based on Figure 6 of IEC 60664-4:2005, shows the 1713

reduction factor for the value of breakdown electric field strength at higher 1714

frequencies. The electric field strength of materials drops differently at 1715

higher frequencies. The reduction of the insulation prope rty is to be 1716

considered when replacing the calculation method by the alternative ES 1717

test at mains frequency, as shown after the sixth paragraph of 5.4.4.9. 1718

Table 21 is for materials of 0,75 mm in thickness or more. Table 22 is for 1719

materials of less than 0,75 mm in thickness. 1720

The 1,2 times multiplier comes from IEC 60664-4:2005, subclause 7.5.1, 1721

where the partial discharge (PD) extinction voltage must include a safety 1722

margin of 1,2 times the highest peak periodic voltage. 1723

Page 52: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:2019 © IEC 2019 – 53 –

5.4.5 Antenna terminal insulation 1724

Source: IEC 60065 1725

Purpose: To prevent breakdown of the insulation safeguard. 1726

Rationale: The insulation shall be able to withstand surges due to overvoltages 1727

present at the antenna terminals. These overvoltages are caused by 1728

electrostatic charge build up, but not from lightning effects. A maximum 1729

voltage of 10 kV is assumed. The associated test of G.10.4 simulates this 1730

situation by using a 10 kV test voltage discharged over a 1 nF capacitor. 1731

5.4.6 Insulation of internal wire as a part of a supplementary safe guard 1732

Source: IEC 60950-1 1733

Purpose: To specify constructional requirements of accessible internal wiring 1734

Rationale: Accessible internal wiring isolated from ES3 by basic insulation only 1735

needs a supplementary insulation. If the wiring is reliably routed away so 1736

that it will not be subject to handling by the ordinary person, then smaller 1737

than 0,4 mm thick supplementary insulation has been accepted in 1738

IEC 60950-1. But the insulation still has to have a certain minimum 1739

thickness together with electric strength withstand capability. The given 1740

values have been successfully used in products covered by this document 1741

for many years (see Figure 16 in this document). 1742

1743

Figure 16 – Example illustrating accessible internal wiring 1744

Page 53: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 54 – IEC TR 62368-2:2019 © IEC 2019

5.4.7 Tests for semiconductor components and for cemented joints 1745

Source: IEC 60950-1 1746

Purpose: To simulate lifetime stresses on adjoining materials. 1747

To detect defects by applying elevated test voltages after sample 1748

conditioning. 1749

To avoid voids, gaps or cracks in the insulating material and delaminating 1750

in the case of multilayer printed boards. 1751

Rationale: This method has been successfully used for products in the scope of this 1752

document for many years. 1753

5.4.8 Humidity conditioning 1754

Source: IEC 60950-1 and IEC 60065. Alternative according to IEC 60664-1:2007, 1755

6.1.3.2 1756

Purpose: Material preparations for dielectric strength test . Prerequisite for further 1757

testing. 1758

A tropical climate is a location where it is expected to have high 1759

temperatures and high humidity during most of the year. The document 1760

does not indicate what levels of temperature or humidity constitute a 1761

tropical climate. National authorities define whether their country requires 1762

products to comply with tropical requirements. Only a few countries, such 1763

as Singapore and China, have indicated in the CB scheme that they require 1764

such testing. 1765

5.4.9 Electric strength test 1766

Source: IEC 60664-1: 2007 1767

Purpose: To test the insulation to avoid breakdown. 1768

Rationale: Values of test voltages are derived from Table F.5 of IEC 60664-1:2007, 1769

however the test duration is 60 s. 1770

This method has been successfully used for products in the scope of 1771

IEC 60065 and IEC 60950-1 for many years. 1772

The DC voltage test with a test voltage equal to the peak value of the AC 1773

voltage is not fully equivalent to the AC voltage test due to the different 1774

withstand characteristics of solid insulation for these types of voltages. 1775

However in case of a pure DC voltage stress, the DC voltage test is 1776

appropriate. To address this situation the DC test is made with both 1777

polarities. 1778

Table 25 Test voltages for electric strength tests based on transient voltages 1779

Source: IEC 60664-1:2007 1780

Rationale: To deal with withstand voltages and cover transients. 1781

The basic insulation and supplementary insulations are to withstand a 1782

test voltage that is equal to the transient peak voltage. The test voltage for 1783

the reinforced insulation shall be equal to the transient in the next in the 1784

preferred series. According to 5.1.6 of IEC 60664-1:2007, the use of 160 % 1785

test value for basic insulation as the test value for reinforced insulation 1786

is only applicable if other values than the preferred series are used. 1787

Functional insulation is not addressed, as is it presumed not to provide 1788

any protection against electric shock. 1789

Page 54: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:2019 © IEC 2019 – 55 –

Table 26 Test voltages for electric strength tests based on the peak of the working 1790

voltages and recurring peak voltages 1791

Source: IEC 60664-1:2007 1792

Rationale: Column B covers repetitive working voltages and requires higher test 1793

voltages due to the greater stress to the insulation. 1794

Recurring peak voltages ( IEC 60664-1:2007, 5.3.3.2.3) need to be 1795

considered, when they are above the temporary overvoltage values, or in 1796

circuits separated from the mains. 1797

If the recurring peak voltages are above the temporary overvoltage 1798

values, these voltages have to be used, multiplied by the factor given in 1799

IEC 60664-1:2007, 5.3.3.2.3. 1800

Table 27 Test voltages for electric strength tests based on temporary overvoltages 1801

Source: IEC 60664-1:2007 1802

Rationale: Temporary overvoltages (IEC 60664-1:2007, 5.3.3.2.2) need to be 1803

considered as they may be present up to 5 s. The test voltage for 1804

reinforced insulation is twice the value of basic insulation . 1805

5.4.10 Safeguards against transient voltages from e xternal circuits 1806

Source: IEC 62151:2000, Clause 6 1807

Purpose: To protect persons against contact with external circuits subjected to 1808

transients (for example, telecommunication networks). 1809

Rationale: External circuits are intended to connect the equipment to other 1810

equipment. Connections to remote equipment are made via communication 1811

networks, which could leave the building. Examples for such 1812

communication networks are telecommunication networks and Ethernet 1813

networks. The operating voltages of communication netwo rks are usually 1814

within the limits of ES1 ( for example, Ethernet) or within the limits of ES2 1815

(for example, telecommunication networks). 1816

When leaving the buildings, communication networks may be subjected to 1817

transient overvoltages due to atmospheric dischar ges and faults in power 1818

distribution systems. These transients are depending on the infrastructure 1819

of the cables and are independent on the operating voltage of the 1820

communication network. The expected transients on telecommunication 1821

networks are specified in ITU-T recommendations. The transient value in 1822

Table 13 ID 1 is taken from ITU-T K.21 as 1,5 kV 10/700 µs (terminal 1823

equipment). This transient of 1,5 kV 10/700 µs does not cause a hazardous 1824

electric shock, but it is very uncomfortable to persons effectin g by such a 1825

transient. To avoid secondary hazards a separation between an external 1826

circuit connected to communication networks subjected transients is 1827

required. 1828

Because the transient does not cause a hazardous electric shock the 1829

separation element needs not to be a reinforced safeguard nor a basic 1830

safeguard in the meaning of IEC 62368-1. It is sufficient to provide a 1831

separation complying with an electric strength test, only. Therefore for this 1832

separation no clearance, no creepage distances and no thickness 1833

requirements for solid insulation are required. 1834

The separation is required between the external circuit subjected to 1835

transients and all parts, which may accessible to ordinary persons or 1836

instructed persons. 1837

Page 55: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 56 – IEC TR 62368-2:2019 © IEC 2019

The likelihood a transient occurs and a body cont act with an accessible 1838

part occurs at the same time increases with the contact time. Therefore 1839

non-conductive parts and unearthed parts of the equipment maintained in 1840

continuous contact with the body during normal use ( for example, a 1841

telephone handset, head set, palm rest surfaces) the separation should 1842

withstand a higher test voltage. 1843

Two test procedures for the electric strength test are specified in 5.4.10.2. 1844

5.4.10.2.2 Impulse test 1845

The impulse test is performing an impulse test by using the impulse 1846

generator for the 10/700 µs impulse (see test generator D.1 of Annex D). 1847

With the recorded waveforms it could be judged whether a breakdown of 1848

insulation has occurred, or if the surge suppression device has worked 1849

properly. 1850

The examples in Figure 17, Figure 18, 1851

1 – gas discharge type

2 – semiconductor type

3 – metal oxide type

Consecutive impulses are identical in their waveforms.

1852

Figure 19 and Figure 20 in this document could be used to assist in judging whether or not 1853

a surge suppressor has operated or insulation has broken down. 1854

1855

Consecutive impulses are identical in their waveforms.

1856

Figure 17 – Waveform on insulation without surge suppressors and no breakdown 1857

Page 56: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:2019 © IEC 2019 – 57 –

Consecutive impulses are not identical in their waveforms. The pulse shape changes from pulse to pulse until a stable resistance path through the insulation is established. Breakdown can be seen clearly on the shape of the pulse voltage oscillogram.

1858

Figure 18 – Waveforms on insulation during breakdown without surge suppressors 1859

1 – gas discharge type

2 – semiconductor type

3 – metal oxide type

Consecutive impulses are identical in their waveforms.

1860

Figure 19 – Waveforms on insulation with surge suppressors in operation 1861

1862

Figure 20 – Waveform on short-circuited surge suppressor and insulation 1863

Page 57: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 58 – IEC TR 62368-2:2019 © IEC 2019

5.4.10.2.3 Steady-state test 1864

The steady-state test is performing an electric strength test according to 1865

5.4.9.1. This test is simple test with an RMS voltage. But if for example, 1866

surge suppressors are used to reduce the transients from the external 1867

circuits within the equipment this RMS test may by not adequate. In this 1868

case an impulse test is more applicable. 1869

5.4.11 Separation between external circuits and earth 1870

Source: IEC 62151:2000, 5.3 1871

Purpose: To protect persons working on communication networks, and users of other 1872

equipment connected to the network from hazards in the equipment. 1873

Rationale: Class I equipment provides basic insulation between mains and earthed 1874

conductive parts and requires the conductive parts to be connected to a PE 1875

conductor that has to be connected to the earthing terminal in the buildings 1876

installation to be safe to use. In an isolated environment such an earth 1877

terminal is not present in the building installation. Nevertheless the use of 1878

class I equipment in such an isolated environment is still safe to use, 1879

because in case of a breakdown of the insulation in the equipment (fault of 1880

basic insulation) the second barrier is provided by the isolated 1881

environment (similar to a supplementary insulation). 1882

With the connection of the equipment via an external circuit to a 1883

communication network from outside the building installation to a remote 1884

environment the situation will change. It is unknown whether the remote 1885

environment is an isolated or non-isolated environment. During and after a 1886

fault of the basic insulation in a class I equipment (from mains to 1887

conductive parts) installed in an isolated installation (non -earthed 1888

installation) the conductive parts will become live ( mains potential). If now 1889

the conductive parts are not separated from the external circuit, the 1890

mains voltage will be transferred to the remote installation via the 1891

communication network. This is a hazardous situation in the remote 1892

environment and can be dangerous for persons in that remote environment. 1893

Also in old building installations socket outlet s exist with no earth contact. 1894

This situation will not be changed in the near future. 1895

To provide protection for those situations, a separation between an 1896

external circuit intended to be connected to communication networks 1897

outside the building (for example, telecommunication networks) and a 1898

separation between the external circuit and earthed parts is required. 1899

For this separation, it is sufficient to comply with the requirements of 1900

5.4.11.2 tested in accordance with 5.4.11.3. For this separation, no 1901

clearance, no creepage distances and no thickness requirements for 1902

solid insulation is required. 1903

5.5 Components as safeguards 1904

Rationale: For failure of a safeguard and a component or device that is not a 1905

safeguard: 1906

Safeguard failure: A failure is considered to be a safeguard failure if the 1907

part itself or its function, during normal operating conditions , contributes 1908

to change an ES class to a lower ES class. In this case, the part is 1909

assessed for its reliability by applying the applicable safeguard component 1910

requirements in 5.5 and the associated requirements in Annex G. When 1911

establishing ES1, ES2 limits apply during single fault condition of these 1912

parts. In case no requirements for the component are provided in 5.5 or 1913

Annex G, the failure is regarded as a non-safeguard failure. 1914

Page 58: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:2019 © IEC 2019 – 59 –

Non-safeguard failure: A failure is considered to be a non -safeguard 1915

failure if the part itself or its function, under normal operating conditions , 1916

does not contribute to change an ES class to a lower ES Class. In this 1917

case, there is no need to assess the reliability of the part. When 1918

establishing ES1, ES1 limits apply for the single fault condition of these 1919

parts. Where applicable, 5.3.1 applies. Figure 21 and Figure 22 in this 1920

document give practical examples of the requirements when ordin ary 1921

components bridge insulation. 1922

Example 1 1923

1924

Figure 21 – Example for an ES2 source 1925

A single fault of any component or part may not result in the accessible 1926

part exceeding ES1 levels, unless the part complies with the requirements 1927

for a basic safeguard. 1928

The basic safeguard in parallel with the part(s) is to comply with: 1929

– the creepage distance requirements; and 1930

– the clearance requirements 1931

for basic insulation. 1932

There are no other requirements for the components or parts if the 1933

accessible part remains at ES1. 1934

Example 2 1935

1936

Figure 22 – Example for an ES3 source 1937

A single fault of any component or part may not result in the accessible 1938

part exceeding ES1 levels, unless the parts comply with the requirements 1939

for a double or reinforced safeguard. 1940

Page 59: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 60 – IEC TR 62368-2:2019 © IEC 2019

The double or reinforced safeguard in parallel with the part(s) is to comply 1941

with: 1942

– the creepage distance requirements; and 1943

– the clearance requirements, 1944

for double insulation or reinforced insulation. 1945

There are no other requirements for the components or parts if the 1946

accessible part remains at ES1. 1947

5.5.2.1 General requirements 1948

Source: Relevant IEC component documents 1949

Purpose: The insulation of components has to be in compliance with the relevant 1950

insulation requirements of 5.4.1, or with the safety requirements of the 1951

relevant IEC document. 1952

Rationale: Safety requirements of a relevant document are accepted if they are 1953

adequate for their application, for example, Y2 capacitors of IEC 60384-14. 1954

5.5.2.2 Capacitor discharge after disconnection of a connector 1955

Source: IEC TS 61201:2007, Annex A 1956

Rationale: The 2 s delay time represents the typical access time after disconnecting a 1957

connector. When determining the accessible voltage 2 s after 1958

disconnecting a connector, the tolerance of the X capacitor is not 1959

considered. 1960

If a capacitor is discharged by a resistor ( for example, a bleeder resistor), 1961

the correct value of the resistor can be calculated using the following 1962

formula: 1963

R = (2 / C) x [1 / ln(E / Emax)] M 1964

where: 1965

C is in microfarads 1966

E is 60 for an ordinary person or 120 for an instructed person 1967

Emax is the maximum charge voltage or mains peak voltage 1968

ln is the natural logarithm function 1969

NOTE 1 When the mains is disconnected, the capacitance is comprised of both the X 1970 capacitors and the Y capacitors, and other possible capacitances. The circuit is analyzed to 1971 determine the total capacitance between the poles of the connector or plug. 1972

NOTE 2 If the equipment rated mains voltage is 125 V, the maximum value of the 1973 discharge resistor is given by : 1974

R = 1,85 / C M 1975

NOTE 3 If the equipment rated mains voltage is 250 V, the maximum value of the 1976 discharge resistor is given by : 1977

R = 1,13 / C M 1978

NOTE 4 The absolute value of the above calculations is used for the discharge resistor 1979 value. 1980

The test method includes a maximum time error of about 9% less than the 1981

calculated time for a capacitive discharge. This error was deemed 1982

acceptable for the sake of consistency with past practice. 1983

For measuring the worst case, care should be taken that t he discharge is 1984

measured while at the peak of the input voltage. To ensure this, an 1985

automatic control system that switches off at the peak voltage can be used. 1986

Page 60: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:2019 © IEC 2019 – 61 –

A method used by several other documents, such as IEC 60065 and 1987

IEC 60335-1 is to repeat the measurement 10 times and record the 1988

maximum value. This assumes that one of the 10 measurements will be 1989

sufficiently close to the peak value. 1990

Another possibility might be to use an oscilloscope during the 1991

measurement, so one can see if the measurement was don e near the 1992

maximum. 1993

Single fault conditions need not be considered if the component complies 1994

with the relevant component requirements of the document. For example, a 1995

resistor connected in parallel with a capacitor where a capacitor voltage 1996

becomes accessible upon disconnection of a connector, need not be 1997

faulted if the resistor complies with 5.5.6. 1998

When determining the accessible voltage 2 s after disconnection of the 1999

connector, the tolerance of the X-capacitor is not considered. 2000

5.5.6 Resistors 2001

Source: IEC 60950-1 and IEC 60065 2002

Rationale: When a group of resistors is used, the resistors are in series. The whole 2003

path consists of the metal lead and helical end (metal) and resistor body. 2004

The clearance and creepage distance is across the resistor body only. 2005

The total path then consists of conductive metal paths and resistor bodies 2006

(all in series). In this case, Figure O.4 becomes relevant when you want to 2007

determine the total clearance and creepage distance. 2008

5.5.7 SPDs 2009

Rationale: See Attachment A for background information on the use of SPD’s . 2010

It should be noted that the issue is still under discussion in IEC TC 108. 2011

The rationale will be adapted as soon as the discussion is finalized. 2012

A GDT is a gap, or a combination of gaps, in an enclosed discharge 2013

medium other than air at atmospheric pressure, and designed to protect 2014

apparatus or personnel, or both, from high transient voltages (from ITU-T 2015

K.12- Characteristics of gas discharge tubes for the protection of 2016

telecommunications installations). It shall be used to protect equipment 2017

from transient voltages. 2018

Even if a GDT operates during the occurrence of transient voltages, it is not 2019

hazardous according to 5.2.2.4, Electrical energy source ES1 and ES2 2020

limits of Single pulses. 2021

NOTE These single pulses do not include transients 2022

Because a transient does not cause a hazardous electric shock , the 2023

separation element does not need to be a reinforced safeguard nor a 2024

basic safeguard in the meaning of IEC 62368-1. 2025

If suitable components are connected in-series to the SPD (such as a VDR, 2026

etc.), a follow current will not occur, and there will be no harmful effect. 2027

5.5.8 Insulation between the mains and an external circuit consisting of a coaxial 2028

cable 2029

Source: IEC 60065:2014, 10.2 and IEC 60950-1:2005, 1.5.6. 2030

Rationale: The additional conditioning of G.10.2 comes from IEC 60950-1:2005, 1.5.6 2031

Capacitors bridging insulation 2032

Met opmerkingen [RJ2]: See Brussels minutes 6.2.11

Met opmerkingen [JR3]: See Shanghai minutes item 6.1.4

Page 61: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 62 – IEC TR 62368-2:2019 © IEC 2019

5.6 Protective conductor 2033

See Figure 23 in this document for an overview of protective earthing and 2034

protective bonding conductors. 2035

2036

Figure 23 – Overview of protective conductors 2037

5.6.1 General 2038

Source: IEC 60364-5-54, IEC 61140, IEC 60950-1 2039

Purpose: The protective earthing should have no excessive resistance, sufficient 2040

current-carrying capacity and not be interrupted in all circumstances. 2041

5.6.2.2 Colour of insulation 2042

Source: IEC 604461 2043

Purpose: For clear identification of the earth connection. 2044

An earthing braid is a conductive material, usually copper, made up of 2045

three or more interlaced strands, typically in a diagonally overlapping 2046

pattern. 2047

It should be noted that IEC 60227-1:2007 has specific requirements for the 2048

use of the colour combination as follows: 2049

2050

2051

___________

1 This publication was withdrawn.

Page 62: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:2019 © IEC 2019 – 63 –

5.6.3 Requirements for protective earthing conductors 2052

Source: IEC 60950-1 2053

Purpose: The reinforced protective conductor has to be robust enough so that the 2054

interruption of the protective conductor is prevented in any case 2055

(interruption is not to be assumed). 2056

Rationale: These requirements have been successfully used for products in the scope 2057

of this document for many years. 2058

Where a conduit is used, if a cord or conductor exits the conduit and is not 2059

protected, then the values of Table 30 cannot be used for the conductor 2060

that exits the conduit. 2061

For pluggable equipment type B and permanently connected 2062

equipment, an earthing connection is always expected to be present. The 2063

earthing conductor can therefore be considered as a reinforced 2064

safeguard. 2065

5.6.4 Requirements for protective bonding conductors 2066

Source: IEC 60950-1 2067

Purpose: To demonstrate the fault current capability and the capability of the 2068

termination. 2069

Rationale: These requirements and tests have been successfully used for products in 2070

the scope of this document for many years (see Figure 3 in this document). 2071

5.6.5 Terminals for protective conductors 2072

5.6.5.1 Requirements 2073

Source: IEC 60998-1, IEC 60999-1, IEC 60999-2, IEC 60950-1 2074

Purpose: To demonstrate the fault current capability and the capability of the 2075

termination. 2076

Rationale: Conductor terminations according to Table 3 2 have served as reliable 2077

connection means for products complying with IEC 60950-1 for many years. 2078

The value of 25 A is chosen to cover the minimum protective current rating 2079

in all countries of the world. 2080

5.6.6.2 Test method 2081

Source: IEC 60950-1 2082

Rationale: This method has been successfully used for products in the scope of this 2083

document for many years. 2084

5.6.7 Reliable connection of a protective earthing conductor 2085

Source: IEC 60309 (plugs and socket outlets for industrial purpose) 2086

Purpose: To describe reliable earthing as provided by permanently connected 2087

equipment, pluggable equipment type B, and pluggable equipment 2088

type A. 2089

Rationale: Permanently connected equipment is considered to provide a reliable 2090

earth connection because it is wired by an electrician. 2091

Pluggable equipment type B is considered to provide a reliable earth 2092

connection because IEC 60309 type plugs are more reliable and earth is 2093

always present as it is wired by an electrician. 2094

For stationary pluggable equipment type A where a skilled person 2095

verifies the proper connection of the earth conductor . 2096

Page 63: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 64 – IEC TR 62368-2:2019 © IEC 2019

5.7 Prospective touch voltage, touch current and protective conductor current 2097

Source: IEC 60990 2098

5.7.3 Equipment set-up, supply connections and earth connections 2099

Rationale: Equipment that is designed for multiple connections to the mains, where 2100

more than one connection is required, shall be subjected to either of the 2101

tests below: 2102

– have each connection tested individually while the other connections 2103

are disconnected, 2104

– have each connection tested while the other connections are 2105

connected, with the protective earthing conductors connected 2106

together. 2107

For simultaneous multiple connections, the requirement in the document is 2108

that each connection shall be tested while the other connections are 2109

connected, with the protective earthing conductors connected together. 2110

If the touch current exceeds the limit in 5.2.2.2, the touch current shall 2111

be measured individually. 2112

This means that if the total touch current with all connections tested 2113

together does not exceed the limit, the equipment complies with the 2114

requirement, if not, and each of the individual conductor touch currents 2115

don’t exceed the limit, the equipment also compl ies with the requirement. 2116

5.7.5 Earthed accessible conductive parts 2117

Rationale: Figure 24 in this document is an example of a typical test configuration for 2118

touch current from single phase equipment on star TN or TT systems. 2119

Other distribution systems can be found in IEC 60990. 2120

2121

Figure 24 – Example of a typical touch current measuring network 2122

5.7.6 Requirements when touch current exceeds ES2 limits 2123

Source: IEC 61140:2001, IEC 60950-1 2124

Rationale: The 5 % value has been used in IEC 60950-1 for a long time and is 2125

considered acceptable. The 5 % value is also the maximum allowed 2126

protective conductor current (7.5.2.2 of IEC 61140:2001). 2127

Page 64: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:2019 © IEC 2019 – 65 –

In the case that the protective conductor current exceeds 10 mA, 2128

IEC 61140 requires a reinforced protective earthing conductor with a 2129

conductor size of 10 mm2 copper or 16 mm2 aluminium or a second 2130

terminal for a second protective earthing conductor . This paragraph of 2131

IEC 62368-1 takes that into account by requiring a reinforced or double 2132

protective earthing conductor as per 5.6.3. 2133

IEC 61140:2001, 7.5.2.2 requires information about the value of the 2134

protective conductor current to be in the documentation and in the 2135

instruction manual, to facilitate the determination that the equipment with 2136

the high protective conductor current is compatible with the residual 2137

current device which may be in the building installation. 2138

The manufacturer shall indicate the value of the protective conductor 2139

current in the installation instructions if the current exceeds 10 mA, this to 2140

be in line with the requirements of IEC 61140:2001, 7.6.3.5. 2141

5.7.7 Prospective touch voltage and touch current associated with external circuits 2142

5.7.7.1 Touch current from coaxial cables 2143

Source: IEC 60728-11 2144

Purpose: To avoid having an unearthed screen of a coaxial network within a building. 2145

Rationale: An earthed screen of a coaxial network is reducing the risk to get an 2146

electric shock. 2147

Coaxial external interfaces very often are connected to antennas to receive 2148

TV and sound signals. Antennas installed outside the buildings are 2149

exposed to external atmospheric discharges ( for example, indirect 2150

lightning). To protect the antenna system and the equipment connecte d to 2151

such antennas, a path to earth needs to be provided via the screen of the 2152

coaxial network. 2153

Each piece of mains-powered equipment delivers touch current to a 2154

coaxial external circuit via the stray capacitance and the capacitor (if 2155

provided) between mains and coaxial interface. This touch current is 2156

limited by the requirement for each individual equipment to comply with the 2157

touch current requirements (safe value) to be measured according 2158

IEC 60990. Within a building, much individual equipment ( for example, TV’s 2159

receivers) may be connected to a coaxial network ( for example, cable 2160

distribution system). In this case , the touch current from each individual 2161

equipment sums up in the shield of the coaxial cable. With an earthed 2162

shield of a coaxial cable, the touch current has a path back to the source 2163

and the shield of the coaxial cable remains safe to touch. 2164

5.7.7.2 Prospective touch voltage and touch current associated with paired 2165

conductor cables 2166

Source: IEC 62151 2167

Purpose: To avoid excessive prospective touch voltage and excessive currents 2168

from equipment into communication networks ( for example, 2169

telecommunication networks). 2170

Rationale: All touch current measurements according to IEC 60990 measure the 2171

current from the mains to accessible parts. ES1 circuits are permitted to 2172

be accessible by an ordinary person and therefore it is included in the 2173

measurement according to IEC 60990. Circuits of class ES2 are not 2174

accessible and therefore these classes of circuits are not covered in the 2175

measurements according to IEC 60990. 2176

Page 65: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 66 – IEC TR 62368-2:2019 © IEC 2019

Because ES2 circuits may be accessible to instructed persons and may 2177

become accessible during a single fault to an ordinary person, the touch 2178

current to external circuit has to be limited, to protect people working on 2179

networks or on other equipment, which are connected to the external 2180

circuit via a network. 2181

An example for an external interface ID 1 of Table 13 is the connection to a 2182

telecommunication network. It is common for service personal of 2183

telecommunication networks and telecommunication equi pment to make 2184

servicing under live conditions. Therefore, the telecommunication networks 2185

are operating with a voltage not exceeding energy class ES2. 2186

The rationale to limit the touch current value to 0,25 mA (lower than ES2) 2187

has a practical background. Telecommunication equipment very often have 2188

more than one external circuit ID 1 of Table 13 (for example, connection 2189

to a telecommunication network). In such configurations a summation of the 2190

touch current may occur (see 5.7.7). With the limitation to 0,25 mA per 2191

each individual external circuit up to 20 external circuits could be 2192

connected together without any additional requirement. In 5.7.7 this value 2193

of 0,25 mA is assumed to be the touch current from a network to the 2194

equipment. 2195

5.7.8 Summation of touch currents from external circuits 2196

Source: IEC 60950-1 2197

Purpose: To avoid excessive touch currents when several external circuits are 2198

connected. 2199

Rationale: When limiting the touch current value to each individual external circuit 2200

(as required in 5.7.6.2), more circuits can be connected together before 2201

reaching the touch current limit. This allows better utilization of resources. 2202

Detailed information about touch currents from external circuits is given 2203

in Annex W of IEC 60950-1:2005. 2204

a) Touch current from external circuits 2205

There are two quite different mechanisms that determine the current 2206

through a human body that touches an external circuit, depending on 2207

whether or not the circuit is earthed. This distinction between earthed and 2208

unearthed (floating) circuits is not the same as between class I equipment 2209

and class II equipment. Floating circuits can exist in class I equipment and 2210

earthed circuits in class II equipment. Floating circuits are commonly, but 2211

not exclusively, used in telecommunication equipment and earthed circuits 2212

in data processing equipment, also not exclusively. 2213

In order to consider the worst case, it will be assumed in this annex that 2214

telecommunication networks are floating and that the AC mains supply and 2215

human bodies (skilled persons, instructed persons or ordinary 2216

persons) are earthed. It should be noted that a skilled person and an 2217

instructed person can touch some parts that are not accessible by an 2218

ordinary person. An "earthed" circuit means that the circuit is either 2219

directly earthed or in some way referenced to earth so that its potential with 2220

respect to earth is fixed. 2221

a.1) Floating circuits 2222

If the circuit is not earthed, the current ( Ic) through the human body is 2223

"leakage" through stray or added capacitance ( C) across the insulation in 2224

the mains transformer (see Figure 25 in this document). 2225

Page 66: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:2019 © IEC 2019 – 67 –

2226

Figure 25 – Touch current from a floating circuit 2227

This current comes from a relatively high voltage, high impedance source, 2228

and its value is largely unaffected by the operating voltage on the external 2229

circuit. In this document, the body current (Ic) is limited by applying a test 2230

using the measuring instrument in Annex D of IEC 60950-1:2005, which 2231

roughly simulates a human body. 2232

a.2) Earthed circuits 2233

If the external circuit is earthed, the current through the human body ( Iv) 2234

is due to the operating voltage (V) of the circuit, which is a source of low 2235

impedance compared with the body (see Figure 26 in this document). Any 2236

leakage current from the mains transformer (see a.1), will be conducted to 2237

earth and will not pass through the body. 2238

2239

Figure 26 – Touch current from an earthed circuit 2240

In this document, the body current (Iv) is limited by specifying maximum 2241

voltage values for the accessible circuit, which shall be an ES1 circuit or 2242

(with restricted accessibility) an ES2 circuit. 2243

b) Interconnection of several equipments 2244

It is a characteristic of information technology equipment, in particular in 2245

telecommunication applications, that many equipments may be connected 2246

to a single central equipment in a "star" topology. An example is tele phone 2247

extensions or data terminals connected to a PABX, which may have tens or 2248

hundreds of ports. This example is used in the following description (see 2249

Figure 27 in this document). 2250

Page 67: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 68 – IEC TR 62368-2:2019 © IEC 2019

2251

Figure 27 – Summation of touch currents in a PABX 2252

Each terminal equipment can deliver current to a human body touching the 2253

interconnecting circuit ( I1, I2, etc.), added to any current coming from the 2254

PABX port circuitry. If several circuits are connected to a common point, 2255

their individual touch currents will add together, and this represents a 2256

possible risk to an earthed human body that touches the interconnection 2257

circuit. 2258

Various ways of avoiding this risk are considered in the following 2259

subclauses. 2260

b.1) Isolation 2261

Isolate all interconnection circuits from each other and from earth, and limit 2262

I1, I2, etc., as described in a.1. This implies either the use in the PABX of a 2263

separate power supply for each port, or the provision of an individual line 2264

(signal) transformer for each port. Such solutions may not be cost effective. 2265

b.2) Common return, isolated from earth 2266

Connect all interconnection circuits to a common return point that is 2267

isolated from earth. (Such connections to a common point may in any case 2268

be necessary for functional reasons.) In this case the total current from all 2269

interconnection circuits will pass through an earthed human body that 2270

touches either wire of any interconnection circuit. This current can only be 2271

limited by controlling the values I1, I2, .. In. In relation to the number of 2272

ports on the PABX. However, the value of the total current will probably be 2273

less than I1 + I2 +... + In due to harmonic and other effects. 2274

b.3) Common return, connected to protective earth 2275

Connect all interconnection circuits to a common return point and connect 2276

that point to protective earthing. The situation described in a.2) applies 2277

regardless of the number of ports. Since safety depends on th e presence of 2278

the earth connection, it may be necessary to use high -integrity earthing 2279

arrangements, depending on the maximum value of the total current that 2280

could flow. 2281

Page 68: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:2019 © IEC 2019 – 69 –

5.8 Backfeed safeguard in battery backed up supplies 2282

Source: IEC 62040-1:2017, IEC 62368-1, UL 1778 5 th edition 2283

Purpose: To establish requirements for certain battery backed up power supply 2284

systems that are an integral part of the equipment and that have the 2285

capability to backfeed to the mains of the equipment during stored energy 2286

mode. Examples include CATV network distribution supplies and any other 2287

integral supply commonly evaluated under this document with a battery 2288

backed option. 2289

Rationale: Principles of backfeed protection 2290

Battery backed up supplies store and generate hazardous energy . These 2291

energies may be present at the input terminals of the unit. 2292

A backfeed safeguard is intended to prevent ordinary persons, 2293

instructed persons or skilled persons from unforeseeable or 2294

unnecessary exposure to such hazards. 2295

A mechanical backfeed safeguard should meet a minimum air gap 2296

requirement. If not, the mechanical device (contacts) may be forced closed, 2297

and this will not be counted as a fault. The backfeed safeguard operates 2298

with any and all semiconductor devices in any single phase of the mains 2299

power path failed. 2300

A backfeed safeguard works under any normal operating condition . This 2301

should include any output load or input source condition deemed normal by 2302

the manufacturer; however, it is common practice to only test at full - and 2303

no-load conditions, unless analysis of the circuitry proves other conditions 2304

would be less favourable. The circuitry that controls the backfeed 2305

safeguard is intended to be single-fault tolerant. 2306

A backfeed safeguard can accomplish this by disconnecting the mains 2307

supply wiring from the internal energy source, by disabling the inverter and 2308

removing the hazardous source(s) of energy, reducing the source to a safe 2309

level, or by placing a suitable safeguard between the ordinary person, 2310

instructed person or skilled person and the hazardous energy. ES1 is 2311

defined in the body of this document. The method of measurement is as 2312

follows: 2313

– For pluggable equipment, it is determined by opening all phases, 2314

neutral and ground. 2315

– For permanently connected equipment, the neutral and ground are not 2316

removed during the backfeed tests. 2317

Measurements are taken at the unit input connections across the phases, 2318

from phase to neutral and phase and neutral to ground, using the body 2319

impedance model as the measurement device. 2320

Air gap requirements for mechanical disconnect: 2321

An air gap is only required when the backfeed safeguard is mechanical in 2322

nature. The air gap is defined as the clearance distance. There are several 2323

elements to consider when determining the clearance requirement: 2324

– Under normal operation, the space between poles of phases must meet 2325

the requirements for basic insulation (see 5.4.2). 2326

– If the unit is operating on inverter, the source is considered to be a 2327

secondary supply, which is transient free (see 5.4.2). 2328

For a unit with floating outputs, opening all phases and the neutral using 2329

the required clearance for basic insulation is considered acceptable. If 2330

the output is grounded to the chassis , reinforced insulation or equivalent 2331

is required. 2332

Page 69: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 70 – IEC TR 62368-2:2019 © IEC 2019

Fault testing 2333

All backfeed safeguard control circuits are subjected to failure analysis 2334

and testing. 2335

Relays 2336

Relays in the mains path that are required to open for mechanical 2337

protection should be normally open when not energized. 2338

If the relay does not meet the required clearances, the shorting of either 2339

pole/contact may be considered as a single fault to simulate the welding of 2340

the contacts. The failure of a single relay contact may be sensed and the 2341

inverter disabled to prevent feedback. 2342

A relay used for mechanical protection shall be horsepower-rated or pass a 2343

50-cycle endurance test at 600 % of the normal switching current. 2344

Electronic protection 2345

Electronic protection for a backfeed safeguard is acceptable if the 2346

operation of the electronic protection device is sensed and the inverter is 2347

disabled if a fault is found. This is the same requirement as for a relay 2348

having less than the required air gap or clearance or is not relied upon 2349

entirely for mechanical protection. 2350

Mechanical protection 2351

Mechanical protection for a backfeed safeguard is acceptable if it prevents 2352

the user from accessing greater than ES1 and cannot be readily defeated 2353

without the use of tool. The voltage rating of the mechanical protection 2354

should be no less than the maximum out -of-phase voltage. 2355

Control circuitry 2356

The failure, open- or short-circuit, of any component of the backfeed 2357

safeguard circuitry may be analyzed to evaluate the effects on the proper 2358

operation of the backfeed safeguard. Testing may be done on all 2359

components where analysis of the results is arguable. 2360

Components, such as resistors and inductors, are considered to fail open-2361

circuit only. In general, capacitors may fail open or shorted. Solid -state 2362

devices typically fail short and then open. 2363

Microprocessor controls are considered to be acceptable if the circuit 2364

operates safely with any single control line open or shorted to control logic 2365

ground, or shorted to Vcc where such fault is likely to occur . Failure of the 2366

microprocessor can also be simulated by opening the Vcc pin or shorting 2367

the Vcc pin to ground. 2368

If the control circuitry is fully redundant, (for example, N + 1), failure 2369

analysis of individual components is not required if the failure of one circuit 2370

results in a fail-safe mode of operation. 2371

_____________ 2372

6 Electrically-caused fire 2373

Rationale: Electrically-caused fire is due to conversion of electrical energy to thermal 2374

energy, where the thermal energy heats a fuel material to pyrolyze the solid 2375

into a flammable gas in the presence of oxygen. The resulting mixture is 2376

heated further to its ignition temperature which is followed by c ombustion of 2377

that fuel material. The resulting combustion, if exothermic or with additional 2378

thermal energy converted from the electrical source, can be sustained and 2379

subsequently ignite adjacent fuel materials that result in the spread of fire. 2380

Page 70: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:2019 © IEC 2019 – 71 –

The three-block model (see 0.7.2, Figure 6) for electrically (internally) 2381

caused fire addresses the separation of a potential ignition sources from 2382

combustible materials. In addition, it can also represent an ignited fuel and 2383

the safeguards interposed between ignited fuels and adjacent fuels or to 2384

fuels located outside the equipment. 2385

6.2 Classification of power sources (PS) and potential ignition sources (PIS) 2386

Rationale: The first step in the application of this clause is to determine which energy 2387

sources contain potential ignition sources requiring a safeguard. The 2388

power available to each circuit can first be evaluated to determine the 2389

energy available to a circuit. Then each point or component within a circuit 2390

can be tested to determine the power that would be avail able to a fault at 2391

that component. With this information each part of the component energy 2392

sources within the product can be classified as either a specific ignition 2393

source or a component within a power source. 2394

Throughout the clause, the term “reduce the likelihood of ignition” is used 2395

in place of the terms “prevent” or “eliminate”. 2396

6.2.2 Power source circuit classifications 2397

Source: IEC 60950-1, IEC 60065 2398

Rationale: These power source classifications begin with the lowest available energy 2399

necessary to initiate an electronic fire (PS1) and include an intermediate 2400

level (PS2) where ignition is possible but the spread of fire can be localized 2401

with effective material control or isolation safeguards. The highest energy 2402

level (PS3), assumes both ignition and a po tential spread of fire beyond the 2403

ignition source. Criteria for safeguards will vary based on the type of 2404

power source that is providing power to the circuit. 2405

This power measurement and source classification are similar to LPS test 2406

requirements from IEC 60950-1 but are applied independently and the 2407

criteria limited to available power as opposed to in combination of criteria 2408

required in IEC 60950-1. 2409

All circuits and devices connected or intended to be connected as a load to 2410

each measured power source are classified as being part of that power 2411

source. This test method determines the maximum power available from a 2412

power source to any circuit connected to that power source. 2413

The identification of test points for determination of power source is at the 2414

discretion of the manufacturer. The most obvious are outputs of internal 2415

power supply circuits, connectors, ports and board to board connections. 2416

However, these measurements can be made anywhere within a circuit. 2417

When evaluating equipment (peripherals) connected v ia cables to an 2418

equipment port or via cable, the impedance of any connecting cable may be 2419

taken into account in the determination of the PS classification of a 2420

connected peripheral. Therefore, it is acceptable to make the measurement 2421

at the supply connector or after the cable on the accessory side. 2422

The location of the wattmeter is critical , as the total power available from 2423

the power source (not the power available to the fault) is measured during 2424

each fault condition. As some fault currents may be limited by a protective 2425

device, the time and current breaking characteristics of the protective 2426

device used is considered where it has an effect on the value measured. 2427

This test method assumes a single fault in either the power source or the 2428

load circuits of the circuit being classified. It assumes both: 2429

a) a fault within the circuit being classified , and 2430

b) any fault within the power source supplying power to the circuit being 2431

classified, 2432

each condition a) or b) being applied independently. 2433

Page 71: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 72 – IEC TR 62368-2:2019 © IEC 2019

The higher of the power measured is considered the PS circuit 2434

classification value. 2435

6.2.2.2 Power measurement for worst-case fault 2436

Rationale: This test method determines the maximum power available from a power 2437

source that is operating under normal operating conditions to any c ircuit 2438

connected to that power source, assuming any single fault condition within 2439

the circuit being classified. This power measurement assumes normal 2440

operating conditions are established before applying the single fault to any 2441

device or insulation in the load circuit to determine the maximum power 2442

available to a circuit during a fault. 2443

This is different for potential ignition source power measurements where 2444

the measured power available is that at the fault location. 2445

A value of 125 % was chosen to have some degree of certainty that the 2446

fuse will open after a certain amount of time. As such, the measured 2447

situation will not be a continuous situation. It was impossible to use the 2448

interruption characteristics of a fuse, since different types of interrupting 2449

devices have completely different interrupting characteristics. The value of 2450

125 % is a compromise that should cover the majority of the situations. 2451

6.2.2.3 Power measurement for worst-case power source fault 2452

Rationale: This test method determines the maximum power available to a normal load 2453

from a power source assuming any single fault within the power source. A 2454

power source fault could result in an increase in power drawn by a normal 2455

operating load circuit. 2456

6.2.2.4 PS1 2457

Source: IEC 60065, IEC 60695, IEC 60950-1 2458

Rationale: A PS1 source is considered to have too little energy to cause ignition in 2459

electronic circuits and components. 2460

The requirement is that the continuous available power be less than 15 W 2461

to achieve a very low possibility of ignition. The value of 15 W has been 2462

used as the lower threshold for ignition in electronic components in many 2463

documents, including IEC 60950-1 and IEC 60065. It has also routinely 2464

been demonstrated through limited power fault testing in electronic circuits. 2465

– In order to address the ease of measurement, it was decided to make 2466

the 15 W measurement after 3 s. The value of 3 s was chosen to permit 2467

ease of measurement. Values as short as 100 ms and as high as 5 s 2468

were also considered. Quickly establishing a 15 W limit (less than 1 s) is 2469

not practical for test purposes and not considered important for typical 2470

fuel ignition. It is recognized that it normally takes as long as 10 s for 2471

thermoplastics to ignite when impinged directly by a small flame 2472

(IEC 60695 small scale material testing methods). 2473

– In principle the measurements are to be made periodically (for example, 2474

each second) throughout the 3 s period with the expectation that after 3 2475

s, the power would “never” exceed 15 W. 2476

– Historically telecommunication circuits (Table 13, ID 1) are power limited 2477

by the building network to values less than 15 W and the circuits 2478

connected to them are considered PS1 (from IEC 60950-1). 2479

It should be noted that the statement for external circuits is not intended 2480

to cover technologies such as USB and PoE. It is meant to relate to 2481

analogue ringing signals only. 2482

Page 72: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:2019 © IEC 2019 – 73 –

6.2.2.5 PS2 2483

Source: IEC 60695-11-10, IEC 60950-1 2484

Rationale: Power Source 2 assumes a level of energy that has the possibility of 2485

ignition and subsequently requires a safeguard. Propagation of the ignition 2486

beyond the initially ignited component is limited by the low energy 2487

contribution to the fault and subsequently by safeguards to control the 2488

ignition resistance of nearby fuels. 2489

The primary requirement is to limit power available to these circ uits to no 2490

more than 100 W. This value includes both power available for normal 2491

operation and the power available for any single fault condition . 2492

– This value has been used in IEC 60950-1 for a similar purpose, where 2493

ignition of internal components is poss ible but fire enclosures are not 2494

required. 2495

– The value of 100 W is commonly used in some building or fire codes to 2496

identify where low power wiring can be used outside of a fire containing 2497

enclosure. 2498

– The value is also 2 × 50 W, which can be related to the energy of 2499

standard flaming ignition sources ( IEC 60695-11-10 test flame) on 2500

which our small-scale V-rating material flammability classes are 2501

based. It is recognized that the conversion of electrical energy to 2502

thermal energy is far less than 100 %, so this value is compatible with 2503

the safeguards prescribed for PS2 circuits, which are generally 2504

isolation and V-rated fuels. 2505

The 5 s measurement for PS2 ensures the available power limits are both 2506

limited and practical for the purposes of measurement. The value is also 2507

used in IEC 60950 series as referenced above. No short-term limits are 2508

considered necessary, as possibility of ignition is presumed for 2509

components in these power limited circuits , recognizing that it generally 2510

takes 10 s or more for thermoplastics to pyrolyze and then ignite when 2511

impinged directly by a small 50 W flame. 2512

Reliability of overcurrent devices (such as those found in IEC 60950 series) 2513

is not necessary as these circuits are used within or directly adjacent to the 2514

product (not widely distributed like IEC 60950-1 LPS circuits used for 2515

connection to building power). The reliability assessment for PS2 circuits 2516

that are intended to be distributed within the building wiring is addressed 2517

for external circuits later in this document. 2518

6.2.2.6 PS3 2519

Rationale: PS3 circuits are circuits that are not otherwise classified as PS1 or PS2 2520

circuits. No classification testing is required as these circuits can have 2521

unlimited power levels. If a circuit is not measured, it can be assumed to be 2522

PS3. 2523

6.2.3 Classification of potential ignition sources 2524

Rationale: With each power source, points and components within a circuit can be 2525

evaluated to determine if potential ignition sources are further identified. 2526

These ignition sources are classified as either an arcing PIS for arcing 2527

sources or a resistive PIS for resistance heating sources. Criteria for 2528

safeguards will vary based on the type of PIS being addressed. 2529

Ignition sources are classified on their ability to either arc or dissipate 2530

excessive heat (resistive). It is important to distinguish the type of ignition 2531

source as distances through air from arcing parts v ersus other resistive 2532

ignition sources vary due to a higher thermal loss in radiated energy as 2533

compared to conducted flame or resistive heat impinging direc tly on a 2534

combustible fuel material. 2535

Page 73: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 74 – IEC TR 62368-2:2019 © IEC 2019

6.2.3.1 Arcing PIS 2536

Source: IEC 60065 2537

Rationale: Arcing PIS are considered to represent a thermal energy source that 2538

results from the conversion of electrical energy to an arc, which may 2539

impinge directly or indirectly on a fuel material. 2540

Power levels below 15 W (PS1) are considered to be too low to initiate an 2541

electrical fire in electronic circuits. This value is used in IEC 60065 (see 2542

also 6.2.1). 2543

The minimum voltage (50 V) required to initiate arcing is also from 2544

IEC 60065 and through experimentation. 2545

For low-voltages, the fault that causes arc -heating is generally a result of a 2546

loose connection such as a broken solder connection, a cold -solder 2547

connection, a weakened connector contact, an improperly crimped wire, an 2548

insufficiently tightened screw connection, etc. As air does not breakdown 2549

below 300 V RMS. (Paschen’s Law), most low voltage arc -heating occurs 2550

in direct contact with a fuel. For voltages greater than 300 V, arcing can 2551

occur through air. 2552

The measurement of voltage and current necessary to establish an arcing 2553

PIS is related the energy that is available to the fault (as opposed to 2554

energy available from a power source). The value ( Vp × Irms) specified is 2555

neither a W or VA but rather a calculated number reflecti ng a peak voltage 2556

and RMS current. It is not directly measurable. 2557

Arcing below 300 V is generally the result of a disconnection of current -2558

carrying connections rather than the mating or connection of potentially 2559

current-carrying connections. 2560

Once the basic parameters of voltage and power are met, there are three 2561

conditions for which safeguards are required: 2562

– those that can arc under normal operating conditions ; 2563

– all terminations where electrical failure resulting in heating is more 2564

likely; and 2565

– any electrical separation that can be created during a single fault 2566

condition (such as the opening of a trace). 2567

A reliable connection is a connection which is expected not to become 2568

disconnected within the lifetime of the equipment . The examples in the note 2569

give an idea as to what kinds of connections can be considered reliable. 2570

The manufacturer may declare any location to be an arcing PIS. 2571

6.2.3.2 Resistive PIS 2572

Source: IEC 60065 2573

Rationale: Resistive potential ignition sources can result from a fault that causes 2574

over-heating of any impedance in a low-resistance that does not otherwise 2575

cause an overcurrent protection to operate. This can happen in any circuit 2576

where the power to the resistive heating source is greater than 15 W (see 2577

above). A resistive PIS may ignite a part due to excessive power 2578

dissipation or ignite adjacent materials a nd components. 2579

Under single fault conditions , this clause requires that two conditions 2580

exist before determining that a part can be a resistive PIS. The first is that 2581

there is sufficient available fault energy to the component. The second is 2582

that ignition of the part or adjacent materials can occur. 2583

The requirement for a resistive PIS under normal operating conditions is 2584

not the available power but rather the power dissipation of th e part under 2585

normal operating conditions. 2586

Page 74: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:2019 © IEC 2019 – 75 –

The value of 30 s was used in IEC 60065 and has historically proven to be 2587

sufficient. The value of 100 W was used in IEC 60065 and has historically 2588

proven to be adequate. 2589

The manufacturer may declare any location to be a resistive PIS. 2590

6.3 Safeguards against fire under normal operating conditions and abnormal 2591

operating conditions 2592

Rationale: The basic safeguard under normal operating conditions and abnormal 2593

operating conditions is to reduce the likelihood of igniti on by limiting 2594

temperature of fuels. This can be done by assuring that any available 2595

electrical energy conversion to thermal energy does not raise the 2596

temperature of any part beyond its ignition temperature. 2597

2598

Figure 28 – Possible safeguards against electrically-caused fire 2599

There are several basic safeguards and supplementary safeguards against 2600

electrically-caused fire under abnormal operating conditions and single fault 2601

conditions (see Figure 28, Table 8 and Table 9 in this document). These 2602

safeguards include, but are not limited to: 2603

S1) having insufficient power to raise a fuel material to ignition temperature; 2604

S2) limiting the maximum continuous fault current; limiting the maximum duration 2605

for fault currents exceeding the maximum continuous fault current (for example, 2606

a fuse or similar automatic-disconnecting overcurrent device); 2607

S3) selecting component rating based on single fault conditions rather than 2608

normal operating conditions (prevents the component from overheating); 2609

S4) ensuring high thermal resistance of the thermal energy transfer path from the 2610

thermal energy source to the fuel material (reduces the temperature and the 2611

rate of energy transfer to the fuel material so that the fuel material cannot 2612

attain ignition temperature); or a barrier made of non-combustible material; 2613

S5) using an initial fuel material located closest to an arcing PIS or resistive PIS 2614

having a temperature rating exceeding the temperature of the source (prevents 2615

Page 75: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 76 – IEC TR 62368-2:2019 © IEC 2019

fuel ignition); or a flame-retardant fuel material (prevents sustained fuel 2616

burning and spread of fire within the equipment); or a non-combustible 2617

material (for example, metal or ceramic); 2618

S6) ensuring high thermal resistance of the thermal energy transfer path from the 2619

initial fuel to more fuel material; or flame isolation of the burning initial fuel from 2620

more fuel material (prevents spread of fire within the equipment); 2621

S7) ensuring that subsequent material is either non-combustible material (for 2622

example, metal or ceramic); or is a flame-retardant material (prevents 2623

sustained fuel burning and spread of fire within the equipment); 2624

S8) use of a fire-containing enclosure (contains the fire within the equipment) or 2625

an oxygen-regulating enclosure (quenches a fire by suffocating it); 2626

S9) use of reliable electrical connections; 2627

S10) use of non-reversible components and battery connections; 2628

S11) use of mechanical protection (for example, barriers, mesh or the like) with 2629

limited openings; 2630

S12) use of clear operating instructions, instructional safeguards, cautions. 2631

Methods of protection 2632

A) Protection under normal operating conditions and abnormal 2633

operating conditions 2634

Materials and components shall not exceed their auto-ignition temperatures. 2635

B) Protection under single fault conditions 2636

There are two methods of providing protection. Either method may be applied 2637

to different circuits in the same equipment: 2638

– Prevent ignition: equipment is so designed that under abnormal operating 2639

conditions and single fault conditions no part will ignite; 2640

– Control fire spread: selection and application of components, wiring, 2641

materials and constructional measures that reduce the spread of flame and, 2642

where necessary, by the use of a fire enclosure. 2643

Thermoplastic softening values or relative thermal indices (RTI) were not 2644

considered appropriate as they do not relate specifically to ignition properties 2645

of fuel materials. 2646

Any device that operates as a safeguard during normal operation (when left in 2647

the circuit) shall be assessed for reliability. If a device is taken out of the circuit 2648

during the normal operation testing then it is not considered as being a 2649

safeguard. 2650

Abnormal operating conditions that do not result in a single fault are 2651

considered in much the same way as normal operating conditions as the 2652

condition is corrected and normal operation is presumed to be restored. 2653

However, abnormal operating conditions that result in a single fault 2654

condition are to be treated in accordance with 6.4 rather than 6.3. See 2655

Figure 29 in this document for a fire clause flow chart. 2656

Page 76: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:2019 © IEC 2019 – 77 –

Table 8 – Examples of application of various safeguards 2657

Cause Prevention/protection methods Safeguard

Start of f ire under normal operating conditions

Limit temperature of combustible material Basic

Start of fire under abnormal operating conditions and single fault conditions

Select prevent ignition or control fire spread method

Supplementary

PS1 circuit Low available power reduces the likelihood of ignition

S1

PS2 or PS3 circuit Reduce the likelihood of ignition

Use of protection devices

S1, S2, S3, S5

S2

Sufficient distance or solid barrier interposed between any combustible material and each potential ignition source

S4 (S6)

PS2 circuit Limit the available power

Sufficient distance or solid barrier interposed between any combustible material and each potential ignition source

Use flame-retardant or non-combustible material

S1, S2

S4, S6

S5

PS3 circuit Use all PS2 options and:

− use fire containing enclosures

− use flame-retardant or similar materials

S8

S7

Internal and external wiring Reliable construction

Limit of wire temperature and use of fire resistant insulation

S9

Fire caused by entry of foreign obj ects and subsequent bridging of electrical terminals in PS2 circuits and PS3 circuits

Prevent entry of foreign objects S11

Mains supply cords Reliable construction

Limit of wire temperature and use of fire resistant insulation

S9

Fire or explosion due to abnormal operating conditions of batteries

Limit charge/discharge currents

Limit short-circuit currents

Prevent use of wrong polarity

S1

S2

S10

2658

Page 77: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 78 – IEC TR 62368-2:2019 © IEC 2019

2659

Figure 29 – Fire clause flow chart 2660

6.3.1 Requirements 2661

Source: IEC 60950-1, ISO 871 2662

Rationale: Spontaneous-ignition temperature as measured by ISO 871 for materials 2663

was chosen as the ignition point of fuels. The materials specific tables 2664

were deleted in favour of a simple requirement or completely referring 2665

instead to the ASTM standard for material auto-ignition temperatures. 2666

Page 78: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:2019 © IEC 2019 – 79 –

The 300 °C value for thermoplastics is approximately 10 % less than the 2667

lowest ignition temperature of materials commonly used in ICT and CE 2668

equipment. This value has also been used in IEC 60950-1. The designer is 2669

permitted to use material data sheets for materials that exceed this value 2670

but the auto-ignition specification has to be reduced by 10 % to 2671

accommodate measurement variations and uncertainty. 2672

In the context of fire, abnormal operating conditions (blocked vents, 2673

connector overload, etc.) are to be considered just as a normal operating 2674

condition unless the abnormal operating condition results in a single 2675

fault condition. 2676

As part of the compliance check, first the datasheets of the materials used 2677

have to be checked to be able to evaluate the results of the temperature 2678

rise measurements. 2679

The glow-wire test is a fire test method of applying a heat source to the 2680

sample. The test provides a way to compare a material’s tendency to resist 2681

ignition, self-extinguish flames (if ignition occurs), and to not propagate 2682

fire. Manufacturers have been using this test method to determine a 2683

plastic’s flame resistance characteristics to IEC 60950-1 for many years 2684

without field issues identified with the suitability of the test. Hence, the 2685

glow-wire test should continue to be an option to the HB rating for plastics 2686

outside of the fire enclosure or mechanical enclosures and for electrical 2687

enclosures housing PS1 circuits. This precedence has been set in 2688

IEC 60950-1 and should be included in IEC 62368-1. 2689

Table 9 – Basic safeguards against fire under normal operating conditions 2690

and abnormal operating conditions 2691

Normal operating conditions and abnormal operating conditions

The objective of this subclause is to define requirements to reduce the likelihood of ignition under normal operating conditions and abnormal operating conditions .

PS1

PS2

PS3

6.3.1

Ignition is not allowed

Tmax

90 % auto ignition temperature according to ISO 871; or

Tmax

300 ºC

Combustible materials for components and other parts outside fire enclosures (including electrical enclosures, mechanical enclosures and decorative parts), shall have a material flammability class of at least: – HB75 if the thinnest significant thickness of this material is < 3 mm, or

– HB40 if the thinnest significant thickness of this material is 3 mm, or – HBF.

NOTE Where an enclosure also serves as a fire enclosure, the requirements for fire enclosures apply.

These requirements do not apply to:

– parts with a size of less than 1 750 mm3; – supplies, consumable materials, media and recording materials; – parts that are required to have particular properties in order to perform

intended functions, such as synthetic rubber rollers and ink tubes; – gears, cams, belts, bearings and other parts that would contribute negligible

fuel to a fire, including labels, mounting feet, key caps, knobs and the like.

2692

Page 79: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 80 – IEC TR 62368-2:2019 © IEC 2019

6.3.2 Compliance criteria 2693

Rationale: Steady state for temperature measurements in excess of 300 °C requires 2694

more tolerance on the rise value due to the difficulty in achieving a stable 2695

reading. However, the value in B.1.6 was considered adequate, as these 2696

values typically do not continue to rise but rather cycle . The value of 3 °C 2697

over a 15 min period was also considered for measurement of these very 2698

high temperatures but was not used in favour of harmonization with other 2699

clauses. 2700

The use of temperature-limiting safeguards under normal operating 2701

conditions and abnormal operating conditions is considered acceptable 2702

only where the safeguard or device has been deemed a reliable 2703

temperature control device. 2704

6.4 Safeguards against fire under single fault conditions 2705

6.4.1 General 2706

Source: IEC 60065, IEC 60950-1 2707

Rationale: The consideration in the prior clause is to li mit the likelihood of 2708

ignition of fuels under normal operating conditions and abnormal 2709

operating conditions with a basic safeguard. All fuels should be used 2710

below their ignition temperatures and separated from a rcing parts. 2711

The requirements in this clause are to limit the ignition or the spread of fire 2712

under single fault conditions by employing supplementary safeguards, 2713

see Table 10 in this document. There are two approaches that can be used 2714

either jointly or independently: 2715

– method 1 minimizes the possibility of ignition through the use of 2716

safeguards applied at each potential point of ignition ; 2717

– method 2 assumes the ignition of limited fuels within the product and 2718

therefore requires safeguards that limit the spread of fire beyond the 2719

initial ignition point or for higher energy, beyond the equipment 2720

enclosure. 2721

Table 10 – Supplementary safeguards against fire under single fault conditions 2722

Single fault conditions

There are two methods of provid ing protection. Either method may be applied to different circuits of the same equipment (6.4.1)

Method 1

Reduce the likelihood of

ignition

Equipment is so designed that under single fault conditions no part shall ignite.

This method can be used for any circuit in which the available steady state power to the circuit does not exceed 4 000 W.

The appropriate requirements and tests are detailed in 6.4.2 and 6.4.3.

Method 2

Control fire spread

Selection and application of supplementary safeguards for components, wiring, materials and constructional measures that reduce the spread of fire and, where necessary, by the use of a second supplementary safeguard such as a fire enclosure.

This method can be used for any type of equipment.

The appropriate requirements are detailed in 6.4.4, 6.4.5 and 6.4.6.

2723

The document’s user or product designer will select a method to apply to each 2724

circuit, (either prevent ignition method or control the spread of fire method). 2725

The selection of a method can be done for a complet e product, a part of a 2726

product or a circuit. 2727

Page 80: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:2019 © IEC 2019 – 81 –

The power level of 4 000 W was chosen to ensure that products which are 2728

connected to low power mains (less than 240 V × 16 A), common in the office 2729

place or the home, could use the ignition protection methods , and to provide a 2730

reasonable and practical separation of product types. It is recognized that this 2731

is not representative of fault currents available but is a convenient and 2732

representative separation based on equipment connected to normal office and 2733

home mains circuits where experience with potential ignition sources 2734

safeguards is more common. 2735

Limit values below 4 000 W create a problem for the AC mains of almost all 2736

equipment used in the home or office , which is not the intent. It would be much 2737

more practical to use an energy source power of 4 000 W based on mains 2738

voltage and overcurrent device rating which would effectively permit all 2739

pluggable type A equipment to use either method, and restrict very high-2740

power energy sources to use only the method to contr ol fire spread. 2741

The 4 000 W value can be tested for individual circuits; however, a note has 2742

been added to clarify which types of products are considered below without 2743

test. Calculation of the product of the mains nominal voltage and mains 2744

overcurrent device rating is not a normal engineering convention but rather the 2745

product of two numbers should not exceed 4 000 (see text below). 2746

NOTE All pluggable equipment type A are considered to be below the steady state value of 2747 4 000 W. Pluggable equipment type B and permanently connected equipment are considered 2748 to be below this steady state value if the product of nominal mains voltage and the current rating 2749 of the installation overcurrent protective device is less than 4 000. 2750

Prevent ignition method: Prescribes safeguard requirements that would 2751

prevent ignition and is predominantly based on fault testing and component 2752

selection and designs that reduce the likelihood of sustained flaming. Where a 2753

PIS is identified, additional safeguards are required to use barriers and the fire 2754

cone ‘keep out’ areas for non -flame rated materials (see Table 11 and 2755

Figure 30 in this document). 2756

The prevent ignition method has been used in IEC 60065 where the 2757

predominant product connection is to low power (< 16 A) mains circuits. The 2758

use of this method was not considered adequate enough for larger mains 2759

circuits because the size of the fire cone does not adequately address large 2760

ignition sources common in higher power circuits. 2761

This approach limits the use of prevent ignition methods to those products 2762

where the ignition sources is characterized by the fire cones and single fault 2763

conditions described in 6.4.7. 2764

Page 81: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 82 – IEC TR 62368-2:2019 © IEC 2019

Table 11 – Method 1: Reduce the likelihood of ignition 2765

Method 1: Reduce the likelihood of ignition under single fault conditions

PS1

(≤ 15 W after 3) 6.4.2

No supplementary safeguards are needed for protection against PS1.

A PS1 is not considered to contain enough energy to result in materials reaching ignition temperatures.

PS2

( PS1 and

≤ 100 W after 5 s)

and

PS3

( PS2 and

≤ 4 000 W)

6.4.3

The objective of this subclause is to define the supplementary safeguards needed to reduce the likelihood of ignition under single fault conditions in PS2 circuits and PS3 circuits where the available power does not exceed 4 000 W. All identified supplementary safeguards need to be considered based on the equipment configuration.

Sustained flaming 10 s is not allowed and no surrounding parts shall have ignited.

Separation from arcing PIS and resistive PIS according to 6.4.7

– Distances have to comply with Figures 37, 38, 39a and 39b; or

– In case the distance between a PIS and combustible material is less than specified in Figures 37, 38, 39a and 39b;

• Mass of combustible material < 4 g, or

• Shielded from the PIS by a fire barrier, or

• Flammability requirements:

o V-1 class material ; VTM-1 class material or HF-1 class material , or needle flame in Clause S.2, or

o Relevant component IEC document

Using protective devices that comply with G.3.1, G.3.2, G.3.3 and G.3.4 or the relevant IEC component documents for such devices;

Using components that comply with G.5.3, G.5.4 or the relevant IEC component document;

Components associated with the mains shall comply with:

the relevant IEC component documents; and

the requirements of other clauses of IEC 62368-1

2766

2767

Page 82: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:2019 © IEC 2019 – 83 –

IEC

TR

62

36

8-2

:20

19

© IE

C 2

01

9

– 8

3 –

Figure 30 – Prevent ignition flow chart

Page 83: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 84 – IEC TR 62368-2:2019 © IEC 2019

Control fire spread method: Prescribes safeguards that are related to the spread of fire from acknowledged ignition sources. This assumes very little performance testing (no single fault conditions) and the safeguards are designed to minimize the spread of flame both within th e product and beyond the fire enclosure. The safeguards described are based on power level , with higher power sources requiring more substantial safeguards (see Figure 31, Figure 32 and Table 12 in this document).

This power (4 000 W) separation is also used in the control of fire spread method to delineate safeguard criteria for fire enclosure materials (V-1 versus 5 V). IEC 60950-1 has historically used weight to define fire enclosure criteria and it was felt that the use of available power was more appropriate and generally reflective of current practice.

Page 84: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:2019 © IEC 2019 – 85 –

IEC

TR

62

36

8-2

:20

19

© IE

C 2

01

9

– 8

5 –

Figure 31 – Control fire spread summary

Page 85: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 86 – IEC TR 62368-2:2019 © IEC 2019 –

86

IEC

TR

62

36

8-2

:20

19

© IE

C 2

01

9

Figure 32 – Control fire spread PS2

Page 86: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:2019 © IEC 2019 – 87 –

IEC

TR

62

36

8-2

:20

19

© IE

C 2

01

9

– 8

7 –

Figure 33 – Control fire spread PS3

Page 87: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 88 – IEC TR 62368-2:20xx © IEC 2019

6.4.2 Reduction of the likelihood of ignition under single fault conditions in PS1 1

circuits 2

Rationale: Low available power prevents ignition – 15 W is recognized as the lower 3

limit of ignition for electronic products. The limiting of power is not 4

considered the basic safeguard but rather the characteristic of the circuit 5

being considered. This determination is made as part of the classification 6

of power sources. 7

6.4.3 Reduction of the likelihood of ignition under single fault conditions in PS2 8

circuits and PS3 circuits 9

Rationale: To identify all potential ignition sources, all circuits and components 10

within the PS2 and PS3 circuits should be evaluated for their propensity to 11

ignite. 12

The ignition source derived from either PS2 or a PS3 circuit is considered 13

equivalent. The resulting flame size and burn time is identical in all PS2 14

and PS3 circuits unless the power available is very large (for example, 15

greater than 4 000 W). 16

For very large sources (greater than 4 000 W) the safeguards described 17

for addressing potential ignition sources are not recognized as being 18

adequate and the control fire spread method is used (see 6.4.1 for 4 000 W 19

rationale). 20

6.4.3.1 Requirements 21

Source: IEC 60065, IEC 60695-2-13, IEC 60950-1 22

Rationale: Flaming of a fuel under single fault conditions is only permitted if very 23

small and quickly extinguished (for example , a fusing fuse resistor). A 24

length of time is necessary during single fault conditions to permit the 25

characteristic “spark” or short term “combustion flash” common when 26

performing single fault conditions in electronic circuits. The value of 10 s 27

is used, which has been used by IEC 60065 for many years. The energy of 28

this short-term event is considered too low to ignite other parts. This value 29

corresponds with IEC 60695-2-13 and has been used in practice by IEC TC 30

89 for glow wire ignition times. The time period is necessary to 31

accommodate the expected flash/short duration flames that often result as 32

a consequence of faults. The value of 10 s is considered to be the 33

minimum time needed for ignition of commonly used thermoplastics by 34

direct flame impingement. It is recognized that times as short as 2 s are 35

used by other documents. 36

Protection is achieved by identifying each PIS and then limiting the 37

temperature of parts below auto-ignition temperatures during single fault 38

conditions, minimizing the amount of flammable material near a PIS, 39

separating combustible materials from PIS by barriers, and by using 40

reliable protection devices to limit temperature of combustible parts. 41

Single fault testing, while not statistically significant, has been common 42

practice in both IEC 60065 and IEC 60950-1. 43

Temperatures limiting ignition are considered to be the material self -44

ignition points or flash temperatures for flammable liquids and vapours (this 45

value should include a 10 % margin to take into account ambient, 46

laboratory and equipment operat ing conditions). The spread to surrounding 47

parts during and after the fault is also checked. 48

Page 88: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:20xx © IEC 2019 – 89 –

Providing sufficient distance or solid barrier between any combustible 49

material and a potential ignition source should minimize the potential for 50

the spread of fire beyond the fuels directly in contact with the potential 51

ignition source. The fire cone distances developed for IEC 60065 are 52

used and considered adequate. We prescribed the use of the cone 53

because it is more reliable than single fault testing. Single fault testing is 54

not completely representative; therefore, some material and construction 55

requirements are necessary (fuel control area or keep out area). 56

Use of reliable protection devices – This includes reliability requirements 57

for the devices that are used to prevent ignition. This permits only the use 58

of devices that have reliability requirements included in Annex G. 59

Components that comply with their relevant IEC component documents 60

standards are also considered to comply given these documents standards 61

also have ignition protection requirements. The components included are 62

those that are almost always part of a potential ignition source as they 63

are mains connected. 64

Opening of a conductor: In general, opening of a conductor is not permitted 65

during single fault conditions as it is not considered reliable protection 66

device for limiting ignition. However for resistive PIS, it may be suitable 67

provided the printed wiring board is adequately flame retardant and the 68

opening does not create an arcing PIS. The V-1 printed circuit board is 69

considered adequate to quench low voltage events and will not propagate 70

the flame. It is not sufficient when the opening creates an arcing PIS 71

(< 50 V). 72

As a consequence of the test, any peeling of conductor during these tests 73

shall not result in or create other hazards associated with the movement of 74

conductive traces during or after the test provided they do so predictably. 75

During a single fault the peeling could bridge a basic safeguard but should 76

not result in the failure of a supplementary safeguard or reinforced 77

safeguard. 78

6.4.3.2 Test method 79

Source: IEC 60065, IEC 60127 80

Rationale: The available power and the classification criteria for resistive and arcing 81

potential ignition sources should be used to determine which 82

components to fault. 83

If the applied single fault condition causes another device or subsequent 84

fault, then the consequential failure is proven reliable by repeating the 85

single fault condition two more times (total of three times). This is a 86

method used historically in IEC 60065. 87

Steady state determination for single fault conditions is related to 88

temperature rise and the requirement is the same as the steady state 89

requirements of Annex B, even though material ignition temperatures 90

( 300 °C) are much higher than required temperatures of other clauses 91

(~25 °C – 100 °C). Shorter time periods (such as 15 min) were considered 92

but dropped in favour of harmonization of other parts. The term steady 93

state should take into account temperatures experienced by a material 94

throughout the test. 95

Maximum attained temperature for surrounding material of heat source 96

should be considered if further temperature increase is observed after 97

interruption of the current. 98

Limit by fusing: The reliability of protection devices is ensured where they 99

act to limit temperatures and component failures. The criteria used by the 100

component document applying to each are considered adequate provided 101

the parts are used as intended. The requirements included assume an 102

IEC 60127 type fuse as the most common device. 103

Met opmerkingen [RJ4]: See Raleigh minutes item 7.1.2

Page 89: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 90 – IEC TR 62368-2:20xx © IEC 2019

The test methodology is established to ensure that available energy 104

through the fuse link based on its current hold and interrupt conditions the 105

breaking time characteristics of specified in IEC 60127. IEC 60127 permits 106

2,1 times the breaking current rating for 1 min. 107

In order to determine the impact of a fuse on the results of a single fault 108

condition, if a fuse operates, it is replaced with a short circuit and the test 109

repeated. There are three possible conditions when comparing the actual 110

fault current through the fuse to the pre -arcing current and time data 111

sheets provided by the fuse manufacturer. 112

– Where the measured current is always below the fuse manufacturer's 113

pre-arcing characteristics (measured current is less than 2,1 times the 114

fuse rating), the fuse cannot be relied upon as a safeguard and the test 115

is continued with the fuse short circuited until steady state where the 116

maximum temperature is measured. 117

– Where the measured current quickly exceeds the fuse p re-arcing 118

characteristics (measured current is well above 2,1 times the rating 119

current of the fuse) then the test is repeated with the open circuit in 120

place of the fuse (assumes fuse will open quickly and be an open circuit ) 121

and then the maximum temperature recorded. 122

– Where the measured current does not initially exceed the fuse pre -123

arcing characteristics, but does at some time after introduction of the 124

fault. The test is repeated with the short circuit in place and the 125

temperature measured at the time where measured current exceeds the 126

fuse pre-arcing characteristics. It is assumed the measured current 127

through the short circuit can be graphed and compared with the fuse 128

manufacturer’s pre-arcing curves provided on the fuse datasheet to 129

determine the test time. 130

6.4.4 Control of fire spread in PS1 circuits 131

Rationale: Low available power reduces the likelihood for ignition – 15 W is 132

recognized as the lower limit of ignition for electronic circuits. This lower 133

power limit is considered as a circuit characteristic o f the circuit, not a 134

basic safeguard. 135

Page 90: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:20xx © IEC 2019 – 91 –

Table 12 – Method 2: Control fire spread 136

Method 2: Control fire spread

PS1

(≤ 15 W) 6.4.4

No supplementary safeguards are needed for protection against PS1.

A PS1 is not considered to contain enough energy to result in materials reaching ignition temperatures.

PS2

(≤ 100 W after 5 s) 6.4.5

The objective of this subclause is to describe the supplementary safeguards needed to reduce the likelihood of fire spread from a PIS in PS2 circuits to nearby combustible materials.

The limiting of power available to PS2 circuits is the basic safeguard used to minimize the available energy of an ignition source.

A supplementary safeguard is required to control the spread of fire from any possible PIS to other parts of the equipment

For conductors and devices with a PIS the following apply:

– Printed boards shall be at least V-1 class material

– Wire insulation shall comply with IEC 60332 series or IEC 60695-11-21

Battery cells and battery packs shall comply with Annex M.

All other components:

– Mounted on V-1 class material , or

– Materials V-2 class material , VTM-2 class material , or HF-2 class material, or

– Mass of combustible material < 4 g, provided that when the part is ignited the fire does no t spread to another part, or

– Separated from PIS according to 6.4.7,

Distances have to comply with Figures 37; 38; 39 and 40, or

In case distances do not comply with Figures 37; 38; 39 and 40

– Mass of combustible material < 4 g, or

– Shielded from the PIS by a fire barrier, or

– Flammability requirements: V-1 class material ; VTM-1 class material or HF-1 class material , or comply with the needle flame test of IEC 60695-11-5 as described in Clause S.2; or

– Comply with IEC component document flammability requirements, or comply with G.5.3 and G.5.4

– Insulation materials used in transforme rs, bobbins, V-1 class material

– In a sealed enclosure ≤ 0,06 m3 made of non-combustible material and having no ventilation openings

The following shall be separated from a PIS according to 6.4.7 or shall not ignite due to fault conditional testing

– Supplies, consumables, media and recording materials

– Parts which are required to have particular properties in order to perform intended functions, such as synthetic rubber rollers and ink tubes

137

Page 91: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 92 – IEC TR 62368-2:20xx © IEC 2019

138

Method 2: Control fire spread

PS3

( PS2)

The objective of this subclause is to describe the supplementary safeguards needed to reduce the likelihood of fire spread from a PIS in PS3 circuits to nearby combustible materials.

6.4.6

Fire spread in PS3 circuit shall be controlled by;

– the use of a fire enclosure as specified in 6.4.8. and

– applying all requirements for PS2 circuits as specified in 6.4.5

Devices subject to arcing or changing contact resistance (for example, pluggable connectors) shall comply with one of the following :

– Materials V-1 class material ; or

– Comply with IEC component document flammability requirements; or

– Mounted on V-1 class material and volume ≤ 1 750 mm 3

Exemptions:

– Wire and tubing insulation complying with IEC 60332 series or IEC 60695-11-21

– Components, including connectors complying wi th 6.4.8.2.2 and that fill an opening in a fire enclosure

– Plugs and connectors forming a part of a power supply cord or complying with 6.5, G. 4.1 and G.7

– Transformers complying with G .5.3

– Motors complying with G.5.4

6.4.6

For PS2 or a PS3 circuit

within a fire en-closure

See all requirements for PS2 (6.4.5)

6.4.6

For a PS1 circuit

within a fire

enclosure

Combustible materials:

Needle flame test in Clause S.1 or V-2 class material or VTM-2 class material or HF-2 class material

Exemptions:

– Parts with a size less than 1 750 mm3

– Supplies, consumable materials , media and recording materials

– Parts that are required to have particular properties in order to perform intended functions such as synthet ic rubber rollers and ink tubes

– Gears, cams, belts, bearings and other small parts that wo uld contribute negligible fuel to a fire, including, labels, mounting fee t, key caps, knobs and the like

– Tubing for air or any fluid systems, containers for powders or liquids and foamed plastic parts, provided that they are of HB75 class material if the thinnest significant thickness of the material is < 3 mm, or HB40 class material if the thinnest significant thickness of the material is ≥ 3 mm, or HBF class foamed material

139

6.4.5 Control of fire spread in PS2 circuits 140

Source: IEC 60950-1 141

Rationale: In principle, limiting the available power to the circuit (100 W) in PS2 142

circuits and control of adjacent fuel materials will reduce the spread of fire, 143

assuming that ignition of components can occur. This power level limit 144

minimizes the size of the ignition source and its impingement on adjacent 145

fuels that are in the PS2 circuits. 146

Page 92: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:20xx © IEC 2019 – 93 –

The purpose of this clause is to establish control of fuels in or near circuits 147

that have the possibility of ignition. As no fault testing is done for PS2 148

circuits, it is assumed that a fire ignition can occur anywhere within the 149

circuits. These safeguards are to be based on component material 150

flammability characteristics that keep the initial ignition source from 151

spreading to surrounding internal materials. 152

This clause assumes only construction safeguards in a manner consistent 153

with the historically effective requirements of IEC 60950-1. 154

Only fuels that would contribute significant fuel to a fire are considered. 155

Acceptance of limited power sources in Annex Q .1 to be classified as PS2 156

has been added to allow continued use of the long existing practice in 157

IEC 60950-1. 158

6.4.5.2 Requirements 159

Source: IEC 60065, IEC 60950-1 160

Rationale: Requirements around conductors and devices subject to arcing parts and 161

resistive heating have the most onerous requirements for sustained ignition 162

and protection of wiring and wiring boards. 163

– Mounting on a flame-retardant material to limit fire growth. V-1 164

mounting materials are considered important as they limit fuel to reduce 165

sustained flaming and also would not contribute to large fires or pool 166

fire. The spread of fire from ignited small parts can be managed by the 167

larger printed wiring board. This provision is made to allow the use of a 168

longstanding IEC 60950-1 provision for small devices mounted directly 169

on boards. The value 1 750 mm3 has been used in practice in 170

IEC 60065. 171

– Use of flame retardant wiring is identical to the internal and external 172

wiring requirements of Clause 6. 173

– Accepting existing component requirements for devices that have their 174

own requirements (IEC or annexes of this document) are considered 175

adequate. 176

– Sufficient distance or solid flame-resistant barrier between any 177

combustible material and potential ignition sources. (KEEP OUT 178

ZONES or RESTRICTED AREA). 179

All other components (those that are not directly associated with arcing or 180

resistive heating components) have a reduced set of safeguards when 181

compared to those parts more likely to ignite. Those safeguards include 182

any of the following: 183

– For parts not directly subject to arcing or resistive heating, V-2 ratings 184

are considered adequate. This is also a historical requirement of 185

IEC 60950-1 for parts used in limited power circuits. Sustained ignition 186

of V-2 class materials is similar to that of V-1 class materials in the 187

small-scale testing. The use of VTM-2 or HF-2 class materials were 188

also considered adequate. 189

– Limiting the combustible fuel mass within the area around PS2 circuit 190

devices. The limit of 4 g is brought from the small parts definition used 191

with PIS requirements of this clause and which were originally used in 192

IEC 60065. 193

– As an alternative, components and circuits can be separated from fuels 194

per the requirements of the fire cone described for isolation of fuels 195

from potential ignition sources. 196

– Enclosing parts in small oxygen limiting, flame proof, housing. The 197

0,06 m2 value has been in practice in IEC 60950-1 and small enough to 198

mitigate fire growth from a low power source. 199

Page 93: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 94 – IEC TR 62368-2:20xx © IEC 2019

The exceptions included are based on common constructions of material 200

that do not routinely have flame retardants or that cannot contain flame 201

retardants due to functional reasons. They are either isolated from any PIS 202

or through single fault condition testing demonstrate that they will simply 203

not ignite in their application. 204

Supplies are quantities of materials such as paper, ink, toner, staples etc ., 205

and that are consumed by the equipment and replaced by the user when 206

necessary. 207

6.4.5.3 Compliance criteria 208

Rationale: Material flammability requirements are checked by the testing of Annex S, 209

by compliance with the component document or through review of material 210

data sheets. 211

6.4.6 Control of fire spread in a PS3 circuit 212

Source: IEC 60950-1 213

Rationale: There are two basic requirements to control the spread of fire from PS3 214

circuits: 215

a) use of materials within the fire enclosure that limit fire spread. This 216

includes the same requirements as for components in PS2 circuits and 217

includes a requirement from IEC 60950-1 to address all combustible 218

materials that are found within the fire enclosure; 219

b) use fire-containing enclosures – Product enclosures will have a 220

design capable of preventing the spread of fire from PS 3 circuits. The 221

criteria for fire enclosures is based on the available power. 222

Rationale: PS3 sourced circuits may contain a significant amount of energy. During 223

single fault conditions, the available power may overwhelm the 224

safeguard of material control of fuels adjacent to the fault or any 225

consequential ignition source making a fire enclosure necessary as part of 226

the supplementary safeguard. A fire enclosure and the material controls 227

constitute the necessary supplementary safeguard required for a PS3 228

circuit. 229

Use adequate materials, typically permitting material pre -selection of non-230

combustible or flame-resistant materials for printed wiring and 231

components in or near PS3. Only fuels that would contribute significant fuel 232

to a fire are considered. This implies compliance with all the requirements 233

for PS2 circuits and in addition, application of a fire containing enclosure. 234

Material flammability requirements for all materials inside a fire enclosure 235

are included in this clause. This model has been used historically in 236

IEC 60950-1 to control the amount and type of fuel that may become 237

engaged in a significant fire. Because there is no single fault tes ting when 238

applying this method, a significant ignition source may engage other fuels 239

located inside the fire enclosure. PS3 circuits, particularly higher power 240

PS3 circuits can create significant internal fires if adjacent combustible 241

materials, not directly associated with a circuit, become involved in an 242

internal fire. These fires, if unmitigated , can overwhelm the fire 243

enclosures permitted in this document. Control of material flammability of 244

fuels located within the enclosure should be sufficient based on historical 245

experience with IEC 60950-1. 246

The exceptions provided in this clause for small parts, consumable 247

material, etc. that are inside of a fire enclosure, mechanical components 248

that cannot have flame retardant properties are exempt from the materia l 249

flammability requirements. This is the current practice in IEC 60950-1. 250

Components filling openings in a fire enclosure that are also V-1 are 251

considered adequate, as it is impractical to further enclose these devices. 252

These constructions are commonly used today in IT and CE products. 253

Page 94: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:20xx © IEC 2019 – 95 –

Wiring already has requirements in a separate part of this clause. 254

Motors and transformers have their own flammability spread requirements 255

and as such do not need a separate enclosure (see G.5.3 and G.5.4). 256

6.4.7 Separation of combustible materials from a PIS 257

Rationale: Where potential ignition sources are identified through classification and 258

single fault conditions , separation from the ignition source by distance 259

(material controls) or separation by barriers are used to li mit the spread of 260

fire from the ignition source and are necessary to ensure the ignition is not 261

sustained. 262

6.4.7.2 Separation by distance 263

Source: IEC 60065 264

Rationale: The safeguard for materials within the fire cone includes material size 265

control (and including prohibition on co-location of flammable parts). 266

Otherwise the parts close to the PIS shall be material flammability class 267

V-1, which limits sustained ignition and spread. 268

Small parts (less than 4 g) are considered too small to significantly 269

propagate a fire. This value is also used for components used in PS2 and 270

PS3 circuits. It has been used in IEC 60065 with good experience. 271

Where these distances are not maintained, a needle flame test option is 272

included with 60 s needle flame application based on previous 273

requirements in IEC 60065. This alternative to these distance requirements 274

(the needle flame test) can be performed on the barrier to ensure that any 275

additional holes resulting from the test flame are still compliant (openings 276

that will limit the spread of fire through the barrier). 277

Redundant connections: An arcing PIS cannot exist where there are 278

redundant or reliable connections as these connections are considered not 279

to break or separate (thereby resulting in an arc). 280

Redundant connections are any kind of two or more connections in parallel, 281

where in the event of the failure of one connection, the remaining 282

connections are still capable of handling the full power. Arcing is not 283

considered to exist where the connections are redundant or otherwise 284

deemed not likely to change contact resistance over time or through use. 285

Some examples are given, but proof of reliable connections is left to the 286

manufacturer and there is no specific criteria that can be given: 287

– Tubular rivets or eyelets that are addit ionally soldered – this assumes 288

that the riveting maintains adequate contact resistance and the 289

soldering is done to create a separate conductive path. 290

– Flexible terminals, such as flexible wiring or crimped device leads that 291

remove mechanical stress (due to heating or use) from the solder joint 292

between the lead and the printed wiring trace. 293

– Machine or tool made crimp or wire wrap connections – well-formed 294

mechanical crimps or wraps are not considered to loosen. 295

– Printed boards soldered by auto-soldering machines and the auto-296

soldering machines have two solder baths , but they are not considered 297

reliable without further evaluation. This means most printed boards 298

have been subjected to a resoldering process. But there was no good 299

connection of the lead of the component(s) and the trace of the printed 300

board in some cases. In such cases, resoldering done by a worker by 301

hand may be accepted. 302

Page 95: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 96 – IEC TR 62368-2:20xx © IEC 2019

Combustible materials, other than V-1 printed wiring boards are to be 303

separated from each PIS by a distance based on the size of resulting 304

ignition of the PIS. The flame cone dimensions 50 mm and 13 mm 305

dimensions were derived from IEC 60065, where they have been used for 306

several years with good experience. The area inside the cone is 307

considered the area in which an open flame can exist and where material 308

controls should be applied. 309

Resistive potential ignition sources are never a point object as presented 310

in Figure 37 of IEC 62368-1. They are more generally three-dimensional 311

components, however only one dimension and two-dimension drawings are 312

provided. The three-dimensional drawing is difficult to understand and 313

difficult to make accurate. 314

Figure 34 in this document shows how to cope with potential ignition 315

sources that are 3D volumes. This drawing does not include the bottom 316

part of the fire cone. The same approach should be used for the bottom 317

side of the part. 318

Figure 34 – Fire cone application to a large component

The fire cone is placed at each corner. The locus of the outside lines 319

connecting each fire cone at both the top and the base defines the 320

restricted volume. 321

Figure 37 Minimum separation requirements from a PIS 322

This drawing of a flame cone and its dimensions represents the one-323

dimension point ignition source drawn in two dimensions. The three-324

dimension envelope (inverted ice cream cone) of a flame from a potential 325

ignition source. This PIS is represented as a point source in the drawing 326

for clarity, however these PISs are more often three-dimensional 327

components that include conductors and the device packaging. 328

Figure 38 Extended separation requirements from a PIS 329

A two-dimensional representation of an ignition source intended to provide 330

more clarity. 331

6.4.7.3 Separation by a fire barrier 332

Source: IEC 60065 333

Page 96: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:20xx © IEC 2019 – 97 –

Rationale: The use of flame retardant printed wiring is considered necessary as the 334

fuel and the electrical energy source are always in direct contact. V -1 has 335

historically been adequate for this purpose. 336

Printed wiring boards generally di rectly support arcing PIS and as such, 337

cannot be used as a barrier. There is a potential that small openings or 338

holes may develop, thus permitting the arc to cross through the board. 339

A printed board can act as a barrier for an arcing PIS, provided the PIS is 340

not directly mounted on the board acting as a barrier. 341

For resistive PIS, printed wiring boards can be used provided they are of 342

V-1 or meet the test of Clause S.1. Any V-1 and less-flammable fuels are 343

required to minimize the possibility flammable mate rial falling onto the 344

supporting surface or contact with combustible fuels (resulting in pool 345

fires). If a PIS is located on a board and supplied by a PS2 or PS3 source, 346

there should be no other PS2 or PS3 circuits near the PIS, as this could 347

create faults due to PIS heating that was not otherwise considered. 348

Figure 39 Deflected separation requirements from a PIS when a fire barrier is used 349

This figure demonstrates the change on the fire cone when there is a fire 350

barrier used to separate combustible material from a potential ignition 351

source. This drawing was retained as an example application for only two 352

angles. Recognizing that many examples are possible, only two are kept 353

for practical reasons. History with multiple drawings of barriers in varying 354

angles could be difficult to resolve. The fire team decided to keep only two 355

drawings with an angle barrier as representative. 356

6.4.8 Fire enclosures and fire barriers 357

Rationale: The safeguard function of the fire enclosure and the fire barrier is to 358

impede the spread of fire through the enclosure or barrier (see Table 13 359

in this document). 360

Page 97: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 98 – IEC TR 62368-2:20xx © IEC 2019

Table 13 – Fire barrier and fire enclosure flammability requirements 361

Flammability requirements

Fire barrier

6.4.8.2.1

Fire barrier requirements

Non-combustible material or

Needle flame test Clause S.1 or V-1 class material or VTM-1 class material

6.4.8.4

Separation of a PIS to a fire barrier

– Distance 13 mm to an arcing PIS and

– Distance 5 mm to a resistive PIS

Smaller distances are allowed provided that the part of the fire barrier complies with one of the following :

– Needle flame Clause S.2; After the test no holes bigger than in 6.4.8. 3.3 and 6.4.8.3.4 allowed or

– V-0 class material

Fire enclosure

6.4.8.2.2

Fire enclosure materials:

– Non-combustible, or

– For PS3 ≤ 4 000 W, needle flame test Clause S.1 or V-1 class material

– For PS3 > 4 000 W, needle flame test Clause S.5 or 5VB class material

Component materials which fill an opening in a fire enclosure or intended to be mounted in such opening

– Comply with flammability requirements of relevant IEC component document; or

– V-1 class material ; or

– needle flame test Clause S.1

6.4.8.4

Separation of a PIS to a fire enclosure

– Distance 13 mm to an arcing PIS and

– Distance 5 mm to a resistive PIS

Smaller distances are allowed , provided that the part of the fire enclosure complies with one of the following :

– Needle flame Clause S.2; After the test no holes bigger than in 6.4.8. 3.3 and 6.4.8.3.4 allowed; or

– V-0 class material

362

6.4.8.2.1 Requirements for a fire barrier 363

Source: IEC 60065, IEC 60950-1 364

Rationale: Barriers used to separate PIS from flammable fuels reduce the abilit y of a 365

resulting PIS flame from impinging on flammable materials. This can be 366

achieved by using flame retardant materials that pass the performance test 367

in Clause S.1 or the pre-selection criteria of a minimum V-1 flame class. 368

The test in Clause S.1 is based on the needle flame test which is currently 369

an option for enclosure testing in both IEC 60950-1 and IEC 60065. 370

6.4.8.2.2 Requirements for a fire enclosure 371

Source: IEC 60065, IEC 60950-1 372

Rationale: The material flammability class V-1 was chosen as the minimum value 373

based on its historical adequacy, and recent testing done during the 374

development of the requirements for externally caused fire. 375

IEC 60950-1 – Prior requirements for 5 V class materials based on 376

product weight lacked sufficient rationale . This has been improved and 377

related to power available to a fault in this document. 378

Page 98: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:20xx © IEC 2019 – 99 –

IEC 60065 – V-2 class material performance during large scale test 379

reviewed by the fire team indicated inconsistencies in performance over a 380

range of different V-2 materials. The propensity for V-2 class materials to 381

create ‘pool’ fires is also detrimental to fire enclosure performance and 382

therefore not accepted unless it passes the end-product testing. 383

In addition to pre-selection requirements, an end-product test (material 384

test) is also included by reference to Clauses S.1 (for < 4 000 W) and S.5 385

(for 4 000 W). This test is based on the needle flame test which is 386

currently an option for enclosure testing in both IEC 60950-1 and 387

IEC 60065. 388

This power (4 000 W) separation is also used in the control of fire spread 389

method to delineate safeguard criteria for fire enclosure materials (V-1 390

versus 5 V). IEC 60950-1 has historically used weight to define fire 391

enclosure criteria and it was felt the use of available power was more 392

appropriate and generally reflective of current practice. 393

Both 5 VA and 5 VB class materials are considered acceptable for 394

equipment with power above 4 000 W. This is consistent with current 395

practice in IEC 60950-1. 396

6.4.8.2.3 Compliance criteria 397

Rationale: In each case there is a performance test, and construction (pre -selection) 398

criteria given. For material flammability, compliance of the material is 399

checked at the minimum thickness used as a fire enclosure or fire barrier. 400

6.4.8.3 Constructional requirements for a fire enclosure and a fire barrier 401

Rationale: Opening requirements for barriers and fire enclosure should limit the 402

spread of flame through any existing opening. A fire enclosure limits the 403

spread of fire beyond the equipment and is permitted to have holes (within 404

established limits). 405

6.4.8.3.1 Fire enclosure and fire barrier openings 406

Rationale: These requirements are intended to reduce the spread of an internal fuel 407

ignition through a fire enclosure or barrier. 408

Openings are restricted based on the location of each potential ignition 409

source using the flame cones or in the case of control fire spread, above 410

all PS3 circuits. 411

Figure 40 Determination of top, bottom and side openings 412

In the left figure, when the vertical surface has an inclination (angle) of less 413

than 5° from vertical, then only the side opening requirements of 6.4.8.3.5 414

apply. 415

In the right figure, when the vertical surface has an inclination (angle) of 416

more than 5° from the vertical, then the openings are subject to the 417

requirements for top openings of 6.4.8.3.3 or bottom openings of 6.4.8.3.4. 418

6.4.8.3.2 Fire barrier dimensions 419

Rationale: Edges can be more easily ignited than a solid surface. Barrier dimensions 420

shall also be sufficient to prevent ignition of the barrier edges. 421

Barriers made of non-combustible materials shall have edges that extend 422

beyond the limits of the fire cone associated with each potential ignition 423

source. If the barrier edge does not extend beyond the cone, then it is 424

assumed the edges may ignite. 425

Met opmerkingen [JR5]: See Raleigh minutes item 9.5.8

Page 99: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 100 – IEC TR 62368-2:20xx © IEC 2019

6.4.8.3.3 Top openings and top opening properties 426

Source: IEC 60065 427

Rationale: Top opening drawings are restricted in the areas of likely flame 428

propagation to the side and above an ignition source. 429

Top openings are also considered to cover what has historically been 430

called side opening where the opening is above the horizontal plane 431

containing the ignition source. 432

The top/side openings that are subject to controls are only those within the 433

fire cone drawing (Figure 37) plus a tolerance of 2 mm, as shown in Figure 434

41. The application of the fire cone dimensions has been used in 435

IEC 60065 and proven historically adequate. 436

Control of openings above the flame cone is also not necessary given that 437

the heat transfer (convection) will follow the gases moving through those 438

openings and is not sufficient to ignite adjacent materials. If the openings 439

are directly blocked, the convection path will be blocked which would 440

restrict any heat transfer to an object blocking the opening. 441

Openings to the side of the fire cone dimensions were reviewed and 442

ultimately not considered necessary as the radiant heat pr opagation 443

through openings to the side of the ignition is very small. This radiant heat 444

is not considered sufficient to ignite adjacent materials given the 445

anticipated flame size and duration in AV and ICT products. 446

In this aspect, the virtual flame cone deflection as per Figure 39 need not 447

be considered since the actual needle flame application will cover that. 448

The test method option proposed provides a test option for direct 449

application of a needle flame. The test (S. 2) referred to in this clause is 450

intended to provide a test option where holes do not comply with the 451

prescriptive measures. S.2 is originally intended to test the material 452

flammability, but in this subclause the purpose of the test is to see the 453

potential ignition of outer material covering the openings, so application of 454

the needle flame is considered for that aspect rather than the burning 455

property of the enclosure itself. 456

Cheesecloth is used as a target material for the evaluation of flame spread 457

due to its flexible nature (ease of use) and its quick propensity to ignite. 458

The flame cone envelope is provided as a single point source. The 459

applicable shape and any affecting airflow are taken into account for 460

determining the whole shape of the PIS, not just a single point. The point is 461

applied from the top edge of the component being considered and , in 462

practice, it is rarely a single point. 463

The opening dimensions for the 5 mm and 1 mm dimensions have been 464

determined through test as being restrictive enough to cool combustible 465

gases as they pass through the openings and those mitigate any flame 466

from passing through the opening. Top openings properties are based on 467

tests conducted by the fire team with open flames (alcohol in a Petri dish) 468

that demonstrated these opening dimensions are adequate . 469

6.4.8.3.4 Bottom openings and bottom opening properties 470

Source: IEC 60065, IEC 60950-1 471

Rationale: The location of openings is restricted for barriers inside the flame cone of 472

Figure 37 and for enclosures, inside the cone and directly below to protect 473

against flammable drips from burning thermoplastic as shown in Figure 42. 474

The application of the fire cone dimensions has been used in IEC 60065 475

and proven historically adequate. 476

Page 100: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:20xx © IEC 2019 – 101 –

There are several options for opening compliance (see Table 14 in this 477

document). Flaming oils and varnishes are not common in ICT equipment 478

today. The performance test based on the hot flaming oil test, in use for 479

IEC 60950-1, have other opening options and are developed based on 480

lower viscosity materials (when burning). They are more commonly found 481

in ICT (that provide additional options ). 482

Clause S.3 (hot flaming oil test) is the base performance option and 483

provides a test option (hot flaming oil test) that historically has been 484

adequate for tests of bottom openings. 485

The values in items band c) come directly from IEC 60950-1 where they 486

have been historically adequate and have demonstrated compliance with 487

the S.3 performance testing. These requirements, previously from 488

IEC 60950-1, 4.6.2 Bottoms of fire enclosures, have been updated in the 489

third edition of IEC 62368-1. The IEC 60950-1 requirements are more 490

stringent than the new IEC 62368-1 requirements and may still be used as 491

an option without additional tests, which is likely since designs based on 492

the IEC 60950-1 requirements have been in use for some time. 493

The work done to validate top openings was also considered adequate for 494

bottom openings under materials of any properties (3 mm and 1 mm slots). 495

This requirement is less onerous than those found in IEC 60950-1 which 496

permitted NO openings unless they complied with the other options. 497

Openings under V-1 class materials (or those that comply with Clause 498

S.1) are controlled in the same manner as done in IEC 60950-1 which was 499

considered adequate however an additional option to use 2 mm slots of 500

unlimited length is also considered adequate. 501

The 6 mm maximum dimension relates to a maximum square opening 502

dimension of 36 mm2 and a round opening of 29 mm2. In IEC 60950-1 the 503

requirement was 40 mm2, which relates to a maximum 7 mm diameter if 504

round or 6,3 mm maximum if not round. 505

The only option where flammable liquids are used is to meet the 506

requirements of the hot flaming oil test ( Clause S.3). 507

An option for equipment that is installed in spe cial environments where a 508

non-combustible flooring is used (environmental safeguard) may obviate 509

the need for an equipment bottom safeguard. This is current practice in 510

IEC 60950-1 where equipment is used in “restricted access locations”. 511

Baffle plate constructions were added, as they have been used in 512

IEC 60950-1 and have proven to be an acceptable solution. 513

Page 101: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 102 – IEC TR 62368-2:20xx © IEC 2019

Table 14 – Summary – Fire enclosure and fire barrier material requirements 514

Parameters Fire barrier Fire enclosure

Input < 4 000 W Input 4 000 W

Co

mb

us

tib

le m

ate

ria

l:

Separation from PIS

13 mm or more from arcing PIS

5 mm or more from resistive PIS

Note: exceptions may apply

Dimensions Sufficient to prevent ignition of the edges

Not applicable

Flammability

a) Test S.1; or

b) V-1; or

c) VTM-1

a) Test S.1; or

b) V-1

a) Test S.5; or

b) 5 VA; or

c) 5 VB

No

n-

Co

mb

us

tib

le

ma

teri

al:

Acceptable

Top openings See 6.4.8.3.3

Bottom openings See 6.4.8.3.4

515

6.4.8.3.5 Side opening and side opening properties 516

Source: IEC 60950-1 517

Rationale: For Edition 3, IEC TC 108/WG HBSDT agreed to adopt from 518

IEC 60950-1:2005 (4.6.1, 4.6.2 and Figure 4E) the principles and criteria 519

for determination of suitable side openings using a five (5) degree 520

projection. The primary rationale for a dopting these principles was the 521

demonstration of many years of a solid safety record of use for ITE with 522

IEC 60950-1. However, one issue that had to be resolved was that in 523

IEC 60950-1 the 5-degree projection of Figure 4E was always made from 524

the outer surface of a combustible internal component or assembly rather 525

than a defined potential ignition source (PIS), typically a metallic circuit 526

inside the component. The PIS principle was not inherent to IEC 60950-1. 527

For example, in a component or assembly, el ectrical or not, made of 528

combustible material that might ignite within a f ire enclosure, the 5-degree 529

projection was made from the surface of the component or assembly 530

closest to the side enclosure and not from a metallic circuit inside the 531

component or subassembly that could be a potential source of ignition. 532

Therefore, for example, if a printed board was considered the 533

component/subassembly likely to ignite, the 5-degree projection was made 534

from the edge of the printed board and not the current carrying t race, which 535

in IEC 62368-1 is the PIS. In some cases throughout the history of 536

IEC 60950-1, this distance from the metallic trace to component edge could 537

have been up to several centimetres. 538

Page 102: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:20xx © IEC 2019 – 103 –

However, when IEC TC 108/WG HBSDT considered the common 539

construction of internal components and subassemblies likely to be 540

associated with a PIS, including printed boards, it was determined that it 541

was reasonable to assume that in modern AV/ICT equipment the distance 542

between the PIS and the outer edge of a component or sub-assembly was 543

likely to have negligible impact on the overall fire safety of the product, in 544

particular in the application of the 5 degree principle. Due to general 545

miniaturization of products, material cost optimization, and modern design 546

techniques (including CAD/CAM), printed boards and other electronic 547

components and assemblies associated with a PIS typically do not use 548

unnecessary amounts of combustible materials – modern printed boards 549

more typically now have metallic traces very close to the board edge rather 550

than many millimetres away. 551

As a result IEC TC 108/WG HBSDT considered that the IEC 60950-1 five 552

(5) degree projection principle for side openings remained sound even if 553

projected from the actual PIS rather than the edge of combustible mater ial 554

associated with the PIS. This view also is consistent with the Note to 555

Figure 38, Extended separation requirements from a PIS, which states, for 556

a resistive PIS “…measurements are made from the nearest power 557

dissipating element of the component involved. If in practice it is not readily 558

possible to define the power dissipating part, then the outer surface of the 559

component is used.” 560

6.4.8.3.6 Integrity of a fire enclosure 561

Source: IEC 60950-1 562

Rationale: The clause ensures that a fire enclosure where required, is assured to 563

remain in place and with the product through either an equipment or 564

behavioural safeguard. This requirement is a service condition safeguard 565

for ordinary persons to ensure that a fire enclosure (if required) is 566

replaced prior to placing the equipment back into use. This safeguard is 567

also required in IEC 60950-1. 568

6.4.8.3.7 Compliance criteria 569

Rationale: In each case, there is a performance test, and construction (pre -selection) 570

criteria given. 571

6.4.8.4 Separation of a PIS from a fire enclosure and a fire barrier 572

Source: IEC 60065, IEC 60950-1 573

Rationale: Non-metallic fire enclosures and fire barriers may not be sufficient to limit 574

the spread of fire where an enclosure is close or in direct contact with a 575

potential ignition source. 576

The 13 mm and 5 mm distances were used in IEC 60065 to prevent an 577

ignition source from transferring sufficient energy to adjacent flame-578

retardant V-1 barriers. These distances are intended to reduce the 579

likelihood of melting or burn-through of the barrier of fire enclosure. 580

Where these distances are not maintained, a needle flame test option is 581

included with 60 s needle flame application based on work in IEC 60065. 582

Openings following the needle flame test were discussed with criteria 583

being: 584

a) no additional opening, 585

b) no enlargement of existing holes, 586

c) compliance with the fire enclosure opening requirements. 587

Due to test repeatability, the criteria of a) are considered most readily 588

reproduced. 589

Page 103: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 104 – IEC TR 62368-2:20xx © IEC 2019

The option to use V-0 or 5 V class materials without distance or thickness 590

requirements is based on historical practices in IEC 60065 and 591

IEC 60950-1 where no distance requirements were applied. 592

The material thickness requirements where ignition sources are in close 593

proximity to a barrier were not included based on dis cussions in 594

IEC TC 108 and current practice for IEC 60950-1 enclosures. There is fire 595

test data (barrier testing from IEC 60065) indicating that 2 mm thick (or 596

greater) V-0 barriers and 5 VA barriers have sufficient flame resistance to 597

minimize a risk of creating openings when used in direct contact with PIS’s. 598

Good HWI or HAI tests are not available internationally to address the 599

distance from ignition sources to fire enclosure and barriers. The fire team 600

has chosen to use the needle flame test as a surrog ate test (similar to that 601

done for barriers). 602

6.5.1 General requirements 603

Source: IEC 60332-1-2, IEC 60332-2-2 604

Rationale: Wiring flammability proposals have now been included for all wiring 605

(external and internal). 606

Compliance with IEC 60332-1-2 for large wires and IEC 60332-2-2 for 607

small wires has historically proven adequate for mains wiring. These 608

documents include their own material flammability requirements. 609

The requirements of IEC TS 60695-11-21 are also considered adequate 610

given that the flame spread requirements for vertical testing are more 611

onerous than the IEC 60332 series of documents. 612

The compliance criteria are based on application of the above test 613

methods. These are consistent with international wiring standards. National 614

standards may have more onerous requirements. 615

6.5.2 Requirements for interconnection to building wiring 616

Source: IEC 60950-1:2005 617

Rationale: Externally interconnected circuits that are intended for connection to 618

unprotected building wiring equipment can receive sufficient pow er from 619

the product to cause ignition and spread of fire with the building wall, 620

ceiling, or remotely interconnected equipment. These requirements limit the 621

power available to connectors/circuits intended for interconnection to 622

specific types of wiring where the product is responsible for protection of 623

that wiring. 624

Where a circuit is intended for connection to equipment that is directl y 625

adjacent to the equipment, 6.6 prescribes the appropriate safeguards and 626

limits associated for PS2 and PS3 sources. 627

Telecommunication wiring is designed based on the expected power from 628

the network. The requirements of IEC 60950-1 were considered adequate 629

and were included. Wiring in this application should be equivalent to 0,4 630

mm diameter wiring (26 AWG) and have a default 1,3 A current limit 631

established. This value has been used in IEC 60950-1 for the smaller 632

telecommunication wiring. 633

For some building wiring, the PS2 and PS3 safeguards are not considered 634

adequate in some countries for connection to building wiring where tha t 635

wiring is run outside of the conduit or other fire protective enclosures. The 636

requirements for this clause come directly from requirements in IEC 60950-637

1, 2.5 for circuits identified as limited power circuits. These requirements 638

have proven to be historically adequate for connection of IT equipment to 639

building wiring in these jurisdictions. 640

The values used and protection requirements included in IEC 60950-1 and 641

included in Annex Q.1 came from the building and fire codes requiring this 642

protection. 643

Page 104: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:20xx © IEC 2019 – 105 –

These requirements do not apply to connectors/circuits intended for 644

interconnection of peripheral equipment used adjacent to the equipment. 645

This requirement is also important for the use of ICT equipment in 646

environments subject to electrical codes such as Natio nal Fire Protection 647

Association NFPA 70, which permit the routing of low power wiring outside 648

of a fire containment device. 649

Annex Q.1 was based on requirements from IEC 60950-1 that are designed 650

to comply with the external circuit power source requirements necessary 651

for compliance with the electrical codes noted above. 652

6.6 Safeguards against fire due to the connection of additional equipment 653

Source: IEC 60950-1 654

Rationale: This subclause addresses potential fire hazards due to the connection of 655

accessories or other additional equipment to unknown power source 656

classifications. Most common low-voltage peripherals are not evaluated for 657

connection to PS3 and therefore power sources should be identified. This 658

is a current requirement of IEC 60950-1. 659

Where the interconnected devices are known (device requirements are 660

matched to the appropriate power source), this requirement for safeguard 661

is not necessary. 662

___________ 663

7 Injury caused by hazardous substances 664

Rationale: The majority of chemical injuries arise from inhalation or ingestion of 665

chemical agents in the form of vapours, gases, dusts, fumes and mists, or 666

by skin contact with these agents (see Table 15 in this document). The 667

degree of risk of handling a given substance depends on the magnitude 668

and duration of exposure. These injuries may be either acute or chronic. 669

Many resins and polymers are relatively inert and non -toxic under normal 670

conditions of use, but when heated or machined, they may decompose to 671

produce toxic by-products. 672

Toxicity is the capacity of a material to produce injury or harm when the 673

chemical has reached a sufficient concentration at a certain site in the 674

body. 675

Potentially hazardous chemicals in the equipment are either: 676

– as received in consumable material or items, such as printer 677

cartridges, toners, paper, cleaning fluids, batteries; 678

– produced under normal operating conditions as a by-product of the 679

normal function of the device (for example, dust from paper handling 680

systems, ozone from printing and photocopying operations, and 681

condensate from air conditioning/de-humidifier systems); or 682

– produced under abnormal operating conditions or as a result of a 683

fault. 684

It is essential to: 685

– determine what substances are present in relative amounts in t he 686

equipment or could be generated under normal operating conditions ; 687

and 688

– minimize the likelihood of injury to a person due to interaction with 689

these substances. 690

NOTE In addition to their potential toxicity, loss of containment of chemical materials may 691 cause or contribute to failure of safeguards against fire, electric shock, or personal injury 692 due to spillages. 693

Page 105: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 106 – IEC TR 62368-2:20xx © IEC 2019

The number of different chemical materials that may be used in the wide 694

variety of equipment covered by this document makes it impossible to 695

identify specific hazards within the body of this document. Information 696

needs to be sought by equipment manufacturers from the material 697

suppliers on the hazards associated with their products and their 698

compliance with any national and/or governmental regulati ons on the use 699

and disposal of such materials. 700

Energy source: 701

The energy source for most chemically -caused injuries is ultimately the 702

ability of a material to chemically react with human tissue, either directly or 703

indirectly. The exception would be inert m aterials that can damage tissues 704

by preventing them from functioning by limiting certain chemical reactions 705

necessary for life. An example of this would be types of dust, which do not 706

react with lung tissue, but prevent air from reaching the bloodstream. T he 707

reactions may be very energetic and damaging, such as acids on the skin, 708

or can be very slow, such as the gradual build -up of substances in human 709

tissues. 710

Transfer mechanism: 711

Transfer can only occur when chemical energy makes contact with human 712

tissue. The routes for contact with human tissue are through the skin [or 713

any outer membrane such as the eyes or nasal lining] (absorption), through 714

the digestive tract (digestion), or through the lungs (inhalation). The route 715

taken will depend largely on the phys ical form of the chemical: solid, liquid, 716

or gas. 717

Injury: 718

An injury can be either acute or chronic. Acute injuries are injuries with 719

immediate and serious consequences (for example, a strong acid in the 720

lungs) or the injury can be mild and result in irrita tion or headache. Chronic 721

injuries are injuries with long term consequences and can be as serious as 722

acute injuries (for example, consequences of long-term exposure to 723

cleaning solvents). 724

In most cases, the difference is the quantity and lethality of the t oxic 725

substance. A large amount of acetone can lead to death; a small amount 726

may simply result in a headache. Many chemical compounds essential to 727

life in small quantities (for example, zinc, potassium and nickel) can be 728

lethal in larger amounts. The human body has different degrees of 729

tolerance for different hazardous chemical substances. Exposure limits 730

may be controlled by government bodies for many chemical substances. 731

Where the use of hazardous chemical substances in equipment cannot be 732

avoided, safeguards shall be provided to reduce the likelihood of 733

exceeding the exposure limits. 734

The different types of chemical hazards are identified in Table 15 and 735

Figure 35 in this document demonstrating the hierarchy of hazard 736

management. 737

Page 106: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:20xx © IEC 2019 – 107 –

Table 15 – Control of chemical hazards 738

Transfer mechanism Prevention / safeguards

Ingestion, inhalation, skin contact, or other exposure to potentially hazardous chemicals

Hierarchy of hazard management:

1. Eliminate the chemical hazard by avoiding the use of the chemical.

2. Reduce the chemical hazard by substitution of a less hazardous chemical.

3. Minimize the exposure potential of the chemical by containment, ventilation and/or reduced quantities of the chemicals.

4. Use of personal protective equipment (PPE).

5. Provide use information and instructional safeguards.

Exposure to excessive concentrations of ozone during equipment operation

Hierarchy of hazard management:

1. Where possible, minimize the use of functions that produce ozone.

2. Provide adequate room ventilation.

3. Provide filtration to remove ozone.

Explosion caused by chemical reaction during use

Hierarchy of hazard management:

1. Eliminate the explosive charge.

2. Reduce the amount of explosive charge to the least amount possible.

3. Minimize hazard by the means of vents.

4. Provide use information and instructional safeguards.

739

740

Page 107: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 108 – IEC TR 62368-2:20xx © IEC 2019

741

Figure 35 – Flowchart demonstrating the hierarchy of hazard management 742

743

Page 108: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:20xx © IEC 2019 – 109 –

Chemical hazards may also degrade or destroy the safeguards provided 744

for other hazards such as fire and electric shock (for example, ozone attack 745

on electrical insulation or corrosion of metallic parts). Chemical spillages or 746

loss of containment can also lead to other hazards such as electric shock 747

or fire depending on the location of any spillage and proximity to electric 748

circuits. The same methods used for chemical health exposure control 749

should also protect against such liquid spillages. 750

Using a hazard-based engineering approach, Figure 36 in this document 751

shows the main types of chemical health hazards and their transfer 752

mechanisms. 753

754

Figure 36 – Model for chemical injury 755

_____________ 756

8 Mechanically-caused injury 757

8.1 General 758

Rationale: Mechanically caused injury such as cuts, bruises, broken bones, etc., may 759

be due to relative motion between the body and accessible parts of the 760

equipment, or due to parts ejected from the equipment colliding with a 761

body part. 762

8.2 Mechanical energy source classifications 763

Purpose: To differentiate between mechanical energy source levels for normal 764

operating conditions, abnormal operating conditions and single fault 765

conditions applicable to each type of person. 766

8.2.1 General classification 767

Table 35 Classification for various categories of mechanical energy sources 768

Line 3 – Moving fan blades 769

Rationale: The acceptance criteria is based upon any number of factors such as 770

location, but the key factor for judging acceptance is based upon the K 771

factor, the relationship between mass (m) in kg, radius ( r) in mm and speed 772

(N) in rpm. This relationship can be used to find the K factor for the fan. 773

Fans with a low K factor and low speeds are considered safer. See 774

Figure 45 and Figure 46 for MS1 values. An MS2 fan requires an 775

instructional safeguard in addition to the limitation on the K factor value 776

and the speed of the fan. The need for the relevant safeguard is based on 777

the classification of fans. The K factor formula is taken from the UL 778

standard for fans, UL 507 (which is based on a University of Waterloo 779

study of fan motors). 780

Single fault condition on a fan includes, but is not limited to, 781

inappropriate input voltage due to the fault of a voltage regulator located 782

upstream. 783

Page 109: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 110 – IEC TR 62368-2:20xx © IEC 2019

As plastic fan blades are regarded less hazardous than metal fan blades, 784

different values are used to determine separation between energy class 2 785

and class 3. 786

Typical parameters for fans used in products covered by this document are 787

as follows: 788

fan mass (m) = about 25 g or 0,025 kg; 789

fan diameter (r) = 33 mm; 790

fan speed (N) = 6 000 rpm (maximum speed when the system is hottest, 791

slower if the system is cool) . 792

Line 4 – Loosening, exploding or imploding parts 793

Rationale: IEC TC 108 has tried to come up with specific requirements for solid 794

rotating media. However, the result became too com plex to be useful at 795

this time. 796

Line 5 – Equipment mass 797

Rationale: The values chosen align with some commonly used values today. However, 798

it is noticed that these are not completely r eflecting reality and not a very 799

good hazard-based approach. IEC TC 108 plans to work on these values in 800

the future. 801

Line 6 – Wall/ceiling or other structure mount 802

Rationale: The values chosen align with some commonly used values today. However, 803

it is noticed that these are not completely reflecting reality and not a very 804

good hazard-based approach. IEC TC 108 plans to work on these values in 805

the future. 806

Notes b and c 807

Rationale: The current values are based on experience and basic safety publications. 808

8.2.2 MS1 809

Rationale: Safe to touch. No safeguard necessary. 810

8.2.3 MS2 811

Rationale: Contact with this energy source may be painful, but no injury necessitating 812

professional medical assistance occurs, for example, a small cut, abrasion 813

or bruise that does not normally require professional medical attention. A 814

safeguard is required to protect an ordinary person. 815

8.2.4 MS3 816

Rationale: An injury may occur that is harmful, requiring professional medical 817

assistance. For example, a cut requiring stitches, a broken bone or 818

permanent eye damage. A double or reinforced safeguard is required to 819

protect an ordinary person and an instructed person. 820

8.3 Safeguards against mechanical energy sources 821

Purpose: To determine the number of safeguards needed between the type of 822

person and the relevant energy source classification. 823

Rationale: An instructional safeguard describing hazard avoidance may be 824

employed to circumvent the equipment safeguard permitting access to 825

MS2 part locations to perform an ordinary person service function. The 826

instructional safeguard indicates that the equipment safeguard be 827

restored after the service activity and before power is reconnected. When 828

an instructional safeguard is allowed, a warning is also required to 829

identify insidious hazards. 830

Page 110: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:20xx © IEC 2019 – 111 –

For an instructed person and a skilled person, an instructional 831

safeguard, in the form of a warning marking, is necessary to supplement 832

the instruction they have received to remind them of the location o f hazards 833

that are not obvious. 834

However, for a skilled person, an equipment safeguard is required in the 835

service area of large equipment with more than one level 3 energy sources, 836

where the skilled person can insert their entire head, arm, leg or complete 837

body. This safeguard is intended to protect the skilled person against 838

unintentional contact with any other level 3 energy source due to an 839

involuntary startle reaction to an event in the equipment while servicing 840

intended parts. 841

The involuntary reaction may occur for a number of reasons, such as an 842

unexpected loud noise, an arc flash or receipt of a shock, causing the 843

person to recoil away from the energy source or part being serviced. 844

Where more than one of the level 3 energy sources may require servicing 845

at some time, removable equipment safeguards shall be designed such 846

that any level 3 sources not being serviced can remain guarded. The 847

equipment safeguards for this purpose only need to protect against larger 848

body contact, since the potential involuntary recoil reaction will likely be full 849

limb or body and not small body parts. 850

8.4 Safeguards against parts with sharp edges and corners 851

Rationale: Engineering judgment shall be used to class a mechanical energy source 852

as MS1, MS2 or MS3 and an appropriate safeguard shall be provided. 853

Where a MS2 or MS3 cannot be fully guarded without interfering with the 854

intended function of the equipment, it shall be guarded as much as 855

practical. Such an energy source shall not be accessible to children and 856

be obvious to an adult. Instructional safeguards shall be provided to warn 857

the person about potential contact with the energy source and what steps 858

to take to avoid unintentional contact. 859

We rely on engineering judgment as there are too many variables involved 860

to define the type of edge or corner combined with the applied force and 861

direction of contact or to provide specific values. 862

8.5 Safeguards against moving parts 863

Rationale: Enclosures and barriers protect against access to hazardous moving 864

parts. See 8.5.1 for the exception of requirements related to parts not fully 865

guarded because of their function in the equipment. 866

8.5.1 Requirements 867

Rationale: The MS2 or MS3 energy sources need to be guarded against accidental 868

access by a person's extremities, jewellery that may be worn, hair and 869

clothing, etc. Access is determined by applying the appropriate tool from 870

Annex V, and no further testing is necessary. We note that while it may be 871

technically possible for some jewellery and hair to enter an opening smaller 872

than the test finger, in such cases, the jewellery strands would have to be 873

very thin and flexible enough to enter (as would a few strands of hair). As 874

such while some pain may result if they hap pen to be caught in the 875

mechanical device, it is deemed unlikely an injury would occur as 876

described by this document. The residual risk can be considered a MS2 877

energy source at most. 878

Page 111: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 112 – IEC TR 62368-2:20xx © IEC 2019

8.5.4.3 Equipment having an electromechanical device for destruction of media 879

Source: UL/CSA 60950-1 second edition [national difference] 880

Rationale: Recent large scale introduction of media shredders into the home 881

environment resulted in an increase of children being injured when 882

inserting their fingers through the shredder openings. These incidents were 883

studied and a new probe was developed to assess potential access by 884

children. The new probe/wedge has been desig ned for both application 885

with force when inserted into the shredder openings and assessment of 886

access to MS3 moving parts by a population consisting of both adults and 887

children. This design differs from the existing UL and IEC accessibility 888

probes since the UL Articulated Accessibility Probe is not intended to be 889

used with a force applied to it, and the current IEC probes, while having an 890

unjointed version for application under force, do not adequately represent 891

the population for both adults and children. 892

Because cross-cut shredders typically apply more force to the media than 893

straight-cut shredders, the requirements include differentiated application 894

forces for the two designs. The force values consider typical forces 895

associated with straight-cut and cross-cut designs, taking into account data 896

generated by the USA Consumer Product Safety Commission on typical 897

pull forces associated with both strip type and crosscut type shredders. 898

The dimensions of the new probe/wedge are based on the data generated 899

during the development of the UL Articulated Accessibility Probe. However, 900

the dimensions of the UL Articulated Accessibility Probe were defined in 901

consideration of causal handling of products. Because of this, the 95th 902

percentile points from the data were used to define the UL Articulated 903

Accessibility Probe. The thickness and length dimensions of the new 904

proposed probe/wedge have been developed in consideration of all data 905

points. Articulation points are identical to those for the UL Articulated 906

Accessibility Probe. 907

8.6 Stability of equipment 908

Source: IEC 60950-1 and IEC 60065 909

Purpose: To align existing practice with the MS1, MS2 and MS3 energy. 910

Rationale: Equipment weighing more than 25 kg is considered MS3. Regardless of 911

weight, equipment mounted to the wall o r ceiling is considered MS3 when it 912

is to be mounted above 2 m height. 913

Equipment weighing between 7 kg and not exceeding 25 kg is considered 914

MS2. Equipment with a weight of 1 kg or more and that is mounted to the 915

wall or ceiling to a maximum height of 2 m is also considered MS2. 916

Equipment with weight not exceeding 7 kg is considered MS1 if floor 917

standing, but can be either MS2 or MS3 if mounted to the wall or ceiling . 918

Also see carts and stands, and wall or ceiling mounted equipment . 919

Children are naturally attracted to moving images and may attempt to touch 920

or hold the image by pulling or climbing up on to the equipment. The tests 921

assess both the static stability and mounting grip when placed on a 922

slippery surface such as glass. Children might also misuse c ontrols that 923

are readily available to them. 924

8.6.2.2 Static stability test 925

Rationale: Equipment is assessed for stability during expected use by applying force 926

horizontally and downward on surfaces that could be used as a step or 927

have other objects placed upon it. 928

The value of 1,5 m was chosen as the maximum height where an average 929

person could lean on or against the product. 930

Page 112: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:20xx © IEC 2019 – 113 –

The 1,5 m is also used for table top equipment, since we do not know 931

whether the product is going to be placed on a table or, if so, what the 932

height of the table will be. 933

8.6.2.3 Downwards force test 934

Rationale: The height of 1 m represents the maximum height one could expect that 935

people could try to use as a step to reach something. 936

8.6.3 Relocation stability 937

Source: IEC 60950-1 and IEC 60065 938

Rationale: The 10° tilt test simulates potential horizontal forces applied to the 939

equipment either accidentally or when attempting to move the equipment. 940

In addition it simulates moving the equipment up a ramp during transport. 941

The test on the horizontal support may be necessary (for example, for 942

equipment provided with small feet, casters or the like). 943

8.6.4 Glass slide test 944

Source: IEC 60065:2011 945

Purpose: To address the hazard of equipment with moving images sliding off a 946

smooth surface when a child attempts to climb onto the equipment. 947

Rationale: To ensure the display does not slide too easily along a smooth surface that 948

could result in the display falling from an elevated height on to a child. 949

8.6.5 Horizontal force test and compliance criteria 950

Purpose: To simulate the force of a child climbing up on t o equipment with front 951

mounted user controls or with moving images. 952

Rationale: Field data and studies in the US have shown that children 2 -5 years of age 953

were attracted to the images on the display that may result in the child 954

climbing onto the display to touch/get close to the image. The equipment 955

could then tip over and crush the child. Also, products with accessible 956

controls or that are shorter than 1 m in height are considered likely to be 957

handled by children. 958

– Data was gathered in the 1986 to 1998 for CRT TV sets ranging from 959

48,26 cm to 68,58 cm (19 to 27 inches). The average horizontal force 960

was 13 % of the equipment weight. 961

– The 15° tilt test (an additional 5° over static stability test) provides an 962

additional safety factor. 963

8.7 Equipment mounted to a wall, ceiling or other structure 964

Source: IEC 60065 and 60950 series 965

Purpose: The objective of this subclause is to minimize the likelihood of injury 966

caused by equipment falling due to failure of the mounting means. 967

Rationale: Equipment intended to be mounted to a wall or ceiling should be tested to 968

ensure adequacy for all possible mounting options and all possible failure 969

modes. For typical equipment, such as flat panel televisions, mounting 970

bosses are usually integrated into the equipment and used with an 971

appropriate wall or ceiling mounting bracket to attach to a wall or ceiling. 972

Typical mounting bosses are comprised of threaded inserts into the rear 973

panel of the equipment. 974

The appropriate load is divided by the number of mounting means ( for 975

example, mounting bosses) to determine the force applied to each 976

individual mounting means. 977

The horizontal force values of 50 N and 60 s have been successfully used 978

for products in the scope of these documents for many years. 979

Page 113: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 114 – IEC TR 62368-2:20xx © IEC 2019

8.7.2 Test methods 980

Figure 37 in this document gives a graphical view of the different tests 981

required by Test 2 and show the directions that the forces are applied . 982

983

Figure 37 – Direction of forces to be applied 984

Table 37 Torque to be applied to screws 985

Source: IEC 60065 986

Rationale: These torque values have been successfully used for products in the scope 987

of this document for many years. 988

8.8 Handle strength 989

Source: IEC 60065 and IEC 60950-1 990

Rationale: A handle is a part of the equipment that is specifically designed to carry the 991

equipment or subassembly around. A grip which is made for easy removal 992

or placement of a subassembly in an equipment is not considered to be a 993

handle. 994

The 75 mm width simulates the hand width. The safety factors take into 995

account the acceleration forces and additional stresses that could be 996

applied due to extra weight on top of the equipment when being lifted. The 997

safety factor is less at the higher weight ( MS3) because the equipment 998

would be lifted more slowly, reducing the acceleration force, and there is 999

less probability that extra weight would be added before lifting , as this 1000

would exceed the normal weight to be lifted by one person without 1001

assistance of a tool. Equipment classed as MS1 with more than one 1002

handle could be used to support additional objects when being carried and 1003

should be tested. 1004

8.8.2 Test method 1005

Rationale: There is no test for MS1 with only one handle. Having 2 handles facilitates 1006

transporting the equipment while carrying additional objects adding stress 1007

to the handles. 1008

8.9 Wheels or casters attachment requirements 1009

Purpose: To verify that wheels or casters are securely fixed to the equipment . 1010

Source: UL 1667 1011

Page 114: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:20xx © IEC 2019 – 115 –

Purpose: For wheel size, reduce the likelihood of the equipment on the cart or stand 1012

tipping while being moved from room to room where the wheels may 1013

encounter a variety of obstacles, such as: friction of different surfaces ( for 1014

example, transition from a hard surface over carpet edgi ng), cables, and 1015

doorway sills. 1016

Rationale: The 100 mm min wheel size was found to be adequate to enable rolling 1017

over these obstacles without abruptly stopping that could cause the cart or 1018

stand to tip, or the equipment located on the cart or stand to slide off. 1019

8.10 Carts, stands, and similar carriers 1020

Source: UL 60065 1021

Rationale: To avoid tipping, the 20 N test simulates cart wheels being unintentionally 1022

blocked during movement. 1023

8.10.1 General 1024

Source: IEC 60065 1025

Rationale: A wheel of at least 100 mm diameter can be expected to climb over usual 1026

obstacles such as electrical cords, door jambs , etc., and not be halted 1027

suddenly. 1028

8.10.2 Marking and instructions 1029

Rationale: Various means of marking may apply depending on the method of 1030

associating the equipment with a particular cart, stand of similar carrier. 1031

8.10.3 Cart, stand or carrier loading test and compliance criteria 1032

Source: IEC 60065 1033

Purpose: To verify that a cart or stand can withstand foreseeable overloading without 1034

creating a hazardous situation. 1035

Rationale: The 220 N force simulates the weight of a small child approximately 5 1036

years of age, who may attempt to climb onto the cart or stand. The 30 mm 1037

circular cylinder simulates a child’s foot. The 750 mm height is the 1038

approximate access height of the 5-year-old child. The additional 440 N 1039

force test simulates potential additional materials or equipment being 1040

placed on the cart or stand. The additional 100 N simulates overloading by 1041

the user. Testing has been limited to 1 min as experience has shown that 1042

the likelihood of a test failure will occur within that time. 1043

8.10.4 Cart, stand or carrier impact test 1044

Purpose: To verify that a cart or stand can withstand a foreseeable impact without 1045

creating a hazardous situation. 1046

Source: IEC 60065 and IEC 60950 series 1047

Rationale: The 7 joules simulate intentional and accidental contact with the equipment 1048

and come from the T.6 enclosure test. 1049

8.10.5 Mechanical stability 1050

Purpose: To verify that a cart or stand remains stable under specified loading. The 1051

equipment installed on the cart may come loose, but not fall off the cart. 1052

Rationale: The weight of the force test is reduced to 13 % should the equipment on 1053

the cart or stand move, as the equipment would then be considered 1054

separately from the cart or stand. When the equipment does not move 1055

during the force test, together they are considered a single u nit. 1056

8.10.6 Thermoplastic temperature stability 1057

Source: IEC 60065 and IEC 60950-1 1058

Page 115: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 116 – IEC TR 62368-2:20xx © IEC 2019

Rationale: Intended to prevent shrinkage, relaxation or warping of materials that could 1059

expose a hazard. 1060

8.11 Mounting means for slide-rail mounted equipment (SRME) 1061

8.11.1 General 1062

Source: UL/CSA 60950-1 second edition 1063

Rationale: The potential hazardous energy source is a product that contains 1064

significant mass, and which is mounted on slide-rails in a rack. A joint 1065

US/Canadian Adhoc researched and developed these requirements based 1066

on hazard-based assessment and tests. 1067

The center of gravity was chosen to apply the downward force because in 1068

general, when installing equipment in a rack, it is foreseeable that 1069

previously installed equipment of similar size/mass may be pulled out into 1070

the service position (fully extended) and used to set the new equipment on 1071

while positioning and installing the new slide/rails. In this scenario, it is not 1072

likely that the new equipment would be significantly off -centre from the 1073

installed equipment that it is being set on. 1074

Vertically mounted SRMEs are not addressed in this document. 1075

8.11.3 Mechanical strength test 1076

Purpose: To simulate temporary placement of another server on to p of an existing 1077

one during installation of the new one. So the test is the downward force. 1078

Rationale: 50 % of the equipment mass is derived from the mass of the equipment, 1079

and a 50 % tolerance allowed for manufacturing differences in the rails 1080

which effectively adds a safety buffer. 1081

The 330 N to 530 N additional force accounts for equipment that is about to 1082

be installed in a rack being placed or set on a previously installed piece of 1083

equipment where the previously installed equipment is being used as a 1084

temporary shelf or work space. It is estimated that 530 N is the maximum 1085

mass of equipment allowed to be safely lifted by two persons without the 1086

use of mechanical lifting devices. Equipment having a mass greater than 1087

530 N will have mechanical lifting devices and it is therefore unlikely that 1088

the equipment being installed will be set on any equipment previously 1089

installed in the rack. 1090

Taking the actual installation environment into consideration, an additional 1091

force is limited to maximum 800 N (average weight of an adult man) that is 1092

same value as the downward test force in 8.6.2.3. The 800 N value comes 1093

from IEC 60950-1:2005, 4.1 Stability. 1094

8.11.3.2 Lateral push foce test 1095

8.11.3.3 Integrity of slide rail end stops 1096

Source: UL/CSA 60950-1 second edition 1097

Purpose: To simulate maintenance on the server itself, by smaller applying forces 1098

equivalent to what is expected during subassembly and card replacement, 1099

etc. So this also tests the laterally stability of the slide rails. It is not 1100

necessary to retest the downward vertical force if it is already tested for 1101

8.11.3, but that should be common sense when preparing a test plan. 1102

The cycling of the slide rail after the tests ensures they have not been bent 1103

in a way that could easily fly apart after the service operatio n. 1104

Page 116: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:20xx © IEC 2019 – 117 –

Rationale: The 250 N force is considered a force likely to be encountered during 1105

servicing of the equipment, and normal operations around equipment. The 1106

force is partially derived from the existing IEC 60950-1:2005, 4.1, and 1107

partially from research into normally encountered module plug forces seen 1108

on various manufacturers’ equipment. The application of force at the most 1109

unfavourable position takes into account the servicing of a fully extended 1110

piece of equipment, leaning on or bumping into an extended pi ece of 1111

equipment and other reasonably foreseen circumstances which may be 1112

encountered. 1113

___________ 1114

9 Thermal burn injury 1115

9.1 General 1116

Source: ISO 13732-1:2006 and IEC Guide 117 1117

Rationale: A General 1118

A burn injury can occur when thermal energy is conducted to a body part to 1119

cause damage to the epidermis. Depending on the thermal mass of the 1120

object, duration of contact and exposure temperature, the body response 1121

can range from perception of warmth to a burn. 1122

The energy transfer mechanism for equipment typically covered by the 1123

document is via conduction of thermal energy through physical contact with 1124

a body part. 1125

The likelihood of thermal injury is a function of several thermal energy 1126

parameters including: 1127

– temperature difference between the part and the body; 1128

– the thermal conductivity (or thermal resistance) between the hot part 1129

and the body; 1130

– the mass of the hot part; 1131

– the specific heat of the part material; 1132

– the area of contact; 1133

– the duration of contact. 1134

B Model for a burn injury 1135

A skin burn injury occurs when thermal energy impinges on the skin and 1136

raises its temperature to a level that causes cell damage. The occurrence 1137

of a burn will depend on several parameters. The hazard based three block 1138

model applied to the occurrence of a burn (see Figure 38 in this document) 1139

takes account of not just the temperature of the source, but its total thermal 1140

energy, which will depend on its temperature (relative to the skin), as well 1141

as its overall heat capacity. The model also takes account of the energy 1142

transfer mechanism, which will depend on the thermal conductivity between 1143

the body and the thermal source as well as the area and duration of 1144

contact. The occurrence and severity of a burn will depend on the amount 1145

of thermal energy transferred. 1146

1147

Figure 38 – Model for a burn injury 1148

Page 117: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 118 – IEC TR 62368-2:20xx © IEC 2019

Normally, the energy transfer mechanism from the energy source to a body 1149

part is through direct contact with the body part and sufficient contact 1150

duration to allow transfer of thermal energy causing a burn. The higher the 1151

temperature of the thermal source and the more efficient the transfer 1152

mechanism, the shorter the contact time becomes before the occurrence of 1153

a burn. This is not a linear function and it is depend ent on the material, the 1154

temperature and the efficiency of the thermal transfer. The following 1155

examples demonstrate the impact of this non-linear relationship to short -1156

term/high temperature and longer term/lower temperature contact burns. 1157

Example 1: An accessible metal heat sink at a temperature of 60 °C may 1158

have sufficient energy to cause a burn after contact duration of about 5 s. 1159

At a temperature of 65 °C, a burn may occur after contact duration of just 1160

1,5 s (see IEC Guide 117:2017, Figure A.1). As the temperature of the 1161

metal surface increases, the contact time necessary to cause a burn 1162

decreases rapidly. 1163

Example 2: Consider a thermal source with low to moderate conductivity 1164

such as a plastic enclosure. At a temperature of 48 °C, it may take up to 1165

10 min for the transfer of sufficient thermal energy to cause a burn. At 1166

60 °C, a burn may occur after contact duration of just 1 min (see 1167

IEC Guide 117:2010, Table A.1). Although the temperature of the source 1168

has increased by just 25 %, the contact time necessary to cause a burn 1169

threshold has decreased by 90 %. 1170

In practice, the actual thermal energy and duration of exposure required to 1171

cause a burn will also depend on the area of contact and condition of the 1172

skin. For simplification of the model and based up on practice in the past, it 1173

is assumed that the contact area will be 10 % of the body and applied to 1174

healthy, adult skin. 1175

As a general rule, low temperature devices are likely to cause a heating or 1176

pain sensation before causing a significant burn to whi ch ordinary 1177

persons will normally respond (see ISO 13732-1:2009, Note of 5.7.3). 1178

Requirements for persons with impaired neurological systems are not 1179

considered in this document but may be considered in the future. 1180

NOTE 1 The impact of surface area contact is not being addressed in this paper at this 1181 time and is an opportunity for future work. Use and coverage of large contact areas as might 1182 occur in medical applications of heating pads covering more than 10 % of the body surface 1183 are outside the scope of thi s document, as this type of application is more appropriate to 1184 medical device publications. 1185

NOTE 2 The pressure of the contact between the thermal source and the body part can 1186 have an impact on the transfer of thermal energy. Studies have shown this effect to have 1187 appreciable impact at higher pressures. For typical pressures associated with casual 1188 contact up to a pressure of 20 N the effect has been shown to be negligible , and thus 1189 contact pressure is not considered in this document (Ref: ATSM C 1055, X1.2.3.4, ASTM C 1190 1057,7, Note 10). 1191

NOTE 3 Considerations for burns generated by infrared (IR), visible, ultra violet light 1192 radiation and RF radiation sources are outside the scope of Clause 9 dealing with thermal 1193 burn injury. 1194

C Types of burn injuries 1195

Burn injuries are commonly classed as first degree, second degree or third 1196

degree in order of increasing severity: 1197

First degree burn : the reaction to an exposure where the intensity or 1198

duration is insufficient to cause complete necrosis of the epidermis. The 1199

normal response to this level of exposure is dilation of the superficial blood 1200

vessels (reddening of the skin). No blistering occurs. (Reference: ASTM 1201

C1057) 1202

Page 118: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:20xx © IEC 2019 – 119 –

Second degree burn : the reaction to an exposure where the intensity and 1203

duration is sufficient to cause complete necrosis of the epidermis but no 1204

significant damage to the dermis. The normal response to this exposure is 1205

blistering of the epidermis. (Reference: ASTM C1057) 1206

Third degree burn : the reaction to an exposure where significant dermal 1207

necrosis occurs. Significant dermal necrosis with 75 % destruction of the 1208

dermis is a result of the burn. The normal response to this exposure is 1209

open sores that leave permanent scar tissue upon healing. 1210

(Reference: ASTM C1057) 1211

ISO 13732-1, 3.5 classifies burns as follows: 1212

Superficial partial thickness burn – In all but the most superficial burns, 1213

the epidermis is completely destroyed but the hair follicles and sebaceous 1214

glands as well as the sweat glands are spared. 1215

Deep partial thickness burn : a substantial part of the dermis and all 1216

sebaceous glands are destroyed and only the deeper parts of the hair 1217

follicles or the sweat glands survive. 1218

Whole thickness burn : when the full thickness of the skin has been 1219

destroyed and there are no surviving epithelial elements. 1220

Although there is some overlap between the classifications in ASTM C1057 1221

and those in IEC Guide 117, the individual classifications do not 1222

correspond exactly with each other. Further, it should be noted that the 1223

classifications of burns described here is not intended to correspond with 1224

the individual thermal source classifications (TS1, TS2, and TS3) describe d 1225

later in this document. 1226

D Model for safeguards against thermal burn injury 1227

To prevent thermally-caused injury, a safeguard is interposed between the 1228

body part and the energy source. More than one safeguard may be used 1229

to meet the requirements for thermal burn hazard protection. 1230

Figure 39 – Model for safeguards against thermal burn injury

To prevent thermally-caused injury, a safeguard is interposed between the 1231

body part and the energy source (see Figure 39 in this document). More 1232

than one safeguard may be used to meet the requirements for thermal 1233

burn hazard protection. 1234

Safeguards overview 1235

This section shows examples of the different types of safeguards that may 1236

be applied: 1237

a) Thermal hazard not present 1238

The first model, in Figure 40 in this document, presumes contact to a 1239

surface by an ordinary person where a thermal hazard is not present. In 1240

this case, no safeguard is required. 1241

Page 119: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 120 – IEC TR 62368-2:20xx © IEC 2019

1242

Figure 40 – Model for absence of a thermal hazard 1243

b) Thermal hazard is present with a physical safeguard in place 1244

The second model, see Figure 41 in this document, presumes some 1245

contact with a surface by an ordinary person. The thermal energy source 1246

is above the threshold limit value for burns (Table 38 of 1247

IEC 62368-1:2018), but there are safeguards interposed to reduce the rate 1248

of thermal energy transferred such that the surface temperature will not 1249

exceed the threshold limit values for the expected contact durations. 1250

Thermal insulation is an example of a physical safeguard. 1251

1252

Figure 41 – Model for presence of a thermal hazard 1253

with a physical safeguard in place 1254

c) Thermal hazard is present with a behavioural safeguard in place 1255

The third model, see Figure 42 in this document, presumes the possibility 1256

of some contact to the thermal source or part by an ordinary person. The 1257

temperature is above the threshold limit value but the exposure time is 1258

limited by the expected usage conditions or through instructions to the user 1259

to avoid or limit contact to a safe exposure time. The contact time and 1260

exposure will not exceed the threshold limit value. An additional safeguard 1261

may not be required. 1262

1263

Figure 42 – Model for presence of a thermal hazard 1264

with behavioural safeguard in place 1265

9.2 Thermal energy source classifications 1266

Rationale: Surfaces that may be touched are classified as thermal ene rgy sources 1267

TS1, TS2 or TS3 with TS1 representing the lowest energy level and TS3 1268

the highest. The classification of each surface will determine the type of 1269

safeguards required. 1270

Page 120: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:20xx © IEC 2019 – 121 –

The assessment of thermal burn hazards is complex and, as discussed in 1271

the model for a burn injury above, involves several factors. Important 1272

aspects include the overall heat capacity of the source, its temperature 1273

relative to the body, thermal conductivity of the contact and others. To 1274

present a simple model for assessment of a given surface, it is assumed 1275

that the overall heat capacity and the thermal conductivity will remain 1276

constant. 1277

Thus, thermal energy sources are classified in terms of the material of the 1278

surface, its relative temperature and duration of contact only. Usuall y, for a 1279

given material the temperature and duration of contact are likely to be the 1280

only significant variables when assessing the risk of a burn injury. 1281

9.2.1 TS1 1282

Rationale: The lowest thermal energy source is TS1. TS1 represents a level of 1283

thermal energy that generally will not cause a burn injury. 1284

9.2.2 TS2 1285

Rationale: A TS2 thermal energy source has sufficient energy to cause a burn injury in 1286

some circumstances. The occurrence of a burn from a TS2 source will 1287

largely depend on the duration of contact. Depending on the contact time, 1288

and contact area, contact material, and other factors, a TS2 source is not 1289

likely to cause an injury requiring professional medical attention. Table 38 1290

defines the upper limits for TS2 surfaces. 1291

A TS2 circuit is an example of a class 2 energy source where the basic 1292

safeguard may, in some cases, be replaced by an instructional 1293

safeguard. Details are given in Table 38, footnote e. 1294

9.2.3 TS3 1295

Rationale: A TS3 thermal energy source has sufficient energy to cause a burn injury 1296

immediately on contact with the surface. There is no table defining the 1297

limits for a TS3 surface because any surface that is in excess of TS2 limits 1298

is considered to be TS3. Within the specified contact time, as well as 1299

contact area, contact material and other factors, a TS3 source may cause 1300

an injury requiring professional medical attention. As TS3 surfaces require 1301

that maximum level of safeguard defined in the document. All surfaces 1302

may be treated as TS3 if not otherwise classified. 1303

Source: IEC Guide 117. 1304

Rationale: When doing the temperature measurements, an ambient temperature is 1305

used as described in 9.2.5 to measure the temperatures without taking into 1306

account the maximum ambient specified by the manufacturer. 1307

9.3 Touch temperature limits 1308

Table 38 Touch temperature limits for accessible parts 1309

Source: The limits in Table 38 are primarily derived from data in IEC Guide 117. 1310

Rationale: The temperature of the skin and the duration of raised temperature are the 1311

primary parameters in the occurrence of a skin bur n injury. In practice, it is 1312

difficult to measure the temperature of the skin accurately while it is in 1313

contact with a hot surface. Thus the limits in Table 38 do not represent skin 1314

temperatures. These limits do represent the surface temperatures that are 1315

known to cause a skin burn injury when contacted for greater than the 1316

specified time limit. 1317

The thermal energy source criterion takes account of the temperature of 1318

the source, its thermal capacity and conductivity as well as the likely 1319

duration and area of contact. As the thermal capacity and conductivity will 1320

normally remain constant for a given surface, the limits here are expressed 1321

in degrees C for typical material types and contact durations. 1322

Page 121: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 122 – IEC TR 62368-2:20xx © IEC 2019

Contact time duration > 8 h 1323

For devices worn on the body (in direct contact with the skin) in normal use 1324

(> 8 h), examples include portable, lightweight devices such watches, 1325

headsets, music players and sports monitoring equipment. Since the 1326

values in the table do not represent skin temperature as indicated above, 1327

measurements should not be done while wearing the devices . 1328

The value of 43 °C for all materials for a contact period of 8 h and longer 1329

assumes that only a minor part of the body (less than 10 % of the entire 1330

skin surface of the body) or a minor part of the head (less than 10 % of the 1331

skin surface of the head) touches the hot surface. If the touching area is 1332

not local or if the hot surface is touched by vital areas of the face ( for 1333

example, the airways), severe injuries may occur even if the surface 1334

temperature does not exceed 43 °C (see IEC Guide 117). 1335

NOTE Prolonged exposure to 43 °C may result in erythema (temporary redness of the skin 1336 causing dilation of the blood capillaries) which will typically go away within a few hours after 1337 removal of the heat source. For some users, this may be mis perceived as a burn. 1338

Contact time durations > 1 min 1339

For very long-term contact ( 10 min), the temperature below which a burn 1340

will not occur converges towards 43 °C for most materials (see 1341

IEC Guide 117:2010, Figure A.1). Studies carried out on portable IT 1342

Equipment have shown that for long term contact, a surface temperature 1343

will drop by between 5 °C and 12 °C when in contact with the body due to 1344

the cooling effect of the blood circulation. On this basis, and taking ac count 1345

of the probability that long-term contact will normally be insulated by 1346

clothing or some other form of insulation, the TS1 temperature limit for 1347

contact periods greater than 1 min in Table 39 are conservatively chosen 1348

as 48 °C for all materials. 1349

Examples of products with surfaces where expected continuous contact 1350

durations greater than 1 min include joysticks, mice, mobile telephones, 1351

and PDAs. Any handles, knobs or grips on the equipment that are likely, 1352

under normal usage, to be touched or held for greater than 1 min are also 1353

included. 1354

Contact time durations between 10 s and 1 min 1355

For surfaces that are touched for shorter contact durations (up to 1 min), 1356

the temperature below which a burn will not occur is influenced by the 1357

material type as well as other factors. Because the contact time is shorter, 1358

there is insufficient time for heat transfer to cause the cooling effect 1359

described above, so it is not considered in the limits. The TS1 temperature 1360

limits in Table 38 for contact durations up to 1 min are taken directly from 1361

IEC Guide 117:2010, Table A.1. 1362

Examples of surfaces with contact durations up to 1 min include handles or 1363

grips used primarily for moving or adjusting the equipment. Also tuning 1364

dials or other controls where contact for up to 1 min may be expected. 1365

Contact time durations up to 10 s 1366

Even shorter-term contact may occur for surfaces such as push 1367

button/switch, volume control; computer or telephone keys. In this case, 1368

the surfaces will not normally be touched for a duration greater than 10 s. 1369

The TS1 temperature limits in Table 38 for these surfaces are based on the 1370

burn threshold limits in IEC Guide 117 for contact durations of up to 10 s. 1371

Page 122: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:20xx © IEC 2019 – 123 –

For surfaces that are accessible but need not be touched to operate the 1372

equipment, contact duration of up to 1 s is assumed. For healthy adults, a 1373

minimum reaction time of 0,5 s can be assumed. For more general 1374

applications, the reaction time increases to 1 s IEC Guide 117, Table 2. 1375

The TS1 temperature limits in Table 38 for these surfaces are based on the 1376

burn threshold limits in Guide 117 for contact durations of 1 s 1377

(see IEC Guide 117:2010, Figures A.1 – A.6). More conservative values 1378

than those in IEC Guide 117 are chosen for metal and glass to provide 1379

some margin against a reduced reaction time while in contact with a high 1380

thermal energy surface of high thermal conductivity. 1381

Examples of such parts include general enclosure surfaces, accessible 1382

print heads of dot matrix printers or any internal surfaces that may be 1383

accessible during routine maintenance. Accidental contact, with no 1384

intention to hold or contact the surface is also included. 1385

For contact durations between 1 s and 10 s, IEC Guide 117 provides 1386

temperature ranges over which a burn may occur rather than precise limits. 1387

This takes account of the uncertainty that applies to the occurrence of b urn 1388

injury over shorter periods. The texture of the surface can also be a factor 1389

in the occurrence of a burn and this is not taken into account in the limits in 1390

IEC Guide 117. As most surfaces in IT equipment will have some texturing, 1391

values at the higher end of the spreads have been chosen. 1392

Contact time durations up to 1 s 1393

For accessible surfaces that are not normally intended or expected to be 1394

touched while operating or disconnecting the equipment, a contact time 1395

duration of up to 1 second is appropriate. This would apply to any surface 1396

of the equipment that does not have functionality when touched or is 1397

unlikely to be inadvertently contacted when accessing functional surfaces 1398

such as keyboards or handles. Typical and readily expected usage should 1399

be considered when assessing likely contact duration with such a surface. 1400

For example, it is not necessary to touch a direct plug -in external power 1401

supply adapter (Figure x) during normal use of the equipment , but it will 1402

likely be touched or briefly held for disconnection from the mains. Thus, 1403

this type of equipment is expected to be contacted for more than one 1404

second. 1405

1406

1407

1408

1409

1410

1411

Figure x Figure y 1412

Other external power supplies, such as those often supplied with notebook 1413

computers and other equipment (Figure y) , with a connected power cord 1414

will not normally be touched either during usage or for disconnection. For 1415

external power supplies with power cord, to disconnect from mains, the 1416

user will grip the power cord plug. The contact time with the plug would be 1417

more than 1 second and the contact time of the po wer supply would be less 1418

than 1 second. 1419

Met opmerkingen [RJ6]: See Raleigh minutes item 7.1.3

Page 123: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 124 – IEC TR 62368-2:20xx © IEC 2019

Other considerations 1420

In the event of a fault condition arising, the user is less likely to touch the 1421

equipment and any contact with accessible surfaces is likely to be very 1422

brief. Thus higher limits than those allow ed under IEC Guide 117 are 1423

permitted. For metal, glass and plastic surfaces, the limit is 100 °C 1424

(IEC 60065:2010, Table 3). For wood, a temperature of 150 °C was chosen 1425

because 100 °C would be lower than the normal temperature of 140 °C. 1426

When contact with a TS1 surface is unlikely due to its limited size or 1427

accessibility, a temperature up to 100 °C is acceptable if an instructional 1428

safeguard is provided on the equipment (see IEC 60950-1:2005, Table 4C, 1429

IEC 60065:2001, Table 3). 1430

In the case where a surface is hot in order to carry out its function, the 1431

occurrence of contact with the surface or a subsequent burn injury is 1432

unlikely if the user is made aware that the surface is hot. Thus, a 1433

temperature up to 100 °C or higher is acceptable if there is an effec tive 1434

instructional safeguard on the body of the equipment indicating that the 1435

surface is hot (see IEC 60950-1:2005, Table 4C and IEC 60065:2001, 1436

Table 3). 1437

Factors for consideration in determining test conditions 1438

For consistency with other parts of the document and to reflect typical user 1439

conditions, the ambient conditions described in B.1. 6 apply. 1440

Assessment of safeguards should be carried out under normal operating 1441

conditions of the product that will result in elevated surface temperatures. 1442

The chosen normal operating conditions should be typical of the 1443

manufacturer’s intended use of the product while precluding deliberate 1444

misuse or unauthorized modifications to the product or its operating 1445

parameters by the user. For some simple equipment, this will be 1446

straightforward. For more complex equipment, there may be several 1447

variables to be considered including the typical usage model. The 1448

manufacturer of the equipment should perform an assessment to determine 1449

the appropriate configuration. 1450

Example: Factors that may be considered in determining the test conditions 1451

for a notebook computer: 1452

– Mode of operation 1453

• Variable CPU speed 1454

• LCD brightness 1455

– Accessories installed: 1456

• Number of disk drives 1457

• USB devices 1458

• External HDD 1459

– Software installed: 1460

• Gaming applications 1461

• Duration of continuous use 1462

• Long term contact likely? 1463

• Other specialist applications 1464

– Battery status: 1465

• Fully charged/ Discharged 1466

• AC connected 1467

Page 124: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:20xx © IEC 2019 – 125 –

9.3.1 Touch temperature limit requirements 1468

Rationale: Table 38 provides touch temperature limits for accessible parts, assuming 1469

steady state. IEC Guide 117 provides the methodology to assess products 1470

with changing temperatures or small parts which are likely to drop in 1471

temperature upon touch. Using a thermesthesiometer for a specified time 1472

interval, the thermesthesiometer simulates the skin temperature of human 1473

finger and heating effects caused by contact with the product surface under 1474

test. Once contact is made, the thermesthesiometer and product under test 1475

will eventually reach thermal equilibrium at which point finger skin 1476

temperature can be determined. 1477

Background: The touch limits from Table 38 for > 1 s and < 10 s may be used for small 1478

hand-held devices with localized hotspots, given a small thermal energy 1479

source and touching can be easily avoided by changing holding posit ion of 1480

the device. 1481

This same rationale would also apply to small multi -media peripherals 1482

which are removed from a host device ( for example, USB memory stick, 1483

PCMCIA cards, SD card, Compact Flash card, ejectable media, etc.). In 1484

many cases, these peripherals may be removed from their host ( for 1485

example, power source) exposing higher thermally conductive materials 1486

(for example, metals), but are in thermal decay (i.e. no longer powered). 1487

In cases of doubt, the method in IEC Guide 117 may be used for steady-1488

state conditions. An example of a simplified method for thermally decaying 1489

parts is provided as a reference: 1490

Touch temperature limits in IEC Guide 117 are based on time-weighted 1491

exposure for burn (for example, thermal energy). As long as integrated 1492

thermal energy calculations (for example, area of temp vs. time) of the part 1493

at specified time intervals is less than the associated integrated thermal 1494

energy calculated limits over that duration, the measured temperatures 1495

should be acceptable. 1496

The most significant time internals to consider for decaying thermal energy 1497

is between 1 s to 10 min (using 10 s, 1 min, 10 min intervals). 1498

– For exposure times < 1 s, the 1 s temperature limits of the 1499

IEC Guide 117 should be used for 2 reasons: 1) Reaction times – 1500

under general applications reaction times of < 1 s are not probable and 1501

greatest risk of burn. 2) Repeatability – temperature measurement 1502

capability < 1 s intervals is less common and more difficult to accurately 1503

calculate the part energy. 1504

– For exposure times > 10 min, the temperature limits of IEC Guide 117 1505

should be used: after 10 min parts should either have cooled or reach 1506

sufficient equilibrium to utilize the temperature limits without the need 1507

for assessing thermal energy. 1508

This simplified method requires the part under test to be mounted using 1509

thermally insulating clamp. Clamp to the part’s least thermally conductive 1510

material and smallest contact needed to hold the part. Measured in still -air 1511

room ambient. 1512

NOTE Parts that are hand-held will decay faster than open-air measurements (for example, 1513 radiation and convection) owing to direct conduction of heat to skin. 1514

9.3.2 Test method and compliance criteria 1515

Rationale: The general intent of the requirements are to use an ambient temperature 1516

as follows without taking into account the maximum ambient specified by 1517

the manufacturer: 1518

– The test may be performed between 20 °C and 30 °C. 1519

– If the test is performed below 25 °C, the results are normalized to 1520

25 °C. 1521

Page 125: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 126 – IEC TR 62368-2:20xx © IEC 2019

– If the test is performed above 25 °C, the results are not normalized to 1522

25 °C and the limits (Table 38) are not adjusted. In case the product 1523

fails the requirements, the test may be repeated at 25 °C. 1524

9.4 Safeguards against thermal energy sources 1525

Rationale: TS1 represents non-hazardous energy and thus, no safeguard is required. 1526

Because the energy is non-hazardous, and there is no possibility of an 1527

injury, it may be accessible by ordinary persons and there is no 1528

restriction on duration of contact under normal operating conditions. 1529

TS2 represents hazardous energy that could cause a burn injury if the 1530

contact duration is sufficient. Therefore, a safeguard is required to protect 1531

an ordinary person. A TS2 surface will not cause a burn immediately on 1532

contact. Because the burn injury from a TS2 surface is likely to be minor 1533

and pain or discomfort is likely to precede the occurrence of a burn injury, 1534

a physical safeguard may not be required if there is an effective means to 1535

inform the ordinary person about the risks of touching the hot surface. 1536

Thus, a TS2 safeguard may be one of the following: 1537

– a physical barrier to prevent access; or 1538

– an instructional safeguard to limit contact time below the threshold 1539

limit value versus time. 1540

TS3 represents hazardous energy that is li kely to cause a burn injury 1541

immediately on contact. Because a TS3 surface is always likely to cause a 1542

burn immediately or before the expected reaction time due to pain or 1543

discomfort, an equipment safeguard is required. 1544

Unless otherwise specified in the document, ordinary persons need to be 1545

protected against all TS2 and TS3 energy sources. 1546

Instructed persons are protected by the supervision of a skilled person 1547

and can effectively employ instructional safeguards. Thus, equipment 1548

safeguards are not required for TS2 energy sources. An instructional 1549

safeguard may be required. 1550

TS3 energy sources can cause severe burns after very short contact 1551

duration. Thus, an instructional safeguard alone is not sufficient to 1552

protect an instructed person and an equipment safeguard is required. 1553

Skilled persons are protected by their education and experience and are 1554

capable of avoiding injury from TS3 sources. Thus, an equipment 1555

safeguard is not required to protect against TS3 energy sources. As a pain 1556

response may cause an unintentional reflex action even in skilled 1557

persons, an equipment or instructional safeguard may be required to 1558

protect against other class 3 energy sources adjacent to the TS3 energy 1559

source. 1560

9.5.1 Equipment safeguard 1561

Rationale: The function of the equipment safeguard is to limit the transfer of 1562

hazardous thermal energy. An equipment safeguard may be thermal 1563

insulation or other physical barrier. 1564

9.5.2 Instructional safeguard 1565

Rationale: An instructional safeguard will inform any person of the presence of 1566

hazardous thermal energy. Instructional safeguards may be in a text or 1567

graphical format and may be placed on the product or in the user 1568

documentation. In determining the format and location of the safeguard, 1569

consideration will be given to the expected user group, the likelihood of 1570

contact and the likely nature of the injury arising. 1571

Page 126: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:20xx © IEC 2019 – 127 –

9.6 Requirements for wireless power transmitters 1572

Rationale: Transmitters for near-field wireless power transfer can warm up foreign 1573

metallic objects that may be placed close to or on s uch a transmitter. To 1574

avoid burn due to high temperatures of the foreign metallic objects, the 1575

transmitter is tested as specified in 9.6.3. 1576

Far-field transmitters are generally called "power-beaming" and are not 1577

covered by these requirements. 1578

9.6.3 Test method and compliance criteria 1579

Rationale: While 9.6.3 specifies a maximum temperature of 70 °C, aluminum foil that 1580

reaches 80 °C is considered to comply with the requirement. The foil 1581

described in figure 49 complies with the method allowed in in 9.3.1 based 1582

on the foil dimensions and low mass. 1583

This requirement is expected to align with the current Qi standard. 1584

Rationale: While many devices (servers, laptops, etc.) may be evaluated accurately 1585

for thermal burn injury using Table 38, foreign objects (FO’s) and other 1586

similar devices with low thermal mass and finite heat flux cannot be 1587

evaluated for thermal burn injury accurately. 1588

Both the experimental (thermesthesiometer method) and the computational 1589

(bio-heat equation model) in conjunction with the thermal burn thresholds 1590

from ASTM C 1055 provide for a greater level of accuracy than IEC Guide 1591

117 in assessing the potential risk for thermal burn injury from foreign 1592

objects by, 1593

- representing temperatures of the skin; 1594

- being material and geometry agnostic and; 1595

- considering quality of contact. 1596

Both methods take into account conservative assumptions th at build in a 1597

margin of safety: 1598

- single finger (typically, finger and thumb would be used to pick up 1599

object); 1600

- no perfusion; 1601

- children/elderly reaction times; and 1602

- full thickness burn thresholds (vs +10˚C to obtain TS2). 1603

However, the findings from the experimental thermesthesiometer testing 1604

are being recommended due to the simplicity of the test method and to 1605

further promote future hazard-based testing using the thermesthesiometer. 1606

____________ 1607

10 Radiation 1608

10.2 Radiation energy source classifications 1609

Rationale: The first step in application is determining which energy sources repre sent 1610

potential radiation energy sources. Each energy source within the product 1611

can be classified as a radiation source based on the available energy 1612

within a circuit that can be used to determine the type of and number of 1613

safeguards required. The radiation energy source classifications include 1614

electromagnetic radiation energy sources. 1615

Met opmerkingen [JR7]: See Shanghai minutes item 6.1.10

Page 127: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 128 – IEC TR 62368-2:20xx © IEC 2019

10.2.1 General classification 1616

Rationale: Radiation energy source classifications for X -rays and acoustics are given in 1617

Table 39. For optical radiation (“Lasers” and “Lamps and lamp systems”), the 1618

classification is defined by the IEC 60825 series or the IEC 62471 series as 1619

applicable. 1620

The general classification scheme specified in IEC 60825-1 is for laser 1621

products and is not a classification scheme for energy sources. It is no t 1622

practical to classify laser radiation as RS. The classification according to 1623

IEC 60825-1 is used without modification. 1624

The classification schemes given in IEC 62471 and IEC 62471-5 specify a 1625

measurement distance (200 mm other than lamps intended for gen eral lighting 1626

service and 1m for Image projectors) for the determination of the Risk Group. 1627

The Risk Group classification is not the actual source of the light. It is not 1628

practical to classify the radiation from lamps and lamp systems as RS. The 1629

classification according to IEC 62471 is used without modification. 1630

Abnormal operating conditions (see Clause B.3) and single fault 1631

conditions (see Clause B.4) need to be taken into account. If it becomes 1632

higher risk group when abnormal operating condition or single fault 1633

condition is applied, the higher risk group is applied for classification. 1634

Laser equipment classified as Class 1C is generally not within the scope of this 1635

document as it mainly applies to medical related applications. 1636

1637

Page 128: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:20xx © IEC 2019 – 129 –

Source: IEC 60825-1:2014 and IEC 62471-5 1638

Rationale: Image Projectors are evaluated using the process in Figure 43 in this 1639

document (see IEC 60825-1:2014 and IEC 62471-5). 1640

1641

Figure 43 – Flowchart for evaluation of Image pro jectors (beamers) 1642

10.2.2 & 10.2.3 RS1 and RS2 1643

Rationale: The output circuits of personal music players are not subject to single 1644

fault conditions, since the outputs will not increase to a level exceeding 1645

RS2 by nature of their highly integrated hardware de signs. Typically, when 1646

component faults are introduced during testing (by bypassing or shorting of 1647

the audio related ICs), the outputs are either shut down, reduced in level or 1648

muted. 1649

Page 129: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 130 – IEC TR 62368-2:20xx © IEC 2019

10.2.4 RS3 1650

Rationale: RS3 energy sources are those that are not otherwis e classified as RS1 or 1651

RS2. No classification testing is required as these energy sources can 1652

have unlimited levels. If an energy source is not measured, it assumed to 1653

be RS3 for application of the document. A skilled person uses personal 1654

protective equipment or measures to reduce the exposure to safe limits 1655

when working where RS3 may be present. 1656

10.3 Safeguards against laser radiation 1657

Source: IEC 60825-1:2014, Annex A 1658

Rationale: IEC 60825-1:2014, Annex A provides an explanation of the different 1659

classes of products. Accessible emission limits (AELs) are generally 1660

derived from the maximum permissible exposures (MPEs). MPEs have 1661

been included in this informative annex to provide manufacturers with 1662

additional information that can assist in evaluating the safet y aspects 1663

related to the intended use of their product , such as the determination of 1664

the nominal ocular hazard distance (NOHD). 1665

10.4 Safeguards against optical radiation from lamps and lamp systems (including 1666

LED types) 1667

Source: IEC 62471 and IEC TR 62471-2 1668

Rationale: Excessive optical radiation may damage the retina and cause vision 1669

impairment or blindness. The limits in the referenced documents are 1670

designed to reduce the likelihood of vision impairment due to optical 1671

radiation sources. 1672

For the Instructional safeguard for lamps and lamp systems, see IEC 1673

TR 62471-2. 1674

10.4.1 General Requirements 1675

Source: IEC 60065 1676

Rationale: The term ‘Electronic light effect equipment ’ has been used in IEC 60065 1677

(see 1.1) and is a commonly understood term for entertainment/sta ge 1678

effect lighting. 1679

10.5 Safeguards against X-radiation 1680

Source: IEC 60950-1; IEC 60065 1681

Rationale: Exposure to X-radiation will cause injury with excessive exposure over 1682

time. The limits in this document have been selected from IEC 60950-1 and 1683

IEC 60065 in order to limit exposure to that which is below harmful levels. 1684

10.6 Safeguards against acoustic energy sources 1685

Source: EN 60065:2002/A11:2008 1686

Rationale: The requirements of this subclause are made to protect against hearing 1687

loss due to long term exposure to high sound pressure levels. Therefore, 1688

the requirements are currently restricted to those kind s of products that are 1689

designed to be body-worn (of a size suitable to be carried in a clothing 1690

pocket) such that a user can take it with them all day long to l isten to music 1691

(for example, on a street, in a subway, at an airport, etc.) . 1692

At this moment, the clause does not contain requirements against the 1693

hazard of short term exposure to very high sound pressure levels. 1694

Rationale: Significance of LAeq,T in EN 50332-1 and additional information 1695

LAeq,T is derived from the general formula for equivalent sound pressure: 1696

Page 130: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:20xx © IEC 2019 – 131 –

1697

This can be represented graphically as given in Figure 44 in this document. 1698

1699

Figure 44 – Graphical representation of LAeq,T 1700

In EN 50332-1 the measurement time interval (t2 – t1) is 30 s. 1701

In practice, and for the purposes of listening to personal music player 1702

content, LAeq,T has a time interval T (t2 – t1) in the order of minutes / hours 1703

and not seconds. 1704

Subclause 6.5 (Limitation value) of EN 50332-1:2000 acknowledges this 1705

fact and states that the 100-dB limit equates to a long time average of 90 1706

dB LAeq,T. By using the IEC 60268-1 “programme simulation noise” test 1707

signal, this also takes the spectral content into account. 1708

The SCENHIR report states that 80 dB(A) is considered safe for an 1709

exposure time of 40 h/week. Most persons do not listen to 40 h/week to 1710

their personal music player. In addition, not all music tracks are at the 1711

same level of the simulated noise signal. Whilst modern music tends to be 1712

at around the same level, most of the available music is at a lower average 1713

level. Therefore, CLC TC 108/WG03 considered a value of 85 dB(A) to be 1714

safe for an overwhelming majority of the users o f personal music players. 1715

10.6.3 Requirements for dose-based systems 1716

Rationale: The requirements on dose measurement have been developed to replace 1717

the requirements on maximum exposure as this better protects against 1718

hearing damage, which results from the combination of exposure and time 1719

(dose). For now, both systems can be used. See Table 16 in this document 1720

for a comparison. 1721

Page 131: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 132 – IEC TR 62368-2:20xx © IEC 2019

The dose-based system mainly uses the expression CSD, meaning 1722

"calculated sound dose". The value is based on the values mentioned in 1723

the EU Commission Decision 2009/490/EC, which stipulated that sound is 1724

safe when below 80 dB(A) for a maximum of 40 h per week. Therefore, the 1725

value of 100 % CSD corresponds to 80 dB(A) for 40 h. This also means 1726

that the safe limit in the dose measurement system is chosen to be lower 1727

than the safe limit in the maximum exposure system, as this specifies the 1728

safe limit at 85 dB(A). Consequently, a user will normally receive warnings 1729

earlier with the dose measurement system compared to the maximum 1730

exposure limit. In the maximum exposure system, the warning only had to 1731

be given once every 20 h of listening when exceeding 85 dB(A). In the 1732

dose measurement system, the warning and acknowledgement has to be 1733

repeated at least at every 100 % increase of the dose. In practice, this 1734

means that the warning is repeated at a comparable level of 83 dB(A), 1735

meaning a dose that corresponds to listening to 83 dB(A) for 40 h. At each 1736

next 100 % increase of dose level, the increase in correspon ding dB’s is 1737

halved. Manufacturers have the freedom to give warnings earlier or ask for 1738

acknowledgement more frequently, but it has to be no later than at the next 1739

100 % CSD increase since the last acknowledgement. For example, a 1740

device has provided the warning and acknowledgement at 100 % CSD. The 1741

manufacturer may choose to provide the next warning before 200 % CSD, 1742

for example, at 175 % CSD. If that is done, the next warning and 1743

acknowledgement may not be later than at 1744

275 % CSD. While there are no requi rements for manufacturers to warn 1745

users before the 100 % CSD is reached, it is allowed to do so. Even more, 1746

it was felt by the document writers that it would be responsible behaviour if 1747

manufacturers warn consumers about the risks before the 100 % CSD leve l 1748

is reached. With the maximum exposure measurement, the maximum 1749

allowable sound output is 100 dB(A). With the dosage system, only a 1750

momentary exposure limit (MEL) is required when exceeding 100 dB(A) if a 1751

visual or audible warning is provided. Where a vis ual or audible MEL is not 1752

provided the maximum exposure measurement of 100 dB(A) is required. 1753

An essential element to educating the user and promoting safe listening 1754

habits is appropriate and useful guidance. This can be accomplished with 1755

informative CSD and MEL warnings that allow the user to understand the 1756

hazard, risks, and recommended action. Appropriate warnings about using 1757

the device and user instructions shall be provided. It should be noted that 1758

the CSD warning can be provided in various forms not limited to visual or 1759

audio. However, the MEL can only be provided visually or audibly. 1760

Consideration should be given to not over-message and annoy the user to 1761

the point where the message is neglected or evasive attempts (software 1762

hacks) to defeat the safe guards are taken. Extreme care should be given 1763

when implementing the MEL warning and shall be at the discretion of the 1764

manufacturer. 1765

Manufacturers should be aware that digital sensitivity between PMP and 1766

unknown listening devices may result in excessive f alse positives. It is 1767

recommended industry to promote sharing of sensitivity data through a 1768

standardized means. 1769

Page 132: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:20xx © IEC 2019 – 133 –

Table 16 – Overview of requirements for dose-based systems 1770

Devices with Visual or Audible MEL EN 50332-3

SPL

before transition3

SPL

after transition3

Dose

requirements

Dose

test method

Analog known 1

> 85 dB(A) if ack,

< 100 dB(A) max

<80 dB(A) max

CSD warn at every 100 %

MEL warn at >100 dB(A)

cl 5.2

Analog unknown 2

> 27 mV r.m.s. if ack,

< 150 mV r.m.s. max

< 15 mV rms max

CSD warn at every 100 % (= integrate. rms level 15 mV)

MEL warn at > 150 mV r .m.s.

cl 5.3

Digital known 1

> 85 dB(A) if ack,

< 100 dB(A) max

< 80 dB(A) max

CSD warn at every 100 %

MEL warn at > 100 dB(A)

cl 5.2

Digital unknown 2

> -25 dBFS if ack,

< 100 dB(A)4 max

< -30 dBFS max

CSD warn at every 100 % (= integrate level -30 dBFS)

< 100 dB(A) max or MEL warn at > 100 dB(A)4

TBD 5

Devices without MEL EN 50332-3

SPL

before transition3

SPL

after transition3

Dose

requirements

Dose

test method

Analog known 1

> 85 dB(A) if ack,

< 100 dB(A) max

< 80 dB(A) max

CSD warn at every 100 %

< 100 dB(A) max

cl 5.2

Analog unknown 2

> 27 mV r.m.s. if ack,

< 150 mV r.m.s. max

< 15 mV r.m.s. max

CSD warn at every 100 % (= integrate rms level 15 mV)

< 150 mV r.m.s. max

cl 5.3

Digital known 1

> 85 dB(A) if ack,

< 100 dB(A) max

< 80 dB(A) max

CSD warn at every 100 %

< 100 dB(A) max

cl. 5.2

Digital unknown 2

> -25 dBFS if ack,

< 100 dB(A)4 max

< -30 dBFS max

CSD warn at every 100 % (= integrate level -30 dBFS)

< 100 dB(A)4 max

TBD 5

1 PMP includes or can detect listening device

2 PMP cannot detect listening device

3 Transition period allows migration to CSD before becoming mandatory

4 Defaults to 100 dB(A) gain cap from digital listening device. Need to develo p industry wide protocol for digital (wired/wireless) listening device for PMPs to learn sensitivity lookup table.

5 Need to create test requirements with EN 50332-3. Otherwise, SPL requirements (30 dBFS gain cap) will be only feasible option.

1771

Page 133: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 134 – IEC TR 62368-2:20xx © IEC 2019

10.6.6.1 Corded listening devices with analogue input 1772

Rationale: The value of 94 dB(A) was chosen to align with current practice in EN 1773

50332. In addition, some equipment may already start clipping at 100 1774

dB(A). The value used does not influence the result of the me asurement. 1775

_____________ 1776

Annex A Examples of equipment within the scope of this standard 1777

Rationale: A variety of personal electronic entertainment products/systems can be 1778

covered by this document, including self-propelling types sometimes known 1779

as entertainment robots, which typically contain electronic components and 1780

circuits that power the device's motion, a battery system and charger, the 1781

electric motor(s) and control systems, together with wireless 1782

communications and audio. When no other IEC or ISO document explicitly 1783

covers these products, they can be accommodated by IEC 62368-1. 1784

Examples of Entertainment-type Robots: 1785

1786

____________ 1787

Annex B Normal operating condition tests, abnormal operating condition 1788

tests and single fault condition tests 1789

General Equipment safeguards during various operating conditions 1790

Purpose: To identify the various operating and use conditions of equipment that are 1791

taken into account in the document. This clause was proposed to be added to 1792

the document as a Clause 0.12, but was agreed to be added to the Rationale 1793

instead. 1794

Rationale: Operating conditions 1795

Normal operating condition – A normal operating condition is a state with 1796

intended functionality of the equipment. All equipment basic safeguards, 1797

supplementary safeguards, and reinforced safeguards remain effective and 1798

comply with all required safeguard parameters. 1799

Page 134: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:20xx © IEC 2019 – 135 –

Abnormal operating condition – An abnormal operating condition is a 1800

temporary state. The equipment may have full, limited, or no functionality. The 1801

equipment generally requires operator intervention for restoration to normal 1802

operating condition. All equipment basic safeguards remain effective but 1803

may not need to comply with the required safeguard parameters. All 1804

equipment supplementary safeguards and reinforced safeguards remain 1805

effective and comply with the required safeguard parameters. 1806

Upon restoration of normal operating conditions, all basic safeguards 1807

comply with the required parameters unless the abnormal operating 1808

condition leads to a single fault condition, in which case the requirements 1809

for single fault condition apply. 1810

Reasonably foreseeable misuse condition – Reasonably foreseeable 1811

misuse is a form of an abnormal operating condition but may be either a 1812

temporary or a permanent state. The equipment may have full, l imited, or no 1813

functionality. The equipment may not be capable of restoration to a normal 1814

operating condition . Reasonably foreseeable misuse may lead to a single 1815

fault condition, in which case equipment basic safeguards are not required 1816

to remain effective. All equipment supplementary safeguards and reinforced 1817

safeguards remain effective and comply with the required safeguard 1818

parameters. 1819

Other misuse condition – Other misuse (unreasonable or unforeseeable) may 1820

lead to a single or multiple fault condition, in which basic safeguards, 1821

supplementary safeguards and reinforced safeguards may not remain 1822

effective. The equipment may not be repairable to a normal operating 1823

condition. Safeguards against unreasonable or unforeseeable misuse are not 1824

covered by this document. 1825

Single fault condition – A single fault condition is a component or 1826

safeguard fault. The equipment may have full, limited or no functionality. The 1827

equipment requires repair to return to a normal operating condition . 1828

Equipment basic safeguards are not required to be functional, in this case the 1829

supplementary safeguards are functional and comply with the required 1830

safeguard parameters; or equipment supplementary safeguards are not 1831

required to be functional, in this case the basic safeguards are functional and 1832

comply with the required safeguard parameters. 1833

NOTE As a basic safeguard and a supplementary safeguard may be interchangeable, the 1834 concept of which safeguard is not required to remain effective can be reversed. 1835

B.1.5 Temperature measurement conditions 1836

Source: IEC 60950-1 1837

Purpose: To determine whether the steady state temperature of a part or material does 1838

or does not exceed the temperature limit for that part or material. 1839

Rationale: Steady state is considered to exist if the temperature rise does not exceed 1840

3 K in 30 min. If the measured temperature is less than the required 1841

temperature limit minus 10 %, steady state is considered to exist if the 1842

temperature rise does not exceed 1 K in 5 min. 1843

Temperature rise follows an exponential curve and asymptotically approaches 1844

thermal equilibrium. The rate of temperature rise can be plotted as a function of 1845

time and used to guess the value at steady state. The actual steady state value 1846

needs to be accurate only to the extent to prove whether the value will exceed 1847

the limit or not. 1848

Steady-state conditions of typical electronic devices have many different 1849

temperatures, so thermal equilibrium does not exist. 1850

Page 135: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 136 – IEC TR 62368-2:20xx © IEC 2019

The resistance method may be used to measure temperature rises of windings 1851

unless the windings are non-uniform or if it is difficult to make the necessary 1852

connections, in which case the temperature rise is determined by other means. 1853

When the resistance method is used, t he temperature rise of a winding is 1854

calculated from the formula: 1855

Δt = 1

12

R

RR − (k + t1) – (t2 – t1) 1856

where: 1857

Δt is the temperature rise of the winding; 1858

R1 is the resistance at the beginning of the test; 1859

R2 is the resistance at the end of the test; 1860

k is equal to: 1861

• 225 for aluminium windings and copper/aluminium windings with an 1862

aluminium content ≥ 85 %, 1863

• 229,75 for copper/aluminium windings wi th a copper content 15 % 1864

to 85 %, 1865

• 234,5 for copper windings and copper/aluminium windings with an 1866

copper content ≥ 85 %; 1867

t1 is the room temperature at the beginning of the test; 1868

t2 is the room temperature at the end of the test. 1869

NOTE It is recommended that the resistance of windings at the end of the test be determined by 1870 taking resistance measurements as soon as possible after switching off and then at short 1871 intervals so that a curve of resistance against time can be plotted for ascertaining the resist ance 1872 at the instant of switching off. 1873

B.2.3 Supply Voltage 1874

Rationale: Where a test subclause does not require the most unfavourable supply voltage, 1875

the supply voltage is the value of the rated voltage or any value in the rated 1876

voltage range. This is applicable to the tests in abnormal operation 1877

condition and single fault condition as well. 1878

B.2 – B.3 – B.4 Operating modes 1879

See Figure 45 in this document for an overview of operating modes. 1880

1881

Figure 45 – Overview of operating modes 1882

Page 136: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:20xx © IEC 2019 – 137 –

B.4.4 Functional insulation 1883

Rationale: The use of a functional insulation is only acceptable when the circuit does 1884

not exceed its limits of its class under normal operating conditions and 1885

abnormal operation conditions and single fault conditions of a component 1886

not serving as a safeguard (see 5.2.1.1 and 5.2.1.2). Otherwise a basic 1887

insulation/safeguard would be required. 1888

If the functional insulation possesses a certain quality (clearance, creepage 1889

distances, electric strength) comparable to a basic safeguard, it is acceptable 1890

to omit short-circuit. 1891

This cannot be compared to the short -circuiting of a basic safeguard as 1892

required in B.4.1, because this basic safeguard is a required one, while the 1893

added quality of the functional insulation is not required. 1894

If the short-circuiting of this functional insulation with added quality would 1895

lead to a changing of the class, the functional insulation was wrongly chosen, 1896

and a basic safeguard would have been required. 1897

B.4.8 Compliance criteria during and after single fault conditions 1898

Source: IEC 60065 1899

Rationale: During single fault conditions , short term power is delivered in components 1900

which might be outside the specifications for that component. As a result, the 1901

component might interrupt. During the interruption, sometimes a small flame 1902

escapes for a short period of time. The current practice in IEC 60065 allows 1903

these short term flames for a maximum period of 10 s. This method has been 1904

successfully used for products in the scope of this document for many years. 1905

____________ 1906

Annex C UV Radiation 1907

C.1.1 General 1908

Rationale: UV radiation can affect the physical properties of thermoplastic materials and 1909

so it can have a consequential effect on components protecting body parts 1910

from a range of injurious energy sources. 1911

____________ 1912

Annex D Test generators 1913

Source: ITU-T Recommendation K.44 1914

Rationale: The circuit 1 surge in Table D.1 is typical of voltages induced into telephone 1915

wires and coaxial cables in long outdoor cable runs due to lightning strik es to 1916

their earthing shield. 1917

The circuit 2 surge is typical of earth potential rises due to either lightning 1918

strikes to power lines or power line faults . 1919

The circuit 3 surge is typical of voltages induced into antenna system wiring 1920

due to nearby lightning strikes to earth. 1921

Figure D.3 provides a circuit diagram for high energy impulse to test the high-1922

pressure lamps. 1923

____________ 1924

Page 137: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 138 – IEC TR 62368-2:20xx © IEC 2019

Annex E Test conditions for equipment containing audio amplifiers 1925

Source: IEC 60065:2011 1926

Rationale The proposed limits for touch voltages at terminals involving audio signals that 1927

may be contacted by persons have been extracted without deviation from 1928

IEC 60065:2011, 9.1.1.2 a). Under single fault conditions, 11.1 of 1929

IEC 60065:2011 does not permit an increase in acceptable touch volt age limits. 1930

The proposed limits are quantitatively larger than the accepted limits of 1931

Table 4, but are not considered dangerous for the following reasons: 1932

– the output is measured with the load disconnected ( worst-case load); 1933

– defining the contact area of connectors and wiring is very difficult due to 1934

complex shapes. The area of contact is considered small due to the 1935

construction of the connectors ; 1936

– normally, it is recommended to the user, in the instruction manual provided 1937

with the equipment, that all connections be made with the equipment in the 1938

“off” condition. 1939

– in addition to being on, the equipment would have to be playing some 1940

program at a high output with the load disconnected to achieve the 1941

proposed limits. Although possible, it is highly unlikely. Historically, no 1942

known cases of injury have been recorded for amplifiers with a non-clipped 1943

output less than 71 V RMS. 1944

– the National Electrical Code (USA) permits accessible terminals with a 1945

maximum output voltage of 120 V RMS. 1946

It seems that the current normal condition specified in IEC 60065 is appropriate 1947

and a load of 1/8 of the non-clipped output power should be applied to the 1948

multichannel by adjusting the individual channels. 1949

___________ 1950

Annex F Equipment markings, instructions, and instructional safeguards 1951

F.3 Equipment markings 1952

Source: EC Directives such as 98/37/EC Machinery Directive, Annex I clause 1.7.3 1953

marking; NFPA 79:2002, clause 17.4 nameplate data; CSA C22.1 Canadian 1954

Electric Code, clause 2-100 marking of equipment give organized 1955

requirements. The requirements here are principally taken from IEC 60065 and 1956

IEC 60950 series. 1957

F.3.3.2 Equipment without direct connection to mains 1958

Source: IEC 60950-1 1959

Purpose: To clarify that equipment powered by mains circuits, but not directly connected 1960

to the mains using standard plugs and connectors, need not have an electrical 1961

rating. 1962

Rationale: Only equipment that is directly connected to the mains supplied from the 1963

building installation needs to have an electrical rating that takes into account 1964

the full load that may be connected to the building supply outlet. For equipment 1965

that is daisy-chained or involves a master-slave configuration, only the master 1966

unit or the first unit in the daisy chain needs to be marked. 1967

Page 138: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:20xx © IEC 2019 – 139 –

F.3.6.2 Equipment class marking 1968

Rationale: For compliance with EMC standards and regulations, more and more class II 1969

products are equipped with a functional earth connection. The latest version of 1970

the basic safety publication IEC 61140 allows this construction. On request of 1971

IEC TC 108, IEC SC3C has developed a new symbol, which is now used in 1972

IEC 62368-1. 1973

Rationale: Equipment having a class II construction, but that is provided with a class I 1974

input connector with the internal earthing pin not connected is also considered 1975

to be a class II equipment with functional earth. The class I connector is used 1976

to provide a more robust connection means, which is considered to be a 1977

functional reason for the earth connection. 1978

F.4 Instructions 1979

Rationale: The dash requiring graphical symbols placed on the equipment and used as an 1980

instructional safeguard to be explained does not apply to symbols used for 1981

equipment classification (see F.3.6). 1982

F.5 Instructional safeguards 1983

Rationale: When a symbol is used, the triangle represents the words “Warning” or 1984

“Caution”. Therefore, when the symbol is used, there is no need to also use the 1985

words “Warning” or “Caution”. However, when only element 2 is used, the text 1986

needs to be preceded with the words. 1987

___________ 1988

Annex G Components 1989

G.1 Switches 1990

Source: IEC 61058-1 1991

Rationale: A contact should not draw an arc that will cause pitting and damage to the 1992

contacts when switching off and should not weld when switching on if located 1993

in PS2 or PS3 energy sources. A PS1 energy source is not considered to have 1994

enough energy to cause pitting and damage to the contacts. Both these actions 1995

(pitting and damage) may result in a lot of heating that may result in fire. There 1996

should be sufficient gap between the two contact points in the off position 1997

which should be equal to the reinforced clearance if the circuit is ES3 and 1998

basic clearance if the circuit is ES2 or ES1 (we may have an arcing PIS or 1999

resistive PIS in an ES1 circuit) in order to avoid shock and fire hazards. The 2000

contacts should not show wear and tear and pitting after tests simulating 2001

lifetime endurance; and overload tests and operate normally after such tests. 2002

G.2.1 Requirements 2003

Source: IEC 61810-1, for electromechanical relays controlling currents exceeding 0,2 A 2004

AC or DC, if the voltage across the open relay contacts exceeds 35 V peak AC 2005

or 24 V DC 2006

Rationale: A contact should not draw an arc that will cause pitting and damage to the 2007

contacts when switching off and should not weld when switching on if located 2008

in PS2 or PS3 energy sources. A PS1 energy source is not considered to have 2009

enough energy to cause pitting and damage to the contacts. Both these actions 2010

(pitting and damage) may result in lot of heating that may result in fire. There 2011

should be sufficient gap between the two contact points in the off position 2012

which should be equal to the reinforced clearance if the circuit is ES3 and 2013

basic clearance if the circuit is ES2 or ES1 (we may have an arcing PIS or 2014

resistive PIS in an ES1 circuit) in order to avoid shock and fire hazards. The 2015

contacts should not show wear and tear and pit ting after tests simulating 2016

lifetime endurance, and overload tests and operate normally after such tests. 2017

Page 139: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 140 – IEC TR 62368-2:20xx © IEC 2019

G.3.3 PTC thermistors 2018

Source: IEC 60730-1:2006 2019

Rationale: PTC thermistor for current limitation is always connected in series with the load 2020

to be protected. 2021

In a non-tripping stage, the source voltage is shared by the load impedance 2022

and the resistance of PTC thermistor (which is close to the zero-power 2023

resistance at 25 °C). In order to define the power dissipation of the PTC 2024

thermistor in this stage, the source voltage and the load impedance are also 2025

important parameters. 2026

In a tripping stage, the PTC thermistor heats up by itself and increases the 2027

resistance value to protect the circuit. The zero-power resistance at 25 °C is no 2028

longer related to the power dissipation of PTC thermistors in this stage. The 2029

power dissipation of PTC thermistor in this stage depends on factors such as 2030

mounting condition and ambient temperature. 2031

In either stage, some parameters other than the rated zero-power resistance at 2032

an ambient temperature of 25 C are required to calculate the power 2033

dissipation of PTC thermistor . 2034

The tripping stage is more hazardous than the non-tripping stage because the 2035

temperature of the PTC thermistor in the tripping stage becomes much higher 2036

than in the non-tripping stage. 2037

Figure 46 in this document shows “Voltage-Current Characteristics”. The blue 2038

dotted lines show the constant power dissipation line. It shows that the power 2039

at the operation point, during the tripping stage, is the highest power 2040

dissipation. This point is calculable with “Ires x Umax” of IEC 60738-1:2006, 2041

3.38. 2042

(Umax = maximum voltage, Ires = residual current, measured by the PTC 2043

manufacturers.) 2044

2045

Page 140: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:20xx © IEC 2019 – 141 –

2046

Figure 46 – Voltage-current characteristics (Typical data) 2047

If the PTC is installed in a PS1 circuit, the power dissipation of the PTC will be 2048

15W or less. In this state, the PTC is not considered to be a resistive PIS, 2049

regardless of its Ires x Umax. 2050

A PTC with a size of less than 1 750 mm3 is not considered to be a resistive 2051

PIS, described in 6.3.1, 6.4.5.2 and 6.4.6. 2052

G.3.4 Overcurrent protective devices 2053

Rationale: Just like any other safety critical component, p rotective devices are not allowed 2054

to be used outside their specif ications, to guarantee safe and controlled 2055

interruption (no fire and explosion phenomena’s) during single fault 2056

conditions (short circuits and overload conditions) in the end products. This 2057

should include having a breaking capacity capable of interrupting the maximum 2058

fault current (including short -circuit current and earth fault current) that can 2059

occur. 2060

G.3.5 Safeguard components not mentioned in G.3.1 to G.3.4 2061

Rationale: Protective devices shall have adequate ratings, including breaking capacity. 2062

G.5.1 Wire insulation in wound components 2063

Source: IEC 60317 series, IEC 60950-1 2064

Purpose: Enamel winding wire is acceptable as basic insulation between external 2065

circuit at ES2 voltage level and an ES1. 2066

Rationale: ES1 becomes ES2 under single fault conditions. The enamel winding wires 2067

have been used in telecom transformers for the past 25 years to provide basic 2068

insulation between TNV and SELV. The winding wire is type tested for 2069

electric strength for basic insulation in addition to compliance with IEC 60317 2070

series of standards. Enamel is present on both input and output winding wires 2071

and therefore, the possibility of having pinholes aligned is minimized. The 2072

finished component is tested for routine test for the applicable electric 2073

strength test voltage. 2074

Page 141: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 142 – IEC TR 62368-2:20xx © IEC 2019

G.5.2 Endurance test 2075

Source: IEC 60065:2011, 8.18 2076

Rationale: This test is meant to determine if insulated winding wires without additional 2077

interleaved insulation will isolate for their expected lifetime. The endurance test 2078

comprises a heat run test, a vibration tes t and a humidity test. After those 2079

tests, the component still has to be able to pass the electric strength test. 2080

G.5.2.2 Heat run test 2081

Rationale: In Table G.2, the tolerance is ± 5 °C. It is proposed that the above tolerance be 2082

the same. 2083

G.5.3 Transformers 2084

Source: IEC 61558-1, IEC 60950-1 2085

Rationale: Alternative requirements have been successfully used with products in the 2086

scope of this document for many years. 2087

G.5.3.3 Transformer overload tests 2088

G.5.3.3.2 Compliance criteria 2089

Source: IEC 61558-1, IEC 60950-1 2090

Rationale: The transformer overload test is conducted mainly to check the deterioration by 2091

thermal stress due to overload conditions, and the compliance criteria is to 2092

check whether the temperature of the windings are within the allowable limits 2093

specified in Table G.3. For that purpose, the maximum temperature of winding s 2094

is measured. 2095

However, in the actual testing condition, the winding s or other current carrying 2096

parts of the transformer under testing may pose temperature higher than the 2097

measured value due to uneven temperature, such as a w indings isolated from 2098

the mains (see third paragraph of G.5.3.3.2) , so that such spot exposed to 2099

higher temperature may have thermal damage. 2100

In order to evaluate such potential damage, electric strength test after the 2101

overload condition is considered necessary. 2102

Both of the source documents require the electric strength test after the 2103

overload test. 2104

Table G.3 Temperature limits for transformer windings and for motor windings 2105

(except for the motor running overload test) 2106

Although the document does not clearly state it, the first row should also be 2107

used in cases where no protective device is used or the component is 2108

inherently protected by impedance. 2109

For example, in the test practice of a switch mode power supply, a transformer 2110

is to be intentionally loaded to the maximum current without a protection 2111

operating. In this case, the method of protection is NOT ‘inherently ’ or 2112

‘impedance’, but other sets of limits are specified with the time of protection to 2113

operate. In reality, a switch mode transformer tested with a maximum load 2114

attempting the protection not to operate, but the limits in first row have been 2115

considered appropriate, because the thermal stress in that loading condition 2116

continues for a long time (no ending). Thus, the lowest limit should be applied. 2117

In this context, the application of the first row limit shall be chosen according to 2118

the situation of long lasting overloading rather than the type o f protection. 2119

G.5.3.4 Transformers using fully insulated winding wir e (FIW) 2120

Source: IEC 60317-56, IEC 60317-0-7 2121

Page 142: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:20xx © IEC 2019 – 143 –

Rationale: In 2012, IEC TC 55 published IEC 60317-56 and IEC 60317-0-7, Specification 2122

for Particular Types of Winding Wires – Part 0-7: General requirements – Fully 2123

insulated (FIW) zero-defect enamelled round copper wire with nominal 2124

conductor diameter of 0,040 mm to 1,600 mm. 2125

This wire is more robust enameled-coated wire used with minimal amounts of 2126

interleaved insulation. It is another step in the advancement of technology to 2127

allow manufacturers to design smaller products safely. 2128

IEC TC 96 was the first TC to incorporate the use of FIW in their safety 2129

documents for switch mode power supply units, IEC 61558-2-16. Since 2130

IEC 62368-1:2018 references in G.5.3.1 IEC 61558-1-16 as one of the 2131

acceptable documents for transformers used in switch mode power supplies, 2132

FIW already is acceptable in equipment investigated to IEC 62368-1 that use 2133

an IEC 61558-1-16 compliant transformer. 2134

FIW may not be accessible, whether it has basic insulation, double 2135

insulation or reinforced insulation. Note that this differs from other parts of 2136

the document that permit supplementary insulation and reinforced 2137

insulation to be accessible to an ordinary person. The reason is that this 2138

kind of wire is fragile and the insulation could easily b e damaged when it is 2139

accessible to an ordinary person. 2140

G.5.4 Motors 2141

Source: IEC 60950-1 2142

Rationale: Requirements have been successfully used with products in the scope of this 2143

document for many years. 2144

G.7 Mains supply cords 2145

Source: IEC 60245 (rubber insulation), IEC 60227 (PVC insulation), IEC 60364-5-54 2146

Rationale: Mains connections generally have large normal and fault energy available from 2147

the mains circuits. It is also necessary to ensure compatibility with installation 2148

requirements. 2149

Stress on mains terminal that can result in an ignition source owing to loose or 2150

broken connections shall be minimized. 2151

Terminal size and construction requirements are necessary to ensure adequate 2152

current-carrying capacity and reliable connection such that the possibilit y of 2153

ignition is reduced. 2154

Wiring flammability is necessary to reduce flame propagation potential should 2155

ignition take place. 2156

Conductor size requirements are necessary to ensure adequate current -2157

carrying capacity and reliable connection such that the poss ibility of ignition is 2158

reduced. 2159

Alternative cords to rubber and PVC are accepted to allow for PVC free 2160

alternatives to be used. At the time of development of the document, IEC TC20 2161

had no published documents available for these alternatives. However, several 2162

countries do have established requirements. Therefore, it was felt that these 2163

alternatives should be allowed. 2164

G.7.3 – G.7.5 Mains supply cord anchorage, cord entry, bend protection 2165

Source: IEC 60065:2011 and IEC 60950-1:2013 2166

Purpose: Robustness requirements for cord anchorages 2167

Rationale: The requirements for cord anchorages, cord entry, bend protection and cord 2168

replacement are primarily based on 16.5 and 16.6 of IEC 60065:2011 and 3.2.6 2169

and 3.2.7 of IEC 60950-1:2013. 2170

Page 143: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 144 – IEC TR 62368-2:20xx © IEC 2019

Experience shows that 2 mm displacement is the requirement and if an 2171

appropriate strain relief is used there is no damage to the cord and therefore, 2172

no need to conduct an electric strength test in most cases. This method has 2173

been successfully used for products in the scope of these documents for many 2174

years. 2175

G.8 Varistors 2176

Source: IEC 61051-1 and IEC 61051-2 2177

Rationale: The magnitude of external transient overvoltage (mainly attributed to lightning), 2178

to which the equipment is exposed, depends on the location of the equipment. 2179

This idea is described in Table 14 of IEC 62368-1:2018 and also specified in 2180

IEC 60664-1. 2181

In response to this idea, IEC 61051-2 has been revised taking into account the 2182

location of the equipment, which also influences the requirement for the 2183

varistors used in the equipment. 2184

The combination pulse test performed according to G.8.2 of IEC 62368-1:2018 2185

can now refer to the new IEC 61051-2 with Amendment 1. 2186

G.9 Integrated circuit (IC) current limiters 2187

Source: IEC 60730-1, IEC 60950-1 2188

Rationale: Integrated circuits (containing numerous integral components) are frequently 2189

used for class 1 and class 2 energy source isolation and, more frequently ( for 2190

example, USB or PoE), for functions such as current limiting. 2191

IEC 60335 series already has requirements for “electronic protect ion devices,” 2192

where conditioning tests such as EMF impulses are applied to such ICs, and 2193

the energy source isolation or current limiting function is evaluated after 2194

conditioning tests. When such energy isolation or current limitation has been 2195

proven reliable via performance, pins on the IC associated with this energy 2196

isolation or limitation are not shorted. 2197

For ICs used for current limitation, t wo test programs were used in 2198

IEC 60950-1:2009. An additional program was developed in IEC 62368-1:2010. 2199

It was felt that all three programs were considered adequate. Therefore , the 2200

three methods were kept. 2201

An Ad Hoc formed at the March 2015, Northbrook HBSDT meeting revised this 2202

test program with the following guiding principles: 2203

a) Streamline the number of tests in overall test program to concentrate on 2204

those tests and conditions that most likely will identify deficiencies in IC 2205

Current Limiter design from a safety perspective, such as allowing more 2206

current to flow than designed for. Some of the existing conditions are 2207

redundant or have questionable value identifying such deficiencies. 2208

b) Focus on test conditions that are applicable for semiconductor devices 2209

rather than test conditions more suited for traditional electro -mechanical 2210

devices. For example, 10 000-cycle testing has more applicability to 2211

electro-mechanical devices (in relation to parts wearing out) versus 2212

semiconductor devices (such as IC current limiters). 2213

c) Combine test conditions when justified to increase efficiency when 2214

conducting individual tests, also trying to make the testing more 2215

compatible with automated testing processes (e.g. combine individual 2216

temperature tests as individual sub-conditions of other required tests). 2217

Table G.10 provides the specific performance test program for IC current 2218

limiters. 2219

Page 144: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:20xx © IEC 2019 – 145 –

– Input loading to the device should be representative of the manufacturer’s 2220

IC specification (as typically communicated in the IC application notes for 2221

the particular device). 2222

– Output loading is intended to represent a short circuit condition (0 Ω 2223

shunt), with parallel capacitive loading (470 µF +/- 20 %) to better 2224

accommodate on/off cycling. 2225

See Figure 47 in this document for additional detail. 2226

2227

Figure 47 – Example of IC current limiter circuit 2228

Regarding the 250 VA provision, this provision is intended to mean that the 2229

usual test power source has 250 VA capability as long as the IC is designed for 2230

installation in a system with a source of 250 VA or larger. If the power source 2231

capability is intended to be less than 250 VA, then the manufacturer must 2232

specify so, or test in the end product. Testing at 250 VA is intended to include 2233

250 VA or larger sources because the test program is covering relatively small 2234

and low-voltage silicon devices – if these devices pass at 250 VA they likely 2235

would pass at higher VA too since they are not electro -mechanical. Also, this 2236

allows for more practical associated certification test programs. 2237

Also, to avoid recertification of existing components , IC current limiters that 2238

met a previous legacy test program (G.9.2, G.9.3 or G.9.4) are an equivalent 2239

level of safety as the proposed rewritten Clause G.9, primarily because Clause 2240

G.9 is derivation of the legacy requirements. Therefore, IC current limiters that 2241

comply with the legacy test program should not need to be reinvestigated to 2242

the latest document that includes this revised Clause G.9. However, this is a 2243

certification consideration outside the scope of this technical committee. 2244

G.11 Capacitors and RC units 2245

Source: IEC 60384-14:2005 2246

Rationale: Table G.11: Test voltage values aligned with those used in IEC 60384-14 2247

(Tables 1, 2 and 10 of IEC 60384-14:2005). 2248

Table G.12: Minimum number of Y capacitors based on required withstand 2249

voltage of Table 25 of IEC 62368-1:2018. 2250

Table G.13: Maximum voltage that can appear across a Y capacitor based on 2251

the peak value of the working voltage of Table 26 of IEC 62368-1:2018. 2252

Table G.14: Minimum number of Y capacitors based on the test voltages (due 2253

to temporary overvoltages) of Table 27 of IEC 62368-1:2018. 2254

Page 145: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 146 – IEC TR 62368-2:20xx © IEC 2019

Table G.15: Minimum number of X capacitors (line to line or line to neutral) 2255

based on the mains transient withstand voltage of Table 13 of 2256

IEC 62368-1:2018. 2257

All of the above are aligned with the requirements of IEC 60384-14. 2258

G.13 Printed boards 2259

Source: IEC 60950-1 or IEC 60664-3:2003. 2260

Purpose: To provide details for reliable construction of PCBs. 2261

Rationale: This proposal is based on IEC 60664-3 and the work of IBM and UL in testing 2262

coatings on printed boards when using coatings to achieve insulation 2263

coordination of printed board assemblies. Breakdown voltages of more than 2264

8 000 V for 0,025 mm were routinely achieved in this program. 2265

These parts have multiple stresses on the materials with limited separation 2266

between conductors. This section is taken from IEC 60950-1, where these 2267

requirements have been used for many years. 2268

G.13.6 Tests on coated printed boards 2269

Purpose: Prevent breakdown of the insulation safeguard. 2270

Rationale: Avoid pinholes or bubbles in the coating or breakthrough of conductive tracks 2271

at corners. 2272

G.14 Coatings on component terminals 2273

Source: IEC 60950-1 and IEC 60664-3 2274

Purpose: The mechanical arrangement and rigidity of the terminations are adequate to 2275

ensure that, during normal handling, assembly into e quipment and subsequent 2276

use, the terminations will not be subject to deformation which would crack the 2277

coating or reduce the separation distances between conductive parts. 2278

Rationale: The terminations are treated like coated printed boards (see G.13.3) and the 2279

same separation distances apply. 2280

This section is taken from IEC 60950-1 where these requirements have been 2281

used for many years. 2282

G.15 Pressurized liquid filled components 2283

Source: IEC 60950-1, IEC 61010-1, UL 2178, UL 1995 2284

Purpose: Avoid spillage of liquids resulting in electric shock hazard 2285

Rationale: The requirements apply to devices that contain less than 1 l of liquid. A leak in 2286

the system may result in a shock hazard and therefore, needs to be properly 2287

addressed. A leak is not desirable and ther efore, a strict performance criterion 2288

is proposed. Requirements were developed based on the following description 2289

of a typical system using liquid filled heat sinks. If a different type of system is 2290

used, then the requirements need to be re-evaluated. 2291

Liquid filled heat-sink system (LFHS): a typical system consists of a heat 2292

exchanger, fan, pump, tubing, fittings and cold plate or radiator type heat 2293

exchanger. The liquid filled heat sink comes from the vendor already charged, 2294

sealed; and is installed and used inside the equipment (small type, typically 2295

found in cell stations and computing devices or other types of systems). The 2296

proposed requirements are based on a LFHS being internal to a unit, 2297

used/installed adjacent/over ES1 circuits, in proximity to an enclosed power 2298

supply (not open frame). 2299

Page 146: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:20xx © IEC 2019 – 147 –

The liquid-filled heat components are used in desktop units or stationary 2300

equipment and in printers. These are not used in any portable equipment 2301

where orientation may change (unless the product is tested in all such 2302

orientations. If the liquid heat sink system is of a sealed type construction, then 2303

the system is orientation proof (this should not be a concern but a good 2304

engineering practice is that the pump does not become the high point in the 2305

system). 2306

Following assumptions are used: 2307

– The tubing is a single-layered metal (copper or aluminium) or non -metallic 2308

construction. If it is non-metallic, flammability requirements will apply. 2309

– The fittings are metal. If it is non-metallic, flammability requirements will 2310

apply. 2311

– Working pressure is determined under normal operating conditions and 2312

abnormal operating conditions and construction (tubing, fitting, heat 2313

exchanger, any joints, etc.) is suitable for this working pressure; 2314

– The volume of the liquid is reasonable (less than 1 000 ml). 2315

– The fluid does not cause corrosion and is not flammable (for example, 2316

corrosion resistant and non-flammable liquid). 2317

– The liquid is non-toxic as specified for the fluid material. 2318

___________ 2319

Annex H Criteria for telephone ringing signals 2320

H.2 Method A 2321

Source: IEC 62949:2016. 2322

Rationale: Certain voltages within telecommunication networks often exceed the steady 2323

state, safe-to-touch limits set within general safety documents. Years of 2324

practical experience by world-wide network operators have found ringing and 2325

other operating voltages to be electrically safe. Records of accident statistics 2326

indicate that electrical injuries are not caused by operating voltages. 2327

Access to connectors carrying such signals with the standard test finger is 2328

permitted, provided that inadvertent access is unlikely. The likelihood of 2329

inadvertent access is limited by forbidding access with the test probe Figure 2C 2330

of IEC 60950-1:2013 that has a 6 mm radius tip. 2331

This requirement ensures that: 2332

– contact by a large part of the human body, such as the back of the hand, is 2333

impossible; 2334

– contact is possible only by deliberately inserting a small part of the body, 2335

less than 12 mm across, such as a fingertip, which presents a high 2336

impedance; 2337

– the possibility of being unable to let -go the part in contact does not arise. 2338

This applies both to contact with signals arriving from the network and to 2339

signals generated internally in the equipment, for example, ringing signals for 2340

extension telephones. By normal standards, these internally generated sign als 2341

would exceed the voltage limits for accessible parts, but the first exemption in 2342

IEC 60950-1 states that limited access should be permitted under the above 2343

conditions. 2344

Ventricular fibrillation of the heart is considered to be the main cause of death 2345

by electric shock. The threshold of ventricular fibrillation (Curve A) is shown in 2346

Figure 48 in this document and is equivalent to curve c1 of IEC 2347

TS 60479-1:2005, Figure 14. The point 500 mA/100 ms has been found to 2348

correspond to a fibrillation probability of the order of 0,14 %. The let go limit 2349

Page 147: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 148 – IEC TR 62368-2:20xx © IEC 2019

(Curve B) is equivalent to curve 2 of IEC TS 60479-1:2005, Figure 14. Some 2350

experts consider curve A to be the appropriate limit for safe design, but use of 2351

this curve is considered as an absolute limit. 2352

2353

Figure 48 – Current limit curves 2354

Contact with telecommunication operating voltages (EN 41003) 2355

Total body impedance consists of two parts, the internal body resistance of 2356

blood and tissue and the skin impedance. Telecommunication voltages hardly 2357

reach the level where skin impedance begins to rapidly decrease due to 2358

breakdown. The skin impedance is high at low voltages, its value varying 2359

widely. The effects of skin capacitance are negligible at ringing freque ncies. 2360

IEC TS 60479-1 body impedance figures are based upon a relatively large 2361

contact area of 50 cm2 to 100 cm2, which is a realistic value for mains 2362

operated domestic appliances. Practical telecommunication contact is likely to 2363

be much less than this, typically 10 cm2 to 15 cm2 for uninsulated wiring pliers 2364

or similar tools and less than 1 cm2 for finger contact with pins of a telephone 2365

wall socket. For contact with thin wires, wiring tags or contact with tools where 2366

fingers move beyond insulated handles, the area of contact will again be of the 2367

order of 1 cm2 or less. These much smaller areas of contact with the body 2368

produce significantly higher values of body impedance than the IEC TS 60479 2369

figures. 2370

In IEC 60950-1, a body model value of 5 k is used to provide a margin of 2371

safety compared with the higher practical values of body impedance for typical 2372

telecommunication contact areas. 2373

The curve B' [curve C1 of IEC TS 60479-1:2005, Figure 22 (curve A in this 2374

document)] used within the hazardous voltage defini tion is a version of curve B 2375

modified to cover practical situations, where the current limit is maintained 2376

constant at 16 mA above 1 667 ms. This 16 mA limit is still well within the 2377

minimum current value of curve A. 2378

The difficulties of defining conditions that will avoid circumstances that prevent 2379

let-go have led to a very restricted contact area being allowed. 2380

Contact with areas up to 10 cm2 can be justified and means of specifying this 2381

and still ensuring let-go are for further study. 2382

Page 148: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:20xx © IEC 2019 – 149 –

H.3 Method B 2383

Source: This method is based on USA CFR 47 ("FCC Rules") Part 68, Sub part D, with 2384

additional requirements that apply under fault conditions. 2385

___________ 2386

Annex J Insulated winding wires for use without interleaved insulation 2387

Source: IEC 60851-3:2009, IEC 60851-5:2008, IEC 60851-6:1996 2388

Purpose: Winding wires shall withstand mechanical, thermal and electrical stress during 2389

use and manufacturing. 2390

Rationale: Test data indicates that there is not a major difference between rectangular 2391

wires and round wires for electr ic strength after the bend tests. Therefore, 2392

there is no reason to not include them. 2393

Subclause 4.4.1 of IEC 60851-5:2008 covers only solid circular or stranded 2394

winding wires as a twisted pair can easily be formed from round wires. It is 2395

difficult to form a twisted pair from square or rectangular winding wires. 2396

IEC 60851-5:2008, 4.7 addresses a test method that can be used for square 2397

and rectangular wires. A separate test method for square and rectangular wires 2398

has been added. The test voltage is chosen to be half of the twisted pair as a 2399

single conductor is used for the testing. 2400

In addition, the edgewise bend test is not required by IEC 60851-5 and 2401

IEC 60851-6 for the rectangular and square winding wires. 2402

The reference to trichloroethane is being deleted a s trichloroethane is an 2403

environmentally hazardous substance. 2404

For J.2.3 (Flexibility and adherence) and J.2.4 (Heat shock), 5.1.2 in Test 8 of 2405

IEC 60851-3:2009 and 3.2.1 of IEC 60851-6:1996 are not used for solid square 2406

and solid rectangular winding wires. 2407

___________ 2408

Annex K Safety interlocks 2409

Source: IEC 60950-1 2410

Purpose: To provide reliable means of safety interlock devices. 2411

Rationale: Safety interlock constructions have been used for many years in products 2412

within the scope of this document. Safety interlocks should not be associated 2413

with electro-mechanical components only. 2414

K.7.1 Safety interlocks 2415

Source: IEC 60950-1 2416

Purpose: To provide reliable means of safety interlock devices. 2417

Rationale: Clearance values specified in 5.4.2 are based on IEC 60664 -1 and are 2418

specified for protection against electric shock. The values are the shortest 2419

distance through air between two different conduct ive parts. In that context, 2420

one conductor is at hazardous voltage (energy source) and another conductor 2421

is accessible to a person (body part). The required clearance is the minimum 2422

distance required to protect the person from being exposed to current causing 2423

electric shock. The distance acts as a safeguard against the hazardous energy 2424

source (ES2/ES3). 2425

Page 149: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 150 – IEC TR 62368-2:20xx © IEC 2019

Contact gaps of interlock relays or switches are most likely not directly serving 2426

as the safeguard as explained above. Instead, the gap is meant to interrupt 2427

the electrical power to the energy sources, for example, motors generating 2428

MS2/3 energy or laser units generating Class IIIb or larger energy. In this 2429

situation, the distance of the gap is required to interrupt the power supply to 2430

the device so that the device is shut down. Again, it is not for the purpose of 2431

blocking current to a body part. 2432

Although the purpose of the clearance is different, the required values based 2433

on IEC 60664-1 are used because there is no other data available addressing 2434

the minimum values required to establish circuit interruption to shut off the 2435

power to a load device. It is believed that the distance req uired to protect a 2436

person from shock hazard is sufficient to have a circuit interruption as part of 2437

proper circuit operation. The specified voltage in clause 5.4 is from 330 Vpeak 2438

or Vdc, and the contacts for interlock relays/switches most likely operate in DC 2439

low voltage such as 5 or 24 V, so much lower than 330 V. Mains operated 2440

contacts are required to have a gap for disconnect device that is much larger 2441

than the distance for insulation. 2442

Due to the above considerations, slight adjustment by altitude mult iplication 2443

factor is not considered necessary for contact gaps of interlock relays/switches. 2444

___________ 2445

Annex L Disconnect devices 2446

Source: IEC 60950-1 2447

Purpose: To provide adequate protective earth connection. 2448

Rationale: 3 mm separation distances of contac ts. Can be part of building installation. 2449

For class I equipment, the supply plug or appliance coupler, if used as the 2450

disconnect device, shall make the protective earthing connection earlier 2451

than the supply connections and shall break it later than the su pply 2452

connections. 2453

Clearance of 3 mm can withstand peak impulse voltages of 4 000 V, which 2454

corresponds to a transient overvoltage present in overvoltage category III 2455

environment (equipment as part of the building installation). 2456

One instructional safeguard could be used for more than one disconnect 2457

device, as long as it can be visible from each disconnect point. 2458

___________ 2459

Annex M Equipment containing batteries and their protection circuits 2460

M.1 General requirements 2461

Rationale: Stand-alone battery chargers for general purpose batteries shall be evaluated 2462

using their relevant safety document, and not IEC 62368-1. If the battery and 2463

the charger are designed specifically for AV or ICT equipment and not to be 2464

used for other purposes, the provisions of IEC 62368-1:2018 including 2465

Annex M may be applied. 2466

Page 150: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:20xx © IEC 2019 – 151 –

M.2 Safety of batteries and their cells 2467

Rationale: Equipment containing batteries shall be designed to reduce the risk of fire, 2468

explosion and chemical leaks under normal operating conditions and after a 2469

single fault condition in the equipment, including a fault in circuitry within the 2470

equipment battery pack. For batteries replaceable by an ordinary person or 2471

an instructed person, the design shall provide safeguards against reverse 2472

polarity installation or replacement of a battery pack from different component 2473

manufacturers if this would otherwise defeat a safeguard. 2474

Other clauses in this document address in generic terms safeguards 2475

associated with the use of batteries. This annex does not specifically address 2476

those safeguards, but it is expected that batteries and associated circuits 2477

conform to the relevant requirements in this document. 2478

This annex addresses safeguards that are unique to batteries and that are not 2479

addressed in other parts of the document. Energy sources that arise from the 2480

use of batteries are addressed in this annex and include the following: 2481

– situations where the battery is in a state that exceeds its specifications or 2482

ratings (for example, by overcharging, rapid-charge, rapid-discharge, 2483

overcurrent or overvoltage conditions); 2484

– thermal runaway due to overcharge or short circuits within battery cells; 2485

– reverse-charging of the battery; 2486

– leakage or spillage of electrolyte; 2487

– emission of explosive gases; and 2488

– location of safeguards where battery packs may be replaceable by an 2489

ordinary person or an instructed person. 2490

Thermal runaway in the cell can result in explosion or fire, when the 2491

temperature rise in the cell caused by the heat emission raises the internal cell 2492

pressure faster than can be released by the cell pressure release device. 2493

Thermal runaway can be initiated by several causes: 2494

– defects introduced into the cell during cell construction. These defects are 2495

often not detected during the manufacturing process and may bridge an 2496

internal insulation layer or block a vent; 2497

– over-charge and rapid-charge or rapid-discharge; 2498

– high operational temperature or high battery environment temperature; 2499

– other cells in a pack feeding energy to a fault in a single cell; and 2500

– crushing of the enclosure. 2501

NOTE Batteries may contain multiple cells. 2502

During charging operation, gases are emitted from secondary cells and 2503

batteries excluding gastight sealed (secondary) cells, as the result of the 2504

electrolysis of water by electric current. Gases produced are hydrogen and 2505

oxygen. 2506

Table 17 in this document gives an overview of the referenced battery 2507

documents. 2508

2509

Page 151: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

15

2 –

IE

C T

R 6

23

68

-2:2

01

9 ©

IEC

20

19

Table 17 – Safety of batteries and their cells – requirements (expanded information on documents and scope) 2510

Document

Chemistry Category Movability

Scope (details)

Alk

ali

ne

; n

on

-ac

id

Le

ad

Ac

id

NiC

d/N

iMH

Lit

hiu

m

Nic

ke

l; a

lka

lin

e

ele

ctr

oly

te

Va

rio

us

Va

rio

us

, w

ith

aq

ue

ou

s e

lec

tro

lyte

Pri

ma

ry

Se

co

nd

ary

Po

rta

ble

Sta

tio

na

ry

All

IEC 60086-4 (2014); Primary Batteries – Part 4 – Safety of Lithium Batteries

X X X Specifies tests and requirements for primary lithium batteries to ensure their safe operation under intended use and reasonably foreseeable misuse (includes coin / button cell batteries).

IEC 60086-5 (2016): Primary Batteries – Part 5 – Safety of batteries with aqueous electrolyte

X X X Specifies tests and requirements for primary batteries with aqueous electrolyte to ensure their safe operation under intended use and reasonably foreseeable misuse (includes coin/button cell batteries ).

IEC 60896-11 (2002): Stationary Lead Acid Batteries – Part 11 – Vented type

X X X X Applicable to lead-acid cells and batteries that are designed for service in fixed locations ( for example, not habitually to be moved from place to place) and which are permanently connected to the load and to the DC power supply. Batteries operating in such applications are called "stationary batteries". Any type or construction of lead -acid battery may be used for stationary battery applications. Part 11 is applicable to vented types only.

IEC 60896-21 (2004): Stationary Lead Acid Batteries – Part 21 – Valve regulated type – method of test

X X X X Applies to all stationary lead -acid cells and monobloc batteries of the valve regulated type for float charge applications, (for example, permanently connected to a load and to a DC power supply), in a static location (for example, not generally intended to be moved from place to place) and incorporated into stationary equipment or installed in battery rooms for use in telecom, uninterruptible power supply (UPS), utility switching, emergency power or similar applications. The objective is to specify the methods of test for all types and construction of valve regulated stationary lead acid cells and monobloc batteries used in standby power applications.

Page 152: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC

TR

62

36

8-2

:20

19

© IE

C 2

01

9

– 1

53

Document

Chemistry Category Movability

Scope (details) A

lka

lin

e;

no

n-a

cid

Le

ad

Ac

id

NiC

d/N

iMH

Lit

hiu

m

Nic

ke

l; a

lka

lin

e

ele

ctr

oly

te

Va

rio

us

Va

rio

us

, w

ith

aq

ue

ou

s e

lec

tro

lyte

Pri

ma

ry

Se

co

nd

ary

Po

rta

ble

Sta

tio

na

ry

All

IEC 60896-22 (2004): Stationary Lead Acid Batteries – Part 22 – Valve regulated type – requirements

X X X X Applies to all stationary lead -acid cells and monobloc batteries of the valve regulated type for float charge applications, (for example, permanently connected to a load and to a DC power supply), in a static location ( for example, not generally intended to be moved from place to place) and incorporated into stationary equipment or installed in battery rooms for use in telecom, uninterruptible power supply (UPS), utility switching, emergency power or similar applications. The objective is to assist the specifier in the understanding of the purpose of each test containe d within IEC 60896-21 and provide guidance on a suitable requirement that will result in the battery meeting the needs of a particular industry application and operational condition. This document is used in conjunction with the common test methods described in IEC 60896-21 and is associated with all types and construction of valve regulated stationary lead-acid cells and monobloc batteries used in standby power applications.

IEC 61056-1 (2012): General purpose lead-acid batteries (valve-regulated types) – Part 1: General requirements, functional characteristics – Methods of test

X X X X Specifies the general requirements, functional characteristics and methods of test for all general-purpose lead-acid cells and batteries of the valve-regulated type:

– for either cyclic or float charge application;

– in portable equipment, for instance, incorporated in tools, toys, or in static emergency, or uninterruptible power supply and general power supplies.

(For stationary applications, the battery will need to meet IEC 60896-21/-22 or subject to additional evaluation) .

Page 153: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

15

4 –

IE

C T

R 6

23

68

-2:2

01

9 ©

IEC

20

19

Document

Chemistry Category Movability

Scope (details) A

lka

lin

e;

no

n-a

cid

Le

ad

Ac

id

NiC

d/N

iMH

Lit

hiu

m

Nic

ke

l; a

lka

lin

e

ele

ctr

oly

te

Va

rio

us

Va

rio

us

, w

ith

aq

ue

ou

s e

lec

tro

lyte

Pri

ma

ry

Se

co

nd

ary

Po

rta

ble

Sta

tio

na

ry

All

IEC 61056-2 (2012): General purpose lead-acid batteries (valve-regulated types) – Part 2: Dimensions, terminals and marking

X X X X Specifies the dimensions, terminals and marking for all general-purpose lead-acid cells and batteries of the valve regulated type:

– for either cyclic or float charge application;

– in portable equipment, for instance, incorporated in tools, toys, or in static emergency, or uninterruptible power supply and general power supplies.

(For stationary applications, the battery will need to meet IEC 60896-21/-22 or subject to additional evaluation) .

IEC 61427 (all parts) (2013): Secondary cells and batteries for renewable energy storage – General requirements and methods of test – Part 1: Photovoltaic off-grid application

X X X Part of a series that gives general information relating to the requirements for the secondary batteries used in photovoltaic energy systems (PVES) and to the typical methods of test used for the verification of battery performances. This part deals with cells and batteries used in photovoltaic off -grid applications. This document is applicable to all types of secondary batteries.

IEC TS 61430 (1997): Secondary Cells and Batteries – Test Methods for Checking the Performance of Devices Designed for Reducing Explosion Hazards – Lead-Acid Starter Batteries

X X X Specification gives guidance on procedures for testing the effectiveness of devices which are used to reduce the hazards of an explosion, together with the protective measures to be taken.

IEC 61434 (1996): Secondary cells and batteries containing alkaline or other non-acid electrolytes Guide to the designation of current in alkaline secondary cell and battery standards

X X X Applies to secondary cells and batteries containing alkaline or other non-acid electrolytes. It proposes a mathematically correct method of current designation which shall be used in future secondary cell and battery documents.

Page 154: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC

TR

62

36

8-2

:20

19

© IE

C 2

01

9

– 1

55

Document

Chemistry Category Movability

Scope (details) A

lka

lin

e;

no

n-a

cid

Le

ad

Ac

id

NiC

d/N

iMH

Lit

hiu

m

Nic

ke

l; a

lka

lin

e

ele

ctr

oly

te

Va

rio

us

Va

rio

us

, w

ith

aq

ue

ou

s e

lec

tro

lyte

Pri

ma

ry

Se

co

nd

ary

Po

rta

ble

Sta

tio

na

ry

All

IEC 61959 (2004): Secondary cells and batteries containing alkaline or other non-acid electrolytes Mechanical tests for sealed portable secondary cells and batteries

X X X Specifies tests and requirements for verifying the mechanical behavior of sealed portable secondary cells and batteries during handling and normal use.

IEC 62133 (all parts) (2012 – superseded by IEC 62133-1 and IEC 62133-2); Secondary cells and batteries containing alkaline or other non-acid electrolytes – Safety requirements for portable sealed secondary cells, and for batteries made from them, for use in portable applications

X X X Specifies requirements and tests for the safe operation of portable sealed secondary cells and batteries (other than coin / button cell batteries) containing alkaline or other non-acid electrolyte, under intended use and reasonably foreseeable misuse .

IEC 62133-1 (2017): Secondary cells and batteries containing alkaline or other non-acid electrolytes – Safety requirements for portable sealed secondary cells, and for batteries made from them, for use in portable applications – Part 1: Nickel systems

X X X Specifies requirements and tests for the safe operation of portable sealed secondary nickel cells and batteries containing alkaline electroly te, under intended use and reasonably foreseeable misuse.

IEC 62133-2 (2017): Secondary cells and batteries containing alkaline or other non-acid electrolytes – Safety requirements for portable sealed secondary lithium cells, and for batteries made from them, for use in portable applications – Part 2: Lithium systems

X X X Specifies requirements and tests for the safe operation of portable sealed secondary lithium cells and batteries containing non-acid electrolyte, under intended use and reasonably foreseeable misuse .

Page 155: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

15

6 –

IE

C T

R 6

23

68

-2:2

01

9 ©

IEC

20

19

Document

Chemistry Category Movability

Scope (details) A

lka

lin

e;

no

n-a

cid

Le

ad

Ac

id

NiC

d/N

iMH

Lit

hiu

m

Nic

ke

l; a

lka

lin

e

ele

ctr

oly

te

Va

rio

us

Va

rio

us

, w

ith

aq

ue

ou

s e

lec

tro

lyte

Pri

ma

ry

Se

co

nd

ary

Po

rta

ble

Sta

tio

na

ry

All

IEC 62281 (2016): Safety of primary and secondary lithium cells and batteries during transport

X X X X Specifies test methods and requirements for primary and secondary (rechargeable) lithium cells and batteries to ensure their safety during transport other than for recycling or disposal (similar to UN 38.3 ).

IEC 62485-2

(2010): Safety requirements for secondary batteries and battery installations – Part 2: Stationary batteries

X X X X Applies to stationary secondar y batteries and battery installations with a maximum voltage of 1 500 V DC (nominal) and describes the principal measures for protections against hazards generated from:

– electricity,

– gas emission,

– electrolyte.

Provides requirements on safety aspects associated with the erection, use, inspection, maintenance and disposal. It covers lead-acid and NiCd/NiMH batteries (IEC 62485-2 requires the valve regulated batteries to meet safety requirements from IEC 60896).

IEC 62619 (2017): Secondary cells and batteries containing alkaline or other non-acid electrolytes – Safety requirements for secondary lithium cells and batteries, for use in industrial applications

X X X Specifies requirements and tests for the safe operation of secondary lithium cells and batteries used in industrial applications including stationary applications.

2511

2512

Page 156: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:2019 © IEC 2019 – 157 –

M.3 Protection circuits for batteries provided within the equipment 2513

Rationale: Equipment containing batteries is categorized into two types; 2514

1. Equipment containing batteries which are embedded in the equipment and 2515

cannot be separated from the equipment. 2516

2. Equipment containing batteries which can be separated from the 2517

equipment. 2518

The requirements in IEC 62368-1 cover only the battery circuits that are not an 2519

integral part of the battery itself, and as such form a part of the equipment. 2520

M.4 Additional safeguards for equipment containing a portable secondary 2521

lithium battery 2522

Rationale: M.4 applies to all equipment with lithium batteries. M.4.4 applies only to 2523

equipment as specified in clause M.4.4 (typically portable). 2524

Secondary lithium batteries (often called lithium-ion or li-ion batteries) are 2525

expected to have high performance, such as light-weight and high energy 2526

capability. The use of li -ion batteries has been continuously expanding in the 2527

area of high-tech electronic equipment. However, it is said that this technology 2528

involves risks because the safety margin (distance between safe -operation 2529

zone and unsafe-operation zone) is relatively small compared to other battery 2530

technologies. 2531

IEC TC 108 noted that for designing equipment containing or using li -ion 2532

battery, it is imperative to give careful consideration to selecting highly reliable 2533

battery cells, providing high performance battery management systems for 2534

operating batteries within their specified operating environment and parameter 2535

range (for example, battery surrounding temperature or battery 2536

charging/discharging voltage and current) . It is also imperative to introduce 2537

safeguards against abnormal operating conditions, such as vibration during 2538

the use of devices, mechanical shock due to equipment drop, surge signals 2539

caused internally or externally, and a mechanism to reduce the likelihood of 2540

catastrophic failure such as battery explosion or fire. 2541

It is suggested that suppl iers of equipment and batteries should take into 2542

account possible abnormal operating conditions that may occur during use, 2543

transport, stock, and disposal, so that the equi pment is well prepared for such 2544

conditions. 2545

It is important that the key parameters (highest/lowest charging temperatures, 2546

maximum charging current, and upper limit charging voltage) during charging 2547

and discharging of the battery are not exceeded. 2548

IEC TC 108 noted that, when designing battery compartments, the battery 2549

compartment dimensions should allow sufficient space for cells to expand 2550

normally under full operating temperature range or be flexible to prevent 2551

unnecessary compression of the cells. Given the wide range of battery 2552

constructions, corresponding battery compartment dimensional requirements 2553

will differ. When necessary, coordinate with the battery manufacturer to 2554

determine change in battery dimensions over full operating range during 2555

charging and discharging. 2556

M.4.2.2 Compliance criteria 2557

The highest temperature point in the battery may not always exist at the center 2558

of the battery. The battery supplier should specify the point where the highest 2559

temperature in the battery occurs. 2560

To test the charging circuit, instead of using a real battery (which is a chemical 2561

system), an electrical circuit emulating the battery behavior (dummy battery 2562

circuit) may make the test easier by eliminating a possible battery defect. 2563

An example of a dummy battery circuit is given in Figure 49 in this document. 2564

Met opmerkingen [RJ8]: See Raleigh minutes 9.4.8

Page 157: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 158 – IEC TR 62368-2:2019 © IEC 2019

Figure 49 – Example of a dummy battery circuit

M.4.3 Fire enclosure 2565

Lithium-ion batteries with an energy more than PS1 (15 W) must be provided 2566

with a fire enclosure (either at the battery or at the equipment containing the 2567

battery) because even though measurements of output voltage and current 2568

may not necessarily show them to be a PIS, however they contain flammable 2569

electrolyte that can be easily ignited by the enormous amount of heat 2570

developed by internal shorts as a result of possibl e contaminants in the 2571

electrolyte. 2572

M.4.4 Drop test of equipment containing a secondary lithium battery 2573

Annex M.4.4 applies only to batteries used in portable applications. 2574

This includes batteries in the scope of IEC 62133 and IEC 62133 -2 which are 2575

typically used in hand-held equipment or transportable equipment. 2576

Batteries or sub-assemblies containing batteries used in other types of 2577

equipment, that are not routinely held or carried but may be occasionally 2578

removed for service or replacement, are not conside red to be portable batteries 2579

and are not in scope of Annex M.4.4. 2580

Monitoring of lithium-ion battery output voltage and surface temperature during 2581

or after the drop test may not help. The concern is that if a minor dent occurs, 2582

nothing may happen to the battery. Temperature may go up slightly and then 2583

drop down without any significant failure. If the battery is damaged, the 2584

damage may only show up if the battery is then subjected to few charging and 2585

discharging cycles. Therefore, the surface temperature measurement was 2586

deleted and replaced with charging and discharging cycles after the drop test. 2587

The charging and discharging of the battery shall not result in any fire or 2588

explosion. 2589

It is important that the equipment containing a secondary lithium battery 2590

needs to have a drop impact resistance. Equipment containing a secondary 2591

lithium battery should avoid further damage to the control circuit and the 2592

batteries. 2593

As M.4.4 requires the equipment to be tested, the relevant equipment heights 2594

need to be used instead of the height for testing parts that act as a fire 2595

enclosure. 2596

After the drop test: 2597

– Initially, the control functions should be checked to determine if they 2598

continue to operate and all safeguards are effective. A dummy battery or 2599

appropriate measurement tool can be used for checking the function of the 2600

equipment. 2601

Met opmerkingen [RJ9]: See Raleigh minutes 7.1.4

Met opmerkingen [JR10]: See Shanghai meeting minutes item 6.1.21

Page 158: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:2019 © IEC 2019 – 159 –

– Then, the batteries are checked whether or not a slight internal short circuit 2602

occurs. 2603

Discharge and charge cycles under normal operating conditions test hinder 2604

detection of the slight internal short circuit because the current to discharge 2605

and charge is higher than the current caused by a slight internal short circuit. 2606

Thus, it is very important to conduct a voltage observation of the battery 2607

immediately after the drop test without any discharge and charge. 2608

To detect a slight internal short circuit of the battery, IEC TC 108 adopts a no-2609

load test, which can detect a battery open voltage drop caused by an internal 2610

short circuit leak current in a 24 h period. 2611

Equipment containing an embedded type of battery has internal power 2612

dissipation (internal consumption current). Therefore, two samples of the 2613

equipment are prepared, one for the drop test and the other for reference in a 2614

standby mode. In this way, the effect of internal power dissipation can be 2615

detected by measuring a difference between voltage drops in the 24 h period. 2616

M.6.1 Requirements 2617

Examples: Examples of battery documents containing an internal short test are 2618

IEC 62133, IEC 62133-2 and IEC 62619. 2619

Another example of compliance to internal fault requirements is a battery using 2620

cells that have passed the impact test as specified in IEC 62281. 2621

M.7.1 Ventilation preventing an explosive gas concentration 2622

Rationale: During charging, float charging, and overcharging operation, gases are emitted 2623

from secondary cells and batteries excluding gastight sealed (secondary) 2624

cells, as the result of the electrolysis of water by electric current. Gases 2625

produced are hydrogen and oxygen. 2626

M.7.2 Test method and compliance criteria 2627

Source: The formula comes from IEC 62485-2:2010, 7.2. 2628

M.8.2.1 General 2629

Source: The formula comes from IEC 60079-10-1:2015, Clause B.4. 2630

___________ 2631

Annex O Measurement of creepage distances and clearances 2632

Source: IEC 60664-1, IEC 60950-1 2633

Purpose: Clearances are measured from the X-points in the figure 2634

Rationale: Figure O.4. At an IEC/TC 109 meeting in Paris, a draft CTL interpretatio n was 2635

discussed regarding example 11 of IEC 60664 -1. The question was if distances 2636

smaller than X should be counted as zero. There was a quite lengthy debate, 2637

but the conclusion was that, based on the other examples in the standard (and 2638

especially example 1), there is no reason why in this example the distance 2639

should be counted as zero. If this should be done, many other examples should 2640

be changed where it is shown that the distance is measured across X rather 2641

than to disregard X. TC 109 has decided to modi fy the example 11 to remove 2642

the X from the figure to avoid this confusion in future. As IEC 60664 -1 is the 2643

basic safety publication, we should align with this interpretation . Therefore, the 2644

statement that distances smaller than X are disregar ded is deleted from 2645

Figure O.4. 2646 Met opmerkingen [JR11]: See Shanghai meeting minutes item 6.1.22

Page 159: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 160 – IEC TR 62368-2:2019 © IEC 2019

Figure O.13. The clearance determination is made from the X-points in the 2647

figure, as those are the first contact points when the tes t finger enters the 2648

enclosure opening. It is assumed that the enclosure is covered by conductive 2649

foil, which simulates conductive pollution. 2650

___________ 2651

Annex P Safeguards against conductive objects 2652

P.1 General 2653

Rationale: The basic safeguard against entry of a foreign object is that persons are not 2654

expected to insert a foreign object into the equipment. Where the equipment is 2655

used in locations where children may be present, it is expected that there will 2656

be adult supervision to address the issue of reasonable foreseeable misuse by 2657

children, such as inserting foreign objects . Therefore, the safeguards specified 2658

in this annex are supplementary safeguards. 2659

P.2 Safeguards against entry or consequences of entry of a for eign object 2660

Source: IEC 60950-1 2661

Purpose: Protect against the entry of foreign objects 2662

Rationale: There are two alternative methods that may be used. 2663

P.2.2 specifies maximum size limits and construction of openings. The 2664

relatively small foreign conductive objects or amounts of liquids that may p ass 2665

through these openings are not likely to defeat any equipment safeguards. 2666

This option prevents entry of objects that may defeat a safeguard. 2667

Alternatively, if the openings are larger than those specified in P.2.2, P.2.3 2668

assumes that a foreign conductive object or liquid passing through these 2669

openings is likely to defeat an equipment basic safeguard, and requires that 2670

the foreign conductive object or liquid shall not defeat an equipment 2671

supplementary safeguard or an equipment reinforced safeguard. 2672

P.2.3.1 Safeguard requirements 2673

Rationale: Conformal coating material is applied to electronic circuitry to act as protection 2674

against moisture, dust, chemicals, and temperature extremes that, if uncoated 2675

(non-protected), could result in damage or failure of the electronics to function. 2676

When electronics are subject to harsh environments and added protection is 2677

necessary, most circuit board assembly houses coat assemblies with a layer of 2678

transparent conformal coating rather than potting. 2679

The coating material can be applied by various methods, from brushing, 2680

spraying and dipping, or, due to the increasing complexities of the electronic 2681

boards being designed and with the 'process window' becoming smaller and 2682

smaller, by selectively coating via robot. 2683

P.3 Safeguards against spillage of internal liquids 2684

Source: IEC 60950-1 2685

Rationale:If the liquid is conductive, flammable, toxic, or corrosive, then the liquid shall 2686

not be accessible if it spills out. The container of the liquid provides a basic 2687

safeguard. After the liquid spills out, then barrier, guard or enclosure that 2688

prevents access to the liquid acts as a supplementary safeguard. Another 2689

choice is to provide a container that does not leak or permit spillage for 2690

example, provide a reinforced safeguard. 2691

P.4 Metalized coatings and adhesives securing parts 2692

Source: IEC 60950-1 2693

Page 160: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:2019 © IEC 2019 – 161 –

Rationale:Equipment having internal barriers secured by adhesive are subject to 2694

mechanical tests after an aging test. If the barrier does not dislodge as a whole 2695

or partially or fall off, securement by adhesive is considered acceptable. 2696

The temperature for conditioning should be based on the actual temperature of 2697

the adhesive secured part. 2698

The test program for metalized coatings is the same as for aging of adhesives. 2699

In addition, the abrasion resistance test is done to see if particles fall off from 2700

the metalized coating. Alternatively, clearance and creepage distances for 2701

PD3 shall be provided. 2702

___________ 2703

Annex Q Circuits intended for interconnection with building wiring 2704

Source: IEC 60950-1:2013 2705

Rationale: For the countries that have electrical and fire codes based on NFPA 70, this 2706

annex is applied to ports or circuits for external circuits that are 2707

interconnected to building wiring for limited power circuits. Annex Q was based 2708

on requirements from IEC 60950-1 that are designed to comply with the 2709

external circuit power source requirements necessary for compliance with the 2710

electrical codes noted above. 2711

Q.1.2 Test method and compliance criteria 2712

In determining if a circuit is a limited power source, all co nditions of use should 2713

be considered. For example, for circuits that may be connected to a battery 2714

source as well as a mains source, determination whether the available output 2715

from the circuit is a limited power source is made with each of the sources 2716

connected independently or simultaneously (see Figure 50 in this document). 2717

Q.2 Test for external circuits – paired conductor cable 2718

Time/current characteristics of type gD and type gN fuses specified in 2719

IEC 60269-2-1 comply with the limit. Type gD or type gN fuses rated 1 A, would 2720

meet the 1,3 A current limit. 2721

2722

Figure 50 – Example of a circuit with two power sources 2723

___________ 2724

Annex R Limited short-circuit test 2725

Source: IEC SC22E 2726

Page 161: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 162 – IEC TR 62368-2:2019 © IEC 2019

Rationale: The value of 1 500 A is aligned with the normal breaking capacity of a high 2727

breaking fuse. In Japan the prospective short circuit current is considered less 2728

than 1 000 A. 2729

___________ 2730

Annex S Tests for resistance to heat and fire 2731

S.1 Flammability test for fire enclosure and fire barrier materials of equipment 2732

where the steady-state power does not exceed 4 000 W 2733

Rationale: This test is intended to test the ability of an end -product enclosure to 2734

adequately limit the spread of flame from a potential ignition source to the 2735

outside of the product. 2736

– Included the text from IEC 60065 using the needle flame as the ignition 2737

source for all material testing. The reapplication of the flame after the first 2738

flaming was added to clarify that the test flame is immediately re -applied 2739

based on current practices. 2740

– This conditioning requirement of 125 °C for printed wiring boards is derived 2741

from laminate and PCB documents. 2742

S.2 Flammability test for fire enclosure and fire barrier integrity 2743

Rationale: This test method is used to test the integrity of a fire barrier or fire enclosure 2744

where a potential ignition source is in very close proximity to an enclosure 2745

or a barrier. 2746

The criteria of “no additional holes” is considered important as flammable 2747

materials may be located immediately on the other side of the barrier or fire 2748

enclosure. 2749

Rationale: Application of needle flame 2750

The flame cone and the 50 mm distance is a new requirement that was not 2751

applied in IEC 60950 to top openings. This new requirement does impact 2752

already certified IEC 60950 ITE products, and it was found that some 2753

manufacturers’ current designs were not able to comply with the 50-mm 2754

distance prescribed ventilation opening requirements and will not be able to 2755

pass the needle flame test as per IEC 60695-11. An HBSDT’s fire enclosure 2756

adhoc team performed some experimental flame testing with the needle flame 2757

located at various distances from various size ventilation openings. This test 2758

approach was found to align more with hazard-based safety engineering 2759

principles and deemed to be a more realistic representation of when a thermal 2760

event may occur. 2761

A PIS can be in the form of any size/shape , so it was determined not 2762

reasonable to directly apply the needle flame to top surface openings when 2763

realistically a thermal event from smaller components is unlikely to touch the 2764

top surface openings. Additionally, typically it is common for such components 2765

to be mounted on V-0 rated boards that further help reduce the spread of fire. 2766

The test data from the fire experimental testing demonstrat ed clearly that, 2767

when the flame is at distances well within 50 mm, significantly larger openings 2768

can be used beyond the pre-specified sizes by 6.4.8.3.3 ( for example less than 2769

5 mm in any dimension and/or less than 1 mm regardless of length). 2770

Therefore, for the purpose of this standard and to align more with hazard-2771

based safety engineering principles , the needle flame is to be applied at a 2772

distance measured from the closest assessed point of a PIS to the closest 2773

surface point of the test specimen. The appli cation of the flame is measured 2774

from the top of the needle flame burner to the closest surface point. See Figure 2775

S.1 in Clause S.2 of IEC 62368-1:2018. 2776

Page 162: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:2019 © IEC 2019 – 163 –

S.3 Flammability tests for the bottom of a fire enclosure 2777

Source: IEC 60950-1:2013 2778

Rationale: This text was not changed from the original ECMA document which was 2779

originally in IEC 60950-1. This test is intended to determine the acceptability of 2780

holes or hole patterns in bottom enclosures to prevent flaming material from 2781

falling onto the supporting surface. It has been used principally for testing 2782

metal bottom enclosures. 2783

This test is being proposed to test all bottom enclosures. Research is ongoing 2784

to develop a similar test based on the use of flammable (molten) thermoplastic 2785

rather than oil. 2786

S.4 Flammability classification of materials 2787

Rationale: The tables were considered helpful to explain the hierarchy of material 2788

flammability class requirements used in this document. 2789

Whenever a certain flammability class is required, a better classification is 2790

allowed to be used. 2791

S.5 Flammability test for fire enclosure materials of equipment with a steady 2792

state power exceeding 4 000 W 2793

Source: IEC 60950-1:2013 2794

Rationale: The annex for flammability test for high voltage cables was withdrawn and 2795

replaced by flammability test for fire enclosure materials of equipment having 2796

greater than 4 000 W faults. 2797

___________ 2798

Annex T Mechanical strength tests 2799

T.2 Steady force test, 10 N 2800

Source: IEC 60950-1 2801

Rationale: 10 N applied to components and parts that may be touched during operation or 2802

servicing. This test simulates the accidental contact with a finger or part of a 2803

hand. 2804

T.3 Steady force test, 30 N 2805

Source: IEC 60065 and IEC 60950-1 2806

Rationale: This test simulates accidental contact with a part of the hand. 2807

T.4 Steady force test, 100 N 2808

Source: IEC 60065 and IEC 60950-1 2809

Rationale: This test simulates an expected force applied during use or movement. 2810

T.5 Steady force test, 250 N 2811

Source: IEC 60065 and IEC 60950-1 2812

Rationale: 250 N applied to external enclosures (except those covered in Clause T.4). 2813

This test simulates an expected force when leaning against the equipment 2814

surface to ensure clearances are not bridged to introduce a hazard such as 2815

shock. The 30 mm diameter surface simulates a small part of hand or foot. It is 2816

not expected that such forces will be applied to the bottom surface of heavy 2817

equipment ( 18 kg). 2818

Page 163: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 164 – IEC TR 62368-2:2019 © IEC 2019

T.6 Enclosure impact test 2819

Source: IEC 60065 and IEC 60950-1 2820

Rationale: To check integrity of the enclosure, to ensure that no hazard is created by an 2821

impact. 2822

The values in T.6 are taken over from existing requirements in IEC 60065 and 2823

IEC 60950-1. 2824

The impact is applied once for each test point on the enclosure. 2825

T.7 Drop test 2826

Source: IEC 60065 and IEC 60950-1 2827

Rationale: This test addresses potential exposure to a hazard after the impact and not 2828

impact directly on a body part. The test is app lied to desk top equipment under 2829

7 kg as it is more likely these products could be accidentally knocked off the 2830

desk. The drop height was chosen based on intended use of the product. 2831

The term “table-top” has been used in IEC 60065, while the term “desk -top” 2832

has been used in IEC 60950-1. Both terms had been taken over in IEC 62368-1 2833

without the intention to make the different requirements for these types of 2834

equipment. Therefore, the requirements are applicable to both type of 2835

equipment even if only either one is referred to. From edition 3 onwards, the 2836

term “table-top” has been replaced by “desk -top”. 2837

T.8 Stress relief test 2838

Source: IEC 60065 and IEC 60950-1 2839

Rationale: To ensure that the mechanical integrity of moulded plastic parts is not affected 2840

by their relaxation or warping following thermal stress. 2841

T.9 Glass impact test 2842

Source: IEC 60065 2843

Rationale: Test applied to test the strength of the glass. 2844

The value of 7 J is a value that has been used for CRT in the past. Except for 2845

that, the value has also been used in commercial applications, but not in 2846

households, where the forces expected on the glass are much lower. CRT’s 2847

have separate requirements in Annex W. Therefore , a value of 3,5 J is 2848

considered sufficient. 2849

The centre of a piece of glass can be determined via the intersection of two 2850

diagonals for a rectangular piece or any other appropriate means for pieces of 2851

other geometries. 2852

T.10 Glass fragmentation test 2853

Source: IEC 60065 2854

Rationale: Test applied to ensure the fragments are small enough to be consid ered at 2855

MS2 level or less. 2856

___________ 2857

Annex U Mechanical strength of CRTs and protection against the effects of 2858

implosion 2859

U.2 Test method and compliance criteria for non-intrinsically protected CRTs 2860

Source: IEC 61965, IEC 60065 2861

Page 164: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:2019 © IEC 2019 – 165 –

Rationale: The 750 mm simulates the height of a typical supporting surface such as a 2862

table or counter top. Test applied to ensure any expelled fragments are small 2863

enough to be considered at MS2 level or less. The fragment size represents a 2864

grain of sand. The test distances selected ensure fragments do not travel far 2865

enough to strike a person and cause injury. 2866

___________ 2867

Annex V Determination of accessible parts 2868

Figure V.3 Blunt probe 2869

Source: This test probe is taken from Figure 2c, IEC 60950-1:2013 2870

___________ 2871

Annex X Alternative method for determing clearances for insulation in 2872

circuits connected to an AC mains not exceeding 420 V peak (300 V 2873

RMS) 2874

Rationale: IEC TC 108 made a responsible decision to harmonize the requirements for 2875

clearances and creepage distances with the horizontal IEC 60664-x series 2876

documents produced by IEC TC 109. This decision is aligned with IEC 2877

harmonization directives and allows manufacturers the design benefits afforded 2878

by the IEC 60664-x series documents when minimization of spacings is a 2879

primary consideration of the product design. 2880

However, because of the complexity of determining clearances as per 5.4.2, 2881

sometimes the more state-of-art theory is not practical to implement for designs 2882

not requiring minimized spacings. For example, there are a very large number 2883

of existing designs and constructions qualified to IEC 60950-1 that are 2884

associated with products, mainly switch mode power supplies, connected to AC 2885

mains (overvoltage category II) not exceeding 300 V RMS. These 2886

constructions have successfully used the clearance requirements in 2887

IEC 60950-1 without any evidence of field issues, and even at switching 2888

frequencies well above 30 kHz. In fact, almost every switch mode power supply 2889

(SMPS) used today with IT & ICT equipment intended to be connected to 2890

mains less than 300 V RMS, including external power supplies, direct plug -in 2891

type, and internal power supplies, have clearances based on the base 2892

requirements in Subclause 2.10.3.3 and Tables 2K and 2L of IEC 60950-1. 2893

Although the requirements do not incorporate the latest research on 2894

clearances used in circuits operating above 30 kHz, they are considered to be 2895

suitable for the application because they are a conservative implementation of 2896

IEC 60664-1 without minimization. 2897

As a result, and in particular based on their proven history of acceptability in 2898

the broad variety of power supplies used today, IEC TC 108 should support 2899

continued limited application of a prescribed set of clearances as an 2900

alternative to the more state-of-art IEC 60664-based requirements in 2901

IEC 62368-1 today. However, because of the valid concern with circuits 2902

operating above 30 kHz as clearances are further minimized, the IEC 60950-1 2903

option in Tables 2K and 2L for reduced clearances in products with 2904

manufacturing subjected to a quality contro l programme (values in parenthesis 2905

in Tables 2K/2L) are not included in this proposal since the reduced 2906

clearances associated with the quality control option has not been used 2907

frequently under IEC 60950-1, and therefore there is not the same proven track 2908

record of successful implementation in a very large number of products. 2909

Similarly, there is not the same large quantity of qualified designs/construction 2910

associated with equipment connected to mains voltages exceeding 300 V 2911

Page 165: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 166 – IEC TR 62368-2:2019 © IEC 2019

RMS, or for equipment connected to DC mains, so these constructions should 2912

comply with the existing IEC 60664-based requirements in IEC 62368-1. 2913

___________ 2914

Annex Y Construction requirements for outdoor enclosures 2915

Rationale: General 2916

In preparing the requirements for outdoor enclosures, it has been assumed 2917

that: 2918

– exterior to the outdoor equipment there should be no hazards, just as is 2919

the case with other information technology equipment; 2920

– protection against vandalism and other purposeful acts will be treated as a 2921

product quality issue (for example, IEC 62368-1 does not contain 2922

requirements for the security of locks, types of acceptable screw head, 2923

forced entry tests, etc.). 2924

Electric shock 2925

It is believed that most aspects relating to protection against the risk of electric 2926

shock are adequately covered by IEC 62368-1 including current proposals, and 2927

in some cases, quoted safety documents (in particular, the IEC 60364 series), 2928

and with the exception of the following, do not require modification. Specific 2929

requirements not already suitably addressed in IEC 60950-1 were considered 2930

as follows: 2931

– clearing of earth faults for remotely located (exposed) information 2932

technology equipment; 2933

– the degree of protection provided by the enclosure to rain, dust, etc.; 2934

– the effect of moisture and pollution degree on the insulation of the 2935

enclosed parts; 2936

– the possible consequences of ingress by plants and animals (since these 2937

could bridge or damage insulation); 2938

– the maximum permissible touch voltage and body contact impedance for wet 2939

conditions. 2940

It is noted that the voltage limits of user -accessible circuits and parts in 2941

outdoor locations only are applicable to circuits and parts that are actually 2942

“user-accessible”. If the circuits and parts are not user accessible 2943

(determined via application of accessibility probes) and are enclosed in 2944

electrical enclosures, connectors and cable suitable for the outdoor 2945

application, including being subject to all relevant outdoor enclosure testing, 2946

voltage limits for indoor locations may be acceptable bas ed on the application. 2947

For example, a power-over-ethernet (PoE) surveillance camera mounted 2948

outdoors supplied by 48 V DC from PoE would be in compliance with Clause 5 2949

if the electrical enclosure met the applicable requirements for outdoor 2950

enclosures. 2951

Fire 2952

It is believed that most aspects relating to protection against fire emanating 2953

from within the equipment are adequately covered by IEC 62368-1. However, 2954

certain measures that may be acceptable for equipment located inside a 2955

building would not be acceptab le outdoors because they would permit the entry 2956

of rain, etc. 2957

For certain types of outdoor equipment, it could be appropriate to allow the 2958

‘no bottom fire enclosure required if mounted on a concrete base’ exemption 2959

that presently can be used for equipment for use within a restricted access 2960

location. 2961

Page 166: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:2019 © IEC 2019 – 167 –

Mechanical hazards 2962

It is believed that all aspects relating to protection against mechanical hazards 2963

emanating from the equipment are adequately covered by IEC 62368-1. 2964

Heat-related hazards 2965

It is believed that most aspects relating to protection against direct heat 2966

hazards are adequately covered by IEC 62368-1. However, it may be 2967

appropriate to permit higher limits for equipment that is unlikely to be touched 2968

by passersby (for example, equipment that is only intended to be pole mounted 2969

out of reach). A default nominal ambient temperature range for outdoor 2970

equipment has been proposed. The effects of solar heating have not been 2971

addressed. 2972

In addition to direct thermal hazards, there is a need to consider con sequential 2973

hazards. For instance, some plastics become brittle as they become cold. An 2974

enclosure made from such brittle plastic could expose users to other hazards 2975

(for example, electrical or mechanical) if it were to break. 2976

Radiation 2977

It is believed that most aspects relating to direct protection against radiation 2978

hazards are adequately covered by IEC 62368-1. However, there may be 2979

consequential hazards to consider. Just as polymeric materials can be affected 2980

by low temperatures, they can also become embrittled owing to the effect of UV 2981

radiation. An enclosure made from such brittle plastic could expose users to 2982

other hazards (for example, electrical or mechanical) if it were to break. 2983

Chemical hazards 2984

It is believed that certain types of outdoor equipment need to have measures 2985

relating to chemical hazards originating within, or external to, the equipment. 2986

Exposure to chemicals in the environment (for example, salt used to clear 2987

roads in the winter) can also cause problems. 2988

Biological hazards 2989

These are not presently addressed in IEC 62368-1. As with radiation hazards 2990

and chemical hazards, it is thought that there is not likely to be any direct 2991

biological hazard. However, plastics and some metals can be attacked by fungi 2992

or bacteria and this could result in weakening of protective enclosures. As 2993

stated under 'electric shock', the ingress of plants and animals could result in 2994

damage to insulation. 2995

Explosion hazards 2996

Outdoor equipment may need to be weather-tight, in such cases there is an 2997

increased probability that an explosive atmosphere can build up as a result of: 2998

– hydrogen being produced as a result of charging lead -acid batteries within 2999

the equipment and; 3000

– methane and other ‘duct gasses’ entering the equipment from the outdoors. 3001

Y.3 Resistance to corrosion 3002

Rationale: Enclosures made of the following materials are considered to comply with 3003

XX.1 without test: 3004

(a) Copper, aluminum, or stainless steel; and 3005

(b) Bronze or brass containing at least 80 % copper. 3006

Y.4.6 Securing means 3007

Rationale: Gaskets associated with doors, panels or similar parts subject to periodic 3008

opening is an example of a gasket needing either mechanical securement or 3009

adhesive testing. 3010

3011

Page 167: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 168 – IEC TR 62368-2:2019 © IEC 2019

___________ 3012

3013

Page 168: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:2019 © IEC 2019 – 169 –

Annex A 3014

(informative) 3015

3016

Background information related to the use of SPDs 3017

NOTE Since there is ongoing discussion in the committee on the use of SPDs in certain situations, the content of 3018 this Annex is provided for information only. This Annex does not in any way override t he requirements in the 3019 document, nor does it provide examples of universally accepted constructions. 3020

A.1 Industry demand for incorporating SPDs in the equipment 3021

The industry has the demand of providing protection of communication equipment from 3022

overvoltage that may be caused by lightning strike surge effect. There are r eports in Japan 3023

that hundreds of products are damaged by lightening surges every year, including the risk of 3024

fire and/or electrical shock according to the damage to the equipment, especially in the 3025

regions where many thunderstorms are observed. We believe it will be the same in many 3026

other countries by the reason described in the next paragraph where the voltage of the surge 3027

is much higher than expected value for overvoltage category II equipment (1 500 V peak or 3028

2 500 V peak). For the surge protection purpose, the manufacturers have need to introduce 3029

the surge protection devices in the equipment, not only for class I equipment but also for 3030

class II equipment or class III equipment, but facing to the difficulty of designing equipment 3031

because of the limited acceptance in IEC 60950-1, 2nd edition and IEC 62368-1, 1st edition. 3032

If the point of bonding of electrical supply to the equipment is not adjacent to the point of 3033

bonding of telecommunication circuit that is connected to the external circuit of the same 3034

equipment, the surge entered from power line or from communication line causes the high 3035

potential difference on the insulation in the equipment, and cause the insulation/component 3036

breakdown which may cause product out -of-use. In some cases, the damage on the insulation 3037

or safeguard can cause hazardous voltage on the SELV/ES1 and accessible metal, or heat-3038

up of insulation material and fire (see Figure A.1 in this document, with the example of class 3039

II equipment.) 3040

The most effective way to protect equipment from a lightning surge is, as commonly 3041

understood internationally, to have an equipotential bonding system in the building/facility with 3042

a very low in-circuit impedance by the use of main-earth bar concept (see Figure A.2 in this 3043

document). This kind of high-quality earthing provision can be introduced in the 3044

building/facility in the business area , such as computer rooms, or in modern buildings. This 3045

kind of high quality earthing provision may not always be possible in the residential area, in 3046

already-existing buildings and in some countries where the reliably low impedance earth 3047

connection may not be easily obtained from technical (according to the characteristics of land) 3048

or even by practical reasons (because very expensive construction change to the building is 3049

required, or according to the lack of regulatory co -work it is difficult to get the relevant 3050

permission for cabling). We should not disregard the fact that many ICT equipment (including 3051

PCs, fax machines, TVs and printers) are brought to home, school and small business offices 3052

into the existing buildings (see Figure A.3 and Figure A.4 in this document). 3053

If the use of surge suppressors by the means of “a varistor in series with a GDT” is allowed in 3054

the equipment to bridge safeguards for class I equipment and to bridge a double safeguard 3055

or a reinforced safeguard for class II equipment, means can be provided to bypass the 3056

surge current, and to avoid the possibility that the lightening surge breaks the circuit or the 3057

insulation within the equipment (see Figure A.2 in this document). 3058

Thus, there is industry demand for using surge protecting device s (SPDs) in the equipment 3059

independent of whether the product is class I equipment, class II equipment or class III 3060

equipment. 3061

Page 169: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 170 – IEC TR 62368-2:2019 © IEC 2019

3062

Figure A.1 – Installation has poor earthing and bonding; 3063

equipment damaged (from ITU-T K.66) 3064

3065

Figure A.2 – Installation has poor earthing and bonding; using main earth bar 3066

for protection against lightning strike (f rom ITU-T K.66) 3067

3068

Page 170: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:2019 © IEC 2019 – 171 –

3069

Figure A.3 – Installation with poor earthing and bonding, using a varistor 3070

and a GDT for protection against a lightning strike 3071

3072

Figure A.4 – Installation with poor earthing and bonding; equipment damaged (TV set) 3073

A.2 Technical environment of relevant component standards 3074

Before the publication of IEC 62368-1:2010, there was no appropriate component document 3075

for a GDT deemed to be providing a sufficient level of endurance to be accepted as a 3076

safeguard for a primary circuit. For this reason, a GDT could not be accepted as a reliable 3077

component for use as a safeguard between a primary and secondary circuit. 3078

However, recently IEC SC 37B has been developed new documents for GDTs. In these 3079

documents the spark over voltage of GDT’s has been extended up to 4 500 V DC, taking the 3080

use of GDTs in the mains circuit in to account. We believe therefore that a GDT may be used 3081

as a safeguard if it complies with the following documents: 3082

– IEC 61643-311:2013: Components for low-voltage surge protective devices – Part 311: 3083

Performance requirements and test circuits for gas discharge tubes (GDT) ; 3084

– IEC 61643-312:2013: Components for low-voltage surge protective devices – Part 312: 3085

Selection and application principles for gas discharge tubes ; 3086

The sentence “does not deal with GDTs connected in series with voltage -dependent resistors 3087

in order to limit follow-on currents in electrical power systems; ” in the scope of these 3088

Page 171: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 172 – IEC TR 62368-2:2019 © IEC 2019

documents with a purpose for expressing that GDTs connected in series with varistors are a 3089

kind of SPD and this issue should be in IEC 61643-11 for SDP’s standard. But this sentence 3090

may be misread as “a GDT is not allowed to be used for primary circuits”, so SC37B decided 3091

to delete the sentence. This decision was made during the IEC SC 37B meeting at Phoenix, 3092

U.S.A, in Oct, 2010. 3093

A.3 Technical discussion 3094

A.3.1 General 3095

For the use as surge protective devices (SPD), there are many types of components and the 3096

combined use of them. Some of them are relatively large in size and useful only in the outdoor 3097

facility or in the building circuits. Some are reliable but others may not. 3098

For use with equipment in the scope of IEC 62368-1, varistors and GDT’s are very commonly 3099

available with appropriate physical size and reliability. 3100

3101

Figure A.5 – Safeguards 3102

A.3.2 Recommended SPD and its level of sparkover voltage 3103

The recommended construction of SPD for the purpose of protecting human and the 3104

insulations in the equipment is the combined use of a GDT and a varistor in series, by the 3105

reasons described in this subclause and A.3.3. 3106

The level of sparkover voltage of the SPD constructed as recommended as above is important 3107

and should be selected as higher than withstand voltage level of insulation which SPD is 3108

intended to protect from damage by surge overvoltage. IEC 61643-311 and IEC 61643-312 3109

provides the selection of GDT ’s up to 4 500V DC sparkover voltage series (see “A” in 3110

Figure A.5 in this document). 3111

A.3.3 Consideration of a GDT and its follow current 3112

If you are going to use a GDT in the primary circuit , or in the external circuit, you have to 3113

take the follow current in GDT into account. For more information on the GDT’s follow current, 3114

see Clause A.4 in this document. 3115

D

Page 172: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:2019 © IEC 2019 – 173 –

The follow current in the GDT after the surge transient voltage/current that flows through it 3116

may keep the GDT in the low impedance mode while the equipment power is on, resulting in 3117

a risk of electric shock if somebody touches the circuit connected to the GDT. The combined 3118

use of a GDT and a varistor in series is the common method to avoid this risk. Aft er the 3119

transient overvoltage condition is over, the varistor will stop the GDT ’s follow current. 3120

Complying with Clause G.8 is required for the varistor ’s working voltage. It means that 1,25 3121

x Vac is required for the varistor’s working voltage. After the transient, the varistor will stop 3122

the current from the AC line immediately. 3123

For the reliability of the GDT, it is required that the GDT meets the requirements for electric 3124

strength and the external clearance and creepage distance requirements for reinforced 3125

insulation (see “B” in Figure A.5). 3126

A.3.4 Consideration of varistors and its leak current 3127

If a varistor is used in the primary circuit or in the external circuit, the leakage current in the 3128

varistor has to be taken into account. The continuous current caused by the leakage current 3129

may burn the varistor or other components in the circuit, and is energy inefficient. The 3130

combined use of a GDT and a varistor in series is the common method to avoid this effect, 3131

since the GDT can kill the leakage current just after the surge transient voltage passed 3132

through these components. 3133

For the reliability of the varistor, it has to comply with Clause G.8 (see “C” in Figure A.5 in this 3134

document). 3135

A.3.5 Surge voltage/current from mains 3136

A.3.5.1 Case of transversal transient on primary circuit 3137

A surge caused by lightning may enter in the mains circuit and get into the equipment as a 3138

transversal transient overvoltage. In this case, incorporating an SPD (that may be a varistor 3139

only) between the line and neutral of the primary circuit is an effective method to prevent 3140

damage in the circuit, as the surge is bypassed from line to neutral or vice versa. In this case, 3141

the reliability requirement may not be mandatory for the SPD, because the failure of th e SPD 3142

can lead to an equipment fault condition (out of use) but may not lead to risk to human (see 3143

“D” in Figure A.5 in this document). 3144

A.3.5.2 Case of longitudinal transient on primary circuit 3145

A surge caused by lightning may enter in the mains circuit and get into the equipment as a 3146

longitudinal (common mode) transient overvoltage, which may cause high-level potential 3147

difference between the primary circuit and the external circuits in the equipment. In this case, 3148

providing a bypass circuit from the primary circuit to the reliable bonding, or a bypass circuit 3149

between the primary circuit and the external circuits, or both, incorporating an SPD (a 3150

combined use of a GDT and a varistor in series is recommended) is an effective method to 3151

prevent insulations and components in the equipment from being damaged (see “E” in 3152

Figure A.5 in this document). 3153

For preventing the risk of electrical shock in this case, a bypass circuit connected to the SPD 3154

shall be either connected to the earth, or provided with a suitable safeguard from ES1. (A 3155

double safeguard or a reinforced safeguard between the primary side of an SPD and ES1, 3156

and a basic safeguard between external circuit side of SPD and ES1, see “J” and “G” in 3157

Figure A.5 in this document). 3158

There may be a discussion about the safety of the telecommunication network connected to 3159

the external circuit, but it is presumed that the telecommunication network is appropriately 3160

bonded to the earth through the grounding system. Also, the maintenance person accessing 3161

the telecommunication for maintenance is considered to be a skilled person, and knows that 3162

they should not access the network lines when lightning strikes are observed in the nearby 3163

area (see “F” in Figure A.5 in this document). 3164

Page 173: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 174 – IEC TR 62368-2:2019 © IEC 2019

For the risk that the connection of the external circuit to the telecommunication network is 3165

disconnected, the SPD cannot operate. However, in this case, the external circuit is left 3166

open circuit, therefore the telecom side shall have a safeguard to ES1. Under this condition, 3167

the SPD can be the open circuit (see “G” and “F” in Figure A.5 in this document). 3168

A.3.6 Surge voltage/current from external circuits 3169

A.3.6.1 Case of transversal transient on external circuits 3170

A surge caused by lightning may enter from the external circuit (such as the 3171

telecommunication network) as a transversal transient overvoltage. In this case, incorporating 3172

an SPD (may be a GDT only) between the Tip and Ring of the external circuit is the effective 3173

method to prevent damage in the circuit, as the surge is bypassed from one wire of the 3174

external circuit to another wire. In this case, the reliability requirement is not mandatory for 3175

the SPD, because the failure of the SPD can only lead to an equipment fault condition (out of 3176

use) but may not lead to risk to a person (see “H” in Figure A.5 in this document). 3177

A.3.6.2 Case of longitudinal transient on external circuits 3178

A surge caused by lightning may enter the telecommunication network and get into the 3179

external circuit of the equipment as longitudinal (common mode) transient overvoltage, 3180

which may cause high level potential difference between a mains circuit and external 3181

circuits. In this case, providing a bypass circuit between the primary circuit and external 3182

circuits, or between external circuit and bonding, or both, incorporating an SPD (a 3183

combined use of a GDT and a varistor in series is recommended) is an effective method to 3184

protect insulations and components in the equipment (see “I” in Figure A.5 in this document). 3185

For limiting the risk of electrical shock in this case, a bypass circuit connected to the SPD 3186

shall be either connected to the earth, or provided w ith suitable safeguard from ES1 (A 3187

double safeguard or a reinforced safeguard between the primary side of the SPD and ES1, 3188

and a basic safeguard between the external circuit side of the SPD and ES1, see “J” in 3189

Figure A.5 in this document). 3190

About the consideration of some countries that have no polarity of the AC plug, SPDs 3191

installed between power lines in accordance with IEC 60364 will operate and the surge will go 3192

into the AC line (see “I” in Figure A.5 in this document). 3193

A.3.7 Summary 3194

As a summary of the above technical discussions, the following are proposed requirements if 3195

a varistor is connected in series with a GDT and used as safeguard: 3196

– the GDT’s sparkover voltage level should be selected from IEC 61643-311 and IEC 61643-3197

312 in accordance with the bridged insulation (see A.3.2 in this document); 3198

– the GDT shall pass the electric strength test and meet the external clearance and 3199

creepage distance requirements for reinforced insulation (see A.3.3 in this document); 3200

– the varistor shall comply with Clause G.8 (see A.3.3 and A.3.4 in this document); 3201

– the bypass circuit connected to the SPD shall be either connected to earth, or provided 3202

with a suitable safeguard from ES1 (a double safeguard or a reinforced safeguard 3203

between the primary side of the SPD and ES1, and a basic safeguard between the 3204

external circuit side of the SPD and ES1, see A.3.5.2 and A.3.6.2 in this document). 3205

A.4 Information about follow current (or follow-on current) 3206

A.4.1 General 3207

The information was taken from “MITSUBISHI Materials home page” 3208

Page 174: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:2019 © IEC 2019 – 175 –

A.4.2 What is follow-on-current? 3209

Follow-on-current is literally something that will continue to flow. In this case it is the 3210

phenomenon where the current in a discharge tube continues to flow. 3211

Normally surge absorbers are in a state of high impedance. When a surge enters the absorber 3212

it will drop to a low impedance stage, a llowing the surge to bypass the electronic circuit it is 3213

protecting. After the surge has passed, the absorber should return to a high impedance 3214

condition. 3215

However, when the absorber is in a low impedance state and if there is sufficient voltage on 3216

the line to keep the current flowing even when the surge ends , the absorber remains in a 3217

discharge state and does not return to a high impedance state. The current will then continue 3218

to flow. This is the phenomenon known as follow-on-current. 3219

Surge absorbers that display this follow-on-current phenomenon are of the discharge type or 3220

semiconductor switching absorbers. A characteristic of these absorbers is that during surge 3221

absorption (bypass) the operating voltage (remaining voltage) is lower than the starting 3222

voltage. 3223

The advantage of this is that during suppression the voltage is held very low, so as to reduce 3224

stress on the equipment being protected. But there can be a problem when the line current of 3225

the equipment is sufficient so that it continues to drive the absorber when the voltage is at a 3226

low state. 3227

Below are more details about the follow-on-current mechanism. The discharge and power 3228

source characteristics for the discharge tube as well as conditions of follow -on-current will be 3229

explained. 3230

A.4.3 What are the V-I properties of discharge tubes? 3231

The micro-gap type surge absorber is one kind of discharge tube. The discharge 3232

characteristics where the part passes through pre -discharge, glow discharge and then arc 3233

discharge are shown in Figure A.6 in this document. 3234

Figure A.6 in this document shows the V-I characteristics relation between voltage and 3235

current for the discharge tube. When the tube discharges, electric current flows and if moves 3236

to a glow discharge state and then an arc state all while the discharge voltage decreases. 3237

Conversely, as the discharge decreases, the voltage increases as it moves from an arc state 3238

to a glow state. 3239

Page 175: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 176 – IEC TR 62368-2:2019 © IEC 2019

3240

Figure A.6 – Discharge stages 3241

Pre-glow discharge 3242

The voltage that is maintaining this discharge is approximately equal to the DC breakdown 3243

voltage of the part. A faint light can be seen from the part at this point . 3244

Glow discharge 3245

There is a constant voltage rate versus the changing current. The voltage maintai ning this 3246

discharge will depend on the electrode material and the gas in the tube. The discharge light 3247

now covers one of the electrodes. 3248

Arc discharge 3249

With this discharge, a large current flows through the part and it puts out a bright light. The 3250

maintaining voltage at this point (voltage between the discharge tube terminals) is in the 10’s 3251

of volts range. 3252

A.4.4 What is holdover? 3253

When a discharge tube is used on a circuit that has a DC voltage component, there is a 3254

phenomenon where the discharge state in the tube continues to be driven by the current from 3255

the power supply even after the surge voltage has subsided. This is called holdover (see 3256

Figure A.7 in this document). 3257

When holdover occurs, for example, in the drive circuit of a CRT, the screen darkens and 3258

discharge in the absorber continues, which can lead to the glass tube melting, smoking or 3259

burning. 3260

Page 176: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:2019 © IEC 2019 – 177 –

Figure A.7 – Holdover 3261

Holdover can occur when the current can be supplied to the discharge tube due to varying 3262

conditions of output voltage and output resistance of the DC power supply. What are then the 3263

conditions that allow current to continue to flow to the discharge tube? 3264

The relation between the power supply voltage ( V0), serial resistance (R), discharge current (I) 3265

and the terminal voltage (v) are shown in the linear relation below: 3266

v = V0 – I x R 3267

If the voltage V0 is fixed, the slope of the power supply output characteristic line increases or 3268

decreases according to the resistance and may or may not intersect with the V-I 3269

characteristics of the discharge tube. 3270

The characteristic linear line of a power supply shows the relation between the output voltage 3271

and current of the power supply. Likewise, the V -I curve of a discharge tube shows the 3272

relation between the voltage and current. 3273

When static surge electricity is applied to the discharge tube, the shape of the curve shows 3274

that the surge is being absorbed during arc discharge. 3275

As the surge ends, the discharge goes from arc discharge to glow discharge and then to the 3276

state just prior to glow discharge. At this time the relationship between the discharge tubes 3277

V-I curve and the power supply’s output characteristics are very important. 3278

As shown in the figure, with a high resistance in the power supply, the o utput characteristic 3279

line (pink) and the discharge tubes V-I characteristic curve (red) never intersect. Therefore, 3280

current will not flow from the power supply and follow -on-current will not occur. 3281

However, when the output characteristic line of the power supply (pink) intersects with the V-I 3282

curve of the discharge tube (red), it is possible for current from the power supply to flow into 3283

the discharge tube. When the surge ends, the current should decrease from arc discharge to 3284

the pre-glow state, but instead the power supply will continue to drive the current where it 3285

intersects in the glow or arc discharge region. This is called holdover, and is the condition 3286

where the power supply continues to supply current to the discharge tube at the intersection 3287

on its characteristic line and the discharge tubes V -I curve. 3288

Figure A.8 in this document shows where the power supply can continue supplying curren t to 3289

the discharge tube when its characteristic line intersects the discharge tubes V -I line in the 3290

glow or arc discharge sections. 3291

Page 177: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 178 – IEC TR 62368-2:2019 © IEC 2019

Figure A.8 – Discharge 3292

To prevent holdover from occurring, it is important to keep the V -I characteristic line of the 3293

power supply from intersecting with the V-I curve of the discharge tube. 3294

A.4.5 Follow-on-current from AC sources? 3295

When using the discharge tube for AC sources, when follow-on-current occurs as per the case 3296

with DC it is easy to understand. 3297

That is, as can be seen in the figure below, the only difference is that the power supply 3298

voltage (V0) changes with time. 3299

As shown on the previous page, when the power supply voltage is shown as V0(t), the output 3300

power characteristics are displayed as follows: 3301

v = V0(t) – R x I 3302

where 3303

v is the the voltage at the power out terminal 3304

I is the current of the circuit 3305

V0(t) will vary with time, so when displaying the above equation on a graph, it will appear as in 3306

Figure A.9 in this document on the left. Then when V0 (t) is shown as: 3307

V0(t) = V0 sin wt 3308

When the power supply voltage becomes 0 (zero cross), there is a short time around this 3309

crossing where the voltage range and time range of the power supply output and discharge 3310

tube V-I curve do not intersect. 3311

For an AC power supply, because there is always a zero crossing of the supply’s voltage, 3312

more than holdover it is easier to stop the discharge. In the vicinity of the zero crossing, it is 3313

impossible to maintain the discharge since the current to the discharge is cut off. The 3314

discharge is then halted by the fact that the gas molecules, which were ionized during this 3315

time, return to their normal state. 3316

Because the terminal voltage does not exceed the direct current break down voltage, if the 3317

discharge is halted it will not be able to start again. 3318

However, if the gas molecules remain ionized during this period and voltage is again applied 3319

to both terminals of the discharge tube (enters the cycle of opposite voltage), this newly 3320

Page 178: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:2019 © IEC 2019 – 179 –

applied voltage will not allow the discharge to end and it will continue in the discha rge mode. 3321

This is follow-on-current for alternating current. 3322

When follow-on-current occurs, the tube stays in a discharge mode and the glass of the tube 3323

will begin to smoke, melt and possibly ignite. 3324

3325

3326

Figure A.9 – Characteristics 3327

It is important to insert a resistance in series that is sufficiently large to prevent follow -on-3328

current from occurring according to the conditions of the alternating current. 3329

Page 179: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 180 – IEC TR 62368-2:2019 © IEC 2019

Picture 1: with 0 Ω (follow-on current occurs)

Picture 2: with 0,5 Ω (follow-on current is stopped within half a wave)

3330

Figure A.10 – Follow on current pictures 3331

With 1 Ω and 3 Ω resistance, results are the same as those in picture 2, follow-on-current is 3332

disrupted and discharge stops (see Figure A.10 in this document). 3333

For AC power sources, the resistance value that is connected in series with the discharge 3334

tube is small in comparison to DC sources. 3335

If the series resistance is 0,5 Ω or greater it should be sufficient, however for safety a value of 3336

3 Ω (for 100 V) or greater is recommended. 3337

In addition there is also a method to use a varistor in series that acts as a resistor. In this 3338

case the varistor should have an operating voltage greater than the AC voltage and be placed 3339

in series with the discharge tube. Unlike the resistor, discharge will be stopped without follow -3340

on-current occurring during the first half wave. 3341

Recommended varistor values are: 3342

– for 100 VAC lines: a varistor voltage of 220 V minimum; 3343

– for 200 VAC lines: a varistor voltage of 470 V minimum. 3344

Page 180: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:2019 © IEC 2019 – 181 –

A.4.6 Applications with a high risk of follow-on-current 3345

1) Holdover: CRT circuits and circuits using DC power supplies 3346

2) Follow-on-current: Circuits using AC power source 3347

3348

Page 181: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 182 – IEC TR 62368-2:2019 © IEC 2019

Annex B 3349

(informative) 3350

3351

Background information related to measurement of discharges – 3352

Determining the R-C discharge time constant for X- and Y-capacitors 3353

B.1 General 3354

Since the introduction of 2.1.1.7, “Discharge of capacitors in equipment,” in IEC 60950-1:2013, 3355

questions continually arise as to how to measure the R-C discharge time constant. The 3356

objective of this article is to describe how to measure and determine the discharge time 3357

constant. 3358

B.2 EMC filters 3359

EMC filters in equipment are circuits comprised of inductors and capacitors arra nged so as to 3360

limit the emission of RF energy from the equipment into the mains supply line. In EMC filters, 3361

capacitors connected between the supply conductors ( for example, between L1 and L2) of the 3362

mains are designated as X capacitors. Capacitors connect ed between a supply conductor 3363

and the PE (protective earthing or grounding) conductor are designated as Y capacitors 3364

(Safety requirements for X and Y capacitors are specified in IEC 60384-14 and similar 3365

national standards). The circuit of a typical EMC fil ter is shown in Figure B.1. CX is the X 3366

capacitor, and CY are the Y capacitors. 3367

3368

Figure B.1 – Typical EMC filter schematic 3369

B.3 The safety issue and solution 3370

When an EMC filter is disconnected from the mains supply line, both the X (Cx) and the Y 3371

(CYa and CYb) capacitors remain charged to the value of the mains supply voltage at the 3372

instant of disconnection. 3373

Due to the nature of sinusoidal waveforms, more than 66 % of the time (30° to 150° and 210° 3374

to 330° of each cycle) the voltage is more than 50 % of the peak voltage. For 230 V mains 3375

(325 Vpeak), the voltage is more than 162 V for more than 66 % of the time of each cycle. So, 3376

the probability of the voltage exceeding 162 V at the time of disconnection is 0 ,66. This 3377

Page 182: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:2019 © IEC 2019 – 183 –

probability represents a good chance that the charge on the X a nd Y capacitors will exceed 3378

162 V. 3379

If a hand or other body part should touch both pins (L1 and L2) of the mains supply plug at 3380

the same time, the capacitors will discharge through that body part. If the total capacitance 3381

exceeds about 0,1 µF, the discharge will be quite painful. 3382

To safeguard against such a painful experience, safety documents require that the capacitors 3383

be discharged to a non-painful voltage in a short period of time. T he short period of time is 3384

taken as the time from the disconnection from the mains to the time when contact with both 3385

pins is likely. Usually, this time is in the range of 1 s to 10 s, depending on the documents and 3386

the type of attachment plug cap installed. 3387

B.4 The requirement 3388

The time constant is measured with an oscilloscope. The time constant and its parameters are 3389

defined elsewhere. 3390

The significant parameters specified in the requirement are the capacitance exceeding 0,1 µF 3391

and the time constant of 1 s or less (for pluggable equipment type A) or 10 s or less (for 3392

pluggable equipment type B). These values bound the measurement. This attachment 3393

addresses pluggable equipment type A and the 1 s time constant requirement. The 3394

attachment applies to pluggable equipment type B and the time constant is changed to 10 s . 3395

Pluggable equipment type A is intended for connection to a mains supply via a non-3396

industrial plug and socket-outlet. Pluggable equipment type B is intended for connection to 3397

a mains supply via an industrial plug and socket-outlet. 3398

The document presumes that measurements made with an instrument having an input 3399

resistance of 95 M to 105 M and up to 25 pF in parallel with the impedance and 3400

capacitance of the equipment under test (EUT) will have negligibl e effect on the measured 3401

time constant. The effect of probe parameters on the determination of the time constant is 3402

discussed elsewhere in this document. 3403

The requirement specifies a time constant rather than a discharge down to a specified voltage 3404

within a specified time interval . If the document required a discharge to a specific voltage, 3405

then the start of the measurement would need to be at the peak of the voltage. This would 3406

mean that the switch (see Figure B.5) would need to be opened almost exactly at the peak of 3407

the voltage waveform. This would require special switching equipment. The time constant is 3408

specified because it can be measured from any point on the waveform (except zero), see 3409

Figure B.4b. 3410

B.5 100 M probes 3411

Table B.1 in this document is a list of readily available oscilloscope probes with 100 M input 3412

resistance and their rated input capacitances (the list is not exhaustive). Also included is a 3413

400 M input resistance probe and a 50 M input resistance probe. 3414

Page 183: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 184 – IEC TR 62368-2:2019 © IEC 2019

Table B.1 – 100 M oscilloscope probes 3415

Manufacturer Input resistance

M

Input capacitance

pF

A 100 1

B 100 6,5

C 100 3

D 400 10 – 13

E 100 2,5

F 50 5,5

3416

Note that the input capacitances of the 100 M probe input capacitances are very much less 3417

than the maximum capacitance of 25 pFs. This attachment will discuss the effect of the probe 3418

capacitance and the maximum capacitance elsewhere. 3419

100 M probes are meant for measuring high voltages, typically 15 kV and more. These 3420

probes are quite large and are awkward to connect to the pins of a power plug. 3421

3422

Figure B.2 – 100 M oscilloscope probes

General purpose oscilloscope probes have 10 M input resistance and 10 pF to 15 pF input 3423

capacitance. General-purpose probes are easier to connect to the pins of the power plug. This 3424

attachment shows that a 10 M, 15 pF probe can be used in place of a 100 M probe. 3425

B.6 The R-C time constant and its parameters 3426

Capacitor charge or discharge time can be expressed by the R -C time constant parameter. 3427

One time constant is the time duration for the voltage on the capacitor to change 63 %. In five 3428

time constants, the capacitor is discharged to almost zero . 3429

Page 184: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:2019 © IEC 2019 – 185 –

Table B.2 – Capacitor discharge 3430

Time constant Percent capacitor voltage (or

charge)

Capacitor voltage

(230 Vrms

, 331 Vpeak

)

0 100 325

1 37 120

2 14 45

3 5 16

4 2 6

5 0,7 2

3431

The values in Table B.2 in this document are given by: 3432

)(

0RC

t

t eVV−

= 3433

where: 3434

tV is the voltage at time t 3435

0V is the voltage at time 0 3436

R is the resistance, in 3437

C is the capacitance, in F (Farads) 3438

t is the time, in s 3439

The time constant is given by the formula: 3440

EUTEUTEUT CRT = 3441

where: 3442

EUTT is the time, in seconds, for the voltage to change by 63 % 3443

EUTR is the EUT resistance, in 3444

EUTC is the EUT capacitance, in F (Farads) 3445

In the equipment under test (EUT), the EUT capacitance, CEUT, in the line filter (Figure B.1) 3446

includes both the X-capacitor and the Y-capacitors. 3447

The two Y-capacitors, CYa and CYb, are in series. The resultant value of two capacitors in 3448

series, CY, is: 3449

YbYa

YbYa

YCC

CCC

+

= 3450

Assuming the two Y-capacitors have the same value, their L1-L2 value is one-half of the value 3451

of one of the capacitors. 3452

The X-capacitor is in parallel with the two Y-capacitors. The EUT capacitance is: 3453

Page 185: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 186 – IEC TR 62368-2:2019 © IEC 2019

YXEUT CCC += 3454

The EUT resistance is the resistance, REUT, in the EUT that is used for discharging the 3455

capacitance. 3456

The time constant, TEUT, in s, is the product of the EUT capacitance in farads and the EUT 3457

resistance in . More useful units are capacitance in µF and resistance in M. 3458

Two parameters of the time constant formula are given by the requirement: EUT capacitance 3459

is 0,1 µF or larger and the EUT time constant does not exceed 1 s. Solving the time constant 3460

formula for EUT resistance: 3461

EUTEUTEUT CTR = 3462

Substituting the values: 3463

1 / 0,1EUTR s F= 3464

10 = MREUT 3465

This means that the EUT resistance is no greater than 10 M if the EUT capacitance is 3466

0,1 µF or greater. The combinations of EUT resistance and EUT capacitance for EUT time 3467

constant of 1 s are shown in Figure B.3 in this document. 3468

Figure B.3 – Combinations of EUT resistance and capacitance for 1 s time constant

Page 186: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:2019 © IEC 2019 – 187 –

B.7 Time constant measurement. 3469

The objective is to measure and determine the EUT time constant. 3470

Measurement of the time constant is done with an oscilloscope connected to th e mains input 3471

terminals of the equipment under test (EUT). Mains is applied to the EUT, the EUT is turned 3472

off, and then the mains is disconnected from the EUT. The EUT is turned off because the 3473

load circuits of the EUT may serve to discharge the EUT capacitance. The resulting 3474

oscilloscope waveform, the AC mains voltage followed by the discharge of the total 3475

capacitance, is shown in Figure B.4 in this document. 3476

Page 187: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 188 – IEC TR 62368-2:2019 © IEC 2019

a) 240 V mains followed by capacitor discharge V = 50 V/div, H = 1 s /div

3477

b) 240 V mains followed by capacitor discharge V = 50 V/div, H = 0,2 s/div

Figure B.4 – 240 V mains followed by capacitor discharge 3478

The time constant is the time duration measured from the instant of disconnection to a point 3479

that is 37 % of the voltage at the instant of disconnection. 3480

The problem is that the process of measurement affects the measured time constant. This is 3481

because the oscilloscope probe has a finite resistance and capacitance , see Figure B.5 in this 3482

document. 3483

Page 188: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:2019 © IEC 2019 – 189 –

Figure B.5 – Time constant measurement schematic 3484

The probe resistance, Rprobe, is in parallel to the EUT resistance, REUT. And, the probe 3485

capacitance, Cprobe, is in parallel with the EUT capacitance, CEUT. 3486

The measured time constant, Tmeasured, is a function of the Thevenin equivalent c ircuit 3487

comprised of Rtotal and Ctotal. The measured time constant is given by: 3488

totaltotalmeasured CRT = 3489

where: 3490

measuredT is the measured time for the voltage to change by 63 % 3491

totalR is the total resistance, both the probe and the EUT 3492

totalC is the total capacitance, both the probe and the EUT 3493

Rtotal is: 3494

EUTprobe

EUTprobe

totalRR

RRR

+

= 3495

Ctotal is: 3496

Combining terms, the measured time constant is: 3497

)()( EUTprobe

EUTprobe

EUTprobe

measured CCRR

RRT +

+

= 3498

In this formula, Tmeasured, Rprobe, and Cprobe are known. Tmeasured is measured with a given 3499

probe. Rprobe and Cprobe are determined from the probe specifications (see examples in 3500

Page 189: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 190 – IEC TR 62368-2:2019 © IEC 2019

Table B.1 in this document). Elsewhere, we shall see that Cprobe is very small and can be 3501

ignored. 3502

EUTtotal CC = 3503

The measured time constant can now be expressed as: 3504

total

EUTprobe

EUTprobe

measured CRR

RRT

+

= )( 3505

B.8 Effect of probe resistance 3506

As has been shown, the EUT discharge resistance, REUT, is 10 M or less in order to achieve 3507

a 1 s time constant with a 0,1 µF capacitor or larger. 3508

Rtotal is comprised of both the EUT discharge resistance REUT, and the probe resistance, 3509

Rprobe. 3510

If REUT is 10 M and CEUT is 0,1 µF, then we know that TEUT is 1 s. If we measure the time 3511

constant with a 100 M probe, the parallel combination of REUT and Rprobe is about 9,1 M 3512

and the measured time constant, Tmeasured, will be: 3513

totaltotalmeasured CRT = 3514

FMTmeasured 1,01,9 = 3515

sTmeasured 91,0= 3516

So, for a CEUT of 0,1 µF capacitance and a REUT of 10 M, a measured time constant (using 3517

a 100 M probe), Tmeasured, of 0,91 s would indicate a EUT time constant, TEUT, of 1 s. 3518

If we substitute a 10 M probe for the same measurement, then Rtotal, the parallel 3519

combination of REUT (10 M) and Rprobe (10 M), is 5 M. The measured time constant, 3520

Tmeasured, will be: 3521

totaltotalmeasured CRT = 3522

FMTmeasured 1,05 = 3523

sTmeasured 5,0= 3524

So, for a CEUT of 0,1 µF capacitance and a REUT of 10 M, the measured time constant 3525

(using a 10 M probe), Tmeasured, is 0,5 s and would indicate a EUT time constant, TEUT, of 1 3526

s. 3527

B.9 Effect of probe capacitance 3528

According to the document, CEUT is 0,1 µF or more. Also, according to the document, Cprobe 3529

is 25 pF or less. Assuming the worst case for Cprobe, the total capacitance is: 3530

Page 190: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:2019 © IEC 2019 – 191 –

EUTprobetotal CCC += 3531

uFuFCtotal 1,0000025,0 += 3532

uFCtotal 100025,0= 3533

The worst-case probe capacitance is extremely small (0,025 %) compared to the smallest 3534

CEUT capacitance (0,1 µF) and can be ignored. We can say that: 3535

EUTtotal CC = 3536

B.10 Determining the time constant 3537

According to the document, TEUT may not exceed 1 s. 3538

1=EUTT 3539

EUTEUT CR =1 3540

where: 3541

EUTR is 10 M or less 3542

EUTC is 0,1 µF or more 3543

The problem is to determine the values for REUT and CEUT. Once these values are known, the 3544

equipment time constant, TEUT, can be determined by calculation. 3545

As shown in Figure B.1 in this document, REUT can be measured directly with an ohmmeter 3546

applied to the mains input terminals, i.e., between L1 and L2. Care is taken that the 3547

capacitances are fully discharged when the resistance measurement is made. Any residu al 3548

charge will affect the ohmmeter and its reading. Of course, if the circuit is provided with a 3549

discharge resistor, then the capacitances will be fully discharged. If the circuit does not have 3550

a discharge resistor, then the ohmmeter will provide the disch arge path, and the reading will 3551

continuously increase. 3552

CEUT can also be measured directly with a capacitance meter. Depending on the particular 3553

capacitance meter, REUT may prevent accurate measurement of CEUT. For the purposes of 3554

this paper, we assume that the capacitance meter cannot measure the CEUT. In this case, we 3555

measure the time constant and compensate for the probe resistance. 3556

So, the time constant is measured, and the probe resistance is accounted for. 3557

Since probe resistance is more or less standardized, we can calculate curves for 100 M and 3558

10 M probes for all maximum values of REUT and CEUT. The maximum values for 3559

combinations of REUT, CEUT (Ctotal), Rprobe, Rtotal and Tmeasured are given in Table B.3 in this 3560

document. (Rprobe and Rtotal values are rounded to 2 significant digits.) 3561

Page 191: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 192 – IEC TR 62368-2:2019 © IEC 2019

Table B.3 – Maximum Tmeasured values for combinations of REUT 3562

and CEUT for TEUT of 1 s 3563

TEUT

s

CEUT

(Ctotal

)

µF

REUT

M

Rprobe

M

Rtotal

M

Tmeasured

s

1 0,1 10 100 9,1 0,91

1 0,2 5 100 4,8 0,95

1 0,3 3,3 100 3,2 0,97

1 0,4 2,5 100 2,4 0,97

1 0,5 2 100 2,0 0,98

1 0,6 1,7 100 1,6 0,98

1 0,7 1,4 100 1,4 0,99

1 0,8 1,25 100 1,2 0,99

1 0,9 1,1 100 1,1 0,99

1 1,0 1 100 1,0 0,99

1 0,1 10 10 5,0 0,50

1 0,2 5 10 3,3 0,67

1 0,3 3,3 10 2,5 0,75

1 0,4 2,5 10 2,0 0,80

1 0,5 2 10 1,7 0,83

1 0,6 1,7 10 1,4 0,86

1 0,7 1,4 10 1,25 0,88

1 0,8 1,25 10 1,1 0,89

1 0,9 1,1 10 1,0 0,90

1 1,0 1 10 0,91 0,91

3564

For each value of REUT and Rprobe we can calculate the worst-case measured time constants, 3565

Tmeasured for a TEUT of 1 s. These are shown in Figure B.6 in this document. 3566

The process is: 3567

– With the unit disconnected from the mains and the power switch “off,” measure the 3568

resistance between the poles of the EUT. Repeat with the power switch “on” as the filter 3569

may be on the load side of the power switch. Select the higher value as REUT. 3570

– Connect the oscilloscope probe between L1 and L2 as shown in Figure B.5 in this 3571

document. For safety during this test, use a 1:1 isolating transformer between the mains 3572

and the EUT. Set the scope sweep speed to 0 ,2 ms per division (2 s full screen). 3573

– When the display is about 1 or 2 divisions from the start, turn the test switch off, and 3574

measure the time constant as shown in Figure B.4 in this document. This step may need 3575

to be repeated several times to get a suitable waveform on the oscilloscope. This step 3576

should be performed twice, once with the EUT power switch “o ff” and once with the EUT 3577

power switch “on.” Select the maximum value. This value is Tmeasured. 3578

– Plot REUT and Tmeasured on the chart, Figure B.6 in this document. 3579

If the point is below the curve of the probe that is used to meas ure the time constant, then the 3580

EUT time constant, TEUT, is less than 1 s. 3581

Page 192: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:2019 © IEC 2019 – 193 –

3582

Figure B.6 – Worst-case measured time constant values for 100 M and 10 M probes 3583

B.11 Conclusion 3584

Measurement of the time constant can be made with any probe, not just a 100 M probe. 3585

Ideally, the probe input resistance should be at least equal to the worst -case EUT discharge 3586

resistance (10 M for pluggable equipment type A) or higher. The effect of the probe input 3587

resistance is given by the equation for Rtotal. 100 M probes, while approaching ideal in terms 3588

of the effect on the measured time constant, are bulky an d expensive and not necessary. 3589

The document is a bit misleading by ignoring a 9 % error when a 100 M probe is used to 3590

measure the time constant associated with a 10 M discharge resistor (see Figure B.5 in this 3591

document). 3592

3593

Page 193: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 194 – IEC TR 62368-2:2019 © IEC 2019

Annex C 3594

(informative) 3595

3596

Background information related to resistance to candle flame ignition 3597

In line with SMB decision 135/20, endorsing the ACOS/ACEA JTF recommendations, the 3598

former Clause 11 was added to the document up to CDV stage. However, the CDV was 3599

rejected and several national committees indicated that they wanted to have the requirements 3600

removed from the document. At the same time, several countries indicated that they wanted 3601

the requirements to stay, while others commented that they should be limited to CRT 3602

televisions only. 3603

IEC TC 108 decided to publish the requirements as a separate document so that the different 3604

issues can be given appropriate consideration. 3605

3606

3607

Page 194: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

IEC TR 62368-2:2019 © IEC 2019 – 195 –

Bibliography 3608

IEC 60065:2014, Audio, video and similar electronic apparatus – Safety requirements 3609

IEC 60215, Safety requirements for radio transmitting equipment – General requirements and 3610

terminology 3611

IEC 60364-4-43, Low-voltage electrical installations – Part 4-43: Protection for safety – 3612

Protection against overcurrent 3613

IEC 60364-5-52, Low-voltage electrical installations – Part 5-52: Selection and erection of 3614

electrical equipment – Wiring systems 3615

IEC 60364-5-54, Low-voltage electrical installat ions – Part 5-54: Selection and erection of 3616

electrical equipment – Earthing arrangements and protective conductors 3617

IEC 60446, Identification by colours or numerals 2 3618

IEC TS 60479-2, Effects of current on human beings and livestock – Part 2: Special aspects 3619

IEC 60664-2 (all parts), Insulation coordination for equipment within low -voltage systems – 3620

Part 2: Application guide 3621

IEC 60664-4:2005, Insulation coordination for equipment within low -voltage systems – Part 4: 3622

Consideration of high-frequency voltage stress 3623

IEC 60695-2 (all parts), Fire hazard testing – Part 2: Glowing/hot-wire based test methods 3624

IEC 60695-2-13, Fire hazard testing – Part 2-13: Glowing/hot-wire based test methods – 3625

Glow-wire ignition temperature (GWIT) test method for materials 3626

IEC 60695-11-2, Fire hazard testing – Part 11-2: Test flames – 1 kW nominal pre-mixed flame 3627

– Apparatus, confirmatory test arrangement and guidance 3628

IEC 60950-1:2005, Information technology equipment – Safety – Part 1: General requirements 3629

IEC 60950-1:2005/AMD1:2009 3630

IEC 60950-1:2005/AMD2:2013 3631

IEC 61010-1, Safety requirements for electrical equipment for measurement, control, and 3632

laboratory use – Part 1: General requirements 3633

IEC 61051-1, Varistors for use in electronic equipment – Part 1: Generic specification 3634

ISO/IEC Guide 51:1999, Safety aspects — Guidelines for their inclusion in standards 3635

ITU-T K.21:2008, Resistibility of telecommunication equipment installed in customer premises 3636

to overvoltages and overcurrents 3637

EN 41003:2008, Particular safety requirements for equipment to be connected to 3638

telecommunication networks and/or a cable distribution system 3639

EN 60065:2002, Audio, video and similar electronic apparatus – Safety requirements 3640

___________

2 This publication was withdrawn.

Page 195: Blank IEC form - ulstandards.ul.com...178 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in 179 the latter. 180 5) IEC

– 196 – IEC TR 62368-2:2019 © IEC 2019

NFPA 70, National Electrical Code 3641

NFPA 79:2002, Electrical Standard for Industrial Mach inery 3642

UL 1667, UL Standard for Safety Tall Institutional Carts for Use with Audio -, Video-, and 3643

Television-Type Equipment 3644

UL 1995, UL Standard for Safety for Heating and Cooling Equipment 3645

UL 2178, Outline for Marking and Coding Equipment 3646

UL 60065, Audio, Video and Similar Electronic Apparatus – Safety Requirements 3647

UL/CSA 60950-1, Information Technology Equipment – Safety – Part 1: General 3648

Requirements 3649

CAN/CSA C22.1, Information Technology Equipment – Safety – Part 1: General Requirements 3650

CSA C22.1-09, Canadian Electrical Code – Part I: Safety Standard for Electrical Installations 3651

– Twenty-first Edition 3652

ASTM C1057, Standard Practice for Determination of Skin Contact Temperature from Heated 3653

Surfaces Using A Mathematical Model and Thermesthesiometer 3654

EC 98/37/EC Machinery Directive 3655

3656

_____________ 3657

3658