    HANDLING OFBOILERDURINGEMERGENCIES

  • 8/2/2019 Boiler Emergancy

    3/35

    BOILER EMERGENCIES

    1)ONE ID FAN TRIPPED

    2)ONE FD FAN TRIPPED

    3)BOTH ID FANS TRIPPED

    4) BOTH FD FANS TRIPPED

    5) ONE PA FAN TRIPPED 6) BOTH PA FANS TRIPPED

  • 8/2/2019 Boiler Emergancy

    4/35

    7) COAL MILL TRIPPED

    8)DRUM LEVEL VERY LOW

    9)DRUM LEVEL VERY HIGH

    10) ONE BFP TRIPPED

    11)BOTH BFP TRIPPED 12) FURNACE DRAFT VERY LOW

    13) FURNACE DRAFT VERY HIGH

  • 8/2/2019 Boiler Emergancy

    5/35

  • 8/2/2019 Boiler Emergancy

    6/35

    HANDLING OF BOILER DURING EMERGENCY

    EMERGENCY OPERATIONS

    Major emergency situations in Boiler and

    Auxiliary areas and suggested actions:

    1. High Furnace Pressure

    Probable Reasons:

    One I.D. fan tripped or maloperation of control

    vanes of I.D,F.D,P.A. fans or closing of damper.

    Unstable furnace flame condition, Sudden

    starting of coal mill, Low windbox pressure

    nder normal F.D. fans loading conditions),

    proper air distribution at elevations.

    Un-equal burner tilts at corners or Burner tilt in

    extreme up or Down.

    Fouling in Air heater, Air heater tripped.

    Furnace water seal broken, ES.P. or flue gas path

    manhole opened.

    Water wall tube rupture/leakage.

  • 8/2/2019 Boiler Emergancy

    7/35

  • 8/2/2019 Boiler Emergancy

    8/35

    Action to be taken:See that two mills are tripped or

    otherwise trip them.Take running I.D. fans control onmanual & increase for loading. Checkthe cause of I.D. fan tripping and try torestart it, if everything is normal. Checkgas dampers indication & draft readingalong flue gas path. If some damper isclosed try to open that damper.

    Take F.D. / P.A. fan control onmanual. Check control damperoperation. Adjust air flow.

  • 8/2/2019 Boiler Emergancy

    9/35

    Action to be taken:Check air for correct flow. Check com bustionregime, openings of Auxiliary air and fuel airdam pers. wind box p ressure. See cold air andhot air dampers. Watch Furnace flame. TripBoiler if flam e is very much unstable. Purge outexplosive m ixture by maintaining h igh air flow .

    Check Burner tilt at all corners is equal.Adjust Burner tilt between + 10 to -10 andcheck control air pressure.

    See air-preheaters are rotating. Restarttripped air preheater and do A .H. soot blowing.

    Check Furnace seal, water flow through sealtrough overflow. Re-establish seal.

    Stop the boiler in case of tube leakage assoon as possible.

  • 8/2/2019 Boiler Emergancy

    10/35

    2. Furnace Pressure LowProbable Reasons:

    I.D. fan auto control

    failure. I.D. fan vane controlmechanism failure causingvanes to open wide

    Sudden decrease in airinput or tripping of one F.D.fan.

    Sudden tripping of one ormore mills or choking of

    mills/raw coal feeder pipe .

    Partial flame failure

  • 8/2/2019 Boiler Emergancy

    11/35

    Action to be taken

    Take I.D. fans control on manual &reduce load on I.D. fans

    Check I.D. fan control mechanism forproper functioning.

    Check air flow, correct if necessary. Afterchecking restart F.D. fan if it had tripped.

    Control the furnace pressure by adjustingI.D. fan vanes. Simultaneously try standbymill. Remove the choking of affected mill /Raw coal feed pipe.

    Take the oil gun i.nto service to establishflame that locations / corner.

    See the proper functioning of secondary airpath damper.

    l

  • 8/2/2019 Boiler Emergancy

    12/35

    3. Drum Level Low

    Probable Reasons:

    Mal-operation of Feed Auto Control or

    Feed Regulator or Scoop auto.

    Tripping of one of working feed pump

    (standby pump does not start).

    Sudden reduction of load.

    Sudden increase in firing e.g. starting of

    mills having sufficient coal left before

    previous stopping.

    Tube rupture/puncture.

    Inadvertent opening of low point drain

    valves or Emergency drum drain valve.

    A i b k

  • 8/2/2019 Boiler Emergancy

    13/35

    Action to be taken:

    Take feed control valve on

    manual and increase feeding

    rate. Take scoop tube controlon hand increase scoop tube

    position.

    Check that water flow through

    each pump does not exceed

    capacity. Check feed watercontrol valve and tube control

    linkages.

    Starts reserve feed pump on

    tripping of running feed pump,if auto starting fails.

    Try to increase the load if not

    possible, reduce firing rate

    accordingly to control drumpressure.

    A ti t b t k

  • 8/2/2019 Boiler Emergancy

    14/35

    Action to be taken:

    Reduce firing rate by suitablyadjusting the feed rate ofrunning mills. Check water flow andcompare with previous feedingrate and steam flow. High feedflow indicates tube failure.Inspect waterwall and

    economizer or any tubeleakage,If tube leakage observed stopthe boiler as soon as possible,. Check drum drains and, low

    point drains for closing.

    Note: If drum level goes belowgauge glass and low drum leveltrip protection fails, trip boiler

    at on low level.

  • 8/2/2019 Boiler Emergancy

    15/35

    4. High Drum Level

    Probable Reasons:

    Mal-operation of feed watercontrol

    Sudden increase in load

    resulting in drum pressuredrop.

    Sudden decrease in firing

    rate e.g. tripping of the

    running mills . B.F.P. scoop

    tube position suddenly

    increased

    A ti t b t k

  • 8/2/2019 Boiler Emergancy

    16/35

    Action to be taken:

    Take feed control valve on

    manual and reduce feedingrate.

    Try to decrease the load as

    far as possible.

    Increase feeding range of

    running mills.

    Check differential pressureacross feed control valve and

    maintain 5 Kg / cm2 by

    adjusting scoop tube position.

    5 Flame Failure At anElevvation

  • 8/2/2019 Boiler Emergancy

    17/35

    5. Flame Failure At anElevvation

    Probable Reasons:

    Closing of trip valves on H.O./ W.U. Oil

    / Igniter (Causing loss of ignitionsupport energy) Where F.O. is beingused as support fuel or when only oil isbeing used.

    Sudden decrease of mill feeder speedsto minimum.

    Too low or too high windbox pressurecausing unstable combustion.

    Water wall tube failure.

    Malfunction of flame scanners due to

    supply failure or scanner air failure, slagor soot onscanner lenses etc.

    Burner tilt mechanism negativeextreme due to air failure to powercylinders.

    Rapid load changes without adjusting

    airflow leading to improper combustion.

    Action to be taken

  • 8/2/2019 Boiler Emergancy

    18/35

    Action to be taken:

    Do not attempt to introduce igniters oroil guns at elevation where No flamecondition persist.

    Trip out the coal mills of feedingelevation where No flame conditions ispersisting. Allow sometime for purgingthen introduce oil support adjacent toworking mills until furnaceflame is stabilized.

    Check that secondary air wind boxdampers are modulating to maintainabout 80m.m.wcwind box to furnace differentialpressure.

    Check furnace for tube failure.

    If two elevations scanners show Noflame trip the boiler manually

    Check burner tilt keep it between /+10 .

    Check furnaces flame condition.

  • 8/2/2019 Boiler Emergancy

    19/35

    6.0ne Fan Trips (Other in Service)

    Probable Reasons:

    It Is presumed that ID, FD, PA

    fan de-interlocking switches areon Interlock position.

    Fan Bearing temperature, highand/or

    Fan motor Bearing temperaturehigh and/or

    Lube oil pressure for motorbearings low and/or

    Corresponding Air heatertripped (provided de-inter lockingswitch is on Interlock position)and/or.

    Motor protection operated.

    Action to be taken

  • 8/2/2019 Boiler Emergancy

    20/35

    Action to be taken:

    Takes draft control or manual, and / orincrease the loading on running fan and

    maintain furnace draft.

    Check corresponding fan is trippedthrough interlock.

    Take secondary airflow controls onmanual and maintain correct airflow.

    Cut in oil burner adjacent to workingmills. .

    Check drum level is controlled on autoif necessary, take drum level control On

    manual and maintain level.

    Check pulverizers in excess of 3 aretripped starting from bottom.

    Check that the load on the generatorhas reduced to 100 - 120 MW (partial

    load relay energized).

  • 8/2/2019 Boiler Emergancy

    21/35

    Check that interconnecting

    dampers on air and flue gas side

    open and tripped fans are

    correctly isolated through

    interlocks.

    Check windbox pressure left and

    right is maintained normal (about

    75 mmwc).

    Maintain steam temperature.

    Check furnace flames condition.

    Check that tripped pulverizers

    are correct isolated (hot air gatesclose, cold air dampers come to

    minimum).

    Investigate the cause of trip.

    Correct it & restart the tripped fan.

  • 8/2/2019 Boiler Emergancy

    22/35

    7. One Feeder Trips

    Probable Reasons:

    Support energy is removedwithin 3 minutes of feederand/or.

    No. coal flow alarm comes& low current relay picks upsimultaneously. (Feeder

    shear pin given way) and/or.

    Mill trips and/or.

    Feeder motor supply fails.

  • 8/2/2019 Boiler Emergancy

    23/35

    Action to be taken:

    Check that hot air gate closes & cold air

    damper opens full if pulverizer is running.

    Clear the mill of the coal before stopped.

    Stop the pulverizer if feeder cannot be

    restarted immediately.

    Check that running mills share the loading,

    thermal load is on auto.

    Reduce the load on generator and, maintainsteam parameters.

    If 3 mills at less than 50% feeder speed or

    2 mills are left in service, cut in oil gun

    adjacent to working mills.

    Check furnace draft, airflow and drum level

    is normal.

    Check flame is stable and scanners sense

    Flame on.

    Check that associated elevation fuel air

    damper close and windbox pressure is

    maintained 70 mmwc.

  • 8/2/2019 Boiler Emergancy

    24/35

    8. One Mill Trills

    Probable Reasons:

    Mill discharge valves areclosed and/or

    Loss of elevation D.c.supply for more than 2 secs

    and lor

    Support ignition energy isremoved with 3 minutes offeeder starting and / or .

    Motor protection operatesand / or

    One P.A. Fan trips (mill inexcess of 3 will trip starting

    from bottom).

  • 8/2/2019 Boiler Emergancy

    25/35

    Action to be taken:

    Check the running mills sharethe load if thermal load control ofmills is on auto.

    Reduce the generator load ifpressure starts dropping.

    Start reserve mill and take load.

    Check furnace draft is maintainenormal.

    Check the correct airflow ismaintained.

    Check that drum level ismaintained normal.

    Check that tripped mill isisolated (hot air gate closed, coldair damper minimum open,feeder tripped).

  • 8/2/2019 Boiler Emergancy

    26/35

    9. Hang-up in Mill

    Probable Reasons:

    Choking of coal atinlet to mill. H-ighmoisture in coal and /

    or

    Too much fineness incoal with moisture and/ or

    Foreign material atRC feeder inlet

    Action to be taken

  • 8/2/2019 Boiler Emergancy

    27/35

    Action to be taken:

    Check feeder trip on No Coal

    flow & low current protection.

    Check mill outlet temperature

    is less than 85C.

    Check mill hot air gate closes

    on mill outlet temperature high

    protection. Close hot air gate

    and check mill.

    Cold air damper opens full.

    Check the flame condition at

    the sick mill elevation.

    Trip the sick mill after

    clearing it coals.

  • 8/2/2019 Boiler Emergancy

    28/35

    Increase the load on

    running mills if the thermalload control is on manual.

    Start reserve mill.

    Maintain steam pressure

    and temperature by reducing

    load.

    Check that furnace draft

    and airflow are normal.

    If 3 mills (or less) are inservice with speed below

    50% take oil support atelevation adjacent to running

    mills in service.

  • 8/2/2019 Boiler Emergancy

    29/35

    10. Water Wall Tube Leakage

    Probable Reasons:

    Starved water walls due to very

    low drum level and/or

    Sustained flame impingementon water wall tubes and / or

    Blocked tube, scaling of tube,

    resulting in overheating of tube

    Metal, pitting, corrosion of tubesand/or

    Soot blower steam impingement

    (wet steam impingement or directimpingement of steam)and/or

    Circulation affected due toopening of low point drains.

    Action to be taken:

  • 8/2/2019 Boiler Emergancy

    30/35

    Action to be taken:

    Compare feed water flow andsteam flow, assess the

    magnitude of tube leakage.

    Maintain drum level byincreasing feed water flow.

    Inspect the furnace for tubeleakage.

    If the tube leakage is minutethen take the unit out as a

    planned shutdown to cold.

    If tube leakage is heavy & itis likely to damage other tubesor likely to disturb the flame

    stability trip out the unit.

  • 8/2/2019 Boiler Emergancy

    31/35

    Keep close watch in

    furnace flame.

    As the load is beingreduced try to locate

    burst tubes.

    Check economizer

    hoppers for water

    leakage steam noise

    etc. every shift.

    Check that furnace

    draft is maintained

    normal.

    11 Reheater /SuDerheater /

  • 8/2/2019 Boiler Emergancy

    32/35

    11. Reheater/SuDerheater /

    Economizer Tube Failure

    Probable Reasons:

    Sustained high metaltemperature due to waterwall

    Slagging or forcing boiler at the

    time of hot restart and / or

    Erosion on tubes due to highexcess air, high ash content in

    coal, dislocated tubes, soot

    blowing and/or

    Blocked tubes causingoverheating and/or

    S lt d iti d t hi h

  • 8/2/2019 Boiler Emergancy

    33/35

    Salt deposition due to high

    water level in drum. poor

    quality of water and/or

    Inadequpte flow due to open

    Superheater, Reheater drain

    and / or

    Fire side corrosion of tubesand / or

    Economizer tube can fail due

    to over heating if concentrationof Fe, Cu is more in feed water,

    Steaming in economizer occurs

    causing salt deposition and

    harming the tubes.

  • 8/2/2019 Boiler Emergancy

    34/35

    Action to be taken:

    As soon as leakage isdetected start load

    reduction and trip out

    the boiler at theearliest possible time.

    Try to locate leakthrough manholesbefore boiler isdepressurized.