EFFECTIVE BOILER WATER
SYSTEM PROTECTION
Presented by
Paul R. Puckorius
Puckorius & Associates, Inc
December 7, 2010
Presented by Process Heating
![Page 3: Boiler Water System Protection Ppt Puckorius201012](https://reader033.vdocument.in/reader033/viewer/2022050816/55219d85497959b2608b4618/html5/thumbnails/3.jpg)
For an Effective Webinar Experience
Disable Pop-up Blocker
Technical Help link or email
Download & print slides
Enlarge slides for better viewing
Invite a friend to join us
Submit a Question
Resources
Archive
www.process-heating.com – Add to your favorites
![Page 4: Boiler Water System Protection Ppt Puckorius201012](https://reader033.vdocument.in/reader033/viewer/2022050816/55219d85497959b2608b4618/html5/thumbnails/4.jpg)
EFFECTIVE BOILER WATER
SYSTEM PROTECTION
Presented by
Paul R. Puckorius
Puckorius & Associates, Inc
December 7, 2010
Presented by Process Heating
![Page 5: Boiler Water System Protection Ppt Puckorius201012](https://reader033.vdocument.in/reader033/viewer/2022050816/55219d85497959b2608b4618/html5/thumbnails/5.jpg)
THIS WEBINAR WILL
COVER THESE TOPICS
LOW PRESSURE BOILERS- < 900 psi
WHAT WATER QUALITY IS NEEDED
HOW TO PROTECT THE BOILER
WHAT TREATMENTS WORK WELL
WHAT CONTROLS ARE IMPORTANT
![Page 6: Boiler Water System Protection Ppt Puckorius201012](https://reader033.vdocument.in/reader033/viewer/2022050816/55219d85497959b2608b4618/html5/thumbnails/6.jpg)
![Page 7: Boiler Water System Protection Ppt Puckorius201012](https://reader033.vdocument.in/reader033/viewer/2022050816/55219d85497959b2608b4618/html5/thumbnails/7.jpg)
HOW TO PROTECT YOUR
BOILER
Feed it Good Quality Water
Maintain Good Water Treatment Control
Handle Varying Steam Demand
Handle Startup and Shut Down Properly
Protect Boiler When it is Layed Up
![Page 8: Boiler Water System Protection Ppt Puckorius201012](https://reader033.vdocument.in/reader033/viewer/2022050816/55219d85497959b2608b4618/html5/thumbnails/8.jpg)
Objectives of Boiler Water
Treatment Program To Prevent Deposits on Boiler Tubes
To Prevent Corrosion of all Metals in Entire Boiler Cycle
To Produce Good Steam Quality for all Uses at all Times
To Prevent Boiler Tube Failures
To Properly Startup, Shut Down, & Layup Boilers
![Page 9: Boiler Water System Protection Ppt Puckorius201012](https://reader033.vdocument.in/reader033/viewer/2022050816/55219d85497959b2608b4618/html5/thumbnails/9.jpg)
An Effective Boiler Water
Treatment Program Prevent Deposits on Boiler Surfaces
(causes loss of heat transfer & weakens
metal due to over heating)
Prevent Oxygen Corrosion (causes
pitting of boiler tubes & rust deposits)
Prevent low pH (below 9 will cause
corrosion and produce red water)
Prevent condensate contamination (may
result in iron, copper, & oil into boiler)
Produce Acceptable Steam Quality
![Page 10: Boiler Water System Protection Ppt Puckorius201012](https://reader033.vdocument.in/reader033/viewer/2022050816/55219d85497959b2608b4618/html5/thumbnails/10.jpg)
![Page 11: Boiler Water System Protection Ppt Puckorius201012](https://reader033.vdocument.in/reader033/viewer/2022050816/55219d85497959b2608b4618/html5/thumbnails/11.jpg)
WHAT IS GOOD QUALITY
WATER?
Provides Efficient Equipment Operation
Increases Life Expectancy & ROI
Optimizes Water Use and Waste
Cost Effective Programs
Reduces Maintenance and Labor
![Page 12: Boiler Water System Protection Ppt Puckorius201012](https://reader033.vdocument.in/reader033/viewer/2022050816/55219d85497959b2608b4618/html5/thumbnails/12.jpg)
GOOD QUALITY WATER
DEPENDS UPON
Boiler Pressure
Boiler Operation
Boiler Design
Consistent & Effective Makeup Water
![Page 13: Boiler Water System Protection Ppt Puckorius201012](https://reader033.vdocument.in/reader033/viewer/2022050816/55219d85497959b2608b4618/html5/thumbnails/13.jpg)
ASME Boiler WaterGuidelinesNo Superheaters & Turbines
Steam Purity 1 ppm Maximum
0-300 psig 301-600 psig
SiO2 <150 <90
T. Alkalinity; ppm <1000 <850
OH Alkalinity; ppm NS NS
Mmho <7000 <5500
![Page 14: Boiler Water System Protection Ppt Puckorius201012](https://reader033.vdocument.in/reader033/viewer/2022050816/55219d85497959b2608b4618/html5/thumbnails/14.jpg)
ASME Boiler Water GuidelinesFiretube Boilers
1 ppm TDS Maximum Steam Purity
0 to 300 psig
SiO2; ppm <150
T. Alkalinity; ppm <700
OH Alkalinity; ppm NS
Mmho <7000
![Page 15: Boiler Water System Protection Ppt Puckorius201012](https://reader033.vdocument.in/reader033/viewer/2022050816/55219d85497959b2608b4618/html5/thumbnails/15.jpg)
ASME Boiler Water GuidelinesWatertube Boilers
With Super heaters/ Turbines
SiO2 Total Alk. OH Alk. Mmho
0-300 <150 <350 NS 5400-1100
301-450 <90 <300 NS 4600-900
451-600 <40 <250 NS 3800-800
601-750 <30 <200 NS 1500-300
751-900 <20 <150 NS 1200-200
901-1000 <8 <100 NS 1000-200
1001-1500 <2 NS NS <150
1501-2000 <1 NS NS <80
![Page 16: Boiler Water System Protection Ppt Puckorius201012](https://reader033.vdocument.in/reader033/viewer/2022050816/55219d85497959b2608b4618/html5/thumbnails/16.jpg)
ABMA Boiler Water Limits
BW TDS Steam TDS TSS FCO
0-300 psig 3500 1.0 15 0.0003
301-450 psig 3000 1.0 10 0.0003
451-600 psig 2500 1.0 8 0/0004
601-750 psig 1000 0.5 3 0.0005
751-900 psig 750 0.5 2 0.0006
901-1000 psig 625 0.5 1 0.0007
1001-1800 psig 100 0.1 1 0.001
1801-2350 psig 50 0.1 1 0.002
2351-2600 psig 25 0.05 1 0.002
2601-2900 psig 15 0.05 1 0.003
![Page 17: Boiler Water System Protection Ppt Puckorius201012](https://reader033.vdocument.in/reader033/viewer/2022050816/55219d85497959b2608b4618/html5/thumbnails/17.jpg)
TYPICAL BOILER SYSTEM
Boiler
Steam
Uses
Deaerator
Makeup
System
SteamCondensate Makeup
Boiler
Feedwater
Boiler
Feedwater Pump
Losses
Losses
Blowdown
![Page 18: Boiler Water System Protection Ppt Puckorius201012](https://reader033.vdocument.in/reader033/viewer/2022050816/55219d85497959b2608b4618/html5/thumbnails/18.jpg)
![Page 19: Boiler Water System Protection Ppt Puckorius201012](https://reader033.vdocument.in/reader033/viewer/2022050816/55219d85497959b2608b4618/html5/thumbnails/19.jpg)
FIRE TUBE BOILER
![Page 20: Boiler Water System Protection Ppt Puckorius201012](https://reader033.vdocument.in/reader033/viewer/2022050816/55219d85497959b2608b4618/html5/thumbnails/20.jpg)
Firetube Boilers
Heat on Inside of Tubes
Water on Outside of Tubes
Advantages
– Suitable for low pressure operation
– Reliable
– Low Space Requirements
![Page 21: Boiler Water System Protection Ppt Puckorius201012](https://reader033.vdocument.in/reader033/viewer/2022050816/55219d85497959b2608b4618/html5/thumbnails/21.jpg)
Firetube Boilers
Disadvantages
– Limited pressure; ~300 psig
– Relatively poor steam quality; small
steam release space
![Page 22: Boiler Water System Protection Ppt Puckorius201012](https://reader033.vdocument.in/reader033/viewer/2022050816/55219d85497959b2608b4618/html5/thumbnails/22.jpg)
![Page 23: Boiler Water System Protection Ppt Puckorius201012](https://reader033.vdocument.in/reader033/viewer/2022050816/55219d85497959b2608b4618/html5/thumbnails/23.jpg)
WATER TUBE BOILER-TYPE D
![Page 24: Boiler Water System Protection Ppt Puckorius201012](https://reader033.vdocument.in/reader033/viewer/2022050816/55219d85497959b2608b4618/html5/thumbnails/24.jpg)
Watertube Boilers
Water on Inside of Tubes
Heat in Furnace Surrounding Tubes
Various Types/Designs
– “A” Type
– “O” Type
– “D” Type
– “L” Type
“Unlimited” Pressure
Good Steam Quality
![Page 25: Boiler Water System Protection Ppt Puckorius201012](https://reader033.vdocument.in/reader033/viewer/2022050816/55219d85497959b2608b4618/html5/thumbnails/25.jpg)
Watertube Boilers
+ Advantages –
-Suitable for High Pressures
-Reliable
-Excellent Steam Quality
+Disadvantages
-Large Space Required
-Requires Very Good Water Quality
-Sensitive to Deposits/Corrosion
![Page 26: Boiler Water System Protection Ppt Puckorius201012](https://reader033.vdocument.in/reader033/viewer/2022050816/55219d85497959b2608b4618/html5/thumbnails/26.jpg)
PROTECTING BOILER
FROM CORROSION
Boilers are Made of Carbon Steel
Must Form a Protective Coating
Coating is a Form of Iron Oxide
Coating is Called Magnetite
Coating is Black and Hard and Thin
![Page 27: Boiler Water System Protection Ppt Puckorius201012](https://reader033.vdocument.in/reader033/viewer/2022050816/55219d85497959b2608b4618/html5/thumbnails/27.jpg)
HOW TO FORM MAGNETITE
Remove Oxygen to Zero in Boiler
Raise pH of Boiler Water above 10
Prevent all Deposits on Boiler Surface
Carry a High Hydrate Alkalinity in Boiler
![Page 28: Boiler Water System Protection Ppt Puckorius201012](https://reader033.vdocument.in/reader033/viewer/2022050816/55219d85497959b2608b4618/html5/thumbnails/28.jpg)
MAGNETITE- WELL PROTECTED BOILER TUBES
![Page 29: Boiler Water System Protection Ppt Puckorius201012](https://reader033.vdocument.in/reader033/viewer/2022050816/55219d85497959b2608b4618/html5/thumbnails/29.jpg)
DEPOSIT CONTROL
METHODS
Remove Before Boiler- Known as
External Treatment of Makeup Water
Condition Potential Water Deposits in
the Boiler- Known as Internal treatment
of Boiler Water
![Page 30: Boiler Water System Protection Ppt Puckorius201012](https://reader033.vdocument.in/reader033/viewer/2022050816/55219d85497959b2608b4618/html5/thumbnails/30.jpg)
BOILER WATER DEPOSIT
CONTROL – EXTERNAL
VERY COMMON Sodium Zeolite Softening- removes only
the hardness
Cold /Hot Lime Softening- removes
hardness, some alkalinity, and some
dissolved solids
Demineralizers- removes Everything
Reverse Osmosis- removes Everything
![Page 31: Boiler Water System Protection Ppt Puckorius201012](https://reader033.vdocument.in/reader033/viewer/2022050816/55219d85497959b2608b4618/html5/thumbnails/31.jpg)
BOILER DEPOSIT CONTROL–
INTERNAL METHOD-
KEEPING DEPOSITS SOLUBLE
Specialty Chemicals such as
Phosphonates, and Polymers- Very
Common in Boilers Operating at <600 psi
Previous Chemicals used were Chelants
such as EDTA and NTA- Not very common
currently due to Corrosion Concerns
![Page 32: Boiler Water System Protection Ppt Puckorius201012](https://reader033.vdocument.in/reader033/viewer/2022050816/55219d85497959b2608b4618/html5/thumbnails/32.jpg)
BOILER DEPOSIT CONTROL–
INTERNAL METHOD-
KEEPING DEPOSITS SOLUBLE
Often requires low hardness Feed Water
+ Usually less that 2 ppm hardness needed
+ If higher Hardness, Costs for WT higher
Produces a much Cleaner Boiler
+ Due to Solubilized Hardness- no Sludge
+ Maximizes Boiler Heat Transfer
![Page 33: Boiler Water System Protection Ppt Puckorius201012](https://reader033.vdocument.in/reader033/viewer/2022050816/55219d85497959b2608b4618/html5/thumbnails/33.jpg)
BOILER DEPOSIT CONTROL–
INTERNAL METHOD-
FORMING DEPOSITS (SLUDGE)
Most Common- add Phosphate to Boiler
+ Will form hardness “sludge”
+ Will be removed by Blowdown
Use of Phosphate w/Polymer/Phosphonate
+ Will form some soluble and some “sludge”
+ Will provide a “cleaner” Boiler
![Page 34: Boiler Water System Protection Ppt Puckorius201012](https://reader033.vdocument.in/reader033/viewer/2022050816/55219d85497959b2608b4618/html5/thumbnails/34.jpg)
Sludge Conditioners & Dispersants
Sludge conditioners allowed sludge to
remain free flowing and accumulate in
bottom drum
Current approaches
– Low feedwater hardness
– Keep precipitated particles dispersed so
they can be removed with surface
blowdown
![Page 35: Boiler Water System Protection Ppt Puckorius201012](https://reader033.vdocument.in/reader033/viewer/2022050816/55219d85497959b2608b4618/html5/thumbnails/35.jpg)
Naturally Occurring Sludge Conditioners and Dispersants
Tannins
Lignins
Starch
Seaweed derivatives
Sugars
Carboxymethyl cellulose
![Page 36: Boiler Water System Protection Ppt Puckorius201012](https://reader033.vdocument.in/reader033/viewer/2022050816/55219d85497959b2608b4618/html5/thumbnails/36.jpg)
BOILER DEPOSIT CONTROL–
INTERNAL METHOD-
FORMING DEPOSITS (SLUDGE)
Phosphate Levels 20-40ppm in Boiler
+ Ortho Phosphate can cause deposits in
feed water line
+ Poly Phosphate will not cause deposits in
feed water line
Polymers/ Phosphonates Levels often 10-
30ppm in Boiler
![Page 37: Boiler Water System Protection Ppt Puckorius201012](https://reader033.vdocument.in/reader033/viewer/2022050816/55219d85497959b2608b4618/html5/thumbnails/37.jpg)
Summary of Phosphate Treatment Programs
PO4 OH- Na:PO4 Ratio pH
Conventional 20-40 100-350 N/A 11 - 12
Coordinated 5-25 Trace 2.85:1 to 3:1 (9 - 10.5)
Congruent 2-5 Zero 2.3:1 to 2.6:1 (8.8 - 9.4)
Equilibrium <2.4 <1.0 N/A (9.3 - 9.6)
![Page 38: Boiler Water System Protection Ppt Puckorius201012](https://reader033.vdocument.in/reader033/viewer/2022050816/55219d85497959b2608b4618/html5/thumbnails/38.jpg)
Phosphate ProgramsAlternatives Based on Pressure
PSIG 0-300 301-450 450-600 450-600 601-750 751-900
PO4; ppm 30-60 30-60 20-40 5-25 <2.4 <2.4
Mmho 1100-5400 900-4600 800-3800 200-800 <150 <150
TDS; ppm 550-2700 450-2300 400-1900 100-400 <75 <75
OH Alk;
ppm
20-200 6-50 2-20 1-4 0.17-1.0 .17-1.0
pH 11-12 10.5-11.5 10-11 9.7-10.4 9.0-9.7 9.0-9.7
SO3; ppm 20-40 20-40 15-30 10-20 5-10 3-8
SiO2; ppm <150 <90 <40 <8 <2 <2
Polymer 5-10 5-10 3-8 2-5 2-5 1-3
Makeup Soft Soft Soft DI DI DI
![Page 39: Boiler Water System Protection Ppt Puckorius201012](https://reader033.vdocument.in/reader033/viewer/2022050816/55219d85497959b2608b4618/html5/thumbnails/39.jpg)
BOILER DEPOSIT CAUSES
Loss in Heat Transfer- Wasted Fuel
Possible Gradual Boiler Tube Softening
and Eventual Failure
Corrosion Under Deposits due to
Caustic Concentration
![Page 40: Boiler Water System Protection Ppt Puckorius201012](https://reader033.vdocument.in/reader033/viewer/2022050816/55219d85497959b2608b4618/html5/thumbnails/40.jpg)
Effect of Overheating Due to Deposits
![Page 41: Boiler Water System Protection Ppt Puckorius201012](https://reader033.vdocument.in/reader033/viewer/2022050816/55219d85497959b2608b4618/html5/thumbnails/41.jpg)
Long-term Overheating Tube Failure
![Page 42: Boiler Water System Protection Ppt Puckorius201012](https://reader033.vdocument.in/reader033/viewer/2022050816/55219d85497959b2608b4618/html5/thumbnails/42.jpg)
OXYGEN REMOVAL
METHODS
Mechanical Deareation of Feed Water
+ Various Types Of Equipment using
Heat and Steam
Chemical Oxygen Scavengers
+ Various Types Of Chemicals
![Page 43: Boiler Water System Protection Ppt Puckorius201012](https://reader033.vdocument.in/reader033/viewer/2022050816/55219d85497959b2608b4618/html5/thumbnails/43.jpg)
Oxygen Pitting
![Page 44: Boiler Water System Protection Ppt Puckorius201012](https://reader033.vdocument.in/reader033/viewer/2022050816/55219d85497959b2608b4618/html5/thumbnails/44.jpg)
DEAREATOR OPERATION
Maintain Adequate Temperature- This is
at Full Saturation for the Pressure
Maintain Good Agitation- This is to
Obtain Steam & Water Mixing to Strip
Gases from Water
Maintain Proper Steam Plume for
Proper Partial Pressure of Atmosphere
![Page 45: Boiler Water System Protection Ppt Puckorius201012](https://reader033.vdocument.in/reader033/viewer/2022050816/55219d85497959b2608b4618/html5/thumbnails/45.jpg)
Principles of Deaeration
Heating
Agitation
Adequate Venting
Practical Considerations
90 - 95% of oxygen is removed easily by mechanical separation; the remaining 5 -10% must be removed by molecular diffusion.
![Page 46: Boiler Water System Protection Ppt Puckorius201012](https://reader033.vdocument.in/reader033/viewer/2022050816/55219d85497959b2608b4618/html5/thumbnails/46.jpg)
Types of O2 Scavengers
Non-Volatile Oxygen Scavengers– Stay in boiler water
» Sodium sulfite most common
» Erythorbic acid (iso ascorbic acid-vitamin C)
» Sodium erythorbate
» Amine neutralized-proprietary
Volatile Oxygen Scavengers– Exit boiler with steam
– Hydrazine most common; also other “hydrazine substitutes”
![Page 47: Boiler Water System Protection Ppt Puckorius201012](https://reader033.vdocument.in/reader033/viewer/2022050816/55219d85497959b2608b4618/html5/thumbnails/47.jpg)
OXYGEN SCAVENGERS
Sulfite is most Common
Often Sodium Sulfite with Catalyst (Co)
and is a Dry Product
Recently Sodium Bisulfite which is
much more Soluble and thus a liquid but
it is acid and needs more alkali
Common Dosage is 20-40 ppm Sulfite
![Page 48: Boiler Water System Protection Ppt Puckorius201012](https://reader033.vdocument.in/reader033/viewer/2022050816/55219d85497959b2608b4618/html5/thumbnails/48.jpg)
Volatile Oxygen Scavengers
Hydrazine
Diethylhydroxylamine - DEHA
Carbohydrazide
Hydroquinone
Methylethylketoxime - MEKO
![Page 49: Boiler Water System Protection Ppt Puckorius201012](https://reader033.vdocument.in/reader033/viewer/2022050816/55219d85497959b2608b4618/html5/thumbnails/49.jpg)
CONDENSATE SYSTEM
CORROSION CONTROL
Need to Prevent Low pH due to Carbon
dioxide
Need to be sure Oxygen is not Present
since will Cause Pitting Corrosion
![Page 50: Boiler Water System Protection Ppt Puckorius201012](https://reader033.vdocument.in/reader033/viewer/2022050816/55219d85497959b2608b4618/html5/thumbnails/50.jpg)
Carbon Dioxide Gouging
![Page 51: Boiler Water System Protection Ppt Puckorius201012](https://reader033.vdocument.in/reader033/viewer/2022050816/55219d85497959b2608b4618/html5/thumbnails/51.jpg)
CONDENSATE SYSTEM LOW PH
CORROSION CONTROL Need to Neutralize the Carbonic acid
(carbon dioxide dissolved in water)
Consider using a Dealkalizer if very high
Carbon Dioxide
Use Organic Chemicals known as
Neutralizing Amines
Neutralizing Amine will not protect against
Oxygen corrosion
![Page 52: Boiler Water System Protection Ppt Puckorius201012](https://reader033.vdocument.in/reader033/viewer/2022050816/55219d85497959b2608b4618/html5/thumbnails/52.jpg)
Dealkalization of Boiler Feedwater
Purpose of alkalinity reduction– Bicarbonates in makeup water decompose in
boiler to produce carbon dioxide
2NaHCO3 + Heat Na2CO3 + CO2 + H2O
Carbon dioxide is carried with steam
– CO2 combines with water to form carbonic acid. Low pH condensate causes acid corrosion of condensate piping
CO2 + H2O H2CO3
H2CO3 H+ + HCO3-
![Page 53: Boiler Water System Protection Ppt Puckorius201012](https://reader033.vdocument.in/reader033/viewer/2022050816/55219d85497959b2608b4618/html5/thumbnails/53.jpg)
CONDENSATE SYSTEM-
NEUTRALIZING AMINES +Most common are these three amines
+Morpholine/ Cyclohexylamine/ and
Diethylaminoethanol (DEAE)
+Amines are added to the Boiler and the
Steam carries into the Condensate
+These three can be used alone or often
blended to give better system protection-
they condense throughout entire system
![Page 54: Boiler Water System Protection Ppt Puckorius201012](https://reader033.vdocument.in/reader033/viewer/2022050816/55219d85497959b2608b4618/html5/thumbnails/54.jpg)
DISTRIBUTION RATIO
DEFINED AS THE RATIO OF AMINE REMAINING IN STEAM TO AMINE IN CONDENSATE
AMINE WITH HIGH DISTRIBUTION RATIO STAYS IN STEAM LONGER
AMINE WITH LOW DISTRIBUTION RATIO CONDENSES WITH “EARLY” CONDENSATE
![Page 55: Boiler Water System Protection Ppt Puckorius201012](https://reader033.vdocument.in/reader033/viewer/2022050816/55219d85497959b2608b4618/html5/thumbnails/55.jpg)
DISTRIBUTION RATIOS OF COMMON AMINES
AMINE DISTRIBUTION RATIO
MORPHOLINE 0.48
CYCLOHEXYLAMINE 2.6
DEAE 1.45
AMP 0.31
AMMONIA 10
METHOXYPROPYLAMINE 1.0
![Page 56: Boiler Water System Protection Ppt Puckorius201012](https://reader033.vdocument.in/reader033/viewer/2022050816/55219d85497959b2608b4618/html5/thumbnails/56.jpg)
CONDENSATE CORROSION
CONTROL FROM OXYGEN
Need to Prevent any Oxygen Entering
System by stopping any in leakage
If Oxygen continues entering the steam and
in the condensate- Need to use a Filming
Amine to “coat” the condensate pipe
![Page 57: Boiler Water System Protection Ppt Puckorius201012](https://reader033.vdocument.in/reader033/viewer/2022050816/55219d85497959b2608b4618/html5/thumbnails/57.jpg)
CONDENSATE CORROSION
CONTROL FROM OXYGEN
Filming Amines used are –
+Octadecylamine (ODA)
Filming Amines must be added to the
Steam line- not the boiler
Filming Amines difficult to control dosage
Often both Neutralizing & Filming Amines
are blended together to help each
![Page 58: Boiler Water System Protection Ppt Puckorius201012](https://reader033.vdocument.in/reader033/viewer/2022050816/55219d85497959b2608b4618/html5/thumbnails/58.jpg)
STEAM QUALITY NEEDS
Need to Identify Steam Uses
If only Heating-Not as critical
If to drive Turbines- Need low Silica in
Boiler Water and No Carryover
If both Heating and Turbines- Need Low
Silica in Boiler Water and No Carryover
![Page 59: Boiler Water System Protection Ppt Puckorius201012](https://reader033.vdocument.in/reader033/viewer/2022050816/55219d85497959b2608b4618/html5/thumbnails/59.jpg)
BOILER WATER MONITORING Advanced Method-Traces Active Treatment
Automatic Steam Quality & Purity Testing
Continous Conductivity Tests/Blowdown
Numerous Condensate Corrosion Testing
Monitoring “Transport’ of Iron
Automatic Monitoring reduces time for
Manual Testing & Improves Accuracy
Also Phosphate/pH/turbidity, etc
![Page 60: Boiler Water System Protection Ppt Puckorius201012](https://reader033.vdocument.in/reader033/viewer/2022050816/55219d85497959b2608b4618/html5/thumbnails/60.jpg)
NEW BOILER STARTUP
Need to Implement an Alkaline “Boilout”
Will remove Oil/ Grease/Rust to prevent
Deposits and Over Heating of Tubes
Acid Needed if Much Mill Scale on Tubes
If Acid used, Follow with an Alkaline Boilout
Use of Neutral pH Boilout Treatment may
not be as efficient as Alkaline Boilout
![Page 61: Boiler Water System Protection Ppt Puckorius201012](https://reader033.vdocument.in/reader033/viewer/2022050816/55219d85497959b2608b4618/html5/thumbnails/61.jpg)
BOILER LAYUP METHODS
Wet Layup needs “full” Boiler, hi pH. Sulfite
Dry Layup needs no moisture and nitrogen
Volatile Vapor Phase Inhibitors used for
both Wet and Dry Layup
![Page 62: Boiler Water System Protection Ppt Puckorius201012](https://reader033.vdocument.in/reader033/viewer/2022050816/55219d85497959b2608b4618/html5/thumbnails/62.jpg)
TREAT YOUR BOILER WELL
Will Provide Long Life & Good Operation
Will Prevent Poor Quality Steam
Will Save Considerable Energy
Will Reduce Maintenance & Repair
Will Save Manpower Time
You Will Sleep Well
Good Luck with Your Boiler
![Page 63: Boiler Water System Protection Ppt Puckorius201012](https://reader033.vdocument.in/reader033/viewer/2022050816/55219d85497959b2608b4618/html5/thumbnails/63.jpg)
WHO IS PUCKORIUS & ASSOCIATES, INC?
PROVIDE CONSULTING SERVICES ONLY
DO NOT SELL CHEMICALS OR EQUIPMENT
WORK THROUGHOUT THE WORLD
WORK ON ALL TYPES OF WATER SYSTEMS
PROVIDE TROUBLE SHOOTING, PREPARATION
OF SPECIFICATIONS, TRAINING AND LITIGATION
PROVIDE EVALUATION OF WATER TREATMENT
PROGRAMS AND COST EFFECTIVE
APPLICATIONS
SAVE OUR CLIENTS MANY TIMES OUR FEES
![Page 64: Boiler Water System Protection Ppt Puckorius201012](https://reader033.vdocument.in/reader033/viewer/2022050816/55219d85497959b2608b4618/html5/thumbnails/64.jpg)
NEED MORE HELP?HOW TO CONTACT US?
Puckorius & Associates, Inc. 6621 West 56th Ave
Suite 200 Arvada, Colorado 80002
Phone-303-674-9897 Fax-303-674-1453
Florida Office- 9005 Lake Lynn Drive Sebring, FL 33876
Phone 863-655-1036
E-mail [email protected]
Web - www.Puckorius.com &
www.watertrainingservices.com
Paul Puckorius cell- 303-638-0587
![Page 65: Boiler Water System Protection Ppt Puckorius201012](https://reader033.vdocument.in/reader033/viewer/2022050816/55219d85497959b2608b4618/html5/thumbnails/65.jpg)
Please Submit Questions
Thank you!
Type question in box and hit submit.
![Page 66: Boiler Water System Protection Ppt Puckorius201012](https://reader033.vdocument.in/reader033/viewer/2022050816/55219d85497959b2608b4618/html5/thumbnails/66.jpg)
We apologize for this brief interruption but we
are experiencing technical difficulties and
will resume shortly.
Please stand by.