boma qbt meeting 09feb - omicron · boma qbt steps for increasing ... + new ddc control systems –...
TRANSCRIPT
BOMA QBT STEPS FOR INCREASING
BUILDING ENERGY EFFICIENCY
Rod Yeoh, P.Eng., P.E., LEED® APPrincipal, Omicron
February 2009
Outline
+ Existing Systems+ Evaluate Equipment+ Reduce Loads+ “Right-size” Equipment+ Energy Efficiency
Trends+ Re-commissioning
Existing Systems
+ Most Buildings in the downtown core have Central Plants– Central Chiller plant– Central Boiler plant (or steam from Central
Heat)
Existing Systems+ Air Handling Systems
– Central or Floor by Floor• Free cooling available with outside air
Existing Systems
+ Terminal Systems– VAV Terminal Units
• with or without re-heat– Fan Coil Systems
• 4 Pipe and 2 Pipe
Existing Systems
+ Buildings Outside Downtown Core– Rooftop VAV
• Typically with electric re-heat coils
– Fan powered mixing boxes
• Maintains constant volume to space by mixing return air
Existing Systems
+ Buildings Outside Downtown Core– Multi-zone
• Hot Deck• Cold Deck• Dampers mix zone
supply temperatures as required
Existing Systems+ Buildings Outside Downtown Core
– Rooftop VVT• Variable Volume,
Variable Temperature
• “Polls” zones and supplies heating or cooling as required
• Correct zoning is very important
Evaluating Equipment+ ASHRAE Tables
– Data based on Surveys done in the US in 1978 by ASHRAE. Updated in 1986
– Estimates based on time to replacement, not failure
– Various reasons for replacement• Failure• General Obsolescence• Reduced reliability• Maintenance costs• Energy use• Environmental conditions
Evaluating Equipment+ Lawrence Livermore National Laboratory
(LLNL) & Whitestone Research have done studies of equipment service life to failure of various types of equipment
+ Contributing Factors towards longer LLNL service lives– Complete and consistent maintenance schedule– Regular condition assessments– Replace equipment on down slope of failure
distribution
Evaluating Equipment
+ Vibration testing– Can identify issues
with bearings, wear, unbalance
– Can identify problems earlier than other methods
– Can prevent catastrophic failure in equipment
Analysis of existing equipment
Evaluating Equipment
+ Infrared Thermography– Detects “hot spots” in
electrical components and equipment
– Can help identify electrical issues in HVAC equipment
Analysis of existing equipment
Reduce Loads
+ IF the Building is already having envelope issues, or needs to be re-roofed, increasing insulation or replacing glazing may make sense
Envelope upgrades
Reduce Loads
+ Heating and Cooling Calculations and Energy Simulations should be performed
+ In some instances, high performance glazing could actually increase energy use
Envelope upgrades
Reduce Loads
+ Lighting Loads in the past
– Up to 4 watts per square foot
+ New Lighting– Can be under 1
watt per square foot
Lighting
Reduce Loads
+ Replace T12 lights with T8 or T5
+ Magnetic ballasts to electronic
+ Occupancy sensors+ Daylight sensors
Lighting
Reduce Loads
+ Computers– CRT Monitors – 110 Watts operating– LCD Monitors – 30-40 Watts operating
Other cooling loads
Reduce Loads
+ Ventilation Air– Check existing
ventilation levels• May be over ventilating
– ASHRAE 62-2004 Requirements
• 17 cfm per person required for office space
• 7 cfm per person required for reception areas
Heating loads
Reduce Loads
+ Ventilation Air– Heat Recovery on
Ventilation systems• Enthalpy Wheels• Air to Air Heat
Exchangers• Glycol loops• Heat pipes
Heating loads
Reduce LoadsMotor Loads+ Demand Controlled Ventilation+ Variable Speed Drives on VAV systems &
Pump systems
“Right” Size Equipment
+ Once Loads are Reduced– Look at replacing
main plants: chillers, boilers, rooftop units
– Don’t just replace with same size
– Size to suit new loads
– Add Redundancy
“Right” Size Equipment
+ Evergreen Building– Reduced Chiller
Size by 15%– Reduced Boiler size
by 10%– At $1,000 per ton,
saved about $30,000
New Equipment Efficiencies+ Average efficiency of a
chiller installed in 1980-1990 – 0.85-0.90 kW/ton– Could be as high as 1.2
kW/ton+ Old chillers can also get
oil logged – keep adding refrigerant with oil in it, reduces efficiency by up to 10%
New Equipment Efficiencies+ New Centrifugal Chillers have an efficiency of
0.40-0.50 kW per ton+ Efficiency can go down to as low as 0.25 kW
per ton with VFD chillers
New Equipment Efficiencies+ Old boilers were rated
at 70% to 80% efficiency
+ New near condensing boilers are rated at up to 86% efficiency
+ New condensing boilers are rated at up to 98% efficiency– At more practical return
water temperatures, more like 90%
New Equipment Efficiencies+ Motor efficiency
95.8 94.1 250
93.0 90.2 25
91.1 84.0 10
82.578.01
94.1 91.7 50
91.7 87.5 15
89.6 84.05
High Efficiency (%)Standard (%)Horsepower
New Equipment Efficiencies+ VAV Systems
– Older systems use variable inlet vanes or other mechanical means to vary airflow
– New systems (or retrofits) use VFDs
New Equipment Efficiencies+ New DDC Control
systems– Can Increase
Efficiency • Ensuring systems are
operating as intended• Resetting setpoints to
optimize energy use• Optimal start up
routines
New Equipment Efficiencies+ BC Hydro Product Rebates
– VFDs for Fans and pumps– HVAC Occupancy sensors for PTAC and PTHPs– CO sensors for Parking exhaust– Lighting products & controls
Energy Efficiency Trends+ Dedicated Outdoor Air Systems
– Separating space conditioning and ventilation loads+ Displacement Ventilation and Underfloor Air Distribution
systems
Energy Efficiency Trends+ Co-generation
– Generate Heat and Power at the same time
– By-product heat can be used for cooling through absorption chillers
– Generally more efficient for district plants
Re-Commissioning+ Re-commissioning of Building
Systems– The Office of Energy Efficiency
(NRCan) has cited studies that show that re-commissioning can improve energy efficiency by 5-15%, with a payback under two years.
Re-Commissioning+ Monitor your building
efficiency– Utility Bills
• Compare recent bills with historical data & vacancy rates, energy efficiency upgrades, etc.
• Compare peak demand on utility bills with energy usage
• Compare energy usage patterns with weather & occupancy patterns
Re-Commissioning+ Check trends on DDC system
– entering and leaving chilled-water temperature versus time of day– equipment schedule — on/off — versus time of day– zone temperature & setpoints versus time of day
Prioritizing Capital Projects+ Life Cycle Cost
Assessment– Analysis should include
all Costs in life of component
– Life Cycle Cost (LCC) as “the total discounted dollar cost of owning, operating, maintaining, and disposing of a building or a building system” over a period of time
Prioritizing Capital Projects+ Life Cycle Cost Intangibles
+ Issues such as IAQ and thermal comfort affect productivity
+ Productivity cost is very hard to quantify
+ Original Construction 2%+ Maintenance Costs 6%+ Personnel Costs 92%
Evaluating Old Equipment10 Tips for increasing chiller efficiency
1. Keep a daily log– A log builds a history of operating conditions, including
temperature, pressure, fluid level and flow rate. 2. Keep tubes clean
– Chiller efficiency declines rapidly when tubes become fouled. The compressor's approach temperature, the difference between the temperature of the fluid leaving the heat exchanger and the saturation temperature of the refrigerant being cooled or heated, is a good indicator of heat transfer efficiency.
Evaluating Old Equipment
10 Tips for increasing chiller efficiency
3. Treat condenser water– Condenser water loops using open cooling sources,
such as atmospheric cooling towers, require water treatment to prevent fouling. Erosive conditions, for example, sand flowing through the tubes at high velocity, may pit tubes.
4. Reduce entering water temperature– Lowering the temperature of the water entering the
condenser can improve the chiller's efficiency.
Evaluating Old Equipment
10 Tips for increasing chiller efficiency
5. Control water velocity– Too low a flow rate leads to laminar flow, reducing heat
transfer. Too high a flow rate leads to vibration, noise and erosion. Flow rates should be kept between 3 – 12 feet per second velocity in tubes. Confirm with Manufacturer.
6. Maintain refrigerant charge – Low refrigerant charge, usually resulting from leaks,
causes the compressor to work harder and achieve less cooling effect.
Evaluating Old Equipment10 Tips for increasing chiller efficiency
7. Purge non-condensables – Air and moisture are two non-condensables that can
leak into low-pressure chillers. Non-condensables can reduce chiller efficiency by as much as 4% at 60% load and 7% at 100% loads.
8. Analyze compressor oil – High moisture levels can indicate a purge unit
problem, which has a significant effect on efficiency.
Evaluating Old Equipment10 Tips for increasing chiller efficiency
9. Check wiring – check chiller electrical connections, wiring and
switchgear for hot spots and worn contacts.
10. Modulate speed – Under the right operating conditions, variable speed
drives offer significant energy savings. Variable speed drives also act as "soft starters" to reduce the motor's inrush current.