bre global limited lpcb scheme document sd 021: issue no ... · for lpcb listing the manufacturer...

34
© BRE Global Ltd, 2016 BRE Global Limited LPCB Scheme Document SD 021: Issue No. 5.2 21 July 2016 DETECTORS (Fire)

Upload: others

Post on 23-Aug-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: BRE Global Limited LPCB Scheme Document SD 021: Issue No ... · For LPCB listing the manufacturer must have ISO 9001. Where applicants hold ISO 9001 with another Certification body,

© BRE Global Ltd, 2016

BRE Global Limited LPCB Scheme Document

SD 021: Issue No. 5.2

21 July 2016

DETECTORS (Fire)

Page 2: BRE Global Limited LPCB Scheme Document SD 021: Issue No ... · For LPCB listing the manufacturer must have ISO 9001. Where applicants hold ISO 9001 with another Certification body,

Controlled document valid only on date of printing © BRE Global Ltd, 2016

Page 3: BRE Global Limited LPCB Scheme Document SD 021: Issue No ... · For LPCB listing the manufacturer must have ISO 9001. Where applicants hold ISO 9001 with another Certification body,

BRE Global Ltd. Scheme Document SD 021

Issue Date: 21 July 2016 DETECTORS (Fire)

Issue No.: 5.2

Page 1 of 32

Controlled document valid only on date of printing © BRE Global Ltd, 2016

1. Introduction This document sets out the Loss Prevention Certification Board certification

requirements for fire detectors. It is specific to smoke, heat, flame and Carbon-monoxide fire detectors. The performance and test requirements are given in the standards listed in Section 9. The aim of this scheme is to ensure that detectors used in fire detection and alarm systems installed in buildings comply with the requirements specified in the appropriate standards, which should minimise the risk to people and/or property.

2. Scope This scheme provides ongoing independent, third party assessment and certification/approval of detectors to ensure that the requirements of the appropriate standards are met and maintained. This scheme document must be read in conjunction with PN 110 “The product certification process”.

3. Testing of Products

Section 9 lists the applicable standards for various types of detectors. In order to achieve certification or approval, the detector must comply with the requirements specified in the appropriate standard(s) dependent on its designed detection principle(s). The product will be tested periodically for continued compliance with aspects of the standards; Section 10 sets out the audit testing requirements. All samples supplied for testing by the manufacturer must be representative of normal production and fully traceable to a specific production batch through quality control records.

4. Applications to join the Scheme To apply for product certification complete and return the appropriate application forms and submit the technical drawings and documentation as specified in the application form. Your application will be reviewed and, if acceptable, a quotation will be prepared. This will detail all relevant costs, estimated project duration, sample requirements and a period of validity for the quotation. The quotation will be subject to BRE Global Ltd’s Standard Terms and Conditions as detailed in PN101. For more information or help with your application contact BRE Global on 01923 664100.

Page 4: BRE Global Limited LPCB Scheme Document SD 021: Issue No ... · For LPCB listing the manufacturer must have ISO 9001. Where applicants hold ISO 9001 with another Certification body,

BRE Global Ltd. Scheme Document SD 021

Issue Date: 21 July 2016 DETECTORS (Fire)

Issue No.: 5.2

Page 2 of 32

Controlled document valid only on date of printing © BRE Global Ltd, 2016

5. Management Systems Certification to ISO 9001 In order to ensure that the detectors meet and continue to meet the requirements of the standard(s), we expect the manufacturer to maintain full quality control of the production process. For LPCB listing the manufacturer must have ISO 9001. Where applicants hold ISO 9001 with another Certification body, LPCB will carry out Factory Production Control (FPC) assessments. The applicant must also meet the additional requirements set out in Section 11. Full details of the ISO 9001 certification process are set out in SD003 ‘Management System Certification Schemes’.

6. Certification A certificate is awarded following satisfactory completion of the assessment programme by LPCB. Certificates remain valid providing there continues to be:

• Satisfactory results from the annual product audit testing programme set out in

Section 10.

• Satisfactory surveillance results as assessed by LPCB in respect of FPC or ISO 9001 requirements and the requirements identified in Section 11.

• LPCB approval of any proposed modifications to the product which may affect

performance. Requests to assess proposed modifications are made by completing the modification application form.

The applicant will be advised of any further requirements where necessary to retain certification.

7. Alternative Marking (Cross Listing) In certain circumstances, LPCB listed products may be branded with another company's name and product identification incorporating the LPCB Certification Mark. Products that are LPCB approved and Red Book listed for the original manufacturer can, with the agreement of the Owner of the product, be approved and Red Book listed under the name of another company, under a different name or brand. This can be done without having to undergo the full approval process so long as the actual product is not significantly changed in design, construction or function.

8. Certification Mark

The Supplier may use the LPCB Certification Mark as directed in the publication PN103 ‘Rules and Guidance for use of the LPCB Certification Marks’. The Mark that may be used for this scheme is as follows:

Page 5: BRE Global Limited LPCB Scheme Document SD 021: Issue No ... · For LPCB listing the manufacturer must have ISO 9001. Where applicants hold ISO 9001 with another Certification body,

BRE Global Ltd. Scheme Document SD 021

Issue Date: 21 July 2016 DETECTORS (Fire)

Issue No.: 5.2

Page 3 of 32

Controlled document valid only on date of printing © BRE Global Ltd, 2016

EN54-nn Cert/LPCB ref. XXX/XXa

Alternatively, if there is limited space on the product, the following mark may be applied instead.

EN54-nn ssue: YYYY

Cert/LPCB ref. XXX/XXa 9. Type Testing Requirements: The number of samples selected for type testing is dependent on a number of factors, for example:

(1) The standard(s) the detector to be tested to. (2) Detector sensitivities, classifications or modes of operation. (3) Specific detector features to be tested.

Testing will be performed by a UKAS (or equivalent) accredited laboratory acceptable to the LPCB. If no standard is available for testing a specific detector type assessment of the detector will be made against an LPCB test schedule developed and agreed by LPCB, LPC/BREG laboratory, and manufacturers’ technical representatives. Risk assessment for such detectors will be carried out and approved by Expert Group A. Marking will be examined for compliance with the relevant clause of the standard and LPCB publication PN103. Documentation requirements shall include technical information of the products submitted for approval. This includes:

- Schematic diagrams - Installation & operating instructions - General assembly drawings - PCB artwork - Mechanical drawings

The LPCB Ref. No. assigned to the product

The LPCB Ref. No. assigned to the product

Page 6: BRE Global Limited LPCB Scheme Document SD 021: Issue No ... · For LPCB listing the manufacturer must have ISO 9001. Where applicants hold ISO 9001 with another Certification body,

BRE Global Ltd. Scheme Document SD 021

Issue Date: 21 July 2016 DETECTORS (Fire)

Issue No.: 5.2

Page 4 of 32

Controlled document valid only on date of printing © BRE Global Ltd, 2016

- Parts list (including critical components) - Technical specification - Description of operation - Software documentation - Label drawings - Product datasheet

Table 1: Type Testing and Assessment

Standards / regulations applicable Summary of Requirements EN 54: Part 5: 2000 + A1 - Fire detection and alarm systems - Heat detectors - Point detectors All applicable clauses

EN 54: Part 7: 2000 + A1 - Fire detection and alarm systems Smoke detectors - Point detectors using scattered light, transmitted light or ionisation

All applicable clauses

EN 54: Part 10: 2002 – Fire detection and alarm systems - Flame detectors – Point detectors. All applicable clauses

EN 54: Part 12: 2015 - Fire detection and alarm systems - Smoke detectors - Line detectors using an optical light beam

All applicable clauses

EN 54: Part 20: 2006 – Fire detection and fire alarm systems – Aspirating smoke detectors All applicable clauses

EN 54: Part 26: 2015 - Fire detection and fire alarm systems - Carbon monoxide detectors - Point detectors

All applicable clauses

EN 54-29:2015 Fire detection and fire alarm systems -Multi-sensor Fire Detectors Using Smoke / Heat Sensors

All applicable clauses

EN 54: Part 30: 2015 - Fire detection and fire alarm systems - Multi-sensor fire detectors - Point detectors using a combination of carbon monoxide and heat sensors

All applicable clauses

EN 54: Part 31: 2014 - Fire detection and fire alarm system - Multi-sensor fire detectors - Point detectors using a combination of smoke, carbon monoxide and optionally heat sensors

All applicable clauses

CEA 4021: 2003 - Specifications for fire detection and fire alarm systems - Requirements and test methods for multi-sensor detectors, which respond to smoke and heat, and smoke detectors with more than one smoke sensor.

All applicable clauses

CEA 4022: 1999 -12: Specifications for fire detection and fire alarm systems - Requirements and test methods for aspirating smoke detectors

All applicable clauses

ISO 7240: Part 5: 2003 – Fire detection and alarm systems – Part 5: Point-type heat detectors All applicable clauses

Page 7: BRE Global Limited LPCB Scheme Document SD 021: Issue No ... · For LPCB listing the manufacturer must have ISO 9001. Where applicants hold ISO 9001 with another Certification body,

BRE Global Ltd. Scheme Document SD 021

Issue Date: 21 July 2016 DETECTORS (Fire)

Issue No.: 5.2

Page 5 of 32

Controlled document valid only on date of printing © BRE Global Ltd, 2016

Standards / regulations applicable Summary of Requirements ISO 7240: Part 6: 2004 – Fire detection and alarm systems – Part 6: Carbon Monoxide fire detectors using electrochemical cells

All applicable clauses

ISO 7240: Part 7: 2003 – Fire detection and alarm systems – Part 7: Point-type smoke detectors using scattered light, transmitted light or ionization

All applicable clauses

ISO 7240: Part 15: 2004 – Fire detection and alarm systems – Part 15: Multisensor fire detectors All applicable clauses

LPS1265 : 2005 - Requirements and Testing Procedures for the LPCB Approval and Listing of Carbon Monoxide Fire Detectors Using Electrochemical Cells

All applicable clauses

LPS1274 : 2005 - Testing Procedures for the LPCB Approval and Listing of Carbon Monoxide / Heat Multisensor Fire Detectors Using Electrochemical Cells

All applicable clauses

LPS1279 : 2006 - Testing Procedures for the LPCB Approval and Listing of Point Multisensor Fire Detectors using Optical or Ionization Smoke Sensors and Electrochemical Cell CO Sensors and, optionally, Heat Sensors

All applicable clauses

10. Product Audit Test Requirements This section of the document sets out the LPCB product audit testing requirements.

It is specific to smoke, heat, flame and Carbon-monoxide fire detectors. Products will be tested periodically for continued compliance with aspects of the standards they are approved to and audit requirements specified in this document.

If products are not made available for audit testing then LPCB has the right to suspend or withdraw the product approval/certification.

10.1 Selection Criteria The number and type of products selected and the testing required each year are at the discretion of the LPCB. The selection of detectors is dependent on a number of factors including:

(a) Number of products approved/certified by the company (b) Number of products within the range (c) Any testing undertaken since original evaluation (e.g. modification) (d) Modifications made to the product where no testing was required (e) Factory production relocation which coincides with their annual product audit

All samples supplied / selected for testing must be representative of normal production and be fully traceable to a specific production batch through quality control records.

Page 8: BRE Global Limited LPCB Scheme Document SD 021: Issue No ... · For LPCB listing the manufacturer must have ISO 9001. Where applicants hold ISO 9001 with another Certification body,

BRE Global Ltd. Scheme Document SD 021

Issue Date: 21 July 2016 DETECTORS (Fire)

Issue No.: 5.2

Page 6 of 32

Controlled document valid only on date of printing © BRE Global Ltd, 2016

The number of samples selected for audit testing is dependent on a number of factors, for example:

(a) The standard(s) the product is to be tested to. (b) Product classifications or modes of operation. (c) Specific product features to be tested. (d) The similarity between products selected for an audit

10.2 Assessment and Test Requirements: For each product type, the minimum checks and requirements to be applied to the

selected products are outlined in the appropriate Annex:

Table 2: Product Audit Test and Assessment

Annex Product Type Standard(s)

A Commercial Smoke Detectors EN 54-7:2000 & ISO 7240-7:2003

B Commercial Heat Detectors EN 54-5:2000 & ISO 7240-5:2003

C Commercial Multi-sensor Detectors CEA 4021: July 2003 D Line Detectors using an Optical Beam EN 54-12:2015 E Aspirating Smoke Detectors CEA 4022:1999-12 F Aspirating Smoke Detectors EN 54-20: 2006 G Flame Detectors EN 54-10:2002 H Carbon Monoxide Fire Detectors ISO 7240-6 : 2004 I Carbon Monoxide Fire Detectors LPS 1265 Issue 1.1 J Carbon Monoxide / Heat Multi-sensor Fire Detectors LPS 1274 Issue 1.0

K Multi-Sensor Fire Detectors Using Smoke / Carbon Monoxide & Optionally Heat Sensors LPS 1279 Issue 1.0

L Multi-sensor Fire Detectors Using Smoke / Heat Sensors EN 54-29: 2015

M Carbon Monoxide Detectors EN 54-26: 2015

N Multi-Sensor Fire Detectors Using Carbon Monoxide & Heat Sensors EN 54-30: 2015

O Multi-Sensor Fire Detectors Using Smoke, Carbon Monoxide & Optionally Heat Sensors EN 54-31: 2014

Other tests may be specified by LPCB if deemed to be necessary, for example following concerns identified in a previous evaluation or in the field. This will be communicated to the client prior to testing.

10.3 Audit Test Result

The product audit will be deemed successful providing that all audit test requirements have been met.

Page 9: BRE Global Limited LPCB Scheme Document SD 021: Issue No ... · For LPCB listing the manufacturer must have ISO 9001. Where applicants hold ISO 9001 with another Certification body,

BRE Global Ltd. Scheme Document SD 021

Issue Date: 21 July 2016 DETECTORS (Fire)

Issue No.: 5.2

Page 7 of 32

Controlled document valid only on date of printing © BRE Global Ltd, 2016

Failure to meet any of audit test requirements shall be communicated to the client in the form of a report detailing the nature of the failure and the following shall be applied:

- Clients will be expected to investigate the matter and provide a satisfactory

explanation including details of the corrective action to be reviewed by LPCB. The client must respond to the failure within the specified time limit. If the Client fails to respond by the given deadline or LPCB deem the response to be unsatisfactory then the product approval may be suspended.

- If the product is suspended then all LPCB marked devices held in stock or in

transportation must be quarantined until further notice.

- Investigations or further testing which arise as a result of any failure identified during the product audit will incur additional costs.

- Following any suspension of product approval, a final deadline will be set for the

matter to be satisfactorily resolved. Failure to resolve the matter by the final suspension deadline may result in the full withdrawal of the product approval.

Note: Products may be suspended immediately once a failure has been identified depending on the nature of the failure. All timescales involved will be at LPCB’s discretion. 11. Additional Factory Production Control Requirements

Table 3 : FPC Requirements

Topics Notes Checks and tests

The production process should include functional and performance checks to monitor the production process and in particular the sensitivity settings of the detectors. All detectors should be subjected to functional tests that include checks of the ability of the detector to signal an alarm, or in the case of analogue addressable detectors, the correct operation of the signalling protocol. At least a representative sample should be subjected to a performance test that involves stimulating the sensor with the appropriate fire parameter (e.g. smoke, infra-red radiation … etc).

Design and process checks Checks of the approved detectors build status against the LPCB approved

Page 10: BRE Global Limited LPCB Scheme Document SD 021: Issue No ... · For LPCB listing the manufacturer must have ISO 9001. Where applicants hold ISO 9001 with another Certification body,

BRE Global Ltd. Scheme Document SD 021

Issue Date: 21 July 2016 DETECTORS (Fire)

Issue No.: 5.2

Page 8 of 32

Controlled document valid only on date of printing © BRE Global Ltd, 2016

document register. To check any change in production process which may influence the performance and reliability of the detector.

Page 11: BRE Global Limited LPCB Scheme Document SD 021: Issue No ... · For LPCB listing the manufacturer must have ISO 9001. Where applicants hold ISO 9001 with another Certification body,

BRE Global Ltd. Scheme Document SD 021

Issue Date: 21 July 2016 DETECTORS (Fire)

Issue No.: 5.2

Page 9 of 32

Controlled document valid only on date of printing © BRE Global Ltd, 2016

Annex A (Audit requirements for Commercial Smoke Detectors Approved to EN 54-7:2000 & ISO 7240-

7:2003) This annex defines the LPCB audit requirements for continued certification / approval of the product. Failure to meet the audit requirements is deemed as a non-compliance, please refer to Section 10.3 for failure procedure. A.1 Marking:

The product must be marked in accordance with Clause 4.9 of EN54-7:2000 and/or ISO 7240-7:2003 where applicable. In addition it must also meet the LPCB requirements specified in publication PN103.

A.2 Software Issue:

The software version must be the same as the version that was most recently approved by LPCB, this includes internal and external software required to operate the device where applicable.

A.3 Documentation:

The submitted build status of the audited sample shall be identical to the LPCB approved build status. Note: The list of documents that identifies the build status of product is referred to document register and should be submitted to LPCB.

A.4 Smoke Sensitivity Measurements:

Response threshold value measurements shall be conducted in accordance with EN 54-7:2000 Clause 5.1.5 (Measurement of response threshold value) with detectors tested using the same setup as per the original evaluation. The detectors shall be deemed to comply if the following requirements are met: (a) All measurements shall lie within the allowed limits* as defined by Clause 5.4

(Reproducibility) and note 2 of Clause 5.1.6 of EN 54-7: 2000.

* Note 1: Allowed limits are defined as the limits that manufactures’ could potentially manufacture to providing they still meet the requirements of the standard

- The maximum allowed limit is derived as follows :

1.33 x production mean as determined in the original evaluation†

- The minimum allowed limit is derived as follows :

production mean as determined in the original evaluation† / 1.5 & m ≥ 0.05 dB/m or y ≥ 0.2

Page 12: BRE Global Limited LPCB Scheme Document SD 021: Issue No ... · For LPCB listing the manufacturer must have ISO 9001. Where applicants hold ISO 9001 with another Certification body,

BRE Global Ltd. Scheme Document SD 021

Issue Date: 21 July 2016 DETECTORS (Fire)

Issue No.: 5.2

Page 10 of 32

Controlled document valid only on date of printing © BRE Global Ltd, 2016

† Note 2: Where a detector has undergone a modification (approved by LPCB) which has changed the sensitivity range of the detector then the mean of that new range will be considered as the production mean for the above derivation.

(b) All measurements shall lie within the most recent, LPCB approved‡ limits.

‡ Note 3: Approved limits are defined as the limits that have been measured in the BRE smoke tunnel and compliance to the requirements of the standard has been confirmed and verified

(i) If any of the measurements fall below the minimum approved limit then the

detector may be likely to suffer from false alarms so further testing may be deemed to be necessary.

(ii) If any of the measurements exceed the maximum approved limit then the detector

may have insufficient sensitivity for meeting the fire test limits and so may be tested in accordance with EN 54-7:2000 Clause 5.18 (Fire sensitivity) and if tested must meet the requirements of that clause in order to confirm compliance.

Page 13: BRE Global Limited LPCB Scheme Document SD 021: Issue No ... · For LPCB listing the manufacturer must have ISO 9001. Where applicants hold ISO 9001 with another Certification body,

BRE Global Ltd. Scheme Document SD 021

Issue Date: 21 July 2016 DETECTORS (Fire)

Issue No.: 5.2

Page 11 of 32

Controlled document valid only on date of printing © BRE Global Ltd, 2016

Annex B (Audit requirements for Commercial Heat Detectors Approved to EN 54-5:2000 &

ISO 7240-5:2003) This annex defines the LPCB audit requirements for continued certification / approval of the product. Failure to meet the audit requirements is deemed as a non-compliance, please refer to Section 10.3 for failure procedure. B.1 Marking:

The product must be marked in accordance with Clause 4.9 of EN 54-5:2000 and/or ISO 7240-5:2003 where applicable. In addition it must also meet the LPCB requirements specified in publication PN103.

B.2 Software Issue:

The software version must be the same as the version that was most recently approved by LPCB, this includes internal and external software required to operate the device where applicable.

B.3 Documentation:

The submitted build status of the audited sample shall be identical to the LPCB approved build status. Note: The list of documents that identifies the build status of product is referred to document register and should be submitted to LPCB.

B.4 Response Time & Temperature Measurements:

Response time measurements shall be conducted in accordance with EN 54-5:2000 Clause 5.1.5 (Measurement of response time) at rates of rise of 3K min-1 and 20K min-1 with detectors tested in the least sensitive orientation using the same setup as per the original evaluation. The measurements must lie within the limits specified in Table 4 (Response time limits) of Clause 5.4.3. Further testing in general accordance with EN 54-5:2000 Clause 5.3 (Static response) & Clause 5.4 (Response from typical application temperature) will be conducted on one or two selected samples using the same setup as per the original evaluation.

The detectors shall be deemed to comply if the requirements of the above clauses are met.

Page 14: BRE Global Limited LPCB Scheme Document SD 021: Issue No ... · For LPCB listing the manufacturer must have ISO 9001. Where applicants hold ISO 9001 with another Certification body,

BRE Global Ltd. Scheme Document SD 021

Issue Date: 21 July 2016 DETECTORS (Fire)

Issue No.: 5.2

Page 12 of 32

Controlled document valid only on date of printing © BRE Global Ltd, 2016

Annex C (Audit requirements for Commercial Multi-Sensor Detectors Approved to CEA 4021:July 2003)

This annex defines the LPCB audit requirements for continued certification / approval of the product. Failure to meet the audit requirements is deemed as a non-compliance, please refer to Section 10.3 for failure procedure. C.1 Marking:

The product must meet requirements set out in Annex A.1 & B.1 where applicable. In addition the product must indicate the CEA standard number i.e. “CEA 4021 July 2003”.

C.2 Software Issue:

The software version must be the same as the version that was most recently approved by LPCB, this includes internal and external software required to operate the device where applicable.

C.3 Documentation:

The submitted build status of the audited sample shall be identical to the LPCB approved build status. Note: The list of documents that identifies the build status of product is referred to document register and should be submitted to LPCB.

C.4 Smoke Sensitivity Measurements: Multisensors with smoke detection shall be tested as described in Annex A.4 of this scheme

document. Detectors shall be deemed to comply if the requirements specified in Annex A.4 are met. In addition to Annex A.4 (b) (ii) detectors may be tested in accordance with CEA 4021: July 2003, Clause 5.6 (Flaming liquid fire) and must meet the requirements of that clause in order to confirm compliance.

C.5 Response Time & Temperature Measurements:

(a) Multisensors with heat detection for which the manufacturer claims compliance with EN 54-5: 2000 (or ISO 7240-5) shall be tested as described in Annex B.4 of this scheme document. Detectors shall be deemed to comply if the requirements specified in Annex B.4 are met.

(b) Multisensors with heat detection for which the manufacturer does not claim compliance

with EN 54-5: 2000 (or ISO 7240-5) shall be tested in accordance with EN 54-5: 2000, Clause 5.1.5 (Measurement of response time) at rates of rise of 3K min-1 and 20K min-1 with detectors tested in the most sensitive orientation using the same setup as per the original evaluation.

Further testing in general accordance with EN 54-5: 2000 Clause 5.3 (Static response) & Clause 5.4 (Response from typical application temperature) will be conducted on one or two selected samples in the most sensitive orientation using the same setup as per the original evaluation.

Page 15: BRE Global Limited LPCB Scheme Document SD 021: Issue No ... · For LPCB listing the manufacturer must have ISO 9001. Where applicants hold ISO 9001 with another Certification body,

BRE Global Ltd. Scheme Document SD 021

Issue Date: 21 July 2016 DETECTORS (Fire)

Issue No.: 5.2

Page 13 of 32

Controlled document valid only on date of printing © BRE Global Ltd, 2016

For the test in accordance with EN 54-5: 2000 Clause 5.3 the detector shall not respond before 54◦C. For the test in accordance with EN54-5: 2000 Clause 5.4 and Clause 5.1.4 (at rates of rise of 3K min-1 and 20K min-1), the detector shall not respond before reaching the lower limit of response times for Class A1, as shown in EN 54-5: 2000 Table 4 of Clause 5.4.3.

The detectors shall be deemed to comply if the above requirements are met.

Page 16: BRE Global Limited LPCB Scheme Document SD 021: Issue No ... · For LPCB listing the manufacturer must have ISO 9001. Where applicants hold ISO 9001 with another Certification body,

BRE Global Ltd. Scheme Document SD 021

Issue Date: 21 July 2016 DETECTORS (Fire)

Issue No.: 5.2

Page 14 of 32

Controlled document valid only on date of printing © BRE Global Ltd, 2016

Annex D (Audit requirements for Line Smoke Detectors using an Optical Beam Approved to EN 54-12 :2015) This annex defines the LPCB audit requirements for continued certification / approval of the product. Failure to meet the audit requirements is deemed as a non-compliance, please refer to Section 10.3 for failure procedure. D.1 Marking:

The product must be marked in accordance with EN 54-12: 2015 Clause 8. In addition it must also meet the LPCB requirements specified in publication PN103

D.2 Software Issue :

The software version must be the same as the version that was most recently approved by LPCB, this includes internal and external software required to operate the device where applicable.

D.3 Documentation:

The submitted build status of the audited sample shall be identical to the LPCB approved build status. Note: The list of documents that identifies the build status of product is referred to document register and should be submitted to LPCB.

D.4 Smoke Sensitivity Measurements:

Response threshold value measurements shall be conducted in accordance with EN 54-12: 2015 Clause 5.1.5 (Measurement of response threshold value) with detectors tested using the same setup as per the original evaluation. The detectors shall be deemed to comply if the following requirements are met : (a) All measurements shall lie within the allowed* limits as defined by Clause 5.3.1

(Reproducibility) and Clause 5.1.6 of EN 54-12: 2015.

* Note 1: Allowed limits are defined as the limits that manufactures’ could potentially manufacture to providing they still meet the requirements of the standard

- The maximum allowed limit is derived as follows :

1.33 x production mean as determined in the original evaluation†

- The minimum allowed limit is derived as follows :

production mean as determined in the original evaluation† / 1.5 & m≥ 0.4 dB † Note 2: Where a detector has undergone a modification (approved by LPCB) which has changed the sensitivity range of the detector then the mean of that new range will be considered as the production mean for the above derivation.

Page 17: BRE Global Limited LPCB Scheme Document SD 021: Issue No ... · For LPCB listing the manufacturer must have ISO 9001. Where applicants hold ISO 9001 with another Certification body,

BRE Global Ltd. Scheme Document SD 021

Issue Date: 21 July 2016 DETECTORS (Fire)

Issue No.: 5.2

Page 15 of 32

Controlled document valid only on date of printing © BRE Global Ltd, 2016

(b) All measurements shall lie within the most recent, LPCB, approved‡ limits.

‡ Note 3: Approved limits are defined as the limits that have been measured on the optical bench and compliance to the requirements of the standard has been confirmed and verified

(i) If any of the measurements fall below the minimum approved limit then the

detector may be likely to suffer from false alarms so further testing may be deemed to be necessary.

(ii) If any of the measurements exceed the maximum approved then the detector may

have insufficient sensitivity for meeting the fire test limits and so may be tested in accordance with EN 54-12:2015, Clause 5.5.1 (Fire sensitivity) and must meet the requirements of that clause in order to confirm compliance.

D.5 Response to Rapid changes in attenuation:

Response threshold value measurements shall be conducted in accordance with EN 54-12: 2015, Clause 5.3.4 (Rapid changes in attenuation). The detectors shall be deemed to comply if the requirements of the above clause are met.

Page 18: BRE Global Limited LPCB Scheme Document SD 021: Issue No ... · For LPCB listing the manufacturer must have ISO 9001. Where applicants hold ISO 9001 with another Certification body,

BRE Global Ltd. Scheme Document SD 021

Issue Date: 21 July 2016 DETECTORS (Fire)

Issue No.: 5.2

Page 16 of 32

Controlled document valid only on date of printing © BRE Global Ltd, 2016

Annex E (Audit requirements for Aspirating Smoke Detectors Approved to CEA 4022:1999-12)

This annex defines the LPCB audit requirements for continued certification / approval of the product. Failure to meet the audit requirements is deemed as a non-compliance, please refer to Section 10.3 for failure procedure. E.1 Marking:

The product must be marked in accordance with CEA 4022: 1999-12 Clause 4.13.1 and must indicate the CEA standard number i.e. “CEA 4022: 1999-12”. In addition it must also meet the LPCB requirements specified in publication PN103.

E.2 Software Issue:

The software version must be the same as the version that was most recently approved by LPCB, this includes internal and external software required to operate the device where applicable.

E.3 Documentation:

The submitted build status of the audited sample shall be identical to the LPCB approved build status. Note: The list of documents that identifies the build status of product is referred to document register and should be submitted to LPCB.

E.4 Air Flow Monitoring:

The detectors will be tested in accordance with CEA 4022: 1999-12 Clause 5.1.6 (Test of the airflow monitoring facility) with detectors tested using the same setup as per the original evaluation. The detectors shall be deemed to comply if the requirements of Clause 4.11 (Airflow monitoring) are met.

E.5 Smoke Sensitivity Measurements:

Response threshold value measurements shall be conducted in accordance with CEA 4022: 1999-12 Clause 5.1.5 (Measurement of response threshold value), with detectors tested using the same setup as per the original evaluation. The detectors shall be deemed to comply if the following requirements are met: (a) All measurements shall lie within the allowed* limits as defined by Clause 5.3

(Reproducibility) of CEA 4022: 1999-12.

* Note 1: Allowed limits are defined as the limits that manufactures’ could potentially manufacture to providing they still meet the requirements of the standard

- The maximum allowed limit is derived as follows :

1.3 x production mean as determined in the original evaluation†

Page 19: BRE Global Limited LPCB Scheme Document SD 021: Issue No ... · For LPCB listing the manufacturer must have ISO 9001. Where applicants hold ISO 9001 with another Certification body,

BRE Global Ltd. Scheme Document SD 021

Issue Date: 21 July 2016 DETECTORS (Fire)

Issue No.: 5.2

Page 17 of 32

Controlled document valid only on date of printing © BRE Global Ltd, 2016

- The minimum allowed limit is derived as follows :

production mean as determined in the original evaluation† / 1.5

† Note 2: Where a detector has undergone a modification (approved by LPCB) which has changed the sensitivity range of the detector then the mean of that new range will be considered as the production mean for the above derivation.

(b) All measurements shall lie within the most recent, LPCB, approved‡ limits.

‡ Note 3: Approved limits are defined as the limits that have been measured in the BRE smoke tunnel and compliance to the requirements of the standard has been confirmed and verified

(i) If any of the measurements fall below the minimum approved limit then the

detector may be likely to suffer from false alarms so further testing may be deemed to be necessary.

(ii) If any of the measurements exceed the maximum approved limit then the detector

may have insufficient sensitivity for meeting the fire test limits and so may be tested in accordance with CEA 4022:1999-12, Clause 4.6 (Fire sensitivity) and must meet the requirements of that clause in order to confirm compliance.

Page 20: BRE Global Limited LPCB Scheme Document SD 021: Issue No ... · For LPCB listing the manufacturer must have ISO 9001. Where applicants hold ISO 9001 with another Certification body,

BRE Global Ltd. Scheme Document SD 021

Issue Date: 21 July 2016 DETECTORS (Fire)

Issue No.: 5.2

Page 18 of 32

Controlled document valid only on date of printing © BRE Global Ltd, 2016

Annex F (Audit requirements for Aspirating Smoke Detectors Approved to EN 54-20:2006)

This annex defines the LPCB audit requirements for continued certification / approval of the product. Failure to meet the audit requirements is deemed as a non-compliance, please refer to Section 10.3 for failure procedure. F.1 Marking:

The product must be marked in accordance with EN 54-20: 2006 Clause 8. In addition it must also meet the LPCB requirements specified in publication PN103.

F.2 Software Issue:

The software version must be the same as the version that was most recently approved by LPCB, this includes internal and external software required to operate the device where applicable.

F.3 Documentation:

The submitted build status of the audited sample shall be identical to the LPCB approved build status. Note: The list of documents that identifies the build status of product is referred to document register and should be submitted to LPCB.

F.4 Air Flow Monitoring:

The detectors will be tested in accordance with EN 54-20: 2006 Clause 6.1.6 (Test of the airflow monitoring facility) with detectors tested using the same setup as per the original evaluation. The detectors shall be deemed to comply if the requirements of Clause 5.9 (Airflow monitoring) are met.

F.5 Smoke Sensitivity Measurements:

Response threshold value measurements shall be conducted in accordance with EN 54-20:2006 Clause 6.1.5 (Measurement of response threshold value), with detectors tested using the same setup as per the original evaluation. The detectors shall be deemed to comply if the following requirements are met : (a) All measurements shall lie within the allowed* limits as defined by Clause 6.3

(Reproducibility) of EN 54-20: 2006.

* Note 1: Allowed limits are defined as the limits that manufactures’ could potentially manufacture to providing they still meet the requirements of the standard.

- The maximum allowed limit is derived as follows :

1.33 x production mean as determined in the original evaluation†

- The minimum allowed limit is derived as follows :

Page 21: BRE Global Limited LPCB Scheme Document SD 021: Issue No ... · For LPCB listing the manufacturer must have ISO 9001. Where applicants hold ISO 9001 with another Certification body,

BRE Global Ltd. Scheme Document SD 021

Issue Date: 21 July 2016 DETECTORS (Fire)

Issue No.: 5.2

Page 19 of 32

Controlled document valid only on date of printing © BRE Global Ltd, 2016

production mean as determined in the original evaluation† / 1.5

† Note 2: Where a detector has undergone a modification (approved by LPCB) which has changed the sensitivity range of the detector then the mean of that new range will be considered as the production mean for the above derivation.

(b) All measurements shall lie within the most recent, LPCB, approved‡ limits.

‡ Note 3: Approved limits are defined as the limits that have been measured in the BRE smoke tunnel and compliance to the requirements of the standard has been confirmed and verified

(i) If any of the measurements fall below the minimum approved limit then the

detector may be likely to suffer from false alarms so further testing may be deemed to be necessary.

(ii) If any of the measurements exceed the maximum approved limit then the detector

may have insufficient sensitivity for meeting the fire test limits and so may be tested in accordance with EN 54-20:2006, Clause 6.15 (Fire sensitivity) and must meet the requirements of that clause in order to confirm compliance.

Page 22: BRE Global Limited LPCB Scheme Document SD 021: Issue No ... · For LPCB listing the manufacturer must have ISO 9001. Where applicants hold ISO 9001 with another Certification body,

BRE Global Ltd. Scheme Document SD 021

Issue Date: 21 July 2016 DETECTORS (Fire)

Issue No.: 5.2

Page 20 of 32

Controlled document valid only on date of printing © BRE Global Ltd, 2016

Annex G (Audit requirements for Flame Detectors Approved to EN 54-10:2002)

This annex defines the LPCB audit requirements for continued certification / approval of the product. Failure to meet the audit requirements is deemed as a non-compliance, please refer to Section 10.3 for failure procedure. G.1 Marking:

The product must be marked in accordance with EN54-10: 2002 Clause 6. In addition it must also meet the LPCB requirements specified in publication PN103.

G.2 Software Issue:

The software version must be the same as the version that was most recently approved by LPCB, this includes internal and external software required to operate the device where applicable.

G.3 Documentation:

The submitted build status of the audited sample shall be identical to the LPCB approved build status. Note: The list of documents that identifies the build status of product is referred to document register and should be submitted to LPCB.

G.4 Response Point Measurements:

Response threshold value measurements shall be conducted in accordance with EN 54-10:2002 Clause 5.1.5 (Determination of response point), with detectors tested using the same setup as per the original evaluation. The detectors shall be deemed to comply if the following requirements are met : (a) All measurements shall lie within the allowed* limits as defined by Clause 5.2

(Reproducibility) and the note of Clause 5.1.8 of EN 54-10: 2002.

* Note 1: Allowed limits are defined as the limits that manufactures’ could potentially manufacture to providing they still meet the requirements of the standard

- The maximum allowed limit is derived as follows :

1.15 x production mean as determined in the original evaluation†

- The minimum allowed limit is derived as follows :

production mean as determined in the original evaluation† / 1.22

† Note 2: Where a detector has undergone a modification (approved by LPCB) which has changed the sensitivity range of the detector then the mean of that new range will be considered as the production mean for the above derivation.

Page 23: BRE Global Limited LPCB Scheme Document SD 021: Issue No ... · For LPCB listing the manufacturer must have ISO 9001. Where applicants hold ISO 9001 with another Certification body,

BRE Global Ltd. Scheme Document SD 021

Issue Date: 21 July 2016 DETECTORS (Fire)

Issue No.: 5.2

Page 21 of 32

Controlled document valid only on date of printing © BRE Global Ltd, 2016

(b) All measurements shall lie within the most recent, LPCB, approved‡ limits.

‡ Note 3: Approved limits are defined as the limits that have been measured on the optical bench and compliance to the requirements of the standard has been confirmed and verified

(i) If any of the measurements exceed the maximum approved limitŦ then the detector

may be likely to suffer from false alarms so further testing may be deemed to be necessary.

(ii) If any of the measurements fall below the minimum approved limitŦ then the detector

may have insufficient sensitivity for meeting the fire test limits and so may be tested in accordance with EN 54-10:2002, Clause 5.5 (Fire sensitivity) and must meet the requirements of that clause in order to confirm compliance.

Ŧ Note 4: The maximum approved limit refers to the most sensitive sample (maximum d) whereas the minimum approved limit refers to the least sensitive sample (minimum d).

Page 24: BRE Global Limited LPCB Scheme Document SD 021: Issue No ... · For LPCB listing the manufacturer must have ISO 9001. Where applicants hold ISO 9001 with another Certification body,

BRE Global Ltd. Scheme Document SD 021

Issue Date: 21 July 2016 DETECTORS (Fire)

Issue No.: 5.2

Page 22 of 32

Controlled document valid only on date of printing © BRE Global Ltd, 2016

Annex H (Audit requirements for Carbon Monoxide Detectors Approved to ISO 7240-6:2004)

This annex defines the LPCB audit requirements for continued certification / approval of the product. Failure to meet the audit requirements is deemed as a non-compliance, please refer to Section 10.3 for failure procedure. H.1 Marking:

The product must be marked in accordance with ISO 7240-6:2004 Clause 4.8. In addition it must also meet the LPCB requirements specified in publication PN103.

H.2 Software Issue:

The software version must be the same as the version that was most recently approved by LPCB, this includes internal and external software required to operate the device where applicable.

H.3 Documentation:

The submitted build status of the audited sample shall be identical to the LPCB approved build status. Note: The list of documents that identifies the build status of product is referred to document register and should be submitted to LPCB.

H.4 Sensitivity Measurements:

Measurements shall be conducted in accordance with ISO 7240-6:2004 Clause 5.1.5 (Measurement of response threshold value) with detectors tested using the same setup as per the original evaluation. The detectors shall be deemed to comply if the following requirements are met : (a) All measurements shall lie within the allowed* limits as defined by Clause 5.4

(Reproducibility) of ISO 7240-6:2004.

* Note 1: Allowed limits are defined as the limits that manufactures’ could potentially manufacture to providing they still meet the requirements of the standard

- The maximum allowed limit is derived as follows :

1.33 x production mean as determined in the original evaluation† & m ≤ 45 µl/l

- The minimum allowed limit is derived as follows :

production mean as determined in the original evaluation† / 1.5 & m ≥ 25 µl/l

Page 25: BRE Global Limited LPCB Scheme Document SD 021: Issue No ... · For LPCB listing the manufacturer must have ISO 9001. Where applicants hold ISO 9001 with another Certification body,

BRE Global Ltd. Scheme Document SD 021

Issue Date: 21 July 2016 DETECTORS (Fire)

Issue No.: 5.2

Page 23 of 32

Controlled document valid only on date of printing © BRE Global Ltd, 2016

† Note 2: Where a detector has undergone a modification (approved by LPCB) which has changed the sensitivity range of the detector then the mean of that new range will be considered as the production mean for the above derivation.

(b) All measurements shall lie within the most recent, LPCB, approved‡ limits.

‡ Note 3: Approved limits are defined as the limits that have been measured in the CO chamber and compliance to the requirements of the standard has been confirmed and verified

(i) If any of the measurements fall below the minimum approved limit then the

detector may be likely to suffer from false alarms so further testing may be deemed to be necessary.

(ii) If any of the measurements exceed the maximum approved limit then the detector

may have insufficient sensitivity for meeting the fire test limits and so may be tested in accordance with ISO 7240-6:2004, Clause 5.21 (Fire sensitivity) and must meet the requirements of that clause in order to confirm compliance.

Page 26: BRE Global Limited LPCB Scheme Document SD 021: Issue No ... · For LPCB listing the manufacturer must have ISO 9001. Where applicants hold ISO 9001 with another Certification body,

BRE Global Ltd. Scheme Document SD 021

Issue Date: 21 July 2016 DETECTORS (Fire)

Issue No.: 5.2

Page 24 of 32

Controlled document valid only on date of printing © BRE Global Ltd, 2016

Annex I (Audit requirements for Carbon Monoxide Detectors Approved to LPS 1265 Issue 1.1)

This annex defines the LPCB audit requirements for continued certification / approval of the product. Failure to meet the audit requirements is deemed as a non-compliance, please refer to Section 10.3 for failure procedure. I.1 Marking:

The product must be marked in accordance with LPS 1265 Issue 1.1 Clause 4.8 and must indicate the LPS standard number i.e “LPS 1265 Issue 1.1”. In addition it must also meet the LPCB requirements specified in publication PN103.

I.2 Software Issue:

The software version must be the same as the version that was most recently approved by LPCB, this includes internal and external software required to operate the device where applicable.

I.3 Documentation:

The submitted build status of the audited sample shall be identical to the LPCB approved build status. Note: The list of documents that identifies the build status of product is referred to document register and should be submitted to LPCB.

I.4 Sensitivity Measurements:

Response threshold value measurements shall be conducted in accordance with LPS 1265 Issue 1.1, Clause 5.1.5 (Measurement of response threshold value) with detectors tested using the same setup as per the original evaluation. The detectors shall be deemed to comply if the following requirements are met : (a) All measurements shall lie within the allowed* limits as defined by Clause 5.4

(Reproducibility) and note: 2 of Clause 5.1.6 of LPS 1265 Issue 1.1.

* Note 1: Allowed limits are defined as the limits that manufactures’ could potentially manufacture to providing they still meet the requirements of the standard

- The maximum allowed limit is derived as follows :

1.33 x production mean as determined in the original evaluation†

- The minimum allowed limit is derived as follows :

production mean as determined in the original evaluation† / 1.5 & m ≥ 30 ppm

† Note 2: Where a detector has undergone a modification (approved by LPCB) which has changed the sensitivity range of the detector then the mean of that new range will be considered as the production mean for the above derivation.

Page 27: BRE Global Limited LPCB Scheme Document SD 021: Issue No ... · For LPCB listing the manufacturer must have ISO 9001. Where applicants hold ISO 9001 with another Certification body,

BRE Global Ltd. Scheme Document SD 021

Issue Date: 21 July 2016 DETECTORS (Fire)

Issue No.: 5.2

Page 25 of 32

Controlled document valid only on date of printing © BRE Global Ltd, 2016

(b) All measurements shall lie within the most recent, LPCB, approved‡ limits.

‡ Note 3: Approved limits are defined as the limits that have been measured in the CO chamber and compliance to the requirements of the standard has been confirmed and verified

(i) If any of the measurements fall below the minimum approved limit then the

the detector may be likely to suffer from false alarms so further testing may be deemed to be necessary.

(ii) If any of the measurements exceed the maximum approved limit then the detector

may have insufficient sensitivity for meeting the fire test limits and so may be tested in accordance with LPS 1265 Issue 1.1, Clause 5.19 (Fire sensitivity) and must meet the requirements of that clause in order to confirm compliance.

Page 28: BRE Global Limited LPCB Scheme Document SD 021: Issue No ... · For LPCB listing the manufacturer must have ISO 9001. Where applicants hold ISO 9001 with another Certification body,

BRE Global Ltd. Scheme Document SD 021

Issue Date: 21 July 2016 DETECTORS (Fire)

Issue No.: 5.2

Page 26 of 32

Controlled document valid only on date of printing © BRE Global Ltd, 2016

Annex J (Audit requirements for Carbon Monoxide / Heat Multi-sensor Fire Detectors Approved to LPS

1274, Issue 1.0) This annex defines the LPCB audit requirements for continued certification / approval of the product. Failure to meet the audit requirements is deemed as a non-compliance, please refer to Section 10.3 for failure procedure. J.1 Marking:

The product must be marked in accordance with LPS 1274 Issue 1.0 Clause 4.8 and must indicate the LPS standard number i.e “LPS 1274, Issue 1.0”. In addition it must also meet the LPCB requirements specified in publication PN103.

J.2 Software Issue:

The software version must be the same as the version that was most recently approved by LPCB, this includes internal and external software required to operate the device where applicable.

J.3 Documentation:

The submitted build status of the audited sample shall be identical to the LPCB approved build status. Note: The list of documents that identifies the build status of product is referred to document register and should be submitted to LPCB.

J.4 Carbon Monoxide Response Measurements:

Response threshold value measurements shall be conducted as described in Annex I.4 of this scheme document. Detectors shall be deemed to comply if the requirements specified in Annex I.4 are met.

J.5 Response Time & Temperature Measurements:

(a) Detectors for which the manufacturer claims compliance with EN 54-5: 2000 shall be

subjected to the tests specified in Annex B.4. The detectors shall be deemed to comply if the requirements of Annex B.4 and Clause 5.7 (Reproducibly of heat response) of LPS 1274, Issue 1.0 are met.

(b) Detectors for which the manufacturer does not claim compliance with EN 54-5: 2000

shall be tested in accordance with LPS 1274, Issue 1.0 Clause 5.7 (Reproducibility of heat response) with detectors tested using the same setup as per the original evaluation. The detectors shall be deemed to comply if the requirements of the Clause 5.7 are met.

Page 29: BRE Global Limited LPCB Scheme Document SD 021: Issue No ... · For LPCB listing the manufacturer must have ISO 9001. Where applicants hold ISO 9001 with another Certification body,

BRE Global Ltd. Scheme Document SD 021

Issue Date: 21 July 2016 DETECTORS (Fire)

Issue No.: 5.2

Page 27 of 32

Controlled document valid only on date of printing © BRE Global Ltd, 2016

Annex K (Audit requirements for Multi-sensor Fire Detectors Using Smoke / Carbon Monoxide &, optionally,

Heat Sensors Approved to LPS 1279 Issue 1.0) This annex defines the LPCB audit requirements for continued certification / approval of the product. Failure to meet the audit requirements is deemed as a non-compliance, please refer to Section 10.3 for failure procedure. K.1 Marking:

The product must be marked in accordance with LPS 1274, Issue 1.0 Clause 4.8 and must indicate the LPS standard number i.e “LPS 1274, Issue 1.0”. In addition it must also meet the LPCB requirements specified in publication PN103.

K.2 Software Issue:

The software version must be the same as the version that was most recently approved by LPCB, this includes internal and external software required to operate the device where applicable.

K.3 Documentation:

The submitted build status of the audited sample shall be identical to the LPCB approved build status. Note: The list of documents that identifies the build status of product is referred to document register and should be submitted to LPCB.

K.4 Carbon Monoxide Response Measurements:

Response threshold value measurements shall be conducted as described in Annex I.4 of this scheme document. Detectors shall be deemed to comply if the requirements specified in Annex I.4 are met.

K.5 Smoke Sensitivity Measurements:

Response threshold value measurements shall be conducted as described in Annex A.4 of this scheme document. Detectors shall be deemed to comply if the requirements specified in Annex A.4 are met.

K.6 Response Time & Temperature Measurements:

(a) Detectors for which the manufacturer claims compliance with EN 54-5: 2000 shall be

subjected to the tests specified in Annex B.4. The detectors shall be deemed to comply if the requirements of Annex B.4 and Clause 5.10 (Reproducibly of heat response) of LPS 1279, Issue 1.0 are met.

(b) Detectors for which the manufacturer does not claim compliance with EN 54-5: 2000

shall be tested in accordance with LPS 1279, Issue 1.0, Clause 5.10 (Reproducibility of heat response) with detectors tested using the same setup as per the original evaluation. The detectors shall be deemed to comply if the requirements of the Clause 5.10 are met.

Page 30: BRE Global Limited LPCB Scheme Document SD 021: Issue No ... · For LPCB listing the manufacturer must have ISO 9001. Where applicants hold ISO 9001 with another Certification body,

BRE Global Ltd. Scheme Document SD 021

Issue Date: 21 July 2016 DETECTORS (Fire)

Issue No.: 5.2

Page 28 of 32

Controlled document valid only on date of printing © BRE Global Ltd, 2016

Annex L (Audit requirements for Multi-sensor Fire Detectors Using

Smoke / Heat Sensors Approved to EN 54-29:2015) This annex defines the LPCB audit requirements for continued certification / approval of the product. Failure to meet the audit requirements is deemed as a non-compliance, please refer to Section 10.3 for failure procedure. L.1 Marking:

The product must be marked in accordance with EN 54-29:2015 Clause 8 and must indicate the European standard number i.e “EN 54-29:2015”. In addition it must also meet the LPCB requirements specified in publication PN103.

L.2 Software Issue:

The software version must be the same as the version that was most recently approved by LPCB, this includes internal and external software required to operate the device where applicable.

L.3 Documentation:

The submitted build status of the audited sample shall be identical to the LPCB approved build status. Note: The list of documents that identifies the build status of product is referred to document register and should be submitted to LPCB.

L.4 Smoke Sensitivity Measurements:

Response threshold value measurements shall be conducted as described in Annex A.4 of this scheme document. Detectors shall be deemed to comply if the requirements specified in Annex A.4 are met.

L.5 Heat Response Measurements:

Response time measurements shall be conducted in accordance with EN 54-5:2000 Clause 5.1.5 (Measurement of response time) at a rate of rise of 20K min-1 only with detectors tested in the least sensitive orientation using the same setup as per the original evaluation. The detectors shall be deemed to comply if the requirements of Tmax:Tmin ≤1.3 and if the limits have not changed by more than ±5% for a A2 heat detector or at a value to be determined from the methodology used during the original evaluation.

Page 31: BRE Global Limited LPCB Scheme Document SD 021: Issue No ... · For LPCB listing the manufacturer must have ISO 9001. Where applicants hold ISO 9001 with another Certification body,

BRE Global Ltd. Scheme Document SD 021

Issue Date: 21 July 2016 DETECTORS (Fire)

Issue No.: 5.2

Page 29 of 32

Controlled document valid only on date of printing © BRE Global Ltd, 2016

Annex M (Audit requirements for Carbon Monoxide Detectors to EN 54-26:2015)

This annex defines the LPCB audit requirements for continued certification / approval of the product. Failure to meet the audit requirements is deemed as a non-compliance, please refer to Section 10.3 for failure procedure. M.1 Marking:

The product must be marked in accordance with EN 54-26:2015 Clause 8 and must indicate the European standard number i.e “EN 54-26:2015”. In addition it must also meet the LPCB requirements specified in publication PN103.

M.2 Software Issue:

The software version must be the same as the version that was most recently approved by LPCB, this includes internal and external software required to operate the device where applicable.

M.3 Documentation:

The submitted build status of the audited sample shall be identical to the LPCB approved build status. Note: The list of documents that identifies the build status of product is referred to document register and should be submitted to LPCB.

M.4 Sensitivity Measurements:

Response threshold value measurements shall be conducted in accordance with EN 54-26:2015, Clause 5.1.5 (Measurement of response value) with detectors tested using the same setup as per the original evaluation. The detectors shall be deemed to comply if the following requirements are met : (c) All measurements shall lie within the allowed limits* as defined by Clause 5.2.6

(Reproducibility) and Clause 5.1.6 of EN 54-26:2015.

* Note 1: Allowed limits are defined as the limits that manufactures’ could potentially manufacture to providing they still meet the requirements of the standard

- The maximum allowed limit is derived as follows:

1.33 x production mean as determined in the original evaluation†

- The minimum allowed limit is derived as follows :

production mean as determined in the original evaluation† / 1.5 & Smin ≥ 25 μl/l

† Note 2: Where a detector has undergone a modification (approved by LPCB) which has changed the sensitivity range of the detector then the mean of that new range will be considered as the production mean for the above derivation.

Page 32: BRE Global Limited LPCB Scheme Document SD 021: Issue No ... · For LPCB listing the manufacturer must have ISO 9001. Where applicants hold ISO 9001 with another Certification body,

BRE Global Ltd. Scheme Document SD 021

Issue Date: 21 July 2016 DETECTORS (Fire)

Issue No.: 5.2

Page 30 of 32

Controlled document valid only on date of printing © BRE Global Ltd, 2016

(d) All measurements shall lie within the most recent, LPCB, approved‡ limits.

‡ Note 3: Approved limits are defined as the limits that have been measured in the CO chamber and compliance to the requirements of the standard has been confirmed and verified

(i) If any of the measurements fall below the minimum approved limit then the

the detector may be likely to suffer from false alarms so further testing may be deemed to be necessary.

(ii) If any of the measurements exceed the maximum approved limit then the detector

may have insufficient sensitivity for meeting the fire test limits and so may be tested in accordance with EN 54-26:2015, Clause 5.5.1 (Fire sensitivity) and must meet the requirements of that clause in order to confirm compliance.

Page 33: BRE Global Limited LPCB Scheme Document SD 021: Issue No ... · For LPCB listing the manufacturer must have ISO 9001. Where applicants hold ISO 9001 with another Certification body,

BRE Global Ltd. Scheme Document SD 021

Issue Date: 21 July 2016 DETECTORS (Fire)

Issue No.: 5.2

Page 31 of 32

Controlled document valid only on date of printing © BRE Global Ltd, 2016

Annex N (Audit requirements for Multi-Sensor Fire Detectors Using Carbon Monoxide & Heat Sensors to EN

54-30:2015) This annex defines the LPCB audit requirements for continued certification / approval of the product. Failure to meet the audit requirements is deemed as a non-compliance, please refer to Section 10.3 for failure procedure. N.1 Marking:

The product must be marked in accordance with EN 54-30:2015 Clause 8 and must indicate the European standard number i.e “EN 54-30:2015”. In addition it must also meet the LPCB requirements specified in publication PN103.

N.2 Software Issue:

The software version must be the same as the version that was most recently approved by LPCB, this includes internal and external software required to operate the device where applicable.

N.3 Documentation:

The submitted build status of the audited sample shall be identical to the LPCB approved build status. Note: The list of documents that identifies the build status of product is referred to document register and should be submitted to LPCB.

N.4 Carbon Monoxide Response Measurements:

Response value measurements shall be conducted as described in Annex M.4 of this scheme document. Detectors shall be deemed to comply if the requirements specified in Annex M.4 are met.

N.5 Response Time & Temperature Measurements:

Response time measurements shall be conducted as described in Annex L.5 of this scheme document. Detectors shall be deemed to comply if the requirements specified in Annex L.5 are met.

Page 34: BRE Global Limited LPCB Scheme Document SD 021: Issue No ... · For LPCB listing the manufacturer must have ISO 9001. Where applicants hold ISO 9001 with another Certification body,

BRE Global Ltd. Scheme Document SD 021

Issue Date: 21 July 2016 DETECTORS (Fire)

Issue No.: 5.2

Page 32 of 32

Controlled document valid only on date of printing © BRE Global Ltd, 2016

Annex O (Audit requirements for Multi-Sensor Fire Detectors Using Smoke, Carbon Monoxide & Optionally

Heat Sensors to EN 54-31:2014) This annex defines the LPCB audit requirements for continued certification / approval of the product. Failure to meet the audit requirements is deemed as a non-compliance, please refer to Section 10.3 for failure procedure. O.1 Marking:

The product must be marked in accordance with EN 54-31:2014 Clause 8 and must indicate the European standard number i.e. “EN 54-31:2014”. In addition it must also meet the LPCB requirements specified in publication PN103.

O.2 Software Issue:

The software version must be the same as the version that was most recently approved by LPCB, this includes internal and external software required to operate the device where applicable.

O.3 Documentation:

The submitted build status of the audited sample shall be identical to the LPCB approved build status. Note: The list of documents that identifies the build status of product is referred to document register and should be submitted to LPCB.

O.4 Carbon Monoxide Response Measurements:

Response threshold value measurements shall be conducted as described in Annex M.4 of this scheme document. Detectors shall be deemed to comply if the requirements specified in Annex M.4 are met.

O.5 Smoke Sensitivity Measurements:

Response threshold value measurements shall be conducted as described in Annex A.4 of this scheme document. Detectors shall be deemed to comply if the requirements specified in Annex A.4 are met.

O.6 Response Time & Temperature Measurements:

Response time measurements shall be conducted as described in Annex L.5 of this scheme document. Detectors shall be deemed to comply if the requirements specified in Annex L.5 are met.