DurableCorrosion ResistantCooling Towers
THERMAL PERFORMANCE CERTIFIED
BY THE COOLING TECHNOLOGY INSTITUTE
VALIDATION NO. 00-22-02
REYMSA COOLING TOWERSMarket in providing solutions to their particular cooling needs, always looking for the total satisfaction of our customers.
This commitment and the experience of our Engineers, combined with supreme quality, premium materials and components used to manufacture our products, gave birth to the “state of the art” HRFG Series by REYMSA Cooling Towers.
Certified by the CTI (Cooling Technology Institute), Certificate Number: 00-22-02 and 100% FRP manufactured in order to provide the highest performance and longest service life possible, to serve those who demand the best and we are also committed to maintaning all producion equipment at its optimum condition.
, INC. has been committed for over 30 years to the Commercial and Industrial
HRFG SERIES FEATURES
An FRP laminate is 5 times lighter than its equivalent of the same size and thickness made from steel. You will also find that when compared to a steel laminate of the same mechanical resistance, the FRP laminate is about half as heavy.
The low coefficient of expansion of the FRP material makes it highly resistant to wide variations of temperature and humidity without showing any deformation. These properties allow REYMSA Cooling Towers to withstand many different types of environments.
Only for appearance purposes, such as dusting or waxing.
It is very easy to perform minor repair work on the fiberglass. Materials are available all across the country, and the fixing process is as easy as grinding the surface, applying the Polyester Resin, which is in the form of a liquid, to a layer of fiberglass cloth and applying the resin again. Finally, wait until the resin is dried.
All FRP unitized casing and internal structure
UV Protection for extended life & strength
Optimum Design for all season performance including freezing climates
Fiberglass-Reinforced-Polyamide adjustable pitch Fans
Self extinguish PVC fill & PVC drift eliminator
Direct drive, low speed, TEFC, NEMA fan motors
Low noise operation
No moving internal parts
Fixed distribution nozzles with variable flow rates
Triple-pass PVC Air Inlet Louvers
Large, easily removable access doors
Corrosion resistant strainers
Single or multiple fan configurations with common sump
FIBERGLASS REINFORCED POLYESTER (FRP) PROPERTIES
FRP material is highly resistant to tension and compression stresses and to impact forces as well; making it a frequently used material in structural applications.
As a rule of thumb, an FRP laminate requires three times the thickness than a steel laminate in order to have the same mechanical resistance.
A very simple analogy can be used to have a clear understanding of the FRP properties: The Polyester Resin can be seen as the Cement and the Fiberglass as the corrugated bars in reinforced concrete.
FRP has at least twice the mechanical resistance of HDPE.
There are several types of polyester resin available in the market for different applications and resistances. The highest protection against environmental attacks is reached by using Premium Isophalic Polyester Resin with UV inhibitor in the manufacturing process of all our Cooling Towers. The life of FRP with Premium Isopthalic resin is said to be endless, however, REYMSA recommends using 30 years when making a life-cycle cost analysis.
HIGH MECHANICAL RESISTANCE LIGHT WEIGHT
STABILITY
ZERO OR NO MAINTENANCE REQUIRED
VERY EASY TO WORK WITH
GREAT CHEMICAL AND WEATHER RESISTANCE
Great Resistance to Corrosion and many chemical agents.
CORROSION RESISTANCE
2
ALL FIBERGLASS, ONE PIECE, SEAMLESS CONSTRUCTION WITH HIGH MECHANICAL RESISTANCE, LONG LIFE CONSTRUCTION, AND MINIMUM OR ZERO MAINTENANCE, WITHOUT WATER LEAKAGE PROBLEMS
Corrosion resistant.
Major longevity, life expectancy of 30 plus years.
No risk of water leakage, a unique seamless, one piece construction.
Better appearance, aesthetically superior.
Excellent mechanical resistance and stabilty, capable of working in all kinds of environments weathers.
Exterior and interior gelcoat protective layer with UV Inhibitor:
Not affected by corrosive sediments caused by airborne impurities collected of galvanized and stainless steel towers to be drained, cleaned and flushed
quarterly.
Greater resistance to a wide spectrum of pH´s, total dissolved solids, chlorides and sulfates from the water treatement.
(galvanized and/or stainless) Towers. Typically a Pulsed Power Non Chemical water treatment is able to handle up to 400 ppm of concentration of chlorides in the recirculation water, which means more cycles of concentration and less water losses caused by bleeds or blowdowns.
in the basin that require all the cold water in the basin
REYMSA Cooling Towers have the capacity to endure higher levels of concentration of chlorides in the water than Steel
* Great resistance against :
1- Agressive chemical conditions of the water2- Weathering3- Harmful industrial contaminates
Maximum Reliability with Efficiency
REYMSA COOLING TOWERS, INC. 4
Direct drive transmission that eliminates the use of pulleys, belts and bearings.
Our direct drive motors eliminate the frequent service required by the V-belt drive transmissions that have higher operational and maintenance costs. Typically a V-belt drive transmission requires quarterly service for checking and readjusting the tension of the belt, lubrication of fan shaft bearings, lubrication of the motor base adjusting screws and drive alignment to ensure maximum belt life.
Also, by having fewer components between the fan and the motor, the risk of a failure causing a sudden stop of the fan and higher operational water temperatures that may in turn stop the entire air conditioning system is reduced to a minimum.
REYMSA uses the best fan in the market; manufactured using cast aluminum hubs and adjustable pitch air foil blades molded with engineering thermoplastics.
Blade materials: fiberglass reinforced polyamide, which is spark and corrosive resistant and is able to resist high vibration levels and high temperatures. Ambient operating air temperatures may fluctuate from – 50°F to 250°F.
Fan Motors: all our Tower models feature motors that exceed the Cooling Tower duty characteristics. REYMSA Fan Motors are NEMA Premium Efficient, TEFC, 1.15 service factor, 100% cast iron construction for SEVERE DUTY, INVERTER DUTY, and MARINE DUTY applications, EPOXY PAINT, inpro/ seal vbx bearing isolators on both ends of the shaft, brass drain and breather, 6-60 hz variable torque.
DIRECT DRIVE ON ALL OF OUR TOWER MODELS, FOR A MORE RELIABLE OPERATION WITH MUCH LOWER SERVICE AND OPERATION COSTS, AND MINIMAL RISK OF A FAILURE
REYMSA COOLING TOWERS, INC.
Durability & Minimum Maintenance
5REYMSA COOLING TOWERS, INC. 5
Maximum Reliability with Efficiency
REYMSA COOLING TOWERS, INC. 5REYMSA COOLING TOWERS, INC. 6
HIGHEST SURFACE TO VOLUME RATIO PVC FILL FOR SMALLER FOOTPRINT
By having the highest specific
our fill provides the highest
for all HVAC and most Industrial
applications. The PVC compounds used in our fill
have outstanding resistance to weather exposure
and are nearly impervious to chemical degradation
by alkali, acids, grease, fats, oils and biological
attack. fire rating due
to its self-extinguishing characteristics and meets
or exceeds Cooling Technology Institute (CTI)
PVC materials standard 136.
2 3surface area (ft /ft ),
surface area for heat
transfer
Our fill also has an excellent
The hot water manifold is manufactured out of PVC, with PVC welded branches tested at 100 psig., to assure reliability and prevent water leakages that affect the tower efficiency. This avoids wearing of the union gasket unlike other tower manufacturers.
THE MOST RELIABLE HOT WATER DISTRIBUTION SYSTEM
Fixed, non-clogging, 2 ½ , N.P.T., large orifice nozzles are the largest on the market. They are manufactured out of ABS plastic and are able to handle water temperatures up to 180 ºF. Nozzles have with interchangeable internal devices so that water is efficiently and uniformly distributed across the entire fill surface. Nozzle body has a threaded connection and is easy to remove.
"
NON CLOGGING SPRAY NOZZLES
2½" N.P.T. ABS-Spray Nozzleswith interchangeable
internal devices
EASY, REMOVABLE, ENVIRONMENTALLY FRIENDLY AIR INLET LOUVER DESIGN
Our triple pass PVC air inlet louvers are designed to block direct sunlight to the water, to minimize splash-out, and to reduce noise; while at the same time having a low pressure drop that results in less fan motor energy consumption. By blocking direct sunlight and allowing very little light to pass into the tower, the potential of algae growth is reduced and therefore so are the water treatment and maintenance costs. Additionally, the Louvers are durable, corrosion resistant, and impervious to chemical attacks. The PVC is specially formulated for UV and fire resistance and is non-combustible and self-extinguishing.
EASY MAINTENANCE AND CLEANING ACCESS
Wide and easy access for monitoring or cleaning the inside of the Tower and the cold water basin by removing the access door or the air inlet louvers.
RemovableAccess Door
RemovableAir inlet Louvers
In Addition to our Guarantee of the Thermal Performance of our Cooling Towers, the HRFG Series are Certified by the Cooling Technology Institute (CTI) according to the Standard Std-201. Validation No. 00-22-02
CTI CERTIFICATION OF THERMAL PERFORMANCE
Durability & Minimum Maintenance
7REYMSA COOLING TOWERS, INC.
8REYMSA COOLING TOWERS, INC.
A family owned Company founded in 1969 who really understands the importance of having satisfied customers to build long term relationships.
Assembly is reduced to placing and bolting the fan cylinder on top of the one-piece body and basin section. No gasket or caulking is required.
The reduced footprint of our Induced Draft, Counterflow design requires less structural base support, and frequently less piping than the crossflow towers.
´
EASY AND ECONOMICAL ASSEMBLY AND INSTALLATION COST
Every single tower is assembled and tested at our factory prior to shipment.
FACTORY TESTS
FRIENDLY, EASY TO DEAL WITH COMPANY
Maximum Reliability with Efficiency
´
Automatic Sand Filtration System for Suspended Solids RFS SeriesSweeper Piping for Water FiltrationVibration Isolators Variable Frequency DriveBasket Non-Corrosive Strainers for Outlet Connection (Standard)
OPTIONAL DESIGNS WITH CUSTOMIZED COMPONENTS OR COLORS FOR SPECIAL APPLICATIONS
Special Colors, Designs or Configurations
Sickle Fans for Low Noise applications
Special fills for industrial applications with bigger flutes, vertical design or for higher than 130°F water temperature.
OPTIONAL EQUIPMENT
Sound DeflectorsAccess LadderStainless Steel HandrailVibration Cut off SwitchElectric HeatersElectric Water Level ControlBottom Outlet (Dry Sump)Basin Equalizer ConnectionsStainless Steel Davit SupportSpecial Fan Motor ConstructionStainless Steel Non-Skid Catwalk
Tower casing construction with flame retardant resin according to the ASTM-E84 Standard.
Durability & Minimum Maintenance
9REYMSA COOLING TOWERS, INC.
10REYMSA COOLING TOWERS, INC.
Construction Details
11
9
7
12
6
4
2
13
10
5
1
3
8
Water Make up
Cold Water Outlet
Mounting Holes
Overflow (back side)
Drain (back side)
Purge (back side)
11.
12.
13.
14.
15.
16.
Hot Water Inlet
Body Section
Cellular Fill
Air Inlet Louvers
Basin Section
Fan Section
Plenum
Drift Eliminator
Lifting Eyes
Spray Nozzle Manifold
6.
7.
8.
9.
10.
1.
2.
3.
4.
5.
* A Nominal TON is defined as 3 GPM of water cooled from 95°F to 85°F with a 78°F entering wet bulb.** Modular sections to be assembled for higher tonage requirements. Minimum two modules. Contact your Rep for proper selection.1. All dimensions, weights and capacities are in inches, pounds and gallons. Physical dimensions of each tower are approximate and are subject to change.2. All double and quadruple models have double fittings and connections.
Single Double Fan
H H H
L L
L L L
L
Quadruple Fan
OverflowCold WaterOutlet
Height W/OFan Drain
MODELL W H
*NominalTons
DIMENSIONSMotor
HPPurgeHot Water
Inlet
2426
4353
6175
90107
141155
152169192
163184205
171190210
210243266
267 291 313
281311
343 380 420
565 622
685 760 840
954 1056
11561236
477 528
578 618
35¼35¼
4848
6161
7373
83½83½
969696
110¾110¾110¾
969696
120½120½120½
145 145 145
167167
199½ 199½ 199½
175 175
199½ 199½ 199½
268 268
328 328
268 268
328 328
35¼ 35¼
48 48
61 61
73 73
83½ 83½
84 84 84
85¾ 85¾ 85¾
96 96 96
96 96 96
96 96 96
83½ 83½
104¾104¾104¾
174 174
201 201 201
197½ 197½
197½ 197½
98¾98¾
98¾98¾
107½ 107½
122 122
127½127½
128 128
134 134
134 134 134
134 134 134
154 154 154
153 153 153
154 154 154
134 134
159 159 159
134 134
159 159 159
205 205
282 282
282 282
301301
9090
9898
9797
9898
9898
989898
989898
119119119
118118118
119119119
9898
123123123
9898
123123123
246 246
263 263
246246
263263
2½ 2½
2½ 2½
4 4
4 4
6 6
6 6 6
6 6 6
6 6 6
6 6 6
8 8 8
8 8
8 8 8
(2) 8 (2) 8
(2) 10 (2) 10 (2) 10
(2) 10 (2) 10
(2) 10 (2) 10
1010
1010
¾ ¾
¾ ¾
1 1
1 1
1½ 1½
1½ 1½ 1½
1½ 1½ 1½
1½ 1½ 1½
2 2 2
2 2 2
2 2
2 2 2
(2) 2 (2) 2
(2) 2 (2) 2 (2) 2
(2) 2 (2) 2
(2) 2 (2) 2
22
22
1 1
1 1
1 1
1 1
1½ 1½
1½ 1½ 1½
1½ 1½ 1½
1½ 1½ 1½
2 2 2
2 2 2
1½ 1½
2 2 2
(2) 2 (2) 2
(2) 2 (2) 2 (2) 2
(2) 2 (2) 2
(2) 2 (2) 2
22
22
½ ½
½ ½
¾ ¾
¾ ¾
¾ ¾
¾ ¾ ¾
¾ ¾ ¾
¾ ¾ ¾
¾ ¾ ¾
¾ ¾ ¾
¾ ¾
¾ ¾ ¾
(2) ¾ (2) ¾
(2) ¾ (2) ¾ (2) ¾
(2) ¾ (2) ¾
(2) ¾ (2) ¾
¾ ¾
¾ ¾
½ ½
½ ½
½ ½
½ ½
1 1
1 1 1
1 1 1
1 1 1
1 1 1
1 1 1
1 1
1½ 1½ 1½
(2)1½ (2)1½
(2) 1½ (2) 1½ (2) 1½
(2) 1½ (2) 1½
(2) 1½ (2) 1½
1½ 1½
1½1½
2½ 2½
2½ 2½
4 4
4 4
6 6
6 6 6
6 6 6
6 6 6
6 6 6
8 8 8
8 8
8 8 8
(2) 8 (2) 8
(2) 8 (2) 8 (2) 8
(2) 8 (2) 8
(2) 8 (2) 8
88
88
727 727
1022 1022
1366 1366
1890 1890
2553 2553
2717 2717 2717
2912 2912 2912
2986 2986 2986
3548 3548 3548
4028 4028 7028
4674 4674
5476 5476 5476
9349 9349
109531095310953
18210 18210
22330 22330
9105 9105
1116511165
1427 1427
2234 2234
3189 3189
4415 4415
5624 5624
6230 6230 6230
6863 6863 6863
6992 6992 6992
8522 8522 8522
9965 9965 9965
10818 10818
13213 1321313213
2163721637
264272642726427
3998039980
51330 51330
1999019990
2566525665
1.5 2
3 5
3 5
5 7.5
7.5 10
7.5 10 15
7.5 10 15
7.5 10 15
10 15 20
15 20 25
(2)7.5 (2)10
(2)7.5 (2)10 (2)15
(4)7.5 (4)10
(4)7.5 (4)10 (4)15
(4)15 (4)20
(4)15 (4)20
(2)15 (2)20
(2)15 (2)20
HRFG-303115HRFG-303102
HRFG-404103HRFG-404105
HRFG-505103HRFG-505105
HRFG-606105HRFG-606175
HRFG-707175HRFG-707110
HRFG-708175HRFG-708110HRFG-708115
HRFG-709175HRFG-709110HRFG-709115
HRFG-808175HRFG-808110HRFG-808115
HRFG-810110HRFG-810115HRFG-810120
HRFG-812115HRFG-812120HRFG-812125
HRFG-714275HRFG-714210
HRFG-816275HRFG-816210HRFG-816215
HRFG-1414475HRFG-1414410
HRFG-1616475HRFG-1616410HRFG-1616415
HRFG-1622415 HRFG-1622420
HRFG-1627415 HRFG-1627420
HRFG-822215**HRFG-822220**
HRFG-827215** HRFG-827220**
WaterMakeup
CONNECTION DIAMETER WEIGHT
OperatingShipping
Engineering Data
W W
W
11REYMSA COOLING TOWERS, INC.
12REYMSA COOLING TOWERS, INC.
R A N G E R A N G E
62 Deg. Wet Bulb60 Deg. Wet Bulb
APPROACH
5
6
7
8
10
12
14
16
6
3.15
3.60
4.05
4.50
5.49
6.36
8
2.70
3.03
3.42
3.75
4.50
5.31
6.00
10
2.43
2.73
3.00
3.36
3.96
4.59
5.25
5.91
2.49
2.73
3.00
3.60
4.14
4.65
5.25
2.49
2.70
3.21
3.66
4.14
4.62
2.40
2.79
3.18
3.60
4.05
2.55
2.88
3.21
3.60
2.40
2.76
3.09
3.45
2.61
2.88
3.21
12 15 20 26 30 35 APPROACH 6
3.33
3.78
4.26
4.65
5.70
6.75
8
2.85
3.21
3.75
3.96
4.71
5.55
6.45
10
2.55
2.88
3.18
3.51
4.14
4.80
5.55
6.21
12
2.34
2.61
2.91
3.18
3.78
4.32
4.95
5.55
2.37
2.61
2.85
3.33
3.84
4.35
4.85
2.34
2.55
2.88
3.36
3.81
4.23
2.31
2.67
3.00
3.39
3.78
2.55
2.91
3.24
3.63
2.40
2.73
3.06
3.45
15 20 26 30 35
5
6
7
8
10
12
14
16
EXAMPLE:
Select the HRFG Model REYMSA Cooling Tower to cool 1200 GMP of clear water from 95 °F to 85 °F at entering air wet bulb of 78 °F.
STEP 1 RANGE is equal to the temperature differential between the entering water temperature ( T1 ) and the leaving water temperature ( T2). (95 °F - 85 °F ) = 10
STEP 2 APPROACH is equal to the temperature differential between the leaving cool water temperature ( T2 ) and wet bulb temperature ( TWB ). ( 85 °F - 78 °F ) = 7
STEP 3 From Section A: TOWER SELECTION FACTORS; Select the apropriate wet bulb temperature table ( 78 °F ). Select the range column ( 10 ) and in Approach row ( 7 ), the Tower Selection Factor = 4.8
STEP 4 Next, go to Section B: CAPACITY TABLES; Enter the column headed by the “ Tower Selection Factor ” determined from Section A ( 4.8 ) and read down that column to the desired cooling water flow rate equal to or greater than that specified ( 1200 gmp ). Look to the left on the row with the desired cooling water flow and read the corresponding HRFG816215 REYMSA Cooling Tower model to satisfy your requirements.
HRFG SERIES TOWER SELECTION
Sección A: TOWER SELECTION FACTORS
Maximum Reliability with Efficiency
63 Deg. Wet Bulb
66 Deg. Wet Bulb
70 Deg. Wet Bulb
73 Deg. Wet Bulb
R A N G E
R A N G E
R A N G E
R A N G E
64 Deg. Wet Bulb
68 Deg. Wet Bulb
72 Deg. Wet Bulb
74 Deg. Wet Bulb
R A N G E
R A N G E
R A N G E
R A N G E
APPROACH
APPROACH
APPROACH
APPROACH
5
5
5
5
6
6
6
6
7
7
7
7
8
8
8
8
10
10
10
10
12
12
12
12
14
14
14
14
16
16
16
16
APPROACH
APPROACH
APPROACH
APPROACH
5
5
5
5
6
6
6
6
7
7
7
7
8
8
8
8
10
10
10
10
12
12
12
12
14
14
14
14
16
16
16
16
6
3.42
3.90
4.35
4.80
5.85
8
2.88
3.30
3.66
4.05
4.80
5.61
6.54
10
2.58
2.91
3.21
3.54
4.23
4.89
5.61
6.36
12
2.40
2.67
2.94
3.24
3.81
4.41
5.04
5.64
2.43
2.67
2.91
3.42
3.96
4.44
5.04
2.40
2.61
3.00
3.48
3.90
4.35
2.37
2.73
3.12
3.54
3.90
2.64
2.97
3.36
3.75
2.49
2.79
3.15
3.54
6
3.54
4.02
4.47
5.01
6.00
8
2.97
3.39
3.75
4.14
4.95
5.79
6.60
10
2.64
2.91
3.30
3.63
4.29
5.01
5.70
6.36
12
2.43
2.73
3.00
3.30
3.90
4.50
5.16
5.85
2.49
2.76
2.97
3.54
4.02
4.56
5.16
2.46
2.70
3.09
3.60
3.99
4.50
2.43
2.82
3.21
3.63
4.02
2.31
2.67
3.00
3.39
3.78
2.55
2.91
3.24
3.63
15 20 26 30 35
6
3.72
4.26
4.74
5.31
6.36
8
3.21
3.63
3.99
4.41
5.19
6.09
10
2.82
3.15
3.54
3.84
4.59
5.31
6.06
12
2.61
2.91
3.21
3.54
4.17
4.80
5.52
6.15
15
2.37
2.61
2.88
3.12
3.72
4.26
4.80
5.46
2.37
2.61
2.82
3.27
3.75
4.26
4.71
2.37
2.55
2.91
3.36
3.78
4.23
2.43
2.82
3.21
3.60
3.99
2.34
2.70
3.03
3.42
3.81
20 26 30 35 6
3.93
4.41
4.95
5.55
6.75
8
3.33
3.75
4.17
4.59
5.52
6.45
10
2.94
3.30
3.69
4.05
4.74
5.58
6.36
12
2.73
3.03
3.39
3.72
4.35
5.04
5.76
6.51
15
2.49
2.91
3.00
3.30
3.90
4.44
5.04
5.70
20
2.25
2.49
2.70
2.94
3.42
3.93
4.41
4.95
2.28
2.49
2.70
3.09
3.57
3.99
4.41
2.31
2.49
2.85
3.21
3.60
4.02
2.40
2.61
2.97
3.39
3.81
4.26
26 30 35
6
4.05
4.56
5.16
5.46
8
3.54
3.96
4.41
4.89
5.82
6.90
10
3.12
3.51
3.90
4.26
5.04
5.91
6.75
12
2.88
3.21
3.54
3.90
4.56
5.34
6.00
15
2.61
2.91
3.21
3.51
4.11
4.65
5.34
5.94
20
2.37
2.61
2.85
3.06
3.60
4.14
4.65
5.28
26 30
2.43
2.67
3.00
3.48
3.87
4.32
2.31
2.52
2.73
3.15
3.60
4.02
4.47
2.40
2.64
2.85
3.30
3.78
4.23
4.74
35 6
4.35
4.95
5.55
6.09
8
3.69
4.14
4.59
5.04
6.00
10
3.27
3.72
4.11
4.47
5.34
6.15
12
3.00
3.42
3.75
4.11
4.80
5.55
6.36
15
2.73
3.03
3.36
3.69
4.32
5.01
5.64
6.36
20
2.52
2.79
3.03
3.30
3.84
4.38
5.04
5.61
26
2.31
2.55
2.79
3.00
3.51
3.93
4.44
5.04
2.43
2.67
2.85
3.30
3.78
4.26
4.71
2.34
2.55
2.79
3.18
3.60
4.05
4.50
30 35
6
4.38
4.98
5.58
6.15
8
3.78
4.29
4.71
5.25
6.21
10
3.39
3.81
4.23
4.62
5.55
6.36
12
3.12
3.54
3.93
4.26
4.89
5.79
6.60
15
2.82
3.18
3.51
3.78
4.44
5.10
5.79
6.45
20
2.55
2.85
3.09
3.42
3.96
4.50
5.10
5.70
26
2.40
2.64
2.91
3.09
3.60
4.11
4.65
5.16
30
2.28
2.52
2.73
2.94
3.42
3.90
4.35
4.86
2.40
2.64
2.85
3.27
3.72
4.17
4.59
35 6
4.47
5.19
5.76
6.90
8
3.84
4.35
4.86
5.34
6.36
10
3.48
3.90
4.32
4.74
5.61
6.60
12
3.18
3.60
3.96
4.32
5.13
5.88
6.75
15
2.91
3.24
3.60
3.90
4.56
5.31
6.00
20
2.67
2.91
3.21
3.48
4.05
4.59
5.22
5.85
26
2.43
2.67
2.91
3.18
3.66
4.14
4.68
5.25
30
2.37
2.58
2.82
3.00
3.54
3.99
4.47
5.04
35
2.28
2.49
2.70
2.91
3.39
3.84
4.29
4.77
20 26 30 3515
Durability & Minimum Maintenance
13REYMSA COOLING TOWERS, INC.
14REYMSA COOLING TOWERS, INC.
5
6
7
8
10
12
14
16
5
6
7
8
10
12
14
16
APPROACH 6
4.71
5.40
6.00
6.75
8
4.05
4.56
5.10
5.61
6.75
10
3.69
4.14
4.53
5.04
5.91
12
3.42
3.78
4.17
4.56
5.40
6.15
15
3.06
3.45
3.78
4.14
4.80
5.55
6.24
20
2.79
3.09
3.42
3.72
4.29
4.89
5.55
6.15
26
2.61
2.85
3.12
3.42
3.90
4.44
5.04
5.58
30
2.49
2.73
2.97
3.24
3.72
4.26
4.74
5.28
35
2.40
2.64
2.85
3.06
3.60
4.05
4.50
5.10
6
4.62
5.31
5.91
6.45
8
3.96
4.44
5.01
5.52
6.06
10
3.54
3.99
4.41
4.89
5.76
6.66
12
3.27
3.66
4.05
4.41
5.16
6.00
15
3.00
3.36
3.69
4.02
4.71
5.46
6.15
20
2.70
2.97
3.30
3.60
4.17
4.71
5.40
6.00
26
2.52
2.79
3.00
3.30
3.81
4.32
4.86
5.40
30
2.40
2.67
2.88
3.09
3.60
4.05
4.56
5.16
35
2.34
2.55
2.79
2.97
3.36
3.90
4.38
4.89
5
6
7
8
10
12
14
16
APPROACH
5
6
7
8
10
12
14
16
6
4.86
5.55
6.15
8
4.20
4.71
5.28
5.79
10
3.75
4.23
4.59
5.10
6.00
12
3.48
3.87
4.29
4.65
5.52
6.36
15
3.18
3.54
3.87
4.26
4.95
5.70
6.45
20
2.91
3.21
3.51
3.84
4.41
5.04
5.70
6.36
26
2.67
2.91
3.18
3.45
3.99
4.50
5.16
5.76
30
2.55
2.79
3.06
3.30
3.81
4.35
4.86
5.52
35
2.49
2.70
2.94
3.21
3.69
4.17
4.65
5.19
6
5.04
5.70
6.36
8
4.38
4.95
5.52
6.00
10
3.87
4.32
4.80
5.28
6.24
12
3.57
3.99
4.38
4.80
5.67
6.60
15
3.21
3.60
3.93
4.32
5.07
5.85
6.60
20
2.97
3.27
3.60
3.90
4.50
5.19
5.85
6.60
26
2.70
2.97
3.27
3.57
4.11
4.65
5.25
5.85
30
2.67
2.91
3.15
3.45
3.93
4.47
5.04
5.64
35
2.52
2.76
2.97
3.21
3.75
4.26
4.74
5.28
5
6
7
8
10
12
14
16
APPROACH
5
6
7
8
10
12
14
16
6
5.10
5.79
6.51
8
4.44
5.04
5.55
6.15
10
3.93
4.41
4.89
5.40
6.36
12
3.69
4.11
4.50
4.92
5.85
6.75
15
3.36
3.75
4.11
4.44
5.25
6.00
20
3.00
3.36
3.69
3.96
4.59
5.25
5.94
6.75
26
2.82
3.09
3.42
3.69
4.26
4.80
5.46
6.00
30
2.70
2.94
3.21
3.51
4.02
4.59
5.16
5.79
35
2.58
2.88
3.09
3.39
3.90
4.38
4.92
5.52
6
5.28
6.00
6.75
8
4.50
5.10
5.70
6.24
10
4.11
4.56
5.10
5.61
6.60
12
3.78
4.20
4.65
5.10
6.00
15
3.45
3.81
4.20
4.56
5.40
6.15
20
3.09
3.48
3.78
4.14
4.74
5.46
6.09
26
2.85
3.15
3.45
3.75
4.35
4.92
5.55
6.15
30
2.79
3.03
3.33
3.63
4.14
4.68
5.34
5.85
35
2.70
2.94
3.21
3.51
3.99
4.50
5.10
5.64
5
6
7
8
10
12
14
16
APPROACH
5
6
7
8
10
12
14
16
6
5.49
6.15
6.90
8
4.65
5.31
5.88
6.54
10
4.20
4.62
5.16
5.70
6.75
12
3.84
4.32
4.74
5.16
6.15
15
3.54
3.96
4.32
4.71
5.49
6.36
20
3.21
3.57
3.90
4.26
4.89
5.61
6.36
26
2.94
3.24
3.57
3.81
4.41
5.04
5.70
6.36
30
2.85
3.18
3.48
3.75
4.29
4.86
5.49
6.09
35
2.73
3.00
3.30
3.60
4.08
4.65
5.16
5.79
6
5.55
6.33
8
4.74
5.40
6.00
6.60
10
4.26
4.74
5.28
5.79
6.90
12
3.96
4.44
4.89
5.40
6.30
15
3.60
3.99
4.38
4.77
5.64
6.45
20
3.20
3.63
3.93
4.29
5.01
5.70
6.45
26
3.03
3.36
3.69
3.96
4.56
5.25
5.85
6.60
30
2.94
3.21
3.54
3.81
4.35
5.04
5.64
6.21
35
2.85
3.09
3.42
3.63
4.20
4.74
5.34
5.94
APPROACH
75 Deg. Wet Bulb R A N G E
76 Deg. Wet Bulb
APPROACH
77 Deg. Wet Bulb 78 Deg. Wet Bulb
APPROACH
79 Deg. Wet Bulb 80 Deg. Wet Bulb
APPROACH
81 Deg. Wet Bulb 82 Deg. Wet Bulb
R A N G E
R A N G E R A N G E
R A N G E R A N G E
R A N G E R A N G E
Maximum Reliability with Efficiency
Section B: CAPACITY TABLES GPM
2.4 2.8 3.2 4.83.6 54.4 5.8 6.64 5.4 6.2MODEL
Durability & Minimum Maintenance
SELECTION FACTORS
15REYMSA COOLING TOWERS, INC.
303115303102
404103404105
505103505105
606105606175
707175707110
708175708110708115
709175709110709115
808175808110808115
810110810115810120
812115 812120 812125
714275 714210
816275816210816215
822215822220
827215827220
14144751414410
161647516164101616415
16224151622420
16274151627420
3639
6580
92113
135161
212233
228254288
245276308
257285315
315365399
401437470
422467
513570630
716792
869929
848933
102811401260
14321584
17381858
4246
7593
107131
158187
247271
266296336
285322359
299333368
368425466
467509548
492544
599665735
834925
10121083
9891089
119913301470
16681850
20242166
4852
86106
122150
180214
282310
304338384
326368410
342380420
420486532
534582626
562622
684760840
9541056
11571237
11301244
137015201680
19082112
23142474
5459
97119
137169
203241
317349
342380432
367414461
385428473
473547599
601655704
632700
770855945
10741189
13021391
12711400
154117101890
21482378
26042782
6065
108 133
153188
225268
353388
380423480
408460513
428475525
525608665
668728783
703778
855950
1050
11931321
1448 1547
1413 1555
1713 1900 2100
23862642
28963094
6672
118146
168206
248294
388426
418465528
448506564
470523578
578668732
734800861
773855
94110451155
13111454
15901701
15541711
188420902310
26222908
31803402
7278
129159
183225
270321
423465
456507576
489552615
513570630
630729798
801873939
843933
102611401260
14311585
17361855
16951866
205522802520
28623170
34723710
7581
134166
191234
281 334
441484
475528600
509575641
534 594 656
656 759 831
834909978
878972
106911881313
14901651
18071933
17661944
214123752625
29803302
36143866
8188
145179
206253
304361
476523
513570648
550621692
577641709
709820898
901982
1056
9481050
115412831418
16091782
19522087
19072099
231225652835
32183564
39044174
8794
156192
221272
326388
511562
551613696
591667743
620689761
761881964
96810551135
10191127
124013781523
17291915
20982241
20482255
248327553045
34583830
41964482
93101
167205
236291
349415
546601
589655744
632713794
663736814
814942
1031
103511281213
10891205
132514731628
18492046
22432395
21892410
265429453255
36984092
44864790
99107
177219
252309
371441
582639
627697792
672759846
705784866
86610021097
110112001291
11591283
141115681733
19672179
23852552
23312566
282631353465
39344358
47705104
HRFG SERIES SPECIFICATIONS
1. GENERAL
2. PERFORMANCE
3. CONSTRUCTION
4. FILL, DRIFT ELIMINATOR AND LOUVERS
5. HOT WATER DISTRIBUTION SYSTEM
6. FANS
7. MOTORS
8. MANUFACTURER
Furnish and install an induced draft, counter flow, factory assembled, All-Fiberglass Reinforced Polyester (FRP) casing and structure Cooling Tower(s) of ______ cells, as shown on plans. Tower shall be similar and equal in all respects to REYMSA HRFG model ______________.
The tower shall have the capacity to cool _______ GPM of water, from _______ °F Entering Water Temperature, to ______°F leaving water temperature, at a design entering air wet-bulb temperature of _______ °F the performance shall be certified by the Cooling Tower Institute (CTI) in accordance with CTI Certification Standard STD-201. Additionally, the Cooling Tower manufacturer shall guarantee the performance of each cell as installed according to plans.
The entire casing and structure shall be constructed of Fiberglass Reinforced Polyester (FRP). Only a high grade isophalic polyester resin with UV inhibitor shall be used in the manufacturing process. For One and Two Fan units, the entire body and basin shall be constructed in one-piece, seamless, watertight FRP. No side fasteners will be allowed at the sidewalls of the body or the basin. There shall not be any metal support or structure in direct contact with water. For the one and two Fan units, there shall be one or two independent fan cylinders with a motor support to be constructed completely of FRP, no metal motor support shall be allowed; to be mounted on top of the body structure held in place with stainless steel fasteners provided by the manufacturer, no gasket shall be required, and shall include a corrosion resistant protective mesh screen cover to prevent airborne objects from entering into the fan cylinder. Four fan units shall consist of three sections; the body shall be composed of two independent, seamless, watertight FRP pieces, held together with stainless steel fasteners provided by the manufacturer. The basin shall be composed of two independent, seamless, watertight FRP pieces, held together by side stainless steel fasteners provided by the manufacturer. Multi-piece walls or sheet metal wall sections will not be allowed. There shall not be any metal support or structure in direct contact with water. The fan cylinder structure shall have a motor support constructed completely of FRP. No metal supports shall be allowed. All three sections shall be held together by perimetral flanges with stainless steel fasteners provided by the manufacturer, no gasket shall be required. The entire One, Two or Four Fan tower shall be designed and constructed to withstand wind pressure of no less than 30 pounds-force per square foot (psf) on external surfaces. The top of the body shall be designed and constructed to withstand a live load of no less than 40 psf in addition to the concentrated loads of the fan or other equipment mounted thereon. The One, Two and Four Fan unit basin shall be equipped with cold water outlet, drain with mesh screen cover, overflow, water make-up, drain equalizer and purge fittings. All drain fittings 3" and smaller shall be NPT and larger than 3" shall be ANSI flange (FRP or PVC). A bottom sump drain shall be available for dry sump installation, if required.
Fill shall be cross corrugated film-type, thermoformed PVC, in sections not to exceed 1' x 1' x 6'. For hot water temperatures higher than 130°F, Aluminum or Polyestyrene fill may be used, as applicable. For Higher water temperatures, drift eliminators shall be thermoformed PVC, in sections not to exceed 1' x 1/2' x 6'. Drift losses shall not exceed 0.005% of the design circulating flow. Louvers shall be thermoformed PVC on all four sides of the tower(s).
The hot water shall enter the body through a single inlet per cell. All interior distribution piping shall be PVC. For industrial applications with higher water temperatures, fiberglass or Stainless Steel piping may be used as applicable. Water shall be evenly distributed over the fill media by removable, interchangeable ABS (2 ½") Spray Nozzles. Nozzles shall each contain internal, interchangeable flow devices to provide an optimal spray pattern with a 2 to 10 psig pressure differential.
Fan(s) shall be propeller type, fan blades shall be constructed with Fiberglass Reinforced Polyamide, spark and corrosive resistant with adjustable pitch suitable for high temperature operation up to 250°F. Hub(s) shall be aluminum alloy castings. Fan(s) shall be directly driven. Towers utilizing gear reducers or belt driven units will not be accepted.
There shall be single speed, Totally Enclosed Fan Cooled (TEFC), phase, Hertz, volts. Electric Motor(s), NEMA rated for continued operation at a 1.15 service factor. Each motor shall be horsepower for a total Horsepower at RPM.
The Cooling Tower shall be manufactured by REYMSA COOLING TOWERS, INC.