BROKERS CHOICE SUITE 125TENANT IMPROVEMENT Construction Documents
7/23/15
Smart Design. Successful Venture.
535 East Mexico AvenueDenver, Colorado 80210P h o n e : 3 0 3 . 7 2 2 . 9 9 8 8www.venturearchitecture.com-----------------------
TENANTIMPROVEMENT
BROKERSCHOICE
SUITE 125
DRY CREEK CORPORATE CENTERSUITE 125
10700 E. GEDDES AVE.ENGLEWOOD, CO 80112
1518
ISSUE
PROJECT NUMBER:
DATE
654321
C
A
B
D
C
A
B
D
654321
Smart Design. Successful Venture.
535 East Mexico AvenueDenver, Colorado 80210Phone: 303.722.9988www.venturearchitecture.com
TENANTIMPROVEMENT
BROKERSCHOICEDCCC II
125
Dry Creek Corporate Center10700 E Geddes Ave.
Suite 125Englewood, CO 80112
Construction Documents 7/21/15
MP0.0
MECHANICAL/PLUMBINGCOVER SHEET
EXISTING DUCT
EXISTING TO BE REMOVED
NEW DUCT
SUPPLY DIFFUSER
RETURN AIR GRILLE
MANUAL BALANCING DAMPER
FLEXIBLE DUCTWORK
THERMOSTAT
NEW
RELOCATE
COLD WATER
HOT WATER
VENT
WASTE
(N)
MECHANICAL / PLUMBING LEGEND
(R)
MECHANICAL NOTES
I. GENERAL
A. ALL WORK SHALL BE IN ACCORDANCE WITH SMACNA STANDARDS AND SPECIFICATIONS, AND LOCAL AUTHORITY HAVING JURISDICTION.
B. THESE DRAWINGS ARE DIAGRAMMATIC IN NATURE AND NOT INTENDED TO SHOW ALL TRANSITIONS, OFFSETS, ETC. CONTRACTOR SHALL FIELD VERIFY EXISTING CONDITIONS AND PROVIDE ALLNECESSARY FITTINGS TO COMPLETE THE INTENT OF THE DRAWINGS. ANY DISCREPANCIES BETWEEN DRAWINGS AND FIELD CONDITIONS SHALL BE REPORTED TO THE ENGINEER FOR RESOLUTION.CONTRACTOR MAY LOCATE MECHANICAL EQUIPMENT DIFFERENTLY THAN SHOWN ON DRAWINGS DUE TO CONFLICTS, AS LONG AS FUNCTION AND/OR APPEARANCE ARE NOT AFFECTED.
C. COORDINATE SPACE REQUIREMENTS, SUPPORTS, AND INSTALLATION OF MECHANICAL WORK, WHICH ARE INDICATED DIAGRAMMATICALLY ON THE DRAWINGS. FOLLOW ROUTING SHOWN FOR PIPESAND DUCTS AS CLOSELY AS PRACTICABLE; PLACE RUNS PARALLEL WITH LINES OF BUILDING. UTILIZE SPACES EFFICIENTLY TO MAXIMIZE ACCESSIBILITY FOR OTHER INSTALLATIONS, FORMAINTENANCE, AND FOR REPAIRS.
D. COMPLY WITH MANUFACTURER'S INSTRUCTIONS INCLUDING EACH STEP IN SEQUENCE. SHOULD MANUFACTURERS' INSTRUCTIONS CONFLICT WITH THE DRAWINGS REQUEST CLARIFICATION FROMTHE ENGINEER BEFORE PROCEEDING.
E. DUCT SIZES ARE INSIDE DIMENSION.
F. CONTRACTOR SHALL REVIEW THESE DOCUMENTS CAREFULLY. CONTRACTOR SHALL CONTACT DENISE DIHLE AT THREE SIXTY (360) ENGINEERING, INC. (303-940-2050), FOR RESOLUTION OF ANYDISCREPANCIES, OMISSIONS, OR CLARIFICATIONS, BEFORE BID DATE. IN THE EVENT THAT AN INTERPRETATION OF BID DOCUMENTS IS NECESSARY AFTER THE BID DATE, THE DECISION OF 360 SHALLBE FINAL AND BINDING.
G. PRODUCT DELIVERY, STORAGE, AND HANDLING: PROVIDE EQUIPMENT AND PERSONNEL TO HANDLE PRODUCTS BY METHODS TO PREVENT DAMAGE. PROMPTLY INSPECT SHIPMENTS TO ENSURETHAT PRODUCTS ARE UNDAMAGED. STORE AND PROTECT PRODUCTS IN ACCORDANCE WITH MANUFACTURERS' INSTRUCTIONS.
H. ALL REMOVED EQUIPMENT SHALL REMAIN THE PROPERTY OF THE BUILDING MANAGER AND SHALL BE STORED PER THEIR DIRECTION.
I. THE CONTRACTOR IS RESPONSIBLE FOR THE COSTS OF ALL CHANGE ORDERS, WHICH THE OWNER AND ENGINEER HAVE NOT APPROVED IN WRITING PRIOR TO THE EXECUTION OF THE ASSOCIATEDWORK.
II. EQUIPMENT
A. THERMOSTATS: SHALL BE TRANE DDC CONNECTED TO THE EXISTING DDC SYSTEM.
B. NEW RIGID ROUND DUCTWORK: 1. MEDIUM PRESSURE: GALVANIZED STEEL SPIRAL WOUND DUCT. 2. LOW PRESSURE: GALVANIZED STEEL SNAP LOCK DUCT.
C. NEW RECTANGULAR DUCTWORK: 1. ZINC COATED GALVANIZED STEEL WITH 1" ACOUSTIC LINER.
D. RIGID ROUND DUCTWORK INSULATION: FLEX MASTER THERMO SLEEVE TYPE TSM.
E. FLEXIBLE DUCTWORK: 1. LOW PRESSURE: FLEX MASTER TLM (ALUM. FLEX/METAL JACKET), UL181 - CLASS 1 APPROVED, 8'0" MAXIMUM LENGTH.
III. EXECUTION:
A. BALANCING: 1. CONTRACTOR SHALL ADJUST AND BALANCE VARIABLE VOLUME BOXES (VAV'S), FAN POWERED BOXES (FPB'S), AND DIFFUSERS TO THE QUANTITIES SHOWN ON THE DRAWING. BALANCING WORKSHALL BE PERFORMED IN ACCORDANCE WITH NEBB STANDARDS BY A NEBB CERTIFIED CONTRACTOR. SUBMIT BALANCING REPORT TO THE ENGINEER. 2. EXISTING DIFFUSER DESIGNATION INDICATES CFM ONLY. 3. VAV BOX DESIGNATION INDICATES MAXIMUM CFM ADJUST MINIMUM TO 10% OF MAXIMUM. 4. WHERE LOW PRESSURE AIR HANDLING SYSTEMS CROSS INTO AN ADJACENT TENANT AREA, CONTRACTOR SHALL BALANCE ALL DIFFUSERS ASSOCIATED WITH THE SYSTEM. DIFFUSERS NOTSHOWN OR SHOWN WITH NO CFM SHALL MAINTAIN EXISTING CFM. 5. ADJUST SYSTEMS TO PROVIDE SPECIFIED PRESSURE DROPS AND FLOWS THROUGH HEAT TRANSFER ELEMENTS PRIOR TO THERMAL TESTING. PERFORM BALANCING BY MEASUREMENT OFTEMPERATURE DIFFERENTIAL IN CONJUNCTION WITH AIR BALANCING.
B. CONTRACTOR SHALL COORDINATE WORK WITH OTHER TRADES AND NOTIFY 360 ENGINEERING, INC. IF ANY CONFLICTS OCCUR.
C. THERMOSTAT LOCATIONS AND HEIGHTS TO BE COORDINATED WITH BUILDING MANAGEMENT, VERIFIED BY THE ENGINEER. CONTRACTOR TO CALIBRATE ALL THERMOSTATS SHOWN ON THIS PLAN.IT SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY TO ENSURE THAT ALL EXISTING THERMOSTATS REMAIN INTACT DURING DEMOLITION. HEATING THERMOSTATS MUST REMAINOPERATIONAL AT ALL TIMES. IF REQUIRED FOR BETTER PROTECTION, THERMOSTATS MAY BE TEMPORARILY MOUNTED IN THE CEILING PLENUM DURING DEMOLITION.
D. PROVIDE VOLUME DAMPERS AT ALL DIFFUSER TAKEOFFS.
E. ALL TAKEOFFS, RUNOUTS, AND FLEX DUCTWORK TO DIFFUSERS SHALL BE THE SAME SIZE AS DIFFUSER INLET UNLESS OTHERWISE NOTED.
F. MECHANICAL CONTRACTOR TO CHECK OPERATION AND CONDITION OF ALL EXISTING MECHANICAL EQUIPMENT WITHIN THE CONFINES OF THIS SPACE AND PREPARE A WRITTEN LIST OF ANYDEFICIENCIES IN EQUIPMENT OPERATION OR CONDITION. LIST SHALL BE SUBMITTED TO PROPERTY MANAGER TWO WEEKS AFTER THE AWARD OF THE CONTRACT.
G. THERMOSTAT CONTROL LINES SHALL BE SUPPORTED AT INTERVALS NOT TO EXCEED 4'0".
H. PROVIDE EXTERNAL INSULATION ON ALL NEW RIGID ROUND DUCTWORK.
I. PROVIDE ACCESS DOORS IN DUCTWORK AS REQUIRED FOR ACCESS TO FIRE DAMPERS, FIRE/SMOKE DAMPERS, OR ANY OTHER MECHANICAL EQUIPMENT REQUIRING MAINTENANCE OF SERVICE.
AIR
FLO
W
FLEX DUCT, 8 FOOT
MAXIMUM LENGTH.
WORM DRIVE S.S.
CLAMP.
ROUND TWIST-IN FITTING WITH
MANUAL DAMPER, HANDLE
AND LOCK NUT.
USE DUCT SEALANT OR
GASKETED FITTING ON.
PLUMBING NOTES
I. GENERAL
A. THESE DRAWINGS ARE DIAGRAMMATIC IN NATURE AND NOT INTENDED TO SHOW ALL TRANSITIONS, OFFSETS, ETC. CONTRACTOR SHALL FIELD VERIFY EXISTING CONDITIONS AND PROVIDE ALLNECESSARY FITTINGS TO COMPLETE THE INTENT OF THE DRAWINGS. ANY DISCREPANCIES BETWEEN DRAWINGS AND FIELD CONDITIONS SHALL BE REPORTED TO THE DESIGN ENGINEER FORRESOLUTION.
B. CONTRACTOR SHALL COORDINATE WORK WITH OTHER TRADES AND NOTIFY ENGINEER IF ANY CONFLICTS OCCUR.
C. CONTRACTOR SHALL REVIEW THESE DOCUMENTS CAREFULLY. CONTRACTOR SHALL CONTACT DENISE DIHLE AT THREE SIXTY ENGINEERING, INC. (360) (303.940.2050), FOR RESOLUTION OF ANYDISCREPANCIES, OMISSIONS, OR CLARIFICATIONS, BEFORE BID DATE. IN THE EVENT THAT AN INTERPRETATION OF BID DOCUMENTS IS NECESSARY AFTER THE BID DATE, THE DECISION OF 360 SHALLBE FINAL AND BINDING.
D. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE COSTS OF ALL CHANGE ORDERS, WHICH THE OWNER AND ENGINEER HAVE NOT APPROVED IN WRITING PRIOR TO THE EXECUTION OF THEASSOCIATED WORK.
II. PRODUCTS
A. INTERIOR SOIL AND WASTE PIPING: SERVICE WEIGHT CAST IRON SOIL PIPE AND NO HUB FITTINGS OR DWV COPPER PIPE AND FITTINGS WITH 95% TIN/ 5% ANTIMONY SOLDER JOINTS.
B. DOMESTIC WATER LINES AND INDIRECT DRAIN LINES: TYPE "L" HARD DRAWN COPPER TUBING WITH WROUGHT COPPER FITTINGS. SOLDER SHALL BE 95% TIN/ 5% ANTIMONY.
C. VENT PIPING: SERVICE WEIGHT CAST IRON WITH STAINLESS STEEL NO HUB CONNECTORS OR DWV COPPER PIPE AND FITTINGS WITH 95%TIN/ 5% ANTIMONY SOLDER JOINTS.
III. EXECUTION
A. ALL PLUMBING WORK SHALL COMPLY WITH LOCAL CODES AND ORDINANCES.
B. PITCH WASTE LINES NOT LESS THAN 1/8" PER FOOT. (UNLESS NOTED OTHERWISE)
C. INSULATE ALL COLD WATER, HOT WATER, AND INDIRECT WASTE PIPING WITH 1" PREFORMED FIBERGLASS PIPE INSULATION WITH A "K" FACTOR OF 0.23 MAXIMUM AT 75 °F MEAN TEMPERATURE.INSULATION JACKET SHALL BE FACTORY APPLIED KRAFT PAPER WITH VAPOR BARRIER AND SELF-SEALING LAP.
D. RUN ALL PIPING ON WARM SIDE OF BUILDING INSULATION. PIPE INSULATION IS NOT CONSIDERED FREEZE PROTECTION.
E. PROVIDE DIELECTRIC UNIONS AT CONNECTIONS BETWEEN DISSIMILAR METALS, I.E., IRON VALVES AND COPPER TUBING.
F. PROVIDE PIPE HANGERS OF THE SAME MATERIAL AS THE PIPING SYSTEM OR USE COATED HANGERS.
G. SET FLOOR DRAINS SO THAT TOP WILL BE SLIGHTLY LOWER THAN SURROUNDING FLOOR.
H. PROVIDE BALL VALVES AND UNIONS ON ALL LINES TO EQUIPMENT FOR ISOLATION AND REMOVAL.
I. PLUMBING CONTRACTOR SHALL CHECK OPERATION AND CONDITION OF ALL EXISTING PLUMBING EQUIPMENT WITHIN THE CONFINES OF THIS SPACE, AND PREPARE A WRITTEN LIST OFDEFICIENCIES IN EQUIPMENT OPERATION OR CONDITION. LIST SHALL BE SUBMITTED TO GENERAL CONTRACTOR WITHIN 2 WEEKS OF CONTRACT AWARD DATE.
J. WHERE REMOVAL OR RELOCATION OF EXISTING FIXTURES OCCURS, CONTRACTOR SHALL REMOVE ALL WASTE AND VENT BRANCH LINES NOT REQUIRED FOR NEW, OR REMAINING FIXTURELOCATIONS.
FAN POWERED VARIABLE AIR VOLUME UNIT SCHEDULE
TAG
FPB-1
REMARKS:
1.
2.
3.
MFG
TRANE
MOUNT WITH NEOPRENE VIBRATION ISOLATORS
PROVIDE WITH SUPERIOR MERV 13 FILTER. CONTRACTOR TO PROVIDE SPARE.
HEATING CFM INDICATES AIRFLOW OUT OF FAN POWERED BOX WHILE IN HEATING MODE
MODEL
VPEF08
TYPE
PARALLEL
MAX
PRIMARY
CFM
@ ALT
700
MIN
PRIMARY
CFM
@ ALT
150
MAX
HEATING
CFM
@ ALT
700
FAN DATA
CFM
550
ESP
0.25
ELECTRICAL
HP
0.333
4.
5.
VOLTS
277
HEATING CFM TO BE COMBINATION OF COOLING MIN CFM AND PLENUM AIR
SINGLE POINT ELECTRICAL CONNECTION
Ø
1
HEATING COIL
EAT °F
66.79
LAT °F
96.84
kW
5.5
ELECTRICAL
NO. OF
STAGES
2
VOLTS
480
Ø
3
REMARKS
1,2,3,4,5
GRILLES, REGISTERS & DIFFUSERS
TAG
A
B
C
1.
MANUFACTURER
PRICE
PRICE
PRICE
NEW RETURN GRILLS ARE NOTED WITH AN 'N'. ALL OTHERS ARE EXISTING.
MODEL NUMBER
SDB MODEL 100 4-SLOT 48"
SCD
PERF
NECK
SIZE
10"
10"
N/A
FACE
SIZE
46X6
24x24
24X24
MATERIAL
ALUMNIUM
STEEL
STEEL
MOUNTING
TYPE
T-GRID
T-GRID
T-GRID
FINISH
WHITE
WHITE
WHITE
REMARKS:
1
VAV BOX SCHEDULE
TAG
VAV-1
NOTES
1.
MANUFACTURER
TRANE
CONNECT TO EXISTING TRANE DDC SYSTEM
MODEL
VCCF
AREA
SERVED
CONFERENCE
INLET
SIZE
(IN)
8"
MAX
P.D.
(IN W.G.)
2
AIRFLOW DATA
TOTAL CFM
COOLING
480
MIN. PRIMARY
CFM
100
MAX NC
LEVEL @
MAX AIRFLOW
31
REMARKS
1
FIRE SPRINKLER NOTES
1. THE FIRE PROTECTION SYSTEM SHALL BE IN CONFORMANCE WITH THE REQUIREMENTS OF THE FOLLOWING REGULATORY AGENCIES WHENEVER THE REQUIREMENTS OF SUCH AGENCIES
ARE APPLICABLE.
A. LOCAL BUILDING DEPARTMENT
B. LOCAL FIRE DEPARTMENT
C. NFPA 13
2. ALL MATERIALS AND EQUIPMENT USED IN THE INSTALLATION OF THE FIRE PROTECTION SYSTEM SHALL BE AS APPROVED IN THE UNDERWRITERS' LABORATORIES LIST OF INSPECTED
FIRE PROTECTION EQUIPMENT AND MATERIALS, OR THE FACTORY MUTUAL LABORATORIES LIST OF APPROVED EQUIPMENT AND FIRE PROTECTION DEVICES INVOLVING FIRE HAZARD, AND
SHALL BE THE LATEST PRODUCT OF THE MANUFACTURER.
3. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO SIZE THE SPRINKLER SYSTEM PIPES IN ACCORDANCE WITH THE REQUIREMENTS OF NFPA 13.
4. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO DESIGN THE SYSTEM SO THAT NO INTERFERENCE EXIST BETWEEN THE FIRE PROTECTION SYSTEM AND WORK OF OTHER TRADES,
EQUIPMENT, AND SYSTEMS DESIGNED AND INSTALLED BY OTHERS. CEILINGS CONSIST OF MAINLY GYPSUM BOARD CEILINGS. CONTRACTOR SHALL COORDINATE WITH OTHER TRADES TO
LOCATED SPRINKLER HEADS IN THE CENTER OF TILES. SPRINKLER HEADS SHALL BE EXPOSED, CHROME PLATED.
5. PIPE JOINTS ABOVE GROUND SHALL BE SCREWED, FLANGED, WELDED OR MECHANICAL JOINTS TO MATCH EXISTING BUILDING SYSTEM.
6. PIPING ABOVE GROUND FOR THREADED JOINTS SHALL BE SCHEDULE 40 BLACK STEEL AND IN ACCORDANCE WITH SPECIFICATIONS ASTM A135 OR A53. THIN WALL PIPE MAY BE USED WHEN IN
CONFORMANCE WITH NFPA 13. THIN WALL PIPE SHALL BE SCHEDULE 10 BLACK STEEL AND IN ACCORDANCE WITH SPECIFICATION ASTM A135.
7. SCREWED FITTINGS ABOVE GROUND SHALL BE GRAY CAST IRON SUITABLE FOR 175 PSI COLD WATER WORKING PRESSURE AND SO RATED.
8. SPRINKLER HEADS SHALL HAVE A TEMPERATURE RATING OF 165°F, EXCEPT FOR HEADS IN AREAS OF HIGH TEMPERATURE AND IN CLOSE PROXIMITY TO HEAT SOURCES WHICH SHALL BE
TEMPERATURE RATED IN ACCORDANCE WITH NFPA 13. SPRINKLER HEAD TYPE SHALL BE FULLY RECESSED WITH WHITE COVER MOUNTED FLUSH TO CEILING, U.N.O. ALL HEADS SHALL BE
ENTERED IN THE CEILING TILES AND OR SYMMETRICALLY IN THE GYPSUM BOARD CEILINGS AS APPLICABLE.
9. MAKE PROVISIONS TO DRAIN ALL PARTS OF THE PIPING SYSTEM. PROVIDE BAKELITE LABELS INDICATING LOCATIONS OF ALL CONCEALED DRAIN VALVES AND INSTALL LABELS TO THE CEILING
DIRECTLY BELOW THE VALVE. ALL DRAIN VALVES SHALL HAVE HOSE THREADS.
10. PENDANT AND UPRIGHT HEADS SHALL BE INSTALLED WITH THE DEFLECTORS PARALLEL TO THE CEILING; CLEARANCE BETWEEN THE DEFLECTORS AND THE CEILINGS, ROOF DECKING,
ROOF JOINTS, ELECTRIC OR HEATING EQUIPMENT, OR OTHER OBSTRUCTIONS SHALL BE IN ACCORDANCE WITH THE REQUIREMENTS OF NFPA.
11. CONTRACTOR SHALL REVIEW THESE DOCUMENTS CAREFULLY. CONTRACTOR SHALL CONTACT DENISE DIHLE AT 360 ENGINEERING, (303.940.2050), FOR RESOLUTION OF ANY
DISCREPANCIES, OMISSIONS, OR CLARIFICATIONS, BEFORE BID DATE. IN THE EVENT THAT AN INTERPRETATION OF BID DOCUMENTS IS NECESSARY AFTER THE BID DATE, THE DECISION OF 360
ENGINEERING SHALL BE FINAL AND BINDING.
12. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE COSTS OF ALL CHANGE ORDERS WHICH THE OWNER AND ENGINEER HAVE NOT APPROVED IN WRITING PRIOR TO THE EXECUTION OF
THE ASSOCIATED WORK.
PLUMBING FIXTURE SCHEDULE
TAG
S-1
GDU-1
REMARKS:
1.
2.
3.
4.
DESCRIPITION
SINK- DOUBLE COMPARTMENT
(ADA)
GARBAGE DISPOSAL UNIT
17 GA. P-TRAP, LOOSE KEY ANGLE STOPS, STAINLESS STEEL BRAIDED SUPPLIES
PROVIDE LEONARD #270-LF MIXING VALVE UNDER FIXTURE. (ASSE 1070 RATED)
PROVIDE WITH TRUEBRO #103 E-Z P-TRAP AND SUPPLIES INSULATION KIT
6" DEEP BOWL, REAR DRAIN LOCATION
MANUFACTURER
JUST
INSINKERATOR
MODEL NUMBER
DL-ADA-1933-A-GR
BADGER 5
FINISH
STAINLESS
STEEL (18 GA)
-
MANUFACTURER
DELTA
-
MODEL NUMBER
100LF-HDF
-
FINISH
CHROME
-
GPM/GPF
1.5
-
ELECTRICAL
-
120/60/1
1/2 HP
REMARKS
1,2,3,4
OUTSIDE AIR CALCULATION (CALCULATIONS BASED ON 2012 IMC TABLE 403.3)
ROOM NAME
Conference Room
Office
Office
Office
Office
Office
Office
Office
Office
Office
Work Stations
Hotel Stations
Break Room
IT
Conference Room
Reception
SQUARE FEET
332
132
132
132
132
132
191
108
107
108
1638
270
305
69
247
428
OA CFM/
PERSON
5
5
5
5
5
5
5
5
5
5
5
5
5
0
5
5
OA
CFM/SF
0.06
0.06
0.06
0.06
0.06
0.06
0.06
0.06
0.06
0.06
0.06
0.06
0.06
0.00
0.06
0.06
OCCUPANT LOAD
#/1000 SF
50
5
5
5
5
5
5
5
5
5
5
5
30
0
50
30
AIR DIST.
EFFECTIVENESS
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
OA REQUIRED
128.7
14.0
14.0
14.0
14.0
14.0
20.3
11.5
11.4
11.5
174.0
28.7
80.1
0.0
95.7
112.4
744.2
OA PROVIDED
147
70
70
70
70
70
96
20
20
20
176
44
106
0
96
120
1195
FPB (E)
FPB (E)
FPB (E)
VAV (E)
VAV (E) VAV (E)
T
T
18"Ø16"Ø10"Ø8"Ø1
2"Ø
10
"Ø
18"Ø 14"Ø
10
"Ø
22x18
18x18
18x18
8"Ø
8"Ø
16x22
16x26
18"Ø
18"Ø
16x26
8"Ø
8"Ø
8"Ø
8"Ø8"Ø
10"Ø
8"Ø
8"Ø
8"Ø
8"Ø
8"Ø8"Ø
8"Ø
8"Ø
8"Ø
8"Ø
16"Ø14"Ø
18x18
18x18
40x28
10"Ø 10"Ø10"Ø
(245)(245) (245)
R R R
(350) (350) (350) (350) (350) (240)
(100)
(100)
(100)
(240)
(150)
(150)
(110)
(110)
(265) (265)
(110) (110)
(110)
(110)(110)
(110) (110)
R RR
R R R
VAV-1
8"Ø
12"Ø10"Ø
10
"Ø
R
R
R
R R
R
R R
RR
RR
R
R
R
CAP
CAP
S.B. S.B.
S.B.
S.B. S.B.
S.B.
S.B.
S.B.
S.B.
S.B.
R R
R R
R
R
R
FPB-1
12x12
10"Ø10"Ø
10"Ø
10"Ø
10"Ø
10"Ø
10"Ø
10"Ø
8"Ø
T
T T
T
TN
N
NN
N
N
(150)
S.B.
N
N
N
N
(735)
(480)
(1460)
(440)
(1530)
(630)
1518
ISSUE
PROJECT NUMBER:
DATE
654321
C
A
B
D
C
A
B
D
654321
Smart Design. Successful Venture.
535 East Mexico AvenueDenver, Colorado 80210Phone: 303.722.9988www.venturearchitecture.com
TENANTIMPROVEMENT
BROKERSCHOICEDCCC II
125
Dry Creek Corporate Center10700 E Geddes Ave.
Suite 125Englewood, CO 80112
Construction Documents 7/21/15
M2.0
MECHANICAL FLOORPLAN
1
KEYNOTES
PROVIDE AND INSTALL NEW FAN POWER BOX,
FPB-1. PROVIDE TRANSITION FROM 10"Ø
SUPPLY DUCT TO INLET OF THE BOX. PROVIDE
TRANSITION FROM OUTLET OF THE BOX TO
12x12 DUCT.
PROVIDE AND INSTALL NEW VARIABLE AIR
VOLUME BOX, VAV-1. PROVIDE TRANSITION
FROM 8"Ø SUPPLY DUCT TO INLET OF THE BOX.
PROVIDE TRANSITION FROM OUTLET OF THE
BOX TO 12"Ø DUCT.
CONNECT NEW DUCT TO EXISTING DUCT.
EXTEND EXISTING 8"Ø DUCT.
PROVIDE NEW THERMOSTAT.
PROVIDE SOUND BOOT OVER RETURN GRILLE
RELOCATE EXISTING RETURN GRILLE.
INSTALL RELOCATED RETURN GRILLE.
2
3
4
5
1
2
3
3
3 4
4
4
4
5
5
5
5
5
6
6
6
6
6666
66
6
3
3
3
33
3
6
7
8
77
7
8 88
EFPB01
EFPB02EFPB03
VAV01
EVAV01EVAV02 EVAV03
12
3 4
1
2
3
4
5
6
1 2 3 4 512
123
12
12
34
5
6 7
8 9