bs240 eng

Upload: volodymyr-borushok

Post on 04-Jun-2018

283 views

Category:

Documents


2 download

TRANSCRIPT

  • 8/13/2019 BS240 eng

    1/78

    Information

    Base Station System

    Technical Description (TED:BSS)BS-240/241 II

    A30808-X3247-K22-1-7618

  • 8/13/2019 BS240 eng

    2/78

    2 A30808-X3247-K22-1-7618

    Technical Description (TED:BSS)BS-240/241 II

    InformationBase Station System

    !Important Notice on Product Safety

    DANGER - RISK OF ELECTRICAL SHOCK OR DEATH - FOLLOW ALL INSTALLATION INSTRUCTIONS.

    The system complies with the standard EN 60950 / IEC 60950. All equipment connected to the system must

    comply with the applicable safety standards.

    Hazardous voltages arepresent at the AC power supply lines in this electrical equipment. Some components may

    also have high operating temperatures.

    Failure to observe and follow all installation and safety instructions can result in serious personal injury

    or property damage.

    Therefore, only trained and qualified personnel may install and maintain the system.

    The same text in German:

    Wichtiger Hinweis zur ProduktsicherheitLEBENSGEFAHR - BEACHTEN SIE ALLE INSTALLATIONSHINWEISE.

    Das System entspricht den Anforderungen der EN 60950 / IEC 60950. Alle an das System angeschlossenen

    Gerte mssen die zutreffenden Sicherheitsbestimmungen erfllen.

    In diesen Anlagen stehen die Netzversorgungsleitungen unter gefhrlicher Spannung. Einige Komponenten

    knnen auch eine hohe Betriebstemperatur aufweisen.

    Nichtbeachtung der Installations- und Sicherheitshinweise kann zu schweren Krperverletzungen oder

    Sachschden fhren.

    Deshalb darf nur geschultes und qualifiziertes Personal das System installieren und warten.

    Caution:

    This equipment has been tested and found to comply with EN 301489. Its class of conformity is defined in table

    A30808-X3247-X910-*-7618, which is shipped with each product. This class also corresponds to the limits for aClass A digital device, pursuant to part 15 of the FCC Rules.These limits are designed to provide reasonable protection against harmful interference when the equipment is

    operated in a commercial environment.This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accor-

    dance with the relevant standards referenced in the manual Guide to Documentation, may cause harmful inter-ference to radio communications.For system installations it is strictly required to choose all installation sites according to national and local require-

    ments concerning construction rules and static load capacities of buildings and roofs.Forall sites, in particular in residential areas it is mandatory to observe all respectively applicableelectromagneticfield / force (EMF) limits. Otherwise harmful personal interference is possible.

    Trademarks:

    All designations used in this document can be trademarks, the use of which by third parties for theirown purposes

    could violate the rights of their owners.

    Copyright (C) Siemens AG 2002.

    Issued by the Information and Communication Mobile Group

    Hofmannstrae 51

    D-81359 Mnchen

    Technical modifications possible.

    Technical specifications and features are binding only insofar as

    they are specifically and expressly agreed upon in a written contract.

  • 8/13/2019 BS240 eng

    3/78

    A30808-X3247-K22-1-7618 3

    InformationBase Station System

    Technical Description (TED:BSS)BS-240/241 II

    Reason for Update

    Summary:

    First edition for release BR 5.5 and BR6.0

    Details:

    Chapter/Section Reason for Update

    Issue History

    Issue

    Number

    Date of issue Reason for Update

    1 11/2002 First edition for release BR 5.5 and BR6.0

  • 8/13/2019 BS240 eng

    4/78

    4 A30808-X3247-K22-1-7618

    Technical Description (TED:BSS)BS-240/241 II

    InformationBase Station System

  • 8/13/2019 BS240 eng

    5/78

    A30808-X3247-K22-1-7618 5

    InformationBase Station System

    Technical Description (TED:BSS)BS-240/241 II

    This document consists of a total of 78 pages. All pages are issue 1.

    Contents

    1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91.1 Main features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

    1.2 Technical data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

    2 Hardware architecture. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

    2.1 Board redundancy. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

    2.1.1 AC/DC. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

    2.1.2 Core . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

    2.2 Nominal power amplifier output level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

    2.2.1 Carrier Unit (CU) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

    2.2.2 Edge Carrier Unit (ECU) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

    2.3 Rack configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 192.4 Enhanced Observed Time Difference (E-OTD) . . . . . . . . . . . . . . . . . . . . . 24

    2.4.1 Logical Architecture . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

    2.4.2 LMU Interconnection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

    3 Modules Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

    3.1 Core (COBA and COSA) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

    3.1.1 Core Basis (COBA2P8) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

    3.1.2 Core Satellite (COSA6P16) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

    3.2 Carrier Unit (CU) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35

    3.3 Edge Carrier Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

    3.3.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 383.3.2 Mechanics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40

    3.3.3 Transmitter Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40

    3.3.4 Receiver Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40

    3.3.5 Local Test Loop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40

    3.3.6 Supported frequency range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40

    3.3.7 Power Supply Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40

    3.3.8 Functional description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40

    3.3.9 Functional structure of the EDGE Carrier Unit. . . . . . . . . . . . . . . . . . . . . . 41

    3.3.10 Main differences between ECU and CU . . . . . . . . . . . . . . . . . . . . . . . . . . . 41

    3.3.11 EDGE Power Amplifier and Tranceiver Unit(EPATRX) . . . . . . . . . . . . . . . 42

    3.3.12 Signal processing unit (ESIPRO). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 433.3.13 EPSU (Power Supply Unit) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45

    3.4 Duplexer Amplifier Multi Coupler (DUAMCO) . . . . . . . . . . . . . . . . . . . . . . . 45

    3.5 DI(=2) Amplifier Multi Coupler (DIAMCO) . . . . . . . . . . . . . . . . . . . . . . . . . . 46

    3.6 Filter Combiner (FICOM) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46

    3.7 Tower Mounted Amplifier (TMA) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46

    3.8 High Power Duplexer Unit (HPDU) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47

    3.9 DC Panel (DCP). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47

    3.10 DC Link Equipment Panel. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47

    3.11 Alarm Collection Terminal (ACT) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48

    3.12 AC/DC converter (ACDC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49

    3.12.1 DC and Battery Controller (DCBCTRL) . . . . . . . . . . . . . . . . . . . . . . . . . . . 50

  • 8/13/2019 BS240 eng

    6/78

    6 A30808-X3247-K22-1-7618

    Technical Description(TED:BSS)BS-240/241 II

    InformationBase Station System

    3.13 Overvoltage Protection and Tracer (OVPT). . . . . . . . . . . . . . . . . . . . . . . . . 50

    3.14 Abis Link Equipment (LE) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50

    3.15 Cover parts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51

    3.16 Backup Battery (BATTERY). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 513.17 FAN. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51

    3.18 Heater Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52

    4 Antenna combiners and receiving paths . . . . . . . . . . . . . . . . . . . . . . . . . . . 53

    4.1 Methods of combining. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53

    4.1.1 Typical combiner losses (Tx path) and output power level . . . . . . . . . . . . . 62

    4.1.2 Parameters of Tower Mounted Amplifier (TMA) . . . . . . . . . . . . . . . . . . . . . 63

    4.1.3 Examples of possible BTSE configurations . . . . . . . . . . . . . . . . . . . . . . . . . 65

    4.2 Receiving paths. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69

    4.2.1 Antenna diversity techniques. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69

    4.2.1.1 Antenna System Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69

    4.2.2 Receiver sensitivity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70

    4.3 Transmit Diversity/Antenna Hopping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70

    4.3.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70

    4.3.2 Functionality . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71

    4.3.3 CU-Pools. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71

    4.3.4 Algorithm for TX Diversity/Antenna Hopping. . . . . . . . . . . . . . . . . . . . . . . . 72

    5 Power supply and battery backup. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75

    5.1 Support of emergency operation for 3rd party BBU system. . . . . . . . . . . . . 75

    6 Abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77

  • 8/13/2019 BS240 eng

    7/78

    A30808-X3247-K22-1-7618 7

    InformationBase Station System

    Technical Description (TED:BSS)BS-240/241 II

    Illustrations

    Fig. 2.1 BS-240 II indoor Cabinet (Base Rack). . . . . . . . . . . . . . . . . . . . . . . . . . 14

    Fig. 2.2 Units and modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

    Fig. 2.3 Redundant COREs and their interfaces. . . . . . . . . . . . . . . . . . . . . . . . . 17

    Fig. 2.4 BS-240 base rack and 2 extension racks . . . . . . . . . . . . . . . . . . . . . . . 20

    Fig. 2.5 BS-241 base rack and 2 extension racks . . . . . . . . . . . . . . . . . . . . . . . 21

    Fig. 2.6 Possible configuration of Service1-Rack . . . . . . . . . . . . . . . . . . . . . . . . 22

    Fig. 2.7 Possible configuration of Service2-Rack . . . . . . . . . . . . . . . . . . . . . . . . 23

    Fig. 2.8 BS-240/241 II fully equipped with 24 carriers . . . . . . . . . . . . . . . . . . . . 24

    Fig. 2.9 E-OTD Calculation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

    Fig. 2.10 LCS Logical Reference Architecture. . . . . . . . . . . . . . . . . . . . . . . . . . . 26

    Fig. 2.11 LMU Connection to BTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

    Fig. 3.1 Backplane slot configuration of core. . . . . . . . . . . . . . . . . . . . . . . . . . . 31

    Fig. 3.2 COBA2P8 block diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

    Fig. 3.3 Structure of ACLK function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

    Fig. 3.4 COSA6P16 block diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

    Fig. 3.5 Carrier unit block diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35

    Fig. 3.6 PATRX block diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36

    Fig. 3.7 Principal data flow on SIPRO. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

    Fig. 3.8 Position of the ECU and CU in the BTS. . . . . . . . . . . . . . . . . . . . . . . . . 39

    Fig. 3.9 Epatrix and Esipro function block diagram.. . . . . . . . . . . . . . . . . . . . . . 41

    Fig. 3.10 EPATRIX INTERFACES. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43

    Fig. 3.11 Data flow in ESIPRO. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44

    Fig. 3.12 Alarm collection terminal (ACTM and ACTP). . . . . . . . . . . . . . . . . . . . . 49

    Fig. 3.13 Example of battery backup systems connected to the AC/DC . . . . . . . 51

    Fig. 4.1 Overview of combining options. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53

    Fig. 4.2 DUAMCO 2:2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55

    Fig. 4.3 DUAMCO 4:2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55

    Fig. 4.4 DUAMCO 8:2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56

    Fig. 4.5 FICOM 8:1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58

    Fig. 4.6 DIAMCO. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59

    Fig. 4.7 HPDU. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60

    Fig. 4.8 Configuration with HPDU, DUBIAS and TMA. . . . . . . . . . . . . . . . . . . . 61

    Fig. 4.9 Multi-cell (3,3,2): with 3 DUAMCO 4:2 . . . . . . . . . . . . . . . . . . . . . . . . . . 65

    Fig. 4.10 Multi-cell (3,3,2): with 2 DUAMCO 4:2 and 1 DUAMCO 2:2. . . . . . . . . 66

    Fig. 4.11 Single-cell (8,0,0): with FICOM and DIAMCO. . . . . . . . . . . . . . . . . . . . 66

    Fig. 4.12 Single-cell (8,0,0): with 2 DUAMCO 4:2. . . . . . . . . . . . . . . . . . . . . . . . . 67

    Fig. 4.13 Multi-cell (2,2,2): with 3 DUAMCO 2:2. . . . . . . . . . . . . . . . . . . . . . . . . . 67

    Fig. 4.14 Single-cell (11...16,0,0): FICOMs, DIAMCOs and HPDUs in 2 racks. . 68

    Fig. 4.15 Initial Data Structure Necessary For Proposed Algorithm . . . . . . . . . . . 74

  • 8/13/2019 BS240 eng

    8/78

    8 A30808-X3247-K22-1-7618

    Technical Description (TED:BSS)BS-240/241 II

    InformationBase Station System

    Tables

    Tab. 1.1 Technical data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

    Tab. 1.2 Frequency bands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

    Tab. 2.1 Nominal Power Amplifier Output Level (CU). . . . . . . . . . . . . . . . . . . . . . 18

    Tab. 2.2 Nominal Power Amplifier Output Level (ECU) . . . . . . . . . . . . . . . . . . . . 19

    Tab. 3.1 Units and modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

    Tab. 3.2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

    Tab. 4.1 Insertion loss of DUAMCOs, FICOMs, HPDU and TMA. . . . . . . . . . . . . 62

    Tab. 4.2 S22 of the GSM and DCS/PCS FICOMs. . . . . . . . . . . . . . . . . . . . . . . . 62

    Tab. 4.3 Parameters of 900 MHz Tower Mounted Amplifier . . . . . . . . . . . . . . . . . 63

    Tab. 4.4 Parameters of 1800 MHz Tower Mounted Amplifier . . . . . . . . . . . . . . . . 64

    Tab. 4.5 Parameters of 900/1800 MHz Tower Mounted Amplifier . . . . . . . . . . . . 65

  • 8/13/2019 BS240 eng

    9/78

    A30808-X3247-K22-1-7618 9

    InformationBase Station System

    Technical Description (TED:BSS)BS-240/241 II

    1 IntroductionThis manual is common for both BR5.5 and BR6.0 releases. Below are listed the

    features not supported in BR5.5 line:

    Enhanced Observed Time Difference features

    Edge Carrier Unit

    Transmit Diversity/Antenna Hopping

    850 MHz frequency

    The BS-240/241 II is an evolution of the existing BSS products. Some modifications

    have been introduced in the mechanical which represents the latest state of technology.

    The RF performance of the BTSs is not affected by the modifications.The architecture

    of BS-240/241 II provides maximum flexibility to develop higher capacity BTSs with

    reduced volume and an expanded number of 24 TRXs in 3 racks with a modularity of 8

    TRXs per rack. The provision of a full spectrum of combining equipment allows high

    power and minimized number of antennae. High receiver sensitivity is also guaranteed.

    The BS-240/241 II primarily consists of:

    carrier oriented boards called carrier unit (CU),

    core boards (COSA/COBA) and

    combining equipment

    The carrier unit(s) provide all analog and digital signal processing including an RF power

    stage necessary to process a single carrier (e.g., GSM 8 TCHs). The carrier unit(s) inter-

    face with the combining equipment on the one side and with the core modules on the

    other.The core boards provide functions common to all carriers within the BS-240/241 II

    (e.g., clock generation, O&M processing,...) as well as LAPD processing for the different

    carriers.

    Up to 8 PCM lines can be connected to the core boards. In order to provide cost effectivesolutions for small and large BTSs, the core boards are scalable (COBA, /COSA). In

    addition, the BS-240/241 II itself is scalable. It is possible to connect up to 2 extension

    racks to a base rack.

    The primary communication between the modules is provided by means of bi-directional

    serial link communications between the carrier units (CU) and the core boards. The

    serial link also provides an effective means to realize baseband frequency hopping.

    Despite the fact that synchronization information is transported via the serial links, no

    differential length constraints apply for the lines of the serial link.

    All alarms, except the alarms generated in the core and in the CU boards, are trans-

    ported via the CAN bus. Alarms of the CU boards are transmitted via CC-Link. Core

    boards use their interface bus.

  • 8/13/2019 BS240 eng

    10/78

    10 A30808-X3247-K22-1-7618

    Technical Description (TED:BSS)BS-240/241 II

    InformationBase Station System

    1.1 Main features

    The BS-240/241 II is designed for max. 24 carriers in 3 racks/shelters plus service

    racks/shelters, if needed. The minimum configuration is one rack or one shelter with a

    service shelter. Service racks/shelters can be configured to accommodate BackupBatteries and Link Equipment. A service rack/shelter can be equipped with AC/DC

    Converters. Easy rack/shelter extension is possible with one or two Extension

    Racks/Shelters.

    The BS-240/241 II can be configured for the systems D850, D900, D1800 and D1900

    with the following configurations:

    Dual band: D900/D1800, D900/D1900, D850/D1800 and D850/D1900

    GSM-DCS cell

    mixed cell configuration to enlarge GSM cells with DCS frequencies

    Common BCCH channel for GSM-DCS cell (dual band)

    Single cell

    Multi cell

    Up to 6 cells per rack and up to 12 cells can be supported. A special case is the feature

    concentric cell; one cell with 2 supply areas (inner and complete area). This feature

    can be used in omnicells as well as in multicells with sectors.

    The following combining options are supported:

    antenna combining with duplexers (DUAMCO) can be applied for 2, 4 and 8 carriers.

    RF amplifier and multicoupler for the RX path are integrated

    antenna combining with Filter Combiners (FICOM) is possible for up to 8 carriers

    onto one TX antenna

    cascading of multicoupler equipment (DIAMCO) is possible for up to 24 carriers

    High Power Duplexer (HPDU) for reduction of the necessary numbers of antennas

    in case of FICOM per cell for up to 8 carriers can be applied every BTSE has core equipment in the Base Rack/Shelter

    sensitivity is better than GSM requirements at the rack entry by using DUAMCO or

    DIAMCO units

    BTSplus sensitivity is better than GSM requirements at the antenna connector by

    using Tower Mounted Amplifiers (TMA)

    EDGE Carrier Units (ECU)

    Mixed Configurations of Cells/Sectors applying both EDGE Carrier Units (ECU) and

    normal Carrier Units (CU)

    Traffic Channels:

    Full-Rate (FR)

    Half-Rate (HR) Enhanced Full-Rate (EFR)

    Adaptive Multi Rate Codec (AMR)

    Services:

    GPRS

    HSCSD

    Frequency Hopping:

    Baseband

    Synthesizer

    Redundancy:

    SW Support of Core Redundancy

    SW Support of BCCH Redundancy

  • 8/13/2019 BS240 eng

    11/78

    A30808-X3247-K22-1-7618 11

    InformationBase Station System

    Technical Description (TED:BSS)BS-240/241 II

    AC/DC n+1 redundancy. (n+1) AC/DC Converters work in load sharing, but n AC/DC

    are able to supply the whole BS-240/241 II including Service Racks/Shelters

    Abis interface:

    Enhanced Full-Rate TCH Full-Rate and Half-Rate TCH

    submultiplexing 4 x 16 kbit/s onto one 64 kbit/s timeslot for handling Full-Rate TCH

    on Um interface

    handling of 4x(2x8) kbit/s onto one 64 kbit/s timeslot for half-rate TCH on Um inter-

    face

    drop and Insert feature on 2 Mbit/s and 1.5 Mbit/s (T1) links is available on a 16 kbit/s

    and a 64 kbit/s basis

    star, loop and multidrop chain connections

    cross connect function

    change of PCM line configuration from star to multidrop or loop and vice versa is

    possible without any interruption of service

    multiple Abis LAPD links; load sharing and LAPD fault recovery

    external clock synchronization

    over-voltage protection with OVPT (optional feature)

    Abis link media:

    wire

    fiber optic

    Wave

    Fault procedures:

    Automatic Recovery procedure of faulty objects in BTS

    Online RF Loopback

  • 8/13/2019 BS240 eng

    12/78

    12 A30808-X3247-K22-1-7618

    Technical Description (TED:BSS)BS-240/241 II

    InformationBase Station System

    1.2 Technical data

    The BS-240/241 II family with 24 transceivers can be supplied in the following versions:

    A BS-240 for indoor installation.

    A BS-241 for outdoor installation (also equipped with: integrated power supply,battery, microwave equipment, integrated link equipment, heat exchanger and cross

    connector).

    BS-240/241 II consist in a split BTS architecture, with:

    - 1 base rack

    - 2 extension racks

    - up to 5 service racks (service1 or service2).

    Characteristics BS-240 (indoor) BS-241 (outdoor)

    Max. TRX per BTSE 24 24

    (in more than one rack)Max. TRX per cell 24 24

    (in more than one rack)

    Dimensions (mm) (HxWxD) 1600x600x450 (53x2x16) 1750x700x650 (59x24x22)

    (Base Racks) (incl. Plinth)

    Volume net 432 l 705 l796 l (incl. Plinth)

    Maximum power consumption 1600 W 1750 W

    Weight of Basic Rack / Shelter ca. 66 kg (146 Lbs) ca. 66 kg (146 Lbs)

    Weight of Service1 Rack equipped with: - 1 Frame AC/DC incl. 6 AC/DC Modules (ca. 27 kg/60 Lbs)- 1 Frame for Battery incl. 1Battery (48V / 85 Ah) (ca. 140 kg/309Lbs)- 1 Mounting Kit for Link Equipment incl. 1 Frame NTPM, Frame forFan Unit and two FAN's (ca. 16 kg/ 35 Lbs)- 1 Rack (ca. 66 kg/146 Lbs)SUM: ca. 249 kg (549 Lbs)

    Weight of Service1 Rack equipped with: - 1 Frame AC/DC incl. 6 AC/DC Modules (ca. 27 kg/60 Lbs)- 1 Mounting Kit for Link Equipment incl. 2 Frame NTPM, Frame forFan Unit and two FAN's (ca. 21 kg/46 Lbs)- 1 Rack (ca. 66 kg/146 Lbs)SUM: ca. 114 kg (251 Lbs)

    Weight of sub-racks: Sub-rack with Battery ca. 140 kg (309 Lbs)Sub-rack AC/DC with 6 AC/DC Modules ca. 27 kg (60 Lbs)Sub-rack with 4 CU's and 2 MUCO's ca. 40 kg (88 Lbs)Sub-rack with 4 ACOM's ca. 40 kg (88 Lbs)Rack (empty) ca. 66 kg (146 Lbs)Shelter (empty) ca. 27 kg (60 Lbs)1 HEX ca. 5.6 kg (12 Lbs)

    Temperature range (C) -5 C to +55 C+23 F to +131 F

    -45 C to +50 C-49 F to +122 F

    Tab. 1.1 Technical data

  • 8/13/2019 BS240 eng

    13/78

    A30808-X3247-K22-1-7618 13

    InformationBase Station System

    Technical Description (TED:BSS)BS-240/241 II

    Frequency-Band Uplink (MHz) Downlink (MHz)

    GSM 850 824.2 - 848.8 869.2 - 893.8

    P-GSM 900 890.2 - 914.8 935.2 - 959.8

    E-GSM 900 880.2 - 914.8 925.2 - 959.8

    R-GSM 900 876.2 - 914.8 921.2 - 959.8

    GSM-RE 900 876.2 - 901.0 921.2 - 946.0

    DCS 1800 1710.2 -1784.8 1805.2 -1879.8

    PCS 1900 1850.2 -1909.8 1930.2 -1989.8

    Tab. 1.2 Frequency bands

  • 8/13/2019 BS240 eng

    14/78

    14 A30808-X3247-K22-1-7618

    Technical Description (TED:BSS)BS-240/241 II

    InformationBase Station System

    2 Hardware architectureThe BS-240/241 II is designed to achieve commonality of boards to serve both

    GSM850/GSM900 with its different deviates (DCS1800/PCS1900) and standards

    selected for mobile communication systems. Moreover, the architecture of

    BS-240/241 II provides maximum flexibility to develop large and small BTSs which have

    similar costs per TRX. Fig. 2.1shows the base rack cabinet.

    Fig. 2.1 BS-240 II indoor Cabinet (Base Rack)

    The BTS functional blocks of the BS-240/241 II are shown in Fig. 2.2

  • 8/13/2019 BS240 eng

    15/78

    A30808-X3247-K22-1-7618 15

    InformationBase Station System

    Technical Description (TED:BSS)BS-240/241 II

    Fig. 2.2 Units and modules

    CU 7

    CU 0

    CU 7

    Base Rack

    Service Rack

    DUAMCO CU 0

    COSA

    ACTM

    CAN BUS

    CC-Links

    FICOM

    DIAMCO

    HPDU

    4xTX

    RX

    RXDIV

    4xTX

    RX

    RXDIV

    ACTC ACTP

    LE 0 LE 1

    BATTERY

    TMA

    DCB-

    ACP

    CTRL

    ACTC

    FAN

    Cell 0

    Cell 1

    FICOM

    DIAMCO

    4xTX

    4xTX

    RX

    RXDIV

    Cell 1

    RX

    RXDIV

    RX

    RXDIV

    ACTC ACTP

    FAN

    to next ext. rack

    RXCA1RXCA0

    BATTERY

    DCB-CTRL

    AC/DCAC/DC

    DCP

    DCP

    DCP

    Extension Rack

    Cascading

    DUBIAS

    COBA

    2 PCM

    Ext. Sync.

    2 PCM

    4 PCM

    Abis

    Sync.

    Abis

    TMA

    FAN

    TMA

    TMA

    OVPT

    OVPT

    * not present in case of BTSE with reduced number of fan

    *

    *

    *

  • 8/13/2019 BS240 eng

    16/78

    16 A30808-X3247-K22-1-7618

    Technical Description (TED:BSS)BS-240/241 II

    InformationBase Station System

    The architecture of BS-240/241 II provides maximum flexibility to develop large and

    small BTSs which have similar costs per TRX.

    The BS-240/241 II mainly consists of:

    carrier oriented boards called carrier unit (CU), core boards (COSA/COBA) and

    combining equipment

    Up to 8 PCM lines can be connected to the core boards. In order to provide cost effective

    solutions for small and for large BTSs, the core boards are scalable (COBA, /COSA). In

    addition, also the BTS itself is scalable. It is possible to connect up to 2 extension racks

    to a base rack.

    The main communication between the modules is provided by means of bi-directional

    serial link communications between the carrier units (CU) and the core boards. The

    serial link also provides an effective means to realize baseband frequency hopping.

    Despite the fact that synchronization information is also transported via the serial links,

    no differential length constraints apply for the lines of the serial link.

    All alarms, beside the alarms that are generated in the core and in the CU boards, are

    transported via the CAN bus. Alarms of the CU boards are transmitted via CC-Link. Core

    boards use their interface bus.

    The carrier unit(s) provide all analog and digital signal processing including a RF power

    stage necessary to process a single carrier (e.g., GSM 8 TCHs). The carrier unit(s) inter-

    face with the combining equipment on the one side and with the core modules on the

    other. The core boards provide functions common to all carriers within the BS-240/241 II

    (e.g., clock generation, O&M processing,...) as well as LAPD processing for the different

    carriers.

    AC/DC AC/DC converter DCBCTRL DC and Battery Controller

    ACP AC Panel DCP DC Panel

    ACTC Alarm Collection Terminal Connection module DIAMCO DI(2) Amplifier Multi Coupler

    ACTM Optional Alarm Collection Terminal for Master Rack DUAMCO Duplex Amplifier Multicoupler

    ACTP Alarm Collection Terminal for Slave Rack FICOM Filter Combiner

    CAN Controller Area Network HPDU High Power Duplexer

    COBA Core Basis (COBA2P8) LE Link Equipment

    COSA Core Satellite (COSA6P16) TMA Tower Mounted Amplifier

    CU Carrier Unit

  • 8/13/2019 BS240 eng

    17/78

    A30808-X3247-K22-1-7618 17

    InformationBase Station System

    Technical Description (TED:BSS)BS-240/241 II

    2.1 Board redundancy

    Redundancy in the SBS ensures survival of the system even in the event of multiple fail-

    ures. Modular architecture, in conjunction with the concept of split functions, guarantees

    maximum survivability with a minimum of additional hardware.

    2.1.1 AC/DC

    Up to 6 AC/DC converters (only one Frame) can be equipped in the service1 rack which

    provide N+1 redundancy. AC/DC converters work in load sharing, but n AC/DC are able

    to supply the whole BS-240/241 II .

    .

    2.1.2 Core

    The Core can consist of up to 2 (without redundancy) or up to 4 (with redundancy)

    boards, which have a common backplane. The block diagram depicts the 2n CORE

    redundancy and the embedding of the active and the passive CORE into the BTS, and

    the interrelation of both COREs.

    Fig. 2.3 Redundant COREs and their interfaces

    Both COREs (COBA0/COSA0 and COBA1/COSA1) have link interfaces to the ABIS

    lines, but only one (the active CORE) can physically be connected.

    On the backplane of the BTS, one connector provides a link of the LMT to the current

    active CORE. In the case of a CORE switch over, the switch logic switches that

    connector to the new active CORE. The same holds for the CAN bus (alarm bus), i.e.,

    both COREs have the same CAN bus address where at any time at most one CORE is

    an active CAN bus node.

    Both the active and the passive CORE have links to the carrier units (CU); in reverse,

    each CU is linked with both COREs. The traffic data are transmitted transparently

    through the active CORE. Signal processing takes place only within the CUs.

    CUSELIC

    SELIC

    BISON

    RDInterf.

    SwitchLogic

    FALC

    CORE 0CLK

    Route Clock

    Redundancy Link

    Switch Logic Link

    Route Clock

    (Frame Sync)

    ABISCAN

    LMT

    P

    CUSELIC

    CUSELIC

    SELIC SELIC SELIC

    BISON

    RDInterf.

    SwitchLogic

    FALC

    CORE 1CLK

    Route Clock

    P

    SELICSELIC

  • 8/13/2019 BS240 eng

    18/78

    18 A30808-X3247-K22-1-7618

    Technical Description (TED:BSS)BS-240/241 II

    InformationBase Station System

    The endpoints of each link are built up by SELIC ASICs (note: one SELIC contains

    double functionality), where on the CU, one SELIC serves two COREs. In the case of a

    switch over, the SELICs on the active CORE are disabled by the switch logic and the

    SELICs on the passive one are enabled. The SELICs on the CORE have to know

    whether they are on the active or on the passive CORE. For this reason the SELICs

    need a active/passive pin, which is served by the redundancy switch logic. When a

    switch over occurs, the switch logic sets the active/passive pin of the former active

    SELICs to "passive" and that of the former passive SELICs to "active".

    The SELICs on the CUs have to recognize automatically which link comes from the

    active CORE and which link from the passive one, i.e. it has to recognize a CORE switch

    over by itself.

    The RD interface (redundancy interface) is realized as a 2 Mbit/s HDLC link which

    provides a communication interface between the two main processors (mP).

    The switch logic is a flip-flop distributed over the two COREs. It manages the HW part

    of a switch over and enables the COREs to know about their states as active/passive.

    The ACLK of the active CORE is connected with the one on the passive CORE. It allows

    the passive ACLK to be synchronized to the active one.

    NOTE: the redundancy is implemented in a cold-standby mode, i.e., all calls will get lost

    if a CORE switch over occurs.

    2.2 Nominal power amplifier output level

    2.2.1 Carrier Unit (CU)

    D900 output powerat PA output

    D1800 output powerat PA output

    D1900 output powerat PA output

    60 Watt 40 Watt 40 Watt

    Tab. 2.1 Nominal Power Amplifier Output Level (CU)

    iGSM: minimum guaranteed output power CU = 50 Watt tolerance value: 47.0 dBm -47.6 dBm (50 W - 57.5 W) DCS/PCS: minimum guaranteed output power CU = 34 Watttolerance value: 45.3 dBm - 46.0 dBm (34 W - 39.5 W).The mentioned data are guaranteed form Module Factory Test only. The typical outputpower at CU output is for:GSM: 47,3 dBm DCS: 45.7 dBmTo verify the typical output power values in field measurements, the tolerance value ofthe used measurement equipment, environmental conditions and GSM 05.05 specifica-tions have to be considered.

  • 8/13/2019 BS240 eng

    19/78

    A30808-X3247-K22-1-7618 19

    InformationBase Station System

    Technical Description (TED:BSS)BS-240/241 II

    2.2.2 Edge Carrier Unit (ECU)

    2.3 Rack configurationThe BS-240/241 II family, with 8 transceivers per rack, which is expandable up to 24

    transceivers in 3 racks and can be supplied in two versions:

    a BS-240 for indoor installation, and

    a BS-241 for outdoor installation (also equipped with integrated link equipment,

    battery backup and a cooling system).

    There are 4 different types of rack:

    Base Rack/Shelter (with Core modules)

    Extension Rack/Shelter (for more then 8 CUs)

    Service1 Rack/Shelter (with AC/DC modules)

    Service2 Rack/Shelter (for LE and batteries)

    It is possible to connect up to 3 Racks/Shelters together (1 Base Rack, 2 Extension

    Racks; the more possible racks/shelters called Service Rack/Shelter are not part of a

    Rack Extension in the proprietary sense) that realizes then the performance of a 24 TRX

    BTSE as shown in Fig. 2.4and Fig. 2.5:

    D850/D900 output power

    at PA output

    D1800 output power

    at PA output

    D1900 output power

    at PA output

    70 Watt GMSK44 Watt 8PSK

    54 Watt GMSK34 Watt 8PSK

    54 Watt GMSK34 Watt 8PSK

    Tab. 2.2 Nominal Power Amplifier Output Level (ECU)

    iGSM: minimum guaranteed output power ECU = 63 Watt (GMSK) / 40 Watt (8PSK).DCS/PCS: minimum guaranteed output power ECU = 50 Watt (GMSK) / 32 Watt(8PSK).The mentioned data are guaranteed from Module Factory Test only.

  • 8/13/2019 BS240 eng

    20/78

    20 A30808-X3247-K22-1-7618

    Technical Description (TED:BSS)BS-240/241 II

    InformationBase Station System

    Fig. 2.4 BS-240 base rack and 2 extension racks

    ACOM

    0

    ACOM

    1

    ACOM

    2

    ACOM

    3

    DC-PANEL

    ACT-C

    CU2

    CU3

    CU6

    CU7

    MUCO0

    MUCO1

    CU

    0

    CU

    1

    CU

    4

    CU

    5

    BS-240SIEMENS

    ACOM

    0

    ACOM

    1

    ACOM

    2

    ACOM

    3

    CU2

    CU3

    CU6

    CU7

    MUCO0

    MUCO1

    CU

    0

    CU

    1

    CU

    4

    CU

    5

    BS-240SIEMENS

    C

    OBA

    0

    C

    OSA

    0

    C

    OBA

    1

    C

    OSA

    1

    FAN 0 FAN 1

    ACOM

    0

    ACOM

    1

    ACOM

    2

    ACOM

    3

    DC-PANEL

    ACT-C

    CU2

    CU3

    CU6

    CU7

    MUCO0

    MUCO1

    CU

    0

    CU

    1

    CU

    4

    CU

    5

    BS-240SIEMENS

    FAN 0 FAN 1

    DC-PANEL

    ACT-C

    FAN 0 FAN 1

    FAN 2 FAN 3

    FAN 4 * FAN 5*

    FAN 2 FAN 3

    FAN 4* FAN 5*

    FAN 2 FAN 3

    FAN 4* FAN 5*

    * not present in case of BTSE with reduced number of fans

  • 8/13/2019 BS240 eng

    21/78

    A30808-X3247-K22-1-7618 21

    InformationBase Station System

    Technical Description (TED:BSS)BS-240/241 II

    Fig. 2.5 BS-241 base rack and 2 extension racks

    Fig. 2.8 shows one of the possible configurations. The Base Rack and the Extension

    Racks can be located physically in any position.

    The Service Rack (see Fig. 2.6 and Fig. 2.7) satisfies various applications depending

    on number of CU units configured and/or number and kind of Network termination equip-

    ment provided and the Battery Backup time required.

    CU2

    CU3

    CU6

    CU7

    MUCO0

    MUCO1

    CU

    0

    CU

    1

    CU

    4

    CU

    5

    BS-241SIEMENS

    COBA

    0

    COSA

    0

    COBA

    1

    COSA

    1

    DC-PANEL

    ACT-C

    FAN 0 FAN 1

    FAN 2 FAN 3

    FAN 4* FAN 5*

    ACOM

    0

    ACOM

    1

    ACOM

    2

    ACOM

    3

    CU2

    CU3

    CU6

    CU7

    MUCO0

    MUCO1

    CU

    0

    CU

    1

    CU

    4

    CU

    5

    BS-241SIEMENS

    DC-PANELACT-C

    FAN 0 FAN 1

    FAN 2 FAN 3

    FAN 4* FAN 5*

    ACOM

    0

    ACOM

    1

    ACOM

    2

    ACOM

    3

    CU

    2

    CU

    3

    CU

    6

    CU

    7

    MUCO0

    MUCO1

    CU

    0

    CU

    1

    CU

    4

    CU

    5

    BS-241SIEMENS

    DC-PANELACT-C

    FAN 0 FAN 1

    FAN 2 FAN 3

    FAN 4* FAN 5*

    ACOM

    0

    ACOM

    1

    ACOM

    2

    ACOM

    3

    * not present in case of BTSE with reduced number of fans

  • 8/13/2019 BS240 eng

    22/78

    22 A30808-X3247-K22-1-7618

    Technical Description (TED:BSS)BS-240/241 II

    InformationBase Station System

    Fig. 2.6 Possible configuration of Service1-Rack

  • 8/13/2019 BS240 eng

    23/78

    A30808-X3247-K22-1-7618 23

    InformationBase Station System

    Technical Description (TED:BSS)BS-240/241 II

    Fig. 2.7 Possible configuration of Service2-Rack

    On the digital side there is an extension of the CC links (connection between Core Back-

    plane and the CUs not housed in the Base Rack) and the CAN Bus. The CAN Bus

    connection cannot be shown in the right way because it strongly depends on the number

    of Extension and Service Racks present.

    On the RF side there is an extension in the RX path only for omni and specific sector

    cell (e.g., 5/5/5) configurations and diversity reception with more than 8 TRX. Thus amaximum of 2 RF cables (cascading) are connected between two racks. There is no TX

    combining over rack borders thus the TRXs of different racks is combined on air only.

    Some configurations are not possible with 2 racks only e.g., 5/5/5 with FICOM because

    of the number of available ACOM slots.

  • 8/13/2019 BS240 eng

    24/78

    24 A30808-X3247-K22-1-7618

    Technical Description (TED:BSS)BS-240/241 II

    InformationBase Station System

    Fig. 2.8 BS-240/241 II fully equipped with 24 carriers

    For the BS-241 II outdoor cabinet only one type of the Shelter exists to be used for all

    outdoor Base Shelter, Extension Shelters, Service1 and Service2 Shelters.

    2.4 Enhanced Observed Time Difference (E-OTD)

    In the GSM Location using an E-OTD Service, the LMUs (Location Measurement Unit)

    are used to provide timing measurements of broadcast channel synchronization frames

    (SCH). This is used within an E-OTD Service to provide location measurements for an

    E-OTD equipped mobile station (MS).

    In the E-OTD positioning method, the LMU measures the relative time of arrival of thesignals from several BTSs. The position of the MS is determined by deducing the

    geometrical components of the time delays to an MS from the BTS. The Siemens LMU

    measures real-time differences between synchronization bursts of BTS pairs. The accu-

    racy of the location estimate depends on the MS being able to receive signals from a

    sufficient number of BTSs whose timing is known.

    An E-OTD location service works as follows:

    The MS takes measurements of the time differences between the SCH of at least

    three received BCCH. If it can see more than three BCCHs, it should take additional

    measurements, as these will improve the accuracy of the result.

    Extension Rack

    Base Rack

    Service1 Rack

    Service2 Rack

    Extension Rack

  • 8/13/2019 BS240 eng

    25/78

  • 8/13/2019 BS240 eng

    26/78

    26 A30808-X3247-K22-1-7618

    Technical Description (TED:BSS)BS-240/241 II

    InformationBase Station System

    communicate with the PLMN via a fixed, wired interface. Two potential interfaces are

    provided, a CAN interface or a high speed serial interface.

    The Siemens Type B LMU is a dual band unit operating over the GSM850 BCCH band

    and the PCS1900 BCCH band.To improve measurement accuracy and allow for expendability, the LMU includes a

    GPS receiver based on the SiRF chip set. Serial output of the GPS data can be enabled,

    and a 1 PPS, TTL level signal is provided. The recommended GPS antenna for co-

    located installation is the Trimble Bullet III. This has high immunity to jamming and

    allows for both easier installation and less disruption of the GPS service.

    For location services, the LMU sends and receives LLP messages compliant with the

    ETSI standard, GSM 04.71.

    2.4.1 Logical Architecture

    The figure below shows the components of interest for the SMLC within the LCS logicalarchitecture. Siemens has adopted a BSS centric architecture for its LCS.

    Fig. 2.10 LCS Logical Reference Architecture

    LCS components of interest for the SMLC and their LCS-related functionalists:

    BSC (Base Station Controller)

    The BSC receives a location request for a particular MS from an LCS client via the

    GMLC and MSC. It may append additional information and forward the request to a

    BSS-based SMLC. It also transfers positioning related messages between the SMLC,

    the target MS, and LMU. The BSC forwards the location response received from the

    SMLC to the GMLC via the MSC.

    BTS (Base Transceiver Station)

    The BTS provides the radio interface to the MS.

    GMLC (Gateway Mobile Location Center)

    The GMLC provides external LCS clients with access to the GSM PLMN and its locationservice. There can be several GMLCs in one PLMN. The GMLC stores LCS subscription

  • 8/13/2019 BS240 eng

    27/78

    A30808-X3247-K22-1-7618 27

    InformationBase Station System

    Technical Description (TED:BSS)BS-240/241 II

    information on a per-LCS-client basis. It uses this information when receiving an LCS

    request to identify the requesting LCS client and to authorize it to use the specified

    request

    LMU (Location Measurement Unit)

    The LMU makes the radio measurements needed by different positioning methods and

    supplies the data to the SMLC associated with it. The radio measurements can be

    specific to one MS (location measurements) or specific to all MSs in a certain

    geographic area (assistance measurements).

    MSC/VLR (Mobile Switching Center/Visitor Location Registry)

    With a BSS based SMLC, the MSC relays location requests and responses between the

    GMLC and the BSC serving the MS to be located.

    SMLC (Serving Mobile Location Center)The SMLC manages the overall coordination and scheduling of resources required to

    position MSs in a PLMN. There may be more than one SMLC in one PLMN. The BSS-

    based variant receives location requests from its associated BSCs. It determines the

    positioning method to be used based on the QoS, the capabilities of the network, and

    the MSs location capabilities. It can instigate location-related measurements in the MS

    itself or in separate LMUs. The SMLC calculates the final location estimate and accu-

    racy and returns it in a location response to the requesting BSC.

    LCS Client

    The LCS client provides location dependent services to the MS subscriber. It represents

    a location application.

    MS (Mobile Station)

    The MS is the target to be located. For MS-assisted and MS-based positioning methods,

    it generates additional measurement data or even calculates the location itself.

    2.4.2 LMU Interconnection

    The LMU module is controlled over the BTS CAN bus. The CAN bus will support LLP

    messages, for the support of LCS, and O&M functions.

    The LMU module is connected to external antennas and to the test signal ports of any

    DUAMCOs, etc, that carry BCCH sniffer signals for the collocated BTS, as shown inFigure 2.10

  • 8/13/2019 BS240 eng

    28/78

    28 A30808-X3247-K22-1-7618

    Technical Description (TED:BSS)BS-240/241 II

    InformationBase Station System

    Fig. 2.11 LMU Connection to BTS

    The LMU module is provisioned for the connection of two external GSM antennas. The

    provisions for the use of a second antenna will cover those situations were a single

    antenna would not acceptably receive all of the desired BCCH signals.

    The LMU module is provisioned for the connection of an external GPS antenna.The LMU module is provisioned for the connection of three sniffer signals, one for each

    sector. When multiple sniffer signals need to be combined then all of those serving a

    particular sector will be combined into a single feeder cable using resistive combiners.

  • 8/13/2019 BS240 eng

    29/78

    A30808-X3247-K22-1-7618 29

    InformationBase Station System

    Technical Description (TED:BSS)BS-240/241 II

    3 Modules Description

    iIn Tab. 3.1"x" indicates the frequency range: G =GSM, D =DCS, P = PCS

    Name Freq.Var.

    Remarks

    Core modules:COBACOSA

    Core basisCore satellite

    no Up to 8 PCM lines with COBA and COSAequipped (COBA and COSA can beequipped only in the base rack/shelter).

    Carrier related modules:CUxECUx

    Carrier unit yes Carrier unit and edge carrier unit can beequipped only in the base and extensionracks/shelters (see also section 2.2)

    Antenna system modules:DUAMCO2xDUAMCO4xDUAMCO8xDIAMCOxFICOMBxFICOMXxTMAxHPDUx

    Duplexer 2:2Duplexer 4:2Duplexer 8:2Diversity multi couplerFilter combiner (base)Filter combiner (extension)Tower mounted amplifierHigh power duplexer

    yes Antenna system modules can beequipped only in the base and extensionracks/shelters.DIAMCO, FICOM and HPDU are notavailable for the PCS band.DUAMCO 2:2, DUAMCO 4:2 and HPDUworking in shifted primary GSM band areavailable.A Diplexer can be used in all caseswhere GSM900 and DCS1800/PCS1900or GSM850 and DCS1800/PCS1900Feeder Cables have to be installed inparallel.

    Alarm collection modules:ACTC (part of DC-Panel)ACTMACTP

    Alarm collection terminals no ACTC is equipped in every rack/shelter.ACTM can be equipped only in the baserack/shelter. ACTP can be equipped inthe extension or service racks/shelters.

    Power supply modules:ACDCDCBCTRL

    ACDC converterDC battery controller

    no ACDC controller used for AC power andsupervision of the ACDC converter canbe equipped only in the serviceracks/shelters.

    OVPTOVPTCOAX

    Over voltage protectionand tracer

    no 100 / 120 symmetric line75 coaxial asymmetric line. The OVTPis an optional feature.

    Abis Link Equipment:LE

    Link Equipment no Link Equipment can be equipped only inservice1 and service2 racks/shelters

    Tab. 3.1 Units and modules

  • 8/13/2019 BS240 eng

    30/78

  • 8/13/2019 BS240 eng

    31/78

    A30808-X3247-K22-1-7618 31

    InformationBase Station System

    Technical Description (TED:BSS)BS-240/241 II

    Fig. 3.1 Backplane slot configuration of core

    For a configuration with less or equal 2 PCM30/24-interfaces and no Extension Rack

    one COBA-board is required. The second slot can be used for an expansion of the BTSE

    up to 8 Abis- and 24 CU-interfaces or it can be used for future expansions, e.g. a

    GPS-Receiver for synchronization, better frequency-standards or other Abis-interfaces

    than PCM30/24 (e.g., SDH, ATM).

    The connection of the Abis- and CU-interfaces of the Core to the OVPT/Abis-interface

    and the CUs is done via cables, which are plugged into the backplane.

    The CU-interfaces of the Core and its redundancy are routed with separated wires via

    the backplane and cables to the CUs (2 interfaces on one CU required).

    The Abis-interface-ports of the Core and its redundancy-ports can only be switched to

    the same wires. Only one transceiver at the same time is allowed to be switched to the

    same wires (no simultaneous transmitting/receiving of Core and its redundancy on the

    same Abis-port possible).

    To find the physical place of a Abis-interface/CU out of the logical/memory-map

    address, appropriate configuration-rules are created and considered!

    Two Core-boards, COBA2P8 (see section 3.1.1) and COSA6P16 (see section 3.1.2),

    are developed. The first digit gives the number of Abis-Interfaces, the following letter the

    kind of Abis-interface (e.g. P for PCM30/24), and the following number the number of

    CU-interfaces, e.g., COSA6P16 (6 PCM30/24 Abis-interfaces, 16 CU interfaces).

    Hot Plug-in: A Hot Plug-in of the Core-boards (COBA and COSA) is possible. This

    means that these boards can be plugged in/out with voltage switched on and no other

    HW inside of the rack is disturbed (no loss of data on other boards) or a board is

    destroyed.

    CABLE

    2 Abis 6 Abis

    COBA COSA COBA red. COSA red.

    2 Abis 6 Abis

    Abis

    8 CU 16 CU 8 CU 16 CU other

    interfaces

    Backplane Plugs

    Extension

    CUs

    CUOVPT Rack

    iA COBA-board can only be pulled out, if before the COSA-board is pulled out

  • 8/13/2019 BS240 eng

    32/78

    32 A30808-X3247-K22-1-7618

    Technical Description (TED:BSS)BS-240/241 II

    InformationBase Station System

    After plug-in of a Core-board, this board is in the reset-state and all bus-drivers of

    external busses are in tristate. These drivers will be enabled not before initialization of

    the devices, which serve the external busses (e.g., BISONs, SELICs).

    3.1.1 Core Basis (COBA2P8)

    The COBA is the central board of the core. The functionality of the advanced clock

    generation (ACLK) and the base core controller (BCC) of the entire BTSE are inte-

    grated. Additionally two PCM30/24 Abis-interfaces are available on the COBA2P8.

    The controller maintains the SW of all BTSE units in FLASH-EPROMs, supervises the

    SW download and terminates all internal system alarms. Beside the O&M functions, the

    controller handles the signalling messages between the BSC (Abis) and CUs (CC-Link).

    For interface and feature extensions the COBA can be expanded with one satellite

    (COSA).

    To fulfill the CORE redundancy aspects, the COBA board with its satellite COSA board

    can be duplicated. In this case, one CORE (COBA+COSA) is "providing service" and

    works as the master and the other CORE is "cold standby" or is "disabled" if HW prob-

    lems have occurred. The redundancy switch is controlled by the COBA board. Special

    links are provided for information exchange between the two board sets.

    Fig. 3.2 COBA2P8 block diagram

    The ACLK generates the system specific timing signals that are distributed by the

    SELIC2s to the CUs. Fig. 3.3shows the structure of the ACLK function.

    SMC2

    SMC1

    SMC4

    SMC3

    SMC2

    TSA-SCC1SIU

    BCC

    MPC860MH

    SESA

    OASI

    RDL

    TPC

    LMT/OTP

    LAPD

    ACLK

    SELIC

    SELIC

    SELIC

    SELIC

    CUCU

    CUCUCUCU

    CU

    CU

    SELIC-BUS

    Abis1

    Abis2

    BISON-BUS

    SA

    T-Interface

    DC/DC Converter

    SRAM16MB

    FLASH3 X 8MB

    CAN I/OBISON

    RDLLOGIC WATCHDOGEEPROMsA/D-Conv. MUX

    CAN-BUS, ALARMs LEDs, Redundancy Control,CU_DC_OFF ect.

    Route clock

    ext CLK sync

  • 8/13/2019 BS240 eng

    33/78

    A30808-X3247-K22-1-7618 33

    InformationBase Station System

    Technical Description (TED:BSS)BS-240/241 II

    Fig. 3.3 Structure of ACLK function

    The tracking oscillator TOP synchronizes the oven controlled VCXO to the selected

    frequency reference source. The TOP is realized as a phase/frequency locked loop. The

    regulation parameters (P and I constant) are variable by SW. The regulating algorithm

    is also implemented by SW. The output clock of the oscillator is called the master clock.The cut-off frequency of the TOP depends directly on the pulling gradient of the used

    OCVCXO. Since the ACLK must synchronize to jittered lines, the scattering of the cut-off

    frequency is very critical. The cut-off frequency must choose very low to eliminate lowest

    frequency wander and is therefore near the range of the temperatures cut-off

    frequency. To guarantee less deviation of the required cut-off frequency, also with

    components from different manufactures (2nd and 3rd source), the OCVCXO is cali-

    brated on the COBA in the factory. The pulling gradient is measured against an atomic

    clock and the calibration values are stored on the COBA in a serial EEPROM. Uncali-

    brated ACLKs must not work in the field. This can be achieved by the software, which

    should check whether or not the ACLK is calibrated.

    The clock line of the current select so synchronization source is also linked to the redun-dant ACLK function, which may also track this frequency. For redundancy switch-overs,

    no warm up and only a short synchronization phase (because of the effects at the

    switch-over) of the redundant ACLK is necessary.

    The loadable timing generation hardware LTG is implemented in a FPGA device, which

    can be loaded by the BCC with the current hardware function. In this stage, all neces-

    sary system clocks and the master sync pulse are generated. Also, the master counter

    is realized. The count value of the master counter is fed via a serial interface to the

    SELIC. In active redundancy mode, the master sync pulse is forwarded to the standby

    ACLK. In standby redundancy mode, the generator is synchronized with the master

    sync pulse coming from the active ACLK function. Therefore, both redundant ACLKs

    generate their clocks in alignment. If necessary, a very fast redundancy switch-over ispossible.

    referenceclockdivider

    masterclock

    divider

    phase/

    frequency

    detector

    D

    A

    BCC interface

    OCVCXO

    32, 768 MHz

    master clock

    referenceclock input

    TOPtrackingoscillatorprocessorcontrolled

    master sync inputfrom redundant ACLK

    LTG

    loadabletiminggenerator

    2

    48

    164096

    1966080master counterBCC Interface

    SYNC

    16,384 MHz8,192 MHz

    4,096 MHz2,048 MHz

    8 kHz

    60 ms

    SYNC

    Driver

    Stage

    systemclocks

    master syncmaster counts

    master sync to redundant ACLK

    reference clock to redundant ACLK

  • 8/13/2019 BS240 eng

    34/78

    34 A30808-X3247-K22-1-7618

    Technical Description (TED:BSS)BS-240/241 II

    InformationBase Station System

    The FPGA is configured after a power-on reset from the BCC. Until the configuration has

    finished, no output clocks are available, i.e., a communication via Abis or CUs is not

    possible. The communication path from the LMT to the BCC is not affected, i.e., a

    SW-download via the LMT is possible.

    3.1.2 Core Satellite (COSA6P16)

    The COSA6P16 board (COSA6P16) has the following functions:

    6 PCM30/24-interfaces for Abis

    16 CU-interfaces

    The board is controlled from the COBA via the SAT-interface (satellite-interface; 32bit

    data). Fig. 3.4shows a block diagram of the COSA6P16:

    Fig. 3.4 COSA6P16 block diagram

    The key-element of the PCM-interfaces is the FALC (Framing and Line InterfaceComponent for PCM30 and PCM24). It has the following tasks:

    analogue receive and transmit circuitry for PCM30 and PCM24

    data- and clock-recovery

    frame alignment/synthesis

    line-supervision

    timing-adaptation to BISONs

    Data arriving from the Abis-Interface via a PCM-port can be switched non-blocking and

    bitwise (8 kbit/s and n x 8 kbit/s data-rate possible) with the BISONs to another

    PCM-Port or via a SELIC2 to a CU.

    SELIC

    BISON

    OVPT

    FALC54 for PCM30/24&

    PCMport5

    PCMport6

    Interfacesto COBA

    Real-Time BUS (Hopping)Non-Real-Time BUS (O&M)

    toCUs

    BISONBUS

    RouteClocks

    RouteClock

    Preselector

    RCLK1-6

    CLKX1-6

    WorkingClocks

    DC/DCConverter

    SAT-Interface(32bit data)

    SELIC

    SELIC

    SELIC

    SELIC

    SELIC

    SELIC

    SELIC

    OVPT

    FALC54 for PCM30/24&

    PCMport1

    PCMport2

    OVPT

    FALC54 for PCM30/24&

    PCMport3

    PCMport4

  • 8/13/2019 BS240 eng

    35/78

    A30808-X3247-K22-1-7618 35

    InformationBase Station System

    Technical Description (TED:BSS)BS-240/241 II

    The route-clocks of one FALC can be switched with the route-clock multiplexer to the

    COBA for synchronization purposes. The COSA6P16 gets its working-clocks from the

    COBA.

    The COSA6P16 is switched with relays to the PCM-lines. In case of failures, thePCM-port 1(3)(5) and 2(4)(6) can be short-circuit with each other via appropriate relays.

    There is a power-on device on the COSA6P16, which generates a reset at power-on

    (board-reset). Via a line, the COSA6P16 can be reset from the COBA (board-reset).

    Additionally, single devices on the COSA6P16 can be reset from the COBA via the

    SAT-interface.

    3.2 Carrier Unit (CU)

    The Carrier Unit (CU) takes care for all carrier oriented tasks. In the uplink (UL) direction

    two RF signals (diversity) are received and finally converted into TRAU frames and

    signalling data. In the downlink (DL) direction, TRAU frames and signalling data arereceived and converted into a GMSK modulated RF signal, which is amplified to the

    desired power level.

    The CU consists of the following sub-units:

    Power Amplifier and Transceiver Unit (PATRX)

    Signal Processing Unit (SIPRO)

    Power Supply Unit (PSU)

    There are four variants of the CU for the frequency bands GSM850, R-GSM900,

    DCS1800 and PCS1900. The differences of the variants arise mainly on the sub-unit

    PATRX.

    Fig. 3.5 Carrier unit block diagram

    Power Amplifier and Transceiver Unit (PATRX)

    PATRX provides the main analog functions of the CU:

    receives the two (diversity) RF signals from the antenna combining equipment and

    dawnconverts them to IF. The downconverted RF signals are then transmitted to

    SIPRO where they are sampled and digitally downconverted to baseband.

    receives the GMSK modulated signal from the SIPRO. The signal is then I/Q modu-

    lated, upconverted, levelled, power amplified, and transmitted to the antenna

    combining equipment.

    supports the synthesizer frequency hopping provides an RF loop between downlink and uplink path for the unit test of the CU

    SIPRO

    PSU

    PATRXCC-Link

    -48V DC

    Rx inputs

    Tx output

    Test PC/OMT, SCC,Layer 1 Trace, JTAG,PID, Vcce Loop

    Display

  • 8/13/2019 BS240 eng

    36/78

    36 A30808-X3247-K22-1-7618

    Technical Description (TED:BSS)BS-240/241 II

    InformationBase Station System

    The power control loop implements 6 static power steps (each 2 dB) and an additional

    15 dynamic power levels (each 2 dB). For low output power versions of the CU, a further

    reduction of 2 dB is provided.

    Fig. 3.6 PATRX block diagram

    The functional sub-unit PATRX consists of three PCBs:

    RXA:Analog receiver board with modules RXFEM, RXFED, RXLO and LTL

    TXA:Analog transmitter board with modules MODUP, TXLO,and PWRDET

    PWRSTG:Power stage including heat sink

    Signal Processing Unit (SIPRO)

    The SIPRO-Board is a part of the Carrier Unit. It contains all digital functions of the

    carrier unit, including the following:

    Signal Processing in uplink and downlink

    Control of RF on PATRX

    Baseband and synthesizer hopping

    Channel Control

    Radio Link Control

    O&M parts relevant for carrier unit

    Link to Core via CC linkAdditionally, following analog functions are located on SIPRO:

    Analog to digital conversion (IF)

    Digital to analog conversion (baseband)

    Local clock of CU

    Due to the analog functions, SIPRO is specific for the different frequency variants. There

    are two types of SIPROs (one for GSM850/GSM900, and one for DCS1800/PCS1900).

    Fig. 3.7illustrates the principal data flow on SIPRO:

    receives two (diversity!) IF signals from the receiver, then analog to digital conver-

    sion takes place. The next step is digital down conversion to the base band and

    filtering. The output of the filter is equalized. The soft decisions from the equalizer

    are then deciphered. Thedeciphered data stream is processed by thedecoder. After

    to SIPRO for

    LCLK from SIPRO

    GMSK modulated

    TXBB

    Rx input

    Tx output

    RXFEM

    RXFED

    RXLO

    TXLO

    LTL

    PWSTG MODUP

    PWRDET

    (diversity) downconversionto baseband

    signal from SIPRO

    RF Controlfrom SIPRO

    from SIPRO

  • 8/13/2019 BS240 eng

    37/78

    A30808-X3247-K22-1-7618 37

    InformationBase Station System

    Technical Description (TED:BSS)BS-240/241 II

    decoding (including bad frame indication), the data stream is packed into TRAU

    frames and sent to the TRAU. Signalling data (e.g., FACCH) are processed by layer

    3 of BTS software

    receives the TRAUframes or signalling data. The TRAU frames are unformatted and

    sent to the coder. After encoding, data are ciphered. Now, baseband hopping takes

    place. Training sequence is inserted in the data received via the hopping bus. These

    bursts are sent to the GMSK modulator. This stream is converted into an analog

    baseband signal leaving the SIPRO.

    parallel to the data stream, the PLLs for synthesizer hopping are programmed.

    Therefore, both for uplink and downlink, a data stream to the PLLs is generated.

    Fig. 3.7 Principal data flow on SIPRO

    Power Supply Unit (PSU)

    The PSU is the DCDC converter for the CU for all applications. The PSU generates the

    voltages +26/28V, +6V (only DCS/PCS), +12V, +5.3V and -5.3V for the analog circuitry

    and +3.35V for the digital circuitry from a -48V primary input voltage. The PSU is

    mechanically incorporated in the CU.

    3.3 Edge Carrier Unit

    The ECU unit is a modified CU using the same interfaces as CU but supporting EDGE

    functionality in uplink and downlink. In downlink direction, the signalling and traffic data

    are received from the core network and converted into GMSK or EDGE modulated

    signal, which is amplified to the desired power level.

    With the introduction of EDGE it is possible to mix EDGE and non EDGE timeslots on

    the same carrier.

    The ECU carries two independent receivers (normal and diversity channel) to provide

    the antenna diversity function. In uplink direction, the received signal is converted to

    IF-band. The IF-band is converted to a digital GMSK/8PSK-signal.

    The 8PSK is a linear modulation, where three consecutive bits are mapped to symbol

    as shown in table 3.2.

    Uplink

    Downlink

    A

    D

    A

    D

    Hopping PLL

    Hopping PLLControl

    Central

    diversity 2 2Digital Down-Conversion Equalization Deciphering Decoding

    TRAU FrameFormatting

    Signalling

    TRAU FrameDeformatting

    Signalling

    CodingCipheringGMSK

    Modulation

  • 8/13/2019 BS240 eng

    38/78

    38 A30808-X3247-K22-1-7618

    Technical Description (TED:BSS)BS-240/241 II

    InformationBase Station System

    With the 8PSK modulation, the payload/burst is three times more.

    The mechanical design of ECU is identical to that of CU versions.

    ECU and CU modules may be installed in any kind of mixed configurations concerning

    BS-240/241 hardware (Base/Extension Cabinets). Further, any cell/sector configuration

    with a mixture of EDGE CU and normal CUs can be implemented.

    3.3.1 General

    The EDGE Carrier Unit (ECU) takes care for all carrier oriented tasks of the BTS. In

    uplink (UL) direction, two RF signals (diversity) are received and finally converted into

    TRAU frames and signalling data. In downlink (DL) direction, TRAU frames and signal-

    ling data are received and converted into a GMSK or EDGE modulated RF signal, which

    is amplified to the desired power level.

    An BTS rack can be equipped by any combination of ECU and CU (see fig 3.8)

    Modulating bits Symbol

    (1,1,1) 0

    (0,1,1) 1

    (0,1,0) 2

    (0,0,0) 3

    (0,0,1) 4

    (1,0,1) 5

    (1,0,0) 6

    (1,1,0) 7

    Tab. 3.2

  • 8/13/2019 BS240 eng

    39/78

    A30808-X3247-K22-1-7618 39

    InformationBase Station System

    Technical Description (TED:BSS)BS-240/241 II

    Fig. 3.8 Position of the ECU and CU in the BTS

  • 8/13/2019 BS240 eng

    40/78

    40 A30808-X3247-K22-1-7618

    Technical Description (TED:BSS)BS-240/241 II

    InformationBase Station System

    3.3.2 Mechanics

    Mechanical design of the ECU 1800 is identical to that of CU versions for BTSplus. The

    EPATRX , ESIPRO and PSU Blocks are integrated in one insert-card. In EPATRX Block

    are situated the ERXA, ETXA and EPWRST groups.

    3.3.3 Transmitter Function

    In the downlink direction, the EPATRX receives from ESIPRO a GMSK-or 8PSK modu-

    lated signal in baseband (I and Q modulated), which is upconverted to final transmit

    frequency. Linearization of the transmitter is done by means of an adaptive predistor-

    tion.

    3.3.4 Receiver Function

    The EPATRX carries two independent receivers (normal and diversity channel) to

    provide the antenna diversity function. In uplink direction, the received signal is

    converted via one frequency to IF-band. This IF-band signal is direct A/D converted to

    a digital GMSK/8PSK-signal.

    3.3.5 Local Test Loop

    A local test loop allows a basic functional test of ECU (EPATRX and ESIPRO groups).

    This test is initiated and controlled by ESIPRO group. In contrast to the CU, the LTL test

    of the ECU includes the EPWRSTD.

    3.3.6 Supported frequency range

    PCS-band:

    RX band:(1850 - 1910) MHz

    TX band:(1930 - 1990) MHz

    GSM-band:

    RX band: (824 - 849) MHz

    TX band: (869 - 894) MHz

    3.3.7 Power Supply Unit

    The ECU is supplied by -48 V DC and uses incorporated DC/DC converters.

    3.3.8 Functional description

    The ECU unit is a new developed and enhanced CU unit which supports the GMSK and

    8PSK Modulation in uplink and downlink. It is a HW compatible to the CU unit and fits

    into the BTSplus rack. A functional description of the whole receive and transmit path

    including the EDGE Carrier Unit and the antenna combining equipment can be found in

    [3.3.9].

  • 8/13/2019 BS240 eng

    41/78

    A30808-X3247-K22-1-7618 41

    InformationBase Station System

    Technical Description (TED:BSS)BS-240/241 II

    3.3.9 Functional structure of the EDGE Carrier Unit

    The ECU (Figure 3.9) consists of following functional subunits:

    Power Amplifier and Transceiver Unit (EPATRX)

    Signal Processing Unit (ESIPRO)

    EDGE Power Supply Unit (EPSU)

    Fig. 3.9 Epatrix and Esipro function block diagram.

    3.3.10 Main differences between ECU and CU

    The design approach of this early ECU was to support the EDGE capability by mini-

    mizing the changes to the CU HW. The following major changes to the CU HW weremade to support the EDGE functionality:

    1. New Power Amplifier with better linearity and approximately 3 dB higher peak power

    capability

    2. New power levelling concept including a digital power control loop

    3. New TX-VGA and PWRDET due to new power control

    4. Adaptive predistortion to linearize the transmitter

    5. New module Predistortion receiver (PDRX)

    6. New IQDEM (IF-sampling ADC) with higher dynamic

    7. RXA adaption to new IQDEM

    8. New Power Supply Unit (EPSU) with higher power capability

  • 8/13/2019 BS240 eng

    42/78

    42 A30808-X3247-K22-1-7618

    Technical Description (TED:BSS)BS-240/241 II

    InformationBase Station System

    3.3.11 EDGE Power Amplifier and Tranceiver Unit(EPATRX)

    EPATRX (figure 3.10) provides the main analog functions of the CU. In uplink direction,

    two (diversity) preamplified and filtered RF signals are received from the antenna

    combining equipment. These signals are down converted to IF and channel filtered inthe RXFE stage. The IF signals are then transmitted to ESIPRO, where they are

    sampled and digitally down converted to baseband. In downlink direction, the GMSK or

    8PSK modulated signal is received from the ESIPRO, I/Q modulated and up converted

    by the MODUP stage, which also provides the levelling of the output power.

    The obtained RF signal is then power amplified by the module EPWRST and transmitted

    to the antenna combining equipment. A part of the transmitted power is fed to the

    module PWRDET, which performs the power detection. This signal is used to close the

    digital power loop.

    The Predistortion Receiver (PDRX) down converts the transmit signal to the TX-IF for

    the I/Q-Demodulation and adjusting the predistortion values. The transmitter is linear-

    ized by means of an adaptive digital predistortion which is applied to the basebandsignals. For the introduction of the ECU (BR6.01), a static predistortion was choosen for

    linearization of the transmit path. The HW is able to do adaptive predistortion, which can

    be installed by SW update during BR 7.0. EPATRX is able to support synthesizer

    frequency hopping by the implementation of the synthesizer modules RXLO and TXLO.

    The unit test of the ECU is supported by the module LTL, which provides an RF loop

    between downlink and uplink path.

  • 8/13/2019 BS240 eng

    43/78

    A30808-X3247-K22-1-7618 43

    InformationBase Station System

    Technical Description (TED:BSS)BS-240/241 II

    Fig. 3.10 EPATRIX INTERFACES

    3.3.12 Signal processing unit (ESIPRO)

    The ESIPRO-Board of the BTSPLUS is a part of the Carrier Unit. It contains all digital

    functions of the Carrier Unit:

    Signal Processing in uplink and downlink

    Control of RF on EPATRX

    Baseband and synthesizer frequency hopping

    Channel Control

    Radio Link Control

    O&M parts relevant for carrier unit

    Link to Core via ASIC SELIC

    Digital Modulation

    Predistortion signal processing

    Digital part of Power control

    Additonally, following analog functions are located on ESIPRO:

    Analog to digital conversion (RXIF)

    Digital to analog conversion (TX-baseband, TX-ramping)

    Analog to digital conversion (PDRX)

  • 8/13/2019 BS240 eng

    44/78

    44 A30808-X3247-K22-1-7618

    Technical Description (TED:BSS)BS-240/241 II

    InformationBase Station System

    Analog to digital conversion of Diode voltage

    Analog to digital conversion of temperature

    Local clock of CU

    To understand the functional structure of ESIPRO, knowledge of the principal data flow(see Figure 3.11) on ESIPRO is very useful.

    In uplink direction, an IF-signal with a frequency of more than 100 MHz (GSM -

    151.2MHz, DCS/PCS/GSM850 - 248.6MHz) arrives from ERXA at the ADC (Analog

    Digital Converter). The ADC output is processed by a DDC (Digital Down Converter).

    The DDC transforms the signal into baseband and filters the useful part of the signal.

    The quasi analog signal at the output of the DDC is converted into bits with reliability

    information (soft decisions) in the equalizer block. The soft decisions are deciphered

    and decoded. Traffic channels (e.g., TCH/FS) are sent via TRAU/PCU frames to

    TRAU/PCU. Signalling channels (e.g., SDCCH) are sent to the CORE of the BTS.In

    downlink direction traffic channels arrive as TRAU/PCU frames from TRAU/PCU and

    signaling data come from CORE. The data symbols are coded and ciphered. Afterwardsbase band hopping takes place via the CC link. ESIPRO sends the ciphered data to

    another ECU and receives data to be transmitted. The received data are modulated as

    GMSK or 8 PSK signals and given as a base band signal to ETXA.Both in uplink and

    downlink direction PLLs have to be programmed once each burst to implement synthe-

    sizer hopping.

    Fig. 3.11 Data flow in ESIPRO

  • 8/13/2019 BS240 eng

    45/78

    A30808-X3247-K22-1-7618 45

    InformationBase Station System

    Technical Description (TED:BSS)BS-240/241 II

    3.3.13 EPSU (Power Supply Unit)

    The EPSU is the DC/DC converter for the ECU for all applications. The EPSU generates

    the voltages +26V/+28V, +12V, +5,3V and -5,3V for the analog circuitry and +3.3V for

    the digital circuitry from a -48V primary input voltage. The only interface relevant changewas the change of the analog bias voltage for the EPWRSTD to +12V. The EPSU is

    mechanically incorporated in the ECU.

    The EPSU is a slightly modified version of the PSU of the GSM CU. In this document,

    not all Interface names are changed to EPSU. Therefore, PSU can be seen as a

    synchronym for EPSU in this document.

    3.4 Duplexer Amplifier Multi Coupler (DUAMCO)

    The DUAMCO consists of two identical modules. Every module contains a duplex filter,

    which combines the RX and the TX path together, to be fed to a common antenna. The

    DUAMCO combines 1 (see Fig. 4.2), up to 2 (see Fig. 4.3) or up to 4 (see Fig. 4.4)carriers to one antenna and consists of two branches constituted by:

    a LNA (Low Noise Amplifier) which takes care of a low system noise figure

    an attenuator (in case of installed TMAs, additional gains greather than the cable

    losses must be adjusted by means of the attenuator)

    a second low noise amplifier

    a power splitter which distributes the received band to the CUs (Carrier Units)

    a transmit path which consists of:

    an isolator which protects the PAs (Power Amplifiers) inside the CUs from each

    other in order to assure the required intermodulation suppression

    a hybrid coupler which provides the reference signal for dynamic and static power

    control. The corresponding not transmittedpower is terminated in a load including

    a cooler (for DUAMCO 4:2 and DUAMCO 8:2)

    an ASU (Antenna Supervision Unit) which is responsible for detecting certain

    reflection factors at the antenna connector. The ASU detects the VSWR failure

    and generates a failure information towards the O&M (CAN bus interface). This

    information is subdivided in several levels with the following characteristics:

    - VSWR < 2 neither generation of warning nor of an alarm

    - 2 VSWR 3 generation of warning 'Antenna not Adjusted'

    - VSWR > 3 generation of VSWR alarm 'Antenna Faulty'.

    and a common part constituted by:

    a PDU (Power Distribution Unit) for two TMAs (Tower mounted Amplifier) connected

    to the TMAs by means of an antenna feeder cable

    an O&M interface which transmits error messages to the BTS core via a slow O&M

    bus (CAN bus)

    The DUAMCO amplifier has two different operation modes:

    the AMCO mode where no TMA is used

    in case a TMA is used the DUAMCO is configured in the MUCO mode

    The PDU provides the DC power supply and the alarm supervision of the TMAs. Alarm

    monitoring is done with a signalling interface between DUAMCO and TMA, modulated

    onto a IF carrier at 7.86 MHz.

  • 8/13/2019 BS240 eng

    46/78

    46 A30808-X3247-K22-1-7618

    Technical Description (TED:BSS)BS-240/241 II

    InformationBase Station System

    3.5 DI(=2) Amplifier Multi Coupler (DIAMCO)

    For the uplink direction, the DIAMCO is used to filter and distribute the received signals

    to the Carrier Units in one rack. The DIAMCO consists of two branches constituted by:

    a receive filter a low noise amplifier (LNA) which takes care of a low system noise figure

    an attenuator

    a second low noise amplifier

    a power splitter which distributes the received band to the CUs (Carrier Units)

    and a common part constituted by:

    a PDU (Power Distribution Unit) for two TMAs (Tower mounted Amplifier) connected

    to the TMAs by means of an antenna feeder cable

    an O&M interface which transmits error messages to the BTS core via a slow O&M

    bus (CAN bus)

    The DIAMCO RX amplifier has two different operation modes:

    the AMCO mode where no TMA is used

    in case a TMA is used the DIAMCO is configured in the MUCO mode

    3.6 Filter Combiner (FICOM)

    With the FICOM, it is possible to combine up to 8 frequencies in downlink direction (TX)

    in one rack. For the uplink direction (RX), the DIAMCO has to be used to filter and

    distribute the received signals to the Carrier Units. The FICOM consists of remote

    tunable narrowband filters (TNF). The advantage of this filter combining technique is the

    very low insertion loss, if e.g., 8 transmitters are combined to one antenna.

    In principle, the FICOM offers the following functions:

    RF Functions: RF Power Combining

    Transmitter Spurious Signal Suppression

    Isolation between inputs

    Isolation output to input

    Control / Monitoring Functions:

    Antenna VSWR alarm thresholds setting and status reporting

    Internal Performance Monitoring

    Interfacing with BTSE

    LED Display:

    Antenna VSWR alarms

    Tuning alarms Presence of DC

    Lightning Protection at the RF output connector (7/16)

    3.7 Tower Mounted Amplifier (TMA)

    The TMA connects the antenna with the BTSE in order to amplify the receive signal and

    pass through the transmit signal. The TMA contains two duplex filters, each on one RF

    connector, to separate and combine the receive and transmit path inside of the TMA.

    The TMA consists of the following:

    RX parts of the duplex filter and

    LNA (Low Noise Amplifier) that takes care of a low system noise figure of the RX part

    TX parts of the duplex filter

  • 8/13/2019 BS240 eng

    47/78

    A30808-X3247-K22-1-7618 47

    InformationBase Station System

    Technical Description (TED:BSS)BS-240/241 II

    The DC power for the TMA is feed into the triplexer by the PDU (Power Distribution Unit)

    functionality of the DUAMCO/DIAMCO.

    The Encoder/Decoder units of the TMA signalling interface generate an alarm for each

    TMA separately by supervising the DC current consumption of each unit.Note: When the TMA is used the DUAMCO/DIAMCO works in the so called MUCO

    (multi coupler) mode. In the MUCO mode, the DUAMCO/DIAMCO mainly works as multi

    coupler to split the receive signal for the following CUs.

    3.8 High Power Duplexer Unit (HPDU)

    The High Power Duplexer has the task of combining the TX- and the RX-path into one

    antenna, in order to minimize the number of antennas when FICOM is used. The HPDU

    contains a duplex filter for the transmit frequency band and for the receive frequency

    band, but no Low Noise.

    Amplifier in the RX path.If the TMA shall be used together with a HPDU a so calledBIAS-T (DUBIAS) for powering and signalling of the TMA is required. Up to two HPDU

    can be integrated on top of the rack below the cover and also up to two HPDU could be

    fit in the gap between the inner side wall and the sub-rack in the shelter.

    Note: HPDU is available working in the GSM-PS Primary Shifted band.

    3.9 DC Panel (DCP)

    The DC Panel contains the circuit breakers to protect the DC power lines for the

    modules, the ACTP, FAN units, HEX, LE units. The LMT connector is integrated into the

    front of DC panel located in the Base rack.

    The DC Mains Supply Unit is located at the EMI-Panel of the BS-240/241 II Base rack,Extension rack, and Service 2 rack.

    The DC Mains Supply Unit comprises the lightning protection (optional feature), the

    EMI-filter, and the terminal clamps for external DC supply cable (-48V, 0V).

    The lightning protection element indicates a fault condition at an alarm output (Lightning

    Protection Alarm - LPA). The LPA signal is linked to the Alarm Collection Terminal.

    3.10 DC Link Equipment Panel

    The DC Link Equipment Panel provides the distribution of the 48 V supply voltage to

    the modules within the BS-240/241 II Service 2 Racks and integrates the required DC

    breakers for the different circuits.

    If link equipment is installed into Service 1A and Service 2 cabinets then the associated

    DC:LE-panel can be equipped with breakers. The LE breakers can be plug-in during

    installation of link equipment at the BTSE site.

    At the front of panel, the high-current clamp terminals are located for connecting the DC

    supply lines (-48V, 0V).

    The Alarm Collection Terminal module (ACT-C) is also integrated into the DC:LE-Panel

    assigned to Service 2 cabinet. The ACT-C module is capable for collecting up to 8

    cabinet alarms, and the alarms generated by fan units, battery temperature sensors,

    lightning protection alarm (LPA / OVP), and rack door open sensor.

  • 8/13/2019 BS240 eng

    48/78

    48 A30808-X3247-K22-1-7618

    Technical Description (TED:BSS)BS-240/241 II

    InformationBase Station System

    3.11 Alarm Collection Terminal (ACT)

    The physical function of the ACT is to transfer the alarm and command signals from the

    alarm command connectors of the BTSE subsystem via the CAN BUS to the Core

    Controller.The ACT functionality is realised by a set of modules :

    processor board - ACTP

    interface board for external signals - ACTA

    interface module for internal signals - ACTC

    The interface of operator specify alarms (site inputs and site outputs) is allocated to the

    Base rack. For this purpose, an ACT master module (ACTM) is installed into the Base

    rack. The ACTM module consists of an ACTP board and an ACTA board.

    The tasks of the ACTP are :

    Interface to CAN BUS

    Collection of alarms for units having no access to O&M bus or to the Core Controller;

    Collection of so-called cabinet specific alarms (Door open, FAN0 to FANx, Smoke.. Temperature supervision via an external temperature sensor .

    Rack address adjustment.

    The special tasks of the ACTA are :

    Collection of so-called operator available alarms (24 site inputs and 8 site outputs).

    Indoor lightning protection

    ACTC is installed once in each cabinet to collect all internal alarms. It has inputs for the

    following alarm lines: rack door alarm, fan alarms, temperature alarms and internal

    cabinet alarms, which can be defined by the operator. In the Base rack, the ACTC is

    directly connected to the COBA.

    For input of rack alarms, a 24-Pin WAGO terminal clamp is used on the ACTC-3. The

    ACTC-3 board provides 4-pin connectors for DC output (-48 V) / alarm interface and2-pin connectors for alarm interface only.

    Fan units

    Smoke sensor

    Location Measurement Unit (LMU)

    Rack Door Open sensor

    Temperature sensor

    Lightning Protection Alarm (LPA, also called Over Voltage Protection - OVP)

    Types of Alarm Collection Terminal Modules:

    ACTMV2 Alarm Collection Terminal (ACT) Master

    M:ACTPV3 ACT Processor Module

    M:ACTC-3Vx ACT Collector Version

    Different ACT, are available depending on the applications in the Base Rack/Shelter

    (ACTM) or in the Service and Extension Rack/Shelter (ACTP) as shown in Fig. 3.12.

  • 8/13/2019 BS240 eng

    49/78

    A30808-X3247-K22-1-7618 49

    InformationBase Station System

    Technical Description (TED:BSS)BS-240/241 II

    Fig. 3.12 Alarm collection terminal (ACTM and ACTP)

    3.12 AC/DC converter (ACDC)

    Up to 6 AC/DC converters (only one Frame) can be equipped in the service1 rack which

    provide N+1 redundancy. AC/DC converters work in load sharing, but n AC/DC are ableto supply the whole BS-240/241 II .

    Each AC/DC rectifier has an integrated fan to force airflow through the module for

    cooling purposes.

    A local AC/DC supervision and management system has been implemented which is

    accessible via RS232 interface and external PC.

    The AC/DC system alarms are collected at the ACTC and through-wired to the ACTP