DESCRIPTION
BS_EC - Building Services_Easy Cable – is a easiest way to select the cable with the required inputs of current rating and length – created by me during 2007TRANSCRIPT
InstructionsYou may move from worksheet to worksheet by clicking on the dark blue buttons located at the top of each worksheet or the blue tabs at the bottom of this workbook.The datas inside the black border line is protected for the safety of program.
Enter data in only the white cells with borders: Use the drop down boxes to select the standard cable sizes(10,16,…..)
Create a quick and easy selection of cable by filling out the white cells on the "Quick Cals" sheet. Enter the "Amps rating,length of cable"in the white cell.Select the "Standard Cable Size"by using the drop down menu provided in the cell. The Total Voltage drop & Percentage of Votage Drop (Vd) are calculated for you.
Use the "Specs" sheet to get more details like Standard sizes & Amps ratings,Various factors considering,Voltage Drop Chart, Group / Correction factors,Cable Data,Format by clicking on the dark blue buttons on the top of each worksheet or the blue tabs at the bottom of this work book.
Use this sheet we can refer the amps ratings & Voltage drops in various installtion methods of single core,two core ,three core & four core XLPE insulated cables.
Use this sheet we can refer the Dimensions & Weights including overall Diameter,Armour size,Approximate Weight of single core,two core ,three core & four core XLPE insulated cables.
Use this sheet we can refer the amps ratings & Voltage drops in various installtion methods of single core,two core ,three core & four core PVC insulated cables.
Use this sheet we can refer the Dimensions & Weights including overall Diameter,Armour size,Approximate Weight of single core,two core ,three core & four core PVC insulated cables.
Use this sheet to get the cable ratings of stranded Four Core Cables at various installation methods including Ambient Temperature,Laying,Resistivity,Max.Operating Conductor Temperature,Group factor & the Derating factor with respect to Grouping and without Grouping.White colour back arrow in the dark blue button located at the top end will helps you to get back into the Spec Sheet.
Use this sheet to see the chart of Approximate Voltage drop of 4C XLPE & PVC Cables.White colour back arrow in the dark blue button located at the top end will helps you to get back into the Spec Sheet.
Quick Cals
Specs
XLPE
XLPE_Dim/Wgt
PVC
PVC_Dim/Wgt
Standard
Voltage Drop Chart
Group/Correction Factor
Questions?Suggestions to improve this
programEmail at
Questions?Suggestions to improve this
programEmail at
Easy Cables - Overview / Help
81
Quick calsQuick cals
Use this sheet to see the correction factor for groups with respect to the number of cables for single core & multi core.White colour back arrow in the dark blue button located at the top end will helps you to get back into the Spec Sheet.
Use this sheet you can get the formulae applied in this program,max.voltage drop,factors & the required datas for easy calculations& selection of cable by exact voltage drops...White colour back arrow in the dark blue button located at the top end will helps you to get back into the Spec Sheet.
Use this sheet you can see one reference simplest format for making cable schedule.White colour back arrow in the dark blue button located at the top end will helps you to get back into the Spec Sheet.
Cable Data
Format
Create a quick and easy selection of cable by filling out the white cells on the "Quick Cals" sheet. Enter the "Amps rating,length of cable"in the white cell.Select the "Standard Cable Size"by using the drop down menu provided in the cell. The Total Voltage drop & Percentage of
Use the "Specs" sheet to get more details like Standard sizes & Amps ratings,Various factors considering,Voltage Drop Chart, Group / Correction factors,Cable Data,Format by clicking on the dark blue buttons on the top of each worksheet or the blue tabs at
Use this sheet we can refer the amps ratings & Voltage drops in various installtion methods of single core,two core ,three core
Use this sheet we can refer the Dimensions & Weights including overall Diameter,Armour size,Approximate Weight of single core,
Use this sheet we can refer the amps ratings & Voltage drops in various installtion methods of single core,two core ,three core
Use this sheet we can refer the Dimensions & Weights including overall Diameter,Armour size,Approximate Weight of single core,
Use this sheet to get the cable ratings of stranded Four Core Cables at various installation methods including Ambient Temperature,Laying,Resistivity,Max.Operating Conductor Temperature,Group factor & the Derating factor with respect to Grouping and without Grouping.White colour back arrow in the dark blue button located at the top end will helps you to get back into the Spec Sheet.
White colour back arrow in the dark blue button located at the top end will helps you to get back into the Spec Sheet.
Questions?Suggestions to improve this
programEmail at
Questions?Suggestions to improve this
programEmail at
Easy Cables - Overview / Help
Quick calsQuick cals
Specs Specs
Use this sheet to see the correction factor for groups with respect to the number of cables for single core & multi core.White colour back arrow in the dark blue button located at the top end will helps you to get back into the Spec Sheet.
Use this sheet you can get the formulae applied in this program,max.voltage drop,factors & the required datas for easy calculations
White colour back arrow in the dark blue button located at the top end will helps you to get back into the Spec Sheet.
White colour back arrow in the dark blue button located at the top end will helps you to get back into the Spec Sheet.
By V.Pradeesh on 07.10.07
Quick Cals.Quick Cals.
Standard
Standard
Vd Chart
Vd Chart
Cable Data Cable Data
Group GroupForma
tForma
t
Overview
/Help
Overview
/Help
Non-Grouped GroupedNominal Ratings (A) Derated Ratings (A) Derated Ratings (A)
Fo
ur
Co
re
16 99 94 115
Fo
ur
Co
re
16 81 68 75
Fo
ur
Co
re
16 81 6425 131 125 150 25 107 91 97 25 107 8435 162 150 180 35 133 109 117 35 133 10150 197 175 215 50 162 127 139 50 162 11870 251 215 265 70 206 156 172 70 206 14595 304 260 315 95 249 189 204 95 249 17612 353 300 360 12 289 218 233 12 289 203
150 406 335 405 150 333 243 262 150 333 226185 463 380 460 185 380 276 298 185 380 257240 546 440 530 240 448 320 343 240 448 297300 628 495 590 300 515 360 382 300 515 334400 728 570 667 400 597 414 432 400 597 385500 800 605 720 500 656 440 466 500 656 409
DIRECT IN GROUND - CABLES TOUCHING DIRECT IN GROUND - CABLES TOUCHING
SINGLE WAY DUCTS - DUCTS TOUCHING SINGLE WAY DUCTS - DUCTS TOUCHING Air DuctAMBIENT AIR TEMP = 30 deg.C AMBIENT AIR TEMP = 50 deg.C f = 0.82 1GROUND TEMP = 15 deg.C GROUND TEMP = 35 deg.C f = 1 0.86DEPTH OF LAYING = 0.5m DEPTH OF LAYING = 1.5m f = 1 0.96SOIL.TERM. RESISTIVITY = 1.2 SOIL.TERM. RESISTIVITY = 2 f = 1 0.88MAX. OPERATING CONDUCTOR TEMP = 90 MAX. OPERATING CONDUCTOR TEMP = 90 f = 1 1
GROUP FACTOR FOR 2 CABLES 0.3m SPACE f = 1 0.93
F = 0.65 0.73F = 0.59 0.68
Nominal Area of conductor in Sq.mm
Installed in Air
Installed in Duct
Installed in Ground
Nominal Area of conductor in Sq.mm
Installed in Air
Installed in Duct
Installed in Ground
Nominal Area of conductor in Sq.mm
Installed in Air
Installed in Duct
Quick Cals.Quick Cals.
Vd Chart
Vd Chart
Group GroupForma
tForma
tCable DataCable Data
Cable ratings of Standard Copper Four Core Cables Cu/XLPE/SWA/PVC(For Installation)
Overview
/Help
Overview
/Help
GroupedDerated Ratings (A)
6888
106127156186212239271312348393424
Ground1
0.860.930.81
10.91
0.820.82
Installed in Ground
Cable ratings of Standard Copper Four Core Cables Cu/XLPE/SWA/PVC(For Installation)
Current Rating (amps)
in Air in Duct in Ground in Air Ground in Ducts
Sin
gle
Co
re i
n T
refo
il
50 181 199 203 0.82 0.88
Th
ree
Co
re
1670 228 241 248 0.58 0.66 2595 280 282 297 0.44 0.53 35
120 326 311 337 0.36 0.47 50150 371 342 376 0.31 0.42 70185 425 375 423 0.27 0.38 95240 500 419 485 0.23 0.34 120300 571 459 542 0.2 0.32 150400 649 489 600 0.19 0.3 185500 729 523 660 0.18 0.28 240630 817 563 721 0.16 0.26 300800 886 587 756 0.16 0.25
1000 945 621 797 0.16 0.23 * 1900/3300 V PVC Insulated cables
Tw
o C
ore
1.5 22 26 32 292.5 31 34 41 184 41 45 55 116 53 57 69 7.3
10 72 76 92 4.416 96 98 119 2.825 128 129 158 1.735 156 154 190 1.350 189 183 225 0.9470 237 225 277 0.66
Th
ree
& F
ou
r C
ore
1.5 19 22 27 252.5 26 29 35 154 35 38 47 9.56 45 48 59 6.4
10 62 64 78 4.016 82 83 101 2.425 109 107 132 1.535 133 129 159 1.150 162 153 188 0.8270 205 190 233 0.5795 252 228 279 0.4212 291 260 317 0.35
150 334 292 355 0.29185 383 331 401 0.25240 451 382 462 0.21300 514 428 517 0.18
* 600/1000 V PVC Insulated cables to BS 6346
Approx.millivolt drop per amp per metre(mV)
Nominal Area of conductor in Sq.mm
Nominal Area of conductor in Sq.mm
Amps & Voltage Drops of PVC Insulated cables Amps of PVC Insulated cables
Current Rating (amps)
in Air in Duct in Ground85 82 97
111 105 125134 126 151163 150 178204 184 219250 221 264290 252 299330 282 336379 319 379446 368 436508 412 488
* 1900/3300 V PVC Insulated cables
Amps of PVC Insulated cables
Current Rating (amps)
in Air in Duct in Ground in Air Ground in Ducts
Sin
gle
Co
re i
n T
refo
il
50 222 235 235 0.87 0.93
Th
ree
Co
re
70 285 280 290 0.62 0.795 346 330 345 0.47 0.56
120 402 370 390 0.39 0.48150 463 405 435 0.33 0.43185 529 440 490 0.28 0.39240 625 500 560 0.24 0.35300 720 550 630 0.21 0.32400 815 580 700 0.20 0.30500 918 620 770 0.18 0.28630 1027 670 840 0.17 0.26800 1119 692 888 0.165 0.25
1000 1214 735 942 0.155 0.24
Tw
o C
ore
1.5 29 31 38 312.5 39 41 49 194 52 53 65 126 66 67 81 7.9
10 90 89 109 4.716 115 115 140 2.925 152 145 180 1.935 188 175 215 1.350 228 210 255 170 291 260 315 0.69
Th
ree
& F
ou
r C
ore
1.5 25 26 32 272.5 33 34 42 164 44 45 55 106 56 56 69 6.8
10 78 75 92 4.016 99 94 115 2.525 131 125 150 1.6535 162 150 180 1.1550 197 175 215 0.8770 251 215 265 0.695 304 260 315 0.4512 353 300 360 0.37
150 406 335 405 0.3185 463 380 465 0.26240 546 440 530 0.21300 628 495 590 0.19
* 600/1000 V XLPE Insulated cables to BS 5467/IEC 502
Approx.millivolt drop per amp per metre(mV)
Nominal Area of conductor in Sq.mm
Amps & Voltage Drops of XLPE Insulated Cables Amps of XLPE Cables
Current Rating (amps)
in Air in Duct in Ground16 106 96 11425 142 124 14735 168 147 17550 202 174 20770 255 214 25495 312 257 304
120 361 293 345150 410 328 387185 471 371 436240 554 428 502300 634 480 563
* 1900/3300 V PVC Insulated cables
Nominal Area of conductor in Sq.mm
Amps of XLPE Cables
Approximate Diameter
Approx. Weight kg/km
Sin
gle
Co
re
50 13.8 1.6 20.8 1340
Th
ree
Co
re
1670 15.4 1.6 22.5 1650 2595 17.8 1.6 25 2120 35
120 19.2 1.6 27 2500 50150 21.2 1.6 29 2960 70185 23.6 1.6 31.5 3600 95240 26.7 1.6 35 4900 120300 29.4 1.6 37.5 5300 150400 33 2 43 6700 185500 38.3 2 48 8470 240630 42.2 2 52 10260 300800 47.3 2.5 59 12900
1000 53 2.5 64.8 15700 * 1900/3300 V PVC Insulated cables * Tolerance on the above dimensions are -0.3mm & +0.5mm
Tw
o C
ore
1.5 8 0.9 13.5 600 * Cable sizes marked + higher have sector shaped conductors2.5 9.5 0.9 15.2 7504 11.2 0.9 16.8 9006 12.2 0.9 18 1020
10 15.2 1.25 22 147016 16.4 1.25 23 167025 20 1.6 28 242035 22.2 1.6 30.2 290050 20.8 1.6 29.5 300070 23.5 1.6 31.8 360095 27 2 37 5620
Th
ree
Co
re
1.5 8.6 0.9 14 6652.5 10.4 0.9 16 8204 11.8 0.9 17 9606 13.4 0.9 19.5 1260
10 15.8 1.25 22.8 1660.016 17.5 1.25 24.2 197025 21.6 1.6 29.8 290035 24 1.6 32 348050 25.5 1.6 33.8 396070 27.5 2 37.2 512095 32.5 2 42.5 668012 35 2 45 7700
150 39.1 2.5 51 9500185 44 2.5 56 11600240 49 2.5 61 14200300 54.5 2.5 68 17340
Fo
ur
Co
re
1.5 10 0.9 15.5 8002.5 11.1 0.9 16.8 9254 13 1.25 19.5 12256 14.5 1.25 21 1430
10 18 1.25 24.5 197016 20 1.6 28 240025 21.8 1.6 30 314035 24.5 1.6 32.5 3760
Nominal Area of conductor in Sq.mm
Over Lead mm
Armour Wire mm
Overall Cable mm
Nominal Area of conductor in Sq.mm
Quick Cals.Quick Cals.
Specs.
Specs.
XLPE XLPEMethodologyMethodology
PVC PVCOvervi
ew/Help
Overview
/Help
Dimensions & Weights of PVC Insulated Cables
Fo
ur
Co
re
50 28.5 2 38 500070 32 2 42 640095 37.5 2 47.5 810012 40.8 2.5 52.5 10100
150 45.2 2.5 57 11900185 50 2.5 62.5 14350240 55.8 2.5 68.5 17900
* 600/1000 V PVC Insulated cables to BS 6346* Tolerance on the above dimensions are -1.5mm & +0.5mm* Cable sizes marked + higher have sector shaped conductors
Approximate Diameter
23.6 1.6 31.8 294026 1.6 34.4 3560
28.5 1.6 37 423027.2 2 37 475032 2 42 586036 2 46.2 7200
38.2 2.5 50 880042 2.5 53.8 10200
44.6 2.5 57 1170050.2 2.5 63 1440054.8 2.5 67.8 17300
* 1900/3300 V PVC Insulated cables * Tolerance on the above dimensions are -0.3mm & +0.5mm* Cable sizes marked + higher have sector shaped conductors
Over Lead mm
Armour Wire mm
Overall Cable mm
Approx. Weight kg/km
Dimensions & Weights of PVC Insulated Cables
Approximate Diameter
Sin
gle
Co
re
50 13 1.6 20.8 1300
Th
ree
Co
re
70 15 1.6 22.6 162095 16.8 1.6 24.5 2040
120 18.5 1.6 26.2 2380150 20.5 1.6 28.5 2840185 22.8 1.6 30.8 3365240 25.5 1.6 33.5 4180300 28.1 1.6 36.4 5060400 32.3 2 41.8 6400500 37 2 46.6 8000630 40.8 2 50.8 9720800 47.5 2.5 59.2 12700
1000 52.5 2.5 64.2 15400
Tw
o C
ore
1.5 8.6 0.9 14 6402.5 9.5 0.9 15 7304 10.8 0.9 16.5 8406 11.6 0.9 17.5 960
10 13.7 0.9 19.8 118016 15.5 1.25 21.8 154025 18.9 1.25 25.5 206035 21.3 1.6 29.4 267050 19 1.6 27.2 264070 22.2 1.6 30.5 340095 24.8 2 34.5 4530
Th
ree
Co
re
1.5 9.2 0.9 14.5 7002.5 10.4 0.9 16 8154 11.4 0.9 17 9206 13 0.9 18.5 1080
10 14.8 1.25 21.5 150016 16.5 1.25 23 175025 20.5 1.6 28.6 265035 23 1.6 31.2 322050 24 1.6 32 363070 26.5 1.6 35 456095 30.5 2 40.5 611012 33.5 2 43.5 7300
150 37.8 2.5 49.4 8980185 42.8 2.5 54.5 10870240 48.2 2.5 60.2 13500300 52.2 2.5 65.2 16150
Nominal Area of conductor in Sq.mm
Over Lead mm
Armour Wire mm
Overall Cable mm
Approx. Weight kg/km
Quick Cals.Quick Cals.
Specs.
Specs.
XLPE XLPEMethodologyMethodology
PVC PVCOvervi
ew/Help
Overview
/Help
Dimensions & Weights of XLPE Insulated Cables
Fo
ur
Co
re1.5 10.1 0.9 15.6 7652.5 11.1 0.9 16.8 8704 12.8 0.9 18.5 10306 13.8 1.25 20.3 1330
10 16.5 1.25 22.8 167016 18.8 1.25 25.5 212025 20.5 1.6 28.5 280035 23.2 1.6 31.3 343050 26.2 1.6 34.6 426070 30.5 2 40.5 585095 34.8 2 44.8 734012 37.8 2.5 49.8 9400
150 43.2 2.5 55 11280185 47.8 2.5 60 13600240 53.8 2.5 66.5 17000
* 600/1000 V XLPE Insulated cables to BS 6346
Approximate Diameter
Approx. Weight kg/km16 22.5 1.6 31 275025 25 1.6 33.5 330035 27.5 1.6 36 396050 26 2 36 436070 31 2 41 550095 35.2 2 45.5 6900
120 37 2.5 49 8450150 41.2 2.5 53.2 9800185 44 2.5 56 11350240 49.4 2.5 62.2 14000300 53 2.5 66 16350
* 1900/3300 V PVC Insulated cables * Tolerance on the above dimensions are -0.3mm & +0.5mm* Cable sizes marked + higher have sector shaped conductors
Nominal Area of conductor in Sq.mm
Over Lead mm
Armour Wire mm
Overall Cable mm
Dimensions & Weights of XLPE Insulated Cables
Conductor Size in Sq.mm VD/MTR/A (mV)1.5 272.5 164 106 6.8
10 416 2.525 1.6535 1.1550 0.8770 0.695 0.45
120 0.37150 0.3185 0.26240 0.21300 0.185400 0.165
Voltage drop factor (Vd) for 4C XLPE Cables
Quick Cals.Quick Cals.
Standard
Standard
Group GroupForma
tForma
tCable DataCable Data
Conductor Size in Sq.mm VD/MTR/A (mV)1.5 252.5 154 9.56 6.4
10 416 2.425 1.535 1.150 0.8270 0.5795 0.42
120 0.35150 0.29185 0.25240 0.21300 0.18400 0.16
Voltage Drop factor (Vd) for 4C PVC Cables
Format
Format
Overview
/Help
Overview
/Help
Correction Factors for groups
Sin
gle
co
re
No.of Cables 4 6 8 10 12 16 20 24 28 32 36Correction factor 0.80 0.69 0.62 0.59 0.55 0.51 0.48 0.43 0.41 0.39 0.38
Mu
lti
co
re
No.of Cables 2 3 4 5 6 8 10 12 14 16 18Correction factor 0.80 0.70 0.65 0.60 0.57 0.52 0.48 0.45 0.43 0.41 0.39
Correction Factor for groups
Quick Cals.Quick Cals.
Vd Chart
Vd Chart
Standard
Standard
Format
Format
Cable DataCable Data
Overview
/Help
Overview
/Help
Ambiant Condition FactorCable Location Temp XLPE PVCBuilding Internal 40º C 0.94 0.91Plant/Machine Rooms 55º C 0.82 0.7
XLPE/CU/4CCurrent Carry.Capacity 33 43 59 80 106 128 155 197 242 280 325Conductor Area in mm2 4 6 10 16 25 35 50 70 95 120 150
Voltage drop for milliamps per meter Conductor Area in mm2 10 16 25 35 50 70 95 120 150 185 240Vm 4 2.5 1.65 1.15 0.87 0.6 0.45 0.37 0.3 0.26 0.21
Grouping ConditionNo of Cables 2 3 4 5 6 8 10 12 14 16 18Correction Factor 0.8 0.7 0.65 0.6 0.57 0.52 0.48 0.45 0.43 0.41 0.39
Cable Tray WidthCable Space factor for 3 Phase 20 % space must be free in the trayCable have to be in single layer in the tray.
Voltage DropFind the breaker Current(More than full load current)Find the length of the cable Fix the maximum voltage drop (6V)From the table apply Vm (V/mA/M)
Voltage Drop of the cabl (VD) Vm*I*L/1000
Cable Data
Quick Cals.Quick Cals.
Vd Chart
Vd Chart
Group GroupForma
tForma
tStand
ardStand
ard
Overview
/Help
Overview
/Help
Cable Schedule
S.No. Type From To Laid onRct 04 Sky Villas
1 XT 4CxXLPE SMP01/SVL-RCT4/05 SMDB01/SVLRCT04/04 95 Cable Tray 812 SMDB02/SVLRCT04/04 100 Cable Tray 813 SMDB03/SVLRCT04/04 115 Cable Tray 814 SMDB01/SVLRCT04/06 40 Cable Tray 815 SMDB02/SVLRCT04/06 65 Cable Tray 816 SMDB03/SVLRCT04/06 20 Cable Tray 817 SMDB04/SVLRCT04/06 65 Cable Tray 818 SMDB05/SVLRCT04/06 45 Cable Tray 819 SMDB06/SVLRCT04/06 85 Cable Tray 81
1 4CxXLPE SMP01/SVL-RCT4/07 SMDB01/SVLRCT04/08 20 Cable Tray 812 SMDB02/SVLRCT04/08 40 Cable Tray 813 SMDB03/SVLRCT04/08 30 Cable Tray 814 SMDB04/SVLRCT04/08 50 Cable Tray 815 SMDB05/SVLRCT04/08 55 Cable Tray 816 SMDB06/SVLRCT04/08 75 Cable Tray 81
Rct 04 Mid Rise Apartments1 XT 4CxXLPE SMDB01/MRRCT04/08 DB/MR/08 20 Cable Tray 19.1512 DB/MR/08 20 Cable Tray 19.1513 DB/MR/08 40 Cable Tray 19.1514 DB/MR/09 25 Cable Tray 19.1515 DB/MR/09 25 Cable Tray 19.1516 DB/MR/09 45 Cable Tray 19.1517 DB/MR/10 30 Cable Tray 19.1518 DB/MR/10 30 Cable Tray 19.1519 DB/MR/10 50 Cable Tray 19.151
10 DB/MR/11 32 Cable Tray 19.15111 DB/MR/11 32 Cable Tray 19.15112 DB/MR/11 52 Cable Tray 19.151
Rct 04 Low Rise Apartments1 XT 4CxXLPE SMDB01/LRRCT04/04 DB/LR/04 90 Cable Tray 15.4082 DB/LR/04 80 Cable Tray 15.4083 DB/LR/04 65 Cable Tray 15.4084 DB/LR/04 50 Cable Tray 15.4085 DB/LR/04 35 Cable Tray 15.4086 DB/LR/04 28 Cable Tray 15.4087 DB/LR/04 22 Cable Tray 15.4088 DB/LR/04 15 Cable Tray 15.4089 DB/LR/05 94 Cable Tray 15.408
10 DB/LR/05 75 Cable Tray 15.40811 DB/LR/05 40 Cable Tray 15.40812 DB/LR/05 30 Cable Tray 15.408
Cable Ref.
Length (M)
Connected Load(A)
Quick Cals.Quick Cals.
Specs.
Specs.
XLPE XLPEMethodologyMethodology
PVC PVCOvervi
ew/Help
Overview
/Help
13 DB/LR/05 20 Cable Tray 15.408
1 XT 4CxXLPE SMDB02/LRRCT04/04 DB/LR/04 60 Cable Tray 15.4082 DB/LR/04 50 Cable Tray 15.4083 DB/LR/04 40 Cable Tray 15.4084 DB/LR/04 30 Cable Tray 15.4085 DB/LR/04 20 Cable Tray 15.4086 DB/LR/05 65 Cable Tray 15.4087 DB/LR/05 55 Cable Tray 15.4088 DB/LR/05 45 Cable Tray 15.4089 DB/LR/05 35 Cable Tray 15.408
10 DB/LR/05 25 Cable Tray 15.408
Rct 03 Sky Villas1 XT 4CxXLPE SMP01/SVL-RCT03/05 SMDB01/SVLRCT03/04 95 Cable Tray 812 SMDB02/SVLRCT03/04 100 Cable Tray 813 SMDB03/SVLRCT03/04 115 Cable Tray 814 SMDB01/SVLRCT03/06 40 Cable Tray 815 SMDB02/SVLRCT03/06 65 Cable Tray 816 SMDB03/SVLRCT03/06 20 Cable Tray 817 SMDB04/SVLRCT03/06 65 Cable Tray 818 SMDB05/SVLRCT03/06 45 Cable Tray 819 SMDB06/SVLRCT03/06 85 Cable Tray 81
10 SMDB04/SVLRCT03/06 65 Cable Tray 81
1 4CxXLPE SMP01/SVL-RCT03/07 SMDB01/SVLRCT03/08 20 Cable Tray 812 SMDB02/SVLRCT03/08 40 Cable Tray 813 SMDB03/SVLRCT03/08 40 Cable Tray 814 SMDB04/SVLRCT03/08 40 Cable Tray 815 SMDB05/SVLRCT03/08 55 Cable Tray 816 SMDB06/SVLRCT03/08 60 Cable Tray 817 SMDB04/SVLRCT03/09 60 Cable Tray 818 SMDB05/SVLRCT03/09 75 Cable Tray 81
Rct 03 Low Rise Apartments1 XT 4CxXLPE SMDB01/LRRCT03/04 DB/LR/04 90 Cable Tray 15.4082 DB/LR/04 70 Cable Tray 15.4083 DB/LR/04 35 Cable Tray 15.4084 DB/LR/04 25 Cable Tray 15.4085 DB/LR/04 15 Cable Tray 15.4086 DB/LR/05 94 Cable Tray 15.4087 DB/LR/05 75 Cable Tray 15.4088 DB/LR/05 40 Cable Tray 15.4089 DB/LR/05 30 Cable Tray 15.408
10 DB/LR/05 20 Cable Tray 15.408
1 XT 4CxXLPE SMDB02/LRRCT03/04 DB/LR/04 60 Cable Tray 15.4082 DB/LR/04 50 Cable Tray 15.4083 DB/LR/04 40 Cable Tray 15.4084 DB/LR/04 30 Cable Tray 15.4085 DB/LR/04 20 Cable Tray 15.4086 DB/LR/05 65 Cable Tray 15.4087 DB/LR/05 55 Cable Tray 15.4088 DB/LR/05 45 Cable Tray 15.408
9 DB/LR/05 35 Cable Tray 15.40810 DB/LR/05 25 Cable Tray 15.408
Rct 02 Low Rise Apartments1 XT 4CxXLPE SMDB01/LRRCT02/05 DB/LR/05 10 Cable Tray 18.722 DB/LR/05 15 Cable Tray 18.723 DB/LR/05 15 Cable Tray 18.724 DB/LR/05 20 Cable Tray 18.725 DB/LR/05 35 Cable Tray 18.726 DB/LR/06 15 Cable Tray 18.727 DB/LR/06 20 Cable Tray 18.728 DB/LR/06 20 Cable Tray 18.729 DB/LR/06 25 Cable Tray 18.72
10 DB/LR/06 40 Cable Tray 18.72
1 XT 4CxXLPE SMDB01/LRRCT02/01 DB/LR/04 20 Cable Tray 18.722 DB/LR/04 20 Cable Tray 18.723 DB/LR/04 40 Cable Tray 18.724 DB/LR/05 25 Cable Tray 18.725 DB/LR/05 25 Cable Tray 18.726 DB/LR/05 45 Cable Tray 18.727 DB/LR/06 30 Cable Tray 18.728 DB/LR/06 30 Cable Tray 18.729 DB/LR/06 50 Cable Tray 18.72
10 DB/LR/07 33 Cable Tray 18.7211 DB/LR/07 33 Cable Tray 18.7212 DB/LR/07 53 Cable Tray 18.7213 DB/LR/08 36 Cable Tray 18.7214 DB/LR/08 36 Cable Tray 18.7215 DB/LR/08 56 Cable Tray 18.72
1 XT 4CxXLPE SMDB01/LRRCT02/02 DB/LR/04 20 Cable Tray 18.722 DB/LR/04 20 Cable Tray 18.723 DB/LR/04 40 Cable Tray 18.724 DB/LR/05 25 Cable Tray 18.725 DB/LR/05 25 Cable Tray 18.726 DB/LR/05 45 Cable Tray 18.727 DB/LR/06 30 Cable Tray 18.728 DB/LR/06 30 Cable Tray 18.729 DB/LR/06 50 Cable Tray 18.72
10 DB/LR/07 33 Cable Tray 18.7211 DB/LR/07 33 Cable Tray 18.7212 DB/LR/07 53 Cable Tray 18.7213 DB/LR/08 36 Cable Tray 18.7214 DB/LR/08 36 Cable Tray 18.7215 DB/LR/08 56 Cable Tray 18.72
1 XT 4CxXLPE SMDB01/LRRCT02/03 DB/LR/04 20 Cable Tray 18.722 DB/LR/04 20 Cable Tray 18.723 DB/LR/04 40 Cable Tray 18.724 DB/LR/05 25 Cable Tray 18.725 DB/LR/05 25 Cable Tray 18.726 DB/LR/05 45 Cable Tray 18.727 DB/LR/06 30 Cable Tray 18.72
8 DB/LR/06 30 Cable Tray 18.729 DB/LR/06 50 Cable Tray 18.72
10 DB/LR/07 33 Cable Tray 18.7211 DB/LR/07 33 Cable Tray 18.7212 DB/LR/07 53 Cable Tray 18.7213 DB/LR/08 36 Cable Tray 18.7214 DB/LR/08 36 Cable Tray 18.7215 DB/LR/08 56 Cable Tray 18.72
Rct 01 Low Rise Apartments1 XT 4CxXLPE SMDB01/LRRCT02/05 DB/LR/05 10 Cable Tray 18.722 DB/LR/05 15 Cable Tray 18.723 DB/LR/05 15 Cable Tray 18.724 DB/LR/05 20 Cable Tray 18.725 DB/LR/05 35 Cable Tray 18.726 DB/LR/06 15 Cable Tray 18.727 DB/LR/06 20 Cable Tray 18.728 DB/LR/06 20 Cable Tray 18.729 DB/LR/06 25 Cable Tray 18.72
10 DB/LR/06 40 Cable Tray 18.72
1 XT 4CxXLPE SMDB01/LRRCT02/01 DB/LR/04 20 Cable Tray 18.722 DB/LR/04 20 Cable Tray 18.723 DB/LR/04 40 Cable Tray 18.724 DB/LR/05 25 Cable Tray 18.725 DB/LR/05 25 Cable Tray 18.726 DB/LR/05 45 Cable Tray 18.727 DB/LR/06 30 Cable Tray 18.728 DB/LR/06 30 Cable Tray 18.729 DB/LR/06 50 Cable Tray 18.72
10 DB/LR/07 33 Cable Tray 18.7211 DB/LR/07 33 Cable Tray 18.7212 DB/LR/07 53 Cable Tray 18.7213 DB/LR/08 36 Cable Tray 18.7214 DB/LR/08 36 Cable Tray 18.7215 DB/LR/08 56 Cable Tray 18.72
1 XT 4CxXLPE SMDB01/LRRCT02/02 DB/LR/04 20 Cable Tray 18.722 DB/LR/04 20 Cable Tray 18.723 DB/LR/04 40 Cable Tray 18.724 DB/LR/05 25 Cable Tray 18.725 DB/LR/05 25 Cable Tray 18.726 DB/LR/05 45 Cable Tray 18.727 DB/LR/06 30 Cable Tray 18.728 DB/LR/06 30 Cable Tray 18.729 DB/LR/06 50 Cable Tray 18.72
10 DB/LR/07 33 Cable Tray 18.7211 DB/LR/07 33 Cable Tray 18.7212 DB/LR/07 53 Cable Tray 18.7213 DB/LR/08 36 Cable Tray 18.7214 DB/LR/08 36 Cable Tray 18.7215 DB/LR/08 56 Cable Tray 18.72
1 XT 4CxXLPE SMDB01/LRRCT02/03 DB/LR/04 20 Cable Tray 18.72
2 DB/LR/04 20 Cable Tray 18.723 DB/LR/04 40 Cable Tray 18.724 DB/LR/05 25 Cable Tray 18.725 DB/LR/05 25 Cable Tray 18.726 DB/LR/05 45 Cable Tray 18.727 DB/LR/06 30 Cable Tray 18.728 DB/LR/06 30 Cable Tray 18.729 DB/LR/06 50 Cable Tray 18.72
10 DB/LR/07 33 Cable Tray 18.7211 DB/LR/07 33 Cable Tray 18.7212 DB/LR/07 53 Cable Tray 18.7213 DB/LR/08 36 Cable Tray 18.7214 DB/LR/08 36 Cable Tray 18.7215 DB/LR/08 56 Cable Tray 18.72
Cable Schedule Derating Factor
100 40 0.7 1.28 6 70 123.10030395137 1.154100 40 0.7 1.35 6 70 123.10030395137 1.215100 40 0.7 1.55 6 70 123.10030395137 1.397100 40 0.65 0.54 6 35 132.56955810147 0.931100 40 0.65 0.88 6 50 132.56955810147 1.145100 40 0.65 0.27 6 35 132.56955810147 0.466100 40 0.65 0.88 6 50 132.56955810147 1.145100 40 0.65 0.61 6 35 132.56955810147 1.048100 40 0.65 1.15 6 50 132.56955810147 1.497
100 40 0.7 0.27 6 35 123.10030395137 0.466100 40 0.7 0.54 6 35 123.10030395137 0.931100 40 0.7 0.41 6 35 123.10030395137 0.699100 40 0.7 0.68 6 35 123.10030395137 1.164100 40 0.7 0.74 6 35 123.10030395137 1.281100 40 0.7 1.01 6 50 123.10030395137 1.321
30 40 0.45 0.06 6 16 45.274231678487 0.23930 40 0.45 0.06 6 16 45.274231678487 0.23930 40 0.45 0.13 6 16 45.274231678487 0.47930 40 0.45 0.08 6 16 45.274231678487 0.29930 40 0.45 0.08 6 16 45.274231678487 0.29930 40 0.45 0.14 6 16 45.274231678487 0.53930 40 0.45 0.10 6 16 45.274231678487 0.35930 40 0.45 0.10 6 16 45.274231678487 0.35930 40 0.45 0.16 6 16 45.274231678487 0.59830 40 0.45 0.10 6 16 45.274231678487 0.38330 40 0.45 0.10 6 16 45.274231678487 0.38330 40 0.45 0.17 6 16 45.274231678487 0.622
30 40 0.45 0.23 6 16 36.425531914894 0.86730 40 0.45 0.21 6 16 36.425531914894 0.77030 40 0.45 0.17 6 16 36.425531914894 0.62630 40 0.45 0.13 6 16 36.425531914894 0.48230 40 0.45 0.09 6 16 36.425531914894 0.33730 40 0.45 0.07 6 16 36.425531914894 0.27030 40 0.45 0.06 6 16 36.425531914894 0.21230 40 0.45 0.04 6 16 36.425531914894 0.14430 40 0.45 0.24 6 16 36.425531914894 0.90530 40 0.45 0.19 6 16 36.425531914894 0.72230 40 0.45 0.10 6 16 36.425531914894 0.38530 40 0.45 0.08 6 16 36.425531914894 0.289
Breaker Amps (A)
Amb. Temp. (C)
Group Factor
Volt. Drop/mA
Max Volt. Drop (V)
Cab. Size from table MM2
Total Amps Req.(A) For Cable
Total Vd in %
30 40 0.45 0.05 6 16 36.425531914894 0.193
30 40 0.48 0.15 6 16 34.148936170213 0.57830 40 0.48 0.13 6 16 34.148936170213 0.48230 40 0.48 0.10 6 16 34.148936170213 0.38530 40 0.48 0.08 6 16 34.148936170213 0.28930 40 0.48 0.05 6 16 34.148936170213 0.19330 40 0.48 0.17 6 16 34.148936170213 0.62630 40 0.48 0.14 6 16 34.148936170213 0.53030 40 0.48 0.12 6 16 34.148936170213 0.43330 40 0.48 0.09 6 16 34.148936170213 0.33730 40 0.48 0.06 6 16 34.148936170213 0.241
100 40 0.7 1.28 6 70 123.10030395137 1.154100 40 0.7 1.35 6 70 123.10030395137 1.215100 40 0.7 1.55 6 70 123.10030395137 1.397100 40 0.65 0.54 6 35 132.56955810147 0.931100 40 0.65 0.88 6 50 132.56955810147 1.145100 40 0.65 0.27 6 35 132.56955810147 0.466100 40 0.65 0.88 6 50 132.56955810147 1.145100 40 0.65 0.61 6 35 132.56955810147 1.048100 40 0.65 1.15 6 50 132.56955810147 1.497100 40 0.65 0.88 6 50 132.56955810147 1.145
100 40 0.7 0.27 6 35 123.10030395137 0.466100 40 0.7 0.54 6 35 123.10030395137 0.931100 40 0.7 0.54 6 35 123.10030395137 0.931100 40 0.7 0.54 6 35 123.10030395137 0.931100 40 0.7 0.74 6 35 123.10030395137 1.281100 40 0.7 0.81 6 35 123.10030395137 1.397100 40 0.7 0.81 6 35 123.10030395137 1.397100 40 0.7 1.01 6 50 123.10030395137 1.321
30 40 0.48 0.23 6 16 34.148936170213 0.86730 40 0.48 0.18 6 16 34.148936170213 0.67430 40 0.48 0.09 6 16 34.148936170213 0.33730 40 0.48 0.06 6 16 34.148936170213 0.24130 40 0.48 0.04 6 16 34.148936170213 0.14430 40 0.48 0.24 6 16 34.148936170213 0.90530 40 0.48 0.19 6 16 34.148936170213 0.72230 40 0.48 0.10 6 16 34.148936170213 0.38530 40 0.48 0.08 6 16 34.148936170213 0.28930 40 0.48 0.05 6 16 34.148936170213 0.193
30 40 0.48 0.15 6 16 34.148936170213 0.57830 40 0.48 0.13 6 16 34.148936170213 0.48230 40 0.48 0.10 6 16 34.148936170213 0.38530 40 0.48 0.08 6 16 34.148936170213 0.28930 40 0.48 0.05 6 16 34.148936170213 0.19330 40 0.48 0.17 6 16 34.148936170213 0.62630 40 0.48 0.14 6 16 34.148936170213 0.53030 40 0.48 0.12 6 16 34.148936170213 0.433
30 40 0.48 0.09 6 16 34.148936170213 0.33730 40 0.48 0.06 6 16 34.148936170213 0.241
30 40 0.48 0.03 6 16 41.489361702128 0.11730 40 0.48 0.05 6 16 41.489361702128 0.17530 40 0.48 0.05 6 16 41.489361702128 0.17530 40 0.48 0.06 6 16 41.489361702128 0.23430 40 0.48 0.11 6 16 41.489361702128 0.40930 40 0.48 0.05 6 16 41.489361702128 0.17530 40 0.48 0.06 6 16 41.489361702128 0.23430 40 0.48 0.06 6 16 41.489361702128 0.23430 40 0.48 0.08 6 16 41.489361702128 0.29330 40 0.48 0.12 6 16 41.489361702128 0.468
30 40 0.45 0.06 6 16 44.255319148936 0.23430 40 0.45 0.06 6 16 44.255319148936 0.23430 40 0.45 0.12 6 16 44.255319148936 0.46830 40 0.45 0.08 6 16 44.255319148936 0.29330 40 0.45 0.08 6 16 44.255319148936 0.29330 40 0.45 0.14 6 16 44.255319148936 0.52730 40 0.45 0.09 6 16 44.255319148936 0.35130 40 0.45 0.09 6 16 44.255319148936 0.35130 40 0.45 0.16 6 16 44.255319148936 0.58530 40 0.45 0.10 6 16 44.255319148936 0.38630 40 0.45 0.10 6 16 44.255319148936 0.38630 40 0.45 0.17 6 16 44.255319148936 0.62030 40 0.45 0.11 6 16 44.255319148936 0.42130 40 0.45 0.11 6 16 44.255319148936 0.42130 40 0.45 0.17 6 16 44.255319148936 0.655
30 40 0.45 0.06 6 16 44.255319148936 0.23430 40 0.45 0.06 6 16 44.255319148936 0.23430 40 0.45 0.12 6 16 44.255319148936 0.46830 40 0.45 0.08 6 16 44.255319148936 0.29330 40 0.45 0.08 6 16 44.255319148936 0.29330 40 0.45 0.14 6 16 44.255319148936 0.52730 40 0.45 0.09 6 16 44.255319148936 0.35130 40 0.45 0.09 6 16 44.255319148936 0.35130 40 0.45 0.16 6 16 44.255319148936 0.58530 40 0.45 0.10 6 16 44.255319148936 0.38630 40 0.45 0.10 6 16 44.255319148936 0.38630 40 0.45 0.17 6 16 44.255319148936 0.62030 40 0.45 0.11 6 16 44.255319148936 0.42130 40 0.45 0.11 6 16 44.255319148936 0.42130 40 0.45 0.17 6 16 44.255319148936 0.655
30 40 0.45 0.06 6 16 44.255319148936 0.23430 40 0.45 0.06 6 16 44.255319148936 0.23430 40 0.45 0.12 6 16 44.255319148936 0.46830 40 0.45 0.08 6 16 44.255319148936 0.29330 40 0.45 0.08 6 16 44.255319148936 0.29330 40 0.45 0.14 6 16 44.255319148936 0.52730 40 0.45 0.09 6 16 44.255319148936 0.351
30 40 0.45 0.09 6 16 44.255319148936 0.35130 40 0.45 0.16 6 16 44.255319148936 0.58530 40 0.45 0.10 6 16 44.255319148936 0.38630 40 0.45 0.10 6 16 44.255319148936 0.38630 40 0.45 0.17 6 16 44.255319148936 0.62030 40 0.45 0.11 6 16 44.255319148936 0.42130 40 0.45 0.11 6 16 44.255319148936 0.42130 40 0.45 0.17 6 16 44.255319148936 0.655
30 40 0.48 0.03 6 16 41.489361702128 0.11730 40 0.48 0.05 6 16 41.489361702128 0.17530 40 0.48 0.05 6 16 41.489361702128 0.17530 40 0.48 0.06 6 16 41.489361702128 0.23430 40 0.48 0.11 6 16 41.489361702128 0.40930 40 0.48 0.05 6 16 41.489361702128 0.17530 40 0.48 0.06 6 16 41.489361702128 0.23430 40 0.48 0.06 6 16 41.489361702128 0.23430 40 0.48 0.08 6 16 41.489361702128 0.29330 40 0.48 0.12 6 16 41.489361702128 0.468
30 40 0.45 0.06 6 16 44.255319148936 0.23430 40 0.45 0.06 6 16 44.255319148936 0.23430 40 0.45 0.12 6 16 44.255319148936 0.46830 40 0.45 0.08 6 16 44.255319148936 0.29330 40 0.45 0.08 6 16 44.255319148936 0.29330 40 0.45 0.14 6 16 44.255319148936 0.52730 40 0.45 0.09 6 16 44.255319148936 0.35130 40 0.45 0.09 6 16 44.255319148936 0.35130 40 0.45 0.16 6 16 44.255319148936 0.58530 40 0.45 0.10 6 16 44.255319148936 0.38630 40 0.45 0.10 6 16 44.255319148936 0.38630 40 0.45 0.17 6 16 44.255319148936 0.62030 40 0.45 0.11 6 16 44.255319148936 0.42130 40 0.45 0.11 6 16 44.255319148936 0.42130 40 0.45 0.17 6 16 44.255319148936 0.655
30 40 0.45 0.06 6 16 44.255319148936 0.23430 40 0.45 0.06 6 16 44.255319148936 0.23430 40 0.45 0.12 6 16 44.255319148936 0.46830 40 0.45 0.08 6 16 44.255319148936 0.29330 40 0.45 0.08 6 16 44.255319148936 0.29330 40 0.45 0.14 6 16 44.255319148936 0.52730 40 0.45 0.09 6 16 44.255319148936 0.35130 40 0.45 0.09 6 16 44.255319148936 0.35130 40 0.45 0.16 6 16 44.255319148936 0.58530 40 0.45 0.10 6 16 44.255319148936 0.38630 40 0.45 0.10 6 16 44.255319148936 0.38630 40 0.45 0.17 6 16 44.255319148936 0.62030 40 0.45 0.11 6 16 44.255319148936 0.42130 40 0.45 0.11 6 16 44.255319148936 0.42130 40 0.45 0.17 6 16 44.255319148936 0.655
30 40 0.45 0.06 6 16 44.255319148936 0.234
30 40 0.45 0.06 6 16 44.255319148936 0.23430 40 0.45 0.12 6 16 44.255319148936 0.46830 40 0.45 0.08 6 16 44.255319148936 0.29330 40 0.45 0.08 6 16 44.255319148936 0.29330 40 0.45 0.14 6 16 44.255319148936 0.52730 40 0.45 0.09 6 16 44.255319148936 0.35130 40 0.45 0.09 6 16 44.255319148936 0.35130 40 0.45 0.16 6 16 44.255319148936 0.58530 40 0.45 0.10 6 16 44.255319148936 0.38630 40 0.45 0.10 6 16 44.255319148936 0.38630 40 0.45 0.17 6 16 44.255319148936 0.62030 40 0.45 0.11 6 16 44.255319148936 0.42130 40 0.45 0.11 6 16 44.255319148936 0.42130 40 0.45 0.17 6 16 44.255319148936 0.655
4.6174.8605.5893.7264.5811.8634.5814.1925.990
1.8633.7262.7954.6585.1235.285
0.9580.9581.9151.1971.1972.1541.4361.4362.3941.5321.5322.490
3.4673.0822.5041.9261.3481.0790.8470.5783.6212.8891.5411.156
Total Voltage drop in Volts(V)
0.770
2.3111.9261.5411.1560.7702.5042.1191.7331.3480.963
4.6174.8605.5893.7264.5811.8634.5814.1925.9904.581
1.8633.7263.7263.7265.1235.5895.5895.285
3.4672.6961.3480.9630.5783.6212.8891.5411.1560.770
2.3111.9261.5411.1560.7702.5042.1191.733
1.3480.963
0.4680.7020.7020.9361.6380.7020.9360.9361.1701.872
0.9360.9361.8721.1701.1702.1061.4041.4042.3401.5441.5442.4801.6851.6852.621
0.9360.9361.8721.1701.1702.1061.4041.4042.3401.5441.5442.4801.6851.6852.621
0.9360.9361.8721.1701.1702.1061.404
1.4042.3401.5441.5442.4801.6851.6852.621
0.4680.7020.7020.9361.6380.7020.9360.9361.1701.872
0.9360.9361.8721.1701.1702.1061.4041.4042.3401.5441.5442.4801.6851.6852.621
0.9360.9361.8721.1701.1702.1061.4041.4042.3401.5441.5442.4801.6851.6852.621
0.936
Cable Schedule
S.No Cable Ref. Type From To Lain on
1 4C XLPE 100 Cable Tray 130
Length in mtrs (m)
Connected Load Amps (A)
Breaker Amps(A)
Quick Cals.Quick Cals.
Vd Chart
Vd Chart
Group GroupStand
ardStand
ardCable DataCable Data
Overview
/Help
Overview
/Help
Cable Schedule
Cable size in Sq.mmReq.Amps for cable(A)
Derating factor (f)
Voltage drop(Vd)
(Vd) in %
25 75 3.09375Total Voltage Drop in % 0.7546
25 75 2.8125Total Voltage Drop in % 0.6860
Connected Load in Amps (A)
Length in mtrs
Total Voltage Drop (Vd) in Volts
Cable Size in Sq.mm
Connected Load in Amps (A)
Length in mtrs
Total Voltage Drop (Vd) in Volts
Cable Size in Sq.mm
Quick Cals.Quick Cals.
Specs.
Specs.
XLPE XLPEMethodologyMethodology
PVC PVCOvervi
ew/Help
Overview
/Help
Voltage Drop - Quick Cals for XLPE Cables
Voltage Drop - Quick Cals for PVC Cables